Top Banner

of 20

S-SMR-DM

Apr 08, 2018

Download

Documents

chiquilin2
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/7/2019 S-SMR-DM

    1/20

    RECTIFIER MODULE

    SMR-DM 48V-1800W -B

  • 8/7/2019 S-SMR-DM

    2/20

    VOCABULARY

    AC Alternating Current

    ADC Amps, Direct Current

    BTS Base Transceiver Station

    Temperature in degrees centigrade

    dB Decibel

    DC Direct current

    EMC Electro Magnetic Compatibility

    EN Europe Norm

    FCC Federal Communications Commission

    Temperature in degrees FahrenheitHz Frequency in hertz

    IEC International Elektrotechnical Commission

    I/O Input / Output, bi-directional

    IP Ingress protection

    ISO International Standards Organization

    Kg Kilo grams

    LED Light emitting diode

    Lbs Pounds

    mA Milli Amps

    MHz Mega Hertz

    mm Milli meter

    ms Milli second

    m/s Meters per second

    MTBF Mean time between failure

    NS Not Specified

    OVP Over voltage protection

    RH Relative humidity

    VAC Alternating current voltage

    VDC Direct current voltageUL Underwriters Laboratories

  • 8/7/2019 S-SMR-DM

    3/20

    CONTENTS

    1. FEATURES, BENEFITS & DESCRIPTIONS ....................................................4

    2. ELECTRICAL SPECIFICATIONS - INPUT PARAMETERS ..............................5

    3. ELECTRICAL SPECIFICATIONS - OUTPUT PARAMETERS ..........................7

    4. PROTECTION ..................................................................................................9

    5. INDICATORS & ADJUSTMENT......................................................................10

    6. MECHANICAL SPECIFICATIONS..................................................................12

    7. OUTLINE DIMENSIONS.................................................................................13

    8. STANDARD (CONTINUED)............................................................................15

    9. ENVIRONMENTAL .........................................................................................16

    10. LIFE TIME.....................................................................................................17

    11. SETTINGS AND CONTROLS.......................................................................18

    12. OUTPUT CONNECTOR DESCRIPTION......................................................20

  • 8/7/2019 S-SMR-DM

    4/20

    1. Features, Benefits & Descriptions

    Features & Benefits

    2U/3U height form factors

    Modular design for scalable, cost effective expansion

    Modular can be positioned in vertical (3U) or horizontal (2U) type

    Hot swappable- no system shutdown for maintenance

    Light weight plug-in modules for simple installation and maintenance

    High power density saves valuable floor space

    Unity power factor correction High efficiency

    Temperature compensation - Voltage correction for VRLA batteries

    Advanced load share technology

    Front access for simplified operation and maintenance

    Fan cooling

    Full protection function

    Description

    Sunlights SMR-DM 48V-1800W -B is a compact and very reliable family of front

    end modules offering 1800W at the output. The module can be inserted into 2U

    (horizontal) or 3U (vertical) racks, convenient to customers applications. These

    UL Listed SMR-DM Series Plug-in modules are rated at 30 Amps for -48VDC

    operation. These features afford you the flexibility to meet both todays power

    requirements and future growth as you increase your network demands.

  • 8/7/2019 S-SMR-DM

    5/20

    2. Electrical Specifications - Input Parameters

    Item Specification/Function Standard/Comment

    Number ofPhase/Number of Wire - Single phase/two wire with

    grounding wire

    Input Voltage- Nominal voltage

    - Input voltage range

    - No damage operation

    - 220V, Single Phase

    - 176V~275V: full load operation,150V~175V: 80% load operation,90V~150V: 50% load operation,

    -

    276V-300V

    Input Current- Maximum r.m.s.

    current- 12A At low line 176Vac

    input, rated power

    Input Power Factor- > 0.99 Full load, Nominal

    line

    Input Frequency- Input frequency range - 45Hz~65Hz

    Efficiency- >91% (Full Load) At Nominal Line

    Input, Rated OutputVoltage, Full Load

    Inrush Current-

  • 8/7/2019 S-SMR-DM

    6/20

    2. Electrical Specifications - Input Parameters (Continued)

    Item Specification/Function Standard/Comment

    Start Time Delay(Walk-in)- 3 ~ 10 seconds Full load, Nominal

    line, Rated outputvoltage

    DC and Signal Connector

    - Supplier

    - Component No.

