© ABB Oy Distribution Automation May 13, 2010 | 1MRS756901 A | Slide 1 Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation Relion ® 615 series
© ABB Oy Distribution AutomationMay 13, 2010 | 1MRS756901 A | Slide 1
Transformer Protection and Control RET615 Ver. 2.0Technical Presentation
Relion® 615 series
© ABB Oy May 13, 2010 | Slide 2
ContentRET615 Technical Presentation
Introduction
Application examples
Hardware and options
Functionality highlights
Communication
Mechanical design
Front panel HMI
Tools
Conclusions
© ABB Oy May 13, 2010 | Slide 3
Introduction
Relion® 615 seriesRET615
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615 is a member of ABB’s Relion®
product family and part of its 615 protection and control product series
The 615 series IEDs are characterized by their compactness and withdrawable design
Other members of the 615 product series:
REF615
REM615
RED615
© ABB Oy May 13, 2010 | Slide 4
RET615Description
© ABB Oy May 13, 2010 | Slide 5
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615 is a dedicated transformer protection and control IED (intelligent electronic device) for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems
© ABB Oy May 13, 2010 | Slide 6
RET615Transformer Protection and Control
Designed for unit protection applications calling for stabilized differential protection
Main application area: two winding transformers in power distribution networks
Designed for IEC 61850
RET615 also supports:
Modbus®
DNP3
IEC 60870-5-103
Optional three-channel arc protection system
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 7
RET615 Standard configurations
Four standard configurations to match the most commonly applied transformer neutral earthing principles with the relevant earth-fault protection schemes
Possibility to add, delete and change signal connections for binary inputs, binary outputs and between function blocks using PCM600
The number and type of function blocks is fixed
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 8
RET615 Standard configurations
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Standard configuration AThree-phase transformer differential protection for two-winding transformers, with numerical restricted earth-fault protection for the high-voltage (HV) side
Standard configuration BThree-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side
Standard configuration CThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the high-voltage (HV) side
Standard configuration DThree-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the low-voltage (LV) side
© ABB Oy May 13, 2010 | Slide 9
= included, = optional at the time of order
RET615 Standard configurations, page 1(3)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
●●●●Negative-sequence overcurrent protection, instance 1
●●●●Circuit breaker failure protection
●●●●Three-phase non-directional overcurrent protection, high stage, instance 1
●●●●Three-phase non-directional overcurrent protection, instantaneous stage, instance 1
-●-●Non-directional earth-fault protection, low stage, instance 1
-●-●Non-directional earth-fault protection, high stage, instance 1
●●●●Three-phase thermal overload protection for power transformers, two time constants
●●●●Stabilized and instantaneous differential protection for two-winding transformers
--●●Numerical stabilized low impedance restricted earth-fault protection
●●--High impedance based restricted earth-fault protection
●●●●Master Trip, instance 1
●●●●Master Trip, instance 2
HV-side protection
Standard configuration A B C DProtection
Three-phase non-directional overcurrent protection, low stage, instance 1 ● ● ● ●
●●●●Disconnector position indication, instance 2
●●●●Disconnector position indication, instance 3
●●●●Disconnector position indication, instance 1
●●●●Negative-sequence overcurrent protection, instance 2
●●●●Three-phase non-directional overcurrent protection, low stage, instance 2
●●●●Three-phase non-directional overcurrent protection, high stage, instance 2
●●●●Three-phase non-directional overcurrent protection, instantaneous stage, instance 2
●-●-Non-directional earth-fault protection, low stage, instance 2
●-●-Non-directional earth-fault protection, high stage, instance 2
LV-side protection
Standard configuration A B C D
Arc protection, instance 1 o o o o
Arc protection, instance 2 o o o o
Arc protection, instance 3 o o o o
ControlCircuit-breaker control ● ● ● ●
© ABB Oy May 13, 2010 | Slide 10
RET615 Standard configurations, page 2(3)
= included, = optional at the time of order
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 11
RET615 Standard configurations, page 3(3)
= included, = optional at the time of order
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
●●●●Earthing switch indication
●●●●Tap changer position indication
ControlStandard configuration A B C D
Condition monitoringCircuit-breaker condition monitoring ● ● ● ●
Trip circuit supervision, instance 1 ● ● ● ●
Trip circuit supervision, instance 2 ● ● ● ●
MeasurementDisturbance recorder ● ● ● ●
Three-phase current measurement, instance 1 (HV side) ● ● ● ●
Three-phase current measurement, instance 2 (LV side) ● ● ● ●
Sequence current measurement (HV side) ● ● ● ●
Residual current measurement, instance 1 (HV side) ● - ● -
Residual current measurement, instance 2 (HV side) - ● - ●
© ABB Oy May 13, 2010 | Slide 12
Application examples
© ABB Oy May 13, 2010 | Slide 13
Three-phase transformer differential protection for two-winding transformers, with numerical restricted earth-fault protection for the high-voltage (HV) side
