Series Ratings For NQOD, NF and I-LINE Panelboards Class 1630, …stevenengineering.com/pdf/45PanelBoard_Lighting_ Appliance.pdf · The circuit breakers shown are the lowest rated
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure, except for LC mains (see footnote).
NQOD Series Ratings
Note:
All series ratings with QO and QOB branches include devices with EPD, GFI, HID, SWN, HM, PL and AS suffixes, except as noted.
c
Applicable to 208 V maximum systems.
a
SWN suffix is not available with LC mains. LC mains are remote mounted only.
NQOD Series Ratings
NF Series Ratings
I-LINE Series Ratings
q
The circuit breakers shown are the lowest rated in the frame type for which the series rating may be applied. The series ratings shown may also be applied to higher interrupting circuit breakers of the same frame type.
System Voltage
(Maximum)
UL SeriesConnected Rating
(AIR)
Main Branch
Type Max. Amperes Type Amperes Poles
240 Vac
22,000
QOB-VH 150 QO, QOB10–70 110–125 210–100 3
Q2-H 225 QO, QOB10–70 110–125 210–60 3
25,000 KD 250 QO, QOB10–70 110–125 210–60 3
65,000 KG 250 QO, QOB10–70 110–100 210–100 3
42,000 LC
a
400
QO, QOB15–70 1
. . . 2
. . . 3
QO-VH,QOB-VH
15–30 115–125 215–100
c
3
QO-GFI,QOB-GFI
15–30 115–60 2
. . . 3
65,000 LC
a
400
QO, QOB15–30 1
. . . 2
. . . 3
QO-VH,QOB-VH
15–30 115–125 215–100
c
3
QO-GFI,QOB-GFI
15–30 1. . . 2. . . 3
100,000
FC 100 QO, QOB10–70 110–100 210–100 3
KC 250 QO, QOB10–70 110–150 210–150 3
200,000
FI 100 QO, QOB10–70 110–100 210–100 3
KI 250 QO, QOB10–70 110–150 210–150 3
SystemVoltage
(Maximum)
UL SeriesConnected Rating
(AIR)Remote Main Fuse
Branch Type
Type Amperes Poles
240 Vac 200,000
200 Ampere MaximumClass J or T (600 V)
QO,QOB
15–70 115–125 215–100 3
QO-AS,QOB-AS
15–30 115–30 215–30 3
QO-GFI,QOB-GFI
15–30 115–60 2
400 Ampere MaximumClass T (300 V)
QO,QOB
15–70 115–125 215–100 3
QO-AS,QOB-AS
15–30 115–30 215–30 3
QO-GFI,QOB-GFI
15–30 115–60 2
System Voltage
(Maximum)
UL SeriesConnected
Rating(AIR)
Main Type Branch Type Poles
240
65,000 EG, FH, FG, KH, LH, MH, MX EDB
1, 2 & 3100,000 EJ, FC, FJ, KC, LC, LX EDB, EGB
200,000 FI, KI, LI, LXI EDB, EGB, EJB
480Y/277
35,000 EG, FG, KH, LH EDB
1, 2 & 365,000 EJ, FC, FJ, KC, LC, LX EDB, EGB
200,000 FI, KI, LI, LXI EDB, EGB, EJB
Remote Main Fuse
480Y/277100,000 400 Ampere Maximum
Class J or T (600 V) EDB, EGB, EJB 1, 2 & 3
200,000 200 Ampere MaximumClass J or T (600 V) EDB, EGB, EJB 1, 2 & 3
System Voltage
(Maximum)
UL SeriesConnected Rating (AIR)
Main Branch
Type Max. Amperes
Type
q
Amperes Poles
240 Vac 100,000
FC 100
FY 15-30 1
FA15-100 115-100 215-100 3
KC 250
FY 15-30 1
FA15-100 115-100 215-100 3
KA 70-250 270-250 3
LC, LX 600
FY 15-30 1
FH15-100 115-100 215-100 3
KA 70-250 270-250 3
LA 125-400 2125-400 3
240 Vac 200,000
FI 100
FY 15-30 1
FA15-100 115-100 215-100 3
KI 250
FY 15-30 1
FA15-100 115-100 215-100 3
KA 70-250 270-250 3
LI, LXI 600
FY 15-30 1
FH15-100 115-100 215-100 3
KA 70-250 270-250 3
LA 125-400 2125-400 3
LC 300-600 2300-600 3
480 Vac 65,000
FC 100
FY 15-30 1
FA15-100 115-100 215-100 3
KC 250
FY 15-30 1
FA15-100 115-100 215-100 3
KA 70-250 270-250 3
LC, LX 400
FY 15-30 1
FH15-100 115-100 215-100 3
KA 70-250 270-250 3
LA 125-400 2125-400 3
LC, LX 600
FY 15-30 1
KA 70-250 270-250 3
LA 125-400 2125-400 3
480 Vac 200,000
FI 100
FY 15-30 1
FA15-10015-10015-100
123
KI 250
FY 15-30 1
FA15-10015-10015-100
123
KA 70-25070-250
23
LI, LXI 400
FY 15-30 1
FH15-10015-10015-100
123
KA 70-25070-250
23
LA 125-400125-400
23
LI, LXI 600
FY 15-30 1
FC 20-10020-100
23
KC 110-250110-250
23
LA 125-400125-400
23
Series Ratings
For NQOD, NF and I-LINE
®
PanelboardsClass 1630, 1670, 2110
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
The fuse used in this UL test is an envelope (umbrella) fuse. This fuse is designed as a “worst case’’ fuse. Thus, no matter what manufacturer’s fuse is used, the Square D circuit breaker is protected.
