8/9/2019 Refrigeration Cycle Demonstration Unit
1/76
(ii)
EDUCATION AND TRAINING EQUIPMENT
Declaration of Conformity:
Directives
(where applicable) 89/392/CEE as amended by 91/368/EEC
89/336/CEE
72/23/CEE
We declare hat the following unit complieswith the aboveEEC directives:
R633
Refrigeration Cycle Demonstration Unit
For and on behalf of
P.A. HILTON LIMITED
4,~;._AA
Technical Director
P .A. HILTON LIMITED
HorsebridgeMill, King's Sombome,
Stockbridge,Hampshire,S020 6PX,
England.
Tel No. National Romsey 01794) 388382
International +44 1794 388382
Fax No. +44 1794388129
E-mail: [email protected]
8/9/2019 Refrigeration Cycle Demonstration Unit
2/76
(i)
POLICY STATEMENT
After Sales Service
We, P.A Hilton Ltd., attach considerable imJX)rtanCen being able to retain die confi(k;nce and goodwill
of our clients in offering an effective after sales service. Every effort is made to answer clients
COrIesponOODCCromptly and to JXOvide a rapid follow up of spares and repi.:ement parts by
maintaining comprehensive stocks of COIDJXmentssually available ex-stock.
Shouldour clients encounterany difficulty in ~g or maintaininga Hilton prodtx;t we would ask
that as a first step dley COIU.:tdle Hilton ~tative in their country or. in me absence f a 1
8/9/2019 Refrigeration Cycle Demonstration Unit
3/76
INDEX
~
SCHEMATIC DIAGRAM
1
VALVE POSITIONS DIAGRAM
2
SYMBOLS AND UNITS
3
4
4
4
INTRODUCTION
The Refrigeratiooor Heat Pump Cycle
The ValX>urCompressionCycle
INSf ALLA nON AND COMMISSIONING
6
THE mLTON REFRIGERATION CYCLE DEMONSTRATION UNIT:
Useful Data
Specification
Description
10
10
11
13
OPERATING PROCEDURE
Nonnal Operation
EvaporationPnx:ess
Condensation rocess
Shutting Down the Unit
RefrigerantPump Down
Oil Return
Air Venting
IS
IS
IS
16
16
17
11
18
19
19
19
20
20
20
20
20
21
MAINTENANCE:
High PressW'e ut Out
Thennometers
Minjanue Cin:uit B~ (MCB)
ResidualCunent Circuit Breaker RCCB)
Testing the RCCB
Checking or Leaks
Chargingor Rechargingwidt Refrigerant
8/9/2019 Refrigeration Cycle Demonstration Unit
4/76
23
APABILITIES OF THE REFRIGERATION CYCLE DEMONSTRATION UNIT:
24
emonsb'ation of die Vspour Com}Xession Cycle
.
The Pressme- emperatmeRelationship 27
.
30
.
Demonstration f PumpingOver
31
emonstration f Charging.
32
emonsttationof Effect of Air in a Refrigelation System
.
3Sffect of EvaJX)rating and Condensing Temperatures on the Refrigeration Rate
.
39
ffect of Compressor ressureRatio OIl SystemPerformance
.
43
.
Detenninationof Overall Heat TransferCoefficient
47
.
Generationof a RefrigerationCycle Diagram
Measurement f dIe Effect of Conoonsing emperature n Com~r Power Input 51
0.
53
BSERVAllON SHEET (Blank)
54
141b SATURA nON PRESSURE v TEMPERATURE GRAPH
ss
141bP~SURE-ENTHALPY DIAGRAM
S6
141b COSHH DATA
58
IRING DIAGRAM. R633
59IRING DIAGRAM - 11O-130Vransformer
APPENDIX:
61
. Optional R633A Digital Temper:ature
ndicator
-
Fitting Instructions
67
. Optional R633B Digital Wattmeter-
Fitting Instructions
8/9/2019 Refrigeration Cycle Demonstration Unit
5/76
of-'
.-
c
:)
1
~
4)
...
=
0)
it
"Qj
~
"-
II
D
~
+-
8/9/2019 Refrigeration Cycle Demonstration Unit
6/76
2
NORMAL OPERATION
SHUTDOWN
8/9/2019 Refrigeration Cycle Demonstration Unit
7/76
3
SYMBOLS AND UNITS
Svrnool
kNm-2
ressure f Refrigerant n Condenser
c
tNm-1
ressure f Refrigerant n Evaporator
.
Water Mass Row Rate
dU'OughCondenser
e
1i1.
Water Mass F1owRate through Evaporator
Temperature f Water enteringEvaporattl' oc
t
oc
em~ of Water eavingEvaporator
~
emperature f Water leaving Condenser
,
Temperature f Water enteringCondenser
~
,.
oc
vaporating Tempel8t1n"e
s
oc
emperaturen Condenser
.
oc
,
CompressorDischargeTemperature
oc
s
Condensed iquid TemperabJre
W m-~K-1
Overall Heat Transfer Coefficient
Presentation f Numerical Data
In dlis manual, numerical quantities obtained during experiments,etc., are expressed n a non-
dimensionalmanner. That is, me physical quantity nvolved hasbeendivided by me units in which it
has beenmeasured.
As an example:
p
0' Nm-1 . 150
This indicates hat
p = 150 x 10' N m-2
r
p = ISOkN m°2.
alternatively
8/9/2019 Refrigeration Cycle Demonstration Unit
8/76
4
INTRODUCTION
Tbe Refriaeratk»D or Heat PumD Cycle:
A refrigerator is defined as a m~hine w~ prime function is to remove heat from a low temperature
region. Since energy cannot be deSU'OYed.ie heat Iaken in at a low temperature plus any other eneJ'gy
inJX1tm~t be dissipated to die SUn'()Undings.H the tempezabJreat which die heat is dissipated is high
enough ro be useful, e.g. for SpIM:;eeating, the ~hine is then called a heat pump.
By selectivedesignof the components he cycle may be optimisedeidler for heat pump applications
or for refrigeration applications. Indeed unckr certain applicationsboth useful functions may be
performedby one machinewhere circumstances enniL For example, n a dairy where refrigeration
is required or milk cooling and storageand hot water s required or OOuIe r tank washing.
The aausius Statement f the SecorKI aw of Thennodynamics tates hat heat will not pass rom a
cold to a ootter region without the aid of an "external agency". Thus. a refrigerator will require an
"externalagency", .e. an input of high gradeerergy, for it to operate.
This energy nput may be in me foon of wrateor a va[X)urwill coodense) s dependenton die
pressure,hus f a suitable luid is introduced t will evaporate t a low temperatm'en the low pressure
evapora1Ortaking in heat) and will condense t a higher remperatW'en die high pressurecondenser
(rejecting heat).
The high IXeSStD'eiquid fomted in the condenser must then be returned to the evaporator at a controlled
rate.
Thus. the simple vapour compression efrigerationcycle has our main components.
(1) An evaporatorwhere heat s taken n at a low tempe1'atures a liquid evaporates t a low p-essure.
(2) A compressorwhich usesa work input to redI.K:ehe ~ure in the evaporatorand increase he
.. pressuref die vapour eing ransferredo die condenser.
(3) A cOIxienser here he high pressure apour condenses.ejecting heat o its surroundings.
(4) A flow control device which controls die flow of liquid 00ck to die evaporatorand which brings
about die pressure eduction.
The refrigeratioocycle is most interesting rom the thennodynamic iew poinL It is one of the few
~tical plants which operateson a true thennodynamic ycle and nvolves
(a) Nucleateboiling and filmwise condensation.
(b) Steady low processes,.e. dn'ottling, compression nd beat exchange.
(c) Row conttOl.
(d) The thermodynamic roperties, .e. pressure, pecifICvolume, emperature, pecific enthalpy and
specifIC nttOpy, f a pure substance t all conditionsbetweensub-coolediquid and super-heated
vapour.
Ald\Ough he vapourcompression ycle is simple o thosewho are familiar widt it many students ind
great difficulty in visualising and understanding te eventsoccurring within the various components.
8/9/2019 Refrigeration Cycle Demonstration Unit
9/76
5
With dtis in mind P.A. Hilton Ltd., designeddie RefrigerationCycle DemoosuatiooUnit in which die
major pan of the cycle takesp~ inside glass chambers nd can dlerefore be observed.
The unit is a valuable hing aid for studentsn a wide ange f co~ from craft and eChnician
training o first degree t a Universityor PolyteClmic.
8/9/2019 Refrigeration Cycle Demonstration Unit
10/76
6
IN~ ALLA nON AND COMMISSIONING
Removeme unit from its p.:king caseand carefully examine t for damage. f any is foulKi. notify tile
insurers mmediately.
Stand he unit on a table at a convenientheight aM cl~ to an elec1rical upply, a water supply and
adlain.
Do not stand he unit in a positionwhere t will be in strong direct sunlight or long periods.
This may result in high chamberpressures ith the subsequentossof the refrigerant charge
through he safetY alves.
(i)
The tmit is fitted with two long life fluorescent amps which for shippingare ~ separately.
In orOOro fit the lamps the rear panel of the m.:hine must be removed.
Ensuredlat die m&:hine S NOT CONNEcrED 10 nIB MAINS ELEC1RICAL SUPPLY and
remove die hexagooalbolts and one Dut secmingdie rear panel Note that die bolts are 8mm
across lats and the COn'ect ize spanner s recommended.
The lamp socketsare located nternally and are under die two vertical slots in ~ unit panel.
Carefully remove me lamps from their packing ma1erialand imezt diem in me white plastic
socketson the left hand and right hand sidesof me panel. SUR>Orthe socketsby hand as tm
lamps are inserted.
While me rear panel is removed ensure mat die Residual C1DTCOt iIcuit Breaker switch situated
on DIN rail the right side of the panel is in die ON positioo. The unit will have been left in d1e
ON position when shipped but transit vibration or shock loading can ~ the switched to jwnp
to me OFF position.
(0)
Connectdie mainswater supply o die water nlet at the rear of die unit using he diagooainylon
reinforcedhose. When facing the rear of the machine the water
~
~ on the extreme left
or thepanel.
It ~ recommendedhat the water supply s red through an isolatingvalve that can be
turned ofTwhen he unit is not in use.
In older to increase he stability of the condenser water ftowmeter and evaporator water
flowmeter the conttol valves on thesedevicesare fitted to the discharge ide of the flowmeter.
