Feeder Terminal
Buyer’s Guide
REF 541,REF 543,REF 545.
8/19/2019 Relay 543 - 545 Manual (2)
2/76
8/19/2019 Relay 543 - 545 Manual (2)
3/76
3
Feeder Terminal REF 541, REF 543, REF 545.
Features • Feeder terminal for protection, control,measurement and supervision of medium
voltage networks.
• Voltage and current measurement via con-ventional measuring transformers or cur-
rent sensors and voltage dividers.
• Fixed human-machine interface including a
large graphic display, or an external display
module for flexible switchgear installation.
• Protection functions including e.g. non-
directional and directional overcurrent and
earth-fault protection, residual voltage,
overvoltage and undervoltage protection,
thermal overload protection, CBFP and
auto-reclosing.
• Control functions including local andremote control of switching objects with
synchro-check, status indication of the
switching objects and interlockings on bay
and station level
• Measurement of phase currents, phase-to-
phase and phase-to-neutral voltages, neu-
tral current and residual voltage, frequency,
power factor, active and reactive power
and energy.
• Advanced power quality measurement
capabilities. Total harmonic distortion
(THD) measurements for both currents and
voltages. Measurement for short durationvoltage variations like sags, swells and
short interruptions.
• Condition monitoring including circuit-
breaker condition monitoring, trip circuit
supervision and internal self-supervision of
the feeder terminal.
• Time synchronization via binary input. Syn-
chronization pulse once per second or
once per minute.
• Fault locator for short circuits in all kinds of
network and for earth-faults in effectively
earthed and low resistance/low reactanceearthed networks.
• Additional functions including synchro-
check, frequency protection, capacitor
bank protection and control.
• RTD/analogue module for temperaturemeasurement, current/voltage measure-
ment and mA-outputs.
• Communication over three communication
interfaces: one for local communication
with a PC and two for simultaneous dual
port communication for e.g. a substation
communication system and a substation
monitoring system.
• Selectable function block naming: ANSI
device numbers, IEC symbols or ABB nam-
ing.
• Support for IEC 61850 protocol through theSPA-ZC 400 adapter.
• Support for Profibus-DPV1 protocol
through the SPA-ZC 302 adapter
• Part of the ABB Distribution Automation
system.
Fig. 1 Setting group example window.
1MRS750443-MBGIssued: June 1999Status: UpdatedVersion: F/06.07.2005Data subject to change without notice
8/19/2019 Relay 543 - 545 Manual (2)
4/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
4
Appl ication The REF 541, REF 543 and REF 545 feederterminals are designed to be used for protec-tion, control, measurement and supervision ofmedium voltage networks.
They can be used with different kinds ofswitchgear including single busbar, double
busbar and duplex systems. The protectionfunctions also support different types of net-works such as isolated neutral networks, reso-nant-earthed networks and partially earthednetworks..
Fig. 2 Distributed protection and control systembased on REF 54_ feeder terminals.
Application area also covers protection func-tions for a large variety of applications, e.g.frequency and voltage based protection,motor protection, thermal overload protec-tion, capacitor bank protection and synchro-check/voltage check function.
In addition to protection, measurement, con-trol and condition monitoring functions, thefeeder terminals are provided with a largeamount of PLC functions allowing severalautomation and sequence logic functionsneeded for substation automation to be inte-grated into one unit.
The data communication properties includethe following communications: SPA bus,LON bus, IEC 60870-5-103, IEC 61850,
Profibus-DPV1, DNP 3.0 or Modbus commu-nication with higher-level equipment. Fur-ther, LON communication, together withPLC functions, minimizes the need for hard-wiring between the units.
Design The feeder terminals REF 541, REF 543 andREF 545 differ from each other regarding thenumber of digital inputs and outputs avail-able. Please, refer to section “Ordering” formore details.
The REF 54_ feeder terminals incorporate awide range of feeder terminal functions:
• Protection functions
• Measurement functions
• Disturbance recorder
• Power quality functions
• Control functions
• Fault locator
• Condition monitoring functions
• General functions
• Communication functions
• Standard functions
The function blocks are documented on theCD-ROM “Technical Descriptions of Func-tions” (1MRS 750889-MCD).
Protection functionsProtection is one of the most important func-tions of the REF 54_ feeder terminal. The
protection function blocks (e.g. NOC3Low)are independent of each other and have e.g.their own setting groups and data recording.The non-directional overcurrent protectionincludes e.g. the three stages NOC3Low,
NOC3High and NOC3Inst, each with inde- pendent protection functions.
Either Rogowski coils or conventional cur-rent transformers can be used for protectionfunctions based on current measurement.
Correspondingly, voltage dividers or voltagetransformers are used for protection functions
based on voltage measurement
For further information about functionalitylevels and the protection functions includedin them, refer to the table “Functionality lev-els, protection functions” in section“Ordering”.
Measurement functionsThe measurement functions include three-
phase currents, neutral current, three-phase
voltages, residual voltage, frequency, active
8/19/2019 Relay 543 - 545 Manual (2)
5/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
5
and reactive power and power factor. In addi-tion, other measurement functions are avail-able.
As a standard feature the REF 54_ terminal
includes pulse counter inputs. The number of pulse inputs varies from 7 (REF 541) to 10(REF 545) according to the REF variant.
Disturbance recorder The transient disturbance recorder is able torecord 16 current or voltage waveforms and16 logic digital signals. The sampling fre-quency of the analogue inputs is 2 kHz at therated frequency of 50 Hz and 2.4 kHz at therated frequency of 60 Hz.
The user can set the length of a recording
within a range determined by the number ofanalogue inputs used. The number of record-ings depends on the sampling frequency,length of recordings and number of analogueinputs.
The recordings can be uploaded with a DR-Collector Tool which converts the data to aCOMTRADE format. The DR-Collector Toolis supported in CAP501 and CAP505 relaytools.
Power quality functionsPower quality functions enable measurement
of total harmonic distortion (THD) of voltageand current, and total demand distortion(TDD) of current. Individual harmonics aremeasured up to 13th.
Power quality functions also include mea-surement of short duration voltage variationslike sags, swells and short interruptions. Mea-surements are done according to the IEC stan-dard 61000-4-30.
LIB 510 supports tools for presentation ofharmonics and short duration voltage varia-tions.
Control functionsThe control functions are used to indicate the
position of switching devices, i.e. circuit breakers and disconnectors, and to executeopen and close commands for controllableswitching devices in the switchgear. Further-more, there are supplementary functions forcontrol logic purposes, e.g. on/off switches,MIMIC alarm, LED control, numerical datafor the MIMIC and logic controlled positionselection.
The control functions configured using the Relay Configuration Tool can be associatedwith position indicators that are part of the
MIMIC configuration picture displayed onthe HMI. Position indicators are used to indi-cate the position of switching devices via theMIMIC picture and to control them locally.The status of different objects, e.g. open/close/undefined, displayed in the MIMICview can be freely designed.
Fault locator The fault locator function for radial distribu-tion systems. Short-circuit localization in allkind of distribution networks. Earth-faultlocalization in effectively earthed networksand in low reactance/low resistance earthednetworks. Assists fast power restoration afterthe fault. Improves system availability and
performance.
Condition monitoring functionsCondition monitoring function blocks such assupervision of the energizing current andvoltage input circuit, operation time counter,circuit breaker electric wear, scheduled main-tenance, trip circuit supervision and breakertravel time are available for the REF 54_feeder terminals.
General functionsAdditional functions are available for differ-ent general purposes to be used in logics such
as activation of HMI backlight, switchgroups,and resetting of operation indications, latchedoutput signals, registers and disturbancerecorder.
Communication functionsThe REF 54_ feeder terminal provides theIEC 60870-5-103, IEC 61850, Profibus-DPV1, Modbus, DNP 3.0, SPA and LONserial communication protocols.
In a customer-specific feeder terminal config-uration, special events can be generated via
an EVENT230 event function.
Standard functionsStandard functions are used for logics such asinterlocking, alarming and control sequenc-ing. The use of logic functions is not limitedand the functions can be interconnected witheach other as well as with protection, mea-surement, power quality, control, conditionmonitoring and general functions. In addition,the digital inputs and outputs as well as LONinputs and outputs can be connected to stan-dard functions by using the Relay Configura-
tion Tool.
8/19/2019 Relay 543 - 545 Manual (2)
6/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
6
Other functions
Low auxiliary voltage indicationThe REF 54_ feeder terminal is providedwith a low auxiliary voltage indication fea-ture. The power supply module issues aninternal alarm signal when a drop in the
power supply voltage is detected (ACFail,active low). The alarm signal is activated ifthe power supply voltage falls about 10%
below the lowest rated DC input voltage ofthe power supply module.
