Product Data Sheet October 2014 00813-0300-4801, Rev AA Enable online mass and density calculation – no need for manual density sampling Use in all storage applications, including crude oil tanks, pressurized tanks and tanks with/without floating roofs Benefit from convenient and safe installation with 2-wire IS bus power supply Measure with industry leading 0.025% pressure accuracy, and density according to API chapter 3.6 Includes a wireless version utilizing a long-life IS power module Rosemount 3051S Pressure Transmitter High accuracy pressure measurement for tank gauging systems Note For the general 3051S Product Data Sheet, see document number 00813-0100-4801.
20
Embed
Rosemount 3051S Pressure Transmitter - Emerson · Rosemount 3051S pressure transmitter in tank gauging applications Get online mass and density measurement ... SG SST plug(s) for
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Product Data SheetOctober 2014
00813-0300-4801, Rev AA
Enable online mass and density calculation – no need for manual density sampling
Use in all storage applications, including crude oil tanks, pressurized tanks and tanks with/without floating roofs
Benefit from convenient and safe installation with 2-wire IS bus power supply
Measure with industry leading 0.025% pressure accuracy, and density according to API chapter 3.6
Includes a wireless version utilizing a long-life IS power module
Rosemount 3051S Pressure TransmitterHigh accuracy pressure measurement for tank gauging systems
NoteFor the general 3051S Product Data Sheet, see document number 00813-0100-4801.
Rosemount 3051S October 2014
Rosemount 3051S pressure transmitter in tank gauging applications
Get online mass and density measurement
Enhance your bulk liquid measurement and eliminate the need for manual sampling. By complementing the high accuracy level measurement with high performance temperature and pressure measurement, the density and mass of the product in the tank as well as net volume can be continuously calculated.
Rosemount 3051S is the standard pressure transmitter for Rosemount Tank Gauging Systems:
One or several pressure transmitters per tank can be used for liquid and vapor pressure
State-of-the-art pressure accuracy gives highest density precision
3051S supplies pressure data to the self-configured FOUNDATION™ fieldbus communication based Tankbus
The 3051S Series consists of transmitters and flanges suitable for all kinds of applications, including crude oil tanks and tanks with/without floating roofs.
3051S is also available as a wireless device, which can be used in an IEC 62591 (WirelessHART) network. It is powered by a long-life intrinsically safe power module, and has the same outstanding performance as the wired version.
For more information, see the 3051S Product Data Sheet (00813-0100-4801). Also see the Product Data Sheets 5900S (00813-0100-5900), 2240S (00813-0100-2240) and 565/566/765 (00813-0100-5565).
•Level•Temperature (spot and average)•Flow•Pressure•Density•Volume
•Mass2180Modem
2410 Tank Hub:
•Level•Oil/water interface level•Temperature (spot and average)•Pressure•Volume
•Observed density
5900SGauge
3051SPressureTransmitter(s)
2240STemperature
Transmitterwith sensor
A RosemountTank Gauging system configuration including level, temperature and pressure measurement instruments for high performance mass, density, volume, and level gauging
(TOV, GOV, GSV, NSV, WIA/WIV)
(TOV, 100 strapping points)
3051S Wireless Scalable Pressure Transmitter
2 www.rosemount-tg.com
Rosemount 3051SOctober 2014
Ordering Information
Rosemount 3051S Coplanar™ Pressure Transmitter
Rosemount 3051S Coplanar Pressure Transmitters are the industry leader for Differential, Gage, and Absolute pressure measurement.
For density measurement on non-viscous liquids such as diesel, and vapor pressure measurement. Capabilities include:
This section includes a selection of Rosemount pressure transmitter products and options. For complete information, see the 3051S Product Data Sheet (00813-0100-4801).
