WATER SUPPLY LAYOUT SYMBOLS TEE 45 DEG ELBOW UNION WC LAV SHO WATER CLOSET LAVATORY SHOWER FD FLOOR DRAIN PU PD RISER (PIPE UP) RISER (PIPE DOWN) RISER (PIPE UP & DOWN) WATER SERVICE ENTRANCE 25 mm Ø PPR CWL PIPE 20 mm Ø PPR CWL PIPE 90 DEG ELBOW M GV CV WATER METER GATE VALVE CHECK VALVE HB HOSE BIBB 32 mm Ø PPR CWL PIPE SANITARY LAYOUT LEGENDS WYE SANITARY TEE 45 DEG ELBOW 90 DEG ELBOW 90 DEG ELBOW co WC LAV SHO WATER CLOSET LAVATORY SHOWER FD FLOOR DRAIN PU PD STACK (PIPE UP) STACK (PIPE DOWN) STACK (PIPE UP & DOWN) 75 mm Ø uPVC WASTE PIPE 50 mm Ø uPVC WASTE PIPE 75 mm Ø uPVC VENT PIPE 50 mm Ø uPVC VENT PIPE P - TRAP 75 mm Ø uPVC STORM DRAIN PIPE WS WASTE PIPE STACK VS VENT PIPE STACK DP DOWNSPOUT CB CATCH BASIN 63 mm Ø PPR CWL PIPE END CAP 20 mm Ø PPR HWL PIPE E. INDIRECT WASTE 1. NO EVAPORATIVE COOLER, OR SIMILAR AIR CONDITIONING EQUIPMENT SHALL HAVE ANY DRAIN PIPE IN CONNECTION THEREWITH, DIRECTLY CONNECTED TO ANY SOIL, WASTE AND VENT PIPE SUCH EQUIPMENT SHALL BE DRAINED BY MEANS OF INDIRECT WASTE PIPES AND ALL WASTES DRAINED BY THEM SHALL DISCHARGE THROUGH AN AIRBREAK INTO AN OPEN FLOOR SINK OR OTHER APPROVED TYPE RECEPTOR PROPERLY CONNECTED TO THE DRAINAGE SYSTEM. F. VENT PIPES 1. EACH PLUMBING FIXTURE TRAP, EXCEPT AS OTHERWISE PROVIDED IN THIS CODE, SHALL BE PROTECTED AGAINST SIPHONAGE AND BACK-PRESSURE, AIR CIRCULATION SHALL BE ASSURED THROUGHOUT ALL PARTS OF THE EXCRETA DRAINAGE SYSTEM BY MEANS OF VENT PIPES. 2. ALL VENT PIPES SHALL EXTEND UNDIMINISHED IN SIZE ABOVE THE ROOF SHALL BE RECONNECTED WITH THE SOIL OR WASTE STACK VENT OF PROPER SIZE AT A POINT BELOW THE ROOF, THE VENT THROUGH THE ROOF (VSTR) SHALL INCREASE ONE (1) PIPE SIZE ABOVE. G. STORM DRAINAGE 1. STORM DRAINAGE SHALL BE PROVIDED FOR ROOF AREAS, COURTS AND COURTYARDS TO COLLECT STORM WATER AND DISCHARGE THE STORMWATER TO AN APPROVED POINT OF DISPOSAL NOT IN CONFLICT WITH OTHER ORDINANCES OR REGULATIONS. H. HANGERS AND SUPPORT 1. PIPES SHALL BE SUPPORTED AT SUFFICIENTLY CLOSE INTERVALS TO KEEP THEM IN ALIGNMENT AND PREVENT SAGGING. MATERIAL SPECIFICATIONS COLD WATERLINE SHALL BE POLYPROPYLENE RANDOM CO-POLYMER TYPE 3 SEWERLINE/ SHALL BE UNPLASTICIZED POLYVINYL CHLORIDE (UPVC SERIES) VENT PIPES/ DOWNSPOUTS/ STORM DRAINAGE LABORATORY/ SHALL BE HIGH DENSITY POLYETHYLENE (HDPE PB16) PLUMBING GENERAL NOTES ALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED ACCORDING TO THE PROVISION OF THE NATIONAL PLUMBING CODE OF THE PHILIPPINES AND THE LOCAL RULES AND REGULATION A. VERTICAL PIPING 1. PLASTIC PIPE - SHALL BE SUPPORTED AT EVERY - (1) METER INTERVAL B. HORIZONTAL PIPING 1. PLASTIC PIPE - SHALL BE SUPPORTED BY STIFF METAL BACKING HANGERS IN ITS ENTIRE LENGTH FOR SMALL SIZE TUBING UP TO 38mm DIAMETER AND WITHOUT BACKINGS BUT WITH SPACED METAL HANGERS AT APPROVED FOR LARGER-SIZE TUBING. C. PLUMBING FIXTURES 1. PLUMBING FIXTURE SHALL BE MANUFACTURED OF DENSE, DURABLE, NON-BORBENT MATERIALS AND HAVE SMOOTH, IMPERVIOUS SURFACES, FREE FROM UNNECESSARY CONCEALED FOULING SURFACES, EXCEPT AS PERMITTED ELSEWHERE IN THIS CODE, ALL FIXTURE SHALL CONFORM IN QUALITY AND NATIONAL RECOGNIZED APPLICABLE STANDARDS. WATER SUPPLY 1. EACH PLUMBING FIXTURE SHALL BE APPROVED WITH AN ADEQUATE SUPPLY OF POTABLE RUNNING WATER, SO ARRANGED AS TO FLUSH AND KEEP SAME IN CLEAN AND HEALTHFUL CONDITIONS WITHOUT DANGER OF BACKFLOW OR CROSS-CONNECTION. D. SEWERLINE 1. DRAINAGE PIPING SHALL BE PROVIDED WITH APPROVED INLET FITTINGS FOR FIXTURE CONNECTIONS, CORRECTLY LOCATED ACCORDING TO THE SIZE AND TYPE OF FIXTURE PROPOSED TO BE CONNECTED. 