The indication of a low auxiliary voltage isavailable in the feeder terminal configurationand can be connected to any signal output ofthe REF 54_.
Overtemperature indicationThe REF 54_ feeder terminal includes aninternal temperature supervision function.The power supply module issues an internalalarm signal when overtemperature has beendetected inside the terminal enclosure. Thealarm signal will be activated once the tem-
perature inside the terminal enclosureincreases to +78°C (+75°...+83°C). Over-temperature indication is available in thefeeder terminal configuration and can be con-nected to any signal output of the terminal.
Analog channels
The feeder terminal measures the analoguesignals needed for protection, measuring, etc.via sensors or galvanically separated match-ing transformers.
Depending on whether sensors are includedor not, REF 54_ feeder terminals have 9(without sensors) or 10 (with sensors) ana-logue channels. The number of channels useddepends on the feeder terminal configurationand the kind of matching transformers or sen-sor inputs used. Furthermore, the feeder ter-minal includes virtual analogue channels for
calculating the phase-to-phase voltages, neu-tral current and residual voltage from phasecurrents and voltages.
In addition to 9 conventional matching trans-formers, sensors developed by ABB can beused parallel in REF 54_ feeder terminals.The feeder terminal has 9 sensor inputs. Acurrent sensor (Rogowski coil) or a voltagedivider can be connected to each sensor input.Please, see the connection diagram fordetails. When ordering, please note the typeof analogue inputs.
Each analog channel is separately configuredwith the Relay Configuration Tool. Both themeasuring unit for each analog channel andthe type of signal to be measured are to beconfigured.
A separate scaling factor can be set for eachanalogue channel. The factors enable differ-ences between the ratings of the protectedunit and those of the measuring device (CTs,VTs etc.). The setting value 1.00 means thatthe rated value of the protected unit is exactlythe same as that of the measuring device.
Calculated analogue channelsThe REF 54_ feeder terminal includes virtualchannels to obtain phase-to-phase voltages,neutral current and residual voltage when
sensors are used. Sensors are connected to thefeeder terminal via coaxial cables and there-fore a residual connection of phase currentsor an open-delta connection of phase voltagescannot be made. Both the amplitude and the
phase angle are calculated for the virtualchannels.
Though primarily meant to be used with sen-sors, the calculated analogue channels canalso be used with conventional current andvoltage transformers.
Note! When sensitive earth-fault protection is
needed, core balance transformers are notrecommended to be replaced with the numer-ically derived sum of phase currents. Nor-mally, an earth-fault setting below 10% of therated value requires the use of a core balancetransformer.
Digital inputsThe digital inputs of the feeder terminals arevoltage-controlled and optically isolated. Thefunction of a digital input can be inverted.The programmable filter time removesdebounces and short disturbances on a digital
input. The filter time can be set for each digi-tal input separately.
Some specific digital inputs can be pro-grammed to operate either as digital inputs, as
pulse counters or as used for time synchroni-zation. When a digital input operates as a
pulse counter, pulse counting frequency can be up to100 Hz.
Oscillation suppression
The feeder terminals have two global parame-ters for the suppression of digital input oscil-lation. The settings of these parameters
8/19/2019 Relay 543 - 545 Manual (2)
7/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
7
determine the oscillation level and hysteresisfor all digital inputs. Event is generated incase oscillation is detected.
At tr ibutes of a dig ital input for feeder ter-minal configurationFor each digital input, the status of the input(value), the time tag for the status change(time) and the validity of the digital input(invalidity) can be issued by the attributes.These attributes are available in the feederterminal configuration and can be used forvarious purposes.
RTD/analogue inputs
The REF 541 and REF 543 feeder terminalsequipped with an RTD/analogue module(RTD1) have eight general purpose analogue
inputs for DC measurement. The RTD/ana-logue inputs are galvanically isolated fromthe feeder terminal power supply and enclo-sure. However, the inputs have a commonground. The general purpose RTD/analogueinputs accept voltage-, current- or resistance-type signals. For each measuring mode, aseparate parameter is provided for choosing
between the available measurement ranges.RTD/analogue inputs can be applied for e.g.temperature measurement.
Digital outputsThe outputs of the feeder terminal are catego-
rized as follows:
• HSPO: High-speed power output, double- pole contact, preferred for tripping pur- poses and for circuit breaker and discon-nector control
• PO: Power output, either single-pole ordouble-pole contact, preferred for circuit
breaker and disconnector control
• SO: Signal output, either NO (NormallyOpen) or NO/NC (Normally Open/Nor-
mally Closed) contact. The output contactis a normal-duty contact and cannot beused for controlling a heavy load such as acircuit breaker.
Analogue outputsThe REF 541 and REF 543 feeder terminalsequipped with an RTD/analogue module havefour general purpose 0...20 mA analogue cur-rent outputs. All outputs are galvanically iso-lated from the supply and enclosure of thefeeder terminal and from each other.
Analogue outputs can be utilized for transfer-
ring any measured or calculated informationto panel meters or e.g. PLCs.
Alarm LED indicatorsThe feeder terminal offers eight alarm LEDindicators to be configured with the RelayMimic Editor. The LED colours (green, yel-low, red), their use, and the ON and OFF statetexts can be freely defined. Three basic oper-ation modes are supported: non-latched,latched-steady and latched flashflashing.Alarms can be acknowledged remotely,locally or by using logic of the feeder termi-nal.
The alarm channels include time tagging fordetected alarms. The time tagging principleused depends on the operation mode.
Interlocking LED indicator The interlocking LED indicates that control
operation has been interlocked or that theinterlocking is in bybass mode, e.g. whencontrol is possible despite of interlocking.
Trip Circuit SupervisionThe purpose of this function is to supervisethe tripping circuitry of the circuit breaker.An alarm will be generated in case a faultytripping circuit, e.g. a circuit is not able to
perform a trip, is detected.
The supervision is based on the constant-cur-rent injection through the tripping circuitry.
Display panelThe feeder terminal is provided with either afixed display or an external display module.The external display module requires a sepa-rate voltage supply from a common sourcewith the main unit. The display consists of 19rows divided into two windows: a main win-dow (17 rows) and an assisting window(2 rows).
The graphic display presents detailed infor-mation on MIMIC, objects, events, measure-ments, control alarms, and parameters. The
assisting window is used for terminal-depen-dent indications/alarms and help messages.
Additionally, the panel includes the followingHMI items:
• three push-buttons for object control (I, O,object selection)
• eight freely programmable alarm LEDswith different colours and modes accord-ing to the configuration
• LED indicator for control interlocking
• three protection LED indicators
• HMI push-button section with four arrow buttons and buttons for clear and enter
8/19/2019 Relay 543 - 545 Manual (2)
8/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
8
• optically isolated serial communication port
• backlight and contrast control
• freely programmable button (F) which can
be used in the configuration of the feederterminal
• a button for remote/local control
HMI has two main levels, the user level andthe technical level. The user level is for“everyday” measurements and monitoringwhereas the technical level is intended foradvanced feeder terminal programming.
Serial communicationThe feeder terminal has three serial commu-nication ports, one on the front panel and twoon the rear panel.
Front panel opti cal connection for PCThe front panel is intended for the connectionof a PC for configuring the feeder terminalwith the CAP 50_ tools. The front interfaceuses the SPA bus protocol.
The optical connector on the front panel iso-lates the PC galvanically from the feeder ter-minal. The front connector for the PC isstandardized for ABB relay products andrequires a specific opto cable. The cable isconnected to the serial RS-232 port of the PC.The other communication parameters for the
rear RS-485 interface are also set in the Com-munication menu of the REF 54_ feeder ter-minal.
SPA/IEC_103 communication on the rearconnector X3.2The 9-pin D-type subminiature male connec-tor (RS-232 connection) on the rear panelconnects the feeder terminal to the distribu-tion automation system via the SPA bus or theIEC_103. The fibre-optic interface moduletype RER 123 is used for connecting thefeeder terminal to the fibre-optic communica-
tion bus for SPA and IEC_103 protocol.
DNP3.0/Modbus communication on therear connector X3.2
The 9-pin D-type subminiature male connec-tor (RS-232 connection) on the rear panelconnects the feeder terminal to the distribu-tion automation system via the DNP 3.0 orthe Modbus protocol. The interface betweenthe feeder terminal and a RS-485 communi-cation bus can be made through the RER 133Bus Connection Module. The interface
between the feeder terminal and an optical bus can be made through the RER 123 Bus
Connection Module.
