C2W36CE-DQME2M99 (Master) C2X36CE-DQME2M99 (Expansion) The Server Technology® PRO2® Switched PDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched “Master” PDU can be connected to as many as three (with optional module) PRO2 Switched “Link” PDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking configuration. Key Features Alt Phase Branch Circuit Protection Branch Current Monitoring Enviromental Monitoring Flexible Mounting High Density Outlet Technology High Retention Outlets High Temperature Hot Swappable Input Current Monitor Multi Link Expansion Network Monitoring
7
Embed
Server Technology Datasheet C2W36CE-DQME2M99 · SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP Certifications North American: cTUVus Mark
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
C2W36CE-DQME2M99 (Master)
C2X36CE-DQME2M99 (Expansion)
The Server Technology® PRO2® Switched PDU provides control of outlet power and local LEDinput current monitoring, allowing IT personnel to determine safe levels of loading on a per-phasebasis while installing equipment into the rack/cabinet. The integral PIPS® technology providesbilling-grade accurate measurement of current, voltage, active power, apparent power, power factor,crest factor, and accumulated energy at the input. These power data points, along with temperatureand humidity measurements (provided via optional probes), are accessible through the built-in Weband CLI interfaces as well as through SNMP. The PRO2 Switched “Master” PDU can be connectedto as many as three (with optional module) PRO2 Switched “Link” PDUs to extend the networkaccess to the redundant or secondary power feed without the risks of a daisy chain linkingconfiguration.
Key Features
Alt Phase Branch CircuitProtection
Branch CurrentMonitoring
EnviromentalMonitoring
Flexible Mounting High Density OutletTechnology
High RetentionOutlets
High Temperature Hot Swappable Input CurrentMonitor
Multi LinkExpansion
Network Monitoring
Inputs
Input Voltage:Input Voltage: 208 Input Plug:Input Plug: IEC 60309 3P + PE 60A IP44 Input Current:Input Current: 60 Input Current Rated:Input Current Rated: 48 Cord Entry:Cord Entry: End Cord:Cord: 10ft (3m), 4-conductor, 6AWG
Outputs
Connector:Connector: (18) x IEC 60320/C13 North American Rating (C13):North American Rating (C13): ≤ 12A @208V L-L (15A Peak)
Connector:Connector: (18) x IEC 60320/C19 North American Rating (C19):North American Rating (C19): ≤ 16A @208V L-L (20A Peak)
Outlet #1 opposite cord end
Locking outlets provide high-retention even for non-locking cords.
Dimens ions :Dimens ions : 70in (1778mm) tall x 2.2in (56mm) wide x 2.5in (64mm) deep | Weight: 34.8lbs(15.79kg) Highlight Color:Highlight Color: Choose Black, White, Red, Green, Blue, Yellow
Environmental
Operating Environment:Operating Environment: 32°F to 140°F / 0°C to 60 °C | 8%RH to 90%RH non-condensing |6,500ft/2km elevation Storage Environment:Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing |50,000ft/15km elevation
Outlet Control PDU Colors Per Inlet PowerSensing
Quiescent / Unloaded Power Draw: < 10W for all configurations
Communications & Security
10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector) Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU} Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet,SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
North American:North American: cTUVus Mark to UL 60950-1:2007 R10.14 CAN/CSA-C22.2 No. 60950-1-07+A1:2011+A2:2014 FCC Part 15 Subpart B Sections 15.107 and 15.109, Class A
Measurement Accuracy
Input Meas urement Accuracy: Input Meas urement Accuracy: LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp) Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%) Active Power = ± 1% at 1 watt resolution Apparent Power = ± 1% at 1 volt-amp resolution Power Factor = ± 3% at 0.01 resolution Crest Factor = ± 10% at 0.1 resolution Energy = ± 1% at 0.1 kilowatt-hour resolution
Accessories
Included Accessories
Mounting Buttons included for tool-less mounting (KIT-0020)
Two (2) temperature/humidity ports (one probe included)One (1) water sensor port (probe sold separately) (EMWS-1-1)Four (4) dry contact (NO/NC) monitoring pointsOne (1) 8-bit analog-to-digital converter (0 to 5VDC)
StartUp Stick™ for rapid configuration. (KIT-SUS-01) Multi linking adapters, provides ability to link (2) additional PRO units (KIT-PRO2LINK-01M or -01D) Server Tech DB9-RJ12 adapter (ADP-0019)
Server Tech RJ45-8P8C-rolled telco-type patch cable (CAB-1205) Mounting Brackets:
See the Mounting Bracket Guide for further suggestionsCustom mounting options available. Contact your local Server Technology representative
Cable Retention Devices for non-locking cords:
Ezip Cable Retainer for HDOT C13 outlets (KIT-HD13)Ezip Cable Retainer for HDOT C19 outlets (KIT-HD19)Cable Sleeve C13 (KIT-0070) C19 (KIT-0071)
Raritan IEC Secure Lock Power Cords – https://www.raritan.com/products/power/accessories/securelock-power-cords
Drawings
Mechanical Drawing Mechanical Drawing
Electrical Drawing Electrical Drawing
Additional Information
Warranty:Warranty: Server Technology offers a standard 2-year limited parts & labor warranty. Extendedsupport is available at the time of purchase. See the Support Options on the website, or contact yourlocal Server Technology representative for more information.
Patents :Patents : Information on Server Technology patents is available on the website at:
www.servertech.com/products/patents
PRO2, HDOT, PIPS, POPS, CDU, Sentry, Server Technology, and the globe logo are U.S. registeredtrademarks of Server Technology, Inc. Power Pivot, EZip, and StartUp Stick are trademarks of ServerTechnology, Inc.