2. CHANGE IN DIRECTION OF DRAINAGE PIPING SHALL BE MADE BY THE APPROPRIATE USE OF APPROVED FITTINGS AND SHALL BE OF THE ANGLES PRESENTED BY A 22 1 2 DEGREES OR 1 18 BEND, 45 DEGREES OR 1 8 BEND AND 60 DEGREES OR 1 6 BEND OR OTHER APPROVED FITTINGS. SCALE 1 1 P NTS PLUMBING NOTES SCALE 1 2 P NTS PLUMBING LEGENDS P1 SHEET NO. APPROVED Drawings and specifications and other contract documents duly signed, stamped or sealed, as instruments of service, are the intellectual property and documents of the architect, whether the object for which they are made is executed or not. It shall be unlawful for any person to duplicate or make copies of said documents for use in the repetition of and for other projects or buildings, whether executed partly or in whole, without the written consent of the architect or author of said documents. RA 9266 SECTION 33 Drawings and specifications and other contract documents duly signed, stamped or sealed, as instruments of service, are the intellectual property and documents of the architect, whether the object for which they are made is executed or not. It shall be unlawful for any person to duplicate or make copies of said documents for use in the repetition of and for other projects or buildings, whether executed partly or in whole, without the written consent of the architect or author of said documents. RA 9266 SECTION 33 CONCURRED RECOMMENDING APPROVAL PROJECT TITLE LOCATION AS SHOWN PROPOSED RENOVATION OF BGHMC THREE-STOREY BUILDING FOR ISOLATION ROOMS BGHMC Compound, Baguio City Cordillera Administrative Region SHEET CONTENTS CHECKED RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESE Medical Center Chief II Baguio General Hospital & Medical Center RAY P. SUANDING, MD, FPCP, FPCCP Chief of Medical Professional Staff Baguio General Hospital & Medical Center VILMA O. MOLTIO, MPA Supervising Administrative Officer OIC,Chief Administrative Officer, HOPSS-BGHMC RICHIE RHEY R. DIRIGE, CE Engineer IV, Head EFMO - HOPSS Baguio General Hospital & Medical Center LENON S. BANA-E, CE, SE SANITARY ENGINEER BAGUIO GENERAL HOSPITAL AND MEDICAL CENTER REPUBLIC OF THE PHILIPPINES DEPARTMENT OF HEALTH BAGUIO CITY CORDILLERA ADMINISTRATIVE REGION 100 mm Ø uPVC WASTE PIPE 150 mm Ø uPVC WASTE PIPE
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
WATER SUPPLY LAYOUT SYMBOLSTEE
45 DEG ELBOW
UNION
WCLAVSHO
WATER CLOSET
LAVATORY
SHOWER
FDFLOOR DRAIN
PU
PD
RISER (PIPE UP)
RISER (PIPE DOWN)
RISER (PIPE UP & DOWN)
WATER SERVICE ENTRANCE
25 mm Ø PPR CWL PIPE
20 mm Ø PPR CWL PIPE
90 DEG ELBOW
MGV
CV
WATER METER
GATE VALVE
CHECK VALVE
HB HOSE BIBB
32 mm Ø PPR CWL PIPE
SANITARY LAYOUT LEGENDSWYE
SANITARY TEE
45 DEG ELBOW
90 DEG ELBOW
90 DEG ELBOWco
WCLAVSHO
WATER CLOSET
LAVATORY
SHOWER
FDFLOOR DRAIN
PU
PD
STACK (PIPE UP)
STACK (PIPE DOWN)
STACK (PIPE UP & DOWN)
75 mm Ø uPVC WASTE PIPE
50 mm Ø uPVC WASTE PIPE
75 mm Ø uPVC VENT PIPE
50 mm Ø uPVC VENT PIPE
P - TRAP
75 mm Ø uPVC STORM DRAIN PIPE
WS WASTE PIPE STACK
VS VENT PIPE STACK
DP DOWNSPOUT
CB CATCH BASIN
63 mm Ø PPR CWL PIPE
END CAP
20 mm Ø PPR HWL PIPE
E. INDIRECT WASTE
1. NO EVAPORATIVE COOLER, OR SIMILAR AIR CONDITIONING EQUIPMENT SHALL HAVE ANYDRAIN PIPE IN CONNECTION THEREWITH, DIRECTLY CONNECTED TO ANY SOIL, WASTE ANDVENT PIPE SUCH EQUIPMENT SHALL BE DRAINED BY MEANS OF INDIRECT WASTE PIPESAND ALL WASTES DRAINED BY THEM SHALL DISCHARGE THROUGH AN AIRBREAK INTO ANOPEN FLOOR SINK OR OTHER APPROVED TYPE RECEPTOR PROPERLY CONNECTED TO THEDRAINAGE SYSTEM.
