USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC E-3
E
R
ela
ys
Key features of the RU series include:• Non-polarized LED indicator standard• Solder-free construction (spot welded, no solder points, lead-free)• No internal wires• Mechanical flag indicator standard• Manual latching lever with color coding for AC or DC coil• Available without latching lever (or with momentary check button)• Snap-on marking plate standard• Cadmium-free contacts• Color coded coils for visual distinction• Contact rating 6A: 4PDT 10A: DPDT
RU2 RU4
Spec
ifica
tions
Contact Material
AgSnOIn (silver tin oxide indium)
AuAg/Ag (gold-silver alloy on silver)
Contact Resistance
50 m
Ω
maximum
MinimumApplicable Load
24VDC, 5mA (reference value)
1V DC, 1mA (standard)1V DC, 0.1mA (bifurcated)
Operating Time
20 msec maximum
Release Time
20 msec maximum
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110%
Minimum Operating Voltage (AC/DC) at 20°C
80%
Drop-Out Voltage (AC) at 20°C
30%
Drop-Out Voltage (DC) at 20°C
10%
Power Consumption
1.1-1.4VA (AC); 0.9-1.0W (DC)
Dielectric Strength
Between contact and coil: 2,500VAC, 1 minuteBetween poles: 2,500VAC, 1 minuteBetween contacts of the same pole: 1,000VAC, 1 minute
Between contact and coil: 2,500VAC, 1 minuteBetween poles: 2,000VAC, 1 minuteBetween contacts of the same pole: 1,000VAC, 1 minute
Frequency Response
1,800 operations/hr
Vibration Resistance
Operating extremes: 10 to 55Hz,
Amplitude 1.0 mm p-pDamage limits: 10 to 55Hz,
Amplitude 1.0 mm p-p
Shock Resistance
Operating extremes: 150 m/s2 (15G)Damage limits:
1,000 m/s2 (100G)
Life Expectancy
Mechanical:AC: 20,000,000 operations
minimumDC: 30,000,000 operations
minimumElectrical:
see electrical life curve
Degree of Protection
IP40
Operating Temperature
-55 to +70°C (no freezing)
Weight
35g
RU Series — General Purpose Relays
Consult factory for other voltages.
UL RecognizedFile No. E66043, Vol 8, sec. 1 Vol 8, sec. 2
Key features of the RH series include:• Compact midget size saves space• High switching capacity (10A)• Choice of blade or PCB style terminals• Relay options include indicator light, check button, and top
mounting bracket• DIN rail, surface, panel, and PCB type sockets
available for a wide range of mounting applications
Spec
ifica
tions
Contact Material Silver cadmium oxide
Contact Resistance 50mΩ maximum (initial value)
Minimum Applicable Load
24V DC/30mA, 5V DC/100mA (reference value)
Operating Time SPDT (RH1), DPDT (RH2): 20ms maximum3PDT (RH3), 4PDT (RH4): 25ms maximum
Release Time SPDT (RH1), DPDT (RH2): 20ms maximum3PDT (RH3), 4PDT (RH4): 25ms maximum
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110% of the rated voltage
Minimum Operating Voltage (AC/DC) at 20°C 80% of the rated voltage
Drop-Out Voltage (AC) 30% or more of the rated voltage
Drop-Out Voltage (DC) 10% or more of the rated voltage
Insulation Resistance 100MΩ min (measured with a 500V DC megger)
Dielectric Strength
SPDT (RH1)Between live and dead parts: 2,000V AC, 1 minute; Between contact circuit and oper-ating coil: 2,000V AC, 1 minute; Between contacts of the same pole: 1,000V AC, 1 minute
DPDT (RH2), 3PDT (RH3), 4PDT (RH4)Between live and dead parts: 2,000V AC, 1 minute; Between contact circuit and oper-ating coil: 2,000V AC, 1 minute; Between contact circuits: 2,000V AC, 1 minute; Between contacts of the same pole: 1,000V AC, 1 minute
Frequency Response 1,800 operations/hour
Temperature Rise Coil: 85°C maximumContact: 65°C maximum
Total length from panel surface including socket:SH1B-05: 2.40" (61.5mm) maximum; SH1B-51: 1.54" (39mm) maximumTotal length from panel surface including hold-down spring:SH1B-05: 2.48" (63.5mm) maximum; SH1B-51: 1.62" (41.6mm) maximum
0.546"
Plug-in Blade Terminal
(0.5mm)
(14mm)or less
1.39" (35.6mm) 0.25"(6.4mm)
0.019"
0.183"(4.7mm)
1.07
" (2
7.5m
m)
Total length from panel surface including socket:SH2B-05: 2.40" (61.5mm) maximum; SH2B-51: 1.54" (39.6mm)Total length from panel surface including hold-down spring:SH2B-05: 2.48" (63.5mm) maximum; SH2B-51: 1.62" (41.6mm)
