Boiler - Protections, Emergencies and Losses

Kumar RupeshDate: 04-Sep-13

Page 2: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 2

Objectives and other details of modules

Duration – 90 + 75 minutes

Training aids Power point Presentations

Reading Material

Objective At the end of the session participants will be able to: Describe various boiler protections List out events occurring at the time tripping of boiler Illustrate events associated with boiler emergencies Apply procedures prescribed for handling boiler emergencies Undertake planned boiler shutdown Describe reasons for boiler efficiency losses and components wise heat

losses Calculate boiler efficiency Apply corrective action for reducing boiler losses

Page 3: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 3

Contents

Boiler Protections Boiler Emergency Boiler Planned Shutdown Boiler Losses and Efficiency

Page 4: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Protections

Page 5: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Protections

Boiler Trip Conditions

Both FD Fans Off

All ID Fans Off

Inadequate Waterwall Circulation

Loss Of Reheat Protection

Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic)

All Boiler Feed Pumps Off

Drum Level High-High (> + 250 mm, delay of 10 seconds)

Drum Level Lo-Lo (< - 375 mm, delay 10 seconds)

Elevation Power Failure For > 2 seconds.

Furnace Pressure High-High (> + 325 mmWC, 2 / 3 logic)

Furnace Pressure Lo-Lo ( < -250 mmWC, 2 / 3 logic )

Page 6: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Trip Conditions

Loss Of All Fuel

Unit Flame Failure

Loss Of Critical Power For > 2 seconds

Loss Of 220 V DC For > 2 seconds

Loss Of ACS Power > 2 seconds

Less than fire ball & loss of AC at any Elevation in service

Simulator Trip

Air Flow < 30 %

Both Emergency Push Buttons Pressed.

Boiler Protections contd.

Page 7: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 7

When the boiler trips the following events takes place: Boiler Trip red lamp comes on MFT A & B trip lamp comes on and reset lamp goes off Cause of trip memory can not be reset till the furnace purge is completed FD Fans Control is transferred to manual ID fans vane position is transferred to manual Pulverizers are tripped Coal feeders are tripped P A Fans are tripped and permit to start PA fan signal is removed. Cold air dampers opens to 100 % (TD – 300 Secs) HFO trip valve closes and the Oil elevation trip memory signal is established. All HFO Nozzle valves close Upper and Lower Fuel air damper opens Auxiliary air damper opens and control is transferred to manual Loss of all fuel trip protection disarms S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed Turbine Trips

Boiler Protections – MFT actions

Page 8: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Protections contd.

Inadequate Water Circulation (500 MW)Condition-1: (Boiler Load > 60 %) And (Less Than Two Pumps ON OR Pump On And Differential Pressure < 10 Psi). Condition-2: (Boiler Load < 60 %) And (no Pump ON OR Pump On And Differential Pressure < 10 Psi)Reheat Protection (500 MW)Condition-1: (Turbine Trip OR Generator Circuit Breaker Open)

AND (HP/ LP Bypass Opening <2%)

Condition-2: Turbine Working (HPCVs and IPCVs opening > 2%)AND (Load Shedding Relay Operated)AND (HP/ LP Bypass Opening <2%)

Condition-3: (Turbine not working AND Boiler Working i.e. 2 oil guns proven) AND (HP/ LP Bypass Opening <2%)

Page 9: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Protections contd.

September 4, 2013 Footer text 9

Page 10: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Protection - Loss of All Fuel

September 4, 2013 Footer text 10

Loss of All Fuel Protection Arming (500 MW)Any Elevation OIL nozzle valve not closed AND MFT Reset (TD – 5 Secs)

Loss of All Fuel Protection (500 MW) – No Coal and No OilLoss of all fuel trip arming setANDAll feeders offAND(HOTV not open) OR (All Elevation (AB,CD,EF,GH) backup trip) OR (All HO nozzle valves closed )AND(LOTV not open) OR (Elevation AB backup trip) or (All LO nozzle valves closed)

