REGIONAL ENERGY ACCOUNT BASED ON AVAILABILITY BASED TYARIFF T. SRINIVAS MANAGER,SRLDC BANGALORE
Jan 03, 2016
REGIONAL ENERGY ACCOUNTBASED ON
AVAILABILITY BASED TYARIFF
T. SRINIVASMANAGER,SRLDC
BANGALORE
BRIEF ABOUT SR BRIEF ON ABT
REA
CONVENTIONAL REA
SCHEDULING
SOUTHERN REGIONAL GRID▀ Centre Generating Stations in the Region are
• RSTPS STAGE I & II : 2,100 MW (200x3 + 500x3)
• RSTPS STAGE III : 500 MW (500x1)
• NLC TPS2 STAGE I : 630 MW (210 x 3)
• NLC TPS2 STAGE II : 630 MW (210 x 3)
• Madras Atomic Power Station : 340 MW (170 x 2 )
• Kaiga Atomic Power Station : 440 MW (220x2)
• NLC EXPANSION TPS 1 : 420 MW (210X2)
• TALCHER STAGE II : 2000 MW (500X4) situated
in ER
SOUTHERN REGIONAL GRID
▀ Beneficiaries in southern Region are
• ANDHRA PRADESH• KARNATAKA• KERALA• TAMIL NADU• Union Territory of Pondicherry• NLCMINES• GOA has share of 100MW from RSTPS
SR STATES – POWER SYSTEM STATISTICSANDHRA PRADESH
INSTALLED CAPACITY – 8939.7 MW
MAX DEMAND MET – 8241 MW
DAILY CONSUMPTION MAX – 171 MU
DAILY CONSUMPTION AVG – 142 MU
CONSUMER PROFILE –
INDS -27%, DOM-22%, COMM-5%, IRRI-39% & OTHERS-7%
KARNATAKA
INSTALLED CAPACITY – 6177 MW
MAX DEMAND MET – 5612 MW
DAILY CONSUMPTION MAX – 125 MU
DAILY CONSUMPTION AVG – 95 MU
CONSUMER PROFILE –
INDS -26%, DOM-19%, COMM-7%, IRRI-39% & OTHERS-9%
KERALA
INSTALLED CAPACITY – 2280 MW
MAX DEMAND MET – 2519 MW
DAILY CONSUMPTION MAX – 41 MU
DAILY CONSUMPTION AVG – 34 MU
CONSUMER PROFILE –
INDS -34%, DOM-44%, COMM-13%, IRRI-2%& OTHERS-7%
TAMIL NADU
INSTALLED CAPACITY – 9322 MW
MAX DEMAND MET – 7902 MW
DAILY CONSUMPTION MAX – 166 MU
DAILY CONSUMPTION AVG – 135 MU
CONSUMER PROFILE –
INDS -39%, DOM-25%, COMM-7%, IRRI-24% & OTHERS-5%
ANDHRA PRADESH
POPULATION :- 7.6 CRORES
AREA :- 275 (‘000 SQ KM)
NO OF CONSUMERS :- 162 LAKHS
PER CAPITA CONS. :- 719 UNITS
MAIN AGRICULTURE CROP :- RICE
CLIMATIC CONDITION :- HOT AND HOT & HUMID
SR STATES – GEOGRAPHYKARNATAKA
POPULATION :- 5.3 CRORES
AREA :- 192 (‘000 SQ KM)
NO OF CONSUMERS :- 105 LAKHS
PER CAPITA CONS. :- 642 UNITS
MAIN AGRICULTURE CROP :- COFFEE & RAGI
CLIMATIC CONDITION :- HOT AND HOT & HUMID
KERALA
POPULATION :- 3.2 CRORES
AREA :- 39 (‘000 SQ KM)
NO OF CONSUMERS :- 61 LAKHS
PER CAPITA CONS. :- 386 UNITS
MAIN AGRICULTURE CROP :- COCONUT & SPICES
CLIMATIC CONDITION :- HUMID
TAMIL NADU
POPULATION :- 6.2 CRORES
AREA :- 130 (‘000 SQ KM)
NO OF CONSUMERS :- 152 LAKHS
PER CAPITA CONS. :- 866 UNITS
MAIN AGRICULTURE CROP :- SUGAR CANE & OIL SEEDS
CLIMATIC CONDITION :- HOT AND HOT & HUMID
GROWTH OF INSTALLED CAPACITY OF SR
1947
5
1983
0
2030
4
2129
8
2213
3
2298
3
2417
3
2616
3 2850
1
2952
6 3273
3 3603
1
10000
15000
20000
25000
30000
35000
40000
1994-95 1995-96 1996-97 1997-98 1998-99 1999-00 2000-01 2001-02 2002-03 2003-04 2004-05 2005-06
YEARS - - ->
IN MW
INSTALLED CAPACITY IN SR
SUMMARY OF INSTALLED CAPACITY(MW)
AS ON 01.03.2006
AGENCY HYDRO THERMAL GAS/DIESEL WIND/OTHERS NUCLEAR TOTAL
ANDHRA PRADESH 3586.36 2962.5 272 2 --- 6822.86
KARNATAKA 3386.55 1470 127.8 4.55 --- 4988.9
KERALA 1831.1 --- 234.6 2.025 --- 2067.725
TAMILNADU 2137.35 2970 422.88 19.355 --- 5549.585
PONDICHERRY --- --- 32.5 --- --- 32.5
CENTRAL SECTOR --- 8090 359.58 --- 830 9279.58
IPP 278.13 387.01 2997.46 3627.2 0 7289.8
TOTAL11219 (31%)
15880 (44%) 4447 (12%) 3655 (10%) 830 (2%)
36031 (100%)
15880 (45%)
11219 (31%)830 (2%)
3655 (10%)
4447 (12%)
SOURCE-WISE INSTALLED CAPACITY OF SR
All Figures In MW
TOTAL 33,162 MW
HYDRO
THERMAL
WIND/OTHERS
NUCLEAR
GAS
RSTPS Stage I
& II
RSTPS Stage III
Talcher Stage II
NLC2 Stage I
NLC2
Stage II
NLC TPS1 Exp.
MAPS KGS FARAK
KAKAHALG
AONTALCH
ER
IC 2100 500 2000 630 840 420 340 440 1600 840 1000APTRANSCO 32.25 32.14 22.50 16.78 22.80 --- 9.34 --- --- --- --- 21.71
KPTCL 19.88 21.68 21.55 23.12 23.35 27.29 7.65 29.93 --- --- --- 21.09KSEB 14.74 15.77 23.00 11.63 12.32 18.53 6.27 13.12 --- --- --- 15.87TNEB 25.25 27.17 28.35 29.57 33.16 50.44 75.39 54.49 5.25 5.20 5.25 34.71
PONDY 3.01 3.24 4.40 10.96 2.42 3.74 1.35 2.46 --- --- --- 3.86GOA 4.76 --- --- --- --- --- --- --- --- --- --- 1.34
NLCMINES --- --- --- 7.94 5.95 --- --- --- --- --- --- 1.34PG HVDC 0.11 --- 0.20 --- --- --- --- --- --- --- --- 0.08
100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00 5.25 5.20 5.25 100.00
ISGSWeighted Average
NTPC NLC NPC NTPC (ER)
% ALLOCATED CAPACITY SHARE OF BENEFICIARIES FROM ISGS AS PER GOI ORDER
MW ALLOCATED CAPACITY SHARE OF BENEFICIARIES FROM ISGS AS PER GOI ORDER
RSTPS Stage I &
II
RSTPS Stage III
Talcher Stage 2
NLC2 Stage 1
NLC2
Stage II
NLC TPS1 Exp.
