8/13/2019 Rapcon-24 Usermanual-[1]
1/31
8/13/2019 Rapcon-24 Usermanual-[1]
2/31
CONTENTS
1.0 Introduction
2.0 Technical Data
3.0 Controls
4.0 Function
5.0 Operation5.1 Function Selection5.1.1 Using Password5.1.2 Setting Rapper Times5.1.3 Setting Real Time5.1.4 Starting and stopping a Rapper5.1.5 Starting and stopping a rapper manually5.1.6 Setting Program set no.5.1.7 Checking the Rapper Times5.1.8 Checking the Real Time5.1.9 Checking the RAPCON-24 Address5.1.10 Checking the Program set NO.5.1.11 Alarm Action
6.0 Standby
7.0 System Messages7.1 RAPCON-24:MASTER7.2 Key Board Timeout7.3 2004.04.25 09:10,407.4 Input Out of Range!
8.0 Fault Finding
APPENDIX-AAPPENDIX-B
8/13/2019 Rapcon-24 Usermanual-[1]
3/31
1.0 Introduction
RAPCON-24 (Rapper Controller) is a microprocessor-based unit that controls andsurveys the operation of rapping motors in Electrostatic Precipitators. One RAPCON-24 unit can control up to 24 rapping motors. RAPCON-24 starts and stops the rappingmotors as programmed and will give an alarm if a rapping motor fails.
RAPCON-24 is a component of BHELs Integrated Operating System (IOS), but canalso be used as a stand alone unit. In BHELs Integrated Operating System a maximumof eight RAPCON-24s will communicate on a data link with other control units.
From RAPCON-24 each rapping motor can be manually started or stopped duringoperation, without interfering with other rapping motors. The operation state of eachrapping motor is indicated with light emitting diodes on the RAPCON-24 panel.
The RAPCON-24 is pre-programmed with number of Rapping Sequences, any of whichcan be selected depending on the field failure condition of the Electrostatic Precipitator.
2.0 Technical data
Dimension Weight ~8kg
Width 280mm Operation Temperature +5 to+50CDepth 180mm
Height 210mm Storage Temperature 0 to +70C
CutoutWidth 255mm Panel Protection IP 54Height 180mm
Mains Requirement 24V10%
(RAPCON-24 only) 50Hz5%, 50VA
All RAPCON-24 inputs & outputs are brought to screw type terminal strips via short(2.5m) Flat Ribbon cables
Inputs :One for each rapping motor: (Opto coupled that acknowledgeRapping motor ON/OFF status.)
Outputs : One for each rapping motor.(A relay contact. Closure operates theContactor of the rapping motor.)
Communication link:10mA, (balanced current loop.) Page. No.: 01
8/13/2019 Rapcon-24 Usermanual-[1]
4/31
3.0 Controls
1.ERROR -REDLEDthatlightsiftherappingmotordoesnotstartwithin3secs.Afterstartorder,oriftherappingmotorstopsduringoperationorrappingmotorrunsmorethan10mnts.continuouslyinmanual
mode.2.MOTOR -RappingmotorNo.Appropriatenumberlightswhenrappingisinprogrammedrunningmode.3.RUNNING -GreenLEDthatlightswhentherappingmotorisrunning.4.1(ON)-NumericpushbuttonalsousedforONcommands5.CLEAR(OFF) -Pushbuttonforclearingthedisplaye.g.aftertypingerrors,orbeforeenteringnewvaluesandforOFFcommands6.NumericalPushbuttons-forenteringtimes,rappingmotornumbers,passwordetc.,7.ENTER(YES) -Pushbuttonforconfirmingcommandsanddataentered