Hence f externaldamage esults n the flowmeter ubesbeing brokenan external solating valve
will be req~ to stop the flow of water from the unit
(ill) Connectdie remainingwater coupling at the rear of the panel o a suitabledrain using he dear
plastic pipe provided.
(iv) 220/240V Units
Replace he rear panel BEFORE connecting he unit to the mains suWly.
The power supply cable will be foWld emerging rom die rear panel. Connect die cable to a
suitable fixed power supply via a fused outlet (for 5 Amps) which canplies with die ~
regulatioos.
Brown cable
Bloo cable
GreenlY ellow cable
LIVE or LINE
NEtn'RAL
EARTHor groond
Note hat cx safeoperationhe greenlY llow cableshouldbe ~ted to a low impedance
earthing oint hatcomplieswith the ocal egulations.
8/9/2019 Refrigeration Cycle Demonstration Unit
11/76
7
110/I20V Units
The unit hasan internally fitted transformerwhich is suitable or input voltagesof between110
and 130 Volts (110 to 130V in 5 volt steps). The integral SUWly ~ must be coonected 0d1e
nearest uitablevoltage ennina1s nd mis can ooly be ~hieved by first removing Ix: rear panel
from the unit. The transfonner s locatedon the right hand side of the unit when ooking at the
rear of the machine.
Before connection to dte transfr8fOrnd conde~ cooling water JXx:ke~at dte ends of the evapora~ and
condenser oils.
It is recommendedhat in order to imlXOve he resolution of the thennometers few drops of
light machineoil is OOdedo ~h thennometer
8/9/2019 Refrigeration Cycle Demonstration Unit
12/76
8
If die djagramsare to be fitted to die panel hen t will be ~- -ry to fit me four clips suwlied
to die ~ of d1epanel.
Auach the 4 spring cli~ to the ~ of 1be -nel using the 8 self-tapping~WS povided. Note
that 8 small pre-drilled holesexist on the ~ of ~ panel o a:ceIX he ~ws.
The clips should be fitted wid the OPEN end king toward the fratt of die panel.
The L shaped lear plastic schematicooldersare dIeDslid under he spring clips.
In order to utilise the plastk COV~ or the unit the L shaped chemabc oldezsmay be removed
and stored under he unit panel
8/9/2019 Refrigeration Cycle Demonstration Unit
13/76
9
1
2
3
4
Amendments
2 MAINS FL TER ADDED
10.9.97 JB
A
B
c
SlFPL y m -130Y SO/60Hz
SEe HA" ~ aAGRAH F~ TERttNAL KEY
[Drawn y
JBhe ~ier is req.jred to deliver goods strictly ~cordi-9 to
drowing. Component nspection is the suppliers responsibiity
R8IIIDveoil sharp edges a~ burrs.
[
Checked
by:
Dimensions: mm
@Q
rojection'
Issue: 2
Date:4.3.96
Scale.
-
no/rig. 1
ENGLAND
Limits unless otherwise stated
Fractions * 1/6"
Decimals * 0.25 mm
I DRG. No.
633365
110
-
130V TRANSFORMERWIRINGDlRGRAM
TITLE:
MTL:
FIIIISH:
KINGS SOMBORNEHAMPSHIRE
. A. HL TON l TO
8/9/2019 Refrigeration Cycle Demonstration Unit
14/76
10
THE HD..TON REFRIGERAnON CYCLE DEMONSTRAnON UNrr
USEFUL DATA
Condenser:
Wal« coil surf~ area: O.O32m3
E VSDOratOC
Water coil surfacearea: 0.032012
Specific beat capacity of Wafa' c,>: 4.18 kJ tg"1 K-1
Refri~erant:
R141b
1,1,dicbloro-1- flooroetbane
Quantity: approximately800 cm' (awroximately 1 kg)
8/9/2019 Refrigeration Cycle Demonstration Unit
15/76
11
SPECIFICADON
Compreaor
Hennetic ype ~pressor with inlegrall/2
H
8/9/2019 Refrigeration Cycle Demonstration Unit
16/76
12
of die StaDdaIdpanel and may easily be fined by the CUSfDm~.or if
purchased widt the standard unit can be a f~tory fitted 0IKia1.
SAFETY
No moving parts.
Intemally mounted relief val~ ~t to 2SOkN m"2 gauge fitted to
cOIxIen= aOO vaporator.
High ~ure cut out fitted to stop compress
8/9/2019 Refrigeration Cycle Demonstration Unit
17/76
13
DESCRIYnON
(please efer to me schematicdiagram on Page 1)
All COlDJX)nentsre mounted 00 an attractive durable glass reinfrator.
On entering the evaJX)rat(X"he low pressure iquid aOO aJX}ur eparate. he liquid passing nto the
"pool" for re-evaporation.while the vapour mixes with the vaJX}ur roducedby the boiling ~tion of
the water coil. The vapour mixture then returns to the compressoro repeat he cycle.
In the standardunit instrumentations provided to measure:
(i) The tem~rature and pressure f die refrigerant vapour n die evaporatorand condenser.
(ii) The tem~rature of die water entering and leaving die coils in d1eevaporatorand condenser.
(ill) The water flow rates hroughbodi coils.
(iv) The tem~rature of die oot gas eaving the canpessor.
All temperatures re measured n die standardunit using red spirit dlennometers.
An optional digital temperatW'epgrade it is available hat allows measurement f the temperature f
the condensediquid te as well as the above ist of temperatures.
With the addition of this optional upgradedie completecycle diagram may be plotted on an R141b
pressure-enthalpy iagram.
An isolating valve is fitted at the condenser utlet and this may re cl~ed to ~onstrate a technique
used in refrigeration maintenaocewhere the refrigerant charge s collected and contained n the
conde~ or in most CMesa specialisediquid receiveradjocent o the condenser.
8/9/2019 Refrigeration Cycle Demonstration Unit
18/76
14
This ~hnique is imJX)rtantn onk:r to demOOSb'ateow to pevcnt ~ escapeof refrig~t during
maintermnce.
In common with all refrigeration and heat pump systems he unit containsa small amount of oil for
lutxication of ~ CaDpessa. During normal operation~e oil. in die fOOD f mist and oil/refrigerant
~Iution is carried from the compessor to the condenser nd ultimately to die evap
8/9/2019 Refrigeration Cycle Demonstration Unit
19/76
IS
OPERATING PROCEDURE
(please refer to Figure 1- SchematicDiagram, and Figme 2 -R633 Valve Positionsdiagram)
To assiSt n unOOrstandingration. item namesand relevant tems on the two scoomaticdiagrams
suppliedare refelTed o in bold type in the following sections.For example.Refrigerant Pump Down
on Figure 2 and Condenser or Evaporator etc on Figure 1.
The five baD valves shown on the two schematicdiagramshave been nsIalled for ~ ~
Figure 2 (Page2) diagram shows he four standardvalve combinations.
The vent valve on die condensers namally only openedbriefly to vent air from the systemaId this
is referred o elsewhere.
Note mat when the mrlt is shut down the ball valves should AlL be in the closed positioo. This
preven~ the refrigerant migrating to the lowest temperature art of the systemdue to vapourpressure
effects and in most ~s dtis would be the compressor asing as this will respond most rapidly to
variations n ambient emperature.
Normal Ooeration
To start the unit first turn on the cooling water supply and the mains supply to the unit
Open the valves ndicated n Figme 2 (Page2) for Normal Operation.
11ris llowsvapour o be
8/9/2019 Refrigeration Cycle Demonstration Unit
20/76
16
Unlessdie supply water emperatures high men altera1ion f ~ evaIJ
8/9/2019 Refrigeration Cycle Demonstration Unit
21/76
17
Normal running condition is widl aPJK'Oximatelyo-25mmof liquid in the bottom of the condenser
chamberand dle float valve maintaining his level constanL
Once normal operatingconditionshavebeen~hieved men me main switch shouldbe turnedoff. The
compressorwill stop and me lights on the unit will be extinguished. If the optional temperature
indicator has been itted the display on this too will be extinguished.
Turn off die cooling water suWly to die unit It is recommended lat die (water) control valves are
left open so that f die usersuppliedexternal solating valve eakswater will be allowed to run to drain
and will be noticed more readily. In addition, f conditionsare such hat the water supply s likely to
freeze dlen leaving die control valves on the flowmeterSopen may not prevent die glass ubesbeing
broken but it will make breakage ess ikely.
Once he unit b$ been urnedoff then me ball valveson me unit shouldbe closed o mimic me
shutdowncondition. SeeFigure2 (page2).
This will prevent the large volume of refrigerant contained n the evaporcUormigrating into the
compressor asingdue o vapourpressure hanges.The small volume of liquid in the condensermay
migrate to the compressor nder certain ambient conditionsbut this is no cause or concern.
Refri2erant Pumo Down
This is a procedureoften used n industrial and commercial efrigerationpractisewhere die refrigerant
charge s condensed nd collectedeidier in the condensertself or more commonly n a liquid receiver.
In die RefrigerationCycle DemonstrationUnit R633 die condenser nd liquid receiver are combined
in die sameglass cylinder.
In order to carry out pumping down dte unit shouldhavebeenoperatingnormally f
8/9/2019 Refrigeration Cycle Demonstration Unit
22/76
18
cooling water aM evaJX)rator ater flow rates are left as for normal nD1ningand me unit remaim
switched00. The only pam from me evapa-ator o the compressors via the capillary tube.
The oil in the baseof the evaporatorwill start to flow mrough the capillary blK:t to the com~
casing.
The evaporator chamber may be at low JXeSSure nd therefore the oil return process will be slow due
to the low differential pressure. This may be increased and the ~ speeded up if a small amount
of refrigerant liquid is OOmitted o the evalXJ[ator by briefly opening the ball valve at the base of the
condenser. However DO NOT leave this valve open.
Once the oil has been eturned o die CODlpresD' asing d1endie ball valves may be ~ to dx:;
position for normal operation as shown n Figm'e2 (page 2).
Once die operating coOOiuons have rewrned to noonal and the liquid level in the conde~ is
apJX'Oximately2O-2Smm tOOn OOunit may be eithez shut oown as described ai)Ove or adjusted for
further experiment.
Air Ventin2
A vent valve is siwatedon dle top of the con
8/9/2019 Refrigeration Cycle Demonstration Unit
23/76
19
MAINTENANCE
Hi2b Pressure Cut Out
At regular ntervals and according o the local safety regulations he high pressure ut out shouldbe
testedas follows:
Start dte unit as detailed for normal operation in the operating procedure 00 Page 15 and
operatewidt a modezate ooling water flow to both dte condenser nd evaporaror s detailed.