MAPS KGS FARAK
KAKAHALG
AONTALCH
ER
IC 2100 500 2000 630 840 420 340 440 1600 840 1000APTRANSCO 677.25 160.70 450.00 105.71 191.52 --- 31.76 --- --- --- --- 1616.94
KPTCL 417.48 108.40 431.00 145.66 196.14 114.62 26.01 131.69 --- --- --- 1571.00KSEB 309.54 78.85 460.00 73.27 103.49 77.83 21.32 57.73 --- --- --- 1182.02TNEB 530.25 135.85 567.00 186.29 278.54 211.85 256.33 239.76 84.00 43.50 52.50 2585.87
PONDY 63.21 16.20 88.00 69.05 20.33 15.71 4.59 10.82 --- --- --- 287.91GOA 99.96 --- --- --- --- --- --- --- --- --- --- 99.96
NLCMINES --- --- --- 50.02 49.98 --- --- --- --- --- --- 100.00PG HVDC 2.31 --- 4.00 --- --- --- --- --- --- --- --- 6.31
2100.00 500.00 2000.00 630.00 840.00 420.00 340.00 440.00 84.00 43.50 52.50 7450.00
NPC NTPC (ER)
ISGSTOTAL
MW
NTPC NLC
NUCLEAR STATION
KHAMMAM
VIJAYAWADAN’SAGAR
GAZUWAKA HYDERABAD
RAICHUR
GOOTY
BANGALORE
SALEM
UDUMALPET
TRICHUR
MADURAI
TRICHY
MADRAS
NEYVELI
GUTTUR
KAIGA
RSTPP
BHADRAVATI
`HOODY
MUNIRABAD
P
P
P
P
P
P
P
PP
P
P
N
KOLAR
TALCHER
JEYPORE
HOSUR
SSLMM
MMDP
THIRUVANANTHAPURAM
NELLORE
NELAMANGALA
KURNOOL
KALPAKKA
SIMHADRI
HIRIYURTALGUPPA
KADAPA
1000 MW HVDC BACK TO BACK LINK
2000 MW HVDC BIPOLE
500 KV HVDC LINE
400 KV LINE POWERGRID
400 KV LINE APTRANSCO
400 KV LINE KPTCL
400 KV LINE OPERATED AT 220 KV
THERMAL GENERATING STATION
NEYVELI TPS – 1 (EXP)
400KV SUB-STATION
NARENDRA
MAHABOOB NAGAR
CHITTOOR
VEMAGIRI
GVKGMR
MAPS
SRLDC, BANGALORE
MARCH 2006
CONTROL AREAS
REGIONAL GRID
SEB’S GRID
CS -3CS - 2
CS - 1
CENTRALSHARE
STATEGENR
STATEIPP
DISTR-B
DISTR- A
DISTR- C
SEB - A SEB -CSEB -B
SLDCCOORDINATESDIRECTS
RLDCCOORDINATES
CONVENTIONAL METHOD OF OPERATION
• SHARE BASED ON ACTUAL GENERATION:-
– DOES NOT REFLECT THE AVAILABILITY OF
ISGS –RATHER ITS EX-BUS GENERATION– IS FIXED AND TIME INVARIANT– INSENSITIVE TO CONSTRAINTS– DOES NOT ALLOW FOCUSED CHANGES
• SUB OPTIMAL UTILIZATION OF RESOURCES
CONVENTIONAL METHOD OF ENERGY ACCOUNTING
• PAYMENTS ARE MADE AS PER THE DRAWALS
• OVER AND UNDER DRAWALS - UNAVOIDABLE
• UNUTILISED RESOURCES ARE OFTEN BILLED.
• INFLEXIBLE – BILATERALS, SHORT TERM
CONTRACTS – NOT ALLOWED
ADVANTAGES OF SCHEDULING
• SCHEDULE REFLECTS BOTH –AVAILABILITY OF ISGS & REQUIREMENT OF CONSTITUENT
• FLEXIBILITY• TIME VARIANT - MIRRORS GRID BEHAVIOUR• SENSITIVE TO CONSTRAINTS• FOCUSED – SCHEDULE IS NON GENERIC• OPTIMAL UTILIZATION OF RESOURCES• ECONOMIC OPERATION• INDEPENDENT OF SETTLEMENT SYSTEM.
INDIAN ELECTRICITY GRID CODE (IEGC)
• CERC HAS ISSUED THE REVISED INDIAN ELECTRICITY GRID CODE (IEGC) on 29th DECEMBER 2005 WHICH WILL BE EFFECTIVE FROM 01st APRIL 2006.
C H A P T E R - 6 SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
The Procedures to be adopted for scheduling of the inter-State generating stations (ISGS) and net drawals of concerned constituents on a daily basis with the modality of the flow of information between the ISGS/ RLDCs /beneficiaries of the Region.
The procedure for submission of capability declaration by each ISGS and submission of drawal schedule by each beneficiary is intended to enable RLDCs to prepare the dispatch schedule for each ISGS and drawal schedule for each beneficiary.
It also provides methodology of issuing real time dispatch/drawal instructions and rescheduling, if required, to ISGS and beneficiaries along with the commercial arrangement for the deviations from schedules, as well as, mechanism for reactive power pricing.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
1.0 The Regional grids shall be operated as loose power pools (with decentralized scheduling and dispatch), in which the States shall have full operational autonomy, and SLDCs shall have the total responsibility for
(i) Scheduling/dispatching their own generation (including generation of their embedded
licensees),
(ii) Regulating the demand of their customers (iii) Scheduling their drawal from the ISGS
(within their share in the respective plant’s expected capability)
(iv) Arranging any bilateral interchanges (v) Regulating their net drawal from the regional
grid
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
2.0 The system of each State shall be treated and operated as anotional control area.
The algebraic summation of scheduled drawal from ISGS and any bilateral inter-change shall provide the drawal schedule of each
State, and this shall be determined in advance on daily basis.
While the States would generally be expected to regulate their generation and/or consumers’ load so as to maintain their actual drawal from the regional grid close to the above schedule, a tight control is not mandated.
The States may, at their discretion, deviate from the drawal schedule, as long as such deviations do not cause system parameters to deteriorate beyond permissible limits and/or do not lead to unacceptable line loading.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
3.0 The above flexibility has been proposed in view of the fact that all States do not have all requisite facilities for minute-to-minute on-line regulation of the actual net
drawal from the regional grid. Deviations from net drawal schedule are however, to be appropriately priced through the Unscheduled Interchange (UI) mechanism.
4.0 Provided that the States, through their SLDCs, shall always endeavour to restrict their net drawal from the grid to within their respective drawal schedules, whenever the system frequency is below 49.5 Hz. When the frequency falls below 49.0 Hz, requisite load shedding shall be carried out in the concerned State(s) to curtail the over-drawal.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
5.0 The SLDCs/STUs shall regularly carry out the necessary exercises regarding short-term and long-term demand estimation for their respective States, to enable them to plan in advance as to how they would meet their
consumers’ load without overdrawing from the grid.
6.0 The ISGS shall be responsible for power generation generally according to the daily schedules advised to them by the RLDC on the basis of the requisitions received from the SLDCs, and for proper operation and maintenance of their generating stations, such that these stations achieve the best possible long-term availability and economy.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
7.0 While the ISGS would normally be expected to generate power according to the daily schedules advised to them, it would not be mandatory to follow the schedules
tightly. In line with the flexibility allowed to the States, the ISGS may also deviate from the given schedules
depending on the plant and system conditions. In particular, they would be allowed / encouraged to generate beyond the given schedule under deficit
conditions. Deviations from the ex-power plant generation schedules shall, however, be appropriately priced through the UI mechanism.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
8.0 Provided that when the frequency is higher than 50.5 Hz, the actual net injection shall not exceed the scheduled dispatch for that time. Also,while the frequency is above 50.5 Hz, the ISGS may (at their discretion) back down without waiting for an advice from RLDC to restrict the frequency rise. When the frequency falls below 49.5 Hz, the generation at all ISGS (except those on peaking duty) shall be maximized, at least upto
the level which can be sustained, without waiting for an advise from RLDC.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
9.0 However, notwithstanding the above, the RLDC may direct the SLDCs/ISGS to increase/decrease their drawal/generation in case of contingencies e.g. overloading of lines/transformers, abnormal voltages,
threat to system security. Such directions shall immediately be acted upon. In case the situation does not call for very urgent action, and RLDC has some time for analysis, it shall be checked whether the situation has arisen due to deviations from schedules, or due to any power flows pursuant to short-term open access. These shall be got terminated first, in the above sequence, before an action which would affect the scheduled supplies from ISGS to the long term customers is initiated.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
10.0 For all outages of generation and transmission system, which may have an effect on the regional grid, all
constituents shall cooperate with each other and coordinate their actions through Operational Coordination Committee (OCC) for outages foreseen sufficiently in advance and through RLDC (in all other cases), as per procedures finalized separately by OCC. In particular, outages requiring restriction of ISGS generation and/or restriction of ISGS share which a beneficiary can receive (and which may have a commercial implication) shall be planned carefully to
achieve the best optimization.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
11.0 The regional constituents shall enter into separate joint/bilateral agreement(s) to identify the State’s shares in ISGS projects (based on the allocations by the Govt. of India, where applicable), scheduled drawal pattern, tariffs, payment terms etc. All such agreements shall be filed with the concerned RLDC(s) and RPC Secretariat, for being considered in scheduling and regional energy accounting. Any bilateral agreements between constituents for scheduled interchanges on long- term/short-term basis shall also specify the interchange schedule, which shall be duly filed in advance with the RLDC.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
12.0 All constituents should abide by the concept of frequency-linked load dispatch and pricing of deviations from schedule, i.e., unscheduled interchanges.
