Prepared By Operations Division April 2, 2007 FIREFIGHTER NEAR MISS Auto Fire with Compressed Natural Gas (CNG) Fuel Tank Explosion
38

Seattle CNG Near Miss

Nov 08, 2014

Download

Documents

sprashant5

Seattle CNG Near Miss
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Seattle CNG Near Miss

Prepared By Operations Division

April 2, 2007

Prepared By Operations Division

April 2, 2007

FIREFIGHTERNEAR MISS

Auto Fire withCompressed Natural Gas

(CNG) Fuel Tank Explosion

FIREFIGHTERNEAR MISS

Auto Fire withCompressed Natural Gas

(CNG) Fuel Tank Explosion

Page 2: Seattle CNG Near Miss

Seattle Fire Department22

Arson: Incident #26564 Arson: Incident #26564

• Dispatch 0230 hours for car fire (E10)

• E10 arrived and requested FIB for multiple vehicles with possible structural exposures (freeway columns and overpasses)

• 12 vehicles damaged or destroyed

• Firefighter near miss when CNG vehicle exploded as E10 crew approached with a handline (approximately 50-75’ away)

• Dispatch 0230 hours for car fire (E10)

• E10 arrived and requested FIB for multiple vehicles with possible structural exposures (freeway columns and overpasses)

• 12 vehicles damaged or destroyed

• Firefighter near miss when CNG vehicle exploded as E10 crew approached with a handline (approximately 50-75’ away)

Page 3: Seattle CNG Near Miss

Seattle Fire Department33

FireFireGarageGarage

FireFireGarageGarage

Page 4: Seattle CNG Near Miss

Seattle Fire Department44

Royal Brougham

Royal Brougham

88thth A

ve S

ou

th A

ve S

ou

th

Access GateAccess GateAccess GateAccess Gate

E10

E10

E10

E10

Page 5: Seattle CNG Near Miss

Seattle Fire Department55

E10 parked outsideE10 parked outsidethe gate herethe gate hereE10 parked outsideE10 parked outsidethe gate herethe gate here

Debris from the explosion was thrown up to Debris from the explosion was thrown up to 100’ in all directions including on the over-100’ in all directions including on the over-

passes above the incident.passes above the incident.

Debris from the explosion was thrown up to Debris from the explosion was thrown up to 100’ in all directions including on the over-100’ in all directions including on the over-

passes above the incident.passes above the incident.

Page 6: Seattle CNG Near Miss

Seattle Fire Department66

++++++++++++ ++++

BackhoeBackhoeBackhoeBackhoe

Fuel tankFuel tank(original location)(original location)Fuel tankFuel tank(original location)(original location)

Trunk lidTrunk lidTrunk lidTrunk lid

Bumper frameBumper frameBumper frameBumper frame

Roof debrisRoof debrisRoof debrisRoof debris

Roof debrisRoof debrisRoof debrisRoof debris

100’

Page 7: Seattle CNG Near Miss

Seattle Fire Department77

Honda CNG VehicleHonda CNG Vehicle

Page 8: Seattle CNG Near Miss

Seattle Fire Department88

Page 9: Seattle CNG Near Miss

Seattle Fire Department99

Rear of vehicleRear of vehicle

Page 10: Seattle CNG Near Miss

Seattle Fire Department1010

Roof is blown completelyRoof is blown completelyoff vehicle and doors blownoff vehicle and doors blownopenopen

Page 11: Seattle CNG Near Miss

Seattle Fire Department1111

Page 12: Seattle CNG Near Miss

Seattle Fire Department1212

Page 13: Seattle CNG Near Miss

Seattle Fire Department1313

Page 14: Seattle CNG Near Miss

Seattle Fire Department1414

Page 15: Seattle CNG Near Miss

Seattle Fire Department1515

Metal mountingMetal mountingstraps for CNG tankstraps for CNG tank

Metal mountingMetal mountingstraps for CNG tankstraps for CNG tank

Page 16: Seattle CNG Near Miss

Seattle Fire Department1616

Trunk lidTrunk lidTrunk lidTrunk lid

Page 17: Seattle CNG Near Miss

Seattle Fire Department1717

Tank landed here,Tank landed here,moved down hill to heremoved down hill to herefor extinguishmentfor extinguishment

Tank landed here,Tank landed here,moved down hill to heremoved down hill to herefor extinguishmentfor extinguishment

Page 18: Seattle CNG Near Miss

Seattle Fire Department1818

Rear bumper frame 90’+ awayRear bumper frame 90’+ away

Page 19: Seattle CNG Near Miss

Seattle Fire Department1919

Bumper shrapnelBumper shrapnelNote burn marks onNote burn marks onground. ground.