Table 1. Rosemount 3051S Coplanar Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Table 1. Rosemount 3051S Coplanar Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
4 www.rosemount-tg.com
Rosemount 3051SOctober 2014
I5 FM Intrinsically Safe; Nonincendive ★
IE(8) FM FISCO Intrinsically Safe (FOUNDATION fieldbus protocol only) ★
E6 CSA Explosion-proof, Dust Ignition-proof, Division 2 (Not available with M20 or G ½ conduit entry size) ★
Q8 Material traceability certification per EN 10204 3.1 ★
QT(9) Safety-certified to IEC 61508 with certificate of FMEDA data ★
T1(10)(11) Transient terminal block ★
GE(11)(12) M12, 4-pin, male connector (eurofast®) ★
GM(11)(12) A size Mini, 4-pin, male connector (minifast®) ★
P1 Hydrostatic testing with certificate
Typical Model Number: 3051S - 1 C G 3A 2 G11 F 1A - IA Q4
(1) For vapor pressure measurement (P3).
(2) For liquid pressure measurement (P1).
(3) Requires PlantWeb housing.
(4) Requires Housing Style code 5A and Wireless Options.
(5) Requires Transmitter Output code X.
(6) Requires Transmitter Output code X and Housing Style code 5A. Also see section for Hazardous Location Certification.
(7) Long-Life Power Module must be shipped separately, order power module 701 PBKKF.
(8) For use with Rosemount 2410 Tank Hub.
(9) Not available with Transmitter Output code F or X.
(10) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO Product Certification codes IA, IB, IE, IF and IG.
(11) Not available with Housing Style code 5A.
(12) Available with Intrinsically Safe approvals only. For FM Intrinsically Safe; Nonincendive (option code i5) or FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009. Suitable for use with all IS approvals (I1, I5, I6, I7, IA, IB, IE, IF and IG).
Table 1. Rosemount 3051S Coplanar Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
5www.rosemount-tg.com
Rosemount 3051S October 2014
Rosemount 3051S Liquid Level Pressure Transmitter
For density measurement of viscous liquids such as crude oil:
Integrated transmitter and direct mount seal in a single model number
Variety of process connections including flanged, threaded, and hygienic direct mount seals
This section includes a selection of Rosemount pressure transmitter products and options. For complete information, see the 3051S Product Data Sheet (00813-0100-4801).
Table 2. Rosemount 3051S Liquid Level Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
Model Product Description
3051SAL Scalable Advanced Level Transmitter for liquid level applications
Direct-Mount Extension (between transmitter flange and seal)
10 No extension
Transmitter Reference Pressure Connection
20 316 L SST Isolator with SST Transmitter flange ★
Seal Fill Fluid
D Silicone 200, -45 to 205 °C (-49 to 401 °F) ★
Process Connection Type
FF Flush flanged seal
Process Connection Size
G 2 in./DN50/50 A ★
7 3 in./80 A ★
J DN 80 ★
9 4 in./DN 100/100 A ★
Flange/Pressure Rating
1 ANSI/ASME B16.5 Class 150 ★
2 ANSI/ASME B16.5 Class 300 ★
G PN 40 per EN 1092-1 ★
E PN 10/16 per EN 1092-1, (DN100 only)
Materials of Construction
Isolating diaphragm Upper housing Flange
DA 316L SST 316L SST 316 SST ★
Flushing Connection Ring (lower housing)
A 316 SST ★
0 None ★
Flushing Connection Quantity & Size
0 None ★
3 Two ¼-18 NPT Flushing connections ★
Wireless options(4)
Update rate
WA User configurable update rate ★
Operating frequency and protocol
3 2.4 GHz DSSS, IEC 62591(WirelessHART) ★
Table 2. Rosemount 3051S Liquid Level Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
7www.rosemount-tg.com
Rosemount 3051S October 2014
Omni-directional wireless antenna
WK External antenna ★
WM Extended range, external antenna ★
SmartPower
1(5) Adapter for power module (intrinsically safe power module is sold separately) ★
Other options – none or multiple selections are possible
Q8 Material traceability certification per EN 10204 3.1 ★
QT(9) Safety-certified to IEC 61508 with certificate of FMEDA data ★
T1(10)(11) Transient terminal block ★
GE(12) M12, 4-pin, male connector (eurofast) ★
GM(12) A size Mini, 4-pin, male connector (minifast) ★
Q15(13) Certificate of Compliance to NACE MR0175/ISO 15156 for wetted materials ★
Table 2. Rosemount 3051S Liquid Level Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
8 www.rosemount-tg.com
Rosemount 3051SOctober 2014
Q25(13) Certificate of Compliance to NACE MR0103 for wetted materials ★
P1 Hydrostatic testing with certificate
Typical Model Number: 3051SAL - 2 C G 3A F 1A 10 20 D FF G 1 DA 0 0 - IA Q4
(1) Requires PlantWeb housing.
