Introduction.Gyprock® plasterboard and CSR Fibre Cement
Wallboard can be used with masonry walls for effectivefire and acoustic solutions. These linings can eliminatethe need for render, increase the fire rating of themasonry, or provide an acoustic performance to meetsound transmission and sound impact ratings.
Systems incorporating masonry and an insulatedcavity are generally used where there is a requirementfor excellent acoustic performance and discontinuousconstruction. The provision of a cavity also allows theinclusion of services such as water pipes.
Gyprock® plasterboard may be directly applied tothe masonry substrate, screw fixed to metal furringchannels that are fixed to the masonry, or may be fixedto separate stud framing. CSR Fibre Cement Wallboardmay be fixed to furring channels or studs.
Systems in this section are suitable for a wide rangeof masonry products. These are typically clay andconcrete blocks, autoclaved aerated concrete blocks andpanels, and may include cast concrete elements.Minimum performance conditions apply to thesubstrates to achieve the system performance values,and these are stated in the system specifications. Specificfixing details apply to each type of substrate.
These wall systems are generally used in internalapplications in commercial, industrial, institutional,domestic and high-rise domestic construction, or in therenovation of older buildings. A number of systems forexternal masonry veneer walls can be found in Section‘B’ and Section ‘C’.
DesignConsiderations.
STRUCTURAL PERFORMANCE.
All wall elements must be designed for the appliedloads. Vertical loads may be supported by the masonryelement of the wall or by the stud framing.
Lateral loads should be considered separately forframed and masonry parts of a wall. To achieve thespecified sound performance, ties from masonry to thestud framing must not be used.
Framed Wall Elements.
Guidance is given in Tables D2, D3, & D4 for theselection of Rondo studs and other specific sections innon-loadbearing internal walls only, for 0.25kPa and0.35kPa. For other brand of studs, studs that arerequired to be loadbearing, and studs subject to highlateral pressures, contact the manufacturer for designinformation. Maximum spans for Rondo furr ingchannels are given in Table D1.
Tall multi-residential buildings often have operabledoors and windows, resulting in internal walls beingsubject to wind pressure. In these cases, walls must bedesigned for the appropriate loads.
Stud frames that are part of a masonry wall systemmay be load bearing. A qualified structural engineermust complete the structural design of loadbearing wallsystems. Walls with shelving attached are consideredloadbearing.
Further information on the design of stud walls isgiven in Section ‘B’.
Walls lined with GYPROCK plasterboard designedas loadbearing, and non-loadbearing walls selected fromTables D2-D4, meet the requirements of BCASpecification C1.8 Clause 3.4 – Walls generally.
TABLE D1. MAXIMUM SPACING OF WALL SUPPORT
CLIPS FOR FURRING CHANNELS.
Walls Generally (UDL = 0.35kPa)
Rondo Maximum Furring Channel Spacing of Clips Part Nº (mm)
308 (16mm) 900
129 (28mm) 1200
NOTE: Support clips include Gyprock® ResilientMounts and Rondo direct fixing clips.
The Red Book™D3.
TABLE D2. MAXIMUM WALL HEIGHT WITH RONDO LIPPED STEEL STUDS.NON LOADBEARING INTERNAL WALLS – NON FIRE RATED OR FIRE RATED.
The values in Tables D2 and D3 have been prepared by Rondo Building Services Pty Ltd.
2.32
2.32
2.32
2.84
2.84
2.84
3.00
3.16
3.16
3.00
3.54
3.54
3.00
3.27
3.27
3.00
3.86
3.86
3.00
4.08
4.08
3.00
3.73
3.73
3.00
4.24
4.24
3.00
4.73
4.73
3.00
5.73
5.73
3.00
5.99
6.86
One Row Nogging6mm
Two Rows Nogging6mm
Three Rows Nogging6mm
600mm max. cts
TABLE D3. MAXIMUM WALL HEIGHT WITH RONDO LIPPED STEEL STUDS.NON LOADBEARING WALLS – NON FIRE RATED OR FIRE RATED.Walls of Shafts and Fire Isolated Exits Generally (Load UDL = 0.35kPa).
TABLE D4. MAXIMUM WALL HEIGHT FOR STAGGERED STEEL STUDS LINED TWO SIDESOR WALLS LINED ONE SIDE ONLY – NON LOADBEARING WALLS.
Walls Generally (Load UDL = 0.25kPa).
