8

Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

Aug 06, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

Screened separable connectorsEnsto Underground

Page 2: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

2

Ensto’s underground solutionssupplemented with separable connectors

Safe and reliable screened separable connectors sup-plement Ensto’s under-ground solutions. In addi-tion to the heat and cold shrink connectors, the product range now includes 250 A elbow connector set URZJ 250 and straight con-nector set URZTJ 250, as well as a 630 A deadbreak set for use at voltages up to 24 kV.

Ensto’s screened connectors are used for installing plastic cables (12 and 24 kV) for transformers, motors, and especially SF6 switchgears both indoors and outdoors. Installation is quick and easy.

Page 3: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

3

Ensto’s screened connectors havemany benefits

The screened separable connectors are safe to use and easy to install • The screened construction provides gre-

ater personal safety and reliability during use

• The construction is watertight as well• The connectors do not require a lot of

space, and there is no need for minimum installation clearances

• Disconnecting and connecting is quick and easy

• There is no need for any special tools • The cable can be connected to the network

immediately after installation• The connectors are manufactured from fle-

xible silicone rubber (USQJ 630) or EPDM rubber (URZJ 250 and URZTJ 250)

Tested According to StandardsThe connectors are suitable for switchgears as to DIN 47636 and EN 50181. They are tested according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard.

Page 4: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

4

type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOnØ MM

URZTJ250.35 35 mm2 6418677438127 16.8-19.2

URZTJ250.50 50 mm2 6418677438134 19.7-22 .5

URZTJ250.70 70 mm2 6418677438141 21.5-24.6

URZTJ250.95 95 mm2 6418677438158 21.5-24.6

URZTJ250.120 120 mm2 6418677438165 23.9-27.3type 6/10 (12) kV ean DIaMeteR OVeR InSULatIOn

Ø MM

URZJ250.5 50 mm2 6418677443985 16.8-19.2

URZJ250.7 70 mm2 6418677443992 16.8-19.2

URZJ250.9 95 mm2 6418677444005 19.7-22 .5

URZJ250.12 120mm2 6418677443978 19.7-22 .5eaRthIng Set fOR aMXaMk (WISkI) (10/20k V)

SJCW70240.2 70-240 mm2 6418677433276 23.0-39.0

URZJ 250 Screened ElbowConnector

Contact Pin

Inner semi-conducting layer

EPDM insulating

Outer semi-conducting layer

Cable lug

Capacitivemeasuring point

Cable’s PEX- insulation

Use• For the installation of plastic cables in

transformers, motors, and especially SF6 switchgears

• For indoor and outdoor installations• Maximum operating voltage of 24 kV• Nominal current 250 A• Cables:

- Plastic cables (XLPE) - Copper and aluminium cables, 35-

120 mm2

URZJ 250 Screened Elbow Connector 250 A

KitDelivery is in complete three phase kits inclu-ding all necessary parts and accessories (e.g. compression cable lugs, pin contact earthing braid, silicone grease, and installation instruc-tions).

Note! Earthing Kit for the AHXAMK-W Cable must be ordered separately.

Electrical ValuesMaximum operating voltage 24 kVImpulse voltage test, 1.2/50 μs 125 kVPartial dischargetest less than 10 pC, 20 kVVoltage test (AC)(1 min, 50 Hz) 54 kVNominal current 250 A

Note! The values are based on the IEC stan-dard. They are not the maximum tolerances of the product.

Page 5: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

5

URZTJ 250 Screened StraightConnector

Use• For the installation of plastic cables in

transformers, motors, and especially SF6 switchgears

• For indoor and outdoor installations• Maximum operating voltage of 24 kV• Nominal current 250 A • Cables:

- Plastic cables (PEX) (XLPE)- Copper and aluminium cables, 35-

120 mm2

type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOnØ MM

URZTJ250.35 35 mm2 6418677438127 16.8-19.2

URZTJ250.50 50 mm2 6418677438134 19.7-22 .5

URZTJ250.70 70 mm2 6418677438141 21.5-24.6

URZTJ250.95 95 mm2 6418677438158 21.5-24.6

URZTJ250.120 120 mm2 6418677438165 23.9-27.3type 6/10 (12) kV ean DIaMeteR OVeR InSULatIOn

