Sheet No. Component /Detail Description 1 Draw ing Guide MGE Galaxy 3500 10-20kVA, 3:3 2 MOD Narrow w ith SBP Draw ing Guide 2-4 Solution MGE Galaxy 3500 Narrow Tow er 10-20kVA 2 MOD, SBP, 400V. 5-7 UPS MGE Galaxy 3500 10-20kVA 400V, 3Ph In 3Ph Out, Narrow Tow er 8-11 SBP MGE Galaxy 3500 System Bypass Panel, Wall Mount, 60kVA, 400V 12-13 System One Line Diagram MGE Galaxy 3500 10-20kVA 400V 2MOD w ith SBP System One Line Diagram 14 System Wiring Diagram MGE Galaxy 3500 10-20kVA 400V 2MOD w ith SBP System Control Wiring Diagram
14
Embed
Sheet No. Component /Detail Description - APC by Schneider …€¦ · · 2016-02-1515kVA 2 x G35T15KH2B2S. ... Consult Schneider Electric for application specific assistance. 6.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Sheet No. Component /Detail Description1 Draw ing Guide MGE Galaxy 3500 10-20kVA, 3:3 2 MOD Narrow w ith SBP Draw ing Guide
2-4 Solution MGE Galaxy 3500 Narrow Tow er 10-20kVA 2 MOD, SBP, 400V.5-7 UPS MGE Galaxy 3500 10-20kVA 400V, 3Ph In 3Ph Out, Narrow Tow er8-11 SBP MGE Galaxy 3500 System Bypass Panel, Wall Mount, 60kVA, 400V12-13 System One Line Diagram MGE Galaxy 3500 10-20kVA 400V 2MOD w ith SBP System One Line Diagram
14 System Wiring Diagram MGE Galaxy 3500 10-20kVA 400V 2MOD w ith SBP System Control Wiring Diagram
40kVA/32kW G35T40KH4B4S 98.2 108 115.4 40kVA/32kW 115.4 110.1 63 63 63 1491x523x838 662 1510 1279Notes. 1. Nominal Input current based on nominal mains voltage + batteries fully charged at 100% ohmic load. 2. Maximum Input current based on fully battery recharge + nominal mains voltage at 100% ohmic load. 3. Suggested input overcurrent protection based on continuous full load. 4. Nominal battery voltage assumed to be 2.0 volts/ cell (lead technology) 5. Over current protection device rating selection based on Nominal input current is acceptable provided battery recharge time is short. Consult Schneider Electric for application specific assistance. 6. Voltage tolerance is 304 - 477V, 47 - 53Hz nominal 50Hz. 7. Input power-factor is > 0.98 for > 50% loading. 8. Cable installation to comply with EN60364-5-52, max ambient 30 deg C, cable sizes shown refer to 600V rated,90 degree C multicore copper conductors with thermosetting insulation unless otherwise mentioned 9. AC input & output to be L1, L2, L3, N & PE depending on 400/230V configuration, PE may be separate or SWA of armored cable 10. Overcurrent protective devices (OCPD) may be either gL fuse type or MCB/MCCB rated at 30kA fault rating 11. DC cabling should be sized to give < 1% voltage drop at the nominal battery discharge current using three-wire separate conductors in positive, centre-tap and negative poles 12. Top or bottom cable entry with removable gland plates 13. Control wiring to be run separately using screened conductors away from power cabling preferably in a separate conduit or cable tray
18. Input : THD < 1.5% Linear Load, <3.5% Non Linear Load17. Input : THD < 5% at Full Load 16. Refers to maximum battery recharge conditions 15. Heat loss refers to max loading and fully charged batteries in conjunction with cable drop to size cabling from cabinet to UPS 14. Weights and dimensions are with internal batteries, with extended battery cabinets use battery discharge current
50
Galaxy 3500® 10K and 40K UPS Frame (2 Module) Site Planning Data - with MBP
16
25
3232 32
50 50
25 25
27.5
Recommended Over current Protection Device Ratings