SEISMIC DESIGN GUIDE FOR FIRE SPRINKLER COMPONENTS EDITION 2.0 FOR NFPA-13 2016 COLOR CODED – PRE-STRETCHED – BREAK STRENGTH CERTIFIED
SEISMIC DESIGN GUIDE
FOR FIRE SPRINKLER COMPONENTS
EDITION 2.0 FOR NFPA-13 2016
COLOR CODED – PRE-STRETCHED – BREAK STRENGTH CERTIFIED
PREFACE
Whether it’s drawn stainless steel wire, miniature or aircraft cable, wire rope, Seismic Wire Rope
assemblies, fittings or tools, Loos & Co. Inc. can deliver. We have developed, over the last fifty eight
years, the technical capabilities essential in providing such materials to such varied industries as
aerospace, data processing, automotive, aircraft and farm equipment. Special products have been
designed and made for ocean research, mineral exploration and military markets as well as many other
scientific and industrial applications. Technical competence, combined with modern production
equipment and rigid quality control guarantee on time delivery of our wire, cable and cable related
products, made to the most exacting specifications.
Loos & Co. has earned its reputation by continuously meeting and exceeding the increasingly stringent
safety requirements of the aerospace industry. We have taken that level of safety, combined with 50+
years of knowledge and expertise and applied this methodology to our Seismic Bracing Cable system.
Loos & Co. has been providing Seismic Bracing cable and hardware since 1993. What we have seen over
the past 23 years is an evolution from what was once confusion and misconception to an industry that
has gone above and beyond to embrace nationally accepted codes and standards. Loos & Co. has taken
this position to the next level, by incorporating most, if not all of the certifications required to make our
Seismic Bracing Cable the most cost effective, most certified and accepted bracing system on the
market.
Loos & Co. certifications include:
* Third party listed (UL & ICC ES) for use in complying with NFPA 13 for fire sprinkler systems.
* Third party listed (ICC ES) for use in complying with the International Building Code (IBC)
* Are third party tested/listed to verify that cable assemblies, including fittings, maintain the
nominal breaking strength per ASCE 19, as required by IBC, ASCE 7 & NFPA 13
*Have swaged end fittings as required by the 2012 IBC per ASCE 19-10, which does not permit
wedge or clip type fittings.
*Certify the minimum breaking strength of the sway bracing assemblies.
*Comply with NFA 13, ASCE 19, the IBC and ASCE 7.
*Are listed by the FBC for system compatibility with CPVC pipe.
In this guide, you will find all of the specifications, descriptions and applicable drawings for all of the
Seismic products Loos & Co. offers. This will allow the user to identify and specify the proper
components to satisfy the code requirements of the local authority having jurisdiction (AHJ).
Thank you for your interest in our Seismic Cable Bracing System manufactured by Loos & Co. Inc.
© Loos & Co., Inc. - Cableware Division 1.2
APPLICATION OF THIS PUBLICATION
In this publication you will find information regarding proper installation techniques and guidelines
applicable to Loos & Co. Seismic Cable Bracing System for meeting existing codes and standards. It has
been compiled using proven engineering ethics and principles developed over the past 23 years. Final
accountability for approving specific designs, code interpretations and/or installations rests with the
engineer responsible for the specific design and/or the agency or authority having jurisdiction (AHJ).
Loos & Co. Inc. and/or contributors to this publication assume no liability for the specific installation of
its products or the design, application, approval or interpretation of the requirements or guidelines
contained in this publication. Users of this publication are encouraged to confer with certified design
Engineers (P.E.) as well as all applicable Federal, State and local a regulations or requirements for
specific installations.
REPRINT PERMISSION RESTRICTIONS
Permission is granted to government and private sector users of this publication to reproduce unaltered
conceptual drawings from this publication for their use relating to the specific design, specification,
installation or approval of Loos & Co. Seismic Cable Bracing. Reproduction for the purpose of its sale is
prohibited. Any other use or reproduction of this publication shall be first approved in writing by Loos &
Co. Inc. Liability for the specific application of such information, including errors or omissions in
reproduction is solely the responsibility of the party reproducing such material.
GENERAL INTRODUCTION
Loos & Co. Seismic Design Guide will assist you in the design and installation of our Seismic Cable
Bracing System. All of the materials and products presented have been designed and tested to exceed
the requirements set forth in NFPA 13. In Fact, the provisions of NFPA 13 directly provide for the use of
Loos & Co. UL Listed Seismic Cable Bracing.
Loos & Co. has been providing our Seismic Cable Bracing since 1993 in structures located all over the
world, both for new and retro-fit buildings.
This Design Guide can be used in conjunction with our New Seismic Design Calculator. (Downloadable
for free on our Website www.loosseismicbracing.com) Our Seismic Design Calculator will allow the user
to enter all the details for fire sprinkler installations from the building blueprints then print out of the
completed NFPA 13 form with all of the calculation preapproved, ready to submit to your local AHJ. As
an added bonus, our Seismic Design Calculator software will also generate a Bill of material and all
applicable drawings.
© Loos & Co., Inc. - Cableware Division 1.3
Locoloc® #0-3-SBHS Handswager
Preferred tool for Swaging Gold cable #G03-CBL
A well-made, economical handswaging tool for swaging #GO3 cable sleeves, our most popular cable size. Loos
offers the correct tools to use in swaging our zinc-plated oval sleeves. Using the correct tool and following
proper swaging instructions will ensure proper cable connections that actually exceed the breaking strength of
the cable.
Length: 12"
Use: For size #GO3 (GOLD) cable only.
