Top Banner
B0700AX REV H I/A Series ® System The MESH Control Network System Planning and Sizing November 30, 2008
60
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Rede Mesh

B0700AXREV H

I/A Series® SystemThe MESH Control Network System Planning and Sizing

November 30, 2008

Page 2: Rede Mesh
Invensys, Foxboro, FoxCAE, FoxPanels, FoxView, and I/A Series are trademarks of Invensys plc, its subsidiaries, and affiliates.All other brand names may be trademarks of their respective owners.

Copyright 2004-2008 Invensys Systems, Inc.All rights reserved

SOFTWARE LICENSE AND COPYRIGHT INFORMATION

Before using the Invensys Systems, Inc. supplied software supported by this documentation, you should read and understand the following information concerning copyrighted software.

1. The license provisions in the software license for your system govern your obligations and usage rights to the software described in this documentation. If any portion of those license provisions is violated, Invensys Systems, Inc. will no longer provide you with support services and assumes no further responsibilities for your system or its operation.

2. All software issued by Invensys Systems, Inc. and copies of the software that you are specifically permitted to make, are protected in accordance with Federal copyright laws. It is illegal to make copies of any software media provided to you by Invensys Systems, Inc. for any purpose other than those purposes mentioned in the software license.

Page 3: Rede Mesh
Contents

Figures..................................................................................................................................... v

Tables.................................................................................................................................... vii

Preface.................................................................................................................................... ix

Purpose .................................................................................................................................... ix

Who This Document Is For ..................................................................................................... ix

What You Should Know .......................................................................................................... ix

Revision Information ............................................................................................................... ix

Reference Documents .............................................................................................................. ix

Glossary ................................................................................................................................... xi

1. Overview ........................................................................................................................... 1

Introduction .............................................................................................................................. 1

Accessing Spreadsheets .............................................................................................................. 3Accessing Spreadsheets from the Electronic Documentation CD-ROM ............................... 3

2. System Planning................................................................................................................ 5

Workstations ............................................................................................................................. 5Virus Scanning ..................................................................................................................... 6

Virus Scan Software on Windows Platforms .................................................................... 6Virus Scan Software on Solaris Platforms ......................................................................... 6

SMONS ............................................................................................................................... 6OS Configurable Parameters ................................................................................................ 6FoxView ............................................................................................................................... 9Alarming ............................................................................................................................ 10Historians ........................................................................................................................... 11Printers ............................................................................................................................... 13Application Object Services ................................................................................................ 13Applications ....................................................................................................................... 13

Control ................................................................................................................................... 14Alarming ............................................................................................................................ 15Control Distribution .......................................................................................................... 15Peer-to-Peer Relationships .................................................................................................. 15OM Scan Load ................................................................................................................... 16

FoxAPI Application Examples ....................................................................................... 16Peer-To-Peer Examples .................................................................................................. 17FoxView Application Examples ..................................................................................... 18

Control Processor Load Analysis ........................................................................................ 19

iii

Page 4: Rede Mesh

B0700AX – Rev H Contents

Block Processing Cycle ....................................................................................................... 19Running with 100 ms and 50 ms Block Processing Cycle (BPC) ................................... 19Phasing .......................................................................................................................... 19

I/O Points ............................................................................................................................... 20

Network .................................................................................................................................. 20

System Planning Summary Tables .......................................................................................... 22

Data Access to I/A Objects ...................................................................................................... 23

3. System Sizing .................................................................................................................. 25

Workstations ........................................................................................................................... 25Workstation Summary Worksheet ..................................................................................... 26

Control Processors .................................................................................................................. 30Maximum Loading Table ................................................................................................... 30

Inter-Network Traffic ............................................................................................................. 32Example – Gradual Migration ............................................................................................ 33

LI Traffic Rates ....................................................................................................................... 37

Index .................................................................................................................................... 39

iv

Page 5: Rede Mesh
Figures

3-1. Original Nodebus Traffic Rates ................................................................................... 343-2. Adding an ATS in Extender Mode .............................................................................. 353-3. Migrate Nodebus 1 ..................................................................................................... 353-4. Migrate Nodebus 4 and Nodebus 5 ............................................................................ 363-5. Final Migration ........................................................................................................... 36

v

Page 6: Rede Mesh

B0700AX – Rev H Figures

vi

Page 7: Rede Mesh

vii

Tables

2-1. OM Scan Load: FoxAPI Application Examples ........................................................... 162-2. OM Scan Load: Peer-To-Peer Examples ..................................................................... 172-3. OM Scan Load: FoxView Application Examples ......................................................... 182-4. Windows Workstation System Planning Summary ..................................................... 222-5. Solaris Workstation System Planning Summary .......................................................... 222-6. Data Access to CIO Objects on CP270 ....................................................................... 233-1. Windows Workstation Specification ........................................................................... 253-2. Solaris Workstation Specification ................................................................................ 253-3. Workstation Summary Worksheet .............................................................................. 263-4. Alarm Manager Worksheet ......................................................................................... 273-5. Default AST Table for Number Alarm Managers on a Windows-Based Workstation

(Local and Remote) ..................................................................................................... 283-6. Default AST Table for Number Alarm Managers on a Solaris-Based Workstation

(Local and Remote) ..................................................................................................... 283-7. FoxView Worksheet .................................................................................................... 293-8. AIM*Historian Worksheet .......................................................................................... 293-9. Loading Summary (% of BPC) ................................................................................... 313-10. Station Free Memory (Bytes) ...................................................................................... 313-11. Peer-to-Peer Data ........................................................................................................ 313-12. Resource Table ............................................................................................................ 32

Page 8: Rede Mesh

B0700AX – Rev H Tables

viii

Page 9: Rede Mesh
Preface

PurposeThe purpose of this document is to provide system planning and sizing guidelines for I/A Series Mesh control network systems for both I/A Series Windows V8.4.1 or later and I/A Series Solaris V8.3 or later platforms residing on The Mesh control network. Additional performance and siz-ing guidelines for the Windows Server 2003 platform can be found in the following documents:

♦ Model P91 System Administration Guide (Windows Server 2003, Standard Edition with Service Pack 1) (B0700BX)

♦ Model P91 Workstation Server for Windows Server 2003 (PSS 21H-4U6 B4)

♦ Workstation Server for Windows 2003 Software Overview Microsoft Windows Server 2003 Operating System (PSS 21S-1B10 B3).

Who This Document Is ForThis document is intended to be used by engineering, applications, plant management, and other qualified and authorized personnel involved in the planning and sizing of their I/A Series Mesh control network system. It is also suitable for Invensys personnel.

What You Should KnowPrior to using this document, you should be familiar with I/A Series process control principles and strategies. Detailed information relating to the various I/A Series software and hardware ele-ments is found in the reference documents listed below.

You should also be familiar with Microsoft® Excel™ operating principles and procedures prior to using spreadsheets.

Revision InformationFor this revision of the document (B0700AX-H), the following changes were made:

♦ Updated document for V8.4.2 control station performance for OM Scan Load %.

Reference DocumentsThe following documents provide additional and related information.

♦ Address Translation Station User’s Guide (B0700BP)

♦ Application Object Services User’s Guide (B0400BZ)

♦ Alarm and Display Manager Configurator (ADMC) (B0700AM)

♦ Control Processor 270 (CP270) Integrated Control Software Concepts (B0700AG)

♦ Control Processor 270 (CP270) On-Line Image Update (B0700BY)

ix

Page 10: Rede Mesh

B0700AX – Rev H Preface

♦ DIN Rail Mounted FBM Subsystem User's Guide (B0400FA)

♦ Enclosures and Mounting Structures Site Planning and Installation User's Guide (B0700AS)

♦ Field Control Processor 270 (FCP270) Sizing Guidelines and Excel Workbook (B0700AV)

♦ Field Control Processor 270 (FCP270) User’s Guide (B0700AR)

♦ Field Device System Integrator (FBM230/231/232/233) User’s Guide (B0700AH)

♦ FOUNDATION™ fieldbus User’s Guide for the Redundant FBM228 Interface (B0700BA)

♦ FoxAPI User’s Guide (B0193UD)

♦ FoxPanels Configurator (B0700BB)

♦ FoxView™ Software (B0700BD)

♦ Hardware and Software Specific Instructions for Model P92*F Workstation (PW380) (B0700CB)

♦ Hardware Installation Procedures for Model P79 Workstation (Solaris 8 and 10 Operat-ing Systems) (B0400SR)

♦ Hardware Installation Procedures for Model P80 Workstation (Solaris 8 and 10 Operat-ing Systems) (B0400SS)

♦ Hardware Installation Procedures for Model P81 Workstation (Solaris 8 and 10 Operat-ing Systems) (B0400SU)

♦ Hardware Installation Procedures for Model P82*B Workstation (Solaris 10 Operating System) (B0700CS)

♦ I/A Series Information Suite AIM*Historian User’s Guide (B0193YL)

♦ Implementing FOUNDATION Fieldbus on the I/A Series System (B0700BA)

♦ Integrated Control Block Descriptions (B0193AX)

♦ Integrated Control Configurator (B0193AV)

♦ Model P91 System Administration Guide (Windows Server 2003, Standard Edition with Service Pack 1) (B0700BX)

♦ Model P91 Workstation Server for Windows Server 2003 (PSS 21H-4U6 B4)

♦ Object Manager Calls (B0193BC)

♦ Power, Earthing (Grounding, EMC and CE Compliance (B0700AU)

♦ Process Operations and Displays (B0700BN)

♦ Software Utilities (B0193JB)

♦ System Administration Guide (Solaris 10 Operating System) (B0700CT)

♦ System Administration Guide (Windows® XP Operating System) (B0400HE)

♦ System Definition V2.9 Release Notes (B0193XW)

♦ System Management Displays (B0193JC)

♦ Transient Data Recorder and Analyzer User’s Guide (B0700AL)

♦ The MESH Control Network Architecture Guide (B0700AZ)

♦ Ultra 25 Model P82*B Workstation (Solaris 10 Operating System) (PSS 21H-4U8 B4)

x

Page 11: Rede Mesh

Preface B0700AX – Rev H

♦ V8.4.2 Release Notes and Installation Procedures for the Windows Operating System (B0700RW)

♦ V8.x System Error Messages (B0700AF)

♦ Workstation Alarm Management (B0700AT)

♦ Workstation Components (PSS 21H-4D1 B3)

♦ Workstation Server for Windows 2003 Software Overview Microsoft Windows Server 2003 Operating System (PSS 21S-1B10 B3)

♦ Z-Module Control Processor 270 (ZCP270) User’s Guide (B0700AN)

♦ Z-Module Control Processor 270 (ZCP270) Sizing Guidelines and Excel Workbook (B0700AW).

Glossary

Expression Meaning

AMS Alarm Management System

AIM*API AIM* Product Line Application Programming Interface

AIM*Historian AIM*API application that collects I/A Objects.

AO API The Application Object API that is part of the OM and is used by AOS to access (e.g., create, locate) AO objects.

AO Objects The hierarchically named objects created and managed by either the Applica-tion Object Services (AOS) or by the AO API on an OM station. They are similar to CIO compounds, blocks, and parameters but provide increased flexibility. You define the data parameters, attributes, and so forth. AO objects take the form application:object.attribute.

API Application Programming Interface

AST Alarm Server Task

ATS Address Translation Station

CBL Carrierband LAN

CIO Control & Input/Output

CIO Objects The hierarchically named process control and input/output objects created through the control configurator and managed by the control software. CIO objects take the form compound:block.parm or compound.parm.

CP Control Processor. The control processor performs any mix of integrated first-level automation functions such as continuous, sequential, or discreet logic functions.