13.0 It shall be incumbent upon the ISGS to declare the plant capabilities faithfully, i.e., according to their best
assessment. In case, it is suspected that they have deliberately over/under declared the plant capability
contemplating to deviate from the schedules given on the basis of their capability declarations (and thus make money either as undue capacity charge or as the charge for deviations from schedule), the RLDC may ask
the ISGS to explain the situation with necessary backup data.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
14.0 The CTU shall install special energy meters on all inter connections between the regional constituents and
other identified points for recording of actual net MWh interchanges and MVArh drawals. The type of meters
to be installed, metering scheme, metering capability, testing and calibration requirements and the scheme for collection and dissemination of metered data are detailed in the enclosed Annexure-2. All concerned
entities (in whose premises the special energy meters are installed) shall fully cooperate with the CTU/RLDC and extend the necessary assistance by taking weekly meter readings and transmitting them to the RLDC.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
15.0 The RLDC shall be responsible for computation of actual net MWh injection of each ISGS and actual net drawal of each beneficiary, 15 minute-wise, based on the above meter readings and for preparation of the Regional Energy Accounts. All computations carried out by RLDC shall be open to all constituents for checking/ verifications for a period of 15 days. In case any mistake/omission is detected, the RLDC shall forthwith
make a complete check and rectify the same.
16.0 RLDC shall periodically review the actual deviation from the dispatch and net drawal schedules being issued, to check whether any of the constituents are indulging in unfair gaming or collusion.
SCHEDULING & DESPATCHING CODE
SRLDC/Comml/IEGC/33
Demarcation of Responsibilities
17.0 In case the State in which an ISGS is located has a predominant share in that ISGS, the concerned parties may mutually agree (for operational convenience) to assign the responsibility of scheduling of the ISGS to the state’s LDC. The role of the concerned RLDC, in such a case, shall be limited to consideration of the schedule for inter-state exchange of power on account of this ISGS while determining the net drawal schedules
of the respective states.
Scheduling And Despatching ProceedureOn Day-l
09 AM ISGSs advise foreseen plant-wise ex- . power plant MW, MWh * capability for next day
10 AM RLDC advises SEBs their MW, MWh* shares in foreseen ISGSs' availability
3 PM SLDCs furnish their ,time-wise MW requisition from the above, and schedule of bilateral exchanges, if any
5 PM RLDC issues' despatch schedules' for ISGSs and 'net drawal schedules' for SEBs, for each hour the next day starting at midnight
10 PM SLDCs may inform any change of the above or bilateral exchanges to RLDC, if required by any new development during the day
11 PM Schedules frozen for the next day. RLDC Issues final drawal schedules to each State & Despatch schedule to each ISGS
SRLDC/Comml/IEGC/41
Scheduling And Despatching ProceedureOn Day-0
SRLDC/Comml/IEGC/41
In case of forced outage of a unit, the RLDC shall revise theschedules on the basis of revised declared capability. The revised declared capability and the revised schedules shall become effective from the 4th time block, counting the time block in which the revision is advised by the ISGS to be the first one.In the event of bottleneck in evacuation of power due to any constraint, outage, failure or limitation in the transmission system, associated switchyard and sub- stations owned by the Central Transmission Utility or any other transmission licensee involved in interstate transmission (as certified by the RLDC) necessitating reduction in generation, the RLDC shall revise the schedules which shall become effective from the 4th time block, counting the time block in which the bottleneck in evacuation of power has taken place to be the first one. Also,during the first, second and third time blocks of such an event, the scheduled generation of the ISGS shall be deemed to have been revised to be equal to actual generation, and the scheduled drawals of the beneficiaries shall be deemed to have been revised to be equal to their actual drawals.
Scheduling And Despatching ProceedureOn Day-0
SRLDC/Comml/IEGC/41
In case of any grid disturbance, scheduled generation of all the ISGS and scheduled drawal of all the beneficiaries shall be deemed to have been revised to be equal to their actual generation/drawal for all the time blocks affected by the grid disturbance. Certification of grid disturbance and its duration shall be done by the RLDC.
Revision of declared capability by the ISGS(s) and requisition by beneficiary(ies) for the remaining period of the day shall also be permitted with advance notice. Revised schedules/ declared capability in such cases shall become effective from the 6th time block, counting the time block in which the request for revision has been received in the RLDC to be thefirst one.If, at any point of time, the RLDC observes that there is need for revision of the schedules in the interest of better system operation, it may do so on its own, and in such cases, the revised schedules shall become effective from the 4th time block, counting the time block in which the revised schedule is issued by the RLDC to be the first one.
Scheduling And Despatching ProceedureOn Day-0
SRLDC/Comml/IEGC/41
To discourage frivolous revisions, an RLDC may, at its sole discretion, refuse to accept schedule/capability changes of less than two (2) percent of the previous schedule/ capability.
On Day + 1
.
RLDC to issue before-the- fact Capacity Declaration/Schedules finally implemented by RLDC (Datum for accounting and working out average ex-power plant capability).
The procedure for scheduling and the final schedules issued by RLDC, shall be open to all constituents for any checking/verification, for a period of 5 days. In case any mistake/omission is detected, the RLDC shall forthwith make a complete check and rectify the same.
While availability declaration by ISGS may have a resolution of one (1) MW and one (1) MWh, all entitlements, requisitions and schedules shall be rounded off to the nearest decimal, to have a resolution of 0.1
MW.SRLDC/Comml/IEGC/42
SCHEDULING METHODOLOGY
The station-wise (Ex-bus) capability would be submitted by the ISGSs in the specified format. ISGSs would declare the capability i.e. the MW and MWH quantum in the absolute values and not in the form of some relative percentages or in any other manner.
SCHEDULING METHODOLOGY
Based on the declared capability & the allocations of different States / Beneficiaries in different ISGSs, the station wise entitlements would be worked out and intimated to all the States/Beneficiaries by SRLDC.
SCHEDULING METHODOLOGY
The requisitions would be submitted by the States in the specified format. The States would submit the requisitions indicating the quantum desired against the given entitlement, and not the quantum surrendered. The requisitions in case of nuclear and run of the river hydro stations would be equal to the entitlements.
SCHEDULING METHODOLOGY
The details of the despatch and drawal schedules and Unrequisitioned, surpluses shall be made by SRLDC and the information would be exchanged through fax and/or through FTP.
SCHEDULING METHODOLOGY
In the event of any unrequisitioned surpluses, the Owner State ( the State to which the share actually belongs and pays the capacity charges) may find out a suitable Buyer/ Willing State to take such unrequisitioned surplus and/or the Buyer/Willing State may contact the Owner State for such exchange. The agreed Short Term Open Access Transactions be intimated / consented to SRLDC by both the States for incorporating in the final schedules.