Total length from panel surface including socket:SH3B-05: 2.57" (66mm) maximumTotal length from panel surface including hold-down spring:SH3B-05: 2.65" (68mm) maximum
1.21" (31mm)
0.183"(4.7mm)
Ø 0.101" (2.6mm)
Plug-in Blade Terminal
1.39" (35.6mm) or less
0.25"(6.4mm)
0.019" (0.5mm)
1.07
" (2
7.5m
m)
Total length from panel surface including socket:SH4B-05: 2.40" (61.5mm) or less; SH4B-51: 1.54" (39.6mm)Total length from panel surface including hold-down spring:SH4B-05: 2.48" (63.5mm) or less; SH4B-51: 1.62" (41.6mm)
Key features of the RR series include:• High reliability and long service life• Available in octal (8- and 11-pin) or square (11-blade) base• Options include check button for test operation, indicator light, and
side flange (contact IDEC for diodes)• DIN rail, surface and panel type sockets available for a wide range of
mounting applications
Spec
ifica
tions
Contact Material Silver
Contact Resistance 30mΩ maximum (initial value)
MinimumApplicable Load
24V DC/10mA, 5V DC/20mA (reference value)
Operating Time 25ms maximum
Release Time 25ms maximum
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110% of the rated voltage
Minimum Operating Voltage (AC/DC) at 20°C 80% of the rated voltage
Drop-Out Voltage (AC) at 20°C 30% of the rated voltage
Drop-Out Voltage (DC) at 20°C 15% of the rated voltage
Power Consumption AC: approximately 3VA (50Hz), 2.5VA (60Hz)DC: approximately 1.5W
Insulation Resistance 100MΩ minimum (measured with 500V DC megger)
Dielectric Strength
Pin (RR2P, RR3PA)Between live and dead parts: 1,500V AC, 1 minuteBetween contact circuit and operating coil: 1,500V AC, 1 minuteBetween contact circuits: 1,500V AC,1 minute (1,000V AC between NO-NC contacts)
Blade (RR1BA, RR2BA, RR3B)Between live and dead parts: 2,000V AC, 1 minuteBetween contact circuit and operating coil: 2,000V AC, 1 minuteBetween contact circuits: 2,000V AC, 1 minuteBetween contacts of same polarity: 1,000V AC, 1 minute
Frequency Response 1,800 operations/hour
Temperature Rise Coil: 85°C maximumContact: 65°C maximum
Vibration Resistance 0 to 6G (55Hz maximum)
Shock Resistance 100N (approximately 10G)
Life Expectancy Electrical: over 500,000 operations (120V, 50/60Hz, 10A)Mechanical: over 10,000,000 operations
Key features of the RY series include:• Compact miniature size saves space• 2PDT and 4PDT models, available with bifurcated crossbar contacts,
ensure reliable low-current switching for dry circuit applications• Choice of plug-in/solder or PCB type terminals• Options include check button for test operation and indicator lights • DIN rail, surface, panel, and PCB type sockets available for a wide
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110% of the rated voltage
Minimum Operating Voltage (AC/DC) at 20°C 80% of the rated voltage
Drop-Out Voltage (AC) 30% or more of the rated voltage
Drop-Out Voltage (DC) 10% or more of the rated voltage
Power ConsumptionRY2, RY22: DC: approximately 0.8WAC: approximately 1.1VA (50Hz), 1VA (60Hz)RY4, RY42, RM2: DC: approximately 0.9WAC: approximately 1.4VA (50Hz), 1.2VA (60Hz)
Insulation Resistance 100MΩ minimum(measured with 500V DC megger)
Dielectric Strength
RY2, RY22: Between live and dead parts: 1,500V AC, 1 minute; Between contact and coil: 1,500V AC, 1 minute; Between contacts of different poles: 1,500V AC, 1 minute; Between contacts of the same pole: 1,000V AC, 1 minuteRY4, RY42, RM2,: Between live and dead parts: 2,000V AC, 1 minute; Between contact and coil: 2,000V AC, 1 minute; Between contacts of differ-ent poles: 2,000V AC, 1 minute; Between contacts of the same pole: 1,000V AC, 1 minute
Frequency Response 1,800 operations/hour
Temperature Rise Coil: 85°C maximumContact: 65°C maximum
Total length from panel surface including socket:SY2S-02: 2.40" (61.6mm) maximum; SY2S-51: 1.56" (40mm)Total length from panel surface including hold-down spring:SY2S-02: 2.48" (63.6mm) maximum; SY2S-51: 1.64" (42mm)
Ø 0.119" x 0.047"
1.40" (36mm)
0.019"
or Less
1.07
” (27
.5m
m)
0.552"0.214"(5.5mm)