OPERATION INSTRUCTIONS:
To open tool squeeze handles hard or push release lever (Figure 1) forward while squeezing handles to relieve
tension.
Figure 1 Figure 2 Figure 3
1. Place the sleeve on the cable and make a loop around the item to which you are securing the cable.
2. Next, insert cable end through the sleeve and at least 1/8" or more beyond (Figure 3).
3. While holding sleeve in place, swage one compression. Move over and swage (second compression). Two
compressions are required. The tool won't release until compression is complete. (Figure 2)
4. Check sleeve for proper after swage diameter with gauge provided (Figure
7). The clamping action of the ratchet allows the sleeve to be held by the
tool before completing the swage. This allows for the user to adjust the
position of the sleeve on the cable.
5. After swaging, excess cable may be trimmed off with our FELCO C7 cutters
below.
Figure 7
© Loos & Co., Inc. - Cableware Division 1.4
Locoloc® #3-346-SB Handswager
Used for #GO3-CBL, #OR4-CBL, #GR6-CBL
A well-made, economical handswaging tool for swaging cable sleeves. Loos offers the correct tools to use in swaging our
zinc-plated oval sleeves. Using the correct tool and following proper swaging instructions included with each tool will
ensure proper cable connections that actually exceed the breaking strength of the cable.
Length: 26"
Use: Two-handed tool for size #GO3 (GOLD), #OR4 (ORANGE) and
#GR6 (GREEN) cables.
Each Loos & Co. #3-346SB swaging tool is designed to work with #3, #4, and #6 Zinc-Plated Copper Oval Sleeves. For use
only on Loos & Co. Seismic Cable Bracing sizes #GO3, #OR4, and #GR6. You will not obtain proper performance or meet
UL standards if you do not use the proper Loos & Co. swaging tool and sleeve combination.
Place sleeve to be compressed in proper size groove in swaging tool by matching cable color to colored dot next to
groove in tool. A length of cable equal to the cable diameter should extend beyond the length of sleeve to achieve
maximum holding. (See arrow in Figure 4). Finished sleeve should look like this. Be sure sleeves have been compressed
the proper number of times. See below for proper # of compressions.
Keep jaws of swaging tool at right angles to the sleeve to be compressed, making sure the sleeve is aligned in the jaw
grooves. Close tool completely. Tool handles should snap shut indicating complete closure. After swaging, excess cable
may be trimmed off with our FELCO C7 Cable cutters.
Figure 5
Use the swaging gauge provided with the tool to check proper after swage diameter of sleeve. Compressed sleeve
should slide freely into corresponding size and color slot in gauge. (Figure 5)
Cable Size Zinc-Plated Copper
Oval Sleeve
#GO3 (Gold) 2
#OR4 (Orange) 2
#GR6 (Green) 3 Figure 4
© Loos & Co., Inc. - Cableware Division 1.5
Locoloc® HC-3010-SB Battery Handswager
A well-made and powerful, state-of-the-art battery-powered swaging tool. This newest technology eliminates
the need to swage Loos zinc-plated oval sleeves by hand. This is especially helpful when a large number of
brace connections are required for the job. Kit comes with complete with two long-lasting, fast charge lithium-
ion batteries, I hour quick charger and handy carrying case so you can be sure to have strong portable power
at all times.
Use: For size #GO3 (GOLD), #OR4 (ORANGE) and #GR6
(GREEN) cable sleeves.
Length: 22" Height: 4" Weight: 13 lbs.
OPERATING INSTRUCTIONS
Place the cable sleeve to be crimped in the appropriate cavity. Press on the Grey forward trigger to crimp the sleeve
onto the cable. An audible click advises when the swage (crimp) is completed. Open the jaws of the tool by pressing the
Black retract trigger, you may now crimp another sleeve or you may start another crimp cycle of the tool.
Number of Compressions
Cable size Zinc-plated Copper oval sleeves
#GO3 (GOLD) 2
#OR4 (ORANGE) 2
#GR6 (GREEN) 3
Figure 1 Figure 2 Figure 3
Finished sleeve should look like (Figure 2) on Gold cable. Be sure sleeves have been compressed the proper number of
times. (See Number of Compressions Figure 1). Using the swaging gauge provided with the tool to check proper “after
swage” diameter of sleeve. Compressed sleeve should slide into size slot in gauge: GO (Gold), OR (Orange) and GR
(Green). Sleeves elongate after compression. To assure maximum holding allow the end of the cable to extend beyond
the sleeve after it is compressed. Select the proper cavity size for the sleeve to be swaged. Use only #GO3 sleeves with
#GO3 cavity, #OR4 sleeve with #OR4 cavity and so on. For lap splices at least two oval sleeves should be used.
© Loos & Co., Inc. - Cableware Division 1.6
FELCO C7 CABLE CUTTER
Loos & Co. offers the complete line of Swiss-made FELCO Brand Cable Cutters. FELCO cutters are recognized around
the world for their precision manufacture and cutting capabilities.
Lightweight enough for overhead cutting yet strong enough for
underwater work.
Plastic-coated handles afford a firm, comfortable grip. A cable
when crushed or deformed in cutting is difficult to use with fittings.
These cable cutters, with unique triangular jaws, never leave a
frayed end.
Capacity: 5/32" on stainless steel diameter and smaller. For use on #GO3-CBL (GOLD) and #OR4-CBL (ORANGE) cable.
Length: 7.5" / 190 mm
Weight: 9.5 oz. / 270g
FELCO C9 CABLE CUTTER
FELCO cutters are recognized around the world for their precision manufacture and cutting capabilities. Lightweight
enough for overhead cutting yet strong enough for underwater work.
