A101
1SIM
SF-1
1i
Name
101
1
A101
SIM
101
1
A101
SIM
0STRUCTURAL GRID LINES
SECTION ELEVATION
DETAILS IN PLAN, SECTION
WALL TYPE, SEE A501
ROOM NAME AND NUMBER
WINDOW TAG
DOOR TAG
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
NEW WALL
BRICK
CAST STONE
CONCRETE
CONCRETE MASONRY UNITS
SHINGLES
EARTH
PARTICLE BOARD
RIGID INSULATION
STEEL-LARGE SCALE
GLASS-LARGE SCALE
BATT INSULATION
STUD PARTITION
WOOD-FINISH
ACOUSTIC C.M.U. SMALL SCALE
ACOUSTIC C.M.U. LARGE SCALE
GLAZED C.M.U.
WOOD BLOCKING
SOLID CONCRETE MASONRY UNITS
ALL METALS-SMALL SCALE
1. CODES: ALL WORK ON THIS PROJECT SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE BUILDING CODES, ORDINANCES, REGULATIONS, STANDARDS, AND ANY ADDITIONAL REQUIREMENT STATED IN ANY LAW, ORDINANCE, OR REGULATION PERTAINING TO CONSTRUCTION WITHIN THE LIMITS OF THE AUTHORITY HAVING JURISDICTION OVER THE PROPOSED WORK (INCLUDING BUT NOT LIMITED TO: FIRE, ACCESSIBILITY, ZONING, WATER, WASTEWATER, ENVIRONMENTAL, STRUCTURAL, ARCHITECTURAL, HEALTH, FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL, AND ENERGY CONSERVATION). CONFORMITY TO ALL CODES APPLICABLE TO THIS PROJECT SHALL BE THE CONTRACTORS RESPONSIBILITY.
2. EGRESS: ALL MEANS OF EGRESS SHALL BE CONTROLLED BY THE AUTHORITY HAVING JURISDICTION, INCLUDING EXITS, EXIT ACCESS, EXIT DISCHARGE, OTHER EGRESS PATHS, OCCUPANTS LOADS, SPRINKLER PROTECTION, ETC..
3. ACCESSIBILITY: ALL BUILDING COMPONENTS, FIXTURES, ACCESSORIES, ETC. SHALL BE INSTALLED WITH MANEUVERING AND OPERATING CLEARANCES, MOUNTING HEIGHTS, ETC. IN ACCORDANCE WITH AMERICANS WITH DISABILITIES ACT STANDARDS, ICC/ANSI A117.1, AND STATE ACCESSIBILITY CODE.
4. FIELD VERIFICATION: THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS AND PROPOSED BUILDING DIMENSIONS PRIOR TO CONSTRUCTION, ANY VARIATIONS, DISCREPANCIES, OR FIELD ALTERATIONS TO THESE DESIGN DRAWINGS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION PRIOR TO CONSTRUCTION. IF CONTRACTOR COMMENCES CONSTRUCTION WITHOUT NOTIFYING ARCHITECT OF VARIATIONS, DISCREPENCIES, OR FIELD ALTERATIONS, THAT SHALL CONSTITUTE WAIVER TO ANY CLAIM BY CONTRACTOR FOR ADDITIONAL EXPENSES NECESSARY TO PERFORM WORK ASSOCIATED WITH THOSE CONDITIONS.
5. SUBMITTALS: CONTRACTOR SHALL SUBMIT ALL NECESSARY BUILDING COMPONENTS, SYSTEMS, EQUIPMENT, MATERIALS, FINISHES, ETC. FOR REVIEW BY ARCHITECT/OWNER PRIOR TO PROCUREMENT, FABRICATION, AND/OR INSTALLATION.
6. INSTALLATION: PROPER ASSEMBLY, INSTALLATION, AND OPERATION OF ALL MATERIALS, COMPONENTS, SYSTEMS, AND FINISHES IS THE CONTRACTOR'S RESPONSIBILITY AND SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTRUCTIONS AND ALL APPLICABLE CODES.
7. INCIDENTAL WORK: ANY ITEMS NOT SPECIFICALLY SHOWN ON THE DRAWINGS, BUT WHICH ARE REASONABLY INCIDENTAL TO AND NECESSARY FOR THE SATISFACTORY COMPLETION OF THE PROJECT IN ACCORDANCE WITH APPLICABLE CODES, ORDINANCES, REGULATIONS, AND STANDARDS, ARE INCLUDED WITHIN THE INTENT OF THESE DESIGN DRAWINGS.
8. OWNER-PROVIDED WORK: LOCATION OF ALL OWNER-PROVIDED FIXTURES, EQUIPMENT, ETC. SHALL BE COORDINATED TO ENSURE PROPER ALIGNMENT FOR INSTALLATION AND OPERATION, BLOCKING, ETC.
9. SAFETY: COMPONENTS FOR CONSTRUCTION SAFETY ARE NOT INDICATED IN THESE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE TO COMPLY WITH ALL RULES AND OTHER REQUIREMENTS OF THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA), AND APPLICABLE STATE AND LOCAL SAFETY REQUIREMENTS DURING ALL CONSTRUCTION ACTIVITIES.
10. INSPECTIONS: CONTRACTOR IS RESPONSIBLE FOR SCHEDULING ALL ON-SITE INSPECTIONS REQUIRED PRIOR TO OCCUPANCY APPROVAL.
11. DIMENSIONS: UNLESS OTHERWISE INDICATED: WALLS ARE TO FACE OF STUD FRAMING AND TO FACE OF MASONRY; WINDOWS AND DOORS ARE TO CENTERLINE OF OPENING IN STUD FRAMING AND TO FACE OF MASONRY OPENING IN MASONRY; PLUMBING FIXTURES ARE TO CENTERLINE OF FIXTURE.
12. BLOCKING: PROVIDE BLOCKING AS REQUIRED FOR INSTALLATION OF ALL PORTIONS OF THE WORK AND PER MANUFACTURER'S WRITTEN RECOMMENDATIONS, WHETHER OR NOT SPECIFICALLY INDICATED IN THESE DRAWINGS.
13. METAL PROTECTION AT TREATED WOOD: METAL CONNECTORS THAT COME IN CONTACT WITH TREATED LUMBER SHALL BE STAINLESS STEEL OR "ZMAX" CORROSION RESISTANT MATERIALS TO HELP PROTECT AGAINST ACCELERATED CORROSION. CONTRACTOR SHALL COORDINATE COMPATIBILITY OF ALL METALS USED WITH TREATMENT PRODUCT(S) MANUFACTURER(S)'S WRITTEN RECOMMENDATIONS.
14. HURRICANE TIES: CONTRCATOR SHALL PROVIDE HURRICANE TIES AND CONSTRUCTION CONNECTORS PER CODE AND AS REQUIRED BY AUTHORITY HAVING JURISDICTION.
15. WINDOWS AND DOORS: WINDOWS AND DOORS ARE INDICATED USING NOMINAL DIMENSIONS. MATERIALS AND INSTALLATION SHALL COMPLY WITH DESIGN PRESSURE (DP) RATINGS, WATER INFILTRATION RATING, IMPACT/SAFETY GLAZING, WIND REQUIREMENTS, EGRESS HARDWARE, U-FACTOR / R-VALUE, ETC.. ALL EXTERIOR UNITS SHALL HAVE CORROSION-RESISTANT HARDWARE.