8.REMOTE -PushbuttonforselectionofcontrolbyIntegratedOperatingSystem9.LOCAL -PushbuttonforselectingofLOCALcontrol10.STANDBY -PushbuttonON/OFFselectionofstandby11.SETFUNCTION -Pushbuttonfordisplayingthedesiredvalue.12.DISPLAY -Alphanumericdisplaythatpresentsthefunctions,setvalueetc.,duringsettingandcontrolofprocesstimes,alarmresets,rappersonandoffandpasswordentries.13.ACTIVE-REDLEDindicatortoshowtheunitiscontrollingtherappingmotors14.ALIVE -REDLEDindicatortoBLINKtoshowhealthinessofthecontroller
PageNo.02
21 22 23 24
9 10 11 121 2 `3 4 5 6 7 8
13 14 15 16 17 18 19 20
2004.05.20 08:10,30
RAPCON-24
SETFUNCTION
STANDBY
ERROR
MOTOR
RUNNING
RUNNING
MOTOR
ERROR
ACTIVEALIVE
01
02
03
04 05 06 07
13121110
09
08
RAPCON-24 FRONT PANEL
87 9
4 5 6
1ON 2 3CLEAR
OFF0 ENTER
YES
LOCAL
REMOTE
8/13/2019 Rapcon-24 Usermanual-[1]
5/31
4.0 Function
RAPCON-24 controls and monitors the operation of up to 24 rapping motors. RAPCON-24 has three timers for each rapping motor, so that start time, repetition time run time canbe independently set for each rapper.
The start time is set in actual clock time (hour, minutes). The repetition time is set inhours and minutes and the run time is set in minutes and seconds.
RAPCON-24 gives a relay contact closure to order a rapping motor start. If the rappingmotor has not acknowledged the start order within 3 secs, an ERROR alarm will beobtained and the rapping motor will be switched off. This will also occur if the rappingmotor should stop during the set run time.
Timer operation principle.(Only one rapper shown)
Page No. 03
R R R S
G G G G G G
S Start time (reset every 24 hour)R Repetion time
G Run time
8/13/2019 Rapcon-24 Usermanual-[1]
6/31
5.0 Operation
5.1 Function Selection
Function selection and settings are both made interactively using the RAPCON-24
pushbuttons and the display. Some function can be used during operation, while othersrequire the RAPCON-24 to be in LOCAL mode. The first event operation from (no.2 to
6) Only permits access if the password is answered correctly.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the SET FUNCTIONPush button
And you will getNEXT FUNCTION NO =where you can select thefunction you went to use. Thefollowing are available, andwill appear as text on the
display.
PASSWORD?
SET RAPPER TIMES?
SET REAL TIME? FFFFF
SET AUTO ON/OFF?
SET MANUAL ON/OFF?
Page No. 04
1. NEXT FUNCTION NO =
2. SET RAPPER TIMES?
3. SET REAL TIME?
4. SET AUTO ON/OFF?
5. SET MANUAL ON/OFF?
SET
FUNCTION
1. PASSWORD?
8/13/2019 Rapcon-24 Usermanual-[1]
7/31
SET PROGRAMSET NO?
DISPLAY TIMES?
DISPLAY REAL TIME?
PROGRAMSET NO?
RAPCON-24 ADDRESS?
RESET ALARM?
SET MOTOR LABEL?
There are two methods to reach a function, when you are at NEXT FUNCTION No.=.
Method A:
Jump directly to a specificFunction by entering the
Number of the function youWant
You confirm the selectionWith ENTER (YES)Pushbutton.
Page No. 03Page No.05
6. SET PROGRAMSET NO?
7. DISPLAY TIMES?
8. DISPLAY REAL TIME?
9. PROGRAMSET NO?
10. RAPCON-24 ADDRESS?
11. RESET ALARM?
7
NEXT FUNCTION NO =
ENTER
YES
NEXT FUNCTION NO =7
7 DISPLAY TIMES?
12. SET MOTOR LABEL?
8/13/2019 Rapcon-24 Usermanual-[1]
8/31
Method B:
Step from function toFunction by pushing
The SET FUNCTIONPushbutton repeatedlyUntil desired functionIs obtained.
NOTE:
To reach a function withFunction no. 1 to 6 theRAPCON-24 must be inLOCAL mode.