Solder TerminalPlug-inRY2S
0.103"(2.64mm)
Ø 0.119" x 0.047"
0.137"(3.5mm)
0.839"
1.50
" (3
8.4m
m)
1.70
" (4
3.6m
m)
0.078"(2mm)
1.40" (36mm)0.253"(6.5mm)
0.253"(6.5mm)
0.019" 0.162"(4.15mm)
0.25"(6.4mm)
1.07
” (27
.5m
m)
(3.05x1.2mm) Hole
With Top BracketPlug-inRY2S-UT, RY22S-UT
Total length from panel surface including socket:SY4S-02: 2.40" (61.6mm) maximum; SY4S-51: 1.56" (40mm)Total length from surface including hold-down spring:SY4S-02: 2.48" (63.6mm) maximum; SY4S-51: 1.64" (42mm)
Key features of the RR2KP series include:• Standard octal base (11-pin) termination• Operates by pulse input and maintains condition even
during power failure• Coils rated for continuous duty• High vibration and shock resistance• Excellent self-holding performance (magnetic latch)• Optional manual check button for circuit testing• DIN rail, surface, and panel mount sockets
available for a wide range of mounting applications
Spec
ifica
tions
Contact Material Silver
Contact Resistance 30mΩ maximum (initial value)
MinimumApplicable Load 5V DC, 100mA
Operating Time 25ms maximum
Maximum Continu-ous Applied Volt-age (AC/DC) at 20°C
110% of the rated voltage without overheating
Minimum Set and Reset Voltage at 20°C
80% of the rated voltage
Power Consumption AC: approximately 2.4VA (50Hz), 2.2VA (60Hz)DC: approximately 1.5W
InsulationResistance 100MΩ minimum (with 500V DC megger)
Dielectric Strength
Between live and dead parts: 1,500V AC, 1 minuteBetween contact circuit and opposite coil: 1,500V AC, 1 minuteBetween contact circuits: 1,500V AC, 1 minute (1,000V between NO-NC contacts)
Frequency Response 1,800 operations/hour
Temperature Rise Coil: 85°C maximum; Contact: 65°C maximum
Vibration Resistance 0 to 6G (55Hz maximum)
Shock Resistance 100N (approximately 10G)
Life Expectancy Electrical: over 500,000 operations (120V, 10A)Mechanical: over 5,000,000 operations
Operating Temperature –30 to +70°C
Weight 170g (approximately)
RR2KP Series — Magnetic Latching Relays
Order standard voltages for fastest delivery. Allow extra delivery time fornon-standard voltages.
Total length from panel surface including socket:SR3P-05: 4.13" (106mm) maximum; SR3P-51: 3.45" (88.4mm) maximumTotal length from panel surface including hold down springs:
1.42" (36.4mm)
1.42
" (3
6.4m
m)
SR3P-05: 4.27" (109.5mm) maximum; SR3P-51: 3.62" (92.9mm) maximum
Key features of the RH2L series include:• Compact miniature size saves board space• Power-saving operation by pulse inputs eliminates the
need for continuous control voltage• Coils rated for continuous duty• Built-in mechanical indicator to show set/reset condition• Available with blade and PC mount terminals• DIN rail, surface, panel, and PCB type sockets available
for a wide range of mounting applications• Excellent self-holding performance (magnetic latching)
Spec
ifica
tions
Contact Material Silver cadmium oxide
Contact Resistance 50mΩ or less (initial value)
Minimum Applicable Load 5V DC, 100mA
Operating Time 30ms (AC); 20 ms (DC)
Maximum Continuous Applied Voltage (AC/DC) 110% of rated voltage
Minimum Set and Reset Voltage at 20°C 80% of rated voltage
Set Time 30ms or less (AC); 20ms or less (DC)
Reset Time 30ms or less (AC); 20ms or less (DC)
Power ConsumptionSet coil: AC: approximately 1.2V; DC: approximately 2WReset coil: approximately 0.5VA; DC: approximately 0.9W
Insulation Resistance 100MΩ minimum
Dielectric Strength
Between live and dead parts:2,000V AC, 1 minuteBetween contact circuit and opposite coil: 2,000V AC, 1 minuteBetween contact circuits: 1,500V AC, 1 minuteBetween contacts of same pole: 1,000V AC, 1 minute
Frequency Response 1,800 operations/hour
Vibration Resistance 60N (approximately 6G)Maximum frequency 55Hz
Shock Resistance 100N or more (approximately 10G)
Life Expectancy Electrical: over 200,000 operationsMechanical: over 10,000,000 operations
Operating Temperature –30 to +70°C
Weight 50g
RH2L Series — Magnetic Latching Relays
Order standard voltages for fastest delivery. Allow extra delivery time fornon-standard voltages.