Allow die unit to warm up and hen cl~ the control valve on the condenserwater nowmeter.
This will cause he condenserpressure o rise. At approximately22OkN m"1 he compressc.'
shouldbe shutdown by the nternal high pressure ut out An audible click shouldbe heard rom
the cut out device.
If the compressor oesnot turn off automaticallyat a oressure f 230kN mol hen turn off the
unit at the main switch. It will then be necessary o adjust the pressure switch as detailed
below.
If the compress
8/9/2019 Refrigeration Cycle Demonstration Unit
24/76
20
Th~ differencesmay be added B'subtlaCtedrom dJe~ as awropriare.
If greater~uracy is requiredmen he water may be gently warmedand me diff~nces notedat ~vera1
temperatures. In d1is case a graph of indk-lt~ against difference should be plotted for ~h
th~omeleJ' .
H the optional temperature indkator hasbeen itted then d1eaOOveiffera1sitionwhen he unit is not in use
Cbeckinl for Leaks
If a leak in the refrigerant circuit is suspected. e.g. if d1ere s a loss of refrigerant from the system, me
following procedlD'e should be adopted:
(A) If tOOres refri9.erantn the system:
~e die unit in a WanD laceuntil its temperatureea:hes32-3SoC.The pressure hrooghoutdie
systemwill now be aboveabnospheric JKIdie leak may be loca1ed i~ by
(i) Applying a Sb'Ongmp or detergentsolution to all joints,
(ill Using an electronic eak detector.
(B) If there s no refrl2erant n the System:
Pressuriseme system o SO N m""wim air by applying a manualpump.e.g. motOrcar tyre ~p.
to me charging valve at me baseof the evaporator. The leak may then be located as n A.
8/9/2019 Refrigeration Cycle Demonstration Unit
25/76
21
Cbarg2 or Recharge
Under nonnal conditions me vapour press\U'e f die refrigerant does not reach abnospheric pressure Wltil
die liquid is at a temperatme of approximately 32°C.
In order. merefore. o make charging me unit simpler. the one bip can supplied by P.A. Hilton LId
containsa small amolDltof Niuogen gas n order to raise me internal press\D'e rtificially.
Before charging t is recommendedhat me unit is set up in me following way:
Start die unit as detailed for normal operation in die operating procedure on Page 15 and operate
widl a moderate ooling water flow to bodl die condenser nd evaporatoras detailed.
Allow the evaporatorpress1D'eo reduceand then position the ball valves or shutdown condition (see
Figure 2
-
Page2) and
bJrn
off the compressor. Note that if the unit is not chargedand containsair
then t may be necessaryo vent this from the condenser ia the vent valve on the condenserop plate.
The unit s now~y for charging.
The chargecan only be released rom the can by using the brasschargingvalve (VCl7/2) supplied n
the accessaieskiL
Unscrewdie small brasshexagonalnut from die chargingvalve and screw diis onto die dtreadon die
top of the can. Screw die rest of the charging valve (VC27 l.) into the straight connector on die
refrigerant charging ine (C45/2), also supplied n die accessories it
Remove he brasscap from the fixed charging valve at the baseof the evaporatoron the R633 uniL
Note that the angled end of the refrigerantcharging ine hasa b~ pin in the. entreof the connector.
This end should be connected o the fixed charging valve on the baseof the evaporatOr.When d1e
connector s screwed ight the pin depresseshe centre of the fixed charging valve and allows access
to the evaporator.
The can should be inverted and me two components f the brasscharging valve should be screwed
togetherby rotating me can. SeeFigure 4, Page22. When the components f the charging valve are
screwed ogemerme refrigerantwill flow into me charging ine due o me nittOgenpressuren d1e an.
Open me ball valve at me baseof me evaJX>ratornd me refrigerant will flow into the evaporator.
Switch on die writ and d1iswill again educedie evaporator ressure nd assistdie flow of die
refrigerant into die evaJX)rator.
When the iquid level in the evaporatOrs above he level of the tOpcoil close he ball valve at the base
of the evaporatOr.
Allow die unit to run under nonna operatingconditions until die liquid level in die condenser as
stabilised. Ensure he liquid level is still above die top coil of die evapomtol. If this is not die case
then open he ball valve at die 00seof die evaporatorbriefly until d1e equired evel is ~hieved.
Unscrew he charging ine from the can and this will close he valve in the can. The ball valve at die
baseof the evaporatorcan be briefly opened o draw in any liquid remaining n die charging ine.
The chargingprocedure s likely to result in someair entering he system. To remove he air follow
the procedure or Air Venting describedon Page 18.
8/9/2019 Refrigeration Cycle Demonstration Unit
26/76
22
0,. Tr~Can
RMX74/1
-
Figure 4
Bras.C~gi'1g
Valva VC27/2
rn
B
Refrigerant Charging
Line CI.5/2
IN c~~
Valw With Centre
Pin
Angled Comector
With Central Pn
8/9/2019 Refrigeration Cycle Demonstration Unit
27/76
23
CAPABILmES
OF THE REFRIGERATION CYCLE DEMONSTRATION UNIT
Demonstration of vaJX)m' ompressioo refrigeration or heat pump cycle widt visual observation of
the important ~.
2. Investigation/demonstmtion of d1esaturation pressure-temperature relationship during evapoIation
and con~nsation.
Demonstration of "plDlping over" or "pumping down" into the condenser.
.
Demonstrationof charging.
.
5.
Demonstration f effect of air in a refrigeration system.
6. Detenninationof effect of evaporatingand condensing emperamres n me refrigeration rate and
condenser eat output
7. Investigationof die effect of compressor ressure atio on systemperfonnance.
8. Deterntinationof overall heat ransferbetweenR141b and water n the evaporatorand condenser.
With the addition of the optional temperature indicator:-
Generationof a refrigerationcycle diagram on a pressure-enthalpyhart.
.
With the addition of the optionalwattmeter:-
10. Measurement f me eff~t of condensing emperature n compressor ower input.
8/9/2019 Refrigeration Cycle Demonstration Unit
28/76
24
1. DEMONSTRA nON OF VAPOUR COMPRESSION REFRIGERA nON OR REA T PUMP
CYCLE
The ex~cnt shouldbegin wid the unit at rest.having been eft in die shutdown (SeeFigure 2, Page
2) condition for some ime in order for all of the compo~nu to be at a similar ambient empelabD'e.
Open he ball valveson the cylinders as for normal operation (SeeFigure 2, Page2) but do oot bIrD
on die unit and do not bIrD on die water supply to the evaporatorand condenser oils.
The stu1D".
Reference houldbe made o the Pressure nthalpy diagramon Page55 or the argee~uJaIed
diagram C57/10) supplied n the accessoriesit
In order to changephaseat constant X'e8Sure,nergy s required o increase he endlalpy of me
vaJX>ur. his energy s taken rom the water passing hrough he evaPnhe water nlet tem~rature and the ocal ambient em~rabJre, he surroW1dingtmospbete.
If the water supply temperature s high (awroximately 16OC r mur ubbles are being prodtx;ed rom me evaporaUX'oil within the evaporator
chamber hen heat is being exb'Xted from me cooling water flowing through the coil. If the
evaporator nlet water tempelabJrel is examined after several minutes operation and this is
comparedwith the water discharge emperature the discharge emperatm'e hould be fouOOo
be slighdy lower than the inlet tem~. In
8/9/2019 Refrigeration Cycle Demonstration Unit
29/76
25
addition, dependingupon me local ambient conditions,water vapour will also condense n die
outside surfaceof me glasscylinder and baseplate. The change n phaseof me water vapour o
a liquid will in itself IX'Ovioo eat o causeevaporation f die refrigerant n me chamber.
In addition, f the evaporator ooling water flow is stopped hen the rate of condensationonning
on the condenser oils will also reducedue o me reduced apourgeneration ate n the evaporata-
and me reducedvolumettic efficiency of the compressor nd ncrease n specific volume of me
vapour generatedn the evaporatorchamberat low pressure.
(ill) With the evaporatorand condenserwater again flowing as described n the normal operation
conditions on Page 15 the condenser ressure houldbe observed.
The condenser ressmewill be seen o be higher than that of the evaporator. This is obviously
due to the compressor. The ratio of condenser ressure o evaporatorpressure.PJP.. is known
as the compressorPressureRatio. This will vary ID1der ifferent operating conditions and may
be investigated.
After the W1ithas been nmning for several minutes under nonna conditions the condenser cooling
water inlet temperabD'eand the discharge temperawre should be compared.
It will be found that the discharge emperature , s greater han the inlet temperature ..
This is due to the heat given up by the hot high pressure as entering the condenser rom die
compress
8/9/2019 Refrigeration Cycle Demonstration Unit
30/76
26
As soon as the liquid passes hrough he expansion alve U pressure rops o awroximately the
pressIU'enside he eV8lXX8fOr. his ~ me liquid to immediaIelystart o changephase rom
liquid to V81XXJr. s in the evaporatm' ragy is required o bring about me phasechangeand
someof this is taken from the baseplate of the condenser the expansion alve is ~hcd to
the hue plate.
ExtrlK:tingbeat rom me baseplate edIx:ests te~ and his n bIrD educes he tem~nue
of the condenseriquid at me baseof the condenser.This results n ~ liquid being "sub cooled"
below its satUIation empelatm'e.
If the optional temperature indicator is fitled ~ an IKiditional thennocouple r. is supplied to
be fitled in the base of the colxleDSQ" hamber. Hence the sub cooled liquid tem~ may be
measured and this together with the other measured remperattlreSand pressures allows a complete
refrigeration cycle diagram to be plotted on the pfeSSW'C-enthalpy iagram supplied.
In the condenserrerefore the refrigerantchanges rom superheated apouron entry. through o
sanuated apour hen to sabJratediquid and ultimately to sub cooJediquid before t leaves he
condenser hamber.
As ~ refrigezant~ along the pipe leaiing from the exlBn8ioo valve to the eValJ(Xatoreat
will be exb'.:ted from the SUn'Oundingsnd ~ liquid will be further converted o a v8fX)Ur.The
si,ht ,- just before nb'y o the evaporatorllows he iquid/vaJX)urixture o be ~ed.