16. LIFE SAFETY COMPONENTS: FINAL LOCATION OF FIRE EXTINGUISHERS, EMERGENCY LIGHTING, AND EXIT SIGNS TO BE AS DIRECTED BY LOCAL FIRE MARSHAL, AND ARE SUBJECT TO FINAL ON-SITE INSPECTION AND EVALUATION. CONTRACTOR SHALL MAKE REVISIONS AND/OR ADDITIONS IN ACCORDANCE WITH FIRE MARSHAL'S INSPECTION..
17. FIRE PROTECTION, PLUMBING, MECHANICAL, ELECTRICAL WORK: ALL FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL WORK SHALL BE PERFROMED BY QUALIFIED, LICENSED (SUB)CONTRACTORS, AND BE IN ACCORDANCE WITH ALL APPLICABLE CODES, REGULATIONS, STANDARDS, ETC.. ALL COMPONENTS SHALL BE INSTALLED ABOVE THE FLOOD ELEVATION AS REQUIRED BY FEMA, LOCAL A.H.J., AND ALL APPLICABLE CODES
18. PIPE INSULATION: CONTRACTOR SHALL INSULATE AND PROTECT PIPES AS REQUIRED BY CODE, AND AS REQURIED TO PROTECT PIPING EXPOSED TO EXTERIOR CONDITIONS.
19. GRADING: CONTRACTOR SHALL COORDINATE SITE GRADING TO COMPLY WITH CODES AND ORDINANCES, AND TO MAINTAIN POSITIVE DRAINAGE AWAY FROM BUILDING.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
FACING TILES.H. SHOWER HEADSHT. SHEETSIM. SIMILARS.M. SURFACE MOUNTEDS.P. STAND PIPES.S. SERVICE SINKSS STAINLESS STEELSTL. STEELSTOR. STORAGESTRUCT. STRUCTURALSUSP. SUSPENDEDSYN.FL. SYNTHETIC FLOORTB, T.B. TACKBOARDTEL. TELEPHONET.& G. TONGUE AND GROOVETHRESH. THRESHOLDT.O.B. TOP OF BEARINGT.O.M. TOP OF MASONRY PARAPETT.P. TOILET PAPER HOLDERT.S. TACK STRIP,
THE PROFESSIONAL SERVICES OF THE ARCHITECT ARE UNDERTAKEN FOR AND ARE PERFORMED IN THE INTEREST OF:1)
NO CONTRACTURAL OBLIGATION IS ASSUMED BY THE ARCHITECT FOR THE BENEFIT OF ANY OTHER PERSON INVOLVED IN THE PROJECT.
DATE OF SIGNATURE: X.X.2021DATE OF REGISTRATION EXPIRATION:01/31/2022
GENERAL NOTES
1" = 1'-0"
3/3
1/2
021
9:4
4:5
0 A
MC
:\U
se
rs\jd
eg
race\D
ocu
me
nts
\202
01
79
00_
jdeg
race
FX
JN
W.r
vt
G001
COVER SHEET
AMCJAD
04/01/2021
2020179.00
TERRY CAMPUS100 CAMPUS DRIVE, DOVER, DE
DTCCHEALTHCARECENTER OFEXCELLENCE
DTCC HEALTHCARE CENTER OFEXCELLENCE
TERRY CAMPUS100 CAMPUS DRIVE, DOVER, DE
ISSUED FOR BIDDING
04/01/2021
DELAWARE TECHNICAL COMMUNITYCOLLEGE
SHEET No. SHEET TITLE
GENERAL
G001 COVER SHEET
G101 LIFE SAFETY PLAN AND CODE STUDY
STRUCTURAL
S100 FOUNDATION PLAN
ARCHITECTURAL
AD101 FIRST FLOOR DEMOLITION PLAN
A001 CONSTRUCTION TYPES - WALL TYPES AND DETAILS
A101 FIRST FLOOR NEW WORK PLAN
A102 FIRST FLOOR REFLECTED CEILING PLAN
A103 FIRST FLOOR FINISH PLAN
A104 EQUIPMENT AND FURNITURE PLAN - FOR REFERENCE ONLY
A401 ENLARGED PLANS AND SECTIONS
A601 DETAILS, DOOR AND WINDOW TYPES AND SCHEDULE
A701 INTERIOR ELEVATIONS
MECHANICAL
M000 MECHANICAL LEAD SHEET
MD101 FIRST FLOOR DUCTWORK DEMO PLAN
M101 FIRST FLOOR NEW DUCTWORK PLAN
M401 MECHANICAL CONTROL DIAGRAMS
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M901 MECHANICAL FIRST FLOOR ZONING PLAN
PLUMBING
P000 PLUMBING LEAD SHEET
PD101 FIRST FLOOR SANITARY PIPING DEMO PLAN
PD110 FIRST FLOOR SERVICE PIPING DEMO PLAN
P101 FIRST FLOOR SANITARY PIPING NEW WORK
P110 FIRST FLOOR SERVICE PIPING NEW WORK
P500 PLUMBING DETAILS
ELECTRICAL
E000 ELECTRICAL NOTES LEGENDS & ABBREVIATIONS
E001 ELECTRICAL SPECIFICATIONS
ED101 ELECTRICAL FIRST FLOOR LIGHTING & POWER DEMOLITION PLAN
E101 ELECTRICAL FIRST FLOOR POWER NEW WORK PLAN
E201 ELECTRICAL FIRST FLOOR LIGHTING NEW WORK PLAN
E300 ELECTRICAL PANELBOARD SCHEDULES
ISSUED:
ISSUED
FOR BIDDING
04/01/21
SITE
Mark Date Description
1 12/16/2020 ISSUED FOR AABREVIEW
2 12/18/2020 ISSUED FOR FINALOWNER REVIEW
3 04/01/21 ISSUED FOR BIDDING
DN
PATH OF EXIT ACCESS TRAVEL
LIFE SAFETY PLAN LEGEND
LIFE SAFETY PLAN NOTES1. PROVIDE NEW FIRE EXTINGUISHERS IN CABINETS (FEC)
AND FIRE EXTINGUISHERS ON BRACKETS (FE) AS SHOWN ON FLOOR PLANS. PROVIDE NEW FIRE EXTINGUISHERS IN MECHANICAL, ELECTRICAL (TYPE B-C).
