Top Banner
RELION® 670 SERIES Railway application RER670 Version 2.2 IEC Application manual
460

Railway application RER670 Version 2.2 IEC ... - ABB

Mar 14, 2023

Download

Documents

Khang Minh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Railway application RER670 Version 2.2 IEC ... - ABB

RELION® 670 SERIES— Railway application RER670 Version 2.2 IEC Application manual

Page 2: Railway application RER670 Version 2.2 IEC ... - ABB
Page 3: Railway application RER670 Version 2.2 IEC ... - ABB

Document ID: 1MRK 506 375-UENIssued: May 2017

Revision: -Product version: 2.2

© Copyright 2017 ABB. All rights reserved

Page 4: Railway application RER670 Version 2.2 IEC ... - ABB

Copyright

This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license andmay be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographicsoftware written/developed by: Eric Young ([email protected]) and Tim Hudson([email protected]).

TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

Page 5: Railway application RER670 Version 2.2 IEC ... - ABB

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.

Page 6: Railway application RER670 Version 2.2 IEC ... - ABB

Conformity

This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandard EN 60255-26 for the EMC directive, and with the product standards EN60255-1 and EN 60255-27 for the low voltage directive. The product is designed inaccordance with the international standards of the IEC 60255 series.

Page 7: Railway application RER670 Version 2.2 IEC ... - ABB

Table of contents

Section 1 Introduction.....................................................................17This manual...................................................................................... 17Intended audience............................................................................ 17Product documentation.....................................................................18

Product documentation set..........................................................18Document revision history........................................................... 19Related documents......................................................................19

Document symbols and conventions................................................20Symbols.......................................................................................20Document conventions................................................................21

IEC 61850 edition 1 / edition 2 mapping...........................................22

Section 2 Application......................................................................25General IED application....................................................................25Main protection functions..................................................................26Back-up protection functions............................................................ 27Control and monitoring functions......................................................28Communication.................................................................................33Basic IED functions.......................................................................... 35

Section 3 Configuration..................................................................37Description of configuration RER670............................................... 37

Introduction..................................................................................37Description of configuration – transformer protectionapplication in compensated networks.................................... 38Description of configuration – transformer protectionapplication in solidly earthed networks...................................39Description of configuration – line protection application incompensated networks.......................................................... 40Description of configuration – line protection application insolidly earthed networks.........................................................41

Section 4 Analog inputs..................................................................43Introduction.......................................................................................43Setting guidelines............................................................................. 43

Setting of the phase reference channel.......................................44Example................................................................................. 44

Setting of current channels..........................................................44Example 1.............................................................................. 45Example 2.............................................................................. 45Example 3.............................................................................. 46

Table of contents

Railway application RER670 2.2 IEC 1Application manual

Page 8: Railway application RER670 Version 2.2 IEC ... - ABB

Examples on how to connect, configure and set CT inputsfor most commonly used CT connections.............................. 48Example on how to connect a star connected two-phaseCT set to the IED....................................................................50Example how to connect single-phase CT to the IED............ 53

Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protection IED.. 54Setting of voltage channels......................................................... 55

Example................................................................................. 55Examples how to connect, configure and set VT inputs formost commonly used VT connections....................................55Examples on how to connect a two phase-to-earthconnected VT to the IED........................................................ 56Example on how to connect a residually connected IED....... 57Example on how to connect a neutral point VT to the IED.....59

Section 5 Local HMI....................................................................... 61Display..............................................................................................62LEDs.................................................................................................64Keypad............................................................................................. 65Local HMI functionality..................................................................... 67

Protection and alarm indication................................................... 67Parameter management .............................................................68Front communication...................................................................69

Section 6 Differential protection..................................................... 71Low impedance restricted earth fault protection REFPDIF ............. 71

Identification................................................................................ 71Application...................................................................................71

Transformer winding, solidly earthed..................................... 72CT earthing direction.............................................................. 73Railway specific applications for REFPDIF function...............73

Setting guidelines........................................................................ 73Setting and configuration........................................................73Settings.................................................................................. 74

Single-phase railway power transformer differential protectionT1PPDIF...........................................................................................74

Identification................................................................................ 74Application...................................................................................74Setting guidelines........................................................................ 75

Restrained and unrestrained differential protection................75Elimination of zero sequence currents................................... 78Inrush restraint methods.........................................................78Overexcitation restraint method............................................. 78Protections based on the directional criterion........................ 79

Table of contents

2 Railway application RER670 2.2 IECApplication manual

Page 9: Railway application RER670 Version 2.2 IEC ... - ABB

Setting examples.........................................................................79Application examples............................................................. 81How to wire the transformer differential protection to theIED using CTs........................................................................ 86

Section 7 Impedance protection.....................................................91Automatic switch onto fault logic ZCVPSOF ................................... 91

Identification................................................................................ 91Application...................................................................................91Setting guidelines........................................................................ 91

Distance protection, quadrilateral characteristic ZRWPDIS............. 93Identification................................................................................ 93Application...................................................................................93

Compensated earthing systems.............................................94Solidly earthed systems....................................................... 109High impedance earthing systems....................................... 120

Setting examples.......................................................................131Compensated earthed systems............................................131Solidly earthed systems....................................................... 138

Underimpedance protection for railway transformers ZGTPDIS.... 145Identification.............................................................................. 145Application.................................................................................145

Zone 1 operation.................................................................. 147Zone 2 operation.................................................................. 147Zone 3 operation.................................................................. 147

Setting guidelines...................................................................... 148Catenary Protection...................................................................150Wrong phase coupling protection..............................................150

Section 8 Current protection.........................................................153Instantaneous phase overcurrent protection 2-phase outputPHPIOC..........................................................................................153

Identification.............................................................................. 153Application.................................................................................153Setting guidelines...................................................................... 153

Meshed network without parallel line................................... 154Two-step directional phase overcurrent protection D2PTOC......... 156

Identification.............................................................................. 156Application.................................................................................156Setting guidelines...................................................................... 157

Settings for step 1................................................................ 160Settings for step 2................................................................ 162

Instantaneous residual overcurrent protection EFRWPIOC........... 162Identification.............................................................................. 162

Table of contents

Railway application RER670 2.2 IEC 3Application manual

Page 10: Railway application RER670 Version 2.2 IEC ... - ABB

Application.................................................................................163Setting guidelines...................................................................... 163

Two step residual overcurrent protection EF2PTOC......................166Identification.............................................................................. 166Application.................................................................................166Setting guidelines...................................................................... 167

Settings for each step (x = 1 and 2)..................................... 167Common settings................................................................. 1692nd harmonic restrain...........................................................170

Sensitive directional residual overcurrent and power protectionSDEPSDE ..................................................................................... 170

Identification.............................................................................. 170Application.................................................................................170Setting guidelines...................................................................... 172

Thermal overload protection, one time constant, Celsius LPTTR.. 180Identification.............................................................................. 181Application.................................................................................181Setting guideline........................................................................182

Breaker failure protection CCRWRBRF......................................... 184Application.................................................................................184Setting guidelines...................................................................... 184

Overcurrent protection with binary release BRPTOC.....................187Identification.............................................................................. 187Application.................................................................................187Setting guidelines...................................................................... 187

Tank overcurrent protection TPPIOC............................................. 188Identification.............................................................................. 188Application.................................................................................188Setting guidelines...................................................................... 190

Section 9 Voltage protection........................................................ 193Two step undervoltage protection U2RWPTUV............................. 193

Identification.............................................................................. 193Application.................................................................................193Setting guidelines...................................................................... 194

Disconnected equipment detection...................................... 194Power supply quality ........................................................... 194Voltage instability mitigation................................................. 194Backup protection for power system faults...........................194Settings for two step undervoltage protection...................... 194

Two step overvoltage protection O2RWPTOV............................... 196Identification.............................................................................. 196Application.................................................................................196Setting guidelines...................................................................... 197

Table of contents

4 Railway application RER670 2.2 IECApplication manual

Page 11: Railway application RER670 Version 2.2 IEC ... - ABB

Equipment protection, transformers..................................... 197Power supply quality............................................................ 197The following settings can be done for the two stepovervoltage protection.......................................................... 197

Two step residual overvoltage protection ROV2PTOV ................. 199Identification.............................................................................. 199Application.................................................................................199Setting guidelines...................................................................... 199

High impedance earthed systems........................................ 199Solidly earthed systems....................................................... 200Settings for two step residual overvoltage protection...........200

Section 10 Frequency protection....................................................203Underfrequency protection SAPTUF ............................................. 203

Identification.............................................................................. 203Application.................................................................................203Setting guidelines...................................................................... 203

Section 11 Secondary system supervision.....................................205Current circuit supervision CCSSPVC............................................205

Identification.............................................................................. 205Application.................................................................................205Setting guidelines...................................................................... 206

Fuse failure supervision FRWSPVC...............................................206Identification.............................................................................. 206Application.................................................................................206Setting guidelines...................................................................... 207

DeltaU and DeltaI detection................................................. 207Dead line detection...............................................................208

Sudden current and voltage change..........................................208

Section 12 Control..........................................................................209Synchrocheck, energizing check, and synchronizing SESRSYN...209

Identification.............................................................................. 209Application.................................................................................209

Synchronizing.......................................................................209Synchrocheck.......................................................................211Energizing check.................................................................. 213External fuse failure..............................................................214

Application examples.................................................................215Single circuit breaker with single busbar.............................. 216

Setting guidelines...................................................................... 216Autoreclosing for railway system SMBRREC ................................ 221

Identification.............................................................................. 221

Table of contents

Railway application RER670 2.2 IEC 5Application manual

Page 12: Railway application RER670 Version 2.2 IEC ... - ABB

Application.................................................................................221Auto reclosing operation Off and On.................................... 224Start auto reclosing and conditions for start of a reclosingcycle..................................................................................... 224Start auto reclosing from circuit breaker open information...224Blocking of the auto recloser................................................ 225Control of the auto reclosing dead time for shot 1................225Long trip signal..................................................................... 225Maximum number of reclosing shots....................................225Auto reclosing reclaim timer................................................. 225Pulsing of the circuit breaker closing command and counter226Transient fault.......................................................................226Permanent fault and reclosing unsuccessful signal............. 226Lock-out initiation................................................................. 226Thermal overload protection holding the auto recloser back228

Setting guidelines...................................................................... 228Configuration........................................................................ 228Auto recloser settings...........................................................232

Apparatus control APC................................................................... 235Application.................................................................................235

Bay control QCBAY..............................................................239Switch controller SCSWI...................................................... 240Switches SXCBR/SXSWI..................................................... 241Proxy for signals from switching device via GOOSEXLNPROXY..........................................................................242Reservation function (QCRSV and RESIN)......................... 244

Interaction between modules.....................................................246Setting guidelines...................................................................... 248

Bay control (QCBAY)........................................................... 249Switch controller (SCSWI)....................................................249Switch (SXCBR/SXSWI)...................................................... 250Proxy for signals from switching device via GOOSEXLNPROXY..........................................................................251Bay Reserve (QCRSV).........................................................251Reservation input (RESIN)................................................... 251

Interlocking .................................................................................... 252Configuration guidelines............................................................253Interlocking for line bay ABC_LINE .......................................... 253

Application............................................................................253Signals from bypass busbar................................................. 254Signals from bus-coupler......................................................255Configuration setting............................................................ 257

Interlocking for bus-coupler bay ABC_BC ................................ 258Application............................................................................259

Table of contents

6 Railway application RER670 2.2 IECApplication manual

Page 13: Railway application RER670 Version 2.2 IEC ... - ABB

Configuration........................................................................ 259Signals from all feeders........................................................259Signals from bus-coupler......................................................261Configuration setting............................................................ 263

Interlocking for transformer bay AB_TRAFO ............................ 264Application............................................................................264Signals from bus-coupler......................................................265Configuration setting............................................................ 265

Interlocking for bus-section breaker A1A2_BS..........................266Application............................................................................266Signals from all feeders........................................................266Configuration setting............................................................ 269

Interlocking for bus-section disconnector A1A2_DC ................ 270Application............................................................................270Signals in single breaker arrangement.................................270Signals in double-breaker arrangement............................... 273Signals in 1 1/2 breaker arrangement.................................. 276

Interlocking for busbar earthing switch BB_ES .........................277Application............................................................................277Signals in single breaker arrangement.................................277Signals in double-breaker arrangement............................... 281Signals in 1 1/2 breaker arrangement.................................. 282

Interlocking for double CB bay DB ........................................... 283Application............................................................................283Configuration setting............................................................ 284

Interlocking for 1 1/2 CB BH .....................................................285Application............................................................................285Configuration setting............................................................ 285

Logic rotating switch for function selection and LHMIpresentation SLGAPC.................................................................... 286

Identification.............................................................................. 286Application.................................................................................286Setting guidelines...................................................................... 287

Selector mini switch VSGAPC........................................................287Identification.............................................................................. 287Application.................................................................................287Setting guidelines...................................................................... 288

Generic communication function for Double Point indicationDPGAPC........................................................................................ 288

Identification.............................................................................. 288Application.................................................................................289Setting guidelines...................................................................... 289

Single point generic control 8 signals SPC8GAPC........................ 289Identification.............................................................................. 290

Table of contents

Railway application RER670 2.2 IEC 7Application manual

Page 14: Railway application RER670 Version 2.2 IEC ... - ABB

Application.................................................................................290Setting guidelines...................................................................... 290

AutomationBits, command function for DNP3.0 AUTOBITS.......... 290Identification.............................................................................. 290Application.................................................................................291Setting guidelines...................................................................... 291

Single command, 16 signals SINGLECMD.................................... 291Identification.............................................................................. 291Application.................................................................................291Setting guidelines...................................................................... 293

Transformer energizing control XENCPOW................................... 294Identification.............................................................................. 294Application.................................................................................294Setting guidelines...................................................................... 295

Setting examples..................................................................296

Section 13 Scheme communication...............................................297Scheme communication logic for distance or overcurrentprotection ZCPSCH........................................................................ 297

Identification.............................................................................. 297Application.................................................................................297

Blocking schemes................................................................ 298Permissive schemes............................................................ 298Intertrip scheme....................................................................301

Setting guidelines...................................................................... 302Blocking scheme.................................................................. 302Permissive underreaching scheme...................................... 302Permissive overreaching scheme........................................ 303Unblocking scheme.............................................................. 303Intertrip scheme....................................................................303

Current reversal and Weak-end infeed logic for distanceprotection 2-phase ZCRWPSCH.................................................... 303

Identification.............................................................................. 303Application.................................................................................303

Current reversal logic........................................................... 303Weak-end infeed logic..........................................................304

Setting guidelines...................................................................... 305Current reversal logic........................................................... 305Weak-end infeed logic..........................................................306

Scheme communication logic for residual overcurrent protectionECPSCH ........................................................................................306

Identification.............................................................................. 306Application.................................................................................306Setting guidelines...................................................................... 307

Table of contents

8 Railway application RER670 2.2 IECApplication manual

Page 15: Railway application RER670 Version 2.2 IEC ... - ABB

Current reversal and weak-end infeed logic for residualovercurrent protection ECRWPSCH...............................................308

Identification.............................................................................. 308Application.................................................................................308

Fault current reversal logic................................................... 308Weak-end infeed logic..........................................................309

Setting guidelines...................................................................... 309Current reversal....................................................................309Weak-end infeed.................................................................. 311

Section 14 Logic.............................................................................313Tripping logic SMPPTRC ...............................................................313

Identification.............................................................................. 313Application.................................................................................313

Tripping................................................................................ 313Lock-out................................................................................314Example of directional data.................................................. 314Blocking of the function block...............................................316

Setting guidelines...................................................................... 316Trip matrix logic TMAGAPC........................................................... 316

Identification.............................................................................. 316Application.................................................................................316Setting guidelines...................................................................... 316

Logic for group alarm ALMCALH....................................................317Identification.............................................................................. 317Application.................................................................................317Setting guidelines...................................................................... 317

Logic for group alarm WRNCALH.................................................. 317Identification.............................................................................. 317

Application............................................................................318Setting guidelines................................................................. 318

Logic for group indication INDCALH...............................................318Identification.............................................................................. 318

Application............................................................................318Setting guidelines................................................................. 318

Configurable logic blocks................................................................318Application.................................................................................319Setting guidelines...................................................................... 319

Configuration........................................................................ 319Fixed signal function block FXDSIGN............................................ 320

Identification.............................................................................. 320Application.................................................................................320

Boolean 16 to Integer conversion B16I.......................................... 321Identification.............................................................................. 321

Table of contents

Railway application RER670 2.2 IEC 9Application manual

Page 16: Railway application RER670 Version 2.2 IEC ... - ABB

Application.................................................................................322Boolean to integer conversion with logical node representation,16 bit BTIGAPC.............................................................................. 323

Identification.............................................................................. 323Application.................................................................................323

Integer to Boolean 16 conversion IB16.......................................... 324Identification.............................................................................. 324Application.................................................................................324

Integer to Boolean 16 conversion with logic node representationITBGAPC........................................................................................325

Identification.............................................................................. 325Application.................................................................................325

Elapsed time integrator with limit transgression and overflowsupervision TEIGAPC.....................................................................326

Identification.............................................................................. 326Application.................................................................................327Setting guidelines...................................................................... 327

Comparator for integer inputs - INTCOMP..................................... 327Identification.............................................................................. 327Application.................................................................................328Setting guidelines...................................................................... 328Setting example.........................................................................328

Comparator for real inputs - REALCOMP...................................... 329Identification.............................................................................. 329Application.................................................................................329Setting guidelines...................................................................... 329Setting example.........................................................................330

Section 15 Monitoring.....................................................................331Measurement..................................................................................331

Identification.............................................................................. 331Application.................................................................................331Zero clamping............................................................................333Setting guidelines...................................................................... 334

Setting examples..................................................................337Gas medium supervision SSIMG................................................... 340

Identification.............................................................................. 340Application.................................................................................340Setting guidelines...................................................................... 340

Liquid medium supervision SSIML................................................. 341Identification.............................................................................. 341Application.................................................................................341Setting guidelines...................................................................... 342

Breaker monitoring SSCBR............................................................342

Table of contents

10 Railway application RER670 2.2 IECApplication manual

Page 17: Railway application RER670 Version 2.2 IEC ... - ABB

Identification.............................................................................. 342Application.................................................................................343Setting guidelines...................................................................... 345

Setting procedure on the IED............................................... 346Event function EVENT....................................................................347

Identification.............................................................................. 347Application.................................................................................347Setting guidelines...................................................................... 347

Disturbance report DRPRDRE....................................................... 348Identification.............................................................................. 348Application.................................................................................348Setting guidelines...................................................................... 349

Recording times................................................................... 351Binary input signals.............................................................. 352Analog input signals............................................................. 353Sub-function parameters...................................................... 353Consideration....................................................................... 354

Logical signal status report BINSTATREP..................................... 355Identification.............................................................................. 355Application.................................................................................355Setting guidelines...................................................................... 355

Limit counter L4UFCNT..................................................................356Identification.............................................................................. 356Application.................................................................................356Setting guidelines...................................................................... 356

Running hour-meter TEILGAPC.....................................................356Identification.............................................................................. 356Application.................................................................................357Setting guidelines...................................................................... 357

Fault locator RWRFLO................................................................... 357Identification.............................................................................. 357Application.................................................................................357Setting guidelines...................................................................... 359

Setting example....................................................................360

Section 16 Metering....................................................................... 363Pulse-counter logic PCFCNT......................................................... 363

Identification.............................................................................. 363Application.................................................................................363Setting guidelines...................................................................... 363

Function for energy calculation and demand handling ETPMMTR 364Identification.............................................................................. 364Application.................................................................................364Setting guidelines...................................................................... 365

Table of contents

Railway application RER670 2.2 IEC 11Application manual

Page 18: Railway application RER670 Version 2.2 IEC ... - ABB

Section 17 Ethernet-based communication....................................367Access point................................................................................... 367

Application.................................................................................367Setting guidelines...................................................................... 367

Redundant communication.............................................................368Identification.............................................................................. 368Application.................................................................................369Setting guidelines...................................................................... 370

Merging unit....................................................................................371Application.................................................................................371Setting guidelines...................................................................... 372

Routes............................................................................................ 372Application.................................................................................372Setting guidelines...................................................................... 372

Section 18 Station communication.................................................373Communication protocols............................................................... 373IEC 61850-8-1 communication protocol......................................... 373

Application IEC 61850-8-1.........................................................373Setting guidelines...................................................................... 375Horizontal communication via GOOSE..................................... 375

Sending data........................................................................ 375Receiving data......................................................................376

IEC/UCA 61850-9-2LE communication protocol............................ 377Introduction................................................................................377Setting guidelines...................................................................... 379

Specific settings related to the IEC/UCA 61850-9-2LEcommunication..................................................................... 380Loss of communication when used with LDCM....................380Setting examples for IEC/UCA 61850-9-2LE and timesynchronization.................................................................... 384

IEC 61850 quality expander QUALEXP.................................... 389LON communication protocol......................................................... 390

Application.................................................................................390MULTICMDRCV and MULTICMDSND..................................... 392

Identification......................................................................... 392Application............................................................................392Setting guidelines................................................................. 392

SPA communication protocol......................................................... 392Application.................................................................................392Setting guidelines...................................................................... 393

IEC 60870-5-103 communication protocol..................................... 395Application.................................................................................395

Table of contents

12 Railway application RER670 2.2 IECApplication manual

Page 19: Railway application RER670 Version 2.2 IEC ... - ABB

Functionality......................................................................... 395Design.................................................................................. 396

Settings......................................................................................398Settings for RS485 and optical serial communication.......... 399Settings from PCM600......................................................... 400

Function and information types................................................. 402DNP3 Communication protocol...................................................... 403

Application.................................................................................403

Section 19 Remote communication................................................405Binary signal transfer......................................................................405

Identification.............................................................................. 405Application.................................................................................405

Communication hardware solutions..................................... 406Setting guidelines...................................................................... 407

Section 20 Security........................................................................ 411Authority status ATHSTAT............................................................. 411

Application.................................................................................411Self supervision with internal event list INTERRSIG...................... 411

Application.................................................................................411Change lock CHNGLCK................................................................. 412

Application.................................................................................412Denial of service SCHLCCH/RCHLCCH ....................................... 413

Application.................................................................................413Setting guidelines...................................................................... 413

Section 21 Basic IED functions...................................................... 415IED identifiers TERMINALID.......................................................... 415

Application.................................................................................415Product information PRODINF....................................................... 415

Application.................................................................................415Factory defined settings............................................................ 415

Measured value expander block RANGE_XP................................ 416Identification.............................................................................. 416Application.................................................................................417Setting guidelines...................................................................... 417

Parameter setting groups............................................................... 417Application.................................................................................417Setting guidelines...................................................................... 418

Rated system frequency PRIMVAL................................................ 418Identification.............................................................................. 418Application.................................................................................418Setting guidelines...................................................................... 418

Table of contents

Railway application RER670 2.2 IEC 13Application manual

Page 20: Railway application RER670 Version 2.2 IEC ... - ABB

Global base values GBASVAL....................................................... 418Identification.............................................................................. 418Application.................................................................................419Setting guidelines...................................................................... 419

Signal matrix for binary inputs SMBI.............................................. 419Application.................................................................................419Setting guidelines...................................................................... 419

Signal matrix for binary outputs SMBO ......................................... 419Application.................................................................................420Setting guidelines...................................................................... 420

Signal matrix for mA inputs SMMI.................................................. 420Application.................................................................................420Setting guidelines...................................................................... 420

Signal matrix for analog inputs SMAI............................................. 420Application.................................................................................420Frequency values...................................................................... 421Setting guidelines...................................................................... 421

Test mode functionality TESTMODE..............................................422Application.................................................................................422

IEC 61850 protocol test mode..............................................422Setting guidelines...................................................................... 423

Time synchronization TIMESYNCHGEN........................................423Application.................................................................................423Setting guidelines...................................................................... 424

System time..........................................................................425Synchronization....................................................................425Process bus IEC/UCA 61850-9-2LE synchronization.......... 426

Section 22 Requirements...............................................................429Current transformer requirements.................................................. 429

Current transformer basic classification and requirements....... 429Conditions..................................................................................431Fault current.............................................................................. 432Secondary wire resistance and additional load......................... 432General current transformer requirements................................ 432Rated equivalent secondary e.m.f. requirements......................433

Breaker failure protection..................................................... 433Restricted earth fault protection (low impedance differential)434

Current transformer requirements for CTs according to otherstandards...................................................................................436

Current transformers according to IEC 61869-2, class P, PR436Current transformers according to IEC 61869-2, class PX,PXR (and old IEC 60044-6, class TPSand old British Standard, class X)........................................ 437

Table of contents

14 Railway application RER670 2.2 IECApplication manual

Page 21: Railway application RER670 Version 2.2 IEC ... - ABB

Current transformers according to ANSI/IEEE..................... 437Voltage transformer requirements.................................................. 438SNTP server requirements............................................................. 438PTP requirements...........................................................................439Sample specification of communication requirements for theprotection and control terminals in digital telecommunicationnetworks......................................................................................... 439IEC/UCA 61850-9-2LE Merging unit requirements ....................... 440

Section 23 Glossary....................................................................... 443

Table of contents

Railway application RER670 2.2 IEC 15Application manual

Page 22: Railway application RER670 Version 2.2 IEC ... - ABB

16

Page 23: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provide assistance forcalculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for planning,pre-engineering and engineering.

The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand communication principles.

1MRK 506 375-UEN - Section 1Introduction

Railway application RER670 2.2 IEC 17Application manual

Page 24: Railway application RER670 Version 2.2 IEC ... - ABB

1.3 Product documentation

1.3.1 Product documentation set

IEC07000220-4-en.vsd

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gD

eins

talli

ng &

dis

posa

l

Application manual

Operation manual

Installation manual

Engineering manual

Communication protocol manual

Cyber security deployment guideline

Technical manual

Commissioning manual

IEC07000220 V4 EN

Figure 1: The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs using thevarious tools available within the PCM600 software. The manual providesinstructions on how to set up a PCM600 project and insert IEDs to the projectstructure. The manual also recommends a sequence for the engineering of protectionand control functions, LHMI functions as well as communication engineering for IEC60870-5-103, IEC 61850, DNP3, LON and SPA.

The installation manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in the chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for the checkingof external circuitry and energizing the IED, parameter setting and configuration as

Section 1 1MRK 506 375-UEN -Introduction

18 Railway application RER670 2.2 IECApplication manual

Page 25: Railway application RER670 Version 2.2 IEC ... - ABB

well as verifying settings by secondary injection. The manual describes the process oftesting an IED in a substation which is not in service. The chapters are organized in thechronological order in which the IED should be commissioned. The relevantprocedures may be followed also during the service and maintenance activities.

The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for the monitoring, controlling andsetting of the IED. The manual also describes how to identify disturbances and how toview calculated and measured power grid data to determine the cause of a fault.

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provide assistance forcalculating settings.

The technical manual contains operation principle descriptions, and lists functionblocks, logic diagrams, input and output signals, setting parameters and technicaldata, sorted per function. The manual can be used as a technical reference during theengineering phase, installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.

The point list manual describes the outlook and properties of the data points specificto the IED. The manual should be used in conjunction with the correspondingcommunication protocol manual.

The cyber security deployment guideline describes the process for handling cybersecurity when communicating with the IED. Certification, Authorization with rolebased access control, and product engineering for cyber security related events aredescribed and sorted by function. The guideline can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.

1.3.2 Document revision historyDocument revision/date History–/May 2017 First release

1.3.3 Related documentsDocuments related to RER670 Document numbersApplication manual 1MRK 506 375-UEN

Commissioning manual 1MRK 506 377-UEN

Product guide 1MRK 506 378-BEN

Technical manual 1MRK 506 376-UEN

Type test certificate 1MRK 506 378-TEN

1MRK 506 375-UEN - Section 1Introduction

Railway application RER670 2.2 IEC 19Application manual

Page 26: Railway application RER670 Version 2.2 IEC ... - ABB

670 series manuals Document numbersOperation manual 1MRK 500 127-UEN

Engineering manual 1MRK 511 398-UEN

Installation manual 1MRK 514 026-UEN

Communication protocol manual, DNP3 1MRK 511 391-UUS

Communication protocol manual, IEC60870-5-103

1MRK 511 394-UEN

Communication protocol manual, IEC 61850Edition 2

1MRK 511 393-UEN

Communication protocol manual, LON 1MRK 511 395-UEN

Communication protocol manual, SPA 1MRK 511 396-UEN

Point list manual, DNP3 1MRK 511 397-UUS

Accessories guide 1MRK 514 012-BEN

Cyber security deployment guideline 1MRK 511 399-UEN

Connection and Installation components 1MRK 513 003-BEN

Test system, COMBITEST 1MRK 512 001-BEN

Application guide, Communication set-up 1MRK 505 382-UEN

1.4 Document symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.

The warning icon indicates the presence of a hazard which couldresult in personal injury.

The caution hot surface icon indicates important information orwarning about the temperature of product surfaces.

Class 1 Laser product. Take adequate measures to protect the eyes anddo not view directly with optical instruments.

The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence of

Section 1 1MRK 506 375-UEN -Introduction

20 Railway application RER670 2.2 IECApplication manual

Page 27: Railway application RER670 Version 2.2 IEC ... - ABB

a hazard which could result in corruption of software or damage toequipment or property.

The information icon alerts the reader of important facts andconditions.

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. It is importantthat the user fully complies with all warning and cautionary notices.

1.4.2 Document conventions

• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using thepush button icons.For example, to navigate between the options, use and .

• HMI menu paths are presented in bold.For example, select Main menu/Settings.

• LHMI messages are shown in Courier font.For example, to save the changes in non-volatile memory, select Yes and press

.• Parameter names are shown in italics.

For example, the function can be enabled and disabled with the Operation setting.• Each function block symbol shows the available input/output signal.

• the character ^ in front of an input/output signal name indicates that thesignal name may be customized using the PCM600 software.

• the character * after an input signal name indicates that the signal must beconnected to another function block in the application configuration toachieve a valid application configuration.

• Logic diagrams describe the signal logic inside the function block and arebordered by dashed lines.• Signals in frames with a shaded area on their right hand side represent

setting parameter signals that are only settable via the PST, ECT or LHMI.• If an internal signal path cannot be drawn with a continuous line, the suffix

-int is added to the signal name to indicate where the signal starts andcontinues.

• Signal paths that extend beyond the logic diagram and continue in anotherdiagram have the suffix ”-cont.”

1MRK 506 375-UEN - Section 1Introduction

Railway application RER670 2.2 IEC 21Application manual

Page 28: Railway application RER670 Version 2.2 IEC ... - ABB

Illustrations are used as an example and might show other productsthan the one the manual describes. The example that is illustrated isstill valid.

1.5 IEC 61850 edition 1 / edition 2 mapping

Function block names are used in ACT and PST to identify functions. Respectivefunction block names of Edition 1 logical nodes and Edition 2 logical nodes are shownin the table below.

Table 1: IEC 61850 edition 1 / edition 2 mapping

Function block name Edition 1 logical nodes Edition 2 logical nodesAGSAL AGSAL

SECLLN0AGSAL

ALMCALH ALMCALH ALMCALH

ALTIM - ALTIM

ALTMS - ALTMS

ALTRK - ALTRK

BRPTOC BRPTOC BRPTOC

BTIGAPC B16IFCVI BTIGAPC

CCRWRBRF CCRWRBRF CCRWRBRF

CCSSPVC CCSRDIF CCSSPVC

CMMXU CMMXU CMMXU

CMSQI CMSQI CMSQI

CVMMXN CVMMXN CVMMXN

D2PTOC D2LLN0D2PTOCPH1PTRC

D2PTOCPH1PTRC

DPGAPC DPGGIO DPGAPC

DRPRDRE DRPRDRE DRPRDRE

ECPSCH ECPSCH ECPSCH

ECRWPSCH ECRWPSCH ECRWPSCH

EF2PTOC EF2LLN0EF2PTRCEF2RDIRGEN2PHARPH1PTOC

EF2PTRCEF2RDIRGEN2PHARPH1PTOC

EFPIOC EFPIOC EFPIOC

ETPMMTR ETPMMTR ETPMMTR

ITBGAPC IB16FCVB ITBGAPC

L4UFCNT L4UFCNT L4UFCNT

LPHD LPHD -

Table continues on next page

Section 1 1MRK 506 375-UEN -Introduction

22 Railway application RER670 2.2 IECApplication manual

Page 29: Railway application RER670 Version 2.2 IEC ... - ABB

Function block name Edition 1 logical nodes Edition 2 logical nodesLPTTR LPTTR LPTTR

MVGAPC MVGGIO MVGAPC

O2RWPTOV GEN2LLN0O2RWPTOVPH1PTRC

O2RWPTOVPH1PTRC

PHPIOC PHPIOC PHPIOC

QCBAY QCBAY BAY/LLN0

QCRSV QCRSV QCRSV

RCHLCCH RCHLCCH RCHLCCH

REFPDIF REFPDIF REFPDIF

ROV2PTOV GEN2LLN0PH1PTRCROV2PTOV

PH1PTRCROV2PTOV

RWRFLO - RWRFLO

SAPTUF SAPTUF SAPTUF

SCHLCCH SCHLCCH SCHLCCH

SCILO SCILO SCILO

SCSWI SCSWI SCSWI

SDEPSDE SDEPSDE SDEPSDESDEPTOCSDEPTOVSDEPTRC

SESRSYN RSY1LLN0AUT1RSYNMAN1RSYNSYNRSYN

AUT1RSYNMAN1RSYNSYNRSYN

SLGAPC SLGGIO SLGAPC

SMBRREC SMBRREC SMBRREC

SMPPTRC SMPPTRC SMPPTRC

SP16GAPC SP16GGIO SP16GAPC

SPC8GAPC SPC8GGIO SPC8GAPC

SPGAPC SPGGIO SPGAPC

SSCBR SSCBR SSCBR

SSIMG SSIMG SSIMG

SSIML SSIML SSIML

SXCBR SXCBR SXCBR

SXSWI SXSWI SXSWI

T1PPDIF - T1PPDIFT1PPHART1PPTRC

TEIGAPC TEIGGIO TEIGAPCTEIGGIO

TEILGAPC TEILGGIO TEILGAPC

TMAGAPC TMAGGIO TMAGAPC

Table continues on next page

1MRK 506 375-UEN - Section 1Introduction

Railway application RER670 2.2 IEC 23Application manual

Page 30: Railway application RER670 Version 2.2 IEC ... - ABB

Function block name Edition 1 logical nodes Edition 2 logical nodesTPPIOC TPPIOC TPPIOC

U2RWPTUV GEN2LLN0PH1PTRCU2RWPTUV

PH1PTRCU2RWPTUV

VMMXU VMMXU VMMXU

VMSQI VMSQI VMSQI

VNMMXU VNMMXU VNMMXU

VSGAPC VSGGIO VSGAPC

WRNCALH WRNCALH WRNCALH

XENCPOW - XENCPOW

ZCPSCH ZCPSCH ZCPSCH

ZCRWPSCH ZCRWPSCH ZCRWPSCH

ZCVPSOF ZCVPSOF ZCVPSOF

ZGTPDIS ZGTLLN0ZGPDISZGPTRC

ZGPDISZGPTRC

ZRWPDIS - PSRWPDISZRWPDISZRWPTRC

Section 1 1MRK 506 375-UEN -Introduction

24 Railway application RER670 2.2 IECApplication manual

Page 31: Railway application RER670 Version 2.2 IEC ... - ABB

Section 2 Application

2.1 General IED application

RER670 is used for the protection, control and monitoring of transmission lines,catenary lines or transformers in two- and single-phase 16.7Hz, 50Hz and 60Hzrailway applications. It supports isolated, compensated and solidly earthed networks.

The line protection covers distance protection functions with quadrilateral or circularstarting characteristic. The six zones have fully independent measuring and settingwhich gives high flexibility for all types of lines. Load encroachment and adaptivereach compensation are included.

Communication to the remote ends can be used for even more selective protection.Backup functions like directional earth fault or overcurrent as well as breaker failureprotection are equally available as autoreclosure and synchrocheck functions.

A line fault locator for up to 10 line segments supports efficient remedial actions afterfaults on the transmission line.

The transformer protection covers transformer differential protection for two-phase totwo-phase as well as two-phase to one-phase transformers. Besides the transformerdifferential protection, a wide range of backup functions are available.

A very fast transformer tank protection helps to avoid damages in case of short circuitsto the transformer tank.

The transformer energizing functions allow smooth energizing of transformers tominimize stress on equipment and power system which operate at 16.7Hz.

The control functionality can be combined backup, line or transformer protection touse RER670 as protection, control or combined protection and control IED.

The autorecloser co-operates with the synchrocheck function with high-speed ordelayed reclosing.

Logic is prepared with a graphical tool. The advanced logic capability allows, forexample, to combine protection functions with logic gates or to create customsolutions.

Disturbance recording is available to allow post-fault analysis after primarydisturbances.

RER670 provides IEC 60870-5-103 as well as IEC 61850 communication to asubstation automation system or, in case of IEC 61850, also for horizontalcommunication between IEDs. Redundant communication is obtained through the

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 25Application manual

Page 32: Railway application RER670 Version 2.2 IEC ... - ABB

built-in PRP and HSR features which can be used in star or ringbus architectures.Further, also communication between IEDs in different substations is supported usingthe IEEE C37.94 standard. Up to 192 channels for intertrip and binary signals areavailable per LDCM communication module in the communication between theIEDs.

The IED can be used in applications with the IEC/UCA 61850-9-2LE process bus withup to eight Merging Units (MU). Each MU has eight analogue channels, four currentand four voltages. Conventional input transformer module and Merging Unit channelscan be mixed freely in your application.

RER670 can be ordered with three functional packages:

• A50: Transformer protection (main and backup functions)• B60: Line distance protection (main and backup functions)• H50: Control

The packages A50 and B60 contain all main and backup protection functions fortransformer or line protection. Only one of them can be ordered for a single IED. Bothpackages can be extended with additional functions like synchrocheck (H51) andautoreclosure (H52). Also full control functionality can be added to these packages.

The package H50 describes a control IED, which can be extended with synchrocheck,autoreclosure and backup protection (C60).

More optional functions can be added as described in the next chapter.

The number and type of analog inputs and binary input/output as well as the mA inputand communication modules can be selected when ordering.

The following tables list all the functions available in the IED. Thosefunctions that are not exposed to the user or do not need to beconfigured are not described in this manual.

