Standards Quality Assurance Excitation and Voltage Regulators AVR Type DM110 DECS100 DECS150 Voltage Regulation ± 0.25% ± 0.25% ± 0.25% AVR Power PMG PMG PMG S9H1D-B4 Wdg.83 - Technical Data Sheet STAMFORD industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and AS1359. Other standards and certifications can be considered on request. Excitation System Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. with 4% Engine Governing No Load Excitation Voltage (V) 10.9 No Load Excitation Current (A) 0.99 Full Load Excitation Voltage (V) 41.9 Full Load Excitation Current (A) 3.81 Exciter Time Constant (seconds) 0.34 Page 1 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
9
Embed
S9H1D-B4 Wdg.83 - Technical Data Sheet - AvK · 2/20/2019 · Ta Armature Time Const. 0.0630 T’’q Sub-Transient Time Const. 0.0240 Resistances in Ohms (Ω) at 220C Stator Winding
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Standards
Quality Assurance
Excitation and Voltage Regulators
AVR Type DM110 DECS100 DECS150
Voltage Regulation ± 0.25% ± 0.25% ± 0.25%
AVR Power PMG PMG PMG
S9H1D-B4 Wdg.83 - Technical Data Sheet
STAMFORD industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant
section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and
AS1359. Other standards and certifications can be considered on request.
Excitation System
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
with 4% Engine Governing
No Load Excitation Voltage (V) 10.9
No Load Excitation Current (A) 0.99
Full Load Excitation Voltage (V) 41.9
Full Load Excitation Current (A) 3.81
Exciter Time Constant (seconds) 0.34
Page 1 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
50 Hz
THF<2%
2.78 m³/sec
10500 11000
- -
- -
2300 2300
Saturated Values in Per Unit at Base Ratings and Voltages
2.64 2.41
0.25 0.23
0.17 0.16
1.34 1.22
0.35 0.32
0.22 0.20
0.32 0.30
0.15 0.14
Unsaturated Values in Per Unit at Base Ratings and Voltages
3.17 2.89
0.29 0.26
0.20 0.18
1.38 1.26
0.42 0.38
0.25 0.23
0.28 0.25
0.39 0.35
0.18 0.16
S9H1D-B4 Wdg.83
Electrical Data
Insulation System H
Stator Winding Double Layer Lap
Winding Pitch 5/6
Winding Leads 6
Winding Number 83
NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
Short Circuit Ratio 1/Xd
Steady State X/R Ratio 18.25
4
IP Rating IP23
RFI Suppression BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N.
Refer to factory for others
Cooling Air Flow
Voltage Star (V)
kVA Base Rating (Class H) for
Reactance Values (kVA)
Telephone Interference
Number of Poles
Waveform Distortion
Xq Quad. Axis Reactance
Xd Dir. Axis Synchronous
X'd Dir. Axis Transient
X''d Dir. Axis Subtransient
Voltage Parallel Star (V)
Voltage Delta (V)
Xd Dir. Axis Synchronous
X''q Quad. Axis Subtransient
XL Stator Leakage Reactance
X2 Negative Sequence Reactance
X0 Zero Sequence Reactance
X'd Dir. Axis Transient
X''d Dir. Axis Subtransient
Xq Quad. Axis Reactance
X''q Quad. Axis Subtransient
XL Stator Leakage Reactance
Xlr Rotor Leakage Reactance
X2 Negative Sequence Reactance
X0 Zero Sequence Reactance
Page 2 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
11000V
SG1.0 0.168
SG1.2 0.72
S9H1D-B4 Wdg.83
Time Constants (Seconds) T’d Transient Time Const. 0.23
T’’d Sub-Transient Time Const. 0.0210
Exciter Stator Winding Resistance 9.8
T’do O.C. Field Time Const. 2.431
Ta Armature Time Const. 0.0630
T’’q Sub-Transient Time Const. 0.0240
Resistances in Ohms (Ω) at 220C
Stator Winding Resistance (Ra),
per phase for series connected0.6180
Rotor Winding Resistance (Rf) 0.5
Exciter Rotor Winding Resistance per
phase0.014
PMG Phase Resistance (Rpmg) per
phase3.8
Positive Sequence Resistance (R1) 0.7725
Shaft and Keys
All alternator rotors are dynamically balanced to better than BS6861: Part 1 Grade 2.5 for
minimum vibration in operation. Two bearing generators are balanced with a half key.
Negative Sequence Resistance (R2) 0.8899
Zero Sequence Resistance (R0) 0.7725
Saturation Factors
Mechanical Data
1 Bearing 2 Bearing
SAE Adaptor 0, 00 0, 00, None
Moment of Inertia 71.7 kgm² 68.6 kgm²
Weight Wound Stator 1638kg 1638kg
Shipping weight in a Crate 5350kg 5300kg
Weight Complete Alternator 5000kg 4950kg
Weight Wound Rotor 1776kg 1680kg
Packing Crate Size 260 x 200 x 220(cm) 260 x 200 x 220(cm)
Maximum Over Speed 2250 RPM for two minutes
Bearing Drive End - 6232
Bearing Non-Drive End 6324 6324
Page 3 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
S9H1D-B4 Wdg.83
50Hz
THREE PHASE EFFICIENCY CURVES
Page 4 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
Locked Rotor Motor Starting Curves - Separately Excited
Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
For voltage rise multiply voltage dip by 1.25
S9H1D-B4 Wdg.83
0.9 0.83
0.6 0.930.7 0.90.8 0.85
PF Factor
< 0.5 10.5 0.97
50Hz
60Hz
Page 5 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
3-phase 2-phase L-L 1-phase L-N
50Hz 60Hz Instantaneous x 1.00 x 0.87 x 1.30
Voltage Factor Voltage Factor Minimum x 1.00 x 1.80 x 3.20
10500V X 0.95 - - Sustained x 1.00 x 1.50 x 2.50
11000V X 1.00 - - Max. sustained duration 10 sec. 5 sec. 2 sec.
- - - -
- - - -
The sustained current value is constant irrespective of
voltage level
All other times are unchanged
S9H1D-B4 Wdg.83
Three-phase Short Circuit Decrement Curve - Separately Excited
Sustained Short Circuit = 430 Amps
Sustained Short Circuit = 500 Amps
Note 1The following multiplication factors should beused to adjust the values from curve betweentime 0.001 seconds and the minimum currentpoint in respect of nominal operating voltage :
Note 2The following multiplication factor should be used to convert thevalues calculated in accordance with NOTE 1 to thoseapplicable to the various types of short circuit :
Note 3Curves are drawn for Star connections under no-load excitation at rated speeds. For other connection (where applicable) the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2Series Delta = Curve current value X 1.732
50Hz
60Hz
Page 6 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
S9H1D-B4 Wdg.83
Typical Alternator Operating Charts
11000V/50Hz
4160V/60Hz
Page 7 S9H1D-B4_Wdg.83_A062J031_Rev.A_20.02.2019
S9H1D-B4 Wdg.83
RATINGS AT 0.8 POWER FACTOR
Class - Temp Rise
Star (V) 10500 11000 10500 11000 10500 11000 10500 11000