The low impedance REF protection(employed on the HV side) complements the stabilized differential protection
The low impedance principle allows the transforming ratio of the neutral earthing CT to differ from those of the phase CTs
Three-phase thermal overload protectionprevents accelerated aging of the windinginsulation
RET615Standard configuration A
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 14
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side
The low impedance REF protection(employed on the LV side) complements the stabilized differential protection
The low impedance principle allows the transforming ratio of the neutral earthing CT to differ from those of the phase CTs
Three-phase thermal overload protectionprevents accelerated aging of the windinginsulation
RET615 Standard configuration B
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 15
Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the high-voltage (HV) side
High impedance REF (employed on the HV side) complements the stabilized differential protection
The high impedance principle enablessensitive and absolutely selective E/F protection
Three-phase thermal overload protectionprevents accelerated aging of the windinginsulation
RET615Standard configuration C
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 16
Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-fault protection for the low-voltage (LV) side
High impedance REF (employed on the LV side) complements the stabilized differential protection
The high impedance principle enablessensitive and absolutely selective E/F protection
Three-phase thermal overload protectionprevents accelerated aging of the windinginsulation
RET615Standard configuration D
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
615 series Supported ABB solutions, page 1(2)
The 615 series IEDs together with COM600 constitute a genuine IEC 61850 solution for reliable power distribution in utility and industrial power systems
The native IEC 61850 support offer:
Fast software based communication
Continuous supervision of the integrity of the protection and communication system
Inherent flexibility for reconfiguration and upgrades
ABB’s Connectivity Package concept enables:
Streamlining of the system engineering and IED configuration
Easy integration with COM600 and MicroSCADA Pro
© ABB Oy May 13, 2010 | Slide 17
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
Supported ABB solutions Version
Station Automation COM600 3.3 or later
MicroSCADA Pro 9.2 SP1 or later
© ABB Oy May 13, 2010 | Slide 18
615 seriesSupported ABB solutions, page 2(2)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
The 615 series IEDs complemented with COM600 offer several benefits:
Enhanced substation level functionality using the data content of the bay level IEDs
A web HMI providing single-line mimic diagrams for switchgear bay solutions
COM600 can be used as a local data warehouse for technical documentation and for network data
Extensive reporting and analyzing of network fault situations
Seamless connectivity to MicroSCADAPro and System 800xA
Industrial example
Utility example
© ABB Oy May 13, 2010 | Slide 19
Hardware and options
© ABB Oy May 13, 2010 | Slide 20
RET615 Hardware modules
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
[X000] Communication module (option)with or without arc- protection
[X100] Power supply and binary output module
[X110] Binary I/O module
[X120] Basic analog input module
[X130] Optional binary I/O module
© ABB Oy May 13, 2010 | Slide 21
Examples: Ethernet/Serial modules (RJ-45 and LC) with optional arc sensors
RET615Option: Communication modules [X000]
Ethernet options:
100BASE-TX with an RJ-45 connector
100BASE-FX with a fibre-optic LC connector
Serial options:
RS-485 + IRIG-B 9 or 10-pin screw terminal connector
2-wire or 4-wire connection
RS-485 / RS-232 + IRIG-B
Fibre (ST connector)
Three arc sensors (option)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 22
RET615Power supply and binary output modules [X100]
Power supply options:
48 V…250 V DC, 100 V…240 V AC,
24…60 V DC
Four power output contacts capable of direct CB operation
Two contacts with integrated trip circuit supervision; also to be used with double-pole operation
The TCS can be disconnected by excluding the resistor from the trip circuit
Two signal output contacts (1 normally open contact, 1 changeover contact)
IRF output for self-supervision signalling
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 23
RET615Binary I/O module [X110]
8 binary inputs
6 inputs, grouped in pairs of two
2 inputs, separated (potential free)
4 binary outputs
3 outputs, changeover contacts
1 output, normally open
Selectable binary input thresholds(17 – 186 V DC)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 24
RET615Basic analog input modules [X120]
Seven analog current inputs I0_A ,IL1_A, IL2_A, and IL3_A, IL1_B, IL2_B, and IL3_B
rated currents user selectable 1 A or 5 A
If required 1 A can be used on the HV side and 5 A on the LV side, or vice versa
Both for ring and pin type wire terminals
Max. wire 1 x 6 mm2 or 2 x 2.5 mm2
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 25
RET615Option: Additional binary I/O module [X130]
Binary I/O module
6 binary inputs, grouped in pairs of two (common ground)
3 binary outputs, changeover contacts
Selectable binary input thresholds(17 – 186 V DC)
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 26
RET615Communication modules
Modules
Protocols