2.2 Main protection functions

Table 2: Example of quantities

2 = number of basic instances0-3 = option quantities3-A03 = optional function included in packages A03 (refer to ordering details)

Section 2 1MRK 506 375-UEN -Application

26 Railway application RER670 2.2 IECApplication manual

Page 33: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 orfunction name

ANSI Function description Railway

RER670

Differential protection

REFPDIF 87N Restricted earth fault protection, low impedance 2-A501-B60

T1PPDIF 87T Transformer differential protection, two windings 2-A50

Impedance protection

ZCVPSOF Automatic switch onto fault logic, voltage and current based 1-B60

ZGTPDIS 21T Underimpedance protection for generators and transformers 2-A501-B60

ZRWPDIS 21 Distance protection, quadrilateral characteristic 1-B60

2.3 Back-up protection functions

IEC 61850 orfunction name

ANSI Function description Railway

RER670

Current protection

PHPIOC 50 Instantaneous phase overcurrent protection 2-C60

D2PTOC 51_67 Directional phase overcurrent protection, two steps 8-C60

EFRWPIOC 50N Instantaneous residual overcurrent protection 1-C60

EF2PTOC 51N67N1)

Directional residual overcurrent protection, two steps 3-C60

SDEPSDE 67N Sensitive directional residual overcurrent and powerprotection

1-C60

LPTTR 26 Thermal overload protection, one time constant 2-C60

CCRWRBRF 50BF Breaker failure protection 2-C60

BRPTOC 50 Overcurrent protection with binary release 8-C60

TPPIOC 64 Transformer tank overcurrent protection 1-A501-B60

Voltage protection

U2RWPTUV 27 Undervoltage protection, two steps 2-C60

O2RWPTOV 59 Overvoltage protection, two steps 2-C60

ROV2PTOV 59N Two step residual overvoltage protection 2-C60

Frequency protection

SAPTUF 81L Underfrequency protection 2-C60

1) 67N requires voltage

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 27Application manual

Page 34: Railway application RER670 Version 2.2 IEC ... - ABB

2.4 Control and monitoring functions

IEC 61850 orfunction name

ANSI Function description Railway

RER670

Control

SESRSYN 25 Synchrocheck, energizing check and synchronizing 1-H51

SMBRREC 79 Autorecloser 1-H52

APC10 3 Control functionality for a single bay, max 10 objects(1CB), including interlocking (see Table 4)

1-H37

APC15 3 Control functionality for a single bay, max 15 objects(2CB), including interlocking (see Table 5)

1-H38

QCBAY Bay control 1

LOCREM Handling of LR-switch positions 1

LOCREMCTRL LHMI control of PSTO 1

SXCBR Circuit breaker 6

TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 1-H53

TCLYLTC 84 Tap changer control and supervision, 32 binaryinputs

1-H54

SLGAPC Logic rotating switch for function selection and LHMIpresentation

15

VSGAPC Selector mini switch 30

DPGAPC Generic communication function for Double Pointindication

16

SPC8GAPC Single point generic control function 8 signals 5

AUTOBITS Automation bits, command function for DNP3.0 2

SINGLECMD Single command, 16 signals 4

I103CMD Function commands for IEC 60870-5-103 1

I103GENCMD Function commands generic for IEC 60870-5-103 35

I103POSCMD IED commands with position and select for IEC60870-5-103

50

I103POSCMDV IED direct commands with position for IEC60870-5-103

50

I103IEDCMD IED commands for IEC 60870-5-103 1

I103USRCMD Function commands user defined for IEC60870-5-103

3

XENCPOW 25T Transformer energization control 1-A50/1-H55

Secondary systemsupervision

CCSSPVC 87 Current circuit supervision 3-G04

FRWSPVC Fuse failure supervision 3-C60

Logic

SMPPTRC 94 Tripping logic 8-C60

Table continues on next page

Section 2 1MRK 506 375-UEN -Application

28 Railway application RER670 2.2 IECApplication manual

Page 35: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 orfunction name

ANSI Function description Railway

RER670

SMAGAPC General start matrix block 12-C60

STARTCOMB Start combinator 32

TMAGAPC Trip matrix logic 6

ALMCALH Logic for group alarm 5

WRNCALH Logic for group warning 5

INDCALH Logic for group indication 5

AND, GATE, INV,LLD, OR,PULSETIMER,RSMEMORY,SRMEMORY,TIMERSET, XOR

Basic configurable logic blocks (see Table 3) 40-420

ANDQT,INDCOMBSPQT,INDEXTSPQT,INVALIDQT,INVERTERQT,ORQT,PULSETIMERQT,RSMEMORYQT,SRMEMORYQT,TIMERSETQT,XORQT

Configurable logic blocks Q/T (see Table 6) 1-L01

AND, GATE, INV,LLD, OR,PULSETIMER,RSMEMORY,SLGAPC,SRMEMORY,TIMERSET,VSGAPC, XOR

Extension logic package (see Table 7) 1-L02

FXDSIGN Fixed signal function block 1

B16I Boolean to integer conversion, 16 bit 18

BTIGAPC Boolean to integer conversion with logical noderepresentation, 16 bit

16

IB16 Integer to Boolean 16 conversion 14

ITBGAPC Integer to Boolean 16 conversion with Logic Noderepresentation

16

TEIGAPC Elapsed time integrator with limit transgression andoverflow supervision

12

INTCOMP Comparator for integer inputs 30

REALCOMP Comparator for real inputs 30

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 29Application manual

Page 36: Railway application RER670 Version 2.2 IEC ... - ABB

Table 3: Total number of instances for basic configurable logic blocks

Basic configurable logic block Total number of instancesAND 280

GATE 40

INV 420

LLD 40

OR 298

PULSETIMER 40

RSMEMORY 40

SRMEMORY 40

TIMERSET 60

XOR 40

Table 4: Number of function instances in APC10

Function name Function description Total number of instancesSCILO Interlocking 10

BB_ES 3

A1A2_BS 2

A1A2_DC 3

ABC_BC 1

BH_CONN 1

BH_LINE_A 1

BH_LINE_B 1

DB_BUS_A 1

DB_BUS_B 1

DB_LINE 1

ABC_LINE 1

AB_TRAFO 1

SCSWI Switch controller 10

SXSWI Circuit switch 9

QCRSV Apparatus control 2

RESIN1 1

RESIN2 59

POS_EVAL Evaluation of position indication 10

XLNPROXY Proxy for signals from switchingdevice via GOOSE

12

GOOSEXLNRCV GOOSE function block toreceive a switching device

12

Section 2 1MRK 506 375-UEN -Application

30 Railway application RER670 2.2 IECApplication manual

Page 37: Railway application RER670 Version 2.2 IEC ... - ABB

Table 5: Number of function instances in APC15

Function name Function description Total number of instancesSCILO Interlocking 15

BB_ES 3

A1A2_BS 2

A1A2_DC 3

ABC_BC 1

BH_CONN 1

BH_LINE_A 1

BH_LINE_B 1

DB_BUS_A 1

DB_BUS_B 1

DB_LINE 1

ABC_LINE 1

AB_TRAFO 1

SCSWI Switch controller 15

SXSWI Circuit switch 14

QCRSV Apparatus control 2

RESIN1 1

RESIN2 59

POS_EVAL Evaluation of position indication 15

XLNPROXY Proxy for signals from switchingdevice via GOOSE

20

GOOSEXLNRCV GOOSE function block toreceive a switching device

20

Table 6: Total number of instances for configurable logic blocks Q/T

Configurable logic blocks Q/T Total number of instancesANDQT 120

INDCOMBSPQT 20

INDEXTSPQT 20

INVALIDQT 22

INVERTERQT 120

ORQT 120

PULSETIMERQT 40

RSMEMORYQT 40

SRMEMORYQT 40

TIMERSETQT 40

XORQT 40

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 31Application manual

Page 38: Railway application RER670 Version 2.2 IEC ... - ABB

Table 7: Total number of instances for extended logic package

Extended configurable logic block Total number of instancesAND 180

GATE 49

INV 180

LLD 49

OR 180

PULSETIMER 89

RSMEMORY 40

SLGAPC 74

SRMEMORY 130

TIMERSET 109

VSGAPC 120

XOR 89

IEC 61850 orfunction name

ANSI Function description Railway

RER670

Monitoring

CVMMXN Power system measurement 6

CMMXU Current measurement 10

VMMXU Voltage measurement phase-phase 6

CMSQI Current sequence measurement 6

VMSQI Voltage sequence measurement 6

VNMMXU Voltage measurement phase-earth 6

AISVBAS General service value presentation of analog inputs 1

EVENT Event function 14

DRPRDRE,A1RADR-A4RADR,B1RBDR-B22RBDR

Disturbance report 1

SPGAPC Generic communication function for Single Pointindication

64

SP16GAPC Generic communication function for Single Pointindication 16 inputs

16

MVGAPC Generic communication function for measuredvalues

24

BINSTATREP Logical signal status report 3

RANGE_XP Measured value expander block 66

SSIMG 63 Insulation supervision for gas medium 21

SSIML 71 Insulation supervision for liquid medium 3

SSCBR Circuit breaker condition monitoring 6-M15

Table continues on next page

Section 2 1MRK 506 375-UEN -Application

32 Railway application RER670 2.2 IECApplication manual

Page 39: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 orfunction name

ANSI Function description Railway

RER670

RWRFLO Fault locator, multi section 1-B60

I103MEAS Measurands for IEC 60870-5-103 1

I103MEASUSR Measurands user defined signals for IEC60870-5-103

3

I103AR Function status auto-recloser for IEC 60870-5-103 1

I103EF Function status earth-fault for IEC 60870-5-103 1

I103FLTPROT Function status fault protection for IEC 60870-5-103 1

I103IED IED status for IEC 60870-5-103 1

I103SUPERV Supervison status for IEC 60870-5-103 1

I103USRDEF Status for user defined signals for IEC 60870-5-103 14

L4UFCNT Event counter with limit supervision 30

TEILGAPC Running hour meter 6

Metering

PCFCNT Pulse-counter logic 16

ETPMMTR Function for energy calculation and demandhandling

6

2.5 Communication

IEC 61850 or functionname

ANSI Function description Railway

RER670 Station communication

LONSPA, SPA SPA communication protocol 1

ADE LON communication protocol 1

HORZCOMM Network variables via LON 1

RS485GEN RS485 1

DNPGEN DNP3.0 communication general protocol 1

CHSERRS485 DNP3.0 for EIA-485 communication protocol 1

CH1TCP, CH2TCP,CH3TCP, CH4TCP

DNP3.0 for TCP/IP communication protocol 1

CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol 1

MSTSER DNP3.0 serial master 1

MST1TCP,MST2TCP,MST3TCP,MST4TCP

DNP3.0 for TCP/IP communication protocol 1

DNPFREC DNP3.0 fault records for TCP/IP and EIA-485communication protocol

1

IEC 61850-8-1 IEC 61850 1

Table continues on next page

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 33Application manual

Page 40: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 or functionname

ANSI Function description Railway

RER670

GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59

GOOSEBINRCV GOOSE binary receive 11

GOOSEDPRCV GOOSE function block to receive a double point value 40

GOOSEINTRCV GOOSE function block to receive an integer value 24

GOOSEMVRCV GOOSE function block to receive a measurand value 56

GOOSESPRCV GOOSE function block to receive a single point value 40

MULTICMDRCV,MULTICMDSND

Multiple command and transmit 60/10

OPTICAL103 IEC 60870-5-103 Optical serial communication 1

RS485103 IEC 60870-5-103 serial communication for RS485 1

AGSAL Generic security application component 1

LD0LLN0 IEC 61850 LD0 LLN0 1

SYSLLN0 IEC 61850 SYS LLN0 1

LPHD Physical device information 1

PCMACCS IED configuration protocol 1

SECALARM Component for mapping security events on protocols suchas DNP3 and IEC103

1

FSTACCS Field service tool access 1

IEC 61850-9-2 Process bus communication, 8 mergingunits

1-P30

ACTIVLOG Activity logging 1

ALTRK Service tracking 1

PRP IEC 62439-3 Parallel redundancy protocol 1-P23

HSR IEC 62439-3 High-availability seamless redundancy 1-P24

PTP Precision time protocol 1

FRONTSTATUS Access point diagnostic for front Ethernet port 1

SCHLCCH Access point diagnostic for non-redundant Ethernet port 6

RCHLCCH Access point diagnostic for redundant Ethernet ports 3

DHCP DHCP configuration for front access point 1

QUALEXP IEC 61850 quality expander 96

Remote communication

BinSignRec1_1BinSignRec1_2BinSignReceive2

Binary signal transfer receive 3/3/6

BinSignTrans1_1BinSignTrans1_2BinSignTransm2

Binary signal transfer transmit 3/3/6

BinSigRec1_12MBinSigRec1_22MBinSigTran1_12MBinSigTran1_22M

Binary signal transfer, 2Mbit receive/transmit 3

LDCMTRN Transmission of analog data from LDCM 1

Table continues on next page

Section 2 1MRK 506 375-UEN -Application

34 Railway application RER670 2.2 IECApplication manual

Page 41: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 or functionname

ANSI Function description Railway

RER670

LDCMTRN_2M Transmission of analog data from LDCM, 2Mbit 6

LDCMRecBinStat1LDCMRecBinStat2LDCMRecBinStat3

Receive binary status from remote LDCM 6/3/3

LDCMRecBinS2_2M Receive binary status from LDCM, 2Mbit 3

LDCMRecBinS3_2M Receive binary status from remote LDCM, 2Mbit 3

Scheme communication

ZCPSCH 85 Scheme communication logic for distance or overcurrentprotection

1-B60

ZCRWPSCH 85 Current reversal and weak-end infeed logic for distanceprotection

1-B60

ECPSCH 85 Scheme communication logic for residual overcurrentprotection

1-B60

ECRWPSCH 85 Current reversal and weak-end infeed logic for residualovercurrent protection

1-B60

2.6 Basic IED functions

Table 8: Basic IED functions

IEC 61850 or functionname

Description

INTERRSIG Self supervision with internal event list

TIMESYNCHGEN Time synchronization module

BININPUT,SYNCHCAN,SYNCHGPS,SYNCHCMPPS,SYNCHLON,SYNCHPPH,SYNCHPPS, SNTP,SYNCHSPA

Time synchronization

PTP Precision time protocol

TIMEZONE Time synchronization

IRIG-B Time synchronization

SETGRPS Number of setting groups

ACTVGRP Parameter setting groups

TESTMODE Test mode functionality

CHNGLCK Change lock function

SMBI Signal matrix for binary inputs

SMBO Signal matrix for binary outputs

SMMI Signal matrix for mA inputs

Table continues on next page

1MRK 506 375-UEN - Section 2Application

Railway application RER670 2.2 IEC 35Application manual

Page 42: Railway application RER670 Version 2.2 IEC ... - ABB

IEC 61850 or functionname

Description

SMAI1 - SMAI12 Signal matrix for analog inputs

ATHSTAT Authority status

ATHCHCK Authority check

AUTHMAN Authority management

FTPACCS FTP access with password

GBASVAL Global base values for settings

ALTMS Time master supervision

ALTIM Time management

COMSTATUS Protocol diagnostic

Table 9: Local HMI functions

IEC 61850 or functionname

ANSI Description

LHMICTRL Local HMI signals

LANGUAGE Local human machine language

SCREEN Local HMI Local human machine screen behavior

FNKEYTY1–FNKEYTY5FNKEYMD1–FNKEYMD5

Parameter setting function for HMI in PCM600

LEDGEN General LED indication part for LHMI

OPENCLOSE_LED LHMI LEDs for open and close keys

GRP1_LED1–GRP1_LED15GRP2_LED1–GRP2_LED15GRP3_LED1–GRP3_LED15

Basic part for CP HW LED indication module

Section 2 1MRK 506 375-UEN -Application

36 Railway application RER670 2.2 IECApplication manual

Page 43: Railway application RER670 Version 2.2 IEC ... - ABB

Section 3 Configuration

3.1 Description of configuration RER670

3.1.1 Introduction

All IEDs shall be configured with the help of the application configuration tool inPCM600. The IED can be adapted to special applications and special logic can bedeveloped, such as logic for automatic opening of disconnectors and closing of ringbays, automatic load transfer from one busbar to the other, and so on.

On request, ABB is available to support the configuration work, either directly or todo the design checking. Example configurations are given in following sections as aguide what can be achieved using RER670.

1MRK 506 375-UEN - Section 3Configuration

Railway application RER670 2.2 IEC 37Application manual

Page 44: Railway application RER670 Version 2.2 IEC ... - ABB

3.1.1.1 Description of configuration – transformer protection application incompensated networks

QB1

W1-QA1

WA1RER670 V 2.2 – Application for Transformer Protection

¾-19“-Casing, 1xBIM, 1xSOM, 1xMIM 12AI (7I+5U)

CT

VT

BR PTOC

51 IBR>

SMP PTRC

94 1→0

VN MMXU

MET UN

FRW SPVC

U>/I<

L PTTR

26 θ>

CCRW RBRF

50BF 2I>BF

Temp.-Sensor

Other Functions available from the function library

optional Functions

ROV2 PTOV

59N 2(U0>)

S CSWI

3 Control

S XSWI

3 Control

S XCBR

3 Control

Q CRSV

3 Control

S CILO

3 Control

PH PIOC

50 2I>>

EFRW PIOC

50N IN>>

O2RW PTOV

59 2(2U>)

Q CBAY

3 Control

S SIML

71

W2-QA1

L2

VT

L1-L2

ZGT PDIS

21 Z<

C MSQI

MET Isqi

W1

W2

T1P PDIF

87T Id/I>

Transducer

D2 PTOC

51_67 2(2I>)

D2 PTOC

51_67 2(2I>)

L1, nicht benutzt

C MMXU

MET I

SA PTUF

81 f<

L2

CT

L2CV MMXN

MET P/Q

TP PIOC

64 IN>>>

BF Prot.

C MMXU

MET I

D2 PTOC

51_67 2(2I>)

D2 PTOC

51_67 2(2I>)

FRW SPVC

U>/I<

CCRW RBRF

50BF 2I>BF

EF2 PTOC

51N_67N 2(IN>)

CV MMXN

MET P/Q

I> ASY

SA PTUF

81 f<

U2RW PTUV

27 2(2U<)

V MMXU

MET U

V MSQI

MET Usqi

VN MMXU

MET UN

SMP PTRC

94 1→0

SMP PTRC

94 1→0

SMP PTRC

94 1→0

SMP PTRC

94 1→0

SMP PTRC

94 1→0

Trip 1 HV Trip 2 HV Trip to BBP

Trip 1 LV Trip 2 LV Back-up prot.

4-20 mA

XENC POW

25T POW

67N

SDE PSDE

IN>

REF PDIF

87N IdN/I

L1 L2

T1P PDIF

87T Id/I>

long. Diff Prottransv. Diff Prot.

IEC17000009-1-en.vsdx

IEC17000009 V1 EN

Figure 2: Configuration diagram for transformer protection application incompensated networks

Section 3 1MRK 506 375-UEN -Configuration

38 Railway application RER670 2.2 IECApplication manual

Page 45: Railway application RER670 Version 2.2 IEC ... - ABB

3.1.1.2 Description of configuration – transformer protection application insolidly earthed networks

QB1

W1-QA1

WA1RER670 V2.1 – Application for Transformer Protection

½-19“-casing, 1xIOM, 1xBOM, 1xMIM 12AI (7I+5U)

CT

VT

IEC17000010-1-en.vsdx

BR PTOC

51 IBR>

SMP PTRC

94 1→0

VN MMXU

MET UN

FRW SPVC

U>/I<

L PTTR

26 θ>

CCRW RBRF

50BF 2I>BF

Temp.-Sensor

Other Functions available from the function library

Optional functions

ROV2 PTOV

59N 2(U0>)

S CSWI

3 Control

S XSWI

3 Control

S XCBR

3 Control

Q CRSV

3 Control

S CILO

3 Control

PH PIOC

50 2I>>

EFRW PIOC

50N IN>>

O2RW PTOV

59 2(2U>)

Q CBAY

3 Control

S SIML

71

W2-QA1

L2

VT

L1-L2

ZGT PDIS

21 Z<

C MSQI

MET Isqi

W1

W2

T1P PDIF

87T Id/I>Transducer

D2 PTOC

51_67 2(2I>)

C MMXU

MET I

SA PTUF

81 f<

L2

CT

L2CV MMXN

MET P/Q

TP PIOC

64 IN>>>

BF Logic

C MMXU

MET I

D2 PTOC

51_67 2(2I>)

FRW SPVC

U>/I<

CCRW RBRF

50BF 2I>BF

EF2 PTOC

51N_67N 2(IN>)

CV MMXN

MET P/Q

I> ASY

SA PTUF

81 f<

U2RW PTUV

27 2(2U<)

V MMXU

MET U

V MSQI

MET Usqi

VN MMXU

MET UN

SMP PTRC

94 1→0

Trip 1 HV-side

Trip 1 LV-side

4-20 mA

XENC POW

25T POW

67N

SDE PSDE

IN>

REF PDIF

87N IdN/I

D2 PTOC

51_67 2(2I>)

T1P PDIF

87T Id/I>

D2 PTOC

51_67 2(2I>)

IEC17000010 V1 EN

Figure 3: Configuration diagram for transformer protection application insolidly earthed networks

1MRK 506 375-UEN - Section 3Configuration

Railway application RER670 2.2 IEC 39Application manual

Page 46: Railway application RER670 Version 2.2 IEC ... - ABB

3.1.1.3 Description of configuration – line protection application incompensated networks

QB1

QA1

QB9

QC9

WA1RER670 V2.1 – Application for Line Protection

¾-19“-Casing, 1xBIM, 1xBOM, 12AI (7I+5U)

VT

CT

VT

SMB RREC

79 5(0→1)

IEC17000011-1-en.vsdx

RW RFLO

21FL FL

ZCRW PSCH

85

67N

SDE PSDE

IN>

SES RSYN

25 SC/VC

BR PTOC

51 IBR>

BR PTOC

51 IBR>

Emergency OC

CCS SPVC

∆I

SMP PTRC

94 1→0

ZC PSCH

85

VN MMXU

MET UN

V MSQI

MET Usqi

V MMXU

MET U

CV MMXN

MET P/Q

S SCBR

FRW SPVC

U>/I<

EF2 PTOC

51N(67N) 2(IN>)

L PTTR

26 θ>

CCRW RBRF

50BF 2I>BF

ZRW PDIS

21 2Z<

ZCV PSOF

Temp.-Sensor

Other Functions available from the function library

Optional functions

ROV2 PTOV

59N 2(U0>)

S CSWI

3 Control

S XSWI

3 Control

S XCBR

3 Control

Q CRSV

3 Control

S CILO

3 Control

PH PIOC

50 2I>>

EFRW PIOC

50N IN>>

O2RW PTOV

59 2(2U>)

U2RW PTUV

27 2(2U<)

Q CBAY

3 Control

S SIML

71

GOOSE

IEC17000011 V1 EN

Figure 4: Configuration diagram for line protection application in compensatednetworks

Section 3 1MRK 506 375-UEN -Configuration

40 Railway application RER670 2.2 IECApplication manual

Page 47: Railway application RER670 Version 2.2 IEC ... - ABB

3.1.1.4 Description of configuration – line protection application in solidlyearthed networks

QB1

QA1

QB9

QC9

WA1RER670 V2.1 – Application for Line Protection

1/2-19“-Casing, 1xBIM, 1xBOM, 1xMIM, 12AI (7I+5U)

VT

CT

VT

SMB RREC

79 5(0→1)

IEC17000012-1-en.vsdx

RW RFLO

21FL FL

ZCRW PSCH

85

67N

SDE PSDE

IN>

SES RSYN

25 SC/VC

BR PTOC

51 IBR>

BR PTOC

51 IBR>

Emergency OC

CCS SPVC

∆I

SMP PTRC

94 1→0

ZC PSCH

85

VN MMXU

MET UN

V MSQI

MET Usqi

V MMXU

MET U

CV MMXN

MET P/Q

S SCBR

FRW SPVC

U>/I<

EF2 PTOC

51N(67N) 2(IN>)

L PTTR

26 θ>

CCRW RBRF

50BF 2I>BF

ZRW PDIS

21 2Z<

ZCV PSOF

Other Functions available from the function library

Optional functions

ROV2 PTOV

59N 2(U0>)

S CSWI

3 Control

S XSWI

3 Control

S XCBR

3 Control

Q CRSV

3 Control

S CILO

3 Control

PH PIOC

50 2I>>

EFRW PIOC

50N IN>>

O2RW PTOV

59 2(2U>)

U2RW PTUV

27 2(2U<)

Q CBAY

3 Control

S SIML

71

4-20mAAmb. temp sens.Transducer

EF2 PTOC

51N(67N) 2(IN>)

IEC17000012 V1 EN

Figure 5: Configuration diagram for line protection application in solidlyearthed networks

1MRK 506 375-UEN - Section 3Configuration

Railway application RER670 2.2 IEC 41Application manual

Page 48: Railway application RER670 Version 2.2 IEC ... - ABB

42

Page 49: Railway application RER670 Version 2.2 IEC ... - ABB

Section 4 Analog inputs

4.1 Introduction

Analog input channels must be configured and set properly in order to get correctmeasurement results and correct protection operations. For power measuring, alldirectional and differential functions, the directions of the input currents must bedefined in order to reflect the way the current transformers are installed/connected inthe field ( primary and secondary connections ). Measuring and protection algorithmsin the IED use primary system quantities. Setting values are in primary quantities aswell and it is important to set the data about the connected current and voltagetransformers properly.

Under the Logical Node AISVBAS, the TRM channel for phase angle referencePhaseAngleRef can be defined to facilitate service values reading. This TRMchannel's phase angle will always be forced to zero degrees and remaining analogchannel's phase angle information will be shown in relation to this channel. Duringtesting and commissioning of the IED, the reference channel can be changed tofacilitate testing and service values reading.

The IED has the ability to receive analog values from primaryequipment, that are sampled by Merging units (MU) connected to aprocess bus, via the IEC 61850-9-2 LE protocol.

In RER670 7I+5U TRM is always used. However several variantsexist in order to cover 1A and/or 5A main CTs.

4.2 Setting guidelines

The available setting parameters related to analog inputs aredepending on the actual hardware (TRM) and the logic configurationmade in PCM600.

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 43Application manual

Page 50: Railway application RER670 Version 2.2 IEC ... - ABB

4.2.1 Setting of the phase reference channel

All phase angles are calculated in relation to a defined reference. An appropriateanalog input channel is selected and used as phase reference. The parameterPhaseAngleRef defines the analog channel that is used as phase angle reference.

4.2.1.1 Example

Usually the L1 phase-to-earth voltage connected to the first VT channel number of thetransformer input module (TRM) is selected as the phase reference. The first VTchannel number depends on the type of transformer input module.

For a TRM with 7 current and 5 voltage inputs the first VT channel is 8. The settingPhaseAngleRef=8 shall be used if the phase reference voltage is connected to thatchannel.

4.2.2 Setting of current channels

The direction of a current to the IED is depending on the connection of the CT. Unlessindicated otherwise, the main CTs are supposed to be star connected and can beconnected with the earthing point to the object or from the object. This informationmust be set in the IED. The convention of the directionality is defined as follows: Apositive value of current, power, and so on means that the quantity has the directioninto the object and a negative value means direction out from the object. Fordirectional functions the direction into the object is defined as Forward and thedirection out from the object is defined as Reverse. See Figure 6

A positive value of current, power, and so on (forward) means that the quantity flowstowards the object. A negative value of current, power, and so on (reverse) means thatthe quantity flows away from the object. See Figure 6.

Protected ObjectLine, transformer, etc

ForwardReverse

Definition of directionfor directional functions

Measured quantity ispositive when flowing

towards the object

e.g. P, Q, I

ReverseForward

Definition of directionfor directional functions

e.g. P, Q, IMeasured quantity ispositive when flowing

towards the object

Set parameterCTStarPoint

Correct Setting is"ToObject"

Set parameterCTStarPoint

Correct Setting is"FromObject" en05000456.vsd

IEC05000456 V1 EN

Figure 6: Internal convention of the directionality in the IED

Section 4 1MRK 506 375-UEN -Analog inputs

44 Railway application RER670 2.2 IECApplication manual

Page 51: Railway application RER670 Version 2.2 IEC ... - ABB

With correct setting of the primary CT direction, CTStarPoint set to FromObject orToObject, a positive quantities always flowing towards the protected object and adirection defined as Forward always is looking towards the protected object. Thefollowing examples show the principle.

4.2.2.1 Example 1

Two IEDs used for protection of two objects.

Transformer

protection

Transformer

Line

Line

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional functions

Line protection

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input:

Set parameter

CTStarPoint with

Line as

reference object.

Correct setting is

"FromObject"

IEC05000753=IEC05

000753=1=en=Origin

al[1].vsd

IsIs

Ip Ip Ip

IED IED

IEC05000753 V2 EN

Figure 7: Example how to set CTStarPoint parameters in the IED

Figure 7 shows the normal case where the objects have their own CTs. The settings forCT direction shall be done according to the figure. To protect the line, direction of thedirectional functions of the line protection shall be set to Forward. This means that theprotection is looking towards the line.

4.2.2.2 Example 2

Two IEDs used for protection of two objects and sharing a CT.

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 45Application manual

Page 52: Railway application RER670 Version 2.2 IEC ... - ABB

Transformer

protection

Transformer

Line

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional functions

Line protection

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input:

Set parameter

CTStarPoint with

Line as

reference object.

Correct setting is

"FromObject"

IED IED

IEC05000460 V2 EN

Figure 8: Example how to set CTStarPoint parameters in the IED

This example is similar to example 1, but here the transformer is feeding just one lineand the line protection uses the same CT as the transformer protection does. The CTdirection is set with different reference objects for the two IEDs though it is the samecurrent from the same CT that is feeding the two IEDs. With these settings, thedirectional functions of the line protection shall be set to Forward to look towards theline.

4.2.2.3 Example 3

One IED used to protect two objects.

Section 4 1MRK 506 375-UEN -Analog inputs

46 Railway application RER670 2.2 IECApplication manual

Page 53: Railway application RER670 Version 2.2 IEC ... - ABB

Transformer and

Line protection

Transformer

Line

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ReverseForward

Definition of direction

for directional

line functions

Setting of current input:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

IED

IEC05000461 V2 EN

Figure 9: Example how to set CTStarPoint parameters in the IED

In this example, one IED includes both transformer and line protections and the lineprotection uses the same CT as the transformer protection does. For both current inputchannels, the CT direction is set with the transformer as reference object. This meansthat the direction Forward for the line protection is towards the transformer. To looktowards the line, the direction of the directional functions of the line protection mustbe set to Reverse. The direction Forward/Reverse is related to the reference object thatis the transformer in this case.

If the IED has sufficient number of analog current inputs, an alternative solution isshown in Figure 10. The same currents are fed to two separate groups of inputs and theline and transformer protection functions are configured to the different inputs. TheCT direction for the current channels to the line protection is set with the line asreference object and the directional functions of the line protection shall be set toForward to protect the line.

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 47Application manual

Page 54: Railway application RER670 Version 2.2 IEC ... - ABB

Transformer and

Line protection

Transformer

Line

Setting of current input

for transformer functions:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

ForwardReverse

Definition of direction

for directional

line functions

Setting of current input

for transformer functions:

Set parameter

CTStarPoint with

Transformer as

reference object.

Correct setting is

"ToObject"

Setting of current input

for line functions:

Set parameter

CTStarPoint with

Line as

reference object.

Correct setting is

"FromObject"

IED

IEC05000462 V2 EN

Figure 10: Example how to set CTStarPoint parameters in the IED

4.2.2.4 Examples on how to connect, configure and set CT inputs for mostcommonly used CT connections

Figure 11 defines the marking of current transformer terminals commonly usedaround the world:

In the SMAI function block, you have to set if the SMAI block ismeasuring current or voltage. This is done with the parameter:AnalogInputType: Current/Voltage. The ConnectionType: phase -phase/phase-earth and GlobalBaseSel.

Section 4 1MRK 506 375-UEN -Analog inputs

48 Railway application RER670 2.2 IECApplication manual

Page 55: Railway application RER670 Version 2.2 IEC ... - ABB

ISec

I Pri

S1 (X1)

P1(H1)

P2(H2)

S2 (X2)

P2(H2)

P1(H1)

x x

a) b) c)

en06000641.vsd

S2 (X2) S1 (X1)

IEC06000641 V1 EN

Figure 11: Commonly used markings of CT terminals

Where:

a) is symbol and terminal marking used in this document. Terminals marked with a squareindicates the primary and secondary winding terminals with the same (that is, positive) polarity

b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that forthese two cases the CT polarity marking is correct!

It shall be noted that depending on national standard and utility practices, the ratedsecondary current of a CT has typically one of the following values:

• 1A• 5A

However, in some cases, the following rated secondary currents are used as well:

• 2A• 10A

The IED fully supports all of these rated secondary values.

It is recommended to:

• use 1A rated CT input into the IED in order to connect CTs with1A and 2A secondary rating

• use 5A rated CT input into the IED in order to connect CTs with5A and 10A secondary rating

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 49Application manual

Page 56: Railway application RER670 Version 2.2 IEC ... - ABB

4.2.2.5 Example on how to connect a star connected two-phase CT set to theIED

Figure 12 gives an example about the wiring of a star connected two-phase CT set tothe IED. It gives an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within the IEDas well.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

L1

IL1

IL2

L2

Protected Object

CT 600/5A

Star Connected

IL1

IL2

IED

IEC16000136-1-en.vsdx

1 2

3

4

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5

IN

IEC16000136 V1 EN

Figure 12: Star connected two-phase CT set with star point towards theprotected object

Where:

1) Shows how to connect two individual phase currents from a star connected two-phase CT setto the two CT inputs of the IED.

2) The current inputs are located in the TRM. It shall be noted that for all these current inputs thefollowing setting values shall be entered for the example shown in Figure 12.

• CTprim=600A• CTsec=5A• CTStarPoint=ToObject

Ratio of the first two parameters is only used inside the IED. The third parameter(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.In other words, currents are already measured towards the protected object.

Table continues on next page

Section 4 1MRK 506 375-UEN -Analog inputs

50 Railway application RER670 2.2 IECApplication manual

Page 57: Railway application RER670 Version 2.2 IEC ... - ABB

3) These two connections are the links between the two phase current inputs and the two inputchannels of the preprocessing function block 4).

4) The preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for the two input channels• harmonic content for the two input channels• positive and zero sequence quantities by using the fundamental frequency phasors for

the first two input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For this applicationmost of the preprocessing settings can be left to the default values.

5) AI2P in the SMAI function block is a grouped signal which contains all the data about thephases L1, L2, L1–L2, and neutral quantity; in particular the data about fundamentalfrequency phasors, harmonic content, positive sequence and zero sequence quantities areavailable.AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain thefundamental frequency phasors and the harmonic content of the corresponding inputchannels of the preprocessing function block.AIN is the signal which contains the fundamental frequency phasors and the harmoniccontent of the neutral quantity. In this example, GRP2N is not connected so this data iscalculated by the preprocessing function block on the basis of the inputs GRPL1 and GRPL2.If GRP2N is connected, the data reflects the measured value of GRP2N.

Another alternative is to have the star point of the two-phase CT set as shown in Figure13:

L1

IL1

IL2

L2

Protected Object

IL1

IL2

IED

IEC16000137-1-en.vsdx

4 1

2

3IN

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5CT 600/5A

Star Connected

IEC16000137 V1 EN

Figure 13: Star connected two-phase CT set with its star point away from theprotected object

In the example, everything is done in a similar way as in the above described example(Figure 12). The only difference is the setting of the parameter CTStarPoint of theused current inputs on the TRM (item 2 in Figure 12 and 13):

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 51Application manual

Page 58: Railway application RER670 Version 2.2 IEC ... - ABB

• CTprim=600A• CTsec=5A• CTStarPoint=FromObject

The ratio of the first two parameters is only used inside the IED. The third parameteras set in this example will negate the measured currents in order to ensure that thecurrents are measured towards the protected object within the IED.

A third alternative is to have the residual/neutral current from the two-phase CT setconnected to the IED as shown in Figure 14.

L1

IL1

IL2

L2

Protected Object

CT 600/5A

Star ConnectedIL1

IL2

IN

IED

1

3

4

2

IEC16000138-1-en.vsdx

6

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5

5

IEC16000138 V1 EN

Figure 14: Star connected two-phase CT set with its star point away from theprotected object and the residual/neutral current connected to theIED

Where:

1) Shows how to connect two individual phase currents from a star connected two-phase CT setto the two CT inputs of the IED.

2) Shows how to connect residual/neutral current from the two-phase CT set to the fourth inputin the IED. It shall be noted that if this connection is not made, the IED will still calculate thiscurrent internally by vectorial summation of the two individual phase currents.

3) Is the TRM where these current inputs are located. It shall be noted that for all these currentinputs the following setting values shall be entered.

• CTprim=600A• CTsec=5A• CTStarPoint=FromObject

The ratio of the first two parameters is only used inside the IED. The third parameteras set inthis example will negate the measured currents in order to ensure that the currents aremeasured towards the protected object within the IED.

Table continues on next page

Section 4 1MRK 506 375-UEN -Analog inputs

52 Railway application RER670 2.2 IECApplication manual

Page 59: Railway application RER670 Version 2.2 IEC ... - ABB

4) Are two connections made in the Signal Matrix tool (SMT) and Application configuration tool(ACT) which connects these two phase current inputs to the first two input channels on thepreprocessing function block 6).

5) Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool(ACT), which connects the residual/neutral current input to the fourth input channel of thepreprocessing function block 6). Note that this connection in SMT shall not be done if theresidual/neutral current is not connected to the IED.

6) Is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive and zero sequence quantities by using the fundamental frequency phasors of

the first two input channels (channel one taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application, most of the preprocessing settings can be left to the default values.

4.2.2.6 Example how to connect single-phase CT to the IED

Figure 15 gives an example how to connect the single-phase CT to the IED. It givesan overview of the required actions by the user in order to make this measurementavailable to the built-in protection and control functions within the IED as well.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

Protected Object

L1 L2

IED

INP

INS

INS

2

IEC16000139-1-en.vsdx

4

3

CT

600

/1A

a)

b)

(+)

(+)

(-)

(-)(+)

(-)

1SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5

IEC16000139 V1 EN

Figure 15: Connections for single-phase CT input

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 53Application manual

Page 60: Railway application RER670 Version 2.2 IEC ... - ABB

Where:

1) shows how to connect single-phase CT input in the IED.

2) is TRM where these current inputs are located. It shall be noted that for all these currentinputs the following setting values shall be entered.For connection (a) shown in Fgure 15:CTprim= 600 ACTsec= 1ACTStarPoint=ToObject For connection (b) shown in Figure 15:CTprim= 600 ACTsec= 1ACTStarPoint=FromObject

3) shows the connection made in SMT tool, which connect this CT input to the fourth inputchannel of the preprocessing function block 4).

4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate values. The calculated values are then available for all built-in protection andcontrol functions within the IED, which are connected to this preprocessing function block.

4.2.3 Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protectionIED

Note that for all line protection applications the parameter Base Current (i.e. IBasesetting in the IED) used by the relevant protection function, shall always be set equalto the largest rated CT primary current among all CTs involved in the protectionscheme. The rated CT primary current value is set as parameter CTPrim under the IEDTRM settings.