FCP270 Field Control Processor 270

FDSI Field Device System Integrator

I/A Objects The set of AO, CIO, and OM objects on I/A Series systems for which the OM provides applications with OM Services.

I/A Series Intelligent Automation Series

I/O Input/Output

xi

Page 12: Rede Mesh

B0700AX – Rev H Preface

IPC Inter-Process Communications: a proprietary, Foxboro communications layer for applications.

IPC Connec-tion

When two applications in different stations require a permanent connection between them, an IPC connection is formed. The number of IPC connec-tions is fixed based on station type except on workstations where it is an OS configurable parameter. For change-driven data access via OM open lists, the OM uses one IPC connection on each station (sink and source) regardless of how many applications open lists on the sink station.

LI LAN Interface

Nucleus Plus An embedded real-time operating system that is used on the FCP270 and ZCP270 control stations

OM Object Manager: a proprietary, Foxboro OS extension that supports data access to I/A objects.

OM API The Object Manager API that provides OM Services.

OM List An OM list is a set of points for which an application wants to receive change-driven data access. These data points can consist of CIO objects, AO objects, and OM objects that can reside locally or in remote stations. OM lists can be opened by user applications using FoxAPI or by Foxboro applica-tions using OM API. When an operator on a workstation brings up a new display, the connected data points on this display are requested from the sta-tion containing these points via an OM list. When the AIM*Historian asks for data collection points, it also uses an OM list. When a CP block has peer-to-peer block connections, it uses an OM list. While an OM list is open, it exists in the station that has requested the data (sink side) and a subset of the list exists in the station that contains remote data (source side).

OM Objects The flat named shared objects created and managed by OM Services, includ-ing shared objects of the following types: variable, alias, process, device, let-terbug, and socket.

OM Scanner An OM process that monitors the database of a station and sends data on an exception basis (change-driven basis) to other stations that have requested the data. Examples of stations that request change-driven data are CPs (for peer-to-peer connections) and Workstations (for displays, historians and other applications). Note that the OM scanner task always sends the change-driven data to the OM server task of the station that requested the data via an OM list.

OM Server An OM process that services all OM message requests. This includes change-driven data updates, get/set requests, object location requests, etc.

OM Services The object manager services used by applications for creating and deleting the OM objects and locating and accessing the OM objects, the AO objects, and the CIO objects.

Expression Meaning

xii

Page 13: Rede Mesh

Preface B0700AX – Rev H

Peer-to-Peer Connection

The control block mechanism that uses OM lists to refresh its block inputs with data from a remote station. That data can be from CIO, OM or AO objects. For most control strategies peer-to peer connections will be between CIO objects. The block that requests data is referred to as the sink of the block connection and the block that has the requested remote data is referred to as the source of the block connection. A block connection is normally local to another block that exists in the same CP. However, the full path name defined for a block parameter may be to a CIO object that is in another CP. This remote type of connection is referred to as a peer-to-peer block con-nection.

SMDH System Management Display Handler (Graphical User Interface for Systems Management)

Workstations Stations that connect to bulk storage devices and optimally to information networks to allow bi-directional information flow. These processors perform computation intensive functions as well as process file requests from tasks within themselves or from other stations. They also interface to a CRT and the input devices associated with it. These may be alphanumeric keyboards, mice, trackballs, touchscreens, or up to two modular keyboards. Each proces-sor manages the information on its CRT and exchanges data with other pro-cessor modules.

ZCP270 Z-Format Control Processor 270

Expression Meaning

xiii

Page 14: Rede Mesh

B0700AX – Rev H Preface

xiv

Page 15: Rede Mesh
1. Overview

This chapter provides an introduction to the document and the subject of sizing and the sizing spreadsheets and worksheets.

IntroductionThis document is the top level user’s guide for planning and sizing an I/A Series Mesh control net-work for I/A Series V8.4.1 and later software for the Windows operating system and I/A Series V8.3 and later software for the Solaris operating system. Lower level documents are referenced to provide detailed specific descriptions, suggestions, and procedures for major areas such as Con-trol, The Mesh control network, and I/O. System planning is described with respect to the overall performance and sizing of your I/A Series system, and does not take into consideration factors such as cost, environment, installation, and configuration. These factors are described in sales guidelines, sales tools, and other user documents.

Spreadsheets and worksheets are provided to make a variety of sizing calculations for I/A Series workstations and control stations. I/A Series sizing spreadsheets are Microsoft Excel® application software packages that execute on a Windows PC and provide automated calculations based on user input. Worksheets are provided for manual calculations if spreadsheets are not available.

The spreadsheets and worksheets should be used before final system configuration to expedite the configuration process and eliminate the need for reconfiguration. They can also be used to assist in developing a process control strategy that allows for maximum usage of all stations while pro-viding for expedient throughput for process control blocks.

Planning and sizing The Mesh control network for performance requires you to determine the distribution of equipment and software to guarantee that the system responds well to user actions, controls the process in real time, and meets published performance and sizing specifications for control, alarming, AIM*Historian data collection, and so forth.

Additional planning and sizing is needed if The Mesh network is connected via an Address Trans-lation Station (ATS) to a Nodebus network. Chapter 3 “System Sizing” describes the sizing calcu-lations for inter-network traffic between The Mesh network and the Nodebus network. Refer to the “Standard I/A Series Migration Strategies” section in V8.3 Software for the Solaris Operating System Release Notes and Installation Procedures (B0700RR) for planning recommendations regard-ing the ATS usage.

This document coupled with the lower level reference documents and the sizing spreadsheets and worksheets will help you successfully plan and size your system by providing information and data calculations that answer questions regarding control stations loading, workstations loading, and network traffic:

Control Stations:

♦ How many control stations do I need to support the number and type of I/O points in my system?

♦ How do I distribute my control process load between control stations?

♦ How many peer-to-peer connections can my system support?

♦ What is the estimated Field Bus Scan Load % for each control station?

1

Page 16: Rede Mesh

B0700AX – Rev H 1. Overview

♦ What is the estimated Control Block Load % for each control station?

♦ What is the estimated Sequence Block Load % for each control station?

♦ What is the estimated Total Control Cycle Load % for each control station?

♦ What is the estimated OM Scan Load % for each control station?

♦ What is the estimated CPU Load % for each control station to support my AIM*His-torian application?

♦ What is the estimated CPU Load % for each control station to support my FoxView displays?

♦ What is the estimated CPU Load % for each control station to support my worksta-tion applications?

♦ What is the estimated CPU Load % for each control station if I choose to use the default Aprint services for alarm notification?

♦ What is the estimated Idle Time % for each control station to support sustained alarm rates, alarm bursts, and alarm destinations?

♦ What is the estimated memory consumption for each control station?

♦ Do the sizing estimates for each control station exceed the recommended control sta-tion CPU loading guidelines?

Workstations:

♦ Do the default OS configurable parameter settings for each workstation satisfy the number of connections I need between the workstation and control stations?

♦ What is the estimated CPU Load % for each workstation to support my AIM*Histo-rian application?

♦ What is the estimated CPU Load % for each workstation to support my FoxView displays?

♦ What is the estimated CPU Load % for each workstation if I choose to use the default Aprint services for alarm notification?

♦ Do the sizing estimates for each workstation exceed the recommended workstation CPU Load % loading guidelines?

Network Traffic:

♦ What is my estimated Mesh network traffic flow and can my network configuration handle the estimated sustained and peak traffic rates?

♦ If connecting to a Nodebus system via ATSs, do I need to do a total replacement of LAN Interfaces (LIs) or can I do a gradual migration using an ATS running in Extender mode?

NOTEAll references to workstations apply to both Windows and Solaris workstations, unless explicitly referred to as either a Windows workstation or a Solaris workstation.

2

Page 17: Rede Mesh

1. Overview B0700AX – Rev H

Accessing SpreadsheetsSpreadsheets can be accessed on the I/A Series Electronic Documentation CD-ROM or from the IPS Global Client Support Center (Global CSC) web site (http://[email protected]). These spreadsheets can be run on any personal computer that has Microsoft Excel software. You should use the Microsoft Office 97 or later version of Excel.

For personal computer hardware and software requirements, refer to documentation for the Excel spreadsheet. Also, refer to the Excel documentation for general principles of operation.

Accessing Spreadsheets from the Electronic Documentation CD-ROMTo access the spreadsheets on the I/A Series Electronic Documentation CD:

1. Insert the CD in the CD-ROM drive.

2. Install the software.

3. Access the file for the spreadsheet desired.

3

Page 18: Rede Mesh

B0700AX – Rev H 1. Overview

4

Page 19: Rede Mesh
2. System Planning

This section contains system recommendations and guidelines that you should follow to ensure your I/A Series system does not exceed published I/A Series performance and sizing specifications.

The system planning phase will result in an I/A Series system that provides fast response to user actions, provides real-time control with no overruns, handles sustained alarm rates and alarm bursts, and supports customer applications and data access.

You should be familiar with the various sizing guidelines related to the configuration of a system prior to system definition/configuration. The Mesh control network no longer requires that you extensively plan Mesh network traffic rates, because the bandwidth usage will typically be less than 2% on an I/A Series system. If connecting The Mesh network to a Nodebus network using an ATS in Extender mode, you will need to size traffic rates for the LI associated with the ATS in Extender mode. Refer to the “Standard I/A Series Migration Strategies” section in V8.3 Software for the Solaris Operating System Release Notes and Installation Procedures (B0700RR) for planning inter-network communications between Mesh and Nodebus networks. System planning also requires that you determine the following:

♦ Workstation Loading

♦ Control Station Loading

♦ Distribution of I/O

♦ OS Configurable Parameters.

WorkstationsThe general workstation CPU loading guideline is that you should keep the sustained workstation idle time to at least the recommended value of Reserved CPU Load (Windows=40%, Solaris=40%). Reserved CPU Load % ensures that the workstation has a reserve performance capacity to support temporary peak loads for virus scanning, alarm bursts, alarm recovery, historian data reduction, historian archiving, large application startups, end of shift reports, file printing, file copies, network backup/restore, and so forth.

Workstation planning requires you to consider the following:

♦ Virus Scanning

♦ System Monitor configuration

♦ OS Configurable Parameters

♦ FoxView displays

♦ Alarming

♦ AIM*Historian

♦ Application Object Services

♦ Customer applications.

5

Page 20: Rede Mesh

B0700AX – Rev H 2. System Planning

Virus ScanningVirus scan protection is recommended regardless if you have any external network connections, because the system must still protect against file transfers done from local devices.

Virus Scan Software on Windows PlatformsMcAfee® Virus Protection Software V8.0i has been qualified and is recommended for use on V8.2 or later Windows workstations on The Mesh control network. V8.0i is not supported on I/A Series system Windows workstations running previous versions of I/A Series software. Addi-tionally, V8.2 and later Windows workstations do not support versions of McAfee Virus Scan software prior to V8.0i.

McAfee full virus protection software typically consumes a sustained CPU Load of <1% and a peak CPU Load of 10% (configured during McAfee installation). McAfee virus protection soft-ware, however, contains a file exclusion protection option that allows you to eliminate virus checking for selected files. Enabling the file exclusion protection feature can considerably reduce peak load usage and is recommended for all workstations.

Because the sustained CPU Load % for virus protection is extremely low and the workstation has a Reserved CPU Load of 40% that can handle temporary peak loads, the workstation summary sizing worksheet does not require a separate line entry for virus scanning; virus scan loading is absorbed in the line entry for Reserved CPU Load %.

Virus Scan Software on Solaris PlatformsCurrently there is no virus scan software available for workstations running I/A Series V8.3 soft-ware for the Solaris operating system.

SMONSSystem Monitor (SMON) is used to monitor the status of stations and devices on The Mesh con-trol network. The SMON limits enforced by System Definition software are:

♦ 30 SMONS maximum per system

♦ 64 stations (includes switches) maximum per SMON.

