SEISMIC DESIGN GUIDE

FOR FIRE SPRINKLER COMPONENTS

EDITION 2.0 FOR NFPA-13 2016

COLOR CODED – PRE-STRETCHED – BREAK STRENGTH CERTIFIED

Page 2: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

PREFACE

Whether it’s drawn stainless steel wire, miniature or aircraft cable, wire rope, Seismic Wire Rope

assemblies, fittings or tools, Loos & Co. Inc. can deliver. We have developed, over the last fifty eight

years, the technical capabilities essential in providing such materials to such varied industries as

aerospace, data processing, automotive, aircraft and farm equipment. Special products have been

designed and made for ocean research, mineral exploration and military markets as well as many other

scientific and industrial applications. Technical competence, combined with modern production

equipment and rigid quality control guarantee on time delivery of our wire, cable and cable related

products, made to the most exacting specifications.

Loos & Co. has earned its reputation by continuously meeting and exceeding the increasingly stringent

safety requirements of the aerospace industry. We have taken that level of safety, combined with 50+

years of knowledge and expertise and applied this methodology to our Seismic Bracing Cable system.

Loos & Co. has been providing Seismic Bracing cable and hardware since 1993. What we have seen over

the past 23 years is an evolution from what was once confusion and misconception to an industry that

has gone above and beyond to embrace nationally accepted codes and standards. Loos & Co. has taken

this position to the next level, by incorporating most, if not all of the certifications required to make our

Seismic Bracing Cable the most cost effective, most certified and accepted bracing system on the

market.

Loos & Co. certifications include:

* Third party listed (UL & ICC ES) for use in complying with NFPA 13 for fire sprinkler systems.

* Third party listed (ICC ES) for use in complying with the International Building Code (IBC)

* Are third party tested/listed to verify that cable assemblies, including fittings, maintain the

nominal breaking strength per ASCE 19, as required by IBC, ASCE 7 & NFPA 13

*Have swaged end fittings as required by the 2012 IBC per ASCE 19-10, which does not permit

wedge or clip type fittings.

*Certify the minimum breaking strength of the sway bracing assemblies.

*Comply with NFA 13, ASCE 19, the IBC and ASCE 7.

*Are listed by the FBC for system compatibility with CPVC pipe.

In this guide, you will find all of the specifications, descriptions and applicable drawings for all of the

Seismic products Loos & Co. offers. This will allow the user to identify and specify the proper

components to satisfy the code requirements of the local authority having jurisdiction (AHJ).

Thank you for your interest in our Seismic Cable Bracing System manufactured by Loos & Co. Inc.

© Loos & Co., Inc. - Cableware Division 1.2

Page 3: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

APPLICATION OF THIS PUBLICATION

In this publication you will find information regarding proper installation techniques and guidelines

applicable to Loos & Co. Seismic Cable Bracing System for meeting existing codes and standards. It has

been compiled using proven engineering ethics and principles developed over the past 23 years. Final

accountability for approving specific designs, code interpretations and/or installations rests with the

engineer responsible for the specific design and/or the agency or authority having jurisdiction (AHJ).

Loos & Co. Inc. and/or contributors to this publication assume no liability for the specific installation of

its products or the design, application, approval or interpretation of the requirements or guidelines

contained in this publication. Users of this publication are encouraged to confer with certified design

Engineers (P.E.) as well as all applicable Federal, State and local a regulations or requirements for

specific installations.

REPRINT PERMISSION RESTRICTIONS

Permission is granted to government and private sector users of this publication to reproduce unaltered

conceptual drawings from this publication for their use relating to the specific design, specification,

installation or approval of Loos & Co. Seismic Cable Bracing. Reproduction for the purpose of its sale is

prohibited. Any other use or reproduction of this publication shall be first approved in writing by Loos &

Co. Inc. Liability for the specific application of such information, including errors or omissions in

reproduction is solely the responsibility of the party reproducing such material.

GENERAL INTRODUCTION

Loos & Co. Seismic Design Guide will assist you in the design and installation of our Seismic Cable

Bracing System. All of the materials and products presented have been designed and tested to exceed

the requirements set forth in NFPA 13. In Fact, the provisions of NFPA 13 directly provide for the use of

Loos & Co. UL Listed Seismic Cable Bracing.

Loos & Co. has been providing our Seismic Cable Bracing since 1993 in structures located all over the

world, both for new and retro-fit buildings.

This Design Guide can be used in conjunction with our New Seismic Design Calculator. (Downloadable

for free on our Website www.loosseismicbracing.com) Our Seismic Design Calculator will allow the user

to enter all the details for fire sprinkler installations from the building blueprints then print out of the

completed NFPA 13 form with all of the calculation preapproved, ready to submit to your local AHJ. As

an added bonus, our Seismic Design Calculator software will also generate a Bill of material and all

applicable drawings.

© Loos & Co., Inc. - Cableware Division 1.3

Page 4: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Locoloc® #0-3-SBHS Handswager

Preferred tool for Swaging Gold cable #G03-CBL

A well-made, economical handswaging tool for swaging #GO3 cable sleeves, our most popular cable size. Loos

offers the correct tools to use in swaging our zinc-plated oval sleeves. Using the correct tool and following

proper swaging instructions will ensure proper cable connections that actually exceed the breaking strength of

the cable.

Length: 12"

Use: For size #GO3 (GOLD) cable only.

OPERATION INSTRUCTIONS:

To open tool squeeze handles hard or push release lever (Figure 1) forward while squeezing handles to relieve

tension.

