  • 8/10/2019 Refrigiration and Aircondition Notes

    1/18

    Refrigeration

    - an introduction to the basics

    LectureREFRIGERATION &

    AIR CONDITIONING DIVISION

    MAKING MODERN LIVING POSSIBLE

  • 8/10/2019 Refrigiration and Aircondition Notes

    2/18

    Automatic Controls and Compressors for refrigeration

    Automatic controls for

    commercial refrigeration

    Automatic controls for

    Industrial refrigeration

    Electronic controls for refrigeration Appliance controls

    Compressors for household

    and commercial refrigeration

    Condensing units

  • 8/10/2019 Refrigiration and Aircondition Notes

    3/18

    This Danfoss publication must be regarded as a supplement to the comprehensive literature on refrigera-

    tion that is available today and which is primarily aimed at readers with a professional relationship to the

    refrigeration industry/trade e.g. refrigeration engineers and installers.

    The contents of this book are intended to interest those who are not engaged every day with refrigeration

    plant but who wish to extend their knowledge on the basic principles of appliances they see every day.

    When compiling the material for the booklet a deliberate attempt was made to provide a thorough descrip-

    tion of the elementary principles involved together with an explanation in everyday language of the practical

    design of the individual components.

    For additional training material we refer to:

    http://www.danfoss.com/BusinessAreas/RefrigerationAndAirConditioning

    Choose Training & Education.

    Nordborg, 2007

    Refrigeration -an introduction to the basics

    Contents

    1. Introduction....................... ........................ ........................ ........................ ........................ ........................ ........................ ................... 3

    2. Fundamental terms........................ ........................ ........................ ........................ ......................... ....................... ........................ ... 42.1 Unit systems .............................................. ..................................................... .................................................... .................................................... ...................... 42.2 Temperature .............................................. ..................................................... .................................................... .................................................... ...................... 42.3 Force and pressure .................................................... .................................................... .................................................... ..................................................... ....5

    2.4 Heat, work, energy and power .............................................. ..................................................... .................................................... ....................................... 52.5 Substances and phase change .............................................. ..................................................... .................................................... ....................................... 62.6 Latent heat ................................................. ..................................................... .................................................... .................................................... ...................... 72.7 Superheat ................................................... ..................................................... .................................................... .................................................... ...................... 72.8 Refrigerant diagrams.......................................................................................... .................................................... .................................................... ...............8

    3. Refrigerant circuit....................... ........................ ........................ ........................ ........................ ........................ ........................ ....... 93.1 Evaporator.....................................................................................................................................................................................................................................93.2 Compressor...................................................................................................................................................................................................................................93.3 Compressor, method of operation ................................................ .................................................... ..................................................... .............................. 93.4 Condenser .................................................. ..................................................... .................................................... .................................................... ................... 103.5 Expansion process ..................................................... .................................................... .................................................... ..................................................... . 103.6 High and low pressure sides of the refrigeration plant .....................................................................................................................................................10

    4. Refrigeration process, pressure/enthalpy diagram ....................................................................................................... 11

    5. Refrigerants ....................................................................................................................................................................................... 125.1 General requirements .............................................. .................................................... .................................................... ..................................................... . 125.2 Fluorinated refrigerants .................................................. ..................................................... .................................................... ............................................. 125.3 Ammonia NH3.................................................... .................................................... ..................................................... .................................................... .......... 125.4 Secondary refrigerants ..................................................... .................................................... .................................................... ............................................. 12

    6. Refrigeration plant main components.................................................................................................................................. 136.1 Compressor......................................................... .................................................... ..................................................... .................................................... .......... 136.2 Condenser .................................................. ..................................................... .................................................... .................................................... ................... 136.3 Expansion valve ................................................ .................................................... ..................................................... .................................................... .......... 156.4 Evaporation systems ................................................ .................................................... .................................................... ..................................................... . 16

    7. The practical build-up of a refrigeration plant ................................................................................................................. 17

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H0924 1

  • 8/10/2019 Refrigiration and Aircondition Notes

    4/18

  • 8/10/2019 Refrigiration and Aircondition Notes

    5/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 3

    The job of a refrigeration plant is to cool articlesor substances down to, and maintain them at atemperature lower than the ambient tempera-ture. Refrigeration can be defined as a processthat removes heat.

    The oldest and most well-known among refrige-rants are ice, water, and air. In the beginning, the

    sole purpose was to conserve food. The Chinesewere the first to find out that ice increased the lifeand improved the taste of drinks and for centu-ries Eskimos have conserved food by freezing it.

    1. Introduction

    Aa0_

    0003

    _00_

    A1

    heat heat

    Aa0_

    0002_

    00_

    A1

    Danfoss

    R64-1869.1

    0

    At the beginning of the last century, terms likebacteria, yeast, mould, enzymes etc. were known.It had been discovered that the growth of micro-organisms is temperature-dependent, thatgrowth declines as temperature falls, and thatgrowth becomes very slow at temperatures be-low +10 C.

