No 1 in Global Refrigeration. Dedicated solutions deliver higher energy efficiency, optimum system performance and enhanced reliability VLT® Refrigeration Drive FC 103 improves efficiency of compressors, condensers, evaporators and pumps Selection Guide | 1.1 kW – 630 kW drives.danfoss.com
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
No 1 in Global Refrigeration.Dedicated solutions deliver higher energy effi ciency, optimum system performance and enhanced reliability
VLT® Refrigeration Drive FC 103 improves efficiency of compressors, condensers, evaporators and pumps
VLT® Refrigeration Drive FC 103 reduces lifecycle costs
For over 60 years the Danfoss Refrigeration team has specialised in the development of innovative and eff ective refrigeration technology solutions. Danfoss has now developed the ideal drive for refrigeration system compressors, condensers, evaporators, fans and pumps – the VLT® Refrigeration Drive FC 103.
To help signifi cantly reduce lifecycle costs of your refrigeration systems, the VLT® Refrigeration Drive FC 103 off ers effi ciency and reliability enhancing features, integrated process control functions and commissioning environment specifi cally designed to meet the needs of refrigeration compressor, condenser, evaporator, fan and pump applications.
All-inclusive• Top effi ciency (98%)• Automatic Energy Optimisation (AEO)• DC link chokes• Refrigerant tables• Large performance range• Open for all kind of controllers including Danfoss ADAP-KOOL®
Integrated functions save money• Multi-zone cascade controller• Neutral zone controller• Floating condensing temperature control• Oil return management• Multi-feedback evaporator control• Safe stop• Sleep mode• Dry-running protection• Overload protection• Flow compensation
Easy installation• Quick Menu • Easy & swift commissioning via built-in wizard. • Speaks “refrigeration language”• Small enclosure size• IP20–IP66 enclosure rating
3Danfoss Drives · DKDD.PB.103.A6.02
Reducing the operating costs of
refrigeration systems with quick
payback is becoming increasingly
important. Speed control of the electric
drives used in these systems is a
pragmatic and eff ective approach.
Load-dependent speed control
reduces power consumption and
therefore saves money.
When you consider that energy costs
amount to 90% or more of total
operating costs over the total product
lifetime, it’s easy to see that there is
plenty of potential for savings in this
area. Speed control also lowers
mechanical stress in the system, which
reduces service and maintenance costs.
VLT® Refrigeration Drive FC 103 – simply uncomplicatedDanfoss developed the VLT®
Refrigeration Drive FC 103 to allow all
users in the refrigeration world to
benefi t from the advantages of speed
control in a simple, uncomplicated
manner.
Faster system payback with speed control
Starting with the fi rst VLT® Drive – the VLT® 5 from 1968
– every drive series from Danfoss has proven the reliability of VLT® drives.
Proven reliability
Accumulator Compressor
Expansion valve
Spiral drumHeat exchanger
Solenoid valve
Horizon circuited air cooled condenser
Sightglass
Ball valve
Filter drier
Glycol tank
Glycol supply
Circulation pump
Process pumpCondenser
circuit
Finned receivercircuit
Subcoolingcircuit
Heat reclaim coil Heated water out
Well water in
VLT® Refrigeration Drive FC 103 provides speed control of allmotor driven components and interacts with the major components
Refrigeration system without speed controlIn a refrigeration system without speed
control, the compressor always runs at
full speed, regardless of the cooling
capacity actually required. The cooling
output is regulated by the evaporator,
which is fi lled by the expansion device.
Since the expansion valve constantly
tries to fi ll the evaporator optimally, this
adjustment causes the evaporation
pressure to change and therefore
creates oscillation in the system.
With the compressor operating at full
output capacity, this oscillation can
persist for a very long time. As a result,
the evaporator is never properly fi lled
and operates ineff ectively, and the
cooling capacity of the refrigerant is
not optimal.
Refrigeration system with speed controlThe continuous variable speed control
by VLT® Refrigeration Drive FC 103
makes intelligent capacity control
possible. By creating stability while
balancing the capacity to the actual
load, system-wide COP improves
providing signifi cant energy savings.
Intelligent compressor and condenser
fan control is a “must” in any optimised
refrigeration system.
The following positive eff ects can be
achieved in a refrigeration system with
variable-speed compressor operation:
Compressor• 6 compressors pack controller
• Stable suction pressure
• Increased capacity using a smaller
compressor
• Built-in soft starter function
• Built-in oil return management
improves reliability and lifetime
• Low and high pressure monitoring
• Reduced mechanical load
• Fewer start and stops extends the
lifetime
• No mechanical capacity control
• Improves system COP
Condenser fan control• Load dependent capacity control
• Operate single fans/multiple
parallel operating fans
• Stable condensing pressure
• Floating condensing temperature
adapts to outdoor temperature
• Reduced charge of refrigerant
• Less dirt build-up on condenser
• Stand-alone control using VLT®
Refrigeration Drive FC 103
• Improves system COP
6 Danfoss Drives · DKDD.PB.103.A6.02
The fi gure on the left shows the condensation temperature curve (red) and the evaporation temperature curve (blue). The eff ect of on/off operational behaviour compared to a stable temperature (straight line) is clearly visible.
The right-hand fi gure shows a log (p) h diagram. The standard condensation or evaporation processes are shown as dark red and dark blue lines.
Time h
T(ºC) Log(p)
COP = 1.87835
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
-30
Condensing
Surroundings
Cold room
Evaporation
R290
COP = 2.441
τ/2
τ
Pumps in process cooling or air-conditioning systems• Coolant pump capacity according
to demand
• Stable coolant fl ow and pressure
• Stand-alone control using
VLT® Refrigeration Drive FC 103
• Operate from direct signal
(0/4-20 mA or 0-10 V DC)
Fans in process cooling or air-conditioning systems• Optimized operation of air
handling units
• High effi ciency
• Airfl ow according to demand
• Stand-alone control using VLT®
Refrigeration Drive FC 103
• Operate from direct signal
(0/4-20 mA or 0-10 V DC)
Depending on the application, speed
control can result in energy savings
ranging from 10% to as much as 70%.
7Danfoss Drives · DKDD.PB.103.A6.02
Multi-zone pack controller– Improved energy savings and stable operation
There is a speed range in the inter-
action between the compressor and
frequency converter that allows the
system to save energy. The compressor
should function within this range most
of the time. If the diff erence between
the maximum required performance
and the average performance under
partial load is too great, it is a good
idea to use a cascade confi guration.
In many cases the required capital in-
vestment, including the conversion of
an existing system, will be amortised
quickly.