OS Configurable ParametersWorkstations support OS configurable parameters that enable you to fine tune OS extension resources for a particular application. These OS configurable parameters consist mainly of Object Manager shared memory resources. They include:

♦ Number of OM lists for change-driven data access

♦ Number of I/A objects that can be imported to minimize system multicast messages

♦ Number of OM objects which also supports the number of Application Objects.

Default values have been set for a typical workstation that supports the recommended guidelines for workstation applications such as FoxView, Alarm Manager, AIM*Historian, and so forth. In general, you do not need to modify the default settings. The OS configurable parameter usage can be viewed using the /usr/local/show_params utility. Refer to Application Object Services User’s Guide (B0400BZ) for information on setting OS configurable parameters.

Below is the table of OS configurable parameters with default and maximum values followed by a brief description of each parameter and typical I/A Series Mesh usage:

6

Page 21: Rede Mesh

2. System Planning B0700AX – Rev H

CMX_NUM_CONNECTIONS

♦ Maximum number of concurrent connections allowed by the workstation.

♦ CMX_NUM_CONNECTIONS ≥ OM_NUM_CONNECTIONS.

URFS_NUM_CONNECTIONS (Solaris Only)

♦ Number of connections used by uRFS.

OM_NUM_OBJECTS

♦ Total number of OM objects that can be created by applications. The number of OM objects is also used to support the number of Application Objects because they share OM memory space.

♦ You can use the /usr/local/show_params utility to view the usage of OM objects.

♦ You can use the /opt/fox/bin/tools/som utility (“list” command) to view the names of OM objects created.

♦ Each FoxView creates ~65 OM objects.

♦ Each Alarm Manager Subsystem creates ~10 OM objects.

OM_NUM_CONNECTIONS

♦ Total number of station connections used by OM Server for local OM change-driven lists. The number of connections determines how many stations can source data for workstation displays, AIM*Historian, and user applications.

♦ You can use the /usr/local/show_params utility to view the usage of station connections.

OM_NUM_IMPORT_VARS

♦ Total number of entries used to save station addresses for I/A objects to minimize mes-sage multicasts.

♦ You can use the /usr/local/show_params utility to view the usage of I/A objects imported.

♦ You can use the /opt/fox/bin/tools/som utility (“imp” command) to view the names of imported I/A objects (for example, compounds).

OS Parameter Name

Default Value Max Value

Windows Solaris Windows Solaris

CMX_NUM_CONNECTIONS 200 200 255 255

URFS_NUM_CONNECTIONS (Solaris Only) N/A 200 N/A 255

OM_NUM_OBJECTS 4000 4000 6000 6000

OM_NUM_CONNECTIONS 200 200 255 255

OM_NUM_IMPORT_VARS 1000 1000 10000 10000

OM_NUM_LOCAL_OPEN_LISTS 100 100 300 300

OM_NUM_REMOTE_OPEN_LISTS 100 100 100 100

IPC_NUM_CONN_PROCS 200 200 255 255

IPC_NUM_CONNLESS_PROCS 250 250 255 250

7

Page 22: Rede Mesh

B0700AX – Rev H 2. System Planning

OM_NUM_LOCAL_OPEN_LISTS

♦ Total number of workstation OM lists that can be opened for change-driven data access.

♦ Each FoxView opens one list per 1-75 display points.

♦ Each AIM*Historian opens (via FoxAPI) one list per 1-255 points sampled.

♦ Each user application opens (via FoxAPI) one list per 1-255 points requested for change-driven access.

♦ You can use the /usr/local/show_params utility to view the usage of local OM lists.

♦ You can use the /opt/fox/bin/tools/som utility (“opdb” command) to view local OM lists.

OM_NUM_REMOTE_OPEN_LISTS

♦ Total number of remote OM lists that source data (for example, remote shared vari-ables) for corresponding local OM lists (for example, FoxView displays) opened on other workstations.

♦ You can use the /usr/local/show_params utility to view the usage of remote OM lists.

♦ You can use the /opt/fox/bin/tools/som utility (“opdb” command) to view remote OM lists on workstations.

♦ You can use the /opt/fox/bin/tools/rsom utility (“opdb” command) to view remote OM lists on control stations.

IPC_NUM_CONN_PROCS

♦ Maximum number of workstation software processes that register for IPC connected services.

♦ I/A Series baseline software running on a Windows workstation consumes approxi-mately 35 I/A Series processes registered for IPC connected services.

♦ I/A Series baseline software running on a Solaris workstation consumes approximately 35 I/A Series processes registered for IPC connected services.

♦ You can use the /usr/local/show_params utility to view the usage of IPC connected services.

♦ You can use the /opt/fox/bin/tools/sipc utility (“list dt” command) to view the names of the processes registered for IPC connected services.

IPC_NUM_CONNLESS_PROCS

♦ Maximum number of workstation software processes that register for IPC connection-less services.

♦ I/A Series baseline software running on a Windows workstation consumes approxi-mately 65 I/A Series processes registered for IPC connectionless services.

♦ I/A Series baseline software running on a Solaris workstation consumes approximately 70 I/A Series processes registered for IPC connectionless services.

♦ You can use the /usr/local/show_params utility to view the usage of IPC connection-less services.

♦ You can use the /opt/fox/bin/tools/sipc utility (“list cdt” command) to view the names of the processes registered for IPC connectionless services.

8

Page 23: Rede Mesh

2. System Planning B0700AX – Rev H

FoxView In general, FoxView displays affect I/A Series control network systems as follows:

♦ Each FoxView display consumes a workstation CPU Load % for updating display val-ues, bar graphs, trend lines, and so forth.

♦ Each FoxView display consumes one workstation OM Server connection per remote station that sources display points.

♦ Each FoxView instance and its display consumes the following workstation OS con-figurable parameters:

♦ OM_NUM_OBJECTS

♦ OM_NUM_LOCAL_OPEN_LISTS

♦ OM_NUM_CONNECTIONS.

♦ Each FoxView display causes a control station OM Scan Load % based on the num-ber of display points the control station scans each second.

♦ Each FoxView display causes each control station that sources display points to con-sume one OM Scanner connection.

FoxView display updates are based on the display scan rate and the fast scan option configured when building a display using FoxDraw. The display configurable scan rate (which has a default of 1 s) applies to all stations sourcing display points. It determines how often the source stations scan the display points and send updated values to the workstation. The fast scan option applies only to control stations with a BPC of 100 ms or faster that are configured by SysDef to allow the OM fast scan option. A display configured with the fast scan option, coupled with a control sta-tion configured for OM fast scan, will cause a control station sourcing display points to scan the points every 100 ms and send updated values to the workstation.

The default display scan rate of 1 second coupled with the default NO fast scan option guarantees the following:

♦ Display call-up with initial data values within 1 to 2 seconds.

♦ Display updates of data sourced by I/A Series stations within 1 second.

NOTEThe fast scan option will increase the OM Scan load on each control station that sources display data approximately ten times the normal rate for the display points. It is recommended that you use the FoxView display fast scan option only if you have control stations running at 100 ms BPC or faster and require an initial display call-up time less than 1 second or if your data source is external to I/A and the dis-play update time needs to be faster.

A workstation can support multiple FoxViews (Windows 1-16, Solaris 1-16) and each worksta-tion worksheet calculates a CPU Load % based on a 200-point display with all the display points changing value every scan cycle. When building FoxView displays, you should consider the fol-lowing system impacts:

♦ Displays consume workstation OM Server connections equal to the number of sta-tions that source the display points. If the number of stations sourcing display points exceeds the number of OM Server connections, the display will not connect to all source stations and update all the points. The number of OM Server connections is an

9

Page 24: Rede Mesh

B0700AX – Rev H 2. System Planning

OS configurable parameter (OM_NUM_CONNECTIONS) and can be increased to correct this condition. The OM multiplexes station connections for all OM lists on a single workstation. The default value (Windows=200, Solaris=200) should not require you to make any modifications.

♦ Displays use one local OM list on the workstation for each of 1 to 75 unique display points. The number of OM local lists is an OS configurable parameter (OM_NUM_LOCAL_OPEN_LISTS). The default value (Windows=100, Solaris=100) should not require you to make any modifications.

♦ Displays should contain 200 points maximum to ensure an initial call-up time of less than 2 seconds.

♦ A 200-point display with the default scan rate of 1 second consumes a workstation CPU Load of 2.0% for Windows workstations and 5.2% for Solaris workstations.

♦ A 200-point display configured to use the fast scan option consumes a workstation CPU Load of 4.0% for Windows workstations and 10% for Solaris workstations.

♦ Displays configured to use the fast scan option increase the workstation CPU Load % because they cause FoxView software to update the display values at a faster rate and the workstation to process ten times the number of OM Scanner update messages sent by source control stations every 100 ms.

♦ Displays cause a control station that sources display points to have an OM Scan Load of 1.8% per 1,000 points/second changing every scan cycle.

♦ A 200-point display with the default scan rate of 1 second that has all the display points sourced by a single control station increases the control station’s OM Scan Load by 0.4%.

♦ Displays configured to use the fast scan option increase (by ten times) the OM Scan Load % on each 100 ms control station that sources display points and is configured for the fast scan option. Each source control station scans display points every 100 ms rather than every 1 second and sends 10 times the number of update messages.

♦ A 200-point display with the display fast scan option that has all display points sourced by a single OM fast scan control station causes a control station OM Scan Load of 4.0%.

♦ If you are configuring displays with the fast scan option, you must consider the num-ber of FoxView displays that can simultaneously access data from the same control station. This factor is covered in the OM Scan Loading section of the Control Station spreadsheets.

AlarmingThe Mesh control network requires that you configure alarm destinations for control station alarms. APRINT services on each control station sends control process alarm messages to the Alarm Management Subsystem (AMS) for configured alarm destinations such as workstations, printers, and AIM*Historian workstations. It sends multiple alarm messages (1 per destination) for each process alarm occurrence.

When planning alarm handling for your system, you should consider the following:

♦ What is the expected sustained alarm rate (alarms/second) for each controller? Sustained alarm rate = 5% of the control loops, where the number of control loops = (blocks per second)/5.

10

Page 25: Rede Mesh

2. System Planning B0700AX – Rev H

Example: 5000 blocks per second = 1000 control loops.

Sustained alarm rate = 1000 * 5% = 50 alarms per second.

♦ How many alarm destinations do I need for each controller?

♦ How many alarm messages per second do I require for each controller? Alarm mes-sages per second = sustained alarm rate * alarm destinations

♦ How heavily loaded are my controllers; how much Idle Time is needed to support the number of alarm messages?

♦ Aprint increases the control station alarming load significantly for each alarm destina-tion configured. The alarming CPU Load % doubles for 2 destinations, triples for 3, and so on.

♦ Aprint services on a control station consumes 0.1% Idle Time for each alarm message generated. For example, the Idle Time needed for 100 alarm messages per second =100 *0.1% = 10%.

♦ The Alarm Management Services (AMS) on a Windows workstation consumes 2.5% CPU Load % for every 100 alarm messages per second processed.

♦ The Alarm Management Services (AMS) on a Solaris workstation consumes 5% CPU Load % for every 100 alarm messages per second processed plus an additional 5% base load.

♦ The AMS base load on a workstation also depends on the number of Alarm Managers and the refresh rate of each Alarm Manager.

HistoriansIn general, AIM*Historian affects The Mesh control network as follows:

♦ AIM*Historian consumes workstation CPU Load % based on data collection rates, data reduction, and data archiving.

♦ AIM*Historian consumes workstation Disk Load Time % and physical disk space based on Real-Time Point (RTP) file sizes.

