Top Banner

of 76

Refrigeration Cycle Demonstration Unit

Jun 01, 2018

Download

Documents

Robert Gilmore
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    1/76

    (ii)

    EDUCATION AND TRAINING EQUIPMENT

    Declaration of Conformity:

    Directives

    (where applicable) 89/392/CEE as amended by 91/368/EEC

    89/336/CEE

    72/23/CEE

    We declare hat the following unit complieswith the aboveEEC directives:

    R633

    Refrigeration Cycle Demonstration Unit

    For and on behalf of

    P.A. HILTON LIMITED

    4,~;._AA

    Technical Director

    P .A. HILTON LIMITED

    HorsebridgeMill, King's Sombome,

    Stockbridge,Hampshire,S020 6PX,

    England.

    Tel No. National Romsey 01794) 388382

    International +44 1794 388382

    Fax No. +44 1794388129

    E-mail: [email protected]

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    2/76

    (i)

    POLICY STATEMENT

    After Sales Service

    We, P.A Hilton Ltd., attach considerable imJX)rtanCen being able to retain die confi(k;nce and goodwill

    of our clients in offering an effective after sales service. Every effort is made to answer clients

    COrIesponOODCCromptly and to JXOvide a rapid follow up of spares and repi.:ement parts by

    maintaining comprehensive stocks of COIDJXmentssually available ex-stock.

    Shouldour clients encounterany difficulty in ~g or maintaininga Hilton prodtx;t we would ask

    that as a first step dley COIU.:tdle Hilton ~tative in their country or. in me absence f a 1

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    3/76

    INDEX

    ~

    SCHEMATIC DIAGRAM

    1

    VALVE POSITIONS DIAGRAM

    2

    SYMBOLS AND UNITS

    3

    4

    4

    4

    INTRODUCTION

    The Refrigeratiooor Heat Pump Cycle

    The ValX>urCompressionCycle

    INSf ALLA nON AND COMMISSIONING

    6

    THE mLTON REFRIGERATION CYCLE DEMONSTRATION UNIT:

    Useful Data

    Specification

    Description

    10

    10

    11

    13

    OPERATING PROCEDURE

    Nonnal Operation

    EvaporationPnx:ess

    Condensation rocess

    Shutting Down the Unit

    RefrigerantPump Down

    Oil Return

    Air Venting

    IS

    IS

    IS

    16

    16

    17

    11

    18

    19

    19

    19

    20

    20

    20

    20

    20

    21

    MAINTENANCE:

    High PressW'e ut Out

    Thennometers

    Minjanue Cin:uit B~ (MCB)

    ResidualCunent Circuit Breaker RCCB)

    Testing the RCCB

    Checking or Leaks

    Chargingor Rechargingwidt Refrigerant

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    4/76

    23

    APABILITIES OF THE REFRIGERATION CYCLE DEMONSTRATION UNIT:

    24

    emonsb'ation of die Vspour Com}Xession Cycle

    .

    The Pressme- emperatmeRelationship 27

    .

    30

    .

    Demonstration f PumpingOver

    31

    emonstration f Charging.

    32

    emonsttationof Effect of Air in a Refrigelation System

    .

    3Sffect of EvaJX)rating and Condensing Temperatures on the Refrigeration Rate

    .

    39

    ffect of Compressor ressureRatio OIl SystemPerformance

    .

    43

    .

    Detenninationof Overall Heat TransferCoefficient

    47

    .

    Generationof a RefrigerationCycle Diagram

    Measurement f dIe Effect of Conoonsing emperature n Com~r Power Input 51

    0.

    53

    BSERVAllON SHEET (Blank)

    54

    141b SATURA nON PRESSURE v TEMPERATURE GRAPH

    ss

    141bP~SURE-ENTHALPY DIAGRAM

    S6

    141b COSHH DATA

    58

    IRING DIAGRAM. R633

    59IRING DIAGRAM - 11O-130Vransformer

    APPENDIX:

    61

    . Optional R633A Digital Temper:ature

    ndicator

    -

    Fitting Instructions

    67

    . Optional R633B Digital Wattmeter-

    Fitting Instructions

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    5/76

    of-'

    .-

    c

    :)

    1

    ~

    4)

    ...

    =

    0)

    it

    "Qj

    ~

    "-

    II

    D

    ~

    +-

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    6/76

    2

    NORMAL OPERATION

    SHUTDOWN

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    7/76

    3

    SYMBOLS AND UNITS

    Svrnool

    kNm-2

    ressure f Refrigerant n Condenser

    c

    tNm-1

    ressure f Refrigerant n Evaporator

    .

    Water Mass Row Rate

    dU'OughCondenser

    e

    1i1.

    Water Mass F1owRate through Evaporator

    Temperature f Water enteringEvaporattl' oc

    t

    oc

    em~ of Water eavingEvaporator

    ~

    emperature f Water leaving Condenser

    ,

    Temperature f Water enteringCondenser

    ~

    ,.

    oc

    vaporating Tempel8t1n"e

    s

    oc

    emperaturen Condenser

    .

    oc

    ,

    CompressorDischargeTemperature

    oc

    s

    Condensed iquid TemperabJre

    W m-~K-1

    Overall Heat Transfer Coefficient

    Presentation f Numerical Data

    In dlis manual, numerical quantities obtained during experiments,etc., are expressed n a non-

    dimensionalmanner. That is, me physical quantity nvolved hasbeendivided by me units in which it

    has beenmeasured.

    As an example:

    p

    0' Nm-1 . 150

    This indicates hat

    p = 150 x 10' N m-2

    r

    p = ISOkN m°2.

    alternatively

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    8/76

    4

    INTRODUCTION

    Tbe Refriaeratk»D or Heat PumD Cycle:

    A refrigerator is defined as a m~hine w~ prime function is to remove heat from a low temperature

    region. Since energy cannot be deSU'OYed.ie heat Iaken in at a low temperature plus any other eneJ'gy

    inJX1tm~t be dissipated to die SUn'()Undings.H the tempezabJreat which die heat is dissipated is high

    enough ro be useful, e.g. for SpIM:;eeating, the ~hine is then called a heat pump.

    By selectivedesignof the components he cycle may be optimisedeidler for heat pump applications

    or for refrigeration applications. Indeed unckr certain applicationsboth useful functions may be

    performedby one machinewhere circumstances enniL For example, n a dairy where refrigeration

    is required or milk cooling and storageand hot water s required or OOuIe r tank washing.

    The aausius Statement f the SecorKI aw of Thennodynamics tates hat heat will not pass rom a

    cold to a ootter region without the aid of an "external agency". Thus. a refrigerator will require an

    "externalagency", .e. an input of high gradeerergy, for it to operate.

    This energy nput may be in me foon of wrateor a va[X)urwill coodense) s dependenton die

    pressure,hus f a suitable luid is introduced t will evaporate t a low temperatm'en the low pressure

    evapora1Ortaking in heat) and will condense t a higher remperatW'en die high pressurecondenser

    (rejecting heat).

    The high IXeSStD'eiquid fomted in the condenser must then be returned to the evaporator at a controlled

    rate.

    Thus. the simple vapour compression efrigerationcycle has our main components.

    (1) An evaporatorwhere heat s taken n at a low tempe1'atures a liquid evaporates t a low p-essure.

    (2) A compressorwhich usesa work input to redI.K:ehe ~ure in the evaporatorand increase he

    .. pressuref die vapour eing ransferredo die condenser.

    (3) A cOIxienser here he high pressure apour condenses.ejecting heat o its surroundings.

    (4) A flow control device which controls die flow of liquid 00ck to die evaporatorand which brings

    about die pressure eduction.

    The refrigeratioocycle is most interesting rom the thennodynamic iew poinL It is one of the few

    ~tical plants which operateson a true thennodynamic ycle and nvolves

    (a) Nucleateboiling and filmwise condensation.

    (b) Steady low processes,.e. dn'ottling, compression nd beat exchange.

    (c) Row conttOl.

    (d) The thermodynamic roperties, .e. pressure, pecifICvolume, emperature, pecific enthalpy and

    specifIC nttOpy, f a pure substance t all conditionsbetweensub-coolediquid and super-heated

    vapour.

    Ald\Ough he vapourcompression ycle is simple o thosewho are familiar widt it many students ind

    great difficulty in visualising and understanding te eventsoccurring within the various components.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    9/76

    5

    With dtis in mind P.A. Hilton Ltd., designeddie RefrigerationCycle DemoosuatiooUnit in which die

    major pan of the cycle takesp~ inside glass chambers nd can dlerefore be observed.

    The unit is a valuable hing aid for studentsn a wide ange f co~ from craft and eChnician

    training o first degree t a Universityor PolyteClmic.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    10/76

    6

    IN~ ALLA nON AND COMMISSIONING

    Removeme unit from its p.:king caseand carefully examine t for damage. f any is foulKi. notify tile

    insurers mmediately.

    Stand he unit on a table at a convenientheight aM cl~ to an elec1rical upply, a water supply and

    adlain.

    Do not stand he unit in a positionwhere t will be in strong direct sunlight or long periods.

    This may result in high chamberpressures ith the subsequentossof the refrigerant charge

    through he safetY alves.

    (i)

    The tmit is fitted with two long life fluorescent amps which for shippingare ~ separately.

    In orOOro fit the lamps the rear panel of the m.:hine must be removed.

    Ensuredlat die m&:hine S NOT CONNEcrED 10 nIB MAINS ELEC1RICAL SUPPLY and

    remove die hexagooalbolts and one Dut secmingdie rear panel Note that die bolts are 8mm

    across lats and the COn'ect ize spanner s recommended.

    The lamp socketsare located nternally and are under die two vertical slots in ~ unit panel.

    Carefully remove me lamps from their packing ma1erialand imezt diem in me white plastic

    socketson the left hand and right hand sidesof me panel. SUR>Orthe socketsby hand as tm

    lamps are inserted.

    While me rear panel is removed ensure mat die Residual C1DTCOt iIcuit Breaker switch situated

    on DIN rail the right side of the panel is in die ON positioo. The unit will have been left in d1e

    ON position when shipped but transit vibration or shock loading can ~ the switched to jwnp

    to me OFF position.

    (0)

    Connectdie mainswater supply o die water nlet at the rear of die unit using he diagooainylon

    reinforcedhose. When facing the rear of the machine the water

    ~

    ~ on the extreme left

    or thepanel.

    It ~ recommendedhat the water supply s red through an isolatingvalve that can be

    turned ofTwhen he unit is not in use.

    In older to increase he stability of the condenser water ftowmeter and evaporator water

    flowmeter the conttol valves on thesedevicesare fitted to the discharge ide of the flowmeter.

