CITY OF FARMINGTON 800 Municipal Drive Farmington, NM 87401-2663 (505) 599-1373 Fax (505) 599-1377 http://www.fmtn.org AD1-1 Request For Qualifications-Based Proposals for Construction Contract Farmington Civic Center Renovations & Expansion PROJECT NO. CCEXP, RFP NO. 18-122315 IMMEDIATE ATTENTION ADDENDUM ONE August 25, 2017 Receipt of this addendum shall be noted on Page 3 in the Request for Qualifications-based Proposal documents for the above referenced RFQP. The addendum is hereby made part of the Contract Documents to the same extent as though it were originally included therein. Refer to "Submittal Form" for acknowledgment of addenda. All Contractors, Subcontractors and suppliers are reminded that they shall be familiar with all addenda items (as well as all parts of the construction documents) so as to understand the extent of their work and its interrelation with other trades. To all bidders for furnishing all labor and materials necessary for the following contract: CIVIL ITEMS CIVIL SHEETS ITEM AD1-C1 Clarification: in all sheets where metal handrails or guardrails are referenced, handrails or guardrails must be primed and painted. The paint color shall be coordinated between the City of Farmington and the Architect. LANDSCAPING ITEMS PROJECT MANUAL ITEM AD1-L1 Section 01 56 39 – Temporary Tree Protection Delete section 01 56 39 – Temporary Tree Protection in its entirety from the project manual. Contractor shall refer to TREE PROTECTION NOTES on SHEET ADS101 for this scope of work. DRAWING SHEETS ITEM AD1-L2 Sheet LS102 – CONSTRUCTION PLAN NOTES Add ENLARGEMENT GENERAL NOTE "E", which shall read as follows: "SEE SHEET E504 FOR ADDITIONAL GROUNDING AND BONDING REQUIREMENTS OF FOUNTAIN EQUIPMENT AND PAVING AS PART OF THE ADDITIVE ALTERNATE."
24

Request For Qualifications-Based Proposals for ...

Jan 24, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Request For Qualifications-Based Proposals for ...

CITY OF FARMINGTON

800 Municipal Drive Farmington, NM 87401-2663

(505) 599-1373 Fax (505) 599-1377

http://www.fmtn.org

AD1-1

Request For Qualifications-Based Proposals for Construction Contract Farmington Civic Center Renovations & Expansion

PROJECT NO. CCEXP, RFP NO. 18-122315

IMMEDIATE ATTENTION ADDENDUM ONE

August 25, 2017

Receipt of this addendum shall be noted on Page 3 in the Request for Qualifications-based Proposal documents for the above referenced RFQP. The addendum is hereby made part of the Contract Documents to the same extent as though it were originally included therein. Refer to "Submittal Form" for acknowledgment of addenda. All Contractors, Subcontractors and suppliers are reminded that they shall be familiar with all addenda items (as well as all parts of the construction documents) so as to understand the extent of their work and its interrelation with other trades. To all bidders for furnishing all labor and materials necessary for the following contract: CIVIL ITEMS CIVIL SHEETS ITEM AD1-C1 Clarification: in all sheets where metal handrails or guardrails are referenced, handrails or guardrails must be primed and painted. The paint color shall be coordinated between the City of Farmington and the Architect. LANDSCAPING ITEMS PROJECT MANUAL ITEM AD1-L1 Section 01 56 39 – Temporary Tree Protection Delete section 01 56 39 – Temporary Tree Protection in its entirety from the project manual. Contractor shall refer to TREE PROTECTION NOTES on SHEET ADS101 for this scope of work. DRAWING SHEETS ITEM AD1-L2 Sheet LS102 – CONSTRUCTION PLAN NOTES Add ENLARGEMENT GENERAL NOTE "E", which shall read as follows: "SEE SHEET E504 FOR ADDITIONAL GROUNDING AND BONDING REQUIREMENTS OF FOUNTAIN EQUIPMENT AND PAVING AS PART OF THE ADDITIVE ALTERNATE."

Page 2: Request For Qualifications-Based Proposals for ...

CITY OF FARMINGTON

800 Municipal Drive Farmington, NM 87401-2663

(505) 599-1373 Fax (505) 599-1377

http://www.fmtn.org

AD1-2

ITEM AD1-L3 Sheet LS101 – Construction Plan South Revise a portion of SHEET LS101 - CONSTRUCTION PLAN SOUTH, per SKL-001 attached to this addendum. ITEM AD1-L4 Sheet LS501 – Planting Plan South Revise SHEET TITLE to read: "CONSTRUCTION DETAILS". ITEM AD1-L5 Sheet LS502 – Planting Plan North Revise SHEET TITLE to read: "CONSTRUCTION DETAILS". Revise a portion of SHEET LS502 - CONSTRUCTION DETAILS, to include new detail A3 per SKL-002 attached to this addendum. ITEM AD1-L6 Sheet LS503 – Planting Plan North Revise SHEET TITLE to read: "CONSTRUCTION DETAILS". Revise a portion of SHEET LS503 - CONSTRUCTION DETAILS, to include new detail C2 per SKL-003 attached to this addendum. ARCHITECTURAL ITEMS PROJECT MANUAL ITEM AD1-A1 Section 01 30 00 – Administrative Requirements Page 01 30 00, page 3, replace section 3.06 with section 3.06 below: 3.06 CONSTRUCTION DOCUMENTS

A. The Owner distributes Bidding Documents and issues Addenda for securing Bids for the project Work. The Owner will provide to the Contractor 1 hard copy set of the Contract Documents. The Contractor shall pay the printing costs for additional sets.

ITEM AD1-A2 Section 01 30 00 – Administrative Requirements Page 01 30 00, page 5, section 3.13 replace paragraph “G” with paragraph “G” below:

G. Contractor must submit packaged roof top unit submittal and electrical lighting submittal for A/E team and Owner’s energy conservation contractor review and approval within the first group of submittals. For these submittals allow for 45 days for review time. Do not proceed with equipment ordering until approvals from A/E team and ECI have been received. For all other submittal reviews, allow 15 days excluding delivery time to and from the General Contractor.

ITEM AD1-A3 Section 10 22 27 – Operable Partitions Delete section 10 22 27 in the project manual and replace with section 10 22 27, dated 8/22/2017 attached to this addendum.

Page 3: Request For Qualifications-Based Proposals for ...

CITY OF FARMINGTON

800 Municipal Drive Farmington, NM 87401-2663

(505) 599-1373 Fax (505) 599-1377

http://www.fmtn.org

AD1-3

ARCHITECTURAL SHEETS ITEM AD1-A4 Sheet ADS101 – Demolition Site Plan Replace Tree Protection Notes legend with Tree Protection Legend on sheet ADD-1-01, dated 8/23/17 attached to this addendum. ITEM AD1-A5 Sheet AS101 – New Site Plan & Phasing Descriptions Add the following tree protection note to the Tree Protection Notes legend: 7. CONTRACTOR SHALL PROVIDE TEMPORARY WATER TO TREES, SHRUBS AND TURFGRASS SHOWN TO REMAIN, AS IS REQUIRED IN ORDER TO MAINTAIN ALL PLANT MATERIAL IN A HEALTHY, THRIVING AND DISEASE-FREE CONDITION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE FREQUENCY AND DURATION OF WATERING." ITEM AD1-A6 Sheet AS501 – Details – Site Delete keynote legend box, no keyed notes are used for this sheet. ITEM AD1-A7 Sheet A505 – Details – Casework Delete general notes -details legend box, no general notes are used for this sheet. MECHANICAL ITEMS DRAWING SHEETS ITEM ADD1-M1 Sheet M601 – MECHANICAL DETAILS

1. Revise rooftop unit schedule to provide direct drive ECM motors in lieu of belt drive with VFD. Units to be a minimum of 17 SEER.

ELECTRICAL ITEMS ELECTRICAL SHEETS ITEM ADD1-E1 Sheet EDL103 – Electrical Lighting Demo Plan – Theater Ground Floor

1. Revise existing seat junction box layout. 2. Revise keyed note 26.57 to read “LOCATION OF EXISTING FLOOR MOUNTED

JUNCTION BOX UNDER SEAT. MANY ARE DAMAGED OR NOT ENTIRELY RECESSED IN CONCRETE. SOME WILL BE REUSED FOR POWER SUPPLIES FOR NEW AISLE LIGHTING (SEE NEW PLAN, SHEET EL104). REMOVE EXISTING BOXES AND MC CABLE UNDER SEATS IN ALL LOCATIONS. IN LOCATIONS BEING REUSED, PROVIDE NEW BOX AND WIRING TO POWER SUPPLY. IN LOCATIONS NOT BEING REUSED, CAP WIRING AND COVER BOX WITH BLANK PLATE.”

3. Replace sheet with sheet EDL103 attached to this addendum.

Page 4: Request For Qualifications-Based Proposals for ...

CITY OF FARMINGTON

800 Municipal Drive Farmington, NM 87401-2663

(505) 599-1373 Fax (505) 599-1377

http://www.fmtn.org

AD1-4

ITEM ADD1-E2 Sheet ES101-Electrical Site Plan

1. Add outline and keyed notes related to splash pad bonding and minimum distance of other underground electrical.

2. Revise keyed note 26.94 to read: “EXISTING TREE SCULPTURE TO BE RELOCATED HERE. SCULPTURE ORIGINALLY HAD INTERNAL FLUORESCENT LIGHTING. IN THIS PROJECT, REPLACE INTERNAL FIXTURE WITH NEW LED AND RECONNECT. FOR BIDDING PURPOSES, INCLUDE AN ALLOWANCE OF $1000 TO COVER LABOR AND MATERIALS FOR THIS FIXTURE.”

3. Add missing type tags to fixture Z in alternate plan. 4. Replace sheet with sheet ES101 attached to this addendum.

ITEM ADD1-E3 Sheets EL101 – EL105 Electrical Lighting Plans

1. Correction to lighting control scenario schedule: LC.04 description should read “manual switching,” not “manual dimming.”

2. Replace sheets with sheets EL101 – EL 105 attached to this addendum. ITEM ADD1-E4 Sheet EL101 – Electrical Lighting Plan – Exhibit Hall

1. Add missing type tags for exit signs. 2. Add note indicating existing exhibit hall controls to be combined where partition wall is

being removed. 3. Replace sheet with sheet EL101 attached to this addendum.

ITEM ADD1-E5 Sheet EL102 - Electrical Lighting Plan – Exhibit Hall Addition

1. Add lighting control zoning details for exhibit hall. 2. Replace sheet with sheet EL102 attached to this addendum.

ITEM ADD1-E6 Sheet EL103 - Electrical Lighting Plan – Theater Basement

1. Remove duplicate fixture shown in elevator area. 2. Replace sheet with sheet EL103 attached to this addendum.

ITEM ADD1-E7 Sheet EL104 - Electrical Lighting Plan – Theater Ground Floor

1. Revise theater floor level lighting plan. 2. Replace sheet with sheet EL104 attached to this addendum.

ITEM ADD1-E8 Sheet EP105 – Elec Power & Special Systems Plan – Theater Mezzanine

1. Add ceiling receptacle in control booth for added security camera. 2. Replace sheet with sheet EP105 attached to this addendum.

Page 5: Request For Qualifications-Based Proposals for ...

CITY OF FARMINGTON

800 Municipal Drive Farmington, NM 87401-2663

(505) 599-1373 Fax (505) 599-1377

http://www.fmtn.org

AD1-5

ITEM ADD1-E9 Sheet E503 – Lighting Control Details & Schedules

1. Revise exhibit hall lighting control one-line diagram. 2. Replace sheet with sheet E503 attached to this addendum.

ITEM ADD1-E10 Sheet E504 – Electrical Details

1. Add splash pad grounding and bonding detail. 2. Replace sheet with sheet E504 attached to this addendum.

ITEM ADD1-E11 Sheet E601 – Light Fixture Schedule

1. Fill in pre-approved alternate fixture specification columns where applicable. 2. Revise specification for theater aisle fixtures (Q, R, and S types). 3. Clarification: amount of allowance for type D fixture can be found in specification section

01 21 00-1.06, Allowances Schedule. 4. Replace sheet with sheet E601 attached to this addendum.

END OF ADDENDUM NO. 1

Jennifer Rowland, CPPB Buyer II Phone: (505) 599-1386 Fax: (505) 599-1377 Email: [email protected]

Page 6: Request For Qualifications-Based Proposals for ...
Page 7: Request For Qualifications-Based Proposals for ...
Page 8: Request For Qualifications-Based Proposals for ...
Page 9: Request For Qualifications-Based Proposals for ...

FCC Renovation & Expansion G/S SJCF Arch 5164.00

OPERABLE PARTITIONS 10 22 27 - 1 8/22/2017

SECTION 10 22 27OPERABLE PARTITIONS

PART 1: GENERAL1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract including General and Supplementary Conditions and Division1 Specification Sections, apply to this Section.

1.02 SUMMARYA. This Section includes the following:

1. Electrically operated, continuously hinged partitions.B. Related Sections include the following:

1. Division 3 Sections for concrete tolerances required.2. Division 5 Sections for primary structural support, including pre-punching of support members by

structural steel supplier per operable partition supplier's template.3. Division 6 Sections for wood framing and supports, and all blocking at head and jambs as required.4. Division 9 Sections for wall and ceiling framing at head and jambs.

1.03 QUALITY ASSURANCEA. Installer Qualifications: An experienced installer who is certified in writing by the operable partition

manufacturer, as qualified to install the manufacturer's partition systems for work similar in material, design, andextent to that indicated for this Project.

B. Acoustical Performance: Test operable partitions in an independent acoustical laboratory in accordance withASTM E90 test procedure to attain no less than the STC rating specified. Provide a complete and uneditedwritten test report by the testing laboratory upon request.

C. Preparation of the opening shall conform to the criteria set forth per ASTM E557 "Standard Practice forArchitectural Application and Installation of Operable Partitions."

1.04 SUBMITTALSA. Product Data: Material descriptions, construction details, finishes, installation details, and operating instructions

for each type of operable partition, component, and accessory specified.B. Shop Drawings: Show location and extent of operable partitions. Include plans, sections, details, attachments to

other construction, and accessories. Indicate dimensions, weights, conditions at openings, and at storage areas,and required installation, storage, and operating clearances. Indicate location and installation requirements forhardware and track, including floor tolerances required and direction of travel. Indicate blocking to be providedby others.

C. Setting Drawings: Show imbedded items and cutouts required in other work, including support beam punchingtemplate.

D. Samples: Color samples demonstrating full range of finishes available by architect. Verification samples will beavailable in same thickness and material indicated for the work.

1.05 DELIVERY, STORAGE, AND HANDLINGA. Clearly mark packages and panels with numbering systems used on Shop Drawings. Do not use permanent

markings on panels.B. Protect panels during delivery, storage, and handling to comply with manufacturer's direction and as required to

prevent damage.1.06 WARRANTY

A. Provide written warranty by manufacturer of operable partitions agreeing to repair or replace any componentswith manufacturing defects.

B. Partition Warranty period: Three (3) years from date of shipment.C. Suspension System Warranty:

Page 10: Request For Qualifications-Based Proposals for ...

FCC Renovation & Expansion G/S SJCF Arch 5164.00

OPERABLE PARTITIONS 10 22 27 - 2 8/22/2017

1. OP-01: Ten (10) years from date of shipment.2. OP-02: Ten (10) years from date of shipment.3. OP-03: Ten (10) years from date of shipment.

PART 2 - PRODUCTS2.01 MANUFACTURERS, PRODUCTS, AND OPERATIONS

A. Manufacturers: Subject to compliance with requirements, provide products by the following:1. Modernfold, Inc.2. Products: Subject to compliance with the requirements, provide the following product:

a. OP-01: Acousti-Seal Encore - Automatic Panel: Electrically operated continuously hinged operablepartition.

b. OP-02: Acousti-Seal Encore - Automatic Panel: Electrically operated continuously hinged operablepartition.

c. OP-03: Acousti-Seal Encore - Automatic Panel: Electrically operated continuously hinged operablepartition.

2.02 OPERATIONA. OP-01: Acousti-Seal Encore - Series of continuously hinged flat panels, electrically operated, top supported with

operable floor seals and automatic top seals.B. OP-02: Acousti-Seal Encore - Series of continuously hinged flat panels, electrically operated, top supported with

operable floor seals and automatic top seals.C. OP-03: Acousti-Seal Encore - Series of continuously hinged flat panels, electrically operated, top supported with

operable floor seals and automatic top seals.2.03 Final Closure:

A. OP-01: Partition shall be operated by two push button control stations wired in series and located on oppositesides of the partition. Control stations shall be activated by key switch at stack end of partition. Motor unit shallbe reversible, continuous duty, and class A insulated. Motor unit shall have NEMA MG1 service factor, highstarting torque, thermal overload protection, and open/drip proof enclosure. Motor assembly shall have wiringcompliant with NFPA 70, 24 volt controls, compliant with UL508A, and speed of 28 feet/minute. The drive unitmotor shall be equipped with outboard limit switches to prevent over-extension. A positive-chain drive attachedto the lead panel shall pull the partition across the opening. Cable, belt or other friction type drives will not beaccepted.

B. OP-02: Partition shall be operated by two push button control stations wired in series and located on oppositesides of the partition. Control stations shall be activated by key switch at stack end of partition. Motor unit shallbe reversible, continuous duty, and class A insulated. Motor unit shall have NEMA MG1 service factor, highstarting torque, thermal overload protection, and open/drip proof enclosure. Motor assembly shall have wiringcompliant with NFPA 70, 24 volt controls, compliant with UL508A, and speed of 28 feet/minute. The drive unitmotor shall be equipped with outboard limit switches to prevent over-extension. A positive-chain drive attachedto the lead panel shall pull the partition across the opening. Cable, belt or other friction type drives will not beaccepted.

C. OP-03: Partition shall be operated by two push button control stations wired in series and located on oppositesides of the partition. Control stations shall be activated by key switch at stack end of partition. Motor unit shallbe reversible, continuous duty, and class A insulated. Motor unit shall have NEMA MG1 service factor, highstarting torque, thermal overload protection, and open/drip proof enclosure. Motor assembly shall have wiringcompliant with NFPA 70, 24 volt controls, compliant with UL508A, and speed of 28 feet/minute. The drive unitmotor shall be equipped with outboard limit switches to prevent over-extension. A positive-chain drive attachedto the lead panel shall pull the partition across the opening. Cable, belt or other friction type drives will not beaccepted.

D. Electric motor shall consist of:1. OP-01: A 480-volt, 3-phase2. OP-02: A 480-volt, 3-phase3. OP-03: A 480-volt, 3-phase

Page 11: Request For Qualifications-Based Proposals for ...

FCC Renovation & Expansion G/S SJCF Arch 5164.00

OPERABLE PARTITIONS 10 22 27 - 3 8/22/2017

2.04 PANEL CONSTRUCTIONA. Nominal 4.25-inch (108mm) thick panels in manufacturer's standard 51-inch (1295mm) widths. All panel

horizontal and vertical framing members fabricated from minimum 16-gage formed steel with overlapped andwelded corners for rigidity. Top channel is reinforced to support suspension system components. Frame isdesigned so that full vertical edges of panels are of formed steel and provide concealed protection of the edges ofthe panel skin.

B. Panel skin shall be:1. OP-01: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray of

material. Acoustical ratings of panels with this construction minimum:a. 52 STC

2. OP-02: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray ofmaterial. Acoustical ratings of panels with this construction minimum:a. a. 52 STC

3. 3. OP-03: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray ofmaterial. Acoustical ratings of panels with this construction minimum:a. a. 52 STC

4. Hinges for Panels, Closure Panels, Pass Doors, and Pocket Doors shall be:a. OP-01: Full leaf butt hinges, attached directly to the panel frame with welded hinge anchor plates

within panel to further support hinge mounting to frame. Lifetime warranty on hinges. Hingesmounted into panel edge or vertical astragal are not acceptable.

b. OP-02: Full leaf butt hinges, attached directly to the panel frame with welded hinge anchor plateswithin panel to further support hinge mounting to frame. Lifetime warranty on hinges. Hingesmounted into panel edge or vertical astragal are not acceptable.

c. OP-03: Full leaf butt hinges, attached directly to the panel frame with welded hinge anchor plateswithin panel to further support hinge mounting to frame. Lifetime warranty on hinges. Hingesmounted into panel edge or vertical astragal are not acceptable.