Figure 1 Figure 2 Figure 3

1. Place the sleeve on the cable and make a loop around the item to which you are securing the cable.

2. Next, insert cable end through the sleeve and at least 1/8" or more beyond (Figure 3).

3. While holding sleeve in place, swage one compression. Move over and swage (second compression). Two

compressions are required. The tool won't release until compression is complete. (Figure 2)

4. Check sleeve for proper after swage diameter with gauge provided (Figure

7). The clamping action of the ratchet allows the sleeve to be held by the

tool before completing the swage. This allows for the user to adjust the

position of the sleeve on the cable.

5. After swaging, excess cable may be trimmed off with our FELCO C7 cutters

below.

Figure 7

© Loos & Co., Inc. - Cableware Division 1.4

Page 5: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Locoloc® #3-346-SB Handswager

Used for #GO3-CBL, #OR4-CBL, #GR6-CBL

A well-made, economical handswaging tool for swaging cable sleeves. Loos offers the correct tools to use in swaging our

zinc-plated oval sleeves. Using the correct tool and following proper swaging instructions included with each tool will

ensure proper cable connections that actually exceed the breaking strength of the cable.

Length: 26"

Use: Two-handed tool for size #GO3 (GOLD), #OR4 (ORANGE) and

#GR6 (GREEN) cables.

Each Loos & Co. #3-346SB swaging tool is designed to work with #3, #4, and #6 Zinc-Plated Copper Oval Sleeves. For use

only on Loos & Co. Seismic Cable Bracing sizes #GO3, #OR4, and #GR6. You will not obtain proper performance or meet

UL standards if you do not use the proper Loos & Co. swaging tool and sleeve combination.

Place sleeve to be compressed in proper size groove in swaging tool by matching cable color to colored dot next to

groove in tool. A length of cable equal to the cable diameter should extend beyond the length of sleeve to achieve

maximum holding. (See arrow in Figure 4). Finished sleeve should look like this. Be sure sleeves have been compressed

the proper number of times. See below for proper # of compressions.

Keep jaws of swaging tool at right angles to the sleeve to be compressed, making sure the sleeve is aligned in the jaw

grooves. Close tool completely. Tool handles should snap shut indicating complete closure. After swaging, excess cable

may be trimmed off with our FELCO C7 Cable cutters.

Figure 5

Use the swaging gauge provided with the tool to check proper after swage diameter of sleeve. Compressed sleeve

should slide freely into corresponding size and color slot in gauge. (Figure 5)

Cable Size Zinc-Plated Copper

Oval Sleeve

#GO3 (Gold) 2

#OR4 (Orange) 2

#GR6 (Green) 3 Figure 4

© Loos & Co., Inc. - Cableware Division 1.5

Page 6: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Locoloc® HC-3010-SB Battery Handswager

A well-made and powerful, state-of-the-art battery-powered swaging tool. This newest technology eliminates

the need to swage Loos zinc-plated oval sleeves by hand. This is especially helpful when a large number of

brace connections are required for the job. Kit comes with complete with two long-lasting, fast charge lithium-

ion batteries, I hour quick charger and handy carrying case so you can be sure to have strong portable power

at all times.

Use: For size #GO3 (GOLD), #OR4 (ORANGE) and #GR6

(GREEN) cable sleeves.

Length: 22" Height: 4" Weight: 13 lbs.

OPERATING INSTRUCTIONS

Place the cable sleeve to be crimped in the appropriate cavity. Press on the Grey forward trigger to crimp the sleeve

onto the cable. An audible click advises when the swage (crimp) is completed. Open the jaws of the tool by pressing the

Black retract trigger, you may now crimp another sleeve or you may start another crimp cycle of the tool.

Number of Compressions

Cable size Zinc-plated Copper oval sleeves

#GO3 (GOLD) 2

#OR4 (ORANGE) 2

#GR6 (GREEN) 3

Figure 1 Figure 2 Figure 3

Finished sleeve should look like (Figure 2) on Gold cable. Be sure sleeves have been compressed the proper number of

times. (See Number of Compressions Figure 1). Using the swaging gauge provided with the tool to check proper “after

swage” diameter of sleeve. Compressed sleeve should slide into size slot in gauge: GO (Gold), OR (Orange) and GR

(Green). Sleeves elongate after compression. To assure maximum holding allow the end of the cable to extend beyond

the sleeve after it is compressed. Select the proper cavity size for the sleeve to be swaged. Use only #GO3 sleeves with

#GO3 cavity, #OR4 sleeve with #OR4 cavity and so on. For lap splices at least two oval sleeves should be used.

© Loos & Co., Inc. - Cableware Division 1.6

Page 7: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

FELCO C7 CABLE CUTTER

Loos & Co. offers the complete line of Swiss-made FELCO Brand Cable Cutters. FELCO cutters are recognized around

the world for their precision manufacture and cutting capabilities.

Lightweight enough for overhead cutting yet strong enough for

underwater work.

Plastic-coated handles afford a firm, comfortable grip. A cable

when crushed or deformed in cutting is difficult to use with fittings.

These cable cutters, with unique triangular jaws, never leave a

frayed end.

Capacity: 5/32" on stainless steel diameter and smaller. For use on #GO3-CBL (GOLD) and #OR4-CBL (ORANGE) cable.

