Top Banner
Safety Instruction Diagnostic Faceplate Adding a safety Instruction faceplate to existing safety program with Control Logix and Panel View Studio Download the content from the AB website and place it in a folder named “Resources” Open Control Logix program and panel view application that you want to edit. In Control Logix Import “SafetyInsructtion_FaceplateAnimation_UDT.L5X” from the resources folder.
7

Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Dec 05, 2018

Download

Documents

lamkhue
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Safety Instruction Diagnostic Faceplate

Adding a safety Instruction faceplate to existing safety program with Control Logix

and Panel View Studio

Download the content from the AB website and place it in a folder named

“Resources”

Open Control Logix program and panel view application that you want to edit.

In Control Logix Import “SafetyInsructtion_FaceplateAnimation_UDT.L5X” from the

resources folder.

Page 2: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

After the UDT is imported, add the faceplate animation tags to the controller tags.

Name the animation tags to match the name of the Safety Instruction block you are

adding the diagnostic to.

Open Controller Tags/Edit Tags Tab and add the faceplate animation UDT. Enter the

name then edit tag, select the animations tags UDT.

Page 3: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

In Factory Talk View Studio import the safety instruction faceplate and the GoTo

Safety instruction graphic from the resource folder.

Repeat for the GoTo safety instruction graphic.

Import all of the safety instruction images from the resource folder.

Page 4: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Import the safety instruction parameter file from the resource folder.

Open the safety instruction faceplate from the graphics area. Right click the Safety

Instruction faceplate. Select Tag substitution.

Search and replace the #1 with the tag pointing to the Safety Instruction you are

intending to monitor.**DO NOT FORGET TO REMOVE BRACKETS**

Page 5: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Search and replace the #2 with the tag pointing to the “Faceplate Animation Tag”

of the UDT tag that was created In the Logix program.

**DO NOT FORGET TO REMOVE BRACKETS**

Open the GoTo Safety Instruction Graphic and copy Instruction_1 and paste it to

the desired screen. Instruction_1 has more detailed diagnostic functions than

Instruction_2.

Search and replace the “[GLX-L62S]InstructionName_1” with the tag pointing to

the Safety Instruction you are intending to monitor.

Page 6: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Right click the bottom graphic in the GoTo instruction and select properties. Under

the label tab, change the image to the type of safety device you intend to monitor.

Right click the Top text box in the GoTo instruction and select properties. Under the

States tab, change the states text to the name of safety device you intend to

monitor.

Page 7: Safety Instruction Diagnostic Faceplate - Home - D&D ... posts/Rockwell's... · In Factory Talk View Studio import the safety instruction faceplate and the GoTo Safety instruction

Testing

Create a runtime file to test

Press the E-Stop object to open the diagnostic window

To rename the faceplate, click in the title bar, type the new name by using the

popup Keyboard, and press Enter.

In Control Logix or on the physical safety device you can force the safety instruction to

fault (eg. jumpering the channels together, removing one channel while the other in still

energized…).

The faceplate includes these buttons:

• The Fault button launches the fault Probable Cause and Recommended Actions

views.

• The Diagnostics button launches the diagnostic Probable Cause and

Recommended Actions views.