fr 1PS100-24 Vc / PS100-48 Vc

S1B1233100-01 1/4

en en

fr

fr

3

4 Description / Description

5 Dimensions / Dimensions 6 Installation / Installation

p PS100 is a power supply unit that supplies backup operating power for:p MV switchgear motor mechanismsp Transmission equipment (e.g. radio)p Control units such as RTU or Automatic Transfer Systemp Protection relays, Fault Passage Indicators and others electronic devices.p PS100 fournit une alimentation secourue pour :p La motorisation des cellules moyenne tension,p les équipements de communication (par exemple radio),p les unités de commande comme les RTU ou les automatismes de transfert de sources,p les relais de protection, les indicateurs de défaut et autres équipements électroniques.

Features / Fonctions

2 Unpacking / Déballage

EMS58580 24 VcEMS58581 48 Vc

en110/230 Va power supply terminal blockBattery state indication output contact

AB

110/230 Va power supply presence indication output contact Network voltage absence (red LED)

C

DBattery state not OK (red LED) PS100 internal fault (red LED)

EF

24/48 Vc output presence (green LED)12 Vc output presence (green LED)

GH

Modbus communication indicator (yellow LED)Power supply fault reset push button

J

KBattery connection terminal12 Vc output terminal

LM

24/48 Vc output terminalRJ45 Modbus network connectors

NP

Modbus address (rotary switches)Q

Bornier d'alimentation 110/230 Va

Contact de la sortie de signalisation de l’état de charge de la batterie

AB

Contact de la sortie de signalisation dela présence de l'alimentation 110/230 Va Absence de tension réseau (voyant rouge)

C

DEtat de la batterie non OK (voyant rouge) Faute interne PS100 (voyant rouge)

EF

Présence tension sortie 24/48 Vc (voyant vert)Présence tension sortie 12 Vc (voyant vert)

GH

Indicateur de communication Modbus(voyant jaune)Bouton de réarmement après défaut de l'alimentation

J

K

Connecteur batterieBornier de sortie 12 Vc

LM

Bornier de sortie 24/48 Vc

Connecteurs RJ45 réseau ModbusNP

Adresse Modbus (roues codeuses)Q

165

15

48V

12V

Test / Reset

Easergy

PS 100 - 48V

EMS58581

OK

OK

x10

N0

91

82

73

45 6

09

1

82

73

45 6

x1Ph.

48V24V

48V

12V

Test / Reset

Easergy

PS 100 - 48V

EMS58581

OK

OK

x10

N0

91

82

73

45 6

09

1

82

73

45 6

x1Ph.

48V24V

PS100-24 VcEMS58580

Bat 12V 24 AhEMS58582

PS100-48 VcEMS58581

7

1

2160

125

3

Click!

D

F

H

E

G

J

K

B C

NP M LQ

A

Bat 12V 38 AhEMS58583

Page 2: s1b1233100-01 (ps100)

8.1 Battery monitoring / Etat de la batterie

Ph

+-

N

S1B1233100-01

en p Test performed when battery fully loadedp Automatically every 12 hp By pushing the Test / Reset button

fr p Test effectué quand la batterie est complètement chargéep Automatiquement, toutes les 12 hp En appuyant sur le bouton Test / Reset

2/4

7 Connection / Raccordement

8 Battery Control / Gestion de la batterie

A

A

B

C

M

M

N

12 Vc

12 Vc

24/48 Vc

+-

12 Vc 24/38 Ah

24/48 V couplingCouplage du 24/48 V

Modbus

+-

C

Ph / N

10 mm 1.35 N.m4 mm2

10 mm 1.75 N.m10 mm2

N 24 / 48 Vc

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASHTurn off all power supplying this equipment before working on the equipment.Failure to follow these instructions will result in death or serious injury.

RISQUE D'ÉLECTROCUTION, D'EXPLOSION OU D’ARC ELECTRIQUECoupez l'alimentation de ce matériel avant intervention.Le non-respect de ces instructions provoquera la mort ou des blessures graves.

DANGER

++ -- +-

12 Vc

24/48 Vc

+ +

C

BB C

Voltage

Energy1 2

Serious discharge thresholdSeuil de déchargement critique

OFF éteinte

ON allumée

Backup thresholdSeuil de réserve1

2

8.2 Battery Testing / Test de la batterie

c

(Red / Rouge) (Green / Vert)

Page 3: s1b1233100-01 (ps100)

9.1 Modbus Register Table / Tableaux des registres Modbus

Modbus address 01 99Adresse Modbus 01 99

S1B1233100-01 3/4

9 Modbus Communication / Communication Modbus

x10 x1

+ = 01

Modbus cableCâble Modbus0.3 m VW3 A8 306 R031 m VW3 A8 306 R103 m VW3 A8 306 R30

Baud rateVitesse de transmission 9600 / 19200 / 38400

Parity / ParitéFormat / Format

Available values by automatic detection after power-up or long push on reset button. Permanent traffic is necessary to allow automatic detection. Valeurs possibles par détection automatique après mise sous tension ou après un appui long sur le bouton reset. Un trafic permanent est nécessaire pour la détection automatique.