For all other protection applications (e.g. transformer protection) it is typicallydesirable to set IBase parameter equal to the rated current of the protected object.However this is only recommended to do if the rated current of the protected object iswithin the range of 40% to 120% of the selected CT rated primary current. If for anyreason (e.g. high maximum short circuit current) the rated current of the protectedobject is less than 40% of the rated CT primary current, it is strongly recommended toset the parameter IBase in the IED to be equal to the largest rated CT primary currentamong all CTs involved in the protection scheme and installed on the same voltagelevel. This will effectively make the protection scheme less sensitive; however, suchmeasures are necessary in order to avoid possible problems with loss of themeasurement accuracy in the IED.

Regardless of the applied relationship between the IBase parameter and the rated CTprimary current, the corresponding minimum pickup of the function on the CTsecondary side must always be verified. It is strongly recommended that the minimumpickup of any instantaneous protection function (e.g. differential, restricted earthfault, distance, instantaneous overcurrent, etc.) shall under no circumstances be lessthan 4% of the used IED CT input rating (i.e. 1A or 5A). This corresponds to 40mAsecondary for IED 1A rated inputs and to 200mA secondary for IED 5A rated inputsused by the function. This shall be individually verified for all current inputs involvedin the protection scheme.

Section 4 1MRK 506 375-UEN -Analog inputs

54 Railway application RER670 2.2 IECApplication manual

Page 61: Railway application RER670 Version 2.2 IEC ... - ABB

4.2.4 Setting of voltage channels

As the IED uses primary system quantities, the main VT ratios must be known to theIED. This is done by setting the two parameters VTsec and VTprim for each voltagechannel. The phase-to-phase value can be used even if each channel is connected to aphase-to-earth voltage from the VT.

4.2.4.1 Example

Consider a VT with the following data:

110 100/

2 2

kV V

IECEQUATION16054 V1 EN (Equation 1)

The following setting should be used: VTprim=110 (value in kV) VTsec=100 (valuein V)

4.2.4.2 Examples how to connect, configure and set VT inputs for mostcommonly used VT connections

Figure 16 defines the marking of voltage transformer terminals commonly usedaround the world.

A(H1)

B(H2)

b(X2)

a(X1)

A(H1)

N(H2)

n(X2)

a(X1)

b) c)

A(H1)

N(H2)

dn(X2)

da(X1)

d)

UPri

+ +USec

a)

en06000591.vsd

IEC06000591 V1 EN

Figure 16: Commonly used markings of VT terminals

Where:

a) is the symbol and terminal marking used in this document. Terminals marked with a squareindicate the primary and secondary winding terminals with the same (positive) polarity

b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth connected VTs

c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open deltaconnected VTs

d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs

It shall be noted that depending on national standard and utility practices the ratedsecondary voltage of a VT has typically one of the following values:

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 55Application manual

Page 62: Railway application RER670 Version 2.2 IEC ... - ABB

• 100 V• 110 V

The IED fully supports all of these values and most of them will be shown in thefollowing examples.

4.2.4.3 Examples on how to connect a two phase-to-earth connected VT to theIED

Figure 17 gives an example on how to connect a two phase-to-earth connected VT tothe IED. It gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

L1

IED L2

132

2110

2

kV

V

1

3

2

132

2110

2

kV

V

IEC16000140-1-en.vsdx

4

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5

IEC16000140 V1 EN

Figure 17: A two phase-to-earth connected VT

Where:

1) shows how to connect two secondary phase-to-earth voltages to two VT inputs on the IED

2) is the TRM where these voltage inputs are located. For these voltage inputs, the followingsetting values shall be entered:VTprim =132 kVVTsec = 110 VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.

132 / 2132 /110

110 / 2

kk

IECEQUATION16055 V1 EN (Equation 2)

Table continues on next page

Section 4 1MRK 506 375-UEN -Analog inputs

56 Railway application RER670 2.2 IECApplication manual

Page 63: Railway application RER670 Version 2.2 IEC ... - ABB

3) are two connections made in Signal Matrix Tool (SMT), which connect these two voltageinputs to first two input channels of the preprocessing function block 5). Depending on thetype of functions which need this voltage information, more than one preprocessing blockmight be connected in parallel to these VT inputs.

4) shows that in this example the fourth (that is, residual) input channel of the preprocessingblock is not connected in SMT tool. Thus the preprocessing block will automaticallycalculate 2Uo inside by vectorial sum from the two phase to earth voltages connected tothe first two input channels of the same preprocessing block. Alternatively, the fourth inputchannel can be connected to open delta VT input, as shown in Figure 18.

5) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive and zero sequence quantities by using the fundamental frequency phasors

for the first two input channels (channel one taken as reference for sequence

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values. However the following settings shall be set as shown here:UBase=132 kV (that is, rated Ph-Ph voltage)

4.2.4.4 Example on how to connect a residually connected IED

Figure 18 gives an example about the wiring of a residually connected VT to the IED.It shall be noted that this type of VT connection presents a secondary voltageproportional to 2U0 to the IED.

The primary rated voltage of an open Delta VT is always equal to UPh-E. Two seriesconnected VT secondary windings gives a secondary voltage equal to the sum of thetwo phase voltages. Thus the secondary windings of open deltaVTs may have asecondary rating of 110/2V.

Figure 18 gives overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IEDas well.

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 57Application manual

Page 64: Railway application RER670 Version 2.2 IEC ... - ABB

L1

IED L2

+2Uo

132

2100

2

kV

V

132

2100

2

kV

V

1

2

4

3

5

IEC16000152-1-en.vsdx

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

IEC16000152 V1 EN

Figure 18: Residually connected VT in two-phase power system

Where:

1) shows how to connect the secondary side of the residually connected VT to one VT inputon the IED.

+2U0 shall be connected to the IED

2) is the TRM where this voltage input is located. It shall be noted that for this voltage input thefollowing setting values shall be entered:VTprim=132kVVTsec=100VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.

3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool or ACT tool.

4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool(ACT), which connect this voltage input to the fourth input channel of the preprocessingfunction block 5).

5) is a Preprocessing block that has the task to digitally filter the connected analog input andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• zero sequence quantities by using the fundamental frequency phasors for the fourth

input channel

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values.

Section 4 1MRK 506 375-UEN -Analog inputs

58 Railway application RER670 2.2 IECApplication manual

Page 65: Railway application RER670 Version 2.2 IEC ... - ABB

4.2.4.5 Example on how to connect a neutral point VT to the IED

Figure 19 gives an example on how to connect a neutral point VT to the IED. This typeof VT connection presents secondary voltage proportional to U0 to the IED.

In case of a solid earth fault in high impedance earthed or unearthed systems theprimary value of Uo voltage will be equal to:

02

Ph PhPh N

UU U

IECEQUATION16056 V1 EN (Equation 4)

Figure 19 gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.

L1 L2

IED

6.6

2100

kV

V

RUo

IEC16000141-1-en.vsdx

Protected Object

1

2

3

4

SMAI2BLOCK

^GRP2L1

^GRP2L2

^GRP2L1L2

^GRP2N

AI2P

AI1

AI2

AI3

AI4

AIN

5

IEC16000141 V1 EN

Figure 19: Neutral point connected VT

1MRK 506 375-UEN - Section 4Analog inputs

Railway application RER670 2.2 IEC 59Application manual

Page 66: Railway application RER670 Version 2.2 IEC ... - ABB

Where:

1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.

U0 shall be connected to the IED.

2) is the TRM or AIM where this voltage input is located. For this voltage input the followingsetting values shall be entered:

6.63.3

2VTprim kV

IECEQUATION16057 V1 EN (Equation 6)

sec 100VT V

EQUATION1934 V2 EN (Equation 7)

Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of the neutral point VT.

3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool or ACT tool.

4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool(ACT), which connects this voltage input to the fourth input channel of the preprocessingfunction block 5).

5) is a preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all the fourth input channels• harmonic content for all the fourth input channels

• zero sequence quantities by using the fundamental frequency phasors

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application, most of the preprocessing settings can be left to the default values.

Section 4 1MRK 506 375-UEN -Analog inputs

60 Railway application RER670 2.2 IECApplication manual

Page 67: Railway application RER670 Version 2.2 IEC ... - ABB

Section 5 Local HMI

IEC13000239-3-en.vsd

IEC13000239 V3 EN

Figure 20: Local human-machine interface

The LHMI of the IED contains the following elements:

• Keypad• Display (LCD)• LED indicators• Communication port for PCM600

1MRK 506 375-UEN - Section 5Local HMI

Railway application RER670 2.2 IEC 61Application manual

Page 68: Railway application RER670 Version 2.2 IEC ... - ABB

The LHMI is used for setting, monitoring and controlling.

5.1 Display

The LHMI includes a graphical monochrome liquid crystal display (LCD) with aresolution of 320 x 240 pixels. The character size can vary. The amount of charactersand rows fitting the view depends on the character size and the view that is shown.

The display view is divided into four basic areas.

IEC15000270-1-en.vsdx

IEC15000270 V1 EN

Figure 21: Display layout

1 Path

2 Content

3 Status

4 Scroll bar (appears when needed)

The function key button panel shows on request what actions are possible with thefunction buttons. Each function button has a LED indication that can be used as a

Section 5 1MRK 506 375-UEN -Local HMI

62 Railway application RER670 2.2 IECApplication manual

Page 69: Railway application RER670 Version 2.2 IEC ... - ABB

feedback signal for the function button control action. The LED is connected to therequired signal with PCM600.

IEC13000281-1-en.vsd

GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN

Figure 22: Function button panel

The indication LED panel shows on request the alarm text labels for the indicationLEDs. Three indication LED pages are available.

IEC13000240-1-en.vsd

GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN

Figure 23: Indication LED panel

The function button and indication LED panels are not visible at the same time. Eachpanel is shown by pressing one of the function buttons or the Multipage button.Pressing the ESC button clears the panel from the display. Both panels have a dynamicwidth that depends on the label string length.

1MRK 506 375-UEN - Section 5Local HMI

Railway application RER670 2.2 IEC 63Application manual

Page 70: Railway application RER670 Version 2.2 IEC ... - ABB

5.2 LEDs

The LHMI includes three status LEDs above the display: Ready, Start and Trip.

There are 15 programmable indication LEDs on the front of the LHMI. Each LED canindicate three states with the colors: green, yellow and red. The texts related to eachthree-color LED are divided into three panels.

There are 3 separate panels of LEDs available. The 15 physical three-color LEDs inone LED group can indicate 45 different signals. Altogether, 135 signals can beindicated since there are three LED groups. The LEDs are lit according to priority,with red being the highest and green the lowest priority. For example, if on one panelthere is an indication that requires the green LED to be lit, and on another panel thereis an indication that requires the red LED to be lit, the red LED takes priority and is lit.The LEDs can be configured with PCM600 and the operation mode can be selectedwith the LHMI or PCM600.

Information panels for the indication LEDs are shown by pressing the Multipagebutton. Pressing that button cycles through the three pages. A lit or un-acknowledgedLED is indicated with a highlight. Such lines can be selected by using the Up/Downarrow buttons. Pressing the Enter key shows details about the selected LED. Pressingthe ESC button exits from information pop-ups as well as from the LED panel as such.

The Multipage button has a LED. This LED is lit whenever any LED on any panel islit. If there are un-acknowledged indication LEDs, then the Multipage LED blinks. Toacknowledge LEDs, press the Clear button to enter the Reset menu (refer todescription of this menu for details).

There are two additional LEDs which are next to the control buttons and .These LEDs can indicate the status of two arbitrary binary signals by configuring theOPENCLOSE_LED function block. For instance, OPENCLOSE_LED can beconnected to a circuit breaker to indicate the breaker open/close status on the LEDs.

IEC16000076-1-en.vsd

IEC16000076 V1 EN

Figure 24: OPENCLOSE_LED connected to SXCBR

Section 5 1MRK 506 375-UEN -Local HMI

64 Railway application RER670 2.2 IECApplication manual

Page 71: Railway application RER670 Version 2.2 IEC ... - ABB

5.3 Keypad

The LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured either asmenu shortcut or control buttons.

1MRK 506 375-UEN - Section 5Local HMI

Railway application RER670 2.2 IEC 65Application manual

Page 72: Railway application RER670 Version 2.2 IEC ... - ABB

1

18

19

7

6

5

4

3

2

8

20

21

22

17161514131211109

23

24

IEC15000157-2-en.vsd

IEC15000157 V2 EN

Figure 25: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

1...5 Function button

6 Close

7 Open

8 Escape

9 Left

10 Down

11 Up

12 Right

13 Key

14 Enter

15 Remote/Local

16 Uplink LED

17 Not in use

18 Multipage

Section 5 1MRK 506 375-UEN -Local HMI

66 Railway application RER670 2.2 IECApplication manual

Page 73: Railway application RER670 Version 2.2 IEC ... - ABB

19 Menu

20 Clear

21 Help

22 Communication port

23 Programmable indication LEDs

24 IED status LEDs

5.4 Local HMI functionality

5.4.1 Protection and alarm indication

Protection indicatorsThe protection indicator LEDs are Ready, Start and Trip.

The start and trip LEDs are configured via the disturbance recorder.The yellow and red status LEDs are configured in the disturbancerecorder function, DRPRDRE, by connecting a start or trip signalfrom the actual function to a BxRBDR binary input function blockusing the PCM600 and configure the setting to Off, Start or Trip forthat particular signal.

Table 10: Ready LED (green)

LED state DescriptionOff Auxiliary supply voltage is disconnected.

On Normal operation.

Flashing Internal fault has occurred.

Table 11: Start LED (yellow)

LED state DescriptionOff Normal operation.

On A protection function has started and an indication message is displayed.The start indication is latching and must be reset via communication, LHMIor binary input on the LEDGEN component. To open the reset menu on theLHMI, press .

Flashing The IED is in test mode and protection functions are blocked, or theIEC61850 protocol is blocking one or more functions.The indication disappears when the IED is no longer in test mode andblocking is removed. The blocking of functions through the IEC61850protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellowLED changes to either On or Off state depending on the state of operation.

1MRK 506 375-UEN - Section 5Local HMI

Railway application RER670 2.2 IEC 67Application manual

Page 74: Railway application RER670 Version 2.2 IEC ... - ABB

Table 12: Trip LED (red)

LED state DescriptionOff Normal operation.

On A protection function has tripped. An indication message is displayed if theauto-indication feature is enabled in the local HMI.The trip indication is latching and must be reset via communication, LHMI orbinary input on the LEDGEN component. To open the reset menu on theLHMI, press .

Flasing Configuration mode.

Alarm indicatorsThe 15 programmable three-color LEDs are used for alarm indication. An individualalarm/status signal, connected to any of the LED function blocks, can be assigned toone of the three LED colors when configuring the IED.

Table 13: Alarm indications

LED state DescriptionOff Normal operation. All activation signals are off.

On • Follow-S sequence: The activation signal is on.• LatchedColl-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedAck-F-S sequence: The indication has been acknowledged, but the

activation signal is still on.• LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedReset-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.

Flashing • Follow-F sequence: The activation signal is on.• LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedAck-S-F sequence: The indication has been acknowledged, but the

activation signal is still on.

5.4.2 Parameter management

The LHMI is used to access the relay parameters. Three types of parameters can beread and written.

• Numerical values• String values• Enumerated values

Numerical values are presented either in integer or in decimal format with minimumand maximum values. Character strings can be edited character by character.Enumerated values have a predefined set of selectable values.

Section 5 1MRK 506 375-UEN -Local HMI

68 Railway application RER670 2.2 IECApplication manual

Page 75: Railway application RER670 Version 2.2 IEC ... - ABB

5.4.3 Front communication

The RJ-45 port in the LHMI enables front communication.

• The green uplink LED on the left is lit when the cable is successfully connectedto the port.

• The yellow LED is not used; it is always off.

IEC13000280-1-en.vsd

1

2

GUID-AACFC753-BFB9-47FE-9512-3C4180731A1B V1 EN

Figure 26: RJ-45 communication port and green indicator LED

1 RJ-45 connector

2 Green indicator LED

The default IP address for the IED front port is 10.1.150.3 and the correspondingsubnetwork mask is 255.255.254.0. It can be set through the local HMI path Mainmenu/Configuration/Communication/Ethernet configuration/FRONT port/AP_FRONT.

Do not connect the IED front port to a LAN. Connect only a singlelocal PC with PCM600 to the front port. It is only intended fortemporary use, such as commissioning and testing.

1MRK 506 375-UEN - Section 5Local HMI

Railway application RER670 2.2 IEC 69Application manual

Page 76: Railway application RER670 Version 2.2 IEC ... - ABB

70

Page 77: Railway application RER670 Version 2.2 IEC ... - ABB

Section 6 Differential protection

6.1 Low impedance restricted earth fault protectionREFPDIF

6.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Restricted earth fault protection, lowimpedance

REFPDIF

IdN/I

SYMBOL-AA V1 EN

87N

6.1.2 Application

A breakdown of the insulation between a transformer winding and the core or the tankmay result in a large fault current which causes severe damage to the windings and thetransformer core. A high gas pressure may develop, damaging the transformer tank.

Fast and sensitive detection of earth faults in a power transformer winding can beobtained in solidly earthed or low impedance earthed networks by the restricted earthfault protection. The only requirement is that the power transformer winding isconnected to earth in the star point (in case of star-connected windings).

The low impedance restricted earth fault protection REFPDIF is a winding protectionfunction. It protects the power transformer winding against faults involving earth.Observe that single phase-to-earth faults are the most common fault types intransformers. Therefore, a sensitive earth fault protection is desirable.

A restricted earth fault protection is the fastest and the most sensitive protection, apower transformer winding can have and will detect faults such as:

• earth faults in the transformer winding when the network is earthed through animpedance

• earth faults in the transformer winding in solidly earthed network when the pointof the fault is close to the winding star point.

The restricted earth fault protection is not affected, as a differential protection, withthe following power transformer related phenomena:

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 71Application manual

Page 78: Railway application RER670 Version 2.2 IEC ... - ABB

• magnetizing inrush currents• overexcitation magnetizing currents• load tap changer• external and internal phase faults which do not involve earth• symmetrical overload conditions

Due to its features, REFPDIF is often used as a main protection of the transformerwinding for all faults involving earth.

6.1.2.1 Transformer winding, solidly earthed

The most common application is on a solidly earthed transformer winding. Theconnection is shown in Figure 27.

IEC16000117-1-en.vsdx

REFPDIF

I2P

ISI

IdN/I

Protected

winding

IEC16000117 V1 EN

Figure 27: Connection of the low impedance Restricted earth fault functionREFPDIF for a directly (solidly) earthed transformer winding

Section 6 1MRK 506 375-UEN -Differential protection

72 Railway application RER670 2.2 IECApplication manual

Page 79: Railway application RER670 Version 2.2 IEC ... - ABB

6.1.2.2 CT earthing direction

To make the restricted earth fault protection REFPDIF operate correctly, the mainCTs are always supposed to be star -connected. The main CT's neutral (star) formationcan be positioned in either way, ToObject or FromObject. However, internallyREFPDIF always uses reference directions towards the protected transformers, asshown in Figure 27. Thus the IED always measures the primary currents on all sidesand in the neutral of the power transformer with the same reference direction towardsthe power transformer windings.

The main CT's connection type can be freely selected for each of the involved currenttransformers.

6.1.2.3 Railway specific applications for REFPDIF function

If appropriate configuration and settings are applied, the REFPDIF function can alsobe used for the following special applications in the railway supply system:

• Defrost protection, when a single phase differential protection is temporaryarranged among two CTs during de-icing operation of the catenary contact linewires.

• Single phase differential protection applied across one winding (i.e. either overone single-phase transformer winding or a generator winding).

6.1.3 Setting guidelines

6.1.3.1 Setting and configuration

Recommendation for analog inputsISI: Neutral current input.

I2P: Phase currents from winding HV side current transformer set.

Recommendation for Binary input signalsBLOCK: The input will block the operation of the function. It can be used, forexample, to block the operation during special service conditions for a limited time.

Recommendation for output signalsSTART: The start output indicates that Idiff is in the operate region of the operate-restraint characteristic.

TRIP: The trip output is activated when all operating criteria are fulfilled.

DIROK: The output is activated when the directional criteria has been fulfilled.

BLK2H: The output is activated when the function is blocked due to high level ofsecond harmonic.

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 73Application manual

Page 80: Railway application RER670 Version 2.2 IEC ... - ABB

6.1.3.2 Settings

The parameters for the restricted earth fault protection, low impedance functionREFPDIF are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

Operation: The operation of REFPDIF can be switched On/Off.

IdMin: The setting gives the minimum operation value. The setting is in percent of theIBase value of the chosen GlobalBaseSel. For function operation, the neutral currentmust be larger than half of this value. A recommended setting is 30% of powertransformer-winding rated current for a solidly earthed winding.

ROA: Relay operate angle for zero sequence directional feature. It is used todifferentiate an internal fault and an external fault based on measured zero sequencecurrent and neutral current. Default value of 60 deg is recommended.

6.2 Single-phase railway power transformer differentialprotection T1PPDIF

6.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Single-phase railway power transformerdifferential protection

T1PPDIF

Id/I>

IEC15000166 V1 EN

87T

6.2.2 Application

The railway transformer differential protection is a unit protection. The function isdesigned to operate properly for 16.7Hz, 50Hz and 60Hz railway power transformers.It serves as the main protection of railway power transformers in case of windingfailure. Internal electrical faults are very serious and will cause immediate damage.Short circuits and earth faults in windings and terminals will normally be detected bythe differential protection. It is possible to detect inter-turn faults if a sufficientnumber of turns is short-circuited. Inter-turn faults are the most difficult transformerwinding fault to detect with electrical protections.

It is important that the faulty power transformer can be disconnected as fast aspossible. As the differential protection is a unit protection, it can be designed for fast

Section 6 1MRK 506 375-UEN -Differential protection

74 Railway application RER670 2.2 IECApplication manual

Page 81: Railway application RER670 Version 2.2 IEC ... - ABB

tripping, thus providing selective disconnection of the faulty railway powertransformer. The differential protection should never operate on faults outside theprotective zone. A transformer differential protection compares the current flowinginto the transformer with the current leaving the transformer.

The differential current should be zero during normal load or external faults if the turn-ratio and the phase shift are correctly compensated. However, there are severalphenomena other than internal faults that will cause unwanted and false differentialcurrents. The main reasons for unwanted differential currents are:

• different characteristics, loads and operating conditions of the currenttransformers

• zero sequence currents that flow only on one side of the power transformer• normal magnetizing currents• magnetizing inrush currents• overexcitation magnetizing currents

6.2.3 Setting guidelines

The parameters for the transformer differential protection T1PPDIF function are setvia the local HMI or Protection and Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: This is used for transformer differential protection Off/On.

6.2.3.1 Restrained and unrestrained differential protection

To make a differential IED as sensitive and stable as possible, restrained differentialprotections have been developed and are now adopted as the general practice in theprotection of power transformers. The protection should be provided with aproportional bias, which makes the protection operate for a certain percentagedifferential current related to the current flowing through the transformer. Thisstabilizes the protection under through-fault conditions while still permitting the relayto have good basic sensitivity.

The bias current should be defined as the highest power transformer current becausethis will reflect the difficulties met by the current transformers much better. Thedifferential protection function uses the highest differential current contribution fromthe two sides as bias current. The principle with the operate-bias characteristic is toincrease the pick-up level when the current transformers have difficult operatingconditions.

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 75Application manual

Page 82: Railway application RER670 Version 2.2 IEC ... - ABB

The usual practice for transformer protection is to set the bias characteristic to a valueof at least twice the value of the expected spill current under through-fault conditions.These criteria can vary considerably from application to application.

The default settings for the operating characteristic with IdMin = 30% of the railwaypower transformer rated current can be recommended in normal applications. If theconditions are known in more detail, a higher or a lower sensitivity can be chosen. Insuch cases, the selection of the suitable characteristic should be based on the class ofthe current transformers, the short-circuit power of the systems, and so on.

The second section of the restrain characteristic has an increased slope in order to dealwith the increased differential current during heavy loading of the transformer andexternal fault currents.

The third section of the restrain characteristic further decreases the sensitivity of therestrained differential function in order to cope with CT saturation during heavythrough faults.

The unrestrained operation level has a default value of IdUnre = 800% of the railwaypower transformer rated current, which is typically acceptable for most of the standardapplications. The overall operating characteristic of the transformer differentialprotection is shown in Figure 28:

Section 6 1MRK 506 375-UEN -Differential protection

76 Railway application RER670 2.2 IECApplication manual

Page 83: Railway application RER670 Version 2.2 IEC ... - ABB

Unrestrained Limit IdUnre

Restrain

Restrain current [%]

(bias current)

Operate

unconditionally

Operate

conditionally

Section 1 Section 2 Section 3

SlopeSection 2

SlopeSection 3

EndSection 1

EndSection2

Operate current [%]

(differential current)

IdMin

IEC15000390-2-en.vsdx

IEC15000390 V2 EN

Figure 28: Operate-restrain characteristic

The operate-restrained characteristic is determined by five parameter settings:

• IdMin• EndSection1• EndSection2• SlopeSection2• SlopeSection3

The slope is relative to the characteristic breakpoint.

%100

BIAS

DIFF

I

Islope

IECEQUATION15054 V1 EN (Equation 8)

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 77Application manual

Page 84: Railway application RER670 Version 2.2 IEC ... - ABB

6.2.3.2 Elimination of zero sequence currents

To avoid unwanted trips for external earth faults, zero sequence currents should besubtracted on the side of the protected railway power transformer where they can flowduring external earth faults.

Eliminating the zero sequence component is necessary when:

• the protected railway power transformer cannot transform the zero sequencecurrents to the other side.

• the zero sequence currents can only flow on one side of the protected railwaypower transformer.

If zero sequence current reduction is not done, it can cause false differential currentsconsisting exclusively of the zero sequence currents. If high enough, these falsedifferential currents can cause an unwanted disconnection of a healthy railway powertransformer.

Removing zero sequence currents is important for the stability of T1PPDIF againstexternal earth faults.

The disadvantage of eliminating the zero sequence current is that T1PPDIF becomesless sensitive to the single-phase earth faults within the protected zone. To counteractfor this effect to some degree, the zero sequence current is subtracted not only from thefundamental frequency differential current, but also from the bias current (seeTransformer connection types in Technical Manual). For a railway power transformerwinding, the zero sequence current is subtracted when for the phase selectionparameter on the respective side the value (L1-L2)/2 is selected. For a detailedexplanation, see the calculations done in Solution 1 in section Setting example in thismanual.

6.2.3.3 Inrush restraint methods

With a combination of the 2nd harmonic restraint and the waveform restraint methodsit is possible to get a protection with high security and stability against inrush effectsand, at the same time, maintain high performance in case of heavy internal faults evenif the current transformers are saturated. Both these restraint methods are used by theT1PPDIF function. The 2nd harmonic restraint function has a settable level. If the ratioof the 2nd harmonic to the fundamental in the differential current is above the settablelimit, the operation of the differential protection is blocked. It is recommended to setparameter I2/I1Ratio = 15% as default value if there are no reasons to choose anothervalue.

6.2.3.4 Overexcitation restraint method

In case of an overexcited transformer, the winding currents contain odd harmoniccomponents because the current waveform is symmetrical to the time axis. Thedifferential protection function is provided with a 5th harmonic restraint to prevent the

Section 6 1MRK 506 375-UEN -Differential protection

78 Railway application RER670 2.2 IECApplication manual

Page 85: Railway application RER670 Version 2.2 IEC ... - ABB

protection from operating during an overexcitation condition of a power transformer.If the ratio of the 5th harmonic to the fundamental in the differential current is abovea settable limit, the operation is restrained. It is recommended to use I5/I1Ratio = 25%as default value if there are no special reasons to choose another setting.

6.2.3.5 Protections based on the directional criterion

Two kinds of protections based on the directional criterion are integrated into therailway differential protection function:

• The directional unrestrained differential protection• The directional sensitive differential protection

These two subfunctions are based on the internal-external fault discriminator, whichis a supplementary criterion to the traditional differential protection. The internal/external fault discriminator detects even minor faults, with a high sensitivity and athigh speed and, at the same time, discriminates between internal and external faultswith a high degree of dependability. The goal is to be able to quickly switch off thefaulty power transformer before the fault develops into a severe one (for example, afault involving the iron core). This feature should always be used when protecting arailway power transformer (by setting DirDiffEn = On).

6.2.4 Setting examples

For the transformer in Figure 29, there are two solutions for balancing the transformerdifferential protection.

IEC16000067-1-en.vsd

15kV132kV

I

U

v

IU

IsSV

R

IEC16000067 V1 EN

Figure 29: A railway transformer with rating 16MVA, 132/15kV

Solution 1 (see Figure 35 for CT connections and ACT configuration):

Connection to the preprocessing blocks:

HV side: IL1=IV; IL2=IU

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 79Application manual

Page 86: Railway application RER670 Version 2.2 IEC ... - ABB

LV side: IL1=IS, IL2= 0

Settings within the transformer differential protection:

PhSelW1 = (IL1-IL2)/2

PhSelW2 = IL1

InvW2Curr = No

Solution 2 (see Figure 36 for CT connections and ACT configuration):

Connection to the preprocessing blocks:

HV side: IL1=IU; IL2=IV

LV side: IL1=0, IL2= IS

Settings within the transformer differential protection:

PhSelW1 = (IL1-IL2)/2

PhSelW2 = IL2

InvW2Curr = Yes

Base current

The base current is calculated for each side (winding 1 and winding 2) of the powertransformer:

1

10001 121

W

SBaseIBaseW A

UBase

IECEQUATION16075 V1 EN (Equation 9)

2

10002 1067

W

SBaseIBaseW A

UBase

IECEQUATION16076 V1 EN (Equation 10)

where:

SBase Rated power of transformer [MVA]

UBaseW1 Rated phase-to-phase voltage of winding 1 [kV]

UBaseW2 Rated phase-to-phase voltage of winding 2 [kV]

The base currents for T1PPDIF functions are set under Global Base Values inParameter Setting tool.

Section 6 1MRK 506 375-UEN -Differential protection

80 Railway application RER670 2.2 IECApplication manual

Page 87: Railway application RER670 Version 2.2 IEC ... - ABB

6.2.4.1 Application examples

Five examples of railway power transformer connections are presented here. Othertransformer connections may also be protected using the single-phase T1PPDIFfunction.

Transformer connection – example 1

In all the following figures the phases are indicated as U and V on theHV side and R and S on the LV side of the transformer. Equivalentwinding ends are U & R and V & S.

IEC15000170-3-en.vsdx

132/15kV

15kV132kV

I

U

v

IU

Is

SV

R

IEC15000170 V3 EN

Figure 30: Transformer connection – example 1

Base current calculation:

kVU

MVASI

WxPhPh

WxBase

__

_

1000

IECEQUATION058 V1 EN (Equation 11)

The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV current Is shall beconnected as IL1 current for the winding 2 side towards the T1PPDIF function.

Zero sequence current calculation on the HV side:

02U VI I I IECEQUATION200 V2 EN (Equation 12)

Removal of zero sequence current from the V phase:

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 81Application manual

Page 88: Railway application RER670 Version 2.2 IEC ... - ABB

0 2 2

U V V UV V

I I I II I I

IECEQUATION201 V2 EN (Equation 13)

The phase selection settings for the T1PPDIF function shall be:

PhSelW1=(L1-L2)/2

PhSelW2=L1

InvW2Curr=No

Calculation of differential and bias currents:

1 2

1 2

100 100% 1 2

2

100 100% 1 , 2 ,

2

V UDiff S

BaseW BaseW

V UBias S

BaseW BaseW

I II IDLW IDLW I

I I

I II IDLW IDLW Max I

I I

IECEQUATION202 V2 EN (Equation 14)

Transformer connection – example 2

IEC15000171-3-en.vsdx

66/15kV

15kV66kV

I

U

v

IU

Is

SV

R

IEC15000171 V3 EN

Figure 31: Transformer connection – example 2

The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV current Is shall beconnected as IL1 current for the winding 2 side towards the T1PPDIF function.

Zero-sequence current removal is not necessary in this arrangement.

The phase selection settings for the first instance of the T1PPDIF function shall be:

PhSelW1=L1

PhSelW2=L1

Section 6 1MRK 506 375-UEN -Differential protection

82 Railway application RER670 2.2 IECApplication manual

Page 89: Railway application RER670 Version 2.2 IEC ... - ABB

InvW2Curr=No

Then the internal calculations will be:

1

1 2

1

1 2

100 100% IDLW1 IDLW2

100 100% 1 , 2 ,

Diff V S

BaseW BaseW

Bias V S

BaseW BaseW

I I II I

I Max IDLW IDLW Max I II I

IECEQUATION203 V2 EN (Equation 15)

The phase selection settings for the second instance of the T1PPDIF function shall be:

PhSelW1=L2

PhSelW2=L1

InvW2Curr=Yes

Then the internal calculations will be:

2

1 2

2

1 2

100 100% IDLW1 IDLW2

100 100% 1 , 2 ,

Diff U S

BaseW BaseW

Bias U S

BaseW BaseW

I I II I

I Max IDLW IDLW Max I II I

IECEQUATION204 V2 EN (Equation 16)

Transformer connection – example 3

IEC15000172-2-en.vsdx

132/66kV

66kV132kV

I

U

v

IU

IS

SV

IR

R

IEC15000172 V2 EN

Figure 32: Transformer connection – example 3

The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV currents IS and IR shallbe connected as IL1 and IL2 currents, respectively, for the winding 2 side towards theT1PPDIF function.

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 83Application manual

Page 90: Railway application RER670 Version 2.2 IEC ... - ABB

To calculate the zero sequence current reduction for U and V phases, see connectionexample 1.

The phase selection settings for the first instance of the T1PPDIF function shall be:

PhSelW1=(L1-L2)/2

PhSelW2=L1

InvW2Curr=No

Then the internal calculations will be:

1

1 2

1

1 2

100 100% IDLW1 IDLW2

2

100 100% 1 , 2 ,

2

V UDiff S

BaseW BaseW

V UBias S

BaseW BaseW

I II I

I I

I II Max IDLW IDLW Max I

I I

IECEQUATION205 V2 EN (Equation 17)

The phase selection settings for the second instance of the T1PPDIF function shall be:

PhSelW1=(L1-L2)/2

PhSelW2=L2

InvW2Curr=Yes

Then the internal calculations will be:

2

1 2

2

1 2

100 100% IDLW1 IDLW2

2

100 100% 1 , 2 ,

2

V UDiff R

BaseW BaseW

V UBias R

BaseW BaseW

I II I

I I

I II Max IDLW IDLW Max I

I I

IECEQUATION206 V2 EN (Equation 18)

Section 6 1MRK 506 375-UEN -Differential protection

84 Railway application RER670 2.2 IECApplication manual

Page 91: Railway application RER670 Version 2.2 IEC ... - ABB

Transformer connection – example 4

IEC15000173-2-en.vsdx

132/110kV

110kV132kV

I

U

v

IU

IS

SV

IR

R

IEC15000173 V2 EN

Figure 33: Transformer connection – example 4

The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV currents IS and IR shallbe connected as IL1 and IL2 currents, respectively, for the winding 2 side towardsT1PPDIF function.

To calculate zero sequence current reduction for U, V, R and S phases, see connectionexample 1.

The phase selection settings for the first instance of the T1PPDIF function shall be:

PhSelW1=(L1-L2)/2

PhSelW2=(L1-L2)/2

InvW2Curr=No

Then the internal calculations will be:

1 2

1 2

100 100% IDLW1 IDLW2

2 2

100 100% 1 , 2 ,

2 2

V U S RDiff

BaseW BaseW

V U S RBias

BaseW BaseW

I I I II

I I

I I I II Max IDLW IDLW Max

I I

IECEQUATION207 V2 EN (Equation 19)

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 85Application manual

Page 92: Railway application RER670 Version 2.2 IEC ... - ABB

Transformer connection – example 5

IU

Iv Is

110kV 15kV

U

SV

110/15kV

IEC15000174-3-en.vsdx

R

IEC15000174 V3 EN

Figure 34: Transformer connection – example 5

The starpoint of the 110/15kV railway transformer can either be earthed (via coil) orisolated.

For information on how to arrange the differential protection for this transformer, seeexample 2.

6.2.4.2 How to wire the transformer differential protection to the IED using CTs

Here are two examples of how to wire and connect a star-connected, two-phase CT (onthe high-voltage side) and a one-phase CT (on the low-voltage side) to the IED forprotection of a railway power transformer (shown in Figure 29) using the T1PPDIFfunction.

For the correct terminal designations, see the connection diagramsvalid for the delivered IED.

Section 6 1MRK 506 375-UEN -Differential protection

86 Railway application RER670 2.2 IECApplication manual

Page 93: Railway application RER670 Version 2.2 IEC ... - ABB

Solution 1

V U

S

I V I U

IV

IU

IS

HV-side

LV-side

16MVA132/15kV

T1PPDIFI2PW1

BLOCKBLKRES

TRIPI2PW2

BLKUNRESBLKDRUNRBLKDRSEN

TRRESTRUNRESTRDRUNRTRDRSEN

STARTIDALARM

ST2NDHRMST5THHRMSTWAVDET

IDLIDLMAG

IBIAS

SMAI2BLOCKGRP2L1GRP2L2GRP2L1L2GRP2N

G2AI2PG2AI1G2AI2G2AI3G2AI4

G2N

SMAI1BLOCKGRP1L1GRP1L2GRP1L1L2GRP1N

G1AI2PG1AI1G1AI2G1AI3G1AI4

G1N

IED

1

2

2

3

3

4

4

5

CT

20

0/1

Star

co

nn

ecte

dC

T 1

60

0/1

I S

1

IEC16000064-1-en-original.vsd

IN

IEC16000064 V1 EN

Figure 35: CT wiring, pre-processing blocks and T1PPDIF connections for theproposed Solution 1

1 HV side: Two individual phase currents from a star-connected two-phase CT set are connected to twoCT inputs in the IEDLV side: A single phase current from the one-phase CT is connected to a third CT input in the IED

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 87Application manual

Page 94: Railway application RER670 Version 2.2 IEC ... - ABB

2 The current inputs are located in the TRM. The following settings shall be used for the current inputsin this example:HV side (two inputs):

• CTprim = 200A• CTsec = 1A• CTStarPoint = ToObject

LV side (one input):

• CTprim = 1200A• CTsec = 1A• CTStarPoint = ToObject

Inside the IED, only the ratio of the first two parameters is used. The third parameter (CTStarPoint =ToObject) causes no change on the measured currents. In other words, currents are alreadymeasured towards the protected object.

3 These connections are the links between the current inputs and the input channels of the twopreprocessing function blocks. The preprocessing block digitally filters the connected currents andcalculates:

• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive- and zero-sequence quantities by using the fundamental frequency phasors (phase L1

taken as reference for sequence quantities)

These calculated values are then available for all built-in protection and control functions within theIED that are connected to this preprocessing function block. For this application most of thepreprocessing settings can be left to the default values.

4 GxAI2P output on the SMAI function block is a grouped signal which contains all the data about thephase L1, phase L2 and the neutral quantity; in particular, the data about fundamental frequencyphasors, harmonic content, positive sequence and zero sequence quantities are available.