Cascading the systemIn a system with cascaded compres-
sors, the base load is handled by a
speed-controlled compressor. If the
demand rises, the drive starts up
additional compressors one at a time.
As a result, the compressors work large-
ly at their optimum effi ciency point, wi-
th the control constantly ensuring that
the system is operating at maximum
energy effi ciency. Step-less capacity
control thus achieved eliminates the
need for large number of small size
compressors. This cascading principle
can also be applied to fans and pumps
using the VLT® Refrigeration Drive FC
103.
Advanced Multi-zone pack controller• Eff ectively cascades and controls up
to 6 compressors pack
• Focused towards piston, screw and
scroll compressors
• Three zone setups avoid too
frequent staging and de-staging
• Makes pressures & temperatures
stable.
• Reduces compressor wear & tear
• Can also control groups of
condenser fans
Easy commissioningThe VLT® Refrigeration FC 103 drive of-
fers a setup wizard, using common re-
frigeration terms rather than computer
language. Field testing shows that ease
of programming makes installers and
service technicians more comfortable
and confi dent, making their jobs easier
and quicker.
The wizard menu also supports the
commissioning engineers if they en-
counter any problems. The menu will
help the engineer troubleshoot and of-
fer ‘quick fi xes’ to get the drive up and
running if there is a problem.
Read the compressor status directly from the display. D = Variable speed control, O = Off , R = Mains operation, X = Deactivated
8 Danfoss Drives · DKDD.PB.103.A6.028
Implement speed control of the lead compressor plus one additional compressor, to improve and streamline design alternatives. The broader choice of compressor sizing enables adaptation to varying load conditions
60 Hz50 Hz
25 Hz50 Hz
25 Hz
10%
1
1
3
3
3
3
4
4
4
2
2
2
2
2
5
51
1
1
1
1
Commissioning is fast and easy using
the the frequency converter display
panel. The wizard that appears the fi rst
time the device is switched on guides
the user through the necessary set-
tings.
The user only has to switch from exter-
nal to internal control. If necessary, the
wizard can be called up again from the
Quick Menu. Confi guring the necessa-
ry parameters is even easier with the
wizard in theVLT® Motion Control Tool
MCT 10 software.
During operations, the FC 103 can
show the compressor status on the fre-
quency converter display panel and log
the compressor’s operating time and
number of starts.
Reduced service costsMechanical wear is automatically re-
duced by the fact that only as many
compressors are running as are actually
needed. This allows service intervals to
be extended. The user can confi gure
rotation of mains-powered compres-
sors to ensure that they all end up with
a similar number of operating hours.
9Danfoss Drives · DKDD.PB.103.A6.02
10 Danfoss Drives · DKDD.PB.103.A6.0210
Dedicated compressor features
Condensing temperaturemonitoring The frequency converter can monitor
the Floating Head Pressure high
pressure levels using connected
temperature sensors. Speed is reduced
before the head pressure reaches a
critical value. This allows safe operation
of system for longer duration thus
enhancing food safety and process
control.
Single compressor or packThe user has the choice of operating
the system with a single large
compressor or using the pack
controller to operate the system with
several smaller compressors which are
activated as the demand for cooling
capacity increases. The built in Pack
Controller can distribute running hours
evenly across all compressors, keeping
wear and tear on individual compres-
sors to a minimum and ensures that all
compressors are in great shape.
Direct entry of evaporatortemperatureThe user can enter the desired evapo-
rator temperature directly in the
control panel of the FC 103. The
frequency converter also takes the
properties of the refrigerant into
account. Tables for the most commonly
used refrigerants are preloaded in the
frequency converter. User-defi ned
entry of the refrigerant used in the
system is also possible. Simplifi es
commissioning.
Inject ONWhen all connected compressors on
the FC 103 are stopped due to a
missing safety circuit, this will be
registered by the system unit which
will close all valves connected to the
case controllers. This supports preven-
tion of liquid fl ow to the compressor
when FC 103 starts the compressor
again. As soon as a compressor starts
running again, the valves will reopen.
Fewer starts and stopsStart-up is the critical phase of
compressor operation. The FC 103
minimises the number of required
starts and stops by varying the speed
of the compressor to match the
capacity to the cooling demand. This
ensures maximum run time and
minimum number of starts and stops.
In addition, the maximum number of
start/stop cycles in a given period can
be confi gured using the control panel.
Unloaded startTo further extend the lifetime of the FC
103 a pressure relief valve can be
opened to allow the compressor to
start up quickly with no load.
135% Starting torqueThe FC 103 delivers 135% of the rated
starting torque for a period of half a
second. In normal operation, 110% of
the rated torque is available for 60
seconds.
Smaller compressors with the same peak loadThe operator can confi gure the system
with a smaller compressor for a given
peak load. This provided that the
compressor is designed for over-speed
operation, the FC 103 can run it at up
to 90 Hz. This may allow brief peak
loads to be handled in this way without
necessarily requiring a larger
compressor for this purpose.
P0 optimisation The FC 103 supports connection of an
ADAP-KOOL® LonWorks control for P0
optimisation.
The VLT® Refrigeration Drive FC 103
is designed for operating piston,
scroll, screw compressors and
centrifugal compressors. Variable
speed control allows the refrigera-
tion capacity of a compressor to be
adapted to exactly match the
demand.
Day/night controlCompressors usually operate with
diff erent setpoints depending on the
time of day. This in turn results in
diff erent evaporator fan speeds,
resulting in reduced energy consump-
tion. This function can be easily
programmed with day/night control.
Neutral ZoneThe FC 103 continues to control fi xed
speed compressors in situations where
the variable speed compressor fails.
Neutral zone is in a fail situation set by
a special parameter ”Fixed speed
neutral zone”. This gives the opportu-
nity to have fewer starts by expanding
the neutral zone and longer duration
of safe operation even under chal-
lenging situations.
Oil Return ManagementIf compressors run at low speed for
longer periods of time, lubrication oil
will end up in the refrigerant and
pipelines. Lack of oil in crankcase
causes insuffi cient lubrication. Built-in
oil return management in the FC 103
ensures oil is returned to crankcase
thus signifi cantly improving system
reliability. Oil management function-
ality increases the compressor speed
up to its maximum value for the user
defi ned interval of time and brings the
oil back to the compressor.
• Oil boost functionality activates at
fi xed time intervals
• Or when the compressor speed
has been lower than nominal
speed for too long time
• Improves lubrication and system
reliability
11Danfoss Drives · DKDD.PB.103.A6.02
Resonance monitoringBy pressing a few buttons on the Local
Control Panel, the drive can be set to
avoid frequency bands, at which
connected fans create resonances in
the in condensers or evaporators.