Length: 7.5" / 190 mm

Weight: 9.5 oz. / 270g

FELCO C9 CABLE CUTTER

FELCO cutters are recognized around the world for their precision manufacture and cutting capabilities. Lightweight

enough for overhead cutting yet strong enough for underwater work.

Plastic-coated handles afford a firm, comfortable grip. Replacement parts are available from stock. All cutters tested

before leaving the factory. Fills the gap between C7 and C12 - cuts

1/4" steel cable. Ideal for the tool kit. All cutters available from

stock.

Capacity: Cuts 1/4" steel cable. For use on #GR6-CBL (GREEN) and

#BL8-CBL (BLACK) cable.

Length: 13" / 325mm

Weight: 1.5 lbs. / 750g

High-Strength Blades

Hardened and tempered blades for cutting the strongest of cables.

Triangular Cutting Action

FELCO's innovative triangular cut allows you to progressively cut cable wires and at the same time avoid squashing of

strands. Thanks to this feature, it is generally not necessary to tie the cable before the cut.

Forged Aluminum Handles

Lightweight, strong and sturdy thanks to special aluminum alloys and advanced precision forging methods.

© Loos & Co., Inc. - Cableware Division 1.7

Page 8: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Description of Standard Cable Brace Kit Part Numbers

Detailed Cable Kit Part Numbers1. Choose your brace type:

Brace Type Description To Fit Cable Fastener Code2 Two-Way All All4 Four-Way All 00, 2B, 3B, 4B, 5B

2: Choose the cable that best fits your load requirement:Cable Code Description Fastener Code

GO3 Gold, 600 lb. Load Rating 00, 2S, 2B, 3S, 3B

OR4 Orange, 1100 lb. Load Rating 00, 2S, 2B, 3S, 3B, 4S, 4B

GR6 Green, 2667 lb. Load Rating 00, 3S, 3B, 4S, 4BBL8 Black, 4400 lb. Load Rating 00, 5S, 5B

3. Choose the fastener that best fits your requirement:Fastener Code Description To Fit Cable

00 No Stake Eye, Loop GO, OR, GR, BL2S 1/4” Straight Stake Eye GO, OR2B 1/4” 45° Stake Eye GO, OR3S 3/8” Straight Stake Eye GO, OR, GR3B 3/8” 45° Stake Eye GO, OR, GR4S 1/2” Straight Stake Eye OR, GR4B 1/2” 45° Stake Eye OR, GR5S 5/8” Straight Stake Eye BL

5B 5/8” 45° Stake Eye BL

4. Choose desired brace length:Length Code Description To Fit Cable

01 1 foot (+4 ft. extra) All04 4 feet (+4 ft. extra) All07 7 feet (+4 ft. extra) All10 10 feet (+4 ft. extra) All13 13 feet (+4 ft. extra) All

© Loos & Co., Inc. - Cableware Division 1.8

Page 9: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Index

SECTION 1 – GENERAL INFORMATION

1.2 Preface

1.3 Application

1.3 Reprint Permission Restrictions

1.3 General Introduction

1.4 – 1.7 Hand Tool Information

1.8 Description of Cable Kit Part Numbers

SECTION 2 – PRODUCTS

2.1 – 2.4 Seismic Bracing Cable

2.5 Zinc-Plated Oval Sleeves

2.6 – 2.14 Seismic Attachment Fitting (SAF) Series

2.15 – 2.19 Seismic Attachment Fitting Retrofit (SAFR) Series

2.20 – 2.26 Seismic Attachment Fitting 2 (SAF2) Series

2.27 – 2.33 Seismic Attachment Fitting Retrofit 2 (SAFR2) Series

2.34 – 2.39 Low-Pry Fitting (LPF) Series

SECTION 3 – INSTRUCTIONS

3.1 Lateral Bracing Installation

3.2 Longitudinal Bracing Installation

3.3 4-Way Bracing Installation

3.4 Through Bolts in Wood – Angles A, B, and C

3.5 Lag Bolts in Wood – Angles A, B, and C

3.6 Wedge Anchors in 3000 psi Lightweight Concrete Filled Metal Decking –

Angles A, B, and C

3.7 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –

Angles A, B, and C

3.8 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles A, B, and C

3.9 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles A, B, and C

© Loos & Co., Inc. - Cableware Division 1.9

Page 10: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

3.10 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –

Angles A, B, and C

3.11 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –

Angles A, B, and C

3.12 Connections to Steel – Angles A, B, and C

3.13 Through Bolts in Wood – Angles D, E, and F

3.14 Lag Bolts in Wood – Angles D, E, and F

3.15 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –

Angles D, E, and F

3.16 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles D, E, and F

3.17 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles D, E, and F

3.18 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –

Angles D, E, and F

3.19 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –

Angles D, E, and F

3.20 Connections to Steel – Angles D, E, and F

3.21 Through Bolts in Wood – Angles G, H, and I

3.22 Lag Bolts in Wood – Angles G, H, and I

3.23 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –

Angles G, H, and I

3.24 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles G, H, and I

3.25 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles G, H, and I

3.26 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –

Angles G, H, and I

3.27 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –

Angles G, H, and I

3.28 Connections to Steel – Angles G, H, and I

3.29 Cable Looped Around Top Member of Bar Joist – Angles A, B, and C

© Loos & Co., Inc. - Cableware Division 1.10

Page 11: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com

specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster

ESL-1004 & 1007

Seismic Cable BracingBulk Spool - Size #3 (Gold)

Certified Minimum Break Strength (lbs)

Allowable Load at 90° (lbs)

Allowable Load at 30°-

44° (lbs)

Allowable Load at 45°-

59°(lbs)

Allowable Load at 60°-

89° (lbs)

Min. Cable Diameter (in.)

