7/30/2019 SAT-S & D System
1/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 1 of 23
Author
Title Name Company Sign / Date
Validation engineer Mr.Abhijit Thete
Firstname Lastname
Christ Nishotech
Approved by
Title Name Company Sign / Date
Project Manager Mr.Yogesh Bendre
Firstname Lastname
Christ Nishotech
Project leader Mr.Bhavik Bhatti
Firstname Lastname
Christ Nishotech
Project leader
Firstname Lastname
TERAPIA-RANBAXI
QA
Firstname Lastname
TERAPIA-RANBAXI
Revision history
Revision Change Date Initials
0 First issue 12.03.07 MC
7/30/2019 SAT-S & D System
2/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 2 of 23
CONTENTS
1.0 SAT Plan................................................................................................................31.1 Introduction.................................................................................................................31.2 Abbreviation................................................................................................................31.3 Purpose of the tests................................................................................................... 31.4 Object Description......................................................................................................31.5 Performance................................................................................................................3
1.5.1 Responsibilities......................................................................................................31.5.2 Good Testing Practice...........................................................................................41.5.3 How to fill in the tests /inspections.........................................................................41.5.4 Deviation handling.................................................................................................5
1.6 Acceptance criteria.....................................................................................................51.7 SAT Results................................................................................................................ 5
2.0 Tests.......................................................................................................................52.1 Mechanical & Documentation Inspection.................................................................6
2.1.1 P&ID...................................................................................................................... 62.1.2 Components..........................................................................................................72.1.3 Air gap to drain...................................................................................................... 8
2.2 Hardware Acceptance Tests (IQ)...............................................................................92.2.1 Main Switch........................................................................................................... 92.2.2 Hardware operating environment.........................................................................10
2.3 System Acceptance Tests (OQ)...............................................................................112.3.1 Software Version................................................................................................. 112.3.2 Back-up............................................................................................................... 12
2.4 Operation tests (OQ)................................................................................................ 132.4.1 Leak Test.............................................................................................................132.4.2 Operation of UV 301.1.1......................................................................................142.4.2 Operation of UV 301.1.2......................................................................................152.4.3 Operation, Purified water system in normal mode................................................162.4.4 Sanitisation PW storage & loop control................................................................17
2.4.5 System Parameters.............................................................................................182.4.6 Water Quality.......................................................................................................192.4.7 Deviation list........................................................................................................ 20
........................................................................................................................................ 22
3.0 SAT Report..........................................................................................................223.1 Purpose of the report...............................................................................................223.2 Deviations................................................................................................................. 223.3 Retests.......................................................................................................................223.4Final Approval............................................................................................................23
Handover of the water treatment system...............................................................23
7/30/2019 SAT-S & D System
3/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 3 of 23
1.0 SAT Plan
1.1 Introduction
The SAT for Purified water Storage & loop control system shall show that the system is installed andoperates in accordance with the design specifications. The SAT is divided into four test sections:
Mechanical & Documentation Inspections (IQ).
Hardware Acceptance Tests (IQ)
Software Acceptance Tests (OQ)
Operation Test (OQ)
1.2 Abbreviation
GTP Good Testing PracticeIQ Installation QualificationN/A Not ApplicableOQ Operation QualificationP&ID Process & Instrumentation DiagramSAT Site Acceptance Test
PWS Purified Water System
1.3 Purpose of the tests
To test, inspect and show that the PW storage & loop control system is installed correctly accordingto design specifications.
1.4 Object Description
Product : Purified water Storage & loop control system.Function : Storage & Distribution of Purified water.Manufacturer : Christ Nishotech Water Systems Pvt. Ltd.Project no. : CWI 147
Year of manufacture : 2007
1.5 Performance
The tester shall first read this SAT Plan section, then perform the tests and finally fill in the Report inthe end of this document. The performance of the specific Site Acceptance Tests is described foreach test in the test sheets.
1.5.1 ResponsibilitiesThe person who performs the tests (Tester) is responsible for the execution of the tests. The testerconfirms with his/her initials that the test is performed correctly. A second person, (witness) checks if
7/30/2019 SAT-S & D System
4/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 4 of 23
the test was correctly performed and that the result was in accordance with the acceptance criteria
and if not, that a deviation report is filled in.
