Page 1: Re-Commissioning Buildings

RECOMMISSIONING:

The Low Cost Way to Improved Building Performance

CaGBC Building Advisor ProgramOctober, 2012John Kokko, P.Eng., CCP, LEED [email protected] x2424

Page 2: Re-Commissioning Buildings

RECOMMISSIONINGLearning Objectives

► Understand the RCx process► Appreciate RCx costs and

benefits► Know how to prepare RCx

goals and objectivers► See how RCx fits within LEED

EB: O&M

Page 3: Re-Commissioning Buildings

RECOMMISSIONINGWhat is Building RCx

► Taking existing building systems and getting them working as best they can

► A systematic process for review and implementation of mainly operational improvements

► Bring building performance in line with current requirements and expectations

Page 4: Re-Commissioning Buildings

RECOMMISSIONINGWhat Does RCx Do?

► Reviews all building energy related systems including:

► Controls, HVAC, Building Envelope, Electrical, Plumbing

► Improves the operation of existing systems and equipment

► Includes implementation of low cost / no cost measures

► Identifies capital cost improvements► Provides both energy and non-energy

benefits

Page 5: Re-Commissioning Buildings

RECOMMISSIONINGWhy RCx?

► Higher than acceptable energy costs

► Escalating maintenance costs

► Significant occupant complaints

► Building use has changed

► Building is > 5 years old with no RCx

► Retrofits have been made with no RCx

► Staff turnover with minimal training of new staff

Page 6: Re-Commissioning Buildings

RECOMMISSIONINGRCx vs. Energy Audit

Page 7: Re-Commissioning Buildings

RECOMMISSIONINGSample RCx Findings

RCx opportunities found during walk-through:► Outdoor air on rooftop at 80% when it should be 20%► Heating coil and cooling coil operating simultaneously► RTU constantly cycling between heating and cooling► VFD pump with throttled discharge valve► Lighting and ventilation on in the middle of the night► Building doors blowing open due to over-pressurization► Piping that was hot when it should be cold► 3 compressors turning on and off simultaneously► Water storage tanks set higher than boiler output► Humidifier dumping water whenever setpoint reached

Page 8: Re-Commissioning Buildings

RECOMISSIONINGRCx Process in a Nutshell

Planning Phase:► Pre-Screening: Benchmarking, selecting building(s), defining goals

& objectives► MILESTONE: Approval to proceed to Scoping

► Scoping: Select RCx provider, preliminary investigation, RCx plan► MILESTONE: Approval to proceed to Investigation Phase

Investigation:► Kick-off, in-depth investigation, document findings and present

recommendations► MILESTONE: Approval to proceed to Implementation Phase

Page 9: Re-Commissioning Buildings

RECOMISSIONINGRCx Process in a Nutshell

Implementation:► Implementation plan, implement measures, verify improvements

► MILESTONE: Owner accepts Implementation Report

Hand-Off:► Final RCx report, on-going / next RCx plan, staff training

► MILESTONE: Provider holds Hand-Off Meeting

Finally:► Persistence measures and long-term benchmarking

Page 10: Re-Commissioning Buildings

RECOMISSIONINGInformation and Materials

Recomissioning Guide for Building Owners and Managers canmetenergy.nrcan.gc.ca/eng/rcs.html

► Recommissioning Guide► Pre-Screening Tool► Benchmarking Tool► Case Studies

Other Resources:► Peci.org/resources/commissioning.html► ASHRAE► LEED EB: O&M

Page 11: Re-Commissioning Buildings

MMM GROUP LIMITED

PLANNING

Page 12: Re-Commissioning Buildings

RECOMMISSIONINGIdentify Candidate Building

Page 13: Re-Commissioning Buildings

RECOMMISSIONINGSet RCx Goals and Objectives

Energy Issues:► Reduce energy consumption by

15% annuallyIEQ Issues:► Reduce occupant comfort

complaints by 50%Operational Issues:► Update O&M documentation and

provide staff training, needed to maintain performance

Page 14: Re-Commissioning Buildings

MMM GROUP LIMITED

INVESTIGATION

Page 15: Re-Commissioning Buildings

RECOMMISSIONINGBenchmarking – Energy Star

Page 16: Re-Commissioning Buildings

RECOMMISSIONINGUtility Bill Breakdown

Two years utility data

Modeling used to identify load breakdown

1% 3%

6%

14%

19%

22%

35%

Base Case Energy End Use

Exterior Electric (1%)

Electric Hot Water (3%)

Fan Electric (6%)

Lights (14%)

Cooling Electric (19%)

Plug Loads (22%)

Space Heat Electric (35%)

Page 17: Re-Commissioning Buildings

RECOMMISSIONINGEnvelope Air Tightness and Thermal Bridging

Page 18: Re-Commissioning Buildings

RECOMMISSIONINGLighting

► Indoor lighting 2x4 T-12 Troffers at 2.4 W/ft2 with minimal zoning. Discoloured lenses , low light levels

