PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
MIN. 75mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
X
Z
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
EAVE FLASHING REQUIRED WHEN- ROOF PITCH ≤ 10°, OR- SOFFIT WIDTH ≤ 100mm, OR- WIND ZONES = VERY HIGH OR EXTRA HIGH OR- ENGINEER SPECIFIC DESIGN
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
ScaleDate SheetCRCG 1 : 2
FLUSH EAVE WITH EXTERNAL GUTTER BRACKET
04 / 142014
* CORRUGATE MIN. ROOF PITCH = 8°
EAVE FLASHING REQUIRED WHEN- ROOF PITCH ≤ 10°, OR- SOFFIT WIDTH ≤ 100mm, OR- WIND ZONES = VERY HIGH OR EXTRA HIGH OR- ENGINEER SPECIFIC DESIGN
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (CORRUGATE)
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
Y
Z
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (CORRUGATE)
MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)
Y
Z
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
ScaleDate SheetCRCG 1 : 2
BARGE WITH PROFILED CLADDING
07 / 142014
* CORRUGATE MIN. ROOF PITCH = 8°
BUILDING PAPERSHOWN DASHED
PRE-FINISHEDPARAPET CAPFLASHING
15.0
0°
CONTINUOUSTIMBER PACKING
MIN
. 5.0
0°
L
STOPENDS ROOFCLADDING
CONCRETE WALLBY ENGINEER
METALCRAFT MSS PURLIN BY ENGINEER
METALCRAFT CORRUGATE ROOFING
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
PRE-FINISHED FLATHEAD EXPANDINGMASONRY ANCHORSCREW WITH RUBBERWASHER FORFLASHING
PRE-FINISHED APRON FLASHING
METALCRAFTCORRUGATECLADDING ON CAVITY
SEPARATE BATTENAND CLADDING WITHEPDM AS REQUIRED
PVC CAVITY CLOSER
SOFT EDGE DRESSED OVERCORRUGATE RIBS
SAFETY MESH TO WORKSAFE NZREQUIREMENTS
NG
Z
CLE
ARAN
CE
25m
m
Z
SITUATION 1
1. LOW, MEDIUM, HIGH WIND ZONES2. ROOF PITCH ≥ 10°
MIN. 35mm
MIN. 75mm
MIN. 130mm(EXCLUDDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)
MIN. 50mm
SITUATION 2
1. VERY HIGH WIND ZONE2. ALL ROOF PITCHES
MIN. 35mm
MIN. 75mm
MIN. 200mm(EXCLUDDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)
MIN. 70mm
G
N
L
Z
SITUATION 3
1. EXTRA HIGH WIND ZONE2. ALL ROOF PITCHES
MIN. 35mm
MIN. 75mm
MIN. 200mm
MIN. 90mm
PLEASE REFER TO E2 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
CATEGORY A
1. NORMAL EXPOSURE2. ROOF PITCH >10°
25mm
MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)
MIN. 150mm
MIN. 50mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)
MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)
MIN. 200mm
MIN. 75mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)
G
N
L
Z
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
ScaleDate SheetCRCG 1 : 2
PARAPET WITH TRANSVERSE APRON
08 / 142014
* CORRUGATE MIN. ROOF PITCH = 8°
STOPENDS TO ROOFCLADDING
BUILDING PAPERSHOWN DASHED
METALCRAFT CORRUGATE ROOFING
CONCRETE WALL BYENGINEER
15.0
0°
PRE-FINISHED SELF DRILLING/TAPPINGSCREW WITH RUBBER WASHER
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (CORRUGATE)
M
PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2/2012 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
ScaleDate SheetCRCG 1 : 2
PARALLEL APRON
10 / 142014
* CORRUGATE MIN. ROOF PITCH = 8°
PRE-FINISHED FLASHING
STOPENDS TO ROOFCLADDING
METALCRAFT MSS PURLIN BY ENGINEER
METALCRAFTCORRUGATEROOFING
PRE-FINISHED POP RIVETS BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREWS
PRE-FINISHED FLAT HEADSELF DRILLING/TAPPINGSCREW WITH RUBBERWASHER FOR FLASHING
COMPRESSIBLE FOAM SEAL UNDER ROOFING.REFER TO MRM CODE OF PRACTICE VERSION2.2 /2012 FOR REQUIRMENT. STRUCTURAL STEEL
FRAMING BY ENGINEER
200mm
SAFETY MESH TOWORKSAFE NZREQUIREMENTS
PRE-FINISHEDFLASHING
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.
ScaleDate SheetCRCG 1 : 2
ROOF STEP
11 / 142014
SAFETY MESH TOWORKSAFE NZREQUIREMENTS
METALCRAFTCORRUGATETRANSLUCENT SHEET
FIXING WITH PROFILEDWASHER AND EPDMWASHER
METALCRAFT MSS PURLINBY ENGINEER
MID SPAN SUPPORT
PURLIN PROTECTION
PURLIN TAPE BARRIER STRIPSTRUCTURAL STEELFRAMING BY ENGINEER
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
ScaleDate SheetCRCG 1 : 5
TRANSLUCENT SHEETS - LONG
12 / 142014
SAFETY MESH TOWORKSAFE NZREQUIREMENTS
METALCRAFT CORRUGATETRANSLUCENT SHEET
FIXING WITH PROFILED WASHERAND EPDM WASHER
METALCRAFT MSS PURLINBY ENGINEER
MID SPAN SUPPORT
PURLIN PROTECTION
PURLIN TAPE BARRIER STRIP
METALCRAFT CORRUGATEROOFING
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.
COMMERCIAL ROOFING
- BUILDING PAPER IS THE COMMON GENERIC NAME FOR PERMEABLEROOF AND WALL UNDERLAYS. PLEASE REFER TO NZBC E2/AS1 ANDMRM CODE OF PRACTICE VERSION 2.2 /2012.
ScaleDate SheetCRCG 1 : 5
TRANSLUCENT SHEETS - CROSS
13 / 142014
METALCRAFT CORRUGATE ROOFING
METALCRAFT MSS PURLINBY ENGINEER
FIXING WITH PROFILED WASHERAND EPDM WASHER
STRUCTURALSTEEL FRAMINGBY ENGINEER
METALCRAFT TRANSLUCENTSHEET
STOPEND FLASHING SEALED TOTHE SHEETING
MID SPAN SUPPORT
Corrugate
Reference
DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRMcode of pratice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanismsis the responsibility of the designer. Construction detail can vary for wall cladding. The underlay isdetailed as a single line for simplicity and is indicative only. Building paper type and method ofinstallation should comply with underlay manufacturers recommendations and NZBC regulations.