Push the pushbuttonLOCAL so that theLight Emitting DiodeIn the pushbutton light.
NOTE:To reach function no.2 to 6 also have to
answer the password.
You will automaticallyGet function No.2 afterAnswering the password.
Page No.06
NEXT FUNCTION NO =
7 DISPLAY TIMES?
8 DISPLAY REAL TIME?
SET
FUNCTION
SET
FUNCTION
LOCAL
LOCAL
8/13/2019 Rapcon-24 Usermanual-[1]
9/31
5.1.1 Using Password
This function will only appear if the RAPPER is in LOCAL mode. The Password isfactory set and there is on provision to set a new Password. To know the set Passwordrefer Appendix-A Password is required to reach the set function of no.2 to 6.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the pushbutton ENTER (YES)and PASSWORD=appearson the display.
Give the Password code,Consisting of 4 numbers,On the numerical push-Button, e,g,
Confirm by pushing theENTER (YES) pushbutton.
Page No. 07
1 PASSWORD?
ENTERYES
PASSWORD =
1
2
3
4
PASSWORD = ****
ENTER
YES
8/13/2019 Rapcon-24 Usermanual-[1]
10/31
5.1.2 Setting Rapper Times
Refer the function Using Password also.
In this function you set the different times for each motor. During Power ON, all thetimes will be set as per the Program Set No.01 as default. Set times will be valid untilyou set new times or charge the Program Set No.(Ref. The function SETPROGRAMSET NO.). The rapper motor will not start to operate according to set time ifthe rapper is not selected in AUTO ON.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER (YES)Pushbutton.
Give the desired rapper no. (1-24)On the numerical pushbuttons.
. And push the ENTER (YES)pushbutton. The display answerswith START TIME =hh:mm.
Press CLEAR (OFF)Pushbutton to erase theOld time.
Page No. 08
2 SET RAPPER TIMES?
ENTER
YES
RAPPER NO
2
RAPPER NO: 2
ENTER
YES
START TIME =09.00
CLEAR
OFF START TIME =
8/13/2019 Rapcon-24 Usermanual-[1]
11/31
Give the new time byThe numerical pushbuttons.
Valid value is 00:00 to
23:59
Confirm by pushing ENTER (YES)Pushbutton.
Repeat time Will appear on theDisplay. If you want to change the
Repeat time(hh:mm), do the sameAs for the setting time. Valid value
Is 00:01 to 24:00
Otherwise push ENTER (YES)Pushbutton and..
.run time (mm:ss) will appearon the display. To change the run time
do the same as for setting timeValid value is 00:01 to 59:59
To leave the SET RAPPER TIMESPress SET FUNCTION pushbuttonUntil next function appears.
Page No.09
0
9
2
7
START TIME = 09:27
ENTER
YES
RAPEAT TIME = 00:06
ENTER
YES
RUN TIME = 00:00
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
12/31
5.1.3 Setting Real Time
Refer the function Using Password also
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER (YES) pushButton and the display showsThe real date and time.
If you want to change date pushThe ENTER (YES) push buttonAgain.
Press CLEAR (OFF) to eraseThe old date and
Page No.10
3. SET REAL TIME?
ENTERYES
1995.01.15 10:23,45
ENTER
YES
SET DATE 1995.01.15
CLEAR
OFF
SET DATE: . .
8/13/2019 Rapcon-24 Usermanual-[1]
13/31
.give new date by thenumerical pushbuttons.
Confirm by pushing ENTER (YES)Pushbutton. If you dont want to change
The date push ENTER (YES) push-Button for the next function.
Set time will appear on the display.If you want to change the time, do
The same as for setting date.
To leave the SET REAL TIME pressSET FUNCTION pushbutton untilnext function appears.