♦ AIM*Historian increases control station CPU Load % for OM scanning of data col-lection points sourced by the control station.

♦ AIM*Historian consumes the following workstation OS configurable parameters:

♦ OM_NUM_LOCAL_OPEN_LISTS

♦ OM_NUM_CONNECTIONS

♦ AIM*Historian consumes one workstation OM Server connection for every station that sources collection points.

♦ AIM*Historian causes a control station to consume one OM Scanner connection for collection points it sources.

The data collection rate determines how much data will be collected in a particular time frame and is controlled by the following:

♦ Delta – specifies the minimum change of a data collection point relative to the previ-ous collected value. A delta is assigned to each data collection point and should be the controlling variable for the data collection rate.

11

Page 26: Rede Mesh

B0700AX – Rev H 2. System Planning

♦ Collection Frequency – specifies how often the data collection points are scanned for changes on the stations (for example, control stations) that source the data. AIM*His-torian supports a slow and fast frequency option. By default, the fast frequency is in effect, and in most implementations there is little need to switch to the slow fre-quency. In many cases, making the collection frequency the controlling variable can be used as a convenient alternative to fine-tuning the individual deltas of data collec-tion points.

♦ Max Time Between Samples – guarantees that a value is placed in the database at least at the specified interval regardless if the value has changed more than the delta since the last collection. This parameter can be considered to have the opposite functional-ity as the Collection Frequency.

Data collection points are combined and collected into RTP files. A new RTP file is started when-ever the active one becomes “full” or when the specified Real-Time Retention Time parameter (RTTIME) has expired. The finished files are eventually repacked, which shrinks their sizes to about one-third without compression, and by an additional 40% to 60% when compression is on. Data retrieval is less efficient from a large number of small files when compared to a small number of large files; however, if the RTP files are too large, performance problems can occur because RTP files may not comfortably fit into physical memory. Disk activity increases and sys-tem performance may degrade.

A workstation can support multiple AIM*Historian instances, each capable of collecting in excess of 20,000 points. When using AIM*Historian software, you should consider the following system impacts:

♦ AIM*Historian software consumes an average workstation CPU Load (Windows=2%, Solaris=3%) for data collections that change at a rate of 1,000 points/second.

♦ AIM*Historian software consumes a workstation CPU Load (Windows=1%, Solaris=1.5%) for every 1,000 data collection points reduced at a rate ≥ 15 minutes.

♦ AIM*Historian software consumes a workstation CPU Load (Windows=5%, Solaris=4%) for every 5,000 data collection points archived at the default rate.

♦ AIM*Historian software consumes workstation OM Server connections based on the number of stations that source the data collection points. If the number of stations sourcing the data collection points exceeds the number of OM Server connections, not all the data will be collected. The number of OM Server connections is an OS configurable parameter (OM_NUM_CONNECTIONS) and can be increased to correct this condition. The default value should not require you to make any modifi-cations. The OM multiplexes station connections for all OM lists on a single workstation.

♦ AIM*Historian software uses 1 local OM list for each of 1 to 255 data collection points. The number of OM local lists is an OS configurable parameter (OM_NUM_LOCAL_OPEN_LISTS) and can be increased if necessary.

♦ AIM*Historian software causes a control station OM Scan Loading of 1.7% per 1,000 collection points/second changing every scan cycle.

♦ AIM*Historian software causes a control station OM Scanner connection to be used by each control station that sources data collection points

12

Page 27: Rede Mesh

2. System Planning B0700AX – Rev H

♦ The ARCHSIZE parameter controls the size of the RTP files and experience shows that a good compromise is to configure ARCHSIZE to a value that results in about one RTP file per day, or very few RTP files per day.

♦ The largest recommended RTP size is estimated to be 1/8 of the physical memory size. For example, if your Windows computer has 512 MB of RAM, ARCHSIZE should not be configured greater than 64 MB; if your Solaris computer has 1.0 GB of RAM, ARCHSIZE should not be configured greater than 128 MB.

♦ A good value for RTTIME is usually 86,400 seconds (1 day).

Refer to I/A Series Information Suite AIM*Historian User’s Guide (B0193YL) for information regarding the AIM*Historian configuration parameters that you may need to configure based on your system requirements and constraints. The AIM*Historian Excel spreadsheet HistSize.xls can be used to estimate the Historian Configuration Parameters.

PrintersThe workstation sizing spreadsheet entry Reserved CPU Load % has been set to include handling printer operations such as system messages and alarm messages. When deciding which worksta-tions should host local printers, consider the following:

♦ Local printers consume approximately 10% CPU Load for printing alarms.

♦ All alarm printers should be operated in the HSD (High Speed Draft) mode. This allows the best system performance when printing alarms and documents.

♦ Printing reports has about the same CPU Load % effect as printing alarms when the alarm rate is 30 alarms/minute or 10% load.

Application Object ServicesApplication Object Services (AOS) provides hierarchical application objects that are similar to control objects but are under the control of the user application. When using AOS, consider the following:

♦ AOS is not a small application. Its size is approximately 25 MB.

♦ AOS uses Object Manager shared memory. Run calcAppSize to determine the correct size of the OS configurable parameter OM_NUM_OBJECTS.

♦ The workstation CPU Load % is low and optimized, buffered AOA accesses using the AO API are greater than 10,000 per second on a workstation.

Refer to Application Object Services User’s Guide (B0400BZ) for detailed information regarding AOS.

ApplicationsIt is the responsibility of the user to determine the system impact of customer application pack-ages or third-party applications installed on The Mesh control network. Consider the following when installing application packages on the workstation:

♦ The general workstation CPU Loading guideline is that you should keep the Reserved Overhead % (Windows=40%, Solaris=40%) to ensure enough reserve capacity to sup-port peak loads for process upsets, large application startups, end of shift reports, printing, file copies, network backup/restore, and so forth.

13

Page 28: Rede Mesh

B0700AX – Rev H 2. System Planning

♦ Customer applications that access I/A Series data need to estimate the workstation CPU Load % based on FoxAPI performance guidelines.

♦ Third-party applications’ specifications for minimal system requirements (for exam-ple, RAM size) may affect I/A Series applications like AIM*Historian.

♦ The number of application software packages.

♦ The size of user-developed applications and programs.

♦ The frequency of application executions.

♦ Simultaneous application executions.

♦ Minimizing system broadcasts and multicasts.

For Windows platforms, you can determine the effect an application has on the workstation by using the Windows Performance Meter (Programs > Administrator Tools > Performance). The Windows Performance Meter provides metrics for the system, processor, processes, memory, physical disk, and so forth.

For Solaris platforms, you can determine the effect an application has on the workstation using the ps command and the perfmeter utility (click Launch > Applications > Utilities > Performance Meter).

Depending on the number and types of applications being run at the same time, increasing the workstation memory may improve system performance. Increased memory usually reduces the amount of paging and swapping to the physical hard disk.

ControlThis section presents an overview of the system planning and sizing guidelines required for you to adequately plan your control strategy on The Mesh control network. Refer to Field Control Proces-sor 270 (FCP270) User’s Guide (B0700AR) and Z-Module Control Processor 270 (ZCP270) User’s Guide (B0700AN) for detailed specifications regarding the FCP270 and ZCP270 control stations respectively.

In general, you must determine the number of control locations desired and properly size each control station. The key performance measures associated with sizing a control station are:

♦ Making sure the control station has enough execution time to read and write the I/O.

♦ Making sure the control station has enough execution time to execute the installed function blocks.

♦ Making sure the control station has enough memory to hold the control database and sequence code.

♦ Making sure the control station has enough Idle Time to send alarm messages to all configured alarm destinations.

♦ Making sure the control station has enough execution time to scan all data points it sources for FoxView displays, AIM*Historian, Peer-to-Peer connections, and worksta-tion application packages.

♦ Making sure the control station has enough OM Scanner connections for data it sources for FoxView displays, AIM*Historian, Peer-to-Peer connections, and worksta-tion application packages.

14

Page 29: Rede Mesh

2. System Planning B0700AX – Rev H

♦ Making sure the control station can support the number of scanner update messages it sends based on the number of OM Scanner connections and the OM scan rate. Each scanner update message takes an OM Scan Load of 0.03%. The OM scanner update messages are per list with a maximum of 100 scan points per message. An application that opens a list of 225 points can require 3 update messages per scan cycle if the list points change every scan cycle. A control station scanning at the fast scan option rate of 100 ms sends ten times the number of scanner update messages it would send if it scanned at 1 second.

♦ Making sure the control station has enough OM Server connections for peer-to-peer sink data.

Refer to FCP270 Sizing Guidelines and Excel Workbook (B0700AV) and ZCP270 Sizing Guidelines and Excel Workbook (B0700AW) for detailed operations on sizing the FCP270 and ZCP270 con-trol stations respectively.

AlarmingAlarms and status messages are generated by an Alarm block or by alarm options in selected blocks. Consider the following:

♦ Number of points with alarm indication

♦ Priority of alarms

♦ Criticality of alarms within each compound

♦ Devices and applications to be notified of process alarms

♦ Use of the compound alarm inhibit parameter

♦ Frequency of alarms.

The frequency of spontaneous alarms impacts the devices configured to be notified of alarms, communication traffic on the network, and operator responsiveness. Alarming strategies include:

♦ Providing a significant delta to eliminate nuisance alarming caused by the process drifting in and out of alarm when it is near a high or low limit

♦ Using the compound alarm inhibit function to eliminate alarms on a priority level basis.

Control DistributionDistribution of the various control schemes among the process control hardware, control proces-sors and Fieldbus Modules, require you to consider the following:

♦ CP storage memory required

♦ CP compound or block throughput

♦ Interprocess communication (IPC) connections

♦ Peer-to-peer relationships

♦ FBMs supported per CP.

Peer-to-Peer RelationshipsPeer-to-peer connections between stations are established when a compound:block.parameter in a source (supplier of data) station is connected to a compound:block.parameter in a sink (receiver of data) station. An IPC connection is formed in each station. Multiple peer-to-peer connections

15

Page 30: Rede Mesh

B0700AX – Rev H 2. System Planning

between two stations result in only one IPC connection for each station.

Peer-to-peer supports the following:

♦ 7500 sink points

♦ 100 OM Scanner connections for source points

♦ 30 OM Server connections for sink points.

OM Scan LoadThe OM Scan Load % is based on the following:

♦ The number of data points scanned/second.

♦ The number and size of scanner update messages sent each second for OM list updates.

Below are tables with examples of OM Scan Load for a CP270 sourcing data.

FoxAPI Application Examples

Table 2-1. OM Scan Load: FoxAPI Application Examples

DescriptionPoints per Second Scanned

% Points Changing per Second

Source CP270OM Scan Load %

FoxAPI Application 10,000 100 16.4

FoxAPI Application 10,000 50 11.7

FoxAPI Application 10,000 25 9.4

FoxAPI Application 9,000 100 14.8

FoxAPI Application 9,000 50 10.5

FoxAPI Application 9,000 25 8.5

FoxAPI Application 8,000 100 13.2

FoxAPI Application 8,000 50 9.4

FoxAPI Application 8,000 25 7.5

FoxAPI Application 7,000 100 11.5

FoxAPI Application 7,000 50 8.3

FoxAPI Application 7,000 25 6.6

FoxAPI Application 6,000 100 9.9

FoxAPI Application 6,000 50 7.1

FoxAPI Application 6,000 25 5.6

FoxAPI Application 5,000 100 8.2

FoxAPI Application 5,000 50 5.9

FoxAPI Application 5,000 25 4.7

FoxAPI Application 4,000 100 6.6

FoxAPI Application 4,000 50 4.7

FoxAPI Application 4,000 25 3.8

FoxAPI Application 3,000 100 5.0

FoxAPI Application 3,000 50 3.5

FoxAPI Application 3,000 25 2.8

FoxAPI Application 2,000 100 3.3

FoxAPI Application 2,000 50 2.4

FoxAPI Application 2,000 25 1.9

16

Page 31: Rede Mesh

2. System Planning B0700AX – Rev H

NOTEAIM*Historian software is an application that uses FoxAPI software. The default list scan rate for FoxAPI software is 0.5 seconds. Scanning 5,000 points every 0.5 seconds is equivalent to scanning 10,000 points/second.