F. VENT PIPES
1. EACH PLUMBING FIXTURE TRAP, EXCEPT AS OTHERWISE PROVIDED IN THIS CODE, SHALLBE PROTECTED AGAINST SIPHONAGE AND BACK-PRESSURE, AIR CIRCULATION SHALL BEASSURED THROUGHOUT ALL PARTS OF THE EXCRETA DRAINAGE SYSTEM BY MEANS OFVENT PIPES.
2. ALL VENT PIPES SHALL EXTEND UNDIMINISHED IN SIZE ABOVE THE ROOF SHALL BERECONNECTED WITH THE SOIL OR WASTE STACK VENT OF PROPER SIZE AT A POINTBELOW THE ROOF, THE VENT THROUGH THE ROOF (VSTR) SHALL INCREASE ONE (1) PIPESIZE ABOVE.
G. STORM DRAINAGE
1. STORM DRAINAGE SHALL BE PROVIDED FOR ROOF AREAS, COURTS AND COURTYARDS TOCOLLECT STORM WATER AND DISCHARGE THE STORMWATER TO AN APPROVED POINT OFDISPOSAL NOT IN CONFLICT WITH OTHER ORDINANCES OR REGULATIONS.
H. HANGERS AND SUPPORT
1. PIPES SHALL BE SUPPORTED AT SUFFICIENTLY CLOSE INTERVALS TO KEEP THEM INALIGNMENT AND PREVENT SAGGING.
MATERIAL SPECIFICATIONSCOLD WATERLINE SHALL BE POLYPROPYLENE RANDOM CO-POLYMER TYPE 3
SEWERLINE/ SHALL BE UNPLASTICIZED POLYVINYL CHLORIDE (UPVC SERIES)VENT PIPES/DOWNSPOUTS/STORM DRAINAGE
LABORATORY/ SHALL BE HIGH DENSITY POLYETHYLENE (HDPE PB16)
PLUMBING GENERAL NOTESALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED ACCORDING TOTHE PROVISION OF THE NATIONAL PLUMBING CODE OF THE PHILIPPINES ANDTHE LOCAL RULES AND REGULATION
A. VERTICAL PIPING1. PLASTIC PIPE - SHALL BE SUPPORTED AT EVERY - (1) METER INTERVAL
B. HORIZONTAL PIPING1. PLASTIC PIPE - SHALL BE SUPPORTED BY STIFF METAL BACKING
HANGERS IN ITS ENTIRE LENGTH FOR SMALL SIZE TUBING UP TO 38mmDIAMETER AND WITHOUT BACKINGS BUT WITH SPACED METAL HANGERSAT APPROVED FOR LARGER-SIZE TUBING.
C. PLUMBING FIXTURES1. PLUMBING FIXTURE SHALL BE MANUFACTURED OF DENSE, DURABLE,
NON-BORBENT MATERIALS AND HAVE SMOOTH, IMPERVIOUS SURFACES,FREE FROM UNNECESSARY CONCEALED FOULING SURFACES, EXCEPT ASPERMITTED ELSEWHERE IN THIS CODE, ALL FIXTURE SHALL CONFORM INQUALITY AND NATIONAL RECOGNIZED APPLICABLE STANDARDS.
WATER SUPPLY
1. EACH PLUMBING FIXTURE SHALL BE APPROVED WITH AN ADEQUATESUPPLY OF POTABLE RUNNING WATER, SO ARRANGED AS TO FLUSH ANDKEEP SAME IN CLEAN AND HEALTHFUL CONDITIONS WITHOUT DANGER OFBACKFLOW OR CROSS-CONNECTION.
D. SEWERLINE
1. DRAINAGE PIPING SHALL BE PROVIDED WITH APPROVED INLET FITTINGSFOR FIXTURE CONNECTIONS, CORRECTLY LOCATED ACCORDING TO THESIZE AND TYPE OF FIXTURE PROPOSED TO BE CONNECTED.
2. CHANGE IN DIRECTION OF DRAINAGE PIPING SHALL BE MADE BY THEAPPROPRIATE USE OF APPROVED FITTINGS AND SHALL BE OF THEANGLES PRESENTED BY A 22 1
2 DEGREES OR 118 BEND, 45 DEGREES OR 1
8BEND AND 60 DEGREES OR 16 BEND OR OTHER APPROVED FITTINGS.