Page No.11
1
2
7
SET DATE 1995.01.27
ENTER
YES
SET TIME 10:24,12
SET
FUNCTION
9
8/13/2019 Rapcon-24 Usermanual-[1]
14/31
5.1.4 Starting and stopping a rapper
Refer the function Using Password also. This function allows the operator to set therequired rapping motors in auto sequencing (as per the rapping program set) mode.During power ON, the motors As per the project configuration will be set ON, as default.(Refer Appendix-A.)
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER (YES) pushbutton.
Give the desired rapper number(1 24) on the numerical push-button
.and push the ENTER (YES)Pushbutton. The display nowReplies with ON or OFF.
Push the 1(ON) Pushbutton forON. The rapper will now stop &
Start according to set new times &The MOTOR NO on RAPCON-24Panel ligts.
Push the CLEAR (OFF) Push-
Button for OFF. The rapper willNot any longer operate according
To set times i,e., the rapper hasbeen shut off.
Page No.12
4 SET AUTO ON/OFF?
ENTERYES
RAPPER NO
2
RAPPER NO 2
ENTER
YES
RAPPER NO 2 OFF
1ON
RAPPER NO 2 ON
CLEAROFF
RAPPER NO 2 OFF
8/13/2019 Rapcon-24 Usermanual-[1]
15/31
To have the SET AUTO ON/OFF
Press the SET FUNCTION push-
Button until next function appears.
5.1.5 Starting and stopping a Rapper Manually
Refer to the function Using Password also. In this function you can start a rapper
manually, independent of set times. After start the Rapper will run continuously until itis shut off and if the Rapper is set to AUTO ON it continues to operate according to sertime. If manual runtime exceeds 10 minutes an alarm will appear as warning.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER (YES) pushbutton.
Give the desired rapper number(1 24) on the numerical push-button
.and push the ENTER (YES)Pushbutton. The display now
Replies with ON or OFF.
Push the 1(ON) Pushbutton forON.(start) The rapper will now Startrunning continuously until you pushthe CLEAR (OFF) push button forOFF (stop) . Now the rapper is setto AUTO ON , the rapper continuesto operate according to set times
Page No.13
SET
FUNCTION
ENTERYES
RAPPER NO
2RAPPER NO 2
ENTER
YES
RAPPER NO 2 OFF
1ON
RAPPER NO 2 ON
8/13/2019 Rapcon-24 Usermanual-[1]
16/31
Push the CLEAR (OFF) Push-Button for OFF. The rapper will
Not any longer operate according
To set times i,e., the rapper hasbeen shut off.
To have the SET MANUAL ON/OFF
Press the SET FUNCTION push-Button until next function appears.
5.1.6 Setting Program Set No.
Refer the function Using Password also The RAPCON is pre- programmed with numberof program sets to operate the RAPCON depending upon the ESP field availability. Anydesired program set among the available program sets can be selected. The existing starttime , repeat time and run time of all the rappers are replaced with the set of new timesas per the selected program set. According the rappers are switched over to new timingswith out any disturbance to the ESP operation, During power ON the PROGRAM SETNo. 01 is loaded as default set number.
EVENT/OPERATION PUSHBUTTON DISPALY
Push the ENTER(YES)push-Button.
Push the CLEAR(OFF) PUSH-Button to erase old program setOn. And.give new program set no.,By pressing the numerical push-
button. Valid value is 1 to X.(for X ref. Maximum Set Nos.,in Appendix-B.)
Page No.14
6 SET PROGRAMEST NO ?
ENTER
YESPROGRAMSET NO = 1
CLEAR
OFF
2
PROGRAMSET NO . = 2
CLEAR
OFF
RAPPER NO 2 OFF
SETFUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
17/31
Confirm by pushing ENTER(YES)Pushbutton.
To leave the SET PROGRAMSETFunction pushbutton next function
Appears.
5.1.7 Checking the Rapper Times
The function does not require password.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER(YES) Push-Button
Give the desired rapper no.(1-24)
On the numerical pushbutton.
and push the ENTER(YES)
pushbutton. The display nowreplies with START TIME=hh:mm.