5 Two group signals (G1AI2P and G2AI2P) in the preprocessing blocks SMAI1 and SMAI2 areconnected to the inputs I2PW1 and I2PW2 in T1PPDIF.Phase selection settings for the measured currents in T1PPDIF:

• PhSelW1 = (IL1-IL2)/2• PhSelW2 = IL1• InvW2Curr = No

Section 6 1MRK 506 375-UEN -Differential protection

88 Railway application RER670 2.2 IECApplication manual

Page 95: Railway application RER670 Version 2.2 IEC ... - ABB

Solution 2

V U

S

I V I U

IU

IV

IS

HV-side

LV-side

16MVA132/15kV

T1PPDIFI2PW1

BLOCKBLKRES

TRIPI2PW2

BLKUNRESBLKDRUNRBLKDRSEN

TRRESTRUNRESTRDRUNRTRDRSEN

STARTIDALARM

ST2NDHRMST5THHRMSTWAVDET

IDLIDLMAG

IBIAS

SMAI2BLOCKGRP2L1GRP2L2GRP2L1L2GRP2N

G2AI2PG2AI1G2AI2G2AI3G2AI4

G2N

SMAI1BLOCKGRP1L1GRP1L2GRP1L1L2GRP1N

G1AI2PG1AI1G1AI2G1AI3G1AI4

G1N

IED

1

2

2

3

3

4

4

5

CT

20

0/1

Star

co

nn

ect

edC

T 1

60

0/1

I S

1

=IEC16000065=1=en=Original.vsd

IN

IEC16000065 V1 EN

Figure 36: CT wiring, pre-processing blocks and T1PPDIF connections for theproposed Solution 2

This solution is similar to Solution 1. The only differences are the following:

1. In point 5 the settings in T1PPDIF are the following:• PhSelW1 = (IL1-IL2)/2• PhSelW2 = IL2• InvW2Curr = Yes

2. The sequence of the HV currents is swapped by wiring towards the IED.3. LV current is connected as phase L2 on the preprocessing function block.

1MRK 506 375-UEN - Section 6Differential protection

Railway application RER670 2.2 IEC 89Application manual

Page 96: Railway application RER670 Version 2.2 IEC ... - ABB

90

Page 97: Railway application RER670 Version 2.2 IEC ... - ABB

Section 7 Impedance protection

7.1 Automatic switch onto fault logic ZCVPSOF

7.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Automatic switch onto fault logic ZCVPSOF - -

7.1.2 Application

Automatic switch onto fault logic, voltage- and current-based function ZCVPSOF isa complementary function to impedance measuring functions, but may use theinformation from such functions.

With ZCVPSOF, a fast trip is achieved for a fault on the whole line when the line isbeing energized. The ZCVPSOF tripping is generally non-directional to secure a tripat fault situations where directional information cannot be established, for example,due to lack of polarizing voltage when a line potential transformer is used.

Automatic activation based on dead-line detection can only be used when the voltagetransformer is situated on the line side of a circuit breaker.

When line side voltage transformers are used, the use of the nondirectional distancezones secures switch onto fault tripping for close-in three-phase short circuits. The useof the nondirectional distance zones also gives a fast fault clearance when energizinga bus from the line with a short circuit fault on the bus.

Other protection functions like time-delayed phase and zero-sequence overcurrentfunction can be connected to ZCVPSOF to increase the dependability in the scheme.

When the voltage transformers are situated on the bus side, the automatic switch ontofault detection based on dead-line detection is not possible. In such cases the switchonto fault logic is activated using the binary input BC.

7.1.3 Setting guidelines

The parameters for automatic switch onto fault logic, voltage- and current-basedfunction ZCVPSOF are set via the local HMI or Protection and Control ManagerPCM600.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 91Application manual

Page 98: Railway application RER670 Version 2.2 IEC ... - ABB

The distance protection zone used for instantaneous trip by ZCVPSOF has to be set tocover the entire protected line with a safety margin of minimum 20%.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel is used to select GBASVAL for reference of base values.

Operation: The operation of ZCVPSOF is by default set to On. The parameter must beset to Off if ZCVPSOF is not to be used.

IPh< is used to set the current level for the detection of a dead line. IPh< is, by default,set to 20% of IBase. It shall be set with a sufficient margin (15–20%) below theminimum expected load current. In many cases, the minimum load current of a line isclose to zero and even can be zero. The operating value must exceed the maximumcharging current of an overhead line when only one phase is disconnected (mutualcoupling in the other phases).

UPh< is used to set the voltage level for the detection of a dead line. UPh< is, bydefault, set to 70% of UBase. This is a suitable setting in most cases, but it isrecommended to check the suitability in the actual application.

AutoInitMode: automatic activating of ZCVPSOF is, by default, set to DLD disabled,which means the dead-line logic detection is disabled. If an automatic activation of thedead-line detection is required, the parameter AutoInitMode has to be set to eitherVoltage, Current or Current & Voltage.

When AutoInitMode is set to Voltage, the dead-line detection logic checks that thetwo-phase voltages are lower than the set UPh< level.

When AutoInitMode is set to Current, the dead-line detection logic checks if the two-phase currents are lower than the set IPh< level.

When AutoInitMode is set to Current & Voltage, the dead-line detection logic checksthat both two-phase currents and two-phase voltages are lower than the set IPh< andUPh< levels.

Otherwise, the logic is activated by an external BC input.

tSOTF: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is suitablefor most applications.

tDLD: The time delay for activating ZCVPSOF by the internal dead-line detection is,by default, set to 0.2 seconds. It is suitable in most applications. The delay shall not beset too short to avoid unwanted activations during transients in the system.

Mode: The operation of ZCVPSOF has three modes for defining the criteria fortripping. The setting of Mode is, by default, UILevel, which means that the trippingcriterion is based on the setting of IPh< and UPh<. The choice of UILevel gives afaster and more sensitive operation of the function, which is important for reducing the

Section 7 1MRK 506 375-UEN -Impedance protection

92 Railway application RER670 2.2 IECApplication manual

Page 99: Railway application RER670 Version 2.2 IEC ... - ABB

stress that might occur when energizing onto a fault. However, the voltage recoverycan be slow in some systems when energizing the line. Therefore, if the timertDuration is set too short, ZCVPSOF can interpret this as a fault and release a trip.

When Mode is set to Impedance, the operate criterion is based on the BC input (breakerclosing), which can be the start of the overreaching zone from the impedance zonemeasurement. A nondirectional output signal should be used from an overreachingzone. The selection of the Impedance mode gives increased security.

When Mode is set to UILvl&Imp, the condition for tripping is an ORed betweenUILevel and Impedance.

tDuration: The setting of the timer for the release of UILevel is, by default, 0.02seconds, which has proven to be suitable in most cases from field experience. If ashorter time delay is to be set, it is necessary to consider the voltage recovery timeduring line energization.

7.2 Distance protection, quadrilateral characteristicZRWPDIS

7.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEEidentification

Distance protection, quadrilateralcharacteristic

ZRWPDISZ<

IEC15000305 V1 EN

21

7.2.2 Application

The distance protection, quadrilateral characteristic ZRWPDIS function is applicablefor all earthing types in 2-phase power networks. The SystemEarthing setting isprovided in order to have the distance protection function suitable for a specific typeof earthing system.

The ZRWPDIS application function is designed to detect and clear the faultsmentioned in Table 14 with reliability in order to maintain the system stability.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 93Application manual

Page 100: Railway application RER670 Version 2.2 IEC ... - ABB

Table 14: Earthing systems and possible faults

Earthing system Types of faultCompensated earthing systems • Single phase earth fault of short duration

• Sustained single phase earth fault• Cross country double earth faults• Two phase short circuit with and without

earth connection

Solidly earthing systems • Single phase earth fault• Two phase short circuit with and without

earth connection

High impedance earthing systems • Single phase earth fault• Cross country double earth faults• Two phase short circuit with and without

earth connection

7.2.2.1 Compensated earthing systems

In compensated grids, a distinction must be made between the following types offaults:

• Single earth fault, short-term (< 5sec)• Single earth fault, sustained (> 5sec) (= sustained earth fault)• Double cross country line-to-earth faults with separate earth contact points• Phase-to-phase short-circuit, earthed and unearthed

When the single earth faults occurs, the fault currents are reduced by the earth-faultneutralizers or the active compensation facility level decreases until the flashovers areneutralized automatically. The concerned phase is not to be tripped. However, thefaulty phase has to be identified and indicated (earth-fault protection/determination ofthe earth fault direction).

When the cross country phase-to-earth faults occurs, the two phases have to behandled with different time grading so that a delayed disconnection of the L2 phaseenables elimination of the fault via the earth-fault neutralizing function. The L2 phaseis tripped only if the neutralization after a cross country line-to-earth fault and a tripof the L1 phase has failed.

Phase preference logicIn compensated earthing systems, phase preference logic is used to achieve the correctphase selective tripping during two simultaneous single phase earth faults in differentphases on different line sections.

Due to compensated earthing, the earth faults in these systems involve very low faultcurrents, typically below 25A. At the same time, the system voltage on the healthyphase increases to phase-to-phase voltage level since the neutral displacement is equalto the phase voltage level at a fully developed earth fault. Increase of the healthy phase

Section 7 1MRK 506 375-UEN -Impedance protection

94 Railway application RER670 2.2 IECApplication manual

Page 101: Railway application RER670 Version 2.2 IEC ... - ABB

voltage together with slow tripping increases the risk a second fault in a healthy phaseand the second fault can occur at any location.

UL1'UL2'

IEC15000382-2-en.vsdx

2U0

UL2 UL1

IEC15000382 V2 EN

Figure 37: Phase preference logic

The phase preference logic is mainly used in systems where the single phase-to-earthfaults are not automatically cleared, only alarm is given and the fault remains until asuitable time to send people to track down and repair the fault. When the cross countryfault occurs, the practice is to trip only one of the faulty lines. Alternatively, theresidual earth fault protection is used to trip both lines. But due to the low faultcurrents, long tripping times are used.

Phase preference logic is used to decide the tripping mode for distance protection andthe following two selection modes are provided:

• Equal priority• L1 before L2

The typical waveform of recovery voltage following arc extinction (earth faults) incompensated earthing systems is shown in Figure 38. The resonance establishedbetween the capacitance of system and inductance of Petersen coil delays the recoveryvoltage build up after arc extinction. The resonance enables the dielectric strength ofthe insulation at the point of fault to recover and prevent restriking of the arc. Hence,special care has to be taken in clearing earth faults in compensated earthed systems.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 95Application manual

Page 102: Railway application RER670 Version 2.2 IEC ... - ABB

IEC15000383-1-en.vsdx

10

5

0

- 5

- 10

0 50 100 150 200 250

Time (mS) Time (mS)

IEC15000383 V1 EN

Figure 38: Recovery voltage after arc extinction

Three situations are possible when a cross country double earth fault occurs in thesystem:

• Line L1 is tripped, voltage on line L2 recovers after a while, the distance andresidual current protections reset.

• Line L1 is tripped, voltage on line L2 recovers after a while, the distance andresidual current protections reset, line L2 restrikes immediately after the reset.

• Line L1 is tripped, voltage on line L2 does not recover, the distance and/orresidual current protections does not reset.

After tripping the line with fault on phase L1, wait for a while to make sure that thevoltage on L2 has recovered and the distance and residual protection functions havereset, refer to Figure 38. The time delay to detect cross country fault is normally (0.1- 0.15)s.

After the above event, another restrike occurs on L2, the voltage on L1 increases andthe distance or residual current protection operates again. To confirm that the faultexists on phase L2, phase-to-earth voltage of L1 will be checked. Normally in acompensated earthing system, the change in measured voltage is big if fault persistson L2 and is typically 70% UB.

The voltage function has a reset drop-off about 0.1s to ensure the correct functionwithout timing problems.

Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that hasbeen set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.

Section 7 1MRK 506 375-UEN -Impedance protection

96 Railway application RER670 2.2 IECApplication manual

Page 103: Railway application RER670 Version 2.2 IEC ... - ABB

The default values given should be validated for each application and adopt theappropriate setting values.

The parameters for ZRWPDIS are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.

General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the protection to On or Off.

System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).

LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.

IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.

RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:

max

2

min8.0P

URLd

IECEQUATION15051 V1 EN (Equation 20)

Where,

Pmax is the maximum exporting power

Umin is the minimum voltage for which Pmax can occur

0.8 is security factor.

ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 97Application manual

Page 104: Railway application RER670 Version 2.2 IEC ... - ABB

OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.

OpModetEnd1: It is used to select operation On or Off of the end zone 1.

OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.

tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.

OpModetEnd2: This is used to select the operation On or Off of the end zone 2.

OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.

tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.

OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.

ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.

StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).

Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.

X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.

RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.

RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.

Section 7 1MRK 506 375-UEN -Impedance protection

98 Railway application RER670 2.2 IECApplication manual

Page 105: Railway application RER670 Version 2.2 IEC ... - ABB

I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.

KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.

REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.

ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.

Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.

DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.

LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.

X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.

X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.

REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 99Application manual

Page 106: Railway application RER670 Version 2.2 IEC ... - ABB

RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.

RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.

RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.

RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.

TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.

tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.

OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.

tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.

Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.

DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.

LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.

Section 7 1MRK 506 375-UEN -Impedance protection

100 Railway application RER670 2.2 IECApplication manual

Page 107: Railway application RER670 Version 2.2 IEC ... - ABB

X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.

X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.

REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.

RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.

tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.

tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.

DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 101Application manual

Page 108: Railway application RER670 Version 2.2 IEC ... - ABB

PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.

LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.

X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.

X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.

REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.

RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.

tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.

Section 7 1MRK 506 375-UEN -Impedance protection

102 Railway application RER670 2.2 IECApplication manual

Page 109: Railway application RER670 Version 2.2 IEC ... - ABB

tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.

DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.

PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.

LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.

X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.

X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.

RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.

RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus fault

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 103Application manual

Page 110: Railway application RER670 Version 2.2 IEC ... - ABB

resistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.

tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.

OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.

tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.

Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.

DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.

LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.

X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.

X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.

REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

Section 7 1MRK 506 375-UEN -Impedance protection

104 Railway application RER670 2.2 IECApplication manual

Page 111: Railway application RER670 Version 2.2 IEC ... - ABB

RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.

RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.

RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.

TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.

tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.

tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.

DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.

LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due toremote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.

X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 105Application manual

Page 112: Railway application RER670 Version 2.2 IEC ... - ABB

X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.

RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.

RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.

tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.

tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

Phase SelectionModePhSelKI: This setting is used to enable/disable current ratio of the phasecurrents. The default setting is Off.

KI: The current ratio of phase currents used for phase selection. The recommendedsetting is 2.0.

tI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.

If magnitude of the phase L1 current is more than KI times magnitude of phase L2current together with delayed residual overcurrent start signal and ModePhSelKI is set

Section 7 1MRK 506 375-UEN -Impedance protection

106 Railway application RER670 2.2 IECApplication manual

Page 113: Railway application RER670 Version 2.2 IEC ... - ABB

to Off, the L1E loop will be released for distance measuring. This is valid for phase L2as well.

Phase selection based on residual overcurrent start is done only if the stub mode is notselected. This means that the setting ModeStubline is set to Off and there are no outputsfrom the underimpedance starting loops.

I01: This setting is used to detect the high short circuit current during the blocking timetI01 when starting element impedance loop has picked up. A default setting of 300%IB is used.

tI01: This is used as the blocking time of distance measuring for the transient earthfault. A default setting of 0.1s is used.

The underimpedance start and residual overcurrent start operates in the event of anearth fault. Once the earth fault is detected, it is blocked for a set time delay tI01 toavoid tripping in any of the transient earth fault conditions. However, if the measuredcurrent in a phase exceeds the set value I01 and the respective underimpedance loophas also picked up, the distance measuring loop of that loop is released immediately.This is done in order to clear the high current faults instantaneously. Phase-to-phasefault loop is released if there is output from the under impedance starting and there isno residual overcurrent start output.

I0MinPhSel: This is the minimum current that should be present to detect a phase-to-phase fault. The recommended setting is 4.0% IB.

ModeI0StRel: This is used to release the L1E & L2E / L1L2 distance measuring loopsusing the residual overcurrent start. The default setting is L1E & L2E.

If magnitudes of both phase currents (IL1 and IL2) are almost equal or less than the setvalue I0MinPhSel, it indicates that a phase-to-phase fault has occurred in the system.At this condition, the measuring loops are enabled based on the setting modeModeI0StRel and the respective loops will be released for distance measuring.

Phase preference

The time steps from t0L2 to t6L2 listed below can be selected bysettings OpModet0L2 to OpModet6L2 for stub line and each distancezone 1 to zone 6 respectively.

For faults on phase L2, after distance and direction decision is fulfilled, an alarm willappear and the additional timers t1L2 to t6L2 will start. If the starting element is resetbefore the expiry of (and therefore before trip) the zone timers tPEZx plus basic timetGL2, the UL1E will be checked against a set limit UL1E < U0Min at the end of 100msafter the reset of starting element.

The basic time tGL2 is effective only during the underimpedance or residualovercurrent start. If the voltage UL1E is greater than the set limit U0Min, the startsignal is maintained. A trip will occur if the voltage UL1E does not fall below the setlimit by the end of extra time t1L2 to t6L2 that are assigned to the respective zones.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 107Application manual

Page 114: Railway application RER670 Version 2.2 IEC ... - ABB

ModePhPref: In compensated earthed systems, phase L2 will be specially treated.Two operation modes i.e. Equal priority and L1 before L2 of phase preference variantsare implemented. The default is set to Equal priority.

OpModet0L2: This is used for Off/On operation of the t0L2 timer if phase preferenceis set.

t0L2: This is an additional time delay to the trip phase L2 in stub line.

OpModet1L2: This is used for Off/On operation of the t1L2 timer if phase preferenceis selected. The default setting is On.

t1L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 1. The default setting is 1.5s.

OpModet2L2: This is used for Off/On operation of the t2L2 timer if phase preferenceis selected. The default setting is Off.

t2L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 2. The default setting is 2.5s.

OpModet3L2: This is used for Off/On operation of the t3L2 timer if phase preferenceis selected. The default setting is Off.

t3L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 3. The default setting is 0.0s.

OpModet4L2: This is used for Off/On operation of the t4L2 timer if phase preferenceis selected. The default setting is Off.

t4L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 4. The default setting is 0.0s.

OpModet5L2: This is used for Off/On operation of the t5L2 timer if phase preferenceis selected. The default setting is Off.

t5L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 5. The default setting is 0.0s.

OpModet6L2: This is used for Off/On operation of the t6L2 timer if phase preferenceis selected. The default setting is Off.

t6L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 6. The default setting is 0.0s.

U0Min: This is used to check the minimum residual voltage on phase L1 if the startsignal falls back, and indicates the fault on phase L2 is cleared successfully. Thedefault value is 50% UBase.

tVL2: This is used to extend the time for phase L2 to check the voltage shift. For thetimes from t0L2 to t6L2, a settable time tVL2 (operation time extension L2) is added.

Section 7 1MRK 506 375-UEN -Impedance protection

108 Railway application RER670 2.2 IECApplication manual

Page 115: Railway application RER670 Version 2.2 IEC ... - ABB

When a cross country fault occurs and the phase L1 has tripped, wait for some time toensure that:

• The fault on phase L2 is cleared successfully• The voltage on phase L2 has recovered• The distance and residual protection functions have reset.

OpModetGL2: This is used for Off/On operation of an additional timer tGL2 used inthe compensated earthed network. The default setting is On.

tGL2: This is an additional time delay to trip L2 in compensated earthing. If the startsignal continues to be active, trip is given after expiration tPEZx plus tGL2. Thedefault setting is 0.6s.

dUOverdt: This is the rate of change of voltage for phase L1 and phase L2. When thepriority L1 before L2 is selected, the time steps t1L2, t2L2, t3L2, t4L2, t5L2 and t6L2are extended by tVL2. During trip time of the corresponding zone, a normalization ofthe supply voltage can be identified (i.e. dUL1/dt < dUOverdt and dUL2/dt>dUOverdt). If a restrike of the earth fault is detected during the tVL2 time (i.e. dUL1/dt > dUOverdt, dUL2/dt < dUOverdt), an instantaneous trip will be issued.Calculation of algorithm for both voltage step functions dUL1/dt and dUL2/dt is setwith a common parameter dUOverdt. The default setting is 100 V/s.

Stub lineModeStubLine: This is used to enable/disable the compensated network contains astub line.

UPPMin: This is the minimum phase-to-phase voltage in %UB in case of a stub line.This is considered before deciding to trip the line that has lower phase-to-earthvoltage. The default setting is 80% UB.

tI0Stub: Time delay to trip for residual current in case of a stub line. The default settingis 0.2s.

KU: This is the phase-to-earth voltage ratio in case of a stub line.

7.2.2.2 Solidly earthed systems

In directly earthed networks, a distinction is made between the following types offaults:

• Double phase-to-phase fault, earthed or unearthed• Single phase-to-earth fault

The fault currents are high during all short circuit events. In the event of high-resistance earth faults, e.g. through trees, the earth current is low. These types of faultsshall be detected and tripped selectively by a sensitive earth-fault detection device inconjunction with protection signaling devices.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 109Application manual

Page 116: Railway application RER670 Version 2.2 IEC ... - ABB

Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that hasbeen set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.

The default values given should be validated for each application and adopt theappropriate setting values.

The parameters for ZRWPDIS are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.

General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the protection to On or Off.

System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).

LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.

IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.

RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:

max

2

min8.0P

URLd

IECEQUATION15051 V1 EN (Equation 21)

Where,

Pmax is the maximum exporting power

Umin is the minimum voltage for which Pmax can occur

Section 7 1MRK 506 375-UEN -Impedance protection

110 Railway application RER670 2.2 IECApplication manual

Page 117: Railway application RER670 Version 2.2 IEC ... - ABB

0.8 is security factor.

ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.

OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.

OpModetEnd1: It is used to select operation On or Off of the end zone 1.

OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.

tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.

OpModetEnd2: This is used to select the operation On or Off of the end zone 2.

OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.

tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.

OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.

ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.

StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).

Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.

X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.

RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 111Application manual

Page 118: Railway application RER670 Version 2.2 IEC ... - ABB

RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.

I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.

KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.

REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.

ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.

Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.

DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.

LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.

X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.

X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.

Section 7 1MRK 506 375-UEN -Impedance protection

112 Railway application RER670 2.2 IECApplication manual

Page 119: Railway application RER670 Version 2.2 IEC ... - ABB

REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.

RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.

RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.

RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.

TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.

tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.

OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.

tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.

Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.

DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 113Application manual

Page 120: Railway application RER670 Version 2.2 IEC ... - ABB

LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.

X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.

X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.

REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.

RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.

tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.

tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

Section 7 1MRK 506 375-UEN -Impedance protection

114 Railway application RER670 2.2 IECApplication manual

Page 121: Railway application RER670 Version 2.2 IEC ... - ABB

Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.

DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.

LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.

X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.

X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.

REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.

RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 115Application manual

Page 122: Railway application RER670 Version 2.2 IEC ... - ABB

tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.

tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.

DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.

PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.

LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.

X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.

X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.

RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus fault

Section 7 1MRK 506 375-UEN -Impedance protection

116 Railway application RER670 2.2 IECApplication manual

Page 123: Railway application RER670 Version 2.2 IEC ... - ABB

resistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.

RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.

tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.

OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.

tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.

Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.

DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.

LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.

X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.

X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 117Application manual

Page 124: Railway application RER670 Version 2.2 IEC ... - ABB

REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.

RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.

RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.

TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.

tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.

tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.

DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.

LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due to

Section 7 1MRK 506 375-UEN -Impedance protection

118 Railway application RER670 2.2 IECApplication manual

Page 125: Railway application RER670 Version 2.2 IEC ... - ABB

remote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.

X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.

X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.

RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.

RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.

tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.

tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

Phase selectiontI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 119Application manual

Page 126: Railway application RER670 Version 2.2 IEC ... - ABB

7.2.2.3 High impedance earthing systems

In isolated/high impedance networks, following types of errors can be anticipated:

• 2-phase short circuit, with or without earth connection• Single phase-to-earth fault• cross country double earth faults

For double earth faults, the disconnection by the distance measurement should beselective.

For single phase earth fault in isolated systems, voltage shifts occur and a smallcapacitive current generates. Trip will occur after a time delay. In an isolated neutralsystem, the neutral has no intentional connection to earth. The system is connected toearth through the phase-to-earth capacitances. Single phase-to-earth faults will shiftthe system neutral voltage.

Earth fault

IEC15000384-1-en.vsdx

IEC15000384 V1 EN

Figure 39: Earth fault in isolated systems

Two major earth fault-current limiting factors are possible for the isolated earthingsystems; the zero sequence phase-to-earth capacitance and fault resistance. Since thevoltage and their phase angles are relatively undisturbed, these systems can remainoperational during the sustained low magnitude faults.

Self-extinction of earth faults in the overhead lines is possible for the low values ofearth fault current. At higher magnitudes of fault current, faults are unlikely to self-extinguish at the natural zero crossing of fault current because of the high transientrecovery voltage.

The zero sequence voltage relays can detect earth faults in the isolated systems. Thismethod of fault detection is not selective and requires sequential disconnection orisolation of the feeders to determine the faulted feeder.

Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that has

Section 7 1MRK 506 375-UEN -Impedance protection

120 Railway application RER670 2.2 IECApplication manual

Page 127: Railway application RER670 Version 2.2 IEC ... - ABB

been set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.

The default values given should be validated for each application and adopt theappropriate setting values.

The parameters for ZRWPDIS are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.

General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the protection to On or Off.

System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).

LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.

IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.

OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.

RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:

max

2

min8.0P

URLd

IECEQUATION15051 V1 EN (Equation 22)

Where,

Pmax is the maximum exporting power

Umin is the minimum voltage for which Pmax can occur

0.8 is security factor.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 121Application manual

Page 128: Railway application RER670 Version 2.2 IEC ... - ABB

ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.

OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.

OpModetEnd1: It is used to select operation On or Off of the end zone 1.

OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.

tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.

OpModetEnd2: This is used to select the operation On or Off of the end zone 2.

OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.

tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.

OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.

ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.

StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).

Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.

X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.

RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.

RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to a

Section 7 1MRK 506 375-UEN -Impedance protection

122 Railway application RER670 2.2 IECApplication manual

Page 129: Railway application RER670 Version 2.2 IEC ... - ABB

value greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.

I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.

KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.

REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.

DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.

ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.

Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.

DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.

LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.

X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.

X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.

REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 123Application manual

Page 130: Railway application RER670 Version 2.2 IEC ... - ABB

XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.

RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.

RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.

RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.

TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.

tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.

OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.

tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.

Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.

DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.

LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive fault

Section 7 1MRK 506 375-UEN -Impedance protection

124 Railway application RER670 2.2 IECApplication manual

Page 131: Railway application RER670 Version 2.2 IEC ... - ABB

due to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.

X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.

X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.

REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.

RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.

TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.

tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.

tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.

Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 125Application manual

Page 132: Railway application RER670 Version 2.2 IEC ... - ABB

DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.

PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.

LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.

X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.

X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.

REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.

RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.

TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.

tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

Section 7 1MRK 506 375-UEN -Impedance protection

126 Railway application RER670 2.2 IECApplication manual

Page 133: Railway application RER670 Version 2.2 IEC ... - ABB

OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.

tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.

Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.

DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.

PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.

LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.

X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.

X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.

RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 127Application manual

Page 134: Railway application RER670 Version 2.2 IEC ... - ABB

RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.

TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.

tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.

OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.

tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.

Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.

DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.

LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.

X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.

X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.

REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.

Section 7 1MRK 506 375-UEN -Impedance protection

128 Railway application RER670 2.2 IECApplication manual

Page 135: Railway application RER670 Version 2.2 IEC ... - ABB

RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.

RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.

RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.

RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.

TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.

tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.

tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.

zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.

DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.

PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.

LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.

LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due toremote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.

X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 129Application manual

Page 136: Railway application RER670 Version 2.2 IEC ... - ABB

X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.

REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.

RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.

RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.

RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.

TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.

OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.

tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.

tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.

Phase SelectiontI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.

ModeU0DetMin: This is used to enable/disable the neutral voltage shift protection.The default setting is Off.

U0DetMin: This is used to set the minimum operate value for the neutral voltage shift.The default value is 20% UB.

Section 7 1MRK 506 375-UEN -Impedance protection

130 Railway application RER670 2.2 IECApplication manual

Page 137: Railway application RER670 Version 2.2 IEC ... - ABB

UDispOpModeU0: This is used for the Off/On operation of the neutral voltage displacementlogic. The default value is Off.

UMinDisp: This is used to check the neutral voltage displacement for single phase-earth-faults occur in the system. The default setting is 150% UB.

tU0: This is the time delay to trip for the neutral voltage displacement start. The defaultvalue is 5.0s.

7.2.3 Setting examples

7.2.3.1 Compensated earthed systems

Example in Figure 40 illustrates how the distance protection ZRWPDIS protects a110kV overhead transmission line. The earthing considered is compensated earthedsystem.

Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 areconsidered in this example. Zones 4, 5 and 6 can be set on similar lines depending onthe application they are being used.

All the settings for impedance are in Ohms Primary.

Z<

A B C

Line 1 Line 2

IEC15000385-1-en.vsdx

IEC15000385 V1 EN

Figure 40: Considered single line diagram

Table 15: System Data

Parameter ValueSystem Voltage 110kV

System Frequency 16.7Hz

Full load 50MVA

Short time maximum Power 250% of Full load

Minimum operating voltage 90% of rated voltage

PT Ratio 110kV/110V

CT Ratio 600/1A

Line length A-B 50km

Line length B-C 100km

Positive sequence impedance of line 0.097 + j0.112 Ohm/km = 0.1481 ∟ 49.3° Ohm/km

Table continues on next page

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 131Application manual

Page 138: Railway application RER670 Version 2.2 IEC ... - ABB

Parameter ValueZero sequence impedance of line 0.151 + j0.298 Ohm/km = 0.334 ∟ 63.13° Ohm/km

Arc resistance 2 Ohm

Tower footing resistance 10 Ohm

GeneralCommon base IED values for primary current (IBase) and primary voltage (UBase)are set in a Global base values for settings function GBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

IBase: Sets the base current in primary ampere. This is 50MVA/110kV = 454.54A.

UBase: Sets the base voltage in kV. This is 110.0kV.

Operation: Sets the protection to On/Off. Set this to On.

System Earthing: It is used to select the type of system earthing. Select theCompensated.

LineAng: Set it to 50 deg.

IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. Set this to 10% IB.

IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. Set this to 10% IB.

OpLoadEnch: This setting is used to select the load discrimination characteristic. Setthis to On.

RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. RLd can be calculated according to equation:

max

2

min8.0P

URLd

IECEQUATION15051 V1 EN (Equation 23)

Where,

Pmax is the maximum exporting power = 2.5 times the rated power of 50MVA.

Umin is the minimum voltage which can be taken as 90% of 110.0kV which is equalto 99kV.

0.8 is security factor.

Therefore RLd = 0.8 (99.0)2 /2.5 x 50.0 = 62.7 Ohm.

Section 7 1MRK 506 375-UEN -Impedance protection

132 Railway application RER670 2.2 IECApplication manual

Page 139: Railway application RER670 Version 2.2 IEC ... - ABB

ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. Set this to 30 deg.

OpModetEnd1: It is used to select the On/Off operation of the first stage timer tEnd1.Set this to On.

OpDirEnd1: This is used to select the direction mode of end zone 1. Set this toForward.

tEnd1: This is used to set time delay for the first stage remote backup. Set this higherthan zone 3 time delay of 0.7s plus additional delays provided. Set this to the default2.5s.

OpModetEnd2: This is used to select the operation On/Off of the second stage timertEnd2. Set this to On.

OpDirEnd2: This is used to select the direction mode of the end zone 2. Set this toNon-directional.

tEnd2: This is used to set the time delay for the second stage trip. Set this after thetEnd1 has operated. Since the tEnd1 is set to 2.5s, set it to 3.0s.

OpModeGenSt: This is used to select On/Off of zone timers start by general startsignal. Set this to On.

ZoneCharSym: This is used to set On/Off of the zone symmetry. Set this to Symmetry.

StartCharStartZ<: It is used to select the underimpedance start characteristic. Set this toQuadrilateral.

X1Start: This is to set positive sequence reactance reach of the starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea.

Therefore, set the X1Start to 150% of zone 3 reach. Zone 3 reach being 20.16 Ohm, setX1Start to 1.5 x 20.16 = 30.24 Ohm.

RFPEStart: This is used to set the forward and reverse resistive reach for PE startingelement. It will be set to operate for all faults within the protected area. To providemaximum coverage for the high resistive faults, it may be set as high as possiblesubject to check of possibility against load point encroachment.

Therefore, set this to 80% of the setting RLd resistive reach of the starter. The settingRLd being 62.7 Ohm, the RFPEStart can be set to 0.8 x 62.7 = 50.16 Ohm.

I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. Set this to 10% IB.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 133Application manual

Page 140: Railway application RER670 Version 2.2 IEC ... - ABB

KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. Set this to 0.8.

DirectionArgNegRes: This is the angle for blinder in the second quadrant. Set this to 120 deg.

ArgDir: This is the angle of setting in the fourth quadrant. Set this to 15 deg.

Zone 1OpZ1: Set this to On.

DirModeZ1: This is used to set the zone 1 direction mode. Set this to Forward.

PhSelModeZ1: This is used to enable the measuring loops of zone 1. Set this to Phsellogic.

LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.Set this to On.

LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. Set this to On.

X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. The recommended setting is 90% of the protected line length.

Therefore, set the X1FwZ1 to 0.9 x 50.0 x 0.112 = 5.6 Ohm.

REoverRLZ1: It provides zero sequence compensation for phase-to-earth faults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 24)

Therefore, set this to 0.28.

XEoverXLZ1: It provides zero sequence compensation for phase-to-earth faults.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 25)

Therefore, set this to 0.83.

RFPEFwZ1: It should be set to give maximum coverage considering the arc resistanceand tower footing resistance.

Arc resistance = 2 Ohm primary and Tower footing resistance = 10 Ohm Primary.Therefore, RFPEFwZ1 should be minimum of 12 Ohm.

Since the RFPEStart is set to 50.16 Ohm to give more resistive coverage, RFPEFwZ1can be set at 0.8 x 50.16 = 40.13 Ohm. However, to avoid overreach due to the remote

Section 7 1MRK 506 375-UEN -Impedance protection

134 Railway application RER670 2.2 IECApplication manual

Page 141: Railway application RER670 Version 2.2 IEC ... - ABB

end infeed, it is recommended that the resistive reach does not exceed 4.5 timesreactive reach.

Therefore, RFPEFwZ1 may be set to 4.5 x X1FwZ1 = 4.5 x 5.6 = 25.52 Ohm.

RFPPFwZ1: It should be set to cover the arc resistance for phase-to-phase faults. Itmay be set identical to RFPEFwZ1, which is 25.52 Ohm.

TimerSelZ1: This is used to set the zone timer selection mode of zone 1. Set this toTimers Separated.

OpModetPEZ1: Set this to On.

tPEZ1: Set this to 0.0s.

OpModetPPZ1: Set this to On.

tPPZ1: Set this to 0.0s.

Zone 2OpZ2: Set this to On.

DirModeZ2: This is used to set the zone 2 direction mode. Set this to Forward.

PhSelModeZ2: This is used to enable the measuring loops of zone 2. Set this to Phsellogic.

LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.Set this to On.

LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. Set this to Off.

X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. This should be set to 120% of line 1 reactance.

Therefore, set the X1FwZ2 to 1.2 x 50 x 0.112 = 6.72 Ohm.

REoverRLZ2: It provides zero sequence compensation for phase-to-earth faults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 26)

Therefore, set this to 0.28.

XEoverXLZ2: It provides zero sequence compensation for phase-to-earth faults.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 27)

Therefore, set this to 0.83.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 135Application manual

Page 142: Railway application RER670 Version 2.2 IEC ... - ABB

RFPEFwZ2: It should be set to give maximum coverage considering the maximumpermissible load.

Since the RFPEFwStart is set to 50.16 Ohm to give more resistive coverage,RFPEFwZ2 can be set at 0.8 x 50.16 = 40.13 Ohm.

RFPPFwZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.

TimerSelZ2: This is used to set the zone timer selection mode of zone 2. Set this toTimers Separated.

OpModetPEZ2: Set this to On.

tPEZ2: Choose a time delay for zone 2 with margin to assure selectivity to zone 1 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient.Therefore, the time delay for zone 2 can be set to 0.4s.

OpModetPPZ2: Set this to On.

tPPZ2: Set this identical to tPEZ2, which is 0.4s.

Zone 3OpZ3: This is for operation Off/On of zone 3. Set this to On.

DirModeZ3: This is used to set the zone 3 direction mode. Set this to Forward.

PhSelModeZ3: This is used to enable the zone 3 measuring loops. Set this to Phsellogic.

LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.Set this to On.

LCModeZ3: This is used to enable/disable load compensation mode for zone 3. Setthis to Off.

X1FwZ3: This is used to set the forward positive sequence reactance reach for zone 3in Ohm/p. This should be set to 120% of reactance of (Line 1 + Line 2).

Therefore, set X1FwZ3 to 1.2 x (50 +100) x 0.112 = 20.16 Ohm.

REoverRLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 28)

Therefore, set this to 0.28.

XEoverXLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.

Section 7 1MRK 506 375-UEN -Impedance protection

136 Railway application RER670 2.2 IECApplication manual

Page 143: Railway application RER670 Version 2.2 IEC ... - ABB

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 29)

Therefore, set this to 0.83.

RFPEFwZ3: This may be set identical to setting RFPEFwZ2 which is 40.13 Ohm.

RFPPFwZ3: This may be set identical to setting RFPEFwZ3 which is 40.13 Ohm.

TimerSelZ3: This is used for Zone timer selection mode of zone 3. Set this to Timersseparated.

OpModetPEZ3: Set this to On.

tPEZ3: Choose a time delay for zone 3 with a margin to assure selectivity to zone 2 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient. Thetime delay for zone 3 therefore can be set to 0.8s.

OpModetPPZ3: Set this to On.

tPPZ3: Set this identical to tPPZ3 = 0.8s.

Zones 4, 5 and 6 can be set on similar lines based on the application.

Phase selectionModePhSelKI: Set this to Off.

KI: Set this to 1.2.

I01: This setting is used to detect high short circuit current during blocking time tI01when starting element impedance loop has picked up. Set at 400% IB.

ModeI0StRel: Set this to L1E and L2E

I0MinPhSel: Set this to 4% IB.

tI0: This is delay time for residual overcurrent start. Residual overcurrent start isdelayed by settable time delay tI0. Set this to 0.2s.

tI01: This is blocking time of distance measuring for transient earth fault. Set this to0.1s.

Phase preferenceModePhPref: Set this to L1 before L2.