    As a consequence of this knowledge, it was nowpossible to use refrigeration to conserve food-stuffs and natural ice came into use for this pur-pose.

    The first mechanical refrigerators for the produc-tion of ice appeared around the year 1860. In1880 the first ammonia compressors and insulat-ed cold stores were put into use in the USA.

    Electricity began to play a part at the beginningof this century and mechanical refrigerationplants became common in some fields: e.g. brew-

    eries, slaughter-houses, fishery, ice production,for example.

    After the Second World War the development ofsmall hermetic refrigeration compressors evolvedand refrigerators and freezers began to take theirplace in the home. Today, these appliances are re-garded as normal household necessities.

    There are countless applications for refrigerationplants now. Examples are:

    Foodstuff conservationProcess refrigerationAir conditioning plantsDrying plantsFresh water installationsRefrigerated containersHeat pumpsIce productionFreeze-drying

    Transport refrigeration

    In fact, it is difficult to imagine life without airconditioning, refrigeration and freezing - theirimpact on our existence is much greater thanmost people imagine.

    Danfoss

    R64-1866.1

    0

  • 8/10/2019 Refrigiration and Aircondition Notes

    6/18

    Lecture Refrigeration - an introduction to the basics

    4 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    2.1 Unit systems

    2. Fundamental terms On an international level, agreement has beenreached on the use of the Systeme InternationaldUnits- often referred to as the SI-system. For anumber of countries the implementation of theSI-system is still an on-going process.

    In this booklet the SI-system will be the primaryunit system used. However, in many parts of the

    refrigeration community it is still practice to usemetric units or other alternative units. Therefore,the practically used alternative units will be givenin parenthesis where needed.

    The table shows the SI-units and the other oftenused alternative units for the quantities that areused in this booklet.

    Quantity SI-unit Alternative units

    Time s (second) h (hour)

    Length m (meter) in (inch)ft (foot)

    Mass kg (kilogram) lb (pound)

    Temperature K (Kelvin) C (Celsius)F (Fahrenheit)

    Force N (Newton) kp (kilopond)

    Pressure Pa (Pascal) = N/m2 bar

    atm (atmosphere)

    mm Hg (millimeter mercu-ry column)

    psi (pound per square inch)

    Energy J (Joule) = Nm kWh (kilowatt hour)

    cal (calorie)

    Btu (British thermal unit)

    Power W (Watt) = J/s calorie/h, Btu/h

    Name pico nano micro mili kilo Mega Giga Tera Peta

    Prefix p n m m k M G T P

    Factor 10-12 10-9 10-6 10-3 103 106 109 1012 1015

    2.2 Temperature Temperature is a very central property in refriger-ation. Almost all refrigeration systems have thepurpose of reducing the temperature of anobject like the air in a room or the objects storedin that room.

    The SI-unit for temperatureKelvin[K]is an abso-lute temperature because its reference point [0 K]is the lowest temperature that it in theory wouldbe able to obtain.

    When working with refrigeration systems thetemperature unit degree Celsius [C]is a morepractical unit to use. Celsius is not an absolute

    temperature scale because its reference point(0 C) is defined by the freezing point of water(equal to 273.15 K).

    The only difference between Kelvin and Celsius isthe difference in reference point. This means thata temperature difference of 1 C is exactly thesame as a temperature difference of 1 K.

    In the scientific part of the refrigeration commu-nity temperature differences are often describedusing [K] instead of [C]. This practice eliminatesthe possible mix-up of temperatures and temper-ature differences.

    The choice of prefix is free but the best choicewill normally be the one where the value written

    will be in the range from 0.1 to 999.9.

    Prefixes should not be used for combined SI-units- except when [kg] is used.

    Example:2000 W/m2K should be written as 2.000 103W/m2K and not as 2 kW/m2K.

    The practical use of the SI-units is strongly associ-ated with the use of the decadic prefixes to avoid

    writing either very small or large numbers. A partof the prefixes used can be seen in the table be-low.

    Example:The atmospheric air pressure is 101325 Pa. Usingthe decadic prefixes from the table below thebest way of writing this would be 101.325 kPa.

  • 8/10/2019 Refrigiration and Aircondition Notes

    7/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 5

    Fundamental terms The SI-unit for force is Newton(N)which is actual-ly a [kg m/s2].

    A man wearing skis can stand in deep snow with-out sinking very deep - but if he steps out of hisskis his feet will probably sink very deep into thesnow. In the first case the weight of the man isdistributed over a large surface (the skis). In the

    second case the same weight is distributed onthe area of his shoe soles - which is a much small-er area than the area of the skis. The differencebetween these two cases is the pressure that theman exerts on the snow surface.

    Pressure is defined as the force exerted on anarea divided by the size of the area. In the exam-ple with the skier the force (gravity) is the same inboth cases but the areas are different. In the firstcase the area is large and so the pressure be-comes low. In the second case the area is smalland so the pressure becomes high.