k
The line side fused switch may be in a separate enclosure, or in the same enclosure as the loadside circuit breaker. A line side fused switch may be a submain, integral main, or remote main. A load side circuit breaker may be a branch, submain, or an integral main used on the load side of a remote main. This series combination short circuit current rating shall not exceed that of the line side fused switch. The charts apply to Square D Company load side circuit breakers only. However, the line side fuse ratings are independent of the fuse manufacturer.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
1. List circuit breakers required, either plug-on or bolt-on. See appropriate pages for catalog numbers.
2. Determine equivalent number of pole spaces required.
3. Select proper main lugs interior or main lugs interior and main breaker adapter kit based on equivalent number of poles and ampere rating from appropriate page. Interiors include solid neutral and are field convertible to top feed.
4. Select enclosure from appropriate page.
NEMA Type 1 — Select box and front catalog number corresponding to interior catalog number.
NEMA Types 3R, 5, 12 — Select enclosure and interior trim kit.
5. For complete price, add the component prices. Include panelboard accessories.
6. Apply appropriate discount schedule.
NQOD Merchandised Example:
208Y/120 Vac, 3Ø4W, 10 kAIR, 225 A, MLO, NEMA Type 1 surface mount, bolt-on branch breakers, main sub-feed lugs.
NF Merchandised Example:
480Y/277 Vac, 3Ø4W, 25 kAIR, fully rated, copper bus, 100 A, Main Breaker NEMA Type 1 flush mount, bolt-on branch breakers.
Factory Assembled Pricing Procedure
The following Factory Assembled pricing procedure may be used to price NQOD and NF panelboards.
1. Select BASE PRICE for main lugs or main breaker from BASE PRICE TABLE. Include equipment ground bar when required.
2. List BRANCH BREAKERS (either plug-on or bolt-on) and determine total spaces required. Select price from BRANCH BREAKERS TABLE. Include space only charge for future requirements.
3. If total spaces required exceeds the maximum listed, price as two or more panelboards and add price for sub-feed or feed-thru lugs, so installer can cable between sections.
4. Add price for special features from appropriate page. Contact field office for additional special features.
5. For complete price, add all prices. Order by description.
6. Apply appropriate discount schedule.
NQOD Factory Assembled Example:
208Y/120 Vac, 3Ø4W, 10 kAIR, 225 A, MLO, NEMA Type 1 surface mount, bolt-on branch breakers, main sub-feed lugs.
NF Factory Assembled Example:
480Y/277 Vac, 3Ø4W, 25 kAIR, fully rated, copper bus, 100 A, Main Breaker, NEMA Type 1 flush mount, bolt-on branch breakers.
Branches Page No. Catalog Number Spaces Price
(20) 20/1
8-11
(20) QOB120
20 $ 504.
(2) 40/2
8-11
(2) QOB240
4 112.
(2) 30/3
8-11
(2) QOB330
6 372.
Total 30
225A MLO Interior
8-8
NQOD430L225
$ 771.
Box
8-8
MH32
71.
Cover
8-8
MHC32S
315.
Main Sub-Feed Lugs
8-8
NQOD225SFL
129.
Total List Price $2274.
Branches Page No. Catalog Number Spaces Price
(13) 20/1
8-17
EGB14020
13 $2106.
(1) 40/2
8-17
EGB24040
2 410.
(1) 50/3
8-17
EGB34050
3 718.
Total 18
Main Breaker Kit
8-15
N3100FCMB
$1908.
100A MLO Cu Bus Int.
8-15
NF418L1C
1167.
Box
8-15
MH38
71.
Cover
8-15
NC38F
349.
Total List Price $6729.
Item Page No. Price
225A MLO Base Price
8-12 $464.
(20) 20/1 Bolt-on
8-12 680.
(2) 40/2 Bolt-on
8-12 134.
(2) 30/3 Bolt-on
8-12 352.
Main Sub-Feed Lugs
8-13 64.
Total List Price $1694.
Item Page No. Price
100A Main Breaker Base Price
8-18 $1208.