SCALE1
1P NTS
PLUMBING NOTESSCALE1
2P NTS
PLUMBING LEGENDS
P1
SHEET NO.APPROVED Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33
Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33 CONCURREDRECOMMENDING APPROVALPROJECT TITLE
LOCATION AS SHOWN
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTS CHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LENON S. BANA-E, CE, SE
SANITARY ENGINEER
BAGUIO GENERAL HOSPITAL
AND MEDICAL CENTER
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
100 mm Ø uPVC WASTE PIPE
150 mm Ø uPVC WASTE PIPE
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
SCALE2
1P 1:1,000 MTRS
SITE DEVELOPMENT PLANPARTIAL INDICATIVE BGHMC MASTER
10
17
OLD PS
A
C E F
6B
2
22
ST
GATE
H
J
G
1
23
24
VU
WATER TANK
1819
R
I
SHED
WATER TANK
P
Q3
BENECO POST
BENECO POST
W
AT
ER
TA
NK
OLD
BU
ILD
ING
25
13
14
27
STAIRS
K
L
STORE
26
W
MAIN ENTRANCE
MAIN EXIT
B G H M C D R I V E W A Y
TO BRGY. PHIL-AM
NORTHF L Y - O V E R
0 10 20 30 40 50 60 70 80 90 100m
0 10 000 50 000 100 000mm
PROJECT:PROPOSED RENOVATION OF
THREE-STOREY BUILDING FORISOLATION ROOMS
P2
SHEET NO.APPROVED Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33
Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33 CONCURREDRECOMMENDING APPROVALPROJECT TITLE
LOCATION AS SHOWN
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTS CHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LENON S. BANA-E, CE, SE
SANITARY ENGINEER
BAGUIO GENERAL HOSPITAL
AND MEDICAL CENTER
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
AutoCAD SHX Text
21
AutoCAD SHX Text
CUT- OFF
AutoCAD SHX Text
MILITARY
AutoCAD SHX Text
M
AutoCAD SHX Text
A
AutoCAD SHX Text
R
AutoCAD SHX Text
C
AutoCAD SHX Text
S
AutoCAD SHX Text
O
AutoCAD SHX Text
H
AutoCAD SHX Text
I
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
W
AutoCAD SHX Text
A
AutoCAD SHX Text
Y
AutoCAD SHX Text
K
AutoCAD SHX Text
E
AutoCAD SHX Text
O
AutoCAD SHX Text
N
AutoCAD SHX Text
N
AutoCAD SHX Text
R
AutoCAD SHX Text
O
AutoCAD SHX Text
A
AutoCAD SHX Text
D
AutoCAD SHX Text
LEGEND: 1. MAIN BUILDING (TWO STOREY) MAIN BUILDING (TWO STOREY) 2. FLAVIER BUILDING (6-STOREY) FLAVIER BUILDING (6-STOREY) 3. PAY WARD BUILDING (3-STOREY) PAY WARD BUILDING (3-STOREY) 4. OLD E.R. (2-STOREY) FOR DEMOLITION OLD E.R. (2-STOREY) FOR DEMOLITION 5. REPRODUCTIVE HEALTH REPRODUCTIVE HEALTH 6. INFECTIOUS DISEASE BUILDING INFECTIOUS DISEASE BUILDING 7. PSYCHIATRIC BUILDING PSYCHIATRIC BUILDING 8. UNDER 5 BUILDING (FOR DEMOLITION) UNDER 5 BUILDING (FOR DEMOLITION) 9. TB DOTS BUILDING FOR DEMOLITION) TB DOTS BUILDING FOR DEMOLITION) 10. CANCER CENTER BUILDING CANCER CENTER BUILDING 11. OUT PATIENT DEPARTMENT BUILDING OUT PATIENT DEPARTMENT BUILDING 12. ADMINISTRATION BUILDING (FOR DEMOLITION) ADMINISTRATION BUILDING (FOR DEMOLITION) 13. DOH-CAR BUILDING DOH-CAR BUILDING 14. DOH TRAINING CENTER DOH TRAINING CENTER 15. BGHMC DORMITORY BGHMC DORMITORY 16. OLD RESIDENTIAL BUILDING (FOR DEMOLITION) OLD RESIDENTIAL BUILDING (FOR DEMOLITION) 17. SECRETARY'S COTTAGE SECRETARY'S COTTAGE 18. GUEST HOUSE GUEST HOUSE 19. MEDICAL CENTER CHIEF COTTAGE MEDICAL CENTER CHIEF COTTAGE 20. RESCUE 911 (FOR DEMOLITION) RESCUE 911 (FOR DEMOLITION) (FOR DEMOLITION) 21. BGHMC COTTAGE BGHMC COTTAGE 22. MAINTENANCE & MOTORPOOL MAINTENANCE & MOTORPOOL 23. DOCTOR'S QUARTERS DOCTOR'S QUARTERS 24. TEMPORARY STORAGE BUILDING TEMPORARY STORAGE BUILDING 25. LAUNDRY BUILDING LAUNDRY BUILDING 26. DOH-CAR BUILDING (2-STOREY) DOH-CAR BUILDING (2-STOREY) 27. DOH-CAR MOTORPOOL & ADMIN BUILDING DOH-CAR MOTORPOOL & ADMIN BUILDING 28. BGHMC LIBRARY BUILDING (FOR DEMOLITION)BGHMC LIBRARY BUILDING (FOR DEMOLITION)