To continue push the ENTER(YES) pushbuttonENTERYES
Page No. 15
ENTER
YES
7 DISPLAY TMES?
ENTER
YES
RAPPER NO =
2RAPPER NO =2
ENTER
YES
STSART TIME = 00:00
RAPEAT TIME = 00:06
ENTER
YES
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
18/31
The display now replies withREPEAT RIME =hh:mm
To continue push the ENTER(YES) pushbutton.
The display now replies with
N RIME =mm:ss
To leave the DISPLAY TIMES
Press SET FUNCTION push-Button until next function appears.
5.1.8 Checking the Real Time
This function does not require any password.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER(YES)pushbutton
The display then shows theReal date and time.
To leave DISPLAY REAL
TIME press SET FUNCTIONPushbutton until next function
Appears.
Page No. 16
ENTER
YES
RUN TIME = 01: 00
8 DISPLAY REAL TIME?
ENTER
YES
1995.01.15 10:35,15
SET
FUNCTION
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
19/31
5.1.9Checking the RAPCON-24 address
This function does not require any password
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER(YES) pushbutton
To leave the RAPCON-24 ADDRESSPress SET FUNCTION until nextFunction appears.
NOTE:RAPCON-24 address is required to be set when the RAPCON-24 is communicating
with BHELs Integrated Operating System. The RAPCON-24 Address is set using DIPswitch (SWI) provided in the CPU card of the RAPCON-24. The following table showsthe switch position for various addresses.
Address set at factory - 1
Address Set at factory = 1
Page No.17
9 RAPCON-24 ADDRESS?
ENTER
YES
RAPCON-24 ADDRESS = 1
Maximum Address Acceptable =161 2 3 4 ADDRESS
OFF OFF OFF OFF 1
ON OFF OFF OFF 2OFF ON OFF OFF 3
ON ON OFF OFF 4OFF OFF ON OFF 5ON OFF ON OFF 6OFF ON ON OFF 7ON ON ON OFF 8OFF OFF OFF ON 9ON OFF OFF ON 10OFF ON OFF ON 11ON ON OFF ON 12OFF OFF ON ON 13ON OFF ON ON 14OFF ON ON ON 15ON ON ON ON 16
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
20/31
5.1.10 Checking Program Set No.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the ENTER(YES) Pushbutton.
To leave the PROGRAMSET NO. pressSET FUNCTION pushbutton until nextFunction appears.
5.1.11Alarm Actions
This function does not require any password.
EVENT/OPERATION PUSHBUTTON DISPLAY
Note the type of alarm and
What rappers are affected.
To remedy the alarm referTo plant instruction manual.
Select function No.11
Push the ENTER(YES)Pushbutton.
Give the rapper no., affected(1-24) on the numerical push-
buttons.
Page No.18
10 PROGRAM SET NO?
ENTER
YES
PROGRAM SET NO = 1
11 RESET ALARM?
ENTER
YESRAPPER NO
2 RAPPER NO. 2
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
21/31
Push the ENTER(YES)
Pushbutton.
To reset the alarm pushCLEAR (OFF) pushbutton.
The display then changes fromALARM to------------- and the
Summation alarm are reset.
To leave the RESET ALARMPress SET FUNCTION pushButton until the NEXTFUNCTION =appears on theDisplay.
5.1.12 Set/View Motor label
This function does not require passwordEVENT/OPERATION PUSHBUTTON DISPLAY
Select function No.12
To VIEW
Press ENTER(YES)Pushbutton.
Page No. 19
ENTER
YESRAPPER NO 2 ALARM
CLEAR
OFF
RAPPER NO 2 ------------
12 SET MOTOR LABEL?
ENTERYES
MOTOR No:1
PASS-A CERM-1
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
22/31
Press ENTER(YES)to see next motors assignment
(For every ENTER(YES) keypress, next motor label will beshown)
To SET
Select appropriate motor number using the above procedure
Press CLEAR(OFF)Pushbutton.