► Outdoor lighting and signage remains on 24 hr/day due to malfunctioning timer

Page 19: Re-Commissioning Buildings

RECOMMISSIONINGHVAC

► Electric heaters in ceiling space above boardroom and other offices on 3rd floor running continuously

► Economizer not operational due faulty to sensor and broken damper linkage

Page 20: Re-Commissioning Buildings

RECOMMISSIONINGAir and Heat Delivery

► Non-powered diffusers, some inoperable, others mismatched masters and slaves

► Electric baseboard heaters operating at the same time as cooling due to excessively high t’stat control setting

Page 21: Re-Commissioning Buildings

Electricity Retrofit Incentive Program (ERIP) – OPA► For retrofit of existing facilities focuses on lighting, motors, HVAC

and overall electricity savings► Chiller Re-Commissioning

Enbridge Gas Retrofit Incentives ► Provides up to $0.10 per m3 of natural gas saved for saving

measures based on projected first year gas savings.

Union Gas Run it Right► Provides 100% of implementation costs up to $5,000 ► Plus up to $3,000 to provide monitoring showing savings

21

RECOMMISSIONINGIncentives

Page 22: Re-Commissioning Buildings

RECOMMISSIONINGNext Steps

► Review of recommendations, costs, and paybacks with owner

► Owner decides which options to accept and which to reject

► Has hired 3rd party PM firm to oversee installation ► Next steps will be retrofit of lighting, air handlers, and

other capital cost items► RCx will then include Cx of newly installed systems

and remainder of RCx items

Page 23: Re-Commissioning Buildings

MMM GROUP LIMITED

COSTS AND BENEFITS

Page 24: Re-Commissioning Buildings

RECOMMISSIONINGApproximate RCx Costs

► Planning ~$5,000 to $8,000► Investigation, Implementation, and Hand-off $1.40 to $10.84/m2 for the

total RCx process depending on:

► External consultant costs range from 35% to 71% of total costs

Building size Complexity of systems Up-to-date

Documentation BMS data availability

Project scope Subcontractor requirements Implementation involvement Owner involvement

Page 25: Re-Commissioning Buildings

RECOMMISSIONINGIssues Identified with RCx

Top Cumulative Savings Measures and % of Savings

Key Measure Mix % of Total SavingsRevise control sequence 21%

Reduce equipment runtime 15%Optimize airside economizer 12%

Add / optimize SAT reset 8%Add VFD to pump 6%

Reduce coil leakage 4%Reduce / reset DSP setpoint 4%

Add / optimize optimum start/stop 3%

Add / optimize CWST reset 2%A study on Energy Savings and Measure Cost Effectiveness of EBCx

Portland Energy Conservation, Inc. Dec 15th, 2009

Page 26: Re-Commissioning Buildings

RECOMMISSIONINGApplicability of RCx Measures

Comparison of key measure mix to building attributesBuilding Attribute

Sub-CategoryPercent of savings achieved

through key measure mixBuilding TypeLarge Office 72%Hotel/Motel 64%

Building Size0-200 73%

200-350 55%350-550 69%

>550 69%Building Age

<1920 63%1980-1989 72%

2000-Present 71%Climate Zone

3B 77%3C 78%

Page 27: Re-Commissioning Buildings

RECOMMISSIONINGEnergy Savings and Payback

Page 28: Re-Commissioning Buildings

RECOMISSIONINGAdditional RCx Benefits

Protect of enhance property value:► Maintain high occupancy rates► Reduce tenant turnover► Gain marketplace competitive edge

Protect against future liability:► Reduce potential for sick building syndrome► Identify and address indoor environmental issues

Reduce repair and replacement costs:► Increase equipment life► Reduce maintenance requirements► Reduce comfort complaints

Page 29: Re-Commissioning Buildings

RECOMMISSIONINGValue of Non-Energy Impacts

For typical commercial buildings≈ $1.61 to $3.23/m2

Median value:$1.94/m2

Range:$1.08 - $4.84/m2

1%

5%5%

7%

10%

17%21%

33%

Liability (1%)

Change Orders & WarrantyClaims (5%)Productivity/Safety (5%)

Ongoing Labour Cost (7%)

Other First Cost (10%)

Indoor Air Quality (17%)

Thermal Comfort (21%)

Equipment Life (33%)

Reported NEIs for 36 projects in existing buildings (USA)

Source: Lawrence Berkeley National Laboratory, “The Cost Effectiveness of Commercial-Buildings Commissioning,” December 2004.