IEC 61850 communication using SPA-ZC400 on the rear connector X3.2
The 9-pin D-type subminiature male connec-tor (RS-232 connection) on the rear panelconnects the feeder terminal to the distribu-
tion automation system via the IEC 61850 protocol. In the IEC 61850 mode, the SPA-ZC 400 Bus Connection Module is needed.
Profibus-DPV1 communication using SPA-ZC 302 on the rear connector X3.2The 9-pin D-type subminiature male connec-tor (RS-232 connection) on the rear panelconnects the feeder terminal to the distribu-tion automation system via the Profibus pro-tocol. The interface between the feederterminal and Profibus can be made throughthe SPA-ZC 302 Gateway.
LON/SPA bus communication on the rearconnector X3.3
The 9-pin D-type subminiature female con-nector (RS-485 connection) on the rear panelconnects the feeder terminal to the substationautomation system via the SPA bus or theLON bus. The fibre-optic interface moduletype RER 103 is used to connect the feederterminal to the fibre-optic communication
bus. The RER 103 module supports both SPA bus and LON bus communication.
Self-supervisionThe feeder terminal REF 54_ is providedwith an extensive self-supervision system.The self-supervision system handles run-timefault situations and informs the user of faultsvia the HMI and LON/SPA bus communica-tion.
When a fault has been detected, the greenReady indicator starts flashing, a fault indica-tion text is displayed on the HMI and anevent 0/E57 is generated. The fault indicationtext on the HMI consists of two rows: a gen-eral message ‘internal fault’, followed by the
generated IRF code of the fault.
The relay will try to recover from a faulteither by restarting the module (I/O moduleor HMI) that reported the fault, or by restart-ing the whole relay. During restarting the IRFstate will remain active until the internal self-supervision program has determined that therelay is operating normally. If the fault is still
persistent after restarting three times, therelay will be in permanent IRF state.
8/19/2019 Relay 543 - 545 Manual (2)
9/76
8/19/2019 Relay 543 - 545 Manual (2)
10/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
10
Profibus is available through the SPA-ZC 302Gateway and IEC 61850 is available throughthe SPA-ZC 400 Ethernet Adapter
The serial interface RS-485 on the rear panelis used for connecting the feeder terminal tothe SPA bus or the LON bus. The SPA/LON
bus is connected via the RER 103 ConnectionModule fitted to the 9-pin D-type subminia-ture connector and screwed to the rear panel.
The digital input and output contacts of thefeeder terminal are connected to the multi-
pole connectors.
Protective earth is connected to the screwmarked with the earth symbol.
Basic connection diagrams
A050202
Fig. 3 Basic connection diagram of REF 541.
8/19/2019 Relay 543 - 545 Manual (2)
11/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
11
A050203
Fig. 4 Basic connection diagram of REF 543.
8/19/2019 Relay 543 - 545 Manual (2)
12/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
12
A050204
Fig. 5 Basic connection diagram of REF 545.
8/19/2019 Relay 543 - 545 Manual (2)
13/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
13
A050205
Fig. 6 Terminal diagram of the RTD/analog module
Auxi liary vol tageFor its operation, the REF 54_ terminal,including the external display module,requires a secured auxiliary voltage supply.The feeder terminal’s internal power supplymodule forms the voltages required by thefeeder terminal electronics. The power supply
module is a galvanically isolated (fly-backtype) dc/dc converter. A green protectionLED indicator on the front panel is lit whenthe power supply module is in operation.
The feeder terminal is provided with a 48-hour capacitor back-up protection thatenables the internal clock to keep time in caseof an auxiliary power failure.
Power supplyThere are two basic types of power supply
modules available for the REF 54_: typePS1/_ and type PS2/_. See Tecnical data table9.The operating range of digital inputsdepends on the type of the power supplymodule. See Technical data table 10.
8/19/2019 Relay 543 - 545 Manual (2)
14/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
14
Technical data .
Table 1: General functions
Function Description
INDRESET Resetting of operation indicators, latched output signals, registers
and waveforms i.e. the disturbance recorder
MMIWAKE Activation of HMI backlight
SWGRP1 Switchgroup SWGRP1
SWGRP2 Switchgroup SWGRP2
SWGRP3 Switchgroup SWGRP3
... ...
SWGRP20 Switchgroup SWGRP20
Table 2: Standard functions
Function Description
ABS Absolute value
ACOS Principal arc cosine ADD Extensible adder
AND Extensible AND connection
ASIN Principal arc sine
ATAN Principal arc tangent
BITGET Get one bit
BITSET Set one bit
BOOL_TO_* Type conversion from BOOL to WORD / USINT / UINT / UDINT /
SINT / REAL / INT / DWORD / DINT / BYTE
BOOL2INT Type conversion from BOOL inputs to INT output
BYTE_TO_* Type conversion from BYTE to WORD / DWORD
COMH Hysteresis comparator
COS Cosine in radians
CTD Down-counter
CTUD Up-down counter
CTU Up-counter
DATE_TO_UDINT Type conversion from DATE to UDINT
DINT_TO_* Type conversion from DINT to SINT / REAL / INT
DIV Divider
DWORD_TO_* Type conversion from DWORD to WORD / BYTE
EQ Extensible comparison to equal
EXP Natural exponential
EXPT Exponentiation
F_TRIG Falling edge detector
GE Extensible comparison to greater or equal
GT Extensible comparison to greater INT_TO_* Type conversion from INT to REAL / DINT
INT2BOOL Type conversion from INT input to BOOL outputs
LE Extensible comparison to less or equal
LIMIT Limitation
LN Natural logarithm
LOG Logarithm base 10
LT Extensible comparison to less
MAX Extensible maximum
MIN Extensible minimum
MOD Modulo
MOVE Move
MUL Extensible multiplier
MUX Extensible multiplexer
8/19/2019 Relay 543 - 545 Manual (2)
15/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
15
1) This function is only supported in the feeder terminalrevisions of Release 2.0 or later.
NE Comparison to greater or less
NOT Complement
OR Extensible OR connection
R_TRIG Rising edge detector
REAL_TO_* Type conversion from REAL to USINT / UINT / UDINT / SINT / INT /
DINT
ROL Rotate to left
ROR Rotate to right
RS Reset dominant bistable function block
RS_D Reset dominant bistable function block with data input
SEL Binary selection
SHL Bit-shift to left
SHR Bit-shift to right
SIN Sine in radians
SINT_TO_* Type conversion from SINT to REAL / INT / DINTSUB Subtractor
SQRT Square root
SR Set dominant bistable function block
XOR Extensible exclusive OR connection
TAN Tangent in radians
TIME_TO_* Type conversion from TIME to UDINT / TOD / REAL
TOD_TO_* Type conversion from TOD to UDINT / TIME / REAL
TOF Off-delay timer
TON On-delay timer
TP Pulse
TRUNC_* Truncation toward zero
UDINT_TO_* Type conversion from UDINT to USINT / UINT / REAL
UINT_TO_* Type conversion from UINT to USINT / UDINT / REAL / BOOL
USINT_TO_* Type conversion from USINT to UINT / UDINT / REAL
WORD_TO_* Type conversion from WORD to DWORD / BYTE
Table 3: Condition monitoring functions
Function ANSIdevice no.
IECsymbol
Description
CMBWEAR1 CB wear1 CB wear1 Circuit-breaker electric wear 1
CMBWEAR2 CB wear2 CB wear2 Circuit-breaker electric wear 2
CMCU3 MCS 3I MCS 3I Supervision function of the energizing current input circuit
CMGAS1 CMGAS1 GAS1 Gas pressure monitoring
CMGAS3 1) CMGAS3 GAS3 Three-pole gas pressure monitoring
CMSCHED CMSCHED SCHED Scheduled maintenanceCMSPRC1 CMSPRC1 SPRC1 Spring charging control 1
CMTCS1 TCS1 TCS1 Trip circuit supervision 1
CMTCS2 TCS2 TCS2 Trip circuit supervision 2
CMTIME1 TIME1 TIME1 Operate time counter 1 for the operate time used (e.g. motors)
CMTIME2 TIME2 TIME2 Operate time counter 2 for the operate time used (e.g. motors)
CMTRAV1 CMTRAV1 TRAV1 Breaker travel time 1
CMVO3 MCS 3U MCS 3U Supervision function of the energizing voltage input circuit
Table 2: Standard functions
Function Description
8/19/2019 Relay 543 - 545 Manual (2)
16/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
16
.
1) This function is only supported in the feeder terminalrevisions of Release 2.0 or later.
Table 4: Control funct ions
Function ANSI
device no.