With arc protection Without arc protectionEthernet (RJ-45 or LC)+ 3 arc
sensors
Serial (RS-485) + IRIG-B
+3 arc sensors
Ethernet (RJ-45 or LC)
Serial (RS-485 /RS-232) + IRIG-B
Serial(fibreST)
+ IRIG-B
IEC 61850-8-1 - - -
IEC 60870-5-103 - -
DNP3 TCP/IP - - -
DNP3 serial - -
MODBUS TCP/IP - - -
MODBUS RTU/ASCII
- -
= supported, - = not supported
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 27
Standard configuration Analog inputs Binary inputs/outputsCT VT BI BO
Standard configuration A 7 - 8 (14) 1) 10 (13) 1)
Standard configuration B 7 - 8 (14) 1) 10 (13) 1)
Standard configuration C 7 - 8 (14) 1) 10 (13) 1)
Standard configuration D 7 - 8 (14) 1) 10 (13) 1)
1) With optional binary I/O module ( )
RET615Input/output overview
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 28
Functionality highlights
© ABB Group May 13, 2010 | Slide 29
RET615Transformer differential protection
Three-phase stabilized differential protection for two-winding power transformers
Provides two stages for winding short-circuit and interturn protection: Instantaneous, unrestrained stage provides a
very fast clearance of severe faults with high differential current regardless of harmonics
Stabilized stage provides a fast clearance of faults while remaining stabile with high currents passing through the protected zone causing CT saturation
Easily adjustable operating characteristic of the stabilized stage for different applications
Possibility to automatically adapt to the position changes of the tap changer enables more sensitive settings of the characteristic
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
1
b
1 2 3 4 5
2
3
Id2
Ib2
I
Id1
n
Ib3
Id3
I
In
I
Id
n
Maximum settingsDefault settings
Minimum settings
OPERATION
NO OPERATIONTurn-point 1
Turn-point 2
© ABB Group May 13, 2010 | Slide 30
RET615Transformer differential protection
Short operate times at faults occurring in the zone to be protected (internal faults), even with partially saturated current transformers
High stability at external faults, also with partially saturated current transformers Second harmonic features 2nd harmonic and advanced waveform-based restraints
Fifth harmonic restraint ensures that the protection does not operate on apparent differential current caused by transformer over-excitation
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Group May 13, 2010 | Slide 31
RET615Stabilized restricted earth-fault protection
Stabilized restricted earth-fault protection using a calculated difference between residual current from line CTs and star-point neutral current
No external stabilizing resistor nor varistorneeded
Definite time operation
Unit protection for transformer windings
Neutral current second harmonic is used for blocking during the transformer inrush situation
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Group May 13, 2010 | Slide 32
RET615High impedance restricted earth fault protection
Complements the stabilized differential function against earth-faults
Provides protection for all earth faults that fall in the area between the phase and neutral CTs, even single phase earth faults close to star-point
Necessitates use of external stabilizing resistors and varistors
REFIo> 87N
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Group May 13, 2010 | Slide 33
RET615Thermal overload protection
Thermal overload protection to prevent accelerated aging of the insulation
Thermal model with two settable time constants
Early warning to allow operators to take action before transformer tripping
If the temperature rise continues the function will operate based on the thermal model of the transformer
Re-energizing inhibition during the cooling time of the transformer
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 34
RET615Arc protection (option)
Increases safety during maintenance work
Reduces material damage
Minimizes system downtime
Continuously supervises the CB, cable and busbar compartment of metal-enclosed switchgear
Same lens and optic fibre as for REA 107
Automatic reference level adjustment based on background-light intensity
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 35
RET615Arc protection (option), cont’d
Arc trip based on: Current and light
Current and binary input signal
Light only
Separate trip value settings for phase currents and earth-fault current
Operate time typically
12 ms (current and light)
10 ms (light only)
Possible to block the function or change operation mode via a binary input
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 36
RET615Control functions
Control of the HV side circuit-breaker via the IED’s HMI or a remote control system
Dedicated push-buttons for opening and closing of the CB
Interlocking schemes
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 37
RET615 Operation traceability
For pre and post fault analysis
Data is stored in non-volatile memory
Setting values
Configuration
Trip lock-out
Disturbance recorder data
Up to 50 event codes
Recorded data of the four latest starts/trips of the protection stages (incl. time stamp)
CB conditioning monitoring values
Thermal loading level
Operation indications and alarm LEDs show the status of the IED
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 38
RET615 Disturbance recorder
Records up to 12 analog channels and 64 binary channels
Triggering by:
Analog or binary channel
Manual or periodic command
Recording modes:
Wave form or trend
Selectable sampling rate, 32/16/8 samples per cycle
Max 2 X 10 sec with the highest sampling rate and the maximum number of recorded channels.
