    BASIC SHUTDOWN SYSTEMS & INTERLOCKS

    PT Chandra Asri Petrochemical Company

    Ciwandan, Cilegon, Indonesia

    July 2007CAUTIONARY NOTICE

    This document contains information which is proprietary to Kellogg Brown & Root, Inc. This information is to be held in confidence. No disclosure,

    reproduction or other use of this document is to be made without the prior written consent of the Kellogg Brown & Root, Inc.

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    2/31

    CONFIDENTIAL

    Shutdown System / Permissives

    • Low Fire Trip

    • Complete Trip

    • Permissives for Hydrocarbon Cracking

    • Permissives for Decoking

    • Permissives for Burner Lightoff 

    • Burner Lightoff Procedure

    • Permissives for MOV Switching

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    3/31

    CONFIDENTIAL

    Furnace Shutdown Systems

    • Low Fire Trip – Not a complete shutdown

     – Furnace remains hot (so-called hot standby condition)

     – Rarely results in mechanical work

    • Complete trip

     – No firing – Furnace cold

     – May require mechanical work if furnace has been cracking more

    than ~10 days

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    4/31

    CONFIDENTIAL

    Furnace Shutdown Systems

    LOW FIRE TRIP ACTIONS – 6376-IC3522-01 Sheet 1 of 9

     – Isolates HC Feed

     – Trips Main Burners Leaving Decoke Burners On – Resets Fuel Gas Control Valve Set Point

     – Dilution Steam Flow Set Same As SAD

     – Purge Steam To FPHT I Coil Initiated

     – Firing Rate Reduced To LFT Setpoint – Isolates Decoke Air (If In SAD Prior To LFT)

     – Isolates Decoke Water (If In SWD Prior To LFT)

     – Isolates Cracked Gas Analyzer 

     – Disables Total Feed Controllers

     – Isolates DMDS

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    5/31

    CONFIDENTIAL

    Low Fire Trip

    • Avoids a complete trip!

    • Furnace sent to “safe condition” (similar to decoke)

    • Thermal swing reduced

     – Furnace remains hot (no shut down)

     – Possibility of mechanical work reduced

    • Hydrocarbon operation resumed after decoking

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    6/31

    CONFIDENTIAL

    Furnace Shutdown Systems

    COMPLETE TRIP ACTIONS – 6376-IC3522-01 Sheet 1 of 9

     – Close Decoke Burners – Pilots Remain On

     – Open Main Burner XV-10850 – Isolates HC Feed

     – Isolates Decoke Air (If In SAD Prior To CT)

     – Isolates Decoke Water (If In SWD Prior To CT)

     – Dilution Steam Flow Reset To Complete Trip Rate – Isolate Quench Oil – Purge Quench Oil Nozzles

     – Isolates Cracked Gas Analyzer 

     – Isolates DMDS

     – Pilots Typically Stay Lit – Exception If CT Initiated By Operator or High-High-High Furnace Arch Pressure

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    7/31

    CONFIDENTIAL

    Complete Trip

    Furnace is shut down

    • Furnace is cold (pilots typically firing)

    • Mechanical work probably required.

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    8/31

    CONFIDENTIAL

    Low Fire Trip

    • Initiators for Low Fire Trip:

     – Low-Low hydrocarbon feed pass flow (any pass)

     – Low-Low dilution steam pass flow (any pass)

     – Low-Low SHP steam drum level

     – High-High SHP steam temperature

     – High-High arch pressure (Hot Furnace Only)

     – High-High transfer line temperature (either side of furnace)

     – Manual trip

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    9/31

    CONFIDENTIAL

    Low HC Feed Flow Trip

    LOW HC FEED

    FLOW

    LOW

    FIRE

    TRIP

    IF IN SWD,  ADD HC

    FEED, DS, DECOKE

    STEAM & DECOKEBFW FLOW RATES

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    10/31

    CONFIDENTIAL

    Low Dilution Steam Flow Trip

    LOW DILUTION

    STEAM FLOW

    LOW

    FIRE

    TRIP

    IF IN SAD,

     ADD DIL STEAM

    & PURGE STEAMFLOW RATES

    IF FURNACE

    COLD, DISABLE

    IF IN SWD,

    RESET

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    11/31

    CONFIDENTIAL

    Low Steam Drum Level Trip

    LOW STEAM

    DRUM LEVEL

    LOW

    FIRE

    TRIP

    60 SEC

    DELAY

    COMPLETE

    FURNACE

    TRIP

    REQUIRED TO PROTECT PQE’S

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    12/31

    CONFIDENTIAL

    High SHP Steam Temperature Trip

    HIGH-HIGH

    STEAM

    TEMP

    LOW

    FIRE

    TRIP

    8 MIN

    DELAY

    COMPLETE

    FURNACE

    TRIP

    HIGH STEAM

    TEMP

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    13/31

    CONFIDENTIAL

    High Arch Pressure Trip

    COMPLETE

    FURNACE

    TRIP

    30 SECDELAY

    FIREBOX

    COLD?