    Hence f externaldamage esults n the flowmeter ubesbeing brokenan external solating valve

    will be req~ to stop the flow of water from the unit

    (ill) Connectdie remainingwater coupling at the rear of the panel o a suitabledrain using he dear

    plastic pipe provided.

    (iv) 220/240V Units

    Replace he rear panel BEFORE connecting he unit to the mains suWly.

    The power supply cable will be foWld emerging rom die rear panel. Connect die cable to a

    suitable fixed power supply via a fused outlet (for 5 Amps) which canplies with die ~

    regulatioos.

    Brown cable

    Bloo cable

    GreenlY ellow cable

    LIVE or LINE

    NEtn'RAL

    EARTHor groond

    Note hat cx safeoperationhe greenlY llow cableshouldbe ~ted to a low impedance

    earthing oint hatcomplieswith the ocal egulations.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    11/76

    7

    110/I20V Units

    The unit hasan internally fitted transformerwhich is suitable or input voltagesof between110

    and 130 Volts (110 to 130V in 5 volt steps). The integral SUWly ~ must be coonected 0d1e

    nearest uitablevoltage ennina1s nd mis can ooly be ~hieved by first removing Ix: rear panel

    from the unit. The transfonner s locatedon the right hand side of the unit when ooking at the

    rear of the machine.

    Before connection to dte transfr8fOrnd conde~ cooling water JXx:ke~at dte ends of the evapora~ and

    condenser oils.

    It is recommendedhat in order to imlXOve he resolution of the thennometers few drops of

    light machineoil is OOdedo ~h thennometer

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    12/76

    8

    If die djagramsare to be fitted to die panel hen t will be ~- -ry to fit me four clips suwlied

    to die ~ of d1epanel.

    Auach the 4 spring cli~ to the ~ of 1be -nel using the 8 self-tapping~WS povided. Note

    that 8 small pre-drilled holesexist on the ~ of ~ panel o a:ceIX he ~ws.

    The clips should be fitted wid the OPEN end king toward the fratt of die panel.

    The L shaped lear plastic schematicooldersare dIeDslid under he spring clips.

    In order to utilise the plastk COV~ or the unit the L shaped chemabc oldezsmay be removed

    and stored under he unit panel

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    13/76

    9

    1

    2

    3

    4

    Amendments

    2 MAINS FL TER ADDED

    10.9.97 JB

    A

    B

    c

    SlFPL y m -130Y SO/60Hz

    SEe HA" ~ aAGRAH F~ TERttNAL KEY

    [Drawn y

    JBhe ~ier is req.jred to deliver goods strictly ~cordi-9 to

    drowing. Component nspection is the suppliers responsibiity

    R8IIIDveoil sharp edges a~ burrs.

    [

    Checked

    by:

     

    Dimensions: mm

    @Q

    rojection'

    Issue: 2

    Date:4.3.96

    Scale.

    -

    no/rig. 1

    ENGLAND

    Limits unless otherwise stated

    Fractions * 1/6"

    Decimals * 0.25 mm

    I DRG. No.

    633365

    110

    -

    130V TRANSFORMERWIRINGDlRGRAM

    TITLE:

    MTL:

    FIIIISH:

    KINGS SOMBORNEHAMPSHIRE

    . A. HL TON l TO

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    14/76

    10

    THE HD..TON REFRIGERAnON CYCLE DEMONSTRAnON UNrr

    USEFUL DATA

    Condenser:

    Wal« coil surf~ area: O.O32m3

    E VSDOratOC

    Water coil surfacearea: 0.032012

    Specific beat capacity of Wafa' c,>: 4.18 kJ tg"1 K-1

    Refri~erant:

    R141b

    1,1,dicbloro-1- flooroetbane

    Quantity: approximately800 cm' (awroximately 1 kg)

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    15/76

    11

    SPECIFICADON

    Compreaor

    Hennetic ype ~pressor with inlegrall/2

    H

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    16/76

    12

    of die StaDdaIdpanel and may easily be fined by the CUSfDm~.or if

    purchased widt the standard unit can be a f~tory fitted 0IKia1.

    SAFETY

    No moving parts.

    Intemally mounted relief val~ ~t to 2SOkN m"2 gauge fitted to

    cOIxIen= aOO vaporator.

    High ~ure cut out fitted to stop compress

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    17/76

    13

    DESCRIYnON

    (please efer to me schematicdiagram on Page 1)

    All COlDJX)nentsre mounted 00 an attractive durable glass reinfrator.

    On entering the evaJX)rat(X"he low pressure iquid aOO aJX}ur eparate. he liquid passing nto the

    "pool" for re-evaporation.while the vapour mixes with the vaJX}ur roducedby the boiling ~tion of

    the water coil. The vapour mixture then returns to the compressoro repeat he cycle.

    In the standardunit instrumentations provided to measure:

    (i) The tem~rature and pressure f die refrigerant vapour n die evaporatorand condenser.

    (ii) The tem~rature of die water entering and leaving die coils in d1eevaporatorand condenser.

    (ill) The water flow rates hroughbodi coils.

    (iv) The tem~rature of die oot gas eaving the canpessor.

    All temperatures re measured n die standardunit using red spirit dlennometers.

    An optional digital temperatW'epgrade it is available hat allows measurement f the temperature f

    the condensediquid te as well as the above ist of temperatures.

    With the addition of this optional upgradedie completecycle diagram may be plotted on an R141b

    pressure-enthalpy iagram.

    An isolating valve is fitted at the condenser utlet and this may re cl~ed to ~onstrate a technique

    used in refrigeration maintenaocewhere the refrigerant charge s collected and contained n the

    conde~ or in most CMesa specialisediquid receiveradjocent o the condenser.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    18/76

    14

    This ~hnique is imJX)rtantn onk:r to demOOSb'ateow to pevcnt ~ escapeof refrig~t during

    maintermnce.

    In common with all refrigeration and heat pump systems he unit containsa small amount of oil for

    lutxication of ~ CaDpessa. During normal operation~e oil. in die fOOD f mist and oil/refrigerant

    ~Iution is carried from the compessor to the condenser nd ultimately to die evap

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    19/76

    IS

    OPERATING PROCEDURE

    (please refer to Figure 1- SchematicDiagram, and Figme 2 -R633 Valve Positionsdiagram)

    To assiSt n unOOrstandingration. item namesand relevant tems on the two scoomaticdiagrams

    suppliedare refelTed o in bold type in the following sections.For example.Refrigerant Pump Down

    on Figure 2 and Condenser or Evaporator etc on Figure 1.

    The five baD valves shown on the two schematicdiagramshave been nsIalled for ~ ~

    Figure 2 (Page2) diagram shows he four standardvalve combinations.

    The vent valve on die condensers namally only openedbriefly to vent air from the systemaId this

    is referred o elsewhere.

    Note mat when the mrlt is shut down the ball valves should AlL be in the closed positioo. This

    preven~ the refrigerant migrating to the lowest temperature art of the systemdue to vapourpressure

    effects and in most ~s dtis would be the compressor asing as this will respond most rapidly to

    variations n ambient emperature.

    Normal Ooeration

    To start the unit first turn on the cooling water supply and the mains supply to the unit

    Open the valves ndicated n Figme 2 (Page2) for Normal Operation.

    11ris llowsvapour o be

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    20/76

    16

    Unlessdie supply water emperatures high men altera1ion f ~ evaIJ

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    21/76

    17

    Normal running condition is widl aPJK'Oximatelyo-25mmof liquid in the bottom of the condenser

    chamberand dle float valve maintaining his level constanL

    Once normal operatingconditionshavebeen~hieved men me main switch shouldbe turnedoff. The

    compressorwill stop and me lights on the unit will be extinguished. If the optional temperature

    indicator has been itted the display on this too will be extinguished.

    Turn off die cooling water suWly to die unit It is recommended lat die (water) control valves are

    left open so that f die usersuppliedexternal solating valve eakswater will be allowed to run to drain

    and will be noticed more readily. In addition, f conditionsare such hat the water supply s likely to

    freeze dlen leaving die control valves on the flowmeterSopen may not prevent die glass ubesbeing

    broken but it will make breakage ess ikely.

    Once he unit b$ been urnedoff then me ball valveson me unit shouldbe closed o mimic me

    shutdowncondition. SeeFigure2 (page2).

    This will prevent the large volume of refrigerant contained n the evaporcUormigrating into the

    compressor asingdue o vapourpressure hanges.The small volume of liquid in the condensermay

    migrate to the compressor nder certain ambient conditionsbut this is no cause or concern.

    Refri2erant Pumo Down

    This is a procedureoften used n industrial and commercial efrigerationpractisewhere die refrigerant

    charge s condensed nd collectedeidier in the condensertself or more commonly n a liquid receiver.

    In die RefrigerationCycle DemonstrationUnit R633 die condenser nd liquid receiver are combined

    in die sameglass cylinder.

    In order to carry out pumping down dte unit shouldhavebeenoperatingnormally f

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    22/76

    18

    cooling water aM evaJX)rator ater flow rates are left as for normal nD1ningand me unit remaim

    switched00. The only pam from me evapa-ator o the compressors via the capillary tube.

    The oil in the baseof the evaporatorwill start to flow mrough the capillary blK:t to the com~

    casing.

    The evaporator chamber may be at low JXeSSure nd therefore the oil return process will be slow due

    to the low differential pressure. This may be increased and the ~ speeded up if a small amount

    of refrigerant liquid is OOmitted o the evalXJ[ator by briefly opening the ball valve at the base of the

    condenser. However DO NOT leave this valve open.

    Once the oil has been eturned o die CODlpresD' asing d1endie ball valves may be ~ to dx:;

    position for normal operation as shown n Figm'e2 (page 2).

    Once die operating coOOiuons have rewrned to noonal and the liquid level in the conde~ is

    apJX'Oximately2O-2Smm tOOn OOunit may be eithez shut oown as described ai)Ove or adjusted for

    further experiment.

    Air Ventin2

    A vent valve is siwatedon dle top of the con

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    23/76

    19

    MAINTENANCE

    Hi2b Pressure Cut Out

    At regular ntervals and according o the local safety regulations he high pressure ut out shouldbe

    testedas follows:

    Start dte unit as detailed for normal operation in the operating procedure 00 Page 15 and

    operatewidt a modezate ooling water flow to both dte condenser nd evaporaror s detailed.

    Allow die unit to warm up and hen cl~ the control valve on the condenserwater nowmeter.

    This will cause he condenserpressure o rise. At approximately22OkN m"1 he compressc.'

    shouldbe shutdown by the nternal high pressure ut out An audible click shouldbe heard rom

    the cut out device.