Copper bus adder
8-18 229.
(13) 20/1
8-18 2106.
(1) 40/2
8-18 373.
(1) 50/3
8-18 632.
Total List Price $4548.
NQOD and NF
Pricing Procedure/ExamplesClass 1630, 1670
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
In recent years, the volume usage of various types of office equipment, such as computers, copiers, printers, FAX machines and video display terminals has escalated dramatically. As the volume of such equipment grows to become a major portion of an office’s electrical load, the peculiar current demand characteristics of switching mode power supplies have created some unusual problems:
k
Circuit breakers trip or fuses blow at currents far below their rating.
k
Neutral cables and panelboard neutrals are found to be much hotter than their ratings, even with balanced loads.
The root cause for these problems lies with the non-linear nature of switching mode power supplies.
The Square D Solution
Square D has performed an extensive testing program to address this problem. The result of our efforts is a panelboard which is UL Listed for non-linear loads. This listing documents the ability of the neutral to carry current up to 200% of the phase bus current.
The following tables provide information for required neutral main conductor sizes and quantities on merchandised and factory assembled panelboards as well as catalog numbers for merchandised NQOD and NF panelboards with 200% rated neutrals. The full line of 100–400 A NQOD and 125–600 A NF factory assembled panelboards is available. See appropriate factory assembled panelboard page for pricing.
NQOD Main Neutral Conductors — Required Size and Quantity
a
Main neutral conductors must be copper or aluminum conductors of minimum size and quantity shown to maintain UL Listing. Requirement is based on heat rise testing.
NF Main Neutral Conductors — Required Size and Quantity
Panelboard Ampacity Neutral Conductors Required
a
Actual Lug Wire Range
100/125 (2) 1/0 Cu or Al (2) 1/0
225 (2) 4/0 Cu or (2) 300 kcmil Al (2) #4-300 kcmil
400
(4) 3/0 Cu or(4) 250 kcmil Al(2) 600 kcmil Cu(2) 750 kcmil Al
(2) 1/0-300 kcmil or(1) 750 kcmil
Panelboard Ampacity Neutral Conductors Required Actual Lug Wire Range
125 (2) 1/0 Cu or (2) 1/0 Al (2) #6-2/0
250 (2) 4/0 Cu or (2) 300 kcmil Al (2) #6-350 kcmil
400 (4) 250 kcmil Al or (4) 3/0 Cu or (2) 600 kcmil Al
(2) 1/0-300 kcmil or(1) 1/0-750 kcmil
600 (4) 500 kcmil Al or (4) 350 kcmil Cu (2) 1/0-750 kcmil
NQOD, NF and I-LINE
®
Panelboards
For Non-Linear Loads (200% Rated Neutral)Class 1630, 1670, 2110
200% Rated Neutral Application Data
I-LINE panelboards with 200% rated neutrals offer many advantages in neutral configurations. The terminal configuration table below lists the standard terminal quantities and sizes on 200% rated neutrals.
Custom neutral configurations offer added flexibility. This option allows matching neutral terminals to a specific circuit breaker layout when the standard neutral configuration is not adequate. These configurations are engineered per job; contact your nearest Square D/Schneider Electric sales office for assistance.
The following reference tables list conductor sizes required for branch circuit breakers. These conductor sizes take into account the derating required by the NEC when more than three current-carrying conductors are in a conduit or raceway.
See Article 310–Notes to Ampacity Tables of 0 to 2000 Volts
, note 10 (c). All conductor selections in the following tables are based on the 75°C ampacity table.
Another benefit of I-LINE with 200% rated neutrals is the ability to use sub-feed/feed-through lugs. These optional lug kits are available on
800 A maximum
HCM or HCWM I-LINE panelboards using copper conductors.
I-LINE 200 Neutral – Standard Terminal Configuration
t
Panel Type Ampacity TypeBranch Space
Neutral Terminals Quantity & Size NEMA Type 1 Enclosure
FA-100 A Not AvailableQ2-225 A Not AvailableKA-250 A Not AvailableLA-400 A Al 350 kcmil 2 4LC-600 A Not AvailableMA-800 A Al 350 kcmil 4 8
c Conductors derated per NEC Article 310—Notes to Ampacity Tables of 0 to 2000 Volts. See note 8(a).f All conductor selections are based on the 75°C ampacity table.a Derated ampacity is 228 A using 300 kcmil conductor. Use 250 A LA circuit breaker with 350 kcmil conductor for 250 A rated conductor.k Minimum conductor size for parallel conductors is 1/0 per the N.E.C.t NEMA Type 1 only.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
k “Cu’’ suffix indicates copper bus.q Neutral conductors must be of size and quantity per table on page 8-5.r Embossed mounting holes add a .25 inch standoff to back of MH box.a Add “F’’ for flush, “S’’ for surface.u NQOD 225A main circuit breaker panelboards must use K-frame main circuit breaker. Q2 circuit breakers are not acceptable.c Enclosure includes trim kit.
q Neutral conductors must be of size and quantity per table on page 8-5.r Embossed mounting holes add a .25 inch standoff to back of MH box.k “C” suffix indicates copper bussing.a Add “F” for flush or “S” for surface.c Enclosure includes trim kit.