8/9/2019 Refrigeration Cycle Demonstration Unit
31/76
27
2..
PRESSURE TEMPERATURE RELATIONSHIP
The relationshipbetweensanuationpressure nd temperaturemay be observed n both me evaporator
and condenser. However as variation in the evaporating emperat1D'es small for aU but extreme
changes n cooling water flow me condenserX"Ovides
moregraphicllustration.
As the conoonser contains refrigeJ'ant n all stages rom superheatedvapour through to sub cooled liquid
the dlermometer pocket ~ only records temperatures close to saturation when die pocket is showing
signs of condensed liquid Therefore it is recommended that die pressure temperature relationship in
the condenser is investigated as the condenser pressure increases.
If the pressure empemture elationship s investigated y reducing he condenser ressure hen the ft
thennometerpocket will be at a tempenuure hat is higher than the surroundingvapour due to its
thermal nertia. Thereforeno vapour will condense n the pocket and an inCOIreCtemperaturewill be
measured.
Note that dJepressures referred to on dJe pressure-enthalpy chart and on the p-essure-temperature chart
on Page 29 are "absolute" values.
Absolute pressure=Pressure gauge value + Local abnospheric pressure
Procedure:
(i)
Start the unit for normal operation as shown on Page 15 but iocrease the condenser cooling water
flow to the flowmeter maximum (50 g S.l). The pressure at which the condenser stabilises will
depend upon the water inlet temperawre.
(ii) Allow die unit to run for approximately IS minutes in order to reach a uniform operating
temperature. Then record die condenserpressmePc, evaporatorpressurePe' die condensing
temperature and die evaporating emperature ,.
(ill) ReducedIe cooling water flow by a small incrementso that dIe condenser ressure ncrease y
approximately
0-2CBcN
-z. This amountwill vary depending pon dIe coolingwater nlet
temperature.
Allow the unit to stabilise or a few minutesand again record the above parameters.
(iv) Re~ the procedureup to the maximumcondenser X'eSSureequiredor to the high pressure ut
out value of 22OkNm4
Typical resultsare shown n the table below.
Local Aunospheric~: lOlkN mol
PcI
kN
m-1 gaugeondenserressure
-31
-21
+4
+49
41 -11
CondenserPressure
PcI
kN m-1- bsolute
~ 70 80
90
105 150
Condensing
temperature
../~
15.0 19.5 24.0
27.0 31.0
41.0
P.I kN m°7. gauge
vaporatol' Pressure
-68 -69
-69 -69
-69 -69
32 32 32
vaporata Pressure
P
I
kN m4 absolute
33
32 32
Evaporating
temperature
.,/OC
6.S
4.0
4~
4.0 4.0
4.0
8/9/2019 Refrigeration Cycle Demonstration Unit
32/76
28
Note that tem~ have been estimated o d1enearestO.soC~ing die SIaOOardbenDOIDC1m
SUWIied. Whezc he opdoul temperature indicator is fitted ~~ may be ~ to d1e
nearestO.loC.
The resultsare ploUCd n graphical onn on Page29.
Note that the standard D'eSSUIeauge~y of tl % of gauge ull ..::a)e as beat shown as 00Ued
lines about a mean. The absolute :curacy of the dlermometersm-~(XIa} tem~ iDd-k.J1O 'nd
thmnocouples)plus readingerrors will also .sd to any disc~ies.
8/9/2019 Refrigeration Cycle Demonstration Unit
33/76
8
.
t
1
_
3
I
~
~
0
0
0
0
L
)
0
N
~
~
t
_
W
N
a
D
d
U
J
1
D
J
S
.
T
.
~
f
5
0
0
~
0
a
V
0
0
8/9/2019 Refrigeration Cycle Demonstration Unit
34/76
30
3.
DEMONSTRA ON OF "PUMPING OVER" OR "PUMPING DOWN" INTO mE
CONDENSER
Duringmaintenancef refrigemOOo Jaob.partkularly when repl-=ement f com~nb is involved.
it is convenient o transf~ the ~gerant to me conck.nser. This ba the ~vantage of saving me
refrigerant or f1D1her se and also may avoid the needof ev~ua1ionprior to rechargink.
In addition. or ecologicaleasonsollowingme guidelines f d1eMontreal l. ~ ventingof
refrigerants in manycountries owa criminaloffence.
This is a proc.edure ften used n indusbial and commercial efrigeration ~tise where the entire
refrigerant charge s condensed nd collected either in die corKlensertself or more commooiy in a
liquid receiver co~ted to the condenser. Once the chargebas beenplrDped nto the condenser r
liquid receiver hen work may be carriedout on the systemwidiout losing argequantitiesof refrigerant
to atmosphere.For ecological~ following die guidelinesof die Montteal Protorol, the venting
of refrigerant s in many countriesnow a criminal offence.
In the RefrigerationCycle Demonsb'81ion nit R633 d1ecoOOe~ and iquid receiver are combined
in d1esameglass cylinder.
In order o carry out pumping down, dIe unit should have beenoperatingnormally for ~veral minutes
widt an evaporatorand condenser ooling water flow rate of approximately40 gS.I.
By setting me ball valves as shown in me Refrigerant
Pump Down mode (~ Fig1De 2
- Page2), me
flow of condensediquid from the
expansion alve
at the ~ of the conoonSel:s
~
and iquid
will thereforecontinue o colle(:t n me condenser hamber.
As liquid ttansfecs rom the evapcnror, the level will fall and ess of the evaporaur coil surf~ will
be effective n evaporaling he liquid. The evaporatioo ate will reduceand die processwill become
slower. This effect may be offset as the liquid level becomes ery low by opening ONLY) the baD
valve at the baseof the evaporaU>r.
This will have the effect of utilising die capillary surface area and ambient air temperawre to eVa(X)rate
additiona1liquid.
If, beforepumping down, the unit basbeenoperated or a prolmged period, die liquid collectedat d1e
baseof the evaporaUX' ay appear hicker and less viscoos. It may also appear slightly yellow in
colour. The liquid remaining n die eva X)rators primarily the oil d1athas been carried over in die
form of mist and refrigerant oil mixture from the com~.
The oil will not evaporateat die pessures .:hieved by d1ecanpressor and tOOreforet must be
physically rewmed to die compressor asing.
Note that the unit should ~ SHUT DOWN when the refrigerant charge is in the PUMP DOWN
condition as under certain ambient conditions it is possible for die charge to migrate to the compreS&:Jr
casing.
~:
In an industrial plant, isolating valves are usually fitted between all major components. As ~
as the refrigerant has been b'ansferred to the condenser (or liquid receiver) the valves may be
closed. trapping the liquid. The defective comlX>nentcan dIeD be serviced or repJ.lK:edwid¥>Ut
losing the refrigerant charge.
At me end of the demonsb'8tionhe opportunity may be taken o reblrn the oil collected n the baseof
me evaporator o die condenser.The procedure or this is given underOil Return on Page 17.
However, f oil is not to be returned o the compressor t this stage,~ mIl valves should be set for
normal operation (SeeFigwe 2, Page2) and me refrigerant allowed o rewrn to the evaporator.
8/9/2019 Refrigeration Cycle Demonstration Unit
35/76
31
4.
DEMONSTRATION OF CHARGING
Due to die restrictions of die Montreal Protocol t is not recommended 1at he refrigerant charge s
removed rom the machine or any ~n other than essential epair.
If charge emoval s necessary 1en echargingmay be "demonstrated"f convenient o 00 so.
Charging rom a Hilton suppliedone nip can should ollow the Chargingor Recharging X'OCeduren
Page21.
Note that any refrigerant emoved rom the machine shouldbe stored n a screw topped metal can to
prevent evaporationand to stop moistme being absorbedby the oil in solution.
Any refrigerantstored n sucha can may be drawn ~k into the evaporator y connecting he charging
line to the charging valve in a similar way to the standard hargingprocedurebut then mmersing he
open end in the liquid inside the container. If the unit is turned on for normal operation then the
pressuredrop in the evaporatorwill cause he refrigerant o flow into the evaporator. Note that air is
likely to need venting from the condenser.
8/9/2019 Refrigeration Cycle Demonstration Unit
36/76
32
s.
DEMONSTRA nON OF mE EFFECT OF AIR IN A REFRIGERA nON SYSTEM
When air is present n a refrig~oo plant. t will O(X'Inally e swept rom the evaporata by me flow
of refrigerant vapourand will become tapped n the con(k;D.W'.
For a combinationof reasons.he air will ~ the com~ delivery IX'CSSIJreo rise. reducing die
coefficient of peifonnance.arxl increasing he power input for a given duty.
The ilx:reaseof pressures due to
(i)
The total pressure in the coodensu is approximately equal to die sum of the refrigeJ'aDtsatumtion
pressure~ the pressure of die air Jl'CseDt Dalton's Law of partial pressures).
and
(ii) The air tends o be swept towards die heat transfer surfaces. onning an insuJating ayer which
reduces~ heat b'ansfer oefficient. This in Ulm drives up die temperature ifference equjred
for a given heat ransfer ate and this results n a higher refrigerant sabJratiooemperature nd
pressure.
The effect of air in the systemmay be demonsttated s follows:
Procedure:
(i) Start the unit for normal operation and adjust the evaJX)ratorcooling water flow rate so dlat the
evaporator pressure is below abnospheric pressure. Unless the cooling water temperablre is v«y
high this is likely to be the case in all conditions.
Ensure that the unit is free of air and if o«.essary follow the air vendng procedtDe shown 00 Page
18.
(ii) Run the lmit for ~veral minutes n order to reachnormal operating emperattD'es en record all
system emperatures, essures and flow rates. Also visually note the condensationate on
me
corKlenser ooling coils.
(ill) Connect he angl~ endof the charging ire (C45/2)supplied n the ~es kit to the charging
valve at the baseof the evaporator.
(iv) Observe ~ evapc:ntor pressuregauge and ~ open the ball valve at the base of me
evaporator. The evaporatorpressuregaugewill indicate an increase n JXessureollowed by a
return to its original value.
The condenser ressure auge,however,will increaseand remain at the new value.
(v) Re~ openingof d1eball valve until the condenser Xessureasapproximatelydoubled rom its
original val~. Note that f the condenser esswe ~~ 22OkNmo1hen me high presswecut
out will operateand the experimentwill have o be repeated ran an air free conditioo.