Max. Cable Diameter (in.)

920 600 300 424 519 0.09375 0.10575

Number of Wires

Nom. Dia. of Wires (in.)

Min. Stress at 0.7% Extension

Under Load

Min. Ultimate Tensile Strength

49 .010 to .013 150,000 PSI 300,000 PSI

Applied Load (lbs) Applied Load (% of Min. Break Strength)

% Elongation at Applied Load Modulus of Elasticity

92 10% 0.15% 12.7 x 106

184 20% 0.28% 14.6 x 106

276 30% 0.40% 15.8 x 106

368 40% 0.48% 17.7 x 106

460 50% 0.59% 18.5 x 106

552 60% 0.74% 17.3 x 106

613 66.67%* 0.84% 17.1 x 106

*66.67% is equal to the allowable working load (break strength ÷ 1.5)

©Loos & Co., Inc. - Cableware Division 2.1

Page 12: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com

specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster

ESL-1004 & 1007

Seismic Cable BracingBulk Spool - Size #4 (Orange)

Number of Wires

Nom. Dia. of Wires (in.)

Min. Stress at 0.7% Extension

Under Load

Min. Ultimate Tensile Strength

49 .014 to .015 150,000 PSI 300,000 PSI

Applied Load (lbs) Applied Load (% of Min. Break Strength)

% Elongation at Applied Load Modulus of Elasticity

170 10% 0.17% 11.0 x 106

340 20% 0.30% 13.4 x 106

510 30% 0.42% 14.7 x 106

680 40% 0.52% 16.8 x 106

850 50% 0.64% 17.1 x 106

1020 60% 0.75% 17.0 x 106

1133 66.67%* 0.84% 17.5 x 106

*66.67% is equal to the allowable working load (break strength ÷ 1.5)

Certified Minimum Break Strength (lbs)

Allowable Load at 90° (lbs)

Allowable Load at 30°-

44° (lbs)

Allowable Load at 45°-

59°(lbs)

Allowable Load at 60°-

89° (lbs)

Min. Cable Diameter (in.)

Max. Cable Diameter (in.)

1,700 1,100 550 778 952 .125 .139

©Loos & Co., Inc. - Cableware Division 2.2

Page 13: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com

specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster

ESL-1004 & 1007

Seismic Cable BracingBulk Spool - Size #6 (Green)

Number of Wires

Nom. Dia. of Wires (in.)

Min. Stress at 0.7% Extension

Under Load

Min. Ultimate Tensile Strength

133 .0125 to .016 150,000 PSI 300,000 PSI

Applied Load (lbs) Applied Load (% of Min. Break Strength)

% Elongation at Applied Load Modulus of Elasticity

420 10% 0.17% 12.8 x 106

840 20% 0.31% 14.6 x 106

1,260 30% 0.44% 15.8 x 106

1,680 40% 0.56% 17.1 x 106

2,100 50% 0.69% 17.4 x 106

2,520 60% 0.82% 17.4 x 106

2,800 66.67%* 0.93% 17.3 x 106

*66.67% is equal to the allowable working load (break strength ÷ 1.5)

Certified Minimum Break Strength (lbs)

Allowable Load at 90° (lbs)

Allowable Load at 30°-

44° (lbs)

Allowable Load at 45°-

59°(lbs)

Allowable Load at 60°-

89° (lbs)

Min. Cable Diameter (in.)

Max. Cable Diameter (in.)

4,200 2,100 1,050 1,485 1,818 .1875 .2055

©Loos & Co., Inc. - Cableware Division 2.3

Page 14: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com

specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster

ESL-1004 & 1007

Seismic Cable BracingBulk Spool - Size #8 (Black)

Number of Wires

Nom. Dia. of Wires (in.)

Min. Stress at 0.7% Extension

Under Load

Min. Ultimate Tensile Strength

133 .016 to .020 145,000 PSI 290,000 PSI

Applied Load (lbs) Applied Load (% of Min. Break Strength)

% Elongation at Applied Load Modulus of Elasticity

700 10% 0.20% 12.6 x 106

1,400 20% 0.34% 14.6 x 106

2,100 30% 0.47% 15.9 x 106

2,800 40% 0.60% 16.3 x 106

3,500 50% 0.72% 17.2 x 106

4,200 60% 0.85% 17.5 x 106

4,667 66.67%* 0.94% 17.7 x 106

*66.67% is equal to the allowable working load (break strength ÷ 1.5)

Certified Minimum Break Strength (lbs)

Allowable Load at 90° (lbs)

Allowable Load at 30°-

44° (lbs)

Allowable Load at 45°-

59°(lbs)

Allowable Load at 60°-

89° (lbs)

Min. Cable Diameter (in.)

Max. Cable Diameter (in.)

7,000 4,600 2,300 3,253 3,983 .250 .268

©Loos & Co., Inc. - Cableware Division 2.4

Page 15: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

9P62

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

All Zinc Plated Oval Sleeves supplied by Loos & Co. Inc. are in full compliance with the

requirements of Military Specification MS51844, and are certified to maintain the break

strength of the cable to which they are applied (for 3 x 7, 7 x7, 7 x 19, and 6 x 19

construction).