Peer-To-Peer Examples

NOTEThe number of Sink stations does not affect the OM Scan Load % on the Source station. The list scan rate for Peer-To-Peer is 0.5 seconds. Scanning 5,000 points every 0.5 second is equivalent to scanning 10,000 points/second.

FoxAPI Application 1,000 100 1.7

FoxAPI Application 1,000 50 1.2

FoxAPI Application 1,000 25 0.9

Table 2-2. OM Scan Load: Peer-To-Peer Examples

DescriptionNumber of Points

Points per Second Scanned

% Points Changing per Second

Source CP270OM Scan Load %

Peer-To-Peer Source Station 5,000 10,000 100 17.7

Peer-To-Peer Source Station 5,000 10,000 50 12.4

Peer-To-Peer Source Station 4,500 9,000 100 15.9

Peer-To-Peer Source Station 4,500 9,000 50 11.1

Peer-To-Peer Source Station 4,000 8,000 100 14.2

Peer-To-Peer Source Station 4,000 8,000 50 9.9

Peer-To-Peer Source Station 3,500 7,000 100 12.4

Peer-To-Peer Source Station 3,500 7,000 50 8.7

Peer-To-Peer Source Station 3,000 6,000 100 10.6

Peer-To-Peer Source Station 3,000 5,000 50 7.4

Peer-To-Peer Source Station 2,500 5,000 100 8.9

Peer-To-Peer Source Station 2,500 5,000 50 6.2

Peer-To-Peer Source Station 2,000 4,000 100 7.1

Peer-To-Peer Source Station 2,000 4,000 50 5.0

Peer-To-Peer Source Station 1,500 3,000 100 5.3

Peer-To-Peer Source Station 1,500 3,000 50 3.7

Peer-To-Peer Source Station 1,000 2,000 100 3.6

Peer-To-Peer Source Station 1,000 2,000 50 2.5

Peer-To-Peer Source Station 500 1,000 100 1.8

Peer-To-Peer Source Station 500 1,000 50 1.3

Table 2-1. OM Scan Load: FoxAPI Application Examples (Continued)

DescriptionPoints per Second Scanned

% Points Changing per Second

Source CP270OM Scan Load %

17

Page 32: Rede Mesh

B0700AX – Rev H 2. System Planning

FoxView Application Examples

NOTEThe OM Scan Load % for the CP270 is based on the number of unique display points, the lists scan rate (default 1.0 second), and the percentage of display points changing every second. Examples above are for the default 1.0 second scan rate. Displays configured for the fast scan option rate will have an OM Scan Load % ten times the default list rate.

Table 2-3. OM Scan Load: FoxView Application Examples

Description

Number of AWs with FoxView Connections to CP270

Average Active FoxViews per AW

Average Unique Points per Display

Points per Second Scanned

% Points Changing per Second

Source CP270OM Scan Load %

FoxView Application 25 2 200 10,000 100 19.0

FoxView Application 25 1 200 5,000 100 9.5

FoxView Application 25 2 200 10,000 50 15.0

FoxView Application 25 1 200 5,000 50 7.5

FoxView Application 25 2 100 5,000 100 11.5

FoxView Application 25 1 100 2,500 100 5.8

FoxView Application 25 2 100 5,000 50 7.5

FoxView Application 25 1 100 2,500 50 3.8

FoxView Application 10 2 200 4,000 100 7.6

FoxView Application 10 1 200 2,000 100 3.8

FoxView Application 10 2 200 4,000 50 6.0

FoxView Application 10 1 200 2,000 50 3.0

FoxView Application 10 2 100 2,000 100 4.6

FoxView Application 10 1 100 1,000 100 2.3

FoxView Application 10 2 100 2,000 50 3.0

FoxView Application 10 1 100 1,000 50 1.5

FoxView Application 5 2 200 2,000 100 3.8

FoxView Application 5 1 200 1,000 100 1.9

FoxView Application 5 2 200 2,000 50 3.0

FoxView Application 5 1 200 1,000 50 1.5

FoxView Application 5 2 100 1,000 100 2.3

FoxView Application 5 1 100 500 100 1.2

FoxView Application 5 2 100 1,000 50 1.5

FoxView Application 5 1 100 500 50 0.8

FoxView Application 1 2 200 400 100 0.8

FoxView Application 1 1 200 200 100 0.4

FoxView Application 1 2 200 400 50 0.6

FoxView Application 1 1 200 200 50 0.3

FoxView Application 1 2 100 200 100 0.5

FoxView Application 1 2 100 200 50 0.3

FoxView Application 1 1 100 100 100 0.2

FoxView Application 1 1 100 100 50 0.2

18

Page 33: Rede Mesh

2. System Planning B0700AX – Rev H

Control Processor Load AnalysisThe estimated number of CPs required is based on:

♦ Number of FBMs required (both remote and local)

♦ Number and type of control loops consisting of compounds of related blocks which perform a single control scheme

♦ Scan rate per block and compound

♦ CP storage memory capacity

♦ CP throughput based on scan rates and block value point counts

♦ Need for fault-tolerant CPs for critical processes

♦ IPC connections available per CP (supporting various application requests for values)

♦ Peer-to-peer connections (affecting CP storage memory and IPC connections).

Block Processing Cycle

Running with 100 ms and 50 ms Block Processing Cycle (BPC)It is important to consider the number of blocks to be scanned within a compound and the num-ber of compounds to be scanned per control station. Control station processing throughput per second is dependent upon control station type; however, some control blocks count as more than one block and FBM equipment control blocks (ECBs) must be factored in as well. An ECB is a software block created for FBM data storage and is scanned at the fastest scan rate assigned to any control block connected to any point on the FBM.

Careful planning is necessary to prevent control blocks or compounds from being unable to pro-cess within a single scan cycle.

Phasing

CAUTION!Be careful when phasing! Putting blocks at different phases in the same control loop introduces deadtime into that loop that can severely degrade control.

Phasing of blocks, which is the staggering of scan periods, should be used to prevent block proces-sor overload. Refer to Control Processor 270 (CP270) Integrated Control Software Concepts (B0700AG) before attempting to phase a station.

19

Page 34: Rede Mesh

B0700AX – Rev H 2. System Planning

I/O PointsThe control station user guides and control station spreadsheets provide recommendations and sizing guidelines for the following I/O:

♦ Legacy (100 Series) FBMs

♦ DIN Rail Mounted (200 Series) FBMs

♦ FOUNDATION fieldbus (FF)

♦ Profibus

♦ HART

♦ Modbus

♦ FDSI.

NetworkNormally, understanding the details of the network traffic flow is an important part of planning and implementing a mesh network. A reasonable qualitative analysis of traffic profiles can be obtained without performing a rigorous quantitative analysis. To achieve this, a reasonable esti-mate must be made. Normally, the designer needs to know:

♦ What the traffic characteristics are (traffic volume and rates)?

♦ Device throughput

♦ What devices are talking to each other (the traffic flows across the network)?

♦ The physical and logical location of all these devices

♦ What the traffic volumes are by device type and/or technology?

♦ peak and average sustained load

♦ packet/frame size

♦ What is the network percent capacity used?

♦ How much of the bandwidth is being used?

♦ Is there any evidence of network congestion?

♦ number of packet discards

♦ error rates

♦ traffic overhead.

If you do not adequately understand these traffic flows, you can end up with a slow or non-work-ing network. Answering these basic questions and performing some planning allows for a nice load balanced redundant system.

The following I/A Series functionality contributes to the network traffic rate:

♦ FoxView – display updates

♦ AIM*Historian – data collection

♦ Alarming – messages to Alarm Managers, Printers, and Historians

♦ Peer-to-Peer

♦ Application Packages – change-driven data access and get/set operations.

20

Page 35: Rede Mesh

2. System Planning B0700AX – Rev H

However, the network traffic rates for The Mesh control network is not a gating issue because typ-ical traffic rate calculations for the above I/A Series functionality typically yield a network band-width utilization of <2%. Mesh network traffic rates need to be considered only in the case of third-party applications or user applications that generate high packet rates.

Workstation to workstation operations on The Mesh network, such as copying extremely large files, can result in a temporary high bandwidth usage up to 50% of the network. These types of operations also need to be considered.

The following baseline data is assumed for The Mesh bandwidth usage (<2%):

♦ Average I/A Series packet size is 150 bytes.

♦ Average I/A Series sustained packet rate will not normally exceed 1500 packets/second (based on <2% bandwidth and 150-byte packets).

The following table contains packet size and packet rate data for the 100 Mb Mesh network:

NOTEWhen measuring bandwidth on The Mesh, a given measurement applies only to a given link and the conversations on that link.

Refer to The MESH Control Network Architecture Guide (B0700AZ) for configuring The Mesh.

V8.1 introduced connecting The Mesh network to a Nodebus network using ATSs. If using an ATS in Extender mode, you will need to calculate inter-network traffic rates through the ATS in Extender mode to ensure that its corresponding Nodebus LI traffic rate does not exceed the max-imum recommended sustained rate of 220 packets/second. All stations that migrate to The Mesh network and continue to communicate to stations on the Nodebus must maintain their original Nodebus communication limits.

Copying a large data stream from a Nodebus through an ATS to The Mesh network is not recom-mended. Refer to the “Standard I/A Series Migration Strategies” section in V8.3 Software for the Solaris Operating System Release Notes and Installation Procedures (B0700RR) for specific details regarding data transfers between the Nodebus and The Mesh network.

Packet Size (bytes) Max Packets/Second

64 148,810

150 73,529 (2% = 1470)

1518 8,127

21

Page 36: Rede Mesh

B0700AX – Rev H 2. System Planning

WAp

Fo20dese

Fo20fasse

Al10se

AIDachpo

System Planning Summary TablesTable 2-4. Windows Workstation System Planning Summary

Windows Application

WorkstationCPU Load %

WorkstationOM Server Connections

OMLocal Lists

OMObjects

Control StationOM Scan Load %1

1. Control station OM scan load % is 2% for 1000 points changing every second and 0.03% for every scan-ner update message.