SCHEDULING METHODOLOGY
Any unrequisitioned surpluses still available, can be agreed for Short Term Open Access Transactions between the concerned ISGS and one or more desiring States. The agreed Short Term Open Access Transactions from ISGS to a State be intimated to SRLDC by both the agencies (ISGS as well as States) for incorporation in the final schedule.
SCHEDULING METHODOLOGY
During the current day in case the Owner State requisitions back its surrendered share, then the same is withdrawn from the other State/ States to which it was allocated as surplus energy and the schedules are revised in line with the Grid Code.
SCHEDULING METHODOLOGY
While making or revising their declaration of capability the generators shall ensure that the declared capability during peak hours is not less than during other hours.
SCHEDULING METHODOLOGY While communicating the requisitions, the States shall ensure that:
maximum economy and efficiency in the operation of the power system in the State is achieved while requisitioning and /or surrendering power from different ISGSs vis-à-vis from their own stations.
the requisitions are operationally reasonable, particularly in terms of ramping-up / ramping-down rates and ratio between minimum and maximum generation levels, and are in line with the agreed philosophy in the region amongst different agencies.
SCHEDULING METHODOLOGY
In the event of despatch schedule in respect of a particular ISGS, (as agreed between ISGS and the State constituents in respect of thermal units it would be taken as 70%) the changes in requisition between two successive blocks is higher than a ramp up/down quantum, then the State/States due to which such anomaly is being experienced would be requested by SRLDC to change its/their requisition in that particular ISGS, to make the schedule operationally reasonable.
SCHEDULING METHODOLOGY
While issuing the final schedules, SRLDC shall check that the schedules do not give rise to any transmission constraints. In case any imperssible constraints/ anomalies are foreseen, the RLDC shall moderate the schedules to the required extent , under intimation to the concerned agencies.
SCHEDULING METHODOLOGY
During the periods of low demand in the region, in spite of all efforts if the despatch schedule of an ISGS(s) during certain blocks in the off-peak period remains below the minimum agreed value, and the concerned ISGS (s) is not able to operate the units due to technical constraints, then the concerned ISGS(s) may close down some unit(s) in consultation with SRLDC and the despatch schedule of the ISGS(s) shall be revised accordingly. Under such a situation the net drawal schedule of the beneficiary (ies) having share in the ISGS(s), may get reduced during peak hours also.
SCHEDULING METHODOLOGY
If at any point of time SRLDC observes that there is need for revision of schedules in the interest of better system operation, it may do so on its own and make it effective in line with the grid code provisions.
SCHEDULING METHODOLOGY
While entering into a bilateral agreement, the concerned parties shall ensure that the agreements are clear and explicit and contains all the relevant details which may be necessary from scheduling and computation of energy flow.
Scheduling And Despatching ProceedureOn Day-l
09 AM ISGSs advise foreseen plant-wise ex- . power plant MW, MWh * capability for next day
10 AM RLDC advises SEBs their MW, MWh* shares in foreseen ISGSs' availability
3 PM SLDCs furnish their ,time-wise MW requisition from the above, and schedule of bilateral exchanges, if any
5 PM RLDC issues' despatch schedules' for ISGSs and 'net drawal schedules' for SEBs, for each hour the next day starting at midnight
10 PM SLDCs may inform any change of the above or bilateral exchanges to RLDC, if required by any new development during the day
11 PM Schedules frozen for the next day. RLDC Issues final drawal schedules to each State & Despatch schedule to each ISGS
SRLDC/Comml/IEGC/41
Scheduling And Despatching ProceedureOn Day-0
SRLDC/Comml/IEGC/41
In case of forced outage of a unit, the RLDC shall revise theschedules on the basis of revised declared capability. The revised declared capability and the revised schedules shall become effective from the 4th time block, counting the time block in which the revision is advised by the ISGS to be the first one.
Revision of declared capability by the ISGS(s) and requisition by beneficiary(ies) for the remaining period of the day shall also be permitted with advance notice. Revised schedules/ declared capability in such cases shall become effective from the 6th time block, counting the time block in which the request for revision has been received in the RLDC to be thefirst one.
Scheduling And Despatching ProceedureOn Day-0
SRLDC/Comml/IEGC/41
To discourage frivolous revisions, an RLDC may, at its sole discretion, refuse to accept schedule/capability changes of less than two (2) percent of the previous schedule/ capability.
On Day + 1
.
RLDC to issue before-the- fact Capacity Declaration/Schedules finally implemented by RLDC (Datum for accounting and working out average ex-power plant capability).
The procedure for scheduling and the final schedules issued by RLDC, shall be open to all constituents for any checking/verification, for a period of 5 days. In case any mistake/omission is detected, the RLDC shall forthwith make a complete check and rectify the same.
While availability declaration by ISGS may have a resolution of one (1) MW and one (1) MWh, all entitlements, requisitions and schedules shall be rounded off to the nearest decimal, to have a resolution of 0.1
MW.SRLDC/Comml/IEGC/42
METERING LOCATIONS IN SR
• Total No Of SEMS in SR USED FOR REA 350
No.s• Total No Of SEMS in KPTCL USED FOR REA
50 No.s
KAKINADA
PO 05
REA METERING LOCATION OF STATE OWNED INTER STATE LINES IN SOUTHERN REGION
HOSUR
HOSUR
YERANDAHALLY
2
20 KV .
YERANDAHALLY
2
20 KV .
MANJESWAR
UPPATI
KADAKOLA
KNYMPTTAKONEJA
ARAKU
BALIMELA
OS
AP
TN
KERKAR
GOA
LOW
ER
SIL
ER
U
BA
RS
UR
HVDC
KO
LLA
PU R
K'T
HA
RA
I
UD
UM
ALP
ET
KA
YA
TH
AR
TH
EN
I
BELLARY
TANDUR GOOTY
SEDAM
CH
IKK
OD
I
MO
OZ
HIY
AR
ED
MO
N
IDU
KK
I
PA
RA
SA
LA
MH
MP
220
KV
220
KV
220
KV
220
KV
220
KV
220
KV
110
KV
220
KV
132
KV
66 K
V
110
KV
220 KV
110 KV
AP57
AP55
AP56
OS 58
P0 06
TN 56
AP 54 TN 57
TN 54
TN51
TN52
TN53
TN58
KL52
KL53
KL51
TN 55
CK 54
CK 51
CK 52
KL 55
KL 56CK56
CK59
CK58
GO01
GO02
GO03
CK57
AP 58AP 52
CK 60
CK 61
CK 55
CK 53KL58
PONDY(Yanam)
132
KV 21
XELDEM
21
GO04
UPPERSILERU
PONDA
PONDA
AMBEWADI SUPA
MACHKHUNBALIMELA
AP 53CHITOOR TIRUVALEM
SULURPET
G'P
UN
DI
KOOTHAMUNDA
220 KV
220 KV
220 KV
220 KV
220 KV
132 KV
220
KV
110
KV
INTER STATE LINES METERING LOCATIONS
METERING LOCATIONS IN KPTCL'S INTERCONNECTED SYSTEM
AP-51CK-53
TANDUR
GOOTY
A PAP-52CK-55
BELLARY
SEDAM
TN-55CK-54HOSURYERANDAHALLI
T N
CK-22CK-21
CK-05CK-06
CK-03CK-04
BANGALORE
RAICHUR N'SAGAR
MBD
N'SAGAR