AutoCAD SHX Text
. A. RESIDENTIAL RESIDENTIAL B. RESIDENTIAL RESIDENTIAL C. CONCRETE WATER TANK CONCRETE WATER TANK D. WATER TREATMENT PLANT WATER TREATMENT PLANT E. PHARMACY BUILDING PHARMACY BUILDING F. LIQUID OXYGEN LIQUID OXYGEN G. CISTERN TANK CISTERN TANK H. CISTERN TANK CISTERN TANK I. WAITING SHED WAITING SHED J. FOOD COURT FOOD COURT K. CANTEEN CANTEEN L. GARRAGE GARRAGE M. GARBAGE BIN GARBAGE BIN N. WATER TANK WATER TANK O. WATER TANK WATER TANK P. BAGUIO WATER DISTRICT TANK BAGUIO WATER DISTRICT TANK Q. GARBAGE BIN GARBAGE BIN R. BODEGA / STORAGE BODEGA / STORAGE S. WASTE TANK WASTE TANK T. POWER HOUSE POWER HOUSE U. WATER TANK WATER TANK V. WATER TANK WATER TANK W. GENERATOR HOUSE GENERATOR HOUSE X. EXISTING BASKETBALL COURTEXISTING BASKETBALL COURT
AutoCAD SHX Text
PROPOSED COVERED CONNECTING LINK BRIDGE
AutoCAD SHX Text
PROPOSED RENAL CENTER
AutoCAD SHX Text
PROPOSED RENAL CENTER (ON-GOING)
AutoCAD SHX Text
PROPOSED MULTI-SPECIALTY CENTER (ON-GOING)
AutoCAD SHX Text
PARKING BUILDING
AutoCAD SHX Text
PROPOSED PSYCHIATRY COMPLEX (ON-GOING)
AutoCAD SHX Text
ODTRU
AutoCAD SHX Text
PROPOSED NEW LABORATORY BUILDING W/ NEW MOLECULAR LAB
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
WS
WS
WSWS
WS
WS
WSWS
WS
WS
WSWS
WSWS WS
WS
WSWS
WS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WCWC
LAV
LAV
LAV
LAV
LAV
LAV LAV
LAV
LAV
SHO
SHO
SHO
SHO
SHO
SHO
SHO
SHO
EEW
EEW
SCALE3
1P 1:100 MTS
GROUND FLOOR WATERLINE LAYOUT
P3 SHEET NO.
APPROVED Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
AIRLOCK
Up
Ramp
Up
HALLWAY
HALL
WAY
Up
ACCESSGOING FROMDELTA E.R.
EMERGENCYEXIT
PERS
ONNE
L ACC
ESS
ENTRANCE
BEDELEVATOR
Dn
EXIT
Dn
250mm STRUCTURAL GAP
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
Ramp Up
HOSPITAL ROAD
NORTH
Ramp Dn
200m
m ST
RUCT
URAL
GAP
2 938
1 412
1 725
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
32 MM DIA CWL RISER (GF SUPPLY)
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
WS
WS
WSWS
WS
WS
WSWS
WSWS
WSWS WS
WS
WSWS
WS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WCWC
LAV
LAV
LAV
LAV
LAV
LAV LAV
LAV
LAV
SHO
SHO
SHO
SHO
SHO
SHO
SHO
SHO
EEW
EEW
SCALE3a
1P 1:100 MTS
SECOND FLOOR WATERLINE LAYOUT
P3a
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
HALLWAY
HALL
WAY
Up
BEDELEVATOR
Up Dn
Dn
ROOF
ROOF
250mm STRUCTURAL GAP
NORTH
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
200m
m ST
RUCT
URAL
GAP
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
WS WS
32 MM DIA CWL RISER (2F SUPPLY)
32 MM DIA CWL RISER (GF SUPPLY)
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
AutoCAD SHX Text
FW
AutoCAD SHX Text
5
WS
WS
WSWS
WS
WS
WSWS
WSWS
WSWS WS
WS
WSWS
WS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WCWC
LAV
LAV
LAV
LAV
LAV
LAV LAV
LAV
LAV
SHO
SHO
SHO
SHO
SHO
SHO
SHO
SHO
EEW
EEW
SCALE3b
1P 1:100 MTS
THIRD FLOOR WATERLINE LAYOUT
P3b
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
HALLWAY
HALL
WAY
Up
BEDELEVATOR
Up Dn
Dn
ROOF
ROOF
250mm STRUCTURAL GAP
NORTH
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
200m
m ST
RUCT
URAL
GAP
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
WS WS
32 MM DIA CWL RISER (2F SUPPLY)
32 MM DIA CWL RISER (GF SUPPLY)
32 MM DIA CWL RISER (3F SUPPLY)
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
AutoCAD SHX Text
FW
AutoCAD SHX Text
5
PG PS
PRESSURETANK
GV CV
GV CV
GV CV
GV CVGV CV
FV
FV
GV
GV
GV
HB
WATERTANK 1
WATERTANK 2
P
SCALE3c
1P 1:100 MTS
ROOF WATERLINE LAYOUT
P3c
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
APPROVED Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
AIRLOCK
Up
Ramp
Up
HALLWAY
HALL
WAY
Up
ACCESSGOING FROMDELTA E.R.