Less than Fireball and Loss of AC at any Elevation in ServiceAll feeders offANDAny Elevation (AB, CD, EF, GH) started & loss of 110 V AC (TD-2 sec)

Page 11: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 11

Flame Failure Trip Arming (500 MW)Any Feeder (A, B, C, D, E, F, G or H) ProvenFlame Failure TripFlame Failure Trip Protection Arming set

ANDAll Elevations (A, B, C, D, E, F, G and H) Voted No Flame

Elevation A Voted No Flame[(Elevation AB more than one nozzle valves not open)AND (Elevation AB Less than 2 Fire scanners sensing no Flame)]OR[Elevation AB Started and Loss of 110 V AC(TD- Secs)]OR[Feeder-A Not Proven]

Boiler Protection – Flame Failure

Page 12: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 12

Elevation B Voted No Flame[Elevation BC Less than 2 Fire scanners sensing no Flame]AND[(Elevation AB more than one nozzle valves not open)AND (Elevation AB Less than 2 Fire scanners sensing no Flame)]OR[Elevation AB Started and Loss of 110 V AC(TD- Secs)]OR[Feeder-A Not Proven]

Boiler Protection – Flame Failure contd.

Page 13: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 13

Elevation C Voted No Flame[Elevation BC Less than 2 Fire scanners sensing no Flame]AND[(Elevation CD more than one nozzle valves not open)AND (Elevation CD Less than 2 Fire scanners sensing no Flame)]OR[Elevation CD Started and Loss of 110 V AC(TD- Secs)]OR[Feeder-C Not Proven]

Nearest Oil Elevation not provenAND Nearest Scanners not provenOR Coal Feeder not proven

Boiler Protection – Flame Failure contd.

Page 14: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 14

FSSS Power Supply

Page 15: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 15

220 V AC Supply System Analogue Control System Annunciation Aux Relay Panel DAS Feeder Cabinet FSSS AC Supply HP Bypass Cabinet Hydrastep SADC110 V AC Supply System Atomising Steam, HONVs, LONVs Flame Scanner Module Mill Discharge Valve Mill Feeder Control Mill Seal Air Damper etc.

FSSS Power Supply contd.

Page 16: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 16

ORMFT-1

24 V DC Failure

ORMFT-2

24 V DC Failure

ORMFT-3

24 V DC Failure

2/3 Logic Boiler Trip

220 V DC Supply System HFO Trip Valve HFO Recirculation Valve Mill Motor Control Scanner Air Fan Discharge and Emergency Suction Damper etc.Elevation Power Failure – 2 Secs – 110V AC power failure at respective

elevationsLoss of Critical Power Failure – 2 Secs – 24 V DC Power failure (Hardwired)

MFT and 24 V DC Hardwired Integration

FSSS Power Supply contd.

Page 17: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Emergencies and Shutdown

Page 18: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 18

One PA Fan Tripping (2 X 50% configuration) The discharge damper of tripped PA Fan takes time to close full. Due to fan

tripping and running fan air short circuiting the PA Header pressure falls belowexpected.

Take the running PA on manual and restrict its BP from overloading. Stop upper mills such that half of the running mills from bottom are in service. Immediately close the BP of fan tripped, Interconnecting damper of PA fans

and CADs & HADs of mills stopped to reduce running fan demand. Take the oil support only after PA header pressure has recovered. An early

action may result into furnace explosion due to high coal input and oil inputsimultaneously when PA header pressure recovers.

Due to sudden pressure drop, drum level also surges violently. Maintain drumlevel properly.

Boiler Emergencies – PA Fan Tripping

Page 19: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 19

One ID Fan Tripping (2 X 50% configuration) The inlet gate/ damper of tripped ID Fan takes time to close full. Due to fan

tripping and running fan air short circuiting the furnace pressure rises aboveexpected.

Take the running ID Fan on manual and restrict its IGV to avoid fanoverloading.

Stop upper mills one by one in sequence with a time delay of minimum 5 secseach such that half of the running mills from bottom are in service.