5. Panel Trim: No vertical trim required or allowed on edges of panels; minimal groove appearance at allpanel joints.

6. Panel Weights:a. OP-01: 52 STC - 8.2 lbs./square footb. OP-02: 52 STC - 8.2 lbs./square footc. OP-03: 52 STC - 8.2 lbs./square foot

2.05 PANEL FINISHA. Panel finish shall be factory applied, Class "A" rated material. Finish shall be:

1. OP-01: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray ofmaterial: Color: Brocade 003.

2. OP-02: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray ofmaterial: Color: Brocade 003.

3. OP-03: Acoustical, non-woven needle punch carpet, with fused fibers to prevent unraveling or fray ofmaterial: Color: Brocade 003.

4. Panel Trim: Exposed panel trim of one consistent color:a. OP-01: Smoke Gray SW6002b. OP-02: Smoke Gray SW6002c. OP-03: Smoke Gray SW6002

2.06 SOUND SEALSA. Vertical Interlocking Sound Seals between panels: Aluminum astragals, with tongue and groove configuration in

each panel edge. Rigid plastic astragals are not acceptable.B. Horizontal Top Seals shall be Modernfold SureSet™ automatic operable top seals, manually operated top seals

not required or permitted.C. Horizontal bottom floor seals shall be Modernfold Sureset™ bottom seal:

Page 12: Request For Qualifications-Based Proposals for ...

FCC Renovation & Expansion G/S SJCF Arch 5164.00

OPERABLE PARTITIONS 10 22 27 - 4 8/22/2017

1. OP-01: Modernfold SA2E Bottom Seal. Automatic bottom seals providing nominal 2-inch (51 mm)operating clearance with an operating range of +1/2-inch (13 mm) to -1-1/2-inch (38 mm) whichautomatically drop as panels are positioned and final closure made, without the need for tools or cranks.

2. OP-02: Modernfold SA2E Bottom Seal. Automatic bottom seals providing nominal 2-inch (51 mm)operating clearance with an operating range of +1/2-inch (13 mm) to -1-1/2-inch (38 mm) whichautomatically drop as panels are positioned and final closure made, without the need for tools or cranks.

3. OP-03: Modernfold SA2E Bottom Seal. Automatic bottom seals providing nominal 2-inch (51 mm)operating clearance with an operating range of +1/2-inch (13 mm) to -1-1/2-inch (38 mm) whichautomatically drop as panels are positioned and final closure made, without the need for tools or cranks.

2.07 SUSPENSION SYSTEMA. OP-01: #14 Suspension System

1. Suspension Tracks: Minimum 7-gauge, 0.18-inch (4.57mm) roll formed steel. Static loading of track withbrackets at 48-inch (1220mm) centers shall show no failure of track or brackets at 5,000 pounds (2550kg)point loading at mid-span. Track shall be supported by adjustable steel hanger brackets connected tostructural support pairs of 0.50-inch (13mm) diameter threaded rods. Brackets must support the loadbearing surface of the track.a. Exposed track soffit: Steel, removable for service and maintenance, attached to track bracket without

exposed fasteners, and pre-painted off-white.b. Carriers: All-steel trolleys with steel tired ball bearing wheels.

2. OP-02: #14 Suspension Systema. Suspension Tracks: Minimum 7-gauge, 0.18-inch (4.57mm) roll formed steel. Static loading of track

with brackets at 48-inch (1220mm) centers shall show no failure of track or brackets at 5,000 pounds(2550kg) point loading at mid-span. Track shall be supported by adjustable steel hanger bracketsconnected to structural support pairs of 0.50-inch (13mm) diameter threaded rods. Brackets mustsupport the load bearing surface of the track.1) Exposed track soffit: Steel, removable for service and maintenance, attached to track bracket

without exposed fasteners, and pre-painted off-white.b. 2. Carriers: All-steel trolleys with steel tired ball bearing wheels.

3. OP-03: #14 Suspension Systema. 1. Suspension Tracks: Minimum 7-gauge, 0.18-inch (4.57mm) roll formed steel. Static loading of

track with brackets at 48-inch (1220mm) centers shall show no failure of track or brackets at 5,000pounds (2550kg) point loading at mid-span. Track shall be supported by adjustable steel hangerbrackets connected to structural support pairs of 0.50-inch (13mm) diameter threaded rods. Bracketsmust support the load bearing surface of the track.1) Exposed track soffit: Steel, removable for service and maintenance, attached to track bracket

without exposed fasteners, and pre-painted off-white.b. Carriers: All-steel trolleys with steel tired ball bearing wheels.

2.08 OPTIONSA. Available accessories/options:

1. OP-01: Pocket Doors: Acousti-Seal Pocket Doors by Modernfold, Inc., with same construction as panels.Plastic laminate door fronts to match Nevamar Cognac Birdseye W8348V.a. Pocket Door configuration shall be manually operated: Type III double doors hinged to a jamb on

each side and closing in the center. One of the door panels is equipped with a smaller hinged panelthat folds back when the operable partition is extended into the pocket.

2. OP-02: Pocket Doors: Acousti-Seal Pocket Doors by Modernfold, Inc., with same construction as panels.Plastic laminate door fronts to match Nevamar Cognac Birdseye W8348V.a. Pocket Door configuration shall be manually operated: Type III double doors hinged to a jamb on

each side and closing in the center. One of the door panels is equipped with a smaller hinged panelthat folds back when the operable partition is extended into the pocket.

3. OP-03: Pocket Doors: Acousti-Seal Pocket Doors by Modernfold, Inc., with same construction as panels.Plastic laminate door fronts to match Nevamar Cognac Birdseye W8348V.

Page 13: Request For Qualifications-Based Proposals for ...

FCC Renovation & Expansion G/S SJCF Arch 5164.00

OPERABLE PARTITIONS 10 22 27 - 5 8/22/2017

a. Pocket Door configuration shall be manually operated: Type III double doors hinged to a jamb oneach side and closing in the center. One of the door panels is equipped with a smaller hinged panelthat folds back when the operable partition is extended into the pocket.

PART 3: EXECUTION3.01 INSTALLATION

A. General: Comply with ASTM E557, operable partition manufacturer's written installation instructions, Drawingsand approved Shop Drawings.

B. Install operable partitions and accessories after other finishing operations, including painting have beencompleted.

C. Match operable partitions by installing panels from marked packages in numbered sequence indicated on ShopDrawings.

D. Broken, cracked, chipped, deformed or unmatched panels are not acceptable.3.02 CLEANING AND PROTECTION

A. Clean partition surfaces upon completing installation of operable partitions to remove dust, dirt, adhesives, andother foreign materials according to manufacturer's written instructions.

B. Provide final protection and maintain conditions in a manner acceptable to the manufacturer and installer thatinsure operable partitions are without damage or deterioration at time of Substantial Completion.

3.03 ADJUSTINGA. Adjust operable partitions to operate smoothly, easily, and quietly, free from binding, warp, excessive deflection,

distortion, nonalignment, misplacement, disruption, or malfunction, throughout entire operational range.Lubricate hardware and other moving parts.

3.04 EXAMINATIONA. Examine flooring, structural support, and opening, with Installer present, for compliance with requirements for

installation tolerances and other conditions affecting performance of operable partitions. Proceed withinstallation only after unsatisfactory conditions have been corrected.

3.05 DEMONSTRATIONA. Demonstrate proper operation and maintenance procedures to Owner's representative.B. Provide Operation and Maintenance Manual to Owner's representative.

END OF SECTION

Page 14: Request For Qualifications-Based Proposals for ...

1. CONTRACTOR SHALL ESTABLISH A ROOT PROTECTION ZONE AROUND EACH EXISTING TREE TO REMAIN. THE ROOT PROTECTION ZONE SHALL BE AN AREA

DEFINED BY A RADIUS EXTENDING OUTWARD FROM THE TRUNK OF THE TREE A DISTANCE OF ONE LINEAR FOOT FOR EACH INCH DIAMETER OF THE TREE. THE

TREE DIAMETER SHALL BE MEASURED AT BREAST HEIGHT (4.5' ABOVE FINISH GRADE). EXAMPLE: A 10 INCH DIAMETER TREE WILL HAVE A 10 FOOT RADIUS

ROOT PROTECTION ZONE.

2. CONTRACTOR SHALL INSTALL FENCING AT THE PERIMETER OF ROOT PROTECTION ZONES. NO WORK SHALL BEGIN WHERE TREE PROTECTION FENCING HAS NOT BEEN COMPLETED AND APPROVED. TREE PROTECTION

FENCING SHALL BE INSTALLED, MAINTAINED AND REPAIRED BY THE CONTRACTOR DURING CONSTRUCTION. THE FENCING SHALL BE A MINIMUM OF

4' HEIGHT.

3. CONTRACTOR SHALL NOT STORE OR DRIVE EQUIPMENT, VEHICLES OR MATERIALS WITHIN THE ROOT PROTECTION ZONE.

4. CONTRACTOR SHALL PROTECT EXISTING ROOTS FROM DAMAGE WHEN WORKING WITHIN THE ROOT PROTECTION ZONE. THE CONTRACTOR SHALL

LIMIT DEMOLITION OR OTHER CONSTRUCTION ACTIVITIES WITHIN THE ROOT PROTECTION ZONE TO THE MINIMUM DISTURBANCE REQUIRED TO COMPLETE

CONSTRUCTION.

5. CONTRACTOR SHALL NOT ALLOW CONCRETE TRUCKS TO CLEAN CHUTES OR DUMP EXCESS CONCRETE OR ANY OTHER CEMENTITIOUS PRODUCTS IN ANY PORTION OF THE SITE. CONTRACTOR SHALL CLEAN THE WASTE OF OTHER

CEMENTITIOUS MATERIALS FROM THE SURFACE AND THEY SHALL NOT BE TURNED UNDER DURING FINAL GRADING.

6. CONTRACTOR SHALL NOT TRENCH WITHIN THE DRIPLINE OF EXISTING TREES.

AT LOCATIONS WHERE IT IS NECESSARY TO INSTALL LINES OR WIRE WITHIN THE DRIPLINE OF EXISTING TREES, THE UTILITY SHALL BE INSTALLED BY BORING UNDER TREE ROOTS.

7. CONTRACTOR SHALL PROVIDE TEMPORARY WATER TO TREES, SHRUBS AND

TURFGRASS SHOWN TO REMAIN, AS IS REQUIRED IN ORDER TO MAINTAIN ALL PLANT MATERIAL IN A HEALTHY, THRIVING AND DISEASE-FREE CONDITION.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE FREQUENCY AND DURATION OF WATERING."

DATE

PAGE

JOB NO.

C:\

Use

rs\s

mez

a.M

AIN

\Do

cum

ents

\FC

C E

xpan

sio

n_R

17_s

mez

a.rv

t8/

24/2

017

10:1

6:53

AM

5264.00 08/23/17

FARMINGTON CIVIC CENTER RENOVATIONS &

EXPANSION

CITY OF FARMINGTON ADD-01

TREE PROTECTION NOTES

-01

Page 15: Request For Qualifications-Based Proposals for ...

3

33

3

3

K

3

3

3 3

3

3

3

3

3

.14

J

J

J

J J

J

J J

J J

J

J

J

J

J

J

JJ

J

J

J

J

J

J

J JJ

J

J

J

X76.2

X76.2

X74.J

X74.J

X74.J

X74.J

X74.J

X74.J

X74.J

X74.J

X74.HX74.H

X74.H

X74.HX74.HX74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H

X74.H X74.H

X74.H

X74.H

X74.RX74.RX74.R

X74.GX74.J

X74.JX74.B1

X74.B1

X74.A1

X74.A1

X74.A1

X74.A1X74.A1

X74.A1X74.A1

X74.A1

X74.B1

X74.B1

X74.JX74.J

X74.A1

X74.A1

X74.G

X74.R

X74.R

X74.R

X74.J X74.J

X74.J X74.J

X74.J X74.J

X76.EX

X74.EM

X74.EM

X74.J

X74.J

X76.EX

X76.EX

X76.1X76.1 X76.1

X76.1X76.1 X76.1

X76.1X76.1 X76.1

X76.1X76.1 X76.1

X74.JX76.1 X76.1

X76.1 X76.1

X76.1 X76.1

X76.1 X76.1

X76.1

X74.ZX74.Z X74.Z

X74.Z

X74.Z X74.Z

X74.Z X74.Z

X74.Z X74.Z

X74.Z X74.Z

X74.Z X74.Z

X74.Z X74.Z

X76.1X76.EX

X76.1 X76.1 X76.1 X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1

X76.1 X76.1

X76.1

X76.1

X76.EX

X76.EXX76.1 X76.1

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1 X74.B1 X74.B1 X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

X76.EX

X76.EX

X74.Z

X74.Z

X74.ZX74.Z

X74.Z

X74.Z

X74.B1

VESTT101

WOMENT103

MENT113

WOMEN'S DRESST123

WOMENT124

MEN'S DRESST126

MENT127

BOARD RMT122

MAKE-UPT125

STAGET116

AUDITORIUMT115

JANT114

JANT104

PRIVATE DRESST121

PRIVATE DRESST120

JANT119

PRIVATE DRESST118

VESTT128

CORRIDORT117

S STAIRT105

W STAIRT112

??

LOBBYT100

CORRIDORT102

STORAGE 1T109

TECHNICALT110

SUPERVISORST108

STORAGE 2T107

OFFICE 3T106

X74.PX74.PX74.PX74.PX74.P

X74.P

X74.P

X74.P

X74.P

X74.P

X74.P

26.43

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z

X74.Z X74.Z X74.Z X74.Z X74.ZX74.Z

X74.Z

X74.Z

PANEL LAA

PANEL LAB

PANEL LAC

XW

PANEL W

PANEL LAF

26.5726.57

26.5726.57

26.57

26.57 26.57 26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

26.57

X74.KA

X74.KA

X74.KA

X74.KAX74.KAX74.KA

X74.KA

X74.KA

X74.KA

X74.KA

X74.KA

X74.KA

26.57

IN HALL BELOW

IN HALL BELOW

IN HALL BELOW

IN HALL BELOW

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:38:31

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EDL103

ELEC. LIGHTINGDEMOLITION PLAN -THEATER - GROUNDFLOOR

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

NB/AW

AW

N 1/8" = 1'-0"

ELECTRICAL LIGHTING DEMOLITION PLAN - THEATER - GROUND FLOORA1

KEYED NOTES26.43

REMOVE KEYED SWITCHES CONTROLLING TRACK LIGHTING. PER SIGN ON WALL, SWITCHBANK IN OFFICE ALSO CONTROLS TRACK LIGHTING (VERIFY). SEE CENTRAL LIGHTINGCONTROL DETAIL ON SHEET E503 FOR NEW CONTROL SYSTEM.

26.57

LOCATION OF EXISTING FLOOR MOUNTED JUNCTION BOX UNDER SEAT. MANY AREDAMAGED OR NOT ENTIRELY RECESED IN CONCRETE. SOME WILL BE REUSED FOR POWERSUPPLIES FOR NEW AISLE LIGHTING (SEE NEW PLAN, SHEET EL104). REMOVE EXISTINGBOXES AND MC CABLE UNDER SEATS IN ALL LOCATIONS. IN LOCATIONS BEING REUSED,PROVIDE NEW BOX AND WIRING TO POWER SUPPLY. IN LOCATIONS NOT BEING REUSED,CAP WIRING AND COVER BOX WITH BLANK PLATE.

GENERAL ELEC DEMO NOTES1

REFER TO THEATER SYSTEMS DEMOLITION (TDS) AND AUDIO-VISUAL DEMOLITION (AVD)SHEETS FOR ADDITIONAL DEMOLITION WORK BY ELECTRICAL CONTRACTOR. COORDINATEWITH THEATER CONTRACTOR FOR DEMOLITION OBSERVATION WHERE APPLICABLE.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

N 1/8" = 1'-0"

ELECTRICAL LIGHTING DEMOLITION PLAN - THEATER - FLOOR LEVEL1

1

1

Page 16: Request For Qualifications-Based Proposals for ...

LA PLATA STREET

WEST ARRINGTON STREET

BEHRE

ND

AVE

NOR

TH ALLEN

AVE

E

RL

RL

RL

RL

RL

RL

RL

RG

RG

RG

RG

RG

RV

RG

RG

JR

L

RL

RL

RL

J

RF

RF

RF RP RF RP RF RP

RP

RF

RP

RF

RP

RP

RP

RFRP

RF

RP

RP

RP

RFRP

LC.09

J

J

RGRL

RL

RL

RL

RL

RG

RG

RG

RG

RG

RG

RG

RG

RG

RG

RG

RG

RG

RL

RL

RG

JJJ

J

N

J

RG

RG

RL

RL

RL

RL

RP

RF

RP

RF

RP

RP

RFRP

RF

RP

RP

RP

LC.09

J

RG

RG

RG

RG

RG

RG

RL

RL

RG

J

N

J

RF

RG

RL

RP

RV

NEW XFMR"T1" (STEP-UP)

SERVICE #2TRANSFORMER(EXISTING TO

REMAIN)

PANEL MDP2

SERVICE # 1TRANSFORMER

26.15

PANEL LAF

26.21

26.19

SERVICE #1DISCONNECT

26.39

PB

PB

PB

PB

P2

P2

P2 P2 P2

P2

P4

P4

P2

P4

P4

P4

P2

P2

P2

P2

P2

P2

PB

PB

PB

PB

PBPB

PB

PB

PB

PB

PB

PB

26.20TYPTYP

26.21TYP

26.41

26.42

26.4926.49

Z

Z

Z

Z

26.50

26.26

FP

CS3

26.24

X-CH1

X-CH2XFMRSECONDARYDISCONNECT

EXIST. UGE TO REMAIN

NEW UGE

NEW UGE

NEW

UGE

26.55

D - 10D - 4

D - 4LAF - 1,3,5

LAF - 8

D - 6 D - 12

D - 6 D - 12

D - 1,3,5

D - 10D - 2

D - 12D - 6

D - 6 D - 8D - 1,3,5

D - 6 D - 8

D - 1,3,5 D - 2

D - 14D - 2

D - 1,3,5 D - 2

D - 14

D - 2

LAF - 1,3,5

LAF - 8

LAF - 8

LAF - 1,3,5

LAF - 1,3,5LAF - 8

LAF - 22LAF - 6 LAF - 6

LAF - 18

LAF - 8

LAF - 10 LAF - 7,9,11

LAF - 24 LAF - 10

LAF - 10LAF - 24

LAF - 24 LAF - 10LAF - 18LAF - 10

LAF - 20 LAF - 10

LAF - 10LAF - 20

LAF - 16 LAF - 10

LAF - 10LAF - 16

LAF - 7,9,11 LAF - 10

D - 10D - 2

LAF - 22LAF - 6

LAF - 22

D - 11,13

LAF - 25,27

LAF - 33,35

D - 11,13

D - 11,13

D - 11,13

D - 7,9

D - 19

D - 19

D - 19

D - 19

LAF - 25,27

LAF - 25,27

LAF - 25,27

LAF - 33,35

LAF - 25,27 LAF - 25,27 LAF - 25,27

LAF - 25,27

LAF - 29,31

LAF - 29,31

LAF - 29,31

LAF - 29,31

LAF - 33,35

LAF - 33,35D - 7,9

D - 11,13

D - 11,13

D - 11,13

D - 11,13

D - 7,9

LAF - 33,35

LAF - 29,31

LAF - 29,31

D - 7,9

D - 7,9D - 7,9

D - 7,9

LAF - 2

LAF - 19,21,23

HPA - 7,9,11

HPA - 1,3,5

D - 16

LAF - 12

LAF - 14

D - 18D - 20D - 22

26.23

YYD - 11,13D - 11,13

PANEL D

THEATER

EXHIBIT HALL

EXHIBIT HALLADDITION

26.88

26.90

26.90

26.94

26.22

26.18

5'SPLASH PAD

26.25

1

26.42

NOTE:

THIS PLAN SHOWS CHANGES TO THE SITE LAYOUT IN THE TRELLIS STRUCTURE ALTERNATE. FIXTURES OUTSIDE THIS PLAN DO NOT CHANGE.

26.23

26.23

26.23

Y Y Y

Y Y YYY

YY

Y

YY

YYY

Y

Y

Y

PB

PB

P2

P4

P4

P4

P4

P4

P2

P2

PB

PB

PB

PB

PB

26.4926.49

PB

YYLAF - 37,39LAF - 37,39LAF - 37,39LAF - 37,39LAF - 37,39LAF - 37,39LAF - 37,39

LAF - 37,39LAF - 37,39

LAF - 37,39

LAF - 37,39 LAF - 37,39

D - 15,17D - 15,17D - 15,17

TYP.

TYP.