    If the compressor oesnot turn off automaticallyat a oressure f 230kN mol hen turn off the

    unit at the main switch. It will then be necessary o adjust the pressure switch as detailed

    below.

    If the compress

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    24/76

    20

    Th~ differencesmay be added B'subtlaCtedrom dJe~ as awropriare.

    If greater~uracy is requiredmen he water may be gently warmedand me diff~nces notedat ~vera1

    temperatures. In d1is case a graph of indk-lt~ against difference should be plotted for ~h

    th~omeleJ' .

    H the optional temperature indkator hasbeen itted then d1eaOOveiffera1sitionwhen he unit is not in use

    Cbeckinl for Leaks

    If a leak in the refrigerant circuit is suspected. e.g. if d1ere s a loss of refrigerant from the system, me

    following procedlD'e should be adopted:

    (A) If tOOres refri9.erantn the system:

    ~e die unit in a WanD laceuntil its temperatureea:hes32-3SoC.The pressure hrooghoutdie

    systemwill now be aboveabnospheric JKIdie leak may be loca1ed i~ by

    (i) Applying a Sb'Ongmp or detergentsolution to all joints,

    (ill Using an electronic eak detector.

    (B) If there s no refrl2erant n the System:

    Pressuriseme system o SO N m""wim air by applying a manualpump.e.g. motOrcar tyre ~p.

    to me charging valve at me baseof the evaporator. The leak may then be located as n A.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    25/76

    21

    Cbarg2 or Recharge

    Under nonnal conditions me vapour press\U'e f die refrigerant does not reach abnospheric pressure Wltil

    die liquid is at a temperatme of approximately 32°C.

    In order. merefore. o make charging me unit simpler. the one bip can supplied by P.A. Hilton LId

    containsa small amolDltof Niuogen gas n order to raise me internal press\D'e rtificially.

    Before charging t is recommendedhat me unit is set up in me following way:

    Start die unit as detailed for normal operation in die operating procedure on Page 15 and operate

    widl a moderate ooling water flow to bodl die condenser nd evaporatoras detailed.

    Allow the evaporatorpress1D'eo reduceand then position the ball valves or shutdown condition (see

    Figure 2

    -

    Page2) and

    bJrn

    off the compressor. Note that if the unit is not chargedand containsair

    then t may be necessaryo vent this from the condenser ia the vent valve on the condenserop plate.

    The unit s now~y for charging.

    The chargecan only be released rom the can by using the brasschargingvalve (VCl7/2) supplied n

    the accessaieskiL

    Unscrewdie small brasshexagonalnut from die chargingvalve and screw diis onto die dtreadon die

    top of the can. Screw die rest of the charging valve (VC27 l.) into the straight connector on die

    refrigerant charging ine (C45/2), also supplied n die accessories it

    Remove he brasscap from the fixed charging valve at the baseof the evaporatoron the R633 uniL

    Note that the angled end of the refrigerantcharging ine hasa b~ pin in the. entreof the connector.

    This end should be connected o the fixed charging valve on the baseof the evaporatOr.When d1e

    connector s screwed ight the pin depresseshe centre of the fixed charging valve and allows access

    to the evaporator.

    The can should be inverted and me two components f the brasscharging valve should be screwed

    togetherby rotating me can. SeeFigure 4, Page22. When the components f the charging valve are

    screwed ogemerme refrigerantwill flow into me charging ine due o me nittOgenpressuren d1e an.

    Open me ball valve at me baseof me evaJX>ratornd me refrigerant will flow into the evaporator.

    Switch on die writ and d1iswill again educedie evaporator ressure nd assistdie flow of die

    refrigerant into die evaJX)rator.

    When the iquid level in the evaporatOrs above he level of the tOpcoil close he ball valve at the base

    of the evaporatOr.

    Allow die unit to run under nonna operatingconditions until die liquid level in die condenser as

    stabilised. Ensure he liquid level is still above die top coil of die evapomtol. If this is not die case

    then open he ball valve at die 00seof die evaporatorbriefly until d1e equired evel is ~hieved.

    Unscrew he charging ine from the can and this will close he valve in the can. The ball valve at die

    baseof the evaporatorcan be briefly opened o draw in any liquid remaining n die charging ine.

    The chargingprocedure s likely to result in someair entering he system. To remove he air follow

    the procedure or Air Venting describedon Page 18.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    26/76

    22

    0,. Tr~Can

    RMX74/1

    -

    Figure 4

    Bras.C~gi'1g

    Valva VC27/2

    rn

    B

    Refrigerant Charging

    Line CI.5/2

    IN c~~

    Valw With Centre

    Pin

    Angled Comector

    With Central Pn

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    27/76

    23

    CAPABILmES

    OF THE REFRIGERATION CYCLE DEMONSTRATION UNIT

    Demonstration of vaJX)m' ompressioo refrigeration or heat pump cycle widt visual observation of

    the important ~.

    2. Investigation/demonstmtion of d1esaturation pressure-temperature relationship during evapoIation

    and con~nsation.

    Demonstration of "plDlping over" or "pumping down" into the condenser.

    .

    Demonstrationof charging.

    .

    5.

    Demonstration f effect of air in a refrigeration system.

    6. Detenninationof effect of evaporatingand condensing emperamres n me refrigeration rate and

    condenser eat output

    7. Investigationof die effect of compressor ressure atio on systemperfonnance.

    8. Deterntinationof overall heat ransferbetweenR141b and water n the evaporatorand condenser.

    With the addition of the optional temperature indicator:-

    Generationof a refrigerationcycle diagram on a pressure-enthalpyhart.

    .

    With the addition of the optionalwattmeter:-

    10. Measurement f me eff~t of condensing emperature n compressor ower input.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    28/76

    24

    1. DEMONSTRA nON OF VAPOUR COMPRESSION REFRIGERA nON OR REA T PUMP

    CYCLE

    The ex~cnt shouldbegin wid the unit at rest.having been eft in die shutdown (SeeFigure 2, Page

    2) condition for some ime in order for all of the compo~nu to be at a similar ambient empelabD'e.

    Open he ball valveson the cylinders as for normal operation (SeeFigure 2, Page2) but do oot bIrD

    on die unit and do not bIrD on die water supply to the evaporatorand condenser oils.

    The stu1D".

    Reference houldbe made o the Pressure nthalpy diagramon Page55 or the argee~uJaIed

    diagram C57/10) supplied n the accessoriesit

    In order to changephaseat constant X'e8Sure,nergy s required o increase he endlalpy of me

    vaJX>ur. his energy s taken rom the water passing hrough he evaPnhe water nlet tem~rature and the ocal ambient em~rabJre, he surroW1dingtmospbete.

    If the water supply temperature s high (awroximately 16OC r mur ubbles are being prodtx;ed rom me evaporaUX'oil within the evaporator

    chamber hen heat is being exb'Xted from me cooling water flowing through the coil. If the

    evaporator nlet water tempelabJrel is examined after several minutes operation and this is

    comparedwith the water discharge emperature the discharge emperatm'e hould be fouOOo

    be slighdy lower than the inlet tem~. In

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    29/76

    25

    addition, dependingupon me local ambient conditions,water vapour will also condense n die

    outside surfaceof me glasscylinder and baseplate. The change n phaseof me water vapour o

    a liquid will in itself IX'Ovioo eat o causeevaporation f die refrigerant n me chamber.

    In addition, f the evaporator ooling water flow is stopped hen the rate of condensationonning

    on the condenser oils will also reducedue o me reduced apourgeneration ate n the evaporata-

    and me reducedvolumettic efficiency of the compressor nd ncrease n specific volume of me

    vapour generatedn the evaporatorchamberat low pressure.

    (ill) With the evaporatorand condenserwater again flowing as described n the normal operation

    conditions on Page 15 the condenser ressure houldbe observed.

    The condenser ressmewill be seen o be higher than that of the evaporator. This is obviously

    due to the compressor. The ratio of condenser ressure o evaporatorpressure.PJP.. is known

    as the compressorPressureRatio. This will vary ID1der ifferent operating conditions and may

    be investigated.

    After the W1ithas been nmning for several minutes under nonna conditions the condenser cooling

    water inlet temperabD'eand the discharge temperawre should be compared.

    It will be found that the discharge emperature , s greater han the inlet temperature ..

    This is due to the heat given up by the hot high pressure as entering the condenser rom die

    compress

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    30/76

    26

    As soon as the liquid passes hrough he expansion alve U pressure rops o awroximately the

    pressIU'enside he eV8lXX8fOr. his ~ me liquid to immediaIelystart o changephase rom

    liquid to V81XXJr. s in the evaporatm' ragy is required o bring about me phasechangeand

    someof this is taken from the baseplate of the condenser the expansion alve is ~hcd to

    the hue plate.

    ExtrlK:tingbeat rom me baseplate edIx:ests te~ and his n bIrD educes he tem~nue

    of the condenseriquid at me baseof the condenser.This results n ~ liquid being "sub cooled"

    below its satUIation empelatm'e.

    If the optional temperature indicator is fitled ~ an IKiditional thennocouple r. is supplied to

    be fitled in the base of the colxleDSQ" hamber. Hence the sub cooled liquid tem~ may be

    measured and this together with the other measured remperattlreSand pressures allows a complete

    refrigeration cycle diagram to be plotted on the pfeSSW'C-enthalpy iagram supplied.

    In the condenserrerefore the refrigerantchanges rom superheated apouron entry. through o

    sanuated apour hen to sabJratediquid and ultimately to sub cooJediquid before t leaves he

    condenser hamber.

    As ~ refrigezant~ along the pipe leaiing from the exlBn8ioo valve to the eValJ(Xatoreat

    will be exb'.:ted from the SUn'Oundingsnd ~ liquid will be further converted o a v8fX)Ur.The

    si,ht ,- just before nb'y o the evaporatorllows he iquid/vaJX)urixture o be ~ed.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    31/76

    27

    2..

    PRESSURE TEMPERATURE RELATIONSHIP

    The relationshipbetweensanuationpressure nd temperaturemay be observed n both me evaporator

    and condenser. However as variation in the evaporating emperat1D'es small for aU but extreme

    changes n cooling water flow me condenserX"Ovides

    moregraphicllustration.

    As the conoonser contains refrigeJ'ant n all stages rom superheatedvapour through to sub cooled liquid

    the dlermometer pocket ~ only records temperatures close to saturation when die pocket is showing

    signs of condensed liquid Therefore it is recommended that die pressure temperature relationship in

    the condenser is investigated as the condenser pressure increases.

    If the pressure empemture elationship s investigated y reducing he condenser ressure hen the ft

    thennometerpocket will be at a tempenuure hat is higher than the surroundingvapour due to its

    thermal nertia. Thereforeno vapour will condense n the pocket and an inCOIreCtemperaturewill be

    measured.