Max. No. of
One Pole QO
QOB Breakers
Mains Rating
Total PriceInterior
Front and Enclosure
Main Lugs q Interior Only
(Order Branch Circuit Breakers Separately)
NEMA Type 1 Enclosure NEMA Type 3R, 5, 12 Enclosure c
Box 20"W x 5 3⁄4"Dr MONO-FLAT® Front a Enclosure20"W x 6 1⁄2"D Height
(In.)NEMA Type 1
NEMA Type 3R, 5,12 Catalog No. k Price Catalog No. Price Catalog No. Price Catalog No. Price
MONO-FLAT is a Registered Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
MONO-FLAT is a Registered Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
NQODMain Lug Interiors — Accepts Plug-On and Bolt-On Breakers
k “Cu’’ suffix indicates copper bussing.r Embossed mounting holes add a .25 inch standoff to back of MH box.a Add “F’’ for flush, “S’’ for surface.p Refer to 42 circuit rule — NEC Article 384-14 and 384-15.c Copper bus standard on 600 A interiors.h Feed-thru lug interior.t Enclosure includes trim kit.
MONO-FLAT is a Registered Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
NQODMain Circuit Breaker Interiors — Accepts Plug-On and Bolt-On Breakers
k “Cu’’ suffix indicates copper bussing.r Embossed mounting holes add a .25 inch standoff to back of MH box.a Add “F’’ for flush, “S’’ for surface.p Refer to 42 circuit rule — NEC Article 384-14 and 384-15.h Feed-thru lug interior.c Enclosure includes trim kit.t Do not use for POWERLINK AS applications, order the following front:
Main Circuit Breaker Adapter Kits a (Includes Circuit Breaker)
Max.No. of
One-Pole QO QOB Brkers
MainsRating
Total PriceInterior, Front, Box
and Adapter Kit
Main BreakerAdapter Kit
Interior Only(Order Branch
Circuit Breakers Separately)
NEMA Type 1 Enclosure NEMA Type 3R, 5, 12 Enclosure c
MONO-FLAT is a Registered Trademark of Square D Company or related companies.POWERLINK is a Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
QO-HM High magnetic trip circuit breakers are recommended for applications where high initial inrush may occur and for individual dim mer applications.
QO-HID HID circuit breakers are UL Listed for use on circuit feeding fluorescent and High Intensity Discharge (HID) lighting systems su ch as mercury vapor, metal halide, or high pressure sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
120/240 Vac — 10,000 AIR 120/240 Vac — 10,000 AIR 240 Vac — 10,000 AIR
Key Operated QOKey operated QO and QOB circuit breakers are available in single pole construction and can be mounted in any single pole space which will accept a standard QO. These circuit breakers can be turned ON or OFF or to RESET with a special key (Catalog No. QOK10) included with the circuit breaker. These circuit breakers are UL Listed and available as shown in the table below.
Note: For Bolt-On order QOB1_ _K.List price for all key operated QOB breakers is $107.00.
120 Vac — 10,000 AIR
Amp Rating Catalog No. Price
10 QO110K $104.00
15 QO115K 104.00
20 QO120K 104.00
25 QO125K 104.00
30 QO130K 104.00
QOK
QO, QWIK-GARD and VISI-TRIP are Registered Trademarks of Square D Company or related companies.
f UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment having motor group combinations and marked for use with HACR type circuit breakers.
q UL Listed as SWD (switching duty) rated suitable for switching 120 Vac fluorescent lighting loads.
p QO110 through QO130-2 wires #14-10 copper.
c Do not connect to more than 250 feet of load conductor for the total one-way run to prevent nuisance tripping.
a Suitable only for feeding 240 Vac and 208 Vac two wire loads. Does not contain load neutral connection.
u UL Listed 5,000 AIR on 3Ø corner grounded delta systems.
l DC Rating is not available on indicated products.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
QOB-HIDHID circuit breakers are UL Listed for use on circuit feeding fluorescent and High Intensity Discharge (HID) lighting systems su ch as mercury vapor, metal halide, or high pressure sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
u UL Listed 5,000 AIR on 3Ø corner grounded delta systems.f UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment having
motor group combinations and marked for use with HACR type circuit breakers. q UL Listed as SWD (switching duty) rated suitable for switching 120 Vac fluorescent lighting loads.p QOB110 through QOB130-2 wires #14-10 copper.j 100A max breaker mounted opposite.k QOB2150VH uses 4 pole spaces. QOB3110VH, QOB3125VH and QOB3150VH each use 6 pole
spaces. 20 A max breaker mounted opposite. Wire size is #4-300 kcmil Al/Cu. Use with 75°C wire only.