D - 15,17TYP. ALL FIXTURES IN THIS STRUCTURE

Z

Z

Z

Z

26.94

5'SPLASH PAD

1

26.25

26.42

DESCRIPTION

HOLIDAY LIGHTING RECEPTACLE BOX. ANGLED FACE FOR LONG TERM USE. PROVIDE PERMANENT WEATHERPROOF LABEL INSIDE COVER, READING "HOLIDAY LIGHTING ONLY".

GENERAL POWER RECEPTACLE BOX, WITH TWO 20 AMP RECEPTACLES. PROVIDE PERMANENT WEATHERPROOF LABEL INSIDE COVER WITH CIRCUIT NUMBER.

FOOD VENDOR AND GENERAL POWER RECEPTACLE BOX, WITH ONE 50 AMP AND TWO 20 AMP RECEPTACLES.

RV PEDESTAL FOR TOURING COMPANIES. COORDNINATE EXACT LOCATION WITH LANDSCAPE CONTRACTOR.

POLE RECEPTACLE INCLUDED WITH LIGHT POLE. ALSO FOR HOLIDAY LIGHTING USE, SIMILAR TO TYPE RL.

SPECIFICATION

MIDWEST ELECTRICU010SEPGRPGREEN FINISH

MIDWEST ELECTRICU012010GRPGREEN FINISH

MIDWEST ELECTRICU076GWHITE FINISH

MIDWEST ELECTRICU075CP6010GRAY FINISH

REPLACE COVER PROVIDED WITH METAL HEAVY DUTY WHILE-IN-USE COVER (WHITE FINISH).

COMPONENTS INCLUDED

(1) 5-20R, GFCI, TAMPERPROOF

(2) 5-20R, GFCI, TAMPERPROOF

(2) 5-20R, GFCI, TAMPERPROOF(1) 14-50R

(3) CIRCUIT BREAKERS

(1) 5-20R, GFCI, TAMPERPROOF(1) 7-30R(1) 14-50R

(3) CIRCUIT BREAKERS

(1) 5-20R, GFCIINCLUDED WITH POLE

CONTROLS

ROUTE EACH CIRCUIT THROUGH POWERPACK FOR PHOTOCELL CONTROL BY CENTRAL LIGHTING CONTROL SYSTEM. SEE SHEET E503.

NONE

NONE

NONE

SAME AS TYPE RL

PLAN SYMBOL

SITE RECEPTACLE SCHEDULEMOUNTING

UNISTRUT4' AFG

UNISTRUT4' AFG

LIGHT POLE BASESEE DETAIL, SHEET E504

INTEGRAL POST

INTEGRAL TO LIGHT POLE

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:29:40

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

ES101

ELECTRICAL SITEPLAN

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

N 1" = 20'-0"

ELECTRICAL SITE PLAN - BASE BIDA1 N 1" = 20'-0"

ELECTRICAL SITE PLAN - TRELLIS ALTERNATEA4

KEYED NOTES26.15

PROVIDE NEW "COMPANY SWITCH" CAM-LOCK CONNECTION POINT FOR OUTDOOR CONCERTS. REFER TO RISERDIAGRAM AND FEEDER SCHEDULE FOR DETAILED REQUIREMENTS. MOUNT ON UNISTRUT RACK, COORDINATE WITHLANDSCAPING CONTRACTOR FOR EXACT LOCATION, AND ENSURE THAT ANY SCREENING MAINTAINS NEC REQUIREDWORKING SPACE.

26.18LOCATION FOR EXTERIOR LIGHT CONTROL SWITCH STATION. PROVIDE LOCKING WEATHERPROOF COVER. REFER TOCENTRAL CONTROL SYSTEM DETAIL, SHEET E503. COORDINATE EXACT LOCATION WITH A/V CONTRACTOR SO THATA/V AND LIGHT CONTROLS ARE NEATLY GROUPED.

26.19 PROVIDE POWER TO NEW IRRIGATION CONTROLLER.

26.20 ON LIGHT POLE STRUCTURE, PROVIDE RECEPTACLES INDICATED, PER RECEPTACLE SCHEDULE, THIS SHEET. REFERTO POLE BASE ELECTRICAL DETAIL, SHEET E504.

26.21 IN EACH TREE PLANTER, PROVIDE UNISTRUT PEDESTAL WITH TWO RECEPTACLE BOXES PER RECEPTACLESCHEDULE. COORDINATE WITH LANDSCAPE CONTRACTOR FOR EXACT LOCATION.

26.22 AUDIO EQUIPMENT ALSO LOCATED ON THIS WALL. COORDINATE WITH A/V CONTRACTOR FOR EXACT LOCATION.

26.23 MOUNT LINEAR FIXTURES ON SIDES OF TRELLIS BEAMS SUCH THAT FACE OF FIXTURE IS FLUSH WITH BOTTOM OFBEAM.

26.24 HIDE RECEPTACLES BEHIND LOW WALL. COORDINATE EXACT LOCATION WITH ARCHITECT.

26.25 DO NOT INSTALL ANY UNDERGROUND ELECTRICAL LINE WITHIN 5 FEET OF THE SPLASH PAD. REFER TO SPLASH PADGROUNDING AND BONDING DETAIL (SHEET E504) FOR ADDITIONAL REQUIREMENTS.

26.26 PROVIDE POWER FOR NEW HOTBOX.

26.39UNDER ALTERNATE BID #4, PROVIDE FOUR CIRCUITS TO NEW DIGITAL MARQUE. COORDINATE EXACT REQUIREMENTSWITH MARQUE INSTALLER. ALSO PROVIDE CAT6 CABLING AND PATHWAY FROM NEW DIGITAL DISPLAY BOARD TOADMINISTRATION OFFICE. COORDINATE EXACT TERMINATION POINT IN ADMINISTRATION OFFICE WITH OWNER PRIORTO ROUGH-IN.

26.41UNDER BASE BID, PROVIDE CONDUIT AND PULL STRING FOR FUTURE FOUNTAIN PUMP. UNDER ALTERNATE BID #3,PROVIDE CONNECTION FOR FOUNTAIN PUMP (LOCATED IN ABOVE GROUND EQUIPMENT ENCLOSURE). COORDINATEEXACT LOCATION WITH LANDSCAPING CONTRACTOR PRIOR TO ROUGH-IN.

26.42UNDER BASE BID, PROVIDE CONDUIT AND PULL STRING FOR FUTURE SPLASH PAD CONTROL BOLLARD AND CENTERJET WITH INTEGRAL LIGHT, AND TERMINATE IN BELOW-GRADE BOXES. UNDER ALTERNATE BID #3, CONNECTFOUNTAIN CONTROL BOLLARD AND CENTER JET INTEGRAL LIGHT TO SPLASH PAD CONTROL BOX PER LANDSCAPINGPLANS. REFER TO SPLASH PAD GROUNDING DETAIL ON SHEET E504.

26.49 THIS FIXTURE SERVES AS EMERGENCY EGRESS FOR THIS BUILDING EXIT. ROUTE POWER THROUGH MINI-INVERTERMOUNTED ABOVE ACCESSIBLE CEILING JUST INSIDE DOOR. SEE LIGHTING PLAN.

26.50 PROVIDE SOLAR POWERED FLAG LIGHT ON TOP OF RELOCATED FLAG POLE.

26.55 NEW 4" FIBER CONDUIT AND PULL STRING, 2" CONDUIT AND PULL STRING FOR TELEPHONE TWISTED PAIR CABLING,AND 2" SPARE CONDUIT AND PULL STRING. NEW FIBER AND TELEPHONE TERMINATION OUTSIDE SCOPE OF WORK.

26.88 PROVIDE NEW 2" CONDUIT AND PULL STRING FOR TELEPHONE.

26.90

THIS EQUIPMENT IS BEING REPLACED, OR A VFD ADDED TO IT, BY AN ENERGY MANAGEMENT CONTRACTOR (E.C.I.)UNDER SEPARATE CONTRACT WITH THE CITY. THIS WORK IS ANTICIPATED TO BE COMPLETED BEFORE THEBEGINNING OF CONSTRUCTION FOR THIS PROJECT. EQUIPMENT INFORMATION SHOWN HERE, AND ON EQUIPMENTCONNECTION SCHEDULE, IS PER E.C.I. AND COULD NOT BE VERIFIED DURING DESIGN. CONFIRM ELECTRICALREQUIREMENTS PRIOR TO RECONNECTING EQUIPMENT TO NEW PANELS, AND REPORT ANY DISCREPANCIES TOENGINEER FOR FURTHER INSTRUCTIONS.

26.94EXISTING TREE SCULPTURE TO BE RELOCATED HERE. SCULPTURE ORIGINALLY HAD INTERNAL FLUORESCENTLIGHTING. IN THIS PROJECT, REPLACE INTERNAL FIXTURE WITH NEW LED AND RECONNECT. FOR BIDDING PURPOSES,INCLUDE AN ALLOWANCE OF $1000 TO COVER LABOR AND MATERIALS FOR THIS FIXTURE.

GENERAL ELEC. SITE PLAN NOTES1 REFER TO POLE BASE ELECTRICAL DETAIL, SHEET E504, FOR WIRING AND GROUNDING WITHIN POLE BASES.

2 REFER TO SITE CIRCUIT CONDUCTOR SCHEDULE, SHEET E504, FOR WIRE SIZES REQUIRED TO MITIGATEVOLTAGE DROP ON EACH CIRCUIT.

3 SEE THEATER DRAWINGS, PERFORMANCE LIGHTING DRAWINGS, AND AUDIO-VISUAL SYSTEM DRAWINGS FORADDITIONAL ELECTRICAL REQUIREMENTS NOT SHOWN ON POWER OR LIGHTING SHEETS.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

1

1

1

Page 17: Request For Qualifications-Based Proposals for ...

S

S

S

S

S

S

S

S

S

S

DD

DD

3

3

3

D

D

DD D D

LC.06

LC.01

LC.01

LC.03

LC.03

LC.03

LC.03

LC.02LC.02

LC.02

LC.02

LC.04

LC.04

LC.04

LC.04

LC.04

LC.04LC.04

LC.04

LC.04

LC.04

LC.05

LC.05

LC.05

LC.04

LC.06

LC.06

LC.06

LC.06

LC.06

LC.06

LC.02

LC.02

LC.05

LC.04

LC.04

3

EL102A3EL102A3

J2

PANEL B

PANEL L

PANEL A

PANEL AC

PANEL MDP1

MECHE113

JANE120

RESTROOME119

VESTE117

WOMENE118

VESTE107

MENE108

STOR 2E103

ELECE102

TICKETSE104

RESTROOME136

WOMENE134

MENE133

STORAGE 1E131

SERVER RME132

ELECE124

OFFICE 1E138

OFFICE 2E139

RECEPE137

MEETING #1E106

KIT STORE116

KITCHENE114

ENTRYE100

CORRIDOR #2E101

STOR 5E125

STOR 4E122

CORRIDOR #1E105

MEETING #2E109

STORAGE 3E110

VESTE123

EXHIBIT HALL #1E121

STORAGE 1E131

STOR 5E125

CORR #3E135

EXHIBIT HALL #1E121

CORR #3E135

J3, a

J3, a

J3, a

J3, a

J3, a

J3, a

J3, b

J3, b

J3, b

J3, b

J3, b J3, b J3, b

J3, b

J3, b

G2 G2

G2G2

G2 G2E

G2 G2

G2G2

G2 G2

G2EG2

G2G2

G2 G2

G2G2

G2E

G2G2

G2

G2 G2 G2 G2

G2 G2 G2 G2

EX

ab

CLOSETE111

FREEZER(INTEGRAL LIGHTING)

G1G1G1

K

K

K

K

KE

K

KE

K K

KE

K

K KE

H2EH2

H2

H2

H2

H2 H2

H2H2

J2E

J2J2

J2 J2 J2E J2 J2E J2

J2

J2E

J2

J2E

J2

J2E F4

H2F4 F4 F4 J1E

J1 J1E J1 J1J1

F4 F4 F4

J1

J1

J1

J1E

J1

J1E

ab

J3, aJ3, bJ3, b

J3, b J3, b J3, a

J3, b J3, b J3, a

H2

H2

G1G1G1

G1

G1

G1

J1S

J3F

J2

J2E J2

J2 J2E

J2 J2

J2 J2

J2E

abJ3, bJ3, b

J3, a

J3, b

J3, a J3E, a

J3 J3

J3 J3

J3

J3

J3

J3

F2

F4 F4 F4

J1E

J1 J1J1

F4 F4 F4

J1J1

J1E

J1

J2

J2E

J2

J2E

J2E

J2

H2H2H2

H2H2H2EH2

H2H2H2

T

T

T

J1

INV-1

W

WE

W

WE

G1

G1

G1

G1 G1G1G1

G1

G1

G1

EXR

ER

26.56

H2

H2E

H2

EXR

26.7526.75

PANEL K

G1

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

X76.P

H1E

H1

H1

H1E

H1

H1

H2

H1

H1

H2E

H2

26.96

26.95

EXISTING CORRIDOR CKT

EXISTING STORAGE E131 LTG CKT

STORAGE 1E131

STOR 5E125

EXEX

EX

EX

EX

EX

EX EX

EXISTING CONTROLS FOR THESE TWO ROOM SECTIONS TO BE COMBINED BY

MODIFYING CONTROL PANEL PROGRAMMING.SEE SHEETS EL102 AND E503.

1

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/24/2

017 3

:08:30

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EL101

ELECTRICALLIGHTING PLAN -EXHIBIT HALL

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

N 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - EXHIBIT HALLA1

KEYED NOTES26.56 EXISTING LIGHTING TO BE RELOCATED AND RECONNECTED. COORDINATE EXACT

LOCATION WITH THEATRE SYSTEMS DRAWINGS.

26.75RECEPTACLES AND DATA FOR RECEPTION AREA REMODEL ARE PART OF ALTERNATE BID#4. NEW LIGHTING AND FIRE PROTECTION ARE PART OF BASE BID. IF ALTERNATE BID IS NOTTAKEN, CHANGE LIGHTING FROM TWO DIMMING ZONES TO A SINGLE DIMMING ZONE.

26.95 APPROXIMATE LOCATION FOR TOUCHSCREEN LIGHTING CONTROL STATION. COORDINATEEXACT LOCATION WITH OWNER. REFER TO LIGHTING CONTROL DETAIL ON SHEET E503.

26.96 APPROXIMATE LOCATION FOR CENTRAL LIGHTING CONTROL PANEL. COORDINATE EXACTLOCATION WITH OWNER. REFER TO LIGHTING CONTROL DETAIL ON SHEET E503.

NOTES:

1. All lighting control products shall be same manufacturer. Exceptions must be requested in writing.

2. Pre-approved manufacturers are Wattstopper, Eaton/Greengate, and Acuity/NLight. Others must be pre-approvedprior to bidding (see specifications for prior approval request deadline).

3. All occupancy sensors shall be dual technology, ceiling or corner mounted, unless noted otherwise below.

4. Occupancy sensor layout is not shown on drawings due to variation in sensing range between manufacturers.Where occupancy sensing is indicated for a space, provide quantity of sensors required for complete coverage (minoror major motion as indicated below) based on sensing range of the proposed product line. Provide device layout onfloorplan in submittal package.

LIGHTING CONTROL SCENARIO LEGEND

APPLIES TO DESCRIPTION COVERAGE CONTROLZONES

MANUALDIMMING

MANUALSWITCHING

OCCUPANCYSENSING

SCHEDULEDON/OFF

DAYLIGHTSENSING

LC.01 MEETING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE MANUAL ON / AUTO OFF.

MINORMOTION 2 Yes Yes Yes No No

LC.02 OFFICES, DRESSING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALDIMMING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MINORMOTION 1 Yes Yes Yes No No

LC.03 MULTI-OCCUPANTRESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE AUTO ON / AUTO OFF. PROVIDE MANUAL SWITCH AT ENTRANCE FOR SENSOR OVERRIDE.

MAJORMOTION 1 No Yes Yes No No

LC.04 STORAGE, UTILITY, SINGLEOCCUPANT RESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALSWITCHING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MAJORMOTION 1 No Yes Yes No No

LC.05ELEC, MECH ROOMS,KITCHENS, THEATER

CONTROL BOOTHCONTROL BY LOCAL DEVICES ONLY. MANUAL SWITCHING ONLY. AUTOMATIC SHUTOFF NOT PROVIDED DUE TOSAFETY RISK. N/A 1 No Yes No No No

LC.06 CORRIDORS, LOBBIES

PROVIDE POWER PACKS ABOVE CEILING IN EXISTING CIRCUITS. CONNECT POWER PACKS AND NEWOCCUPANCY SENSORS TO CENTRAL CONTROL PANEL VIA CAT5. CORRIDOR LIGHTING SHALL BE ONCONTINUOUSLY DURING SCHEDULED BUILDING HOURS, AND BE CONTROLLED BY OCCUPANCY SENSORS ATALL OTHER TIMES (AUTO ON / AUTO OFF). MANUAL SWITCH ADJACENT TO PANEL SHALL PROVDE MANUALOVERRIDE OF SCHEDULE. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

MAJORMOTION

SEEDETAIL No Yes Yes Yes No

LC.07 EXHIBIT HALLSIX EXISTING SECTIONS ARE CONTROLLED BY AN EXISTING GE CONTROL SYSTEM IN ELEC 124. TIE THE TWONEW SECTIONS INTO EXISTING SYSTEM. DEVICES IN THIS ROOM DO NOT NEED TO BE THE SAMEMANUFACTURER AS THE REST OF THE BUILDING, INSTEAD MATCH THE EXISTING DEVICES AS CLOSELY ASPOSSIBLE. SEE "EXHIBIT HALL LIGHTING CONTROL DETAIL" ON E503 FOR DETAILS.

N/A SEEDETAIL Yes Yes No No No

LC.08 THEATER SEATINGNORMAL OVERHEAD LIGHTING IN THEATER HOUSE SHALL BE CONTROLLED BY THEATRICAL SYSTEM(ELECTRICAL CONTRACTOR RESPONSIBLE FOR CONDUIT PATHS, SEE PLAN KEYED NOTES, AND ET SHEETS FORDETAIL). EMERGENCY LIGHTING AND BACKSTAGE WORK/EGRESS LIGHTING SHALL BE CONTROLLED PER"THEATER EMERGENCY LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL No Yes No No No

LC.09 EXTERIOR

ALL EXTERIOR LIGHTING SHALL BE SWITCHED BY CENTRAL CONTROL PANEL, POLE AND TRELLIS LIGHTINGSHALL BE DIMMED BY CENTRAL CONTROL PANEL. CERTAIN EXTERIOR RECEPTACLES DESIGNATED FORHOLIDAY LIGHTING SHALL ALSO BE SWITCHED BY CENTRAL CONTROL PANEL. CENTRAL PHOTOCELL ON ROOFSHALL SWITCH OFF ALL EXTERIOR LIGHTING DURING DAYLIGHT HOURS. DURING NIGHTTIME HOURS, LIGHTINGSHALL BE SWITCHED ON A PROGRAMMABLE SHCHEDULE AND OVERRIDDEN FOR EVENTS BY MANUALCONTROLS. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL Yes Yes No Yes Yes

GENERAL LIGHTING NOTES1

UNLESS OTHERWISE NOTED, ALL NEW LIGHT FIXTURES REPLACE EXISTING IN SAME ORSIMILAR LOCATIONS. RECONNECT TO EXISTING CIRCUITS. UNLESS OTHERWISE NOTED INLIGHT FIXTURE SCHEDULE, NEW LED FIXTURES HAVE UNIVERSAL VOLTAGE DRIVERS FORUSE WITH 120V OR 277V AS NEEDED.

2NEW LIGHTING CONTROL DEVICES ARE NOT SHOWN ON PLAN, EXCEPT TO INDICATESWITCH LOCATIONS. REFER TO LIGHTING CONTROL SCENRIO LEGEND FOR REQUIREDDEVICES IN EACH SPACE. EXACT QUANTITY AND LOCATION OF SENSORS, POWER PACKS,ETC, SHALL BE DETERMINED BY CONTROLS SUPPLIER AND SHOWN IN SHOP DRAWINGS.

3REFER TO LIGHTING CONTROL DETAILS AND SCHEDULES ON SHEET E503 FORINFORMATION ON WHICH CIRCUITS WILL BE CONTROLLED BY CENTRAL CONTROL SYSTEMS,AND HOW THEY ARE CONNECTED.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

Page 18: Request For Qualifications-Based Proposals for ...