    YES

    30 SEC

    DELAY

    TRIP OPENID FAN

    DAMPER

    LOWFIRE

    TRIP

    30 SECDELAY

    HIGH ARCH

    PRESSURE

    (PT’s)

    HIGH ARCH

    PRESSURE(TT’s)

     ARCH

    PRESSURE

    HIGH?

    (TT’S)

    NO

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    14/31

    CONFIDENTIAL

    High Transfer Line Temperature Trip

    HIGH TRANSFERLINE TEMPERATURE

    (EITHER SIDE)

    COMPLETEFURNACE

    TRIP

    5 MIN.

    DELAY

    LOWFIRE

    TRIP

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    15/31

    CONFIDENTIAL

    Manual Low Fire Trip

    LOW

    FIRE

    TRIP

    MANUAL LOWFIRE TRIP

    CONTROL ROOM

    MANUAL LOW

    FIRE TRIP

    BURNER PANEL

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    16/31

    CONFIDENTIAL

    Checks After Low Fire Trip

    LOW TOTAL

    DILUTION

    STEAM FLOW

    COMPLETEFURNACE

    TRIP

    LOW

    FIRETRIP

    HIGH FLUE

    GAS TEMP

    5 MIN

    DELAY

    30 SEC

    DELAY

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    17/31

    CONFIDENTIAL

    Complete Trip

    Initiators for Complete Trip:

    • High-High / Low-Low fuel gas pressure

    • High-High-High SHP steam temperature

    • High-High-High Firebox Pressure

    • ID Fan Failure

    • Manual trip

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    18/31

    CONFIDENTIAL

    Fuel Gas Complete Trips

    COMPLETE

    FURNACETRIP

    LOW FUELGAS PRESSURE

    HIGH FUELGAS PRESSURE

    MANUAL

    COMPLETE TRIPCONTROL ROOM

    MANUAL

    COMPLETE TRIP

    BURNER PANEL

    HIGH ARCH

    PRESSURE (COLD)HIGH-HIGH-HIGH

     ARCH PRESSURE

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    19/31

    CONFIDENTIAL

    Pilot Trips

    PILOT

    TRIP

    LOW PILOTGAS PRESSURE

    HIGH PILOT

    GAS PRESSURE

    MANUAL

    COMPLETE TRIP

    CONTROL ROOM

    MANUAL

    COMPLETE TRIP

    BURNER PANEL

    HIGH-HIGH-HIGH ARCH PRESSURE

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    20/31

    CONFIDENTIAL

    Interlocks for MOV Switching

    Permissives for MOV Switching• Analyzer sample valves closed

    • HC feed isolated

    • Quench oil isolated

    • Decoke air isolated

    • In “Decoke” mode

    • DMDS isolated

    • Steam flow rates above minimum (Administrative)

    Permissive failure after decoking commences causes alarm

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    21/31

    CONFIDENTIAL

    MOV Switching - From Transfer Line to Decoke Line

    • Control room operator activates local panel

    • Field operator begins transfer line valve (TLV) closure

     – High Transfer line pressure alarm active

    • Operator stops TLV movement based on furnace pressure and/or TLV  ∆P

    • Field operator begins opening of decoke line valve (DLV).

     – Low Transfer line pressure alarm active

    • Operator stops DLV movement based on transfer line pressure and/or TLV ∆P

    • If Transfer Line Low DP or High Pressure Occurs valve movement stopsuntil corrected

    • Close TLV - Low TLV  ∆P alarm disabled

    • Open DLV - High transfer line pressure alarm disabled.

    MOV Switching Sequence From Decoke Line to Transfer Line

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    22/31

    CONFIDENTIAL

    MOV Switching Sequence - From Decoke Line to Transfer Line

    • Control room operator activates local panel

    • Field operator begins DLV closure

     – High Transfer line pressure alarm active

    • Operator stops DLV movement based on transfer line pressureand/or TLV  ∆P

    • Field operator begins opening of TLV – Low Transfer line pressure alarm active

    • If Transfer Line Low DP or High Pressure Occurs valve movement stops

    until corrected

    • Close DLV - Low TLV  ∆P alarm disabled

    • Open TLV - High transfer line pressure alarm disabled.