OpModet1L2: Set this to On.

t1L2: Set this to 1.0s.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 137Application manual

Page 144: Railway application RER670 Version 2.2 IEC ... - ABB

OpModet2L2: Set this to On.

t2L2: Set this to 2.0s.

OpModet3L2: Set this to On.

t3L2: Set this to 3.0s.

U0Min: This is used to check minimum residual voltage if start signal falls back. Setthis to 50% UB.

tVL2: This is used to extend the time for phase L2 to check the voltage shift. To timet0L2 to t6L2 is a settable time tVL2 (operation time extension L2) added. Set this to0.5s.

OpModetGL2: Set this to On.

tGL2: This is an additional time delay to trip L2 in compensated earthing. If the startsignal continues to be active, trip is given after expiration tPEZx plus tGL2. Set this to0.6s.

dUOverdt: Set this to 100V/s.

Stub lineModeStubLine: Set this to Off.

7.2.3.2 Solidly earthed systems

Example in Figure 41 illustrates how the distance protection ZRWPDIS protects a110kV overhead transmission line. The earthing considered is solidly earthed system.

Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 areconsidered in this example. Zones 4, 5 and 6 can be set on similar lines depending onthe application they are being used.

All the settings for impedance are in Ohms Primary.

Z<

A B C

Line 1 Line 2

IEC15000385-1-en.vsdx

IEC15000385 V1 EN

Figure 41: Considered single line diagram

Section 7 1MRK 506 375-UEN -Impedance protection

138 Railway application RER670 2.2 IECApplication manual

Page 145: Railway application RER670 Version 2.2 IEC ... - ABB

Table 16: System Data

Parameter ValueSystem Voltage 110kV

System Frequency 16.7Hz

Full load 50MVA

Short time maximum Power 250% of Full load

Minimum operating voltage 90% of rated voltage

PT Ratio 110kV/110V

CT Ratio 600/1A

Line length A-B 50km

Line length B-C 100km

Positive sequence impedance of line 0.097 + j0.112 Ohm/km = 0.1481 ∟ 49.3° Ohm/km

Zero sequence impedance of line 0.151 + j0.298 Ohm/km = 0.334 ∟ 63.13° Ohm/km

Arc resistance 2 Ohm

Tower footing resistance 10 Ohm

GeneralCommon base IED values for primary current (IBase) and primary voltage (UBase)are set in a Global base values for settings function GBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

IBase: Sets the base current in primary ampere. This is 50MVA/110kV = 454.54A.

UBase: Sets the base voltage in kV. This is 110.0kV.

Operation: Sets the protection to On/Off. Set this to On.

System Earthing: It is used to select the type of system earthing. Select theCompensated.

LineAng: Set it to 50 deg.

IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. Set this to 10% IB.

IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. Set this to 10% IB.

OpLoadEnch: This setting is used to select the load discrimination characteristic. Setthis to On.

RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. RLd can be calculated according to equation:

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 139Application manual

Page 146: Railway application RER670 Version 2.2 IEC ... - ABB

max

2

min8.0P

URLd

IECEQUATION15051 V1 EN (Equation 30)

Where,

Pmax is the maximum exporting power = 2.5 times the rated power of 50MVA.

Umin is the minimum voltage which can be taken as 90% of 110.0kV which is equalto 99kV.

0.8 is security factor.

Therefore RLd = 0.8 (99.0)2 /2.5 x 50.0 = 62.7 Ohm.

ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. Set this to 30 deg.

OpModetEnd1: It is used to select the On/Off operation of the first stage timer tEnd1.Set this to On.

OpDirEnd1: This is used to select the direction mode of end zone 1. Set this toForward.

tEnd1: This is used to set time delay for the first stage remote backup. Set this higherthan zone 3 time delay of 0.7s plus additional delays provided. Set this to the default2.5s.

OpModetEnd2: This is used to select the operation On/Off of the second stage timertEnd2. Set this to On.

OpDirEnd2: This is used to select the direction mode of the end zone 2. Set this toNon-directional.

tEnd2: This is used to set the time delay for the second stage trip. Set this after thetEnd1 has operated. Since the tEnd1 is set to 2.5s, set it to 3.0s.

OpModeGenSt: This is used to select On/Off of zone timers start by general startsignal. Set this to On.

ZoneCharSym: This is used to set On/Off of the zone symmetry. Set this toNonsymmetry.

StartCharStartZ<: It is used to select the underimpedance start characteristic. Set this toQuadrilateral.

X1Start: This is to set positive sequence reactance reach of the starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea.

Section 7 1MRK 506 375-UEN -Impedance protection

140 Railway application RER670 2.2 IECApplication manual

Page 147: Railway application RER670 Version 2.2 IEC ... - ABB

Therefore, set the X1Start to 150% of zone 3 reach. Zone 3 reach being 20.16 Ohm, setX1Start to 1.5 x 20.16 = 30.24 Ohm.

RFPEStart: This is used to set the forward and reverse resistive reach for PE startingelement. It will be set to operate for all faults within the protected area. To providemaximum coverage for the high resistive faults, it may be set as high as possiblesubject to check of possibility against load point encroachment.

Therefore, set this to 80% of the setting RLd resistive reach of the starter. The settingRLd being 62.7 Ohm, the RFPEStart can be set to 0.8 x 62.7 = 50.16 Ohm.

RFPPStart: This is used to set the forward and reverse resistive reach for PP startingelement. This may be set equal to RFPEStart, which is 50.16 Ohm.

I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. Set this to 10% IB.

KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. Set this to 0.8.

REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 31)

XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 32)

DirectionArgNegRes: This is the angle for blinder in the second quadrant. Set this to 120 deg.

ArgDir: This is the angle of setting in the fourth quadrant. Set this to 15 deg.

Zone 1OpZ1: Set this to On.

DirModeZ1: This is used to set the zone 1 direction mode. Set this to Forward.

PhSelModeZ1: This is used to enable the measuring loops of zone 1. Set this to Phsellogic.

LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.Set this to On.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 141Application manual

Page 148: Railway application RER670 Version 2.2 IEC ... - ABB

LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. Set this to On.

X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. The recommended setting is 90% of the protected line length.

Therefore, set the X1FwZ1 to 0.9 x 50.0 x 0.112 = 5.6 Ohm.

X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. Set this to 5.6 Ohm.

REoverRLZ1: It provides zero sequence compensation for phase-to-earth faults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 33)

Therefore, set this to 0.28.

XEoverXLZ1: It provides zero sequence compensation for phase-to-earth faults.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 34)

Therefore, set this to 0.83.

RFPEFwZ1: It should be set to give maximum coverage considering the arc resistanceand tower footing resistance.

Arc resistance = 2 Ohm primary and Tower footing resistance = 10 Ohm Primary.Therefore, RFPEFwZ1 should be minimum of 12 Ohm.

Since the RFPEStart is set to 50.16 Ohm to give more resistive coverage, RFPEFwZ1can be set at 0.8 x 50.16 = 40.13 Ohm. However, to avoid overreach due to the remoteend infeed, it is recommended that the resistive reach does not exceed 4.5 timesreactive reach.

Therefore, RFPEFwZ1 may be set to 4.5 x X1FwZ1 = 4.5 x 5.6 = 25.52 Ohm.

RFPERvZ1: It may be set identical to RFPEFwZ1, which is 25.52 Ohm.

RFPPFwZ1: It should be set to cover the arc resistance for phase-to-phase faults. Itmay be set identical to RFPEFwZ1, which is 25.52 Ohm.

RFPPRvZ1: It may be set identical to RFPPFwZ1, which is 25.52 Ohm.

TimerSelZ1: This is used to set the zone timer selection mode of zone 1. Set this toTimers Separated.

OpModetPEZ1: Set this to On.

tPEZ1: Set this to 0.0s.

Section 7 1MRK 506 375-UEN -Impedance protection

142 Railway application RER670 2.2 IECApplication manual

Page 149: Railway application RER670 Version 2.2 IEC ... - ABB

OpModetPPZ1: Set this to On.

tPPZ1: Set this to 0.0s.

Zone 2OpZ2: Set this to On.

DirModeZ2: This is used to set the zone 2 direction mode. Set this to Forward.

PhSelModeZ2: This is used to enable the measuring loops of zone 2. Set this to Phsellogic.

LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.Set this to On.

LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. Set this to Off.

X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. This should be set to 120% of line 1 reactance.

Therefore, set the X1FwZ2 to 1.2 x 50 x 0.112 = 6.72 Ohm.

X1RvZ2: Set this identical to X1FwZ2 which is 6.72 Ohm.

REoverRLZ2: It provides zero sequence compensation for phase-to-earth faults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 35)

Therefore, set this to 0.28.

XEoverXLZ2: It provides zero sequence compensation for phase-to-earth faults.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 36)

Therefore, set this to 0.83.

RFPEFwZ2: It should be set to give maximum coverage considering the maximumpermissible load.

Since the RFPEFwStart is set to 50.16 Ohm to give more resistive coverage,RFPEFwZ2 can be set at 0.8 x 50.16 = 40.13 Ohm.

RFPERvZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.

RFPPFwZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.

RFPPRvZ2: It may be set identical to RFPPFwZ2, which is 40.13 Ohm.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 143Application manual

Page 150: Railway application RER670 Version 2.2 IEC ... - ABB

TimerSelZ2: This is used to set the zone timer selection mode of zone 2. Set this toTimers Separated.

OpModetPEZ2: Set this to On.

tPEZ2: Choose a time delay for zone 2 with margin to assure selectivity to zone 1 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient.Therefore, the time delay for zone 2 can be set to 0.4s.

OpModetPPZ2: Set this to On.

tPPZ2: Set this identical to tPEZ2, which is 0.4s.

Zone 3OpZ3: This is for operation Off/On of zone 3. Set this to On.

DirModeZ3: This is used to set the zone 3 direction mode. Set this to Forward.

PhSelModeZ3: This is used to enable the zone 3 measuring loops. Set this to Phsellogic.

LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.Set this to On.

LCModeZ3: This is used to enable/disable load compensation mode for zone 3. Setthis to Off.

X1FwZ3: This is used to set the forward positive sequence reactance reach for zone 3in Ohm/p. This should be set to 120% of reactance of (Line 1 + Line 2).

Therefore, set X1FwZ3 to 1.2 x (50 +100) x 0.112 = 20.16 Ohm.

X1RvZ3: Set this identical to X1FwZ3 which is 20.16 Ohm.

REoverRLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.

28.01097.0

151.0

2

11

2

1

1

0

R

R

R

R

L

E

IECEQUATION15052 V1 EN (Equation 37)

Therefore, set this to 0.28.

XEoverXLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.

83.01112.0

298.0

2

11

2

1

1

0

X

X

X

X

L

E

IECEQUATION15053 V1 EN (Equation 38)

Therefore, set this to 0.83.

Section 7 1MRK 506 375-UEN -Impedance protection

144 Railway application RER670 2.2 IECApplication manual

Page 151: Railway application RER670 Version 2.2 IEC ... - ABB

RFPEFwZ3: This may be set identical to setting RFPEFwZ2 which is 40.13 Ohm.

RFPERvZ3: It is set identical to setting RFPEFwZ3 which is 40.13 Ohm.

RFPPFwZ3: This may be set identical to setting RFPEFwZ3 which is 40.13 Ohm.

RFPPRvZ3: It is set identical to setting RFPEFwZ3 which is 40.13 Ohm.

TimerSelZ3: This is used for Zone timer selection mode of zone 3. Set this to Timersseparated.

OpModetPEZ3: Set this to On.

tPEZ3: Choose a time delay for zone 3 with a margin to assure selectivity to zone 2 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient. Thetime delay for zone 3 therefore can be set to 0.8s.

OpModetPPZ3: Set this to On.

tPPZ3: Set this identical to tPPZ3 = 0.8s.

Zones 4, 5 and 6 can be set on similar lines based on the application.

Phase selectiontI0: It is strongly recommended not to use residual overcurrent based phase selectionincase of solidly earthed systems. Hence, set this to 60.0s.

7.3 Underimpedance protection for railway transformersZGTPDIS

7.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEEidentification

Underimpedance protection for railwaytransformers

ZGTPDISZ<

IEC15000305 V1 EN

21T

7.3.2 Application

ZGTPDIS is generally used as backup protection for faults on the transformer and theassociated transmission lines. These transformers can be classified in two basiccategories:

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 145Application manual

Page 152: Railway application RER670 Version 2.2 IEC ... - ABB

• 2-phase to 2-phase Interconnecting transformers• 2-phase to 1-phase Interconnecting transformers

IEC15000302-1-en.vsdx

Trafo 132/15kV

15kV132kV

U

VV

2-phase to 1-phase interconnectionIEC15000302 V2 EN

IEC15000304-2-en.vsdx

Trafo 132/66kV

66kV132kV

U

VV

U

2-phase to 2-phase interconnectionIEC15000304 V2 EN

Figure 42: Railway transformers connection examples

ZGTPDIS function can be used as primary protection as well as backup protection forthe transformer. It protects both HV and LV side of the transformer. The protection isdesigned to operate for earth faults and phase faults in the transformer and theassociated lines.

Zone 1 can be used to provide high-speed protection for faults in the HV winding ofthe transformer. Zone 2 can be used to cover the entire transformer and substation LVbusbar. Zone 3 can be used to cover power system faults beyond the LV busbar.

Section 7 1MRK 506 375-UEN -Impedance protection

146 Railway application RER670 2.2 IECApplication manual

Page 153: Railway application RER670 Version 2.2 IEC ... - ABB

Backup impedance protection characteristicsThe characteristics of zone 1, zone 2 and zone 3 are shown in Figure 43. All zones haveeither offset mho or non-directional quadrilateral characteristics with adjustable reachin forward and reverse direction. Quadrilateral characteristics have additionalresistive blinders in forward and reverse direction. The quadrilateral characteristiclimits the resistive reach and helps to avoid incorrect operations due to loadencroachment. All three zones have the same characteristic angle which can beadjusted using ImpCharAng setting.

IEC15000196-2-en.vsdx

RFRevZxRFFwZx

ImpCharAng

RFFwZx

RFRevZx RFFwZx

R(Ω)

jX(Ω)

R (Ω)

ZxFwd

ImpCharAng

ZxRev

jX(Ω)

IEC15000196 V2 EN

Figure 43: Non-directional quadrilateral and mho offset characteristic forZGTPDIS

7.3.2.1 Zone 1 operation

For transformer applications, the zone 1 element is typically set to see 70% of thetransformer impedance.

7.3.2.2 Zone 2 operation

Zone 2 can be used to cover the LV side of the transformer and the associated busbar.It is usually set to cover 125% of the transformer impedance. The time to trip must beprovided in order to coordinate with the zone 1 element on the shortest outgoing linefrom the bus.

7.3.2.3 Zone 3 operation

Zone 3 covers the whole of the transformer, the interconnecting station bus to thenetwork and outgoing lines. Within its operating zone, the tripping time for this relayshould be coordinated with the longest time delay of the distance relays on theoutgoing LV lines.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 147Application manual

Page 154: Railway application RER670 Version 2.2 IEC ... - ABB

7.3.3 Setting guidelines

Settings for underimpedance protection for transformers (ZGTPDIS) are done inprimary values. The instrument transformer ratio that has been set for the analog inputcard is used to automatically convert the measured secondary input signals to primaryvalues used in ZGTPDIS.

Default values mentioned below should be validated for each application andappropriate setting values should be adopted.

Parameters for ZGTPDIS application function are set via local HMI or Protection andControl Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: This is used for underimpedance protection Off/On.

ImpCharAng: This is to set the common characteristic angle for all three zones ofunderimpedance element. ImpCharAng should match the associated transformerimpedance angle.

IMinOp: This is to select the minimum operating current for underimpedance element.If the minimum current is exceeded, underimpedance protection calculates theimpedance. A default setting of 10% of IB is recommended.

Zone 1

OpModeZ1: This is to select the operating characteristic of zone 1 underimpedanceelement. This can be selected as Off/Mho offset/Quad non-dir.

Z1Fwd: This is to set the zone 1 forward positive sequence impedance reach in ohm/p. It is recommended to set this to 70% of transformer impedance.

Z1Rev: This is to set the zone 1 reverse positive sequence impedance reach in ohm/p.This should be set as 1% of transformer impedance or lower for better security in caseof reverse faults.

RFFwZ1: This is to set the zone 1 forward fault resistive reach in ohm/p whenquadrilateral characteristic is chosen. It should be set to give maximum coverage offault resistance and the load encroachment (RLdmax).

max

minmax

I

URLd

IECEQUATION226 V2 EN (Equation 39)

Section 7 1MRK 506 375-UEN -Impedance protection

148 Railway application RER670 2.2 IECApplication manual

Page 155: Railway application RER670 Version 2.2 IEC ... - ABB

RFRevZ1: This is to set the zone 1 reverse fault resistive reach in ohm/p whenquadrilateral characteristic is chosen. It may be set identical to RFFwZ1.

tZ1: This is to set the zone 1 time delay to trip. Default setting is 0.0s.

Zone 2

OpModeZ2: This is to select the operating characteristic of zone 2 distance element.This can be selected as Off/Mho offset/Quad non-dir.

Z2Fwd: This is to set the zone 2 forward positive sequence impedance reach in ohm/p. It is recommended to set this to 125% of transformer impedance.

Z2Rev: This is to set the zone 2 reverse positive sequence impedance reach in ohm/p.The recommended setting is 80% of shortest outgoing line in the reverse direction inorder to cover the bus faults.

RFFwZ2: This is to set the zone 2 forward fault resistive reach in ohm/p ifquadrilateral characteristic is selected. It should be set to give maximum coverage offault resistance and the load encroachment (RLdmax).

RFRevZ2: This is to set the zone 2 reverse fault resistive reach in ohm/p if quadrilateralcharacteristic is selected. It may be set identical to RFFwZ2.

tZ2: This is to set the zone 2 time delay to trip. The default setting is 0.5s. It should beset to coordinate with clearance of adjacent circuit fault within reach by the intendedmain protection or breaker fail protection.

Zone 3

OpModeZ3: This is to select the operating characteristic of the zone 3 distanceelement. This can be selected as Off/Mho offset/Quad non-dir.

Z3Fwd: This is to set the zone 3 forward positive sequence impedance reach in ohm/p. It should be set to overreach the remote terminal of the longest adjacent line about20% for all fault conditions.

Z3Rev: This is to set the zone 3 reverse positive sequence impedance reach in ohm/p.This may be set identical to Z2Rev.

RFFwZ3: This is to set the zone 3 forward fault resistive reach in ohm/p ifquadrilateral characteristic is chosen. It should be set to give maximum coverage ofthe fault resistance and load encroachment.

RFRevZ3: This is to set the zone 3 reverse fault resistive reach in ohm/p if quadrilateralcharacteristic is chosen. It may be set identical to RFFwZ3.

tZ3: This is to set the zone 3 time delay to trip. Time delay is used to coordinate withthe slowest circuit backup protection or slowest local backup for faults within zone 3reach. The default setting is 1.5s.

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 149Application manual

Page 156: Railway application RER670 Version 2.2 IEC ... - ABB

7.3.4 Catenary Protection

The ZGTPDIS function can also be utilized for catenary line protection. By using it asimple, three-zone underimpedance protection with independent reach in forward andreverse direction can be easily achieved. Consider the following:

• ZGTPDIS function is using full cycle DFT filtering. Thus, all higher harmonicsare effectively suppressed in measured current and voltage signals.

• The start time of the individual underimpedance zones is typically slightly biggerthan one fundamental power system cycle.

• If directional operation is required (e.g. operation for faults in forward directiononly), the operation of the individual underimpedance zones can be supervised byforward start of the directional overcurrent function D2PTOC. Several instancesof this function are readily available in the IED.

• Second harmonic blocking feature may be required for catenary protection. Forthis purpose, second harmonic blocking feature available in D2PTOC functioncan be utilized.

• Sometimes supervision by sudden change in current and/or voltage signals isrequired for catenary protection. For this purpose, individual zones can besupervised by outputs STDI and STDU from the FRWSPVC function. Severalinstances of FRWSPVC function are readily available in the IED.

• To achieve any of the above mentioned supervisions, correspondingconfiguration logic and appropriate setting in the PCM600 tool shall be done.

• For external supervision from any additional logic input BLKZx on theZGTPDIS function shall be used in the IED configuration.

7.3.5 Wrong phase coupling protection

The ZGTPDIS function in combination with directional overcurrent functionD2PTOC and associated configuration logic can be utilized for wrong phase couplingprotection. The operating characteristic as shown in Figure 44 can be easily achieved.To achieve such application, a simple configuration logic and appropriate setting inthe PCM600 tool shall be done.

Section 7 1MRK 506 375-UEN -Impedance protection

150 Railway application RER670 2.2 IECApplication manual

Page 157: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000116-1-en.vsdx

R

X

Z2

Z1

WrongPhase

Coupling

IEC16000116 V1 EN

Figure 44: Wrong phase coupling protection

1MRK 506 375-UEN - Section 7Impedance protection

Railway application RER670 2.2 IEC 151Application manual

Page 158: Railway application RER670 Version 2.2 IEC ... - ABB

152

Page 159: Railway application RER670 Version 2.2 IEC ... - ABB

Section 8 Current protection

8.1 Instantaneous phase overcurrent protection 2-phaseoutput PHPIOC

8.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous phase overcurrentprotection 2-phase output

PHPIOC

2I>>

IEC15000110 V1 EN

50

8.1.2 Application

The transient stability of a power system depends mostly on three parameters (atconstant amount of transmitted electric power):

• The type of the fault. Two-phase faults are the most dangerous, because no powercan be transmitted through the fault point during fault conditions.

• The magnitude of the fault current. A high fault current indicates that the decreaseof transmitted power is high.

• The total fault clearing time. The phase angles between the EMFs of thegenerators on both sides of the transmission line increase over the permittedstability limits if the total fault clearing time, which consists of the protectionoperating time and the breaker opening time, is too long.

The fault current on railway lines depends mostly on the fault position and decreaseswith the distance from the infeed point. For this reason the protection must operatevery quickly for faults very close to the relay point, for which very high fault currentsare characteristic.

The instantaneous phase overcurrent protection PHPIOC can operate in one-half ofthe fundamental power system cycle for faults characterized by very high currents.

8.1.3 Setting guidelines

The parameters for instantaneous phase overcurrent protection PHPIOC are set via thelocal HMI or PCM600.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 153Application manual

Page 160: Railway application RER670 Version 2.2 IEC ... - ABB

This protection function must operate only in a selective way. So check all system andtransient conditions that could cause its unwanted operation.

Only detailed network studies can determine the operating conditions under which thehighest possible fault current is expected on the line. In most cases, this currentappears during two-phase fault conditions. But also examine single-phase-to-earthcondition.

Also study transients that could cause a high increase of the line current for shorttimes. A typical example is a line with a power transformer at the remote end, whichcan cause high inrush current when connected to the network and can thus also causethe operation of the built-in, instantaneous, overcurrent protection.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: Set the protection to On/Off.

IP>>: Set operate current in % of IB.

IP>>Max and IP>>Min should only be changed if remote setting of operation currentlevel, IP>>, is used. The limits are used for decreasing the used range of the IP>>setting. If IP>> is set outside IP>>Max and IP>>Min, the closest of the limits toIP>> is used by the function. If IP>>Max is smaller than IP>>Min, the limits areswapped.

IP>>MinEd2Set: Minimum settable operate phase current level in % of IBase, forIEC 61850 Ed. 2 settings.

IP>>MaxEd2Set: Maximum settable operate phase current level in % of IBase, forIEC 61850 Ed. 2 settings.

8.1.3.1 Meshed network without parallel line

The following fault calculations have to be done for two-phase and single-phase-to-earth faults. With reference to Figure 45, apply a fault in B and then calculate thethrough-fault phase current IfB. The calculation should be done using the minimumsource impedance values for ZA and the maximum source impedance values for ZB inorder to get the maximum through fault current from A to B.

Section 8 1MRK 506 375-UEN -Current protection

154 Railway application RER670 2.2 IECApplication manual

Page 161: Railway application RER670 Version 2.2 IEC ... - ABB

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsd

IEC09000022 V1 EN

Figure 45: Through fault current from A to B: IfB

Then a fault in A has to be applied and the through fault current IfA has to be calculated,Figure 46. In order to get the maximum through fault current, the minimum value forZB and the maximum value for ZA have to be considered.

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 46: Through fault current from B to A: IfA

The IED must not trip for any of the two through-fault currents. Hence the minimumtheoretical current setting (Imin) will be:

Imin MAX IfA IfB,( )³

EQUATION78 V1 EN (Equation 40)

A safety margin of 5% for the maximum protection static inaccuracy and a safetymargin of 5% for the maximum possible transient overreach have to be introduced. Anadditional 20% is suggested due to the inaccuracy of the instrument transformersunder transient conditions and inaccuracy in the system data.

The minimum primary setting (Is) for the instantaneous phase overcurrent protectionis then:

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 155Application manual

Page 162: Railway application RER670 Version 2.2 IEC ... - ABB

min1.3sI I³ ×

EQUATION79 V3 EN (Equation 41)

The protection function can be used for the specific application only if this settingvalue is equal to or less than the maximum fault current that the IED has to clear, IF inFigure 47.

IEC09000024-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I F

Fault

IEC09000024 V1 EN

Figure 47: Fault current: IF

100Is

IPIBase

>>= ×

EQUATION1147 V3 EN (Equation 42)

8.2 Two-step directional phase overcurrent protectionD2PTOC

8.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Directional phase overcurrentprotection, two steps

D2PTOC2(2I>)

2

2alt

IEC15000155 V2 EN

51_67

8.2.2 Application

The two-step directional phase overcurrent protection D2PTOC is used in severalapplications in the power system. Some applications are:

Section 8 1MRK 506 375-UEN -Current protection

156 Railway application RER670 2.2 IECApplication manual

Page 163: Railway application RER670 Version 2.2 IEC ... - ABB

• Short circuit protection of feeders.• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers.

In many applications several steps with different current pickup levels and time delaysare needed. D2PTOC can have one or two, individually settable steps. The followingoptions are possible:

Non-directional / Directional function: In most applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed from theprotected object itself. In order to achieve both selectivity and fast fault clearance, thedirectional function can be necessary.

If VT inputs are not available or not connected, the setting parameterDirModex (x = step 1, 2) shall be left to the default value Non-directional.

Choice of time delay characteristics: There are several types of time delaycharacteristics available such as definite time delay and different types of inverse timedelay characteristics. The selectivity between different overcurrent protections isnormally enabled by co-ordination between the function time delays of the differentprotections. To enable optimal co-ordination between all overcurrent protections,they should have the same time delay characteristic. Therefore, several inverse timecharacteristics are available within D2PTOC function.

Normally, it is required that the phase overcurrent protection shall reset as fast aspossible when the current level gets lower than the operation level.

Power transformers can have a large inrush current, when being energized. Thisphenomenon is due to saturation of the transformer magnetic core during parts of theperiod. There is a risk that inrush current will reach levels above the pick-up currentof the phase overcurrent protection. The inrush current has a large 2nd harmoniccontent. This can be used to avoid unwanted operation of the protection function.Therefore, D2PTOC has a possibility of 2nd harmonic restrain if the level of 2nd

harmonic component reaches a value above a set percent of the fundamentalfrequency current.

8.2.3 Setting guidelines

When inverse time overcurrent characteristic is selected, the operatetime of the stage will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that stage to zero.

The parameters for two-step directional phase overcurrent protection D2PTOC are setvia the local HMI or Protection and Control Manager PCM600.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 157Application manual

Page 164: Railway application RER670 Version 2.2 IEC ... - ABB

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

The parameter settings for the base quantities, which represent the base (100%) forpickup levels of all measuring stages, shall be entered as setting parameters for everyD2PTOC function.

For two-phase railway supply system, IBase shall be entered as:

• Rated phase current of the protected object in primary amperes, when themeasured current quantity is selected other than phase1-phase2, which is shownin Table 17.

• Rated phase current of the protected object in primary amperes multiplied by 2.0(i.e. 2.0*Iphase), when the measured current quantity is selected as phase1-phase2, which is shown in Table 17.

For two-phase railway supply system, UBase shall be entered as:

• Rated phase-to-earth voltage of the protected object in primary kV, when themeasured voltage quantity is selected other than phase1-phase2, which is shownin Table 18.

• Rated phase-to-phase voltage of the protected object in primary kV, when themeasured voltage quantity is selected as phase1-phase2, which is shown in Table18.

Operation: This is used for two-step directional phase overcurrent protection Off/On.

CurrentInput: This is used to select the type of energizing quantity (i.e. phasor) forcurrent and will be used as operating quantity for operation of both overcurrent steps.

Table 17: Current selection for D2PTOC function

Set value for the parameter CurrentInput Commentphase1 D2PTOC function will measure the phase L1

current

phase2 D2PTOC function will measure the phase L2current

posSeq D2PTOC function will measure internallycalculated positive sequence current 1 2 / 2IL IL

Table continues on next page

Section 8 1MRK 506 375-UEN -Current protection

158 Railway application RER670 2.2 IECApplication manual

Page 165: Railway application RER670 Version 2.2 IEC ... - ABB

Set value for the parameter CurrentInput Comment

MaxPh1) D2PTOC function will measure current of thephase with maximum magnitude

phase1-phase2 D2PTOC function will measure the currentinternally calculated as the vector differencebetween the phase L1 current and phase L2current IL IL

1) = Note that MaxPh current selection shall not be used when D2PTOC function is used as directional.It shall be only used when function is used for non-directional operation.

VoltageInput: This is used to select the type of energizing quantity (i.e. phasor) forvoltage and will be used as polarizing signal to detect the direction of faults if any ofthe two steps is set for Forward/Reverse mode of operation.

Table 18: Voltage selection for D2PTOC function

Set value for the parameter VoltageInput Commentphase1 D2PTOC function will measure the phase L1

voltage

phase2 D2PTOC function will measure the phase L2voltage

PosSeq D2PTOC function will measure internallycalculated positive sequence voltage 1 2 / 2UL UL

phase1-phase2 D2PTOC function will measure the voltageinternally calculated as the vector differencebetween the phase L1 voltage and phase L2voltage UL UL

For directional operation of the D2PTOC function, the identicalvalues for current and voltage measurement selection shall be set (e.g.both set to PosSeq, or both set to phase1).

OperHarmRestr: This is used to Off/On the 2nd harmonic restrain feature for theD2PTOC function.

I_2nd/I_fund: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 10.0 - 50.0% in steps of 1%. The defaultsetting is 20%.

RCADir: Relay characteristic angle set in degrees. It defines the middle line of theforward operating sector in the directional plane.

ROADir: Relay operate angle value, given in degrees, to define the width of theforward operating sector in the directional plane, shown in Figure 48.

LowVolt: This is used to set low-voltage level in % of UBase for the directiondetection. If measure voltage is below this set level, the setting ActLowVoltx (wherex = 1 & 2) decides the function behavior.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 159Application manual

Page 166: Railway application RER670 Version 2.2 IEC ... - ABB

Uref

Idir

IEC09000636_2_vsd

1

2

2

3

4

IEC09000636 V2 EN

Figure 48: Directional function characteristic

1. RCA = Relay characteristic angle2. ROA = Relay operating angle3. Reverse4. Forward

8.2.3.1 Settings for step 1

Operation1: This is used to Off/On the operation of step 1.

StartCurr1: This is used to set operate current level for step 1 given in % of IBase.

CurveType1: Selection of time characteristic for step 1. Definite time delay anddifferent types of inverse time characteristics are available according to Table 19.

Section 8 1MRK 506 375-UEN -Current protection

160 Railway application RER670 2.2 IECApplication manual

Page 167: Railway application RER670 Version 2.2 IEC ... - ABB

Table 19: Inverse time characteristics

Curve nameIEC Normal Inverse

IEC Very Inverse

IEC Extremely Inverse

IEC Definite Time

ASEA RI type

tDef1: Definite time delay for step 1. The definite time tDef1 is added to the inversetime when inverse time characteristic is selected. Note that the value set is the timebetween activation of the start and the trip outputs.

k1: Time multiplier for inverse time delay for step 1.

IMin1: Minimum operate current for step 1 in % of IBase.

tMin1: Minimum operate time for all inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter, the operation time of the step can never be shorter than the setting. Settingrange: 0.000 - 60.000s in steps of 0.001s.

Operate

time

Current

tDef1

tMin1

IMin1

IEC16000212-1-en.vsdx

IEC16000212 V1 EN

Figure 49: Minimum operate current and operate time for inverse timecharacteristics

In order to fully comply with the definition of the curve, the setting parameter tMin1shall be set to a value equal to the operating time of the selected inverse curve fortwenty times the set current pickup value. Note that the operate time is dependent onthe selected time multiplier setting k1.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 161Application manual

Page 168: Railway application RER670 Version 2.2 IEC ... - ABB

HarmRestr1: This is used to block the operation of step1 from the 2nd harmonicrestrain function. This function should be used when there is a risk of an unwanted tripcaused by power transformer inrush currents. It can be set to Off/On.

DirMode1: This is used to set the directional mode of step 1. The possible modes areNon-directional/Forward/Reverse.

ActLowVolt1: This is used to define directional step behavior when the measuredvoltage is below set LowVolt level. The possible modes of operation are Non-directional/block/Memory. It is set to Memory by default.

8.2.3.2 Settings for step 2

Operation2: This is used to Off/On the operation of step 2.

StartCurr2: This is used to set operate phase current level for step 2 given in % ofIBase.

tDef2: Definite time delay for step 2. Note that the value set is the time betweenactivation of the start and the trip outputs.

HarmRestrain2: This is used to block the operation of step 2 from the 2nd harmonicrestrain function. This function should be used when there is a risk if powertransformer inrush currents might cause unwanted trip. It can be set Off/On.

DirMode2: This is used to set the directional mode of step 2. The possible modes areNon-directional/Forward/Reverse.

ActLowVolt2: This is used to define directional step behavior when the measuredvoltage is below set LowVolt level. The possible modes of operation are Non-directional/block/Memory. It is set to Memory by default.

8.3 Instantaneous residual overcurrent protectionEFRWPIOC

8.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous residual overcurrentprotection

EFRWPIOC

IN>>

IEF V1 EN

50N

Section 8 1MRK 506 375-UEN -Current protection

162 Railway application RER670 2.2 IECApplication manual

Page 169: Railway application RER670 Version 2.2 IEC ... - ABB

8.3.2 Application

In many applications, when fault current is limited to a defined value by the objectimpedance, an instantaneous earth-fault protection can provide fast and selectivetripping.

8.3.3 Setting guidelines

The parameters for the Instantaneous residual overcurrent protection EFRWPIOC areset via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

The basic requirement is to assure selectivity, that is EFRWPIOC shall not be allowedto operate for faults at other objects than the protected object (line).

For a normal line in a meshed system single phase-to-earth faults and phase-to-phase-to-earth faults shall be calculated as shown in Figure 50 and Figure 51. The residualcurrents (3I0) to the protection are calculated. For a fault at the remote line end thisfault current is IfB. In this calculation the operational state with high source impedanceZA and low source impedance ZB should be used. For the fault at the home busbar thisfault current is IfA. In this calculation the operational state with low source impedanceZA and high source impedance ZB should be used.

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsd

IEC09000022 V1 EN

Figure 50: Through fault current from A to B: IfB

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 163Application manual

Page 170: Railway application RER670 Version 2.2 IEC ... - ABB

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 51: Through fault current from B to A: IfA

The function shall not operate for any of the calculated currents to the protection. Theminimum theoretical current setting (Imin) will be:

Im ,fA fBin MAX I I

EQUATION284 V2 EN (Equation 43)

A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%for maximum possible transient overreach have to be introduced. An additional 20%is suggested due to inaccuracy of instrument transformers under transient conditionsand inaccuracy in the system data.

The minimum primary current setting (Is) is:

Is = 1.3 × Imin EQUATION285 V3 EN (Equation 44)

In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,as shown in Figure 52, should be calculated.

Section 8 1MRK 506 375-UEN -Current protection

164 Railway application RER670 2.2 IECApplication manual

Page 171: Railway application RER670 Version 2.2 IEC ... - ABB

IEC09000025-1-en.vsd

~ ~ZA ZB

ZL1A B

I M

Fault

IED

ZL2

M

CLine 1

Line 2

IEC09000025 V1 EN

Figure 52: Two parallel lines. Influence from parallel line to the through faultcurrent: IM

The minimum theoretical current setting (Imin) will in this case be:

I m in M AX IfA I fB IM, ,( )³

EQUATION287 V1 EN (Equation 45)

Where:

IfA and IfB have been described for the single line case.

Considering the safety margins mentioned previously, the minimum setting (Is) is:

Is = 1.3 × Imin EQUATION288 V3 EN (Equation 46)

Transformer inrush current shall be considered.

The setting of the protection is set as a percentage of the base current (IBase).

Operation: set the protection to On or Off.

IN>>: Set operate current in % of IB.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 165Application manual

Page 172: Railway application RER670 Version 2.2 IEC ... - ABB

8.4 Two step residual overcurrent protection EF2PTOC

8.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step residual overcurrent protection EF2PTOC

2(IN>)

IEC15000229 V1 EN

51N_67N

8.4.2 Application

The two step residual overcurrent protection EF2PTOC is used in several applicationsin the power system. Some applications are:

• Earth-fault protection of feeders in effectively earthed two-phase railway supplysystem. Normally these feeders have radial structure.

• Back-up earth-fault protection of transmission lines.• Sensitive earth-fault protection of transmission lines. EF2PTOC can have better

sensitivity to detect resistive phase-to-earth-faults compared to distanceprotection.

• Back-up earth-fault protection of power transformers.• Earth-fault protection of different kinds of equipment connected to the power

system such as shunt capacitor banks and others.

In many applications, several steps with different current operating levels and timedelays are needed. EF2PTOC can have up to two, individual settable steps. Theflexibility of each step of EF2PTOC is great. The following options are possible:

Non-directional/Directional: In some applications the non-directional functionality isused. This is mostly the case when no fault current can be fed from the protected objectitself. In order to achieve both selectivity and fast fault clearance, the directionalfunctionality may be necessary. Note that for directional operation additional logic inthe IED configuration tool is needed.

Choice of time characteristics: There are several types of time characteristicsavailable such as definite time delay and different types of inverse timecharacteristics. The selectivity between different overcurrent protections is normallyenabled by co-ordination between the operate time of the different protections. Toenable optimal co-ordination all overcurrent protections, to be co-ordinated againsteach other, should have the same time characteristic.

Section 8 1MRK 506 375-UEN -Current protection

166 Railway application RER670 2.2 IECApplication manual

Page 173: Railway application RER670 Version 2.2 IEC ... - ABB

Table 20: Time characteristics

Curve nameIEC Normal Inverse

IEC Very Inverse

IEC Extremely Inverse

IEC Definite Time

ASEA RI

Normally it is required that EF2PTOC shall reset as fast as possible when the currentlevel gets lower than the operation level.

8.4.3 Setting guidelines

When inverse time overcurrent characteristic is selected, the operatetime of the step will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that step to zero.