    Note that dJepressures referred to on dJe pressure-enthalpy chart and on the p-essure-temperature chart

    on Page 29 are "absolute" values.

    Absolute pressure=Pressure gauge value + Local abnospheric pressure

    Procedure:

    (i)

    Start the unit for normal operation as shown on Page 15 but iocrease the condenser cooling water

    flow to the flowmeter maximum (50 g S.l). The pressure at which the condenser stabilises will

    depend upon the water inlet temperawre.

    (ii) Allow die unit to run for approximately IS minutes in order to reach a uniform operating

    temperature. Then record die condenserpressmePc, evaporatorpressurePe' die condensing

    temperature and die evaporating emperature ,.

    (ill) ReducedIe cooling water flow by a small incrementso that dIe condenser ressure ncrease y

    approximately

    0-2CBcN

    -z. This amountwill vary depending pon dIe coolingwater nlet

    temperature.

    Allow the unit to stabilise or a few minutesand again record the above parameters.

    (iv) Re~ the procedureup to the maximumcondenser X'eSSureequiredor to the high pressure ut

    out value of 22OkNm4

    Typical resultsare shown n the table below.

    Local Aunospheric~: lOlkN mol

    PcI

    kN

    m-1 gaugeondenserressure

    -31

    -21

    +4

    +49

    41 -11

    CondenserPressure

    PcI

    kN m-1- bsolute

    ~ 70 80

    90

    105 150

    Condensing

    temperature

    ../~

    15.0 19.5 24.0

    27.0 31.0

    41.0

    P.I kN m°7. gauge

     vaporatol' Pressure

    -68 -69

    -69 -69

    -69 -69

    32 32 32

     vaporata Pressure

    P

    I

    kN m4 absolute

    33

    32 32

    Evaporating

    temperature

    .,/OC

    6.S

    4.0

    4~

    4.0 4.0

    4.0

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    32/76

    28

    Note that tem~ have been estimated o d1enearestO.soC~ing die SIaOOardbenDOIDC1m

    SUWIied. Whezc he opdoul temperature indicator is fitted ~~ may be ~ to d1e

    nearestO.loC.

    The resultsare ploUCd n graphical onn on Page29.

    Note that the standard D'eSSUIeauge~y of tl % of gauge ull ..::a)e as beat shown as 00Ued

    lines about a mean. The absolute :curacy of the dlermometersm-~(XIa} tem~ iDd-k.J1O 'nd

    thmnocouples)plus readingerrors will also .sd to any disc~ies.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    33/76

    8

    .

    t

    1

    _

    3

    I

    ~

    ~

    0

    0

    0

    0

    L

    )

    0

    N

    ~

    ~

    t

    _

    W

    N

    a

    D

    d

    U

    J

    1

    D

    J

    S

    .

    T

    .

    ~

    f

    5

    0

    0

    ~

    0

    a

    V

    0

    0

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    34/76

    30

    3.

    DEMONSTRA ON OF "PUMPING OVER" OR "PUMPING DOWN" INTO mE

    CONDENSER

    Duringmaintenancef refrigemOOo Jaob.partkularly when repl-=ement f com~nb is involved.

    it is convenient o transf~ the ~gerant to me conck.nser. This ba the ~vantage of saving me

    refrigerant or f1D1her se and also may avoid the needof ev~ua1ionprior to rechargink.

    In addition. or ecologicaleasonsollowingme guidelines f d1eMontreal l. ~ ventingof

    refrigerants in manycountries owa criminaloffence.

    This is a proc.edure ften used n indusbial and commercial efrigeration ~tise where the entire

    refrigerant charge s condensed nd collected either in die corKlensertself or more commooiy in a

    liquid receiver co~ted to the condenser. Once the chargebas beenplrDped nto the condenser r

    liquid receiver hen work may be carriedout on the systemwidiout losing argequantitiesof refrigerant

    to atmosphere.For ecological~ following die guidelinesof die Montteal Protorol, the venting

    of refrigerant s in many countriesnow a criminal offence.

    In the RefrigerationCycle Demonsb'81ion nit R633 d1ecoOOe~ and iquid receiver are combined

    in d1esameglass cylinder.

    In order o carry out pumping down, dIe unit should have beenoperatingnormally for ~veral minutes

    widt an evaporatorand condenser ooling water flow rate of approximately40 gS.I.

    By setting me ball valves as shown in me Refrigerant

    Pump Down mode (~ Fig1De 2

    - Page2), me

    flow of condensediquid from the

    expansion alve

    at the ~ of the conoonSel:s

    ~

    and iquid

    will thereforecontinue o colle(:t n me condenser hamber.

    As liquid ttansfecs rom the evapcnror, the level will fall and ess of the evaporaur coil surf~ will

    be effective n evaporaling he liquid. The evaporatioo ate will reduceand die processwill become

    slower. This effect may be offset as the liquid level becomes ery low by opening ONLY) the baD

    valve at the baseof the evaporaU>r.

    This will have the effect of utilising die capillary surface area and ambient air temperawre to eVa(X)rate

    additiona1liquid.

    If, beforepumping down, the unit basbeenoperated or a prolmged period, die liquid collectedat d1e

    baseof the evaporaUX' ay appear hicker and less viscoos. It may also appear slightly yellow in

    colour. The liquid remaining n die eva X)rators primarily the oil d1athas been carried over in die

    form of mist and refrigerant oil mixture from the com~.

    The oil will not evaporateat die pessures .:hieved by d1ecanpressor and tOOreforet must be

    physically rewmed to die compressor asing.

    Note that the unit should ~ SHUT DOWN when the refrigerant charge is in the PUMP DOWN

    condition as under certain ambient conditions it is possible for die charge to migrate to the compreS&:Jr

    casing.

    ~:

    In an industrial plant, isolating valves are usually fitted between all major components. As ~

    as the refrigerant has been b'ansferred to the condenser (or liquid receiver) the valves may be

    closed. trapping the liquid. The defective comlX>nentcan dIeD be serviced or repJ.lK:edwid¥>Ut

    losing the refrigerant charge.

    At me end of the demonsb'8tionhe opportunity may be taken o reblrn the oil collected n the baseof

    me evaporator o die condenser.The procedure or this is given underOil Return on Page 17.

    However, f oil is not to be returned o the compressor t this stage,~ mIl valves should be set for

    normal operation (SeeFigwe 2, Page2) and me refrigerant allowed o rewrn to the evaporator.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    35/76

    31

    4.

    DEMONSTRATION OF CHARGING

    Due to die restrictions of die Montreal Protocol t is not recommended 1at he refrigerant charge s

    removed rom the machine or any ~n other than essential epair.

    If charge emoval s necessary 1en echargingmay be "demonstrated"f convenient o 00 so.

    Charging rom a Hilton suppliedone nip can should ollow the Chargingor Recharging X'OCeduren

    Page21.

    Note that any refrigerant emoved rom the machine shouldbe stored n a screw topped metal can to

    prevent evaporationand to stop moistme being absorbedby the oil in solution.

    Any refrigerantstored n sucha can may be drawn ~k into the evaporator y connecting he charging

    line to the charging valve in a similar way to the standard hargingprocedurebut then mmersing he

    open end in the liquid inside the container. If the unit is turned on for normal operation then the

    pressuredrop in the evaporatorwill cause he refrigerant o flow into the evaporator. Note that air is

    likely to need venting from the condenser.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    36/76

    32

    s.

    DEMONSTRA nON OF mE EFFECT OF AIR IN A REFRIGERA nON SYSTEM

    When air is present n a refrig~oo plant. t will O(X'Inally e swept rom the evaporata by me flow

    of refrigerant vapourand will become tapped n the con(k;D.W'.

    For a combinationof reasons.he air will ~ the com~ delivery IX'CSSIJreo rise. reducing die

    coefficient of peifonnance.arxl increasing he power input for a given duty.

    The ilx:reaseof pressures due to

    (i)

    The total pressure in the coodensu is approximately equal to die sum of the refrigeJ'aDtsatumtion

    pressure~ the pressure of die air Jl'CseDt Dalton's Law of partial pressures).

    and

    (ii) The air tends o be swept towards die heat transfer surfaces. onning an insuJating ayer which

    reduces~ heat b'ansfer oefficient. This in Ulm drives up die temperature ifference equjred

    for a given heat ransfer ate and this results n a higher refrigerant sabJratiooemperature nd

    pressure.

    The effect of air in the systemmay be demonsttated s follows:

    Procedure:

    (i) Start the unit for normal operation and adjust the evaJX)ratorcooling water flow rate so dlat the

    evaporator pressure is below abnospheric pressure. Unless the cooling water temperablre is v«y

    high this is likely to be the case in all conditions.

    Ensure that the unit is free of air and if o«.essary follow the air vendng procedtDe shown 00 Page

    18.

    (ii) Run the lmit for ~veral minutes n order to reachnormal operating emperattD'es en record all

    system emperatures, essures and flow rates. Also visually note the condensationate on

    me

    corKlenser ooling coils.

    (ill) Connect he angl~ endof the charging ire (C45/2)supplied n the ~es kit to the charging

    valve at the baseof the evaporator.

    (iv) Observe ~ evapc:ntor pressuregauge and ~ open the ball valve at the base of me

    evaporator. The evaporatorpressuregaugewill indicate an increase n JXessureollowed by a

    return to its original value.

    The condenser ressure auge,however,will increaseand remain at the new value.

    (v) Re~ openingof d1eball valve until the condenser Xessureasapproximatelydoubled rom its

    original val~. Note that f the condenser esswe ~~ 22OkNmo1hen me high presswecut

    out will operateand the experimentwill have o be repeated ran an air free conditioo.

    When air is admitted 10 he evaj)(X'a1Ort initially adds 10 the pressure within the evaporator ~cording

    10 Daltoo's Law. However it is almost immediately swept dlrough into die comlX'eSSOf y the flow of

    refrigezant v8lX>ur. The mixbD'e then passesdlrougb 10 he comJX'CSSOrm ultimately to die condenser

    where it can go no further d~ to the liquid at die base of the condenser.

    In addition. the conlinuous flow of refrigerant vapoW' owards the condenser cooling coil causes die air

    to remain around the coil region. The reduced rate of cooOOnsation hould be observed as well as die

    increase in condenser pressure.

    Record aU system temperatures. pessures and flow rates.

    Typical resultsare shown n the following table.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    37/76

    33

    Local AtmosphericPressure: OlkN m-1

    1 Air Free

    1. With Air

    est No.