P

NLC.07LC.07

D

LC.04

LC.04

LC.04

LC.06

LC.06

LC.06

LC.04

P

D

N

P

N

N

EL101A1EL101A1

C3

B

C1

D

A

D

C1

C2

B

B B B

J2E

H2 H2E

H2H2

H2 H2

H2H2

H2 H2

J2E

J2

SERVER RME132

STORAGEE130

CORR #4E129

EXHIBIT HALL #2E126

STORAGEE130

CORR #4E129

VESTE128

STOR 5E127

EXHIBIT HALL #1E121

H2EH2 H2EH2

J2E

J2

J2E

J2

J2J2EJ2

J2E H2H2H2

H2H2H2

BB

26.46

26.46

A

B

WE

WE

W

EX2

EX2EX2

EX2

H1

H1

H1

EXHIBIT HALL"ROOM 7"

EXHIBIT HALL"ROOM 6"

A/V

A/V

26.46

26.46

26.46

26.46

26.46

EX

EXISTING CORRIDOR CKT

EXISTING STORAGE E131 LTG CKT

STORAGE 1E131

STOR 5E125

EXISTING STORAGE E125 LTG CKT

EXISTING WALLPACK LTG CKT

L - 26

AC - 23

AC - 27

L - 30AC - 27

L - 30

L - 30

L - 30 L - 31

L - 31 L - 31

L - 31

L - 28

AC - 21

AC - 25

AC - 25

EX

EX

"ROOM 5" "ROOM 4"

NEW"ROOM 2"

"ROOM 1"

PARTITION PARTITION

PARTITION PARTITION

PAR

TITI

ON

NEW

PAR

TITI

ON

NEW PARTITION NEW PARTITION

NEW"ROOM 6"

NEW"ROOM 3"

(COMBINE ZONES OF EXISTING ROOMS 2 AND 3)

"ROOM 5" "ROOM 4"

"ROOM 2" "ROOM 3"

"ROOM 1"

PARTITION PARTITION

PARTITION PARTITION

PAR

TITI

ON

PAR

TITI

ONTO

BE

REMO

VED

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:14:29

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EL102

ELECTRICALLIGHTING PLAN -EXHIBIT HALLADDITION

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

N 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - EXHIBIT HALL ADDITIONA3

KEYED NOTES

26.46

LOCATION FOR CONTROL STATIONS SPECIFIED IN EXHIBIT HALL LIGHTING CONTROLSYSTEM DETAIL, SHEET E503. SWITCHES MARKED 'N' REPRESENT THE NETWORKEDMULTI-BUTTON SWITCH. SWITCHES MARKED 'D' REPRESENT THE SEPARATEINCANDESCENT DIMMERS FOR THE CHANDELIERS. SWITCHES MARKED 'P' REPRESENT THEOPERABLE PARTITION SWITCHES. GROUP ALL SWITCHES NEATLY WITH AUDIO/VISUALCONTROL STATION WHERE APPLICABLE.

NOTES:

1. All lighting control products shall be same manufacturer. Exceptions must be requested in writing.

2. Pre-approved manufacturers are Wattstopper, Eaton/Greengate, and Acuity/NLight. Others must be pre-approvedprior to bidding (see specifications for prior approval request deadline).

3. All occupancy sensors shall be dual technology, ceiling or corner mounted, unless noted otherwise below.

4. Occupancy sensor layout is not shown on drawings due to variation in sensing range between manufacturers.Where occupancy sensing is indicated for a space, provide quantity of sensors required for complete coverage (minoror major motion as indicated below) based on sensing range of the proposed product line. Provide device layout onfloorplan in submittal package.

LIGHTING CONTROL SCENARIO LEGEND

APPLIES TO DESCRIPTION COVERAGE CONTROLZONES

MANUALDIMMING

MANUALSWITCHING

OCCUPANCYSENSING

SCHEDULEDON/OFF

DAYLIGHTSENSING

LC.01 MEETING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE MANUAL ON / AUTO OFF.

MINORMOTION 2 Yes Yes Yes No No

LC.02 OFFICES, DRESSING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALDIMMING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MINORMOTION 1 Yes Yes Yes No No

LC.03 MULTI-OCCUPANTRESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE AUTO ON / AUTO OFF. PROVIDE MANUAL SWITCH AT ENTRANCE FOR SENSOR OVERRIDE.

MAJORMOTION 1 No Yes Yes No No

LC.04 STORAGE, UTILITY, SINGLEOCCUPANT RESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALSWITCHING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MAJORMOTION 1 No Yes Yes No No

LC.05ELEC, MECH ROOMS,KITCHENS, THEATER

CONTROL BOOTHCONTROL BY LOCAL DEVICES ONLY. MANUAL SWITCHING ONLY. AUTOMATIC SHUTOFF NOT PROVIDED DUE TOSAFETY RISK. N/A 1 No Yes No No No

LC.06 CORRIDORS, LOBBIES

PROVIDE POWER PACKS ABOVE CEILING IN EXISTING CIRCUITS. CONNECT POWER PACKS AND NEWOCCUPANCY SENSORS TO CENTRAL CONTROL PANEL VIA CAT5. CORRIDOR LIGHTING SHALL BE ONCONTINUOUSLY DURING SCHEDULED BUILDING HOURS, AND BE CONTROLLED BY OCCUPANCY SENSORS ATALL OTHER TIMES (AUTO ON / AUTO OFF). MANUAL SWITCH ADJACENT TO PANEL SHALL PROVDE MANUALOVERRIDE OF SCHEDULE. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

MAJORMOTION

SEEDETAIL No Yes Yes Yes No

LC.07 EXHIBIT HALLSIX EXISTING SECTIONS ARE CONTROLLED BY AN EXISTING GE CONTROL SYSTEM IN ELEC 124. TIE THE TWONEW SECTIONS INTO EXISTING SYSTEM. DEVICES IN THIS ROOM DO NOT NEED TO BE THE SAMEMANUFACTURER AS THE REST OF THE BUILDING, INSTEAD MATCH THE EXISTING DEVICES AS CLOSELY ASPOSSIBLE. SEE "EXHIBIT HALL LIGHTING CONTROL DETAIL" ON E503 FOR DETAILS.

N/A SEEDETAIL Yes Yes No No No

LC.08 THEATER SEATINGNORMAL OVERHEAD LIGHTING IN THEATER HOUSE SHALL BE CONTROLLED BY THEATRICAL SYSTEM(ELECTRICAL CONTRACTOR RESPONSIBLE FOR CONDUIT PATHS, SEE PLAN KEYED NOTES, AND ET SHEETS FORDETAIL). EMERGENCY LIGHTING AND BACKSTAGE WORK/EGRESS LIGHTING SHALL BE CONTROLLED PER"THEATER EMERGENCY LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL No Yes No No No

LC.09 EXTERIOR

ALL EXTERIOR LIGHTING SHALL BE SWITCHED BY CENTRAL CONTROL PANEL, POLE AND TRELLIS LIGHTINGSHALL BE DIMMED BY CENTRAL CONTROL PANEL. CERTAIN EXTERIOR RECEPTACLES DESIGNATED FORHOLIDAY LIGHTING SHALL ALSO BE SWITCHED BY CENTRAL CONTROL PANEL. CENTRAL PHOTOCELL ON ROOFSHALL SWITCH OFF ALL EXTERIOR LIGHTING DURING DAYLIGHT HOURS. DURING NIGHTTIME HOURS, LIGHTINGSHALL BE SWITCHED ON A PROGRAMMABLE SHCHEDULE AND OVERRIDDEN FOR EVENTS BY MANUALCONTROLS. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL Yes Yes No Yes Yes

GENERAL LIGHTING NOTES1

UNLESS OTHERWISE NOTED, ALL NEW LIGHT FIXTURES REPLACE EXISTING IN SAME ORSIMILAR LOCATIONS. RECONNECT TO EXISTING CIRCUITS. UNLESS OTHERWISE NOTED INLIGHT FIXTURE SCHEDULE, NEW LED FIXTURES HAVE UNIVERSAL VOLTAGE DRIVERS FORUSE WITH 120V OR 277V AS NEEDED.

2NEW LIGHTING CONTROL DEVICES ARE NOT SHOWN ON PLAN, EXCEPT TO INDICATESWITCH LOCATIONS. REFER TO LIGHTING CONTROL SCENRIO LEGEND FOR REQUIREDDEVICES IN EACH SPACE. EXACT QUANTITY AND LOCATION OF SENSORS, POWER PACKS,ETC, SHALL BE DETERMINED BY CONTROLS SUPPLIER AND SHOWN IN SHOP DRAWINGS.

3REFER TO LIGHTING CONTROL DETAILS AND SCHEDULES ON SHEET E503 FORINFORMATION ON WHICH CIRCUITS WILL BE CONTROLLED BY CENTRAL CONTROL SYSTEMS,AND HOW THEY ARE CONNECTED.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

N 1/16" = 1'-0"

Lighting Control Zoning Detail - NewA2N 1/16" = 1'-0"

Lighting Control Zoning Detail - ExistingA1

1

Page 19: Request For Qualifications-Based Proposals for ...

LC.05

LC.05

LC.05

LC.05

LC.05

LC.05

LC.05

PANEL SDP

PANEL HPA

EX MECH RMT005

EX BOILER ROOMT006

EX EQUIP ROOMT002

EX STAIR FOYERT001

EX LIFT PITT004

EX STORAGET003

H2E

H2H2E

H2E

H2

H2

H2

H2E

H2

H2

H2

H2

H2

H2

H2

H2

H2

H2

H2E

H2E

H2

H2

H2

H2

H2

H2

H2E

H2H2

H2

H2

H2

H2E

H2E

H2

H2E

H2E

H2

H2E

H2

H2

H2E

H2

26.40

26.40

26.40

26.40

EX

EX

EX

EX

EX

EX

EX

PANEL LADPANEL AV

NEW AUDIORACK

1

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:14:35

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EL103

ELECTRICALLIGHTING PLAN -THEATER -BASEMENT

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

N 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - THEATER - BASEMENTA1

KEYED NOTES26.40 THROUGHOUT THEATER BASEMENT, ALL EXISTING MANUAL LIGHT SWITCHES ARE TO

REMAIN (NOT SHOWN). REPLACE ALL FIXTURES IN SAME LOCATIONS.

NOTES:

1. All lighting control products shall be same manufacturer. Exceptions must be requested in writing.

2. Pre-approved manufacturers are Wattstopper, Eaton/Greengate, and Acuity/NLight. Others must be pre-approvedprior to bidding (see specifications for prior approval request deadline).

3. All occupancy sensors shall be dual technology, ceiling or corner mounted, unless noted otherwise below.

4. Occupancy sensor layout is not shown on drawings due to variation in sensing range between manufacturers.Where occupancy sensing is indicated for a space, provide quantity of sensors required for complete coverage (minoror major motion as indicated below) based on sensing range of the proposed product line. Provide device layout onfloorplan in submittal package.

LIGHTING CONTROL SCENARIO LEGEND

APPLIES TO DESCRIPTION COVERAGE CONTROLZONES

MANUALDIMMING

MANUALSWITCHING

OCCUPANCYSENSING

SCHEDULEDON/OFF

DAYLIGHTSENSING

LC.01 MEETING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE MANUAL ON / AUTO OFF.

MINORMOTION 2 Yes Yes Yes No No

LC.02 OFFICES, DRESSING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALDIMMING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MINORMOTION 1 Yes Yes Yes No No

LC.03 MULTI-OCCUPANTRESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE AUTO ON / AUTO OFF. PROVIDE MANUAL SWITCH AT ENTRANCE FOR SENSOR OVERRIDE.

MAJORMOTION 1 No Yes Yes No No

LC.04 STORAGE, UTILITY, SINGLEOCCUPANT RESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALSWITCHING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MAJORMOTION 1 No Yes Yes No No

LC.05ELEC, MECH ROOMS,KITCHENS, THEATER

CONTROL BOOTHCONTROL BY LOCAL DEVICES ONLY. MANUAL SWITCHING ONLY. AUTOMATIC SHUTOFF NOT PROVIDED DUE TOSAFETY RISK. N/A 1 No Yes No No No

LC.06 CORRIDORS, LOBBIES

PROVIDE POWER PACKS ABOVE CEILING IN EXISTING CIRCUITS. CONNECT POWER PACKS AND NEWOCCUPANCY SENSORS TO CENTRAL CONTROL PANEL VIA CAT5. CORRIDOR LIGHTING SHALL BE ONCONTINUOUSLY DURING SCHEDULED BUILDING HOURS, AND BE CONTROLLED BY OCCUPANCY SENSORS ATALL OTHER TIMES (AUTO ON / AUTO OFF). MANUAL SWITCH ADJACENT TO PANEL SHALL PROVDE MANUALOVERRIDE OF SCHEDULE. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

MAJORMOTION

SEEDETAIL No Yes Yes Yes No

LC.07 EXHIBIT HALLSIX EXISTING SECTIONS ARE CONTROLLED BY AN EXISTING GE CONTROL SYSTEM IN ELEC 124. TIE THE TWONEW SECTIONS INTO EXISTING SYSTEM. DEVICES IN THIS ROOM DO NOT NEED TO BE THE SAMEMANUFACTURER AS THE REST OF THE BUILDING, INSTEAD MATCH THE EXISTING DEVICES AS CLOSELY ASPOSSIBLE. SEE "EXHIBIT HALL LIGHTING CONTROL DETAIL" ON E503 FOR DETAILS.

N/A SEEDETAIL Yes Yes No No No

LC.08 THEATER SEATINGNORMAL OVERHEAD LIGHTING IN THEATER HOUSE SHALL BE CONTROLLED BY THEATRICAL SYSTEM(ELECTRICAL CONTRACTOR RESPONSIBLE FOR CONDUIT PATHS, SEE PLAN KEYED NOTES, AND ET SHEETS FORDETAIL). EMERGENCY LIGHTING AND BACKSTAGE WORK/EGRESS LIGHTING SHALL BE CONTROLLED PER"THEATER EMERGENCY LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL No Yes No No No

LC.09 EXTERIOR

ALL EXTERIOR LIGHTING SHALL BE SWITCHED BY CENTRAL CONTROL PANEL, POLE AND TRELLIS LIGHTINGSHALL BE DIMMED BY CENTRAL CONTROL PANEL. CERTAIN EXTERIOR RECEPTACLES DESIGNATED FORHOLIDAY LIGHTING SHALL ALSO BE SWITCHED BY CENTRAL CONTROL PANEL. CENTRAL PHOTOCELL ON ROOFSHALL SWITCH OFF ALL EXTERIOR LIGHTING DURING DAYLIGHT HOURS. DURING NIGHTTIME HOURS, LIGHTINGSHALL BE SWITCHED ON A PROGRAMMABLE SHCHEDULE AND OVERRIDDEN FOR EVENTS BY MANUALCONTROLS. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL Yes Yes No Yes Yes

GENERAL LIGHTING NOTES1

UNLESS OTHERWISE NOTED, ALL NEW LIGHT FIXTURES REPLACE EXISTING IN SAME ORSIMILAR LOCATIONS. RECONNECT TO EXISTING CIRCUITS. UNLESS OTHERWISE NOTED INLIGHT FIXTURE SCHEDULE, NEW LED FIXTURES HAVE UNIVERSAL VOLTAGE DRIVERS FORUSE WITH 120V OR 277V AS NEEDED.

2NEW LIGHTING CONTROL DEVICES ARE NOT SHOWN ON PLAN, EXCEPT TO INDICATESWITCH LOCATIONS. REFER TO LIGHTING CONTROL SCENRIO LEGEND FOR REQUIREDDEVICES IN EACH SPACE. EXACT QUANTITY AND LOCATION OF SENSORS, POWER PACKS,ETC, SHALL BE DETERMINED BY CONTROLS SUPPLIER AND SHOWN IN SHOP DRAWINGS.

3REFER TO LIGHTING CONTROL DETAILS AND SCHEDULES ON SHEET E503 FORINFORMATION ON WHICH CIRCUITS WILL BE CONTROLLED BY CENTRAL CONTROL SYSTEMS,AND HOW THEY ARE CONNECTED.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

Page 20: Request For Qualifications-Based Proposals for ...

D3

3

3

3

D

N

D

3

D

3 3

DD

ND

D

D

D

D

3 3

D

N

LC.01

LC.02

LC.02

LC.02

LC.02

LC.02

LC.03

LC.03

LC.05

LC.04

LC.04

LC.05

LC.06

LC.08

LC.06LC.06

LC.06

LC.06

LC.06

LC.02

LC.03 LC.03

LC.06

LC.08

LC.08

LC.08

LC.06

LC.06

LC.06

LC.02 LC.02

LC.02

LC.02

P

P

P

P

P

P

P

P PP

P

P

P

X74.B1

PANEL LAC

PANEL LAB

PANEL LAA

ENTRYE100

VESTT101

WOMENT103

MENT113

WOMEN'S DRESST123

WOMENT124

MEN'S DRESST126

MENT127

BOARD RMT122

MAKE-UPT125

STAGET116

AUDITORIUMT115

JANT114

JANT104

PRIVATE DRESST121

PRIVATE DRESST120 JAN

T119

PRIVATE DRESST118

CORRIDORT117

S STAIRT105

W STAIRT112

LOBBYT100

CORRIDORT102

STORAGE 1T109

TECHNICALT110

SUPERVISORST108

STORAGE 2T107

OFFICE 3T106

X74.B1

X74.B1

X74.B1

X74.B1

X74.B1

J2

J2E

J2

J2

J2

F4

F4

H2

J4

J4

H2

H2

J4

J4

J4

J4

H2

H2

J4

J4E

H2

U

U

U

U

UU

U U

J2

EXL

EXR

EXR

EX EXL

EXL

EXL

EX EX

EXLR

J4, a

J4, a

J4, a

J4, a

J4, b

J4, b

J4, b

J4, b

J4, b

J4, b

J4, b

J4, b

J4

J4

J4E J4

J4

J4

J4E

J4

J4

J4

J4

J4 J4

J4 J4

J4E

J4 J4

J4

J4

J4J4

J2E J2 J2E J2 J2E

J2

J2E

J2

J2E

J2

J1

J2E

J2

J2E

J2E

J2

J2EJ2E J2 J2E

J2E

J2

J2E

F4

F4

F4

F4F4F4

J1J1J1J1E

J1

J1

J1

J1E

J1

F2

J1E

F2J1J1E

ab

T T T T T

T

T

T

T

T

CORRIDORLIGHTING

CONTROLSSEE E503

T

T

T26.45

J2EJ2 J2

G1

G1

G1

G1

G1G1

G1

ER

EXR

G1ER

W

INV-1

ER

TO BOLLARDS(OR TRELLIS FIXTURES)

SEE SITE PLAN

EX

ER

EX

J2E

J2

G1G1

G1

J2

J2

G1

G1

G1 G1

O-W

W

W

VESTT128

HWE

26.59

N N

N N

N N

N N

26.8226.82

N

N N

N

N

N

N

N

TYP

N

EX

EX

PANEL LAH

EM LTGCNTRL

26.29

STAGET116

AUDITORIUMT115

R26

R26

R26

R26

Q3

Q3

Q3

Q3

R24

R24

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4

S4S4S4S4S4S4S4S4S4S4S4S4S4

R22

R22

Q3

Q3

Q3Q3

R24

R41

R24

R22

R22

S4

R22

S4

S4

S4

S4

S4

S4

S4S4

S4S4

S4S4

W STAIRT202

S STAIRT200

CORRIDORT201

CORRIDORT201

CRL BOOTH 2T206

MIXING BOOTHT205

CRL BOOTH 1T204

Q3

Q3

Q3

Q3

26.9926.99

26.99

26.99

26.99

26.9926.99

26.99

26.9926.99

26.99

S4

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

Q1

R22

S4

Q3

Q3

Q1Q1 Q1 Q1 Q1 Q1

Q1 Q1 Q1 Q1 Q1 Q1 Q1

Q1

IN HALL BELOW

IN HALL BELOW

IN HALL BELOW

IN HALL BELOW

DASHED LINES INDICATE SURFACE MOUNTED WIREWAY AVAILABLE AS ACCESSORY TO FIXTURES(TYPICAL, THIS PLAN)

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:35:26

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EL104

ELECTRICALLIGHTING PLAN -THEATER - GROUNDFLOOR

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW

AW

N 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - THEATER - GROUND FLOORA1

KEYED NOTES26.29 COORDINATE LOCATION OF ALL BACKSTAGE ELECTRICAL EQUIPMENT WITH THEATER

CONTRACTOR PRIOR TO ROUGH-IN. PAINT EQUIPMENT BLACK.

26.45ON BOTTOM OF STAIR LANDING, PROVIDE NEW SURFACE MOUNTED TRACK FOR ARTDISPLAY. SUPPLY FROM NEAREST EXISTING TRACK LIGHTING CIRCUIT. SPRINKLER PIPINGMUST BE RUN TO THIS AREA ALSO; USE SURFACE MOUNTED CONDUIT, GROUP WITH NEWSURFACE PIPING, AND PAINT TO MATCH.