Total length from panel surface including socket;SH3B-05: 2.40" (61.6mm) maximumTotal length from panel surface including hold-down spring:SH3B-05: 2.48" (63.6mm) maximum
Key features of the RY2KS series include:• Standard “ice cube” base, solder lug (14-pin) termination• Operates by pulse input and maintains condition even during power failure• High vibration and shock resistance• Excellent self-holding performance• Optional manual check button for circuit testing• DIN rail, surface, and panel mount socketsavailable for a wide range of mounting applications
Spec
ifica
tions
Contact Material Silver, gold-plated
Contact Resistance 50mΩ maximum (initial value)
Minimum Applicable Load 5V DC, 100mA
Operating Time 25ms maximum
Release Time 25ms maximum
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110% of the rated voltage
Set and Reset Voltages(AC/DC) at 20°C 80% of the rated voltage
Power Consumption AC: approximately 1.6V (50Hz), 1.5VA (60Hz)DC: approximately 1.2W
Insulation Resistance 100MΩ minimum (with 500V DC megger)
Dielectric Strength
Between live and dead parts:1,500V AC, 1 minuteBetween contact circuit and opposite coil: 1,000V AC, 1 minuteBetween contact circuits: 1,000V AC, 1 minute (700V between NO-NC contacts)
Frequency Response 1,800 operations/hour
Temperature Rise Coil: 85°C maximumContact: 65°C maximum
Vibration Resistance 0 to 6G (55Hz maximum)
Shock Resistance 20G minimum
Life ExpectancyElectrical: over 200,000 operations (240V AC, 3A)Mechanical: over 5,000,000 operations
Operating Temperature –30 to +70°C
Weight 67g (approximately)
RY2KS Series — Miniature Magnetic Latching Relays
Order standard voltages for fastest delivery. Allow extra delivery time fornon-standard voltages.
Key features of the RY2L series include:• Standard “ice cube,” 14-pin solder lug termination• Operates by pulse input and maintains condition even
during power failure• Coils rated for continuous duty• Excellent self-holding performance (magnetic latch)• Built-in mechanical indicator to show set/reset condition• DIN rail, surface, and panel mount sockets
available for a wide range of mounting applications
Spec
ifica
tions
Contact Material Silver, gold-plated
Contact Resistance 50mΩ or less (initial value)
Minimum Applicable Load 5V DC, 100mA
Operating Time 30ms or less (AC); 20ms or less (DC)
Release Time 30ms or less (AC); 20ms or less (DC)
Maximum Continuous Applied Voltage (AC/DC) at 20°C
110% of the rated voltage
Set and Reset Voltages(AC/DC) at 20°C 80% of the rated voltage
Power Consumption
Set coil: DC: approximately 1.2WAC: approximately 0.75VA (50Hz); 0.7VA (60Hz)Reset coil: DC: approximately 0.60WAC: approximately 0.35VA
Insulation Resistance 100MΩ minimum
Dielectric Strength
Between live and dead parts:1,500V AC, 1 minuteBetween contact circuit and operating coil: 1,000V AC, 1 minuteBetween contact circuits: 1,000V AC, 1 minuteBetween contacts of same pole: 700V AC, 1 minute
Response Frequency 1,800 operations/hour
Vibration Resistance 60N (0–6G); Maximum frequency 55Hz
Shock Resistance 100N or more (10G or more)
Life Expectancy Electrical: 200,000 operationsMechanical: 10,000,000 operations
Operating Temperature –30 to +70°C
Weight 34g (approximately)
RY2L Series — Miniature Magnetic Latching Relays
Order standard voltages for fastest delivery. Allow extra delivery time fornon-standard voltages.
