INFRARED INSPECTION SURVEY REPORT SAMPLE CUSTOMER MCC SURVEY DATA COLLECTED: 4/9/2018
7

SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

Jan 22, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

INFRARED INSPECTION SURVEY REPORT

SAMPLE CUSTOMER

MCC SURVEY

DATA COLLECTED: 4/9/2018

Page 2: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

REPORT DATE

EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

PAGE #

03/29/18 107L126 APCU Heater Power Panel

Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages.

During scheduled outage, inspect and tighten connections. MODERATE 3

03/29/18 Bottom FuseMain Cooling Tower Cell 3

Fan

The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.

Verify correct fuse and verify load is balanced. MODERATE 4

03/29/18Steam Turbine

Generator Enclosure

Steam Turbine This unit has a loose connection During scheduled outage, inspect and tighten connections. MODERATE 5

03/29/18 Enclosure Vent Fan 1 CTG2 This connection has a comparatively elevated thermal

pattern that indicates a loose connection. During scheduled outage, inspect and tighten connections. MINOR 6

03/29/18 EN1700 Industrial Control Panel

Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection.

During scheduled outage, inspect and tighten connections. MINOR 7

1- CRITICAL

2- DEFECTS ARE IN MODERATE STAGES

3 - DEFECTS MAY BE PRESENT

4 - LEVELS ARE ABOVE NORMAL

5 - NORMAL

2 of 7

Page 3: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F137 °F95.7 °F41.3 °F69 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: Line #2 connection on this power panel has an elevated thermal pattern that indicates a loose connection in early stages. Temperatures are elevated but not excessive at this time.

Facility location: Equipment Name: 107L126Data Collected: Image Filename: IR000010

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: APCU Heater Power Panel

www.conditionmonitoringservices.com

3 of 7

Page 4: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F162.2 °F97.4 °F64.8 °F94.2 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: Verify correct fuse and verify load is balanced.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: The bottom fuse has a comparatively elevated thermal pattern. This could be due to a worn or incorrect fuse, or may be load related.

Facility location: Equipment Name: FusesData Collected: Image Filename: IR000060

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Main Cooling Tower Cell 3 Fan

www.conditionmonitoringservices.com

4 of 7

Page 5: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F113.2 °F73.8 °F39.4 °F45.2 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MODERATE

OBSERVATIONS: This unit has a loose connection at the location marked below.

Facility location: Equipment Name: Steam Turbine Data Collected: Image Filename: IR000061

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Steam Turbine Generator Enc.

www.conditionmonitoringservices.com

5 of 7

Page 6: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F106.7 °F84.6 °F22.1 °F38.7 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR

OBSERVATIONS: This connection has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are elevated but not excessive at this time.

Facility location: Equipment Name: Enclosure Vent Fan 1Data Collected: Image Filename: IR000059

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: CTG2

www.conditionmonitoringservices.com

6 of 7

Page 7: SAMPLE CUSTOMER MCC SURVEY - Condition Monitoring … · 2020. 9. 16. · MCC SURVEY DATA COLLECTED: 4/9/2018. REPORT DATE EQUIPMENT NAME LOCATION COMMENTS CUSTOMER ACTION ITEMS SEVERITY

68 °F97 °F87.7 °F9.3 °F29 °F0.95

INSPECTED / REPAIRED BY: DATE:

DEFECT RISE ABOVE AMBIENTEMISSIVITY

AMBIENT TEMPERATUREDEFECT MAX TEMPERATUREREFERENCE TEMPERATUREDEFECT VS. REFERENCE DELTA TEMP

RECOMMENDATIONS: During scheduled outage, inspect and tighten connections.

Inspected By:March 29, 2018 Jesse Vanhoy Repair Priority: MINOR

OBSERVATIONS: Connection #21 has a comparatively elevated thermal pattern that indicates a loose connection. Temperatures are comparatively elevated but minor at this time.

Facility location: Equipment Name: EN1700Data Collected: Image Filename: IR000062

INFRARED EXCEPTION ANALYSIS REPORT

Company: Location Description: Industrial Control Panel

www.conditionmonitoringservices.com

7 of 7