1.5.2 Good Testing Practice
A (archive resistance) blue pen shall be used for the SAT tests and for approvals. For the correctionsin the attached design documents (such as the P&ID or the circuit diagram) a red pen will be used.Correction fluid and other correction techniques that obscure the original entry should not be used.Spelling mistakes and other changes shall be corrected as follows:
Ex) Installation 20/01/04 Initials
Deviations are recorded and traceable. Fields in a test, that are not filled out, shall be clearly markedas N/A (not applicable).Attachments such as P&ID and component list shall be marked with the name of the SAT test, anddate and initials of the tester. This shall be written on the front page.
Ex) Attachment to SAT 2.1.2 P&ID 20/01/04 Initials
When the SAT is performed are the documents reviewed for correctness and completeness before
the SAT Report section is filled in.
1.5.3 How to fill in the tests /inspections
Inspection name
Inspection procedure
Needed document(s) / equipment
Acceptance criteria
OK / Deviation no
1)Date
2)
Initials
3)
Witnessed by
4)
1) The acceptance criteria is specified in this square and if values are to be recorded there will alsobe a result table here. Fill then in the actual value and Pass or Fail.
Description Required value Actual value Result (Pass /Fail)
Ex) Temperature atTT270.6.3
> 80C
7/30/2019 SAT-S & D System
5/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 5 of 23
2) If the acceptance criteria is fulfilled Pass is written in this square. If not, Fail and deviation
number(s) are written, and a deviation report is filled in. (See deviation handling)3) Comment. This field are used for instance for explanation, or relevant information. For deviations,
a deviation report will be filled in.
4) Date of the execution of the test /inspection and initials of the tester.
5) To be signed by the customer if present during the SAT. Otherwise N/A will be written.
1.5.4 Deviation handling
A Deviation report regarding SAT is filled in if the result of a test is not according to the acceptancecriteria. It could be more than one deviation report per test, and then all numbers have to be filled in,on the test sheet.
1.6 Acceptance criteria
The acceptance criteria for each Site Acceptance Test are specified in the test sheets.
1.7 SAT Results
The result of the SAT will be concluded in the SAT Report section.
2.0 Tests
Signature list for test /inspection personnel
Company Name
(readable in block letters)
Signature / Date
Christ Nishotech
Christ Nishotech
TERAPIA-RANBAXI
TERAPIA-RANBAXI
Attachments to this Site acceptance test
(To be filled in on the day for SAT start)
P&ID no. And revision:
Component List, revision:
Circuit diagram, revision:
7/30/2019 SAT-S & D System
6/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 6 of 23
Control Logics, revisions:
2.1 Mechanical & Documentation Inspection
Name of test
2.1.1 P&ID
Test procedure
Check that the Purified Water System is built according to the P&ID and that the items are marked with
the correct P&ID numbers.
Write, Pass at the valve /instrument /component on the P&ID if both criteria are fulfilled. If not writeFail and the deviation number in the drawing.
Sign & date the P&ID.
Attach the used P&ID to this document.
Parts inspected during FAT will not be re-inspected. If all items are already checked during FAT, writeN/A in the sections below.
Needed document(s) / equipment
The P&ID
Acceptance criteria
All valves, instruments and components shall be located according to the P&ID and be marked with thecorrect P&ID number.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
Witness, Date /Initials
7/30/2019 SAT-S & D System
7/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 7 of 23
Name of test
2.1.2 Components
Test procedure
Check that valves, instruments and components in the Component List are in accordance with the
description in the List.
Write, Pass at the valve /instrument /component in the list, if the item is in compliance with thespecifications. If not write Fail and the deviation number in the list.
Sign & date in the bottom of each page.
Attach the used Component List to this document.
Needed document(s) / equipment
Component List
Acceptance criteria
All valves, instruments and components shall be in accordance with the specifications in the ComponentList.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
7/30/2019 SAT-S & D System
8/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 8 of 23
Witness, Date /Initials
Name of test
2.1.3 Air gap to drain
Test procedure
Check by visual inspection that the pipe to drain leaves an air gap to the drainage
Needed document(s) / equipment
Measuring device.