Plastic-coated handles afford a firm, comfortable grip. Replacement parts are available from stock. All cutters tested
before leaving the factory. Fills the gap between C7 and C12 - cuts
1/4" steel cable. Ideal for the tool kit. All cutters available from
stock.
Capacity: Cuts 1/4" steel cable. For use on #GR6-CBL (GREEN) and
#BL8-CBL (BLACK) cable.
Length: 13" / 325mm
Weight: 1.5 lbs. / 750g
High-Strength Blades
Hardened and tempered blades for cutting the strongest of cables.
Triangular Cutting Action
FELCO's innovative triangular cut allows you to progressively cut cable wires and at the same time avoid squashing of
strands. Thanks to this feature, it is generally not necessary to tie the cable before the cut.
Forged Aluminum Handles
Lightweight, strong and sturdy thanks to special aluminum alloys and advanced precision forging methods.
© Loos & Co., Inc. - Cableware Division 1.7
Description of Standard Cable Brace Kit Part Numbers
Detailed Cable Kit Part Numbers1. Choose your brace type:
Brace Type Description To Fit Cable Fastener Code2 Two-Way All All4 Four-Way All 00, 2B, 3B, 4B, 5B
2: Choose the cable that best fits your load requirement:Cable Code Description Fastener Code
GO3 Gold, 600 lb. Load Rating 00, 2S, 2B, 3S, 3B
OR4 Orange, 1100 lb. Load Rating 00, 2S, 2B, 3S, 3B, 4S, 4B
GR6 Green, 2667 lb. Load Rating 00, 3S, 3B, 4S, 4BBL8 Black, 4400 lb. Load Rating 00, 5S, 5B
3. Choose the fastener that best fits your requirement:Fastener Code Description To Fit Cable
00 No Stake Eye, Loop GO, OR, GR, BL2S 1/4” Straight Stake Eye GO, OR2B 1/4” 45° Stake Eye GO, OR3S 3/8” Straight Stake Eye GO, OR, GR3B 3/8” 45° Stake Eye GO, OR, GR4S 1/2” Straight Stake Eye OR, GR4B 1/2” 45° Stake Eye OR, GR5S 5/8” Straight Stake Eye BL
5B 5/8” 45° Stake Eye BL
4. Choose desired brace length:Length Code Description To Fit Cable
01 1 foot (+4 ft. extra) All04 4 feet (+4 ft. extra) All07 7 feet (+4 ft. extra) All10 10 feet (+4 ft. extra) All13 13 feet (+4 ft. extra) All
© Loos & Co., Inc. - Cableware Division 1.8
Index
SECTION 1 – GENERAL INFORMATION
1.2 Preface
1.3 Application
1.3 Reprint Permission Restrictions
1.3 General Introduction
1.4 – 1.7 Hand Tool Information
1.8 Description of Cable Kit Part Numbers
SECTION 2 – PRODUCTS
2.1 – 2.4 Seismic Bracing Cable
2.5 Zinc-Plated Oval Sleeves
2.6 – 2.14 Seismic Attachment Fitting (SAF) Series
2.15 – 2.19 Seismic Attachment Fitting Retrofit (SAFR) Series
2.20 – 2.26 Seismic Attachment Fitting 2 (SAF2) Series
2.27 – 2.33 Seismic Attachment Fitting Retrofit 2 (SAFR2) Series
2.34 – 2.39 Low-Pry Fitting (LPF) Series
SECTION 3 – INSTRUCTIONS
3.1 Lateral Bracing Installation
3.2 Longitudinal Bracing Installation
3.3 4-Way Bracing Installation
3.4 Through Bolts in Wood – Angles A, B, and C
3.5 Lag Bolts in Wood – Angles A, B, and C
3.6 Wedge Anchors in 3000 psi Lightweight Concrete Filled Metal Decking –
Angles A, B, and C
3.7 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –
Angles A, B, and C
3.8 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles A, B, and C
3.9 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles A, B, and C
© Loos & Co., Inc. - Cableware Division 1.9
3.10 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –
Angles A, B, and C
3.11 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –
Angles A, B, and C
3.12 Connections to Steel – Angles A, B, and C
3.13 Through Bolts in Wood – Angles D, E, and F
3.14 Lag Bolts in Wood – Angles D, E, and F
3.15 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –
Angles D, E, and F
3.16 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles D, E, and F
3.17 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles D, E, and F
3.18 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –
Angles D, E, and F
3.19 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –
Angles D, E, and F
3.20 Connections to Steel – Angles D, E, and F
3.21 Through Bolts in Wood – Angles G, H, and I
3.22 Lag Bolts in Wood – Angles G, H, and I
3.23 Wedge Anchors in 3000 psi Normal Weight Cracked Concrete –
Angles G, H, and I
3.24 Undercut Anchors in 3000 psi Normal Weight Concrete – Angles G, H, and I
3.25 Wedge Anchors in 3000 psi Lightweight Cracked Concrete – Angles G, H, and I
3.26 Wedge Anchors in 4000 psi Normal Weight Cracked Concrete –
Angles G, H, and I
3.27 Wedge Anchors in 6000 psi Normal Weight Cracked Concrete –
Angles G, H, and I
3.28 Connections to Steel – Angles G, H, and I
3.29 Cable Looped Around Top Member of Bar Joist – Angles A, B, and C
© Loos & Co., Inc. - Cableware Division 1.10
901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com
specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster
ESL-1004 & 1007
Seismic Cable BracingBulk Spool - Size #3 (Gold)
Certified Minimum Break Strength (lbs)
Allowable Load at 90° (lbs)
Allowable Load at 30°-
44° (lbs)
Allowable Load at 45°-
59°(lbs)
Allowable Load at 60°-
89° (lbs)
Min. Cable Diameter (in.)