MBD
CENTRAL TR. SYSTEM
CK-51KL-55
KL-56 CK-52
KONAJE
KADAKOLA
MANJESWAR
KANIAMPETTA
KSEB
GO-03
GO-04
GO-01
GO-02AMBEWADI
XELDEMXELDEM
PONDA
PONDA
PONDA SUPA
GOA(SR)
KG-24
KG-23
KG-22
KG-21
KODASALLI
KADRA
SIRSI-2
SIRSI-1
KGS
CK-60
CK-61CHIKKODI
KolhapurWR/MSEB
CK-01CK-02
HOODY
SR-63
SR-64
BANGALORE
BANGALORE
CK-57CK-57
CK-58
CK-56
CK-57
KOLAR
220kV
220kV
220kV
110kV
110kV
220kV
220kV
220kV
220kV
220kV
220kV
220kV
220kV
400kV
220/400kV
220/400kV
220/400kV
CK-11CK-12
KOLARKOLAR
220/400kV
110kV
400kV
GOOTY
CK-21RAICHUR
4 5 6 7
CK-23
CK-05
CK-06
CK-24
CK-27
CK-25
SR-81
DAVANAGERE
CK-26
NELAMANGALA
CK-28
CK-09
CK-10
CK-30
CK-31
HOODY
CK-07
CK-08
CK-15
CK-16
HIRIYUR
CK-29
CK-32 CK-33
CK-13
CK-14
BANGALORE
SR-11
N'Sagar
Kolar
Munirabad
CK-35
CK-34
CK-36
CK-37
Temporary Configuration :Karnataka's drawl in Raichur-Hoody section:Raichur = -(CK-21) -(CK-23) -(CK-25); Muniarabd=(CK-05) ; Davanagere=(CK-07); Hiriyur=(CK-15); Nelamangala= -(CK-29)-(CK-30)-(CK-35) -(CK-36) -(CK-38);Hoody = (CK-09)+(CK-13)
CK-30
CK-31
CK-38
Karnataka's drawl in Raichur-Hoody section:
Raichur = -(CK-21) -(CK-23) -(CK-25);
Muniarabd=(CK-05) ;
Davanagere=(CK-07); Hiriyur=(CK-15);
Nelamangala= -(CK-29)-(CK-30)-(CK-35)
-(CK-36) -(CK-38);
Hoody = (CK-09)+(CK-13)
RAICHUR SECTION
KPTCL'S DRAWL ON 400kV RAICHUR-DAVANAGERE SECTION
(CK-RC)=-(CK-21)-(CK-23)-(CK-25) -(CK-29)-(CK-30)+ (CK-35)+ (CK-36) (CK-38) + (CK-05)+ (CK-07) +(CK-09) + (CK-13) + (CK-15)
KPTCL'S DRAWL ON 400kV
(CK-91)= (CK-01)+(CK-03)+(CK-RC) +(CK-11)
CK'S DRAWL ON 220kV
(CK-92)= -(CK-51)-(CK-53)-(CK-54)-(CK-55)-(CK-58)-(CK-59)+(KG-21)
+(KG-22)+(KG-23)+(KG-24)
CK'S DRAWL ON 132kV
(CK-93)=-(CK-52)-(CK-56)
TOTAL DRAWL (CK-94)=(CK-91)+(CK-92)+(CK-93)NOTE: SEMS ON FEEDERS NOT CARRYING ISGS POWER NOT TO BE CONSIDERED
Payment to Inter State Generating Stations (ISGS) from beneficiaries under
Availability Based Tariff (ABT)
Capacity chargesEnergy chargesUnscheduled Interchange (UI)
1000
900
800
700
600
500
400
300
200
100
0
0 2 4 6 8 10 12 14 16 18 20 22 24
Forecast ex-bus capability of Power Plant
Hours
MW
Net Injection Schedule
SEB - A's Requisition
SEB - A's Entitlement - (40%)
SCHEDULING
CAPACITY CHARGE
Capacity charge will be related to ‘availability’ of the generating station and the percentage capacity allocated to the state. ‘Availability’ for this purpose means the readiness of the generating station to deliver ex-bus output expressed as a percentage of its rated ex-bus output capability.
ENERGY CHARGE
Energy charges shall be worked out on the basis of a paise per kwh rate on ex-bus energy scheduled to be sent out from the generating station as per the following formula
Energy charges = Rate of energy charges
(paise/kwh) x Scheduled Generation (ex-bus MWh)
UNSCHEDULED INTERCHANGE (U I) :
Variation in actual generation / drawal with respect to scheduled generation / drawal shall be accounted for through Unscheduled Interchange (UI).
UI for generating station shall be equal to its total actual generation minus its scheduled generation.
UI for beneficiary shall be equal to its total actual drawal minus its total scheduled drawal.
UNSCHEDULED INTERCHANGE (U I) :
UI shall be worked out for each 15 minute time block.
Charges for all UI transactions shall be based on average frequency of the time block.
UI rates shall be frequency dependent and uniform throughout the country.
0
50
100
150
200
250
300
350
400
450
500
550
600
650
48.9 49 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50 50.1 50.2 50.3 50.4 50.5 50.6 50.7 50.8 50.9 51
Frequency ----------->
UI ra
te
-----
------
------
>
Below 49.0 Hz UI rate =570 p/u
At 50.0 Hz UI rate =150 p/u
At 49.8 Hz UI rate =210 p/u
Above 50.5 Hz UI rate =0 p/u
UI RATE
Rate of Unscheduled Drawal/InjectionFrequency (Hz) Rate (p/u)
Above 50.5 0
50.0 150
49.8 210
49.0 and below 570
AVAILABILITY BASED TARIFF
(A) CAPACITY CHARGE
(B) ENERGY CHARGE
(C) ADJUSTMENT FOR DEVIATIONS
(U I CHARGE)
(A) = a function of the Ex-Bus MW availability of Power Plant for the day declared before the day starts x SEB’s % allocation from the plant
(B) = MWh for the day as per Ex-Bus drawal schedule for the SEB finalised before the day starts x Energy charge rate
(C) = Σ (Actual energy interchange in a 15 minute time block – scheduled energy interchange for the time block) x UI rate for the time block
TOTAL PAYMENT FOR THE DAY = (A) + (B) ± (C)
FEATURES :
(A) and (B) do not depend on actual plant generation / drawal. No metering required for this as they are based on off-line figures. All deviations taken care of by (C)
No complication regarding deemed generation.
Perpetual incentive for maximizing generation and reducing drawal during deficit, but no incentive to over generate during surplus.
Settlement System under ABT Regime
WHAT IS SETTLEMENT ?
• “ Settlement means Closing the payment/receipt/adjustment process of
bill for the period under consideration”• To be FAIR and EQUITABLE• To RECOVER DUES at the EARLIEST
(Billing Cycle)• TRANSPERANCY• Dispute Resolution• Reconciliation
Capacity charge:
Capacity charge is based on Annual Fixed Charge and will be related to availability of generating station. Availability means the readiness of the generating station to deliver ex-bus output expressed as a percentage of its rated ex-bus output capability.
Energy charge:
Energy charge is related to the scheduled ex-bus energy to be sent out from the generating station and will be worked out on the basis of paise per KWh.
AVAILABILITY TARIFF(ABT)(a) CAPACITY CHARGE(b) ENERGY CHARGE(c) ADJUSTMENT FOR DEVIATIONS
(UI CHARGE)
(a) = a function of Ex-bus MW availability of power plant for the day declared before the day starts x SEB’s % share
.(b) = MWh for the day as per ex=bus drawl schedule for the SEB
finalized before the day starts x Energy charge rate
(c) =Σ(Actual energy interchange in a 15 min time block – scheduled energy interchange for the time block) x UI rate for the time block.
TOTAL PAYMENT FOR THE DAY =(a) + (b)± ( c)
SETTLEMENT SYSTEMFor the day: 0000 hrs. to 2400 hrs.
Central Generating Stations 1 2 3
Ex-Bus Capability x1 x2 x3(Forecast) ____ ___ ___
SEB-A’s share a1 a2 a3SEB-B’s share b1 b2 b3SEB-C’s share c1 c2 c3
For a particular 15 minute time block
SEB-A’s requisition a’1 a’2 a’3SEB-B’s requisition b’1 b’2 b’3SEB-C’s requisition c’1 c’2 c’3
___ ___ ___CGS’s schedule x1’ x2’ x3’
MW
SRLDC/Comml/IEGC/37
SETTLEMENT SYSTEM
Total capacity charge payable to CGS-1 for the day= x1 * capacity charge rate of CGS-1
Total Energy charge payable to CGS-1 for the day
= x1’ * Energy charge rate of CGS-1 4
Total capacity charge payable by SEB-A for the day
= a1 * capacity charge rate of CGS-1
+ a2 * -do- CGS-2
+ a3 * -do- CGS-3Total Energy charge payable by SEB-A for the day
= (a1’) * Energy charge rate of CGS-1 ( 4 )
+ (a2’) * -do- CGS-2 ( 4 )
+ (a3’) * -do- CGS-3 ( 4 )
All capacity charge and Energy charge payments to be made by SEBs directly to CGS.
