Standards Quality Assurance Excitation and Voltage Regulators AVR Type MX341 MX322 DECS100 DECS150 Voltage Regulation ± 1% ± 0.5% ± 0.25% ± 0.25% AVR Power PMG PMG PMG PMG Full Load Excitation Voltage (V) 62 Full Load Excitation Current (A) 2.5 Exciter Time Constant (seconds) 0.125 with 4% Engine Governing No Load Excitation Voltage (V) 24.35 No Load Excitation Current (A) 1.1 S7L1D-C4 Wdg.13 - Technical Data Sheet STAMFORD industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and AS1359. Other standards and certifications can be considered on request. Excitation System Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. Page 1 S7L1D-C4_Wdg.13_ES10456651_Rev.A_21.08.2019
9
Embed
S7L1D-C4 Wdg.13 - Technical Data Sheet...Aug 21, 2019 · Voltage Factor Voltage Factor Minimum x 1.00 x 1.80 x 3.20 - - 380V x 1.00 Sustained x 1.00 x 1.50 x 2.50 - - 400V x 1.05
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Standards
Quality Assurance
Excitation and Voltage Regulators
AVR Type MX341 MX322 DECS100 DECS150
Voltage Regulation ± 1% ± 0.5% ± 0.25% ± 0.25%
AVR Power PMG PMG PMG PMG
Full Load Excitation Voltage (V) 62
Full Load Excitation Current (A) 2.5
Exciter Time Constant (seconds) 0.125
with 4% Engine Governing
No Load Excitation Voltage (V) 24.35
No Load Excitation Current (A) 1.1
S7L1D-C4 Wdg.13 - Technical Data Sheet
STAMFORD industrial alternators meet the requirements of the relevant parts of the IEC EN 60034 and the relevant
section of other international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA C22.2-100 and
AS1359. Other standards and certifications can be considered on request.
Excitation System
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
Voltage Factor Voltage Factor Minimum x 1.00 x 1.80 x 3.20
- - 380V x 1.00 Sustained x 1.00 x 1.50 x 2.50
- - 400V x 1.05 Max. sustained duration 10 sec. 5 sec. 2 sec.
- - 416V x 1.09
- - - -
The sustained current value is constant irrespective of
voltage level
All other times are unchanged
S7L1D-C4 Wdg.13
Three-phase Short Circuit Decrement Curve - Separately Excited
Sustained Short Circuit = 8380 Amps
Sustained Short Circuit = Amps
Note 1The following multiplication factors should beused to adjust the values from curve betweentime 0.001 seconds and the minimum currentpoint in respect of nominal operating voltage :
Note 3The following multiplication factor should be used to convert thevalues calculated in accordance with NOTE 1 to thoseapplicable to the various types of short circuit :
Note 4Curves are drawn for Star connections under no-load excitation at rated speeds. For other connection (where applicable) the following multipliers should be applied to current values as shown : Parallel Star = Curve current value X 2Series Delta = Curve current value X 1.732
60Hz
60Hz
Note 2The sustained current values are for MX341AVR. For MX322 and Digital AVR 1.2 factor tobe applied to the sustained short circuit