    2.3 Force and pressure

    In refrigeration pressure is mostly associated withthe fluids used as refrigerants. When a substancein liquid or vapour form is kept within a closedcontainer the vapour will exert a force on the in-side of the container walls. The force of the va-pour on the inner surface divided by its area iscalled the absolutepressure.

    For practical reasons the value for pressure issometimes stated as pressure above atmospher-ic pressure - meaning the atmospheric pressure(101.325 kPa = 1.013 bar) is subtracted from theabsolute pressure. The pressure above atmos-pheric pressure is also often referred to asgauge

    pressure.

    The unit used should reflect the choice of abso-lute pressure or gauge pressure. An absolutepressure is indicated by the use of lowercase aand a gauge pressure is indicated by a lower-case g.

    Example:The absolute pressure is 10 bar(a) which convert-ed to gauge pressure becomes (10 - 1.013) bar(g)9 bar(g). The combination of the SI-unit forpressure [Pa] and the term gauge pressure is notrecommended.

    Other units for pressure that are still used todayare mm of mercury column[mmHg], and meter wa-ter gauge[mwg]. The latter is often used in con-nection with pumps to indicate the height of thewater column that the pump is able to generate.

    Vacuum is defined as an absolute pressure of 0 Pa

    - but since it is almost impossible to obtain thisthe term vacuum is used generally to describe apressure much lower than the atmospheric pres-sure. Example: The absolute pressure is 0.1 bar(a)which converted to gauge pressure becomes(0.1 - 1.013) bar(g) 0.9 bar(g). Vacuum is alsooften described in Torr(1 Torr is equal to 10 Pa)andmillibar(a thousandth of a bar).

    2.4 Heat, work, energy andpower

    Heat and work are both forms of energy that canbe transferred between objects or systems. Thetransfer of heat is closely connected to the tem-perature (or temperature difference) that existsbetween two or more objects. By itself heat is al-ways transferred from an object with high tem-perature to objects with lower temperatures.Heating of water in a pot on a stove is a goodeveryday example of the transfer of heat. Thestove plate becomes hot and heat is transferredfrom the plate through the bottom of the pot andto the water. The transfer of heat to the watercauses the temperature of the water to rise. Inother words, heating an object is the same as trans-ferring energy (heat) to the object.

    In many practical applications there is a need toreduce the temperature of an object instead of

    increasing it. Following the example above thiscan only be done if you have another object with

    a lower temperature than that of the object youwish to cool. Putting these two objects into con-tact will cause a transfer of heat away from theobject you wish to cool and, consequently, itstemperature will decrease. In other words, coolingan object is the same as transferring energy (heat)away from the object.

    The transfer of work is typically connected to theuse of mechanical shafts like the one rotating inan electric motor or in a combustion engine.Other forms of work transfer are possible but theuse of a rotating shaft is the primary methodused in refrigeration systems.

    As mentioned both heat and work are forms of en-ergy. The methods of transfer between objects aredifferent but for a process with both heat and work

    transfer it is the sum of the heat and work transferthat determines the outcome of the process.

  • 8/10/2019 Refrigiration and Aircondition Notes

    8/18

    Lecture Refrigeration - an introduction to the basics

    6 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    Fundamental terms The SI-unitJoule[J]is used to quantify energy,heat and work. The amount of energy needed toincrease the temperature of 1 kg of water from 15to 16 C is 4.187 kJ. The 4.178 kJ can be trans-ferred as heat or as work - but heat would be themost used practical solution in this case.

    There are differences in how much energy is re-

    quired to increase the temperature of varioussubstances by 1 K. For 1 kg of pure iron app.0.447 kJ is needed whereas for 1 kg of atmos-pheric air only app. 1.0 kJ is needed. The propertythat makes the iron and air different with respectto the energy needed for causing a temperatureincrease is called the specific heat capacity. It isdefined as the energy required to cause a tem-perature increase of 1 K for 1 kg of the substance.

    The unit for specific heat capacity isJ/kg K.

    The rate at which energy is transferred is calledpower. The SI-unit for power is Watt (W).

    Example:If 10 J is transferred per second, the rate of energytransfer is stated as 10 J/s = 10 W. In the SI-systemthe choice of unit for power is the same for transferof heat and work. In other unit systems the transferrates for heat and work could have different units.

    All substances can exist in three different phases:solid, liquid, and vapour. Water is the most naturalexample of a substance that we use almost every-day in all three phases. For water the three phaseshave received different names - making it a bitconfusing when using it as a model substance.

    The solid form we call ice, the liquid form we justcall water, and the vapour form we call steam.What is common to these three phases is that thewater molecules remain unchanged, meaningthat ice, water, and steam all have the samechemical formula: H2O.