Ø MM

URZJ250.5 50 mm2 6418677444029 16.8-19.2

URZJ250.7 70 mm2 6418677444036 16.8-19.2

URZJ250.9 95 mm2 6418677444043 19.7-22 .5

URZJ250.12 120mm2 6418677444012 19.7-22 .5eaRthIng Set fOR aMXaMk (WISkI) (10/20k V)

SJCW70240.2 70-240 mm2 6418677433276 23.0-39.0

Contact Pin

Inner semi-conducting layerEPDM insulating

Outer semi-conducting layer

Cable lug

Capacitivemeasuring point

Cable’s PEX- insulation

Electrical ValuesMaximum operating voltage 24 kVImpulse voltage test, 1.2/50 µs 125 kVPartial discharge test less than 10 pC, 20 kVVoltage test (AC) (1 min, 50 Hz) 54 kVNominal current 250 A

Note! The values are based on the IEC stan-dard. They are not the maximum tolerances of the product.

KitDelivery is in complete three phase kits inclu-ding all necessary parts and accessories (e.g. compression cable lugs, pin contact earthing braid, silicone grease, and installation instruc-tions).

Note! Earthing Kit for the AHXAMK-W Cable must be ordered separately

URZTJ 250 Screened Straight connector 250 A

Page 6: Screened separable connectors · 2020. 8. 26. · according to the IEC 61442 standard and meet the requirements of IEC 60502-4 standard. 4 type 12/20 (24) kV ean DIaMeteR OVeR InSULatIOn

6

USQJ 630 ScreenedSeparable Connector 630A

Fixing screw M16

Inner semi-conducting layer

Silicone insulatingOuter semi-

conducting layerCable’s PEX-

insulation

Semiconductingprotecting cap

Cable lug

Capacitivemeasuring point

Cableadapter

Use• For the installation of plastic cables in

transformers, motors, and especially SF6 switchgears

• For indoor and outdoor installations• Maximum operating voltage of

24 kV• Nominal current 630 A • Cables:

- Plastic cable (XLPE)- Copper and aluminium cables, 35-300

mm2

Electrical ValuesMaximum operating voltage 24 kVImpulse voltage test, 1.2/50 µs 125 kVVoltage test (AC) (1 min, 50 Hz) 54 kV Nominal current 630 A

Note! The values are based on the IEC stan-dard. They are not the maximum tolerances of the product.

KitDelivery is in complete three phase kits inclu-ding all necessary parts and accessories (e.g. shear head bolt, cable lugs, earthing braid, adapters (stress control), fixing screws, silicone grease, and installation instructions).

Note! Earthing Kit for the AHXAMK-W Cable must be ordered separately

type 6/10 (12) kV 12/20 (24) kV ean DIaMeteR OVeR InSULatIOnØ MM

USQJ630.1 50-70 mm2 25-35 mm2 6418677438004 16.3-18.6

USQJ630.2 50-70- mm2 6418677438011 19.7-22 .5

USQJ630.25 95-120 mm2 6418677444050 19.7-22 .5

USQJ630.3 150-185 mm2 95-120 mm2 6418677438028 22.9-26.1

USQJ630.4 240 mm2 150 mm2 6418677438035 24.5-28.0

USQJ630.5 185-240 mm2 6418677438042 27.7-31.7

USQJ630.55 300 mm2 6418677444067 2 2 7.7-31.7

USQJ630.6 300 mm2 6418677438059 32.5-37.2eaRthIng Set fOR aMXaMk (WISkI) (10/20 kV)

SJCW2595.1 constant force spring 25-95 mm2 6418677446351 17.0-28.0

SJCW70240.2 constant force spring 70-240 mm2 6418677433276 2 2 3.0-39.0

SJCW70240.3 hose clip 35-240 mm2 6418677445323 2 20.2-37.0