Architecture - Engineering - Planning www.mkcinc.com Mansfield, Ohio New Philadelphia, Ohio Powell, Ohio 419-525-1102 - phone 330-364-8871 - phone 740-657-3202 - phone 419-525-1428 - fax 330-343-3075 - fax 740-657-1717 - fax SHOP DRAWING REVIEW ✔ REVIEWED FURNISH AS CORRECTED REVISE AND RESUBMIT REJECTED SUBMIT SPECIFIED ITEM Date: By: Jun 6, 2012 Comments: This review is only for general conformance with (1) the design concept and (2) the information given in the construction documents. Corrections or comments made on a shop drawing during this review do not relieve the contractor from compliance with the requirements of the plans and specifications. Approval of a specific item does not include approval of an assembly of which the item is a component. The contractor remains responsible for: dimensions to be confirmed and correlated at the job site; information that pertains solely to the fabrication process or to the means, methods, techniques, sequences and procedures of construction; coordination of the Work with that of all other trades; and performing all Work in a safe and satisfactory manner. Trane RTU-11 was chosen File Name: 237413-01a-1
12
Embed
SHOP DRAWING REVIEW - MKC Associates, Inc. CSD/09-ED1-045B Dover...SHOP DRAWING REVIEW ... Corrections or comments made on a shop drawing during ... AAON Model RN, Packaged Rooftop
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
REVIEWEDFURNISH AS CORRECTEDREVISE AND RESUBMITREJECTEDSUBMIT SPECIFIED ITEM
Date:By: Jun 6, 2012
Comments:
This review is only for general conformance with (1) the design concept and (2) the informationgiven in the construction documents. Corrections or comments made on a shop drawing duringthis review do not relieve the contractor from compliance with the requirements of the plans andspecifications. Approval of a specific item does not include approval of an assembly of whichthe item is a component. The contractor remains responsible for: dimensions to be confirmed andcorrelated at the job site; information that pertains solely to the fabrication process or to themeans, methods, techniques, sequences and procedures of construction; coordination of theWork with that of all other trades; and performing all Work in a safe and satisfactory manner.
Trane RTU-11 was chosen
File Name:
237413-01a-1
Westlake City Schools Submittal Cover Sheet
(To be filled out and submitted with each submittal)
School ___High School___ Contractor: _Turner Logistics Date __04/19/12___ Item:____ RTU-11___________________
Specification Section: __237413 _ Sub Specification Section: ________________ Contractor’s Submittal # __237413-01__Revision # __0____ Submittal Type ___PDF__________ Lead Time After Approval (wks) _10__ Manufacturer/Supplier: _Aaon_ Intended Area of Use, Drawing # and Detail Reference: _____________________________________
Contractor Stamp
APPROVED Aaon / Jacco Paul Hinman
_____________________________ 04-19-12
CM Stamp
TURNER/RESOURCE
Reviewed for general acceptance only. This review does not relieve the Contractor of the responsibility for making the work conform to the requirements of the contract. The Contractor is responsible for all dimensions, correct fabrication and accurate fit with the work of other trades. SUBJECT TO ARCHITECT’S APPROVAL Signed: ____________________ Date: _____________ CM Submittal #: ________________________________
http://www.jacco.com Sold To: Turner Date: 4-3-12 Project: Westlake City Schools – New High School Location: Westlake, Ohio
AHU-11 New High School Quantity Of One (1) AAON Model RN, Packaged Rooftop Air Handling Units, Complete With The Following:
Cabinet 2” Double Wall Foam Panel Construction (R-13) w/ G-90 Galvanized Steel Construction w/ Polyurethane Paint Stainless Steel Drain Pan Outside Air Full Modulation Economizer, DDC Actuator Standard 2” Pleated, Throwaway Filters Optional 4” Merv-13 Final Filters Energy Recovery Section Energy Recovery Section w/ Heat Wheel & Pre-Filters Heat Section In-Direct Fired Natural Gas Heating w/ SS Heat Exchanger & Modulating Gas Heat Control Refrigeration Air Cooled Condenser Section Compressorized Refrigeration System R-410a w/ DX Cooling Coil Digital Scroll Compressor – 10-100% Cooling Modulation Modulating Hot Gas Reheat w/ Digital Controller Fan Cycling Fans Direct Drive Supply Air Plenum Fan Assembly w/ ODP Premium Efficiency Motor
o Factory Installed Variable Frequency Drive Power Exhaust Fan Assembly w/ ODP (Premium Efficiency) Motor
o Factory Installed Variable Frequency Drive Electric & Controls Single Point Power Connection w/ Terminal Strip (Non-Fused NEMA-1 Disconnect Switch) & 24v Control Circuit Unit Wired For 460 / 3 / 60 Power Field Installed DDC Controls By Others UV Light Provided And Installed By Jacco Warranty & Service Standard One (1) Year Limited Equipment Warranty – Parts Only Five (5) Year Limited Compressor Warranty, Parts Only Twenty-Five (25) Year Limited Heat Exchanger Warranty, Parts Only Check, Testing & Start-Up Service First Year Labor Warranty Curbs & Accessories Knocked-Down, 14” High, Non-Insulated Roof Curb & Duct Support Rails (Shipped Loose) Spring Vibration Rail (Shipped Loose) No Curb Insulation, Gasket Material & Fasteners, Nor External Vibration Isolators & Flexible Connectors (By Others)
This Submittal Is For Equipment Only. Roof Curb, Controls, Airflow Measuring, & UV Lights Will Be
2.00 in. wg. 0.11 in. wg.0.25 in. wg. 0.15 in. wg.0.23 in. wg. 0.05 in. wg.1 in. wg. 0.53 in. wg.0.03 in. wg. 4.37 in. wg.
Cooling Section Heating Section
Gross Net Equivalent Total Capacity: Total Capacity: Sensible Capacity: Latent Capacity: HW Total Cooling Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Digital Comp. Capacity Ratio: Supply Air Fan: SA Fan RPM / Width: Exhaust Air Fan: EA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity: Energy Recovery Wheel:
306.17 MBH 290.99 MBH207.19 192.02 MBH156.50 141.33 MBH50.69 MBH98.98 MBH79.49 ºF DB 65.48 ºF WB79.49 ºF DB 65.48 ºF WB52.07 ºF DB 51.97 ºF WB54.66 ºF DB 53.06 ºF WB100%1 x 270D60 @ 5.43 BHP1443 / 3.643"1 x RM220A @ 2.17 BHP1349 / 4.920"
19.9 ft² / 6 Rows / 12 FPI270.4 fpm1 x ERC-5262C
PreHeat Type: Std (No Preheat)
Heating Type: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty: Consumption:
Nat. Gas Heat5370218.7 MBH0.0 DB / 0.0ºF WB75.0 ºF DB / 62.0 ºF WB57.9 ºF DB / 51.7 ºF WB95.6 ºF DB / 65.7 ºF WB270.0 MBH1270.0 MBH
Re-Heat Coil: Capacity: 104 MBH LA DB / WB: 70.00 ºF / 59.10 ºF RH: 53%
4870 CFM Ex Bypass: 0 CFM Frost Warning - Conditions for frost forming on the energy recovery wheel exists. Outside air preheat is required to prevent frost formation. Optionally, the return air humidity ratio could be lowered to prevent frost formation. See AAON literature titled 'AAONAIRE ENERGY RECOVERY' for details.
R N- 018-3- 0-EB 0A -349 :VEDE- E0 B- DQG- AGC-CD CA HN3- 00 -000 00 00AB Tag: Music VAV AHU-11 Job Name: Westlake High VCMX For: Job Number: Osborn VCMX Date: November 29, 2011
Hardware Included For VCMX Controller
Part # Included Parts Assigned ChannelV07150 VCMX Controller with EBUSP94320 Space Temp Sensor - Field Installed MainController\AI1R82890 Supply Air Temp Sensor - Field Installed MainController\AI2R82890 Return Air Temp Sensor MainController\AI3R81550 Outside Air Temp Sensor MainController\AI4R69190 VCMX Large Expansion ModuleR37030 Building Static Pressure Sensor LargeExpansionModule\AI4P62520 Proof of Flow Sensor LargeExpansionModule\BI3P62520 Dirty Filter Sensor LargeExpansionModule\BI2R34690 Space Humidity Sensor - Field Installed LargeExpansionModule\AI2R74870 VCMX Full Digital ModuleR28390 Suction Pressure Transducer
1 2 3 4 5 6 7
VCMXControllerwith EBUS
Analog In X X X XAnalog Out X XBinary InRelay Out X X X X XDigital Sensor(s)
1 2 3 4 5 6 7 8VCMXLarge
ExpansionModule
Analog In X XAnalog OutBinary In X X XRelay Out