The parameters for the two step residual overcurrent protection, zero sequencedirection EF2PTOC is set via the local HMI or PCM600.

The following settings can be done for the two step residual overcurrent protection.

GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.

Operation: Sets the protection to On or Off.

8.4.3.1 Settings for each step (x = 1 and 2)

DirModex: The directional mode of step x. Possible settings are Off/Non-directional.

Characterist1: Selection of time characteristic for step 1. Definite time delay anddifferent types of inverse time characteristics are available.

Inverse time characteristic enables fast fault clearance of high current faults at thesame time as selectivity to other inverse time phase overcurrent protections can beassured. This is mainly used in radial fed networks but can also be used in meshednetworks. In meshed networks the settings must be based on network faultcalculations.

To assure selectivity between different protections, in the radial network, there haveto be a minimum time difference Dt between the time delays of two protections. Theminimum time difference can be determined for different cases. To determine theshortest possible time difference, the operation time of protections, breaker openingtime and protection resetting time must be known. These time delays can vary

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 167Application manual

Page 174: Railway application RER670 Version 2.2 IEC ... - ABB

significantly between different protective equipment. The following time delays canbe estimated:

Protection operate time: 15-60 ms

Protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

The different characteristics are described in the technical reference manual.

INx>: Operate residual current level for step x given in % of IBase.

kx: Time multiplier for the dependent (inverse) characteristic for step x.

IN1Min: Minimum operate current for step 1 in % of IBase.

t1Min: Minimum operating time for inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter the operation time of the step can never be shorter than the setting.

Current

Operatetime

IN1Min

t1Min

IEC15000250-1-en.vsdx

IEC15000250 V1 EN

Figure 53: Minimum operate current and operate time for inverse timecharacteristics

In order to fully comply with curves definition the setting parameter t1Min shall be setto the value which is equal to the operate time of the selected IEC inverse curve for

Section 8 1MRK 506 375-UEN -Current protection

168 Railway application RER670 2.2 IECApplication manual

Page 175: Railway application RER670 Version 2.2 IEC ... - ABB

measured current of twenty times the set current pickup value. Note that the operatetime value is dependent on the selected setting value for time multiplier k1.

8.4.3.2 Common settings

tx: Definite time delay for step x. Used if definite time characteristic is chosen.

AngleRCA: Relay characteristic angle given in degree. This angle is defined as shownin Figure 54. The angle is defined positive when the residual current lags the referencevoltage (Upol = -2U0)

Upol = -2U0

I>Dir

RCA

Operation

IEC16000027-1-en.vsdx

IEC16000027 V1 EN

Figure 54: Relay characteristic angle given in degree

In a normal transmission network a normal value of RCA is about 65°.

Normally voltage polarizing from the internally calculated residual sum or an externalopen delta is used.

UPolMin: Minimum polarization (reference) polarizing voltage for the directionalfunction, given in % of UBase/2.

I>Dir: Operate residual current release level in % of IB for directional stage. Thesetting is given in % of IB. The output signals, STFW and STRV can be used in ateleprotection scheme. The appropriate signal should be configured to thecommunication scheme block.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 169Application manual

Page 176: Railway application RER670 Version 2.2 IEC ... - ABB

8.4.3.3 2nd harmonic restrain

If a power transformer is energized there is a risk that the current transformer core willsaturate during part of the period, resulting in a transformer inrush current. This willgive a declining residual current in the network, as the inrush current is deviatingbetween the phases. There is a risk that the residual overcurrent function will give anunwanted trip. The inrush current has a relatively large ratio of 2nd harmoniccomponent. This component can be used to create a restrain signal to prevent thisunwanted function.

At current transformer saturation a false residual current can be measured by theprotection. Here the 2nd harmonic restrain can prevent unwanted operation as well.

2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal. The setting is given in % of the fundamental frequencyresidual current.

8.5 Sensitive directional residual overcurrent and powerprotection SDEPSDE

8.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Sensitive directional residual overcurrent and power protection

SDEPSDEIN>

IEC15000260 V1 EN

67N

8.5.2 Application

In networks with high impedance earthing, the phase-to-earth fault current issignificantly smaller than the short circuit currents. Another difficulty for earth faultprotection is that the magnitude of the phase-to-earth fault current is almostindependent of the fault location in the network.

Directional residual current can be used to detect and give selective trip of phase-to-earth faults in high impedance earthed networks. The protection uses the residualcurrent component 2I0 · cos φ, where φ is the angle between the residual current andthe residual voltage (-2U0), compensated with a characteristic angle. Alternatively,the function can be set to strict 2I0 level with a check of angle φ.

Directional residual power can also be used to detect and give selective trip of phase-to-earth faults in high impedance earthed networks. The protection uses the residual

Section 8 1MRK 506 375-UEN -Current protection

170 Railway application RER670 2.2 IECApplication manual

Page 177: Railway application RER670 Version 2.2 IEC ... - ABB

power component 2I0 · 2U0 · cos φ, where φ is the angle between the residual currentand the reference residual voltage, compensated with a characteristic angle.

A normal non-directional residual current function can also be used with definite orinverse time delay.

A backup neutral point voltage function is also available for non-directional residualovervoltage protection.

In an isolated network, that is, the network is only coupled to earth via the capacitancesbetween the phase conductors and earth, the residual current always has -90º phaseshift compared to the residual voltage (2U0). The characteristic angle is chosen to -90ºin such a network.

In resistance earthed networks or in Petersen coil earthed, with a parallel resistor, theactive residual current component (in phase with the residual voltage) should be usedfor the earth fault detection. In such networks, the characteristic angle is chosen to 0º.

As the amplitude of the residual current is independent of the fault location, theselectivity of the earth fault protection is achieved by time selectivity.

When should the sensitive directional residual overcurrent protection be used andwhen should the sensitive directional residual power protection be used? Consider thefollowing:

• Sensitive directional residual overcurrent protection gives possibility for bettersensitivity. The setting possibilities of this function are down to 0.25 % of IBase,1 A or 5 A. This sensitivity is in most cases sufficient in high impedance networkapplications, if the measuring CT ratio is not too high.

• Sensitive directional residual power protection gives possibility to use inversetime characteristics. This is applicable in large high impedance earthed networks,with large capacitive earth fault currents. In such networks, the active faultcurrent would be small and by using sensitive directional residual powerprotection, the operating quantity is elevated. Therefore, better possibility todetect earth faults. In addition, in low impedance earthed networks, the inversetime characteristic gives better time-selectivity in case of high zero-resistive faultcurrents.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 171Application manual

Page 178: Railway application RER670 Version 2.2 IEC ... - ABB

Phase

currentsIN

Phase-earth

voltagesUN

IEC16000210-1-en.vsdx

IEC16000210 V1 EN

Figure 55: Connection of SDEPSDE to analog preprocessing function block

Overcurrent functionality uses true 2I0, i.e. sum of GRPxL1 and GRPxL2. For 2I0 tobe calculated, connection is needed to both two phase inputs.

Directional and power functionality uses IN and UN. If a connection is made toGRPxN this signal is used, else if connection is made only to inputs GRPxL1 andGRPxL2 the internally calculated sum of these inputs (2I0 and 2U0) will be used.

8.5.3 Setting guidelines

The sensitive earth fault protection is intended to be used in high impedance earthedsystems, or in systems with resistive earthing where the neutral point resistor gives anearth fault current larger than what normal high impedance gives but smaller than thephase-to-phase short circuit current.

In a high impedance system the fault current is assumed to be limited by the systemzero sequence shunt impedance to earth and the fault resistance only. All the seriesimpedances in the system are assumed to be zero.

In the setting of earth fault protection, in a high impedance earthed system, the neutralpoint voltage (zero sequence voltage) and the earth fault current will be calculated atthe desired sensitivity (fault resistance). The complex neutral point voltage (zerosequence) can be calculated as:

Section 8 1MRK 506 375-UEN -Current protection

172 Railway application RER670 2.2 IECApplication manual

Page 179: Railway application RER670 Version 2.2 IEC ... - ABB

0

0

21

phase

f

UU

R

Z

IECEQUATION16029 V1 EN (Equation 47)

Where

Uphase is the phase voltage in the fault point before the fault,

Rf is the resistance to earth in the fault point and

Z0 is the system zero sequence impedance to earth

The fault current, in the fault point, can be calculated as:

00

22

2phase

jf

UI I

Z R

IECEQUATION16030 V1 EN (Equation 48)

The impedance Z0 is dependent on the system earthing. In an isolated system (withoutneutral point apparatus) the impedance is equal to the capacitive coupling between thephase conductors and earth:

0

2 phasec

j

UZ jX j

I

IECEQUATION16031 V1 EN (Equation 49)

Where

Ij is the capacitive earth fault current at a non-resistive phase-to-earth fault

Xc is the capacitive reactance to earth

In a system with a neutral point resistor (resistance earthed system) the impedance Z0can be calculated as:

0

2

2c n

c n

jX RZ

jX R

IECEQUATION16032 V1 EN (Equation 50)

Where

Rn is the resistance of the neutral point resistor

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 173Application manual

Page 180: Railway application RER670 Version 2.2 IEC ... - ABB

In many systems there is also a neutral point reactor (Petersen coil) connected to oneor more transformer neutral points. In such a system the impedance Z0 can becalculated as:

0

4/ /2 / / 2

2 2 2n n c

c n nn c n n c

R X XZ jX R j X

X X j R X X

IECEQUATION16033 V1 EN (Equation 51)

Where

Xn is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 2Xn = Xc In thiscase the impedance Z0 will be: Z0 = 2Rn

Now consider a system with an earthing via a resistor giving higher earth fault currentthan the high impedance earthing. The series impedances in the system can no longerbe neglected. The system with a single phase to earth fault can be described as inFigure 56.

Substation A

Substation B

ZlineAB,1 (pos. seq) ZlineAB,0 (zero seq)

Zl ineBC,1 (pos. seq) Zl ineBC,0 (zero seq)

U0A

U0B

2I0

Phase to earth fault

RN

ZT,1 (pos. seq) ZT,0 (zero seq)

Source impedance Zsc (pos. seq)

IEC16000126-1-en.vsdx

IEC16000126 V1 EN

Figure 56: Equivalent of power system for calculation of setting

The residual fault current can be written:

Section 8 1MRK 506 375-UEN -Current protection

174 Railway application RER670 2.2 IECApplication manual

Page 181: Railway application RER670 Version 2.2 IEC ... - ABB

01 0

22

2 2phase

f

UI

Z Z R

IECEQUATION16034 V1 EN (Equation 52)

Where

Uphase is the phase voltage in the fault point before the fault

Z1 is the total positive sequence impedance to the fault point. Z1 = Zsc+ZT,1+ZlineAB,1+ZlineBC,1

Z0 is the total zero sequence impedance to the fault point. Z0 = ZT,0+2RN+ZlineAB,0+ZlineBC,0

Rf is the fault resistance.

The residual voltages in stations A and B can be written:

0 0 ,02 2A T NU I Z R IECEQUATION16097 V1 EN (Equation 53)

0 0 ,0 ,02 2B T N lineABU I Z R Z IECEQUATION16098 V1 EN (Equation 54)

The residual power, measured by the sensitive earth fault protections in A and B willbe:

0 0 02 2A AS U I IECEQUATION16099 V1 EN (Equation 55)

0 0 02 2B BS U I IECEQUATION16100 V1 EN (Equation 56)

The residual power is a complex quantity. The protection will have a maximumsensitivity in the characteristic angle RCA. The apparent residual power componentin the characteristic angle, measured by the protection, can be written:

0 , 0 02 2 cosA prot A AS U I IECEQUATION16101 V1 EN (Equation 57)

0 , 0 02 2 cosB prot B BS U I IECEQUATION16102 V1 EN (Equation 58)

The angles φA and φB are the phase angles between the residual current and theresidual voltage in the station compensated with the characteristic angle RCA.

The protection will use the power components in the characteristic angle direction formeasurement, and as base for the inverse time delay.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 175Application manual

Page 182: Railway application RER670 Version 2.2 IEC ... - ABB

The inverse time delay is defined as:

0 02 2 cosinv

kSN Sreft

I U measured

IECEQUATION16103 V1 EN (Equation 59)

The function can be set On/Off with the setting of Operation.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

RotResU: It is a setting for rotating the polarizing quantity ( 2U0) by 0 or 180 degrees.This parameter is set to 180 degrees by default in order to inverse the residual voltage( 2U0) to calculate the reference voltage (-2U0 e-jRCADir). Since the reference voltageis used as the polarizing quantity for directionality, it is important to set this parametercorrectly.

With the setting OpMode the principle of directional function is chosen.

With OpMode set to 2I0cosfi the current component in the direction equal to thecharacteristic angleRCADir has the maximum sensitivity. The characteristic forRCADir is equal to 0° is shown in Figure 57.

0 , 90RCADir ROADir

02I

0 refang(2I ) ang(2U )

0 ref2U U 02I cos

IEC16000127-1-en.vsdx

IEC16000127 V1 EN

Figure 57: Characteristic for RCADir equal to 0°

The characteristic is for RCADir equal to -90° is shown in Figure 58.

Section 8 1MRK 506 375-UEN -Current protection

176 Railway application RER670 2.2 IECApplication manual

Page 183: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000128-1-en.vsdx

refU

90 , 90RCADir ROADir

02I

02I cos

0(2 ) ( )refang I ang U

02U

IEC16000128 V1 EN

Figure 58: Characteristic for RCADir equal to -90°

When OpMode is set to 2U02I0cosfi the apparent residual power component in thedirection is measured.

When OpMode is set to 2I0 and fi the function will operate if the residual current islarger than the setting INDir> and the residual current angle is within the sectorRCADir ± ROADir.

The characteristic for this OpMode when RCADir = 0° and ROADir = 80° is shown inFigure 59.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 177Application manual

Page 184: Railway application RER670 Version 2.2 IEC ... - ABB

-2U0

Operate area

2I0

RCADir = 0º

ROADir = 80º

IEC16000129-1-en.vsdx

IEC16000129 V1 EN

Figure 59: Characteristic for RCADir = 0° and ROADir = 80°

DirMode is set Forward or Reverse to set the direction of the operation for thedirectional function selected by the OpMode.

All the directional protection modes have a residual current release level settingINRel> which is set in % of IBase. This setting should be chosen smaller than or equalto the lowest fault current to be detected.

All the directional protection modes have a residual voltage release level settingUNRel> which is set in % of UBase. This setting should be chosen smaller than orequal to the lowest fault residual voltage to be detected.

tDef is the definite time delay, given in s, for the directional residual currentprotection.

tReset is the time delay before the definite timer gets reset, given in s. With a tResettime of few cycles, there is an increased possibility to clear intermittent earth faultscorrectly. The setting shall be much shorter than the set trip delay. In case ofintermittent earth faults, the fault current is intermittently dropping below the set valueduring consecutive cycles. Therefore the definite timer should continue for a certaintime equal to tReset even though the fault current has dropped below the set value.

The characteristic angle of the directional functions RCADir is set in degrees. RCADiris normally set equal to 0° in a high impedance earthed network with a neutral pointresistor as the active current component is appearing out on the faulted feeder only.RCADir is set equal to -90° in an isolated network as all currents are mainly capacitive.

Section 8 1MRK 506 375-UEN -Current protection

178 Railway application RER670 2.2 IECApplication manual

Page 185: Railway application RER670 Version 2.2 IEC ... - ABB

ROADir is Relay Operating Angle. ROADir is identifying a window around thereference direction in order to detect directionality. ROADir is set in degrees. Forangles differing more than ROADir from RCADir the function is blocked. The settingcan be used to prevent unwanted operation for non-faulted feeders, with largecapacitive earth fault current contributions, due to CT phase angle error.

INCosPhi> is the operate current level for the directional function when OpMode isset 2I0Cosfi. The setting is given in % of IBase. The setting should be based oncalculation of the active or capacitive earth fault current at required sensitivity of theprotection.

SN> is the operate power level for the directional function when OpMode is set2I02U0Cosfi. The setting is given in % of SBase. The setting should be based oncalculation of the active or capacitive earth fault residual power at required sensitivityof the protection.

The input transformer for the Sensitive directional residual over current and powerprotection function has the same short circuit capacity as the phase currenttransformers. Hence, there is no specific requirement for the external CT core, i.e. anyCT core can be used.

If the time delay for residual power is chosen the delay time is dependent on twosetting parameters. SRef is the reference residual power, given in % of SBase. kSN isthe time multiplier. The time delay will follow the following expression:

0 02 2 cosinv

kSN Sreft

I U measured

IECEQUATION16103 V1 EN (Equation 60)

INDir> is the operate current level for the directional function when OpMode is set2I0 and fi. The setting is given in % of IBase. The setting should be based oncalculation of the earth fault current at required sensitivity of the protection.

OpINNonDir> is set On to activate the non-directional residual current protection.

INNonDir> is the operate current level for the non-directional function. The setting isgiven in % of IBase. This function can be used for detection and clearance of cross-country faults in a shorter time than for the directional function. The current settingshould be larger than the maximum single-phase residual current on the protected line.

TimeChar is the selection of time delay characteristic for the non-directional residualcurrent protection. Definite time delay and different types of inverse timecharacteristics are available:

Table 21: Inverse time characteristics

Curve nameANSI Extremely Inverse

ANSI Very Inverse

ANSI Normal Inverse

Table continues on next page

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 179Application manual

Page 186: Railway application RER670 Version 2.2 IEC ... - ABB

Curve nameANSI Moderately Inverse

ANSI/IEEE Definite time

ANSI Long Time Extremely Inverse

ANSI Long Time Very Inverse

ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

User Programmable

ASEA RI

RXIDG (logarithmic)

See chapter “Inverse time characteristics” in Technical Manual for the description ofdifferent characteristics

tPCrv, tACrv, tBCrv, tCCrv: Parameters for customer creation of inverse timecharacteristic curve (Curve type = 17). The time characteristic equation is:

[ ] = + ×

->

æ öç ÷ç ÷ç ÷æ öç ÷ç ÷è øè ø

p

At s B InMult

iC

inEQUATION1958 V1 EN (Equation 61)

tINNonDir is the definite time delay for the non directional earth fault currentprotection, given in s.

OpUN> is set On to activate the trip function of the residual over voltage protection.

tUN is the definite time delay for the trip function of the residual voltage protection,given in s.

8.6 Thermal overload protection, one time constant,Celsius LPTTR

Section 8 1MRK 506 375-UEN -Current protection

180 Railway application RER670 2.2 IECApplication manual

Page 187: Railway application RER670 Version 2.2 IEC ... - ABB

8.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Thermal overload protection, one timeconstant, Celsius

LPTTR

θ>

26

8.6.2 Application

Equipment in the power system is designed for a certain maximum load current level.If the current exceeds this level the losses will be higher than expected. As aconsequence the temperature of the conductors will increase. If temperature of theequipment reaches too high values, the equipment might be damaged:

• The sag of overhead lines can reach unacceptable value.• If the temperature of conductors, for example aluminium conductors, gets too

high the material will be destroyed.• In cables the insulation can be damaged as a consequence of the overtemperature.

As a consequence of this phase to phase or phase to earth faults can occur.• The paper insulation used inside a power transformer will deteriorate quicker and

expected life of the transformer will be shortened. Even an internal flash-overmay occur.

In stressed situations in the power system it can be required to overload lines andtransformers for a limited time. This should be done while managing the risks safely.

The thermal overload protection provides information that makes a temporaryoverloading possible. The thermal overload protection estimates the conductortemperature continuously in Celsius. This estimation is made by using a thermalmodel based on the current measurement.

If the temperature of the protected object reaches a set alarm level AlarmTemp, asignal ALARM can be given to the operator. This enables actions in the power systemto be taken before dangerous temperatures are reached. If the temperature continuesto increase to the trip value TripTemp, the protection initiates trip of the protectedobject.

The following applications are possible by using thermal overload protection functionwith one time constant LPTTR:

• Thermal overload protection of overhead lines where the outside air temperatureis given as the ambient temperature to the function. Alternatively, an averageoutside air temperature can be given as a setting value. Note that for suchapplication, the primary conductor heating time constant shall be used. Thereference temperature TRef shall be set as primary conductor temperature raiseabove the ambient temperature for the set reference current. The trip temperature

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 181Application manual

Page 188: Railway application RER670 Version 2.2 IEC ... - ABB

TripTemp shall be set as maximum permissible primary conductor temperature indegrees Centigrade.

• Thermal overload protection of power cables. Note that for such application, theambient temperature shall actually represent the soil temperature. Note that forsuch application, the overall cable heating time constant shall be used. Thereference temperature TRef shall be set as primary conductor temperature raiseabove the soil temperature for the set reference current. The trip temperatureTripTemp shall be set as maximum permissible cable temperature in degreesCentigrade.

• Thermal overload protection of power transformer where the outside airtemperature is given as the ambient temperature to the function. Alternatively, anaverage outside air temperature can be given as a setting value. Note that for suchapplication, the power transformer oil heating time constant, which is typicallyavailable from transformer heat run test (i.e. transformer temperature rise test)shall be used. The reference temperature TRef shall be set as top oil temperatureraise above the ambient for the set reference current of 100% (i.e. 60°C inaccordance with IEC 60076-2). The trip temperature TripTemp shall be set asmaximum permissible top oil temperature in degrees Centigrade. For powertransformer manufactured by ABB, a trip value of 105°C is recommended. Thesame value is also recommended in IEC 60076-7 published in 2005.

• Thermal overload protection of power transformers where the top oil temperatureis measured using a sensor and provided to the function as ambient temperature.Note that for such application, the power transformer winding to oil heating timeconstant (i.e. typically much shorter than the power transformer oil heating timeconstant) shall be used. Some typical values of this time constant is around fiveminutes. The reference temperature TRef shall be set as hot-spot windingtemperature rise above the top oil temperature for the set reference current of100% (e.g. 18°C in accordance with IEC 60076-2 published in 2011). If required,additional safety factor (e.g. 1.3) can be used to increase the TRef value. The triptemperature TripTemp shall be set as maximum permissible winding hot-spottemperature in degrees Centigrade. The conservative trip value, in accordancewith IEC 60076-7 published in 2005, is 98°C or 110°C depending on type ofpaper insulation used. Note that higher value can be used if higher relative ageingrates for the power transformer are allowed. For power transformer manufacturedby ABB, the trip value for hot-spot temperature of 130°C is recommended.

• Any of the above four application where additional configuration logic is usedbased on LCPPTR function output TEMP (i.e. estimated protected objecttemperature in degrees Celsius) and associated comparator (i.e. REALCOMP)and timer (i.e. TIMERSET) function blocks. By using such additional logic, forexample, an automatic control of power transformer cooling fans can beengineered within the IED.

8.6.3 Setting guideline

The parameters for the Thermal overload protection, one time constant, CelsiusLPTTR are set via the local HMI or PCM600.

tPulse: Trip signal pulse length.

Section 8 1MRK 506 375-UEN -Current protection

182 Railway application RER670 2.2 IECApplication manual

Page 189: Railway application RER670 Version 2.2 IEC ... - ABB

SensAvailable: Indication for external temperature sensor availability.

DefaultAmbTemp: Default ambient temperature used when external ambienttemperature sensor is set to off or invalid.

DefaultTemp: Initial temperature raise above ambient temperature during startup.

SensMinTemp: Minimum ambient temperature used for limit check.

SensMaxTemp: Maximum ambient temperature used for limit check.

SenInvRstTim: Sensor invalid signal reset time delay.

TmpAmbMin: Ambient temperature minimum value considered for calculation.

The following settings can be done for the thermal overload protection.

Operation: Off/On

GlobalBaseSel is used to select a GBASVAL function for reference of base values,primary current (IBase), primary voltage (UBase) and primary power (SBase).

Imult: Enter the number of lines in case the protection function is applied on multipleparallel lines sharing one CT.

IRef: Reference, steady state current, given in % of IBase that will give a steady state(end) temperature rise TRef. It is suggested to set this current to the maximum steadystate current allowed for the line/cable under emergency operation (a few hours peryear). For power transformer application, the IRef parameter is typically set to 100%(e.g. equal to the rated current) because the heat run tests are typically conducted insuch way.

TRef: Reference temperature rise (end temperature) corresponding to the steady statecurrent IRef. From cable manuals current values with corresponding conductortemperature are often given. These values are given for conditions such as earthtemperature, ambient air temperature, way of laying of cable and earth thermalresistivity. From manuals for overhead conductor temperatures and correspondingcurrent is given. For power transformers, this value is typically available from thepower transformer manual or from the heat run test report.

Tau: The thermal time constant of the protected circuit given in minutes. Please referto equipment manufacturer manuals for details.

TripTemp: Temperature value for trip of the protected circuit. For cables, a maximumallowed conductor temperature is often stated to be 90°C. For overhead lines, thecritical temperature for aluminium conductor is about 90 - 100°C. However, forrailway catenary lines, the critical temperature can be as low as 48°C. For a copperconductor a normal figure is 70°C. For power transformers, it depends on theapplication and used type of paper insulation. Some typical value is around 100°C.

AlarmTemp: Temperature level for alarm of the protected circuit. ALARM signal canbe used as a warning before the circuit is tripped. Therefore the setting shall be lower

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 183Application manual

Page 190: Railway application RER670 Version 2.2 IEC ... - ABB

than the trip level. It shall at the same time be higher than the maximum conductortemperature at normal operation. A suitable setting can be about 15°C below the tripvalue.

ReclTemp: Temperature where lockout signal LOCKOUT from the protection isreleased. When the thermal overload protection trips, a lock-out signal is activated.This signal is intended to block switch in of the protected circuit as long as theconductor temperature is high. The signal is released when the estimated temperatureis below the set value. This temperature value should be chosen below the alarmtemperature.

8.7 Breaker failure protection CCRWRBRF

8.7.1 Application

In the design of the fault clearance system the N-1 criterion is often used. This meansthat a fault needs to be cleared even if any component in the fault clearance system isfaulty. One necessary component in the fault clearance system is the circuit breaker.It is from practical and economical reason not feasible to duplicate the circuit breakerfor the protected object. Instead a breaker failure protection is used.

Breaker failure protection (CCRWRBRF) will issue a back-up trip command to theadjacent circuit breakers in case of failure to trip of the “normal” circuit breaker for theprotected object. The detection of failure to break the current through the breaker ismade by means of either current measurement or status of CB axillary contact.

CCRWRBRF can also give a re-trip. This means that a separate trip signal is sent tothe protected circuit breaker first. The re-trip function can be used to increase theprobability of operation of the breaker, or it can be used to avoid back-up trip of manybreakers in case of mistakes during relay maintenance and testing.

8.7.2 Setting guidelines

The parameters for Breaker failure protection CCRWRBRF application function areset via the local HMI or Protection and Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: This is used for breaker failure protection Off/On.

Section 8 1MRK 506 375-UEN -Current protection

184 Railway application RER670 2.2 IECApplication manual

Page 191: Railway application RER670 Version 2.2 IEC ... - ABB

FunctionMode: This parameter defines the way the detection of failure of the breakeris performed. In the mode Current the current measurement is used for the detection.In the mode Contact the status of breaker auxiliary contact is used as indicator offailure of the breaker. The mode Current/Contact means that either criterion ofdetections can be activated. Contact mode will then be used in situation where thefault current through the circuit breaker is small at the moment when function isinitiated (current level determined by parameter I>BlkCont). This can be the case forsome generator protection application (for example reverse power protection) or incase of line ends with weak end infeed.

RetripMode: This setting states how the re-trip function shall operate. Retrip Offmeans that the re-trip function is not activated. CB Pos Check (circuit breaker positioncheck) and Current means that a phase current must be larger than the operate level toallow re-trip. CB Pos Check (circuit breaker position check) and Contact means re-tripis done when circuit breaker is closed (breaker position is used). No CBPos Checkmeans re-trip is done without any check of breaker position.

Table 22: Dependencies between parameters RetripMode and FunctionMode

RetripMode FunctionMode DescriptionRetrip Off N/A the re-trip function is not

activated

CB Pos Check Current re-trip is done if the phasecurrent is larger than the operatelevel after re-trip time haselapsed

Contact re-trip is done when auxiliarycontact position indicates thatbreaker is still closed after re-triptime has elapsed

Current/Contact both methods according toabove are used but taken intoaccount also I>BlkCont

No CBPos Check Current re-trip is done without check ofcurrent level

Contact re-trip is done without check ofauxiliary contact position

Current/Contact re-trip is done without check ofcurrent level or auxiliary contactposition

IP>: Current level for detection of breaker failure, set in % of IBase. This parametershould be set so that faults with small fault current can be detected. The setting can bechosen in accordance with the most sensitive protection function to start the breakerfailure protection. Typical setting is 10% of IBase.

I>BlkCont: If contact based detection for breaker failure is used, this feature can beblocked if any phase current is larger than this setting level. If the FunctionMode is setCurrent/Contact breaker failure for high current faults are safely detected by thecurrent measurement function. To increase security the contact based measurement

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 185Application manual

Page 192: Railway application RER670 Version 2.2 IEC ... - ABB

should be enabled only for small currents. The setting can be given within the range5 – 200% of IBase.

t1: Time delay of the re-trip. The setting can be given within the range 0 – 60s in stepsof 0.001 s. Typical setting is 0 – 50ms.

t2: Time delay of the back-up trip. The choice of this setting is made as short aspossible at the same time as unwanted operation must be avoided. Typical setting is 90– 200ms (also dependent of re-trip timer).

The minimum time delay for the re-trip can be estimated as:

_2 1³ + + +cbopen BFP reset margint t t t tEQUATION1430 V1 EN (Equation 62)

where:

tcbopen is the maximum opening time for the circuit breaker

tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)

tmargin is a safety margin

It is often required that the total fault clearance time shall be less than a given criticaltime. This time is often dependent of the ability to maintain transient stability in caseof a fault close to a power plant.

Time

The fault

occurs

Protection

operate time

Trip and Start

CCRWRBRF

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

IEC15000141-1-en.vsdx

IEC15000141 V1 EN

Figure 60: Time sequence

Section 8 1MRK 506 375-UEN -Current protection

186 Railway application RER670 2.2 IECApplication manual

Page 193: Railway application RER670 Version 2.2 IEC ... - ABB

tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker. Thereis a binary input CBFLT from the circuit breaker. This signal is activated wheninternal supervision in the circuit breaker detect that the circuit breaker is unable toclear fault. This could be the case when gas pressure is low in a SF6 circuit breaker.After the set time an alarm is given, so that actions can be done to repair the circuitbreaker. The time delay for back-up trip is bypassed when the CBFLT is active.Typical setting is 2.0 seconds.

tPulse: Trip pulse duration. This setting must be larger than the critical impulse timeof circuit breakers to be tripped from the breaker failure protection. Typical setting is200 ms.

8.8 Overcurrent protection with binary release BRPTOC

8.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Overcurrent protection with binaryrelease

BRPTOC2I>

IEC16000104 V1 EN

50

8.8.2 Application

Overcurrent protection with binary release (BRPTOC) is a simple, non-directionaltwo-phase overcurrent protection function with definite time delay. A single step isavailable within the function. The current pickup level and definite time delay can beset independently. It is possible to release the function operation via a binary signal.If the binary signal is not connected, the function will automatically operate in acontinuous mode of operation. Several function instances are available.

BRPTOC can be used for different line and transformer railway protectionapplications. If required, it can also be used to supervise on-load tap-changeroperation.

The function can be used in 16.7Hz, 50Hz and 60Hz railway supply systems. Thefunction is a two-phase design but it can be used in a single-phase railway supplysystems as well.

8.8.3 Setting guidelines

The parameters for Overcurrent protection with binary release BRPTOC are set viathe local HMI or PCM600.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 187Application manual

Page 194: Railway application RER670 Version 2.2 IEC ... - ABB

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select GBASVAL function for reference of base values.

Operation: By using this setting the function can be set On/Off.

I>: Current pickup level, set in % of IBase.

tDelay: Time delay of the operation.

8.9 Tank overcurrent protection TPPIOC

8.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Tank overcurrent protection TPPIOC

IN>>>

IEC15000111 V1 EN

64

8.9.2 Application

The transformer is placed on an insulated platform using the rails. The rails are cut ateach end and insulated with respect to ground by setting the holding-down bolts in theconcrete foundation without any contact to the reinforcement or by fixing the rails onwooden ties.

The tank is grounded at a certain location by a conductor where a CT measures the tankto ground current as shown in Figure 61.

The transformer tank protection function measures the current in the tank earthconductor and give an instantaneous trip signal in case of an insulation break downbetween a winding or terminal and the tank.

Section 8 1MRK 506 375-UEN -Current protection

188 Railway application RER670 2.2 IECApplication manual

Page 195: Railway application RER670 Version 2.2 IEC ... - ABB

IEC15000105-1-en.vsdx

~ ZG

I>

IF,i

IEC15000105 V1 EN

Figure 61: Transformer tank and grounding arrangement

Transformer tank protection function is used to sense the tank leakage current andoperates if the current is above the set level.

In the case of grounded neutral systems, protection can be provided by insulating thetransformer tank from ground apart from a connection to ground through a CT whosesecondary energizes an overcurrent relay. Such an arrangement gives sensitiveprotection for arc-overs to the tank or to the core, but it will not respond to turn faultsor to faults in the leads to the transformer.

The protection scheme should not initiate a trip in case of an external phase to groundfault. Figure 62 illustrates the different elements that are involved in that case.

The neutral displacement voltage that appears in case of an external phase to groundfault is the source voltage for current flowing through the protection circuit. Theamount of this current is proportional to the ratio given by the ground contactresistance RG,C to the leakage resistance RG,I of the tank as explained in Figure 62.

IEC15000106-1-en.vsdx

~ ZG

I>

IF,e

RG,I RG,cVNG

ING

IEC15000106 V1 EN

Figure 62: Behaviour of ground fault protection during an external fault

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 189Application manual

Page 196: Railway application RER670 Version 2.2 IEC ... - ABB

where:

RG,I Leakage resistance of the tank

RG,C Ground contact resistance

ZG Neutral grounding impedance

ING is described as:

IGCGG

NGNG

RRZ

VI

,,

IECEQUATION051 V2 EN (Equation 63)

IFe RG,I is described as:

CGFeNGIGFe RIIRI ,, )(

IECEQUATION052 V2 EN (Equation 64)

For

CGIGG RRZ ,,,

IECEQUATION053 V2 EN (Equation 65)

IFe is described as:

IG

CG

G

NGFe

R

R

Z

VI

,

,

IECEQUATION054 V2 EN (Equation 66)

The current flow in case of an external phase to ground fault should not operate thetank protection. Therefore, start value is set above the absolute value of this current.In other words, the ratio of ground contact resistance RG,C to leakage resistance RG,Ishould not exceed a certain value regardless of atmospheric conditions.

8.9.3 Setting guidelines

The parameters for transformer tank protection TPPIOC are set via the local HMI orPCM600.

The setting parameters for the transformer tank protection TPPIOC are describedbelow:

Common base IED values for primary current (setting IBase) is set in a Global basevalues for settings function GBASVAL setting.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase).

Section 8 1MRK 506 375-UEN -Current protection

190 Railway application RER670 2.2 IECApplication manual

Page 197: Railway application RER670 Version 2.2 IEC ... - ABB

I>: Instantaneous peak current start value in % of IBase.

1MRK 506 375-UEN - Section 8Current protection

Railway application RER670 2.2 IEC 191Application manual

Page 198: Railway application RER670 Version 2.2 IEC ... - ABB

192

Page 199: Railway application RER670 Version 2.2 IEC ... - ABB

Section 9 Voltage protection

9.1 Two step undervoltage protection U2RWPTUV

9.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Undervoltage protection, two steps U2RWPTUV

2(2U<)

IEC15000109 V1 EN

27

9.1.2 Application

Two-step undervoltage protection function (U2RWPTUV) is applicable in allsituations, where reliable detection of low phase voltages is necessary. It is also usedas a supervision and fault detection function for other protection functions to increasethe security of a complete protection system.

U2RWPTUV is applied to transformers and power lines in order to detect low voltageconditions. Low voltage conditions are caused by abnormal operation or fault in thepower system. U2RWPTUV is used in combination with overcurrent protections,either as restraint or in logic "and gates" of the trip signals issued by the two functions.Other applications are the detection of "no voltage" condition, for example, before theenergization of a HV line or for automatic breaker trip in case of a blackout.

U2RWPTUV is used to disconnect apparatuses which will be damaged when subjectto service under low voltage conditions. U2RWPTUV deals with low voltageconditions at power system frequency, which can be caused by the following reasons:

1. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

2. Overload (symmetrical voltage decrease).3. Short circuits, often as phase-to-earth faults (unsymmetrical voltage decrease).

U2RWPTUV prevents sensitive equipment from running under conditions that couldcause overheating and thus shorten their life time expectancy. In many cases, it is auseful function in circuits for local or remote automation processes in the powersystem.

1MRK 506 375-UEN - Section 9Voltage protection

Railway application RER670 2.2 IEC 193Application manual

Page 200: Railway application RER670 Version 2.2 IEC ... - ABB

9.1.3 Setting guidelines

All the voltage conditions in the system where U2RWPTUV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.

There are wide applications where general undervoltage functions are used. Allvoltage related settings are made as a percentage of the global base value UBase andbase current IBase, which normally is set to the primary rated voltage level (phase-to-phase) of the power system or the high voltage equipment under consideration.

The setting for U2RWPTUV is normally not critical, since there must be enough timeavailable for the main protection to clear short circuits and earth faults.

Some applications and related setting guidelines for the voltage level are described inthe following sections.

9.1.3.1 Disconnected equipment detection

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage, caused by inductive or capacitive coupling, when theequipment is disconnected.

9.1.3.2 Power supply quality

The setting must be below the lowest occurring "normal" voltage and above the lowestacceptable voltage, due to regulation, good practice or other agreements.

9.1.3.3 Voltage instability mitigation

This setting is very much dependent on the power system characteristics, andthorough studies have to be made to find the suitable levels.

9.1.3.4 Backup protection for power system faults

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage during the fault conditions under consideration.

9.1.3.5 Settings for two step undervoltage protection

Parameters for U2RWPTUV application function are set via local HMI or Protectionand Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

Section 9 1MRK 506 375-UEN -Voltage protection

194 Railway application RER670 2.2 IECApplication manual

Page 201: Railway application RER670 Version 2.2 IEC ... - ABB

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

ConnType: Sets whether the measurement shall be phase-to-earth fundamental value,phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phaseRMS value.

Operation: This is used for undervoltage protection Off/On.

UBase (given in GlobalBaseSel): Set as rated phase-to-phase voltage in primary kV.This voltage is used as reference for voltage setting. U2RWPTUV measuresselectively phase-to-earth voltages, or phase-to-phase voltage chosen by the settingConnType. The function will operate if the voltage becomes lower than the setpercentage of UBase. When ConnType is set to PhN DFT or PhN RMS, the IEDautomatically divides set value for UBase by 2. UBase is used as set when ConnTypeis set to PhPh DFT or PhPh RMS. Therefore, always set UBase as rated primaryphase-to-phase voltage of the protected object. This means operation for phase-to-earth voltage under:

2/)((%) kVUBaseU

IECEQUATION048 V1 EN (Equation 67)

and operation for phase-to-phase voltage under:

U (%) UBase(kV)< ×EQUATION1990 V1 EN (Equation 68)

Thus, for any selected measuring type setting of 100% corresponds to the ratedprimary voltage.