Trip one of the FD Fans. Immediately close the IGV of fan tripped, the interconnecting damper and

CADs & HADs of mills stopped to reduce running fan demand. Take the oil support only after furnace pressure has recovered. An early

action may result into furnace explosion. Due to sudden pressure drop, drum level also surges violently. Maintain drum

level properly.

Boiler Emergencies – ID Fan Tripping

Page 20: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 20

HPHs group bypass The HPHs extraction steam may amount to 8-10% of full load steam flows.

Expansion of this amount of steam in turbine leads to sudden load shoot up. As sensible heat is no more added in HPHs, this shall be added in

Economiser and Water Wall. Thus lower heat is available for steamevaporation.

This results into lower heat evaporation. Also, there is higher FG heatconsumption in water wall. Out of these competing features, former dominatesand SH and RH steam temperatures rise rapidly.

Also, due to very high heat consumption in Economiser, PA temperature pick-up in APH is low and its difficult to maintain Mill outlet temperature.

Drum Pressure also drops rapidly due to lower evaporation. This results intolower BFP discharge Pressure.

Increase SH and RH spray to maximum. Also, increase ΔP across FRS forhigher BFP pressure and hence spray.

Bring burner tilt to lowest position. Take-out the highest mill out of service. When temperature stabilises, higher coal than condition before disturbance

shall be required to restore load.

Boiler Emergencies – HPHs Group Bypass

Page 21: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 21

Lower Mill Tripping It has similar effects on MS and RH temperature as HPHs tripping. The action

should be taken accordingly. MS Pressure TX going out of order As MS flow incorporates pressure and temperature correction, a sudden loss of MS

Pressure TX (one used for pressure compensation), results into lower MS flowmeasured by the system.

The three element drum level control reduces the FW flow in response. Thus,BFPs start unloading and the drum level drops fast.

If analyzed in time, take BFPs in manual and restore the flow to suitable value. N-1 mills to N mills operation Assume that a lower number of mills are operating near full load and additional mill

is taken in service. Generally, bowl mills operating at full load have choking tendency. Before cutting in

the new feeder, it is advisable to clear the choking of one mill at a time. Reducing coal flow in all mills and simultaneous command to extra feeder pumps

excess coal in Boiler and all the pressures rise rapidly. This may result into safetyvalve operation, HP/ LP bypass operation, vacuum deterioration etc.

Boiler Emergencies – others

Page 22: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 22

Planned Boiler Shutdown (in conjunction with Turbine operations)

Reduce Loading of TG set to 75% with two pulverizers withdrawn.

Reduce Loading of TG set below 50% with HP-LP bypass in operation with

three pulverizers withdrawn

Remove one ID, one FD and one PA fan

Reduce Loading of TG set to 25% with two pulverizers and AB/ CD oil

elevation in service

Reduce loading of TG set to 10-15% with one pulverizer and AB & CD Oil

elevation in service

Trip Turbine and put on barring gear

Take Boiler under shutdown

Boiler cooling and Shutdown of Air & Flue gas system

Planned Boiler Shutdown - Sequence

Page 23: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 23

Pulverizer shutdown

Take top mill feeder in manual and reduce it to minimum.

Close the HAG and HAD and open CAD full.

Close bunker silo gate. When mill outlet temperature drops rapidly, stop mill

feeder. The other mills may be loaded if Fuel master is on Auto.

Wait till pulverizer grinding current reduces to minimum. Mill bowl DP and

outlet temperature comes down indicating emptying of mill.

Open the tramp iron gate to remove any rejects.

Stop pulverizer. Close Fuel Air Damper.

Close CAD full.

Close Pulverizer seal air valve (may close on interlock). Close pulverizer

discharge valve.

Planned Boiler Shutdown - Pulverizer Shutdown

Page 24: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 24

Load Reduction to 75% Load gradient shall not be more than recommended by OEM. Generally it is

5MW/min for planned shutdown. Reduce the Unit master demand gradually to 75% if in CMC. If in manual, put

machine in load controller, reduce mill firings and withdraw two pulverizersone by one.