SRLDC/Comml/IEGC/38
SETTLEMENT SYSTEM
Actual (metered) injection of CGS-1 in the time block = X1 MWh.
Excess injection = (X1 – x1’ ) MWh.
4
Amount payable to CGS-1 for this =(X1-x1’) * pool price for the block.
4
SEB-A’s scheduled drawl for time block = a1’+a2’+a3’ = a’ MW (ex-CGS Bus)
SEB-A’s NET drawal schedule = (a’ – Notional Transm. Loss) MW
= (a’ – Notional Transm. Loss) = A’ MWH
4
Actual (metered) net drawal of SEB-A during time block = A MWH
Excess drawal by SEB-A = (A-A’) MWh.
Amount payable by SEB-A for this = (A-A’) * pool price for the block.
All above payments for deviations from schedules to be routed through a pool A/C operated by RLDC
SRLDC/Comml/IEGC/39
AVAILABILITY
• Availability in relation to a generating station for any period means the average of the DCs for all the days during that period expressed as a percentage of the installed capacity of generating station minus normative auxiliary consumption in MW and shall be computed as per the following formula:
AVAILABILITY AND PLF
% Availability = i=1
N
DCi/ {NxICx(100-Auxn) }%10000
Where DCi = Average Declared Capacity for i th day of the period in MW N = Total no. of days during the period Auxn = Normative Auxiliary Consumption as % of gross Gen.
IC= installed capacity in MW
% Availability forms the basis for calculations
i=1
N
SGi/ {NxICx(100-Auxn) }%10000PLF =
Recovery of Annual fixed charges 100% recovery if % Availability >=Target Availability
- Pro-rata reduction if %Avb<T.Avb.
- Target Availability For Fixed charges recovery - Target PLF for incentive
-Both to be Notified by CERC-Financial Year forms the basis for calculations
ISGS Target Availabilty Target PLF
RSTPS 80% 80%
NLC 75% 75%
Monthly Capacity charges receivable by an ISGS:
1 st Month = (1xACC1)122 nd Month = (2xACC2-1ACC1)12….….12 th month = (12xACC12-11ACC11)12where ACC1,ACC2…….ACC12 = Annual capacity charges corresponding to the cum. Availability up to the corresponding month.
Monthly Capacity charges payable by a beneficiary :
1 st Month = (1xACC1xWB1)122 nd Month = (2xACC2xWB2-1ACC1xWB1)12….….12 th month = (12xACC12xWB12-11xACC11xWB11)12where WB1,WB2…..WB12 = Weighted average % share up to the corresponding month.
Name Of ISGS Aux.
Consumption
Variable
Charges (Ps)
RSTPS STAGE I & II 7.93% 98
RSTPS STAGE III 7.5% 104
NLC II/1 10.00% 75
NLC II/2 10.00% 100
NLC TPS 1 (EXP) 9.50% 131
TALCHER STAGE II 7.50% 74
Energy charges
The Energy Charges Payable by beneficiary to the ISGS =
Variable Charge of ISGS X Requisition of beneficiary from the ISGS
The Energy Charges Receivable by ISGS from beneficiaries =
Variable Charge of ISGS X Despatch schedule of ISGS
• Flat rate of 25ps/u
• For ex-bus Schedule Energy in Excess of ex-bus energy corresponding to Target PLF
Incentive as per existing norms
Settlement Systems* On weekly basis : For seven day period ending on penultimate Sunday
•RLDC to furnish Scheduling & Metering data to REB• Sectt. by Thursday noon
•REB Sectt. to issue Weekly UI a/c by Tuesday
•Pool a/c operated by RLDC•Settlement for UI on weekly basis•All accounts open for 20 days
SRLDC/Comml/IEGC/34
Settlement System contd..
• On monthly basis :• REB to issue REA specifying % Avb, %
Net Entitlement, % Energy charges, Wt. Avg. Ent. for Tr. Ch. etc.
• Capacity and Energy Charges, Incentive etc.
• –billed directly by ISGS based on REA issued by REB
WEEKLY ENERGY ACCOUNTING:
WEEKLY CYCLE : 00 HRS OF EACH MONDAY TO 24 HRS; OF THE THE FOLLOWING SUNDAY
ACTIVITIES MONDAY MORNING : SEM DATA DOWNLOADED TO DCD
: DCD DATA LOADED TO A LOCAL PC: DATA SENT TO RLDC via E-MAIL
(LATEST TUESDAY MORNING )THURSDAY NOON : RLDC CONVEYS PROCESSED DATA TO
REBTues day : WEEKLY UI a/c & Reactive charges
issued BY REBBILLING
Cap. Charge : BILLED MONTHLY based on DAILY DC BY ISGS
ENERGY CHARGE : BILLED MONTHLY based on DAILY DRAWL SCHEDULES ISSUED BY RLDC
UI a/c Paid/Disbursed as per UI a/c issued by REB
REACTIVE a/c
Variations in actual generation/drawal and scheduled generation /drawal are accounted through UI. This is a frequency linked charge which is worked out for each 15 minute time block.
Charges for all UI transaction, based on average frequency have following rate of paise per KWh from 01.01.03 up to 31.03.04.
UI rate (Paise per KWh)
Average Frequency of time block50.5 Hz. and above 0.0Below 50.5 Hz. and upto 50.48 Hz. 5.6Below 49.04 Hz. and upto 49.02 Hz. 414.4Below 49.02 Hz. 420.0Between 50.5 Hz. and 49.02 Hz. Linear in 0.02 Hz. step
Unscheduled Interchanges (UI)
UI rate w.e.f 01.04.04 to 30.09.04 UI rate (Paise per KWh)
Average Frequency of time block50.5 Hz. and above 0.0Below 50.5 Hz. and upto 50.48 Hz. 8.0Below 49.04 Hz. and upto 49.02 Hz. 592.0Below 49.02 Hz. 600.0Between 50.5 Hz. and 49.02 Hz. Linear in 0.02 Hz. step
• UI rate w.e.f 01.10.04 UI rate (Paise per KWh)
Average Frequency of time block (Hz,)Below Not below ----- 50.50 0.050.50 50.48 6.050.48 50.46 12.0----- ----- ----- ----- ----- ----- 49.84 49.82 204.049.82 49.80 210.049.80 49.78 219.049.78 49.76 228.0----- ----- ----- ----- ----- ----- 49.04 49.02 561.049.02 ----- 570.0(Each 0.02 Hz. Step is equivalent to 6.0 paise/kWh in the 50.5-49.8 Hz. Frequency range and to 9.0 paise/kWh in the 49.8-49.0 Hz. Frequency range).
Energy transactions of UI from/to Pool
Over Gen. By ISGS-1
Under drawl by SEB-A
UI import from IR-1
Under gen. By ISGS-2
No one to one correspondence
System frequency UI
RateRegional Pool
Over drawl by SEB-BUI Export to IR-2
Operation of Pool
Separate Pool a/cs operated by RLDCs on behalf of REBs for UI, IRE and Reactive charges
Regional Pool
Payable by ISGS-2
Payable by SEB-BPayable by IR-2at its UI rate
Receivable by ISGS-1 (up to DC) Receivable by SEB-A Receivable by IR-1
at its UI rateNo one to one correspondence
No cross adjustments allowed between the constituents
Where do SEMs come into picture?