    - Standard

    Positronic BERG

    5145-001

    UL/CSA approved

    AC Connector

    - Type

    - Standard

    Sunlight Standard 15ME2

    UL/CSA/VDE/SEV approved

    Input Protection(Fuse)

    - Type

    - Rating

    - Standard- Allocation

    Fuse

    20A

    UL/VDE approvedOn Board

    GND wiring character Resistance value < 0.1 at current 30A Standard

  • 8/7/2019 S-SMR-DM

    7/20

    3. Electrical Specifications - Output Parameters

    Item Specification/Function Standard/Comment

    Maximum Output Power- 1800W 60V/30A output

    Output Voltage- Nominal output voltage

    - Output voltage range

    - 54.3V

    40V~60V

    Rated Output Current30A

    Current LimitMaximum 110% of rated outputcurrent

    Dynamic Response- Overshoot

    - Recovery time

    - 5% of rated output voltage

    -

  • 8/7/2019 S-SMR-DM

    8/20

    3. Electrical Specifications - Output Parameters (Continued)

    Item Specification/Function Standard/Comment

    Voltage StabilityAccuracy

    0.6% Include load changeand line change

    Line Regulation - 0.1 %:

    100%V

    VVEquation

    B

    BA

    :

    VA: Output Voltage, At Input voltage-20%~+25% Range

    VB: Output Voltage, At Nominal Line

    Input voltage, Load 0~100%

    At rated outputVoltage, 0~ 100%Load, Input Voltage-20%~+25% RangeNormal Voltage 220v

    Noise

    - Audio band

    - Wide band

    - Peak to peak ripple

    voltage

    - Narrow band

    - Acoustic

    - 24 dBrnc

    - 40 dBrnc Or -54.26dbmp

    -

  • 8/7/2019 S-SMR-DM

    9/20

    4. Protection

    Item Condition Protection

    Input- Power Brown Out

    - Mains overvoltage

    - Mains undervoltage

    - 0~80% Of Rated Input Voltage

    - 310V 10V

    - 80V 10V

    No damage to SMR

    SMR shut down, SMRrestart after input voltagereturn to nominal linevoltage range

    SMR shut down , SMRrestart after input

    voltage return to nominalline voltage range

    Output- O/P voltage abnormal

    - Over Current

    - Output Short Circuit

    - >59.50.5V

    - 120%~135% Of Rated Current

    - Output short before start up orshort after start up.

    Shut down and latch

    Shutdown and restart

    Cause no damage toSMR, SMR current limit,

    restart after fault release

    Other Protection

    - Overtemperature

    - DC bus voltage

    abnormal

    - Fan Failure

    - 955 (Output-Diode heat sink)

    (Environment)

    - >440V 10V

    -

  • 8/7/2019 S-SMR-DM

    10/20

    5. Indicators & Adjustment

    Item Specification/Function Standard/Comment

    Line

    - Function

    - Component type

    - Color

    - On condition

    - Off condition

    - AC line ON

    - LED

    - Green

    - Line exceeds 70V (Typical)

    - No line or line under 50V

    (Typical)

    - The LED lights when AC

    line is normal.

    R.F.

    - Function

    - Component type

    - Color

    - On condition

    - Off condition

    - Rectifier Failed

    - LED

    - Red

    - Rectifier Fail

    - Rectifier Normal

    C.L.

    - Function

    - Component type

    - Color

    - On condition

    - Off condition

    - Current Limited

    - LED

    - Yellow

    - Output current is limited.

    - Output current under 110%

    of rated load. Outputcurrent is not limited.

    - The LED lights when the

    output current exceeds

    110% (default) of rated

    load.

    - The current limited point

    can be programmed byCSU.

    I+, I-

    - Function -Output Current Test Points - The I+, I- will send a

    voltage value, which can

    be transferred, to output

    current.

    0.1V =1A

    FLO

    - Function - Float VoltageAdjustment(40-60V)

    -Variable ResistorAdjustment

    - Increase in clockwise,

    decrease in

    counterclockwise.

  • 8/7/2019 S-SMR-DM

    11/20

    5. Indicators & Adjustment (Continued)

    Item Specification/Function Standard/Comment

    CL

    - Function - Current Limit (30-110%) - Variable Resistor

    Adjustment

    - Increase in clockwise,

    decrease in

    counterclockwise

  • 8/7/2019 S-SMR-DM

    12/20

    6. Mechanical Specifications

    Item Specification/Function Standard/Comment

    Width

    - Module Case - 3.3" / 83.6mm

    Height

    - Module Case - 5.2" / 132mm

    Depth

    - Module Case - 10.35" / 263mm -The dimension does

    not include the length

    of front panel screw

    and rear panel

    connector

    Weight - 7.26b / 3.3kg

    Marking Language - English

    Color - Front Panel: Pantone cool gray 5C

    - Case : Zn Plated, color : yellow

  • 8/7/2019 S-SMR-DM

    13/20

    7. Outline Dimensions

    RFA

    ACON

    I-CL

    FLO I+

    CL

    AC

    ON OFF

    83.6

    132.0

    263.0

    298.7

    25.2 263.0

    7.9

    120.5

    12.3

  • 8/7/2019 S-SMR-DM

    14/20

    8. Standard

    Item Specification/Function Standard/Comment

    Safety Mark

    - UL/CUL

    - TUV/CE

    - IEC 950

    - EN 60950

    EMI/RFI - System Meet : FCC Class B

    CISPR 22 Class B

    - SMR Meet : FCC Class A

    CISPR 22 Class A

    - FCC Part 15 Subpart J

    - EN55022,

    BS6527 Class B

    EMS

    - Voltage Fluctuation

    Flicker

    - Electrostatic Discharge

    (ESD)