Key features of the RSS series include:• Input status LED Indicator• Dual SCR output• Direct bond copper substrate• Internal transient protection – built-in snubber• EMC compliant (level 3)• Photo isolation• 1200 volt blocking voltage• 4000 volt optical isolation• Zero voltage turn-on• 100% tested at rated current• High surge capability• Optional finger-safe
Transformer LoadsTransformer loads sometimes result in severe inrush current when the trans-former saturates during the first cycle. Use a relay rated for this surge, which has a 1/2 cycle surge current greater than the maximum applied line voltage ÷ the transformer’s primary resistance (approximately 10x rated current).
Recommended Loads
Heater LoadsWhen using solid state relays for driving heaters where the load is switched on and off rapidly and continuously, severe thermal stress will result. In such cases, use an SSR relay at no more than 75% of the rating.
Recommended Loads
Solenoid Valves and ContactorsRSS relays use high-noise immunity circuitry with a snubber to handle the electrical noise generated by inductive loads.
Recommended Loads
RSS series relays provide a highly reliable means of switching AC loads when applied properly. Read the following technical notes prior to installing IDEC’s quality solid state relays.
UL Motor Load Ratings
SSR Rating at 120V AC at 240V AC
2A 150VA 300VA
4A 200VA 400VA
10A 500VA 1KVA
25A 1KVA 2KVA
50A 2KVA 4KVA
SSR Rating at 120V AC at 240V AC
2A 250W 500W
4A 400W 800W
10A 1KW 2KW
25A 2KW 4KW
50A 3KW 6KW
SSR Rating at 120V AC at 240V AC
2A 250W 500W
4A 400W 800W
10A 900W 1,800W
25A 2,100W 4,200W
50A 3,800W 7,500W
Part Number 120V 240V 480V
10A 1/2 3/4 3/4
25A 1/2 3/4 3/4
50A 3/4 11/2 11/2
75A 3/4 5 5
90A 3/4 5 5
Recommended Loads
Lamp LoadsZero voltage switching is ideal for driving incandescent lamps, since the cold filament will not be subjected to a large inrush current. Using a zero-switched SSR will reduce inrush current and prolong lamp life.
EnvironmentDo not install SSRs near sources of excessive heat. Make sure applications are dry and well ventilated.
If SSRs must be installed in an environment subject to high temperatures or poor ventilation, or if SSRs are mounted collectively, reduce the load current so that it does not approach the ambient temperature-load current recommendation. (See the Temperature Derating Curves on the following page.)
When SSRs are used with inductive loads, suppress the inrush current to half of the peak surge current.
Heat SinksHeat sinks are recommended for 10, 25, 50, 75, and 90 amp rated solid state relays depending on ambient temperature and mounting position. The recommended heat sink dimensions and material are shown in the table:
Using a thermal compound between the base of the SSR and the heat sink for heat dissipation is recommended.
WiringLocate SSRs as far from motor leads as possible to prevent malfunction from induced current.
Use shielded wires for input leads when they are exposed to a source of induced current.
MountingProvide sufficient ventilation.
Use #6 – 32 screws, flat washers, and lock washers to secure mounting on heat sinks.
Vertical mounting is recommended to allow air to flow unimpeded. Horizontal or inverted mounting is possible, but the SSR must be derated according to the der-ating curves on the following page.
Additional InformationDo not exceed the load voltage and current specifications.
A small-capacity load may not turn off due to the leakage current present after the SSR has turned off. If this is the case, use a resistor in parallel with the load toshunt the leakage current.
Observe the polarity of input terminals. Failure to do so may cause damage to the SSR.
When the SSR output is subjected to a higher than rated voltage, a varistor or other element should be connected to the output terminals to absorb the over-volt-age.
When the input signal contains a ripple voltage, the lowest ripple amplitude should exceed the minimum pick-up voltage of 4V.
Output Rating Dimensions Material
10A 12" x 12" x 1/8" Aluminum (black anodized)
25A 12" x 12" x 1/8" (DC/AC) Aluminum (black anodized)
25A 15" x 15" x 1/8" (AC/AC) Aluminum (black anodized)