©Loos & Co., Inc. - Cableware Division 2.5

Page 16: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF SERIES

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

(Structural Attachment Fitting)

Patent # 62/239,394

©Loos & Co., Inc. - Cableware Division 2.6

Page 17: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Mount

The SAF-1/4 is designed for use in attaching Seismic Cable Bracing to steel structural

members. The limitations of use are governed by the fastener diameter as a 1/4 inch (6 mm)

fastener is only listed for use with steel as per NFPA-13. Will accept both metric and

SAF-1/4

imperial fasteners. The cable mount will accept Gold, Orange, and Green cables.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.7

Page 18: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-3/8

Cable Mount

Fastener Mount

The SAF-3/8 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The 3/8 inch (10 mm.) will accept lag bolts,

bolts, and concrete anchors in both metric and imperial sizes. The cable mount will

accept Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.8

Page 19: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-1/2

Cable Mount

Fastener Mount

The SAF-1/2 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The 1/2 inch (13 mm) will accept lag bolts, bolts,

and concrete anchors in both metric and imperial sizes. The cable mount will accept

Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.9

Page 20: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-5/8

Cable Mount

Fastener Mount

The SAF-5/8 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The 5/8 inch (16 mm) will accept lag bolts, bolts,

and concrete anchors in both metric and imperial sizes. The cable mount will accept

Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.10

Page 21: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-3/4

Cable Mount

Fastener Mount

The SAF-3/4 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The 3/4 inch (20 mm) will accept lag bolts, bolts,

and concrete anchors in both metric and imperial sizes. The cable mount will accept

Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.11

Page 22: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-7/8

Cable Mount

Fastener Mount

The SAF-7/8 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The 7/8 inch (22 mm) will accept lag bolts, bolts,

and concrete anchors in both metric and imperial sizes. The cable mount will accept

Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.12

Page 23: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-1

Cable Mount

Fastener Mount

The SAF1 is designed for use in attaching Seismic Cable Bracing to a steel, concrete,

or wood structural member. The1 inch (24 mm) will accept lag bolts, bolts, and

concrete anchors in both metric and imperial sizes. The cable mount will accept Gold,

Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.13

Page 24: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF-11/4

Cable Mount

Fastener Mount

The SAF1 1/4 is designed for use in attaching Seismic Cable Bracing to a steel,

concrete, or wood structural member. The11/4 inch (32 mm) will accept lag bolts,

bolts, and concrete anchors in both metric and imperial sizes. The cable mount will

accept Gold, Orange, and Green cable.

9P62

ESL-1004

ESL-1007

The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF may be used at both ends of the cable for anchoring equipment.

SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,

SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.14

Page 25: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR SERIES

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Structural Attachment Fitting, Retrofit

Patent # 62/239,394

©Loos & Co., Inc. - Cableware Division 2.15

Page 26: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR-1/4

Cable Mount

Fastener Mount

The SAFR-1/4 is designed as a retrofit Seismic Anchoring Fitting for use with

pre-existing equipment and systems that require seismic bracing. The fitting is slotted

to allow an existing fastener to be loosened, and the SAFR positioned without removal

of the fastener.

The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable

without the need of a thimble.

The SAFR may be used at both ends of the cable for anchoring equipment.

SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,

SAFR-1/2, and SAFR-5/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

ESL-1004

ESL-1007

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.16

Page 27: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR-3/8

Cable Mount

Fastener Mount

The SAFR-3/8 is designed as a retrofit Seismic Anchoring Fitting for use with

pre-existing equipment and systems that require seismic bracing. The fitting is slotted

to allow an existing fastener to be loosened, and the SAFR positioned without removal

of the fastener.

The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable

without the need of a thimble.

The SAFR may be used at both ends of the cable for anchoring equipment.

SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,

SAFR-1/2, and SAFR-5/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

ESL-1004

ESL-1007

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.17

Page 28: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR-1/2

Cable Mount

Fastener Mount

The SAFR-1/2 is designed as a retrofit Seismic Anchoring Fitting for use with

pre-existing equipment and systems that require seismic bracing. The fitting is slotted

to allow an existing fastener to be loosened, and the SAFR positioned without removal

of the fastener.

The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable

without the need of a thimble.

The SAFR may be used at both ends of the cable for anchoring equipment.

SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,

SAFR-1/2, and SAFR-5/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

ESL-1004

ESL-1007

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.18

Page 29: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR-5/8

Cable Mount

Fastener Mount

The SAFR-5/8 is designed as a retrofit Seismic Anchoring Fitting for use with

pre-existing equipment and systems that require seismic bracing. The fitting is slotted

to allow an existing fastener to be loosened, and the SAFR positioned without removal

of the fastener.

The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable

without the need of a thimble.

The SAFR may be used at both ends of the cable for anchoring equipment.

SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,

SAFR-1/2, and SAFR-5/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

ESL-1004

ESL-1007

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.19

Page 30: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2 SERIES

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Structural Attachment Fitting, 2 Way

Patent #62/239,394

©Loos & Co., Inc. - Cableware Division 2.20

Page 31: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-1/4

Cable Mount

Fastener Mount

The SAF2-1/4 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 1/4 inch (6 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.21

Page 32: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-3/8

Cable Mount

Fastener Mount

The SAF2-3/8 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 3/8 inch (10 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.22

Page 33: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-1/2

Cable Mount

Fastener Mount

The SAF2-1/2 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 1/2 inch (13 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.23

Page 34: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-5/8

Cable Mount

Fastener Mount

The SAF2-5/8 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 5/8 inch (16 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.24

Page 35: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-3/4

Cable Mount

Fastener Mount

The SAF2-3/4 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 3/4 inch (20 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.25

Page 36: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF2-7/8

Cable Mount

Fastener Mount

The SAF2-7/8 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for

attachment to a steel, concrete, or wood structural member. The 7/8 inch (22 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and

Green cable and are ideal for 2-way bracing.