2. FIRE EXTINGUISHER SHALL BE MINIMUM 3A-40BC RATING.
MIN. EGRESS WIDTHREQ'D (INCHES)
MAX. OCC. ALLOWED
ACTUAL EGRESS WIDTHPROVIDED (INCHES)
ACTUALOCCUPANTS
EXIT CAPACITY
CLASSROOM
119ROOM NAME & NUMBER
786 SF39 OCC.
ROOM AREA
TRAVEL PATH #50' - 0"
EXIT ACCESS TRAVEL DISTANCE
OCCUPANCY LOAD(*AC* = ACCESSORY SPACE)
EXTERIOR WALL
FIRE WALL/PARTY WALL
FIRE BARRIER
FIRE PARTITION
SMOKE BARRIER
SMOKE PARTITION
NON-RATED PARTITION
TYPE OF WALL/PARTITION 1/2
ASSEMBLY RATING, IN HOURS)
0 1 2 3 4
RATED WALL/PARTITION LEGEND
PROPERTY LINE / IMAGINARY LOT LINE
FEC (E) - EXISTING FIRE EXTINGUISHER CABINET, TO REMAINFE (E- EXISTING FIRE EXTINGUISHER, TO REMAINFEC (R) - EXISTING FIRE EXTINGUISHER, RELOCATED
CLASSROOM
217
WOMEN
215
CNA LAB
208
VESTIBULE
200
PROMETRIC
202OFFICE
229
OFFICE
228
OFFICE
226
CLOSET
227
OFFICE
225
CO
RR
IDO
R
224
COPY/ WORKROOM
223
MEN
222
STORAGE
221
CNA LAB
218CCMAA LAB
219
ELEC.
207A
CO
M.
RO
OM
206A
PH
LE
B.
LA
B
214
CLEANSTERILE LAB
211A
DIALYSIS LAB
213 DENTAL LAB
212
CORRIDOR
203
CORRIDOR
210
CO
RR
IDO
R
220
CO
RR
IDO
R
206
STORAGE
231
BREAKROOM
207
COMPUTERLAB
205
CLASSROOM
204
CLASSROOM
216CLASSROOM
209
CORRIDOR
201
330 O
CC
ALLO
W 8 7
7/1
28"
RE
Q
5' -
6"
PR
V43 O
CC
AC
TU
AL
330 O
CC
ALLO
W
8 7
7/1
28"
RE
Q
5' -
6"
PR
V
43 O
CC
AC
TU
AL
LAUNDRY
230
FE(E)
OPERABLE PARTITION
FEC(R)
R 75' - 0"
R 75' - 0"
SOLIEDSTERILE LAB
211B
R 75' - 0"
BUILDING TOTAL GROSS = 8481 SF
OCCUPANCY TYPE = BUSINESS
TOTAL OCCUPANTS= 85 OCC.
TRAVEL PATH B-1
TRAVEL PATH B-2
TRAVEL PATH B-2
TRAVEL PATH B-1
FEC(E)
1. FIRE RESISTIVE MATERIALS AND JOINT TREATMENTS, SUBMITTED DETAILS AND PRODUCTS SHALL BE U.L.-LISTED ASSEMBLIES OR U.L.-LISTED ASSEMBLIES WITH MANUFACTURER'S ENGINEERING JUDGMENT FOR SPECIFIC PENETRATION CONDITION.
2. TEST BUILDING FOR EMERGENCY RESPONDER RADIO COVERAGE PER IBC 915, IFC 510, AND NFPA 72. PROVIDE EMERGENCY RESPONDER RADIO COVERAGE SYSTEM IF MINIMUM SIGNAL STRENGTH IS NOT MET. SUBMIT TEST RESULTS, AND SYSTEM DESIGN (IF REQUIRED), TO A.H.J.
CODE STUDY NOTES
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
PUNCHED HOLES. COORDINATE LOCATION AND DIAMETER WITH PARTITION SUPPLIER
1
1
6 3/4" (COORDIANTE w/ PARTITION SUPPLIER)
GOVERNING CODES
THIS PROJECT SHALL COMPLY WITH THE "INTERNATIONAL BUILDING CODE", INTERNATIONAL CODE
COUNCIL, INC., 2012 EDITION, INCLUDING SPECIFICATIONS REFERENCED WITHIN. USE THEREFERENCED OR LATEST EDITIONS UNLESS NOTED OTHERWISE. MANUFACTURER SPECIFICATIONAND LOCAL CODE REQUIREMENTS, WHEN IN EXCESS OF MINIMUM SPECIFICATION, SHALL CONTROL.
STEEL
FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THELATEST SPECIFICATION OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION STEELCONSTRUCTION MANUAL.
STRUCTURAL STEEL SHALL CONFORM TO:WF BEAMS ASTM A992 (50KSI)RECT. HSS ASTM A500 GRADE B (46KSI)ROUND HSS ASTM A500 GRADE B (42KSI)STEEL PIPE ASTM A53 GRADE B (35KSI)PLATES, ANGLES & CHANNELS ASTM A36 (36KSI)
BOLTS ASTM A325-N (3/4" ∅ U.N.O.)
ANCHOR BOLTS ASTM F1554 GRADE 36
PROVIDE WELDED CONNECTIONS TYPICALLY UNLESS OTHERWISE NOTED.
WELDING ELECTRODES SHALL BE E70 SERIES.
WELDS SHALL BE MADE ONLY BY WELDERS WHO HAVE BEEN PREQUALIFIED BY TESTS OF THEAMERICAN WELDING SOCIETY, PRESCRIBED IN THE STRUCTURAL WELDING CODE," AWS DI.I(LATEST EDITION).
ANY CONNECTION NOT SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS SHALL BEDESIGNED AND DETAILED BY THE STRUCTURAL STEEL FABRICATOR. SEE THE TYPICAL BEAMCONNECTION DETAILS ON THE DRAWINGS.
CONNECTIONS SHALL BE AISC STANDARD.
PROVIDE BASE PLATE FOR ALL STRUCTURAL STEEL BEAMS BEARING ON CONCRETE OR MASONRY.GROUT FOR SETTING BEARING SURFACES SHALL BE NON-SHRINK, NOT-STAINING.
ALL STEEL SUPPORT COLUMNS SHALL BEAR DIRECTLY ON MASONRY OR CONCRETE FOUNDATIONSYSTEMS.
MISCELLANEOUS STRUCTURAL STEEL SHALL CONFORM TO THE LATEST EDITION OF THE AISC"SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FORBUILDINGS", AND SHALL BE ASTM A36. BOLTS SHALL BE HIGH STRENGTH 3/4" DIAMETERCONFORMING TO ASTM A325. WELDING SHALL BE DONE ONLY BY CERTIFIED WELDERS. WELD INACCORDANCE WITH THE AWS "STANDARD CODE FOR ARC AND GAS WELDING IN BUILDINGCONSTRUCTION". STRUCTURAL STEEL SURFACES CAST INTO CONCRETE SHALL BE UNPAINTED.
SUBMIT STRUCTURAL STEEL SHOP DRAWINGS SHOWING COMPLETE DIMENSIONS AND DETAILS FORAPPROVAL PRIOR TO FABRICATION. THE STRUCTURAL STEEL SUBCONTRACTOR SHALL BERESPONSIBLE FOR CHECKING, VERIFICATION, AND FOR COORDINATION OF DIMENSIONS ANDDETAILS WITH THE STRUCTURAL AND OTHER PORTIONS OF THE CONTRACT DRAWINGS. THESTRUCTURAL CONTRACT DRAWINGS SHALL NOT BE REPRODUCED AS SHOP DRAWINGS UNLESSTHE STRUCTURAL ENGINEER'S APPROVAL IS OBTAINED IN WRITING.