This reduces vibration noise and wear
and tear on equipment.
Auto tuning of the PI controllersWith auto tuning of the PI controllers,
the drive monitors how the system
reacts on corrections made by the drive
– and learns from it.
User-friendly, distributed intelli-
gence and reduced power con-
sumption are bene fi cial for con-
denser and evaporator applications.
Floating condensing temperature optimises COPVLT® Refrigeration Drive FC 103
intelligently controls evaporative
condensers or air-cooled condensers to
optimise refrigeration system perfor-
mance (COP) at lower energy consump-
tion. The drive adapts condensing
temperature set point as the outdoor
temperature drops, lowering the set
point to a new stable level. This
functionality provides:
• Increased cooling capacity at lower
power consumption
• Ability to run on fewer compressors,
hence reducing wear and tear
Intelligent functionsThe FC 103 handles logical rules and
inputs from sensors, real time function-
ality and time-related actions. This
enables the FC 103 to control a wide
range of functions, including:
• Weekend and working-day
operations
• Cascaded P-PI for temperature
control
• Belt monitoring
Dedicated condenser and evaporator features
4 x PID controller
(Individual set-points/feed-backs)
• PID for closed loop control of the motor connected to the drive
• 3 PIDs for external closed loop control of refrigeration equipment
• Auto-tuning of all 4 PID loops
• Eliminates the need for other controllers
• Provides fl exibility for the controller and reduces the load
Extended I/O capacityWhen operated by an external
controller, all the FC 103 I/O points are
available as remote I/O to extend the
capacity of the controller. For example,
room temperature sensors (Pt1000/
Ni1000) can be directly connected.
Pc Ref
Pc Ref min
Pc Ref max
Sc3
Floating condensing temperature set point control by VLT® Refrigeration Drive FC 103.
12 Danfoss Drives · DKDD.PB.103.A6.02
Dry Pump Protection and End of Curve Dry Pump Protection and End of
Curve relate to situations where the
pump runs without creating the
desired pressure – for example, when
a pipe leaks. In this situation the drive
sets off an alarm, shuts off the pump,
or performs another pre-
programmed action.
Auto tuning of the PI controllers With auto tuning of the PI con trol lers,
EN 55011Facility operators must comply with EN 55011
Class BHousing
and light industries
Class A Group 1Industrial
environment
Class A Group 2Industrial
environment
EN/IEC 61800-3Converter manufacturersmust conform to EN 61800-3
Category C1First
enviroment, home and offi ce
Category C2First
enviroment, home and offi ce
Category C3Second
enviroment
FC 103 compliance 1)
For further details see the VLT® Refrigeration Drive Design Guide1) Compliance to mentioned EMC classes depends on the selected fi lter
300
150
0
-150
-300
[V]
8 16 24 32 ms
300
150
0
-150
-300
[V]
8 16 24 32 ms
23Danfoss Drives · DKDD.PB.103.A6.02
The mains voltage supplied by electricity utilities to homes, businesses and industry should be a uniform sinusoidal voltage with a constant amplitude and frequency.
Solutions for harmonics mitigation
Adverse effects of harmonics Limitations on supply and
network utilization
Increased transformer, motor
and cable heating
Reduced equipment lifetime
Costly equipment downtime
Control system malfunctions
Pulsating and reduced motor
torque
Audible noise
This ideal situation is no longer found in any power grid
due to harmonics. This is mainly because consumers take
non-sinusoidal current from the grid or have a nonlinear
characteristic, e.g. strip lights, light dampers, energy-saving
bulbs and frequency converters.
Because of the constantly increasing use of non-linear loads,
deviations become increasingly serious. Irregular power
supplies infl uence the performance and operation of electrical
equipment, so motors, frequency converters and transformers
must be more highly rated to maintain proper operation.
The Danfoss harmonic filters AHF 005/010 are specially
designed to be connected in front of a VLT® frequency
converter, and ensure that the harmonic current distortion
generated back to the mains is reduced to a minimum.
One filter can be used for several frequency converters,
helping owners reduce system costs. Easy commissioning
saves installation costs, and due to the filter’s maintenance free
design running expenses for the units are eliminated.
VLT® Advanced Harmonic Filter AHF 005 (5% THiD)
VLT® Advanced Harmonic Filter AHF 010 (10% THiD)
Voltage range: 380-690 V
Filter current range: 10-480 A
VLT® Advanced Active Filter AAF 006VLT® Advanced Active Filters identify harmonic distortion
from non-linear loads and inject counter-phase harmonic and
reactive currents into the AC line to cancel out the distortion,
resulting in distortion levels of no more than 5% THvD. The
optimal sinusoidal waveform of the AC power is restored and
the power factor of the system is reestablished at 1.
Advanced Active Filters follow the same design principles as all
our other drives. The modular platform provides high energy
efficiency , user friendly operation, efficient cooling and high
enclosure ratings.
VLT® Advanced Active Filter AAF 006
Voltage range: 380-480 V
Corrective current range: 190-400 A
25Danfoss Drives · DKDD.PB.103.A6.02
Cost eff ective mitigation
Imbalance and pre-distortionThe harmonic mitigation performance of the diff erent solutions depends on the grid quality.The higher the imbalance andpre-distortion, the more harmonic the equipment has to suppress. The graph shows at what pre-distortion and imbalance level each technolegy can keep its guaranteed THDi performance.
Over-sizingPublished fi lter data are all given at 100% loading but fi lters are seldom run at full load due to over-sizing and load profi le. Serial mitigation equipment must always be sized for the maximum cur-rent, but be aware of the duration of part load operation and evaluate the diff erent fi lter types accordingly. Over-sizing gives poor mitigation perfor-mance and high running costs. It is also a waste of money.
Power size vs. initial costsCompared to the frequency converter, the diff erent solutions have diff erent add-on prices depending on power size. The passive solutions in general off er the lowest initial cost and as the complexity of the solutions in-crease, so does the price.
Standards complianceKeeping equipment immunity higher than system distortion ensures trouble free operation. Most standards set restrictions on total voltage distortion according to a planned level, often between 5% and 8%. Equipment immunity is, in most cases, far higher: for drives, between 15-20%. However, this infl uences prod-uct life adversely.