Max 4 X 10 sec if six analog channels are recorded
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 39
RET615 Self-supervision
Continuous monitoring of:
Memory circuits (RAM, ROM, EEPROM)
CPU operation and program execution
Internal supply voltages
Output relay supervision
External trip circuit (TCS)
Light sensor inputs
Hardware and software configuration
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615 Transformer condition monitoring
Monitoring via binary inputs
Oil level low
Buchholz relay
Winding temperature indicator
Tank pressure relief
Tap-changer position as BCD-signal
© ABB Oy May 13, 2010 | Slide 40
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615 CB condition monitoring
Provides information for scheduling CB maintenance
Monitors the wear and tear of the circuit-breaker
Circuit-breaker gas pressure
Circuit-breaker spring charging
Circuit-breaker travel time
Circuit-breaker operation counter
Scheduled maintenance
© ABB Oy May 13, 2010 | Slide 41
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 42
RET615Access control
Individual user accounts with role-based access control protects the IED from unauthorized access
Four access levels: viewer, operator, engineer and administrator
Applies to:
Front-panel user interface
Web browser based user interface
PCM600
Passwords programmable by the administrator
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 43
Communication
© ABB Oy May 13, 2010 | Slide 44
615 series Designed for IEC 61850
Native support for IEC 61850 communication between devices in substations
IEC 61850 enables “GOOSE” (GenericObject Oriented Substation Event) horizontal communication between IEDs
RET615 can simultaneously report events to five different clients on the station bus
RET615 also supports: Modbus TCP/IP and RTU / ASCII DNP3 TCP/IP and serial IEC 60870-5-103
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 45
615 series IEC 61850 GOOSE communication
Standardized horizontal communication enables interoperability between any IEDs supporting GOOSE communication
Used for transmitting binary process data to peer IEDs within a substation
Ethernet technology offers a fast and reliable station bus for the transfer of data
The publisher-subscriber principle allows the IEDs to send and/or receive time critical data
Station AutomationCOM600
Station bus IEC 61850
Network control centreMicroSCADA Pro
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 46
615 series GOOSE communication benefits
Expandability and flexibility: Flexible modifications without changing the
wiring between the IEDs
No IED I/Os are needed for the transer of data between the IEDs
Reduced wiring between the IEDs
Possible to add functionality like interlocking schemes between the cubicles in existing switchgear (retrofit)
Supervised data transfer (connection and data quality)
RET615 meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 47
RET615 Time synchronization methods
Ethernet-based time synchronization:
SNTP (Simple Network Time Protocol)
With special time synchronization wiring:
IRIG-B (Inter-Range Instrumentation Group - Time Code Format B
Time stamp resolution: 1 ms
Serial protocol based:
Modbus
DNP3
IEC60870-5-103
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 48
RET615 Front port communication
RJ-45 Ethernet connector
IED configuration using PCM600
IED access using the web-browser-based HMI
LED indication on the local HMI during data transfer
Both crossover and regular cables can be used
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 49
Mechanical design
© ABB Oy May 13, 2010 | Slide 50
615 series Patented and compact plug-in design
Speeds up installation, maintenance and testing of the protection
Contributes to a shortened MTTR (mean time to repair)
Allows the cases to be installed and wired before the plug-in units are delivered
Mechanical coding system for preventing insertion of a wrong plug-in unit in a case
Sealable pull-out handle to prevent accidental (or unauthorized) withdrawal of the plug-in unit
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 51
615 series IED case and plug-in unit
Height: frame 177 mm, case 164 mm
Width: frame 177 mm (4U), case 160 mm
Depth: case 155 mm
IP classification
IP54 When panel-mounted
IP20 Rear side
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 52
615 seriesFlush and semi flush mounting
Flush mounting The same cut-out on the cubicle front as for the 610 series
IEDs (height: 161.5 ±1, width: 165.5 ±1) Semi-flush mounting
With a 50 mm rising frame
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 53
615 seriesSemi flush and wall mounting
Semi-flush mounting in a 25° angle With special accessories
Wall mounting The IED can be tilted for easy access to the connectors
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 54
615 seriesPanel and rack mounting
Mounting using a 19” mounting panel One or two IEDs
Mounting with an RTXP test switch in a 19” rack For routine testing purposes