EMERGENCYEXIT
PERS
ONNE
L ACC
ESS
ENTRANCE
BEDELEVATOR
Dn
EXIT
Dn
250mm STRUCTURAL GAP
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
Ramp Up
HOSPITAL ROAD
NORTH
Ramp Dn
200m
m ST
RUCT
URAL
GAP
2 938
1 412
1 725
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
FD
FD
COWC
WC
LAV
LAV
FD
FD
FD
WS
WS
WS
LAV
CO
CO
CO
CO
CO
COCO
CO
CO
COCO
COCO
COCO
CO
CO
CO
CO
CO
COCO
COCO
WS
WS
WS
WSWS
WS
WSWS
WS WS WS
WSWS
WS
WS
WS
WS
WS
LAV
LAV
LAV
LAV LAV
FDFD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD WC
WC
WC
WCWC
WC
WC
WC
WC
LAV
COCO
FD
LAV
FD
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK75 MM DIA VENT STACK
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP 75mmØ DP 75mmØ DP 75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75 MM DIA VENT STACK100 MM DIA WASTE STACK
SCALE4a
1P 1:100 MTS
SECOND FLOOR SEWER LINE LAYOUT
P4a
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
HALLWAY
HALL
WAY
Up
BEDELEVATOR
Up Dn
Dn
ROOF
ROOF
250mm STRUCTURAL GAP
NORTH
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
200m
m ST
RUCT
URAL
GAP
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
AutoCAD SHX Text
FW
AutoCAD SHX Text
5
FD
FD
CO
COWC
WC
LAV
LAV
FD
FD
FD
WS
WS
WS
LAV
CO
CO
CO
CO
CO
COCO
CO
CO
COCO
COCO
COCO
CO
CO
CO
CO
CO
COCO
COCO
WS
WS
WS
WSWS
WS
WSWS
WS WS WS
WSWS
WS
WS
WS
WS
WS
LAV
LAV
LAV
LAV LAV
FDFD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD WC
WC
WC
WCWC
WC
WC
WC
WC
LAV
COCO
FD
LAV
FD
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK75 MM DIA VENT STACK
75mmØ DP
75mmØ DP 75mmØ DP 75mmØ DP 75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
SCALE4b
1P 1:100 MTS
THIRD FLOOR SEWER LINE LAYOUT
P4b
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LE
NO
N S
. B
AN
A-E
, C
E, S
E
SANITARY ENGINEER
BA
GU
IO
G
EN
ER
AL
H
OS
PIT
AL
AN
D M
ED
IC
AL
C
EN
TE
R
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
HALLWAY
HALL
WAY
Up
BEDELEVATOR
Up Dn
Dn
ROOF
ROOF
250mm STRUCTURAL GAP
NORTH
A B C E F G H J
1
2
3
4
5
6
7
8
9
D
1'
G'
10
11
12
13
14
EXISTING INFECTIOUSDESEASE BUILDING
(PROPOSED DELTA E.R.)
200m
m ST
RUCT
URAL
GAP
22 750
2 200 6753 6254 2004 0003 0001 300 2503 500
41 80
0
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275
350
3 050
3 275
3 325
2 700
1 500
1 775
2 100
2 475
1 500
41 80
0
200
2 575 1 725 6751 7501 875 7002 5001 0001 3002 700
15 00
0
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 825
1 500
6 075
26 80
0
2 950
3 050
3 275
1 825
1 500
4 575
2 2004 3004 2004 0004 300 2503 500
22 750
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
AutoCAD SHX Text
FW
AutoCAD SHX Text
5
75 MM DIA VENT STACK
75 MM DIA VTR
75 MM DIA VTR
75 MM DIA VTR75 MM DIA VTR
75mmØ DP
75mmØ DP75mmØ DP
75mmØ DP 75mmØ DP 75mmØ DP 75mmØ DP
75 MM DIA VTR
75mmØ DP 75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
SCALE4c
1P 1:100 MTS
ROOF SEWER LINE LAYOUT
P4c
SHEET NO.APPROVED
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
Drawings and specifications andother contract docum
ents duly signed,stam
ped or sealed, as instruments of
service, are the intellectual propertyand docum
ents of the architect,whether the object for which they arem
ade is executed or not. It shall beunlawful for any person to duplicateor m
ake copies of said documents for
use in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said docum
ents.