    -69

    -66

    vaporala GaugePressure

    p ~ I kN mo2

    p ~ I kN mo2

    35'2

    bsolute EvaporatorPressure

    400

    5.5

    t,/OC

    m.1 g S.l

    ~/OC

    ~/OC

    Po1

    N

    m-2

    Pol kN m-2

    r./OC

    IDa

    1 g S.l

    t./OC

    Evaporating emperature

    20.0

    20.0

    vaporatorwateJ' low

    11.0

    1.0

    vapora1fX water inlet

    9.5

    10.0

    vapora1(X'water outlet

    59

    21

    ondenser Gauge Pressure

    80

    160

    bsolute Condenser Pressure

    30.5

    5.5

    CondensingTemperature

    4.0

    .0

    ondenserwater flow

    12.0

    2.0

    ondenserwater inlet

    22.0

    20.3

    t,/OC

    ondenserwater outlet

    The results are plotted on a

    temperabJre-pressuregraph on Page 34.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    38/76

    3

    0 »

    2

    .

    » : =

    =

    ~

    t

    D

    a

     

    =

    t

    D

    .

    ~ 2

    .

    t

    D

    ~

    0

    ~

    ~

    ~

    C

    8

     

    D

    .

    C (

    J

    (

    J

    c

    .

    C

    <

    G

    Q

    C

    c

    3

    (

    Q

    C

    C

    C

    >

    (

    Q

    (

    c

    ~

    .

    C

    ~

    A

    '

    <

    C

    -

    0

    Q

    ~

    O

    .

    +

    0

    I

    ~

    .

    J

    o

    ~

    -

    -

    n

    C

    c

    -

    n

    =

    W

    .

    (

    :

    A

    Q

    -

    ~

    C

    0

    m

    2

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    39/76

    35

    6.

    EFFECT OF EVAPORATING AND CONDENSING TEMPERA ON THE

    REFRIGERA ON RATE AND CONDENSER EAT OUTPUT

    The effect of evaporating emperatmeon die refrigeration rate can be investigated.but due to d1e

    limited effect on evaporating emperature f all but very argechangesn cooling water low it is more

    graphic to investigatecondensing emperature irst.

    If time pennits. the corresponding ffects of evaporating emperaturemay then be investigated.

    The effect of increasingme condensing emperature n many refrigeration systemsand heat pwnps s

    a reduction n me heat discharged rom me condenser nd in many casesa smaller reduction n the

    refrigerating effect at the evaporator.

    Similar reductionswill be observed f the evaporating emperatures lowered

    The effocts are due pimarily to the reduction in volwnetric efficiency of the compressorat high

    pressure atios (P

    JP

    and the reduction n specific volume of the refrigerant gas as the evaporating

    temperature educes.

    An investigationof die effects of pressure atio are given in the following experiment

    A simple explanation or this is that for eachsuction strokeof die compressor lower massof gas for

    the samevolume) s drawn in to the cylinder to be compressed.

    The effect of increasingcondenser ressuremay be investigated n the following manner.

    Once air free increase he condenser ooling water flow to the flowmeter maximum (50 g S.l).

    The pressureat which the condenser tabiliseswill dependupon the water inlet temperature.

    (ii) Set die evaporator water flow to approximately 20-30 g S'l and allow the unit to run for

    approx,irnately 5-20 minutes. The time taken to stabilisewill dependupon the local ambient

    conditions and the cooling water nlet temperature.

    (ill) Record all the systemparameters s illustrated n the table on Page 36.

    (iv) Reduce the condenser cooling water flow rate until the condenser pressure ncreasesby

    approximately5-10 kN mo1,Allow the unit to stabiliseand again ecord the parameters n Page

    36.

    (v) Repeat or increasing ondenser ressureso dIe minimum readable alue on dIe condenserwater

    flowmeter is ~bed, or the condenser ressure eaches 00 kN roo"gaugepressure.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    40/76

    36

    OBSERVA nONS

    Local AtmosphericPresswe: OlkN m-2

    Test No.

    1

    2

    :t

    4 5

    Pel kN m-2

    Pel kN m-2

    t,/OC

    Evaporaux'GaugePressure

    -68 -69 -69 -69 -69

    32 32

    32

    32bsoluteEvaporalOr Pressme

    33

    6.5

    4.0

    4.0

    4.0

    4.0

     V8IXX8UX' Temperature

    di./ gin S.l

    it/OC

    20

    20

    20

    20

    vaporaUX'Water Row Ra&e

    20

    11.0 IJ.,O 11.0

    11.0

    vapor8tcrWater InJet Temp.

    11.0

    10

    It)

    IG

    10

    vaporat(X'Water Outlet Temp.

    ft/1IC

    ../IIC

    P./ tN m-2-

    P./ tN m-2-

    t,/1IC

    10

    Condensed iquid Temp.

    Condenser Gauge Pressure -41

    .31

    -21 -II 4

    70 80 90 105

    bsoluteCondenser Pressure

    60

    CompressorDischargeTemp.

    - - - -

    r./OC

    m./ gin S*l

    15.0

    J9.5

    24,0

    27.0 31.0

    ondenser Temperawre

    Condenser W &tel' Flow Rate

    50.0

    10.0

    4.0

    2.0

    1.0

    11,0

    11.0

    ondenserWater Inlet Temp.

    r./ac

    11.0

    11.0

    11.0

    26.5

    31.5

    ondenser Water Outlet Temp.

    r,/1:C

    12.0

    16.5

    22.0

    W/Waus

    ompressorPower nput

    Note d1a1he temperatures ecorded have been estimated o the nearest0.5°C using die standard

    thennometerSupplied. If the optional temperature indicator is fitted with the hermocouple ensors

    then the temperaturesmay be recorded o the nearestO.l°C.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    41/76

    37

    SPECIMEN CALCULA nONS FOR TFST NO.2

    EVAPORATOR

    Rate of Heat Transfer to Water in EvaJX)rator:

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    42/76

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    43/76

    39

    7. ~GA nON OF THE EFFECTOF COMPRESSORRESSURE Ano ON SYSTEM

    PERFORMANCE

    The effect of increasing he condensing emperatureor a constantgiven evaporating emperatures to

    increase he compression atio PJP. that the compressors required o deliver.

    Due to die effects of valves and die necessarypiston to cylinder bead clearancesdie volumetric

    efficiency of reciprocatingcompresSOISends o fall with increasingpressure atio.

    Volumetric efficiency

    =Actual Volume Delivered

    CompressorSwept Volume

    In terms of a refrigeration system.

    Volumebic efficiency

    =

    Mass low of refris:erant Soecific volume of refris:erantat inlet

    CompressorSwept Volume

    Hence f dte volurneb'icefficiency falls widt increasing ressure atio then he effect will be a reduction

    in the effective mass low of refrigerant. The mass low of refrigerant hrough he compressor elates

    directly to dte amount condensingon the condensa- oil and this in turn relates to the rate of heat

    b'ansfer o dte cooling water.

    In addition me above equation ndicatesme effect of reducing me specific volume of the refrigerant

    entering me compressor y lowering me evaporating emperature.

    The effect of pressure ratio on system performance may be investigated by the following method which

    is identical to that used in Experiment 6 on Page 35.

    Once air free increase the condenser cooling water flow to the flowmeter maximum (50 g S.l). The

    pressure at which the condenser stabilises will depend ulX>n he water inlet temperature.

    (ii) Set he evaporatorwater low to approximately30 g S.land allow the unit to run for approximately

    15-20minutes. The time taken o stabilisewill dependupon he ocal ambientconditionsand he

    cooling water inlet temperature.

    (ill) Record all the systemparameters s llustrated n the table on Page40.

    (iv) Reduce the condenser cooling water flow rate until the condenser pressure ncreasesby

    aP{X"Oximately-10 kN mol. Allow the unit to stabiliseand again record he parameters n Page

    40.

    (v) Re~ for increasingcondenser ressuresD he minimum readable alue on the condenserwater

    flowmeter s reached,or the condenser ressure eaches200 kN m-zgaugepressure.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    44/76

    40

    OBSERVA nONS

    Local Atmospheric Preaure: 101 kN m4

    3

    s

    est No.

    1 1.

    4

    -69

    68 -69 -69

    -69

    vapoI31a'GaugePressID'e

    33

    32 32

    32

    32

    bsolute Evaporator Pressure

    4.0

    Pel tN m-2

    Pe tN m-2

    t,/OC

    Ih. I gin S.l

    it/OC

    6-"' 4.0

    4.0

    4.0

    vaponI(X'Tem~

    20

    20

    20 20

    20

    vapora1aWater Row Rate

    11.0

    vaporaf« Waf.« InJetTemp.

    11.0 11.0

    11,0

    11.0

    10 10

    10

    10

    vaporalakWater Outlet Temp.

    ta/-C

    10

    Condensed iquid Temp.

    re/OC

    p.1 tN m-2

    p.1 tN m-2

    r.,/OC

    -41

    -31

    -21

    -11

    4

    ondenser Gauge Pressure

    70

    8C

    90

    IOS

    bsoluteCondensezsure

    60

    Cu.u~~ Discharge emp

    24.0

    27.0

    31.0

    ondenserTmnpelabJre

    ../OC

    di./ lID Sol

    15.0

    19.5

    2.0

    1.0

    ondenser Watel' Row Rate 50.0 10.0 4.0

    11.0

    ./OC

    11,0

    11.0 11.0

    11.0ondenserWater Inlet Temp

    22.0

    26.5

    31.5

    ondenserWater Outlet Temp

    's/OC

    12.0 16.5

    CompressorPower Input

    W I Watts

    Note that the temperatures ecorded have been estimated o the nearestO.5°C using the standard

    thermometers upplied. If the optional temperature indicator is fitted with the thermocouple ensors

    then the tempe~ may be recorded o the nearestO.I°C.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    45/76

    41

    SPECIMENCALCULAnONS FOR T~T NO.3

    EVAPORATOR

    Rate of Heat Transfer to Water in EvaJX)rator:

    Q.

    =

    iii. C, (11

    ~

    Q.

    . 20.0

    X

    10-3 4.18

    X 10'X

    (11.0- 10.0)W

    Q = I3..6W

    . -

    CONDENSER

    Rate of Heat Transfer to Water in Condenser:

    Qc

    = "c C, (r, - tJ

    Qc = 4.0

    x 10-' x 4.18 x 10' x (12.0 - 11.0)W

    Q =18.3..2W

      -

    COMP~_SDR

    Note that dIe pressmemtio shouldbe derived using Absolute pres8W'e ot GaugePressures.

    Delivered PressureRatio

    =Pc/P.

    32/80

    = 2.5

    -

    DERIVED RESULTS

    CompressorPressmeRatio

    p./p.