• Only measuring Deviations from Schedulei.e. UI
• To measure 15 min block-wise Energy and Frequency
Issues concerned :-Specifications-Location criterion-Main/Check/Standby philosophy
ISTS
ISGS -II
SEB-B drawalMain = (T+U+X)
Standby = (V+W+Y)
SEB-A drawalMain = (G+H+N+O+Y)Standby = (L+M+Q+R+X)
Metering Philosophy under ABT regime
Other than NTPC Station
ISGS-I injectionMain = (F+G+H+J+K)Check=(F'+L+M+J'+K')Standby = (A+B+C+D+E)
NTPC Station
SEB-B
ISGS-II injectionMain = (M1+M2)Check=(C1+C2)Standby = (S1+S2)
ISGS -I
Aux. Aux.
ISTS
ISTS
SEB-A
SEB-A
A B D EC
FF'
G HJJ'
KK'
L M
SEB-A
ST U
VW
X
Y
SEB-B
N O P
Q R
C1 C2
M1 M2
S1 S2
Aux.
Main Meter
Standby Meter
Check Meter
Points for Energy AccountingInjection by NTPC Generating Stations :
Main &check meters on Outgoing feeders Standby meters on HV side of GT/TT
Injection by other Generating Stations :
Main &check meters on HV side of GT/TT Standby meters on Outgoing feeders
Drawl by SEBs
Main -HV side of ICTs at GS and CTU S/S, Receiving end of Lines directly connected to ISGS
Respective ends of Lines connected to other SEBs Standby – LV/ Tertiary side of ICTs
Other end of lines connected to other SEBs
Special Energy Meter FeaturesSpecial Energy Meter Features
• STATIC TYPE
• COMPOSITE METER
• HIGHEST ACCURACY IN POWER INDUSTRY
• 3 PHASE-4 WIRE CONNECTIONS / MEASUREMENT
• DIRECT MEASUREMENT AS PER CT/PT SECONDARY QUANTITIES
- 110V PH TO PH/63.51 V PH-N
- 1 AMP OR 5 AMP
- VA BURDEN NOT >10 ON ANY OF THE PHASES
• WORKS ON REAL TIME CLOCK
• NO CALIBRATION REQUIRED
• TIME ADJUSTMENT FACILITY
• HIGH SECURITY OF DATA STORAGE
Raw dataWEEK FROM 0000 HRS OF 06-01-01 TO 0837 HRS OF 15-01-01NP-0185-A 91858.5 99968.5 39195.5 06-01-01 00 51 +21.57 48 +21.68 50 +21.71 49 +21.33 …. 04 19 +20.61 23 +20.80 19 +21.05 00 +21.35 … 08 00 +24.95 00 +24.95 00 +25.09 00 +24.38 … 12 71 +24.38 52 +23.98 30 +23.81 13 +24.03 …16 00 +23.37 00 +23.52 00 +22.87 00 +21.66 … 20 00 +25.75 00 +25.32 00 +25.40 00 +25.37 … NP-0185-A 94117.2 99968.5 40313.5 07-01-01 00 59 +20.94 54 +21.01 59 +20.79 58 +21.05 … 04 33 +20.05 38 +20.17 37 +20.49 28 +20.90 …08 00 +22.99 06 +23.10 00 +22.81 00 +22.94 … 12 85 +20.93 51 +20.65 21 +20.79 00 +19.89 … 16 07 +20.14 01 +20.53 00 +20.72 00 +20.66 …20 05 +23.62 08 +23.23 16 +23.25 27 +23.40 … NP-0185-A 96172.2 99968.5 41236.9 08-01-01
Special Energy Meter Various ChecksSpecial Energy Meter Various Checks
CHECKS for DATA VALIDATION :
• NOMINAL VOLTAGE CHECK• FREQUENCY• TIME CORRECTION• WATTHOUR CHECK• PREVIOUS WEEK DATA• ALGEBRAIC SUM
• RAW DATA IN WHr
• MWhr = RAW DATA x CT RATIO x PT RATIO
• PAIR CHECK DONE FOR MAIN/ CHECK/ STANDBY/ FICTMETERS ( ex. : for both sides of ICTs, Lines, GT side & Line side at ISGS.
Special Energy Meter Data ComputingSpecial Energy Meter Data Computing
Reactive Energy Accounting
Reactive Energy is measured
when system voltage is
> 103% of Nominal Voltage< 97% of Nominal Voltage
Loss computations
15 min block-wise % loss =
(Sum of all Injections from ISGS + net IR imports)
X 100
(Sum of all Injections from ISGS + net IR imports) -
(Sum of Drawals by all beneficiaries from Central Grid)
Use of Notional Loss in scheduling
• % Average loss (15 min. blockwise) aggregated over the last week will be used in Scheduling Process for the next week.
(for arriving at the ex-periphery Drawal Schedules of Beneficiaries)
0.5% REDUCTION MEANS MORE THAN 100 CR ANNUAL SAVINGS0.5% REDUCTION MEANS MORE THAN 100 CR ANNUAL SAVINGS
Loss for the week Loss % Week applied for
From To From To
16-Sep-02 22-Sep-02 4.83 30-Sep-02 6-Oct-02
6-Jan-03 12-Jan-03 3.9 20-Jan-03 26-Jan-03
20-Oct-03 26-Oct-03 3.38 3-Nov-03 9-Nov-03
19-Jan-04 25-Jan-04 3.92 2-Feb-04 8-Feb-04
24-May-04 30-May-04 2.55 7-Jun-04 13-Jun-04
9-Aug-04 15-Aug-04 2.54 23-Aug-04 29-Aug-04
17-Jan-05 23-Jan-05 3.25 31-Jan-05 6-Feb-05
7-Feb-05 13-Feb-05 3.04 21-Feb-05 27-Feb-05
30-May-05 5-Jun-05 2.95 13-Jun-05 19-Jun-05
27-Jun-05 3-Jul-05 3.49 11-Jul-05 17-Jul-05
11-Jul-05 17-Jul-05 3.73 25-Jul-05 31-Jul-05
25-Jul-05 31-Jul-05 3.53 8-Aug-05 14-Aug-05
1-Aug-05 7-Aug-05 3.3 15-Aug-05 21-Aug-05
8-Aug-05 14-Aug-05 2.92 22-Aug-05 28-Aug-05
TYPICAL %AVERAGE LOSS FIGURES FOR CENTRAL GRID IN SR
%Average losses In other Regions :
NR 3.5 to 4.5
ER 3.0 to 3.5
WR 5.0 to 6.0
OTHER REGIONS
%loss for different weeks from 2003- 2005
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Week No.