IEC symbol Description
CO3DC1 CO3DC1 IO 3DC1 Three-state disconnector (1) with indication
CO3DC2 CO3DC2 IO 3DC2 Three-state disconnector (2) with indication
COCB1 COCB1 IO CB1 Circuit breaker 1 control with indication
COCB2 COCB2 IO CB2 Circuit breaker 2 control with indication
COCBDIR COCBDIR CBDIR Direct open for CBs via HMI
CODC1 CODC1 IO DC1 Disconnector 1 control with indication
CODC2 CODC2 IO DC2 Disconnector 2 control with indication
CODC3 CODC3 IO DC3 Disconnector 3 control with indication
CODC4 CODC4 IO DC4 Disconnector 4 control with indication
CODC5 CODC5 IO DC5 Disconnector 5 control with indication
COIND1 COIND1 IO IND1 Switching device 1 indication
COIND2 COIND2 IO IND2 Switching device 2 indication
COIND3 COIND3 IO IND3 Switching device 3 indication
COIND4 COIND4 IO IND4 Switching device 4 indication
COIND5 COIND5 IO IND5 Switching device 5 indication
COIND6 COIND6 IO IND6 Switching device 6 indication
COIND7 COIND7 IO IND7 Switching device 7 indication
COIND8 COIND8 IO IND8 Switching device 8 indication
COLOCAT COLOCAT IO POS Logic-controlled control position selector
COPFC 1) 55 COPFC Power factor controller
COSW1 COSW1 SW1 On/off switch 1
COSW2 COSW2 SW2 On/off switch 2
COSW3 COSW3 SW3 On/off switch 3
COSW4 COSW4 SW4 On/off switch 4
MMIALAR1 ALARM1 ALARM1 Alarm channel 1, LED indicator
MMIALAR2 ALARM2 ALARM2 Alarm channel 2, LED indicator
MMIALAR3 ALARM3 ALARM3 Alarm channel 3, LED indicator
MMIALAR4 ALARM4 ALARM4 Alarm channel 4, LED indicator
MMIALAR5 ALARM5 ALARM5 Alarm channel 5, LED indicator
MMIALAR6 ALARM6 ALARM6 Alarm channel 6, LED indicator
MMIALAR7 ALARM7 ALARM7 Alarm channel 7, LED indicator
MMIALAR8 ALARM8 ALARM8 Alarm channel 8, LED indicator
MMIDATA1 MMIDATA1 MMIDATA1 MIMIC data monitoring point 1
MMIDATA2 MMIDATA2 MMIDATA2 MIMIC data monitoring point 2
MMIDATA3 MMIDATA3 MMIDATA3 MIMIC data monitoring point 3
MMIDATA4 MMIDATA4 MMIDATA4 MIMIC data monitoring point 4
MMIDATA5 MMIDATA5 MMIDATA5 MIMIC data monitoring point 5
8/19/2019 Relay 543 - 545 Manual (2)
17/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
17
Power factor cont roller settings
Power factor contro ller, COPFC
The number of capacitor banks to be controlled
The relational step sizes and the type of the switching
sequence
Size of the first capacitor bank (should be the smallest)
Target value for daytime cos ϕ
Day unit
Target value for night-time cos ϕ
Night unit
Setting the reconnection inhibit time (discharge time)
Sensitivity in the inductive side
Sensitivity in the capacitive side
Alarm limit for the maximum reactive power
Alarm limit for the minimum reactive power
Overvoltage limit when the switching in is inhibited
Operation mode
Starting the automatic testing sequenceCalculation method
Control principle
Duration demand
Day&night switch
Manual command
1...4
1:1:1:1 linear; 1:1:1:1 circul.; 1:1:2:2 circul.;
1:2:2:2 linear; 1:2:2:2 circul.; 1:2:4:4 linear;1:2:4:4 circul.; 1:2:4:8
10.0...50000.0 kvar
0.70...1.00
Inductive; Capacitive
0.70...1.00
Inductive; Capacitive
0.5...6000.0 s
60.0...200.0%
0.0...100.0%
0.1...100.0 Mvar
-100.0...0.0 Mvar
0.80...1.60 x Un
Not in use; Automatic mode; Manual mode;
Testing mode
Not activated; StartNormal; Integral
Progressive; Direct
0.5...6000.0 s
Not in use; Digital input; Internal clock;
By setting
Not activated; Remove one step; Add one
step; Disconnect all
Recorded data
Number of switching operations per day
Number of switching operations per week
0...65535
0...65535
Operation accuracies
Accuracy class of operation
±2.0% of set value or ±0.02 x rated value
2.0
Table 5: Measurement funct ions
Function ANSIdevice no.
IECsymbol
Description
MEAI1 2) AI1 AI1 General measurement 1 / analog input on RTD/analog module
MEAI2 2) AI2 AI2 General measurement 2 / analog input on RTD/analog module
MEAI3 2) AI3 AI3 General measurement 3 / analog input on RTD/analog module
MEAI4 2) AI4 AI4 General measurement 4 / analog input on RTD/analog module
MEAI5 2) AI5 AI5 General measurement 5 / analog input on RTD/analog module
MEAI6 2) AI6 AI6 General measurement 6 / analog input on RTD/analog module
MEAI7 2) AI7 AI7 General measurement 7 / analog input on RTD/analog module
MEAI8 2) AI8 AI8 General measurement 8 / analog input on RTD/analog module
MEAO1 2) AO1 AO1 Analog output 1 on RTD/analog module
MEAO2 2) AO1 AO1 Analog output 2 on RTD/analog module
MEAO3 2) AO3 AO3 Analog output 3 on RTD/analog module
MEAO4 2) AO4 AO4 Analog output 4 on RTD/analog module
MECU1A Io Io Neutral current measurement, stage A
MECU1B Io_B Io_B Neutral current measurement, stage B
MECU3A 3I 3I Three-phase current measurement, stage A
MECU3B 2) 3I_B 3I_B Three-phase current measurement, stage B
MEDREC161)
DREC DREC Transient disturbance recorder
8/19/2019 Relay 543 - 545 Manual (2)
18/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
18
1) These functions are only supported in the feeder termi-nal revisions of Release 1.5 or later
2) These functions are only supported in the feeder termi-nal revisions of Release 2.0 or later.
Measurement function settings
MEFR1 f f System frequency measurement
MEPE7 PQE PQE Three-phase power and energy measurementMEVO1A Uo Uo Residual voltage measurement, stage A
MEVO1B 2) Uo_B Uo_B Residual voltage measurement, stage B
MEVO3A 3U 3U Three-phase voltage measurement, stage A
MEVO3B 2) 3U_B 3U_B Three-phase voltage measurement, stage B
Table 5: Measurement funct ions
Function ANSIdevice no.
IECsymbol
Description
General measurement/ analogue input on RTD/analogue module, MEAI1...8 (AI1...AI8)
The general measurement function blocks can be used to measure general purpose dc or ac voltage
signals with a sensor input. They also include a REAL type input which can be used to monitor any internal
REAL type IEC 61131-3 based signal, e.g. input data from the RTD/analogue module.
GE1…3 (V dc/ac)General REAL type input
-10000.00000...10000.00000-10000.00000...10000.00000
Neutral current measurement, MECU1A and MECU1B (Io, Io_B)
Io (A)
Io (%)
0.0…20000.0 A
0.0…80.0% In
Three-phase current measurement, MECU3A and MECU3B (3I, 3I_B)
IL1
IL2
IL3
IL1
IL2
IL3
IL1 demand
IL2 demand
IL3 demand
IL1 demand
IL2 demand
IL3 demand
0.0…20000.0 A
0.0…20000.0 A
0.0…20000.0 A
0.0…1000.0% In
0.0…1000.0% In
0.0…1000.0% In
0.0…20000.0 A
0.0…20000.0 A
0.0…20000.0 A
0.0…1000.0% In
0.0…1000.0% In
0.0…1000.0% In
Transient disturbance recorder f or 16 analogue c hannels, MEDREC16 (DREC)
The transient disturbance recorder MEDREC16 is used for recording the current and voltage waveforms,
as well as the status data of internal IEC 61131-3 based logic signals and digital inputs connected to the
feeder terminals. The maximum number of analogue inputs and logic signals is 16. One fundamental cycle
contains 40 samples.