Average Loading
6
55
80
12 18
150% 140% 120% 100%
Filter VSD M
Hours
Pre-distortion (%)
LHD/AAFTHDi 5%
AFETHDi <5%
AHFTHDi 5 & 10%
12PTHDi 12%
1
2 5 10
2
Imb
alan
ce (%
)Lo
ad (%
)A
dd
-on
pri
ce (%
)
Emission limitsindividualsources
Planning levels
Immunitytest levels
Disturbance level
Pro
bab
ility
de
nsi
ty
0 2 4 6
2
4
6
8
10
8 10
Re
sult
ant
TH
Dv
(%)
Grid impedence (%)
5 7 11 13 17 19 23
0
4
2
25
IEEE 519
VLL
(1)
= 3
89
V
THDv = 3.3%
I (1) = 1082.8 A, THDi = 4.9%
0 200 400 600 800 (kW)
20
60
100
140
AHF 005
LHD
AFE
12 pulse incl. transformer
AHF 010
System disturbance
Equipment immunity
Compability level
1088
90
92
94
96
98
100
30 50 70 90
Effi
cie
nc
y (%
)
Load (%)AHF
12P
LHD
AFE
20 30 40 50 60 70 80 90
0
5
10
15
20
100
TH
Di (
%)
Load (%)AHF 005
AHF 010
18 pulse
12 pulse
LHD and AAF
26 Danfoss Drives · DKDD.PB.103.A6.02
System impedanceAs an example, a 400 kW FC 103 drive on a 1000 kVA transformer with 5% impedance results in ~5% THDv (total harmonic voltage distortion) at ideal grid conditions, whereas the same drive on a 1000 kVA, 8% imp. trans-former leads to 50% higher THDv, namely 7.5%.
Harmonic performanceEach harmonic mitigation technology has its own THDi characteristic which is load dependent. These characteristics are set at ideal grid conditions without pre-distortion and with balanced phases. Variations hereof will result in higher THDi values.
Fulfi lling the standardsTo determine whether or not the harmonic pollution of a given applica-tion/grid exceeds a specifi c standard, many complex calculations must be done. With the help from free Danfoss MCT 31 harmonic calculation soft-ware, this is made easy and less time consuming.
System effi ciencyThe running cost is mainly determined by the overall system effi ciency. This depends on the individual prod-ucts, true power-factors and effi cien-cies. Active solutions tend to keep the true power-factor independent of load and grid variations. On the other hand, active solutions are less effi cient than passive solutions.
Total Harmonic distortionEach drive generates its own total harmonic current distortion (THDi) which depends on the grid conditions. The bigger the drive is in relation to the transformer the smaller the THDi.
Wall spaceIn many applications the amount of available wall space is limited and must be utilized to the greatest extent possible. Based on diff erent technologies, the various harmonic solutions each have their optimum size and power relationship.500
1000
1500
2000
2500
3500
3000
160 355 710 (kW)
5.5 30 90 315 630 1000 (kW)0
10
20
30
40
50
Drive power rating
TH
Di (
%)
Wid
th (m
m)
VLT®
AHF
12-pulse w/o autotransformer
LHD/AAF
27Danfoss Drives · DKDD.PB.103.A6.02
An external watertight USB plug connected to the control card inside IP55/66 enclosures makes USB access easy.
The VLT® Refrigeration Drive is also available with a mains switch option. This switch interrupts the mains supply and has a free useable auxiliary contact.
All VLT® Refrigeration Drive FC 103
versions have manganese phosphor
rear bodies. IP66/Type 4X enclosed
drives are suitable for installation in
demanding environments.
Cooling air is kept outside the device to
prevent any pollution of the elec-
tronics. The surfaces are smooth and
easily cleaned.
The IP55/66, Type 4X series are
designed for easy accessibility and
time-saving installation.
Furthermore, all components such as
EMC fi lters for compliance with
EN 55011, class A1/B, as well as the
DC coils, are protected inside the drive.
Because of the high-density integra-
tion, the tight housings of the VLT®
Refrigeration Drive are signifi cantly
smaller when compared to other drives
of the same performance.
Motor and power cables are mounted
securely through glands in the base
plate.
High reliability in any environment
28 Danfoss Drives · DKDD.PB.103.A6.02
VLT® Refrigeration Drive FC 103– optimized for installation in panels
The functionality fulfi lls the highest
requirements even for applications
with high overload, long motor cables
and ambient temperatures up to 50 °C
(55 °C with derating).
Optimized design
Optimized effi ciency and intelligent
cooling technology make for a
compact and service-friendly design.
Supplementary equipment such as
EMC fi lters, harmonics suppression and
brake modules are integrated into the
enclosure.
Save installation time
The IP20 / UL TYPE 1 enclosure series is
designed for easy accessibility and
time-saving installation.
Total separation between cooling air
and electronics protects the electronics
and allows for installation where heat is
removed from outside of the cabinets.
With the VLT® Refrigeration Drive
FC 103, a fl anged heat sink kit is
available for mounting the drive in the
backplate of a cabinet, separating the
heatsink airfl ow from the electronics.
Eliminating airfl ow over the electronics
increases drive lifetime as contaminants
are excluded from the drive.
Back channel cooling minimizes heat
loss while increasing energy effi ciency,
a signifi cant benefi t for high power
drives.
IP20 / UL TYPE 1 Enclosures
Intelligent heat management – cooling methods for additional benefi ts
Mechanical fastening points are easy
to access from the front even with
automatic tools.
All terminals are suffi ciently dimen-
sioned and clearly marked. Just loosen
a few screws to get to the terminals.
Accessories for bonding screened
cables are included. The compact
enclosures are easier to install. This is
important especially within existing
installations with limited accessibility.
An extensive range of options and
accessories are available, optimizing
the drive for the respective application.
29Danfoss Drives · DKDD.PB.103.A6.02
Download drivers for easy PLC integrationIntegrating a drive into an existing bus
system can be time consuming and
complicated. To make this process easy
and more effi cient, Danfoss provides
all necessary fi eldbus drivers and
instructions, which can be downloaded
for free from the Danfoss website.
After installation the bus parameters,
typically only a few, can be set directly
in the VLT® drive via the local control
panel, the VLT® MCT 10 or the fi eldbus
itself.
Increase productivityWith the range of fi eldbus options the
VLT® Refrigeration Drive FC 103 can
be easily connected to the fi eldbus
system of your choice. This makes the
VLT® Refrigeration Drive a future-ready
solution that can easily be expanded
and updated if your needs change.
See the complete list of fi eldbuses on
page 52.
Danfoss fi eldbus options can also be
installed as a plug-and-play solution at
a later stage, if the production layout
demands a new communication
platform. This way, you can be
confi dent that you can optimize your
plant without being forced to replace
your existing drive system.