WOOD
WOOD AND TIMBER CONSTRUCTION SHALL COMPLY WITH REFERENCED OR LATEST EDITIONS OFTHE FOLLOWING STANDARDS: 1) NATIONAL FOREST PRODUCTS ASSOCIATION: "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION." 2) AMERICAN INSTITUTE OF TIMBER CONSTRICTION: " TIMBER CONSTRUCTION MANUAL." 3) AMERICAN PLYWOOD ASSOCIATION: "PLYWOOD DESIGN SPECIFICATION." 4) AMERICAN WOOD PRESERVERS ASSOCIATION STANDARDS
STRUCTURAL TIMBER SHALL BE STAMPED WITH A GRADE MARK IN ACCORDANCE WITH DOC PS20 WITH MOISTURE CONTENT TO BE 19% MAXIMUM.
JOISTS, HEADERS, TRIMMERS AND EXTERIOR AND INTERIOR BEARING WALL STUDS SHALL BES.P.F. #2 OR BETTER.
4x4 & 6x6 P.T. POSTS SHALL BE S. PINE #2 OR BETTER
LVL'S (LAMINATED VENEER LUMBER) SHALL BE 1 3/4" WIDE, OF THE DEPTH SPECIFIED ON THEPLANS, AND SHALL BE SECURED TOGETHER AS DIRECTED BY THE MANUFACTURER.
LSL'S (LAMINATED STRAND LUMBER) SHALL BE 1 1/2" WIDE (BAND BOARDS FOR PREFABRICATEDFLOOR JOISTS SHALL BE 1 1/4"), OF THE DEPTH SPECIFIED ON THE PLANS, AND SHALL BESECURED TOGETHER AS DIRECTED BY THE MANUFACTURER.
PSL'S (PARALLEL STRAND LUMBER) SHALL BE OF THE WIDTH AND DEPTH SPECIFIED ON THEPLANS, AND SHALL BE SECURED TOGETHER AS DIRECTED BY THE MANUFACTURER.
GLU-LAMS (LAMINATED TIMBER) SHALL BE OF THE WIDTH AND DEPTH SPECIFIED ON THE PLANS.
PREFABRICATED WOOD I-JOISTS: PREFABRICATED WOOD I-JOISTS SHALL BE APPROVED BY ARECOGNIZED TESTING AGENCY AND COMPLY WITH ASTM D 5055. THEY SHALL BE DESIGNED TOCARRY ALL LIVE AND DEAD LOADS WITH THE LIVE LOAD DEFLECTION NOT TO EXCEEDL/480(FLOOR) AND L/240(ROOF). THE MANUFACTURER SHALL SUPPLY ALL REQUIRED HANGERS,SHEER PANELS, BLOCKING PANELS, AND OTHER SPECIAL HARDWARE. THE MANUFACTURERSHALL SUBMIT ERECTION DRAWINGS TO THE ENGINEER PRIOR TO FABRICATION. ALLPREFABRICATED WOOD I-JOISTS SHALL BE INSTALLED AND BRACED IN ACCORDANCE WITH THEMANUFACTURER'S INSTRUCTIONS.
WOOD EXPOSED TO THE ELEMENTS, WOOD IN CONTACT WITH CONCRETE OR MASONRY, ANDWOOD DESIGNATED "PRESERVATIVE TREATED" SHALL BE NO. 2 GRADE SOUTHERN PINE ORBETTER & PRESERVATIVE TREATED IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES,PRODUCT, PRESERVATIVE AND END USE. FIELD CUT ENDS, NOTCHES AND DRILLED HOLES OFP.T. WOOD SHALL BE TREATED IN THE FIELD IN ACCORDANCE WITH AWPA M4.
PLYWOOD: APA EXPOSURE 1, GROUP 1 RATED SHEATHING, MIN. 4 PLY, MIN, SPAN RATING OF32/16. U.N.O. USE 3/4" NOM. THICKNESS FOR FLOORS, 5/8" FOR ROOFS, AND 1/2" FOR WALLS. FORFLOORS, USE TONGUE-AND-GROOVE PLYWOOD GLUED AND SCREW-FASTENED. FOR ROOFS,USE PLYWOOD CLIPS AT ALL UNSUPPORTED BUTT JOINTS. PLYWOOD SHALL BE MARKED PERDOC PS-1.
LUMBER SCHEDULE(MINIMUM ALLOWABLE PROPERTIES)
SPECIES f b(PSI) fv (PSI) E (KSI) S.G.
LVL 2,600 285 1,900 0.50
LSL 1,700 400 1,300 0.50
PSL (BEAM) 2,900 290 2,000 0.50
PSL (COLUMN) 2,400 190 1,800 0.50
GLULAM (24FV5 SP/SP) 2,400 165 1,700 0.50
S.P.F. #2 875 135 1,400 0.42
S. PINE #2 VARIES BY DIMENSIONS 0.50
B
STEEL COLUMN(SEE PLAN)
EX. FOOTING
4" (MIN.) EX. SLAB (V.I.F.)
EX. CMU WALL
HILTI HY-200 w/ (4) 1/2"Ø HIT-Z (3" EMBED.)
1/4" LEVELING PLATE &3/4" NON-SHRINK GROUT
14"x10"x3/4" STEEL BASE PLATE
1/4
6"
A
9"x1/2"x3 1/2" STEEL PLATEw/ (3) 3/4"Ø BOLTS
BEAM (SEE PLAN)
COLUMN (SEE PLAN)
HILTI HY-200 w/ (4) 1/2"Ø HIT-Z (3" EMBED.)
1/4" LEVELING PLATE &3/4" NON-SHRINK GROUT
EX. 4" (MIN.) SLAB (V.I.F.)
11"x11"x3/4" BASE PLATE
1/4" STEEL CAP PLATE
1/4
1/4
1/4
T.O.S. 10' - 0" V.I.F.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
PROFESSIONAL CERTIFICATION:I CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME AND THAT I AM A DULY LICENSED ENGINEER UNDER THE LAWS OF THE
STATE OF DELAWARE.
LICENSE NO:
EXPIRATION DATE:
18535
06/30/2022
Delaware309 S Governors Ave
Dover, DE 19904
302.734.7950
Maryland312 West Main St, Suite 300
Salisbury, MD 21801
410.546.9100
North Carolina3333 Jaeckle Drive, Suite 120
Wilmington, NC 28403
910.341.7600
www.beckermorgan.com
The Tower at STAR Campus
100 Discovery Boulevard, Suite 102
Newark, DE 19711
302.369.3700
As indicated
3/3
1/2
021
8:0
3:5
6 A
M
S101
FOUNDATION PLAN
JIW/JKBHBE
01.15.2021
2020179.00
TERRY CAMPUS100 CAMPUS DRIVE,DOVER DE
DTCCHEALTHCARECENTER OFEXCELLENCE
SCALE: 1/4" = 1'-0"1 FOUNDATION PLANSCALE: 1/4" = 1'-0"2 PARTITION FRAMING PLAN
SCALE: 1" = 1'-0"5 SECTION
SCALE: 3/4" = 1'-0"3 SECTION
SCALE: 3/4" = 1'-0"4 SECTION
Revision Schedule
Mark Date Description
2 12/18/20 ISSUED FOR FINALOWNER REVIEW
3 04/01/21 ISSUED FOR BIDDING
REF. W/D
DN
GENERAL DEMOLITION NOTES
A. REMOVE FLOOR FINISH AND WALL BASE.B. REMOVE ALL METAL LOCKERS.C. REMOVE ALL ACOUSTICAL CEILING TILE, GRID AND
SUSPENSION SYSTEM, REMOVE ALL INSULATION SUPPORTED BY EXISTING CEILING SYSTEM.