When air is admitted 10 he evaj)(X'a1Ort initially adds 10 the pressure within the evaporator ~cording
10 Daltoo's Law. However it is almost immediately swept dlrough into die comlX'eSSOf y the flow of
refrigezant v8lX>ur. The mixbD'e then passesdlrougb 10 he comJX'CSSOrm ultimately to die condenser
where it can go no further d~ to the liquid at die base of the condenser.
In addition. the conlinuous flow of refrigerant vapoW' owards the condenser cooling coil causes die air
to remain around the coil region. The reduced rate of cooOOnsation hould be observed as well as die
increase in condenser pressure.
Record aU system temperatures. pessures and flow rates.
Typical resultsare shown n the following table.
8/9/2019 Refrigeration Cycle Demonstration Unit
37/76
33
Local AtmosphericPressure: OlkN m-1
1 Air Free
1. With Air
est No.
-69
-66
vaporala GaugePressure
p ~ I kN mo2
p ~ I kN mo2
35'2
bsolute EvaporatorPressure
400
5.5
t,/OC
m.1 g S.l
~/OC
~/OC
Po1
N
m-2
Pol kN m-2
r./OC
IDa
1 g S.l
t./OC
Evaporating emperature
20.0
20.0
vaporatorwateJ' low
11.0
1.0
vapora1fX water inlet
9.5
10.0
vapora1(X'water outlet
59
21
ondenser Gauge Pressure
80
160
bsolute Condenser Pressure
30.5
5.5
CondensingTemperature
4.0
.0
ondenserwater flow
12.0
2.0
ondenserwater inlet
22.0
20.3
t,/OC
ondenserwater outlet
The results are plotted on a
temperabJre-pressuregraph on Page 34.
8/9/2019 Refrigeration Cycle Demonstration Unit
38/76
3
0 »
2
.
» : =
=
~
t
D
a
=
t
D
.
~ 2
.
t
D
~
0
~
~
~
C
8
D
.
C (
J
(
J
c
.
C
<
G
Q
C
c
3
(
Q
C
C
C
>
(
Q
(
c
~
.
C
~
A
'
<
C
-
0
Q
~
O
.
+
0
I
~
.
J
o
~
-
-
n
C
c
-
n
=
W
.
(
:
A
Q
-
~
C
0
m
2
8/9/2019 Refrigeration Cycle Demonstration Unit
39/76
35
6.
EFFECT OF EVAPORATING AND CONDENSING TEMPERA ON THE
REFRIGERA ON RATE AND CONDENSER EAT OUTPUT
The effect of evaporating emperatmeon die refrigeration rate can be investigated.but due to d1e
limited effect on evaporating emperature f all but very argechangesn cooling water low it is more
graphic to investigatecondensing emperature irst.
If time pennits. the corresponding ffects of evaporating emperaturemay then be investigated.
The effect of increasingme condensing emperature n many refrigeration systemsand heat pwnps s
a reduction n me heat discharged rom me condenser nd in many casesa smaller reduction n the
refrigerating effect at the evaporator.
Similar reductionswill be observed f the evaporating emperatures lowered
The effocts are due pimarily to the reduction in volwnetric efficiency of the compressorat high
pressure atios (P
JP
and the reduction n specific volume of the refrigerant gas as the evaporating
temperature educes.
An investigationof die effects of pressure atio are given in the following experiment
A simple explanation or this is that for eachsuction strokeof die compressor lower massof gas for
the samevolume) s drawn in to the cylinder to be compressed.
The effect of increasingcondenser ressuremay be investigated n the following manner.
Once air free increase he condenser ooling water flow to the flowmeter maximum (50 g S.l).
The pressureat which the condenser tabiliseswill dependupon the water inlet temperature.
(ii) Set die evaporator water flow to approximately 20-30 g S'l and allow the unit to run for
approx,irnately 5-20 minutes. The time taken to stabilisewill dependupon the local ambient
conditions and the cooling water nlet temperature.
(ill) Record all the systemparameters s illustrated n the table on Page 36.
(iv) Reduce the condenser cooling water flow rate until the condenser pressure ncreasesby
approximately5-10 kN mo1,Allow the unit to stabiliseand again ecord the parameters n Page
36.
(v) Repeat or increasing ondenser ressureso dIe minimum readable alue on dIe condenserwater
flowmeter is ~bed, or the condenser ressure eaches 00 kN roo"gaugepressure.
8/9/2019 Refrigeration Cycle Demonstration Unit
40/76
36
OBSERVA nONS
Local AtmosphericPresswe: OlkN m-2
Test No.
1
2
:t
4 5
Pel kN m-2
Pel kN m-2
t,/OC
Evaporaux'GaugePressure
-68 -69 -69 -69 -69
32 32
32
32bsoluteEvaporalOr Pressme
33
6.5
4.0
4.0
4.0
4.0
V8IXX8UX' Temperature
di./ gin S.l
it/OC
20
20
20
20
vaporaUX'Water Row Ra&e
20
11.0 IJ.,O 11.0
11.0
vapor8tcrWater InJet Temp.
11.0
10
It)
IG
10
vaporat(X'Water Outlet Temp.
ft/1IC
../IIC
P./ tN m-2-
P./ tN m-2-
t,/1IC
10
Condensed iquid Temp.
Condenser Gauge Pressure -41
.31
-21 -II 4
70 80 90 105
bsoluteCondenser Pressure
60
CompressorDischargeTemp.
- - - -
r./OC
m./ gin S*l
15.0
J9.5
24,0
27.0 31.0
ondenser Temperawre
Condenser W &tel' Flow Rate
50.0
10.0
4.0
2.0
1.0
11,0
11.0
ondenserWater Inlet Temp.
r./ac
11.0
11.0
11.0
26.5
31.5
ondenser Water Outlet Temp.
r,/1:C
12.0
16.5
22.0
W/Waus
ompressorPower nput
Note d1a1he temperatures ecorded have been estimated o the nearest0.5°C using die standard
thennometerSupplied. If the optional temperature indicator is fitted with the hermocouple ensors
then the temperaturesmay be recorded o the nearestO.l°C.
8/9/2019 Refrigeration Cycle Demonstration Unit
41/76
37
SPECIMEN CALCULA nONS FOR TFST NO.2
EVAPORATOR
Rate of Heat Transfer to Water in EvaJX)rator:
8/9/2019 Refrigeration Cycle Demonstration Unit
42/76
8/9/2019 Refrigeration Cycle Demonstration Unit
43/76
39
7. ~GA nON OF THE EFFECTOF COMPRESSORRESSURE Ano ON SYSTEM
PERFORMANCE
The effect of increasing he condensing emperatureor a constantgiven evaporating emperatures to
increase he compression atio PJP. that the compressors required o deliver.
Due to die effects of valves and die necessarypiston to cylinder bead clearancesdie volumetric
efficiency of reciprocatingcompresSOISends o fall with increasingpressure atio.
Volumetric efficiency
=Actual Volume Delivered
CompressorSwept Volume
In terms of a refrigeration system.
Volumebic efficiency
=
Mass low of refris:erant Soecific volume of refris:erantat inlet
CompressorSwept Volume
Hence f dte volurneb'icefficiency falls widt increasing ressure atio then he effect will be a reduction
in the effective mass low of refrigerant. The mass low of refrigerant hrough he compressor elates
directly to dte amount condensingon the condensa- oil and this in turn relates to the rate of heat
b'ansfer o dte cooling water.
In addition me above equation ndicatesme effect of reducing me specific volume of the refrigerant
entering me compressor y lowering me evaporating emperature.
The effect of pressure ratio on system performance may be investigated by the following method which
is identical to that used in Experiment 6 on Page 35.
Once air free increase the condenser cooling water flow to the flowmeter maximum (50 g S.l). The
pressure at which the condenser stabilises will depend ulX>n he water inlet temperature.
(ii) Set he evaporatorwater low to approximately30 g S.land allow the unit to run for approximately
15-20minutes. The time taken o stabilisewill dependupon he ocal ambientconditionsand he
cooling water inlet temperature.
(ill) Record all the systemparameters s llustrated n the table on Page40.
(iv) Reduce the condenser cooling water flow rate until the condenser pressure ncreasesby
aP{X"Oximately-10 kN mol. Allow the unit to stabiliseand again record he parameters n Page
40.
(v) Re~ for increasingcondenser ressuresD he minimum readable alue on the condenserwater
flowmeter s reached,or the condenser ressure eaches200 kN m-zgaugepressure.
8/9/2019 Refrigeration Cycle Demonstration Unit
44/76
40
OBSERVA nONS
Local Atmospheric Preaure: 101 kN m4
3
s
est No.
1 1.
4
-69
68 -69 -69
-69
vapoI31a'GaugePressID'e
33
32 32
32
32
bsolute Evaporator Pressure
4.0
Pel tN m-2
Pe tN m-2
t,/OC
Ih. I gin S.l
it/OC
6-"' 4.0
4.0
4.0
vaponI(X'Tem~
20
20
20 20
20
vapora1aWater Row Rate
11.0
vaporaf« Waf.« InJetTemp.
11.0 11.0
11,0
11.0
10 10
10
10
vaporalakWater Outlet Temp.
ta/-C
10
Condensed iquid Temp.
re/OC
p.1 tN m-2
p.1 tN m-2
r.,/OC
-41
-31
-21
-11
4
ondenser Gauge Pressure
70
8C
90
IOS
bsoluteCondensezsure
60
Cu.u~~ Discharge emp
24.0
27.0
31.0
ondenserTmnpelabJre
../OC
di./ lID Sol
15.0
19.5
2.0
1.0
ondenser Watel' Row Rate 50.0 10.0 4.0
11.0
./OC
11,0
11.0 11.0
11.0ondenserWater Inlet Temp
22.0
26.5
31.5
ondenserWater Outlet Temp
's/OC
12.0 16.5
CompressorPower Input
W I Watts
Note that the temperatures ecorded have been estimated o the nearestO.5°C using the standard
thermometers upplied. If the optional temperature indicator is fitted with the thermocouple ensors
then the tempe~ may be recorded o the nearestO.I°C.
8/9/2019 Refrigeration Cycle Demonstration Unit
45/76
41
SPECIMENCALCULAnONS FOR T~T NO.3
EVAPORATOR
Rate of Heat Transfer to Water in EvaJX)rator:
Q.
=
iii. C, (11
~
Q.