Support common fi eldbusses
30 Danfoss Drives · DKDD.PB.103.A6.02
Proven refrigeration experience
31Danfoss Drives · DKDD.PB.103.A6.02
Helsinki Ice Stadium, FinlandHelsinki Ice Stadium opened 1966 and
Sainsbury, United KingsomSainsbury’s stores, amongst the leading
supermarket chain in the United
Kingdom, are committed to achieving
their CO2 milestone supported by
Danfoss Drives, electronic controllers
and related refrigeration controls.
VLT® drives are employed to keep correct and constant temperature in Maersk containers. Compact design, high efficiency, extreme reliability and dedicated refrigeration features are necessary for drives to operate cooling containers at sea and in trains and trucks all over the world. The quality of the cargo depends on it.
Maersk Containers,Denmark
32 Danfoss Drives · DKDD.PB.103.A6.02
Corman, BelgiumLocated a stone’s throw from the
famous Gileppe dam, Belgium, the
Corman public limited company
specialises in a broad range of anhy-
drous dairy fats, concentrated butter
and technically adapted butter to the
needs of food and agriculture industries
throughout the world.
Installing VLT® drives proved to be the
best way to reduce operation costs and
to cater eff ectively for the changing
needs in the production lines.
Grupo Bimbo, S.A.B. de C.V., Mexico Grupo Bimbo, S.A.B. de C.V. is the
largest Mexican-owned baking
company, with operations in the
Americas, Asia and Europe.
The company has used and trusted
Danfoss products for a long time. At
the Hazpan plant in Mexico Bimbo
applied a VLT® frequency converter to
control an 200kW ammonium cooling
compressor – the investment payed
back in two years.
CUB Yatala brewery, AustraliaCarlton & United Breweries’ Yatala
brewery in Queensland, North Aus-
tralia, boasts better than world’s best
practice kWh-per-hectolitre fi gures
after a major revamp of its brine
chilling plant.
The chiller systems’ VLT® drives allow
the pumping and compressor capaci-
ties to be modulated according to
plant demand for chilled brine.
Versacold Group, CanadaThe Versacold Group operates approxi-
3 x 200-240 V AC ...................1.1-45 kW3 x 380-480 V AC ................1.1-450 kW3 x 525-600 V AC ...................1.1-90 kW3 x 525-690 V AC .................75-630 kW
Supply frequency 50/60 Hz
Displacement power factor(cos ф) near unity
> 0.98
True power factor (λ) ≥ 0.9
Switching on input supply L1, L2, L3
1-2 times/min.
Harmonic disturbance Meets EN 61000-3-12
Output data (U, V, W)
Output voltage 0-100% of supply voltage
Output frequency (dependent on power size)
0-590 Hz
Switching on output Unlimited
Ramp times 0.1-3600 sec.
Digital inputs
Programmable digital inputs 6*
Changeable to digital output 2 (terminal 27, 29)
Logic PNP or NPN
Voltage level 0-24 V DC
Maximum voltage on input 28 V DC
Input resistance, Ri Approx. 4 kΩ
Scan interval 5 ms
* Two of the inputs can be used as digital outputs.
Analog inputs
Analogue inputs 2
Modes Voltage or current
Voltage level 0 to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Accuracy of analog inputs Max. error: 0.5% of full scale
Pulse inputs
Programmable pulse inputs 2*
Voltage level 0-24 V DC (PNP positive logic)
Pulse input accuracy (0.1-1 kHz)
Max. error: 0.1% of full scale
* Two of the digital inputs can be used for pulse inputs.
Digital outputs
Programmable digital/pulse outputs
2
Voltage level at digital/frequency output
0-24 V DC
Max. output current (sink or source)
40 mA
Maximum output frequency at frequency output
0-32 kHz
Accuracy on frequency output Max. error: 0.1% of full scale
Analogue output
Programmable analogue outputs
1
Current range at analogue output
0/4-20 mA
Max. load to common at analogue output (clamp 30)
500 Ω
Accuracy on analogue output Max. error: 1% of full scale
Control card
USB interface 1.1 (Full Speed)
USB plug Type “B”
RS485 interface Up to 115 kBaud
Max. load (10 V) 15 mA
Max. load (24 V) 200 mA
Relay output
Programmable relay outputs 2
Max. terminal load (AC) on 1-3 (break), 1-2 (make), 4-6 (break) power card
240 V AC, 2 A
Max. terminal load (AC) on 4-5 (make) power card
400 V AC, 2 A
Min. terminal load on 1-3 (break), 1-2 (make), 4-6 (break), 4-5 (make) power card
24 V DC 10 mA, 24 V AC 20 mA
Surroundings/external
Enclosure IP: 00/20/21/54/55/66
UL Type: Chassis/1/12/4x Outdoor
Vibration test 1.0 g (D, E & F-enclosures: 0.7 g)
Max. relative humidity5-95% (IEC 721-3-3; Class 3K3
(non-condensing) during operation)
Ambient temperatureUp to 55 °C (50 °C without
derating; D-enclosure 45 °C)
Galvanic isolation of all I/O supplies according to PELV
Aggressive environmentDesigned for coated/uncoated
3C3/3C2 (IEC 60721-3-3)
Fieldbus communication
Standard built-in:FC Protocol Modbus RTUMetasys N2FC MC
– Electronic thermal motor protection against overload
– Up to 55 °C (50 °C without derating; D-enclosure 45 °C)
– Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature
– The frequency converter is protected against short-circuits on motor terminals U, V, W
– The frequency converter is protected against earth faults on motor terminals U, V, W
– Protection against mains phase loss
Application options
Extend the functionality of the drive with integrated options:• VLT® General Purpose I/O MCB 101• VLT® Extended Relay Card MCB 113• VLT® 24 V External Supply MCB 107
Relay and analogue I/O option
• VLT® Relay Card MCB 105• VLT® Analog I/O MCB109)
Power options
Choose from a wide range of external power options for use with our drive in critical networks or applications:• VLT® Advanced Active Filter• VLT® Advanced Harmonic Filter• VLT® dU/dt fi lter• VLT® Sine wave fi lter (LC fi lter)
High power options
See the VLT® High Power Drive Selection Guide for a complete list.
PC software tools
• VLT® Motion Control Tool MCT 10• VLT® Energy Box• VLT® Motion Control Tool MCT 31
35Danfoss Drives · DKDD.PB.103.A6.02
VLT® Refrigeration Drive T2 200 – 240 V T4 380 – 480 V T6 525 – 600 V T7 525 – 690 V
1)1) The 3 values for the max. cable cross-section The 3 values for the max. cable cross-section indicate single core, fl exible wire, and fl exible wire indicate single core, fl exible wire, and fl exible wire with sleeve, respectively.with sleeve, respectively.