Operation mode
Pre-trg time
Over limit ILx
Over limit Io
Over limit Iob
Over limit Uo
Over limit Ux
Over limit Uxy
Over limit U12b
Over limit ILxb
Under limit Ux
Under limit Uxy
AI filter time
SaturationOverwrite
Extension
0…100%
0.00…40.00 x In
0.00…40.00 x In
0.00…40.00 x In
0.00…2.00 x Un
0.00…2.00 x Un
0.00…2.00 x Un
0.00…2.00 x Un
0.00…40.00 x In
0.00…2.00 x Un
0.00…2.00 x Un
0.000…60.000 s
8/19/2019 Relay 543 - 545 Manual (2)
19/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
19
Analogue output on RTD/anal ogue module, MEAO1...4 (AO1...AO4)
The analogue output function blocks handle the scaling of any internal REAL type IEC 61131-3 based
signal to fit a selectable 0…20 mA or 4…20 mA range for use with the outputs on the RTD/analogue
module.
General REAL type input -10000.00000...10000.00000
The recording can be triggered by any (or several) of the alternatives listed below:
• triggering on the rising or falling edge of any (or several) of the digital inputs• triggering on overcurrent, overvoltage or undervoltage• manual triggering via the menu or with the push-button F on the front panel (if configured)• triggering via serial communication• periodic triggeringThe recording length depends on the number of recordings and inputs used. For example, the following
combination of recording length, number of recordings and number of inputs is available at 50 Hz:
# recordings \ # inputs 1 3 10
1 1163 cyc.
23.2 s
412 cyc.
8.2 s
126 cyc.
2.5 s
5 232 cyc.
4.6 s
82 cyc.
1.6 s
25 cyc.
0.5 s10 115 cyc.
2.3 s
41 cyc.
0.8 s
12 cyc.
0.24 s
System f requency measurement, MEFR1 (f)
Frequency
Average Freq.
Voltage U
10.00…75.00 Hz
10.00…75.00 Hz
0.0…2.0 x Un
Three-phase power and energy measurement, MEPE7 (PQE)
P3 (kW)
Q3 (kvar)
Power factor DPF
Power factor PF
P3 demand (kW)
Q3 demand (kvar)
Energy kWh
Reverse kWh
Energy kvarh
Reverse kvarh
-999999…999999 kW
-999999…999999 kvar
-1.00…1.00
-1.00…1.00
-999999…999999 kW
-999999…999999 kvar
0…999999999 kWh
0…999999999 kWh
0…999999999 kvarh
0…999999999 kvarh
Residual v oltage measurement, MEVO1A and MEVO1B (Uo, Uo_B)
Uo
Uo
0…150000 V
0.0…120.0% Un
Three-phase voltage measurement, MEVO3A and MEVO3B (3U, 3U_B)
UL1_U12
UL2_U23
UL3_U31
UL1_U12
UL2_U23
UL3_U31
UL1_U12 average
UL2_U23 average
UL3_U31 average
UL1_U12 average
UL2_U23 average
UL3_U31 average
0.00…999.99 kV
0.00…999.99 kV
0.00…999.99 kV
0.00…2.00 x Un
0.00…2.00 x Un
0.00…2.00 x Un
0.00…999.99 kV
0.00…999.99 kV
0.00…999.99 kV
0.00…2.00 x Un
0.00…2.00 x Un
0.00…2.00 x Un
8/19/2019 Relay 543 - 545 Manual (2)
20/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
20
1) These functions are only supported in the feeder termi-nal revisions of Release 1.5 or later.
2) These functions are only supported in the feeder termi-nal revisions of Release 2.0 or later.
3) These functions are only supported in the feeder termi-nal revisions of Release 2.5 or later.
4) This function is only supported in the feeder terminalrevisions of Release 3.5 or later.
Table 6: Protection funct ions
Function ANSIdevice no.
IECsymbol
Description
AR5Func 79 O-->I Auto-reclose function (5 shots)
CUB1Cap 2) 51NC-1 dI>C Current unbalance protection for shunt capacitor banks
CUB3Cap 3) 51NC-2 3dI>C Three-phase current unbalance protection for H-bridge connected
shunt capacitor
CUB3Low 46 Iub> Phase discontinuity protection
DEF2Low 67N-1 Io>--> Directional earth-fault protection, low-set stage
DEF2High 67N-2 Io>>--> Directional earth-fault protection, high-set stage
DEF2Inst 67N-3 Io>>>--> Directional earth-fault protection, instantaneous stage
DOC6Low 1) 67-1 3I>--> Three-phase directional overcurrent protection, low-set stage
DOC6High 1) 67-2 3I>>--> Three-phase directional overcurrent protection, high-set stage
DOC6Inst 1) 67-3 3I>>>--> Three-phase directional overcurrent protection, instantaneous
stage
FLOC 4) 21FL FLOC Fault locator
Freq1St1 1) 81-1 f1 Underfrequency or overfrequency protection, stage 1
Freq1St2 1) 81-2 f2 Underfrequency or overfrequency protection, stage 2
Freq1St3 1) 81-3 f3 Underfrequency or overfrequency protection, stage 3
Freq1St4 1) 81-4 f4 Underfrequency or overfrequency protection, stage 4
Freq1St5 1) 81-5 f5 Underfrequency or overfrequency protection, stage 5
FuseFail 3) 60 FUSEF Fuse failure supervision
Inrush3 68 3I2f> Three-phase transformer inrush and motor start-up current detector
MotStart 2) 48 Is2t n< Three-phase start-up supervision for motors
NEF1Low 51N-1 Io> Non-directional earth-fault protection, low-set stage
NEF1High 51N-2 Io>> Non-directional earth-fault protection, high-set stage
NEF1Inst 51N-3 Io>>> Non-directional earth-fault protection, instantaneous s tage
NOC3Low 51-1 3I> Three-phase non-directional overcurrent protection, low-set stage
NOC3High 51-2 3I>> Three-phase non-directional overcurrent protection, high-set stageNOC3Inst 51-3 3I>>> Three-phase non-directional overcurrent protection, instantaneous
stage
OL3Cap 2) 51C 3I>3I< Three-phase overload protection for shunt capacitor banks
OV3Low 59-1 3U> Three-phase overvoltage protection, low-set stage
OV3High 59-2 3U>> Three-phase overvoltage protection, high-set stage
PSV3St1 2) 47-1 U1U2_1 Phase-sequence voltage protection, stage 1
PSV3St2 2) 47-2 U1U2_2 Phase-sequence voltage protection, stage 2
ROV1Low 59N-1 Uo> Residual overvoltage protection, low-set stage
ROV1High 59N-2 Uo>> Residual overvoltage protection, high-set stage
ROV1Inst 59N-3 Uo>>> Residual overvoltage protection, instantaneous stage
SCVCSt1 1) 25-1 SYNC1 Synchro-check / voltage-check function, stage 1
SCVCSt2 1) 25-2 SYNC2 Synchro-check / voltage-check function, stage 2
TOL3Cab 1) 49F 3Ith> Three-phase thermal overload protection for cables
TOL3Dev 2) 49M/G/T 3Ithdev> Three-phase thermal overload protection for devices
UV3Low 27-1 3U< Three-phase undervoltage protection, low-set stage
UV3High 27-2 3U
8/19/2019 Relay 543 - 545 Manual (2)
21/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
21
Settings of protection funct ions
Three-phase non-di rectional overcu rrent p rotection, low-set stage, NOC3Low, 3I> (51-1)
Start currentOperate time at DT mode
Time multiplier at IDMT mode
Operation mode
Measuring mode
Drop-off time of the operate time counter
0.10…5.00 x In0.05…300.00 s
0.05…1.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
RI-type inverse
RD-type inverse
IEEE Extremely inverse
IEEE Very inverse
IEEE Short time inverse
IEEE Short time extremely inverse
IEEE Long time extremely inverseIEEE Long time very inverse
IEEE Long time inverse
Peak-to-peak
Fundamental frequency
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or ±0.01 x In
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
Class index E = 5.0 or ±20 ms
Three-phase non-di rectional overcu rrent pr otection, high -set stage, NOC3High, 3I>> (51-2) andinstantaneous stage, NOC3Inst, 3I>>> (51-3)
Start current
Operate time
Operation mode
Measuring mode
Drop-off time of the operate time counter
0.10…40.00 x In
0.05…300.00 s
Not in use
Definite time
Instantaneous
Peak-to-peak
Fundamental frequency
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
0.1...10 x In: ±2.5% of set value or ±0.01 x In
10...40 x In: ±5.0% of set value
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
8/19/2019 Relay 543 - 545 Manual (2)
22/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
22
Three-phase direct ional O/C func tion, low-set stage, DOC6Low, 3I>→ (67-1)
Operation mode
Start current
Operate time
Time multiplier
Basic angle ϕbOperation direction
Earth-fault protection
Measuring mode
Drop-off time of the operate time counter
Not in use;
Definite time
Extremely inv.;
Very inverseNormal inverse
Long-time inv.;
RI-type inverse
RD-type inverse
0.05…40.00 x In
0.05…300.00 s
0.05…1.00
0…90°
Forward
Reverse
Disabled
Enabled
Phase-to-phase voltages, peak-to-peak measurement
Phase-to-phase voltages, fundamental freq. measurement
Phase-to-earth voltages, peak-to-peak measurementPhase-to-earth voltages, fundamental freq. measurement
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode Accuracy class index E at IDMT mode
Note! The values below apply when f/fn = 0.95...1.05
0.1...10 x In: ±2.5% of set value or ±0.01 x In
10...40 x In: ±5.0% of set value
±2.5% of measured voltage or ±0.01 x Un
±2°
Injected currents > 2.0 x start current:
internal time < 42 ms
total time < 50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 msClass index E = 5.0 or ±20 ms