    When taking a substance in the solid to the liq-

    uid phase the transition process is called meltingand when taking it further to the vapour phasethe transition process is called boiling (evapora-tion). When going in the opposite direction

    2.5 Substances and phasechange

    taking a substance from the vapour to the liquid

    phase the transition process is called condens-ing and when taking it further to the solid phasethe transition process is called freezing (solidifi-cation).

    2.4 Heat, work, energy andpower (cont.)

    At constant pressure the transition processes dis-play a very significant characteristic. When ice isheated at 1 bar its temperature starts rising untilit reaches 0 C - then the ice starts melting.During the melting process the temperature doesnot change - all the energy transferred to themixture of ice and water goes into melting the iceand not into heating the water. Only when the icehas been melted completely will the furthertransfer of energy cause its temperature to rise.

    The same type of behaviour can be observedwhen water is heated in an open pot. The water

    temperature increases until it reaches 100 C -then evaporation starts. During the evaporationprocess the temperature remains at 100 C. Whenall the liquid water has evaporated the tempera-ture of the steam left in the pot will start rising.

    The temperature and pressure a substance is ex-posed to determine whether it exists in solid, liq-uid, or vapour form - or in two or all three formsat the same time. In our local environment ironappears in its solid form, water in its liquid andgas forms, and air in its vapour form.

    Danfoss

    R64-1850.1

    0

    1 kcal

    (4,187 kJ)

    16 Co

    15 Co

    Danfoss

    R64-1851.1

    0

  • 8/10/2019 Refrigiration and Aircondition Notes

    9/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 7

    Fundamental terms

    Going back to the process of ice melting it is im-portant to note that the amount of energy thatmust be transferred to 1 kg of ice in order to meltit is much higher than the energy needed tochange the temperature of 1 kg of water by say

    1 K. In section 2.4 the specific heat capacity ofwater was given as 4.187 kJ/kg K. The energyneeded for melting 1 kg of ice is 335 kJ. The sameamount of energy that can melt 1 kg of ice canincrease the temperature of 1 kg of water by(335 kJ/4.187 kJ/kg K) = 80 K!

    When looking at the boiling process of water theenergy needed for evaporating 1 kg of water is2501 kJ. The same amount of energy that canevaporate 1 kg of water can increase the tempe-rature of not 1 but 6 kg of water by 100 K!

    These examples show that energy transfer relat-ed to the transitional processes between phases

    is significant. That is also why ice has been usedfor cooling - it takes a lot of energy to melt the

    2.6 Latent heat

    ice and while the ice melts the temperature staysat 0 C.

    The refrigerating effect in refrigeration systems isbased on the use and control of the phase transi-tion processes of evaporation. As the refrigerantevaporates it absorbs energy (heat) from its sur-roundings and by placing an object in thermal

    contact with the evaporating refrigerant it can becooled to low temperature.

    Different substances have different melting andboiling points. Gold for example melts at 1064 C,chocolate at 26 C and most refrigerants melt attemperatures around -100 C!

    For a substance that is present in two of its phas-es at the same time - or undergoing a phasechange - pressure and temperature become de-

    pendent. If the two phases exist in a closed con-tainer and the two phases are in thermal equilib-rium the condition is said to be saturated. If thetemperature of the two-phase mixture is in-creased the pressure in the container will also in-crease. The relationship between pressure andtemperature for saturated conditions (liquid and

    vapour) is typically called the vapour pressurecurve. Using the vapour pressure curve one candetermine what the pressure will be for an evap-orating or condensing process.

    2.5 Substances and phasechange (cont.)

    Superheat is a very important term in the termi-nology of refrigeration - but it is unfortunatelyused in different ways. It can be used to describea process where refrigerant vapour is heatedfrom its saturated condition to a condition athigher temperature. The term superheat can alsobe used to describe - or quantify - the end condi-tion of the before-mentioned process.

    Superheat can be quantified as a temperature dif-ference - between the temperature measuredwith a thermometer and the saturation tempera-ture of the refrigerant measured with a pressuregauge. Therefore, superheat can not be deter-

    2.7 Superheat mined from a single measurement of tempera-ture alone - a measurement of pressure or satura-tion temperature is also needed. When superheatis quantified it should be quantified as a tempera-ture difference and, consequently, be associatedwith the unit [K]. If quantified in [C] it can be thecause of mistakes where the measured tempera-ture is taken for the superheat or vice versa.

    The evaporation process in a refrigeration systemis one of the processes where the term superheatis used. This will be explained further in the nextchapter.

    Danfoss

    R64-1852.1

    0

    0 Co

    26 Co

    Danfoss

    R64-1853.1

    0

    335 kj

    (80 kcal)

  • 8/10/2019 Refrigiration and Aircondition Notes

    10/18

    Lecture Refrigeration - an introduction to the basics

    8 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    Fundamental terms The characteristics of a refrigerant can be illustrat-ed in a diagram using the primary properties asabscissa and ordinate. For refrigeration systemsthe primary properties are normally chosen asenergy content and pressure. Energy content is re-presented by the thermodynamic property of spe-cific enthalpy - quantifying the change in energycontent per mass unit of the refrigerant as it un-

    dergoes processes in a refrigeration system. An ex-ample of a diagram based on specific enthalpy(abscissa) and pressure (ordinate) can be seen be-low. For a refrigerant the typically applicable inter-val for pressure is large - and therefore diagramsuse a logarithmic scale for pressure.