Max. Cable Diameter (in.)
920 600 300 424 519 0.09375 0.10575
Number of Wires
Nom. Dia. of Wires (in.)
Min. Stress at 0.7% Extension
Under Load
Min. Ultimate Tensile Strength
49 .010 to .013 150,000 PSI 300,000 PSI
Applied Load (lbs) Applied Load (% of Min. Break Strength)
% Elongation at Applied Load Modulus of Elasticity
92 10% 0.15% 12.7 x 106
184 20% 0.28% 14.6 x 106
276 30% 0.40% 15.8 x 106
368 40% 0.48% 17.7 x 106
460 50% 0.59% 18.5 x 106
552 60% 0.74% 17.3 x 106
613 66.67%* 0.84% 17.1 x 106
*66.67% is equal to the allowable working load (break strength ÷ 1.5)
©Loos & Co., Inc. - Cableware Division 2.1
901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com
specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster
ESL-1004 & 1007
Seismic Cable BracingBulk Spool - Size #4 (Orange)
Number of Wires
Nom. Dia. of Wires (in.)
Min. Stress at 0.7% Extension
Under Load
Min. Ultimate Tensile Strength
49 .014 to .015 150,000 PSI 300,000 PSI
Applied Load (lbs) Applied Load (% of Min. Break Strength)
% Elongation at Applied Load Modulus of Elasticity
170 10% 0.17% 11.0 x 106
340 20% 0.30% 13.4 x 106
510 30% 0.42% 14.7 x 106
680 40% 0.52% 16.8 x 106
850 50% 0.64% 17.1 x 106
1020 60% 0.75% 17.0 x 106
1133 66.67%* 0.84% 17.5 x 106
*66.67% is equal to the allowable working load (break strength ÷ 1.5)
Certified Minimum Break Strength (lbs)
Allowable Load at 90° (lbs)
Allowable Load at 30°-
44° (lbs)
Allowable Load at 45°-
59°(lbs)
Allowable Load at 60°-
89° (lbs)
Min. Cable Diameter (in.)
Max. Cable Diameter (in.)
1,700 1,100 550 778 952 .125 .139
©Loos & Co., Inc. - Cableware Division 2.2
901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com
specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster
ESL-1004 & 1007
Seismic Cable BracingBulk Spool - Size #6 (Green)
Number of Wires
Nom. Dia. of Wires (in.)
Min. Stress at 0.7% Extension
Under Load
Min. Ultimate Tensile Strength
133 .0125 to .016 150,000 PSI 300,000 PSI
Applied Load (lbs) Applied Load (% of Min. Break Strength)
% Elongation at Applied Load Modulus of Elasticity
420 10% 0.17% 12.8 x 106
840 20% 0.31% 14.6 x 106
1,260 30% 0.44% 15.8 x 106
1,680 40% 0.56% 17.1 x 106
2,100 50% 0.69% 17.4 x 106
2,520 60% 0.82% 17.4 x 106
2,800 66.67%* 0.93% 17.3 x 106
*66.67% is equal to the allowable working load (break strength ÷ 1.5)
Certified Minimum Break Strength (lbs)
Allowable Load at 90° (lbs)
Allowable Load at 30°-
44° (lbs)
Allowable Load at 45°-
59°(lbs)
Allowable Load at 60°-
89° (lbs)
Min. Cable Diameter (in.)
Max. Cable Diameter (in.)
4,200 2,100 1,050 1,485 1,818 .1875 .2055
©Loos & Co., Inc. - Cableware Division 2.3
901 IndustrIal Boulevard | naples, FlorIda | 34101 usat e l e p h o n e : (800) 643-5667 | F a x : (239) 434-5739emaIl: [email protected] | WeB: WWW.loosnaples.com
specIalIsts In WIre rope hardWare and tools | see our catalog In the thomas regIster
ESL-1004 & 1007
Seismic Cable BracingBulk Spool - Size #8 (Black)
Number of Wires
Nom. Dia. of Wires (in.)
Min. Stress at 0.7% Extension
Under Load
Min. Ultimate Tensile Strength
133 .016 to .020 145,000 PSI 290,000 PSI
Applied Load (lbs) Applied Load (% of Min. Break Strength)
% Elongation at Applied Load Modulus of Elasticity
700 10% 0.20% 12.6 x 106
1,400 20% 0.34% 14.6 x 106
2,100 30% 0.47% 15.9 x 106
2,800 40% 0.60% 16.3 x 106
3,500 50% 0.72% 17.2 x 106
4,200 60% 0.85% 17.5 x 106
4,667 66.67%* 0.94% 17.7 x 106
*66.67% is equal to the allowable working load (break strength ÷ 1.5)
Certified Minimum Break Strength (lbs)
Allowable Load at 90° (lbs)
Allowable Load at 30°-
44° (lbs)
Allowable Load at 45°-
59°(lbs)
Allowable Load at 60°-
89° (lbs)
Min. Cable Diameter (in.)
Max. Cable Diameter (in.)
7,000 4,600 2,300 3,253 3,983 .250 .268
©Loos & Co., Inc. - Cableware Division 2.4
9P62
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
All Zinc Plated Oval Sleeves supplied by Loos & Co. Inc. are in full compliance with the
requirements of Military Specification MS51844, and are certified to maintain the break
strength of the cable to which they are applied (for 3 x 7, 7 x7, 7 x 19, and 6 x 19
construction).