The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)

cable without the need of a thimble.

The SAF2 may be used at both ends of the cable for anchoring equipment.

SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,

SAF2-5/8, SAF2-3/4, and SAF2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.26

Page 37: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR2 SERIES

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Structural Attachment Fitting, 2 Way, Retrofit

Patent # 62/239,394

©Loos & Co., Inc. - Cableware Division 2.27

Page 38: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR2-1/4

Cable Mount

Fastener Mount

The SAFR2-1/4 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit

enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used

for attachment to a steel, concrete, or wood structural member. The 1/4 inch (6 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange

cable and are ideal for 2-way bracing.

The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable

without the need of a thimble.

The SAFR2's may be used at both ends of the cable for anchoring equipment.

SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,

SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.28

Page 39: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR2-3/8

Cable Mount

Fastener Mount

The SAFR2-3/8 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit

enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used

for attachment to a steel, concrete, or wood structural member. The 3/8 inch (10 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange

cable and are ideal for 2-way bracing.

The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable

without the need of a thimble.

The SAFR2's may be used at both ends of the cable for anchoring equipment.

SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,

SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.29

Page 40: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR2-1/2

Cable Mount

Fastener Mount

The SAFR2-1/2 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit

enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used

for attachment to a steel, concrete, or wood structural member. The 1/2 inch (13 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange

cable and are ideal for 2-way bracing.

The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable

without the need of a thimble.

The SAFR2's may be used at both ends of the cable for anchoring equipment.

SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,

SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.30

Page 41: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAFR2-5/8

Cable Mount

Fastener Mount

The SAFR2-5/8 is designed for use in attaching Seismic Cable Bracing to cable trays,

HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit

enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used

for attachment to a steel, concrete, or wood structural member. The 5/8 inch (16 mm)

fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors

in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange

cable and are ideal for 2-way bracing.

The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable

without the need of a thimble.

The SAFR2's may be used at both ends of the cable for anchoring equipment.

SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,

SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.31

Page 42: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

LPF SERIES

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Low Pry Fitting

Patent # 62/311,592

©Loos & Co., Inc. - Cableware Division 2.32

Page 43: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Slot

LPF-1/4

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Cable Exit

Inspection Hole

Chamfer

The LPF 1/4 is specifically designed to reduce the prying effect on fasteners. The cable is

nested in the groove provided, and exits through two chamfered slots (to prevent damage to

the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed

in the correct position within the groove.

The LPF has the lowest prying factor yet to be achieved.

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.33

Page 44: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Slot

LPF-3/8

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Cable Exit

Inspection Hole

Chamfer

The LPF 3/8 is specifically designed to reduce the prying effect on fasteners. The cable is

nested in the groove provided, and exits through two chamfered slots (to prevent damage to

the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed

in the correct position within the groove.

The LPF has the lowest prying factor yet to be achieved.

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.34

Page 45: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Slot

LPF-1/2

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Cable Exit

Inspection Hole

Chamfer

The LPF 1/2 is specifically designed to reduce the prying effect on fasteners. The cable is

nested in the groove provided, and exits through two chamfered slots (to prevent damage to

the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed

in the correct position within the groove.

The LPF has the lowest prying factor yet to be achieved.

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.35

Page 46: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Slot

LPF-5/8

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Cable Exit

Inspection Hole

Chamfer

The LPF 5/8 is specifically designed to reduce the prying effect on fasteners. The cable is

nested in the groove provided, and exits through two chamfered slots (to prevent damage to

the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed

in the correct position within the groove.

The LPF has the lowest prying factor yet to be achieved.

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.36

Page 47: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Fastener Mount

Cable Slot

LPF-3/4

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Cable Exit

Inspection Hole

Chamfer

The LPF 3/4 is specifically designed to reduce the prying effect on fasteners. The cable is

nested in the groove provided, and exits through two chamfered slots (to prevent damage to

the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed

in the correct position within the groove.

The LPF has the lowest prying factor yet to be achieved.

NFPA-13 2016

©Loos & Co., Inc. - Cableware Division 2.37

Page 48: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

9P62

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Lateral Bracing

Installation

Instructions

A. Slide Oval Sleeve onto end of cable. Slide sleeve up cable to allow working room.

B. Wrap cable around pipe twice. (TIP - Form simple knot on second wrap holds cable in

place).

C. Slide loose end of cable into sleeve and pull cable to remove slack.

D. Crimp sleeve per Figure 1 below.

E. Repeat in opposite direction.

1 1/2 pipe

dia. min.

1 cable dia.

min. "tag".

Sleeve - See Fig.1

Cable

Figure 1

3.1

Page 49: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

9P62

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Longitudinal Bracing

Installation

Instructions

A. Slide Oval Sleeve onto end of cable. Slide sleeve up cable to allow working room.

B. Wrap cable around pipe twice. (Wrap must be on the far side of a pipe clamp or grooved

coupling).

C. Slide loose end of cable into sleeve and pull cable to remove slack.

D. Crimp sleeve per Figure 1 below.

E. Repeat in opposite direction.

Figure 1

Pipe

1 cable dia. "tag".