c Do not connect to more than 250 feet of load conductor for the total one-way run to prevent nuisance tripping.
a Suitable only for feeding 240 Vac and 208Vac two wire loads. Does not contain load neutral connection.
l DC Rating is not available on indicated products.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Equipment Ground Bar — $19.00c Copper bus standard
Table 2 — Branch Breakers
Shunt Trip, Auxiliary Switch, and Alarm Switch — accessories for circuit breakers — add price from page 6-37 and 6-38.f UL Listed for use on 3Ø, grounded BØ systems, (5,000 AIR for this application).q Bolt-On only, 2-pole requires 4 vertical spaces, 3 pole requires 6 vertical spaces.k Plug-On only.
MainsRating
Main Lugs Main Breaker (Circuit Breaker Interrupting Rating - pages 6-2 through 6-9)
2-Pole 3-PoleStandard IC HIC Extra HIC I-LIMITER ®
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Common Special Features(For additional special features, see page 8-42 and 8-43)
k COPPER BUS BARSCopper bus is standard on 600 A interiors.For Copper bus 100, 225, 250 A ................................................................................... $ 64.
400 A ..................................................................................................... 194.
k WEATHERPROOF or DUSTTIGHT Cabinets — NEMA Type 3R, 5, 12 ........... $758.Note : 400 and 600 Ampere NQOD panelboards with sub-feed breakers and
600 A main breaker panelboards are not available in a weatherproof enclosure. (Use I-LINE®).
k NAMEPLATESStandard white face/black letter laminated bakelite, 1" x 3.5", adhesive backed or screw mountable with screws in a bag assembly. (Price includes engraving).............................. $39.
k 200% RATED NEUTRALSPanelboards with 200% rated neutrals are not available with Q2 main circuit breaker, 250 A K-frame main circuit breakers or integral lighting contactors.
Add Per Panel 100 A ................................................................................................. $293.225 A ................................................................................................... 381.400 A ................................................................................................... 475.
k METAL DIRECTORY FRAME OPTIONSFrame attached to trim with adhesive .............................................................................. $ 60.Frame welded to trim (available on hinged trim only)For hinged trim front add .................................................................................................... 323.
k SUB-FEED CIRCUIT BREAKERMain lugs or main breaker interior — 1Ø or 3Ø.Maximum 1 breaker per 225 A main lug or 250 A main breaker panelboard, 2 breakers per 400-600 A panelboard.
a Not available in NEMA Type 3R, 5, 12.q 63⁄4" Deep Box, surface only.
k SUB-FEED LUGSAn additional mains end termination point that can be used to feed out to another panelboard or device from the incoming service lines. AVAILABLE ON MAIN LUGS INTERIORS ONLY. 1Ø or 3Ø.
k FEED-THRU LUGSA second set of lugs assembled at the opposite end from the mains of the panelboard. Often used to connect another panelboard or device to the incoming lines. Available on main lugs interiors 1Ø or 3Ø, 225-600 A Available on main breaker interiors 1Ø or 3Ø 250-600 A. Not available on panelboard with sub-feed breakers.
q 63⁄4" Deep Box, surface only
Sub-Feed Breaker (110-225 A)
No. of Poles Ampacity Q2 Q2-H KA KD KG KH
2 110-225 A $609. $ 881. $1228. $1228. $1906. $2319.3 110-225 A 924. 1148. 1436. 1436. 2304. 2717.
Space Only 110-225 A 413. 413. 413. 413. 413. 413.
3Ø, 30 Circuit, 400 A Main Lugs InteriorWith Sub-Feed Lugs
(one 2 barrel lug per Ø and N)
3Ø, 42 Circuit, 400 A Main Lugs InteriorWith Feed-Thru Lugs
Feed-ThruLugs
Sub-FeedBreakers
NQOD Factory Assembled PanelboardsCommon Special Features
Class 1630
3Ø, 30 Circuit, 600 A Main Lugs
InteriorWith 2-Q2L Sub-Feed
Circuit Breakers
I-LINE is a Registered Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
k “C” suffix indicates copper bussing.r Embossed mounting holes add a .25 inch standoff to back of MH box.a Add “F” for flush, “S” for surface.p Refer to 42 circuit rule – NEC Article 384-14 and 384-15.c Enclosure includes trim kit.