88 88 88 120 120 120
Stud Depth/BMT mm
Min. Cavity Width
Min. Lining Thickness
Wall Frame
and Lining
Configuration Maximum Wall Height (m)
3.50
3.86
3.50
3.87
4.17
3.87
4.11
4.37
4.11
4.82
4.96
4.82
4.93
5.44
5.30
4.93
5.81
5.65
13mm GYPROCKFYRCHEK
2 layers x 13mmGYPROCK FYRCHEK
9mm CSR Fibre CementWallboard
StramitSupplier
Steel Stud Type TH64075
64/0.75
TH64100
64/1.00
TH64120
64/1.20
TH96075
96/0.75
TH96100
96/1.00
TH96120
96/1.20
600mm max. cts
76 85 85 144 144
Stud Depth/BMT mm
Min. Cavity Width
Min. Lining Thickness
Wall Frame
and Lining
Configuration Maximum Wall Height (m)
3.00
3.00
3.00
3.44
3.50
3.44
3.71
3.90
3.71
4.93
5.90
5.90
4.93
6.40
6.00
13mm GYPROCKFYRCHEK
2 layers x 13mmGYPROCK FYRCHEK
9mm CSR Fibre CementWallboard
Rhino Steel LysaghtSupplier
Steel Stud Type UniSpan 53
53/–
TS61-075
61/0.75
TS61-100
61/1.00
TS120-070
120/0.70
TS120-090
120/0.90
600mm max. cts
D4. The Red Book™
Masonry Wall Elements.
All brick and block wall elements are to be designedin accordance with AS3700 Masonry Structures.Concrete walls must be designed to AS3600, ConcreteStructures, and CSR Hebel Powerpanel™ must bedesigned in accordance with CSR Hebel literature.
FIRE RESISTANCE.
For systems without a stated Fire Resistance Level(FRL), the system FRL is equal to the FRL of themasonry wall element. The FRL of masonry walls isdependant on the height and width of the wall; contactthe manufacturer for more information.
To achieve the required fire performance of a wall, itis essential that installation is in accordance with themasonry manufacturer’s details and relevant installationstandards. This should include fire sealing at the wallhead and perimeters, and filling of mortar joints. Allgaps and penetrations should be effectively fire sealed.
Vermiculite plaster has no capacity to accommodatebuilding movement and may not be suitable for use as ageneral purpose fire rated caulking. Its use is specified insome wall/ceiling junctions. Refer to the Gyprock®
Ceiling Systems Installation Guide, NºGYP570.
In systems with Gyprock Fyrchek® plasterboard,framing, jointing and fire sealing must be in accordancewith Section ‘B’ of this manual. FYRCHEKplasterboard must be fully screw fixed, and the use ofGyprock Acrylic Stud Adhesive is not permitted .
ACOUSTIC PERFORMANCE.
The acoustic performance of some systems isdependant on a minimum Rw of the masonry wallelement. This is to be the tested performance of themasonry without render or sheet linings, and must beverified by the masonry unit manufacturer.
Installation of the masonry element of the wall mustbe in accordance with the manufacturer’s details for thetested product.
Systems that meet the BCA requirements fordiscontinuous construction are noted in the systemspecifications. These have studs that are separated fromthe masonry by at least 12mm. The plasterboard liningon the studs (the wall leaf) therefore has a separation ofat least 12mm plus the depth of the stud, which exceedsthe BCA minimum of 20mm.
Systems that use only resilient mounts or fixing clipswith furring channels to create a cavity, do not meet therequirements of discontinuous construction.
The acoustic performance of wall systems may beaffected by:
• Sound flanking.
• The effectiveness of workmanship and caulking.
• The presence and treatment of penetrations.
• The inclusion of structural elements and bridgingitems.
• Reducing the stated or implied cavity sizes.
The acoustic performance of wall systems will notbe affected by:
• The addition of Gyprock® plasterboard or CSRFibre Cement linings.
• The use of deeper studs or larger cavities.
• The use of timber studs of at least equal depth in lieuof steel studs.
Refer to Section ‘A’ for detailed information.
Perimeter Sealing.
To attain the stated Rw in systems that do not relyon plasterboard for the fire rating, use CSR GyprockWet Area Acrylic Sealant, CSR Gyprock Fire Mastic orother tested acoustic rated material of equivalent orbetter performance.
Installation.MASONRY.
All brick and block walls are to be installed inaccordance with AS3700 Masonry Structures. CSRHebel Powerpanel™ must be installed in accordancewith CSR Hebel literature.
FRAMING.