The below described setting parameters are identical for the two steps (n = 1 and 2).Therefore, the setting parameters are described only once.

OperationStepn: This is used to on/off the operation of step n.

OpModen: This parameter describes how many of the two measured voltages shouldbe below the set level to give operation for step n. The setting can be Any phase or Allphases.

Un<: It is used to set undervoltage operation value for step n, given as %UB. Thesetting is highly dependent on the protection application.

tn: time delay of step n, given in s. This setting is dependent on the protectionapplication. In many applications the protection function shall not directly trip whenthere is a short circuit or earth faults in the system. The time delay must be coordinatedto the other short circuit protections.

1MRK 506 375-UEN - Section 9Voltage protection

Railway application RER670 2.2 IEC 195Application manual

Page 202: Railway application RER670 Version 2.2 IEC ... - ABB

9.2 Two step overvoltage protection O2RWPTOV

9.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617 identification ANSI/IEEE C37.2

device numberOvervoltage protection, two steps O2RWPTOV

2(2U>)

IEC15000214 V1 EN

59

9.2.2 Application

Two step overvoltage protection O2RWPTOV is applicable in situations wherereliable detection of high voltage is necessary. O2RWPTOV is used for supervisionand detection of abnormal conditions, which in combination with other protectionfunctions, to increase the security of a complete protection system.

High overvoltage conditions are caused by abnormal situations in the power system.O2RWPTOV is applied to transformers and power lines in order to detect high voltageconditions. O2RWPTOV is used in combination with low current signals to identifya transmission line open in the remote end.

O2RWPTOV is used to disconnect apparatuses which will be damaged when subjectto service under high voltage conditions. It deals with high voltage conditions atpower system frequency, which can be caused by:

1. Different kinds of faults, where a too high voltage appears in a certain powersystem, like metallic connection to a higher voltage level (broken conductorfalling down to a crossing overhead line, transformer flash over fault from thehigh voltage winding to the low voltage winding and so on).

2. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

3. Low load compared to the reactive power generation (symmetrical voltagedecrease).

4. Earth-faults in high impedance earthed systems causes, beside the high voltage inthe neutral, high voltages in the non-faulted phase, (unsymmetrical voltageincrease).

O2RWPTOV prevents sensitive equipment from running under conditions that couldcause their overheating or stress of insulation material, and, thus, shorten their lifetime expectancy. In many cases, it is a useful function in circuits for local or remoteautomation processes in the power system.

Section 9 1MRK 506 375-UEN -Voltage protection

196 Railway application RER670 2.2 IECApplication manual

Page 203: Railway application RER670 Version 2.2 IEC ... - ABB

9.2.3 Setting guidelines

The parameters for two step overvoltage protection (O2RWPTOV) are set via thelocal HMI or Protection and Control Manager PCM600.

All the voltage conditions in the system where O2RWPTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.

There are wide applications where general overvoltage functions are used. All voltagerelated settings are made as a percentage of a settable base primary voltage, which isnormally set to the nominal voltage level (phase-to-phase) of the power system.

The time delay for the O2RWPTOV can sometimes be critical and related to the sizeof the overvoltage - a power system or a high voltage component can withstandsmaller overvoltages for some time, but in case of large overvoltages the relatedequipment should be disconnected more rapidly.

Some applications and related setting guidelines for the voltage level are given below:

9.2.3.1 Equipment protection, transformers

High voltage will cause overexcitation of the core and deteriorate the windinginsulation. The setting has to be well above the highest occurring "normal" voltageand well below the highest acceptable voltage for the equipment.

9.2.3.2 Power supply quality

The setting has to be well above the highest occurring "normal" voltage and below thehighest acceptable voltage, due to regulation, good practice or other agreements.

9.2.3.3 The following settings can be done for the two step overvoltageprotection

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

ConnType: This is used to set whether the measurement shall be phase-to-earthfundamental value, phase-to-phase fundamental value, phase-to-earth true RMSvalue or phase-to-phase true RMS value.

Operation: This is used for two step overvoltage protection Off/On.

UBase (given in GlobalBaseSel): Set as rated phase-to-phase voltage in primary kV.This voltage is used as reference for voltage setting. O2RWPTOV measures

1MRK 506 375-UEN - Section 9Voltage protection

Railway application RER670 2.2 IEC 197Application manual

Page 204: Railway application RER670 Version 2.2 IEC ... - ABB

selectively phase-to-earth voltages, or phase-to-phase voltage chosen by the settingConnType. The function will operate if the voltage gets higher than the set percentageof UBase. When ConnType is set to PhN DFT or PhN RMS, the IED automaticallydivides set value of UBase by 2. When ConnType is set to PhPh DFT or PhPh RMS,set value of UBase is used. Therefore, always set UBase as rated primary phase-to-phase voltage of the protected object. This means operation for phase-to-earth voltageover:

and operation for phase-to-phase voltage over:

U (%) UBase(kV)> ×EQUATION1993 V1 EN (Equation 70)

Thus, for any selected measuring type setting of 100% corresponds to the ratedprimary voltage.

The below described setting parameters are identical for the two steps (n = 1 and 2).Therefore the setting parameters are described only once.

OperationStepn: This is used to enable/disable the operation of step n.

OpModen: This parameter describes how many of the two measured voltages thatshould be above the set level to give operation. The setting can be Any phase or Allphases. In most applications it is sufficient that one phase voltage is high to giveoperation. If the function shall be insensitive for single phase-to-earth faults Allphases can be chosen, because the voltage will normally rise in the non-faulted phasesat single phase-to-earth faults.

Un>: This is used to set operate overvoltage operation value for step n, given as % ofUBase. The setting is highly dependent of the protection application. Here, it isessential to consider the maximum voltage at non-faulted situations. In general, thisvoltage is less than 110% of nominal voltage.

tn: time delay of step n, given in s. The setting is highly dependent of the protectionapplication. In many applications the protection function is used to prevent damagesto the protected object. The speed might be important for example in case of protectionof transformer that might be overexcited. The time delay must be co-ordinated withother automated actions in the system.

Section 9 1MRK 506 375-UEN -Voltage protection

198 Railway application RER670 2.2 IECApplication manual

Page 205: Railway application RER670 Version 2.2 IEC ... - ABB

9.3 Two step residual overvoltage protectionROV2PTOV

9.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step residual overvoltageprotection

ROV2PTOV

2(U0>)

IEC15000108 V1 EN

59N

9.3.2 Application

The residual voltage will increase in case of any single phase earth-fault occurred inisolated or compensated two-phase railway supply systems. Depending on the type offault and fault resistance, the residual voltage will reach different values. The highestresidual voltage, equal to two times the phase-to-earth voltage, is achieved for a solidsingle phase-to-earth fault. The residual voltage increases approximately to the samelevel in the whole system and does not provide any guidance in finding the faultedcomponent. Therefore, ROV2PTOV is often used as a backup protection or as arelease signal for the feeder earth-fault protection.

9.3.3 Setting guidelines

All the voltage conditions in the system where ROV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltagewithstand capability and time characteristic.

All voltage-related settings are made as a percentage of a settable base voltage, whichshall be set to the primary nominal voltage (phase-phase) level of the power system.

The time delay for ROV2PTOV is seldom critical, since residual voltage is related toearth faults in a high-impedance earthed system, and enough time must normally begiven for the primary protection to clear the fault. In some more specific situations,where the residual overvoltage protection is used to protect some specific equipment,the time delay is shorter.

Some applications and related setting guidelines for the residual voltage level aregiven below.

9.3.3.1 High impedance earthed systems

In high impedance earthed systems, an earth fault on one phase will cause a voltagecollapse in that phase. However, the other healthy phase voltage will raise to full

1MRK 506 375-UEN - Section 9Voltage protection

Railway application RER670 2.2 IEC 199Application manual

Page 206: Railway application RER670 Version 2.2 IEC ... - ABB

phase-to-phase voltage value. The residual voltage sum 2U0 will raise to the samephase-to-phase value during earth fault.

9.3.3.2 Solidly earthed systems

In solidly earthed systems, an earth fault on one phase is indicated by voltage collapsein that phase. The other healthy phase will still have normal phase-to-earth voltage.The residual sum 2U0 will have the same value as the remaining phase-to-earthvoltage.

9.3.3.3 Settings for two step residual overvoltage protection

Parameters for ROV2PTOV application function are set via the local HMI orProtection and Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: This is used for residual overvoltage protection Off/On.

UBase (given in GlobalBaseSel) is used as voltage reference for the set pickup values.UBase shall be set equal to rated phase-to-phase voltage. Note that the set value forUBase will be multiplied by factor 0.5 within the ROV2PTOV function. The voltagecan be fed to the IED in different ways:

1. The IED is fed from two VTs connected phase-to-ground, where the residualvoltage 2U0 is calculated internally within the protection.

2. The IED is fed from a single voltage transformer connected to the neutral point ofa power transformer in the power system. In this connection the protection is fedby the voltage UN=U0 (single input). Section Analog inputs in the Applicationmanual explains how the analog input needs to be set.

The setting parameters described below are identical for the two steps (n = step 1 and2). Therefore the setting parameters are described only once.

OperationStepn: This is to enable/disable operation of step n.

Un>: Set operate overvoltage operation value for step n, given as % of residualvoltage corresponding to UBase:

(%) ( ) / 2Un UBase kV IECEQUATION050 V2 EN (Equation 71)

Section 9 1MRK 506 375-UEN -Voltage protection

200 Railway application RER670 2.2 IECApplication manual

Page 207: Railway application RER670 Version 2.2 IEC ... - ABB

The setting depends on the required sensitivity of the protection and the type of systemearthing. In high impedance earthed systems, the residual voltage can be at maximumrated phase-to-phase voltage, which should correspond to 200%.

In solidly earthed systems, this value depends on the ratio Z0/Z1. The required settingto detect high resistive earth faults must be based on network calculations. Typicallyit shall be lesser than 100%.

tn: time delay of step n, given in s. The setting is highly dependent on the protectionapplication. The time delay must be co-ordinated with other automated actions in thesystem.

1MRK 506 375-UEN - Section 9Voltage protection

Railway application RER670 2.2 IEC 201Application manual

Page 208: Railway application RER670 Version 2.2 IEC ... - ABB

202

Page 209: Railway application RER670 Version 2.2 IEC ... - ABB

Section 10 Frequency protection

10.1 Underfrequency protection SAPTUF

10.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Underfrequency protection SAPTUF

f <

SYMBOL-P V1 EN

81L

10.1.2 Application

Underfrequency protection SAPTUF is applicable in all situations, where reliabledetection of low fundamental power system frequency is needed. The power systemfrequency, and the rate of change of frequency, is a measure of the unbalance betweenthe actual generation and the load demand. Low fundamental frequency in a powersystem indicates that the available generation is too low to fully supply the powerdemanded by the load connected to the power grid. SAPTUF detects such situationsand provides an output signal, suitable for load shedding, generator boosting, HVDC-set-point change, gas turbine start up and so on. Sometimes shunt reactors areautomatically switched in due to low frequency, in order to reduce the power systemvoltage and hence also reduce the voltage dependent part of the load.

SAPTUF is very sensitive and accurate and is used to alert operators that frequencyhas slightly deviated from the set-point, and that manual actions might be enough. Theunderfrequency signal is also used for overexcitation detection. This is especiallyimportant for generator step-up transformers, which might be connected to thegenerator but disconnected from the grid, during a roll-out sequence. If the generatoris still energized, the system will experience overexcitation, due to the low frequency.

10.1.3 Setting guidelines

All the frequency and voltage magnitude conditions in the system where SAPTUFperforms its functions should be considered. The same also applies to the associatedequipment, its frequency and time characteristic.

There are two specific application areas for SAPTUF:

1MRK 506 375-UEN - Section 10Frequency protection

Railway application RER670 2.2 IEC 203Application manual

Page 210: Railway application RER670 Version 2.2 IEC ... - ABB

1. to protect equipment against damage due to low frequency, such as generators,transformers, and motors. Overexcitation is also related to low frequency

2. to protect a power system, or a part of a power system, against breakdown, byshedding load, in generation deficit situations.

The under frequency start value is set in Hz. All voltage magnitude related settings aremade as a percentage of a global base voltage parameter. The UBase value should beset as a primary phase-to-phase value.

Some applications and related setting guidelines for the frequency level are givenbelow:

Equipment protection, such as for motors and generatorsThe setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.

Power system protection, by load sheddingThe setting has to be below the lowest occurring "normal" frequency and well abovethe lowest acceptable frequency for power stations, or sensitive loads. The settinglevel, the number of levels and the distance between two levels (in time and/or infrequency) depends very much on the characteristics of the power system underconsideration. The size of the "largest loss of production" compared to "the size of thepower system" is a critical parameter. In large systems, the load shedding can be setat a fairly high frequency level, and the time delay is normally not critical. In smallersystems the frequency start level has to be set at a lower value, and the time delay mustbe rather short.

The voltage related time delay is used for load shedding. The settings of SAPTUFcould be the same all over the power system. The load shedding is then performedfirstly in areas with low voltage magnitude, which normally are the most problematicareas, where the load shedding also is most efficient.

Section 10 1MRK 506 375-UEN -Frequency protection

204 Railway application RER670 2.2 IECApplication manual

Page 211: Railway application RER670 Version 2.2 IEC ... - ABB

Section 11 Secondary system supervision

11.1 Current circuit supervision CCSSPVC

11.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Current circuit supervision CCSSPVCINd/I

IEC15000306 V1 EN

87

11.1.2 Application

Open or short circuited current transformer cores can cause unwanted operation ofmany protection functions such as differential and earth-fault current functions. Whencurrents from two independent two-phase sets of CTs, or CT cores, measuring thesame primary currents are available, reliable current circuit supervision can bearranged by comparing the currents from the two sets. If an error in any CT circuit isdetected, the protection functions concerned can be blocked and an alarm will begiven.

In case of large currents, unequal transient saturation of CT cores with differentremanence or different saturation factor may result in differences in the secondarycurrents from the two CT sets. Unwanted blocking of protection functions during thetransient stage must then be avoided.

Current circuit supervision CCSSPVC must be sensitive and have short operate timein order to prevent unwanted tripping from fast-acting, sensitive numericalprotections in case of faulty CT secondary circuits.

Open CT circuits creates extremely high voltages in the circuits whichis extremely dangerous for the personnel. It can also damage theinsulation and cause new problems. The application shall, thus, bedone with this in consideration, especially if the protection functionsare blocked.

1MRK 506 375-UEN - Section 11Secondary system supervision

Railway application RER670 2.2 IEC 205Application manual

Page 212: Railway application RER670 Version 2.2 IEC ... - ABB

11.1.3 Setting guidelines

The parameters for Current circuit supervision CCSSPVC are set via local HMI orProtection and Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select GBASVAL function for reference of base values.

Operation: This is used for current circuit supervision function Off/On.

Current circuit supervision CCSSPVC compares the residual current from a two-phase set of current transformer cores with the neutral point current on a separate inputtaken from another set of cores on the same current transformer.

IMinOp: It must be set as a minimum to twice the residual current in the supervised CTcircuits under normal service conditions and rated primary current.

Ip>Block: It is normally set at 150% to block the function during transient conditions.

The FAIL output is connected to the blocking input of the protection function to beblocked at faulty CT secondary circuits.

11.2 Fuse failure supervision FRWSPVC

11.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fuse failure supervision FRWSPVC - -

11.2.2 Application

Different protection functions within the protection IED, operates on the basis of themeasured voltage at the relay point. Examples are:

• Impedance protection functions• Undervoltage function• Energizing check function and voltage check for the weak infeed logic

These functions can operate unintentionally if a fault occurs in the secondary circuitsbetween the voltage instrument transformers and the IED.

It is possible to use different measures to prevent such unwanted operations. Miniaturecircuit breakers in the voltage measuring circuits should be located as close as possible

Section 11 1MRK 506 375-UEN -Secondary system supervision

206 Railway application RER670 2.2 IECApplication manual

Page 213: Railway application RER670 Version 2.2 IEC ... - ABB

to the voltage instrument transformers, and shall be equipped with auxiliary contactsthat are wired to the IEDs. Separate fuse-failure monitoring IEDs or elements withinthe protection and monitoring devices are another possibilities. These solutions arecombined to get the best possible effect in the fuse failure supervision function(FRWSPVC).

FRWSPVC function built into the IED products can operate on the basis of externalbinary signals from the miniature circuit breaker or from the line disconnector. Thefirst case influences the operation of all voltage-dependent and underimpedanceprotection functions while the second one does not affect the impedance measuringfunctions.

In the event of failure of measuring circuit voltage, the underimpedance protectionfunction will be blocked for a set time if residual current exists during the blockingtime.

A criterion based on delta current and delta voltage measurements is used as the fusefailure supervision function in order to detect a fuse failure.

11.2.3 Setting guidelines

The parameters for fuse failure supervision FRWSPVC are set via the local HMI orProtection and Control Manager PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.

GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.

Operation: This is used for fuse failure supervision Off/On.

11.2.3.1 DeltaU and DeltaI detection

To avoid unwanted operation due to the normal switching conditions in the network,the DU> setting should be set high (approximately 60% of UBase) and the currentthreshold DI< setting should be set low (approximately 10% of IBase).

If USetprim is the primary voltage for dU/dt operation:

UBaseUSetDU prim /)100(

IECEQUATION215 V1 EN

If ISetprim is the primary current for dI/dt operation:

IBaseISetDI prim /)100(

IECEQUATION216 V1 EN

1MRK 506 375-UEN - Section 11Secondary system supervision

Railway application RER670 2.2 IEC 207Application manual

Page 214: Railway application RER670 Version 2.2 IEC ... - ABB

The voltage threshold UPh> is used to identify low voltage condition in the system.Set UPh> below the minimum operating voltage during emergency conditions. Asafety margin of approximately 70% of UBase is recommended.

The current threshold IPh> should be set lower than the IMinOp for the distanceprotection function. A safety margin of 5–10% lower value is recommended.

The setting INDeblock is used to block or deblock the underimpedance protection ifresidual current exists during fuse failure conditions in the voltage measuring circuit.

The residual current threshold 2I0< should be set above the maximum occurringresidual current during normal loading conditions.

The timer tIN is used to delay the deblocking of underimpedance protection functionsif required. A default value of 5.0 s is given.

11.2.3.2 Dead line detection

The condition for operation of the dead line detection is set by the parameters IDLD<for the current threshold and UDLD< for the voltage threshold.

Set the IDLD< with a sufficient margin below the minimum expected load current. Asafety margin of at least 15-20% is recommended. The operate value must howeverexceed the maximum charging current of an overhead line, when only one phase isdisconnected (mutual coupling to the other phases).

Set the UDLD< with a sufficient margin below the minimum expected operatingvoltage. A safety margin of at least 15% is recommended.

11.2.4 Sudden current and voltage change

Several instances of FRWSPVC function are available. Therefore if required byapplication, one instance of this function can also be used for sudden current andvoltage change detection. This information, for example, can be used in IEDconfiguration logic to enable higher distance protection zones for catenaryapplications.

Section 11 1MRK 506 375-UEN -Secondary system supervision

208 Railway application RER670 2.2 IECApplication manual

Page 215: Railway application RER670 Version 2.2 IEC ... - ABB

Section 12 Control

12.1 Synchrocheck, energizing check, and synchronizingSESRSYN

12.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Synchrocheck, energizing check, andsynchronizing

SESRSYN

sc/vc

SYMBOL-M V1 EN

25

12.1.2 Application

12.1.2.1 Synchronizing

To allow closing of breakers between asynchronous networks, a synchronizingfeature is provided. The breaker close command is issued at the optimum time whenconditions across the breaker are satisfied in order to avoid stress on the network andits components.

The systems are defined as asynchronous when the frequency difference between busand line is larger than an adjustable parameter. If the frequency difference is less thanthis threshold value the system is defined to have a parallel circuit and thesynchrocheck function is used.

The synchronizing function measures the difference between the U-Line and the U-Bus. It operates and enables a closing command to the circuit breaker when thecalculated closing angle is equal to the measured phase angle and the followingconditions are simultaneously fulfilled:

• The voltages U-Line and U-Bus are higher than the set values forUHighBusSynch and UHighLineSynch of the respective base voltagesGblBaseSelBus and GblBaseSelLine.

• The difference in the voltage is smaller than the set value of UDiffSynch.• The difference in frequency is less than the set value of FreqDiffMax and larger

than the set value of FreqDiffMin. If the frequency is less than FreqDiffMin thesynchrocheck is used and the value of FreqDiffMin must thus be identical to thevalue FreqDiffM resp FreqDiffA for synchrocheck function. The bus and line

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 209Application manual

Page 216: Railway application RER670 Version 2.2 IEC ... - ABB

frequencies must also be within a range of ±10% from the rated frequency. Whenthe synchronizing option is included also for autoreclose there is no reason tohave different frequency setting for the manual and automatic reclosing and thefrequency difference values for synchronism check should be kept low.

• The frequency rate of change is less than set value for both U-Bus and U-Line.• The difference in the phase angle is smaller than the set value of CloseAngleMax.• The closing angle is decided by the calculation of slip frequency and required pre-

closing time.

The synchronizing function compensates for the measured slip frequency as well asthe circuit breaker closing delay. The phase angle advance is calculated continuously.The calculation of the operation pulse sent in advance is using the measuredSlipFrequency and the set tBreaker time. To prevent incorrect closing pulses, amaximum closing angle between bus and line is set with CloseAngleMax. Table 23below shows the maximum settable value for tBreaker when CloseAngleMax is set to15 or 30 degrees, at different allowed slip frequencies for synchronizing. To minimizethe moment stress when synchronizing near a power station, a narrower limit for theCloseAngleMax needs to be used.

Table 23: Dependencies between tBreaker and SlipFrequency with different CloseAngleMaxvalues

tBreaker [s] (max settable value)with CloseAngleMax = 15degrees [default value]

tBreaker [s] (max settable value)with CloseAngleMax = 30 degrees[max value]

SlipFrequency [Hz](BusFrequency -LineFrequency)

0.040 0.080 1.000

0.050 0.100 0.800

0.080 0.160 0.500

0.200 0.400 0.200

0.400 0.810 0.100

1.000 0.080

0.800 0.050

1.000 0.040

The reference voltage can be phase-neutral L1, L2 or positive sequence. By setting thephases used for SESRSYN, with the settings SelPhaseBus and SelPhaseLine, acompensation has to be made for the phase angle difference caused if different settingvalues are selected for the two sides of the breaker. This compensation has to be donewith the PhaseShift setting according to Table 24.

Section 12 1MRK 506 375-UEN -Control

210 Railway application RER670 2.2 IECApplication manual

Page 217: Railway application RER670 Version 2.2 IEC ... - ABB

Table 24: Selection of phase shift for different combinations of SelPhaseBus and SelPhaseLine

SelPhase Bus SelPhase Line PhaseShift in degreesPhase L1 or Positive sequence Phase L1 or Positive sequence 0

Phase L1 or Positive sequence Phase L2 180

Phase L2 Phase L1 or Positive sequence 180

Phase L2 Phase L2 0

12.1.2.2 Synchrocheck

The main purpose of the synchrocheck function is to provide control over closingcircuit breakers in power networks. The purpose for providing control is to prevent theclosing if the conditions of synchronism are not detected. It is also used to prevent re-connection of two systems, which are divided after islanding/after a two polereclosing.

Sometimes first shot in the auto-reclosing cycle shall be performedwithout using synchrocheck for railway applications. For such caseshigh-speed shot within the auto-reclosing function shall be used.

SESRSYN function block includes both the synchrocheck and the energizingfeatures. The energizing function allows closing when one side of the breaker is dead.

IEC16000121-1-en.vsdx

IEC16000121 V1 EN

Figure 63: Two interconnected power systems

Figure 63 shows two interconnected power systems. The cloud means that theinterconnection can be further away, that is, a weak connection through other stations.The need for a check of synchronization increases if the meshed system decreasessince the risk of the two networks being out of synchronization at manual or automaticclosing is greater.

The synchrocheck function measures the conditions across the circuit breaker andcompares against the set limits. Output is generated only when all measuredconditions are within the respective set limits simultaneously. The check consists of:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 211Application manual

Page 218: Railway application RER670 Version 2.2 IEC ... - ABB

• Live line and live bus.• Voltage level difference.• Frequency difference (slip). The bus and line frequency must also be within a

range of ±10% deviated from rated frequency.• Phase angle difference.

A time delay is available to ensure that the conditions are fulfilled for a minimumperiod of time.

In stable power systems, the frequency difference is insignificant or zero for manuallyinitiated closing or closing by automatic restoration. In steady conditions, a biggerphase angle difference can be allowed as this is sometimes the case in a long andloaded parallel power line. For this application we accept a synchrocheck with a longoperation time and high sensitivity regarding the frequency difference. The phaseangle difference setting can be set for steady state conditions.

Another example is the operation of a power network that is disturbed due to a faultevent: After the fault clearance a highspeed auto-reclosing takes place. This can causea power swing in the network and the phase angle difference may begin to oscillate.Generally, the frequency difference is the time derivative of the phase angle differenceand typically oscillates between positive and negative values. When the circuitbreaker needs to be closed by auto-reclosing after fault-clearance some frequencydifference should be tolerated. But if a big and increasing phase angle difference isallowed at the same time, there is some risk in auto-reclosing. In this case it is safer toclose when the phase angle difference is smaller.

To fulfill the requirements above, the synchrocheck function is provided with separatesettings for steady (Manual) conditions and operation under disturbed conditions(Auto).

Section 12 1MRK 506 375-UEN -Control

212 Railway application RER670 2.2 IECApplication manual

Page 219: Railway application RER670 Version 2.2 IEC ... - ABB

SynchroCheck

UHighBusSC > 10 - 120 % of GblBaseSelBus

UHighLineSC > 10 - 120 % of GblBaseSelLine

UDiffSC < 0.02 – 0.50 p.u.

PhaseDiffM < 5 - 90 degrees

PhaseDiffA < 5 - 90 degrees

FreqDiffM < 3 - 1000 mHz

FreqDiffA < 3 - 1000 mHz

Fuse fail

Fuse fail

Line voltage Linereferencevoltage

Bus voltage

IEC16000122-1-en.vsdx

IEC16000122 V1 EN

Figure 64: Principle for the synchrocheck function

12.1.2.3 Energizing check

The main purpose of the energizing check function is to facilitate the controlled re-connection of disconnected lines and buses to energized buses and lines.

The energizing check function measures the bus and line voltages and compares themto both high and low threshold values. The output is given only when the actualmeasured conditions match the set conditions. Figure 65 shows two substations,where one (1) is energized and the other (2) is not energized. The line between CB Aand CB B is energized (DLLB) from substation 1 via the circuit breaker A andenergization of station 2 is done by CB B energization check device for that breakerDBLL. (or Both).

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 213Application manual

Page 220: Railway application RER670 Version 2.2 IEC ... - ABB

~

1 2 A

EnergizingCheckUHighBusEnerg > 10 - 120 % of GblBaseSelBus

UHighLineEnerg > 10 - 120 % of GblBaseSelLine

ULowBusEnerg < 10 - 80 % of GblBaseSelBus

ULowLineEnerg < 10 - 80 % of GblBaseSelLine

UMaxEnerg < 50 - 180 % of GblBaseSelBus and/or

GblBaseSelLine

Line voltageBus voltage

IEC17000008-1-en.vsdx

B

IEC17000008 V1 EN

Figure 65: Principle for the energizing check function

The energizing operation can operate in the dead line live bus (DLLB) direction, deadbus live line (DBLL) direction, or in both directions over the circuit breaker.Energizing from different directions can be different for automatic reclosing andmanual closing of the circuit breaker. For manual closing it is also possible to allowclosing when both sides of the breaker are dead, Dead Bus Dead Line (DBDL).

The equipment is considered energized (Live) if the voltage is above the set value forUHighBusEnerg or UHighLineEnerg of the base voltages GblBaseSelBus andGblBaseSelLine, which are defined in the Global Base Value groups; in a similar way,the equipment is considered non-energized (Dead) if the voltage is below the set valuefor ULowBusEnerg or ULowLineEnerg of the respective Global Base Value groups.A disconnected line can have a considerable potential due to factors such as inductionfrom a line running in parallel, or feeding via extinguishing capacitors in the circuitbreakers. This voltage can be as high as 50% or more of the base voltage of the line.Normally, for breakers with single breaking elements (<330 kV) the level is wellbelow 30%.

When the energizing direction corresponds to the settings, the situation has to remainconstant for a certain period of time before the close signal is permitted. The purposeof the delayed operate time is to ensure that the dead side remains de-energized andthat the condition is not due to temporary interference.

12.1.2.4 External fuse failure

Either external fuse-failure signals or signals from a tripped miniature circuit breakerare connected to HW binary inputs of the IED; these signals are connected to inputsof SESRSYN function in the application configuration tool of PCM600. The internalfuse failure supervision function can also be used if a two-phase voltage is present.The signal BLKU, from the internal fuse failure supervision function, is then used andconnected to the fuse supervision inputs of the SESRSYN function block. In case ofa fuse failure, the SESRSYN energizing function shall be blocked.

Section 12 1MRK 506 375-UEN -Control

214 Railway application RER670 2.2 IECApplication manual

Page 221: Railway application RER670 Version 2.2 IEC ... - ABB

The UBOK and UBFF inputs are related to the busbar voltage and the ULNOK andULNFF inputs are related to the line voltage.

External selection of energizing directionThe energizing can be selected by use of the available logic function blocks. Below isan example where the choice of mode is done from a symbol ,created in the GraphicalDesign Editor (GDE) tool on the local HMI, through selector switch function block,but alternatively there can for example, be a physical selector switch on the front of thepanel which is connected to a binary to integer function block (B16I).

If the PSTO input is used, connected to the Local-Remote switch on the local HMI, thechoice can also be from the station HMI system, typically ABB Microscada throughIEC 61850–8–1 communication.

The connection example for selection of the manual energizing mode is shown infigure 66. Selected names are just examples but note that the symbol on the local HMIcan only show the active position of the virtual selector.

IEC17000001-1-en.vsdx

SESRSYNU2PBB*

U2PLN*

BLOCK

BLKSYNCH

BLKSC

BLKENERG

UBOK

UBFF

ULNOK

ULNFF

STARTSYN

TSTSYNCH

TSTSC

TSTENERG

AENMODE

MENMODE

SYNOK

AUTOSYOK

AUTOENOK

MANSYOK

MANENOK

TSTSYNOK

TSTAUTSY

TSTMANSY

TSTENOK

USELFAIL

SYNPROGR

SYNFAIL

UOKSYN

UDIFFSYN

FRDIFSYN

FRDIFFOK

FRDERIVA

UOKSC

UDIFFSC

FRDIFFA

PHDIFFA

FRDIFFM

PHDIFFM

UDIFFME

FRDIFFME

PHDIFFME

UBUS

ULINE

MODEAEN

MODEMEN

SLGAPCBLOCK

PSTO

UP

DOWN

P01

P02

P03

P04

P05

P06

P07

P08

P09

P10

P11

P12

P13

P14

P15

P16

P17

P18

P19

P20

P21

P22

P23

P24

P25

P26

P27

P28

P29

P30

P31

P32

SWPOSN

INTONE

U2PBB

U2PLN

IEC17000001 V1 EN

Figure 66: Selection of the energizing direction from a local HMI symbol througha selector switch function block.

12.1.3 Application examples

The synchronizing function block can be used in different switchyard arrangements,but with different parameter settings. An example is given below.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 215Application manual

Page 222: Railway application RER670 Version 2.2 IEC ... - ABB

The input used below in example are typical and can be changed byuse of configuration and signal matrix tools.

12.1.3.1 Single circuit breaker with single busbar

WA1_MCB

LINE

WA1

QB1

QA1

IEC16000123-1-en.vsdx

LINE_VT

LINE_MCB

WA1_MCB

SESRSYNU2PBB*

U2PLN*

UBOK

UBFF

ULOK

ULFF

WA1_VT

WA1_VT

LINE_VT

LINE_MCB

WA1_MCB

IEC16000123 V1 EN

Figure 67: Connection of SESRSYN function block in a single busbararrangement

Figure 67 illustrates connection principles for a single busbar. For the SESRSYNfunction there is one voltage transformer on each side of the circuit breaker. Thevoltage transformer circuit connections are straightforward; no special voltageselection is necessary.

The voltage from busbar VT is connected to U2PBB and the voltage from the line VTis connected to U2PLN. The conditions of the VT fuses shall also be connected asshown above.

12.1.4 Setting guidelines

The setting parameters for the Synchronizing, synchrocheck and energizing checkfunction SESRSYN are set via the local HMI (LHMI) or PCM600.

This setting guidelines describes the settings of the SESRSYN function via the LHMI.

Common base IED value for primary voltage ( UBase ) is set in a Global base valuefunction, GBASVAL, found under Main menu//Configuration/Power system/GlobalBaseValue/GBASVAL_X/UBase. The SESRSYN function has one settingfor the bus reference voltage (GblBaseSelBus) and one setting for the line referencevoltage (GblBaseSelLine) which independently of each other can be set to select oneof the twelve GBASVAL functions used for reference of base values (e.g. when apower transformer is installed in-between two VTs used for the function). This means

Section 12 1MRK 506 375-UEN -Control

216 Railway application RER670 2.2 IECApplication manual

Page 223: Railway application RER670 Version 2.2 IEC ... - ABB

that the reference voltage of bus and line can be set to different values. The settings forthe SESRSYN function are found under Main menu/Settings/IED Settings/Control/Synchronizing(25,SC/VC)/SESRSYN(25,SC/VC):X has been dividedinto four different setting groups: General, Synchronizing, Synchrocheck andEnergizingcheck.

General settingsOperation: The operation mode can be set On or Off. The setting Off disables thewhole function.

GblBaseSelBus and GblBaseSelLine

These configuration settings are used for selecting one of twelve GBASVALfunctions, which then is used as base value reference voltage, for bus and linerespectively.

SelPhaseBus

Configuration parameters for selecting the measuring phase of the voltage for busbar,which can be a single-phase (phase-neutral) or a positive sequence voltage.

SelPhaseLine

Configuration parameters for selecting the measuring phase of the voltage for line,which can be a single-phase (phase-neutral) or a positive sequence voltage.

PhaseShift

This setting is used to compensate the phase shift between the measured bus voltageand line voltage when:

• different phase-neutral voltages are selected (for example UL1 for bus and UL2for line);

• one available voltage is positive sequence and the other one is phase-neutral (forexample Pos. Seq. for bus and UL2 for line).

The set value is added to the measured line phase angle. The bus voltage is referencevoltage.

Synchronizing settingsOperationSynch

The setting Off disables the Synchronizing function. With the setting On, the functionis in the service mode and the output signal depends on the input conditions.

UHighBusSynch and UHighLineSynch

The voltage level settings shall be chosen in relation to the bus/line network voltage.The threshold voltages UHighBusSynch and UHighLineSynch have to be set lower

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 217Application manual

Page 224: Railway application RER670 Version 2.2 IEC ... - ABB

than the value where the network is expected to be synchronized. A typical value is80% of the rated voltage.

UDiffSynch

Setting of the voltage difference between the line voltage and the bus voltage. Thedifference is set depending on the network configuration and expected voltages in thetwo networks running asynchronously. A normal setting is 0.10-0.15 p.u.

FreqDiffMin

The setting FreqDiffMin is the minimum frequency difference where the systems aredefined to be asynchronous. For frequency differences lower than this value, thesystems are considered to be in parallel. A typical value for FreqDiffMin is 10 mHz.Generally, the value should be low if both synchronizing and synchrocheck functionsare provided, and it is better to let the synchronizing function close, as it will close atexactly the right instance if the networks run with a frequency difference.

To avoid overlapping of the synchronizing function and thesynchrocheck function the setting FreqDiffMin must be set to a highervalue than used setting FreqDiffM, respective FreqDiffA used forsynchrocheck.

FreqDiffMax

The setting FreqDiffMax is the maximum slip frequency at which synchronizing isaccepted. 1/FreqDiffMax shows the time for the vector to move 360 degrees, one turnon the synchronoscope, and is called Beat time. A typical value for FreqDiffMax is200-250 mHz, which gives beat times on 4-5 seconds. Higher values should beavoided as the two networks normally are regulated to nominal frequencyindependent of each other, so the frequency difference shall be small.

FreqRateChange

The maximum allowed rate of change for the frequency.

CloseAngleMax

The setting CloseAngleMax is the maximum closing angle between bus and line atwhich synchronizing is accepted. To minimize the moment stress when synchronizingnear a power station, a narrower limit should be used. A typical value is 15 degrees.

tBreaker

The tBreaker shall be set to match the closing time for the circuit breaker and shouldalso include the possible auxiliary relays in the closing circuit. It is important to checkthat no slow logic function blocks (e.g. in 100ms loop) are used in the configurationof the IED as there then can be big variations in closing time due to those components.Typical setting is 80-150 ms depending on the breaker closing time.

Section 12 1MRK 506 375-UEN -Control

218 Railway application RER670 2.2 IECApplication manual

Page 225: Railway application RER670 Version 2.2 IEC ... - ABB

tClosePulse

The setting for the duration of the breaker close pulse.

tMaxSynch

The setting tMaxSynch is set to reset the operation of the synchronizing function if theoperation does not take place within this time. The setting must allow for the setting ofFreqDiffMin, which will decide how long it will take maximum to reach phaseequality. At the setting of 10 mHz, the beat time is 100 seconds and the setting wouldthus need to be at least tMinSynch plus 100 seconds. If the network frequencies areexpected to be outside the limits from the start, a margin needs to be added. A typicalsetting is 600 seconds.

tMinSynch

The setting tMinSynch is set to limit the minimum time at which the synchronizingclosing attempt is given. The synchronizing function will not give a closing commandwithin this time, from when the synchronizing is started, even if a synchronizingcondition is fulfilled. A typical setting is 200 ms.

Synchrocheck settingsOperationSC

The OperationSC setting Off disables the synchrocheck function and sets the outputsAUTOSYOK, MANSYOK, TSTAUTSY and TSTMANSY to low. With the settingOn, the function is in the service mode and the output signal depends on the inputconditions.

UHighBusSC and UHighLineSC

The voltage level settings must be chosen in relation to the bus or line network voltage.The threshold voltages UHighBusSC and UHighLineSC have to be set lower than thevalue at which the breaker is expected to close with the synchronism check. A typicalvalue can be 80% of the base voltages.

UDiffSC

The setting for voltage difference between line and bus in p.u. This setting in p.u. isdefined as (U-Bus/GblBaseSelBus) - (U-Line/GblBaseSelLine). A normal setting is0,10-0,15 p.u.