D. REMOVE ALL PARTICAL BOARD CEILING TILES AND ASSOCIATED FURRING WHERE PRESENT ABOVE ACT, REMOVE ALL INSULATION SUPPORTED BY EXISTING CEILING SYSTEM.
E. REMOVE ALL WINDOW COVERINGS.F. REMOVE ALL ROOM SIGNAGE.G. REMOVE ALL CUBICLE CURTAINS AND TRACKS.H. REMOVE FIRE EXTINGUISHER AND CABINETS, SAVE
FOR REUSE.I. SEE PLUMBING DRAWINGS FOR EXTENTS OF SLAB
DEMOLITION. CONTRACTOR SHALL VERIFY EXTENT OF DEMOLITION IN FIELD BASED ON EXISTING CONDITIONS.
DEMOLITION LEGEND
DEMOLITION KEY NOTES
REMOVE PARTITION IN ITS ENTIRETY.
REMOVE DOOR, FRAME AND HARDWARE.
REMOVE DOOR AND HARWARE, FRAME TO REMAIN.
REMOVE PLUMBING FIXTURE.
REMOVE PLUMBING APPLIANCE AND CAP WATER SUPPLY.
REMOVE FLOOR FINISH TO SUBFLOOR. REMOVE WALL BASE.
CUT AND REMOVE PORTION OF PARTITION TO PREPARE FOR NEW OPENING. SEE NEW WORK PLAN AND DOOR SCHEDULE. CONTRACTOR TO VERIFY WALL AS NON-LOAD BEARING AND CONTACT ARCHITECT AND/OR STRUCTURAL ENGINEER IF BEARING WALL CONDITION FOUND IN FIELD.
1
2
3
2A
4
5
6
7
8
9A
10
11
12
13
14
15
9
3A
16
17
REMOVE EXISTING CASEWORK, COUNTERTOP, COUNTERTOP SUPPORT AND SINKS.
REMOVE SOFFIT TO ACCOMODATE NEW CONSTRUCTION.
REMOVE BULKHEAD TO UNDERSIDE OF STRUCTURE.
BULKHEAD TO REMAIN.
REMOVE WOOD SILL.
EXISTING FIRE EXTINGUISHER/CABINET TO REMAIN.
VAULTED GWB VESTIBULE CEILING TO REMAIN.
REMOVE CEILING IN ITS ENTIRETY. REMOVE SECONDARY CEILING WHERE OCCURS.
REMOVE FIRE EXTINGUISHER, SAVE FOR REUSE.
EXISTING MONITOR TO REMAIN.
REMOVE APPLIANCE
REMOVE DOOR HARDWARE AND PREPARE DOOR FOR BLANKING PLATES PRIOR TO SECURING DOOR SHUT.
REMOVE STOREFRONT AND GLAZING.
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
EXISTING DOOR TO BE REMOVED
EXISTING WINDOW TO REMIAN
EXISTING DOOR TO REMAIN
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM CLASSROOM
CLASSROOM
WOMEN
CLO.
MEN
OFFICE
OFFICE
OFFICE
OFFICE LOBBY
RECEP.
STUDY
COPY
CLO.
OFFICE
BREAKROOM
CO
M.
RO
OM
STORAGE
9
66
10
5
6
6
6
5
5
5 5
9
5
8
6
3
22
2
2
2
1
1
1
1
2
1
1
1
21
6
71
4 4
4
4
4
4
4
4
4
4
4
4
4
44
4
4
4
4
4
4
4
4
4
2
12
13
13
13
13
13
13
4
131313
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
4
13
CLO.
13
4
13
13
4
13
9
9
9
14
14
6
1
2
2
1
1
ELEC.
207A
15
22
1
9
2A
2A
2A
5
2A
2A
2A
2A
2A
2A
2A
2A
2A
1
1
9A
68
1
11
2A
14' - 4" 3' - 0"
2' -
8"
7' -
0"
3' -
0"
9' -
10
"
2
3' - 0" 1' - 10"
1' - 2" 3' - 0"
5
3' -
0"
5"
3' -
0"
3' -
6"
3
3
3 3
3
3
3
11
OF
DE
MO
LIT
ION
WIT
H N
EW
WO
RK
NO
TE
13
- C
OO
RD
INA
TE
EX
TE
NT
S
WIT
H N
EW
WO
RK
NO
TE
12
- C
OO
RD
INA
TE
13
3A
16
17
1
3
3
3
3
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
THE PROFESSIONAL SERVICES OF THE ARCHITECT ARE UNDERTAKEN FOR AND ARE PERFORMED IN THE INTEREST OF:1)
NO CONTRACTURAL OBLIGATION IS ASSUMED BY THE ARCHITECT FOR THE BENEFIT OF ANY OTHER PERSON INVOLVED IN THE PROJECT.
DATE OF SIGNATURE: X.X.2021DATE OF REGISTRATION EXPIRATION:01/31/2022
As indicated
3/3
1/2
021
9:3
7:0
2 A
MC
:\U
se
rs\jd
eg
race\D
ocu
me
nts
\202
01
79
00_
jdeg
race
FX
JN
W.r
vt
AD101
FIRST FLOORDEMOLITION PLAN
AMCJAD
04/01/2021
2020179.00
TERRY CAMPUS100 CAMPUS DRIVE, DOVER, DE
DTCCHEALTHCARECENTER OFEXCELLENCE
DELAWARE TECHNICAL COMMUNITYCOLLEGE
SCALE: 1/4" = 1'-0"1 FIRST FLOOR DEMOLITION PLAN
ISSUED:
ISSUED
FOR BIDDING
04/01/21
N
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
Mark Date Description
1 12/16/2020 ISSUED FOR AABREVIEW
2 12/18/2020 ISSUED FOR FINALOWNER REVIEW
1A5/8" GWB. EA. SIDE TO 6" ABOVE FINISH CEILING
FINISH FLOOR (SEE FIN. SCHED.FOR FLOOR FIN. & WALL BASE)
WALL TYPES 1A
6" ABOVE FINISH CEILING
FINISH FLOOR (SEE FIN. SCHED.FOR FLOOR FIN. & WALL BASE)
WALL TYPES 2A
2A5/8" GWB ON ONE SIDE OF WALL ONLY UP TO 6" ABOVE FINISH CEILING
3 5/8" STUD
5/8" 5/8"3 5/8"
5/8"
1B5/8" GWB. EA. SIDE TO 6" ABOVE FINISH CEILING
5/8"
6" STUD
5/8"
6" ABOVE FINISH CEILING
1B
1. FIBERGLASS SOUND BATT INSULATION IN NON-RATED STUD PARTITIONS.2. PROVIDE MOLD AND MOISTURE RESISTANT GWB AT ALL STUD-FRAMED PARTITIONS IN WET
LOCATIONS, INCLUDING TOILET ROOMS, KITCHENS, LABS AND AT ALL SINKS AND LAVATORIES. EXTEND TO END OF CASEWORK RUN, INCLUDING SIDEWALLS WHERE ADJACENT TO SINKS.