Oval Sleeve

Cable

Coupling or Pipe Clamp

<45Á

3.2

Page 50: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

9P62

ESL-1004

ESL-1007

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

4-Way Bracing

Installation

Instructions

A. Slide Oval Sleeve onto end of cable. Slide

sleeve up cable to allow working room.

B. Wrap cable around pipe twice. (Wrap must be

on the far side of a pipe clamp or grooved

coupling).

C. Slide loose end of cable into sleeve and pull

cable to remove slack.

D. Crimp sleeve per Figure 1 below.

E. Repeat in opposite direction.

Figure 1

A. Slide Oval Sleeve onto end of cable. Slide

sleeve up cable to allow working room.

B. Wrap cable around pipe twice. (TIP - Form

simple knot on second wrap holds cable in

place).

C. Slide loose end of cable into sleeve and pull

cable to remove slack.

D. Crimp sleeve per Figure 1 below.

E. Repeat in opposite direction.

A 4-way brace is the combination of a

lateral brace and a longitudinal brace.

Follow the below instructions, starting with

the lateral brace.

Lateral Brace

Longitudinal Brace

<45Á

1 cable dia. min. "tag"

Coupling or Pipe Clamp

Sleeve

3.3

Page 51: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Wood Deck

Wood Deck

SAF Loop

Oval Sleeve

Cable

Cable

Stake Eye

Through Bolt Sizes 1/2, 5/8, 3/4.

(See NFPA-13 Figure 9.3.5.9.1)

Through Bolt Sizes 1/2, 5/8, 3/4.

(See NFPA-13 Figure 9.3.5.9.1)

Pipe

Pipe

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

Through Bolts in Wood

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Wood Deck

LPF

Through Bolt Sizes 1/2, 5/8, 3/4.

(See NFPA-13 Figure 9.3.5.9.1)

Cable

NFPA-13 2016

3.4

Page 52: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

Lag Bolts in Wood

Pipe

Pipe

SAF

Lag Bolt Sizes 3/8, 1/2, 5/8.

Oval Sleeve

Cable

Loop

Wood Deck

(See NFPA-13 Figure 9.3.5.9.1)

Lag Bolt Sizes 3/8, 1/2, 5/8.

(See NFPA-13 Figure 9.3.5.9.1)

Stake Eye

Cable

Wood Deck

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

LPF

Lag Bolt Sizes 3/8, 1/2, 5/8.

(See NFPA-13 Figure 9.3.5.9.1)

Cable

Wood Deck

NFPA-13 2016

3.5

Page 53: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 3000 psi Lightweight Cracked Concrete (207 bar) on Metal Decking

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.6

Page 54: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 3000 psi Nornal Weight Cracked Concrete

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.7

Page 55: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Undercut Anchors in 3000 psi Nornal Weight Cracked Concrete

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.8

Page 56: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 3000 psi Lightweight Cracked Concrete

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.9

Page 57: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 4000 psi Nornal Weight Cracked Concrete

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.10

Page 58: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 6000 psi Nornal Weight Cracked Concrete

Concrete Deck

Cable

SAF Clip

Anchor Sizes 3/8, 1/2, and 5/8

Loop

Cable

Stake Eye

Concrete Deck

Anchor Sizes

1/4, 3/8, 1/2

(See NFPA-13 Figure 9.3.5.12.2(a))

(See NFPA-13 Figure 9.3.5.12.2(a))

Oval Sleeve

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Deck

Anchor Sizes 3/8, 1/2, and 5/8

(See NFPA-13 Figure 9.3.5.12.2(a))

Cable

LPF

NFPA-13 2016

3.11

Page 59: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Loop

Cable

SAF

Stake Eye

Cable

(See NFPA-13 Figure 9.3.5.9.1)

Bolt Sizes 1/4, 3/8, 1/2, 5/8.

Pipe

Pipe

Steel Member

Connections to Steel

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

LPF

Steel Member

Cable

Oval Sleeve

(See NFPA-13 Figure 9.3.5.9.1)

Bolt Sizes 1/4, 3/8, 1/2, 5/8.

NFPA-13 2016

3.12

Page 60: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

1/2 Beam Depth but not <3 in.

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Through Bolts in Wood

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

SAF

Oval Sleeve

Cable

Loop

Wood Beam

Bolt Sizes 1/2, 5/8, 3/4

Wood Beam

Stake Eye

Cable

Bolt Sizes 1/2, 5/8, 3/4

(See NFPA-13 Figure 9.3.5.9.1)

(See NFPA-13 Figure 9.3.5.9.1)

1/2 Beam Depth but not <3 in.

1/2 Beam Depth

but not <3 in.

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

LPF

Wood Beam

Bolt Sizes 1/2, 5/8, 3/4

(See NFPA-13 Figure 9.3.5.9.1)

Bolt Sizes 1/2, 5/8, 3/4

(See NFPA-13 Figure 9.3.5.9.1)

Cable

1/2 Beam Depth but not <3 in.

NFPA-13 2016

3.13

Page 61: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

SAF

Oval Sleeve

Cable

Loop

Wood Beam

Lag Bolt Sizes 3/8, 1/2, 5/8.

Wood Beam

Stake Eye

Cable

Lag Bolt Sizes 3/8, 1/2, 5/8.