Reduce the throttle steam pressure also to 75% of rated value. Withdraw HPHs by closing the extraction steam valves. Drum pressure

increases first then comes down. Reduce AVR set point if required. Take attemperation control in manual and increase sprays slightly to bring

down MS and HRH temperatures for turbine cooling. Also lower burner tilt. MSP and Reheat Pressure also drops. ESV and CV surface temperature and mean temperature starts dropping. HP casing and shaft temperatures also start dropping.

Note: If the unit is withdrawn for short duration, MST and HRHtemperature should not be dropped very low.

Planned Boiler Shutdown - Load Reduction

Page 25: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 25

Load Reduction below 50% with HP-LP Bypass in service Keep machine in pressure controller, and reduce firing further. Take another

mill out of service. Withdraw one set of ID, FD and PA fans. Reduce the throttle steam pressure also to 50% of rated value. Both load and

MS/ HRH pressure, MST, HRHT and valves & shaft temp keeps dropping. Reduce AVR set point if required. Take machine on load controller mode. Put HP bypass set point near throttle pressure set point. Put LPBP also on auto with fix set point slightly below sliding set point. Reduce load set point. As throttle pressure tries to increase, HPBP opens. As

HRH pressure increases above sliding set point LPBP also opens. Take CD or AB Oil elevation and withdraw another Mill. For load < 20%, withdraw LPHs. UAT to Station C/O to be carried out. Take AB oil elevation and withdraw another mill.

Note: If the unit is withdrawn for short duration, MST and HRHtemperature should not be dropped very low.

Planned Boiler Shutdown - Load Reduction contd.

Page 26: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 26

Withdrawal of one set of ID, FD and PA Transfer the furnace pressure controller to manual. Unload one of the ID fans

and load other through IGV. Stop one fan. Ensure that discharge dampercloses on auto. Stop the lube oil pump only after bearing temperature comesto normal.

Transfer the PA header pressure controller to manual. Unload one of the PAfans and load other through BP. Stop one fan. Ensure that discharge dampercloses on auto. Stop the lube oil pump only after bearing temperature comesto normal.

Transfer the oxygen controller to manual. Unload one of the FD fans and loadother through BP. Stop one fan. Ensure that discharge damper closes onauto. Stop the lube oil pump only after bearing temperature comes to normal.

After, killing of Boiler two ID and FD fans running is not recommended asBoiler cooling becomes very fast and drum top-bottom temperature differenceexceeds 50 Deg C.

Planned Boiler Shutdown - Fans withdrawal

Page 27: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 27

Boiler Shutdown Withdraw the last pulverizer. Ensure that all Fuel Air Dampers are closed. Stop the running PA fan. Keep the lube oil pump running till the bearing

temperature comes down. Ensure that discharge dampers of both the fansopen on auto. Stop seal air fans.

Bring burner tilt to horizontal position. Adjust air to 30-40%. Remove CD oil gun elevation. The scavenzing should take place in gun

withdrawal sequence. Remove AB oil guns. As the 4th nozzle valve closes, Boiler MFT operates on

loss of all fuel. Ensure that LOTV and HOTV closes. Start furnace purge cycle and complete furnace purging. Do not drain the Boiler immediately. If fast boiler cooling is required, leave one ID and FD in service. Maintain the air

flow such that Drum top – bottom temp difference maintains below 50 Deg C.

Planned Boiler Shutdown - Firing Shutdown

Page 28: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 28

Boiler ShutdownNote: Boiler draining is advisable only after Drum top-bottom temperaturedifference is below 50 Deg C and Drum top and bottom metal temperaturedrops to < 110 Deg C.

Air and Flue Gas System Withdrawal Reduce the FD fan BP to minimum and stop FD Fan. Stop the lube oil pump only

after the bearing temperature comes to normal. Discharge damper of both thefans open full on auto.