Control StationOM Scanner Connections

Control StationIdle Time %

FoxView:200 point display at default scan rate of 1 second

2% 1 per station sourcing data

3 lists;1 list for each 1-75 points

65 per FoxView

0.4% 1 for each station sourcing data

N/A

FoxView:200 point display at fast scan rate 0.1 seconds

4% 1 per station sourcing data

3 lists;1 list for each 1-75 points

65 per FoxView

4.0% 1 for each station sourcing data

N/A

Alarm Manager:100 message per second

2.5% Refer to AMS User’s Guide (B0700AT)

Refer to AMS User’s Guide (B0700AT)

10 per Alarm Manager

N/A Refer to AMS User’s Guide (B0700AT)

Decreases 0.1% per alarm mes-sage gener-ated

AIM*Historian:Data collection change rate of 1000 points per second

2% 1 per station sourcing data

4 lists;1 list for each 1-255 points

N/A 1.7% 1 for each station sourcing data

N/A

AIM*Historian:Data Reduction of 1000 points reduced >= 15 minutes

1% N/A N/A N/A N/A N/A N/A

AIM*Historian:Data Archiving 5000 points at default rate

5% N/A N/A N/A N/A N/A N/A

Table 2-5. Solaris Workstation System Planning Summary

indows plication

WorkstationCPU Load %

WorkstationOM Server Connections

OMLocal Lists

OMObjects

Control StationOM Scan Load %1

Control StationOM Scanner Connections

Control StationIdle Time %

xView:0 point display at fault scan rate of 1 cond

5.2% 1 per station sourcing data

3 lists;1 list for each 1-75 points

65 per FoxView

0.4% 1 for each station sourcing data

N/A

xView:0 point display at t scan rate 0.1 conds

10% 1 per station sourcing data

3 lists;1 list for each 1-75 points

65 per FoxView

4.0% 1 for each station sourcing data

N/A

arm Manager:0 message per cond

5% plus base load 5%

Refer to AMS User’s Guide (B0700AT)

Refer to AMS User’s Guide (B0700AT)

10 per Alarm Manager

N/A Refer to AMS User’s Guide (B0700AT)

Decreases 0.1% per alarm mes-sage generated

M*Historian:ta collection ange rate of 1000 ints/second

3% 1 per station sourcing data

4 lists;1 list for each 1-255 points

N/A 1.7% 1 for each station sourcing data

N/A

22

Page 37: Rede Mesh

2. System Planning B0700AX – Rev H

AIDa10>=

AIDapo

WAp

Data Access to I/A ObjectsApplications can use the Object Manager (OM) API to access I/A objects that can be either OM Objects, Application Objects (AO), or Control and I/O (CIO) Objects. OM API library func-tions for getting and setting I/A objects are best suited for situations in which you want a single transfer of data. These functions use IPC connectionless services and will perform a message mul-ticast operation if the I/A object’s address is not provided by the application (for example, om_getval) or if the I/A object’s address had not been imported by the OM during a previous data access (for example, getval with import option). I/A Series multicasts are limited by the ATS to 40/sec to Nodebus stations. Nodebus systems that have CP10s should not exceed system multi-cast rates of 10/second. Mesh-only systems should never exceed 50 multicast messages per second but can also be limited by control station CPU load.

If an I/A object’s address is known, the OM API will perform direct connectionless send messages to the station that sources the data. The maximum data access rates for CIO objects are governed by the access method (multicast versus direct send) and the control station load. Below is a table of maximum data access rates to CIO objects for a Mesh system.

Notes:

1. When using multicasts, the load on a single control station is the sum of all the get/set operations performed by all the applications in the entire system because each station must process each message.

2. Sequence code generates get/set requests using the OM API. Refer to High Level Batch Language (HLBL) User’s Guide (B0400DF) for sequence code guidelines.

M*Historian:ta Reduction of 00 points reduced 15 minutes

1.5% N/A N/A N/A N/A N/A N/A

M*Historian:ta Archiving 5000 ints at default rate

4% N/A N/A N/A N/A N/A N/A

1. Control station OM scan load % is 2% for 1000 points changing every second and 0.03% for every scanner update message.

Table 2-6. Data Access to CIO Objects on CP270

CP270 Idle Time

Multicasts (per second) Direct Sends (per second)

Set Set_Confirm Get Global Find (GF) Set Set_Confirm Get

75% 50 50 50 50 75 75 75

65% 50 50 50 50 75 75 65

55% 50 50 50 50 75 70 60

45% 50 50 50 50 75 60 50

35% 50 40 45 50 75 45 40

25% 50 35 30 40 75 35 35

15% 50 25 25 25 75 25 25

Table 2-5. Solaris Workstation System Planning Summary (Continued)

indows plication

WorkstationCPU Load %

WorkstationOM Server Connections

OMLocal Lists

OMObjects

Control StationOM Scan Load %1

Control StationOM Scanner Connections

Control StationIdle Time %

23

Page 38: Rede Mesh

B0700AX – Rev H 2. System Planning

24

Page 39: Rede Mesh
3. System Sizing

The following sections present sizing information for workstations, control stations, and I/O points. All data values presented in tables and worksheets have been rounded to one decimal position.

WorkstationsBelow are the initial Workstation Specification tables (Windows and Solaris platforms) for the V8.3 I/A Series Mesh control network. The performance and sizing metrics are based on each workstation’s specifications and thus each worksheet Workstation CPU Factor is 1.0.

NOTEOther Windows workstations (for example, PW340, PW360, PW370) have a Workstation CPU Factor of 1.5 based on performance and sizing specifications for pre-V8.2 I/A Series releases.

NOTEThe Workstation CPU Factors for each Solaris workstation that can be migrated from V7.x to V8.3 software for the Solaris operating system are listed below:- P79 workstation, SunBlade 150 (550 MHz) = 2.5- P80 workstation, SunBlade 2000 (900 MHz) = 1.5- P81 workstation (silver model), SunBlade 1500/S (1.5 GHz) = 1.0- P81 workstation (red model), SunBlade 1500/R (1.03 GHz) = 1.3

Table 3-1. Windows Workstation Specification

Description Value

System Microsoft Windows XP Professional Version 2002 Service Pack 2

Computer Pentium® 4 CPU 3.2 GHz (PW380, P92)

512 MB of RAMHard Disk Drives XP (C:) 15.6 GB

IA (D:) 217 GB

Workstation CPU Factor 1.0

Table 3-2. Solaris Workstation Specification

Description Value

System Solaris 10 Operating System (6/06 distribution)

Computer UltraSPARC IIIi® (Ultra 25® workstation, P82)1.34 GHz

1 GB of RAM

Hard Disk Drives 160 GB SATAWorkstation CPU Factor 1.0

25

Page 40: Rede Mesh

B0700AX – Rev H 3. System Sizing

Workstation Summary WorksheetThis section contains a workstation summary worksheet that totals the CPU Load % for the workstation based on the detailed worksheets that follow (for example, FoxView, AIM*Historian). The CPU Load % may not exceed 100%; otherwise, you must eliminate selected applications or transfer them to another workstation.

First, calculate the CPU Load % for each of the detailed worksheets that follow and then enter their corresponding values into the summary worksheet below. The Workstation Summary Work-sheet normalizes the CPU Load % based on the Workstation CPU Factor for pre-V8.3 stations migrated to V8.3. Entries for Base CPU Load and Reserved CPU Load are fixed values and should be entered in the Workstation Summary Worksheet based on Windows and Solaris plat-form guidelines.

NOTEValues in the summary worksheet are based on the Windows and Solaris worksta-tion examples from the worksheets that follow in this chapter. For example, the val-ues for the “Alarm Manager” entries in the summary worksheet below are derived from the Total CPU Load % of “4.5%” and “16.5%” calculated for the Windows and Solaris workstations in Table 3-4, “Alarm Manager Worksheet” on page 27.

Examples:

1. Total CPU Load % for a Sun Blade 1500/R Workstation:

(3.0+40.0) + ((1.3)*(16.5+10.4+4.7+5.0)) = 90.6

2. Total CPU Load % for a Sun Blade 2000 Workstation:

(3.0+40.0) + ((1.5)*(16.5+10.4+4.7+5.0)) = 97.9

Table 3-3. Workstation Summary Worksheet

Description

Value (%), Windows

Workstations

Value (%), Solaris

Workstations

1) Base I/A Series CPU Load (Windows=1.0, Solaris=3.0) 1.0 3.0

2) Reserved CPU Load (Windows=40.0, Solaris=40.0) 40.0 40.0

3) Alarm Manager 4.5 16.5

4) FoxView 8.0 10.4

5) AIM*Historian 3.1 4.7

6) Other Applications1 (for example, TDR, ApplicationObject Services, and so forth)

1. Refer to the reference document specific to the application.

5.0 5.0

7) Total CPU Load % =Items 1 + 2 + ((Sum of Items 3-6)*CPU Factor)

61.6 79.6

26

Page 41: Rede Mesh

3. System Sizing B0700AX – Rev H

3. Total CPU Load % for a Sun Blade 150 Workstation:

(3.0+40.0) + ((2.5)*(16.5+10.4+4.7+5.0))= 134.5

This configuration exceeds CPU 100% capacity.

4. Total CPU Load % for a PW340 Workstation:

(1.0+40.0) + ((1.5)*(4.5+8.0+3.1+5.0)) = 71.9

The following table shows an example calculation for a Mesh workstation with 100 alarms/second and 5 Alarm Managers.

NOTEThe Sustained Alarm Rate measures the time to process the alarm message traffic and is independent of the AST refresh rate.

Table 3-4. Alarm Manager Worksheet

Description

Value (%), Windows

Workstations

Value (%), Solaris

Workstations

1) Number of alarm messages per second from AprintServices for all CPsExample: 100 alarms/second

100 100

2) Workstation CPU load % for every 100 alarms/second:Windows Formula = 2.5% * (number of alarms / 100)Solaris Formula = 5.0% * ((number of alarms / 100) + 1)Windows Example: 2.5% * (100/100) = 2.5%Solaris Example: 5.0% * ((100/100)+1) = 10.0%

2.5% 10.0%

3) Base load for Number Alarm ManagersWindows Formula = Default Windows AST Table 3-5 Lookup *(default refresh rate / actual refresh rate)Solaris Formula = Default Solaris AST Table 3-6 Lookup *(default refresh rate / actual refresh rate)Windows Example, 5 AMs at default (3.0) AST refresh rate32K database: 1 * (3.0/3.0) = 1.0%Solaris Example, 5 AMs at default (3.0) AST refresh rate32K database: 4 * (3.0/3.0) = 4.0%

1.0% 4.0%

4) CPU Load for Matching and Filtering (per Alarm Manager)CPU Load % = (Matching and Filtering Load Coefficient[Windows=0.2%, Solaris=0.5%]) * (Number of Matches/Filters) *(Number of Alarm Managers)Windows Example: 5 matches for 1 Alarm ManagerCPU Load = 0.2% * 5 * 1 = 1.0%Solaris Example: 5 matches for 1 Alarm ManagerCPU Load = 0.5% * 5 * 1 = 2.5%

1.0% 2.5%

5) Total CPU Load % = sum of items 2, 3, and 4 above 4.5% 16.5%

27

Page 42: Rede Mesh

B0700AX – Rev H 3. System Sizing

Notes:

1. Each of the Number Alarm Managers tables measures the time to process alarm changes and is dependent on the AST refresh rate and independent of the sustained alarm rate, as long as at least one alarm changes per refresh cycle.

2. CPU load is linear based on AST refresh rate. CPU Load formula is based on refresh rate in table entry lookup.

Formulas:

Windows CPU Load % = (Default Windows AST Table 3-5 Lookup Value for default AST 3.0 second refresh rate) * (default refresh rate/actual refresh rate)

Solaris CPU Load % = (Default Windows AST Table 3-6 Lookup Value for default AST 3.0 second refresh rate) * (default refresh rate/actual refresh rate)

Example 1: 1 AM at default 3.0 second refresh rate for 32K database

Windows Workstation: 0.4 * (3.0/3.0) = 0.4%

Solaris Workstation: 0.9 * (3.0/3.0) = 0.9%

Example 2: 5 AMs at 0.5 second refresh rate for 32K database

Windows Workstation: 1.0 * (3.0/0.5) = 6.0%

Solaris Workstation: 4.0 * (3.0/0.5) = 24.0%

Table 3-5. Default AST Table for Number Alarm Managers on a Windows-Based Workstation(Local and Remote)

# Alarm Managers

AST Refresh Rate

CPU Load %1K Database

CPU Load %5K Database

CPU Load %10K Database

CPU Load %32K Database

1 3.0 seconds 0.2 0.2 0.2 0.4

5 3.0 seconds 0.2 0.2 0.4 1.0

10 3.0 seconds 0.2 0.4 0.8 1.7

15 3.0 seconds 0.2 0.7 1.0 2.2

20 3.0 seconds 0.2 0.7 1.0 3.0

25 3.0 seconds 0.2 0.8 1.5 3.5

Table 3-6. Default AST Table for Number Alarm Managers on a Solaris-Based Workstation(Local and Remote)

# Alarm Managers

AST Refresh Rate

CPU Load %1K Database

CPU Load %5K Database

CPU Load %10K Database

CPU Load %32K Database

1 3.0 seconds 0.9 0.9 0.9 0.9

5 3.0 seconds 4.0 4.0 4.0 4.0

10 3.0 seconds 8.0 8.0 8.0 8.0

15 3.0 seconds 12.0 12.0 12.0 12.0

20 3.0 seconds 16.0 16.0 16.0 16.0

25 3.0 seconds 20.0 20.0 20.0 20.0

28

Page 43: Rede Mesh

3. System Sizing B0700AX – Rev H

Example 3: 25 AMs at default 3.0 second refresh rate for 32K database

Windows Workstation: 3.5 * (3.0/3.0) = 3.5%

Solaris Workstation: 20.0 * (3.0/3.0) = 20.0%

NOTEActual Total CPU Load % is the sum of all FoxView loads.

