RP-2000 Series Deluge & Agent Releasing Panels Alex Luk 23 rd April 2008
RP-2000 SeriesDeluge & Agent
Releasing Panels
Alex Luk
23rd April 2008
2
RP-2001(E)
Deluge System Designed for sprinkler
standards NFPA 13, 15 and 16
Replaces RP-1001(E) Adjustable waterflow
discharge timer and two soak timers
Cross-zone (double-interlock) capability
3
RP-2002(E)
Clean Agent System Designed for clean agent
releasing standards NFPA 12, 12A, and 2001
Replaces RP-1002(E) Adjustable pre-
discharge, discharge and waterflow delay timers
Cross-zone (double-interlock) capability
Programmable Abort operation
4
Common Features
Single or Dual Hazard Operation Six programmable Style B (Class B) IDCs (Initiating
Device Circuit) System Sensor I3 Series Smoke Detectors Any normally-open contact devices
Manual Pull Stations Pressure Switches Waterflow switches
Conventional 2-wire or 4-wire, 24 VDC smoke detectors
System Sensor I3 Series with Maintenance Alert and Freeze Sensor delivers industry first in a deluge system
5
Common Features
Four programmable Style Y (Class B) output circuits programmable for: Releasing Solenoids NACs programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex,
Faraday, Amseco) Selective Silence (horn-strobe mute) Temporal or Steady Signal Silenceable or Nonsilenceable Release Stage Sounder
7.0 amps total 24 VDC output current Resettable and non-resettable output power
2 Outputs, 500 mA each
6
Common Features
80-character LCD display (backlit) Built-in Programmer
Extensive transient protection Disable/Enable control per input zone and output
zone Three programmable Form-C relays
7
Common Features
Real-time clock/calendar with daylight savings time control
History log with 256 event storage Control Buttons
ACK (Acknowledge) Alarm Silence System Reset/Lamp Test Drill
Indicators Fire Alarm Supervisory Trouble AC Power Alarm Silence Discharge Abort (RP-2002 only)
8
Common Features
Piezo sounder for alarm, trouble and supervisory 24 volt operation Low AC voltage sense Integral battery charger automatically charges
batteries from 7 AH to 26 AH Up to 18 AH in the FACP enclosure 26 AH require BB-26 battery box “C” Version charges 7-12 AH
9
Common Features
Automatic battery charger with charger supervision Silent or audible walktest capabilities Optional Dress Panel DP-51050 (red) Optional CAC-5X Class A Converter Module for
Outputs and IDCs Optional 4XTMF Municipal Box Transmitter Module Optional Digital Alarm Communicators (411, 411UD,
411UDAC)
10
Programming Templates
Completely field programmable from the keypad Pre-programmed application templates (Deluge)
Single Hazard - 3 Zone Single Hazard - Cross-Zone With Manual Release Dual Hazard - Combined Release Dual Hazard - Split Release Single Hazard - 3 Zones and Low Pressure Single Hazard - 2 Zones Cross-Zoned With All Active Single Hazard - Dual Zone
Pre-programmed application templates (Agent) Cross-Zone System - Zones 1 & 4: All Active Single Zone System With Horn
Or – Create your own!
11
Common Features
ANN-BUS for connection to optional: N-ANN-80 Remote LCD Annunciator N-ANN-I/O LED Driver N-ANN-S/PG Printer Module N-ANN-RLY Relay Module N-ANN-LED Annunciator Module
12
ANN-Bus Devices
Up to 8 – any mix
N-ANN-80 Remote LCD
N-ANN-I/O LED Driver
N-ANN-S/PG Printer
N-ANN-RLY Relay
N-ANN-LED AnnunciatorRP-2000 Series
13
ANN-Bus Devices
N-ANN-80 Remote LCD Annunciator 80 character LCD Mimics FACP display Key switch controlled Switches
Silence Reset Drill
Switches can be individually disabled
LEDs AC Power Trouble Supervisory Fire Alarm Alarm Silenced
Mounts to single, double or 4” square electrical box. ANN-80BB available for surface mount applications
14
ANN-Bus Devices
N-ANN-I/O LED Driver Provides up to 40 LED outputs Used with custom graphic annunciators http://www.ledinc.com/
15
ANN-Bus Devices
N-ANN-S/PG Printer Module Provides remote serial or parallel output Connects to:
PRN-6 printer PC (Hyper Terminal) Any Serial/Parallel compatible device
Also used to download history
16
ANN-Bus Devices
N-ANN-RLY Relay Module 10 Individually Programmable Relays
2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive)
Mounts Inside the FACP enclosure
17
ANN-Bus Devices
N-ANN-LED Annunciator Module Provides LED annunciation of general
system faults and input zones Alarm (red) Trouble (yellow) Supervisory (yellow)
Supplied mounted to the DP-51050LED Dress Panel (RP-2001C or RP-2002C) Commonly used in City of Denver, Canada &
other jurisdictions requiring this type of annunciation
Remote mount option N-ANN-LEDBB