. 20.0
X
10-3 4.18
X 10'X
(11.0- 10.0)W
Q = I3..6W
. -
CONDENSER
Rate of Heat Transfer to Water in Condenser:
Qc
= "c C, (r, - tJ
Qc = 4.0
x 10-' x 4.18 x 10' x (12.0 - 11.0)W
Q =18.3..2W
-
COMP~_SDR
Note that dIe pressmemtio shouldbe derived using Absolute pres8W'e ot GaugePressures.
Delivered PressureRatio
=Pc/P.
32/80
= 2.5
-
DERIVED RESULTS
CompressorPressmeRatio
p./p.
Q./W
Q./W
1.82 2.19
2.5
2.81
3.28
83.6 83.6
83.6
3.6 83.6
eat Transfer n Evaporator
229.9 183.9
129.6 85.7
eat Transfer n Condenser 200
These esults are presented raphically on Page42.
In order to investigatevolwneuic efficiency it would be necessaryo measure he rotational speedof
the compress
8/9/2019 Refrigeration Cycle Demonstration Unit
46/76
8/9/2019 Refrigeration Cycle Demonstration Unit
47/76
43
8.
DE~ATlON OF OVERALL HEAT TRANSFER BETWEEN R141b AND WATER
IN mE EV APORA TOR AND CONDENSER
The Overall Heat TransferCoefficient (U) is die heat tansfer ate per unit areaof heat tansfer surface
when a temperature ifferenceof ooe degreeexists betweendie hot and cold fluids.
In die evaporator,die refrigerant emperatures sensiblyconstant,but die water temperaturealls as t
passes hrough the coils. In die condenser omedegreeof superheating be presentwhen the gas
enters he condenser lass chamber. However the quantity of heat delivered due to the superheating
will be small relative to that attributable o the condensingphasechange. Examination of the high
pressure ine of the cycle diagram generatedn ExperimentNo.9 on Page47 will confirm this.
In oroor to analyse he overall heatb'aIlSfer oefficient a representativeemperature ifferencemust be
determined hat representshe driving force for heat ransferbetween he refrigerant and the water.
The temperature ifference o be used n this case s the "Logarithmic Mean" which is given by
where9... = Temperawre
ifferencebetweendie two fluids at inlet,
and 9..-1ot Temperatureifference etween ie two fluids at outlet.
A dleoreticalanalysisof dle logarithmic mean emperatme ifferencemay be found in most ext books
on heat transfer and will not dlereforebe expanded n dlis manual.
Once air free increasedie condenser ooling water flow to a mid range value.
which the condenser tabiliseswill dependupon the water nlet temperature.
The pressure t
(ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately
15-20minutes. The time taken o stabilisewill depend pon he ocal ambient conditionsand he
cooling water inlet temperature.
(ill) Record allllie systemparameters s llustrated n the table on Page44.
8/9/2019 Refrigeration Cycle Demonstration Unit
48/76
44
OBSERVATIONS
Local AUDOspheric: lOlkN m.~
Test No.
1
2.
3
4
5
Evaporata GaugePressure
-68
Absolute EvaporatorPressure
33
Pel tN mea
p.1 kN mea
t,/OC
die I gin S.l
rs/OC
'a/OC
6.5
vaporata'Temperature
20
vaporaI« Waf« Flow Rate
11.0vaporata Water Inlet Temp.
EVaporaI« Water Outlet Temp. 10
Condensed iquid Temp.
"lac
p.1 tN m-2
p.1 tN m-2
CondenserGaugePressW'e
-41
AbsoluteCondenser
ro
Compreso Discharge Temp.
-
t,IOC
Condenser Tempelature
r-/OC
Ib./ gin 8"1
15.0
Condenser Water Flow Rate
so.o
CondenserWaf« Inlet Temp.
~/ac
11.0
CondenserWater Outlet Temp.
r,/OC
12.0
W I WatU
ompressor Power Input
Note that the tem~rabJres recorded have been estimated o me nearest0.5°C using me standard
mennometers upplied. If the optional temperature indicator is fitted with the themtocouple~nsors
then the temperaturesmay be recorded o the nearestO.I°C.
8/9/2019 Refrigeration Cycle Demonstration Unit
49/76
45
For the Evaoorator
RaICof Heat Transfer o Wata' in EvaJX)rator:
Q.
S
IN.
C, (t1- t,)
Q.
S
20.0x 10-' x 4.18x 10' x (11.0 10.0)W
Q :.83.6W
-
e~
- 11.0 6.5
e~ = 10.0 - 6.5 =
4.5 3.5
In~
3.5
8 .
-
~K
Q
U=A&:
u . ~~ '- , W.-2 g-l
3.6
u = ~ w..-2 '
For the Condenser
- -
Rare of Heat Transf~ to Water n Coode~
Q~ = *~ c, ("
-
tJ
Q~ - 50.0x 10-' x 4.18x 10' x (12.0 11.0)W
Q~ = . W
8~ . 15.0 12.0
8--
.
15.0 12.0 . 3.0K
4.0 - 3.0
ID~
3.0
8-
.
~K
8/9/2019 Refrigeration Cycle Demonstration Unit
50/76
46
Heat Transfer Rate
u=~
A8.
u .
u = ~ Wm-2K-l
8/9/2019 Refrigeration Cycle Demonstration Unit
51/76
47
9. GENERATION OF A REFRIGERATION CYCLE DIAGRAM ON A PRFSSURE-
ENTHALPY CHART
Note this procedure can ONLY be undertaken by the following detailed method with the optional
temperature indicator fitted to the R633 unit as the temperature of the refrigerant liquid in the
condenser s required for one state point on the cycle diagram. However the procedure may be
modified for use with the standard thermometer set. See Page 48.
The fitting JX'OCedUIeor the optional temperature ndicator kit, if not already fitted. is given in
Appendix A. Details of the kit are available rom P A. Hilton Ltd. or their local representative.
The vapour compression efrigeration cycle is of paramount mportance n tentls of food and drug
preservation,air conditioning, and heat pumps. In order to analyse he systemperformance n tentlS
of die diermodynamic ycle it is common or engineers o record systempressW'eSnd temperawres
and dien to plot the various statepoints on a pressure-enthalpyhart of the wm'king fluid.
The working fluid in me Hilton RefrigerationCycle DemonstrationUnit SeriesR633 is R141b. This
has me chemical name 1.1.-Dichloro-l-fluoroed1ane.
A pressure-enthalpyhart for this substances shown on Page55.
A detaileddescriptionof die variousparameters isplayedand obtainable rom pressure-endtalpyharts
will be found n most text books on thermodynamics nd thereforewill not be expandedupon n this
manual.
In order to plot a cycle diagram or the unit the following procedureshould be adopted.
Procedure:
(i) Start me unit fOf normal operation as shownon Page 15 and ensuredtat me unit is air free by
venting air from the condenser s describedunder air venting on Page 18.
Once air free increase he condenser ooling water flow to a mid range value. The pressureat
which the condenser tabiliseswill dependupon the water nlet temperature.
(ii) Set the evaporatorwater flow to a mid range value and allow the unit to run for approximately
15-20minutes. The time taken o stabilisewill dependupon the ocal ambientconditionsand the
cooling water inlet temperature.
(ill) Record all the systemparameters s llustrated n the table on Page49.
(iv) In order o demonsttatehat the cycle varies or different operatingconditions t is recommended
that die condenser ressures varied by adjusbnent f die condenser ooling water low rate. The
unit should be allowed to stabiliseand die systemparametersecorded.
The proceduremay also be repeated t different evaporating emperatures nd the resultsplotted
on a pressure-enthalpyhart as describedbelow.
The results rom die following table are shown plotted on PageSO.
The statepoints a. b and c on the diagram on Page50 are located n the following manner:-
Pointa is at the ntersectionf theevaporator
hamber pIeSSm-e . = 32 kN moz
absolute nd he
evaporatingemperature Is = 4.0OC.
i)
(ii) Point b is at the ntersectionof the compressor hamberpressurePG= 70 kN
m°2.absolute
and he
8/9/2019 Refrigeration Cycle Demonstration Unit
52/76
48
(ill) Point c is at the inte~tion of the compressor hambel' ressurePc= 70 kN m-1~lute and d1e
condensediquid tem~ r. = 19.5OC.
(iv) The expansion s assumedo be adiabaticand dtereforea ~ of constantenthalpymay be drawn
vertically oown from IK'int c to intersectwidt the evarxratnr presSUIeine Pc.
Considering he processes 1a1 re happening t eachSta1e oint in turn:-
(i)
At JX)inta die v8lX>urrtm die evaporBt« s drawn nto the compe.-,r and me pressures raised
from P. to Pc. It is evident rom die line of constantentropy ntersectingwith JX)inta (1.9 kJ kg-I
K-1) that die compession is not isentropic as die pressure ise is completed at an entropy of
aPJXQximately .92 kJ kg-l K-1. If required the isentropic efficiency of compressionmay be
evaluated.
(ii) The vapour eaving the com~ at point b is superheated s t is to the right of the saturated
vapour ine. The vapoorcools slightly in the pi~ to the condenser nd hen n the condenserk-
su~rl1eating and colxlensing ake p1a;:e t essentiallyconstantpressure.
(ill) At point c me liquid at die baseof me condenser s slightly sub cooled due to me effect of me
cooling water tempembirebeing below the saturation emperature f me conde~ chamber
pressure water tem~ 11.6 o 16.7OC.Sawration emperanue t Pc= 70 kN m-1= 21.7°C).
In addition ~me sub cooling in this unit arrangements addeddue to the expansionvalve being
physically attached o the condenser aseplate. The temperature rop causedby me expansion
conductsheat through me baseplate rom me condensediquid reducing he liquid temperature
furdler.
(iv) The JXessure rop causedby me expansionbrings me refrigerant nto the valX>ur 1iquid ixtm'e
region betweenme saturatediquid and satlD'8ted apour ines. The mixture of vapourand iquid
may be seen n the sight glassadj~t to the evaporator.
The liquid/vapom mixbJIemay be seen eturning o the evalJ(X'atOrhrough he fitting in the tOp
plate.
Note that mough me experimentmay only be carried out in the aOOve etail utilising the optional
temperaturendicator. statepoints a and b may be determired using the standard hermometerS.
The temperature f dIe conOOnsediquid may. however.be estimated rom dIe saturationpressuren
the condenserf it is assumed lere s no sub-
8/9/2019 Refrigeration Cycle Demonstration Unit
53/76
49
OBSERVAnONS
Local AttnospbericPressure: OlkN m-2
Test No.
