Sensible Efficiency: Thermal Effectiveness: Based on temperature differenal between the 2 airstreams Efficiency: Takes into account all power inputs RNC5-TPD HEAT RECOVERY VENTILATOR All units conf orm t o CS A and UL standards ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each airstream has an independent motorized impeller with multiple fan speed operations. FILTERS Washable air filters in exhaust and supply airstreams. MOUNTING THE HRV Threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit. DEFROST Recirculating damper defrost system. CASE 20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent exterior condensation. Drain connections: Two 1/2 in (12 mm) OD. Balancing ports are located on unit. INSTALLER SELECTABLE HIGH SPEED SETTINGS Adjustable DIP switches are located on the circuit board, Hi3 is the factory setting. Refer to the Installation manual for the adjustment instructions. ELECTRONICS The optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge (min.) 100 ft length (max.). CONTROL OPTIONS WEIGHT 51 lbs (23 kg) SHIPPING WEIGHT 54 lbs (25 kg) Units carry a lifeme warranty on the HRV core and a 5 year replacement parts warranty. _ _ _ _ _ _ _ _ _ Date: Tag: Qty: Project: Engineer: Contractor: Supplier: Quote #: Submitted By: Airflow (cfm) 20 40 60 80 100 120 140 0 0 0.1 0.2 0.3 0.4 0.5 0.6 1 2 160 Static Pressure (in w.g.) 0.7 0.8 180 0.9 1.0 1.1 3 Low NOTE: All specificaons are subject to change without noce. 17 1/4 in (438 mm) 22 3/4 in (578 mm) 14 in (356 mm) Front View Top View Fresh Outside Stale Air To Outside Fresh Air From Air To Inside Stale Air From Inside Condensate Drains Motorized Impeller Removable Heat Recovery Core Recirculating Defrost Damper (For TPD Model Only) Filter Note: Front clearance of 25 in (635 mm) is recommended for servicing unit. All ducts use 5 in (125 mm) oval collars, balancing dampers are located on all collars. DIMENSIONS RNC5-TPD ACCESSORY OPTIONS 99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm) 99-185 Weatherhoods - Two 5 in (127 mm) 99-190 Dual Hood - One 6 in (152 mm) opening for supply and exhaust. TIMER OPTIONS 99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes. 99-BC03 Lifebreath Ventilation Control Continuous Low fan speed Humidity control through adjustable Dehumidistat 3 modes of operation: Ventilation, Recirculation, 20/40 Compatible with 99-DET02 Wireless Timers 3 wire connection 99-DXPL02 Lifebreath Digital Control 5 speed operation on each mode Humidity control through adjustable Dehumidistat 5 user selectable operational modes: Continuous Ventilation, Continuous Recirculation, 20 ON/40 OFF, 10 ON/50 OFF, 20 ON/40 Recirculation 20/40/60 min. High speed override button Compatible with 99-DET02 Wireless Timers 3 wire connection 99-BC02 Lifebreath Ventilation Control 2 speed fan setting (Low/High) Humidity control through adjustable Dehumidistat Compatible with 99-DET02 Wireless Timers 3 wire connection between timer and main wall control if timer is out of range. 99-BC04 Lifebreath Ventilation Control 2 speed fan setting (Low/High) 2 modes of operation: Ventilation, 20/40 Compatible with 99-DET02 Wireless Timers 3 wire connection 99-DH01 Lifebreath Dehumidistat Humidity control through adjustable Dehumidistat 3 wire connection 3 wire connecon. 99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes. Wirelessly connects to main control for ease of installation. 40' approximate range. 99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into 120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point Performance (H V I c e rfie d) Net supply airflow in cfm (L /s) against external stac pressure @ 0.1 in (25 Pa) 169 cfm (80 L/s) @ 0.2 in (50 Pa) 156 cfm (73 L/s) @ 0.3 in (75 Pa) 149 cfm (70 L/s) @ 0.4 in (100 Pa) 136 cfm (64 L/s) @ 0.5 in (125 Pa) 126 cfm (59 L/s) @ 0.6 in (150 Pa) 116 cfm (54 L/s) @ 0.7 in (175 Pa) 103 cfm (48 L/s) @ 0.8 in (200 Pa) 89 cfm (42 L/s) @ 0.9 in (225 Pa) 77 cfm (36 L/s) @ 1.0 in (250 Pa) 58 cfm (27 L/s) Max. Temperature Recovery 78% Sens ible Eecvenes s @ 66 cfm (31 L/s ) 32°F (0°C ) 74% Sens ible Eciency @ 66 cfm (31 L/s ) 32°F (0°C ) 61% Sens ible Eciency @ 76 cfm (36 L/s ) -13°F (-25°C ) 61% VAC @ 60Hz 120 Was / L ow speed. 69 Was / High speed 147 Amp ra ng 1.2 External Stac Pressure Airflow
1

RNC5-TPD - lifebreath.com · Sensible Efficiency: Thermal Effectiveness:Based on temperature differential between the 2 airstreams Efficiency: Takes intoaccount all power inputs

Aug 25, 2018

Download

Documents

phamkhanh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: RNC5-TPD - lifebreath.com · Sensible Efficiency: Thermal Effectiveness:Based on temperature differential between the 2 airstreams Efficiency: Takes intoaccount all power inputs