©Loos & Co., Inc. - Cableware Division 2.5
SAF SERIES
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
(Structural Attachment Fitting)
Patent # 62/239,394
©Loos & Co., Inc. - Cableware Division 2.6
Fastener Mount
Cable Mount
The SAF-1/4 is designed for use in attaching Seismic Cable Bracing to steel structural
members. The limitations of use are governed by the fastener diameter as a 1/4 inch (6 mm)
fastener is only listed for use with steel as per NFPA-13. Will accept both metric and
SAF-1/4
imperial fasteners. The cable mount will accept Gold, Orange, and Green cables.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.7
SAF-3/8
Cable Mount
Fastener Mount
The SAF-3/8 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The 3/8 inch (10 mm.) will accept lag bolts,
bolts, and concrete anchors in both metric and imperial sizes. The cable mount will
accept Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.8
SAF-1/2
Cable Mount
Fastener Mount
The SAF-1/2 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The 1/2 inch (13 mm) will accept lag bolts, bolts,
and concrete anchors in both metric and imperial sizes. The cable mount will accept
Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.9
SAF-5/8
Cable Mount
Fastener Mount
The SAF-5/8 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The 5/8 inch (16 mm) will accept lag bolts, bolts,
and concrete anchors in both metric and imperial sizes. The cable mount will accept
Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.10
SAF-3/4
Cable Mount
Fastener Mount
The SAF-3/4 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The 3/4 inch (20 mm) will accept lag bolts, bolts,
and concrete anchors in both metric and imperial sizes. The cable mount will accept
Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.11
SAF-7/8
Cable Mount
Fastener Mount
The SAF-7/8 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The 7/8 inch (22 mm) will accept lag bolts, bolts,
and concrete anchors in both metric and imperial sizes. The cable mount will accept
Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.12
SAF-1
Cable Mount
Fastener Mount
The SAF1 is designed for use in attaching Seismic Cable Bracing to a steel, concrete,
or wood structural member. The1 inch (24 mm) will accept lag bolts, bolts, and
concrete anchors in both metric and imperial sizes. The cable mount will accept Gold,
Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.13
SAF-11/4
Cable Mount
Fastener Mount
The SAF1 1/4 is designed for use in attaching Seismic Cable Bracing to a steel,
concrete, or wood structural member. The11/4 inch (32 mm) will accept lag bolts,
bolts, and concrete anchors in both metric and imperial sizes. The cable mount will
accept Gold, Orange, and Green cable.
9P62
ESL-1004
ESL-1007
The SAF maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF may be used at both ends of the cable for anchoring equipment.
SAF's are offered in eight different mounting sizes,SAF-1/4, SAF-3/8, SAF-1/2, SAF-5/8,
SAF-3/4, SAF-7/8, SAF-1, and SAF 1 1/4.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.14
SAFR SERIES
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Structural Attachment Fitting, Retrofit
Patent # 62/239,394
©Loos & Co., Inc. - Cableware Division 2.15
SAFR-1/4
Cable Mount
Fastener Mount
The SAFR-1/4 is designed as a retrofit Seismic Anchoring Fitting for use with
pre-existing equipment and systems that require seismic bracing. The fitting is slotted
to allow an existing fastener to be loosened, and the SAFR positioned without removal
of the fastener.
The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable
without the need of a thimble.
The SAFR may be used at both ends of the cable for anchoring equipment.
SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,
SAFR-1/2, and SAFR-5/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
ESL-1004
ESL-1007
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.16
SAFR-3/8
Cable Mount
Fastener Mount
The SAFR-3/8 is designed as a retrofit Seismic Anchoring Fitting for use with
pre-existing equipment and systems that require seismic bracing. The fitting is slotted
to allow an existing fastener to be loosened, and the SAFR positioned without removal
of the fastener.
The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable
without the need of a thimble.
The SAFR may be used at both ends of the cable for anchoring equipment.
SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,
SAFR-1/2, and SAFR-5/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
ESL-1004
ESL-1007
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.17
SAFR-1/2
Cable Mount
Fastener Mount
The SAFR-1/2 is designed as a retrofit Seismic Anchoring Fitting for use with
pre-existing equipment and systems that require seismic bracing. The fitting is slotted
to allow an existing fastener to be loosened, and the SAFR positioned without removal
of the fastener.
The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable
without the need of a thimble.
The SAFR may be used at both ends of the cable for anchoring equipment.
SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,
SAFR-1/2, and SAFR-5/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
ESL-1004
ESL-1007
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.18
SAFR-5/8
Cable Mount
Fastener Mount
The SAFR-5/8 is designed as a retrofit Seismic Anchoring Fitting for use with
pre-existing equipment and systems that require seismic bracing. The fitting is slotted
to allow an existing fastener to be loosened, and the SAFR positioned without removal
of the fastener.
The SAFR maintains the rated breaking strength of size 3 (Gold) and 4 (Orange) cable
without the need of a thimble.
The SAFR may be used at both ends of the cable for anchoring equipment.