Three-phase directional O/C function, high-set stage, DOC6High , I>>→ (67-2), and instantaneousstage, DOC6Inst , I>>>→ (67-3)
Operation mode
Start current
Operate time
Basic angle ϕbOperation direction
Earth-fault protection
Non-directional operation (when the direction
cannot be determined)
Measuring mode
Drop-off time of the operate time counter
Not in use
Definite time
Instantaneous
0.05…40.00 x In
0.05…300.00 s
0…90°
Forward
Reverse
Disabled
Enabled
Disabled
Enabled
Phase-to-phase voltages, peak-to-peak measurement
Phase-to-phase voltages, fundamental freq. measurement
Phase-to-earth voltages, peak-to-peak measurement
Phase-to-earth voltages, fundamental freq. measurement
0...1000 ms
8/19/2019 Relay 543 - 545 Manual (2)
23/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
23
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
0.1...10 x In: ±2.5% of set value or ±0.01 x In
10...40 x In: ±5.0% of set value
±2.5% of measured voltage or ±0.01 x Un
±2°
Injected currents > 2.0 x start current:internal time < 42 ms
total time < 50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
Non-directional earth-fault p rotection, low-set stage, NEF1Low, Io> (51N-1)
Start current
Operate time at DT mode
Time multiplier at IDMT mode
Operation mode
Measuring mode
Drop-off time of the operate time counter
1.0…500.0% of In
0.05…300.00 s
0.05…1.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
RI-type inverse
RD-type inverse
IEEE Extremely inverse
IEEE Very inverse
IEEE Short time inverse
IEEE Short time extremely inverse
IEEE Long time extremely inverse
IEEE Long time very inverse
IEEE Long time inverse
Peak-to-peakFundamental frequency
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value + 0.0005 x In
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
Class index E = 5.0 or ±20 ms
Non-directional earth-fault p rotection, high-set stage, NEF1High, Io>> (51N-2), and in stantaneousstage, NEF1Inst, Io>>> (51N-3)
Start current
Operate time
Operation mode
Measuring mode
Drop-off time of the operate time counter
0.10…12.00 x In
0.05…300.00 s
Not in use
Definite time
Instantaneous
Peak-to-peak
Fundamental frequency
0...1000 ms
8/19/2019 Relay 543 - 545 Manual (2)
24/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
24
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or + 0.01 x In
Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set forthe trip output)
0.95
< 45 ms
±2% of set value or ±20 ms
Directional earth-fault protection, low-set stage, DEF2Low, Io>→ (67N-1)
Start current
Start voltage
Operate time at DT mode
Time multiplier at IDMT mode
Operation mode
Operation criteria
Operation direction
Basic angle ϕbOperation characteristic
Intermittent E/F
Measuring mode
Drop-off time of the operate time counter
1.0…500.0% of In
2.0…100.0% of Un
0.1…300.0 s
0.05…1.00
Not in use
Definite time
Extremely inverse
Very inverse
Normal inverse
Long time inverse
Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Forward
Reverse
-90°... 60°
IoSin(ϕ)
IoCos(ϕ)
Not active
Active
Peak-to-peak
Fundamental frequency
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typicallyRetardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value + 0.0005 x In
±2.5% of set value or + 0.01 x Un
Phase angle ±2°
Injected neutral current > 2.0 x start current and
residual voltage > 2.0 x start voltage:
internal time < 72 ms
total time < 80 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95< 50 ms
±2% of set value or ±20 ms
Class index E = 5.0 or ±20 ms
8/19/2019 Relay 543 - 545 Manual (2)
25/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
25
Directional earth-fault p rotecti on, high-set stage, DEF2High, Io>>→ (67N-2), and instantaneousstage, DEF2Inst, Io>>>→ (67N-3)
Start current
Start voltage
Operate timeOperation mode
Operation criteria
Operation direction
Basic angle ϕbOperation characteristic
Intermittent E/F
Measuring mode
Drop-off time of the operate time counter
1.0…500.0% of In
2.0…100.0% of Un
0.1…300.0 sNot in use
Definite time
Instantaneous
Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Forward
Reverse
-90°... 60°
IoSin(ϕ)
IoCos(ϕ)
Not active Active
Peak-to-peak
Fundamental frequency
0...1000 ms
Operation accuracy
Start time
Reset time
Reset ratio, typicallyRetardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value + 0.0005 x In
±2.5% of set value or + 0.01 x Un
Phase angle ±2°
Injected neutral current > 2.0 x start current
and residual voltage > 2.0 x start voltage:
internal time < 72 ms
total time < 80 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95< 50 ms
±2% of set value or ±20 ms
Residual ov ervoltage pro tection, low-set stage, ROV1Low, Uo> (59N-1)
Start voltage
Operate time
Operation mode
Measuring mode
2.0…100.0% of Un
0.05…300.00 s
Not in use
Definite time
Peak-to-peak
Fundamental frequency
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or ±0.01 x Un
Injected voltages >2 x start voltage:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms
±2% of set value or ±20 ms
8/19/2019 Relay 543 - 545 Manual (2)
26/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
26
Residual overvoltage pro tection , high -set stage, ROV1High, Uo>> (59N-2), and i nstantaneousstage, ROV1Inst, Uo>>> (59N-3)
Start voltageOperate time
Operation mode
Measuring mode
2.0…100.0% of Un0.05…300.00 s
Not in use
Definite time
Peak-to-peak
Fundamental frequency
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or ±0.01 x Un
Injected voltages >2 x start voltage:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.95
Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms±2% of set value or ±20 ms
Three-phase thermal overload protection fo r cables, TOL3Cab, 3Ith> (49F)
Time constant for the cable
Maximum load current for the cable
Maximum temperature of conductor
Reference temperature
Trip temperature
Prior alarm temperature
Reclosure temperature
Ambient temperature
Operation mode (principle of ambient
temperature compensation)
1…999 min
1.0…5000.0 A
40.0…150.0°C
-50.0…100.0°C
80.0…120.0%
40.0…100.0%
40.0…100.0%
-50.0…100.0°C
Not in use
No sensors; the set ambient temperature
1 sensor used
2 sensors used
Operation accuracy
Reset ratio
Note! The values below apply when f/fn = 0.95...1.05
±1.0%, I = 0.1...10.0 x In
Trip: (Calculated temp. rise - 0.1) / Trip temperature
Start: (Calculated temp. rise - 0.1) / Prior alarm
temperature
8/19/2019 Relay 543 - 545 Manual (2)
27/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
27
Three-phase thermal overload protection for motors, generators and transformers, TOL3Dev,3Ithdev> (49M/G/T)
BASIC SETTINGSStarting current of the motor
Max. starting time permitted for the motor
Number of starts allowed from cold state
Type of device to be protected
Trip temperature
Prior alarm temperature
Restart inhibit (temperature limit for
successful restarting)
Ambient temperatureCooling time-constant
Heating time-constant for generator or
transformer
0.10...10.00 x In
0.1...120.0 s
1...3
Motor; through-ventilated, rated power < 1500 kW
Motor; through-ventilated, rated power > 1500 kW
Motor; surface cooling, rated power < 500 kW
Motor; surface cooling, rated power > 500 kW
Generator; hydro or small air-cooled turbine generators
Generator; large turbine generators
Transformer
80.0…120.0%
40.0…100.0%
40.0…100.0%
-50.0…100.0°C1.0...10.0 x time constant
1...999 min
ADVANCED SETTINGS
Short time-constant for stator
Long time-constant for stator
Weighting factor of the short time-constant for
stator
Temperature rise of stator at rated current
Maximum temperature of stator
Short time-constant for rotor
Long time-constant for rotor
Weighting factor of the short time-constant for
rotor
Temperature rise of rotor at rated current
Maximum temperature of rotor
0.0...999.0 min
0.0...999.0 min
0.00...1.00
0.0...350.0 °C
0.0...350.0 °C
0.0...999.0 min
0.0...999.0 min
0.00...1.00
0.0...350.0 °C
0.0...350.0 °C
Operation mode (principle of ambient
temperature compensation)
Waiting time for a successful restart (Read-
only parameter)
Predicted time to the trip (Read-only
parameter)
Not in use
No sensors; the set ambient temperature
1 sensor used
2 sensors used
0...99999 s
0...99999 s
Operation accuracy
Reset ratio
Note! The values below apply when f/fn = 0.95...1.05
±1.0%, I = 0.1...10.0 x In
Trip: (Calculated temp. rise - 0.1) / Trip temperatureStart: (Calculated temp. rise - 0.1) / Prior alarm
temperature
Restart: (Calculated temp. rise - 0.1) / Restart inhibit
temperature limit