    The diagram is arranged so that it displays the liq-uid, vapour and mixture regions for the refriger-ant. Liquid is found to the left (with a low energycontent) - vapour to the right (with a high energy

    content). In between you find the mixture region.The regions are bounded by a curve - called thesaturation curve. The fundamental processes ofevaporation and condensation are illustrated.

    The idea of using a refrigerant diagram is that itmakes it possible to represent the processes in therefrigeration system in such a way that analysis

    and evaluation of the process becomes easy.When using a diagram determining system oper-ating conditions (temperatures and pressures) sys-tem refrigerating capacity can be found in a rela-tively simple and quick manner.

    Diagrams are still used as the main tool for analysisof refrigeration processes. However, a number ofPC programmes that can perform the same analy-sis faster and with more details have become gen-erally available.

    2.8 Refrigerant diagrams

    Liquid

    Condensation

    Mixture of

    Liquid + Vapour

    (saturated)

    Evaporation Vapour

    Specific enthalpy(energy content)

    Pressure

  • 8/10/2019 Refrigiration and Aircondition Notes

    11/18

  • 8/10/2019 Refrigiration and Aircondition Notes

    12/18

    Lecture Refrigeration - an introduction to the basics

    10 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    The refrigerant gives off heat in the condenser,and this heat is transferred to a medium having alower temperature. The amount of heat given offis the heat absorbed by the refrigerant in theevaporator plus the heat created by compressioninput.

    The heat transfer medium can be air or water, the

    only requirement being that the temperature islower than that which corresponds to the condens-ing pressure. The process in the condenser can oth-erwise be compared with the process in the evapo-rator except that it has the opposite sign, i.e. theconditional change is from vapour to liquid.

    3.4 Condenser

    3.5 Expansion process Liquid from the condenser runs to a collectingtank, the receiver. This can be likened to the tankmentioned under section 3.1 on the evaporator.

    Pressure in the receiver is much higher than thepressure in the evaporator because of the com-

    pression (pressure increase) that has occurred inthe compressor. To reduce pressure to the samelevel as the evaporating pressure a device mustbe inserted to carry out this process, which iscalled throttling, or expansion. Such a device istherefore known either as a throttling device oran expansion device. As a rule a valve is used - athrottle or expansion valve.

    Ahead of the expansion valve the liquid will be alittle under boiling point. By suddenly reducingpressure a conditional change will occur; the liq-

    uid begins to boil and evaporate. This evapora-tion takes place in the evaporator and the circuitis thus complete.

    There are many different temperatures in-volved in the operation of a refrigerationplant since there are such things as sub-cooled liquid, saturated liquid, saturated va-pour and superheated vapour. There are how-ever, in principle, only two pressures; evapo-rating pressure and condensing pressure. Theplant then is divided into high pressure andlow pressure sides, as shown in the sketch.

    3.6 High and low pressure sidesof the refrigeration plant

    Heat

    Superheat zone

    Condenser

    Condensing

    Compressor

    Saturated liquid

    Compressor

    Vapour

    Liquid/vapour

    Liquid

    CondenserEvaporator

    Receiver

    High pressure sideLow pressure side

    Expansion valve

    Com-pressorEvaporator

    Liquid tank (receiver)

    Expansion (throttle) valve

  • 8/10/2019 Refrigiration and Aircondition Notes

    13/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 11

    The condensed refrigerant in the condenser is incondition A which lies on the line for the boilingpoint of the liquid. The liquid has thus a tempera-ture tc,a pressure pcalso called saturated temper-ature and pressure.

    The condensed liquid in the condenser is furthercooled down in the condenser to a lower temper-

    ature A1and now has a temperature tland an en-thalpy h0. The liquid is now sub-cooled whichmeans that it is cooled to a lower temperaturethan the saturated temperature.

    The condensed liquid in the receiver is in condi-tion A1which is sub-cooled liquid. This liquidtemperature can change if the receiver and liquidis either heated or cooled by the ambient tem-perature. If the liquid is cooled the sub-coolingwill increase and visa versa.

    When the liquid passes through the expansionvalve its condition will change from A1to B. Thisconditional change is brought about by the boil-

    ing liquid because of the drop in pressure to p0.At the same time a lower boiling point is pro-duced, t0, because of the drop in pressure.

    In the expansion valve the enthalpy is constanth0, as heat is neither applied nor removed.