Scanner Air Fan emergency suction damper from atmosphere opens on Auto. Reduce the ID fan IGV to minimum and stop ID Fan. Stop the lube oil pump only

after the bearing temperature comes to normal. Discharge damper of both thefans open full on auto. This helps in natural cooling of furnace.

When FG temperature at APH inlet falls below 120 Deg C, stop APHs. Keep FGand Air side dampers at APH inlet and outlet open for natural air circulation.

Stop SCAPH steam supply if in service. ESP fields can be withdrawn. Scanner Air fan to be stopped only when Furnace is sufficiently cooled.

Planned Boiler Shutdown - Air and FG system shutdown

Page 29: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

Boiler Losses and Efficiency

Page 30: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 30

Boiler Losses - Overview

Page 31: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 31

Important AspectsGCV (Gross Calorific Value) basis vs. NCV (Net Calorific Value) basisCalculation:NCV = GCV – 578(m + 9 H2) kcal/kgwhere, m is mass of moisture/ kg of fuel and H2 is mass of Hydrogen/ kg offuel(As, H2 + ½ O2 = H2O, i.e. 1 g of hydrogen produces 9 g of water)578 kcal/kg is the latent heat of vaporization of moisture

When calculation is done on GCV basis, it is the total fuel heat which isconsidered for evaluation. It gives the pessimistic figure of boiler efficiency asthe heat carried away by moisture is system requirement and not due toinefficacy of heat transfer surfaces. But, for ascertaining the fuel requirementfor specified quantity of steam, this methodology must be adhered to.

When calculation is done on NCV basis, it is the available heat which isconsidered for evaluation. It gives the correct picture of Boiler efficiency.

Boiler Efficiency Calculation – Important Aspects

Page 32: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 32

Important AspectsInput-Output method vs. Heat Loss method:

Input-Output (or Direct method as per BS) gives Gross Boiler Efficiency as(net Output/ Total Input). The net out put is measured by steam flow andsteam enthalpy – FW Flow and FW enthalpy.

Heat Loss Method (or Indirect method as per BS) gives gross boiler efficiencyas (100 – Heat Loss/ Total Input). The heat losses are measures bymeasuring various temperatures, pressures, % by weight, heating value ofash etc.

As the direct method of efficiency measurement involves measurement ofsteam flow which inherently can not be too accurate, its accuracy is lower.Further, the sensitivity of inaccuracy in direct method has larger effect. E.g. ina Boiler of 80% efficiency, a 2% error on parameter measurement reflects1.6% error in final result whereas it reduces to 0.4% for Indirect method.

For both of the methods the Calorific value of the coal should be fairlyconstant throughout the testing.

The direct method being simple and cost effective is used for day-to-dayassessment of Boiler condition. The indirect method is cost intensive and isused as acceptance test for Boilers.

Boiler Efficiency Calculation – Important Aspects

Page 33: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 33

Heat Loss Method Components and CalculationComponents:I. Stack Lossesa. Dry gas loss (Ldg)b. Moisture Loss (Lm)c. Humidity Loss (Lh)II. Unburnt Loss (Lub)III. Radiation Loss (Lr)IV. Unaccountable Loss (Lu)

I. Stack Loss is a measure of how well the exit gases are cooled and flue gasquantities are maintained. The dry gas loss covers 70-80% of total losses,moisture loss varies from 8-20% of total losses and Humidity losses are <0.1%.

Boiler Losses – components and calculation

Page 34: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 34

Dry Gas Loss (Ldg)% on GCV basis = Wg (Tg – Ta) X Cp X 100GCV

Dry Gas Loss (Ldg)% on NCV basis = Wg (Tg – Ta) X Cp X 100NCV

Where,Wg = weight of gas leaving the system in kg/ kg of fuel burnt (not fired)Wh = weight of moisture in air in kg/ kg of fuel burntTg = temperature of flue gas leaving the system in 0 CTa = temperature of air entering the system in 0 CCp = mean specific heat of gas between Tg and Ta

Moisture Loss (Lm)% on GCV basis = (9 H2 + m) X (Hs – ha) X 100GCV

Moisture Loss (Lm)% on NCV basis = (9 H2 + m) X (Hs – ha - 578) X 100NCV

H2 = percentage hydrogen in fuel by weightm = percentage moisture in fuel by weightHs = Enthalpy of steam at Tg and 1 psia is equal to 578 kcal/kgha = enthalpy of water at Ta in kcal/ kg

Boiler Losses – components and calculation contd.