2)2) The typical power loss is at normal load condi- The typical power loss is at normal load condi-tions and expected to be within ± 15 % (tolerance tions and expected to be within ± 15 % (tolerance relates to variations in voltage and cable condi-relates to variations in voltage and cable condi-tions). tions). Values are based on a typical motor effi ciency. Values are based on a typical motor effi ciency. Lower effi ciency motors will also add to the Lower effi ciency motors will also add to the power loss in the frequency converter and vice power loss in the frequency converter and vice versa.versa.If the switching frequency is raised from nominal, If the switching frequency is raised from nominal, the power losses may rise signifi cantly. the power losses may rise signifi cantly. LCP and typical control card power consump-LCP and typical control card power consump-tions are included. Further options and customer tions are included. Further options and customer load may add up to 30 W to the losses. load may add up to 30 W to the losses. (Though typically only 4 W extra for a fully (Though typically only 4 W extra for a fully loaded control card or options for slot A or slot loaded control card or options for slot A or slot B, each).B, each).Although measurements are made with state Although measurements are made with state of the art equipment, some measurement inac-of the art equipment, some measurement inac-curacy must be allowed for (± 5 %).curacy must be allowed for (± 5 %).
3)3) Measured using 5 m screened motor cables at Measured using 5 m screened motor cables at rated load and rated frequency.rated load and rated frequency.
4)4) Enclosure types A2 + A3 can be converted to Enclosure types A2 + A3 can be converted to IP21 using a conversion kit. See also Mechanical IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the mounting and IP21/Type 1 enclosure kit in the Design Guide.Design Guide.
5)5) Enclosure types B3 + B4 and C3 + C4 can be Enclosure types B3 + B4 and C3 + C4 can be converted to IP21 using a conversion kit. See also converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide.kit in the Design Guide.
1)1) The 3 values for the max. cable cross-section indicate single core, fl exible wire, and fl exible wire with sleeve, respectively. The 3 values for the max. cable cross-section indicate single core, fl exible wire, and fl exible wire with sleeve, respectively.2)2) The typical power loss is at normal load conditions and expected to be within ± 15 % (tolerance relates to variations in voltage and cable conditions). The typical power loss is at normal load conditions and expected to be within ± 15 % (tolerance relates to variations in voltage and cable conditions).
Values are based on a typical motor effi ciency. Lower effi ciency motors will also add to the power loss in the frequency converter and vice versa.Values are based on a typical motor effi ciency. Lower effi ciency motors will also add to the power loss in the frequency converter and vice versa.If the switching frequency is raised from nominal, the power losses may rise signifi cantly. If the switching frequency is raised from nominal, the power losses may rise signifi cantly. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. (Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each).(Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (± 5 %).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (± 5 %).
3)3) Measured using 5 m screened motor cables at rated load and rated frequency. Measured using 5 m screened motor cables at rated load and rated frequency.4)4) Enclosure types A2 + A3 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide. Enclosure types A2 + A3 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide.5)5) Enclosure types B3 + B4 and C3 + C4 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide. Enclosure types B3 + B4 and C3 + C4 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide.
1)1) The 3 values for the max. cable cross-section indicate single core, fl exible wire, and fl exible wire with sleeve, respectively. The 3 values for the max. cable cross-section indicate single core, fl exible wire, and fl exible wire with sleeve, respectively.2)2) The typical power loss is at normal load conditions and expected to be within ± 15 % (tolerance relates to variations in voltage and cable conditions). The typical power loss is at normal load conditions and expected to be within ± 15 % (tolerance relates to variations in voltage and cable conditions).
Values are based on a typical motor effi ciency. Lower effi ciency motors will also add to the power loss in the frequency converter and vice versa.Values are based on a typical motor effi ciency. Lower effi ciency motors will also add to the power loss in the frequency converter and vice versa.If the switching frequency is raised from nominal, the power losses may rise signifi cantly. If the switching frequency is raised from nominal, the power losses may rise signifi cantly. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the losses. (Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each).(Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (± 5 %).Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (± 5 %).
3)3) Measured using 5 m screened motor cables at rated load and rated frequency. Measured using 5 m screened motor cables at rated load and rated frequency.4)4) Enclosure types A2 + A3 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide. Enclosure types A2 + A3 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide.5)5) Enclosure types B3 + B4 and C3 + C4 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide. Enclosure types B3 + B4 and C3 + C4 can be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 enclosure kit in the Design Guide.
Technical specifi cations, D-frames 380-480 V, mains supply 3 x 380-480 V AC and E-frames 380-480 V, mains supply 3 x 380-480 V ACTechnical specifi cations, D-frames 380-480 V, mains supply 3 x 380-480 V AC and E-frames 380-480 V, mains supply 3 x 380-480 V AC1)1) American Wire Gauge. American Wire Gauge.2)2) Wiring terminals on N132, N160, and N315 frequency converters cannot receive cables one size larger. Wiring terminals on N132, N160, and N315 frequency converters cannot receive cables one size larger.3)3) For fuse ratings, check reference. For fuse ratings, check reference.4)4) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions).
These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If the switching frequency is raised from nominal, the power losses rise These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If the switching frequency is raised from nominal, the power losses rise signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.a fully loaded control card and options for slots A and B each add only 4 W.
5)5) Measured using 5 m screened motor cables at rated load and rated frequency. Measured using 5 m screened motor cables at rated load and rated frequency.6)6) Additional frame size weights are as follows: D5h – 166 (255) / D6h – 129 (285) / D7h – 200 (440) / D8h – 225 (496). Weights are in kg (lbs). Additional frame size weights are as follows: D5h – 166 (255) / D6h – 129 (285) / D7h – 200 (440) / D8h – 225 (496). Weights are in kg (lbs).
Technical specifi cations, D-frames 525-690 V, mains supply 3 x 525-690 V ACTechnical specifi cations, D-frames 525-690 V, mains supply 3 x 525-690 V AC1)1) American Wire Gauge. American Wire Gauge.2)2) For fuse ratings, check reference. For fuse ratings, check reference.3)3) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions).
These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If theswitching frequency is raised from nominal, the power losses rise These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If theswitching frequency is raised from nominal, the power losses rise signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.a fully loaded control card and options for slots A and B each add only 4 W.
4)4) Measured using 5 m screened motor cables at rated load and rated frequency. Measured using 5 m screened motor cables at rated load and rated frequency.
Technical specifi cations for VLT® Low Harmonic Drive, VLT® Advanced Active Filter AAF 006 and VLT® 12-pulseTechnical specifi cations for VLT® Low Harmonic Drive, VLT® Advanced Active Filter AAF 006 and VLT® 12-pulsePlease see the VLT® High Power Drive Selection Guide.Please see the VLT® High Power Drive Selection Guide.