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    23/31

    CONFIDENTIAL

    Interlocks for Hydrocarbon Service

    • Decoke line MOV 100% closed

    • Decoke air isolated

    • Transfer line MOV 100% open

    • Decoke/Cracking Mode Switch in Cracking position

    • Steam flow rates above minimum (Administrative)

    Permissive failure after cracking commences causes an alarm

    I l k O D k Ai (SAD)

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    24/31

    CONFIDENTIAL

    Interlocks to Open Decoke Air (SAD)

    • Transfer line MOV 100% closed

    • Decoke line MOV 100% open

    • HC feed isolated

    • Quench oil isolated

    • Decoke/Cracking Mode Switch in Decoke position

    • Chromatograph isolated

    • Steam flow rates above minimum (Administrative)

    Permissive failure after decoking commences causes an alarm

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    25/31

    CONFIDENTIAL

    Burner Lightoff System

    • Checks permissives

    • Purges firebox

    • Checks for burner fuel gas cock closure

    • Includes temporary bypasses for:

     – High fuel gas pressure

     – Low fuel gas pressure

    • Firebox purge & fuel gas cock closure tests run in

    parallel to save time

    • Includes bypass switch for pilots usage

    I t l k / P d f B Li ht ff

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    26/31

    CONFIDENTIAL

    Interlocks / Procedure for Burner Light-off 

    Burner Purge Panels:

    • ESD Console Panel

    • Outside Burner Panel• DCS Switches, Lights

    F l G C t l

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    27/31

    CONFIDENTIAL

    Fuel Gas Control

    QIC

     AI

     ATM @ SAFE

    LOCATION

    Burner Header 

    PIC

    FO

    Burner Light Off Sequences

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    28/31

    CONFIDENTIAL

    Burner Light-Off Sequences

    There are four separate burner light-off sequences

    1. Pilot, Main, and Decoke Burner Light-Off 

    1. Furnace is cold or Complete Trip with Pilot Trip

    2. Pilots lit first then Main and Decoke burners can be tested and lit

    2. Main & Decoke Burner Light-Off 

    1. Furnace has had Complete Trip but Pilots remain lit

    2. Main and Decoke burners tested together and enabled

    3. Main Burner Light-Off 1. Furnace has had Low Fire Trip but Pilots and Decoke burners remain lit

    2. Main burners are tested and enabled

    4. Main & Decoke Burner Light-Off – Pilots Bypassed

    1. Furnace has had Complete Trip or is Cold

    2. Main and Decoke burners tested together and enabled

     All three sequences follow a similar pattern

    Burner Light Off Sequence Firebox Purge

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    29/31

    CONFIDENTIAL

    Burner Light-Off Sequence – Firebox Purge

    • If furnace is hot and permissives satisfied, firebox purge

    starts automatically.

    • If furnace is cold, operator must initiate firebox purge.

    • Must satisfy all permissives for 15 minutes.

    • Purge complete light illuminates.

    Burner Light Off Sequence Cock Closure Test

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    30/31

    CONFIDENTIAL

    Burner Light-Off Sequence – Cock Closure Test

    • Field operator closes all burner fuel gas cocks

    • Check that burner fuel gas header pressure is low

    • Operator starts 5 minute timer: – Fuel gas commissioned to spring loaded valve

     – Open isolation valve upstream of spring loaded valve

     – Operator holds spring loaded valve open

     – Fuel gas flows through RO into burner fuel gas header 

     – Fuel gas header pressure rises to set point?

     – Close isolation valve upstream of spring loaded valve

    Burner Light Off Sequence Light Burners

  • 8/17/2019 Section 04 Shutdowns & Interlocks CAPC

    31/31

    CONFIDENTIAL

    Burner Light-Off Sequence – Light Burners

    • Firebox purge & cock closure tests successful• 5 minute timer starts automatically

     – Low & High fuel gas pressure trips bypassed for 5 minutes

     – Fuel gas commissioned to fuel gas header 

     – Operator adjusts fuel gas vent to stabilize pressure between Low

    & High fuel gas pressure trip set points (PCV-1082

    recommended setpoint ~ 0.4 kg/cm2g)

     – Light burners as required

     – Close vent valve when sufficient burners are lit to allow CV to

    control