    At the evaporator inlet, point B, there is a mixtureof liquid and vapour while in the evaporator at Cthere is saturated vapour. At the evaporator outlet

    4. Refrigeration process,pressure/enthalpydiagram

    point C1there is super-heated vapour whichmeans that the suction gas is heated to a highertemperature than the saturated temperature.Pressure and temperature are the same at point Band at outlet point C1where the gas is super-heat-ed the evaporator has absorbed heat from thesurroundings and the enthalpy has changed to h1.

    When the refrigerant passes through the com-pressor its condition changes from C1to D.Pressure rises to condensing pressure pc. Thetemperature rises to thot-gaswhich is higher thanthe condensing temperature tcbecause the va-pour has been strongly superheated. More ener-gy (from the electrical motor) in the form of heathas also been introduced and the enthalpy there-fore changes to h2.

    At the condenser inlet, point D, the condition isthus one of superheated vapour at pressure pc.Heat is given off from the condenser to the sur-roundings so that the enthalpy again changes tomain point A1. First in the condenser there occurs

    a conditional change from strongly superheatedvapour to saturated vapour (point E), then a con-densation of the saturated vapour. From point Eto point A the temperature (condensing tempera-ture) remains the same, in that condensation andevaporation occurs at constant temperature.From point A to point A1in the condenser thecondensed liquid is further cooled down, but thepressure remains the same and the liquid is nowsub-cooled.

    tc = condensing temperaturepc= condensing pressure

    tl = liquid temperature

    t0 = evaporating temperaturep0 = evaporating pressure

    Expansionvalve

    Receiver

    Pressure

    Heat

    Condenser

    Evaporator

    Heat

    Compressor

    Enthalpy

    hot-gas

  • 8/10/2019 Refrigiration and Aircondition Notes

    14/18

    Lecture Refrigeration - an introduction to the basics

    12 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    5. Refrigerants During the examination of the refrigeration processthe question of refrigerants was not discussed sinceit was not necessary to do so in connection with thebasic physical principles of the conditional changeof substances. It is well known, however, that inpractice different refrigerants are used according tothe specific application and requirements. The mostimportant factors are as follows:

    The refrigerant ought not to be poisonous.Where this is impossible, the refrigerant musthave a characteristic smell or must contain atracer so that leakage can quickly be observed.

    The refrigerant ought not to be flammablenor explosive. Where this condition cannotbe met the same precautions as in the firstpoint must be observed and local legisla-tions must be followed.

    The refrigerant ought to have reasonablepressure, preferably a little higher than at-mospheric pressure at the temperatures re-quired to be held in the evaporator.

    5.1 General requirements

    5.2 Fluorinated refrigerants Fluorinated refrigerants always carry the designa-tion R followed by a number, e.g. R22, R134a,R404A and R407C. Sometimes they are met bear-ing their trade names. The fluorinated refrigerantsall have the following features:

    Vapour is smell-free and non-irritant.Extensively non-poisonous. In the presenceof fire the vapour can give off fluoric acidand phosgene, which are very poisonous.Non-corrosive.Non-flammable and non-explosive.

    The most common fluorinated refrigerants are:

    R134a, which is a substance of the ethane groupwith the formula CH2FCF3and has a normal boilingpoint of 26.1 C. Its thermodynamic propertiesmake it suitable as a refrigerant for medium temper-ature applications such as domestic refrigerators.

    R22, which is a substance of the methane groupwith the formula CHF2CI and has a boiling point of40.8 C. Its thermodynamic properties make itsuitable as a refrigerant for a wide range of applica-tions in commercial refrigeration and air condition-ing. R22 is being phased out as refrigerant in manycountries due to its ozone depleting potential.

    R404A/R507A(also known as R507), which is amixture of the refrigerants R125 (CHF2CF3) and

    R143a (CH3CF3) with a boiling point at (46.7 C)which is slightly lower than for R22. Its thermody-namic properties makes it suitable as a refrigerantfor low and medium temperature applications incommercial refrigeration (e.g. supermarkets).

    R407C, which is a mixture of the refrigerants R32(CH2F2), R125 (CHF2CF3) and R134a (CH2FCF3) witha boiling point at (43.6 C) which is slightly lowerthan for R22. Its thermodynamic properties makeit suitable as a refrigerant for medium and hightemperature applications in residential and com-mercial air conditioning.

    R410A, which is a mixture of the refrigerants R32(CH2F2) and R125 (CHF2CF3) with a boiling point at(51.4 C) which is lower than for R22. Its thermo-dynamic properties make it suitable as a refriger-ant for medium and high temperature applicationsin residential and commercial air conditioning.

    Apart from these fluorinated refrigerants there isa long series of others not seen very often today:R23, R123, R124 and R218.

    Except for R22, systems with fluorinated hydro-carbons are in general lubricated with polyol es-ter oils (POE). These oil types are much more sen-sitive to react chemically with water, the so-calledhydrolysis reaction. For that reason systems to-day are kept extremely dry with filter driers.