RA
9
26
6 S
EC
TIO
N 3
3
CONCURREDRECOMMENDING APPROVAL
PROJECT TITLE
LOCATIONAS SHOW
N
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTSCHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
SHEET NO.APPROVED Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33
Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33 CONCURREDRECOMMENDING APPROVALPROJECT TITLE
LOCATION AS SHOWN
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTS CHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LENON S. BANA-E, CE, SE
SANITARY ENGINEER
BAGUIO GENERAL HOSPITAL
AND MEDICAL CENTER
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
WS
WS
WS
WS
WS
WS
WS
WS
WSWS
WS
WSWS
WS
WS
WSWS
WSWS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
LAVLAV
LAV
LAV
LAV
LAV
LAV
LAV
LAV
SHO
SHO
SHO
SHOSHO
SHO
SHO
SHOEEW
EEW
AB
C
E
F
G
HJ
1
23
4
56
78
9
D
1'
G'
10
11
12
13
14
AIRLOCK
Up Ramp Up
HALLWAY
HALLWAY
Up
ACCESS
GOING FROM
DELTA E.R.
EMERGENCY
EXIT
PERSONNEL ACCESS
ENTRANCE
BEDELEVATOR
Dn
EXIT
Dn
250mm STRUCTURAL GAP
EXISTING INFECTIOUS
DESEASE BUILDING
(PROPOSED DELTA E.R.)
Ramp Up
HOSPITAL ROAD
NORTH
Ramp Dn
200mm STRUCTURAL GAP2 938
1 412
1 725
22 750
2 200
675
3 625
4 200
4 000
3 000
1 300
250
3 500
41 800
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275 350
3 050
3 275
3 325
2 700
1 5001 775
2 100
2 475
1 500
41 800 200
2 575
1 725
675
1 750
1 875
700
2 500
1 000
1 300
2 700
15 000
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 8251 500
6 075
26 800
2 950
3 050
3 275
1 8251 500
4 575
2 200
4 300
4 200
4 000
4 300
250
3 500
22 750
WS
WS
WS
WS
WS
WS
WS
WS
WS
WSWS
WS
WS
WSWS
WSWS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
LAVLAV
LAV
LAV
LAV
LAV
LAV
LAV
LAV
SHO
SHO
SHO
SHOSHO
SHO
SHO
SHOEEW
EEW
WS WS
WS
WS
WS
WS
WS
WS
WS
WS
WS
WSWS
WS
WS
WSWS
WSWS
WS
WS
WS
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
WC
LAVLAV
LAV
LAV
LAV
LAV
LAV
LAV
LAV
SHO
SHO
SHO
SHOSHO
SHO
SHO
SHOEEW
EEW
WS WS
PGPS
PRESSURE
TANK
GV CV GV CV
GV CVGV CVGV CV
FV
FVGV
GV
GV
HB
WATERTANK 1
WATERTANK 2
P
TAP TO EXISTING HOSPITAL WATER SUPPLY
32 MM DIA CWL RISER (2F SUPPLY)
32 MM DIA CWL RISER (GF SUPPLY)
32 MM DIA CWL RISER (3F SUPPLY)
SCALE5
1P 1:120 MTRS
WATERLINE ISOMETRY
P5
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
SHEET NO.APPROVED Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33
Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33 CONCURREDRECOMMENDING APPROVALPROJECT TITLE
LOCATION AS SHOWN
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTS CHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS
Baguio General Hospital & Medical Center
LENON S. BANA-E, CE, SE
SANITARY ENGINEER
BAGUIO GENERAL HOSPITAL
AND MEDICAL CENTER
REPUBLIC OF THE PHILIPPINESDEPARTMENT OF HEALTH
BAGUIO CITYCORDILLERA ADMINISTRATIVE REGION
SEPTICTANK
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
COCO
COCOWC
WC
WC
WC
WC
WC
WC
WC
WC
WC
LAVLAV LAV
LAV
LAV
COCO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
FDFD
FD
FD
FD FDFD
FD
FD
FD
FD
COWS
WS
WS WS
WS
WSWS
WS
WS
WS
LAV
LAV
LAV
WS
WS
WS
WSWS
WSWS
WS
LAV
LAV
WS
WSFD
FD
FD
FD
FD
FD
FD
WS
WS
WS
COCO
COCO
CO
CO
TO STP
FD
FDFD
FD
FD
FD
FD
FD
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP 75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
AB
C
E
F
G
HJ
1
23
4
56
78
9
D
1'
G'
10
11
12
13
14
AIRLOCK
Up Ramp Up
HALLWAY
HALLWAY
Up
ACCESS
GOING FROM
DELTA E.R.
EMERGENCY
EXIT
PERSONNEL ACCESS
ENTRANCE
BEDELEVATOR
Dn
EXIT
Dn
250mm STRUCTURAL GAP
EXISTING INFECTIOUS
DESEASE BUILDING
(PROPOSED DELTA E.R.)