    Q./W

    Q./W

    1.82 2.19

    2.5

    2.81

    3.28

    83.6 83.6

    83.6

    3.6 83.6

    eat Transfer n Evaporator

    229.9 183.9

    129.6 85.7

    eat Transfer n Condenser 200

    These esults are presented raphically on Page42.

    In order to investigatevolwneuic efficiency it would be necessaryo measure he rotational speedof

    the compress

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    46/76

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    47/76

    43

    8.

    DE~ATlON OF OVERALL HEAT TRANSFER BETWEEN R141b AND WATER

    IN mE EV APORA TOR AND CONDENSER

    The Overall Heat TransferCoefficient (U) is die heat tansfer ate per unit areaof heat tansfer surface

    when a temperature ifferenceof ooe degreeexists betweendie hot and cold fluids.

    In die evaporator,die refrigerant emperatures sensiblyconstant,but die water temperaturealls as t

    passes hrough the coils. In die condenser omedegreeof superheating be presentwhen the gas

    enters he condenser lass chamber. However the quantity of heat delivered due to the superheating

    will be small relative to that attributable o the condensingphasechange. Examination of the high

    pressure ine of the cycle diagram generatedn ExperimentNo.9 on Page47 will confirm this.

    In oroor to analyse he overall heatb'aIlSfer oefficient a representativeemperature ifferencemust be

    determined hat representshe driving force for heat ransferbetween he refrigerant and the water.

    The temperature ifference o be used n this case s the "Logarithmic Mean" which is given by

    where9... = Temperawre

    ifferencebetweendie two fluids at inlet,

    and 9..-1ot Temperatureifference etween ie two fluids at outlet.

    A dleoreticalanalysisof dle logarithmic mean emperatme ifferencemay be found in most ext books

    on heat transfer and will not dlereforebe expanded n dlis manual.

    Once air free increasedie condenser ooling water flow to a mid range value.

    which the condenser tabiliseswill dependupon the water nlet temperature.

    The pressure t

    (ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately

    15-20minutes. The time taken o stabilisewill depend pon he ocal ambient conditionsand he

    cooling water inlet temperature.

    (ill) Record allllie systemparameters s llustrated n the table on Page44.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    48/76

    44

    OBSERVATIONS

    Local AUDOspheric: lOlkN m.~

    Test No.

    1

    2.

    3

    4

    5

    Evaporata GaugePressure

    -68

    Absolute EvaporatorPressure

    33

    Pel tN mea

    p.1 kN mea

    t,/OC

    die I gin S.l

    rs/OC

    'a/OC

    6.5

    vaporata'Temperature

    20

    vaporaI« Waf« Flow Rate

    11.0vaporata Water Inlet Temp.

    EVaporaI« Water Outlet Temp. 10

    Condensed iquid Temp.

    "lac

    p.1 tN m-2

    p.1 tN m-2

    CondenserGaugePressW'e

    -41

    AbsoluteCondenser

    ro

    Compreso Discharge Temp.

    -

    t,IOC

    Condenser Tempelature

    r-/OC

    Ib./ gin 8"1

    15.0

    Condenser Water Flow Rate

    so.o

    CondenserWaf« Inlet Temp.

    ~/ac

    11.0

    CondenserWater Outlet Temp.

    r,/OC

    12.0

    W I WatU

    ompressor Power Input

    Note that the tem~rabJres recorded have been estimated o me nearest0.5°C using me standard

    mennometers upplied. If the optional temperature indicator is fitted with the themtocouple~nsors

    then the temperaturesmay be recorded o the nearestO.I°C.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    49/76

    45

    For the Evaoorator

    RaICof Heat Transfer o Wata' in EvaJX)rator:

    Q.

    S

    IN.

    C, (t1- t,)

    Q.

    S

    20.0x 10-' x 4.18x 10' x (11.0 10.0)W

    Q :.83.6W

      -

    e~

    - 11.0 6.5

    e~ = 10.0 - 6.5 =

    4.5 3.5

    In~

    3.5

    8 .

    -

    ~K

    Q

    U=A&:

    u . ~~ '- , W.-2 g-l

    3.6

    u = ~ w..-2 '

    For the Condenser

    - -

    Rare of Heat Transf~ to Water n Coode~

    Q~ = *~ c, ("

    -

    tJ

    Q~ - 50.0x 10-' x 4.18x 10' x (12.0 11.0)W

    Q~ = . W

    8~ . 15.0 12.0

    8--

    .

    15.0 12.0 . 3.0K

    4.0 - 3.0

    ID~

    3.0

    8-

    .

    ~K

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    50/76

    46

    Heat Transfer Rate

    u=~

    A8.

    u .

    u = ~ Wm-2K-l

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    51/76

    47

    9. GENERATION OF A REFRIGERATION CYCLE DIAGRAM ON A PRFSSURE-

    ENTHALPY CHART

    Note this procedure can ONLY be undertaken by the following detailed method with the optional

    temperature indicator fitted to the R633 unit as the temperature of the refrigerant liquid in the

    condenser s required for one state point on the cycle diagram. However the procedure may be

    modified for use with the standard thermometer set. See Page 48.

    The fitting JX'OCedUIeor the optional temperature ndicator kit, if not already fitted. is given in

    Appendix A. Details of the kit are available rom P A. Hilton Ltd. or their local representative.

    The vapour compression efrigeration cycle is of paramount mportance n tentls of food and drug

    preservation,air conditioning, and heat pumps. In order to analyse he systemperformance n tentlS

    of die diermodynamic ycle it is common or engineers o record systempressW'eSnd temperawres

    and dien to plot the various statepoints on a pressure-enthalpyhart of the wm'king fluid.

    The working fluid in me Hilton RefrigerationCycle DemonstrationUnit SeriesR633 is R141b. This

    has me chemical name 1.1.-Dichloro-l-fluoroed1ane.

    A pressure-enthalpyhart for this substances shown on Page55.

    A detaileddescriptionof die variousparameters isplayedand obtainable rom pressure-endtalpyharts

    will be found n most text books on thermodynamics nd thereforewill not be expandedupon n this

    manual.

    In order to plot a cycle diagram or the unit the following procedureshould be adopted.

    Procedure:

    (i) Start me unit fOf normal operation as shownon Page 15 and ensuredtat me unit is air free by

    venting air from the condenser s describedunder air venting on Page 18.

    Once air free increase he condenser ooling water flow to a mid range value. The pressureat

    which the condenser tabiliseswill dependupon the water nlet temperature.

    (ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately

    15-20minutes. The time taken o stabilisewill dependupon the ocal ambientconditionsand the

    cooling water inlet temperature.

    (ill) Record all the systemparameters s llustrated n the table on Page49.

    (iv) In order o demonsttatehat the cycle varies or different operatingconditions t is recommended

    that die condenser ressures varied by adjusbnent f die condenser ooling water low rate. The

    unit should be allowed to stabiliseand die systemparametersecorded.

    The proceduremay also be repeated t different evaporating emperatures nd the resultsplotted

    on a pressure-enthalpyhart as describedbelow.

    The results rom die following table are shown plotted on PageSO.

    The statepoints a. b and c on the diagram on Page50 are located n the following manner:-

    Pointa is at the ntersectionf theevaporator

    hamber pIeSSm-e . = 32 kN moz

    absolute nd he

    evaporatingemperature Is = 4.0OC.

    i)

    (ii) Point b is at the ntersectionof the compressor hamberpressurePG= 70 kN

    m°2.absolute

    and he

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    52/76

    48

    (ill) Point c is at the inte~tion of the compressor hambel' ressurePc= 70 kN m-1~lute and d1e

    condensediquid tem~ r. = 19.5OC.

    (iv) The expansion s assumedo be adiabaticand dtereforea ~ of constantenthalpymay be drawn

    vertically oown from IK'int c to intersectwidt the evarxratnr presSUIeine Pc.

    Considering he processes 1a1 re happening t eachSta1e oint in turn:-

    (i)

    At JX)inta die v8lX>urrtm die evaporBt« s drawn nto the compe.-,r and me pressures raised

    from P. to Pc. It is evident rom die line of constantentropy ntersectingwith JX)inta (1.9 kJ kg-I

    K-1) that die compession is not isentropic as die pressure ise is completed at an entropy of

    aPJXQximately .92 kJ kg-l K-1. If required the isentropic efficiency of compressionmay be

    evaluated.

    (ii) The vapour eaving the com~ at point b is superheated s t is to the right of the saturated

    vapour ine. The vapoorcools slightly in the pi~ to the condenser nd hen n the condenserk-

    su~rl1eating and colxlensing ake p1a;:e t essentiallyconstantpressure.

    (ill) At point c me liquid at die baseof me condenser s slightly sub cooled due to me effect of me

    cooling water tempembirebeing below the saturation emperature f me conde~ chamber

    pressure water tem~ 11.6 o 16.7OC.Sawration emperanue t Pc= 70 kN m-1= 21.7°C).

    In addition ~me sub cooling in this unit arrangements addeddue to the expansionvalve being

    physically attached o the condenser aseplate. The temperature rop causedby me expansion

    conductsheat through me baseplate rom me condensediquid reducing he liquid temperature

    furdler.

    (iv) The JXessure rop causedby me expansionbrings me refrigerant nto the valX>ur 1iquid ixtm'e

    region betweenme saturatediquid and satlD'8ted apour ines. The mixture of vapourand iquid

    may be seen n the sight glassadj~t to the evaporator.

    The liquid/vapom mixbJIemay be seen eturning o the evalJ(X'atOrhrough he fitting in the tOp

    plate.

    Note that mough me experimentmay only be carried out in the aOOve etail utilising the optional

    temperaturendicator. statepoints a and b may be determired using the standard hermometerS.

    The temperature f dIe conOOnsediquid may. however.be estimated rom dIe saturationpressuren

    the condenserf it is assumed lere s no sub-

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    53/76

    49

    OBSERVAnONS

    Local AttnospbericPressure: OlkN m-2

    Test No.

    1

    2.

    3

    4 5

    -69 

    vaporala GaugePressure

    p. I kN m4

    P. I kN m4

    bsolute Evaporator Pressure

    32

    ts/OC

    Ib.I gill S-l

    it/OC

    ~/OC

    ../OC

    Pc tN m-l

    Pc tN m-l

    4.0

    va{X)ratCK emperature

    20

    vaporara Water Flow Rate

    11.2

    vapofata Water Inlet Temp

    9.7

    vaporata' Water Outlet Temp

    Condensed iquid Temp.

    19.5

    -31

    ondenser auge

    70

    bsolute Condenser Pressure

    Compressor Discharge Temp.

    t.,/OC

    ../OC

    dlc / gin S.l

    r,./OC

    41.7

    19.5

    ondenser emperablre

    10.0

    ondenser Water Row Rate

    11.6

    ondenserWater Inlet Temp.