    Ammonia NH3is used extensively in large indus-trial refrigeration plants. Its normal boiling pointis 33 C. Ammonia has a characteristic smelleven in very small concentrations in air. It cannot

    5.3 Ammonia NH3 burn, but it is moderately explosive when mixedwith air in a volume percentage of 13 to 28%.Because of corrosion, copper or copper alloysmust not be used in ammonia plants.

    The refrigerants mentioned above are often de-

    signated primary refrigerants. As an interme-diate link in heat transmission from the surround-

    5.4 Secondary refrigerants ings to the evaporator, the so-called secondary

    refrigerants can be used, e.g. water, brine, atmos-pheric air etc.

    To avoid heavy refrigerator design the pres-sure, which corresponds to normal con-densing pressure, must not be too high.Relatively high evaporating temperature isrequired so that heat transmission can occurwith least possible circulating refrigerant.Refrigerant vapour ought not to have toohigh a specific volume because this is a de-

    terminant for compressor stroke at a partic-ular cold yield.

    The refrigerant must be chemically stable atthe temperatures and pressures normal in arefrigeration plant.

    The refrigerant ought not to be corrosiveand must not, either in liquid or vapourform, attack normal design materials.

    The refrigerant must not break down lubri-cating oil.

    The refrigerant must be easy to obtain andhandle.

    The refrigerant must not cost too much.

  • 8/10/2019 Refrigiration and Aircondition Notes

    15/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 13

    The job of the compressor is to suck vapour fromthe evaporator and force it into the condenser.

    The most common type is the piston compressor,but other types have won acceptance, e.g. cen-trifugal scroll and screw compressors.

    The piston compressor covers a very large capac-ity range, right from small single cylinder modeIs

    for household refrigerators up to 8 to 12 cylindermodeIs with a large swept volume for industrialapplications.

    In the smallest applications the hermeticcompressor is used, where compressor andmotor are built together as a complete hermeticunit.

    For medium sized plants one of the mostcommon compressors is the larger sizes ofhermetic compressors in either piston or scrollversions. The applications are both airconditioning, general commercial refrigerationand chillers.

    For larger plants the most common is the semi-hermetic compressor. The advantage here is thatshaft glands can be avoided; these are verydifficult to replace when they begin to leak.However, the design cannot be used on ammoniaplants since this refrigerant attacks motorwindings.

    Still larger HFC compressors, and all ammoniacompressors, are designed as open compres-sors, i.e. with the motor outside the crankcase.Power transmission can be direct to the crank-shaft or through a V-belt drive.

    For quite special applications there is the oil-freecompressor. But lubrication of bearings and cylin-der walls with oil is normally always necessary.On large refrigeration compressors oil is circulat-ed by an oil pump.

    6. Refrigeration plantmain components

    6.1 Compressor

    The purpose of the condenser is to remove theamount of heat that is equal to the sum of theheat absorbed in the evaporator and the heatproduced by compression. There are many diffe-rent kinds of condenser.

    Shell and tube condenser.This type of condenser isused in applications where sufficient cooling wateris available. It consists of a horizontal cylinder withwelded-on flat end caps, which support the cool-ing tubes. End covers are bolted to the end plates.

    The refrigerant condensate flows through thecylinder, the cooling water through the tubes.

    The end covers are divided into sections by ribs.The sections act as reversing chambers for the

    6.2 Condenser

    water so that it circulates several times throughthe condenser. As a rule, the water becomesheated 5-10 C when it has passed through acondenser.

  • 8/10/2019 Refrigiration and Aircondition Notes

    16/18

    Lecture Refrigeration - an introduction to the basics

    14 DKRCC.PF.000.F2.02 / 520H2251 Danfoss A/S (AC-DSL / HBS), 07 - 2007

    If it is desirable or necessary to cut down on theamount of water anevaporating condenser can beused instead. This type of condenser consists of ahousing in which there is a condensing coil, waterdistribution tubes, deflection plates and fans.

    The warm refrigerant vapour is led to the top ofthe condensing coil after which it condenses

    and runs from the bottom of the coil as liquid.

    Refrigeration plant maincomponents

    6.2 Condenser (cont.)

    Water distribution tubes with nozzles are placedover the condensing coil so that water is spreadover and runs down the coil. The fans direct astrong flow of air across the condensing coil.When the falling drops of water meet the up-ward air flow some of the water will evaporate.

    This absorbs the necessary evaporating heatfrom the refrigerant vapour and causes it to con-

    dense.

    1. Fan

    2. Deflector plate

    3. Outer covering

    4. Superheat remover

    5. Condenser tubing

    6. Air intake

    7. Collecting tray

    8. Overflow pipe

    9. Water distribution pipe

    10. Water circulation pump

    11. Air intake

    1. Fan

    2. Deflector plate

    3. Outer covering

    4. Nozzle

    6. Air intake

    7. Collecting tray

    8. Overflow pipe

    9. Cooling water from condenser

    10. Air intake

    11. Cooling water return to condenser

    The principal involving water evaporation isalso used in connection with cooling towers.