8/19/2019 Relay 543 - 545 Manual (2)
28/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
28
Three-phase overvoltage protection, low-set stage, OV3Low, 3U> (59-1)
Start voltage
Operate timeTime multiplier
Operation mode
Measuring mode
Operation hysteresis
0.10…1.60 x Un
0.05…300.00 s0.05…1.00
Not in use
Definite time
A curve
B curve
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode,
typically
Note! The values below apply when f/fn = 0.95...1.05
±35 ms
Injected voltages = 1.1 x start voltage:
internal time < 42 ms
total time < 50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.96 (range0.95...0.99)
< 50 ms
±2% of set value or ±20 ms
±20 ms
Three-phase overvoltage protection, high-set s tage, OV3High, 3U>> (59-2)
Start voltage
Operate time
Operation mode
Measuring mode
Operation hysteresis
0.10…1.60 x Un
0.05…300.00 s
Not in useDefinite time
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value
Injected voltages = 1.1 x start voltage:
internal time < 42 ms
total time < 50 ms
40...1000 ms (depends on the minimum pulse width set for
the trip output)
0.96 (range 0.95...0.99)
< 50 ms
±2% of set value or ±20 ms
Three-phase undervoltage protectio n, low-set stage, UV3Low, 3U< (27-1)
Start voltage
Operate time
Time multiplier
Operation mode
Measuring mode
Operation hysteresis
0.10…1.20 x Un
0.1…300.0 s
0.1…1.0
Not in use
Definite time
C curve
Phase-to-phase voltages; peak-to-peak measurement
Phase-to-phase voltages; fundamental freq. measurement
Phase-to-earth voltages; fundamental freq. measurement
1.0...5.0%
8/19/2019 Relay 543 - 545 Manual (2)
29/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
29
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy at DT mode
Accuracy class index E at IDMT mode,
typically
Note! The values below apply when f/fn = 0.95...1.05
±35 ms
Injected voltages < 0.5 x start voltage:
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set forthe trip output)
1.04 (range 1.01...1.05)
< 60 ms
±2.5% of set value
±35 ms
Three-phase und ervoltage protection, high-set s tage, UV3High, 3U_1,U1 U2< >_2 (47-1, 47-2)
Start value U2>
Start value U1<
Start value U1>
Operate time U2>
Operate time U1<
Operate time U1>
Operation mode
Dir. selection
0.01…1.00 x Un
0.01…1.20 x Un
0.80…1.60 x Un
0.04…60.00 s
0.04…60.00 s
0.04…60.00 s
Not in use; U1< & U2> & U1>; U1< & U2>; U2> & U1>;
U1< & U1>; U2>; U1
Forward; Reverse; Input ROT_DIR
8/19/2019 Relay 543 - 545 Manual (2)
30/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
30
Operation accuracy
Trip time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy
Note! The values below apply when f/fn = 0.95...1.05
± 2.5% of set value or ± 0.01 x Un
U2> operation:
Injected negative-seq. voltage = 1.1 x start value:
internal time < 42 ms
total time < 50 msU1< operation:
Injected positive-seq. voltage = 0.50 x start value:
internal time < 32 ms
total time < 40 ms
U1> operation:
Injected positive-seq. voltage = 1.1 x start value:
internal time < 42 ms
total time < 50 ms
70...1030 ms (depends on the minimum pulse width
set for the TRIP output)
U2> operation: 0.96
U1< operation: 1.04
U1> operation: 0.99
< 45 ms (for all operations)
± 2% of set value or ± 20 ms
Underfrequency or overfrequency protect ion, 5 stages, Freq1St1… Freq1St5, f1 ... f5 (81-1 ... 81-5)
Operation mode
Undervoltage limit for blocking
Start value for under-/overfrequency prot.Operate time for under-/overfrequency prot.
Start value for df/dt protection
Operate time for df/dt protection
Not in use
f 1 timer
f 2 timers
f OR df/dt>
f AND df/dt>
f OR df/dt<
f AND df/dt<
0.30…0.90 x Un
25.00…75.00 Hz0.10…300.00 s
0.2…10.0 Hz/s
0.12…300.00 s
Operation accuracy
Start time
Reset time
Operate time accuracy
Under-/overfrequency (f): ±10 mHz
Frequency rate of change (df/dt);
real df/dt < ±5 Hz/s: ±100 mHz/s
real df/dt < ±15 Hz/s: ±2.0% of real df/dt
Undervoltage blocking: ±1.0% of set value
Total start times at fn = 50 Hz:
Frequency measurement < 100 ms
Df/dt measurement < 120 ms
140...1000 ms (depends on the minimum pulse width set
for the trip output)
±2% of set value or ±30 ms
8/19/2019 Relay 543 - 545 Manual (2)
31/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
31
Start-up supervision for motors, MotStart, Is2t n< (48)
Start current (for motor)
Start time (for motor)Time-based restart inhibit limit
Countdown rate of the time counter
Stalling time permitted for rotor
Operation mode
Start counter (Read-only parameter)
Time to restart enable (Read-only parameter)
Stall input (signal for motor stalling indication;
read-only parameter)
1.0...10.0 x In
0.3...250.0 s1.0...500.0 s
2.0...250.0 s/h
2.0...120.0 s
Not in use
I2t
I2t & Stall
0...99999
0...99999 min
Not active
Active
Operation accuracy
Start time
Reset ratio, typically
Retardation time
f/fn = 0.95...1.05: ±2.5% of set value or ±0.01 x In
f/fn = 0.95...1.50:
internal time < 22 ms
total time < 30 ms
f/fn = 0.50...0.95:
internal time < 32 ms
total time < 40 ms
0.95
< 50 ms
Three-phase overload protection for shunt capacitor banks, OL3Cap, 3I>3I< (51C)
Operate times of the overload stage Ib>
I/Ib> t [s] Standard durations [s] Standard
1.15
1.201.30
1.40
1.70
2.00
2.20
1799
29958
13.5
0.9
0.29
0.1
1800
30060
15
1
0.3
0.12
IEC 60871-1
IEC 60871-1 ANSI/IEEE 37.99, IEC
60871-1
ANSI/IEEE 37.99
ANSI/IEEE 37.99
ANSI/IEEE 37.99
ANSI/IEEE 37.99
Note! The minimum operate time is 100 ms
Start current of trip stage
Time multiplier k for trip stage
Start current of alarm stage
Operate time of alarm stage
Start current of undercurrent stage
Operate time of undercurrent stage
Setting of reconnection inhibit time trec
0.30...1.50 x In
0.05...2.0
0.80...1.20 x Ib
0.5...6000.0 s
0.10...0.70 x Ib
0.1...120 s
0.5...6000 sOperation accuracies
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy at definite time mode
(alarm stage Ia>, undercurrent stage I)
Note! The values below apply when f/f n=0.95...1.05
±2.5% of set value or ±0.01 x InInjected currents = 2.0 x start current
internal time < 32 ms
total time < 40 ms
40...1000 ms (depends on the minimum pulse width set
for the TRIP output)
Overload stages: Typ. 0.95
Undercurrent stage: Typ. 1.05
Total retardation time when the current exceeds the
start value: < 50 ms
±2% of set value or ±20 ms
Depends on the frequency of the current measured:
±10% of theoretical value or ±40 ms
8/19/2019 Relay 543 - 545 Manual (2)
32/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
32
Current unbalance protection for shunt capacitor banks, CUB1Cap, dI>C (51NC-1)
Operation mode
Alarm mode
Start current of the tripping stage
Operate time of the tripping stage in DT mode
Time multiplier k for the tripping stage in
IDMT mode
Start current of the alarm stage
Operate time of the alarm stage
Disallowed number of faulty elements
Level of natural unbalance compensation
Recording of the natural unbalance phasor
Location of capacitor fuses
Not in use; Definite time; Extremely inv.; Very inv.;
Normal inv.; Long-time inv.; RI-type inv.; RD-type inv.Normal mode; Element counter
1.0...100.0%dIn
1.0...300 s
0.05...2.0
1.0...100.0%dIn
1.0...300 s
1...100
0.0...20.0%dIn
Do not activate; Activate
External; Internal
Faulty elements counter
Amount of faulty elements in branch 1 of
phase IL1
Amount of faulty elements in branch 2 of
phase IL1
Amount of faulty elements in branch 1 of
phase IL2
Amount of faulty elements in branch 2 of
phase IL2
Amount of faulty elements in branch 1 of
phase IL3
Amount of faulty elements in branch 2 of
phase IL3
0...100
0...100
0...100
0...100
0...100
0...100
Operation accuracies
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy at definite-time mode
Operate time accuracy at inverse-time mode
Note! The values below apply when f/f n=0.95...1.05
±2.5% of set value + 0.001 x dInPhase angle measurement: ±2°
Injected currents = 2.0 x start current
internal time
8/19/2019 Relay 543 - 545 Manual (2)
33/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
33
Three-phase current unbalance protection for H-bridge connected shunt capacitor banks,CUB3Cap, 3dI>C (51NC-2)
Operation mode
Start current of the tripping stageOperate time of the tripping stage in DT mode
Time multiplier k for the tripping stage in
IDMT mode
Start current of the alarm stage
Operate time of the alarm stage
Comp natural dI1
Comp natural dI2
Comp natural dI3
Rec natural dI
Not in use; Definite time; Extremely inv.; Very inv.;
Normal inv.; Long-time inv.; RI-type inv.; RD-type inv.