    ~/OC

    W I Watts

    16.7ondenser Water Outlet Temp.

    CompressorPower Input

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    54/76

     

    '

    0

    n

    =

    C

    1

    ~=-.

    -

    6

    ;

    O

    ~

    _

    ~=.

    -

    6

    '

    <

    _

    ~c~

    ~

    .

    -

    0

    VV

    0

    V0

    J

    0

    0"

    0

    ~

    :

    ~

    ~

    :

    r~

    P

    :

    ~

    -

    J

    0

    -

    ;

    .

    ~

    w

    .

    N

    ~

    -

    ~

    V

    ~

    -

    .

    ~

    -

    ~~

    f

    ~

     

    -

    1

    »

    ~

    m

    ~

    ~ ~

    m

    ~

     

    "

    9.

    ~

    i

    ;

    ~

    0 0

    0

    -

    §

    '

    c

    8

    ~

    I

    "

    '

    ~

    \

    -

    -

    0

    0

    0

    C

    '

    w

    ~

    i

    ~

    '

    o

    ;

    t

    o

    t

    1

    ~

    ~

    I

    N

    *

    -

    ~

    ~

    0

    ,

    ~

    1

    ~

    "v

    f

    "

    \

    r

    .

    ~

    \

    I

    ~

    '

    .

    ~

    ~

    ~ 1

    -

    ,

    "

    .

    :

    ~

    ~

    1

    v

    1

    1

    '

    "

    ~

    -

    ~

    "

    .

    \

    ~

    N

    V

    O

    ~

    -

    w

    ~

    V

    O

    0

    -

    0

    \

    1

    0

    ~0

    "

    "

    "

    0

    u0

    ~0

    \

    o

    0

    -

    l

    o

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    55/76

    51

    10. MEASUREMENT OF mE EFFECT OF CONDENSING TEMPERATURE ON

    COMPRFSSOR POWER INPUT

    Note his procedure an~ be undertakenby the followingmethodwith the ootionaldi2ital

    wattmeter itted to the R633unit.

    The fitting procedure or the optional wattmeter kit. if not already itted, is given in Appendix B.

    Details of the kit are available rom P.A. Hilton Ltd. or meir local re~tative.

    The vapourcompression efrigerationcycle s utilised n both refrigerationand heatpump awlications.

    In a refrigeration situation he eff~t of high ambient emperaturewill be to both ~rease the loan on

    the refrigeration system (due to heat eakage ntq the cold space hrough thennal insulation) and to

    increase he condensing emperaturen order to reject heat rom the system.

    In a heat pump application he useful heat rom the condenserwill be more easily utilised for heating

    applications f rejected at a high temperature.

    In bodl cases,ncreasing ie condensing

    X'Cssure

    esul~ in a greaterwork requirementor die

    compresscx. In addition, die increased compression ratio will in most cases result in a reduction of

    system efficiency due to a reduction in volumetric efficiency. This is due to die necessary clearance

    required for compressor valve opening and machining tolerances. At die end of a compression stroke

    this clearance value is COOStantut at high pressure will contain a higher mass of unb'ansferred gas dIaD

    at low pressure.

    In addition, due o commercial actors, he motors used n mostdomestic efrigerationcompressors ill

    be of a relatively low elec1rlcal fficiency. Henceelec1rlcal esistance eatingeffects n the windings

    will be relatively high under all operatingconditions.

    Procedure:

    (i) Start the unit as for normal operation as shown on Page 15 and ensure hat the unit is air free

    by venting air from me condenser s describedunder air venting on Page 18.

    Once air free increase he condenser ooling water flow to maximum (50 g/s). The pressureat

    which the condenser tabiliseswill dependupon the water nlet temperatm'e.

    (ii) Set the evaporatorwater flow to a mid range value and allow me unit to run for awroximately

    15-20minutes. The time taken o stabilisewill dependupon he local ambientconditionsand me

    cooling water inlet temperature.

    (ill) Record dJecompressor ower nput shown OIl he digital wattmeterand the condensing ressure

    Pcas illustrated n dJe able on Page52.

    (For referencet is recommendedhat students arefully touch he compressor asing o experience

    the heat loss from die compressordue to electrical heating effects. This represents lectrical

    energy wasted by the system. Care should be exerc~ed as the comoressor casioa will be

      QI.)

    (iv) Adjust the condenser ooling water low to a lower value and againallow the system o stabilise.

    Re~ d1eabove observations.

    (v) The proceduremay be repeatedup to the maximum condensing ressure f local cooling water

    conditions permit

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    56/76

    S2

    OBSERVAnONS

    kNmo2

    ocal AtmosphericPressure:

    5est No.

    1

    1

    3

    4

    E

    aporala

    Gauge re~

    Absolute Evaporator Pressure

    Evaporata T~penIuIC

    Pel tN mol

    Pel tN mol

    "/OC

    Ih. I lID 8-1

    ts/OC

    E Vaporatm' Watrl' Row Rate

    -

    Evaporara Wat« In1etTemp.

    EvaporaIO'Waf« Outlet Temp.

    ~/OC

    Condensed iquid Temp.

    "/OC

    p./tN m4

    p./tN m4

    ",/OC

    CondenserGaugePreaure

    15

    190

    Absolute Condenser Pressure

    Compressor Discharge Temp.

    - -

    ,,/oc

    Ib./ gin S'1

    ~/OC

    Condenser T emperahlre

    Condenser Water Flow Rate

    Condenser Water Inlet Temp.

    CondenserWater Outlet Temp

    r,/OC

    Compressor Power Input

    W I Watts

    274

    302

    Note that the val~ observedwill dependupon the local conditions, he p-essures et and the local

    supply voltage and frequerx:y.

    As indicated above, he power required o drive the com~ increases s ~ condensing ressme

    is increased.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    57/76

    S3

    OBSERVAnONS

    kNm-7.

    ocal Atmospheric~:

    5

    2 3

    4

    est No.

    Evaporata' GaugePressure

    Absolute EvaporatorPressme

    Pel kN m-2

    p.1 kN m-2

    .,/OC

    m. I gin S-1

    "/OC

    t,/OC

    r./OC

    p~ kN m-2

    p~ kN m-2

    t.,/OC

    ~/OC

    Ib.I gin S.1

    r./OC

    t,/OC

    Evaporat(X'Temperature

    Evapotat(X'Water Flow Rate

    EvaporatorWater Inlet Temp.

    EvaporatorWater Outlet Temp

    Condensed iquid Temp-

    Condenser Gauge Pressure

    Absolute Condenser Pressure

    Compres~ DischargeTemp.

    Condenseremperawre

    CondenserWater Flow Rate

    CondenserWater Inlet Temp

    CondenserWater Outlet Temp

    CompressorPower Input

    W / Watts

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    58/76

    n

    ~

    .

    ~

    .

    =

    3

    t

    D

    a

    ~

    ~

    ~

    ~

    .0 m

    t

    n

    0

    ~

    (

    a

    0

    ~

    -

    m

    m

    n

    1

    T

    n

    +

    t

    1

    L

    +

    r

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    59/76

    ~

    0

    0

    n

    '

    o

    0

    0

    0

    1

    '

    1

    0

    n

    -

    0

    <

    >

    I

    N 0 0~

    0

    0

    \

    O

    ~

    ~

    0

     

    .

    -

    ~

    ~

    0N

    \

    8

    3

    1

    ~

    d

    X

    '

    S

    J

    ~

    i

    ~

    I

    ~

    ~

    .

    a

    "

    I

    -

    0

    ~

    O

    q

    M

    ~

    \

    .

    -

    v

    3

    R

    o

    Q

     

    U

    S

    3

    N

    -

    ~

    -

    0

    0

    0

    0

    ~

    0

    -

    0

    )

    -~

    o

    V

    -

    ~

    c

    ".

    c

    -

    O0~

    .

    ".

    c

    -

    0

    V

    ~

    ~

    0

    1

    0

    V

    0

    -

    g

    0N

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    60/76

    S6

    SPECIFIC RISKS

    .

    Contact with liquid will causesevere rost bite

    .

    Decomposesn a fire to give toxic and corrosive fumes

    .

    Containen may bunt if overheated

    .

    Risk of asphyxiation at high concentration

    IDENI1F1Ct770N

    SYDOBymS

    1.

    LI

    l,l,-Dichloru-l-O=roethaDe. R-141

    Uses

    Plastic fOim blowing aaalt,SOlveDt

    .1

    1717-00-6

    404-080-1

    CAS

    EINCS

    OMPOSmON (.rubstanCeJ r impurities giving a hazard)

    Substance 1 I ,-dichloro-l-Qooroethane

    Impurida DOne

    2.

    PHYSIC4LPROPERTIES

    At 2G-C liquid

    3.

    colo1U': colourless

    0d01U': slightly etherial

    3.1

    PbysicalSUte

    Health & Safety

    Data Sheet

    elting point: -lO3.S-C boiliDl point: 32.0-C

    critical taDper8ture: 20S.C

    ~tiOD ~.1Ure: SOO-C

    3.2

    Tempentura

    pH

    DCutr81

    .J

    Solubility

    .4

    in ~ at 20.C: 0.54% y weight

    in solvCDts: misciblewith aliphatic ydrocarbons.

    aromatlcs,ketoaes.chkwiDated

    derivatives 1¥i

    If this material s redistributedo

    sale,detailsof its hazards nd

    recommendedmethods f safe

    handlingshouldbe passed n to

    users.

    at SO.C:

    .83 Ir

    t 2Q8C: 0.81 bar

    .5

    Vapour pressure

    1.24 ,cm)

    5.011Ifm)

    (liquid) at 2S.C:

    (vlpOur) at 32.C:

    3.6

    Deasity

    3.7

    Other data

    criticalpressure: 43.4bar

    4.

    4.1

    STORAGE AND HANDLING

    Spedal torace Dd Store etWeeI1- andSO-Cn a well v~rilated~

    baDdUacrecaadoDS ~t storedn.sp«ial1y einforcednDDS.

    PacklDgmaterials

    .%

    A void alloys with 2% or more of magnesium r

    aluminium.Avoid plastics. Usesteelor polyethyleue

    dr1Dns.

    Stableat ambient emperabl1'e,ut willlDfcrlo thermal

    decomposition t elevated emper8tureso give off

    hydrochloricand hydrofllWric acidsaDdpossiblypbol8~

    4.3

    DecompolltioD prvducu

    HRP Refrigerants Ltd.