Ramp Up
HOSPITAL ROAD
NORTH
Ramp Dn
200mm STRUCTURAL GAP2 938
1 412
1 725
22 750
2 200
675
3 625
4 200
4 000
3 000
1 300
250
3 500
41 800
3 750
3 750
3 750
3 750
1 850
2 950
6 075
200
4 800
1 275 350
3 050
3 275
3 325
2 700
1 5001 775
2 100
2 475
1 500
41 800 200
2 575
1 725
675
1 750
1 875
700
2 500
1 000
1 300
2 700
15 000
3 750
3 750
3 750
3 750
1 850
1 500
6 075
1 8251 500
6 075
26 800
2 950
3 050
3 275
1 8251 500
4 575
2 200
4 300
4 200
4 000
4 300
250
3 500
22 750
FD
FD
CO
WC
WC
LAVLAV FD
FD
FD
WS
WS
WS
LAV
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
WS
WS
WSWS
WS
WS
WS
WSWS
WS
WS
WS
WS
WS
WSWS
WS
WS
LAV
LAV
LAV
LAV
LAVFD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD WC
WC
WC
WC
WC
WC
WC
WCWC
LAV
CO
CO
FD
LAV
FD
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
75 MM DIA VENT STACK
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
FD
FD
CO
WC
WC
LAVLAV FD
FD
FD
WS
WS
WS
LAV
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
CO
WS
WS
WSWS
WS
WS
WS
WSWS
WS
WS
WS
WS
WS
WSWS
WS
WS
LAV
LAV
LAV
LAV
LAVFD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD WC
WC
WC
WC
WC
WC
WC
WCWC
LAV
CO
CO
FD
LAV
FD
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
75 MM DIA VENT STACK
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75 MM DIA VENT STACK
100 MM DIA WASTE STACK
75 MM DIA VENT STACK
75 MM DIA VTR
75 MM DIA VTR
75 MM DIA VTR
75 MM DIA VTR
75mmØ DP75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75 MM DIA VTR
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
75mmØ DP
SCALE5a
1P 1:120 MTRS
SEWER LINE ISOMETRY
P5a
AutoCAD SHX Text
CADD By : LSB
AutoCAD SHX Text
Checked By : RRRD
AutoCAD SHX Text
Date :
AutoCAD SHX Text
Date :
AutoCAD SHX Text
TIN : 709-792-740-000
AutoCAD SHX Text
Validity:
AutoCAD SHX Text
PTR No.:
AutoCAD SHX Text
Place : BAGUIO CITY
AutoCAD SHX Text
PRC REG. No.: 003231
FFL
50mm DIA. PVC WASTE STACK
PPR WATER SUPPLY PIPE
2"DIA. P TRAP W/ CLEAN-OUT
ESCUTCHEON
20mm DIA. PPR AIR CHAMBER
20mm DIA. PPR END CAP
HORIZONTAL PVC PIPE
444m
m
535m
m
800m
m
STAINLESS STEEL (SUS304)
WALL ANGLE VALVE
20MM DIA. PPR PIPE AIR CHAMBER20MM DIA. PPR PIPE WATER SUPPLY
ESCUTCHEONSUS304 TWO-WAYANGLE VALVE
FFL
TOILET
LAVATORY
AIR CHAMBER
PIPE SIZE
OUTLET
INLET
DC
38.10mm
38.10mm
PIPE SIZE
ø60mm
ø75mm
101.60mm
127.00mm
FLOOR DRAIN DETAIL;
50.80mmø150mm 155.80mm
44mm 152.40mmø100mm
D
FLR. LEVELC
PIPE SIZE
D
450mm
300mm
ø20mm
ø20mm
PIPE SIZEAIR CHAMBER DETAIL
50mm DIA. PVC VENT STACK
450m
m400m
m
600m
m
4
5
0
m
m
100m
m
STAINLESS STEEL SINK
(SUS) 3MM THK
STAINLESS STEEL
GOOSENECK FAUCET
SHEET NO.APPROVED Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33
Drawings and specifications andother contract documents duly signed,stamped or sealed, as instruments ofservice, are the intellectual propertyand documents of the architect,whether the object for which they aremade is executed or not. It shall beunlawful for any person to duplicateor make copies of said documents foruse in the repetition of and for otherprojects or buildings, whetherexecuted partly or in whole, withoutthe written consent of the architect orauthor of said documents.
RA 9266 SECTION 33 CONCURREDRECOMMENDING APPROVALPROJECT TITLE
LOCATION AS SHOWN
PROPOSED RENOVATION OF BGHMCTHREE-STOREY BUILDING FOR
ISOLATION ROOMS
BGHMC Compound, Baguio CityCordillera Administrative Region
SHEET CONTENTS CHECKED
RICARDO B. RUNEZ JR. MD, FPCS, MHA, CESEMedical Center Chief II
Baguio General Hospital & Medical Center
RAY P. SUANDING, MD, FPCP, FPCCPChief of Medical Professional Staff
Baguio General Hospital & Medical Center
VILMA O. MOLTIO, MPASupervising Administrative Officer
OIC,Chief Administrative Officer, HOPSS-BGHMC
RICHIE RHEY R. DIRIGE, CEEngineer IV, Head EFMO - HOPSS