(2) Requires Housing Style code 5A and Wireless Options.
(3) Requires Transmitter Output code X.
(4) Requires Transmitter Output code X and Housing Style code 5A. Also see section for Hazardous Location Certification.
(5) Long-Life Power Module must be shipped separately, order Part #00753-9220-0001.
(6) For use with Rosemount 2410 Tank Hub.
(7) See the 3051S Reference manual (document number 00809-0100-4801) for cable requirements. Contact an Emerson Process Management representative for additional information.
(8) Not available with Option code QT.
(9) Not available with Transmitter Output code F or X.
(10) Not available with Housing Style code 5A.
(11) The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, IE, IF and IG.
(12) Not available with Housing Style code 5A. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2 (option code I5) or FM FISCO Intrinsically safe (option code IE), install in accordance with Rosemount drawing 03151-1009.
(13) Materials of construction comply with metallurgical requirements highlighted within NACE MR 0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR 0103 for sour refining environments.
Table 2. Rosemount 3051S Liquid Level Pressure Transmitter ordering information★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
__The Expanded offering is subject to additional delivery lead time.
For complete information and offering, see the Rosemount 3051S Product Data Sheet (document number 00813-0100-4801).
Performance specifications
Reference accuracy
Coplanar Pressure Transmitter: up to ± 0.025% of span for ultra version, up to ± 0.035% of span for classic version.
Liquid Level Pressure Transmitter: up to ± 0.055% of span for ultra version, up to ± 0.065% of span for classic version.
Vibration effect
Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10-60 Hz 0.21 mm displacement peak amplitude / 60-2000 Hz 3g).
Transient protection (option T1)
Tested in accordance with IEEE C62.41.2-2002, Location Category B6 kV crest (0.5 μs - 100 kHz)3 kA crest (8 x 20 microseconds)6 kV crest (1.2 x 50 microseconds)
Electromagnetic compatibility (EMC)
Meets all relevant requirements of EN 61326 and NAMUR NE-21.(1)
Functional specifications
Pressure range
-393 to 1000 inH2O (-0.98 to 2.5 bar). 1000 inH2O <=> 25 mH2O.
FOUNDATION fieldbus
Power supply
Powered by Rosemount 2410 Tank Hub.
Bus current draw
17.5 mA.
Class (basic or link master)
The transmitter can function as a backup Link Active Scheduler (LAS) if the current link master device fails or is removed from the segment.
Standard blocks and execution time
PlantWeb alerts
Yes
IEC 62591 (WirelessHART)
Output
IEC 62591 WirelessHART, 2.4 GHz DSSS.
Radio frequency power output from antenna
External antenna (WK option): Maximum of 10 mW (10 dBM) EIRP.
Extended range, External antenna (WM option): Maximum of 18 mW (12.5 dBm) EIRP.
Update rate
User selectable 1 sec. to 60 min.
Power module
Field replaceable, keyed connection eliminates the risk of incorrect installation, Intrinsically Safe Lithium-thionyl chloride Power Module with polybutadine terephthalate (PTB) enclosure. Ten-year life at one minute update rate.(2)
(1) NAMUR NE-21 does not apply to Transmitter Output code X (Wireless).