3. BRACE NON-STRUCTURAL METAL STUD PARTITIONS WHERE NOT ATTACHED TO STRUCTURE ABOVE OR WHERE HEIGHT OF STRUCTURE EXCEEDS MANUFACTURER'S LIMITING HEIGHT FOR 5 PSF @ 16" O.C., OR PROVIDE COLD-FORM FRAMING. SEE SPECIFICATIONS AND STRUCTURAL DRAWINGS
4. PATCH AND ALIGN FINISHES AT ALL NEW PARTIAL HEIGHT WALLS WHERE PARTITIONS ARE BEING INFILLED.
WALL TYPE GENERAL NOTES
WALL TYPE GENERAL NOTES
UNDERSIDE OF BEAMOR STRUCTURAL DECK
ATTACH GWB TO STUDS ASREQUIRED OR AS DIRECTEDBY ASSEMBLY INSTRUCTIONSWITH EXCEPTION: MAKE NO ATTACHMENTS CLOSER THEN1 1/2" FROM TOP OF WALL ENSURING NO FASTERNERSATTACH INTO THE TOP RUNNER
MTL STUDS TO BE CUT A MINIMUM OF 3/8" (MAX. 1/2")SHORTER THAN UNDERSIDEOF DECK - GWB TO BE CUTA MINIMUM OF 1/2" (MAX. 5/8")SHORTER THAN UNDERSIDEOF DECK
NOTE: DO NOT ATTACH STEELSTUDS TO TOP RUNNERS
METAL STUD TOP RUNNER
TYPICAL STUD WALL DETAILSCALE : 1 1/2" = 1'-0"2
SCALE : 1/4" = 1'-0"
TYPICAL SIGNAGE MOUNTING LOCATIONS1
EXISTING ROOF STRUCTURE TO REMAIN
EXISTING ROOF STRUCTURE TO REMAIN
A. TYPICAL SINGLE LEAF DOOR
18'' x 18'' CLR AREA, TYP.
C. RECESSED SINGLE LEAF DOOR
18'' x 18'' CLR AREA, TYP.
B. TYPICAL PAIR DOOR
D. RECESSED PAIR DOOR
18'' x 18'' CLR AREA, TYP.
E. PAIR DOOR WITH INOPERABLE LEAF
18'' x 18'' CLR AREA, TYP.
OPERABLE LEAF
FIXED LEAF
18'' x 18'' CLR AREA, TYP.
SIGN, TYP.
SIGN, TYP.
SIGN, TYP. SIGN, TYP.
SIGN, TYP.
F. TYPICAL SIGN ELEVATIONS
WHERE SIGN IS MOUNTED ON GLASS, PROVIDE "BLANK" OF SAME SIZE AND FINISH OF SIGN ON OPPOSITE SIDE OF GLASS. ALIGN "BLANK" WITH SIGN TO CONCEAL ALL MOUNTING ADHESIVES AND BACK OF SIGN FROM VIEW.
HINGE SIDE OF DOOR
STRIKE SIDE OF DOOR
ROOM SIGN, TYP.
BOT OF HIGHEST TACTILE CHARACTER
BOT OF LOWEST TACTILE CHARACTER
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
THE PROFESSIONAL SERVICES OF THE ARCHITECT ARE UNDERTAKEN FOR AND ARE PERFORMED IN THE INTEREST OF:1)
NO CONTRACTURAL OBLIGATION IS ASSUMED BY THE ARCHITECT FOR THE BENEFIT OF ANY OTHER PERSON INVOLVED IN THE PROJECT.
DATE OF SIGNATURE: X.X.2021DATE OF REGISTRATION EXPIRATION:01/31/2022
As indicated
3/3
1/2
021
9:3
6:5
2 A
MC
:\U
se
rs\jd
eg
race\D
ocu
me
nts
\202
01
79
00_
jdeg
race
FX
JN
W.r
vt
A001
CONSTRUCTIONTYPES - WALL TYPESAND DETAILS
AMCJAD
04/01/2021
2020179.00
TERRY CAMPUS100 CAMPUS DRIVE, DOVER, DE
DTCCHEALTHCARECENTER OFEXCELLENCE
DELAWARE TECHNICAL COMMUNITYCOLLEGE
SCALE: 1-1/2" = 1'-0"
0' 4" 8" 16"
ISSUED:
ISSUED
FOR BIDDING
04/01/21
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
Mark Date Description
1 12/16/2020 ISSUED FOR AABREVIEW
2 12/18/2020 ISSUED FOR FINALOWNER REVIEW
3 04/01/21 ISSUED FOR BIDDING
REF.
DN
DN
WD
GENERAL NOTES1. DIMENSIONS ARE TO EXTERIOR FACE OF
CONCRETE, MASONRY, OR METAL STUD UNLESS OTHERWISE NOTED.
2. SEE A400-SERIES FOR ENLARGED PLANS AND SECTIONS.
3. SEE A103 FOR FINISH SCHEDULE AND LEGEND.4. SEE A601 FOR DOOR SCHEDULE, DOOR AND FRAME
TYPES, STOREFRONT TYPES AND WINDOW TYPES. 5. COORDINATE REQUIREMENTS OF WORK WITH ALL
OTHER TRADES.6. PATCH AND REPAIR AREAS DAMAGED BY
DEMOLITION ACTIVITIES. FINISH SMOOTH TO BLEND WITH ADJACENT CONSTRUCTION OR IN PREPARATION FOR NEW FINISHES.
7. REPAIR ALL HOLES LEFT BY REMOVAL OF EQUIPMENT. FINISH SMOOTH TO BLEND WITH ADJACENT CONSTRUCTION OR IN PREPARATION FOR NEW FINISHES.
8. SEE SHEET A104 AND MEP DRAWINGS FOR EQUIPMENT AND FURNITURE PLAN. CONTRACTOR SHALL COORDINITATE EQUIPMENT, UTILITIES, CLEARANCES AND EQUIPMENT REQUIREMENTS WITH ALL OTHER TRADES, TYP. FOR ROOMS 202, 208,211A, 211B, 212, 213, 214, 218, 219. EQUIPMENT BY OWNER, SHOWN FOR REFERENCE ONLY, N.I.C.
9. CONTRACTOR SHALL COORDINATE WASHER, DRYER AND MOP SINK WITH OWNER AND ENSURE FITMENT IN LAUNDRY 230.
CLASSROOM
217
WOMEN
215
CNA LAB
208
VESTIBULE
200
PROMETRIC
202
OFFICE
229
OFFICE
228
OFFICE
226
CLOSET
227
OFFICE
225
CORRIDOR
224
COPY/ WORKROOM
223
MEN
222
STORAGE
221
CNA LAB
218CCMAA LAB
219
ELEC.