NF Main Lug Interiors — Use I-LINE® Panelboards on 480 V 3Ø3W DELTA applications
MaxNo. of One-
Pole EDB
Breakers
MainsRating
Total PriceInterior, Frontand Enclosure
Interior Only (Order Branch Circuit Breakers Separately)
NEMA Type 1 Enclosure NEMA Type 3R, 5, 12 Enclosure c
MONO-FLAT is a Registered Trademark of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
k “C” suffix indicates copper bussing.r Embossed mounting holes add a .25 inch standoff to the back of MH box.a Add F” for flush, “S” for surface.p Refer to 42 circuit rule – NEC Article 384-14 and 384-15.q Available factory assembled only.c Refer to pages 6-2 through 6-9 for circuit breaker ampere interrupting ratings.t Enclosure includes trim kit.
I-LINE and MONO-FLAT are Registered Trademarks of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
s Available factory assembled only on non-linear panelboards.c Order appropriate KCL circuit breaker. b Suitable for top or bottom feed applications.k Use copper wire only.q Available factory assembled only.
q Available factory assembled only.
q Boxes over 80" are order only.c 400 A dimension for LA/LH main circuit breakers only.
q Not for use on sub-feed lug and feed-thru lug applications, price as factory assembled.c Use of this kit to terminate larger than standard wire size requires an additional 6" added to box height.k Use of this kit requires an additional 6" added to box height.
PK18GTA with #1 to 4/0 Al/Cu lug PK18GTA-L 24.00 DE3A Handle lockoff/padlock attachment HPAFD 16.20 PE1A
PK23GTA with #1 to 4/0 Al/Cu lug PK23GTA-L 25.80 DE3A Nut - interior mounting (4 per Package) NFNIM 2.90 PE1A
Ground bar insulator kit PKGTAB 27.80 DE3A Leveling nut (flush mount only - 4 per pkg) NFLN 7.10 PE1A
Circuit I.D. number strips: Trim Mounting Screws/Hardware:
1 through 96 80043-379-03 2.40 PE1A 250 A max interiors (10 per package) NFTMS1 3.60 PE1A
600 A max interiors (8 per package) LP9502 3.60 PE1A
Note: N250SFB-KC and N600SFB-KC are for use with KAL, KHL, and KCL circuit breakers.
MainsAmpacity
Sub-Feed Circuit Breaker Kits bs (Breaker not Included) c
Single Sub-feed Breaker Twin Sub-feed Breakers
Catalog No. Price Catalog No. Price
250 N250SFB-KC $653. … …
400 … … N600SFB-KC 819.
600 … … N600SFB-KC 819.
NF Merchandised PanelboardsAccessoriesClass 1670
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
All EDB, EGB, and EJB circuit breakers are UL Listed as HACR Type.q UL Listed as SWD (Switching duty rated).c UL Listed as HID (High Intensity Discharge rated).k UL Listed for use on 240 V Corner-grounded Delta Systems (Grounded B Phase).
j Accessory package takes an additional pole space.
ContinuousCurrent Rating
@ 40°C
“D” Interrupting Level18 kA @ 480Y/277 Vac
“G” Interrupting Level35 kA @ 480Y/277 Vac
“J” Interrupting Level65 kA @ 480Y/277 Vac
TerminalWire
RangeCatalog Number Price Catalog Number Price Catalog Number Price
1-Pole, 277 Vac
15 EDB14015qc $ 95. EGB14015qc $ 162. EJB14015qc $ 259. AL30FD#14-#6Al or Cu
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
k Copper Bus BarsCopper bus is standard on 600 A interiors.For Copper bus 100, 250 A....add $229.
400 A..........add $312.
k Metal Directory Frame Options (Not available with LC/LI main circuit breakers)Frame attached to trim with adhesive................................. $ 60.Frame welded to trim (available on hinged trim only)For hinged trim front add............... $323.
k NameplatesStandard whiteface/black letter laminated Bakelite 1” x 3.5” adhesive backed or screw mountable with screws in a bag assembly.(Price includes engraving) ............ $ 39.
k 200% Rated NeutralsPanelboards with 200% rated neutrals are available with sub-feed lugs, feed-thru lugs, and main circuit breakers.Add Per Panel 250 A ............... $381.
400 A ................ 475.600 A ................ 631.
k Weatherproof or Dust-Tight Cabinets–NEMA Type 3R, 5, 12.............. $758.
k Sub-Feed Circuit BreakerAvailable with 600 A maximum main lugs or main breaker interiorsMaximum (1) 110–250 A breaker per 250 A main lugs or main breaker panelboard or,Maximum (2) 110–250 A breakers per 400/600 A main lugs or main breaker panelboard.
c Dimensions also for 400 A LC/LI main circuit breaker panels.r 600 Ampere main breaker panelboards require an 8" deep, 26" wide.f 600 A main lug panelboards require a 26" wide box.
k Feed-Thru LugsA second set of lugs assembled at the opposite end from the mains of the panelboard. Often used to connect another panelboard or device to the incoming lines. Available on main lugs and main breaker panelboards.