Estimated power loss at 600 V 3) 4) [W] 5323 6010 7395 8209
Estimated power loss at 690 V 3) 4) [W] 5529 6239 7653 8495
Effi ciency 4) 0.98
Output frequency 0-525 Hz
Heatsink overtemperature trip 110 °C 95 °C 110 °C
Power card ambient trip 85 °C 85 °C
WeightWeight
IP00 [kg] 221 236 277
IP21, IP54 [kg] 263 272 313
Technical specifi cations, E-frames 525-690 V, mains supply 3 x 525-690 V ACTechnical specifi cations, E-frames 525-690 V, mains supply 3 x 525-690 V AC1)1) American Wire Gauge. American Wire Gauge.2)2) For fuse ratings, check reference. For fuse ratings, check reference.3)3) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If the switching frequency is raised from nominal, the power losses rise These values are based on a typical motor effi ciency (IE/IE3 border line). Lower effi ciency motors add to the power loss in the frequency converter. If the switching frequency is raised from nominal, the power losses rise
signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually signifi cantly. LCP and typical control card power consumptions are included. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.a fully loaded control card and options for slots A and B each add only 4 W.
4)4) Measured using 5 m screened motor cables at rated load and rated frequency. Measured using 5 m screened motor cables at rated load and rated frequency.
Technical specifi cations for VLT® Low Harmonic Drive, VLT® Advanced Active Filter AAF 006 and VLT® 12-pulseTechnical specifi cations for VLT® Low Harmonic Drive, VLT® Advanced Active Filter AAF 006 and VLT® 12-pulsePlease see the VLT® High Power Drive Selection Guide.Please see the VLT® High Power Drive Selection Guide.
A3 IP20 with option C A4 IP55 with mains disconnect
O
I
Air space outlet
Air space outlet
D D2
D1
Depth
Depth
Air space outlet
Air space inlet
47Danfoss Drives · DKDD.PB.103.A6.02
W
A
Door swing
Width
HH1 Height
Height
Enclose size
D1h/D2h
Enclosure size
D3h/D4h
OAir space outlet
C1Air space inlet
D
Depth
IAir space inlet
C2C1
C2
C2
Air space outletAir space outlet
Air space inlet
Air space outlet
C2
C2
C1
C1
Dimensions and air fl ow
48 Danfoss Drives · DKDD.PB.103.A6.02
Enclosure size
D5h/D6h
Enclosure size
D7h/D8h
D enclosures
C1
C1
C2
C2
C2
C1
C1
C1
C1
C2
VLT® Refrigeration Drive
Enclosure D1h D2h D3h D4h D5h D6h D7h D8h
Protection rating IP21/IP54 IP20 IP21/IP54
H mmHeight of back plate
901 1107 909 1122 1324 1665 1978 2284
H1 mmHeight of product
844 1050 844 1050 1277 1617 1931 2236
W mm 325 420 250 350 325 325 420 420
D mm 378 378 375 375 381 381 384 402
D1 mmWith mains disconnect
– – – – 426 426 429 447
Door swing A mm 298 395 n/a n/a 298 298 395 395
Air
co
oli
ng
I (air space inlet) mm 225 225 225 225 225 225 225 225
O (air space outlet) mm 225 225 225 225 225 225 225 225
C1102 m3/hr(60 cfm)
204 m3/hr(120 cfm)
102 m3/hr(60 cfm)
204 m3/hr(120 cfm)
102 m3/hr(60 cfm)
204 m3/hr(120 cfm)
C2420 m3/hr(250 cfm)
840 m3/hr(500 cfm)
420 m3/hr(250 cfm)
840 m3/hr(500 cfm)
420 m3/hr(250 cfm)
840 m3/hr(500 cfm)
49Danfoss Drives · DKDD.PB.103.A6.02
Dimensions and air fl ow
HH1
A B C D
HeightHeight
W
Door swing Door swing Door swingDoor swing
Width
D D
D1 D1
C2
C2
C2
O
C1
O
C1
Air space outlet
Air space outlet
Air space outlet
Air space outlet
Air space inlet
Air space inlet
Air space inlet
Air space inlet
Air space outlet
Air space inlet
Depth Depth
Depth Depth
Enclosure
size E1
Enclosure
size E2
I
C1
C1
I
C1
50 Danfoss Drives · DKDD.PB.103.A6.02
VLT® Refrigeration Drive
Enclsoure E1 E2
Protection rating IP21/IP54 IP00
H mm (inches)2000(79)
1547(61)
H1 mm (inches) n/a n/a
W mm (inches)600(24)
585(23)
D mm (inches)538(21)
539(21)
D1 mm (inches)494(19)
498(20)
Door swing A mm (inches)
579(23)
579(23)
Door swing Bmm (inches)
n/a n/a
Door swing Cmm (inches)
n/a n/a
Door swing Dmm (inches)
n/a n/a
Air
co
oli
ng
I (air space inlet)mm (inches)
225(9)
225(9)
O (air space outlet)mm (inches)
225(9)
225(9)
C1
1105 m3/hr(650 cfm) or 1444 m3/hr(850 cfm)
1105 m3/hr(650 cfm) or 1444 m3/hr(850 cfm)
C2340 m3/hr(200 cfm)
255 m3/hr(150 cfm)
E enclosures
51Danfoss Drives · DKDD.PB.103.A6.02
A options: FieldbusesAvailable for the full product range
Fieldbus
A
VLT® PROFIBUS DP V1 MCA 101
VLT® PROFINET MCA 120
VLT® AK-LonWorks MCA 107
VLT® PROFIBUS DP MCA 101Operating the frequency converter via a fi eldbus enables you to reduce the cost of your system, communicate faster and more effi ciently, and benefi t from an easier user interface.
VLT® PROFIBUS DP MCA 101 provides wide compatibility, a high level of availability, support for all major PLC vendors, and compatibility with future versions
Fast, effi cient communication, transpa-rent installation, advanced diagnosis and parameterisation and auto- confi guration of process data via GSD-fi le
A-cyclic parameterisation using PROFIBUS DP-V1, PROFIdrive or Danfoss FC profi le state machines, PROFIBUS DP-V1, Master Class 1 and 2
Ordering number 130B1100 standard, 130B1200 coated
VLT® AK-LonWorks MCA 107VLT® AK-LonWorks MCA 107 is a complete electronic refrigeration and control system for monitoring and controlling refrigeration plants. Connecting this drive to ADAP-KOOL® Lon network is really simple. After entering a network address, pressing a service pin starts the automatic confi guration procedure.