For detailed information on wall junctions,intersections, frame attachments and penetrations, referto Section ‘Z’ of this manual.
Refer to manual NºGYP544, Steel Frame WallSystems Installation Guide for detailed information oninstallation of stud framing.
WALLBOARD & PLASTERBOARD FIXING.
Walls may be built to achieve a particular ‘Level ofFinish’ as defined in AS/NZS2589.1. The Level ofFinish specified can have requirements for framealignment, jointing, back blocking methods and sheetor ientation. CSR Fibre Cement Wallboard andGyprock® plasterboard may be installed vertically orhorizontally, although for some Levels of Finishhorizontal sheeting must be used.
The Red Book™D5.
Except for fire grade plasterboard, fixing to framingmay be fastener only or combination fastener/adhesive.Plasterboard fixed direct to masonry may be adhesivedaub fixed as shown in installation diagram FIG D4,full bed adhesive fixed, or mechanically fixed.
JOINTING & FINISHING.
Refer to the Gyprock® Residential InstallationGuide, NºGYP547 and CSR Fibre Cement Wet AreaLining Systems, NºFC101 for detailed jointing andfinishing information.
It should be noted that:
• Multi-layered systems only require jointing andfinishing of the outer layer.
• It is a requirement of the BCA that a water resistanttaping compound, such as CSR Gyprock & FibreCement Wet Area Base Coat, be used at vertical walljunctions (corners), and horizontal and verticaljoints within wet areas such as showers.
CONTROL JOINTS.
Control joints must be installed to allow forstructural movement. Allowance for movement must bemade through the masonry and any direct fixed lining,and through framed wall elements. Refer to Section ‘Z’of this manual for details.
Control joints must be installed at all constructionjoints in the building, and at the following locations:
For masonry with any direct fixed lining or liningfixed to furring channels:
• Refer to masonry manufacturer.
• At 12m maximum centres.
• At change of substrate material.
For stud framed wall elements:
• Non-tiled internal walls with fibre cement outerlayer: at 7.2m maximum centres.
• Tiled internal walls with fibre cement outer layer: at4.2m maximum centres.
• Walls with plasterboard outer layer : at 12mmaximum centres.
Components.LINING & FIXING MATERIALS.
Refer to Section ‘A’ of this manual for detailedinformation on CSR Gyprock and Fibre Cement liningproducts, masonry adhesive, and for fastenerspecifications for fixing GYPROCK plasterboard tosteel studs and furring channel.
CSR Gyprock Masonry Adhesive is a fast andconvenient method of fixing GYPROCK plasterboardsystems to masonry substrates. CSR Gyprock AcrylicStud Adhesive is used for fixing non fire grade linings toframing.
FRAMING.
CSR Gyprock and CSR Fibre Cement recommendsteel components manufactured by Rondo BuildingServices Pty Ltd. Additional information on the steelcomponents can be obtained from the Rondo BuildingServices Pty Ltd, telephone 1300 367 663.
For information on Lysaght, Stramit or UniSpan tophat sections, please refer to the appropriate componentmanufacturer, and the Gyprock® Steel Frame WallSystems Installation Guide, NºGYP544.
Fixing clips include CSR Resilient Mount, Rondodirect fixing clips Nº237, Beta-Fix and STSC clips.Furring channels part Nº308 or Nº129 are to be fittedinto wall track part Nº142 or Nº140 respectively at topand bottom.
MASONRY.
For systems in this section, masonry may includeclay or concrete blocks, autoclaved aerated concreteblocks and panels, and reinforced concrete. Brick andblock substrates shall comply with AS3700.
D6. The Red Book™
TestedBrick,
Block orConcreteWall withRw > 41
Refer to MasonryWall Manufacturerfor FRL Details
TestedBrick,
Block orConcreteWall withRw > 44
Refer to MasonryWall Manufacturerfor FRL Details
(a) 75 Glasswool Partition batts 63/56 65/58
(b) 95 Comfortseal™ R2.0 batts – 66/59
(c) ASB4/TSB4 Polyester batts 63/56 65/58
(d) ASB5/TSB5 Polyester batts – 66/59
ADDITIONAL THICKNESS mm 115 143
CSR 766
STUD SIDE
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 60/52 60/55
(b) 95 Comfortseal™ R2.0 batts – 63/56
(c) ASB4/TSB4 Polyester batts 60/52 62/54
(d) ASB5/TSB5 Polyester batts – 63/56
ADDITIONAL THICKNESS mm 102 130
CSR 765
STUD SIDE
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 59/51 60/52
(b) 95 Comfortseal™ R2.0 batts – 61/53
(c) ASB4/TSB4 Polyester batts 59/51 60/52
(d) ASB5/TSB5 Polyester batts – 61/53
ADDITIONAL THICKNESS mm 102 130
CSR 764STUD SIDE
• 1 x 13mm GYPROCKplasterboard CD.
