RLC AFTERMARKET SITE EVALUATION FORM Page 1 Indoor Unit 1: Indoor Unit 2: Indoor Unit 3: Indoor Unit 4: Indoor Unit 5: Indoor Unit 6: Indoor Unit 7: Indoor Unit 8: 1)Is this a New installation: 2)Is there a Condensate Pump installed: 3)Is there a PI-485 Installed: 4)Are any IDU's Group Controlled: 5)Is there any Remote Temp Sensors Installed: 6)Is there a Dry Contactor Installed: 7)Does this unit have a Surge Protector Installed: 8)Are there any wall stats in system: 9)Are there any 3rd party wall stats in system: 10)Have any trouble shooting steps been taken: ERROR CODE: Additional Information: 11)Interconnecting wire shielded: 12)Interconnecting wiring Grounded: 13)Confirm no wire splices: 14)Confirm no Vertical Loops in piping: Indoor Unit Serial Number: MODEL INFORMATION Outdoor Unit Model Number: Initial System Installation Questions: * If yes to any please provide any additional information below. Zip Code: Installing or Service Contractor Name: City: State: Zip Code: Date of Original Installation: Repair Dates (If Any): Branch Distribution Box 2: Model Number: Serial Number: Indoor Unit Model Number: Indoor Unit Serial Number: Branch Distribution Box 1: Model Number: Serial Number: Outdoor Serial Number: Date of Last System Maintenance: 15)Confirm All Wall penetrations are sealed: CUSTOMER AND SITE INFORAMTION Wholesaler / Distributor Name: Date: Site Address: Address Line 2: City: State: Indoor Unit Model Number: Indoor Unit Serial Number: Indoor Unit Model Number: Indoor Unit Serial Number: Indoor Unit Model Number: Indoor Unit Serial Number: Indoor Unit Model Number: Indoor Unit Serial Number: For Multi F and Multi F Max Please Provide the following (Up to 8 Indoor Units and 2 Branch Distribution Boxes): Indoor Unit Model Number: Indoor Unit Serial Number: Indoor Unit Model Number: Indoor Unit Serial Number: Indoor Unit Model Number: YES YES YES YES YES YES YES YES YES YES NO NO NO NO NO NO NO NO NO NO YES YES YES YES NO NO NO NO YES NO LG AFTERMARKET SITE FORM
4

RLC AFTERMARKET SITE EVALUATION FORM - Target Sales

Apr 29, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: RLC AFTERMARKET SITE EVALUATION FORM - Target Sales

RLC AFTERMARKET SITE EVALUATION FORM

Page 1

Indoor Unit 1:Indoor Unit 2:Indoor Unit 3:Indoor Unit 4:Indoor Unit 5:Indoor Unit 6:Indoor Unit 7:Indoor Unit 8:

1)Is this a New installation:2)Is there a Condensate Pump installed:3)Is there a PI-485 Installed:4)Are any IDU's Group Controlled:5)Is there any Remote Temp Sensors Installed:6)Is there a Dry Contactor Installed:7)Does this unit have a Surge Protector Installed:8)Are there any wall stats in system:9)Are there any 3rd party wall stats in system:10)Have any trouble shooting steps been taken:ERROR CODE:Additional Information:

11)Interconnecting wire shielded:12)Interconnecting wiring Grounded:13)Confirm no wire splices:14)Confirm no Vertical Loops in piping:

Indoor Unit Serial Number:

MODEL INFORMATIONOutdoor Unit Model Number:

Initial System Installation Questions:

* If yes to any please provide any additional information below.

Zip Code:

Installing or Service Contractor Name:

City: State: Zip Code:

Date of Original Installation: Repair Dates (If Any):

Branch Distribution Box 2: Model Number: Serial Number:

Indoor Unit Model Number: Indoor Unit Serial Number:

Branch Distribution Box 1: Model Number: Serial Number:

Outdoor Serial Number:

Date of Last System Maintenance:

15)Confirm All Wall penetrations are sealed:

CUSTOMER AND SITE INFORAMTION

Wholesaler / Distributor Name: Date:

Site Address: Address Line 2:

City: State:

Indoor Unit Model Number: Indoor Unit Serial Number:

Indoor Unit Model Number: Indoor Unit Serial Number:

Indoor Unit Model Number: Indoor Unit Serial Number:

Indoor Unit Model Number: Indoor Unit Serial Number:

For Multi F and Multi F Max Please Provide the following (Up to 8 Indoor Units and 2 Branch Distribution Boxes):Indoor Unit Model Number: Indoor Unit Serial Number:

Indoor Unit Model Number: Indoor Unit Serial Number:

Indoor Unit Model Number:

YESYESYESYESYESYESYESYESYESYES

NONONO

NONONONONO

NO

NO

YESYESYES

YES

NONONONO

YES NO

LG AFTERMARKET SITE FORM

Page 2: RLC AFTERMARKET SITE EVALUATION FORM - Target Sales

RLC AFTERMARKET SITE EVALUATION FORM

Page 2

Insulation Thickness (in.) Gas Line: Liquid Line:

Piping Length (Ft) ODU to Branch (1)/(2):

IDU: Dip Switch Settings

Feet: Vertical Rise from ODU to IDU

Feet: Vertical Rise From IDU to IDU

ESP LO ESP Mid ESP HI ESP VL ESP PO

IDU M1 M2 M3 M4 M5IDU1 M1 Distance from front of unit to closest obstructionIDU2 M2 Distance from bottom of unit to closest obstructionIDU3 M3 Distance from left of unit to closest obstructionIDU4 M4 Distance from right of unit to closest obstructionIDU5 M5 Distance from top of unit to closest obstructionIDU6IDU7IDU8

M1 M3 M4 M5

Indoor Unit 1:

Indoor Unit 2:

Indoor Unit 3:

Indoor Unit 7:

Model Number Static Pressure

Indoor Unit 1:

Indoor Unit 2:

Indoor Unit 3:

Air Flow Clearance Information

Model Number

Clearance Information

*PICTURES WILL BE REQUIRED TO VERIFY DISTANCES

Indoor Unit 4:

Indoor Unit 5:

Indoor Unit 6:

Indoor Unit 7:

Indoor Unit 8:

ESP settings should be set in LG wall stat: Installer setting 03: (options should be

000-255)

Ducted Units Only

*∆ T Readings need to be taken after 15 minutes of systemoperation with fan speed on High

Total Piping (ft.) for Multi F or Multi F Max:Total Refrigerant Charge (oz.):

Indoor Unit 8:

∆ T Cooling – Set Temperature at 64° F

∆ T Heating – Set Temperature at 86° F

Piping Information

*Multi F piping Measurement is from Outdoor Unit to each IDU.\\\\\\\\\\*Multi F Max units have up to 8 IDU's and measurements are from Branch Box

to indoor units.

Indoor Unit 4:

Indoor Unit 5:

Indoor Unit 6:

Branch to IDU(1/2/3/4):

Branch(2) to IDU(1/2/3/4):

Out Door Unit Clearance Information

LG AFTERMARKET SITE FORM

Page 3: RLC AFTERMARKET SITE EVALUATION FORM - Target Sales

RLC AFTERMARKET SITE EVALUATION FORM

Page 3

Disconnect Power ODU Power Branch Box 1 Power Branch Box 2 PowerVoltage A/C Voltage A/C AC/DC AC/DCL1-L2= L1-L2= L1-L2=(AC) L1-L2=(AC)L1-Ground= L1-Ground= L1-S=(AC) L1-S=(AC)L2-Ground= L2-Ground= L2-S=(DCV) L2-S=(DCV)ODU / Branch box check to IDU IDU (A) IDU (B) IDU © IDU (D) IDU (A) IDU (B) IDU © IDU (D)

ODU\ Zone Com Check Branch Box 1 Com check

IDU 1 IDU 2 IDU 3 IDU 4 IDU 5 IDU 6 IDU 7 IDU 8

Air Pipe Suc DIS Hex Out Hex Mid

3A-G= 3C-G= 3A-G= 3C-G=3B-G= 3D-G= 3B-G= 3D-G=

1-4= 4-6= 1-4= 4-6=4-5= 4-7= 4-5= 4-7=

5 Wire EEV1 EEV2 EEV3 EEV4 EEV5 EEV6 EEV7 EEV81-3=1-4=1-5=1-6=6 Wire EEV1 EEV2 EEV3 EEV4 EEV5 EEV6 EEV7 EEV81-3=1-5=2-4=2-6=

Electrical Information

L1-L2=(AC)L1-L3=(AC)

L2-L3=(DCv)

Pipe MidPipe Out

IDU

Out Door Unit

All checks in this section should be provided by LGMV or SIMS diagnostic tool. If using LGMV please record as much data as possible and send in with this

form.

C L2-3C terminal block=(D) L2-3D terminal block=

*Remove com wires off of ODU. These wires will be hot on power up, wire cap to make sure they do not short out. Once youhave checked the ODU you will need to hook up all of the com wires back up. If you are checking a Multi F Max please check

ODU for Com A and B then hook up the com wires back and check Branch Box 1 and 2.

(A) L2-3S terminal block=(B) L2-3S terminal block=C L2-3S terminal block=

(D) L2-3S terminal block=

(A) L2-3S terminal block=(B) L2-3S terminal block=C L2-3S terminal block=

(D) L2-3S terminal block=

*DCv will fluxuateprovide high and low

values.

Power On Checks Power On Checks Power On Checks Power On Checks

(A) L2-3A terminal block=(B) L2-3B terminal block=

EEV 5&6 Wire

Power OFF Checks

L1-Ground=L2-Ground=

Multi F Max Branch Box (2)Multi F / Multi F Max Branch Box (1)ODU Ground Check

Motor Checks (BLDC) ODU Multi F Max Additional Motor ODU

Make sure that your Black lead is on the #4 pin. If your Black lead isn't on #4 pin testing

values could be wrong.

Thermistor ChecksNote: Temperature to be measured after 15 minutes of system operation, with fan speed High

EEV PositionAir

Pipe IN

*DCv will fluxuateprovide high and low

values.

Branch Box 2 Com check

LG AFTERMARKET SITE FORM

Page 4: RLC AFTERMARKET SITE EVALUATION FORM - Target Sales

RLC AFTERMARKET SITE EVALUATION FORM

Page 4

*Resources*

Indoor unit model and serial number tags

Technical Service Support HistoryCase Number(s) Provided by LG Technical Service (contractor must request): Date of Call:

INSTALLATION PHOTOSInstallation photos are required, please attach digital photos of the following (additional photos may be required) :

• This information form is for the sole purpose of collecting data prior to calling Technical Support in order to facilitate a shorter call.• Additional Resources can be found: LGHVAC.com, LGMV obi app, Youtube.com, MyLGHVAC.com/ training videos.• If LGMV Data is required please contact your local TSA, Distributor and/or Rep.• If you are looking for trouble shooting material please go to LGHVAC.com• If training is required please install LGMV Mobil app on your phone and look up the manual accordingly. For further training please contact yourDistributor and/or Rep for additional training.• For informational videos showing how to test the product and assist you with filling out some of this form please go to youtube.com search“RAC Troubleshooting”

Outdoor unit placement Outdoor unit model and serial number tags Outdoor unit wiring and piping connectionsIndoor unit placement

LG AFTERMARKET SITE FORM