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 55
Front panel HMI
© ABB Oy May 13, 2010 | Slide 56
615 series Front panel HMI
4 x 16 characterdisplay (LCD)
Front communication port
Three dedicated LEDs: Ready, Start,Trip
11 programmable LEDs
CB Control, OPEN and CLOSE buttons
ESC button
Navigation buttons
ENTER buttonCLEAR button
MENU button
LOCAL/REMOTE button, HELP
AUTHORIZATION
© ABB Oy May 13, 2010 | Slide 57
615 seriesDisplay options
Large LCD, mono-spaced 10 x 20 characters, variable width 8 x 8 (or more) characters
Small LCD, mono-spaced 4 x 20 characters, variable width 4 x 8 (or more) characters
Background light with power-saving mode
Option:Small LCD
Large LCD
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 58
RET615Display readouts
IEC 61850 naming, “classic”IEC symbols or ANSI codes: (PHLPTOC1, 3I>, 51P-1)
Fault indications
Four fault recordings with time stamp
Measurements
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 59
RET615 Display readouts, cont’d
Name or code of protected objects
Settings in 4 setting groups
Configurations such as protocol settings etc.
Product information, serial number, software version, identification etc.
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 60
Tools
© ABB Oy May 13, 2010 | Slide 61
RET615Tools
Tools VersionPCM600 2.0 SP2 or later
Web-browser-based user interface IE 7.0 or later
RET615 connectivity package 2.5 or later
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 62
PCM600Protection and control IED Manager
A common tool for new and existing protection IEDs and terminals
IED-specific connectivity packages enable the use PCM600 for different ABB protection IEDs and terminals
Supports IEC 61850
GOOSE messaging configuration (PCM600 Engineering Pro)
IED interaction using:
Corporate LAN/WAN
The IED’s communication port
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 63
PCM600 Tools
All tools needed to manage RET615 are included in PCM600:
Signal matrix
Signal monitoring
IED parameter setting
Disturbance recorder handling and viewing
IEC 61850 (GOOSE) communication configuration
Modbus communication configuration
DNP3 communication configuration
IEC 60870-5-103 communication configuration
Access control management
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 64
PCM600 Power system overview
PCM600 offers the possibility to create a tree-structure representing your individual power system, including:
Project name
Substations
Voltage levels
Bays
IEDs/terminals
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 65
615 series Web-browser based user interface
Local or remote IED access using an IE 7.0 (or later) web browser
Disabled by default, enabled by PCM600 or the local front-panel interface
Functions:
Viewing of alarm LEDs and event lists
Saving of event data
Parameter setting
Signal monitoring
Measurement viewing
Phasor diagram viewing (both HV and LV phasors)
Reading of disturbance records
User access level authentication
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615Differential characteristics tool
Included in the connectivity package
Visual presentation of the differential protection characteristics
Possibility to read fault records from the IED and present them on the characteristic
Writing of parameters to the IED using the local HMI, the web-browser based HMI or PCM600
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 67
Conclusions
© ABB Oy May 13, 2010 | Slide 68
RET615Product summary
IEC 61850 communication including GOOSE messaging
Stabilized and instantaneous differential protection for two-winding power transformers
Versatile, user selectable earth-fault protection modes
Non-directional overcurrent back-up protection
Thermal overload protection
Optional arc protection with three sensors
CB control buttons on the HMI
Rapid set-up and commissioning, four standard configurations
Patented plug-in / draw-out design
Optimized size - suitable for retrofit purposes
Versatile tools
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 69
RET615Selection and ordering data, digit 1-3
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 70
RET615Selection and ordering data, digit 4-8
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 71
RET615 Selection and ordering data, digit 9-11
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 72
RET615 Selection and ordering data, digit 9-11
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 73
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
RET615Selection and ordering data, digit 12-18
© ABB Oy May 13, 2010 | Slide 74
RET615 Selection and ordering data, ordering code
IntroductionApplication examplesHardware and optionsFunctionalityCommunicationMechanical designFront panel HMIToolsConclusions
© ABB Oy May 13, 2010 | Slide 75
Please visit our website for the latest product informationwww.abb.com/substationautomation
© ABB Oy May 13, 2010 | Slide 76