1
2.
3
4 5
-69
vaporala GaugePressure
p. I kN m4
P. I kN m4
bsolute Evaporator Pressure
32
ts/OC
Ib.I gill S-l
it/OC
~/OC
../OC
Pc tN m-l
Pc tN m-l
4.0
va{X)ratCK emperature
20
vaporara Water Flow Rate
11.2
vapofata Water Inlet Temp
9.7
vaporata' Water Outlet Temp
Condensed iquid Temp.
19.5
-31
ondenser auge
70
bsolute Condenser Pressure
Compressor Discharge Temp.
t.,/OC
../OC
dlc / gin S.l
r,./OC
41.7
19.5
ondenser emperablre
10.0
ondenser Water Row Rate
11.6
ondenserWater Inlet Temp.
~/OC
W I Watts
16.7ondenser Water Outlet Temp.
CompressorPower Input
8/9/2019 Refrigeration Cycle Demonstration Unit
54/76
'
0
n
=
C
1
~=-.
-
6
;
O
~
_
~=.
-
6
'
<
_
~c~
~
.
-
0
VV
0
V0
J
0
0"
0
~
:
~
~
:
r~
P
:
~
-
J
0
-
;
.
~
w
.
N
~
-
~
V
~
-
.
~
-
~~
f
~
-
1
»
~
m
~
~ ~
m
~
"
9.
~
i
;
~
0 0
0
-
§
'
c
8
~
I
"
'
~
\
-
-
0
0
0
C
'
w
~
i
~
'
o
;
t
o
t
1
~
~
I
N
*
-
~
~
0
,
~
1
~
"v
f
"
\
r
.
~
\
I
~
'
.
~
~
~ 1
-
,
"
.
:
~
~
1
v
1
1
'
"
~
-
~
"
.
\
~
N
V
O
~
-
w
~
V
O
0
-
0
\
1
0
~0
"
"
"
0
u0
~0
\
o
0
-
l
o
8/9/2019 Refrigeration Cycle Demonstration Unit
55/76
51
10. MEASUREMENT OF mE EFFECT OF CONDENSING TEMPERATURE ON
COMPRFSSOR POWER INPUT
Note his procedure an~ be undertakenby the followingmethodwith the ootionaldi2ital
wattmeter itted to the R633unit.
The fitting procedure or the optional wattmeter kit. if not already itted, is given in Appendix B.
Details of the kit are available rom P.A. Hilton Ltd. or meir local re~tative.
The vapourcompression efrigerationcycle s utilised n both refrigerationand heatpump awlications.
In a refrigeration situation he eff~t of high ambient emperaturewill be to both ~rease the loan on
the refrigeration system (due to heat eakage ntq the cold space hrough thennal insulation) and to
increase he condensing emperaturen order to reject heat rom the system.
In a heat pump application he useful heat rom the condenserwill be more easily utilised for heating
applications f rejected at a high temperature.
In bodl cases,ncreasing ie condensing
X'Cssure
esul~ in a greaterwork requirementor die
compresscx. In addition, die increased compression ratio will in most cases result in a reduction of
system efficiency due to a reduction in volumetric efficiency. This is due to die necessary clearance
required for compressor valve opening and machining tolerances. At die end of a compression stroke
this clearance value is COOStantut at high pressure will contain a higher mass of unb'ansferred gas dIaD
at low pressure.
In addition, due o commercial actors, he motors used n mostdomestic efrigerationcompressors ill
be of a relatively low elec1rlcal fficiency. Henceelec1rlcal esistance eatingeffects n the windings
will be relatively high under all operatingconditions.
Procedure:
(i) Start the unit as for normal operation as shown on Page 15 and ensure hat the unit is air free
by venting air from me condenser s describedunder air venting on Page 18.
Once air free increase he condenser ooling water flow to maximum (50 g/s). The pressureat
which the condenser tabiliseswill dependupon the water nlet temperatm'e.
(ii) Set the evaporatorwater flow to a mid range value and allow me unit to run for awroximately
15-20minutes. The time taken o stabilisewill dependupon he local ambientconditionsand me
cooling water inlet temperature.
(ill) Record dJecompressor ower nput shown OIl he digital wattmeterand the condensing ressure
Pcas illustrated n dJe able on Page52.
(For referencet is recommendedhat students arefully touch he compressor asing o experience
the heat loss from die compressordue to electrical heating effects. This represents lectrical
energy wasted by the system. Care should be exerc~ed as the comoressor casioa will be
QI.)
(iv) Adjust the condenser ooling water low to a lower value and againallow the system o stabilise.
Re~ d1eabove observations.
(v) The proceduremay be repeatedup to the maximum condensing ressure f local cooling water
conditions permit
8/9/2019 Refrigeration Cycle Demonstration Unit
56/76
S2
OBSERVAnONS
kNmo2
ocal AtmosphericPressure:
5est No.
1
1
3
4
E
aporala
Gauge re~
Absolute Evaporator Pressure
Evaporata T~penIuIC
Pel tN mol
Pel tN mol
"/OC
Ih. I lID 8-1
ts/OC
E Vaporatm' Watrl' Row Rate
-
Evaporara Wat« In1etTemp.
EvaporaIO'Waf« Outlet Temp.
~/OC
Condensed iquid Temp.
"/OC
p./tN m4
p./tN m4
",/OC
CondenserGaugePreaure
15
190
Absolute Condenser Pressure
Compressor Discharge Temp.
- -
,,/oc
Ib./ gin S'1
~/OC
Condenser T emperahlre
Condenser Water Flow Rate
Condenser Water Inlet Temp.
CondenserWater Outlet Temp
r,/OC
Compressor Power Input
W I Watts
274
302
Note that the val~ observedwill dependupon the local conditions, he p-essures et and the local
supply voltage and frequerx:y.
As indicated above, he power required o drive the com~ increases s ~ condensing ressme
is increased.
8/9/2019 Refrigeration Cycle Demonstration Unit
57/76
S3
OBSERVAnONS
kNm-7.
ocal Atmospheric~:
5
2 3
4
est No.
Evaporata' GaugePressure
Absolute EvaporatorPressme
Pel kN m-2
p.1 kN m-2
.,/OC
m. I gin S-1
"/OC
t,/OC
r./OC
p~ kN m-2
p~ kN m-2
t.,/OC
~/OC
Ib.I gin S.1
r./OC
t,/OC
Evaporat(X'Temperature
Evapotat(X'Water Flow Rate
EvaporatorWater Inlet Temp.
EvaporatorWater Outlet Temp
Condensed iquid Temp-
Condenser Gauge Pressure
Absolute Condenser Pressure
Compres~ DischargeTemp.
Condenseremperawre
CondenserWater Flow Rate
CondenserWater Inlet Temp
CondenserWater Outlet Temp
CompressorPower Input
W / Watts
8/9/2019 Refrigeration Cycle Demonstration Unit
58/76
n
~
.
~
.
=
3
t
D
a
~
~
~
~
.0 m
t
n
0
~
(
a
0
~
-
m
m
n
1
T
n
+
t
1
L
+
r
8/9/2019 Refrigeration Cycle Demonstration Unit
59/76
~
0
0
n
'
o
0
0
0
1
'
1
0
n
-
0
<
>
I
N 0 0~
0
0
\
O
~
~
0
.
-
~
~
0N
\
8
3
1
~
d
X
'
S
J
~
i
~
I
~
~
.
a
"
I
-
0
~
O
q
M
~
\
.
-
v
3
R
o
Q
U
S
3
N
-
~
-
0
0
0
0
~
0
-
0
)
-~
o
V
-
~
c
".
c
-
O0~
.
".
c
-
0
V
~
~
0
1
0
V
0
-
g
0N
8/9/2019 Refrigeration Cycle Demonstration Unit
60/76
S6
SPECIFIC RISKS
.
Contact with liquid will causesevere rost bite
.
Decomposesn a fire to give toxic and corrosive fumes
.
Containen may bunt if overheated
.
Risk of asphyxiation at high concentration
IDENI1F1Ct770N
SYDOBymS
1.
LI
l,l,-Dichloru-l-O=roethaDe. R-141
Uses
Plastic fOim blowing aaalt,SOlveDt
.1
1717-00-6
404-080-1
CAS
EINCS
OMPOSmON (.rubstanCeJ r impurities giving a hazard)
Substance 1 I ,-dichloro-l-Qooroethane
Impurida DOne
2.
PHYSIC4LPROPERTIES
At 2G-C liquid
3.
colo1U': colourless
0d01U': slightly etherial
3.1
PbysicalSUte
Health & Safety
Data Sheet
elting point: -lO3.S-C boiliDl point: 32.0-C
critical taDper8ture: 20S.C
~tiOD ~.1Ure: SOO-C
3.2
Tempentura
pH
DCutr81
.J
Solubility
.4
in ~ at 20.C: 0.54% y weight
in solvCDts: misciblewith aliphatic ydrocarbons.
aromatlcs,ketoaes.chkwiDated
derivatives 1¥i
If this material s redistributedo
sale,detailsof its hazards nd
recommendedmethods f safe
handlingshouldbe passed n to
users.
at SO.C:
.83 Ir
t 2Q8C: 0.81 bar
.5
Vapour pressure
1.24 ,cm)
5.011Ifm)
(liquid) at 2S.C:
(vlpOur) at 32.C:
3.6
Deasity
3.7
Other data
criticalpressure: 43.4bar
4.
4.1
STORAGE AND HANDLING
Spedal torace Dd Store etWeeI1- andSO-Cn a well v~rilated~
baDdUacrecaadoDS ~t storedn.sp«ial1y einforcednDDS.
PacklDgmaterials
.%
A void alloys with 2% or more of magnesium r
aluminium.Avoid plastics. Usesteelor polyethyleue
dr1Dns.
Stableat ambient emperabl1'e,ut willlDfcrlo thermal
decomposition t elevated emper8tureso give off
hydrochloricand hydrofllWric acidsaDdpossiblypbol8~
4.3
DecompolltioD prvducu
HRP Refrigerants Ltd.
Gellibirion Industrial Estate
Pontypridd
Mid Glamorgan
CF37 5SX
DaQcroas reacdODS
Withnaked ameor hot metal~
.4
4.5
lDdJvtduaJ meDdoD
and pAtecd"e measures
Gloya loula r=ommeadedvoidiquid
oDtKt
with kiD eyesDdheDh8Iati~f~.