Table 3-7. FoxView Worksheet

Description

Value (%), Windows

Workstations

Value (%), Solaris

Workstations

1) Number of FoxViews only using displays with defaultconfiguration values at (Windows=2.0%, Solaris=5.2%)per FoxViewWindows Example: 2 FoxViews = 2 * 2.0 = 4.0%Solaris Example: 2 FoxViews = 2 * 5.2 = 10.4%

4.0% 10.4%

2) Number of FoxViews using any displays with Fast ScanOption at (Windows=4.0%, Solaris=10.0%) per FoxViewWindows Example: 1 FoxView with Fast Scan = 1 * 4.0 = 4.0%Solaris Example: 0 FoxViews with Fast Scan = 0 * 10.0 = 0%

4.0% 0%

3) Total CPU Load % = sum of items 1 and 2 above 8.0% 10.4%

Table 3-8. AIM*Historian Worksheet

Description

Value (%), Windows

Workstations

Value (%), Solaris

Workstations

1) CPU Load for data collection change rate(Windows=2.0%, Solaris=3.0%) per 1000 points/secondRefer to “Data Collection Rate Example” below.

3.1% 4.7%

2) CPU Load for data reduction (Windows=1.0%, Solaris=1.5%) per 1000 points, rate >= 15 min-

utesWindows Example: 3100 pts at a rate >= 15 minutes =3100/1000 * 1.0% = 3.1%Solaris Example: 3100 pts at a rate >= 15 minutes =3100/1000 * 1.5% = 4.7%

3.1% 4.7%

29

Page 44: Rede Mesh

B0700AX – Rev H 3. System Sizing

Data Collection Rate Example:

1. Compute configured data collection rate.

♦ 1000 points at 0.5 seconds = 2000 points/second

♦ 1000 points at 1.0 seconds = 1000 points/second

♦ 1000 points at 10.0 seconds = 100 points/second

♦ Configured data collection rate = 3100 points/second.

2. Calculate data collection change rate (½ the points changing).

♦ = (configured data collection rate) * (% of points changing)

♦ = (3100 points/second) * (0.5)

♦ = 1550 points/second.

3. Calculate CPU Load for data collection change rate.

♦ CPU Load = (data collection change rate / 1000) * CPU Load for 1000/second

♦ = (1550/1000) * CPU Load % for 1000 pts/second

♦ Windows = 1.55 * 2 = 3.1%

♦ Solaris = 1.55 * 3 = 4.7%.

Control Processors

Maximum Loading TableInvensys Foxboro does not recommend exceeding any of the following maximums (in any phase where applicable). The control station is considered to be fully loaded with respect to that param-eter when this upper limit is reached. This ensures that adequate time remains for functions that are above and beyond the routine processing load such as checkpointing, alarm message handling, display call-up, and so forth.

3) CPU Load for data archiving (Windows=5%, Solaris=4%) per 5000 points at a default rate Windows Example: 3100 pts at a rate >= 15 minutes =3100/5000 * 5.0% = 3.1%Solaris Example: 3100 pts at a rate >= 15 minutes =3100/5000 * 4.0% = 2.5%

3.1% 2.5%

4) Total CPU Load % = item number 1. Note: Items 2 and 3 are encapsulated in theworkstation reserve CPU load because theyare not sustained loads.

3.1% 4.7%

Table 3-8. AIM*Historian Worksheet (Continued)

Description

Value (%), Windows

Workstations

Value (%), Solaris

Workstations

30

Page 45: Rede Mesh

3. System Sizing B0700AX – Rev H

Notes on Station Block display:

1. You can check the Control Loading for the last 10 block processing cycles (BPCs) by selecting “Control Loading” which also displays the number of control overruns.

2. You can check the OM Scanner Loading for the last 12 BPC cycles by selecting “OM Scanner Loading” which also displays the number of scanner overruns.

NOTEDo not load the CP270 so that the “Total Free” memory available is less than the number of bytes specified in Table 3-10.

Table 3-9. Loading Summary (% of BPC)

Station Block Field FCP270 ZCP270

Maximum % for “Fieldbus Scan” 60.0 60.0Maximum % for “Control Blocks” 70.0 70.0

Maximum % for “Sequence Blocks” 70.0 70.0Maximum % for “Control Blocks” + “Sequence Blocks” 70.0 70.0

Maximum % for “Total Control Cycle” 90.0 90.0Maximum % for “OM Scan Load”(Maximum value for scanning 12,000 points/second)

21.2 21.2

Minimum % for “Station Idle Time”(Note: May need to be increased based on sustained alarm rates and alarm destinations.)

10.0 10.0

Table 3-10. Station Free Memory (Bytes)

Station Block Field FCP270 ZCP270

Total Free Memory Available 500,000 500,000

Table 3-11. Peer-to-Peer Data

Station Block Field FCP270 ZCP270

Total sink points 7500 7500

OM sink connections 30 30

OM source connections 100 100

31

Page 46: Rede Mesh

B0700AX – Rev H 3. System Sizing

Inter-Network TrafficV8.3 supports inter-network traffic between The Mesh and Nodebus networks using ATSs. The preferred method of migration is to replace all Nodebus LIs with ATSs in LI mode at one time. When using the preferred method, you only need to ensure that stations that migrate to The Mesh and continue to communicate with stations on the Nodebus maintain their original Node-bus communications limits.

If you perform a gradual migration using an ATS in Extender mode followed by ATSs in LI mode, you will also need to size the LI traffic rates. The LI with the ATS in Extender mode can become a bottleneck as each Nodebus migrates to The Mesh using an ATS in LI mode. Below is a description of the gradual migration process with sizing calculations required to ensure acceptable inter-network traffic rates. Figure 3-1 depicts a five-node I/A Series system showing the traffic rates between various LI modules. For example, Figure 3-1 shows a 75 packet per second traffic rate between Node 4 and Node 5.

1. Determine traffic rates for all Nodebus LIs. Refer to Figure 3-1. Refer to “LI Traffic Rates” on page 37 for information on computing LI traffic rates on the web.

2. Add connection to The Mesh network by adding ATS in Extender mode to LI (con-sider using LI with lowest traffic rate). The LI will assume an additional load based on the ATS traffic rate. Refer to Figure 3-2.

3. Determine the traffic rate for the ATS in Extender mode (traffic between The Mesh and Nodebus stations). Compute the new traffic rate for the LI with the ATS in Extender mode. The new traffic rate for the LI with the ATS in Extender mode = LI rate + ATS rate to Nodebus stations that are not on the Nodebus that has the ATS in Extender mode. Refer to Figure 3-2. You can optionally measure traffic rates using LIPDUS30 shared variable - see Helpful Hint 960.

4. All remaining LIs can be replaced whenever you wish with ATSs in LI mode, as long as their traffic rates can be added to the LI with the ATS in Extender mode and the LI does not exceed the maximum recommended sustained traffic rate. Refer to Figure 3-3. If two or more nodes have high traffic rates between themselves, it is rec-ommended that the nodes be migrated at the same time. This will not increase the traffic rate through the LI with the ATS in Extender mode because the traffic between them will be routed through the ATSs in LI mode on The Mesh. Refer to Figure 3-4.

5. When migrating a node using an ATS in LI mode causes the LI with the ATS in Extender mode to exceed the maximum recommended sustained traffic rate, you must perform a total replacement using ATSs in LI mode (which includes converting the ATS in Extender mode to LI mode). Refer to Figure 3-5.

Table 3-12. Resource Table

HardwareResources

BlocksPerSecond

BlockNames

UserDatabaseSize

OMScannerCapacity

OMLists

InitializedStationMemory

FCP270 10,000 4000 5000KB 12,000 50 5700KB

ZCP270 10,000 4000 5000KB 12,000 50 5700KB

32

Page 47: Rede Mesh

3. System Sizing B0700AX – Rev H

NOTEIP communications cannot transmit across both an ATS and a LAN Interface sta-tion due to filtering implemented within the LI modules. There is an IP address limit of 64 stations per node. If full IP communication support is required, the net-work migration plan should be the preferred method of a complete replacement of all LAN Interface modules.

Example – Gradual Migration1. Determine traffic rates for all Nodebus LIs. Refer to Figure 3-1.

♦ LI1 – 100 packets/sec, LI2 – 50 packets/sec, LI3 – 75 packets/sec, LI4 – 100 packets/sec, LI5 – 75 packets/sec

2. Add connection to The Mesh network by adding an ATS in Extender mode to LI (consider using LI with lowest traffic rate). Refer to Figure 3-2.

♦ ATS in Extender mode is added to LI2, which has the lowest traffic rate.

3. Determine the traffic rate for the ATS in Extender mode (new traffic between The Mesh and Nodebus stations). Compute the new traffic rate for the LI with the ATS in Extender mode. Compute LI traffic rates for all LIs that have Mesh traffic. Refer to Figure 3-2.

♦ ATS in Extender mode traffic rate = 50 packets/sec (between The Mesh and Nodebus 2 stations)

♦ LI2 traffic rate = LI2 (Nodebus traffic) + ATS in Extender mode traffic rate = 50 (N1↔N2) + 50 (M↔N3) = 100 packets/second

♦ LI3 traffic rate = LI3 (Nodebus traffic rate) + LI Mesh traffic to Nodebus 3 = 50 (N1↔N2) + 25 (N3↔N4) + 50 (M↔N3) = 125 packets/second

4. Migrate Nodebus 1 to The Mesh using an ATS in LI mode (ATS LI1). This decreases the Nodebus traffic rate for the LI with the ATS in Extender mode by transferring all traffic between the migrated Nodebus (Nodebus 1) and the LI Nodebus with the ATS in Extender mode (Nodebus 2) to the ATS in Extender mode. However, it does increase the traffic rate for the LI with the ATS in Extender mode by the Nodebus traffic rates between the migrated Nodebus (Nodebus 1) and all LIs with no ATS in Extender mode (N1↔N3, N1↔N4, N1↔N5). Refer to Figure 3-3.

♦ LI2 traffic rate = LI2 - LI1 (N1↔N2) + LI1 (N1↔N3) + LI1 (N1↔N4) + LI1 (N1↔N5) = 100 - 50 (N1↔N2) + 50 (N1↔N3) + 0 (N1↔N4) + 0 (N1↔N5) = 100 packets/second

♦ ATS in Extender mode traffic rate = ATS in Extender mode + LI1 (Nodebus traf-fic) = 50 + 100 = 150 packets/second

♦ ATS LI1 traffic rate = LI1 (Nodebus traffic) = 100 packets/second

5. Migrate Nodebus 4 and Nodebus 5 to The Mesh using ATSs in LI mode (ATS LI4 and ATS LI5 respectively). Refer to Figure 3-4. Both nodes are migrated at the same time because they have significant traffic between them, and you do not want to impact LI2 with the ATS in Extender mode.