26.59IN ELEVATOR PIT, AT ACCESSIBLE LOCATION FOR MAINTENANCE, PROVIDE GFCIRECEPTACLE WITH WEATHERPROOF IN-USE COVER. CONNECT GFCI RECEPTACLE ANDPIT/SHAFT LIGHT FIXTURES TO A SINGLE DEDICATED CIRCUIT. DO NOT CONNECT LIGHTFIXTURES TO THE LOAD SIDE OF THE GFCI DEVICE.

26.82 COORDINATE WITH GC FOR MIRROR CUTS NECESSARY TO ACCOMMODATE WALL MOUNTEDMAKEUP LIGHTS.

26.99

PROPOSED LOCATION FOR 12V POWER SUPPLY FOR NEARBY AISLE FIXTURES. REPLACEEXISTING JUNCTION BOX AND SECURELY MOUNT POWER SUPPLY UNDER SEAT.ALTERNATELY, ANY OF THE OTHER EXISTING UNDER-SEAT JUNCTION BOXES MAY BE USED(FOR OTHER LOCATIONS, SEE DEMOLITION PLAN, KEYED NOTE 26.57). REUSE EXISTINGCIRCUITING (PANEL LAA PER ORIGINAL DRAWINGS, VERIFY). COORDINATE WITHTHEATERICAL SYSTEMS CONTRACTOR ON LOCATION FOR SWITCHING. TEST ALL CIRCUITSPRIOR TO REUSE AND REPORT ANY DEFICIENCIES TO ENGINEER.

N 1/8" = 1'-0"

ELECTRICAL LIGHTING PLAN - THEATER - FLOOR LEVELA4

NOTES:

1. All lighting control products shall be same manufacturer. Exceptions must be requested in writing.

2. Pre-approved manufacturers are Wattstopper, Eaton/Greengate, and Acuity/NLight. Others must be pre-approvedprior to bidding (see specifications for prior approval request deadline).

3. All occupancy sensors shall be dual technology, ceiling or corner mounted, unless noted otherwise below.

4. Occupancy sensor layout is not shown on drawings due to variation in sensing range between manufacturers.Where occupancy sensing is indicated for a space, provide quantity of sensors required for complete coverage (minoror major motion as indicated below) based on sensing range of the proposed product line. Provide device layout onfloorplan in submittal package.

LIGHTING CONTROL SCENARIO LEGEND

APPLIES TO DESCRIPTION COVERAGE CONTROLZONES

MANUALDIMMING

MANUALSWITCHING

OCCUPANCYSENSING

SCHEDULEDON/OFF

DAYLIGHTSENSING

LC.01 MEETING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE MANUAL ON / AUTO OFF.

MINORMOTION 2 Yes Yes Yes No No

LC.02 OFFICES, DRESSING ROOMS CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALDIMMING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MINORMOTION 1 Yes Yes Yes No No

LC.03 MULTI-OCCUPANTRESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE ROOM CONTROLLER ABOVE ACCESSIBLE CEILING. SENSORCONTROL SHALL BE AUTO ON / AUTO OFF. PROVIDE MANUAL SWITCH AT ENTRANCE FOR SENSOR OVERRIDE.

MAJORMOTION 1 No Yes Yes No No

LC.04 STORAGE, UTILITY, SINGLEOCCUPANT RESTROOMS

CONTROL BY LOCAL DEVICES ONLY. PROVIDE WALLBOX OCCUPANCY SENSOR WITH INTEGRAL MANUALSWITCHING. SENSOR CONTROL SHALL BE AUTO ON / AUTO OFF.

MAJORMOTION 1 No Yes Yes No No

LC.05ELEC, MECH ROOMS,KITCHENS, THEATER

CONTROL BOOTHCONTROL BY LOCAL DEVICES ONLY. MANUAL SWITCHING ONLY. AUTOMATIC SHUTOFF NOT PROVIDED DUE TOSAFETY RISK. N/A 1 No Yes No No No

LC.06 CORRIDORS, LOBBIES

PROVIDE POWER PACKS ABOVE CEILING IN EXISTING CIRCUITS. CONNECT POWER PACKS AND NEWOCCUPANCY SENSORS TO CENTRAL CONTROL PANEL VIA CAT5. CORRIDOR LIGHTING SHALL BE ONCONTINUOUSLY DURING SCHEDULED BUILDING HOURS, AND BE CONTROLLED BY OCCUPANCY SENSORS ATALL OTHER TIMES (AUTO ON / AUTO OFF). MANUAL SWITCH ADJACENT TO PANEL SHALL PROVDE MANUALOVERRIDE OF SCHEDULE. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

MAJORMOTION

SEEDETAIL No Yes Yes Yes No

LC.07 EXHIBIT HALLSIX EXISTING SECTIONS ARE CONTROLLED BY AN EXISTING GE CONTROL SYSTEM IN ELEC 124. TIE THE TWONEW SECTIONS INTO EXISTING SYSTEM. DEVICES IN THIS ROOM DO NOT NEED TO BE THE SAMEMANUFACTURER AS THE REST OF THE BUILDING, INSTEAD MATCH THE EXISTING DEVICES AS CLOSELY ASPOSSIBLE. SEE "EXHIBIT HALL LIGHTING CONTROL DETAIL" ON E503 FOR DETAILS.

N/A SEEDETAIL Yes Yes No No No

LC.08 THEATER SEATINGNORMAL OVERHEAD LIGHTING IN THEATER HOUSE SHALL BE CONTROLLED BY THEATRICAL SYSTEM(ELECTRICAL CONTRACTOR RESPONSIBLE FOR CONDUIT PATHS, SEE PLAN KEYED NOTES, AND ET SHEETS FORDETAIL). EMERGENCY LIGHTING AND BACKSTAGE WORK/EGRESS LIGHTING SHALL BE CONTROLLED PER"THEATER EMERGENCY LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL No Yes No No No

LC.09 EXTERIOR

ALL EXTERIOR LIGHTING SHALL BE SWITCHED BY CENTRAL CONTROL PANEL, POLE AND TRELLIS LIGHTINGSHALL BE DIMMED BY CENTRAL CONTROL PANEL. CERTAIN EXTERIOR RECEPTACLES DESIGNATED FORHOLIDAY LIGHTING SHALL ALSO BE SWITCHED BY CENTRAL CONTROL PANEL. CENTRAL PHOTOCELL ON ROOFSHALL SWITCH OFF ALL EXTERIOR LIGHTING DURING DAYLIGHT HOURS. DURING NIGHTTIME HOURS, LIGHTINGSHALL BE SWITCHED ON A PROGRAMMABLE SHCHEDULE AND OVERRIDDEN FOR EVENTS BY MANUALCONTROLS. SEE "CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAM" ON SHEET E503.

N/A SEEDETAIL Yes Yes No Yes Yes

GENERAL LIGHTING NOTES1

UNLESS OTHERWISE NOTED, ALL NEW LIGHT FIXTURES REPLACE EXISTING IN SAME ORSIMILAR LOCATIONS. RECONNECT TO EXISTING CIRCUITS. UNLESS OTHERWISE NOTED INLIGHT FIXTURE SCHEDULE, NEW LED FIXTURES HAVE UNIVERSAL VOLTAGE DRIVERS FORUSE WITH 120V OR 277V AS NEEDED.

2NEW LIGHTING CONTROL DEVICES ARE NOT SHOWN ON PLAN, EXCEPT TO INDICATESWITCH LOCATIONS. REFER TO LIGHTING CONTROL SCENRIO LEGEND FOR REQUIREDDEVICES IN EACH SPACE. EXACT QUANTITY AND LOCATION OF SENSORS, POWER PACKS,ETC, SHALL BE DETERMINED BY CONTROLS SUPPLIER AND SHOWN IN SHOP DRAWINGS.

3REFER TO LIGHTING CONTROL DETAILS AND SCHEDULES ON SHEET E503 FORINFORMATION ON WHICH CIRCUITS WILL BE CONTROLLED BY CENTRAL CONTROL SYSTEMS,AND HOW THEY ARE CONNECTED.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

1

1

Page 21: Request For Qualifications-Based Proposals for ...

FV

FV

FV

FV

TWC

P

HD

FV

FV

FV

FV

PANEL LAE

STAGET116

MIXING BOOTHT205

CRL BOOTH 1T204

CRL BOOTH 2T206

W STAIRT202

S STAIRT200

CORRIDORT201

MEZZANINET203

LOBBYT100

MR

26.63

26.64

26.6626.66

26.67

26.76

Panel LAE

26.76

LAH - 9

26.76

LAH - 12

LAH -2,4,6

26.64

26.68

1

Panel LAE

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:33:17

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

EP105

ELEC.POWER & SPEC.SYS. PLAN - THEATER- MEZZANINE

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

N 1/8" = 1'-0"

ELECTRICAL POWER & SPECIAL SYSTEMS PLAN - THEATER - MEZZANINEA1

KEYED NOTES26.63

PROVIDE HEAT DETECTORS TO INITIATE ELEVATOR SHUTDOWN WITHIN 2FT OF EACHSPRINKLER HEAD IN ELEVATOR PIT, AND AT ELEVATOR DISCONNECT. HEAT DETECTORSSHALL HAVE BOTH A LOWER TEMPERATURE SETTING AND A HIGHER SENSITIVITY ASCOMPARED TO THE SPRINKLER HEADS, PER ASME A17.1-6.15.4. COORDINATE WITH FIREPROTECTION CONTRACTOR.

26.64PROVIDE SMOKE DETECTORS TO INITIATE ELEVATOR RECALL FUNCTION ADJACENT TOEACH SPRINKLER HEAD IN ELEVATOR PIT, AT ELEVATOR DISCONNECT, AND IN ELEVATORLOBBY ON EACH FLOOR. CONNECT TO ELEVATOR CONTROLLER. COORDINATE WITH FIREPROTECTION CONTRACTOR.

26.66REFER TO PERFORMANCE LIGHTING SHEETS FOR ELECTRICAL WORK RELATED TOREPLACEMENT OF EXISTING DISTRIBUTION STRIPS AND TERMINAL BOXES LOCATED INCATWALKS, ABOVE STAGE, AND AT STAGE LEVEL.

26.67MOTORIZED RIGGING SYSTEM PROVIDED BY THEATRICAL CONTRACTOR AND INSTALLED BYELECTRICAL CONTRACTOR. REFER TO PERFORMANCE LIGHTING SHEETS FOR LAYOUTDETAILS, AND REFER TO EQUIPMENT CONNECTION SCHEDULE FOR ELECTRICAL DETAILS.

26.68 COORDINATE EXACT LOCATION WITH THEATER CONSULTANT PRIOR TO ROUGH-IN.

26.76 PROVIDE 120V/20A BRANCH CIRCUIT(S) TO THIS LOCATION FOR THEATRICAL DEVICE. REFERTO PERFORMANCE LIGHTING DRAWINGS FOR DETAILS.

GENERAL ELECTRICAL PLAN...1

SEE THEATER DRAWINGS, PERFORMANCE LIGHTING DRAWINGS, AND AUDIO-VISUALSYSTEM DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS NOT SHOWN ON POWEROR LIGHTING SHEETS.

2ELECTRICAL CONTRACTOR RESPONSIBLE FOR TELEPHONE/DATA BACKBOXES ANDCONDUIT WITH PULL STRING TO ABOVE CEILING ONLY, UNLESS OTHERWISE NOTED.OWNER TO PROVIDE WIRING, TERMINATIONS, WALL PLATES, AND EQUIPMENT.

3REFER TO THEATER SYSTEMS (TS) AND AUDIO-VISUAL (AV) SHEETS FOR ADDITIONAL WORKBY ELECTRICAL CONTRACTOR. COORDINATE WITH THEATER AND AUDIO VISUAL SYSTEMSCONTRACTORS WHERE APPLICABLE.

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

Page 22: Request For Qualifications-Based Proposals for ...

CONTROL PANELAT MAIN OFFICE

CONTXFMR

LOW

VO

LTA

GE

IN

PU

TS

PROVIDE RECESSED CONTROL PANEL WITH CAPABILITY FOR 7 DAY PROGRAMMED SCHEDULES, HOLIDAY OVERRIDES, AND ASTRONOMICAL TIME CLOCK. SEE LIGHTING CONTROL PANEL CIRCUIT SCHEDULE FOR PROGRAMMING.

PROVIDE A TOUCHSCREEN CONTROL STATION IN THE MAIN RECEPTION AREA (COORDINATE EXACT LOCATION WITH OWNER). PROGRAM TOUCHSCREEN TO CONTROL CIRCUITS IN THE GROUPINGS SHOWN ON THE CENTRAL CONTROL SYSTEM CIRCUIT SCHEDULE. PROGRAM THREE PRE-SET DIMMING LEVELS FOR EACH DIMMING ZONE, LABELED HIGH-MEDIUM-LOW (PLUS AN OFF BUTTON).

INTERCEPT EXISTING CIRCUITS AT LOCATION OF EXISTING MANUAL SWITCHES (SEE PLAN). REMOVE SWITCHES AND PROVIDE CONTACTOR TO BE CONTROLLED BY CENTRAL PANEL. SURFACE MOUNT CONTACTOR ON WALL IN NON-PUBLIC AREA.

INTERCEPT EXISTING CIRCUIT AT LOCATION OF EXISTING MANUAL SWITCH (SEE PLAN). REMOVE SWITCHES AND PROVIDE POWER PACK TO BE CONTROLLED BY CENTRAL PANEL. LOCATE POWER PACK ABOVE NEAREST ACCESSIBLE CEILING (OR SURFACE MOUNT ON WALL IN NON-PUBLIC AREA).

PROVIDE PERMANENT WEATHERPROOF LABELS UNDER COVERS OF ALL RECEPTACES CONTROLLED BY THIS PANEL, READING "HOLIDAY LIGHTS".

INTERCEPT EXISTING CORRIDOR LIGHTING CIRCUITS AND INSTALL POWER PACKS ABOVE ACCESSIBLE CEILINGS (WALL MOUNTING ACCEPTABLE IN UTILITY ROOMS). CONNECT POWER PACKS TO CENTRAL PANEL. LABEL POWER PACKS AND NOTE LOCATIONS FOR AS-BUILT DRAWINGS.

PROVIDE WEATHERPROOF ENCLOSURE ADJACENT TO EACH OF 4 EXTERIOR PANELS. INSIDE ENCLOSURE, PROVIDE ONE POWERPACK FOR EACH CIRCUIT ON THAT PANEL LISTED IN CENTRAL CONTROL PANEL SCHEDULE. PROVIDE DIMMING POWER PACKS FOR CIRCUITS MARKED WITH DIMMING IN SCHEDULE. POWER PACKS CAN BE DAISY CHAINED WITH CAT5 INSIDE ENCLOSURE, AND GROUP CONNECTED TO MASTER PANEL WITH CAT5 FOR CENTRALIZED CONTROL OF ALL ZONES.

PROVIDE EXTERIOR SWITCH STATION WITH ON/OFF BUTTON FOR EACH CONTROL GROUP LISTED. SEE SITE PLAN, COORDINATE EXACT LOCATION TO BE NEATLY GROUPED WITH AUDIO CONTROL STATION.

CL.01

CL.02

CL.03

CL.04

CL.05

CL.06

CL.07

CL.08

CENTRAL LIGHTING CONTROL LEGEND:

CENTRAL LIGHTING CONTROL KEYED NOTES:

CL.01 NEW120V CIRCUIT

ROOFTOPPHOTOCELL

THEATER BLDG CORRIDOR LIGHTINGAND WALLPACKS(EXISTING CIRCUITS)

LV INPUT

EXISTINGCIRCUITS

CL.03( 9 ) POWER PACKS

EXHIBIT HALL CORRIDOR LIGHTINGAND WALLPACKS(EXISTING CIRCUITS)

LV INPUT

EXISTINGCIRCUITS

OCCUPANCY SENSORS IN THEATER BLDG GROUND LEVEL CORRIDORS (SINGLE ZONE)

SWITCH "Holiday Lights"

SWITCH "Center Poles"

SWITCH "Outer Poles"

SWITCH "Bollard Lights"

SWITCH "Trellis Lights"

SWITCH "Sculpture Lights"

OCCUPANCY SENSORS IN EXHIBIT BLDG CORRIDORS (SINGLE ZONE)

LOW

VO

LTA

GE

OU

TPU

TS

CL.03

CL.08

OCCUPANCY SENSORS IN THEATER BLDG MEZZANINE LEVEL CORRIDORS (SINGLE ZONE)

( 15 ) POWER PACKS

CL.06

CL.06

LV INPUT

NEW 120V CIRCUITS

CL.04 CL.05CL.07

CONTROLLED EXTERIOR CIRCUITS ON PANEL "LAG"(THEATER ROOF)

LV INPUT

NEW 120V CIRCUITS

CL.04 CL.05CL.07

CONTROLLED EXTERIOR CIRCUITS ON PANEL "LAF"(THEATER SITE)

POWER PACKS IN 3R ENCLOSURE

LV INPUT

NEW 120V CIRCUITS

CL.04 CL.05CL.07

CONTROLLED EXTERIOR CIRCUITS ON PANEL "D"(EXHIBIT HALL SITE)

LV INPUT

NEW 120V CIRCUITS

CL.04 CL.05CL.07

CONTROLLED EXTERIOR CIRCUITS ON PANEL "F"(EXHIBIT HALL ROOF)

TOUCHSCREENCONTROL STATION

CL.02

EXISTING TO REMAIN =

NEW DEVICE =

NEW LINE VOLT WIRE =

NEW CONTROL WIRE =

POWER PACKS IN 3R ENCLOSURE

POWER PACKS IN 3R ENCLOSURE

POWER PACKS IN 3R ENCLOSURE

ACUITY:

CENTRAL PANEL : NLIGHT SYSTEM

POWER PACKS : NPP16 DIMMING POWER PACK

TOUCHSCREEN : FRESCO 7" LCD

The products above may be bid without prior approval. For any other manufacturer, submit complete product information to engineer before bidding (reference pre-approval deadline specified in bid documents). Review and approval decision will be issued in final addendum.

ACCEPTABLE MANUFACTURERS:

LEVITON:

CENTRAL PANEL : GREENMAX SYSTEM

POWER PACKS : DRC 0-10V SMARTPACK

TOUCHSCREEN : SAPPHIRE 7" LCD

CONTROL PANEL

SEATING AREA EMERGENCY LIGHTING

CONTXFMR

LV IN

PU

T

EMERGENCYBYPASS

POWERPANEL

LAH

120/208V

FACP

TE.01

PROGRAM CONTROL PANEL SUCH THAT THIS RELAY IS SWITCHED TO "ON" WHEN THE FIRE ALARM CONTROL PANEL SIGNALS A FIRE STATUS, BUT REMAINS OFF AT ALL OTHER TIMES.

PROGRAM CONTROL PANEL SUCH THAT THIS RELAY IS CONTROLLED BY MANUAL LOW VOLTAGE SWITCHES LABELED "BACKSTAGE WORK LIGHTS" UNDER NORMAL CONDITIONS, BUT OVERRIDDEN TO "ON" IF THE FIRE ALARM CONTROL PANEL SIGNALS A FIRE STATUS.

NOT USED.

TO SUPPLY THE NEW EMERGENCY FIXTURES ABOVE THEATER SEATING AREA, RE-USE EXISTING CIRCUIT CURRENTLY FEEDING THE EMERGENCY BATTERY IN THE CONTROL BOOTH.

INTERCEPT EXISTING CIRCUIT SERVING BACKSTAGE WORK FIXTURES, AND ROUTE THROUGH LIGHTING CONTROL PANEL. REPLACE EXISTING LINE VOLTAGE SWITCHES WITH NEW LOW VOLTAGE SWITCHES LABELED "BACKSTAGE WORK LIGHTS" AND PROVIDE LOW VOLTAGE CONNECTION TO CONTROL PANEL.

NOT USED.

PROVIDE INVERTER, SPECIFIED IN LIGHTING FIXTURE SCHEDULE. PROVIDE CHARGING CIRCUIT IN SAME PANEL THAT SUPPLIES ASSOCIATED FIXTURES.

THE FUNCTION OF THE EMERGENCY BYPASS MODULE IS TO SENSE WHETHER NORMAL UTILITY POWER IS AVAILABLE (VIA CONNECTION TO EXISTING POWER PANEL). IF UTILITY POWER FAILS, THE MODULE WILL AUTOMATICALLY BYPASS THE LIGHTING CONTROL PANEL AND TRANSFER THE LOAD TO THE INVERTER. PROVIDE 4" ENCLOSURE FOR MODULE AND SURFACE MOUNT ADJACENT TO LIGHTING CONTROL PANEL.