1.0...100.0% dIn1.0...300 s
0.05...2.0
1.0...100.0% dIn
1.0...300.0 s
0.0...20.0% dIn
0.0...20.0% dIn
0.0...20.0% dIn
Do not activate; Rec all phasors; Rec phasor dI1, Rec
phasor dI2, Rec phasor dL3
Operation accuracies
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at definite-time mode
Operate time accuracy at inverse-time mode
Note! The values below apply when f/f n=0.95...1.05
±2.5% of set value + 0.0005 x dInPhase angle measurement: ±2°
Injected currents = 2.0 x start current
internal time
8/19/2019 Relay 543 - 545 Manual (2)
34/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
34
1) These functions are only supported in the feeder termi-nal revisions of Release 2.0 or later.
2) This function is only supported in the feeder terminalrevisions of Release 3.5 or later
Phase discontinuity protection, CUB3Low, Iub> (46)
Start unbalance
Operate time
Operation mode
10.0…95.0%
1.0…300.0 s
Not in use
Definite time
Operation accuracy
Start time
Reset time
Reset ratio, typically
Retardation time
Operate time accuracy at DT mode
Note! The values below apply when f/fn = 0.95...1.05
±2.5% of set value or ±1% unit
internal time < 95 ms
total time < 100 ms
40...1000 ms (depends on the minimum pulse width set for the trip
output)
0.95
Total time for blocking: < 25 ms
Total time when current drops below start value: < 50 ms
±2% of set value or ±50 ms
Fuse failure s upervis ion, FuseFail, FUSEF (60)
Ratio U2/U1> 10...50%
Ratio I2/I1< 10...50%
Operation accuracy When f/fn = 0.98...1.02
±2.0 percentage units (of settings Ratio U2/U1> and Ratio I2/I1 and Ratio I2/I1
(f/fn=0.98...1.02: < 35 ms (within the same task)
Reset time 20 ms (within the same task)
Reset ratio for Ratio U2/U1>: 0.8...0.96
for Ratio I2/I1
8/19/2019 Relay 543 - 545 Manual (2)
35/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
35
Settings of power quality functions
Current waveform distortion measurement, PQCU3H, PQ 3inf (PQ 3inf)
The current waveform distortion measurement PQCU3H is used for measurement and statistical analysis
of current waveform distortion. The standards concerning voltage distortion measurement are applied to
current distortion measurement in PQCU3H. Data collection and analysis is done according to EN 50160.
Measuring principles for individual harmonics and THD are adapted from the International standard IEC
61000-4-7. The American standard IEEE Std 1159 is also partly supported. Analysis can be done for one
selected phase current or most distorted phase current can be tracked.
Measuring modes
Measurement activation
Triggering mode
Distortion factor
Not in use; L1; L2; L3; Worst phase
Triggering by: setting parameter, binary input, date & time setting
Single; Continuous; Periodic
THD; TDD
Monitored values
THD (3 sec and 10 min mean values)
Harmonic components from 1st to
13th (3 sec mean values)
Harmonic components from 2nd to
13th (10 min mean values)
0.0 ... 1000.0%
0.0 ... 1000.0% In
0.0 ... 1000.0% In
Statistics
Observation times for statistics
Percentile setting
Percentiles for each harmonic and
THD
Five fixed percentiles (1,5,50,95,99)
for one selectable harmonic or THD
Maximum values for each harmonic
and THD
Recorded data
1 hour; 12 hours; 1 day; 2 days; 3 days; 4 days; 5 days; 6 days; 1
week
90.0 ... 99.5%
0.0 ... 1000.0% In
0.0 ... 1000.0% In
0.0 ... 1000.0% In
One data set for updating; One data set from the previous
observation period
Harmonic limit supervision
Limit for THD
Limits for each harmonicRecorded data
0.0 ... 60.0%
0.0 ... 40.0% InIf any limit should be exceeded, the whole harmonic set will be
recorded during the maximum THD (3 sec values)
Operation criteria
Fundamental frequency
Frequency deviation
Amplitude of the fundamental wave
0.9 ... 1.1 Fn
≤ 0.5 Hz (difference between max and min values within one
second)
≥ 1% In
Measurement accuracy
Measured harmonic Im = 1st, ... ,
10th
Measured harmonic Im = 11th, ... ,
13th
In accordance with IEC 61000-4-7
± 1.0% In, if Im < 10% In; ± 10% Im, if Im ≥ 10% In
Voltage waveform d isto rtion measurement, PQVO3H, PQ 3unf (PQ 3unf)
The voltage waveform distortion measurement PQVO3H is used for measurement and statistical analysis
of voltage waveform distortion. Data collection and analysis is done according to EN 50160. Measuring
principles for individual harmonics and THD are adapted from the International standard IEC 61000-4-7.
The American standard IEEE Std 1159 is also partly supported. Analysis can be done for one selected
phase or phase-to-phase voltage or most distorted phase or phase-to-phase voltage can be tracked.
Measuring modes
Measurement activation
Triggering mode
Not in use; L1; L2; L3; Worst phase; L1-L2; L2-L3; L3-L1; Worst
main
Triggering by: setting parameter, binary input, date & time setting
Single; Continuous; Periodic
8/19/2019 Relay 543 - 545 Manual (2)
36/76
Feeder Terminal REF 541, REF 543, REF 545.1MRS750443-MBG
36
Monitored values
THD (3 sec and 10 min mean values)
Harmonic components from 1st to
13th (3 sec mean values)
Harmonic components from 2nd to
13th (10 min mean values)
0.0 ... 120.0%
0.0 ... 120.0% Un
0.0 ... 120.0% Un
Statistics
Observation times for statistics
Percentile setting
Percentiles for each harmonic and
THD
Five fixed percentiles (1,5,50,95,99)
for one selectable harmonic or THD
Maximum values for each harmonic
and THD
Recorded data
1 hour; 12 hours; 1 day; 2 days; 3 days; 4 days; 5 days; 6 days; 1
week
90.0 ... 99.5%
0.0 ... 120.0% Un
0.0 ... 120.0% Un
0.0 ... 120.0% Un
One data set for updating; One data set from the previous
observation period
Harmonic limit supervision
Limit for THDLimits for each harmonic
Recorded data
0.0 ... 30.0%0.0 ... 20.0% Un
If any limit should be exceeded, the whole harmonic set will be
recorded during the maximum THD (3 sec values)
Operation criteria
Fundamental frequency
Frequency deviation
Amplitude of the fundamental wave
0.9 ... 1.1 Fn
≤ 0.5 Hz (difference between max and min values within one
second)
≥ 0.7 Un
Measurement accuracy
Measured harmonic Um = 1st, ... ,
10th
Measured harmonic Um = 11th, ... ,
13th
In accordance with IEC 61000-4-7
± 0.3% Un, if Um < 3% Un; ± 10% Um, if Um ≥ 3% Un
Short duration voltage variation measurement, PQVO3Sd, PQ3U< > (PQ3U< >)