    Gellibirion Industrial Estate

    Pontypridd

    Mid Glamorgan

    CF37 5SX

    DaQcroas reacdODS

    Withnaked ameor hot metal~

    .4

    4.5

    lDdJvtduaJ meDdoD

    and pAtecd"e measures

    Gloya loula r=ommeadedvoidiquid

    oDtKt

    with kiD eyesDdheDh8Iati~f~.

    In case of emergency elephone

    Va1ri1arche workiD&area. No aom,. No aaked

    nama.

    4.6

    Sped" protecdve

    mcuara

    01443 842255

    If in m ~loscd -rea. YCDn18le or WaI' tt:1 oCOaIaiDCd

    bratbiDI

    ~ (risk or -.hyxi8lioa/llK)xia).Allow

    to eT8pOrIIc r pump nto salecoatIiIICr. Prevalt. rom

    mtailla ~ bucmCUIS tc.

    4.7

    Meuara after IpWqe

    0 Ieak8Ie

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    61/76

    57

    SPECIFIC RISKS

    . Contact with liquid will causesevere rost bite

    .

    Decomposesn a fire to give toxic and corrosive fumes

    . Containers may burst if overheated

    . Risk of asphyxiation at high concentration

    ...8

    Ret\un to supplia-.

    estnacttoD of

    coDtamiDated coDwDer

    Store at a tanperaturebelow SO-C n a y~latM area,

    away from all ~~ of heat or ignition.

    Other recommeDdatioDS

    .9

    CAS

    EINCS

    1717-00

    404-080

    IGN1110N AND EXPLOSION

    F1ashoiDt none

    5.

    5.1

    5.1

    Auto-ignition temperature none

    Non-flammableproduct Thermal decomposition ives off

    toxic fumesoChydrochloricand hydrofluoric acids and

    phosgene.

    Special ire or explosioD

    hazards

    S.J

    Health & Safet

    Data Sheet

    ot applicable

    .4

    Extinction

    Wear self-contained reathingapparatus nd ull acid

    resistantprotectiveclothing.

    5.5

    Particularmeasura

    during OR-fighting

    Protect. ontainers rom heat~urces. Cool with water to

    avoid ov« pressurisation.EDsure roductdoesnot come

    into contactwith naked lamesor hot metal surfaces.

    5.,

    Other recommendations

    If this material s redistribute

    sale,detailsof its hazards nd

    recommendedmethodsof saf

    handlingshouldbe passed n

    users.

    6.

    TOXlCOLOGICtL NFORMATION

    Employersshouldbe aware hat this product s ~lvent

    abusable.

    Vapour

    2,500 ppm for 30-60minuteswin cause ertigo,

    drowsiness nd respiratoryproblems. May cause ncreased

    sensitivity of myocardiumabove 12,500 pm.

    Uquid

    Repeated nd proloaaedskin contactwill produce

    dermatosis. Eye contactwill lead to irritation. redness nd

    moderate onjunctivitus.

    7.

    HRP Refrigerants Ltd.

    Gellihirion Industrial Estat

    Pontypridd

    Mid Glamorgan

    CF37 5SX

    FIRST AID PROCEDURES

    Skin contact Washwith copious molmts fwater'.

    Inhalation Removeo fresh ir. ApplyoxygenCbreathings

    difficult. Consult doctor.

    EyeCODtact Wash DQ .~a~elyith copious molmts f water.

    Consult an opbtbalmologist.

    8.

    In caseof emergencyelepho

    SPECIAL PRECt U110NS FOR WASTEDISPOSAL

    This matcria1s subj«t to the resttictioasof the

    EnvironmentalProt=tiol1 Act and shouldoot be Va1ted o

    atmosphere.W.. materialcan be ~ to HRPR.

    Movancnt of refri&~ for ~1amation or destIuctioD s

    subj~t to the Duty of Care lK requiIeIlppropt.ate

    01443 842255

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    62/76

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    63/76

    S9

    1 2

    '3

    4

    Amendments

    2 MAINS FILTER ADDED

    10.9.97 JB

    A

    NEW 3 CORE POWER CABLE

    FROM TRANSFORMERSECONDARY

    2'OV

    TO MA~S FILTER

    LENGTH 1000 mm

    ) LINE t

    -0

    )1

    r---

    j

    .

    1 I

    .

    1

    I i: I

    1

    1

    @}

    ~:

    .

    ~I

    ...1

    -

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    64/76

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    65/76

    61

    APPENDIX A

    OP'nONAL DIGITAL TEMPERATURE INDICATOR

    R633A

    If£I-I"iNG INSTRUcnONS

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    66/76

    62

    --

    --

    VjQllK

    mQJCatorl in the centre of the Wlit.

    The addition of the digilal temJ'eraLure ndicator not only increases die resolutioo of tem})el3ture

    measuremenm rom to.soC to O.IOC but a thennocouple sensor is provided to record the temlJeJ'a1Ures

    of the iquid in the baseof the condenser

    hamber re.

    The addi iOnal teJnj el tures al w a compl te vap our comP ssi n cy l di gram to be nrn.i .~_ .. - 1

    refrierant R41b PCssure-enthaIpy digram.

    Once he level has been measured r marked,position the ball valves or shutdown (SeeFigure 2

    -

    R633 Valve Positions)and hJm he unit off. Turn off and disconnect he unit from the water supply.

    Isolate the unit from its electrical supply and then remove

    he bolts and one nut securing the rear

    panel.

    Store he bolts, nut and washersn a containeras thesewill be required or refitting the panel.

    Remove he hermometersrom their pocketsand store hesesafely. Note hat f the original installation

    recommendations ere ollowed dlere will be someoil in ~h of die dlennometer ockets.

    With the help of an assistantay the machineon its back and ocate he 3mm (1/8") diameterblanking

    rod in a pipe fitting in the 00seof the condenser hamber. This is the ocation or the

    1s thennocouple.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    67/76

    63

    Ensure mat the liquid level is below the level of the blanking rod and that the condenser ressure s

    either at or below atmospheric pressure.

    Using a close itting spanner emove he nut securingdIe blanking rod.

    Take the 0 3mm x 8Smm long diennocouple ( MIS/IO) and using a 0 3mm compressionolive

    (PF4/67) and die original nut. insert the diennocouple n die chamber o a depdi JUST BELOW that

    of the measurediquid level.

    Rewm me unit to an upright position. Thosewim accesso a vacuumpump may eXb'act ny air from

    the systemby connecting o me internal pipe leading from me vent valve on top of the condenser

    chamber.

    Note that the oil in the unit is hygroscopic absorbswater vapour rom the air) and the unit shouldDOt

    be left open o atmosphereor long periods.

    Fit the 7 shon rod type thermocouplesIMlS/l6) in placeof the original thermometers.For the present

    time the thermocouple onnecting eadscan be left ttailing at the front of the panel.

    Remove die 92mm x 92mm blank insttument case from the panel by releasing die retaining screws from

    inside die machine panel and withdrawing die case from die front of the unit.

    The digital temperatw'endicator and multi way selecta-switch are two separatetems. A separate

    core bennocoupleable s suppliedo makeme ink betweenmemo

    FirSt nstall the 10 way selector ]MIS/50) at the bottom of the 92mm x 92mm panel orifice. This is

    retained y wire springs ndclips whichpress gainsthe ascia. Refer o FigureA on Page 5.

    The indicator ( MIS/53) is fitted above he multi way selectorand retainedby jacking screwswhich

    bear on me rear of the panel fascia. Refer to Figure B on Page65.

    Make the 2 core thermocouple onnection n accordancewith the wiring diagram on Page71

    The Brown or Green (+) wire runs from COMM I to indicator terminal 25 "VI".

    The Blue or White (-) wire runs from the terminal on die right of COMM 1 to indicator ternrinal26

    "COM",

    Apply the label "Oc" to the fa:e of the indicator to the right of the digital display.

    Apply the yellow label "TemperattJrendicator" to the panel fascia.

    Electrical Installation

    The 3 core IX>wer upply lead for die optional ternperattJrendicator and separate ptional wawneter

    is factory fitted to the following tenninalson the DIN rail connectors n the right handside of die unit

    adjacent o the input IX>weread. Their free endsare dentified ~ follows:

    49 (Eard1

    -ColourGreen Yellow suipe) FromDIN Rail 5

    47 (Line -Colour Red) From DIN Rail 8

    48 (NeuU'al

    -

    Colour Black) From DIN Rail 13

    ~ units already itted widt a wattmeter (R633B) will use the ~k. of loose JinkssuWlied to tap

    into the wattmeter K>wer upply. Refer to the wiring diagramon Page71.

    Units not fitted wim me wattmeterwill useme free wires abelled 7 (Line

    -

    Cololn' Red) and 48

    (Neub'al

    -

    Colour Black) directly.

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    68/76

    64

    The free end of d1e ead will havebeenprotectedwith tenninal covers. Theseshooldbe removedand

    the 3 wires given 1 turn throughme ferrite ring suppliedand ~1Ued ooar o the ndicator. The red and

    b1a;k cablesshooldbe connected o the following terDlinalson the digital temperatW'endicator. Note

    that as ~ digital temper8bJrendicator s double nsulated. he green/yellowearth wire is not used n

    this application.

    18 L Line renninal securesRed wire 47

    17 N N euttal terminal securesB1a:k wire 48

    The themtocouple eadsmay now be ~red to the thennocoupleenninalson the multi way switch

    oox. Note fran the wiring diagram on Page71 that ~h of the 10 switcOOdhannelcoonectioos n

    the rear of the oox has4 terminals. However. n eachcaseonly the eft baOO air of eachgroup of four

    areutilised.

    Note that due o a new EuropeanStandard, ome ype K d1ennocoupie ~ will utilise brown andblue

    insulation and od1ers reenand white to identify the polarity.

    For ~b tbennocouple he brown or green~itive lead s connectedo the tenninal marked 1 in ~b

    group of four. The blue or white negative ead connects o me next terminal on the RIGIrr of me

    tenninal maIked 1 n eocbgroup of four. The remaining ennina1sn eachgroup of four are not used.

    Note that only channels to 8 (CHI, CH2, aD...CH8) are utilised. The remainingchannels,9 and

    0, are not utilised for dlis option kiL

    Start with ~ merm

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    69/76

    6S

    FIGURE A

    PA~L

    ~

    USE A SUITABLE FLAT

    SCREWDRIVERTO PUSH AND

    ROTATE THE ClP ONTO THE

    TWO BRASS STUDS ON THE

    SlOE OF THE SWITCH CASE.

    THE OPPOSITE SVE

    FITTED IN THE SAME

    MANNER BUT INVERTED

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    70/76

    66

    This page is intentionally blank

  • 8/9/2019 Refrigeration Cycle Demonstration Unit

    71/76

    67

    APPENDIX B