TE.01

TE.02

TE.03

TE.04

TE.05

TE.06

TE.07

TE.08

THEATER EMERGENCY LIGHTING CONTROL LEGEND:

THEATER EMERGENCY LIGHTING CONTROL KEYED NOTES: TE.05

BACKSTAGE WORK LIGHTING(DOUBLES AS EGRESS)

TE.02

(2) LV SWITCHES, LABEL:

"BACKSTAGE WORK LIGHTS"SWITCHING

RELAY

(2) LV SWITCHES, LABEL:

"AISLE LIGHTS"

EMERGENCYBYPASS

PROVIDE 120V-20A CONTROLS CIRCUIT

TE.08

TE.08

TE.04

INVERTERINV-2

TE.07

SWITCHINGRELAY

SWITCHINGRELAY

EXISTING TO REMAIN =

NEW DEVICE =

NEW LINE VOLT WIRE =

NEW CONTROL WIRE =

ACCEPTABLE MANUFACTURERS:Manufacturer of this system shall be same as manufacturer of central lighting control system.Refer to central system detail for pre-approved manufacturers and substitutin procedure.

SPARE

EH.02EXISTING GENERAL ELECTRIC "LIGHTSWEEP" MODULAR CONTROL SYSTEM, TO REMAIN AND BE EXPANDED TO ACCOMMODATE EXHIBIT HALL ADDITION. SYSTEM CONSISTS OF TWO PANELS, COMPONENTS CAN BE ADDED TO EITHER PANEL AS SPACE ALLOWS.

USE SPARE OR PROVIDE NEW LINE VOLTAGE RELAY (GE MODEL # CLCRMS6)

USE SPARE OR PROVIDE NEW 0-10V DIMMING MODULE (GE MODEL # CLCDIM4)

UTILIZE EXISTING SPARE DRY CONTACT OUTPUTS IN PANEL.

UTILIZE EXISTING SPARE DRY CONTACT INPUTS IN PANEL.

PROVIDE NEW 8 BUTTON SWITCHES, GE MODEL # CLCSWT8. REFER TO PLAN FOR QUANTITY AND LOCATIONS. MATCH LABELING OF EXISTING.

PROVIDE NEW INCANDESCENT SLIDE DIMMER FOR DECORATIVE CHANDELIER, MATCHING EXISTING DIMMERS. LUTRON VIERTI, MODEL # VT-600M-W-WH. REFER TO PLAN FOR LOCATIONS.

CONNECT KEYED SWITCHES PROVIDED WITH PARTITION OPERATORS TO CONTROL PANEL. REFER TO PLAN FOR QUANTITY AND LOCATIONS.

INCLUDE SITE VISITS BY FACTORY AUTHORIZED REPRESENTATIVES AS NECESSARY FOR RE-PROGRAMMING OF GE PANEL AND TOKISTAR CONTROLLER FOR ADDED ZONES AND SWITCHES.

EH.01

EH.02

EH.03

EH.04

EH.05

EH.06

EH.07

EH.08

EH.09

EXISTING TO REMAIN =

NEW DEVICE =

EXHIBIT HALL LIGHTING CONTROL LEGEND:

EXHIBIT HALL LIGHTING CONTROL KEYED NOTES:

EXI

STI

NG

CO

NTR

OL

PA

NE

L S

YS

TEM

LC

P-1

(MA

STE

R)

/ L

CP

-2 (S

EC

ON

DA

RY

)

EXISTING INVERTER

CAPACITY: 2100 WNEW TOTAL: 1344 W

TYPE A FIXTURES(TYP. OF 2 ROOMS)

277 V

0-10 V

277 V

0-10 V

EXISTING UL 924 RELAY

120 V

DMX

EXISTING TOKISTAR CONTROLLER

120 V NEW TRIAC

DIMMER

EXISTING8 BUTTON SWITCHES

NEW KEYED

SWITCHES

EXISTING8 BUTTON SWITCHES

NEW 8 BUTTON SWITCHES

CAT 5

EH.03

EH.02

EH.03

EH.02

EH.02

EH.04

EH.07

EH.08

EH.08

EH.01

TYPE B FIXTURES(TYP. OF 2 ROOMS)

TYPE C FIXTURES(TYP. OF 2 ROOMS)

TYPE D FIXTURES(TYP. OF 2 ROOMS)

PARTITION OPERATOR(TYP. OF 3 WALLS)

480 V

2 # 18 CU

PANEL MDP1

3 # 18 CUEH.05

ACCEPTABLE MANUFACTURERS:Provide the above specified products only. Due to the need to match the existing components, no substitutions will be allowed for this sytem. Contact at GE Application Support familiar with project : Cornel Saramet, (604) 421-8634Sales Representative Contact : Mark Delaney, Mountain States Agency, (505) 867-5034

EH.09

EH.09

NEW LINE VOLT WIRE =

NEW CONTROL WIRE =

REFER TO LIGHTING ZONING DETAIL ON SHEET EL102. ONE OF THE EXISTING OPERABLE PARTITIONS IS BEING REMOVED IN THIS PROJECT, CONTROL ZONES FOR THE ROOMS ON EITHER SIDE OF IT ARE TO BE COMBINED. THIS WILL FREE UP SPARE RELAYS, DIMMERS, AND INPUTS IN CONTROL PANEL FOR USE IN NEW ADDITION.

EXHIBIT HALL LIGHTING CONTROL GENERAL NOTE:

1

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:13:14

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

E503

LIGHTING CONTROLDETAILS &SCHEDULES

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW

AW

CENTRAL LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAMC3

THEATER EMERGENCY LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAMB3

CIRCUITS CONTROLLED BY NEW CENTRAL CONTROL SYSTEMPANEL CIRCUIT # NAME SCHEDULED NETWORKED

OCCUPANCY SENSOR(S) DIMMING DAYLIGHTHARVESTING

EXT.PHOTOCELL COMMENTS

BOLLARDS

D 11,13 Bollard Lights West Yes No No No Yes

LAF 25,27 Bollard Lights East Yes No No No Yes

CORRIDORS - EXHIBIT HALL

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Exhibit Hall Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

CORRIDORS - THEATER

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Corridor Lighting Yes Yes No No No Existing circuits on various panels, circuit numbers unknown.

EXTERIOR WALL LIGHTS

<unnamed> Exhibit Hall Exterior Wall Lights Yes No No No Yes Existing circuits on various panels, circuit numbers unknown.

<unnamed> Theater Exterior Wall Lights Yes No No No Yes Existing circuits on various panels, circuit numbers unknown.

HOLIDAY LIGHTS

D 2 Holiday Lgt Recept West Yes No No No Yes

D 4 Holiday Lgt Recept Bldg Yes No No No Yes

D 6 Holiday Lgt Recept West Yes No No No Yes

F 1 Holiday Lgt Recept Roof Yes No No No Yes

F 2 Holiday Lgt Recept Roof Yes No No No Yes

F 3 Holiday Lgt Recept Roof Yes No No No Yes

F 4 Holiday Lgt Recept Roof Yes No No No Yes

F 5 Holiday Lgt Recept Roof Yes No No No Yes

LAF 6 Holiday Lgt Recept Bldg Yes No No No Yes

LAF 8 Holiday Lgt Recept Center Yes No No No Yes

LAF 10 Holiday Lgt Recept East Yes No No No Yes

LAG 1 Holiday Lgt Recept Roof Yes No No No Yes

LAG 2 Holiday Lgt Recept Roof Yes No No No Yes

LAG 3 Holiday Lgt Recept Roof Yes No No No Yes

LAG 4 Holiday Lgt Recept Roof Yes No No No Yes

LAG 5 Holiday Lgt Recept Roof Yes No No No Yes

POLES, CENTER

LAF 33,35 Pole Lights Center Yes No Yes No Yes

POLES, OUTER

D 7,9 Pole Lights West Yes No Yes No Yes

LAF 29,31 Pole Lights East Yes No Yes No Yes

SCULPTURE LIGHTING

D 19 Sculpture Flood Lighting Yes No No No Yes

TRELLIS LIGHTS

D 15,17 Trellis Lighting West (Alternate) Yes No Yes No Yes

LAF 37,39 Trellis Lighting East (Alternate) Yes No Yes No Yes

TOTAL CIRCUITS : 48

CIRCUITS BEING ADDED TO EXISTING EXHIBIT HALL CONTROL SYSTEMPANEL CIRCUIT # NAME CONTROL REQUIRED COMMENTS

L 28 LGT - Type A Room 6 RELAY + 0-10V

L 26 LGT - Type A Room 7 RELAY + 0-10V

L 31 LGT - Type B Room 6 RELAY + 0-10V + EM OVERRIDE ROUTE CIRCUIT THROUGH UL924 CONTACTOR, WHICH WILL OVERRIDE CONTROL STATE TO ON/FULL BRIGHTNESS AND TRANSFERPOWER TO INVERTER UPON LOSS OF UTILITY POWER.

L 30 LGT - Type B Room 7 RELAY + 0-10V + EM OVERRIDE ROUTE CIRCUIT THROUGH UL924 CONTACTOR, WHICH WILL OVERRIDE CONTROL STATE TO ON/FULL BRIGHTNESS AND TRANSFERPOWER TO INVERTER UPON LOSS OF UTILITY POWER.

AC 25 LGT - Type C Room 6 RELAY + DMX VIA TOKISTAR CONTROLLER EXISTING FIXTURE DMX DIMMING UNITS ARE DAISY-CHAINED TOGETHER. CONNECT NEW FIXTURES' DMX IN LINE. ON/OFF CONTROL IS BYCONTROL PANEL VIA BUTTON IN EXHIBIT HALL, COLOR SELECTION MUST BE MADE AT TOKISTAR CONTROLLER IN ELECTRICAL ROOM

AC 27 LGT - Type C Room 7 RELAY + DMX VIA TOKISTAR CONTROLLER EXISTING FIXTURE DMX DIMMING UNITS ARE DAISY-CHAINED TOGETHER. CONNECT NEW FIXTURES' DMX IN LINE. ON/OFF CONTROL IS BYCONTROL PANEL VIA BUTTON IN EXHIBIT HALL, COLOR SELECTION MUST BE MADE AT TOKISTAR CONTROLLER IN ELECTRICAL ROOM

AC 21 LGT - Type D Room 6 RELAY + TRIAC DIMMER ON WALL MATCH CONTROL SCHEME FOR EXISTING CHANDELIERS. ON/OFF IS CONTROLLED BY RELAY IN CONTROL PANEL, BUT DIMMING LEVEL ISCONTROLLED FROM MANUAL DIMMING STATION ONLY.

AC 23 LGT - Type D Room 7 RELAY + TRIAC DIMMER ON WALL MATCH CONTROL SCHEME FOR EXISTING CHANDELIERS. ON/OFF IS CONTROLLED BY RELAY IN CONTROL PANEL, BUT DIMMING LEVEL ISCONTROLLED FROM MANUAL DIMMING STATION ONLY.

EXHIBIT HALL EXISTING LIGHTING CONTROL SYSTEM ONE-LINE DIAGRAMA3

CIRCUITS CONTROLLED BY NEW THEATER EMERGENCY CONTROL PANELPANEL CIRCUIT # NAME CONTROL REQUIRED COMMENTS

LAH 1 Backstage Work Lights RELAY + EM OVERRIDE

LAH 3 Seating Area EM Lights RELAY + EM OVERRIDE

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

Page 23: Request For Qualifications-Based Proposals for ...

SS

FIRE RISER KEYED NOTES

MAGNETIC DOOR HOLDER TYP. MDH

TT

TS FS

(LOCKING CLIP CB)20A, 120V

20A 120V

C

SEE NOTE:

FAA

FACP

DS DS

RI

VOICE/STROBE TYP.

STROBE, TYP.

HORN /STROBE WP TYP.

TO COMM. TERM. BD.

FIRE /SMOKEDAMPER TYP.

F/S DAMPER RELAYADDRESSABLE

MANUAL PULLSTATION, TYP.

SMOKEDETECTOR,TYP.

HEAT DETECTOR, TYP.

DUCT SMOKEDETECTOR, TYP.

REMOTEINDICATOR, TYP

KITCHEN HOODSUPPRESSION SYSTEM

17

WP

PROVIDE AND INSTALL A COMPLETE, INTELLIGENT, ADDRESSABLE FIRE ALARM SYSTEM; INCLUDING, BUT NOT LIMITED TO DEVICES, BACK BOXES, CONDUIT SYSTEM, CABLING, EQUIPMENT, ASSOCIATED DEVICES, AND INTERCONNECTIONS. PROVIDE SYSTEM PROGRAMMING, PERSONNEL TRAINING, AND COMMISSIONING. UTILIZE 14-18 GAUGE WIRE, SOLID WIRE ONLY. UNIFORM COLOR CODE FOR WIRING THROUGH OUT. RUN ALL EXISTING CABLING WITHIN CONDUIT, 1/2'' C MINIMUM. PLENUM RATED CABLE ON J-HOOK APPROVED IN ACCESSIBLE CEILINGS. SEE SPECIFICATION SECTION 28 31 11 FOR APPROVED MANUFACTURERS. ALL DEVICES BELOW TO BE BY SAME MANUFACTURER AS PANEL.

1. FIRE ALARM CONTROL PANEL (FACP): SURFACE PER PLAN MOUNTED CABINET. CABLES INCLUDE A 20A, 120V BRANCH CIRCUIT, LOCKING CLIP. FINAL LOCATION SHALL BE VERIFIED WITH THE OWNER PRIOR TO ROUGH-IN. INCLUDE 4 - 3/4" EMT CONDUIT STUB OUTS FROM THE FACP TO THE ACCESSIBLE CEILING CAVITY FOR FUTURE CONNECTIONS. NOTE THAT THE OWNER WILL BE RESPONSIBLE TO OBTAIN CENTRAL STATION MONITORING SERVICES. INSTALL AS-BUILT FIRE ALARM SYSTEM DRAWING COVERED BY GLASS MOUNTED TO BACK OF FACP.

2. MANUAL PULL STATION: DOUBLE ACTION, NON-BREAK GLASS TYPE.

3. PHOTOELECTRIC SMOKE DETECTOR, RECONNECT EXISTING AND PROVIDE NEW AS INDICATED.

4. HEAT DETECTOR: 135 DEGREE FIXED TEMPERATURE.

5. VOICE/STROBE VERTICAL WALL MOUNT.

6. STROBE: VERTICAL WALL MOUNT.

7. HORN/STROBE, WEATHERPROOF COVER: WITH HUMIDITY GASKET.

8. FIRE ALARM ANNUNCIATOR AT ENTRY: LCD TYPE, SEMI-RECESSED MOUNTED. LOCATE ANNUNCIATOR AT A POSITION DETERMINED BY THE FIRE MARSHALL AND COORDINATED WITH THE ARCHITECT.

9. DUCT SMOKE DETECTOR/SENSOR/BAFFLE 1 SMOKE DETECTOR AT THE SUPPLY DUCT AND 1 AT THE RETURN DUCT. LOCATION AND SAMPLE TUBE LENGTH IN ACCORDANCE WITH THE NFPA INSTALLATION GUIDELINES AND UMC. SMOKE DETECTOR SHALL BE PHOTOELECTRIC TYPE. PROVIDE RELAYS AS REQUIRED TO SHUT DOWN A.H.U. FAN.

10. REMOTE ALARM INDICATOR: LOCATE IN CORRIDOR CEILING DIRECTLY BELOW DUCT SMOKE DETECTOR OR AS NEAR DUCT DETECTOR LOCATION AS POSSIBLE.

11. FIRE / SMOKE DAMPER: 120V MOTORIZED ACTUATOR PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL A DISCONNECT MEANS AT EACH MOTORIZED DAMPER WITH 2 #12 + #12 GRD, 1/2''C (MIN) TO A 20A, 120V BRANCH CIRCUIT VIA ADDRESSABLE FIRE SMOKE DAMPER RELAY. DAMPER SHALL REMAIN OPEN WHILE THE ASSOCIATED MECHANICAL UNIT IS IN OPERATION, AND SHALL CLOSE IN THE EVENT OF SMOKE DETECTOR, DUCT DETECTOR, HEAT DETECTOR ACTIVATION, OR POWER LOSS. INCLUDE PROGRAMMING SO THAT MECHANICAL UNIT(S) SHALL SHUT DOWN PRIOR TO DAMPER CLOSING.

12. FIRE / SMOKE DAMPER RELAY: 20A, 120V CONTACTS, COIL VOLTAGE SHALL BE COORDINATED WITH FIRE ALARM SYSTEM. COIL SHALL BE CONTROLLED VIA SIGNAL FROM FACP. REFER TO FIRE / SMOKE DAMPER NOTE.

13. 4 PAIR, CAT 5 TELEPHONE CABLE, 3/4"C TO THE TELEPHONE TERMINAL BOARD.

14. MAGNETIC DOOR HOLDER: SERIES, COORDINATE SINGLE OR DOUBLE DOOR, SEMI-RECESSED WALL MOUNTED, VERIFY SHORT CATCH OR LONG CATCH PLATE WITH EACH DOOR. DOOR HOLDERS ARE PROVIDED AND INSTALLED UNDER ARCHITECTURAL SECTIONS, AND CONNECTED BY THE ELECTRICAL CONTRACTOR. SECURE BACK BOX TO STUD, INCLUDE BRIDGING WHERE REQUIRED. COORDINATE FINAL MOUNTING HEIGHT AND EXACT LOCATION WITH ARCHITECT'S PLANS.MAGNETIC DOOR HOLDER: SERIES, COORDINATE SINGLE OR DOUBLE DOOR, SEMI-RECESSED WALL MOUNTED, VERIFY SHORT CATCH OR LONG CATCH PLATE WITH EACH DOOR. DOOR HOLDERS ARE PROVIDED AND INSTALLED UNDER ARCHITECTURAL SECTIONS, AND CONNECTED BY THE ELECTRICAL CONTRACTOR. SECURE BACK BOX TO STUD, INCLUDE BRIDGING WHERE REQUIRED. COORDINATE FINAL MOUNTING HEIGHT AND EXACT LOCATION WITH ARCHITECT'S PLANS.

15. EMERGENCY COMMAND COVER. SEE SPECS.

16. LABEL ALL CONDUITS IN ACCORDANCE WITH THE SPECIFICATIONS. COORDINATE ROUTING OF CONDUITS BETWEEN FLOOR LEVELS AND BUILDINGS WITH ALL DISCIPLINES PRIOR TO ROUGH-IN.

17. THE SPECIAL SYSTEMS RISER DIAGRAM DOES NOT REFLECT ALL THE DEVICES REQUIRED. REFER TO THE FLOOR PLANS FOR LOCATION AND QUANTITY OF DEVICES.

18. F/A FLOW SWITCH AND TAMPER SWITCH, PROVIDE @ ALL FIRE SPRINKLER RISER VALVES AND WALL / POST INDICATOR VALVES.

8

1

12

F/SF/S

11

16

13

14

F F F

7

6

5

10

9

4

HD

3

15

2

FF

18

V

ECC

1. EMERGENCY TWO-WAY COMMUNICATION COMMAND UNIT: MANUFACTURED BY TALK-A-PHONE CO. AOR-8 OR EQUAL. COMMAND UNIT SHALL INCLUDE BUILT IN UPS. CABINET SHALL BE CONSTRUCTED OF STAINLESS STEEL WITH TWO ACRYLIC WINDOWS, RECESSED MOUNTED WITH RED PHONE AND 12-KEY PAD-SIZE 24.375"W X 18.375"H X 4.25"D. STROBE/SOUNDER SHALL INDICATE INCOMING CALLS, VISUALLY INDICATE THE IDENTITY OF CALLING RESCUE STATION, AND ENABLE TWO-WAY CONVERSATION. EMERGENCY PERSONNEL SHALL ALSO BE ABLE TO SELECTIVELY CALL ANY RESCUE STATION. UNIT SHALL ALSO COME WITH A SIREN ALERT WHICH COMBINES A SIREN AND STROBE CONSTRUCTED WITHIN A 4" SQUARE UNIT (LOCATION OF SIREN AND STROBE UNIT IS NOT SHOWN ON THE FLOOR PLAN AND SHALL BE LOCATED IN FIELD IN ACCORDANCE WITH THE ARCHITECT'S REQUIREMENTS). THE CONTRACTOR SHALL COORDINATE SYSTEM REQUIREMENTS WITH THE ADA CODE AUTHORITY AND THE ARCHITECT PRIOR TO ROUGH-IN.