Acceptance criteria
There shall be an open outlet from the drain pipe to the drain system that is > 5cm
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
7/30/2019 SAT-S & D System
9/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 9 of 23
Witness, Date /Initials
2.2 Hardware Acceptance Tests (IQ)
Name of test
2.2.1 Main Switch
Test procedure
Check that the system turns on in step ready when the main switch has been set to OFF and thenON again.
Needed document(s) / equipment
The Functional Logics, Section special logic.
Acceptance criteria
The system shall start up in step 1 ready.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
Witness, Date /Initials
7/30/2019 SAT-S & D System
10/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 10 of 23
Name of test
2.2.2 Hardware operating environment
Test procedure
Measure the temperature in the Control cabinet. The temperature for the control cabinet equipment shallnot exceed 40C.
Needed document(s) / equipment
Temperature instrument.
Acceptance criteria
For control cabinets without built in ventilation shall the temperature inside the control cabinet notexceed 40C.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
Witness, Date /Initials
7/30/2019 SAT-S & D System
11/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 11 of 23
2.3 System Acceptance Tests (OQ)
Name of test
2.3.1 Software Version
Test procedure
Check the version of the HMI shown in the system menu.Write the version of the HMI:HMI version at SAT:
Needed document(s) / equipment
HMI & Programming tools
Acceptance criteria
The version of the HMI shall be written above in the Test procedure square.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
7/30/2019 SAT-S & D System
12/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 12 of 23
Witness, Date /Initials
Name of test
2.3.2 Back-up
Test procedure
Make a comparison of the version of the loaded software for HMI, and the program version of theBack-up disc or CD-Rom.
Check that the back-up disc is marked correctly with version and date.
Needed document(s) / equipment
Back-up disc (or CD-Rom), the downloaded program, programming software and lap-top.
Acceptance criteria
There shall not be any differences in code between the HMI program on the floppy disk and CPU.Parameters could differ.The disc /CD-Rom shall be marked with the correct version and date.
Pass /Fail + Deviation no.
Comment
Tester, Date /Initials
Witness, Date /Initials
7/30/2019 SAT-S & D System
13/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 13 of 23
2.4 Operation tests (OQ)
Name of test
2.4.1 Leak Test
Test procedure
Put the Purified Water System into Normal (Auto) mode.During operation, the operating pressure is present at the following components:
1. UV2. Storage Tank3. Pump
Let the system run for 1hour.Check the plant connections and the components by visual inspection.
Needed document(s) / equipment
N/A
Acceptance criteria
No leaks shall be present in the system.
Pass /Fail + Deviation no.
Comment
7/30/2019 SAT-S & D System
14/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 14 of 23
Tester, Date /Initials
Witness, Date /Initials
Name of test
2.4.2 Operation of UV 301.1.1
Test procedure
Check that the plant is in the operation step.
1 During operation check working of hour meter2 During operation check working of intensity meter3 Check operation of UV as per control logic.
Needed document(s) / equipment
Control logic.
Acceptance criteria
1. Hour meter indicate working hours.
2. Intensity >= 1.6 milliwatt/cm2
Pass /Fail + Deviation no.
Comment
7/30/2019 SAT-S & D System
15/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 15 of 23
Tester, Date /Initials
Witness, Date /Initials
Name of test
2.4.2 Operation of UV 301.1.2
Test procedure
Check that the plant is in the operation step.
4 During operation check working of hour meter5 During operation check working of intensity meter6 Check operation of UV as per control logic.
Needed document(s) / equipment
Control logic.
Acceptance criteria
3. Hour meter indicate working hours.
4. Intensity >= 1.6 milliwatt/cm2
Pass /Fail + Deviation no.
Comment
7/30/2019 SAT-S & D System
16/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 16 of 23
Tester, Date /Initials
Witness, Date /Initials
Name of test
2.4.3 Operation, Purified water system in normal mode
Test procedure
1. Check the operation of PW System in normal auto mode.
Needed document(s) / equipment
Operating manuals, Control logic.
Acceptance criteriaSystem is operating as per the steps mentioned in control logic.
Pass /Fail + Deviation no.
