48V DC Distribution Rack DOF 159 MHz Base Station Channel Bank Rack CR-5 FHP Filter Duplexer FHP Tx/Rx #1 Motorola FHP Tx/Rx #2 Motorola DVM6-45 MW Repeater Rack CR-2 MAS Call Box Base Station Rack CR-1 G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigL1_QuincyFHP_ShelterFloorPlan_20040422.vsd 04/12/13 Figure L1 Quincy FHP (3-3425) Shelter Floor Plan Scale: 3/8" = 1'-0" RWIS Rack Page L5 of 7 103
25
Embed
Scale 3/8 = 1'-0 - MyFlorida.com · One Eltek Valere integrated power system shall be installed in accordance with this Appendix and Section 2.3 of this Scope of Services. IP Address:
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
The Vendor shall furnish and install the following equipment at the Monticello DOT site located 0.5 miles north of US-19 and I-10 interchange at maintenance yard in Monticello, FL.
A. One Exide Absolyte GP series battery plant model number M87-024-05007-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.68.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.68.19
C. One Eltek Valere integrated power system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.68.20
Subnet Mask: 255.255.254.0
Gateway: 172.16.68.19
114
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page N4 of 7
TABLE N1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
50G07 Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
Q4820N-F19DB01-VC Integrated Power System 1
CBB060E Battery Disconnect 1
CBB010M 10 A Circuit breakers 12
BC2000-A51-10VC System Controller w/ Ethernet Port 1
The Vendor shall furnish and install the following equipment at the Greenville site located on the north side of I-10, 0.6 miles west of the intersection of I-10 and US-221.
A. One Exide Absolyte GP series battery plant model number M87-024-05005-R19AALV shall
be installed in accordance with this Appendix and Section 2.2 of this Scope of Services.
The new battery plant shall be installed in the same location as the removed battery plant.
The Vendor shall replace the existing cable with 1/0 AWG stranded. Red jacketed cable
shall be used for -48 VDC connections and black jacketed cable shall be used for the return.
B. The Generex BACS battery management system shall be installed in accordance with this
Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.66.22
Subnet Mask: 255.255.254.0
Gateway: 172.16.66.19
C. One Eltek Valere -48VDC Integrated Power Distribution System shall be installed in
accordance with this Appendix and Section 2.3 of this Scope of Services.
IP Address: 172.16.66.20
Subnet Mask: 255.255.254.0
Gateway: 172.16.66.19
121
FLORIDA DEPARTMENT OF TRANSPORTATION
I-10 BATTERY PLANT REPLACEMENT
Page O4 of 7
TABLE O1 – MAJOR EQUIPMENT LIST
Model Number Description QTY.
50G05 Exide Battery 19" rack mount 1
AMGBACS 1001 24-2V Master Kit
BACS management system including webmanager, C40 modules with temperature sensor, measuring cables, and bus cables
1
TCL 024-112DC TracoPower DC/DC Converter 1
DR 24500 Atlantic Scientific DIN Rail to Mount BACS Webmanager
1
Q4820N-F19DB01-VC Integrated Power System 1
CBB060E Battery Disconnect 1
CBB010M 10 A Circuit breakers 6
BC2000-A51-10VC System Controller w/ Ethernet Port 1
TPP10 Battery Thermal Probe? 1
V1500A-VC V-Series 30A rectifier 2
BAF19 19”single top baffle - 1U 1
VBLANK-VC Blank V-series rectifier chassis 2
ZB24540 Atlantic Scientific Ethernet SPD 4
122
SCALE: 1/2"=1'
MAS
Minute Man
Enterprise
E750
A/C
Channel Bank/
BPS Network
Rack
DVM6-45
Radio
Rack
-48 Volt
Power Plant
& Batteries
Figure O1Greenville
Shelter Floor Plan
G:\FDOTGC\Battery Replacement\I-10 Replacement 2013\Appendix A\FigO1_Greenville As Built Floor Plan.vsd04/12/13