AC axial fan - HyBlade ® sickled blades (S series) with guard grille for short nozzle S4E500-AM03-01 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type S4E500-AM03-01 Motor M4E110-GF Phase 1~ 1~ Nominal voltage VAC 230 230 Frequency Hz 50 60 Type of data definition ml ml Valid for approval / standard CE CE Speed min -1 1300 1400 Power input W 680 880 Current draw A 3.0 3.88 Motor capacitor μF 12 12 Capacitor voltage VDB 450 450 Max. back pressure Pa 150 100 Min. ambient temperature °C -40 -40 Max. ambient temperature °C 65 40 ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unit Subject to alterations Data according to ErP directive Installation category A Efficiency category Static Variable speed drive No Specific ratio * 1.00 * Specific ratio = 1 + p fs / 100 000 Pa Actual Request 2013 Request 2015 Overall efficiency η es 32.5 28.5 32.5 Efficiency grade N 40 36 40 Power input P e kW 0.65 Air flow q v m³/h 5765 Pressure increase p fs Pa 129 Speed n min -1 1315 Data established at point of optimum efficiency Item no. 10081-5-9980 · Revision 74126 · Release 2011-09-26 · Page 1 / 6 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
6
Embed
S4E500-AM03-01 AC axial fan-HyBlade · 2017-11-30 · AC axial fan-HyBlade ® sickled blades (S series) with guard grille for short nozzle S4E500-AM03-01 Product drawing 1 Direction
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
AC axial fan - HyBlade®
sickled blades (S series)with guard grille for short nozzle
Phase 1~ 1~Nominal voltage VAC 230 230Frequency Hz 50 60
Type of data definition ml mlValid for approval / standard CE CESpeed min-1 1300 1400Power input W 680 880Current draw A 3.0 3.88Motor capacitor µF 12 12Capacitor voltage VDB 450 450Max. back pressure Pa 150 100Min. ambient temperature °C -40 -40Max. ambient temperature °C 65 40ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unitSubject to alterations
Data according to ErP directive
Installation category AEfficiency category StaticVariable speed drive NoSpecific ratio* 1.00* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 32.5 28.5 32.5Efficiency grade N 40 36 40Power input Pe kW 0.65Air flow qv m³/h 5765Pressure increase pfs Pa 129Speed n min-1 1315Data established at point of optimum efficiency
sickled blades (S series)with guard grille for short nozzle
S4E500-AM03-01
Technical features
Size 500 mmSurface of rotor Coated in blackMaterial of terminal box PC/ABS plastic, blackMaterial of blades Press-fitted sheet steel blank, sprayed with PP plasticMaterial of guard grille Steel, phosphated and coated in black plasticNumber of blades 5Direction of air flow "V"Direction of rotation Counter-clockwise, seen on rotorType of protection IP 54Insulation class "F"Humidity class F4-1Max. permissible ambient motortemp. (transp./ storage)
+ 80 °C
Min. permissible ambient motortemp. (transp./storage)
- 40 °C
Mounting position Shaft horizontal or rotor on bottom; rotor on top on requestCondensate discharge holes Rotor-sideOperation mode S1Motor bearing Ball bearingTouch current acc. IEC 60990(measuring network Fig. 4, TNsystem)
<= 3.5 mA
Electrical leads Via terminal box, integrated capacitor connected via terminal boxMotor protection Thermal overload protector (TOP) brought outCable exit AxialProtection class I (if protective earth is connected by customer)Product conforming to standard EN 61800-5-1; CEApproval GOST; VDE; UL 1004-1; CSA C22.2 Nr.100
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1234
UV230230230230
fHz50505050
nmin-1
1380135513301300
Pe
W513571623680
IA2.252.502.733.00
LpAin
dB(A)68656365
LwAin
dB(A)75727072
LwAout
dB(A)75727071
qvm3/h8905793067055140
pfs
Pa050100150
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet sideqv = Air flow · pfs = Pressure increase
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1234
UV230230230230
fHz60606060
nmin-1
1530148514501400
Pe
W793828853880
IA3.453.613.733.88
LpAin
dB(A)70686665
LwAin
dB(A)77757372
LwAout
dB(A)78757372
qvm3/h9850899082207300
pfs
Pa04070100
U = Supply voltage · f = Frequency · n = Speed · Pe = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet sideqv = Air flow · pfs = Pressure increase