125 A (1) #6-250 kcmil Al/Cu $172.250 A (1) #6-350 kcmil Al/Cu 172.
400 A (1) 1/0-750 kcmil or (2) 1/0-350 kcmil Al/Cu
413.
600 A (2) 1/0-600 kcmil Al/Cu 413.
k Sub-Feed (Double) LugsAn additional mains end termination point that can be used to feed out to another panelboard or device from the incoming service lines. AVAILABLE ON MAIN LUGS INTERIORS ONLY .
I-LIMITER and I-LINE are Registered Trademarks of Square D Company or related companies.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
I-LINE Merchandised Pricing Procedure1. Select the appropriate branch circuit breakers and accessories based
on the required ampacity and AIR ratings from pages 8-24 through 8-34.
2. Determine the total mounting inches required by the branch breakers. Pay close attention to the interior types and any branch mounting restrictions by referring to panel layouts on pages 8-22 and 8-23. i.e. Larger frame breakers may mount in only one side of the panel due to physical sizes. Therefore, for larger size branches, you may only be able to consider one half of the total mounting inches available.
3. Select proper main lugs interior or main breaker interior from page 8-22 or 8-23 based on the mains ampacity and branch requirements from step 2.
4. Select blanks from the Accessories table on page 8-21 as required to cover unused mounting space.
5. Select appropriate box and front from page 8-22 or 8-23 to accommodate panel interior selected in step 3.
6. Apply appropriate discount schedule.
I-LINE Factory Assembled Pricing Procedure1. Select price for main lugs or main breaker from Base Price tables on
page 8-35. Include solid neutral and ground bar when required.
2. List branch breakers and determine total mounting inches required. Include space only charge and mounting inches as required. Price branches from pages 8-36 and 8-37.
3. If total space required exceeds the maximum listed, price as two or more panels and add price for sub-feed lugs, so installer can cable between sections.
4. Add price for special features from page 8-37 and 8-42 through 8-43.
5. For complete price, total all prices. Order panel by description.
6. Apply appropriate discount schedule.
QMB Merchandised Pricing Procedure1. Select branch switch catalog numbers from tables on page 8-39
noting switch mounting heights.
2. Select interior, box and front catalog numbers from the appropriate table on page 8-38 based on total branch mounting space required and mains ampere rating.
3. Select blank fillers, neutral assemblies, and fuse rejection clips when required, from the tables on pages 8-38 and 8-39.
Note: Two pole branch switches are shipped with outside (AC) phase connectors. Center (B) phase connector furnished with switches for easy field conversion to AB or BC phasing.
QMB Factory AssembledQMB Panelboards and/or Motor Starter Panelboards — Method of Pricing
1. Make a sketch with main lugs or main switch at the top or bottom.
2. List required branch devices (switches, circuit breaker units, and/or motor starter units). Include ampere rating, number of poles and unit mounting height from the appropriate table on pages 8-40 and 8-41.
30-60 twin units are the same price as 600 V 60-60 twin units.
30-100 and 60-100 twin units are the same price as 600 V 100-100 twin units.
3. List solid neutral from page 8-40 if required. No unit mounting height is required.
4. List mains ampere rating, voltage, number of poles and unit mounting space from the appropriate table on page 8-40.
5. If total unit mounting height of branch devices exceeds maximum mounting space of the mains, price as two or more panelboards, adding sub-feed lugs or feed-thru lugs from the appropriate table on page 8-40.
6. Insert at the right of each item the price from the appropriate table, including any accessories. The sum will be the complete panelboard price including the cabinet.
7. Specify H, R or J fuse clips.
I-LINE Merchandised Pricing Example
Example: 600 Vac, 3Ø3W, 400 A, MLO, 14k AIR, NEMA Type 1 enclosure, 4 piece surface trim without door.
Description Catalog No. DigestPage No. Price
400 Amp MLO Interior HCM3273-4 8-22 $1529.00
4 Piece Surface Trim Without Door HCM73TS 8-22 444.00
NEMA Type 1 Enclosure HC3273B 8-22 154.00
(8) 60/3 FA36060 8-30 4928.00
(1) 100/2 FA26100AC 8-30 601.00
(3) 250/3 KA36250 8-31 8688.00
(1) 41⁄2" Blanks HNM4BL 8-21 80.00
(1) 11⁄2" Blank HNM1BL 8-21 27.90
Total List Price: $16451.90
I-LINE Factory Assembled Pricing Example
Example: 600 Vac, 3Ø3W, 400 A, MLO, 14k AIR, NEMA Type 1 enclosure, 4 piece surface trim without door.
Description Digest Page No. Price
400 A MLO Base Price 8-35 $ 652.(8) 60/3 8-36 4024.
(1) 100/2 8-36 482.(3) 250/3 8-36 7026.
Total List Price: $12184.
