What is the RICE MACT?

• The National Emission Standards for Hazardous Air Pollutants (NESHAP)

for Reciprocating Internal Combustion Engines (RICE). Often called the

RICE MACT or GACT

- MACT - Maximum Achievable Control Technology for Major Sources

of Hazardous Air Pollutants (HAPs)

- GACT - Generally Achievable Control Technology for Area Sources

of HAPs

• The purpose of RICE MACT is to reduce the emissions of Hazardous Air

Pollutants (HAPs) from reciprocating internal combustion engines.

• Major industrial sources that emit 10 tons a year or more of a single

Hazardous Air Pollutant or 25 tons a year or more of a combination of

Hazardous Air Pollutants.

Page 3: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

3

Asset Categories

Page 4: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

4

HAPs Emitted from Engines

Page 5: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

5

Why RICE MACT?

The purpose of RICE MACT is to reduce the emissions of Hazardous Air Pollutants (HAPs) from reciprocating internal combustion engines (RICE) located at major industrial sources of air HAPs or area sources.

Page 6: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

6

Who Does It Affect - Stationary RICE Source Categories

• Emergency stationary RICE• Limited use stationary RICE• Stationary RICE that combust landfill

gas or digester gas equivalent to 10 percent or more of the gross heat input on an annual basis

• Compression Ignition (CI) (Diesel)• Spark ignition 4-stroke rich burn (4SRB)• Spark ignition 2-stroke lean burn (2SLB)• Spark ignition 4-stroke lean burn (4SLB)

Page 7: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

7

How Do I Know If RICE MACT Is For Me?

Page 8: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

8

10+ Tons HAPS on Single Unit, 25+ Tons Combo

Page 9: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

9

RICE MACT Emission Requirements

• Existing and new 4-stroke rich burn (4SRB) engines either reduce formaldehyde by 76% or limit the formaldehyde concentration to 350 ppb.

• New 2-stroke lean burn (2SLB) engines either reduce carbon monoxide (CO) by 58% or limit the formaldehyde concentration to 12 ppm.

• New 4-stroke lean burn (4SLB) engines either reduce CO by 93% or limit the formaldehyde concentration to 14ppm.

• New compression ignition (CI) engines either reduce CO by 70% or limit the formaldehyde concentration to 580 ppb.

Page 10: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

10

Types of RICE MACT Requirements

• Notifications• Emission Limitations• Controls• Operating Limitations• Fuel Requirements• Performance Tests• Monitoring• Recordkeeping• Reporting

Page 11: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

11

Management Practice

• Hoses and Belts must be inspected on all of these engines after 500 hours, or annually, and replaced “as necessary.”

• Air cleaners must be inspected at 1000 hours, or at least annually.

• Oil and Filters must be replaced at 500 hours, or annually, except for non-emergency engines smaller than 100 HP at major sources or smaller than 300 HP at area sources where this inspection can be deferred until 1000 hours.

• For engines with a compliant oil analysis program, these limits may be extended.

Page 12: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

12

Exempt from RICE MACT

If and only if the engine operates as an emergency engine under the rule and is located at residential, institutional, or commercial establishments that are area sources for HAPs

• Residential could be an apartment complex or a house

• Institutional establishments means places such as general medical centers and hospitals, nursing homes, research centers of higher education, correctional facilities, schools, libraries, police and fire stations, physicians and health specialist offices

• Commercial could be office buildings or telecommunication tower sites

Page 13: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

13

What qualifies a limited use stationary RICE?

Limited use and emergency stationary RICE = Less than 100 hours per year.

An Emergency Stationary RICE has…• No limit on use during emergency situations.• Maintenance checks and readiness testing are

limited to 100 hours/year• Up to 50 hours/year of non-emergency operation is

allowable (counts toward the 100 hours/year)

The 50 hours/year cannot be used for peak shaving or to generate income except for up to 15 hours/year for demand response when a regional transmission operator is in danger of a blackout

Page 14: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

14

Stationary RICE that combust landfill gas or digester

Gas Equivalent to 10% or more of the gross heat input…

• Landfill Gas: the gaseous by-product of the land application of municipal refuse typically formed through the anaerobic decomposition of waste materials and is composed primarily of methane and CO2.

• Digester Gas: the gaseous by-product of wastewater treatment typically formed through the anaerobic decomposition of organic waste materials and is composed primarily of methane and CO2.

For each Stationary RICE that combust landfill gas or digester gas equivalent to 10 percent or more of the gross heat input on an annual basis installed after the compliance date is subject to Subpart ZZZZ (4Z), you must submit an initial notification and monitor, record and report annual fuel usage.

Page 15: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

15

Oil Analysis and RICE MACT

Page 16: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

16

Compliance Demonstration – Major Source

Page 17: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

17

Compliance Demonstration - >500hp Major Sources

Page 18: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

18

Compliance Demonstration - ≤ 500hp Area Sources

Page 19: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

19

Compliance Demonstration - > 500hp Area Sources

Page 20: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

20

Record Keeping & Recording

• Recordkeeping is required.

• Records must include hours of operation per a non-resettable hour meter, oil and filter change dates, inspection and replacement of air cleaners, hoses and belts, and other emission related service, all by date and.

• Records of maintenance per manufacturer’s requirements are also required for crankcase systems (closed ventilation or open filtration) for covered engines.

Page 21: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

21

Record Keeping & Reporting

• Reporting is required for stationary CI RICE on a semi-annual basis (or annual basis for limited-use) , as listed in the NESHAP General Provisions, 40 CFR part 63, subpart A, including initial notification, notification of performance test, and notification of compliance.

• Deviations and malfunctions must also be reported.

• Annual fuel consumption and heating value reports are also required.

Page 22: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

22

Record Keeping & Reporting – Major Sources

Page 23: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

23

Record Keeping & Reporting – Area Sources

Page 24: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

24

Record Keeping & Reporting – Area Sources

Page 25: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

25

Best Management Practices Requirements

• Change oil filter annually or every 1,000 hours of operation

• Inspect the air cleaner (filter) annually or every 1,000 hours of operation

• Inspect all hoses and belts annually or every 500 hours of operation

• Records need to be kept for five years

• Duration of startup and shutdown time to less than 30 minutes per event

Page 26: RIGHT SOLUTIONS | RIGHT PARTNER RICE MACT and Oil Analysis Michael Holloway, CLS.

26

Oil Analysis and RICE MACT

• Change Oil or shut down unit within 2 business days (not 48 hours) upon receipt of a RICE MACT ALERT Severe report.

• RICE MACT Notice will always be SEVERE but you can have a SEVERE and not be a RICE MACT.

• Viscosity Testing to be done at 100C.• PQ Particle testing to be done (not a RICE

MACT) replaces the 40C viscosity testing.

What to Expect From the Lab…