SAFR's are offered in four different fastener mounting sizes,SAFR-1/4, SAFR-3/8,
SAFR-1/2, and SAFR-5/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
ESL-1004
ESL-1007
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.19
SAF2 SERIES
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Structural Attachment Fitting, 2 Way
Patent #62/239,394
©Loos & Co., Inc. - Cableware Division 2.20
SAF2-1/4
Cable Mount
Fastener Mount
The SAF2-1/4 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 1/4 inch (6 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.21
SAF2-3/8
Cable Mount
Fastener Mount
The SAF2-3/8 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 3/8 inch (10 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.22
SAF2-1/2
Cable Mount
Fastener Mount
The SAF2-1/2 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 1/2 inch (13 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.23
SAF2-5/8
Cable Mount
Fastener Mount
The SAF2-5/8 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 5/8 inch (16 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.24
SAF2-3/4
Cable Mount
Fastener Mount
The SAF2-3/4 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 3/4 inch (20 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.25
SAF2-7/8
Cable Mount
Fastener Mount
The SAF2-7/8 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports for
attachment to a steel, concrete, or wood structural member. The 7/8 inch (22 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, Orange, and
Green cable and are ideal for 2-way bracing.
The SAF2 maintain the rated break strength of size 3 (Gold), 4 (Orange), and 6 (Green)
cable without the need of a thimble.
The SAF2 may be used at both ends of the cable for anchoring equipment.
SAF2's are offered in six different mounting sizes,SAF2-1/4, SAF2-3/8, SAF2-1/2,
SAF2-5/8, SAF2-3/4, and SAF2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.26
SAFR2 SERIES
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Structural Attachment Fitting, 2 Way, Retrofit
Patent # 62/239,394
©Loos & Co., Inc. - Cableware Division 2.27
SAFR2-1/4
Cable Mount
Fastener Mount
The SAFR2-1/4 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit
enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used
for attachment to a steel, concrete, or wood structural member. The 1/4 inch (6 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange
cable and are ideal for 2-way bracing.
The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable
without the need of a thimble.
The SAFR2's may be used at both ends of the cable for anchoring equipment.
SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,
SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.28
SAFR2-3/8
Cable Mount
Fastener Mount
The SAFR2-3/8 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit
enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used
for attachment to a steel, concrete, or wood structural member. The 3/8 inch (10 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange
cable and are ideal for 2-way bracing.
The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable
without the need of a thimble.
The SAFR2's may be used at both ends of the cable for anchoring equipment.
SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,
SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.29
SAFR2-1/2
Cable Mount
Fastener Mount
The SAFR2-1/2 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit
enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used
for attachment to a steel, concrete, or wood structural member. The 1/2 inch (13 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange
cable and are ideal for 2-way bracing.
The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable
without the need of a thimble.
The SAFR2's may be used at both ends of the cable for anchoring equipment.
SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,
SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.30
SAFR2-5/8
Cable Mount
Fastener Mount
The SAFR2-5/8 is designed for use in attaching Seismic Cable Bracing to cable trays,
HVAC equipment, clevis hangers, sprinkler systems and trapeze supports in a retrofit
enviroment. Existing fastener only needs to be loosened to install the SAFR2. Used
for attachment to a steel, concrete, or wood structural member. The 5/8 inch (16 mm)
fastener mounting hole will accept lag bolts, bolts, threaded rod and concrete anchors
in both metric and imperial sizes. The two cable mounts will accept Gold, and Orange
cable and are ideal for 2-way bracing.
The SAFR2's maintain the rated break strength of size 3 (Gold), and 4 (Orange) cable
without the need of a thimble.
The SAFR2's may be used at both ends of the cable for anchoring equipment.
SAFR2's are offered in six different mounting sizes,SAFR2-1/4, SAFR2-3/8, SAFR2-1/2,
SAFR2-5/8, SAFR2-3/4, and SAFR2-7/8.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.31
LPF SERIES
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Low Pry Fitting
Patent # 62/311,592
©Loos & Co., Inc. - Cableware Division 2.32
Fastener Mount
Cable Slot
LPF-1/4
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Cable Exit
Inspection Hole
Chamfer
The LPF 1/4 is specifically designed to reduce the prying effect on fasteners. The cable is
nested in the groove provided, and exits through two chamfered slots (to prevent damage to
the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed
in the correct position within the groove.
The LPF has the lowest prying factor yet to be achieved.
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.33
Fastener Mount
Cable Slot
LPF-3/8
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Cable Exit
Inspection Hole
Chamfer
The LPF 3/8 is specifically designed to reduce the prying effect on fasteners. The cable is
nested in the groove provided, and exits through two chamfered slots (to prevent damage to
the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed
in the correct position within the groove.
The LPF has the lowest prying factor yet to be achieved.
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.34
Fastener Mount
Cable Slot
LPF-1/2
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Cable Exit
Inspection Hole
Chamfer
The LPF 1/2 is specifically designed to reduce the prying effect on fasteners. The cable is
nested in the groove provided, and exits through two chamfered slots (to prevent damage to
the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed
in the correct position within the groove.
The LPF has the lowest prying factor yet to be achieved.
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.35
Fastener Mount
Cable Slot
LPF-5/8
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Cable Exit
Inspection Hole
Chamfer
The LPF 5/8 is specifically designed to reduce the prying effect on fasteners. The cable is
nested in the groove provided, and exits through two chamfered slots (to prevent damage to
the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed
in the correct position within the groove.
The LPF has the lowest prying factor yet to be achieved.
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.36
Fastener Mount
Cable Slot
LPF-3/4
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Cable Exit
Inspection Hole
Chamfer
The LPF 3/4 is specifically designed to reduce the prying effect on fasteners. The cable is
nested in the groove provided, and exits through two chamfered slots (to prevent damage to
the outer fibers of the cable). An inspection hole is provided to insure that the cable is placed
in the correct position within the groove.
The LPF has the lowest prying factor yet to be achieved.