(2) Reference conditions are 21 °C (70 °F), and routing data for three addi-tional network devices. NOTE: Continuous exposure to ambient temperature limits of -40 °C or +85 °C (-40 °F or +185 °F) may reduce specified life by less than 20 percent.
10 www.rosemount-tg.com
Rosemount 3051SOctober 2014
Temperature limits
Ambient
-40 to +85 °C (-40 to +185 °F)With LCD display(1): -40 to +80 °C (-40 to +175 °F)
Storage
-46 to +85 °C (-50 to 185 °F)With LCD display: -40 to +85 °C (-40 to +185 °F)With Wireless output: -40 to +85 °C (-40 to +185 °F)
Process
Coplanar Pressure Transmitter: -40 to + 149 °C (-40 to + 300 °F)
Liquid Level Pressure Transmitter: -45 to + 205 °C (-49 to + 401 °F)
Humidity limits
0–100% relative humidity.
Physical specifications
Electrical connections
½ - 14 NPT and M20 x 1.5 entries for cable glands and conduits.
Tankbus cabling
0.5-1.5 mm² (AWG 22-16), twisted shielded pairs.
Non-wetted parts
Electronics housing
Low-copper aluminum alloy or CF-8M (Cast 316 SST) NEMA 4X, IP 66, IP 68 (66 ft (20 m) for 168 hours).
Note: IP 68 not available with Wireless Output.
Paint for aluminum housing
Polyurethane.
Weight
4 to 15 kg (9-33 lbs) including tank connection, depending on transmitter choice.
Integral display
Yes.
Configuration tools
Field Communicator, AMS™ Suite, DeltaV® or any other DD (Device Description) compatible host system.
Tank gauging pressure applications
Pressure transmitters are used in two main configuration alternatives:
Tank ventilated to atmosphere: There is one pressure transmitter installed at the bottom of the tank (P1) to measure liquid pressure (PL).
Pressurized, non-ventilated tank (possibly with a vapor recovery system), and blanketed tanks (nitrogen): One pressure transmitter is installed at the bottom of the tank (P1), and one pressure transmitter is installed at the top (P3) to measure vapor pressure. The liquid pressure, PL=P1-P3
The pressure transmitter installed to measure vapor pressure should always be of coplanar type, non-flanged version (E12 in model code).
The pressure transmitter which measures liquid pressure, should be of either flanged liquid level or coplanar type. The liquid level pressure transmitter is used for crude oil applications, and the coplanar pressure transmitter is used for any other liquid type.
Calibration
Use a T-connection with drain valve, which is necessary for zero calibration of the pressure transmitter installed to measure liquid pressure at the bottom of the tank.
(1) LCD display may not be readable and display updates will be slower at temperatures below -20 °C (-4 °F).
Rosemount TankRadar
FBM 2180
Ext.
pwr
RS-
232
US
B
Tx Rx
Lo - GAIN - Hi On - TERM - Off
P3: 3051S, coplanar version
P1: 3051S
Shut-off isolation and drain valves used for zero calibration of the pressure transmitter.
For complete information and offering, see the Rosemount 3051S Product Data Sheet (document number 00813-0100-4801).
European Directive InformationA copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
Ordinary Location Certification from FM ApprovalsAs standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized testing laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
United States of America
E5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)Certificate: 3008216Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class
3810 – 2005, ANSI/NEMA 250 –2003Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II; DIV 1, GP E, F, G;
CL III; T5(-50 °C Ta +85 °C ); Factory Sealed; Type 4X
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)Certificate: 3012350Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class
3611 – 2004, FM Class 3810 – 2005, NEMA 250 –2003Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G
Class III; Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C Ta +70 °C ) [HART]; T4(-50 °C Ta +60 °C ) [fieldbus]; when connectedper Rosemount drawing 03151-1006; Type 4x
Special conditions for safe use (X):
1. The Model 3051S Pressure Transmitter contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
NoteTransmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03051-1006.