Comment
7/30/2019 SAT-S & D System
17/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 17 of 23
Tester, Date /Initials
Witness, Date /Initials
Name of test
2.4.4 Sanitisation PW storage & loop control
Test procedure
Check that the program steps are executed as described in the Functional description. Carry out theSanitisation as specified in the Operating Instructions.Check that the necessary sanitising temperature is reached and maintained for the entire period.
Check that the necessary sanitising temperature is reached and maintained by saving the temperaturelogs printout from the recorder.If there is no recorder for the system, check the temperature value for TE 301.1.5 in the HMI and recordthe result in the table below. Start the counting when the temperature is reached and measure during6 0 minutes.
Needed document(s) / equipment
S & D operating instruction, section Sanitisation. The Functional Logics
Acceptance criteria
7/30/2019 SAT-S & D System
18/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 18 of 23
Description Required
value
Actual value Result (Pass / Fail)
The Sanitisation shall proceed acc to theFunctional Logics
N/A N/A
Temperature at TE 301.1.5 at start 80C
Temperature at TE 301.1.5 after 10 min 80C
Temperature at TE 301.1.5 after 20 min 80C
Temperature at TE 301.1.5 after 30 min 80C
Temperature at TE 301.1.5 after 40 min 80C
Temperature at TE 301.1.5 after 50 min 80C
Temperature at TE 301.1.5 after 60 min 80C
Pass / Fail + Deviation nos
Comment
Tester, Date / Initials
Witness, Date / Initials
Name of test
2.4.5 System Parameters
Test procedure
Run the system in operation mode.
Fill in the Instrumentation list for all parameters and set points.
Needed document(s) / equipment
The Instrumentation List (Functional Logic)
Acceptance criteria
Pass /Fail + Deviation no.
7/30/2019 SAT-S & D System
19/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 19 of 23
Comment
Tester, Date /Initials
Witness, Date /Initials
Name of test
2.4.6 Water Quality
Test procedure
Check the conductivity at V301.1.18Check the TOC value at sample V301.1.18 (analysis by customer)Check the microbiological situation at sample V301.1.18 (analysis by customer)
Needed document(s) / equipment
N/A
Acceptance criteria
Description Required Actual Result (Pass /Fail)
Conductivity 1.3 s/cm @25C
7/30/2019 SAT-S & D System
20/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 20 of 23
TOC
7/30/2019 SAT-S & D System
21/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 21 of 23
7/30/2019 SAT-S & D System
22/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 22 of 23
3.0 SAT Report
3.1 Purpose of the report
To conclude the performed Site Acceptance Test of the PW storage & loop control system system.
3.2 Deviations
The deviations shall be measured until, Date: _______
Deviation summary
Total amount of attached deviations:
3.3 Retests
All tests shall be completed at end of SAT.
No. Test name Test Completed
2.1 Mechanical & Documentation inspections (IQ) (Yes /No)2.1.1 P&ID
2.1.2 Components
2.1.3 Air gap to drain
2.2 Hardware Acceptance Tests (IQ)
2.2.1 Main switch
2.2.2 Hardware, operating environment
2.3 System Acceptance Tests (OQ)
2.3.1 Software version
2.3.2 Back-up
2.4 Operation tests (OQ)
2.4.1 Leak test
2.4.2 Operation of UV
2.4.3 Operation of Purified water system in normal mode2.4.4 Sanitization PW storage & loop control
2.4.5 System Parameters
2.4.6 Water Quality
2.4.7 Deviation list
7/30/2019 SAT-S & D System
23/23
Site Acceptance Test(SAT)
CWI147_SAT_REV0_PWS & LOOP CONTROL
Project no.: CWI 147 Revision: R0
TERAPIA-RANBAXY Page 23 of 23
3.4 Final Approval
To be signed by SAT participants.
The unit is approved for Operation
Title Name Company Sign / Date
Christ Nishotech
Christ Nishotech
TERAPIA-RANBAXI
TERAPIA-RANBAXI
Handover of the water treatment system
To be signed by the SAT participants.
The system is approved for hand-over.
Title Name Company Sign / Date
CHRIST-NISHOTECH
CHRIST-NISHOTECH
TERAPIA-RANBAXI
TERAPIA-RANBAXI