NFPA-13 2016
©Loos & Co., Inc. - Cableware Division 2.37
9P62
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Lateral Bracing
Installation
Instructions
A. Slide Oval Sleeve onto end of cable. Slide sleeve up cable to allow working room.
B. Wrap cable around pipe twice. (TIP - Form simple knot on second wrap holds cable in
place).
C. Slide loose end of cable into sleeve and pull cable to remove slack.
D. Crimp sleeve per Figure 1 below.
E. Repeat in opposite direction.
1 1/2 pipe
dia. min.
1 cable dia.
min. "tag".
Sleeve - See Fig.1
Cable
Figure 1
3.1
9P62
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Longitudinal Bracing
Installation
Instructions
A. Slide Oval Sleeve onto end of cable. Slide sleeve up cable to allow working room.
B. Wrap cable around pipe twice. (Wrap must be on the far side of a pipe clamp or grooved
coupling).
C. Slide loose end of cable into sleeve and pull cable to remove slack.
D. Crimp sleeve per Figure 1 below.
E. Repeat in opposite direction.
Figure 1
Pipe
1 cable dia. "tag".
Oval Sleeve
Cable
Coupling or Pipe Clamp
<45Á
3.2
9P62
ESL-1004
ESL-1007
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
4-Way Bracing
Installation
Instructions
A. Slide Oval Sleeve onto end of cable. Slide
sleeve up cable to allow working room.
B. Wrap cable around pipe twice. (Wrap must be
on the far side of a pipe clamp or grooved
coupling).
C. Slide loose end of cable into sleeve and pull
cable to remove slack.
D. Crimp sleeve per Figure 1 below.
E. Repeat in opposite direction.
Figure 1
A. Slide Oval Sleeve onto end of cable. Slide
sleeve up cable to allow working room.
B. Wrap cable around pipe twice. (TIP - Form
simple knot on second wrap holds cable in
place).
C. Slide loose end of cable into sleeve and pull
cable to remove slack.
D. Crimp sleeve per Figure 1 below.
E. Repeat in opposite direction.
A 4-way brace is the combination of a
lateral brace and a longitudinal brace.
Follow the below instructions, starting with
the lateral brace.
Lateral Brace
Longitudinal Brace
<45Á
1 cable dia. min. "tag"
Coupling or Pipe Clamp
Sleeve
3.3
Wood Deck
Wood Deck
SAF Loop
Oval Sleeve
Cable
Cable
Stake Eye
Through Bolt Sizes 1/2, 5/8, 3/4.
(See NFPA-13 Figure 9.3.5.9.1)
Through Bolt Sizes 1/2, 5/8, 3/4.
(See NFPA-13 Figure 9.3.5.9.1)
Pipe
Pipe
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
Through Bolts in Wood
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Wood Deck
LPF
Through Bolt Sizes 1/2, 5/8, 3/4.
(See NFPA-13 Figure 9.3.5.9.1)
Cable
NFPA-13 2016
3.4
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
Lag Bolts in Wood
Pipe
Pipe
SAF
Lag Bolt Sizes 3/8, 1/2, 5/8.
Oval Sleeve
Cable
Loop
Wood Deck
(See NFPA-13 Figure 9.3.5.9.1)
Lag Bolt Sizes 3/8, 1/2, 5/8.
(See NFPA-13 Figure 9.3.5.9.1)
Stake Eye
Cable
Wood Deck
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
LPF
Lag Bolt Sizes 3/8, 1/2, 5/8.
(See NFPA-13 Figure 9.3.5.9.1)
Cable
Wood Deck
NFPA-13 2016
3.5
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 3000 psi Lightweight Cracked Concrete (207 bar) on Metal Decking
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.6
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 3000 psi Nornal Weight Cracked Concrete
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.7
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Undercut Anchors in 3000 psi Nornal Weight Cracked Concrete
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.8
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 3000 psi Lightweight Cracked Concrete
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.9
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 4000 psi Nornal Weight Cracked Concrete
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.10
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 6000 psi Nornal Weight Cracked Concrete
Concrete Deck
Cable
SAF Clip
Anchor Sizes 3/8, 1/2, and 5/8
Loop
Cable
Stake Eye
Concrete Deck
Anchor Sizes
1/4, 3/8, 1/2
(See NFPA-13 Figure 9.3.5.12.2(a))
(See NFPA-13 Figure 9.3.5.12.2(a))
Oval Sleeve
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Deck
Anchor Sizes 3/8, 1/2, and 5/8
(See NFPA-13 Figure 9.3.5.12.2(a))
Cable
LPF
NFPA-13 2016
3.11
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Loop
Cable
SAF
Stake Eye
Cable
(See NFPA-13 Figure 9.3.5.9.1)
Bolt Sizes 1/4, 3/8, 1/2, 5/8.
Pipe
Pipe
Steel Member
Connections to Steel
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
LPF
Steel Member
Cable
Oval Sleeve
(See NFPA-13 Figure 9.3.5.9.1)
Bolt Sizes 1/4, 3/8, 1/2, 5/8.
NFPA-13 2016
3.12
1/2 Beam Depth but not <3 in.
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Through Bolts in Wood
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
SAF
Oval Sleeve
Cable
Loop
Wood Beam
Bolt Sizes 1/2, 5/8, 3/4
Wood Beam
Stake Eye
Cable
Bolt Sizes 1/2, 5/8, 3/4
(See NFPA-13 Figure 9.3.5.9.1)
(See NFPA-13 Figure 9.3.5.9.1)
1/2 Beam Depth but not <3 in.
1/2 Beam Depth
but not <3 in.