2. EMERGENCY TWO-WAY COMMUNICATION PHONE: MANUFACTURED BY TALK-A-PHONE CO. #ETP-100EB-FRONT PANEL SIZE 9.25"W X 11"H/WALL OPENING 4.5"W X 7.5"H X 2.5"D; AND MOUNTING SLEEVE BOX #MS-100 - SIZE 9"W X 11.25"H X 3"D OR EQUAL. FLUSH MOUNTED, STAINLESS STEEL PANEL, CAST METAL RAISED LETTERS AND BRAILLE SIGNAGE FOR ADA COMPLIANCE. INCLUDE SELF ADHESIVE AREA OF RESCUE SIGNS #ETP-SIGN FOR EACH STATION.

3. CONNECT TO NEW DEDICATED PHONE LINE AND DEDICATED 120V/1PH CIRCUIT.

1ST FLOOR

2ND FLOOR

COMMANDUNIT

EMERGENCY PHONE, TYP.CABLING AND 1/2" C (MIN)

PER MANUFACTURER'SREQUIREMENTS, TYP.

2

1

EMERGENCY TWO-WAYCOMMUNICATION RISERDIAGRAM KEYED NOTES

3

FINISHED CEILING

FLOOR

JUNCTION BOX

FLEXIBLE CORD, PER CIRCUITREQUIREMENTS ALLOW 6' SLACK

SINGLE GANG BOX WITH RECEPTACLES OR CORD-CAP CONNECTION, PER PLAN

STRAIN RELIEF

LAY-IN CEILINGWHERE INDICATED

RETRACTABLE CORDREEL

P2000 UNISTRUT

6'6"

J-HOOKS WIRE MGT.

NEW COAX WIRING

1. GE TRU-VISION CAMERA, OR EQUAL.

2. 24 VOLT POWER SUPPLY.

3. COLOR DIGITAL VIDEO RECORDER.

4. COLOR 19" MONITOR.

41

2

3

SECURITY SYSTEM:PROVIDE AND INSTALL A NEW SECURITY SYSTEM WITH COLOR VIDEO CAMERAS, DVRS AND WIRING. LOCATE POWER SUPPLY, DVR, MONITOR IN SUPERVISORS T108

COLOR DIGITALVIDEO RECORDER

24V POWER SUPPLY

VIDEO CAMERAS COLOR MONITOR

120V

KEYED NOTES

POWER BOX(VENDOR USE)

208 V

3W

+ G

SURF

ACE

MOUN

T ON

POL

E BA

SE

POLE TOP FIXTURE

8 FT COPPER CLADSTEEL GROUND ROD

TOP AT 30" BELOW GRADE

POLE RECEPTACLE(HOLIDAY LIGHTS)

50 A

/ 208

V RE

CEPT

ACLE

20 A

/ 120

V GF

CI

RECE

PTAC

LE

20 A

/ 120

V GF

CI

RECE

PTAC

LE

ENCLOSURE AND E.G.C.

REBAR & POLE

E.G.C.E.G.C.

# 10

CU

0-10

V D

IMMI

NG (

2) #

14 C

U

208 V

2W

+ G

120 V

2W

+ G

TO NEXT HOLIDAY LIGHT RECEPTACLE

TO NEXT POLE LIGHT

TO NEXT VENDOR POWER BOX

REFERENCE STRUCTURAL SHEET S302 FOR POLE BASE DETAIL.

SINGLE 20A GFCI RECEPTACLE INCLUDED WITH POLE. CONNECT TO HOLIDAY LIGHT CIRCUIT CONTROLLED BY CENTRAL LIGHTING CONTROL PANEL. REMOVE STANDARD COVER INCLUDED WITH RECEPTACLE, AND REPLACE WITH METAL HEAVY DUTY WHILE-IN-USE WEATHERPROOF COVER. PROVIDE PERMANENT WEATHERPRROF LABEL ON COVER, READING "HOLIDAY LIGHTS."

PROVIDE VENDOR POWER BOX, SURFACE MOUNTED ON POLE BASE WITH TOP OF BOX FLUSH WITH TOP OF POLE BASE. THIS DETAIL DEPICTS LARGEST BOX REQUIRED, SOME POLES ONLY REQUIRE SMALLER 120V BOXES. REFER TO SHEET ES101 FOR PRODUCT SPECIFICATION AND LAYOUT.

REFER TO SITE CIRCUIT CONDUCTOR SCHEDULE, THIS SHEET, FOR WIRE SIZES REQUIRED TO MITIGATE VOLTAGE DROP ON EACH CIRCUIT.

RUN CONTROL CONDUCTORS IN SEPERATE CONDUIT, AND TERMINATE AT DIMMING POWER PACK ADJACENT TO POWER PANEL. REFER TO CENTRAL LIGHTING CONTROL SYSTEM DETAIL, SHEET E503.

REFER TO AUDIO-VISUAL (AV) SHEETS FOR REQUIREMENTS RELATED TO POLE MOUNTED SPEAKERS.

PB.01

PB.02

PB.03

PB.04

PB.05

PB.06

POLE BASE ELECTRICAL DETAIL KEYED NOTES:

PB.03

PB.02

PB.01

PB.04

PB.04

PB.04

PB.05

SPEAKERS

PB.06

TO NEXT SPEAKER OR A/V CABINET

PB.06

ANCHOR

DRAIN

JET

JET + LIGHT

JET

JET

JET

JET

JET

JET

JET

DRAIN

ANCHOR

ANCHOR

ANCHOR

ACTIVATION BOLLARD

CONTROLLER

PUMP

AREA IN WHICH ALL FIXED METAL PARTS MUST BE BONDED, AND NO UNRELATED UNDERGROUND ELECTRICAL MAY BE INSTALLED

MINUMUM EXTENT OF EQUIPOTENTIAL BONDING GRID BENEATH SPLASH PAD

BOUNDARY OF SPLASH PAD

IN SPLASH PAD CONCRETE, PROVIDE AN EQUIPOTENTIAL BONDING GRID (E.B.G.) COMPLYING WITH NEC 680.26(B)(1)(b). GRID AREA SHALL BE THE ENTIRE PAD PLUS AT LEAST 3 FT FROM THE PAD BOUNDARY ON ALL SIDES. GRID MAY CONSIST OF STRUCTURAL REBAR OR WIRE MESH PROVIDED BY CONCRETE INSTALLER, WITH A SOLID #8 CU CONDUCTOR ADDED AROUND THE PERIMETER AND BONDED TO STRUCTURAL STEEL AT FOUR LOCATIONS SPACED EVENLY AROUND THE GRID. IF STRUCTURAL STEEL IS COMPOSED OF SEPERATE PARTS, BOND THESE TOGETHER USING #8 CU WIRE. IF NO STRUCTURAL STEEL IS PRESENT, THE E.P.G. SHALL CONSIST OF # 8 SOLID COPPER WIRE IN A 12" X 12" GRID BONDED AT ALL INTERSECTIONS, INSTALLED IN OR UNDER THE CONCRETE AT 4" TO 6" BELOW SURFACE, WITH AN OUTER WIRE FOLLOWING THE CONTOUR OF THE PAD, BONDED TO THE GRID IN 4 EVENLY SPACED LOCATIONS. USING #8 SOLID CU, BOND ALL OF THE FOLLOWING TO THE OUTER WIRE OF THE E.B.G.:

BOND ALL FIXED METAL PARTS OF SPLASH PAD. THIS INCLUDES BUT IS NOT LIMITED TO: NOZZLES, LIGHTS, DRAINS, AND STRUCTURAL ANCHORS.

BOND ALL FIXED METAL PARTS OF ANY SYSTEM, IF LOCATED WITHIN 5 FT OF THE PAD BOUNDARY. THIS INCLUDES BUT IS NOT LIMITED TO: ELECTRICAL CONDUIT, WATER PIPING, AND DRAIN PIPING, WHETHER ASSOCIATED WITH SPLASH PAD SYSTEM OR NOT.

BOND ALL FIXED METAL PARTS ASSOCIATED WITH THE SPLASH PAD SYSTEM, IN ANY LOCATION. THIS INCLUDES BUT IS NOT LIMITED TO: ELECTRICAL CONDUIT, WATER PIPING, AND DRAIN PIPING, REGARDLESS OF DISTANCE FROM PAD.

BOND ALL FIXED METAL PARTS IN THE ABOVE GROUND VAULT HOUSING THE SPLASH PAD EQUIPMENT. THIS INCLUDES BUT IS NOT LIMITED TO: EQUIPMENT ENCLOSURES, CONDUIT, AND ANY METAL PARTS OF THE VAULT ITSELF. ENSURE THAT EQUIPMENT ENCLOSURES ARE ALSO BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FROM THE SUPPLY PANELBOARD.

SP.01

SP.02

SP.03

SP.04

SP.05

SPLASH PAD GROUNDING & BONDING DETAIL KEYED NOTES:

SP.05

3'

5'

ANYMETALPIPING

SP.04

SP.01

SP.03

SP.02

SP.04

TYPICAL

GFCICIRCUIT(S)

SPLASH PAD GROUNDING & BONDING GENERAL NOTES:

ALL UNDERGROUND CONDUIT IS PART OF BASE BID ROUGH IN FOR SPLASH PAD (STUB UP UNDER PAVEMENT). GROUNDING / BONDING WORK AND ABOVE GROUND COMPONENTS ARE PART OF WATER FEATURE ALTERNATE BID.

IN GENERAL, COMPLY WITH NEC 680 (II) AS IF THE SPLASH PAD WERE A PERMANENTLY INSTALLED CONCRETE POOL. IF NEEDED, SUBMIT RFI FOR CLARIFICATION OF HOW TO APPLY ARTICLE 680.

ALL BONDING REFERED TO ABOVE MUST UTILIZE A CONNECTION METHOD LISTED FOR GROUNDING USE, AND RATED FOR THE ENVIRONMENTAL CONDITIONS WHERE IT IS USED (FOR EXAMPLE, CONNECTIONS WITHIN EQUIPMENT VAULT MUST BE LISTED FOR CORROSIVE ENVIRONMENTS).

ALL SINGLE PHASE CIRCUITS ASSOCIATED WITH SPLASH PAD SYSTEM MUST HAVE GFCI PROTECTION FOR PERSONNEL. THIS INCLUDES ANY SINGLE PHASE 208 VOLT OR 240 VOLT CIRCUITS, AND ALSO INCLUDES HARDWIRED CONNECTIONS.

ALL ASSOCIATED ELECTRICAL CONDUIT MUST BE PVC OR RMC. USE RMC ONLY WHERE EXPOSED.

BRANCH WIRING METHODS FOR INTEGRAL LIGHTING IN SPLASH PAD SHALL COMPLY WITH NEC 680.23 AND 680.24, SIMILAR TO UNDERWATER POOL LUNINAIRES, WHERE PHYSICALLY APPLICABLE.

DO NOT INSTALL ANY UNDERGROUND ELECTRICAL WITHIN 5 FT OF SPLASH PAD BOUNDARY, UNLESS IT IS NECESSARY FOR THE FUNCTION OF THE SPLASH PAD SYSTEM ITSELF.

1.

2.

3.

4.

5.

6.

7.

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:13:33

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

E504

ELECTRICAL DETAILS

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

NB

TC

FIRE RISER DIAGRAMD5

EMERGENCY 2-WAY COMM. DIAGRAMC5

CORD DROP DETAILA6

SECURITY CAMERA RISER DIAGRAMB5

POLE BASE ELECTRICAL DETAILC1

NOTES:1. The circuit lengths shown are for calculation purposes only.They shall not be used for contractor takeoffs or bidding.

2. Contractor shall notify engineer of any field condition that results in a change of20% or greater circuit distance.

SITE CIRCUIT CONDUCTOR SCHEDULE

PANEL CIRCUIT NAME CONDUCTORS INCLUDE 0-10V DIMMINGCONDUCTORS (2 # 16 CU)

CONTROLLED BYCENTRAL PANEL

EST.LENGTH CB SIZE VOLTAGE

LAF 1,3,5 Food Truck Pedestals East # 4/0 CU + #2 CU EGC No No 441' 100 A 208 V

LAF 2 Fountain Pump (GFCI) # 10 CU + # 10 CU EGC No No 34' 25 A 120 V

LAF 6 Holiday Lgt Recept Bldg # 10 CU + # 10 CU EGC No Yes 198' 20 A 120 V

LAF 7,9,11 Food Truck Pedestals East # 1/0 CU + # 4 CU EGC No No 291' 60 A 208 V

LAF 8 Holiday Lgt Recept Center # 8 CU + # 8 CU EGC No Yes 486' 20 A 120 V

LAF 10 Holiday Lgt Recept East # 8 CU + # 8 CU EGC No Yes 528' 20 A 120 V

LAF 12 Irrigation Controller # 12 CU + # 12 CU EGC No No 148' 20 A 120 V

LAF 13,15,17 Company Switch CS3 # 3 CU + # 6 CU EGC No No 187' 60 A 208 V

LAF 14 Hotbox # 8 CU + # 8 CU EGC No No 184' 20 A 120 V

LAF 16 Vendor Power # 4 CU + # 4 CU EGC No No 295' 20 A 120 V

LAF 18 Vendor Power # 6 CU + # 6 CU EGC No No 182' 20 A 120 V

LAF 19,21,23 RV Pedestal # 8 CU + # 8 CU EGC No No 77' 50 A 208 V

LAF 20 Vendor Power # 4 CU + # 4 CU EGC No No 246' 20 A 120 V

LAF 22 Vendor Power # 4 CU + # 4 CU EGC No No 206' 20 A 120 V

LAF 24 Vendor Power # 6 CU + # 6 CU EGC No No 194' 20 A 120 V

LAF 25,27 Bollard Lights East # 12 CU + # 12 CU EGC No Yes 325' 20 A 208 V

LAF 29,31 Pole Lights East # 8 CU + # 8 CU EGC Yes Yes 478' 20 A 208 V

LAF 33,35 Pole Lights Center # 8 CU + # 8 CU EGC Yes Yes 484' 20 A 208 V

LAF 37,39 Trellis Lighting East (Alternate) # 12 CU + # 12 CU EGC Yes Yes 276' 20 A 208 V

D 1,3,5 Food Truck Pedestals West # 2/0 CU + # 4 CU EGC No No 301' 100 A 208 V

D 2 Holiday Lgt Recept West # 8 CU + # 8 CU EGC No Yes 410' 20 A 120 V

D 4 Holiday Lgt Recept Bldg # 10 CU + # 10 CU EGC No Yes 104' 20 A 120 V

D 6 Holiday Lgt Recept West # 8 CU + # 8 CU EGC No Yes 166' 20 A 120 V

D 7,9 Pole Lights West # 8 CU + # 8 CU EGC Yes Yes 583' 20 A 208 V

D 8 Vendor Power # 6 CU + # 6 CU EGC No No 162' 20 A 120 V

D 10 Vendor Power # 6 CU + # 6 CU EGC No No 197' 20 A 120 V

D 11,13 Bollard Lights West # 12 CU + # 12 CU EGC No Yes 626' 20 A 208 V

D 12 Vendor Power # 8 CU + # 8 CU EGC No No 113' 20 A 120 V

D 14 Vendor Power # 4 CU + # 4 CU EGC No No 283' 20 A 120 V

D 15,17 Trellis Lighting West (Alternate) # 12 CU + # 12 CU EGC Yes Yes 276' 20 A 208 V

D 16 Monument Sign Ckt #1 # 8 CU + # 8 CU EGC No No 156' 20 A 120 V

D 18 Monument Sign Ckt #2 # 8 CU + # 8 CU EGC No No 156' 20 A 120 V

D 19 Sculpture Flood Lighting # 12 CU + # 12 CU EGC No Yes 131' 20 A 120 V

D 20 Monument Sign Ckt #3 # 8 CU + # 8 CU EGC No No 156' 20 A 120 V

D 22 Monument Sign Ckt #4 # 8 CU + # 8 CU EGC No No 156' 20 A 120 V

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

SPLASH PAD GROUNDING AND BONDING DETAIL1

1

1

Page 24: Request For Qualifications-Based Proposals for ...

463

TUR

NE R

DR

, SU

ITE

104A

DU

RAN

GO

, CO

813

03PH

ON

E : 9

70-3

8 5-1

570

FAX:

970

-385

-156

9

ME C

HAN

ICAL

, ELE

CTR

ICA L

& EN

V IR

ON

ME N

TAL

ENG

INEE

RIN

G IN

C.

A

B

C

D

E

A

B

C

D

E

1 2 3 4 5 6

DRAWN BY:

CHECKED BY:

PROJECT NO:

GREER-STAFFORD/SJCF, INC.C

SHEET TITLE

DRAWING SHEET

ISSU

E:

THIS DRAWING IS INCOMPLETE AND NOT TO BE USED FOR CONSTRUCTION UNLESS IT IS STAMPED, SIGNED, AND DATED BELOW

1 2 3 4 5 6

2017-07-20

8/22/2

017 7

:13:41

PM

C:\U

sers\

ambe

r\Doc

umen

ts\15

13_C

OF_C

ivic_

R17_

ambe

r.rvt

E601

LIGHT FIXTURESCHEDULES

1513

6/26

/201

7

FARM

ING

TON

CIV

IC C

ENTE

R R

ENO

VATI

ON

S &

EXPA

NSIO

N

200

W.

ARRIN

GTO

N,

FARM

ING

TON

, N

M 8

7401

CIT

Y O

F FA

RM

ING

TON

AW/NB

AW

NOTES:1. Unless otherwise noted, all fixtures shall be 35K CCT and shall have minimum 80 CRI.2. Unless otherwise noted, all fixtures shall have universal voltage (120-277) drivers.3. Unless otherwise noted, all heights shown are to bottom of fixture.

4. Proposed substitutions must be APPROVED PRIOR TO BIDDING, meet all requirements listed here, and have IES files available. Refer to specification text for detailed requirements for substitutionrequests.

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION BASIS OF DESIGN SPEC-MAKE BASIS OF DESIGN SPEC - MODEL PRE-APPROVED ALTERNATE

SPEC 1 - MAKE PRE-APPROVED ALTERNATE SPEC 1 - MODEL MOUNTING HEIGHT LAMP LOAD LUMENS OPTIC NOTES

NO SUBSTITUTION ALLOWED FOR THESE FIXTURES (MUST MATCH EXISTING FIXTURES):

A FLUORESCENT 4'X4" LENSED LINEAR, MATCHING EXISTING.LIGHTED 90 DEG CORNERS. PINNACLE E4SCH-1T5-G1-UNV-1C-W NONE NONE RECESSED, GRID CEILING F54WT5/830/ECO 54 VA - DIFFUSE 0-10V DIMMING

B 2X2 TROFFER, MATCHING EXISTING GE ET22-A1-0AV-WHITE w/67657 NONE NONE RECESSED,GYPSUM CEILING LED 42 VA 3,500 DIFFUSE 0-10V DIMMING

C1~20'FT COLOR CHANGING LED COVE MATCHING EXSITING.MOUNTING TRACK, ELEC DRIVER, DMX CONTROL, 2" LEDSPACING

TOKISTAR TRI-50-RGB, TRI-MT, LDR8-80, LC-3CH-DMX NONE NONE COVE SHELF CEILING LED 40 VA 17 / FT PEAK DIFFUSE DMX CONTROL. PROVIDE QUANTITY OF DRIVERS AND CONTROLLERS AS NEEDED FORCOPLETE AND FUNCTIONAL SYSTEM OF LENGTH INDICATED.

C2~115'FT COLOR CHANGING LED COVE MATCHING EXSITING.MOUNTING TRACK, ELEC DRIVER, DMX CONTROL, 2" LEDSPACING

TOKISTAR TRI-50-RGB, TRI-MT, LDR8-80, LC-3CH-DMX NONE NONE COVE SHELF CEILING LED 230 VA 17 / FT PEAK DIFFUSE DMX CONTROL. PROVIDE QUANTITY OF DRIVERS AND CONTROLLERS AS NEEDED FORCOPLETE AND FUNCTIONAL SYSTEM OF LENGTH INDICATED.

C3~128'FT COLOR CHANGING LED COVE MATCHING EXSITING.MOUNTING TRACK, ELEC DRIVER, DMX CONTROL, 2" LEDSPACING

TOKISTAR TRI-50-RGB, TRI-MT, LDR8-80, LC-3CH-DMX NONE NONE COVE SHELF CEILING LED 256 VA 17 / FT PEAK DIFFUSE DMX CONTROL. PROVIDE QUANTITY OF DRIVERS AND CONTROLLERS AS NEEDED FORCOPLETE AND FUNCTIONAL SYSTEM OF LENGTH INDICATED.