IE FM FISCO Field DeviceCertificate: 3012350Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class
3611 – 2004, FM Class 3810 –2005, NEMA 250 –2003Markings: IS CL I, DIV 1, GP A, B, C, D; (-50 °C Ta +60 °C ); when
connected per Rosemount drawing 03151-1006; Type4x
Special conditions for safe use (X):
1. The Model 3051S Pressure Transmitter contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
Markings: Explosionproof Class I, Division 1, Groups B, C, D;Dust-Ignitionproof Class II, Division 1, Groups E, F, G;Class III; suitable for Class I, Zone 1, Group IIB+H2, T5;suitable for Class I, Division 2, Groups A, B, C, D;suitable for Class I, Zone 2, Group IIC, T5; whenconnected per Rosemount drawing 03151-1013; Type4x
Markings: FISCO Intrinsically Safe Class I, Division 1; suitable for Class I, Zone 0; T3C; when installed per Rosemount drawing 03151-1016; Type 4X
Europe
E1 ATEX FlameproofCertificate: KEMA 00ATEX2143XStandards: EN 60079-0:2012, EN 60079-1: 2007, EN
60079-26:2007Markings: II 1/2 G Ex d IIC T6...T4 Ga/Gb,
T6(-60 °C Ta +70 °C), T5/T4(-60 °C Ta +80 °C)Temperature class Process temperature
T6 -60 °C to +70 °CT5 -60 °C to +80 °CT4 -60 °C to +120 °C
12 www.rosemount-tg.com
Rosemount 3051SOctober 2014
Special conditions for safe use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints, the manufacturer shall be contacted.
I1 ATEX Intrinsic SafetyCertificate: BAS01ATEX1303XStandards: EN 60079-0: 2012, EN 60079-11: 2012Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
IA ATEX FISCO Field DeviceCertificate: BAS01ATEX1303XStandards: EN 60079-0:2012, EN 60079-11: 2012Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of EN 60079-11:2012. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
IEC 60079-26:2006, IEC 60079-31:2008Markings: Ex d IIC T6... T4 Ga/Gb, T6(-60 °C Ta +70 °C),
T5/T4(-60 °C Ta +80 °C)
Special conditions for safe use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
Certificate: IECEx BAS 09.0014X (Dust)Standards: IEC 60079-0:2011, IEC 60079-31:2008Markings: Ex ta IIIC T105 °C T500 95°C Da, (-20 °C Ta +85 °C)
Vmax = 42.4 V
Special conditions for safe use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient temperature range of the apparatus and capable of withstanding a 7J impact test.
4. The 3051S- SuperModule must be securely screwed in place to maintain the ingress protection of the enclosure.
HART FieldbusVoltage Ui 30 V 30 VCurrent Ii 300 mA 300 mAPower Pi 1 W 1.3 WCapacitance Ci 12 nF 0Inductance Li 0 0
FISCOVoltage Ui 17.5 VCurrent Ii 380 mAPower Pi 5.32 WCapacitance Ci 0Inductance Li 0
Temperature class
Process temperature
T6 -60 °C to +70 °CT5 -60 °C to +80 °CT4 -60 °C to +120 °C
13www.rosemount-tg.com
Rosemount 3051S October 2014
I7 IECEx Intrinsic SafetyCertificate: IECEx BAS 04.0017XStandards: IEC 60079-0: 2011, IEC 60079-11:2011Markings: Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of IEC 60079-11:2011. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish, however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
IG IECEx FISCOCertificate: IECEx BAS 04.0017XStandards: IEC 60079-0: 2011, IEC 60079-11:2011Markings: Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.3.13 of IEC 60079-11:2011. This must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
Brazil
E2 INMETRO FlameproofCertificate: CEPEL 03.0140X [Mfg USA, Singapore, Germany],
60079-1:2009, ABNT NBR IEC 60529:2009Markings: Ex d IIC T* Ga/Gb, T6(-40 °C Ta +65 °C),
T5(-40 °C Ta +80 °C), IP66(AI)/IP66W(SST)
Special conditions for safe use (X):
1. For ambient temperature above 60 °C, cable wiring must have minimum isolation temperature of 90 °C, to be in accordance to equipment operation temperature.