%lo
ss
2003-042004-05
2005-06
METERING LOCATIONS IN SR
• Total No Of SEMS in SR USED FOR REA 350
No.s• Total No Of SEMS in KPTCL USED FOR REA
50 No.s
KAKINADA
PO 05
REA METERING LOCATION OF STATE OWNED INTER STATE LINES IN SOUTHERN REGION
HOSUR
HOSUR
YERANDAHALLY
2
20 KV .
YERANDAHALLY
2
20 KV .
MANJESWAR
UPPATI
KADAKOLA
KNYMPTTAKONEJA
ARAKU
BALIMELA
OS
AP
TN
KERKAR
GOA
LOW
ER
SIL
ER
U
BA
RS
UR
HVDC
KO
LLA
PU R
K'T
HA
RA
I
UD
UM
ALP
ET
KA
YA
TH
AR
TH
EN
I
BELLARY
TANDUR GOOTY
SEDAM
CH
IKK
OD
I
MO
OZ
HIY
AR
ED
MO
N
IDU
KK
I
PA
RA
SA
LA
MH
MP
220
KV
220
KV
220
KV
220
KV
220
KV
220
KV
110
KV
220
KV
132
KV
66 K
V
110
KV
220 KV
110 KV
AP57
AP55
AP56
OS 58
P0 06
TN 56
AP 54 TN 57
TN 54
TN51
TN52
TN53
TN58
KL52
KL53
KL51
TN 55
CK 54
CK 51
CK 52
KL 55
KL 56CK56
CK59
CK58
GO01
GO02
GO03
CK57
AP 58AP 52
CK 60
CK 61
CK 55
CK 53KL58
PONDY(Yanam)
132
KV 21
XELDEM
21
GO04
UPPERSILERU
PONDA
PONDA
AMBEWADI SUPA
MACHKHUNBALIMELA
AP 53CHITOOR TIRUVALEM
SULURPET
G'P
UN
DI
KOOTHAMUNDA
220 KV
220 KV
220 KV
220 KV
220 KV
132 KV
220
KV
110
KV
INTER STATE LINES METERING LOCATIONS
METERING LOCATIONS IN KPTCL'S INTERCONNECTED SYSTEM
AP-51CK-53
TANDUR
GOOTY
A PAP-52CK-55
BELLARY
SEDAM
TN-55CK-54HOSURYERANDAHALLI
T N
CK-22CK-21
CK-05CK-06
CK-03CK-04
BANGALORE
RAICHUR N'SAGAR
MBD
N'SAGAR
MBD
CENTRAL TR. SYSTEM
CK-51KL-55
KL-56 CK-52
KONAJE
KADAKOLA
MANJESWAR
KANIAMPETTA
KSEB
GO-03
GO-04
GO-01
GO-02AMBEWADI
XELDEMXELDEM
PONDA
PONDA
PONDA SUPA
GOA(SR)
KG-24
KG-23
KG-22
KG-21
KODASALLI
KADRA
SIRSI-2
SIRSI-1
KGS
CK-60
CK-61CHIKKODI
KolhapurWR/MSEB
CK-01CK-02
HOODY
SR-63
SR-64
BANGALORE
BANGALORE
CK-57CK-57
CK-58
CK-56
CK-57
KOLAR
220kV
220kV
220kV
110kV
110kV
220kV
220kV
220kV
220kV
220kV
220kV
220kV
220kV
400kV
220/400kV
220/400kV
220/400kV
CK-11CK-12
KOLARKOLAR
220/400kV
110kV
400kV
GOOTY
CK-21RAICHUR
4 5 6 7
CK-23
CK-05
CK-06
CK-24
CK-27
CK-25
SR-81
DAVANAGERE
CK-26
NELAMANGALA
CK-28
CK-09
CK-10
CK-30
CK-31
HOODY
CK-07
CK-08
CK-15
CK-16
HIRIYUR
CK-29
CK-32 CK-33
CK-13
CK-14
BANGALORE
SR-11
N'Sagar
Kolar
Munirabad
CK-35
CK-34
CK-36
CK-37
Temporary Configuration :Karnataka's drawl in Raichur-Hoody section:Raichur = -(CK-21) -(CK-23) -(CK-25); Muniarabd=(CK-05) ; Davanagere=(CK-07); Hiriyur=(CK-15); Nelamangala= -(CK-29)-(CK-30)-(CK-35) -(CK-36) -(CK-38);Hoody = (CK-09)+(CK-13)
CK-30
CK-31
CK-38
Karnataka's drawl in Raichur-Hoody section:
Raichur = -(CK-21) -(CK-23) -(CK-25);
Muniarabd=(CK-05) ;
Davanagere=(CK-07); Hiriyur=(CK-15);
Nelamangala= -(CK-29)-(CK-30)-(CK-35)
-(CK-36) -(CK-38);
Hoody = (CK-09)+(CK-13)
RAICHUR SECTION
KPTCL'S DRAWL ON 400kV RAICHUR-DAVANAGERE SECTION
(CK-RC)=-(CK-21)-(CK-23)-(CK-25) -(CK-29)-(CK-30)+ (CK-35)+ (CK-36) (CK-38) + (CK-05)+ (CK-07) +(CK-09) + (CK-13) + (CK-15)
KPTCL'S DRAWL ON 400kV
(CK-91)= (CK-01)+(CK-03)+(CK-RC) +(CK-11)
CK'S DRAWL ON 220kV
(CK-92)= -(CK-51)-(CK-53)-(CK-54)-(CK-55)-(CK-58)-(CK-59)+(KG-21)
+(KG-22)+(KG-23)+(KG-24)
CK'S DRAWL ON 132kV
(CK-93)=-(CK-52)-(CK-56)
TOTAL DRAWL (CK-94)=(CK-91)+(CK-92)+(CK-93)NOTE: SEMS ON FEEDERS NOT CARRYING ISGS POWER NOT TO BE CONSIDERED
REACTIVE ENERGY CHARGE :
PAYABLE FOR :
1. VAR DRAWALS AT VOLTAGES BELOW 97%2. VAR INJECTION AT VOLTAGES ABOVE 103%
RECEIVABLE FOR:
1. VAR INJECTION AT VOLTAGES BELOW 97%2. VAR DRAWAL AT VOLTAGES ABOVE 103%
APPLIED FOR VAR EXCHANGES BETWEEN :
A) BENEFICIARY SYSTEM AND ISTS- THROUGH A POOL ACCOUNT
B) TWO BENEFICIARY SYSTEMS ON INTER-STATE TIES- BY THEMSELVES
RATE: @ Rs. 51.05/MVArh (for 205-06)Basic Rate : 4 paise/kvArh ( for the year 2000-01 )
5% ESCALATION PER YEAR
Issues in Reactive Energy charges
• Deficit in pool (SR & ER)-due to continuous High voltages in SR
Surplus in Pool (NR &WR)
Utilization of Accruals
Disputes in payments between Beneficiaries for Reactive charges in Inter-state Lines
SOUTHERN REGIONAL ELECTRICITY BOARDABT based U.I. AccountFOR A TYPICAL WEEK
NNOTE:
1. MAPS & KGS not covered under ABT; hence UI reduced to zero, under all conditions. IR Exchanges: - Metering points – For WR it is Chandrapur South Bus.
- For ER it is Gazuwaka East Bus & Talcher stage I&II interconnecting bus. ii) UI for IR exchanges with ER has been calculated at ER frequency.iii) UI charges with WR and ER has been taken as first charge, as per decision taken in Special Committee meeting held on 17.12.2002.
A. ABSTRACT OF UNSCHEDULED INTERCHANGES ( UI figures in Rs. Lakhs)
Utilities UI
PayableUtilities UI Receivable
KPTCL 720.47741 TNEB 641.48459
KSEB 457.19673 APTRANSCO 269.73260
PONDY 124.38710 ER 188.40533
NLC_II_2 14.72798 RSTPS 84.30154
NLC_II_1 13.81846 GOA 10.67606
TALCHER_II 2.36108 NLC_I_EXP 2.25996
WR 1.32476
TOTAL1332.9687
6TOTAL 1198.18484
A. ABSTRACT OF UNSCHEDULED INTERCHANGES (restricting to the lesser of the two as per the 126th SRE Board decision). (UI figures in Rs. Lakhs)Utilities UI Payable Utilities UI Receivable
KPTCL 647.62591 TNEB 641.48459
KSEB 410.96701 APTRANSCO 269.73260
PONDY 111.80962 ER 188.40533
NLC_II_2 13.23876 RSTPS 84.30154
NLC_II_1 12.42120 GOA 10.67606
TALCHER_II 2.12234 NLC_I_EXP 2.25996
WR 1.32476
TOTAL 1198.18484 TOTAL 1198.18484
payable to Pool
receivable from
APTRANSCO 516417KPTCL 1998690KSEB 231733TNEB 3185840
B.NET REACTIVE ENERGY CHARGES BETWEEN BENEFICIERIES:
280
0
APTRANSCOKPTCLKSEBAPTRANSCOKPTCL
11,410
0235,924
KPTCLTNEB
00
TNEBGOA
04,853
APTRANSCOKSEB
0APTRANSCO0
TNEBPONDY
0
A.REACTIVE ENERGY CHARGES WITH THE POOL :
( Amount in Rupees)
BY BENEFICIERY
FROM BENEFICIERY
KPTCL
AMOUNT RECEIVABLE
in Rupees
Beneficiaries Beneficiaries
GOA
KPTCL
KSEB
TNEB
PONDY
0
(as per decision in the 132nd meeting of SRE Board)