Page 35: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 35

Humidity Loss (Lh)% on GCV basis = Wh X (Hs – ha) X 100GCV

Humidity Loss (Lh)% on NCV basis = Wh X (Hs – ha) X 100NCV

Wh= percentage hydrogen in fuel by weightHs = Enthalpy of steam at Tg and 1 psia is equal to 578 kcal/kgha = enthalpy of water at Ta in kcal/ kg

II. Unburnt Loss is a measure of how well the fuel is burnt in the firing equipment forthe excess air chosen. Efficiency of heat release of firing equipment is measured bythe amount of carbon burn-up.Carbon burn-up (Cb) = (100 - % carbon in the residue)

% total carbon at inletThe unburnt loss (Lub)% on GCV basis = Percent ash in fuel X Ca X 80.78

GCVThe unburnt loss (Lub)% on NCV basis = Percent ash in fuel X Ca X 80.78

NCVWhere, Ca = % of combustible in fly ash and bottom/ bed ash

Boiler Losses – components and calculation contd.

Page 36: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 36

III. Radition Loss is a comprehensive measure of losses caused by radiation andconvection conductance for Boiler, ducting and milling plant. This can be calculatedon actual basis with respect to reference temperatures. Alternatively, it can bederived from radiation loss curve given by ABMA (American Boiler Manufacturer’sAssociation).The radiation losses are below 1% and become smaller as the boiler size and watercooled surfaces increase.

There are limitation of the ABMA graph but it is very popular due to its convenienceand low value of radiation loss. For example, the loss is not based on surface areaof boiler but the evaporation capacity. Thus, a compact oil fired boiler of samecapacity as PF fired boiler shall have same radiation loss.

IV. Unaccountable Loss cannot be exactly quantified and are small enough to becombined as a reasonable value. They usually comprise of losses like heat loss inash, unstated instrument tolerances and errors, any other immeasurable losses etc.Generally it is agreed before the test itself.

Boiler Losses – components and calculation contd.

Page 37: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 37

Note: The losses are based on assumption of surface to ambient temperaturedifference as 27 0C and the air velocity of 0.5 m/sec.

Boiler Losses – components and calculation contd.

Page 38: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 38

Optimization – Lowering the losses and Auxiliary ConsumptionI. Stack Loss Reduction Minimum exit FG temperature avoiding low temperature gas corrosion. Larger

surface area for heat recovery at lower temperatures are required. Minimum excess air without compromising combustion with traces of CO. This

requires careful metering. Reduce Air infiltration through leakages to reduce weight of exit flue gas Reduce gas bypassing the banks due to excessive gap between coils Regular Soot BlowingII. Unburnt Loss Reduction Maintain there Ts – Time, Temperature, Turbulence Proper Coal Fineness Proper secondary air controlIII. Radiation Loss Reduction Proper insulation such that surface temperature is about 20-25 0C above ambient.IV. Fan Power Reduction Optimum gas velocity – Optimum pressure drop – Optimum Fan head Optimum Excess Air

Boiler Losses – Controlling measures

Page 39: Session 5 Module 1 & 2 - Boiler Protections, Emergencies and Efficiency

September 4, 2013 Footer text 39

Optimization – Lowering the losses and Auxiliary ConsumptionFan Power Reduction contd.

Highest Efficiency – Axial Flow for clean application and Careful design foroperating point matching best efficiency point

Use of VFDs and VHCs for low load condition savings Low margins on head and flowV. Pump Power Reduction Careful design for operating point matching best efficiency point Low margins on head and flow Use of VFDs and VHCs for low load condition savings

Boiler Losses – Controlling measures contd.