2. The device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
I2 INMETRO Intrinsic SafetyCertificate: CEPEL 05.0722X [Mfg USA, Singapore, Germany],
Markings: Ex ia IIC T4 Ga, T4(-20 °C Ta +70 °C),IP66(AI)/IP66W(SST)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.4.12 of IEC 60079-11. This must be taken into account during installation.
IB INMETRO FISCOCertificate: CEPEL 05.0722X [Mfg USA, Singapore, Germany],
Markings: Ex ia IIC T4 Ga, T4(-20 °C Ta +40 °C),IP66(AI)/IP66W(SST)
Special conditions for safe use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of withstanding the 500 V test as defined in Clause 6.4.12 of IEC 60079-11. This must be taken into account during installation.
HART FieldbusVoltage Ui 30 V 30 VCurrent Ii 300 mA 300 mAPower Pi 1 W 1.3 WCapacitance Ci 12 nF 0Inductance Li 0 0
FISCOVoltage Ui 17.5 VCurrent Ii 380 mAPower Pi 5.32 WCapacitance Ci 0Inductance Li 0
HART FieldbusVoltage Ui 30 V 30 VCurrent Ii 300 mA 300 mAPower Pi 1 W 1.3 WCapacitance Ci 12 nF 0Inductance Li 0 0
FISCOVoltage Ui 17.5 VCurrent Ii 380 mAPower Pi 5.32 WCapacitance Ci 0Inductance Li 0
14 www.rosemount-tg.com
Rosemount 3051SOctober 2014
Wireless Certifications
European Directive InformationA copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
Telecommunication complianceAll wireless devices require certification to ensure they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification.Emerson working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
FCC and ICThis device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons.
Ordinary Location Certification from FM ApprovalsAs standard, the transmitter has been examined and tested to determine that the design meets basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North AmericaThe US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
United States of America
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)Certificate: 3027705Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class
3611 – 2004, FM Class 3810 – 2005, NEMA 250 –2003Markings: IS CL 1, DIV 1, GP 1, B, C, D; CL II, DIV 1, GP E, F, G
CL III, CL 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D, T4; DIP CL II, DIV 1, GP E, F, G; CL III, T5;T4(-50 °C Ta +70 °C ) /T5 (-50 °C Ta +85 °C ) when connected per Rosemount drawing03151-1000; Type 4x
Special conditions for safe use (X):
1. The transmitter may contain more than 10% aluminum and is considered a potential risk of ignition by impact or friction.
2. The surface resistivity of the antenna is greater than 1Gavoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
NoteTransmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing 03051-1000.
Markings: Intrinsically Safe Class I, Division 1; suitable for Class 1,Zone 0, IIC, T3C; when connected per Rosemount drawing 03151-1010; Type 4x
Europe
I1 ATEX Intrinsic SafetyCertificate: Baseefa 13ATEX0127XStandards: EN 60079-0: 2012, EN 60079-11: 2012Markings: II 1 G Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Wireless enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0 area.
2. The surface resistivity of the antenna is greater than 1GTo avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or dry cloth.
International
I7 IECEx Intrinsic SafetyCertificate: IECEx BAS 13.0068XStandards: IEC 60079-0: 2011, IEC 60079-11:2011Markings: Ex ia IIC T4 Ga, T4(-60 °C Ta +70 °C)
Special conditions for safe use (X):
1. The Model 3051S Wireless enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion of located in a zone 0 area.
2. The surface resistivity of the antenna is greater than 1G. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or dry cloth.