(See NFPA-13 Figure 9.3.5.9.1)

(See NFPA-13 Figure 9.3.5.9.1)

1/2 Beam Depth but not <3 in.

Pipe

Pipe

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Lag Bolts in Wood

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

1/2 Beam Depth but not <3 in.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Wood Beam

Lag Bolt Sizes 3/8, 1/2, 5/8.

(See NFPA-13 Figure 9.3.5.9.1)

Cable

LPF

1/2 Beam Depth

but not <3 in.

3.14

Page 62: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

1/2 Beam Depth but not <3 in.

Sleeve

Cable

Loop

Concrete Beam

SAF

Stake Eye

Cable

Concrete Beam

Anchor Sizes 3/8, 1/2,

5/8, 3/4

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

Wedge Anchors in 3000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Concrete Beam

LPF

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

NFPA-13 2016

3.15

Page 63: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Undercut Anchors in 3000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Sleeve

Cable

Loop

Concrete Beam

SAF

Stake Eye

Cable

Concrete Beam

Anchor Sizes 3/8, 1/2,

5/8

Anchor Sizes 3/8, 1/2,

5/8

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

Concrete Beam

LPF

Anchor Sizes 3/8, 1/2,

5/8

(See NFPA-13 Figure 9.3.5.12.2)

Cable

NFPA-13 2016

3.16

Page 64: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 3000 psi Lightweight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Sleeve

Cable

Loop

Concrete Beam

SAF

Stake Eye

Cable

Concrete Beam

Anchor Sizes 3/8, 1/2,

5/8, 3/4

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

Concrete Beam

LPF

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

Cable

NFPA-13 2016

3.17

Page 65: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 4000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Sleeve

Cable

Loop

Concrete Beam

SAF

Stake Eye

Cable

Concrete Beam

Anchor Sizes 3/8, 1/2,

5/8, 3/4

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

Concrete Beam

LPF

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

Cable

NFPA-13 2016

3.18

Page 66: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Wedge Anchors in 6000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Sleeve

Cable

Loop

Concrete Beam

SAF

Stake Eye

Cable

Concrete Beam

Anchor Sizes 3/8, 1/2,

5/8, 3/4

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

Concrete Beam

LPF

Anchor Sizes 3/8, 1/2,

5/8, 3/4

(See NFPA-13 Figure 9.3.5.12.2)

Cable

NFPA-13 2016

3.19

Page 67: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles D(30Á), E(45Á), and F(60Á)

Load Perpendicular to Structural Member

Connections to Steel

Stake Eye

Cable

Steel Beam

Steel Beam

Loop

Oval Sleeve

Cable

Bolt Sizes 1/4, 3/8,

1/2, 5/8.

(See NFPA-13 Figure 9.3.5.12.2)

Bolt Sizes 1/4, 3/8,

1/2, 5/8.

(See NFPA-13 Figure 9.3.5.12.2)

Pipe

Pipe

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Steel Beam

Bolt Sizes 1/4, 3/8,

1/2, 5/8.

SAF

LPF

(See NFPA-13

Figure 9.3.5.12.2)

Cable

Oval Sleeve

3.20

Page 68: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

Through Bolts in Wood

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

Straight Stake Eye

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Wood Beam

Wood Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

LPF

LPF

NFPA-13 2016

3.21

Page 69: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Above listed values based on wood with a specific gravity of 0.35. Values for other woods

can be obtained by multiplying above values by factors listed in figure1.

Lag Bolts in Wood

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

Straight Stake Eye

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Wood Beam

Wood Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

NFPA-13 2016

3.22

Page 70: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Wedge Anchors in 3000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

SAF

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Concrete Beam

Concrete Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

NFPA-13 2016

3.23

Page 71: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Undercut Anchors in 3000 psi Normal Weight Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

SAF

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Concrete Beam

Concrete Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

3.24

Page 72: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Wedge Anchors in 3000 psi Lightweight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

SAF

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Concrete Beam

Concrete Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

3.25

Page 73: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Wedge Anchors in 4000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

SAF

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Concrete Beam

Concrete Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

3.26

Page 74: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Wedge Anchors in 6000 psi Normal Weight Cracked Concrete

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

NFPA-13 2016

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

SAF

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Concrete Beam

Concrete Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

LPF

LPF

3.27

Page 75: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles G(30Á), H(45Á), and I(60Á)

Load Parallel to Structural Member

Pipe

Pipe

Fastener

Straight Stake Eye

Cable

Fastener

Straight Stake Eye

Cable

Oval Sleeve

Oval Sleeve

(See NFPA-13 Figure 9.3.5.12.2)

(See NFPA-13 Figure 9.3.5.12.2)

Steel Beam

Steel Beam

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Min. four fastener diameters

but not <1/3 beam depth and

not <3 in. for wood beams.

Connections to Steel

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

LPF

LPF

NFPA-13 2016

3.28

Page 76: SEISMIC DESIGN GUIDE - Seismic Controlseismiccontrol.com/wp-content/uploads/2016/07/DesignManual2016.pdf · SEISMIC DESIGN GUIDE FOR FIRE ... In this publication you will find information

Angles A(30Á), B(45Á), and C(60Á)

Load Perpendicular to Structural Member

Cable Looped Around Top Member of Bar Joist

901 Industrial Blvd.

Naples, FL 34104

800-321-5667

www.loosseismicbracing.com

MAX

45Á

Loop

around top

chord of bar

joist at a

panel point

Brace

Angle

Pipe

NFPA-13 2016

Oval Sleeve

Cable

3.29