Page 20: Seattle CNG Near Miss

Seattle Fire Department2020

Roof section about 75’ awayRoof section about 75’ awayRoof section about 75’ awayRoof section about 75’ away

Page 21: Seattle CNG Near Miss

Seattle Fire Department2121

This is your only warning ofThis is your only warning ofa CNG – fueled vehicle. Typically a CNG – fueled vehicle. Typically located on the trunk lid or bumperlocated on the trunk lid or bumper

This is your only warning ofThis is your only warning ofa CNG – fueled vehicle. Typically a CNG – fueled vehicle. Typically located on the trunk lid or bumperlocated on the trunk lid or bumper

Page 22: Seattle CNG Near Miss

Seattle Fire Department2222

Page 23: Seattle CNG Near Miss

Seattle Fire Department2323

Composite tank is carbon-fiber / fiberglassComposite tank is carbon-fiber / fiberglasswrapped for strength – similar to our SCBA tanks.wrapped for strength – similar to our SCBA tanks.Composite tank is carbon-fiber / fiberglassComposite tank is carbon-fiber / fiberglasswrapped for strength – similar to our SCBA tanks.wrapped for strength – similar to our SCBA tanks.

Page 24: Seattle CNG Near Miss

Seattle Fire Department2424

Page 25: Seattle CNG Near Miss

Seattle Fire Department2525

Page 26: Seattle CNG Near Miss

Seattle Fire Department2626

Page 27: Seattle CNG Near Miss

Seattle Fire Department2727

Page 28: Seattle CNG Near Miss

Seattle Fire Department2828

Tank blown approximatelyTank blown approximately95’ from the vehicle95’ from the vehicle

Tank blown approximatelyTank blown approximately95’ from the vehicle95’ from the vehicle

Page 29: Seattle CNG Near Miss

Seattle Fire Department2929

Page 30: Seattle CNG Near Miss

Seattle Fire Department3030

August 07, 2003

Airport Taxis, Shuttles Convert to Natural GasNew contract requires fleet conversions to improve air quality

The Port of Seattle Commission today authorized the renewal of contracts with two major providers of ground transportation at Seattle-Tacoma International Airport. The contracts, with the Seattle Tacoma International Taxi Association (STITA) and Shuttle Express, will require the two organizations to make major investments toconvert their fleets to clean-burning natural gas.

Under its new contract, STITA will be required to convert its entire 160-cab fleet to natural gas in the next three years. By converting more quickly, STITA will earn the right to extend the contract from five to seven years.

Page 31: Seattle CNG Near Miss

Seattle Fire Department3131

Historical InformationHistorical Information

• Several NHTSA (National Highway Traffic Safety Administration) investigations– Example: January 27, 2003; Ford Crown

Victoria on fire with flame impingement on CNG tank. The tank failed catastrophically prior to Pressure Relief Device (PRD) functioning.

– Vehicle recall with dealers installing additional insulation behind back seat.

– Number of vehicles still needing repair???

• Several NHTSA (National Highway Traffic Safety Administration) investigations– Example: January 27, 2003; Ford Crown

Victoria on fire with flame impingement on CNG tank. The tank failed catastrophically prior to Pressure Relief Device (PRD) functioning.

– Vehicle recall with dealers installing additional insulation behind back seat.

– Number of vehicles still needing repair???

Page 32: Seattle CNG Near Miss

Seattle Fire Department3232

Code of Federal RegulationsCode of Federal Regulations

• CFR 49, Part 571– Standard 304

Compressed Natural Gas Fuel Container Integrity

Flame Test Standard:Flame impingement generating 1550-1650° F. at the surface for the length of the cylinder for 20 minutes or until fuel is completely vented through PRV.

