BELAJAR MEMBACA GAMBAR SKEMATIK Dok/Syamsuriat/2004 PRINSIP KERJA RANGKAIAN KONTROL DAN RANGKAIAN MOTOR
26

Rangkaian Kontrol Motor

Jan 02, 2016

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

PRINSIP KERJA

RANGKAIAN KONTROL

DAN

RANGKAIAN MOTOR

Page 2: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Cara menjalankan Motor

Tekan “ Saklar-On”

Page 3: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Cara menjalankan Motor

Coil Kontaktor bekerja

Page 4: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Kontak akan menutup

Cara menjalankan Motor

Coil Kontaktor bekerja

Page 5: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Motor operasi

Tangan dilepas

Page 6: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Motor tetap operasi

Page 7: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Menyetop MotorTekan Saklar “Off”

Page 8: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Coil hilang tegangan

Kontak membukaSaklar

“Off” terbuka

Page 9: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Motor Stop

Kontak membuka

Page 10: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Tangan dilepas

Page 11: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Motor siap dioperasikan kembali

Page 12: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Over load bekerja

KontakOverload akanmembuka

PRINSIP KERJA

OVER LOAD

Motor sedang operasi terjadi gangguan

beban lebih

Page 13: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Kontakmembuka

Coil hilang tegangan Netral

Kontak membuka

Page 14: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Motor stop

Kontak terbuka

Page 15: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Kontak over load masih

terbuka/belum direset

Motor tidak bisa operasi

Page 16: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Reset Over load

Page 17: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Kontak over load menutup

kembali

Page 18: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

M

Kontaktor

Over load

Electro

motor

380 / 220 V

Push Buttonswitch

3

On

Off

Coil

Rangkaian kembali ke posisi

semula (siap operasi)

Page 19: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

RSTN

Saklar PushButton

Over load

380 / 220 V

coilKontaktor

Off

On Peralatan rangkaian kontrol meliputi :

1. Saklar push button (On & Off)

2. Coil kontaktor = 220 V AC

3. Saklar NO (normally open) kontaktor

4. Saklar NC (normally close) over load

5. Kabel-kabel kontrol

GAMBAR RANGKAIAN KONTROL

Page 20: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

GAMBAR RANGKAIAN MOTORRSTN

MElectro motor

380 / 220 V

3

Peralatan rangkaian Motor :

1. Kabel-kabel kontrol

2. Kontak NO kontaktor

3. Over load

4. Electro motor

5. Sumber tegangan AC 3 fasa Kontak NO

Over Load

Kontaktor

Page 21: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

GAMBAR RANGKAIAN SAAT TOMBOL “ON” DITEKAN

RSTN

M

Kontaktormenutup

Over load

Motoroperasi

380 / 220 V

3

On

Off

Kondisi rangkaian saat :

1. Tangan masih menekan “Saklar-On”

2. Motor sudah Operasi

Coil

Page 22: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

GAMBAR RANGKAIAN SAAT MOTOR SEDANG OPERASI

RSTN

M

Kontaktormenutup

Over load

Motoroperasi

380 / 220 V

3

On

Off

Kondisi rangkaian saat:

1. Motor sedang operasi,

2.Tangan sudah melepas “Saklar On”

Coil

Page 23: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

•Jika beban motor berlebih (over load) maka kontak NC akan membuka rangkaian kontrol dan motor menjadi stop.

• Fungsi over load untuk mencegah kerusakan pada belitan motor.

•Over load harus disetting lebih kecil dari arus nominal belitan motor.

•Jika over load bekerja, motor harus diperiksa.

•Untuk mengoperasikan kembali : Tombol reset pada over load harus ditekan, agar kontak NC kembali keposisi semula (menutup).

RANGKAIAN MOTOR OVER LOAD

RSTN

Kontaktor

Over load

Motor

380 / 220 V

On

Off

Coil

M3

Jika beban motor lebih, kontak

akan membuka

Page 24: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

MERUBAH PUTARAN MOTOR 3 FASA

RSTN

M

Kontak-tor

Overload

Motor

380 / 220 V

3

On

Off

Coil

RSTN

Kontak-tor

Overload

Motor

380 / 220 V

3

Off

Coil

M3

On

Motor putar kiri Motor putar kanan

Page 25: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

Tegangan coil : 220 volt AC (fasa –netral)

Tegangan coil : 380 volt AC (fasa –fasa)

TEGANGAN COIL KONTAKTOR (AC)

RSTN

M

Overload

Motor

380 / 220 V

3

On

Off

Coil

RSTN

M

Kontak-tor

Overload

Motor

380 / 220 V

3

On

Off

CoilKontak-tor

Rangkaian kontrol 220V AC. Rangkaian kontrol 380V AC.

Page 26: Rangkaian Kontrol Motor

BELAJAR MEMBACA GAMBAR SKEMATIK

Dok/Syamsuriat/2004

TEGANGAN COIL (DC)

RSTN

M

Kontak-tor

Overload

Motor

380 / 220 VAC

3

On

Off

Coil

+_48 VDC R

STN

M

Kontak-tor

Overload

Motor

380 / 220 VAC

3

On

Off

Coil

+_110 VDC

Rangkaian Kontrol teganan DC 48Volt Rangkaian Kontrol teganan DC 110 Volt

Tegangan coil : 48 VDC

Tegangan coil : 110 VDC