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
LPF
Wood Beam
Bolt Sizes 1/2, 5/8, 3/4
(See NFPA-13 Figure 9.3.5.9.1)
Bolt Sizes 1/2, 5/8, 3/4
(See NFPA-13 Figure 9.3.5.9.1)
Cable
1/2 Beam Depth but not <3 in.
NFPA-13 2016
3.13
SAF
Oval Sleeve
Cable
Loop
Wood Beam
Lag Bolt Sizes 3/8, 1/2, 5/8.
Wood Beam
Stake Eye
Cable
Lag Bolt Sizes 3/8, 1/2, 5/8.
(See NFPA-13 Figure 9.3.5.9.1)
(See NFPA-13 Figure 9.3.5.9.1)
1/2 Beam Depth but not <3 in.
Pipe
Pipe
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Lag Bolts in Wood
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
1/2 Beam Depth but not <3 in.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Wood Beam
Lag Bolt Sizes 3/8, 1/2, 5/8.
(See NFPA-13 Figure 9.3.5.9.1)
Cable
LPF
1/2 Beam Depth
but not <3 in.
3.14
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
1/2 Beam Depth but not <3 in.
Sleeve
Cable
Loop
Concrete Beam
SAF
Stake Eye
Cable
Concrete Beam
Anchor Sizes 3/8, 1/2,
5/8, 3/4
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
Wedge Anchors in 3000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Concrete Beam
LPF
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
NFPA-13 2016
3.15
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Undercut Anchors in 3000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Sleeve
Cable
Loop
Concrete Beam
SAF
Stake Eye
Cable
Concrete Beam
Anchor Sizes 3/8, 1/2,
5/8
Anchor Sizes 3/8, 1/2,
5/8
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
Concrete Beam
LPF
Anchor Sizes 3/8, 1/2,
5/8
(See NFPA-13 Figure 9.3.5.12.2)
Cable
NFPA-13 2016
3.16
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 3000 psi Lightweight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Sleeve
Cable
Loop
Concrete Beam
SAF
Stake Eye
Cable
Concrete Beam
Anchor Sizes 3/8, 1/2,
5/8, 3/4
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
Concrete Beam
LPF
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
Cable
NFPA-13 2016
3.17
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 4000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Sleeve
Cable
Loop
Concrete Beam
SAF
Stake Eye
Cable
Concrete Beam
Anchor Sizes 3/8, 1/2,
5/8, 3/4
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
Concrete Beam
LPF
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
Cable
NFPA-13 2016
3.18
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Wedge Anchors in 6000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Sleeve
Cable
Loop
Concrete Beam
SAF
Stake Eye
Cable
Concrete Beam
Anchor Sizes 3/8, 1/2,
5/8, 3/4
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
Concrete Beam
LPF
Anchor Sizes 3/8, 1/2,
5/8, 3/4
(See NFPA-13 Figure 9.3.5.12.2)
Cable
NFPA-13 2016
3.19
Angles D(30Á), E(45Á), and F(60Á)
Load Perpendicular to Structural Member
Connections to Steel
Stake Eye
Cable
Steel Beam
Steel Beam
Loop
Oval Sleeve
Cable
Bolt Sizes 1/4, 3/8,
1/2, 5/8.
(See NFPA-13 Figure 9.3.5.12.2)
Bolt Sizes 1/4, 3/8,
1/2, 5/8.
(See NFPA-13 Figure 9.3.5.12.2)
Pipe
Pipe
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Steel Beam
Bolt Sizes 1/4, 3/8,
1/2, 5/8.
SAF
LPF
(See NFPA-13
Figure 9.3.5.12.2)
Cable
Oval Sleeve
3.20
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
Through Bolts in Wood
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
Straight Stake Eye
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Wood Beam
Wood Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
LPF
LPF
NFPA-13 2016
3.21
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Above listed values based on wood with a specific gravity of 0.35. Values for other woods
can be obtained by multiplying above values by factors listed in figure1.
Lag Bolts in Wood
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
Straight Stake Eye
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Wood Beam
Wood Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
NFPA-13 2016
3.22
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Wedge Anchors in 3000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
SAF
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Concrete Beam
Concrete Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
NFPA-13 2016
3.23
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Undercut Anchors in 3000 psi Normal Weight Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
SAF
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Concrete Beam
Concrete Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
3.24
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Wedge Anchors in 3000 psi Lightweight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
SAF
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Concrete Beam
Concrete Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
3.25
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Wedge Anchors in 4000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
SAF
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Concrete Beam
Concrete Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
3.26
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Wedge Anchors in 6000 psi Normal Weight Cracked Concrete
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
NFPA-13 2016
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
SAF
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Concrete Beam
Concrete Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
LPF
LPF
3.27
Angles G(30Á), H(45Á), and I(60Á)
Load Parallel to Structural Member
Pipe
Pipe
Fastener
Straight Stake Eye
Cable
Fastener
Straight Stake Eye
Cable
Oval Sleeve
Oval Sleeve
(See NFPA-13 Figure 9.3.5.12.2)
(See NFPA-13 Figure 9.3.5.12.2)
Steel Beam
Steel Beam
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Min. four fastener diameters
but not <1/3 beam depth and
not <3 in. for wood beams.
Connections to Steel
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
LPF
LPF
NFPA-13 2016
3.28
Angles A(30Á), B(45Á), and C(60Á)
Load Perpendicular to Structural Member
Cable Looped Around Top Member of Bar Joist
901 Industrial Blvd.
Naples, FL 34104
800-321-5667
www.loosseismicbracing.com
MAX
45Á
Loop
around top
chord of bar
joist at a
panel point
Brace
Angle
Pipe
NFPA-13 2016
Oval Sleeve
Cable
3.29