207A
CO
M.
RO
OM
206A
PHLEB. LAB
214
CLEANSTERILE LAB
211A
DIALYSIS LAB
213
DENTAL LAB
212
CORRIDOR
203
CORRIDOR
210
CORRIDOR
220
CO
RR
IDO
R
206
STORAGE
231
BREAKROOM
207
COMPUTERLAB
205
DOOR TO REMAIN, SECURE DOOR FROM INTERIOR PRIOR TO WALL INFILL, REMOVE HARDWARE AND PROVIDE BLANKING PLATES
A701
1
A701
A701
2
CLASSROOM
204
CLASSROOM
216
CLASSROOM
209
CORRIDOR
201
1A
1A
1A
1A
2A1A
1A
1A
1A
1A
1A
229/1
205/1
208/1
209/1
219/1
3
3
A401
4
A401 6
A401
1
A401
A701
1211
B
A601
1
A701
56
A701
4
OPERABLE PARTITION
231/1
3' -
0"
9' -
10
"
ALIG
N
MIN.
4' - 0"
A701
2
6' - 0" 3' - 6"
ALIG
N
1A2A
ALIGN
BOTTLE FILLING STATION (SEE PLUMB.)
(N.I.C.)
A701
8
7
24' - 7" 24' - 7"
2A
ALIGN
LAUNDRY
230
2' -
0"
4' -
4"
1A 1A
1A
1A
1A
13' - 8 1/2" +/- 2' - 0" 5' - 5"
COPIER(N.I.C.)
SHREDDER(N.I.C.)
5' -
3"
4' -
6"
(N.I.C.) (N.I.C.)
TRANSACTION WINDOW
TRANSACTION WINDOW
212/1
223/1
223/2
4' - 9" 2' - 0"
A701
10
A701
9
8
A401
8
A401
5
A401
7
A401
A601
2
1' - 6" MIN.
8' - 7"
11' - 9"
EXISTING STAIR AND LANDING TO REMAIN
EXISTING HANDRAIL TO REMAIN
EXISTING STAIR AND LANDING TO REMAIN
217/1 216/1
218/1
214/1
215/1
207/1
207A/1206A/1
204/1202/1
227/1
228/1
226/1
230/1 222/1
225/1
213/1
200/1
45.00°
EXISTING MONITOR TO REMAIN
COLUMN(SEE STRUCT.)
1A
SF-2
200/2
9' - 0"
3SIM
SIM
1' -
0"
3' -
6"
3' -
3"
24
' -
9"
A601
3
218/2
217/2
C L1
' -
4"
10
A401
A701
13
10' - 1"
8' -
10
"7
' -
8"
1A
SOLIEDSTERILE LAB
211B
SF-1
5' - 1"
9
A401
ALIG
N
2
A401
B
1
A
B
COLUMN(SEE STRUCT.)
CO
NT
RA
CT
OR
TO
V.I.F
.
19
' -
10
" +
/-
2A
2A 2A
211A/1
211B/1
14
9' - 0"
15
ALIG
N
2A2A
2A
1A
1A
11
A401
14
' -
0"
2' - 0"
ALIGN
1' -
2"
10"
2' -
0"
3' -
6"
7' - 0"
4' - 6"
ALIG
N
TO SOFFIT ABOVE2' - 0" - ALIGN
MAINTAIN REQUIRED CLEARANCES
COORDINATE REQUIRED CLEARANCE WITH OPERABLE PARTITION MANUFACTURER
2A
1A1A
3"
7"
18
' -
7"
10"
6' -
0"
4' -
6"
1A
1A
1A
1A
1A3' - 5"
1B
1' - 0" MIN.
A
A
A
A
A
A
B
B
B
B
A B
BB
BB
B
AA
A
A
SF-3
2' -
0"
5"
COUNTER4" MAX
GL
AS
S
3' -
0"
FIX
ED
SLID
ER
3' -
0"
7"
201/1
HVAC (SEE MECH.)
A701SIM
2
6' - 7"
2' -
1"
6' -
7"
2' - 1"
2' - 1"
A
3' -
4"
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
THE PROFESSIONAL SERVICES OF THE ARCHITECT ARE UNDERTAKEN FOR AND ARE PERFORMED IN THE INTEREST OF:1)
NO CONTRACTURAL OBLIGATION IS ASSUMED BY THE ARCHITECT FOR THE BENEFIT OF ANY OTHER PERSON INVOLVED IN THE PROJECT.
DATE OF SIGNATURE: X.X.2021DATE OF REGISTRATION EXPIRATION:01/31/2022
1/4" = 1'-0"
4/1
/20
21 1
2:2
0:1
6 P
MC
:\U
se
rs\a
ca
mper\
Do
cum
ents
\202
01
79
00
_aca
mpe
r@b
ecke
rmo
rga
n.c
om
. rvt
A103
FIRST FLOOR FINISHPLAN
AMCJAD
04/01/2021
2020179.00
TERRY CAMPUS100 CAMPUS DRIVE, DOVER, DE
DTCCHEALTHCARECENTER OFEXCELLENCE
DELAWARE TECHNICAL COMMUNITYCOLLEGE
SCALE: 1/4" = 1'-0"1 FIRST FLOOR FINSH PLAN
GENERAL FINISH NOTES FINISH SYMBOL LEGEND
1. REVIEW ALL FIELD CONDITIONS AND PLANNED WORK. RESOLVE ALL DISCREPANCIES IN A MANNER APPROVED BY THE ARCHITECT THAT COULD AFFECT THE FINISHES OR TRANSITIONS PRIOR TO PROCEEDING WITH WORK AFFECTED BY DISCREPANCIES.2. SEE G101 CODE SHEET FOR INTERIOR FINISH REQUIREMENTS.3. REFER TO ELEVATIONS, REFLECTED CEILING PLANS AND DETAILS FOR ADDITIONAL INFORMATION REGARDING FINISHES, PATTERNS, ORIENTATIONS AND TRANSITIONS.4.PREPARE SURFACES PER FINISH MANUFACTURERS' INSTRUCTIONS PRIOR TO APPLICATIONS OF FINISHES, CONFIRM SURFACES TO RECEIVE FINISHES ARE CLEAN, TRUE AND FREE OF IRREGULARITIES.5. PREPARE SLAB TO RECEIVE NEW FINISHES, INCLUDING STRUCTURALLY BONDED HYDRAULIC CEMENT UNDERLAYS AND FLASH PATCHING REQUIRED TO LEVEL AND SMOOTH FLOOR TO 1/8" IN 20'-0" NON-CUMULATIVE, UNLESS OTHERWISE INDICATED AS FLATTER AND MORE LEVEL. CONCRETE FLOORS SHALL BE FREE FROM SCALING AND IRREGULARITIES AND SHALL EXHIBIT NEUTRALITY RELATIVE TO ACIDITY AND ALKALINITY. REMOVE GREASE, DIRT CURING COMPOUNDS AND OTHER MATERIALS THAT WILL IMPAIR THE PERFORMANCE AND/OR ADHESION OF THE SCHEDULED FLOORING.6. LOCATE FLOOR FINISH TRANSITIONS AT CENTERLINE OF DOOR, UNLESS OTHERWISE NOTED.7. PAINT AND FINISH EXPOSED SURFACES UNLESS OTHERWISE NOTED. PAINT SURFACES BEHIND REMOVABLE EQUIPMENT/FURNITURE. PAINT BEHIND NON-REMOVABLE ITEMS WITH PRIME COAT ONLY.8. SEALANT TO BE APPLIED BETWEEN BASE OF ALL DOOR FRAMES AND LVT FLOORING. SEALANT TO MATCH COLOR OF DOOR FRAMES.9. EXTEND FLOORING INTO ALL TOE KICKS, KNEE SPACES AND EXPOSED AREAS UNDER ALL CASEWORK. FLOORING AS SCHEDULED SHALL BE INSTALLED UNDER ALL NEW CASEWORK.10. MOLD AND MOISTURE RESISTANT GYPSUM BOARD SHALL BE USED AT ALL TOILET ROOMS, AND CUSTODIAN SERVICE CLOSETS SCHEDULED TO HAVE GYPSUM BOARD FINISHES. THIS INCLUDES UNDER ALL NEW CASEWORK AND APPLIANCES.11. SEE THE REFLECTED CEILING PLAN & NOTES FOR CEILING HEIGHTS, MATERIAL EXTENTS, LOCATIONS & HEIGHTS OF BULKHEADS, SOFFITS, ETC.12. PLAN WALL TYPES TAKE PRECEDENCE OVER SCHEDULED WALL FINISH. PROVIDE APPROPRIATE WALL FINISH TO CORRESPOND TO WALL TYPES.13. PROVIDE SEALANT/CAULK AT INTERSECTIONS OF DISSIMILAR MATERIALS AND AS RECOMMENDED BY MANUFACTURERS' GUIDELINES.