Press 1 to change PASSinformation. The built-in passnames are PASS-A, PASS-BPASS-C & PASS-D. 1 key
can be pressed repeatedly toselect one of those pass labels.
Press 2 to change RAPPERTYPE information. The built-inrapper types CERM, EERM & EEGD.2 key can be pressed repeatedly to
select one of those rapper type labels.
Press 3 to change RAPPERNo information. The built-inmotor numbers are 1,2,3,4,5,6,7,8,9,10,11 & 12. 3 keycan be pressed repeatedly toselect one of those rapper number labels.
Page No.20
ENTER
YESMOTOR No:2
PASS-A CERM-2
CLEAR
OFF
MOTOR No:1
( 1 ) ( 2 ) ( 3 )
1
ON
2
3
MOTOR No:1PASS-A ( 2 ) ( 3 )
MOTOR No:1
PASS-A CERM- ( 3 )
MOTOR No:1
PASS-A CERM- 1
8/13/2019 Rapcon-24 Usermanual-[1]
23/31
After setting all three individual labels,Press ENTER (YES) to save the change.
The labels are saved in NVRAM to retain
values even during power-off.
6.0 Standby
This operation requires password to be answered.
EVENT/OPERATION PUSHBUTTON DISPLAY
Push the STANBY pushbuttonAnd Rappers will be shut off.
(Those rappers that for the momentrun according to set run time willcontinue to operate until actualruntime is over and then they willstop)
Push the STANDBY pushbuttonOnce more to override the STAND-BY mode.
(All rappers that have been set toAUTO ON will now continue to
operate according to set times.)
Page No.21
STANDBY
STANDBY
ENTER
YES
8/13/2019 Rapcon-24 Usermanual-[1]
24/31
7.0 System Messages
7.1
EVENT/OPERATION PUSHBUTTON DISPLAY
During startup, VFD display will showRAPCON-24 : MASTER
ALIVE LED will start blinking & ACTIVE LEDwill glow if controller is active ( meant for redundancy)
RAPCON-24 will start functioning based on defaultvalues (company set values) for the first time it isswitched-on. All operating parameters are stored inNVRAM (Non-Volatile RAM) to preserve the systemstatus. For subsequent resets, RAPCON-24 will startfunctioning only from stored set values. The followingare the list of parameters stored in NVRAM
1. Manual Mode2. Auto Mode3. Program Set Number4. Real Time5. User entered rapper times6. Rapper Labels
Push the SET FUNCTION push-button and you will get NEXT-
FUNCTION No= in the display.
Page No. 22
RAPCON-24 : MASTER
RAPCON-24 : MASTER
NEXT FUNCTION NO =
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
25/31
7.2
EVENT/OPERATION PUSHBUTTON DISPLAY
If no action has been performed byThe operator during the last 2 minutes,The RAPCON-24 gives a timeout warningBy the text KEYBORD TIMEOUT
In the display.By pushing any key you will return
To the previous display.
7.3
EVENT/OPERATION PUSHBUTTON DISPLAY
If no action has been performedDuring the last 2 minutes, theRAPCON-24 times out with theDisplay KEYBORD TIMEOUTAnd operator doesnt respond for theNext 2 minutes display shows theReal time and date.
By pushing the SET FUNCTIONPushbutton you will get the displayNEXT FUNCTION No=
Page No. 23
KEYBOARD TIMEOUT
KEYBOARD TIMEOUT
4
1995.01.20 10:15,17
1995.01.20 10:15,17
SET
FUNCTION
8/13/2019 Rapcon-24 Usermanual-[1]
26/31
7.4
EVENT/OPERATION PUSHBUTTON DISPLAY
All invalid values that are entered
Via the keyboard will be indicatedBy the text INPUT OUT OF RANGET!
falashing on the display.
Reset by pushing any key
Note:
Key 4 is an example only.
Page No.24
INPUT OUT OF RANGE!
4
INPUT OUT OF RANGE!