QMB Merchandised Pricing Example
Example: 600 Vac, 3Ø3W, 400 A, Fusible 10k AIR, NEMA Type 1 Enclosure
Branches Digest Page No. Catalog Number Mounting In. Price
Example: 600 Vac, 3Ø3W, 400 A, Fusible 10k AIR,NEMA Type 1 Enclosure
Branches Digest Page No. Price
400 A MLO Base Price 8-40 $ 672.(4) 60/3 8-40 1446.(1) 100/3 8-40 1137.(1) 30/3 – . . .
Total $3255.
QMB and I-LINE® PanelboardsPricing Procedure/ExamplesClass 2110, 4620
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
Interiors, Boxes and Fronts(100 A and 225 A interiors include solid neutral, all others without solid neutral. Order solid neutral from page 8-21)
a Add “F’’ for Flush or “S’’ for Surface.j Add-on door kit available from Peru. Example: For HCM48TS surface trim kit, order HCM48DS door kit.f For NEMA Type 1 applications, order interior, front, and box. For NEMA Type 3R/5/12 applications, order interior and box only. The front is included with the
box.k Remove drain screws for NEMA Type 3R rating.q Bottom feed standard, for top feed main circuit breaker specify at time of order.
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com
FAc, FH, FC, FY, FI, Q2, Q2-H, Q2H, KA c, KH,KC, KI, Q4, LA, LH, LC, LI, LX, LXI and LE
Box Size: 42" Wide, 9 1⁄2" Deep
TYPE HCWM (Main Lugs Only)800 A Max. Branch Breaker
FAc, FH, FC, FY, FI, Q2, Q2-H, Q2H, KA c, KH,KC, KI, Q4, LA, LH, LC, LI, LX, LXI, LE, MA,
MX, ME and MH
Box Size: 42" Wide, 9 1⁄2" Deep
TYPE HCWM-U Universal Mains1200 A Max. Branch Breaker
FAc, FC, FH, FY, FI, Q2, Q2-H, Q2H, KA c, KH,KC, KI, Q4, LA, LH, LC, LI, LX, LXI, LE, MA,
MX, MEq, MH, NA, NC and NX j
Enclosure Size: 42" Wide, 9 1⁄2" Deep
q ME circuit breakers are available 100% rated.
c FA and KA circuit breakers with field install-able ground fault kits may be mounted in type HCW, HCWM and HCWM-U panelboards as shown, and require L-frame mounting space.
(1200 A Interiors Include solid neutral, all others without solid neutral. Order solid neutral from page 8-21.)
HCWM-U Universal Main Lugs or Main Breaker — 3-Pole.Suitable for use as service equipment when provided with a main breaker. For service equipment main lugs application use HCWM panel.For MAIN LUGS panel, order sub-feed lug kit catalog number SL1200 and back feed as main lugs.For MAIN BREAKER panel, order plug-on I-LINE type NA and NC from page 8-32, or NXj circuit breakers from Page 8-34, and back feed as themain breaker. (Order Solid Neutral Separately)
a Add “F’’ for Flush or “S’’ for Surface.c Add-on door kit available from Peru. Example: For HCM50TS trim kit, order HCM50D door kit.h See page 8-21 for 42" wide weatherproof enclosures. (Not available for use with Type HCWM-U panelboards).k 15" of mounting space is taken up by the back fed main lug kit or NA, NC, NX main circuit breaker, leaving 93" of branch circuit breaker mounting
space.j When NX main circuit breakers with equipment ground fault are applied on a 3Ø4W system, order solid neutral catalog number HCWM12SNCT.
The HCWM12SNCT includes a neutral current transformer.
Circuit Breaker/Sub-Feed Lug Kit Mounting Inch Requirement
Standard Copper Bus Interiors u
u For lower rated merchandised copper interior, select interior shown in the table above and apply at required ampacity.
TotalBreaker
Mtg. Space
(Inches)
MainsAmp.Rat-ing
Max.No. of
LC, MA, NA
Breakers
Complete Surface Price(4 Piece Trim)(Less Branch
Breakers)
Interior Assembly(Less Branch Breakers)
Front
Box h BoxHeight
(In.)
4 Piece Trim Without Door ac Trim With Door
Type 1 Catalog Number Price Catalog Number Price Catalog
Number Price CatalogNumber Price
HCW Main Lugs Only — 3-Pole — Suitable for use as service equipment when provided with a main breaker.
I-LINE is a Registered Trademark of Square D Company or related companies.
I-LINE® Merchandised Panelboards600 Vac, 250 Vdc
Class 2110
Main Breaker Interiors – Standard Frame TypesMain Circuit Breaker
AmpacityPanelboard
TypeFactory Supplied
Main Breaker
100 HCN FA36100
225 HCN, HCM KA36225
400 HCN LAP36400MB
400 HCM LA36400
600or
800HCM, HCW
MAP36600or
MAP36800
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com