No parity - 2 stop-bitEven parity - 1 stop-bitOdd parity - 1 stop-bit

Side female connectorCôté connecteur femelle

Modbus

... Modbus terminationTerminaison ModbusVW3 A8 306 RC

MeasuringWord Address Format Unit Range Default

valueFunction code

Description

0400h 16S % 0 -100 % 03, 04 Battery charge indicator 0401h 16S 0.1V 0-60V 03, 04 48 V output voltage0402h 16S 0.1V 0-16V 03, 04 12 V output voltage0403h 16S 0.1V 0-16V 03, 04 12 V battery voltage0405h 16S 0.1A 0-15A 03, 04 12 V output current0406h 16S 0.1A -200 ... +200A 03, 04 Battery current

Description

Description

Indicateur de charge batterie Tension de sortie 48 VTension de sortie 12 VTension de batterie 12 VCourant de sortie 12 VCourant batterie

StatusBit Address(*)

Format Unit Range Default value

Function code

Description

1008h Bit 01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

01, 02, 03, 04

coverable fault1: PS100 detected an internal minor problem which can be recovered (overtemperature, overcurrent, overvoltage).

Faute mineure récupérableMinor re1 : PS100 a détecté un problème interne mineur qui peut êtrerécupéré (surtempérature, surcourant, surtension).

Faute majeure non récupérable1 : PS100 a détecté un problème interne majeur qui ne peut être récupéré.

Bit

100Bh Bit Major unrecoverable fault1: PS100 detected an internal major problem which

1010h AC power supply off (< 30 % Vac)0 = On, 1= Off

Alimentation secteur arrêtée (< 30 % Vca)0 = Marche, 1 = Arrêt

1011h Bit General shutdown0 = No shut down 1 = Imminent shut down

Arrêt général0 = Pas d’arrêt1 = Arrêt imminent

1012h Bit Battery low0 = Charged 1 = Discharged (< backup threshold) or (10% charge left)

Batterie faible0 = Chargée1 = Déchargée (< seuil de réserve) ou (10% charge restante)

1013h Bit Battery fault0 = Operational 1 = Disconnected or out of order

Défaut batterie0 = Opérationnelle1 = Déconnectée ou hors service

1014h Bit Charger fault0 = Operational 1 = Out of order

Défaut chargeur0 = Opérationnel1 = Hors service

1015h Bit 12 V power supply failure0 = 12 V presence 1 = 12 V absence

Défaillance alimentation 12 V0 = Présence 12 V1 =Absence 12 V

1016h Bit

AC power supply low0 = On1 = Low (< 75% Vac during 1.5 s)

Défaillance alimentation 24/48 V0 = Présence 24/48 V 1 = Absence 24/48 V

CommonD0D1

1

can not be recovered.

01, 02, 03, 04

1017h Bit

24/48 V power supply failure0 = 24/48 V presence 1 = 24/48 V absence

Alimentation secteur basse0 = OK 1 = Niveau bas (< 75% Vca pendant 1,5 s)

Settings

03, 04, 06, 16

03, 04, 06, 16

03, 04, 06, 16

03, 04, 06, 16

03, 04, 06, 16

Word Address Format Unit Range1E04h 16S 0.1V 10 to 12.0 V 10.8 V

1E05h 16S 1 %

1E06h 16S 1: Enabled0: Disabled

0: Disabled

1E07h 16S hour

1E08h 16S 1

12 h

DescriptionDescription

Réserve d’énergie

Période de test de la batterieBattery test periodSélection des seuils Vca : Vac threshold selection:

activée / désactivée

Seuil de décharge critiqueSerious discharge threshold

Energy backup threshold5 % of the batterynominal capacity

Energy backup enabled / disabled

Seuil de réserve d’énergie

Default value Function code

03, 04, 06, 161E09h 16S 0.1 Ah 24 Ah Battery nominal capacity Capacité nominale de la batterie

0: Off = 52 Vac, Low = 129 Vac1: Off = 69 Vac, Low = 172 Vac

0 : Arrêté = 52 Vca, Bas = 129 Vca1 : Arrêté = 69 Vca, Bas = 172 Vca

0: < 180 VacAC power supply

1: > 180 Vac

(*) Word address = 3 first digits of bit address, example bit address = 1013h, word addess = 101h (to be used with Modbus functions 3 and 4)