    - Electromagnetic

    Compatibility(EMC)/Ra

    diated Susceptibility

    - Electrical FastTransient(EFT)

    - Conducted

    Susceptibility

    - Lightning/Surge

    - 15KV Air Discharge, 8KV

    Contact Discharge

    - 10V/m

    - 4KV

    - 10V/m

    - 6KV

    - EN 61000-3-3, EN

    60555-3

    - EN 61000-4-2 Level 4 ,

    IEC 1000-4-2, IEC 801-2

    Level 4

    - IEC 1000-4-3, IEC 801-3

    Level 3

    - EN 61000-4-4 Level 4,

    IEC 1000-4-4, IEC 801-4Level 4

    - IEC 1000-4-6 Level 3

    - IEC 1000-4-5 Level

    Special & ANSI/IEEE

    C62.41-1991 B3

    - Test Condition:

    1. Combination wave

    1.2/50us, 8/20us, 2,

    3KA

    2. Ring wave 100KHz,

    500A

  • 8/7/2019 S-SMR-DM

    15/20

    8. Standard (Continued)

    Item Specification/Function Standard/Comment

    Current Harmonic

    - EN 61000-3-2, EN

    60555-2, IEC 1000-3-2

    Class A

    Insulation Resistance

    - Input to output>2 M (At

    500Vdc)

    - Input to frame ground > 2 M

    (At 500Vdc)- Output to frame ground >2 M

    (At 500Vdc)

    Test Condition:

    - Humidity 90% R.H.,

    Non condensing, 25

    condition

    - Disconnect the FG

    wire from the case

    (Input to frame ground)

    Withstand voltage

    (High Pot) - Input To Output 4242 Vdc 1

    Minute (Or 3000 Vac 50Hz

    30mA)

    - Input to Frame Ground 2837 Vdc

    1 Minute (Or 2006 Vac 50Hz

    30mA)- Output to Frame Ground 707

    Vdc 1 Minute (Or 500 Vac 50Hz

    30mA)

    -For China market,

    1500VDC

    Leakage Current

    -

  • 8/7/2019 S-SMR-DM

    16/20

    9. Environmental

    Item Specification/Function Standard/Comment

    Operation Temperature

    - 0 ~ +50 (32 ~ +122)

    Operation Humidity

    - 0 ~ 95% Relative Humidity

    (Non-Condensing)

    Storage Temperature- -40 ~ +85 (-40 ~ +185)

    Storage Humidity

    - 0 ~ 95% Relative Humidity

    (Non-Condensing)

    Altitude

    - -152m~3048m (-500~10000

    Feet)

  • 8/7/2019 S-SMR-DM

    17/20

    10. Life Time

    Item MTBF Standard/Comment

    Rectifier

    - >150K hours At 25, rated load

    Cooling Fan

    - > 5 years

  • 8/7/2019 S-SMR-DM

    18/20

    11. Settings and Controls

    Setting from CSU

    Settings Description Comment

    Floating/equalize

    charging voltage

    - Function

    - Setting Window

    - Default

    - Floating/equalize charging voltage

    can be set from CSU

    - 53.3VDC-55.3VDC

    - 54.3VDC

    Current Limited

    - Function

    - Setting Window

    - Default

    - Current limited can be set from CSU

    - 0-110% , 1% per step

    - 110%

    DC High Voltage Shutdown

    - Function

    - Setting Window

    - Default

    - High voltage shutdown can be set

    from CSU

    - 57.5VDC~59.5VDC

    - 57.5VDC

    DC High Voltage Alarm

    - Function

    - Setting Window

    - Default

    - High voltage alarm can be set from

    CSU

    - 58VDC~59VDC

    - 57.5VDC

    DC Low Voltage Alarm

    - Function

    - Setting Window

    - Default

    - Low voltage alarm can be set from

    CSU

    - 44VDC~48VDC

    - 44VDC

  • 8/7/2019 S-SMR-DM

    19/20

    11. Settings and Controls (Continued)

    Setting from CSU

    Settings Description Comment

    Remote SMR On/Off

    - Function

    - Description

    - Remote SMR on/off capability exists

    through the CSU control.

    - CSU automatically shuts down SMR in

    case of DC high voltage.

    - Users can manually shut down SMR

    from CSU for optimizing energy

    operation purpose.

    Floating/equalize status

    - Function

    - Description

    - SMR floating/equalize status can be set

    through the CSU control.

    - CSU automatically transfer SMR to

    floating mode in case of

    (1). Periodical operation (Settable from

    CSU)

    (2). Mains recover after deep discharge

    resulted from blackout/battery test

    - Users can manually set SMR to floating

    or equalize from CSU.

    Actual Date or

    Periods Base

  • 8/7/2019 S-SMR-DM

    20/20

    12. Output Connector Description

    Signal

    Pin Meaning

    1 COM

    2 NC

    3 ITP14 RFA

    7 NO

    9 IBUS

    15 VASJ

    16 STDN

    20 CLL

    21 ICOM

    22 I (A/M)

    19

    1

    24