Page 30: Re-Commissioning Buildings

MMM GROUP LIMITED

OTHER CASE STUDIES

Page 31: Re-Commissioning Buildings

RECOMMISSIONINGOffice Tower - Winnipeg

Courtesy NRCan: www.canmetenergy.nrcan.gc.ca/eng/rcx.html

Page 32: Re-Commissioning Buildings

RECOMMISSIONINGAdult Ed Centre, Sherbrooke, QC

Courtesy NRCan: www.canmetenergy.nrcan.gc.ca/eng/rcx.html

Page 33: Re-Commissioning Buildings

RECOMMISSIONINGCase Studies

Savings Items Office Winnipeg Ed Center Sherbrooke

Energy Savings1 (GJ/yr, %) 6,652 GJ (25%) 763 GJ (12%)

% Natural Gas; % Electricity 75% NG; 25% E 84% NG; 16% E

Financial Savings2 ($/yr) $59,000/yr $13,300/yr

GHG Reduction (t CO2 e/yr) 363 t/yr(66 cars)

42 t/yr(8 cars)

Simply Payback3 (yr) 3.3 yr 3.9 yr

1 Savings verified 12 months after implementation of the RCxmeasures and weather-normalized.

2 Monetary savings don’t include non-energy impacts (NEIs) such as equipment durability or reduction of tenant complaints.

3 Includes all 4 phases costs of project

Page 34: Re-Commissioning Buildings

RECOMMISSIONINGCase Studies

Adult Ed Centre

Sherbrooke, QC

Office Tower

Winnipeg, MB:

Courtesy NRCan: www.canmetenergy.nrcan.gc.ca/eng/rcx.html

Page 35: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 1. Turn off equipment that should be off► Over-ridden schedules, systems

set for 24/7 operation► Broken or out of calibration timers► Poor original sequence► Optimum start/stop not working► Equipment set to operate in

HAND rather than Auto

Page 36: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 2. Improper ventilation / outdoor quantities► not set to match current

requirements

Page 37: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 3. Verify dampers and valves on central AHUs operating property► Sticking due to long time

non-use► Broken or damaged linkages► Improper repairs

Page 38: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 4. Verify terminal units operating properly► Inoperative actuators / valves► Defective receiver/controller► Out of calibration sensors► Deficient or excessive flow► Dirty rads or coils not heating

the space► Malfunctioning secondary

loop temperature control

Page 39: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 5. Verify Supply Static Pressure Setpoint (Air and Water Systems)

► 6. Verify Supply Air and Water Temperature Reset Schedule

► 7. Eliminate Simultaneous Heating and Cooling

Page 40: Re-Commissioning Buildings

RECOMMISSIONINGTop RCx Tasks

► 8. Return VFD to Variable Speed Operation

► 9. Calibrate Sensors and Instrumentation

► 10. Interference with Room Controls

Page 41: Re-Commissioning Buildings

MMM GROUP LIMITED

RCx and LEED EB:O&M

Page 42: Re-Commissioning Buildings

RECOMISSIONINGRCx and LEED EB:O&M

EAp1: Energy Efficiency Best Practices Management :

► Planning, Documentation and Opportunity Assessment

EAp2: Minimum Energy Efficiency Performance► EAc2.1: Existing Building Commissioning:

Investigation and Analysis (2 points)► EAc2.2: Existing Building Commissioning:

Implementation (2 points)► EAc2.3: Existing Building Commissioning:

Ongoing Commissioning (2 points)

Page 43: Re-Commissioning Buildings

RECOMMISSIONINGEAp1: Planning, Documentation, and Opportunity Assessment

► 1. Building Operating Plan► 2. Systems Narrative► 3. Sequence of Operations► 4. Preventative Maintenance

Plan► 5. ASHRAE Level I Audit

► Utility Bills review► Energy Utilization Index► Low Cost/No Cost

Improvements

Page 44: Re-Commissioning Buildings

RECOMISSIONINGEAp2: Minimum Energy Efficiency Performance

Option A:► Energy Star® : Energy Performance Rating min 69

Option B:► 19% better efficiency than cohort average

Page 45: Re-Commissioning Buildings

RECOMISSIONINGEAc2.1: Investigation & Analysis

Option A – Commissioning Process:► Site Assessment► Building Energy End-Use Breakdown► Diagnostic Monitoring And Functional Testing► Master List Of Findings

Option B:► ASHRAE Level II Audit► Building Energy End-Use Breakdown► Cost - Savings Analysis► Listing of capital improvements

Page 46: Re-Commissioning Buildings

RECOMISSIONINGEAc2.2: Implementation

1. Implement low cost / no cost measures

2. Provide building staff training

3. Provide the following documentation:► Listing of measures, operational improvements and/or

repairs implemented► Update or revise the Building Operating Plan► Recommended capital plan for major retrofits or

upgrades► Summary of staff training program

Page 47: Re-Commissioning Buildings

RECOMMISSIONINGEAc2.3: Ongoing Commissioning

1. Update the Systems Manual

2. Produce an On-Going Commissioning Plan

3. Implement Ongoing Commissioning

Page 48: Re-Commissioning Buildings

RECOMMISSIONINGConclusions

► RCx is a systematic process that optimize comfort and energy savings of existing buildings

► RCx can reduce whole-building energy uses by 5% to 30%

► Paybacks typically in the 0.5 to 5 yr range► RCx helps the persistence of energy and non-energy

benefits ► RCx can help obtain LEED EB:O&M Certification