• CFR 49, Part 571– Standard 304

Compressed Natural Gas Fuel Container Integrity

Flame Test Standard:Flame impingement generating 1550-1650° F. at the surface for the length of the cylinder for 20 minutes or until fuel is completely vented through PRV.

Page 33: Seattle CNG Near Miss

Seattle Fire Department3333

CNG PropertiesCNG Properties

• Compressed to 3,600 psi in fuel cylinder

• CNG rated at 117 octane fuel

• BTU per # = 22,800 (gasoline = 18,900)

• Not a liquid when compressed (it becomes a very close dense gas)

• Not the same as Liquified Natural Gas – LNG (cryogenic: -260° to become liquified)

• Lighter than air when released ( .6 air)

• Compressed to 3,600 psi in fuel cylinder

• CNG rated at 117 octane fuel

• BTU per # = 22,800 (gasoline = 18,900)

• Not a liquid when compressed (it becomes a very close dense gas)

• Not the same as Liquified Natural Gas – LNG (cryogenic: -260° to become liquified)

• Lighter than air when released ( .6 air)

Page 34: Seattle CNG Near Miss

Seattle Fire Department3434

CNG PropertiesCNG Properties

• LEL / UEL = 4 – 16% (gasoline = 1.3 – 7.6)

• 1 cubic foot of CNG = 245 cu.ft. of natural gas at sea level (uncompressed)

• 1 cubic foot of CNG weighs 13#• 5.66# = 1 Gasoline Gallon Equivalent (GGE)

• Honda Civic tank = 8 GGE• Note: 1 gallon of gasoline properly vaporized has

the explosive equivalency of 83 pounds of dynamite (CDC).

• LEL / UEL = 4 – 16% (gasoline = 1.3 – 7.6)

• 1 cubic foot of CNG = 245 cu.ft. of natural gas at sea level (uncompressed)

• 1 cubic foot of CNG weighs 13#• 5.66# = 1 Gasoline Gallon Equivalent (GGE)

• Honda Civic tank = 8 GGE• Note: 1 gallon of gasoline properly vaporized has

the explosive equivalency of 83 pounds of dynamite (CDC).

Page 35: Seattle CNG Near Miss

Seattle Fire Department3535

Cylinder PropertiesCylinder Properties

• Four Cylinder Types:– Type 1: all metal (steel or aluminum)– Type 2: hoop wrapped steel or aluminum– Type 3: fully wrapped steel or aluminum– Type 4: all-composite (non-metallic)*

*Early model Honda Civic uses Type 4;later models use Type 3

• Four Cylinder Types:– Type 1: all metal (steel or aluminum)– Type 2: hoop wrapped steel or aluminum– Type 3: fully wrapped steel or aluminum– Type 4: all-composite (non-metallic)*

*Early model Honda Civic uses Type 4;later models use Type 3

Page 36: Seattle CNG Near Miss

Seattle Fire Department3636

Honda Civic Tank DesignHonda Civic Tank Design

Page 37: Seattle CNG Near Miss

Seattle Fire Department3737

Honda Civic Tank DesignHonda Civic Tank Design

Note: The PRD (pressure relief device) activates similar to a fusible link (it fails versus resealing like a spring-assisted pressure reducing valve – PRV). The gas is vented out the vent tube until the tank is empty. Discharge time depends on fuel level.

Note: The PRD (pressure relief device) activates similar to a fusible link (it fails versus resealing like a spring-assisted pressure reducing valve – PRV). The gas is vented out the vent tube until the tank is empty. Discharge time depends on fuel level.

Page 38: Seattle CNG Near Miss

Seattle Fire Department3838

Lessons Learned /Best PracticesLessons Learned /Best Practices• Approach from 45° angle to vehicle ends

• Be aware of CNG vehicles– Cabs, city vehicles, shuttles

• Look for CNG placards

• Watch for other hazards, i.e. bumper struts; hood and tailgate struts; airbags; burning fuel runoff; hazardous vehicle contents; exploding tires; other traffic

• Consider cooling streams from a distance

• Approach from 45° angle to vehicle ends

• Be aware of CNG vehicles– Cabs, city vehicles, shuttles

• Look for CNG placards

• Watch for other hazards, i.e. bumper struts; hood and tailgate struts; airbags; burning fuel runoff; hazardous vehicle contents; exploding tires; other traffic

• Consider cooling streams from a distance