In case of emergency elephone
Va1ri1arche workiD&area. No aom,. No aaked
nama.
4.6
Sped" protecdve
mcuara
01443 842255
If in m ~loscd -rea. YCDn18le or WaI' tt:1 oCOaIaiDCd
bratbiDI
~ (risk or -.hyxi8lioa/llK)xia).Allow
to eT8pOrIIc r pump nto salecoatIiIICr. Prevalt. rom
mtailla ~ bucmCUIS tc.
4.7
Meuara after IpWqe
0 Ieak8Ie
8/9/2019 Refrigeration Cycle Demonstration Unit
61/76
57
SPECIFIC RISKS
. Contact with liquid will causesevere rost bite
.
Decomposesn a fire to give toxic and corrosive fumes
. Containers may burst if overheated
. Risk of asphyxiation at high concentration
...8
Ret\un to supplia-.
estnacttoD of
coDtamiDated coDwDer
Store at a tanperaturebelow SO-C n a y~latM area,
away from all ~~ of heat or ignition.
Other recommeDdatioDS
.9
CAS
EINCS
1717-00
404-080
IGN1110N AND EXPLOSION
F1ashoiDt none
5.
5.1
5.1
Auto-ignition temperature none
Non-flammableproduct Thermal decomposition ives off
toxic fumesoChydrochloricand hydrofluoric acids and
phosgene.
Special ire or explosioD
hazards
S.J
Health & Safet
Data Sheet
ot applicable
.4
Extinction
Wear self-contained reathingapparatus nd ull acid
resistantprotectiveclothing.
5.5
Particularmeasura
during OR-fighting
Protect. ontainers rom heat~urces. Cool with water to
avoid ov« pressurisation.EDsure roductdoesnot come
into contactwith naked lamesor hot metal surfaces.
5.,
Other recommendations
If this material s redistribute
sale,detailsof its hazards nd
recommendedmethodsof saf
handlingshouldbe passed n
users.
6.
TOXlCOLOGICtL NFORMATION
Employersshouldbe aware hat this product s ~lvent
abusable.
Vapour
2,500 ppm for 30-60minuteswin cause ertigo,
drowsiness nd respiratoryproblems. May cause ncreased
sensitivity of myocardiumabove 12,500 pm.
Uquid
Repeated nd proloaaedskin contactwill produce
dermatosis. Eye contactwill lead to irritation. redness nd
moderate onjunctivitus.
7.
HRP Refrigerants Ltd.
Gellihirion Industrial Estat
Pontypridd
Mid Glamorgan
CF37 5SX
FIRST AID PROCEDURES
Skin contact Washwith copious molmts fwater'.
Inhalation Removeo fresh ir. ApplyoxygenCbreathings
difficult. Consult doctor.
EyeCODtact Wash DQ .~a~elyith copious molmts f water.
Consult an opbtbalmologist.
8.
In caseof emergencyelepho
SPECIAL PRECt U110NS FOR WASTEDISPOSAL
This matcria1s subj«t to the resttictioasof the
EnvironmentalProt=tiol1 Act and shouldoot be Va1ted o
atmosphere.W.. materialcan be ~ to HRPR.
Movancnt of refri&~ for ~1amation or destIuctioD s
subj~t to the Duty of Care lK requiIeIlppropt.ate
01443 842255
8/9/2019 Refrigeration Cycle Demonstration Unit
62/76
8/9/2019 Refrigeration Cycle Demonstration Unit
63/76
S9
1 2
'3
4
Amendments
2 MAINS FILTER ADDED
10.9.97 JB
A
NEW 3 CORE POWER CABLE
FROM TRANSFORMERSECONDARY
2'OV
TO MA~S FILTER
LENGTH 1000 mm
) LINE t
-0
)1
r---
j
.
1 I
.
1
I i: I
1
1
@}
~:
.
~I
...1
-
8/9/2019 Refrigeration Cycle Demonstration Unit
64/76
8/9/2019 Refrigeration Cycle Demonstration Unit
65/76
61
APPENDIX A
OP'nONAL DIGITAL TEMPERATURE INDICATOR
R633A
If£I-I"iNG INSTRUcnONS
8/9/2019 Refrigeration Cycle Demonstration Unit
66/76
62
--
--
VjQllK
mQJCatorl in the centre of the Wlit.
The addition of the digilal temJ'eraLure ndicator not only increases die resolutioo of tem})el3ture
measuremenm rom to.soC to O.IOC but a thennocouple sensor is provided to record the temlJeJ'a1Ures
of the iquid in the baseof the condenser
hamber re.
The addi iOnal teJnj el tures al w a compl te vap our comP ssi n cy l di gram to be nrn.i .~_ .. - 1
refrierant R41b PCssure-enthaIpy digram.
Once he level has been measured r marked,position the ball valves or shutdown (SeeFigure 2
-
R633 Valve Positions)and hJm he unit off. Turn off and disconnect he unit from the water supply.
Isolate the unit from its electrical supply and then remove
he bolts and one nut securing the rear
panel.
Store he bolts, nut and washersn a containeras thesewill be required or refitting the panel.
Remove he hermometersrom their pocketsand store hesesafely. Note hat f the original installation
recommendations ere ollowed dlere will be someoil in ~h of die dlennometer ockets.
With the help of an assistantay the machineon its back and ocate he 3mm (1/8") diameterblanking
rod in a pipe fitting in the 00seof the condenser hamber. This is the ocation or the
1s thennocouple.
8/9/2019 Refrigeration Cycle Demonstration Unit
67/76
63
Ensure mat the liquid level is below the level of the blanking rod and that the condenser ressure s
either at or below atmospheric pressure.
Using a close itting spanner emove he nut securingdIe blanking rod.
Take the 0 3mm x 8Smm long diennocouple ( MIS/IO) and using a 0 3mm compressionolive
(PF4/67) and die original nut. insert the diennocouple n die chamber o a depdi JUST BELOW that
of the measurediquid level.
Rewm me unit to an upright position. Thosewim accesso a vacuumpump may eXb'act ny air from
the systemby connecting o me internal pipe leading from me vent valve on top of the condenser
chamber.
Note that the oil in the unit is hygroscopic absorbswater vapour rom the air) and the unit shouldDOt
be left open o atmosphereor long periods.
Fit the 7 shon rod type thermocouplesIMlS/l6) in placeof the original thermometers.For the present
time the thermocouple onnecting eadscan be left ttailing at the front of the panel.
Remove die 92mm x 92mm blank insttument case from the panel by releasing die retaining screws from
inside die machine panel and withdrawing die case from die front of the unit.
The digital temperatw'endicator and multi way selecta-switch are two separatetems. A separate
core bennocoupleable s suppliedo makeme ink betweenmemo
FirSt nstall the 10 way selector ]MIS/50) at the bottom of the 92mm x 92mm panel orifice. This is
retained y wire springs ndclips whichpress gainsthe ascia. Refer o FigureA on Page 5.
The indicator ( MIS/53) is fitted above he multi way selectorand retainedby jacking screwswhich
bear on me rear of the panel fascia. Refer to Figure B on Page65.
Make the 2 core thermocouple onnection n accordancewith the wiring diagram on Page71
The Brown or Green (+) wire runs from COMM I to indicator terminal 25 "VI".
The Blue or White (-) wire runs from the terminal on die right of COMM 1 to indicator ternrinal26
"COM",
Apply the label "Oc" to the fa:e of the indicator to the right of the digital display.
Apply the yellow label "TemperattJrendicator" to the panel fascia.
Electrical Installation
The 3 core IX>wer upply lead for die optional ternperattJrendicator and separate ptional wawneter
is factory fitted to the following tenninalson the DIN rail connectors n the right handside of die unit
adjacent o the input IX>weread. Their free endsare dentified ~ follows:
49 (Eard1
-ColourGreen Yellow suipe) FromDIN Rail 5
47 (Line -Colour Red) From DIN Rail 8
48 (NeuU'al
-
Colour Black) From DIN Rail 13
~ units already itted widt a wattmeter (R633B) will use the ~k. of loose JinkssuWlied to tap
into the wattmeter K>wer upply. Refer to the wiring diagramon Page71.
Units not fitted wim me wattmeterwill useme free wires abelled 7 (Line
-
Cololn' Red) and 48
(Neub'al
-
Colour Black) directly.
8/9/2019 Refrigeration Cycle Demonstration Unit
68/76
64
The free end of d1e ead will havebeenprotectedwith tenninal covers. Theseshooldbe removedand
the 3 wires given 1 turn throughme ferrite ring suppliedand ~1Ued ooar o the ndicator. The red and
b1a;k cablesshooldbe connected o the following terDlinalson the digital temperatW'endicator. Note
that as ~ digital temper8bJrendicator s double nsulated. he green/yellowearth wire is not used n
this application.
18 L Line renninal securesRed wire 47
17 N N euttal terminal securesB1a:k wire 48
The themtocouple eadsmay now be ~red to the thennocoupleenninalson the multi way switch
oox. Note fran the wiring diagram on Page71 that ~h of the 10 switcOOdhannelcoonectioos n
the rear of the oox has4 terminals. However. n eachcaseonly the eft baOO air of eachgroup of four
areutilised.
Note that due o a new EuropeanStandard, ome ype K d1ennocoupie ~ will utilise brown andblue
insulation and od1ers reenand white to identify the polarity.
For ~b tbennocouple he brown or green~itive lead s connectedo the tenninal marked 1 in ~b
group of four. The blue or white negative ead connects o me next terminal on the RIGIrr of me
tenninal maIked 1 n eocbgroup of four. The remaining ennina1sn eachgroup of four are not used.
Note that only channels to 8 (CHI, CH2, aD...CH8) are utilised. The remainingchannels,9 and
0, are not utilised for dlis option kiL
Start with ~ merm
8/9/2019 Refrigeration Cycle Demonstration Unit
69/76
6S
FIGURE A
PA~L
~
USE A SUITABLE FLAT
SCREWDRIVERTO PUSH AND
ROTATE THE ClP ONTO THE
TWO BRASS STUDS ON THE
SlOE OF THE SWITCH CASE.
THE OPPOSITE SVE
FITTED IN THE SAME
MANNER BUT INVERTED
8/9/2019 Refrigeration Cycle Demonstration Unit
70/76
66
This page is intentionally blank
8/9/2019 Refrigeration Cycle Demonstration Unit
71/76
67
APPENDIX B