Ordering number 130B1169 standard, 130B1269 coated(Class 3C3/IEC 60721-3-3)
VLT® PROFINET MCA 120VLT® PROFINET MCA 120 uniquely combines the highest performance with the highest degree of openness. The MCA120 gives the user access to the power of Ethernet. The op-tion is designed so that many of the features from the PROFIBUS MCA 101 can be reused, minimising user eff ort to migrate PROFINET, and securing the investment in PLC program.
Other features: Built-in web server for remote diagnosis and
reading out of basic drive parameters Support of DP-V1 Diagnostic allows easy,
fast and standardized handling of warning and fault information into the PLC, impro-ving bandwidth in the system
PROFINET encompasses a suite of messages and services for a variety of manufacturing automation applications, including control, configuration and information.
Ordering number 130B1135 standard, 130B1235 coated
52 Danfoss Drives · DKDD.PB.103.A6.02
B options: Functional extensionsAvailable for the full product range
VLT® General Purpose I/O MCB 101This I/O option off ers an extended number of control inputs and outputs:
Protects control cable connection Spring-loaded control wire connection
Ordering number 130B1110 standard, 130B1210 coated
VLT® Analog I/O MCB 109This analogue input/output option is easily fi tted in the frequency converter for upgrad-ing to advanced performance and control using the additional in/outputs.This option also upgrades the frequency converter with a battery back-up supply for the frequency converter’s built-in clock. This provides stable use of all frequency converter clock functions as timed actions etc.
3 analogue inputs, each configurable as both voltage and temperature input
Connection of 0-10 V analogue signals as well as PT1000 and NI1000 temperature inputs
3 analogue outputs each configurable as 0-10 V outputs
Incl. back-up supply for the standard clock function in the frequency converter
The back-up battery typically lasts for 10 years, depending on environment.
Ordering number130B1143 standard, 130B1243 coated
Funcional extensions
B
VLT® General Purpose I/O MCB 101
VLT® Relay Card MCB 105
VLT® Analog I/O MCB 109
C options: Pack controller and relay cardAvailable for the full product range
VLT® Extended Relay Card MCB 113The VLT® Extended Relay Card MCB 113adds inputs/outputs to VLT® Refrigeration Drive FC 103 for increased fl exibility and pos-sibility to control up to 6 compressors
Ordering number 130B1164 standard, 130B1264 coated
Option slot
C
VLT® Extended Relay Card MCB 113
53Danfoss Drives · DKDD.PB.103.A6.02
D option: External power supplyAvailable for the full product range
Option slot
D
VLT® 24 V DC Supply Option MCB 107
VLT® 24 V DC Supply MCB 107The option is used to connect an external DC supply to keep the control section and any installed option alive during power failure.
Input voltage range ...24 V DC +/- 15% (max. 37 V in 10 sec.)
Max. input current .............................................. 2.2 A Max. cable length ...............................................75 m Input capitance load .................................. < 10 uF Power-up delay .................................................< 0.6 s
Ordering number 130B1108 uncoated, 130B1208 coated
AccessoriesAvailable for the full product range
LCP
VLT® Control Panel LCP 102 (Graphical)Ordering number: 130B1107
LCP Panel Mounting KitOrdering number for IP20 enclosure130B1113: With fasteners, gasket, graphical LCP and 3 m cable130B1114: With fasteners, gasket, numerical LCP and 3 m cable130B1117: With fasteners, gasket and without LCP and with 3 m cable130B1170: With fasteners, gasket and without LCP
Ordering number for IP55 enclosure130B1129: With fasteners, gasket, blind cover and 8 m “free end” cable
Power Options*
VLT® Sine-Wave Filter MCC 101
VLT® dU/dt Filter MCC 102
VLT® Advanced Harmonic Filter AHF 005/010
VLT® Advanced Active Filter
VLT® Brake Resistors MCE 101
Accessories
USB ExtensionOrdering number: 130B1155: 350 mm cable130B1156: 650 mm cable
IP21/Type 1 (NEMA 1) kitOrdering number130B1122: For frame size A2130B1123: For frame size A3130B1187: For frame size B3130B1189: For frame size B4130B1191: For frame size C3130B1193: For frame size C4
[5] RFI fi lter, terminal and monitoring options – EN/IEC 61800-3 (character 16-17)
H1RFI-Filter Class A1/B (C1)(A, B and C frames only)
H2 RFI-Filter, Class A2 (C3)
H4RFI-Filter, Class A2 (C2)(B, C and D frames only)
H5RFI-Filter, Class A2 (C3)Marine ruggedized
[6] Braking and safety (character 18)
X No brake IGBT
T Safe Stop without brake
[7] LCP Display (character 19)
X Blank faceplate, no LCP installed
G Graphical Local Control Panel (LCP 102)
[8] PCB Coating – IEC 721-3-3 (character 20)
X Standard coated PCB Class 3C2
C Coated PCB Class 3C3
R Coated PCB Class 3C3 + ruggedized
[9] Mains input (character 21)
X No mains option
1 Mains disconnect
3Mains disconnect + fuse (D, E and F3, F4, F9, F11, F14, F18 frame only)
4 Mains contactor + fuse (D frame only)
[10] Cable (character 22)
X Standard cable entries
O Metric cable entries
S US cable entries
[11] Auxiliary 24 V supply and external temperature monitoring (character 23)
X No adaptation
Q Heat-sink access panel (D frame only)
[13] LCP language (character 28)
XStandard language package including English, German, French, Spanish, Danish, Italian, Swedish, Dutch and Russian
[14] Fieldbus (character 29-30)
AX No option
A0 VLT® PROFIBUS DP V1 MCA 101
AL VLT® PROFINET MCA 120
AZ VLT® AK-LonWorks MCA 107
[15] Application 1 (character 31-32)
BX No application option
BK VLT® Generel Purpose MCB 101
BP VLT® Relay Option MCB 105
B0 VLT® Analog I/O Option MCB 109
[16] Application 2 (character 33-34)
X No option
R VLT® Extended Relay Card MCB 113
[19] Control Power Backup Input (character 38-39)
DX No DC input installed
D0 VLT® 24 V DC Supply Option MCB 107
1) reduced motor cable length
Please beware that not all combinations are possible. Find help confi guring your drive with the online confi gurator found under: driveconfi g.danfoss.com
Danfoss Drives is a world leader in variable speed control of electric motors. We offer you unparalleled competitive edge through quality, application-optimized products and a comprehensive range of product lifecycle services.