    These are installed when the most practical isto place a shell and tube condenser near acompressor. The water is then circulated in acircuit between condenser and cooling tower.

    In principle, the cooling tower is built up

    the same as the evaporating condenser,

    but instead of condensing elements thereare deflector plates. Air is heated on its waythrough the tower by direct contact with thetrickle of water travelling downwards andis, therefore, able to absorb an increasingamount of moisture coming from part-evaporation. In this way, the cooling waterloses heat. Water loss is made up by supplying

    more water.

  • 8/10/2019 Refrigiration and Aircondition Notes

    17/18

    Lecture Refrigeration - an introduction to the basics

    Danfoss A/S (AC-DSL / HBS), 07 - 2007 DKRCC.PF.000.F2.02 / 520H2251 15

    It is possible to save 90-95% water consumptionby using evaporating condensers or coolingtowers, when compared to the water consump-tion of shell and tube condensers.

    For one reason or another it is not always pos-sible to use water for the condensing process. Insuch cases an air-cooled condensermust be

    used. Since air has poor heat transfer characte-ristics, compared with water, a large surface onthe outside of the condensing tubes is neces-sary. This is achieved using large ribs or fins and,in addition, by ensuring generous air circulationmechanically.

    This is the normal condenser for commercial re-frigeration.

    The main purpose of the expansion valve is to en-sure a sufficient pressure differential between thehigh and low pressure sides of the plant. The sim-

    plest way of doing this is to use a capillary tubeinserted between the condenser and evaporator.

    The capillary tube is, however, only used insmall, simple appliances like refrigerators be-

    Refrigeration plant maincomponents

    6.2 Condenser (cont.)

    6.3 Expansion valve cause it is not capable of regulating the amountof liquid that is injected into the evaporator. Aregulating valve must be used for this process,

    the most usual being the thermostatic expan-sion valve, which consists of a valve housing,capillary tube and a bulb. The valve housing isfitted in the liquid line and the bulb is fitted onthe evaporator outlet.

    This figure shows an evaporator fed by a thermo-static expansion valve. A small amount of liquid iscontained in a part of the bulb. The rest of thebulb, the capillary tube and the space above thediaphragm in the valve housing is charged withsaturated vapour at a pressure corresponding tothe temperature at the bulb. The space under thediaphragm is in connection with the evaporatorand the pressure is therefore equal to the evapo-rating pressure.

    1. Inlet with strainer

    2. Cone

    3. Outlet

    4. Bore

    5. Connection for pressure equalizing

    6. Spring housing

    7. Diaphragm

    8. Capillary tube

    9. Spindle for setting spring pretension

    (opening superheat)

    10. Bulb

  • 8/10/2019 Refrigiration and Aircondition Notes

    18/18

    Lecture Refrigeration - an introduction to the basics

    The degree of opening of the valve is determinedby:

    The pressure produced by the bulb temper-ature acting on the top surface of the dia-phragm.

    The pressure under the diaphragm, which isequal to the evaporating pressure.

    The pressure of the spring acting on the un-

    derside of the diaphragm.

    During normal operation, evaporation will ceasesome distance up in the evaporator.

    Then, saturated gas appears which becomes su-perheated on its way through the last part of theevaporator. The bulb temperature will thus beevaporating temperature plus superheat, e.g. at

    Finned evaporator

    Plain tube evaporator

    Ribbed tube evaporator

    6.4 Evaporation systems

    Refrigeration plant maincomponents

    6.3 Expansion valve (cont.)

    10 C evaporating temperature the bulb tem-perature could be 0 C.

    If the evaporator receives too little refrigerant thevapour will be further superheated and the tem-perature at the outlet pipe will rise. The bulb tem-perature will then also rise and with it the vapourpressure in the bulb element since more of the

    charge will evaporate. Because of the rise in pres-sure the diaphragm becomes forced down, thevalve opens and more liquid is supplied to theevaporator. Correspondingly, the valve will closemore if the bulb temperature becomes lower.

    Thermostatic expansion valves are produced inseveral versions and of course there are manyvariants within each type.

    Depending on the application, various require-ments are imposed on the evaporator. Evapora-tors are therefore made in a series of different

    versions.

    Evaporators for natural air circulationare used lessand less because of the relatively poor heat trans-fer from the air to the cooling tubes. Earlier ver-sions were fitted with plain tubes, but now it iscommon to use ribbed tubes or finned elements.

    Evaporator performance is increased significantlyif forced air circulation is used. With an increase ofair velocity the heat transfer from air to tube isimproved so that for a given cold yield a smallerevaporator surface than for natural circulationcan be used.

    As the name implies, a chillercools down liquid.The simplest method is to immerse a coil of tubein an open tank. Closed systems are coming intouse more and more. Here, tube coolers made simi-lar to shell and tube condensers are employed.