8/13/2019 Rapcon-24 Usermanual-[1]
27/31
8.0 Faultfinding
S.No FAULT CAUSE REMEDY01 Front panel Dark a. Mains power failure
b. Power supply & DigitalI/O card faulty.
a. Check & correct theMains power
b. Change the card
02 Key board LEDS
Are blinking
Faulty CPU card Change the CPU card
03 Alpha-numericalDisplay dark.
VF display faulty Change the VF displayunit.
04 Rapper ERROR LED(s) are glowingpermanently thoughtthe commands areacknowledged by therespective motorModules.
a. Digital Buffer Cardfaulty
b. Power supply and Dig.I/O card faulty.
a. Change Digital bufferCard
b. Change power supplyand Dig. I/O Card
05 Motor ON commandIs not excetended
a. Relay Card faultyb. Power supply and DIG.
I/O Card faulty
a. Change the relay Cardb. Change the power
supply and DIG. I/OCard.
06 Serial CommunicationWith other sub-unitsareNot established
a. Break in serial loop
b. CPU card faulty
a. Check the loop andpolarity, if there is anyproblem correct it.Check the Dats
Communication cardcable. If faulty change
it.b. Change the CPU card.
Page No.25
8/13/2019 Rapcon-24 Usermanual-[1]
28/31
9.0 RAPCON-24 General Scheme
1. Serial Communication -Receive
APPENDIX - A
1. Serial Communication - Receive
2. Serial Communicaiton - Transmit
3. Sum Alarm - External Annunciation
4. 24V AC(INPUT)
5. Pontential free NO contact To extend commands to Rapping Motors (Max 24)
6. Digital Inputs - To receive ack. from Rapping Motors (Max 24)(FOR DETAILED SCHEME REFER TO THE RAPCON-24 PANEL WIRINGDRAWING)
Page No. 26
P.S.& I/O
CARD
RAPCON-24
DATA ADDRESS.I/O CONTROL BUS FLAT RIBBON CABLE
DISPLAYCARD
CPUCARD
DIGITAL
BUFFER CARD
65
RAPPER-24REALY CARD
DATA
COMMUNICATION
1 2 3 4
8/13/2019 Rapcon-24 Usermanual-[1]
29/31
APPENDIX-A
RAPCON-24 DATA
PROJECT: UNIT: PASS/BUS SECTION:
NO.OF COLLECTING RAPPING MOTORS (CERM)
NO. OF EMTTING RAPPING MOTORS (EERM)
NO. OF CERM CONTROLLED BY ONE RELAY:
NO. OF EERM CONTROLLED BY ON RELAY:
IS GD RAPPING MOTOR AVAILABLE:
ALLOCATION OF NUMBERS TO RAPPING MOTORS
MOTORNO
MOTOR FIELD MOTORNO
MOTOR FIELD
1 13
2 14
3 15
4 16
5 17
6 18
7 19
8 20
9 21
10 22
11 23
12 24
RAPCON-24 SL.NO :
PROGRAM VERSION:RAPCON-24 PASSWORD:
Page No. 27
8/13/2019 Rapcon-24 Usermanual-[1]
30/31
APPENDIX-B
RAPPING FREQUENCY CHART
1. Rapping frequency for emitting rapping :__raps/hr
2. Rapping frequency for last field collecting rapping motor : __raps/___ hr.
3. Rapping frequency for GD rapping motor :___raps/hr
PROGRAM SETS WITH RESPECT TO FIELD AVILABLITY
0=Field ON: F1,F2,F3Indicates Field No
1=Field OFF.
Prg.SetNo
FIELD STATUS RAPPING FREQUENCYF1 F2 F3 F4 F5 F6 F1 F2 F3 F4 F5 F6
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
1617
18
19
20
21
22
23
24
25
26
8/13/2019 Rapcon-24 Usermanual-[1]
31/31
27
28
29
30
31
32
33
34
35
36
37
38
39
4041
4243
4345
46
47
48
49
50
515253
5455
5657
58
59
60
61
62
63
64