(a) 75 Glasswool Partition batts 62/54 62/55
(b) 95 Comfortseal™ R2.0 batts – 63/56
(c) ASB4/TSB4 Polyester batts 61/54 62/55
(d) ASB5/TSB5 Polyester batts – 63/56
ADDITIONAL THICKNESS mm 115 143
CSR 762
STUD SIDE
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 58/50 59/52
(b) 95 Comfortseal™ R2.0 batts – 60/53
(c) ASB4/TSB4 Polyester batts 58/50 59/51
(d) ASB5/TSB5 Polyester batts – 60/53
ADDITIONAL THICKNESS mm 102 130
CSR 761
STUD SIDE
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 56/48 58/50
(b) 95 Comfortseal™ R2.0 batts – 59/51
(c) ASB4/TSB4 Polyester batts 56/48 58/50
(d) ASB5/TSB5 Polyester batts – 59/51
ADDITIONAL THICKNESS mm 102 130
CSR 760STUD SIDE
• 1 x 13mm GYPROCKplasterboard CD.
ACOUSTICOPINION
PKA-A027
MEETSBCA
DiscontinuousConstruction
MasonryWall
Requirements
SYSTEM Nº
WALL LININGS
SYSTEM SPECIFICATION TYPICAL LAYOUT
• Plasterboard as per table, fixed to studs.
• Steel stud framing, as per table, at 600mm max. centres.
• Cavity infill as per table.
• 12mm minimum cavity between masonry and framing.
• Single Brick, Block or Concrete wall with Rw as stated.
• 1 x 13mm GYPROCK plasterboard CD direct fixed tomasonry.
STUD WIDTH mm 64 92
CAVITY INFILL (Refer to Section A) Rw / Rw+Ctr
Masonry Wall Systems - Stud One Side.
The Red Book™D7.
TestedBrick,
Block orConcreteWall withRw > 46
Refer to MasonryWall Manufacturerfor FRL Details
TestedBrick,
Block orConcreteWall withRw > 51
Refer to MasonryWall Manufacturerfor FRL Details
(a) 75 Glasswool Partition batts 68/61 70/63
(b) 95 Comfortseal™ R2.0 batts – 71/64
(c) ASB4/TSB4 Polyester batts 71/64 72/65
(d) ASB5/TSB5 Polyester batts – 73/66
ADDITIONAL THICKNESS mm 115 143
CSR 772
STUD SIDE
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 65/57 67/60
(b) 95 Comfortseal™ R2.0 batts – 68/61
(c) ASB4/TSB4 Polyester batts 65/57 67/59
(d) ASB5/TSB5 Polyester batts – 68/61
ADDITIONAL THICKNESS mm 102 130
CSR 771
STUD SIDE
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 64/56 65/57
(b) 95 Comfortseal™ R2.0 batts – 66/58
(c) ASB4/TSB4 Polyester batts 64/56 65/57
(d) ASB5/TSB5 Polyester batts – 66/58
ADDITIONAL THICKNESS mm 102 130
CSR 770STUD SIDE
• 1 x 13mm GYPROCKplasterboard CD.
(a) 75 Glasswool Partition batts 66/59 67/60
(b) 95 Comfortseal™ R2.0 batts – 68/61
(c) ASB4/TSB4 Polyester batts 66/59 67/60
(d) ASB5/TSB5 Polyester batts – 68/61
ADDITIONAL THICKNESS mm 115 143
CSR 769
STUD SIDE
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 63/55 64/57
(b) 95 Comfortseal™ R2.0 batts – 65/58
(c) ASB4/TSB4 Polyester batts 63/55 64/56
(d) ASB5/TSB5 Polyester batts – 65/58
ADDITIONAL THICKNESS mm 102 130
CSR 768
STUD SIDE
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 61/53 63/55
(b) 95 Comfortseal™ R2.0 batts – 64/56
(c) ASB4/TSB4 Polyester batts 61/53 63/55
(d) ASB5/TSB5 Polyester batts – 64/56
ADDITIONAL THICKNESS mm 102 130
CSR 767STUD SIDE
• 1 x 13mm GYPROCKplasterboard CD.