Page 4: s1b1233100-01 (ps100)

fr

Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F - 92506 Rueil Malmaison Cedexwww.schneider-electric.com

S1B1233100-01 4/4

10 Technical data / Caractéristiques

Ce produit doit être installé, raccordé et utilisé en respectant les normes et/ou les règlements d'installation en vigueur.En raison de l'évolution des normes et du matériel, les caractéristiques et cotes d'encombrement données ne nous engagent qu'après confirmation par nos services.This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.As standards, specifications and designs change from time to time, always ask for confirmation of the informationgiven in this publication.

© 04-2012 Schneider Electric - All rights reserved.

en POWER SUPPLY

TECHNICAL CHARACTERISTICS

PS100-48 VcPS100-24 VcInput a voltage

Output c voltage VoltageCurrent

48 Vc ±10%

Output 12 Vc radio Voltage 12 Vc -10%, +25%

Auxiliary contact 2 dry contacts ‘‘Battery OK’’ and ‘‘AC supply ON’’

IEC 60 255-5 Insulation (50 Hz/1 min): 10 kV Surge (1.2/50 µs): 20 kVClimatic -40°C +70°C Operating.-40°C +85°C StorageWeight 2.5 kg

Relay type-breaking capacity 2 A 24 Vc, 1 A 48 Vc, 0-15 A 220 Va

Current 1.5 A rated 8 A 20 s Power 18 W / 100 W 20 sProtection By electronic against overloads and short circuits. Automatic restart after external fault.Limits A limitation, dedicated for radio units, is set up to avoid the battery discharge:

3 A in emitting mode for 3 mn.

2 A rated8 A for 15 s, 17 A peak for 50 ms

4 A rated16 A for 15 s, 25 A peak for 50 ms

Power 90 W rated with/without battery300 W (1 mn) with battery only

90 W rated with/without battery300 W (1 mn) with battery only

Protection By electronic against overloads and short circuits. Automatic restart after external fault.

24 Vc ±10%

Rated

LimitsProtection By electronic against reversal polarity and over voltage. Automatic restart after fault.

380 Vac

110 to 240 Va, +10%, -15%110 Vc , +20%, -20%

Limits Without battery total ouputs are limited to 90 W.Redundancy 2 units may be connected in parallel to increase availability.

Alimentation

Caractéristiques techniques

PS100-24 Vc PS100-48 VcTension a d’entrée

Tension c de sortie TensionCourant

24 Vc ±10%

Sortie 12 V c radio Tension 12 Vc -10%, +25%

Contacts auxiliaires 2 contacts secs Batterie OK et présence secteur

IEC 60 255-5 Isolement (50 Hz/1 min) : 10 kV Onde de choc (1,2/50 µs) : 20 kVClimatique Fonctionnement : -40°C à +70°C / Stockage : -40°C à +85°CPoids 2,5 kg

Pouvoir de coupure 2 A 24 Vc, 1 A 48 Vc, 0-15 A 220 Va

Courant 1,5 A nominal 8 A 20 s Puissance 18 W / 100 W 20 sProtection Electronique contre les surcharges et les court-circuits.

Redémarrage automatique après défaut externe. Limites Une limite dédiée aux unités radio est fixée pour éviter la décharge complète de la

batterie : 3 A pendant 3 mn.

2 A nominal8 A pendant 15 s, 17 A pic, 50 ms

4 A nominal16 A pendant 15 s, 25 A pic, 50 ms

Puissance 90 W nominal avec ou sans batterie300 W (1 mn) avec batterie uniquement

90 W nominal avec ou sans batterie300 W (1 mn) avec batterie uniquement

Protection Electronique contre les surcharges et les court-circuits. Redémarrage automatique après défaut externe.

48 Vc ±10%

Nominale

LimitesProtection Electronique contre les inversions de polarité et les surtensions.

Redémarrage automatique après défaut.

380 Vac

110 à 240 Va, +10%, -15%110 Vc , +20%, -20%

Limites

Redondance Possibilite de connecter en parallèle 2 unités pour augmenter la disponibilité.

Bit Address Format Unit Range Default value

Function code

Description

0F00h Bit 01, 02, 03, 04, 05, 06, 15, 16

01, 02, 03, 04, 05, 06, 15, 16

24V/48V restart 0F0Fh Module check

CommandsDescription

Redémarrage 24/48 VVérification moduleBit

Puissance totale de sortie sans batterie limitée à 90 W.