♦ LI2 traffic rate = LI2 + LI4 + LI5 = 100 + 25 (N3↔N4) + 0 = 125 packets/second. Note: N4↔N5 traffic is routed via The Mesh with no impact on LI2.

33

Page 48: Rede Mesh

B0700AX – Rev H 3. System Sizing

♦ ATS in Extender mode traffic rate = ATS in Extender mode + LI4 (N3↔N4) =150 + 25 = 175 packets/second

♦ ATS LI4 traffic rate = LI4 (Nodebus traffic) = 100 packets/second

♦ ATS LI5 traffic rate = LI5 (Nodebus traffic) = 75 packets/second

6. Migrate Nodebus 3 to The Mesh and change the ATS connected to Nodebus 2 from Extender mode to LI mode (ATS LI2). Refer to Figure 3-5.

♦ ATS LI1 traffic rate = original LI1 Nodebus traffic rate = 100 packets/second

♦ ATS LI2 traffic rate = original LI2 Nodebus traffic rate = 50 packets/second

♦ ATS LI3 traffic rate = original LI3 Nodebus traffic rate + new Mesh to Nodebus 3 traffic rate = 75 + 50 = 125 packets/second

♦ ATS LI4 traffic rate = original LI4 Nodebus traffic rate = 100 packets/second

♦ ATS LI5 traffic rate = original LI5 Nodebus traffic rate = 75 packets/second

The migration from all LI modules to all ATS modules is now complete.

Figure 3-1. Original Nodebus Traffic Rates

Carrierband LAN

LI1 LI2 LI3 LI4 LI5

Nodebus 1

50 (N1↔N2)50 (N1↔N3)

100 Total

50 (N1↔N2)

50 Total

50 (N1↔N3)25 (N3↔N4)

75 Total

75 (N4↔N5)25 (N3↔N4)

100 Total

75 (N4↔N5)

75 Total

(N1)Nodebus 2(N2)

Nodebus 3(N3)

Nodebus 4(N4)

Nodebus 5(N5)

34

Page 49: Rede Mesh

3. System Sizing B0700AX – Rev H

Figure 3-2. Adding an ATS in Extender Mode

Figure 3-3. Migrate Nodebus 1

The Mesh Network (M)

Carrierband LAN

N1

50 (N1↔N2)50 (N1↔N3)

100 Total

50 (N1↔N2)

100 Total

50 (N1↔N3)25 (N3↔N4)

125 Total

75 (N4↔N5)25 (N3↔N4)

100 Total

75 (N4↔N5)

75 Total

N2 N3 N4 N5

50 (M↔N3)

ATS(Extender mode)

LI1 LI2 LI3 LI4 LI5

50 Total

50 (M↔N3)

50 (M↔N3)

The Mesh Network (M)

Carrierband LAN

N1

50 (M↔N3)

100 Total

50 (N1↔N3)25 (N3↔N4)

125 Total

75 (N4↔N5)25 (N3↔N4)

100 Total

75 (N4↔N5)

75 Total

N2 N3 N4 N5

50 (N1↔N3)

LI2 LI3 LI4 LI5

ATSLI1

50 (N1↔N2)50 (N1↔N3)

100 Total

50 (N1↔N2)50 (M↔N3)

150 Total

50 (N1↔N3)

ATS(Extender mode)

50 (M↔N3)

35

Page 50: Rede Mesh

B0700AX – Rev H 3. System Sizing

Figure 3-4. Migrate Nodebus 4 and Nodebus 5

Figure 3-5. Final Migration

Carrierband LAN

N1 N2 N3 N4 N5

LI2 LI3

ATSLI1

50 (N1↔N2)50 (N1↔N3)

100 Total

50 (M↔N3)50 (N1↔N3)

175 Total

25 (N3↔N4)

50 (M↔N3)50 (N1↔N3)

125 Total

25 (N3↔N4)

50 (N1↔N2)

The Mesh Network (M)

ATSLI4

75 (N4↔N5)25 (N3↔N4)

100 Total

ATSLI5

75 (N4↔N5)

75 Total

ATS(Extender mode)

50 (M↔N3)50 (N1↔N3)

125 Total

25 (N3↔N4)

N1 N2 N4 N5

ATSLI2

ATSLI1

50 (N1↔N2)50 (N1↔N3)

100 Total 50 Total

50 (N1↔N2)

ATSLI4

75 (N4↔N5)25 (N3↔N4)

100 Total

ATSLI5

75 (N4↔N5)

75 Total

N3

ATSLI3

50 (N1↔N3)25 (N3↔N4)

125 Total

The Mesh Network (M)

50 (M↔N3)

36

Page 51: Rede Mesh

3. System Sizing B0700AX – Rev H

LI Traffic RatesBelow is the procedure for computing LI traffic rates using the web.

1. Go to the IPS Global CSC web site (http://[email protected]).

2. Log in.

3. Select Support > Foxboro > Trouble Shooting Guides.

4. Select Tokenbus/Nodebus Troubleshooting Guide.

5. Select Next until the LAN Traffic Rates screen appears.

6. Also view Helpful Hint 960.

37

Page 52: Rede Mesh

B0700AX – Rev H 3. System Sizing

38

Page 53: Rede Mesh
Index

AAddress Translation Station, see ATSAIM*Historian software xi, 11

CPU load 11, 12disk load time 11OM scan loading 12OM scanner connections 11, 12OM server connections 11OM_NUM_CONNECTIONS 12OM_NUM_LOCAL_OPEN_LISTS 12RTP file size (ARCHSIZE) 13RTTIME 13worksheet 29workstation summary worksheet 26

Alarm Manager software 10, 26worksheet 27

Alarming in control stations 15Alarming software 10AO API xiAO objects xiAOS software 13

CPU load 13number of objects 13workstation summary worksheet 26

Application Object Services. See also AOSApplications

CPU load 13customer 26performance meter 14planning 13third-party 21third-party and customer 14

ARCHSIZE 13AST, alarm server task xiATS xi

BBlock processing cycle (BPC) 19

CCMX_NUM_CONNECTIONS 7Control distribution 15Control stations xi

39

Page 54: Rede Mesh

B0700AX – Rev H Index

alarming 15estimating number of control stations required 19execution time 14load analysis 19maximum loading table 30memory 14OM scan load 15OM scanner connections 14, 15OM server connections 15planning 14

CP. See also Control stationsCPU load

AIM*Historian 11, 12AOS 13applications 13displays 10FoxView 9printers 13reserved 5virus scanning software 6worksheet calculations 26workstation summary worksheet 26, 27workstations 26

DDIN rail mounted FBMs 20Disk load time

AIM*Historian software 11Displays

CPU load 10Distribution of control 15Documents for reference ix

FFast scan option 9FBMs

DIN rail mounted (200 Series) 20FDSI 20Foundation fieldbus 20HART 20legacy 20Modbus 20Profibus 20

FCP270 xiFDSI xi, 20Field device system integrator. See also FDSIFoundation fieldbus FBMs 20FoxView software 9

40

Page 55: Rede Mesh

Index B0700AX – Rev H

CPU load 9display guidelines and resource usage 9OM scan load 9scan rates 9worksheet 29workstation summary worksheet 26

HHART FBMs 20High speed draft mode 13Historian software 11

II/O points 20Inter-network traffic 32Inter-process communications. See also IPCIPC xii

connected services 8connectionless services 8

IPC connections xii, 15, 19IPC_NUM_CONN_PROCS 7, 8IPC_NUM_CONNLESS_PROCS 7, 8

LLegacy FBMs 20LI

traffic rates 37LI (LAN interface) xiiLoading

control stations 14, 19, 30CPU 5workstation 5

Loading summary (% of BPC) worksheet 31

MMaximum loading table 30McAfee virus scanning software 6Memory 31Mesh. See also The Mesh control networkModbus FBMs 20

NNetwork

bandwidth utilization 21planning 20traffic flow 20

41

Page 56: Rede Mesh

B0700AX – Rev H Index

Nodebussizing when communicating to The Mesh 32

Number of Alarm Managers worksheet 28

OObject Manager. See also OMOM xii

API xiiList xiilists 6number of connections 7, 10number of entries 7number of objects 7, 13number of open lists 8, 10, 12number of processes that register for IPC 8number of processes that register for IPC connectionless 8number of remote lists 8objects xiiOS configurable parameters 6scanner xiiserver xiiserver connections 7services xii

OM scan load 2, 16AIM*Historian software 12control stations 15FoxView software 9, 10

OM scanner connectionsAIM*Historian software 11, 12control stations 14, 15FoxView software 9

OM server connectionsAIM*Historian software 11, 12control stations 15FoxView software 9

OM_NUM_CONNECTIONS 7AIM*Historian software 11, 12FoxView software 9, 10

OM_NUM_IMPORT_VARS 7OM_NUM_LOCAL_OPEN_LISTS 7, 8

AIM*Historian software 11, 12FoxView software 9, 10

OM_NUM_OBJECTS 7AOS 13FoxView software 9

OM_NUM_REMOTE_OPEN_LISTS 7, 8OS configurable parameters 6

default and maximum values 7Other applications

42

Page 57: Rede Mesh

Index B0700AX – Rev H

workstation summary worksheet 26

PPeer-to-peer connections xiii, 14, 19Performance

increasing 14planning and sizing The Mesh control network 1

Phasing 19Planning 5

AIM*Historian software 11alarming software 10AOS 13applications 13BPC 19control distribution 15control stations 14FoxView software 9I/O points 20OM scan load 16OS configurable parameters 6phasing 19printers 13System Monitor (SMON) 6The Mesh control network 20workstations 5

Printersplanning 13reserved CPU load 13

Profibus FBMs 20

RRAM

increasing 14Reference documents ixReserved CPU load 5Resource table worksheet 32RTTIME 13

SScan rates

default 9fast scan option 9

show_params 6, 7, 8Sink peer-to-peer status worksheet 31Sizing

additional sizing for networks connected via ATScontrol stations 30

43

Page 58: Rede Mesh

B0700AX – Rev H Index

workstations 25SMDH xiiiSolaris operating system 25som 7, 8Specifications 25Spreadsheets

accessingfrom electronic documentation CD-ROM 3

Station block display 31Station free memory worksheet 31Summary worksheet 26System Management Display Handler. See also SMDHSystem monitor (SMON) 6System planning 5

requirements 5System sizing 25

TThe Mesh control network 1, 20

configuration and references 21planning and sizing for performance 1sizing when communicating to Nodebus 32workstation specifications 25

Third-party applications 21

VVirus scanning 6

WWindows operating system 1, 25

performance meter 14Worksheets

AIM*Historian 29Alarm Manger 27FoxView 29Loading Summary (% of BPC) 31Number of Alarm Managers 28Resource Table 32Sink Peer-to-Peer Status 31Station Memory Free 31Workstation Summary 26

Workstations xiiiCPU factor 25planning 5sizing 25specifications 25summary worksheet 26

44

Page 59: Rede Mesh

Index B0700AX – Rev H

ZZCP270 xiii

45

Page 60: Rede Mesh

B0700AX – Rev H Index

Printed in U.S.A. 1108

IPS Corporate Headquarters5601 Granite Parkway Suite 1000Plano, TX 75024United States of Americawww.ips.invensys.com

Foxboro Global Client SupportInside U.S.: 1-866-746-6477Outside U.S.: 1-508-549-2424 or contact your local Foxboro representative.Facsimile: 1-508-549-4999