ACOUSTICOPINION
PKA-A027
MEETSBCA
DiscontinuousConstruction
MasonryWall
Requirements
SYSTEM Nº
WALL LININGS
SYSTEM SPECIFICATION TYPICAL LAYOUT
• Plasterboard as per table, fixed to studs.
• Steel stud framing, as per table, at 600mm max. centres.
• Cavity infill as per table.
• 12mm minimum cavity between masonry and framing.
• Single Brick, Block or Concrete wall with Rw as stated.
• 1 x 13mm Gyprock plasterboard CD direct fixed tomasonry.
STUD DEPTH mm 64 92
CAVITY INFILL (Refer to Section A) Rw / Rw+Ctr
Masonry Wall Systems - Stud One Side.
D8. The Red Book™
TestedBrick,
Block orConcreteWall withRw > 41
Refer to MasonryWall Manufacturerfor FRL Details
TestedBrick,
Block orConcreteWall withRw > 44
Refer to MasonryWall Manufacturerfor FRL Details
(a) 75 Glasswool Partition batts 67/60 69/62
(b) 95 Comfortseal™ R2.0 batts – 70/63
(c) ASB4/TSB4 Polyester batts 66/59 68/61
(d) ASB5/TSB5 Polyester batts – 70/63
ADDITIONAL THICKNESS mm 204 260
CSR 785
BOTH SIDES
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 64/56 66/59
(b) 95 Comfortseal™ R2.0 batts – 67/60
(c) ASB4/TSB4 Polyester batts 63/55 65/57
(d) ASB5/TSB5 Polyester batts – 67/60
ADDITIONAL THICKNESS mm 178 234
CSR 784
BOTH SIDES
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 63/55 64/56
(b) 95 Comfortseal™ R2.0 batts – 65/57
(c) ASB4/TSB4 Polyester batts 62/54 63/55
(d) ASB5/TSB5 Polyester batts – 65/57
ADDITIONAL THICKNESS mm 178 234
CSR 783BOTH SIDES
• 1 x 13mm GYPROCKplasterboard CD.
(a) 75 Glasswool Partition batts 65/58 66/59
(b) 95 Comfortseal™ R2.0 batts – 67/60
(c) ASB4/TSB4 Polyester batts 64/57 65/58
(d) ASB5/TSB5 Polyester batts – 67/60
ADDITIONAL THICKNESS mm 204 260
CSR 782
BOTH SIDES
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 62/54 63/56
(b) 95 Comfortseal™ R2.0 batts – 64/57
(c) ASB4/TSB4 Polyester batts 61/53 62/54
(d) ASB5/TSB5 Polyester batts – 64/57
ADDITIONAL THICKNESS mm 178 234
CSR 781
BOTH SIDES
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 60/52 62/54
(b) 95 Comfortseal™ R2.0 batts – 63/55
(c) ASB4/TSB4 Polyester batts 59/51 61/53
(d) ASB5/TSB5 Polyester batts – 63/55
ADDITIONAL THICKNESS mm 178 234
CSR 780BOTH SIDES
• 1 x 13mm GYPROCKplasterboard CD.
ACOUSTICOPINION
PKA-A027
MEETSBCA
DiscontinuousConstruction
MasonryWall
Requirements
SYSTEM Nº
WALL LININGS
SYSTEM SPECIFICATION TYPICAL LAYOUT
• Plasterboard as per table, fixed to studs.
• Steel stud framing, as per table, at 600mm max. centres.
• Cavity infill, as per table.
• 12mm minimum cavity between masonry and framing.
• Single Brick, Block or Concrete wall with Rw as stated.
• 12mm minimum cavity between masonry and framing.
• Steel stud framing, as per table, at 600mm max. centres.
• Cavity infill, as per table.
• Plasterboard as per table, fixed to studs.
STUD DEPTH mm 64 92
CAVITY INFILL (Both Sides) Rw / Rw+Ctr
Masonry Wall Systems - Stud Both Sides.
The Red Book™D9.