CEILING FINISH
WALL FINISH (FIELD)
WALL BASE FINISH
FLOOR FINISH
XX-1
XX-1
XX-1
XX-1
ROOM FINISH TAG:
FINISH TAG:
TARKETT JOHNSONITE RUBBER TRANSITION STRIP-COORDINATE WITH FINISH MATERIAL THICKNESS
SEE FINISH LEGEND
CPT LVT
FLOORING PATTERN INSTALL DIRECTION
FINISH LEGEND
KEYNAME PRODUCT MANUF. PATTERN/STYLE COLOR FINISH SIZE
INSTALLATION LOCATION
EXG EXISTING FINISH TO REMAIN - - - - -
FLOOR
CPT-1 CARPET TILE MANNINGTON RELAY BLUETOOTH 34145 24" X 24" BRICK
LVT-1 LUXURY VINYL TILE MANNINGTON NO RESERVATIONSABSTRACT
SS-1 SOLID SURFACE CORIAN RICE PAPER - LOBBY DESK AND BATHROOMCOUNTERTOPS
N
SCALE: 1/4" = 1'-0"
0' 2' 4' 8'
ISSUED:
ISSUED
FOR BIDDING
04/01/21
Mark Date Description
1 12/16/2020 ISSUED FOR AABREVIEW
2 12/18/2020 ISSUED FOR FINALOWNER REVIEW
3 04/01/21 ISSUED FOR BIDDING
FINISHES NOTED IN FINISH LEGEND ARE BASIS OF DESIGN. SEE SPECIFICATIONS FOR PERFORMANCE REQUIREMENTS
REF.
DN
DN
WD
CLASSROOM
217
WOMEN
215
CNA LAB
208
VESTIBULE
200
OFFICE
229
OFFICE
228
OFFICE
226
CLOSET
227
OFFICE
225
CORRIDOR
224
COPY/ WORKROOM
223
MEN
222
STORAGE
221
CNA LAB
218
CCMAA LAB
219
ELEC.
207A
CO
M.
RO
OM
206A
PHLEB. LAB
214
CLEANSTERILE LAB
211A
DIALYSIS LAB
213
DENTAL LAB
212
CORRIDOR
203
CORRIDOR
210
CORRIDOR
220
CO
RR
IDO
R
206
STORAGE
231
BREAKROOM
207
COMPUTERLAB
205
VENDING (BY OTHERS)
CLASSROOM
204
CLASSROOM
216
CLASSROOM
209
CORRIDOR
201
ALIG
N(N.I.C.)
LAUNDRY
230
(N.I.C.) (N.I.C.)
10
1213
13
11
11
10
10
10
1 1
1 1
1 1
1 1
MS-1 MS-1 MS-1 MS-1 MS-1
MS
-1
MS-1
3SIM
SOLIEDSTERILE LAB
211B
PROMETRIC
202
TABLE
14
5
8
STOR. 16"X 32"
WRAP. 16"X 32"
29
15
3
7
TABLE (BY OWNER)
6
LINEN CABINET, TYP. (BY OWNER)
COPIER(N.I.C.)
SHREDDER(N.I.C.)
11
11
16
16
1
4
SPECIALITY EQUIPMENT LEGEND
3M ATTEST MINI AUTO READER 2
WASHER DISINFECTORS STERILIZING P10003
(STERRAD STERILIZER) STERRAD NX
INTERGRITY STERILIZER 175SG5
HEIGHT ADJUSTABALE PROCESSING SINK6
SURGICAL SCRUB SINK (SINGLE)7
FLEX ULTRASONICS8
ERGOSTAT HEIGHT ADJUSTABLE PREP & PACK TABLE9
PHLEBOTOMY CHAIR10
DIALYSIS CHAIR12
DIALYSIS MACHINE13
DENTAL CHAIR 14
PHLEBOTOMY CART11
PATIENT BED - MED SURG W/ MATRESS 1
15
4
WRAPPING RACK
16 TREATMENT TABLE
EQUIPMENT NAME#
EQUIPMENT AND FURNITURE GENERAL NOTES
1. FURNITURE BY OWNER, SHOWN FOR REFERENCE ONLY, N.I.C.
2. CONTRACTOR SHALL COORDINITATE UTILITY CONNECTIONS FOR EQUIPMENT. MAINTAIN CLEARANCE REQUIREMENTS WITH ALL OTHER TRADES, TYP. FOR ROOMS 202, 208,211A, 211B, 212, 213, 214, 218, 219. EQUIPMENT BY OWNER, SHOWN FOR REFERENCE ONLY, N.I.C.
DEDC, LLC
FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL ENGINEER
315 SOUTH CHAPEL STREETNEWARK, DELAWARE 19711302-738-7172 fax: 302-738-7175
Set 1:(Coordinate with Storefront Manufacturer) 3 Hinge 1 Storeroom Lockset 1 Small Format Inter Core 1 Door Closer/Stop1 Electric Strike (By security vendor) 1 Card Reader, Fail Safe (By Security Vendor1 Power Supply (By security vendor) Notes: Connect power supply to fire alarm.Electronic Operation: Card reader unlocks outside trim. In case of power loss, door trim becomes unlocked. Free egress at all times.
Doors: 200/2, 201/1
Set 2:3 Hinge 1 Classroom Lockset1 Small Format Inter Core 1 Door Stop 1 Kick Plate 3 Silencer