D LARGE DECORATIVE CHANDELIER MATCHING EXISTING SEE NOTE SEE NOTE NONE NONE PENDANT MATCH EXISTING INCAND. 600 VA N/A DIFFUSECUSTOM CHANDELIER MATCHING EXISTING. INCLUDE ALLOWANCE FOR THIS FIXTURE(REFER TO SPEC SECTION 01 21 00-1.06 ALLOWANCES SCHEDULE). OWNER WILLPROVIDE SUPPLIER INFORMATION AFTER PROJECT IS AWARDED.

EX2 EXIT SIGN, MATCHING EXISTING, BLACK ALUMINUM,INTEGRAL BATTERY MCPHILBEN ER55LD3G NONE NONE UNIVERSAL UNIVERSAL LED 5 VA N/A N/A

SUBSTITUTION ALLOWED FOR THESE FIXTURES:

ER EXTERIOR REMOTE LIGHT HEAD POWERED BY TYPE EXR OREXLR COMPASS CORS LITHONIA ELA QWP L0309 WALL 9' AFG LED 0 VA N/A DIFFUSE

EX EXIT SIGN, RED ON WHITE, INTEGRAL BATTERY COMPASS CCR LITHONIA EXR LED EL M6 UNIVERSAL UNIVERSAL LED 5 VA N/A N/A

EXL EXIT SIGN WITH LIGHTS, RED ON WHITE, INTEGRAL BATTERY COMPASS CER LITHONIA EXR LED EL M6 UNIVERSAL UNIVERSAL LED 5 VA N/A N/A

EXLR EXIT SIGN WITH LIGHTS AND REMOTE CAPACITY, RED ONWHITE, INTEGRAL BATTERY COMPASS CCRRC LITHONIA LHQM LED R HO UNIVERSAL UNIVERSAL LED 5 VA N/A N/A

EXR EXIT SIGN WITH REMOTE CAPACITY, RED ON WHITE,INTEGRAL BATTERY COMPASS CERRC LITHONIA LHQM LED R HO R0 UNIVERSAL UNIVERSAL LED 5 VA N/A N/A

F2 DECORATIVE VANITY FIXTURE, 2FT TERON BT24-L20.6-120-277V-TE600-FINISH-WLL-35K BROWNLEE 5461 24 FINISH H16LED 35K WALL 7' AFF LED 20 VA 2,000 DIFFUSE

F4 DECORATIVE VANITY FIXTURE, 4FT TERON BT48-L41.2.0-120-277V-TE350-FINISH-WLL-35K BROWNLEE 5461 48 FINISH H32LED 35K WALL 7' AFF LED 42 VA 4,000 DIFFUSE

G1 DISC LIGHT, 1" H X 10" DIAM, WHITE DALS CFLEDR10-WH SURFACE CEILING LED 11 VA 1,000 DIFFUSE WET LOCATION. 120 VOLT ACCEPTABLE.

G2 SURFACE DISC LIGHT, 2" H X 1 FT DIAM. TMS AR901-12-19LED-35K-120-FINISH-SD-DIML SURFACE CEILING LED 19 VA 1,400 DIFFUSE 120 VOLT ACCEPTABLE.

G2E SURFACE DISC LIGHT, 2" H X 1 FT DIAM., WITH REMOTEBATTERY TMS AR901-12-19LED-35K-120-FINISH-SD-DIML-EM

R SURFACE CEILING LED 19 VA 1,400 DIFFUSE MOUNT BATTERY ABOVE ACCESSIBLE CEILING WITHIN 20 FT

H1 LENSED STRIP, LOW WATTS COLUMBIA LCL4-35LW-EU LITHONIA ZL1D L48 SMR 3000LM FST MVOLT 35K 80CRI WH SURFACE CEILING LED 19 VA 2,500 DIFFUSE

H1E LENSED STRIP, LOW WATTS, EM BATTERY COLUMBIA LCL4-35LW-EU-ELL14 LITHONIA ZL1D L48 SMR 3000LM FST MVOLT 35K 80CRI WHE7W SURFACE CEILING LED 19 VA 2,500 DIFFUSE

H2 LENSED STRIP, MEDIUM OUTPUT COLUMBIA LCL4-35ML-EU LITHONIA ZL1D L48 SMR 5000LM FST MVOLT 35K 80CRI WH SURFACE CEILING LED 42 VA 5,000 DIFFUSE

H2E LENSED STRIP, MEDIUM OUTPUT, EM BATTERY COLUMBIA LCL4-35ML-EU-ELL14 LITHONIA ZL1D L48 SMR 5000LM FST MVOLT 35K 80CRI WHE7W SURFACE CEILING LED 42 VA 5,000 DIFFUSE

H3 LENSED STRIP, HIGH OUTPUT COLUMBIA LCL4-35HL-EU + CSHC LITHONIA ZL1D L48 SMR 7000LM FST MVOLT 35K 80CRI WHHC36 SUSPENDED CEILING LED 52 VA 6,000 DIFFUSE

HWE 2FT LENSED STRIP, WET LOCATION, BATTERY COLUMBIA LXEM2-35LW-RFA-EU-ELL14 LITHONIA DMW2 L24 4000LM AFL WD VOLTAGE GZ1 35K 80CRIPS1050 SURFACE SURFACE LED 29 VA 4,000 DIFFUSE

INV-1 MINI INVERTER, 2X4 GRID CEILING MOUNT DUAL LITE LG125-T-I LITHONIA EAC ISSM 125 120/277 RGM RECESSED, GRID CEILING LED 23 VA N/A N/A MOUNT IN CEILING GRID AND CONNECT TO EXTERIOR FIXTURES SHOWN ON PLAN.

INV-2 FLOOR MOUNTED INVERTER FOR THEATER EMERGENCYLIGHTING DUAL LITE DLS-1500-120-A-20-03 FLOOR FLOOR - 600 VA - N/A SEE ONE-LINE DIAGRAM, SHEET E503

J1 1X4 TROFFER, VERY LOW WATTS, VOLUMETRIC,RECTILINEAR LENS COLUMBIA LCAT14-35VWG-R-EDU LITHONIA BLT4 30L SDSM EZ1 LP835 RECESSED, GRID CEILING LED 28 VA 3,000 DIFFUSE

J1E 1X4 TROFFER, VERY LOW WATTS, VOLUMETRIC,RECTILINEAR LENS, EM BATTERY COLUMBIA LCAT14-35VWG-R-EDU-ELL14 LITHONIA BLT4 30L SDSM EZ1 LP835 EL14L RECESSED, GRID CEILING LED 28 VA 3,000 DIFFUSE

J1S SAME AS A1 BUT WITH SURFACE MOUNTING COLUMBIA LCAT14-35VWSM-R-EDU LITHONIA BLTX4 30L SDSM EZ1 LP835 RECESSED, GRID CEILING LED 28 VA 3,000 DIFFUSE

J2 2X2 TROFFER, LOW WATTS, VOLUMETRIC, RECTILINEARLENS COLUMBIA LCAT22-35LWG-R-EDU LITHONIA 2BLT2 33L SDSM EZ1 LP835 RECESSED, GRID CEILING LED 23 VA 2,700 DIFFUSE

J2E 2X2 TROFFER, LOW WATTS, VOLUMETRIC, RECTILINEARLENS, EM BATTERY COLUMBIA LCAT22-35LWG-R-EDU-ELL14 LITHONIA 2BLT2 33L SDSM EZ1 LP835 EL14L RECESSED, GRID CEILING LED 23 VA 2,700 DIFFUSE

J3 2X2 TROFFER, VERY HIGH OUTPUT, VOLUMETRIC,RECTILINEAR LENS COLUMBIA LCAT22-35VLG-R-EDU LITHONIA 2BLT2 48LHE SDSM EZ1 LP835 RECESSED, GRID CEILING LED 39 VA 4,300 DIFFUSE

J3E 2X2 TROFFER, VERY HIGH OUTPUT, VOLUMETRIC,RECTILINEAR LENS, EM BATTERY COLUMBIA LCAT22-35VLG-R-EDU-ELL14 LITHONIA 2BLT2 48LHE SDSM EZ1 LP835 EL14L RECESSED, GRID CEILING LED 39 VA 4,300 DIFFUSE

J3F SAME AS A3 BUT WITH FLANGE KIT COLUMBIA LCAT22-35VLG-R-EDU-FK22 LITHONIA 2BLT2 48LHE SDSM EZ1 LP835 DGA22 RECESSED,GYPSUM CEILING LED 39 VA 4,300 DIFFUSE

J4 2X4 TROFFER, LOW WATTS, VOLUMETRIC, RECTILINEARLENS COLUMBIA LCAT24-35LWG-R-EDU LITHONIA 2BLT4 48L SDSM EZ1 LP835 RECESSED, GRID CEILING LED 36 VA 4,300 DIFFUSE

J4E 2X4 TROFFER, LOW WATTS, VOLUMETRIC, RECTILINEARLENS, EM BATTERY COLUMBIA LCAT24-35LWG-R-EDU-ELL14 LITHONIA 2BLT4 48L SDSM EZ1 LP835 EL14L RECESSED, GRID CEILING LED 36 VA 4,300 DIFFUSE

K 1X4 KITCHEN TROFFER, GASKETED, WITH FLAT LENSINVERTED FOR EASY CLEANING COLUMBIA LJT14-35HLG-FS-A19INVERTED-EDU-G3 LITHONIA GTL 4 48L A19V EZ1 LP835 ABC RECESSED, GRID CEILING LED 45 VA 4,500 DIFFUSE

KE 1X4 KITCHEN TROFFER, GASKETED, WITH FLAT LENSINVERTED FOR EASY CLEANING, EM BATTERY COLUMBIA LJT14-35HLG-FS-A19INVERTED-EDU-G3-ELLI

4 LITHONIA GTL 4 48L A19V EZ1 LP835 ABC EL14L RECESSED, GRID CEILING LED 45 VA 4,500 DIFFUSE

L DECORATIVE UP/DOWN SCONCE AT STAIRWELLS TMS TIA20-44LED-35K-120-FINISH-OP-DIML WALL MATCH EXISTING LED 44 VA 2,000 UP/DOWN

M SURFACE MOUNT CYLINDER WITH FROSTED GLASS LENS SPECTRUM SPC1203LEDGV-37L-35K-DS10X-8200GV-SG-SO-1FGR-SM-PT STONE CL466 FR WH LED SURFACE CEILING LED 23 VA 3,000 DOWN

N WALL MOUNT MAKEUP LIGHT, INCENDESCENT ONLY,CHROME FINISH PROGRESS P3300-15 TRANS GLOBE LYRIC 48” 3208PC WALL/MIRROR CENTER ON MIRROR INCANDESCENT 200 VA - DIFFUSE/FORWA

RDMOUNT IN WALL MIRROR. REFER TO ARCH ELEVATION. PROVIDE LAMPS, + 20% SPARELAMPS.

P2 POST-TOP POLE FIXTURE, TYPE 2 DISTRIBUTION, WITHGLARE-REDUCING LENS STERNBERG PT-SL660-SV1-84L35K-T2-MDL05-UWH +

RSA10A500-2401-5-(2)GFI-UWH 10' POLE + 2' BASE 14' TOTAL (FIXTURE IS2' TALL) LED 140 VA 10,300 TYPE 2 0-10V DIMMING, TWO RECEPTACLES IN POLE

P4 POST-TOP POLE FIXTURE, TYPE 4 DISTRIBUTION, WITHGLARE-REDUCING LENS STERNBERG PT-SL660-SV1-84L35K-T4-MDL05-UWH +

RSA10A500-2401-5-(2)GFI-UWH 10' POLE + 2' BASE 14' TOTAL (FIXTURE IS2' TALL) LED 140 VA 10,300 TYPE 4 0-10V DIMMING

PB POST-TOP BOLLARD MATCHING POLE FIXTURES STERNBERG BL-4-SL360-SV1-26L35K-T4-F-MDL03-UWH BOLLARD 4' LED 30 VA 2,200 TYPE 4 WIRE FOR 0-10V DIMMING

Q1 1 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, WALL MOUNT PRIMUS PL-PWL-4-A-1 FT WALL 18" AFF LED 1 VA N/A N/A

Q3 3 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, WALL MOUNT PRIMUS PL-PWL-4-A-3 FT WALL 18" AFF LED 3 VA N/A N/A

R22 22 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, CARPET-TO-WALL MOUNT PRIMUS PL-C/W-4-A-22 FT FLOOR FLOOR LED 22 VA N/A N/A LENGTHS SHOWN ARE SLIGHTLY LONGER THAN REQUIRED. FIXTURE IS FIELD CUTTABLE

TO EXACT LENGTH.

R24 24 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, CARPET-TO-FLOOR MOUNT PRIMUS PL-C/F-4-A-24 FT FLOOR FLOOR LED 24 VA N/A N/A LENGTHS SHOWN ARE SLIGHTLY LONGER THAN REQUIRED. FIXTURE IS FIELD CUTTABLE

TO EXACT LENGTH.

R26 26 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, CARPET-TO-FLOOR MOUNT PRIMUS PL-C/F-4-A-26 FT FLOOR FLOOR LED 26 VA N/A N/A LENGTHS SHOWN ARE SLIGHTLY LONGER THAN REQUIRED. FIXTURE IS FIELD CUTTABLE

TO EXACT LENGTH.

R41 41 FT RUN OF THEATER AISLE LIGHT, LEDS 4" ON CENTER,AMBER, CARPET-TO-FLOOR MOUNT PRIMUS PL-C/F-4-A-41 FT FLOOR FLOOR LED 41 VA N/A N/A LENGTHS SHOWN ARE SLIGHTLY LONGER THAN REQUIRED. FIXTURE IS FIELD CUTTABLE

TO EXACT LENGTH.

S4 4 FT THEATER STAIR EDGE LIGHT, LEDS 4" ON CENTER,AMBER PRIMUS PL-LSL-4-A-4 FT STAIR TREAD FLOOR LED 4 VA N/A N/A PROVIDE FIXTURE MANUFACTURER'S SURFACE WIREWAY AND ENDCAPS AS NEEDED

FOR COMPLETE AND FUNCTIONAL SYSTEM.

T STRAIGHT SURFACE MOUNT TRACK, AIMABLE HEADS, WIDEBEAM SPREAD, 90+ CRI ELCO ET756DW + TRACK + 2.5A LIMITER TRACK CEILING LED 15 VA 1,000 ADJUSTABLE 120 VOLT ACCEPTABLE. INCLUDE SURFACE MOUNTED LINE VOLTAGE TRACK PER PLAN,

PLUS ONE 2.5 AMP CURRENT LIMITER PER RUN

U 6" RECESSED DOWNLIGHT, DMX CONTROL, BLACK BAFFLE PRESCOLITE LF6SL11L-120-DMX-6LFSL-11L-30K-BNCTB-DL JUNO LRM6 13LM 30K MVOLT G3 80CRI DMXR BAF BL RECESSED, GRID CEILING LED 14 VA 1,000 DOWN CONTROL BY THEATRICAL DMX SYSTEM.

V1 CYLINDER, LOWER OUTPUT, DMX CONTROL, WIDE BEAMSPREAD, DIFFUSING LENS, 30K METEOR CSS-30-308-UNV-DMX-WD-BLK-AD10-DF GOTHAM ICO CYL 30/20 6AR LSS 70D MVOLT EDXB ACC DBL SUSPENDED MATCH EXISTING LED 30 VA 2,000 WIDE FLOOD

V2 CYLINDER, MEDIUM OUTPUT, DMX CONTROL, WIDE BEAMSPREAD, DIFFUSING LENS, 30K METEOR CSS-50-308-UNV-DMX-WD-BLK-AD10-DF GOTHAM ICO CYL 30/40 6AR LSS 70D MVOLT EDXB ACC DBL SUSPENDED MATCH EXISTING LED 50 VA 4,000 WIDE FLOOD

V3 CYLINDER, HIGH OUTPUT, DMX CONTROL, WIDE BEAMSPREAD, DIFFUSING LENS, 30K METEOR CSS-90-308-UNV-DMX-WD-BLK-AD10-DF GOTHAM ICO CYL 30/70 6AR LSS 70D MVOLT EDXB ACC DBL SUSPENDED MATCH EXISTING LED 90 VA 7,000 WIDE FLOOD

W WALL SCONCE WITH GLARE REDUCING LENS STERNBERG 1W-SL270-SV1-36L35T3R-MDL03/UWH EXTERIOR WALL MATCH EXISTING LED 43 VA 3,500 TYPE 3

WE WALL SCONCE WITH GLARE REDUCING LENS, EM BATTERY STERNBERG 1W-SL270-SV1-36L35T3R-MDL03-EM/UWH EXTERIOR WALL MATCH EXISTING LED 43 VA 3,500 TYPE 3

Y NARROW LINEAR LENSED, WET LOCATION AXIS WBWLED-500-80-35-S-4-W-UNV-DP-1 PAL ML3WL D MO K35 4 W LOH F01M EF 120 DIM1 WALL SURFACE TRELLIS LED 22 VA 2,000 DIFFUSE

Z MINI AIMABLE FLOODLIGHT FOR TREE SCULPTURE HUBBELL MBUL-1L3K-1 FOCUS DL-21-BLT/FA-24/BRS / INCLUDE LED LAMPS GROUND,CONCRETE GROUND LED 13 VA 1,000 FLOOD, AIMABLE

Mar

kD

ate

Des

crip

tion

18/

24/1

7AD

DEN

DU

M 1

EXISTING LTG FIXTURE SCHEDULETYPE DESCRIPTION MOUNTING LAMP

X12.A 11"X11" GLASS LENSED DOWNLIGHT RECESSED - GYP.

X12.B1 2'X2' RECESSED LENSED TROFFER, TO BE REINSTALLED RECESSED - GYP.

X74.A1 2'X4'PENDANT TROFFER PENDANT 4x34W T12

X74.B1 EXISTING 1X4 RECESSED TROFFER PENDANT/SURFACE 2x34W T12

X74.EM EXISTING EMERGENCY LIGHT WALL

X74.F 4' FLUORESCENT STRIP PENDANT/SURFACE 2x34W T12

X74.FE 4' FLUORESCENT STRIP PENDANT/SURFACE 2x34W T12

X74.G 1'X4' PENDANT PENDANT 2x34W T12

X74.H 8" RECESSED DOWNLIGHT RECESSED

X74.J 8" RECESSED DOWNLIGHT RECESSED

X74.K PENDANT CYLINDER PENDANT/SURFACE

X74.K1 PENDANT CYLINDER PENDANT/SURFACE

X74.KA EXISTING WALL MOUNTED STEP LIGHT IN CORRIDOR BELOWSEATING RECESSED WALL

X74.M PENDANT/RECESSED CYLINDER PENDANT

X74.P TRACK LIGHT SURFACE

X74.P1 PENDANT CYLINDER PENDANT/SURFACE

X74.Q PENDANT CYLINDER PENDANT

X74.R 4' FLUORESCENT WALL MOUNT WALL 2x34W T12

X74.U CATWALK LIGHTING PENDANT

X74.V UP/DOWN CYLINDER WALL

X74.Y PENDANT CYLINDER PENDANT

X74.Z WALL MOUNT VANITY STRIP WALL/MIRROR 8x 40W

X74.Z 8" RECESSED DOWNLIGHT

X76.1 2'X4' RECESSED LENSED TROFFER RECESSED - GRID 4 x 32W T12

X76.2 2'X2' RECESSED LENSED TROFFER RECESSED - GRID 2 x 32W T8

X76.2E 2'X2' RECESSED LENSED TROFFER W/ EMERG. RECESSED - GRID 2 x 32W T8

X76.4 PENDANT WALLWASH SURFACE - STRUCTURE

X76.5 PENDANT CYLINDER SURFACE - STRUCTURE

X76.6 SURFACE MOUNT LENSED 8"X8' SURFACE - GRID OR PENDANT 2 x 75W F96T12

X76.7 SURFACE MOUNT LENSED 8"X8' PENDANT 2 x 75W F96T12

x76.8 SINGLE BULB WALL

x76.10 1' RECESSED DOWNLIGHT, WET LISTED RECESSED

X76.11 SURFACE MOUNT LENSED 8"X8' WET LISTED SURFACE - GRID 4x34W T12

X76.11E SURFACE MOUNT LENSED 8"X8' WET LISTED SURFACE - GRID 4x34W T12

X76.13 8" RECESSED DOWNLIGHT

X76.15 11"X11" GLASS LENSED DOWNLIGHT RECESSED - GRID

X76.EX

X76.P TRACK LIGHT SURFACE

X.1 SURFACE MOUNT 1'X4' LENSED SURFACE 2x34W T12

XS EXISTING GLOBE STYLE POST-TOP POLE FIXTURE, TO BE REMOVEDE

XW EXTERIOR WALL PACK TO BE REMOVED

1

1