TestedBrick,
Block orConcreteWall withRw > 46
Refer to MasonryWall Manufacturerfor FRL Details
TestedBrick,
Block orConcreteWall withRw > 51
Refer to MasonryWall Manufacturerfor FRL Details
(a) 75 Glasswool Partition batts 72/65 74/67
(b) 95 Comfortseal™ R2.0 batts – 75/68
(c) ASB4/TSB4 Polyester batts 71/64 73/66
(d) ASB5/TSB5 Polyester batts – 75/68
ADDITIONAL THICKNESS mm 204 260
CSR 791
BOTH SIDES
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 69/61 71/64
(b) 95 Comfortseal™ R2.0 batts – 72/65
(c) ASB4/TSB4 Polyester batts 68/60 70/62
(d) ASB5/TSB5 Polyester batts – 72/65
ADDITIONAL THICKNESS mm 178 234
CSR 790
BOTH SIDES
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 68/60 69/61
(b) 95 Comfortseal™ R2.0 batts – 70/62
(c) ASB4/TSB4 Polyester batts 67/59 68/60
(d) ASB5/TSB5 Polyester batts – 70/62
ADDITIONAL THICKNESS mm 178 234
CSR 789BOTH SIDES
• 1 x 13mm GYPROCKplasterboard CD.
(a) 75 Glasswool Partition batts 70/63 71/64
(b) 95 Comfortseal™ R2.0 batts – 72/65
(c) ASB4/TSB4 Polyester batts 69/62 70/63
(d) ASB5/TSB5 Polyester batts – 72/65
ADDITIONAL THICKNESS mm 204 260
CSR 788
BOTH SIDES
• 2 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 67/59 68/61
(b) 95 Comfortseal™ R2.0 batts – 69/62
(c) ASB4/TSB4 Polyester batts 66/58 67/59
(d) ASB5/TSB5 Polyester batts – 69/62
ADDITIONAL THICKNESS mm 178 234
CSR 787
BOTH SIDES
• 1 x 13mm GYPROCKSOUNDCHEKplasterboard.
(a) 75 Glasswool Partition batts 65/57 67/59
(b) 95 Comfortseal™ R2.0 batts – 68/60
(c) ASB4/TSB4 Polyester batts 64/56 66/58
(d) ASB5/TSB5 Polyester batts – 68/60
ADDITIONAL THICKNESS mm 178 234
CSR 786BOTH SIDES
• 1 x 13mm GYPROCKplasterboard CD.
MasonryWall
Requirements
SYSTEM Nº
WALL LININGSSTUD DEPTH mm 64 92
CAVITY INFILL (Both Sides) Rw / Rw+Ctr
Masonry Wall Systems - Stud Both Sides.ACOUSTICOPINION
PKA-A027
MEETSBCA
DiscontinuousConstruction
SYSTEM SPECIFICATION TYPICAL LAYOUT
• Plasterboard as per table, fixed to studs.
• Steel stud framing, as per table, at 600mm max. centres.
• Cavity infill, as per table.
• 12mm minimum cavity between masonry and framing.
• Single Brick, Block or Concrete wall with Rw as stated.
• 12mm minimum cavity between masonry and framing.
• Steel stud framing, as per table, at 600mm max. centres.
FIG. D1. CONCRETE COLUMN ENCASEMENT SYSTEM – FIRE RATED – STEEL FURRING MOUNTED.
FIG. D3 CONCRETE COLUMN ENCASEMENTSYSTEM – FIRE RATED – DIRECT FIXED.
Fix External Angle Bead and set all external angles
Anchor Clip Nº237 fixed with metal fasteners at 100mm max. from each end and 1200mm max. centres along column
Furring Channel Nº308 or Centre Fix Batten Nº333 at 600mm max. centres
GYPROCK FYRCHEK plasterboard fixed at 200mm maximum centres to all framing
600mm max.50mm max.
Steel reinforced concrete column
Screw fix each layer at 200mm maximum centres to steel framing
Anchor Clips Nº237 at 1200mm maximum vertical centres and Nº308 Furring Channel at 600mm maximum horizontal centres or Centre Fix Batten Nº333 directly fixed at 600mm maximum horizontal centres
GYPROCK FYRCHEK fixed to furring channel at 200mm max. centres
Track cut and fixed to furring channels at top and bottom of column
Apply External Angle Bead to all corners and set
Offset Butt Joints in consecutive layers by 300mm minimum
Fasten at butt joints with laminating screws at 200mm max centres
200mm max.
Fix External Angle Bead and set all external angles
Direct fasten each layer of GYPROCK FYRCHEK plasterboard with Tapcon™ 10g screws (or equivalent) at 400 x 400mm max. horizontal and vertical centres
400mm max.75mm max.
Steel reinforced concrete column
FIG. D2. CROSS SECTIONAL VIEW.
Note: Butt joints in single layer systems to bebacked by furring channel or nogging