Ref: Thyristors SRF .ppt ( 09/06/22) EUROTHERM CONTROLS Why Thyristor Power Control Units Rather Why Thyristor Power Control Units Rather Than Contactors? Than Contactors? Better Temperature Control - Deliver short bursts to match power demand Eliminates Temperature Fluctuations - Sense changes in supply and adjust power delivery to prevent power fluctuations Increased Production - built in diagnostics and partial load failure detection allow preventative maintenance before total failure and costly shut downs of process Lower Maintenance Costs - no moving parts and plug in design increases heating element Lifetime - reduced thermo- mechanical stress Process Protection - Current and Power limits protects process and heating elements Lower Energy Costs - Allows plant wide energy monitoring which reduces peak demand
21
Embed
Ref: Thyristors SRF.ppt (11/06/2014) EUROTHERM CONTROLS a bc Why Thyristor Power Control Units Rather Than Contactors? l Better Temperature Control - Deliver.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
Why Thyristor Power Control Units Rather Than Why Thyristor Power Control Units Rather Than Contactors?Contactors?
Better Temperature Control - Deliver short bursts to match power demand
Eliminates Temperature Fluctuations - Sense changes in supply and adjust power delivery to prevent power fluctuations
Increased Production - built in diagnostics and partial load failure detection allow preventative maintenance before total failure and costly shut downs of process
Lower Maintenance Costs - no moving parts and plug in design increases heating element Lifetime - reduced thermo-mechanical stress
Process Protection - Current and Power limits protects process and heating elements
Lower Energy Costs - Allows plant wide energy monitoring which reduces peak demand
Ref: P .ppt (10/04/23) 2EUROTHERM CONTROLS
Thyristor Power ControlThyristor Power Control
Will only conduct one way
FiringCircuit
Parallel Pairs
Anode CathodeGate
Thyristor Device
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
ProtectionProtectionSnubber - Resistor/ Capacitor for elimination of spikes and false
triggering particularly on transformer loads.
Fuse
MOV
Snubber
FiringCircuit
Isolation
Eurotherm Thyristor
Unit
ControlCircuit
MOV - Metal Oxide Varistor - Resistance changes on voltage, as voltage rises mainly on spikes it will absorb the excess voltage
Fuse - Protecting against over current draw, will blow faster than the thyristor operates.
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
Firing ModesFiring Modes
Logic Burst / Whole Cycle Single Cycle Phase Angle
For lesser disturbance on mains you may increase the cycle time
Typical 1 cycle to 256 cycles approx 5 secsLong cycle time can be few mins
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
Single Cycle Firing - Analog I/PSingle Cycle Firing - Analog I/P Cycle Time is 2 cycles at 50%
50% Power
33% Power
T
T CYCLE
CYCLE
•Silicon carbide•When element new the resistance is low and full voltage must only be applied for short bursts. •As the elements heat up and or age the voltage can be sustained for longer periods. •To prevent problems on new elements a power limiting must be used otherwise the element can shatter
Ref: P .ppt (10/04/23) 8EUROTHERM CONTROLS
TE 200, TC2000 & TC2001TE 200, TC2000 & TC2001
3 Wire Star 3 Wire Delta
TC2000, TE200
or TC2001
TC2000, TE200
or TC2001
Less Expensive than three leg control but when the unit is off the non-controlled leg is at line potential
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
Phase Angle - Analog I/PPhase Angle - Analog I/P
Firing equally delayed for each 1/2 cycle
Shown as 50%
Not widely used in Europe as there are problems with CE requirements.
On
Ref: Thyristors SRF .ppt (10/04/23)
EUROTHERM CONTROLS
Load TypesLoad Types
Fixed Resistance - Any firing mode Variable Resistance - Current limit or
single cycle Transformer Coupled - Phase angle or
burst firing with delayed start. This reduces surge currents. Will switch on at zero crossing point of current.