Sensible Efficiency: Thermal Effectiveness: Based on temperature differential between the 2 airstreamsEfficiency: Takes into account all power inputs

RNC5-TPD HEAT RECOVERY VENTILATOR

All units conform to CSA and UL standards

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM COREThe cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.MOTORS AND BLOWERSEach airstream has an independent motorized impeller with multiple fan speed operations.FILTERSWashable air filters in exhaust and supply airstreams.MOUNTING THE HRVThreaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.DEFROSTRecirculating damper defrost system.CASE20 gauge prepainted galvanized steel for superior corrosion resistance, insulated to prevent exterior condensation. Drain connections: Two 1/2 in (12 mm) OD. Balancing ports are located on unit.INSTALLER SELECTABLE HIGH SPEED SETTINGSAdjustable DIP switches are located on the circuit board, Hi3 is the factory setting. Refer to the Installation manual for the adjustment instructions.ELECTRONICSThe optional controls can be wall mounted in a central location of the home. 3 wire 20 gauge (min.) 100 ft length (max.). CONTROL OPTIONS

WEIGHT 51 lbs (23 kg) SHIPPING WEIGHT 54 lbs (25 kg)

Units carry a lifetime warranty on the HRV core anda 5 year replacement parts warranty.

_

__

_

_

_

_

_

_

Date:

Tag: Qty:

Project:

Engineer:

Contractor:

Supplier:

Quote #:

Submi�tted By:

Air

flow

(cf

m)

20

40

60

80

100

120

140

00

0.1 0.2 0.3 0.4 0.5 0.6

1

2

160

Static Pressure (in w.g.)

0.7 0.8

180

0.9 1.0 1.1

3

Low

NOTE: All specifications are subject to change without notice.

17 1

/4 in (

438 m

m)

22 3/4 in (578 mm)

14 in (

356 m

m)

Front View Top View

Fresh

Outside

Stale Air To

Outside

Fresh Air From Air To

Inside

Stale Air From

Inside

Condensate Drains

Motorized Impeller

Removable Heat

Recovery Core

Recirculating Defrost Damper (For TPD Model

Only)

Filter

Note: Front clearance of 25 in (635 mm) is recommended for servicing unit. All ducts use 5 in (125 mm) oval collars, balancing dampers are located on all collars.

DIMENSIONS RNC5-TPD

ACCESSORY OPTIONS99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm) 99-185 Weatherhoods - Two 5 in (127 mm) 99-190 Dual Hood - One 6 in (152 mm) opening for supply and exhaust.

TIMER OPTIONS99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.

99-BC03 Lifebreath Ventilation Control••

Continuous Low fan speedHumidity control through adjustable Dehumidistat3 modes of operation: Ventilation, Recirculation, 20/40

• Compatible with 99-DET02 Wireless Timers• 3 wire connection

99-DXPL02 Lifebreath Digital Control• 5 speed operation on each mode• Humidity control through adjustable

Dehumidistat• 5 user selectable operational modes: Continuous

Ventilation, Continuous Recirculation, 20 ON/40 OFF, 10 ON/50 OFF, 20 ON/40 Recirculation

• 20/40/60 min. High speed override button• Compatible with 99-DET02 Wireless Timers• 3 wire connection

99-BC02 Lifebreath Ventilation Control• 2 speed fan setting (Low/High)• Humidity control through adjustable

Dehumidistat• Compatible with 99-DET02 Wireless Timers• 3 wire connection

between timer and main wall control if timer is out of range.

99-BC04 Lifebreath Ventilation Control• 2 speed fan setting (Low/High)• 2 modes of operation: Ventilation, 20/40• Compatible with 99-DET02 Wireless

Timers• 3 wire connection

99-DH01 Lifebreath Dehumidistat• Humidity control through adjustable

Dehumidistat• 3 wire connection

3 wire connection.99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60

minutes. Wirelessly connects to main control for ease of install ation. 40' approximate range.99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into

120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point

Performance (H V I c e rtifie d)Net supply airflow in cfm (L /s) against external static pressure

@ 0.1 in (25 Pa) 169 cfm (80 L/s)@ 0.2 in (50 Pa) 156 cfm (73 L/s)@ 0.3 in (75 Pa) 149 cfm (70 L/s)@ 0.4 in (100 Pa) 136 cfm (64 L/s)@ 0.5 in (125 Pa) 126 cfm (59 L/s)@ 0.6 in (150 Pa) 116 cfm (54 L/s)@ 0.7 in (175 Pa) 103 cfm (48 L/s)@ 0.8 in (200 Pa) 89 cfm (42 L/s)@ 0.9 in (225 Pa) 77 cfm (36 L/s)@ 1.0 in (250 Pa) 58 cfm (27 L/s)

Max. Temperature Recovery 78%Sens ible Effectiveness @ 66 cfm (31 L/s ) 32°F (0°C ) 74%Sens ible Efficiency@ 66 cfm (31 L/s ) 32°F (0°C ) 61%

Sens ible Efficiency@ 76 cfm (36 L/s ) -13°F (-25°C ) 61%

VAC @ 60Hz 120

Watts / L ow speed. 69

Watts / High speed 147

Amp rating 1.2

External Static Pressure Airflow