FreqDiffM and FreqDiffA

The frequency difference level settings, FreqDiffM and FreqDiffA, shall be chosendepending on the condition in the network. At steady conditions a low frequencydifference setting is needed, where the FreqDiffM setting is used. For autoreclosing abigger frequency difference setting is preferable, where the FreqDiffA setting is used.A typical value for FreqDiffM can be10 mHz, and a typical value for FreqDiffA canbe 100-200 mHz.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 219Application manual

Page 226: Railway application RER670 Version 2.2 IEC ... - ABB

PhaseDiffM and PhaseDiffA

The phase angle difference level settings, PhaseDiffM and PhaseDiffA, shall also bechosen depending on conditions in the network. The phase angle setting must bechosen to allow closing under maximum load condition. A typical maximum value inheavy-loaded networks can be 45 degrees, whereas in most networks the maximumoccurring angle is below 25 degrees. The PhaseDiffM setting is a limitation toPhaseDiffA setting. Fluctuations occurring at high speed autoreclosing limitPhaseDiffA setting.

tSCM and tSCA

The purpose of the timer delay settings, tSCM and tSCA, is to ensure that thesynchrocheck conditions remains constant and that the situation is not due to atemporary interference. Should the conditions not persist for the specified time, thedelay timer is reset and the procedure is restarted when the conditions are fulfilledagain. Circuit breaker closing is thus not permitted until the synchrocheck situationhas remained constant throughout the set delay setting time. Manual closing isnormally under more stable conditions and a longer operation time delay setting isneeded, where the tSCM setting is used. During auto-reclosing, a shorter operationtime delay setting is preferable, where the tSCA setting is used. A typical value fortSCM can be 1 second and a typical value for tSCA can be 0.1 seconds.

Energizingcheck settingsAutoEnerg and ManEnerg

Two different settings can be used for automatic and manual closing of the circuitbreaker. The settings for each of them are:

• Off, the energizing function is disabled.• DLLB, Dead Line Live Bus, the line voltage is below set value of

ULowLineEnerg and the bus voltage is above set value of UHighBusEnerg.• DBLL, Dead Bus Live Line, the bus voltage is below set value of ULowBusEnerg

and the line voltage is above set value of UHighLineEnerg.• Both, energizing can be done in both directions, DLLB or DBLL.

ManEnergDBDL

If the parameter is set to On, manual closing is also enabled when both line voltage andbus voltage are below ULowLineEnerg and ULowBusEnerg respectively, andManEnerg is set to DLLB, DBLL or Both.

UHighBusEnerg and UHighLineEnerg

The voltage level settings must be chosen in relation to the bus or line network voltage.The threshold voltages UHighBusEnerg and UHighLineEnerg have to be set lowerthan the value at which the network is considered to be energized. A typical value canbe 80% of the base voltages.

ULowBusEnerg and ULowLineEnerg

Section 12 1MRK 506 375-UEN -Control

220 Railway application RER670 2.2 IECApplication manual

Page 227: Railway application RER670 Version 2.2 IEC ... - ABB

The threshold voltages ULowBusEnerg and ULowLineEnerg, have to be set to a valuegreater than the value where the network is considered not to be energized. A typicalvalue can be 40% of the base voltages.

A disconnected line can have a considerable potential due to, forinstance, induction from a line running in parallel, or by being fed viathe extinguishing capacitors in the circuit breakers. This voltage canbe as high as 30% or more of the base line voltage.

Because the setting ranges of the threshold voltages UHighBusEnerg/UHighLineEnerg and ULowBusEnerg/ULowLineEnerg partly overlap each other, thesetting conditions may be such that the setting of the non-energized threshold value ishigher than that of the energized threshold value. The parameters must therefore be setcarefully to avoid overlapping.

UMaxEnerg

This setting is used to block the closing when the voltage on the live side is above theset value of UMaxEnerg.

tAutoEnerg and tManEnerg

The purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure thatthe dead side remains de-energized and that the condition is not due to a temporaryinterference. Should the conditions not persist for the specified time, the delay timeris reset and the procedure is restarted when the conditions are fulfilled again. Circuitbreaker closing is thus not permitted until the energizing condition has remainedconstant throughout the set delay setting time.

12.2 Autoreclosing for railway system SMBRREC

12.2.1 IdentificationFunction Description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Autoreclosing for railway system SMBRREC

5(0 -->1)

IEC15000204 V1 EN

79

12.2.2 Application

Automatic reclosing is a well-established method for the restoration of service in apower system after a transient line fault. The majority of line faults are flashovers,

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 221Application manual

Page 228: Railway application RER670 Version 2.2 IEC ... - ABB

which are transient by nature. When the power line is switched off by the operation ofline protection and line breakers, the arc de-ionizes and recovers its ability towithstand voltage at a somewhat variable rate. Thus, a certain dead time with a de-energized line is necessary. Line service can then be resumed by automatic reclosingof the line breakers. The dead time selected should be long enough to ensure a highprobability of arc de-ionization and successful reclosing.

For individual line breakers, auto reclosing equipment, the required circuit breakerdead time is used to determine the “dead time” setting value. When simultaneoustripping and reclosing at the two line ends occurs, line dead time is approximatelyequal to the auto recloser “dead time”. If the auto reclosing dead time and line “deadtime” differ then, the line will be energized until the breakers at both ends haveopened.

Open

Closed

Operate time

Line

protection

Circuit

breaker

Break time

Tri

p c

om

man

d

Conta

cts s

ep

ara

ted

Arc

extin

gu

ish

ers

Fault duration Circuit breaker open time Fault duration

Resets

Insta

nt

of

fault

Op

era

tes

Break timeClosing time

Operate time

Fa

ult

Op

era

tes

Resets

Clo

se c

om

ma

nd

Conta

ct c

lose

d

Set AR dead time Reclaim timeAuto-reclosing

function

Sta

rt A

R

Reclo

sin

g

com

ma

nd

AR

reset

IEC04000146-3-en.vsd

IEC04000146 V3 EN

Figure 68: Single-shot automatic reclosing at a permanent fault

Automatic reclosing can be performed with or without the use of synchrocheck.

For the individual line breakers and auto reclosing equipment, the auto reclosing deadtime expression is used. This is the dead time setting for the auto recloser. Duringsimultaneous tripping and reclosing at the two line ends, auto reclosing dead time isapproximately equal to the line dead time. Otherwise these two times may differ asone line end might have a slower trip than the other end which means that the line willnot be dead until both ends have opened.

Section 12 1MRK 506 375-UEN -Control

222 Railway application RER670 2.2 IECApplication manual

Page 229: Railway application RER670 Version 2.2 IEC ... - ABB

If the fault is permanent, the line protection will trip again when reclosing is attemptedin order to clear the fault.

It is common to use one automatic reclosing function per line circuit breaker (CB).When one CB per line end is used, then there is one auto- recloser per line end. If autoreclosers are included in duplicated line protection, which means two auto reclosersper CB, one should take measures to avoid uncoordinated reclosing commands.

The auto recloser can be selected to perform multiple shots. The auto reclosing deadtime can be set to give either High-Speed Automatic Reclosing (HSAR) or DelayedAutomatic Reclosing (DAR). HSAR usually means a dead time of less than 1 second.

The mode of automatic reclosing varies. Single-shot and multi-shot are in use. Thefirst shot can have a short delay, HSAR, or a longer delay, DAR. The second andfollowing reclosing shots have a rather long delay. When multiple shots are used thedead time must harmonize with the breaker duty-cycle capacity.

Automatic reclosing is usually started by the line protection and in particular byinstantaneous tripping of such protection. The auto recloser can be inhibited (blocked)when certain protection functions detecting permanent faults (e.g. thermal overloadprotection). Back-up protection zones indicating faults outside the own line aretypically connected to inhibit the auto recloser.

Automatic reclosing should not be attempted when closing a CB and energizing a lineonto a fault (SOTF), except when multiple-shots are used where shots 2 etc. will bestarted at SOTF. Auto reclosing is often combined with a release condition fromsynchrocheck and dead line or dead busbar check.

Protection systems are usually sub-divided and provided with two redundantprotection IEDs. In such systems it is common to provide auto reclosing in only oneof the sub-systems as the requirement is for fault clearance and a failure to reclosebecause of the auto recloser being out of service is not considered a major disturbance.If two auto reclosers are provided on the same breaker, the application must becarefully checked and normally one must be the master and be connected to inhibit theother auto recloser if it has started. This inhibit can, for example, be done from an autorecloser by using operation in progress signal.

A permanent fault will cause the line protection to trip again when it recloses in anattempt to energize the line.

The auto reclosing function allows a number of parameters to be adjusted.

Examples:

• number of auto reclosing shots• auto reclosing dead times for each shot

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 223Application manual

Page 230: Railway application RER670 Version 2.2 IEC ... - ABB

12.2.2.1 Auto reclosing operation Off and On

Operation of the automatic recloser can be set to Off and On by a setting parameter orby external control. The setting parameter Operation = Off, or On sets the function toOff or On. With the settings Operation = On and ExternalCtrl = On , the control ismade by input signal pulses to the inputs On and Off, for example, from a controlsystem or by a control switch.

When the auto recloser is set On, the SETON output is set, and the auto recloserbecomes operative if other conditions such as circuit breaker is closed and circuitbreaker is ready are also fulfilled, the READY output is activated (high). Then the autorecloser is ready to accept a start.

12.2.2.2 Start auto reclosing and conditions for start of a reclosing cycle

The usual way to start an auto reclosing cycle, or sequence, is to start it at selectivetripping by line protection by applying a signal to the START input. Starting signalscan be either, general trip signals or, only the conditions for differential, distanceprotection zone 1 and distance protection aided trip. In some cases also directionalearth fault protection aided trip can be connected to start an auto reclose attempt. Ifgeneral trip is used to start the auto recloser it is important to block it from otherfunctions that should not start an auto reclosing sequence.

In cases where one wants to differentiate auto reclosing dead time, for different powersystem configuration or at tripping by different protection stages, one can also use theSTARTHS input (start high-speed reclosing). When initiating STARTHS, the autoreclosing dead time for high-speed shot 1, t1_HS is used and the closing is donewithout checking the synchrocheck condition.

A number of conditions need to be fulfilled for the start to be accepted and a new autoreclosing cycle to be started. They are linked to dedicated inputs. The inputs are:

• CBREADY, circuit breaker ready for a reclosing cycle, for example, chargedoperating gear.

• CBCLOSED to ensure that the circuit breaker was closed when the line faultoccurred and start was applied.

• No signal at INHIBIT input that is, no blocking or inhibit signal present. After thestart has been accepted, it is latched in and an internal signal “start” is set. It canbe interrupted by certain events, like an “inhibit” signal.

12.2.2.3 Start auto reclosing from circuit breaker open information

If a user wants to initiate auto reclosing from the circuit breaker open position insteadof from protection trip signals, the function offers such a possibility. This startingmode is selected with the setting parameter StartByCBOpen=On. Typically a circuitbreaker auxiliary contact of type NO (normally open) is connected to CBCLOSED andSTART. When the signal changes from circuit breaker closed to circuit breaker openan auto reclosing start pulse is generated and latched in the function, subject to the

Section 12 1MRK 506 375-UEN -Control

224 Railway application RER670 2.2 IECApplication manual

Page 231: Railway application RER670 Version 2.2 IEC ... - ABB

usual checks. The auto reclosing sequence continues then as usual. Signals frommanual tripping and other functions, which shall prevent auto reclosing, need to beconnected to the INHIBIT input.

12.2.2.4 Blocking of the auto recloser

Auto reclose attempts are expected to take place only for faults on the own line. Theauto recloser must be blocked by activating the INHIBIT input for the followingconditions:

• Tripping from delayed distance protection zones• Tripping from back-up protection functions• Tripping from breaker failure function• Intertrip received from remote end circuit breaker failure function• Busbar protection tripping

Depending of the starting principle (general trip or only instantaneous trip) adoptedabove the delayed and back-up zones might not be required. Breaker failure trip localand remote must however always be connected.

12.2.2.5 Control of the auto reclosing dead time for shot 1

For the first shot, there is a separate setting for the dead time, t1. If no particular inputsignal is applied, the auto reclosing dead time t1 will be used. There is also a separatetime setting facility for high-speed auto reclosing without synchrocheck, t1_HS,available for use when required. It is activated by the STARTHS input.

12.2.2.6 Long trip signal

When start pulse duration signal is longer than set maximum start pulse duration, theauto reclosing sequence interrupts in the same way as for a signal to the INHIBITinput.

12.2.2.7 Maximum number of reclosing shots

The maximum number of auto reclosing shots in an auto reclosing cycle is selected bythe setting NoOfShots. A maximum of five shots can be done.

12.2.2.8 Auto reclosing reclaim timer

The tReclaim timer defines the time it takes from issue of the breaker closingcommand, until the auto recloser resets. Should a new trip occur during this time, it istreated as a continuation of the first fault. The reclaim timer is started when the circuitbreaker closing command is given.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 225Application manual

Page 232: Railway application RER670 Version 2.2 IEC ... - ABB

12.2.2.9 Pulsing of the circuit breaker closing command and counter

The circuit breaker closing command, CLOSECB is given as a pulse with a durationset by the tPulse setting. For circuit breakers without an anti-pumping function, closepulse cutting can be used. It is selected by the CutPulse setting. In case of a new startpulse (trip), the breaker closing command pulse is then cut (interrupted). Theminimum breaker closing command pulse length is always 50ms. At the issue of thebreaker closing command, the appropriate auto recloser operation counter isincremented. There is a counter for each type of auto reclosing command and one forthe total number of auto reclosing commands.

12.2.2.10 Transient fault

After the breaker closing command the reclaim timer keeps running for the settReclaim time. If no start (trip) occurs within this time, the auto recloser will reset. Thecircuit breaker remains closed and the operating gear recharges. The CBCLOSED andCBREADY input signals will be set.

12.2.2.11 Permanent fault and reclosing unsuccessful signal

If a new start occurs, and the number of auto reclosing shots is set to 1, and a newSTART or TRSOTF input signal appears, after the circuit breaker closing command,the UNSUCCL output (unsuccessful reclosing) is set high. The timer for the first shotcan no longer be started. Depending on the set number of auto reclosing shots furthershots may be made or the auto reclosing sequence is ended. After reclaim timer time-out the auto recloser resets, but the circuit breaker remains open. The circuit breakerclosed information through the CBCLOSED input is missing. Thus, the auto recloseris not ready for a new auto reclosing cycle. Normally, the UNSUCCL output appearswhen a new start is received after the last auto reclosing shot has been made and theauto recloser is inhibited. The output signal resets after reclaim time. The UNSUCCLoutput can for example, be used in multi-breaker arrangement to cancel the autoreclosing for the second circuit breaker, if the first circuit breaker closed onto apersistent fault. It can also be used to generate a lock-out of manual circuit breakerclosing until the operator has reset the lock-out, see separate section.

12.2.2.12 Lock-out initiation

In many cases there is a requirement that a lock-out is generated when the autoreclosing attempt fails. This is done with logic connected to the in- and outputs of theauto recloser and connected to binary I/O as required. Many alternative ways ofperforming the logic exist depending on whether manual circuit breaker closing isinterlocked in the IED, whether an external physical lock-out relay exists and whetherthe reset is hardwired, or carried out by means of communication. There are alsodifferent alternatives regarding what shall generate lock-out. Examples of questionsare:

Section 12 1MRK 506 375-UEN -Control

226 Railway application RER670 2.2 IECApplication manual

Page 233: Railway application RER670 Version 2.2 IEC ... - ABB

• shall back-up time delayed trip give lock-out (normally yes)• shall lock-out be generated when closing onto a fault (mostly)• shall lock-out be generated when the auto recloser is Off at the fault• shall lock-out be generated if the circuit breaker did not have sufficient operating

power for an auto reclosing sequence (normally not as no auto closing attempt hasbeen given)

In Figures 69 and 70 the logic shows how a closing lock-out logic can be designed withthe lock-out relay as an external relay alternatively with the lock-out created internallywith the manual closing going through the synchrocheck function. An example oflock-out logic.

Lock-out RXMD1

11

1221

MAIN ZAK CLOSE CLOSE COMMAND

SMBO

OR

SMBRREC

OR

CCRBRF

BU-TRIP

ZCVPSOF-TRIP INHIBIT

UNSUCCL

TRBU

IEC05000315-4-en.vsdIEC05000315-WMF V4 EN

Figure 69: Lock-out arranged with an external lock-out relay

CLOSE COMMAND

OR

SMBRREC

OR

CCRBRF

BU-TRIP

ZCVPSOF-TRIP INHIBIT

UNSUCCL

TRBU

SMPPTRC

AND

RESET LOCK-OUT

OR

OR

SESRSYN

Functional key,

SOFTWARE

OR IO RESET

MANSYOK

MAN CLOSE

SMBRREC CLOSE

CLLKOUT

RSTLKOUT

SETLKOUT

IEC05000316-4-en.vsdx

SMBO

MANENOK

IEC05000316-WMF V4 EN

Figure 70: Lock-out arranged with internal logic with manual closing goingthrough in IED

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 227Application manual

Page 234: Railway application RER670 Version 2.2 IEC ... - ABB

12.2.2.13 Thermal overload protection holding the auto recloser back

If the THOLHOLD input (thermal overload protection holding auto reclosing back) isactivated, it will keep the auto recloser on a hold until it is reset. There may thus be aconsiderable delay between start of the auto recloser and the breaker closingcommand to the circuit breaker. An external logic limiting the time and sending aninhibit to the INHIBIT input can be used. The input can also be used to set the autorecloser on hold for a longer or shorter period.

12.2.3 Setting guidelines

12.2.3.1 Configuration

Use the PCM600 configuration tool to configure signals.

Auto recloser function parameters are set via the local HMI or Parameter Setting Tool(PST). Parameter Setting Tool is a part of PCM600.

Recommendations for input signalsPlease see Figure 71 and default factory configuration for examples.

BLKOFFUsed to unblock the auto recloser when it has been blocked due to activating BLKONinput or by an unsuccessful auto reclosing attempt if the BlockByUnsucCl setting is setto On.

BLKONUsed to block the auto recloser, for example, when certain special service conditionsarise. When used, blocking must be reset with BLKOFF.

CBCLOSED and CBREADYThese binary inputs should pick-up information from the circuit breaker. At threeoperating gears in the circuit breaker (single pole operated circuit breakers) theconnection should be “All poles closed” (series connection of the NO contacts) or “Atleast one pole open” (parallel connection of NC contacts). The CBREADY is a signalmeaning that the circuit breaker is ready for an auto reclosing operation, either Close-Open (CO), or Open-Close-Open (OCO). If the available signal is of type “circuitbreaker not charged” or “not ready”, an inverter can be inserted in front of theCBREADY input.

INHIBITTo this input shall be connected signals that interrupt an auto reclosing cycle orprevent a start from being accepted. Such signals can come from protection for a lineconnected shunt reactor, from transfer trip receive, from back-up protection functions,busbar protection trip or from breaker failure protection. When the circuit breakeropen position is set to start the auto recloser, then manual opening must also be

Section 12 1MRK 506 375-UEN -Control

228 Railway application RER670 2.2 IECApplication manual

Page 235: Railway application RER670 Version 2.2 IEC ... - ABB

connected here. The inhibit is often a combination of signals from external IEDs viathe I/O and internal functions. An OR-gate is then used for the combination.

ON and OFFThese inputs can be connected to binary inputs or to a communication interface blockfor external control.

RESETUsed to reset the auto recloser to start conditions. Possible hold by thermal overloadprotection will be reset. Circuit breaker position will be checked and time settings willbe restarted with their set times.

RSTCOUNTThere is a counter for each type of auto reclosing and one for the total number of circuitbreaker close commands issued. All counters are reset with the RSTCOUNT input orby an IEC 61850 command.

SKIPHSThe high-speed auto reclosing sequence can be skipped and be replaced by normalauto reclosing sequence by activating SKIPHS input before the STARTHS high-speedstart input is activated. The replacement is done for the 1st shot.

STARTThe START input should be connected to the trip function (SMPPTRC) output, whichstarts the auto recloser operation. It can also be connected to a binary input for startfrom an external contact. A logical OR-gate can be used to combine the number ofstart sources.

If StartByCBOpen is used, the circuit breaker open condition shallalso be connected to the START input.

STARTHS, Start high-speed auto reclosingIt may be used when one wants to use two different dead times in different protectiontrip operations. This input starts the dead time t1_HS. High-speed reclosing shot 1started by this input is without a synchronization check.

SYNCThis input is connected to the internal synchrocheck function when required or to anexternal device for synchronism. If neither internal nor external synchronism orenergizing check is required, it can be connected to a permanently high source, TRUE.The signal is required for shots 1-5 to proceed (Note! Not the high-speed step).

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 229Application manual

Page 236: Railway application RER670 Version 2.2 IEC ... - ABB

THOLHOLDSignal “Thermal overload protection holding back auto reclosing”. It can beconnected to a thermal overload protection trip signal which resets only when thethermal content has fallen to an acceptable level, for example, 70%. As long as thesignal is high, indicating that the line is hot, the auto reclosing is held back. When thesignal resets, a reclosing cycle will continue. Observe that this have a considerabledelay. Input can also be used for other purposes if for some reason the auto reclosingshot needs to be halted.

TRSOTFThis is the signal “Trip by Switch Onto Fault”. It is usually connected to the “switchonto fault” output of line protection if multi-shot auto reclosing attempts are used. Theinput will start the shots two to five.

Recommendations for output signalsPlease see Figure 71 and default factory configuration for examples.

IPT1, IPT2, IPT3, IPT4 and IPT5Indicates that auto reclosing shots one to five are in progress. The signals can be usedas an indication of progress or for own logic.

ABORTEDThe ABORTED output indicates that the auto recloser is inhibited while it is in one ofthe following internal states:

• inProgress: auto recloser is started and dead time is in progress• reclaimTimeStarted: the circuit breaker closing command has started the reclaim

timer

ACTIVEIndicates that the auto recloser is active, from start until end of reclaim time.

BLOCKEDIndicates that auto recloser is temporarily or permanently blocked.

CLOSECBConnect to a binary output for circuit breaker closing command.

COUNTT1, COUNTT2, COUNTT3, COUNTT4 and COUNTT5Indicates the number of auto reclosing shots made for respective shot.

COUNTARIndicates the total number of auto reclosing shots made.

Section 12 1MRK 506 375-UEN -Control

230 Railway application RER670 2.2 IECApplication manual

Page 237: Railway application RER670 Version 2.2 IEC ... - ABB

INHIBOUTIf the INHIBIT input is activated it is reported on the INHIBOUT output.

INPROGRIndicates that an auto recloser sequence is in progress, from start until circuit breakerclose command.

READYIndicates that the auto recloser is ready for a new and complete auto reclosingsequence. It can be connected to the zone extension if a line protection should haveextended zone reach before auto reclosing.

SETONIndicates that auto recloser is switched on and operative.

SUCCLIf the circuit breaker closing command is given and the circuit breaker is closed withinthe set time interval tUnsucCl, the SUCCL output is activated after the set time intervaltSuccessful.

SYNCFAILThe SYNCFAIL output indicates that the auto recloser is inhibited because thesynchrocheck or energizing check condition has not been fulfilled within the set timeinterval, tSync. Also ABORTED output will be activated.

UNSUCCLIndicates unsuccessful reclosing.

Connection and setting examplesFigure 71 shows an example of how to connect the auto recloser.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 231Application manual

Page 238: Railway application RER670 Version 2.2 IEC ... - ABB

ON

OFF

BLKON

BLKOFF

INHIBIT

BLOCKED

SETON

INPROGR

ACTIVE

UNSUCCL

SUCCL

CLOSECB

CBREADY

CBCLOSED

RESET

START

THOLHOLD

READY

TRSOTF

SYNC

INPUT

xx

xx

xx

xx

xx

xx

xx

xx

xx

OR

OUTPUT

xx

xx

xx

xx

xx

xx

xx

xx

xx

xx

PROTECTION

xxxx-TRIP

ZCVPSOF-TRIP

SESRSYN-AUTOOK

BIM BOM

SMBRREC

STARTHS

SKIPHS

RSTCOUNT

IPT1

IPT2

IPT3

IPT4

IPT5

IEC17000005-1-en.vsdx

IEC17000005 V1 EN

Figure 71: Example of I/O-signal connections at an auto reclosing sequence

12.2.3.2 Auto recloser settings

The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.

This setting guideline describes the settings of the auto recloser using the LHMI.

The settings for the auto recloser are found under Main menu/Settings/IED Settings/Control/AutoRecloser(79,5(0->1))/SMBRREC(79,5(0->)):X and have beendivided into four different setting groups: General, CircuitBreaker, DeadTime andMasterSlave.

General settingsOperation: The operation of the auto recloser can be switched On or Off.

ExternalCtrl: This setting makes it possible to switch the auto recloser On or Off usingan external switch via IO or communication ports.

StartByCBOpen: The normal setting Off is used when the function is started byprotection trip signals. If set On the start of the auto recloser is controlled by an circuitbreaker auxiliary contact.

LongStartInhib: Usually the protection trip command, used as an auto reclosing startsignal, resets quickly as the fault is cleared. A prolonged trip command may depend

Section 12 1MRK 506 375-UEN -Control

232 Railway application RER670 2.2 IECApplication manual

Page 239: Railway application RER670 Version 2.2 IEC ... - ABB

on a circuit breaker failing to clear the fault. A protection trip signal present when thecircuit breaker is reclosed will result in a new trip. The user can set a maximum startpulse duration time tLongStartInh. This start pulse duration time is controlled by theLongStartInhib setting. When the start pulse duration signal is longer than setmaximum start pulse duration, the auto reclosing sequence interrupts in the same wayas for a signal to the INHIBIT input.

tLongStartInh: The user can set a maximum start pulse duration time tLongStartInh.At a set time somewhat longer than the auto reclosing dead time, this facility will notinfluence the auto reclosing. A typical setting of tLongStartInh could be close to theauto reclosing dead time.

tInhibit: To ensure reliable interruption and temporary blocking of the auto recloser aresetting time delay tInhibit is used. The auto recloser will be blocked this time afterthe deactivation of the INHIBIT input. A typical resetting delay is 5.0 s.

CircuitBreaker settingsCBReadyType: The selection depends on the type of performance available from thecircuit breaker operating gear. At setting OCO (circuit breaker ready for an Open –Close – Open cycle), the condition is checked only at the start of the auto reclosingcycle. The signal will disappear after tripping, but the circuit breaker will still be ableto perform the C-O sequence. For the selection CO (circuit breaker ready for a Close– Open cycle) the condition is also checked after the set auto reclosing dead time. Thisselection has a value first of all at multi-shot auto reclosing to ensure that the circuitbreaker is ready for a C-O sequence at shot two and further shots. During single-shotauto reclosing, the OCO selection can be used. A breaker shall according to its dutycycle always have storing energy for a CO operation after the first trip. (IEC 56 dutycycle is O – 0.3sec – CO – 3min – CO).

FollowCB: The usual setting is Follow CB = Off. The setting On can be used fordelayed auto reclosing with long delay, to cover the case when a circuit breaker isbeing manually closed during the auto reclosing dead time before the auto recloser hasissued its breaker close command.

BlockByUnsucCl: Setting of whether an unsuccessful auto reclosing attempt shall setthe auto recloser in blocked status. If used the BLKOFF input must be configured tounblock the function after an unsuccessful auto reclosing attempt. Normal setting isOff.

CutPulse: In circuit breakers without anti-pumping relays, the setting CutPulse = Oncan be used to avoid repeated closing operation when reclosing onto a fault. A newstart will then cut the ongoing pulse.

tPulse: The circuit breaker closing command should be long enough to ensure reliableoperation of the circuit breaker. The circuit breaker closing command pulse has aduration set by the tPulse setting. A typical setting may be tPulse = 200 ms. A longerpulse setting may facilitate dynamic indication at testing, for example, in debug modeof the Application Configuration Tool (ACT) in PCM600. In circuit breakers without

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 233Application manual

Page 240: Railway application RER670 Version 2.2 IEC ... - ABB

anti-pumping relays, the setting CutPulse = On can be used to avoid repeated closingoperations when reclosing onto a fault. A new start will then cut the ongoing pulse.

tReclaim: The reclaim time sets the time for resetting the function to its original state,after which a line fault and tripping will be treated as an independent new case with anew auto reclosing cycle. One may consider a nominal CB duty cycle of for instance,O – 0.3sec – CO – 3min – CO. However the 3 minute (180 s) recovery time is usuallynot critical as fault levels are mostly lower than rated value and the risk of a new faultwithin a short time is negligible. A typical time may be tReclaim = 60 or 180 sdependent on the fault level and circuit breaker duty cycle.

tSync: Maximum wait time for fulfilled synchrocheck conditions. The time windowshould be coordinated with the operate time and other settings of the synchrocheckfunction. Attention should also be paid to the possibility of a power swing whenreclosing after a line fault. Too short a time may prevent a potentially successful autoreclosing.

tCBClosedMin: A typical setting is 5.0 s. If the circuit breaker has not been closed forat least this minimum time, an auto reclosing start will not be accepted.

tSuccessful: If the circuit breaker closing command is given and the circuit breaker isclosed within the set time interval tUnsucCl, the SUCCL output is activated after theset time interval tSuccessful.

tUnsucCl: The reclaim timer, tReclaim, is started each time a circuit breaker closingcommand is given. If no start occurs within this time, the auto recloser will reset. Anew start received in “reclaim time” status will reenter the auto recloser to “inprogress” status as long as the final shot is not reached. The auto recloser will reset andenter “inactive” status if a new start is given during the final reclaim time. The autoreclosing sequence is considered unsuccessful and the UNSUCCL output is activated.

DeadTime settingsNoOfShots: In power transmission one shot is mostly used. In most cases one autoreclosing shot is sufficient as the majority of arcing faults will cease after the first autoreclosing shot. In power systems with many other types of faults caused by otherphenomena, for example wind, a greater number of auto reclosing attempts (shots) canbe motivated.

t1: There is a separate setting for the first shot auto reclosing dead time. Different localphenomena, such as moisture, salt, pollution, can influence the required dead time.Some users apply Delayed Auto Reclosing (DAR) with delays of 10s or more.

t1_HS: There is also a separate time setting facility for high-speed auto reclosing,t1_HS. This high-speed auto reclosing is activated by the STARTHS input and is usedwhen auto reclosing is done without the requirement of synchrocheck conditions to befulfilled. A typical dead time is 400ms.

t2 , t3, t4, t5: The delay of auto reclosing shot two and possible later shots are usuallyset at 30s or more. A check that the circuit breaker duty cycle can manage the selectedsetting must be done. The setting can in some cases be restricted by national

Section 12 1MRK 506 375-UEN -Control

234 Railway application RER670 2.2 IECApplication manual

Page 241: Railway application RER670 Version 2.2 IEC ... - ABB

regulations. For multiple shots the setting of shots two to five must be longer than thecircuit breaker duty cycle time.

12.3 Apparatus control APC

12.3.1 Application

The apparatus control is a functionality for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is given afterevaluation of conditions from other functions such as interlocking, synchrocheck,operator place selection and external or internal blockings.

The complete apparatus control function is not included in thisproduct, and the information below is included for understanding ofthe principle for the use of QCBAY, LOCREM, LOCREMCTRL andSXCBR.

Figure 72 shows from which places the apparatus control function receivescommands. The commands to an apparatus can be initiated from the Control Centre(CC), the station HMI or the local HMI on the IED front.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 235Application manual

Page 242: Railway application RER670 Version 2.2 IEC ... - ABB

Station HMI

GW

cc

Station bus

breakers disconnectors earthing switchesIEC08000227.vsd

ApparatusControl

IED

I/O

Local HMI

ApparatusControl

IED

I/O

ApparatusControl

IED

I/O

Local HMI

Local HMI

IEC08000227 V1 EN

Figure 72: Overview of the apparatus control functions

Features in the apparatus control function:

• Operation of primary apparatuses• Select-Execute principle to give high security• Selection and reservation function to prevent simultaneous operation• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Pole discordance supervision• Operation counter• Suppression of mid position

The apparatus control function is realized by means of a number of function blocksdesignated:

• Switch controller SCSWI• Circuit breaker SXCBR• Circuit switch SXSWI• Bay control QCBAY• Bay reserve QCRSV

Section 12 1MRK 506 375-UEN -Control

236 Railway application RER670 2.2 IECApplication manual

Page 243: Railway application RER670 Version 2.2 IEC ... - ABB

• Reservation input RESIN• Local remote LOCREM• Local remote control LOCREMCTRL

The signal flow between the function blocks is shown in Figure 73. To realize thereservation function, the function blocks Reservation input (RESIN) and Bay reserve(QCRSV) also are included in the apparatus control function. The applicationdescription for all these functions can be found below. The function SCILO in theFigure below is the logical node for interlocking.

When the circuit breaker or switch is located in a breaker IED, two more functions areadded:

• GOOSE receive for switching device GOOSEXLNRCV• Proxy for signals from switching device via GOOSE XLNPROXY

The extension of the signal flow and the usage of the GOOSE communication areshown in Figure 74.

en05000116.vsd

IEC 61850

IEC05000116 V2 EN

Figure 73: Signal flow between apparatus control function blocks when allfunctions are situated within the IED

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 237Application manual

Page 244: Railway application RER670 Version 2.2 IEC ... - ABB

Merging Unit

Bay level IED

XCBRXCBR

XCBR

SCSWI

IEC 61850 on station bus

XSWI

QCBAY

SCILO

SCSWI

GOOSEXLNRCV

SCILO

XLNPROXY

GOOSEXLNRCV XLNPROXY

-QA1

-QB1

-QB9

GOOSE over process bus

IEC16000070-1-EN.vsdx

IEC16000070 V1 EN

Figure 74: Signal flow between apparatus control functions with XCBR andXSWI located in a breaker IED

Control operation can be performed from the local IED HMI. If users are defined inthe IED, then the local/remote switch is under authority control, otherwise the defaultuser can perform control operations from the local IED HMI without logging in. Thedefault position of the local/remote switch is on remote.

Section 12 1MRK 506 375-UEN -Control

238 Railway application RER670 2.2 IECApplication manual

Page 245: Railway application RER670 Version 2.2 IEC ... - ABB

Accepted originator categories for PSTOIf the requested command is accepted by the authority control, the value will change.Otherwise the attribute blocked-by-switching-hierarchy is set in the cause signal. Ifthe PSTO value is changed during a command, then the command is aborted.

The accepted originator categories for each PSTO value are shown in Table 25.

Table 25: Accepted originator categories for each PSTO

Permitted Source To Operate Originator (orCat)

0 = Off 4,5,6

1 = Local 1,4,5,6

2 = Remote 2,3,4,5,6

3 = Faulty 4,5,6

4 = Not in use 4,5,6

5 = All 1,2,3,4,5,6

6 = Station 2,4,5,6

7 = Remote 3,4,5,6

PSTO = All, then it is no priority between operator places. All operator places areallowed to operate.

According to IEC 61850 standard the orCat attribute in originator category aredefined in Table 26

Table 26: orCat attribute according to IE C61850

Value Description

0 not-supported

1 bay-control

2 station-control

3 remote-control

4 automatic-bay

5 automatic-station

6 automatic-remote

7 maintenance

8 process

12.3.1.1 Bay control QCBAY

The Bay control (QCBAY) is used to handle the selection of the operator place perbay. The function gives permission to operate from two main types of locations eitherfrom Remote (for example, control centre or station HMI) or from Local (local HMIon the IED) or from all (Local and Remote). The Local/Remote switch position can

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 239Application manual

Page 246: Railway application RER670 Version 2.2 IEC ... - ABB

also be set to Off, which means no operator place selected that is, operation is notpossible either from local or from remote.

For IEC 61850-8-1 communication, the Bay Control function can be set todiscriminate between commands with orCat station and remote (2 and 3). Theselection is then done through the IEC 61850-8-1 edition 2 command LocSta.

QCBAY also provides blocking functions that can be distributed to differentapparatuses within the bay. There are two different blocking alternatives:

• Blocking of update of positions• Blocking of commands

IEC13000016-2-en.vsd

IEC13000016 V2 EN

Figure 75: APC - Local remote function block

12.3.1.2 Switch controller SCSWI

After the selection of an apparatus and before the execution, the switch controllerperforms the following checks and actions:

Section 12 1MRK 506 375-UEN -Control

240 Railway application RER670 2.2 IECApplication manual

Page 247: Railway application RER670 Version 2.2 IEC ... - ABB

• A request initiates to reserve other bays to prevent simultaneous operation.• Actual position inputs for interlocking information are read and evaluated if the

operation is permitted.• The synchrocheck/synchronizing conditions are read and checked, and performs

operation upon positive response.• The blocking conditions are evaluated• The position indications are evaluated according to given command and its

requested direction (open or closed).

The command sequence is supervised regarding the time between:

• Select and execute.• Select and until the reservation is granted.• Execute and the final end position of the apparatus.• Execute and valid close conditions from the synchrocheck.

At error the command sequence is cancelled.

The switch controller is not dependent on the type of switching device SXCBR orSXSWI. The switch controller represents the content of the SCSWI logical node(according to IEC 61850) with mandatory functionality.

12.3.1.3 Switches SXCBR/SXSWI

Switches are functions used to close and interrupt an ac power circuit under normalconditions, or to interrupt the circuit under fault, or emergency conditions. Theintention with these functions is to represent the lowest level of a power-switchingdevice with or without short circuit breaking capability, for example, circuit breakers,disconnectors, earthing switches etc.

The purpose of these functions is to provide the actual status of positions and toperform the control operations, that is, pass all the commands to the primary apparatusvia output boards and to supervise the switching operation and position.

Switches have the following functionalities:

• Local/Remote switch intended for the switchyard• Block/deblock for open/close command respectively• Update block/deblock of position indication• Substitution of position indication• Supervision timer that the primary device starts moving after a command• Supervision of allowed time for intermediate position• Definition of pulse duration for open/close command respectively

The realizations of these functions are done with SXCBR representing a circuitbreaker and with SXSWI representing a circuit switch that is, a disconnector or anearthing switch.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 241Application manual

Page 248: Railway application RER670 Version 2.2 IEC ... - ABB

The content of this function is represented by the IEC 61850 definitions for the logicalnodes Circuit breaker (SXCBR) and Circuit switch (SXSWI) with mandatoryfunctionality.

12.3.1.4 Proxy for signals from switching device via GOOSE XLNPROXY

The purpose of the proxy for signals from switching device via GOOSE(XLNPROXY) is to give the same internal representation of the position status andcontrol response for a switch modeled in a breaker IED as if represented by a SXCBRor SXSWI function.

The command response functionality is dependent on the connection of the executioninformation, XIN, from the SCSWI function controlling the represented switch.Otherwise, the function only reflects the current status of the switch, such as blocking,selection, position, operating capability and operation counter.

Since different switches are represented differently on IEC 61850, the data that ismandatory to model in IEC 61850 is mandatory inputs and the other useful data for thecommand and status following is optional. To make it easy to choose which data to usefor the XLNPROXY function, their usage is controlled by the connection of eachdata’s signal input and valid input. These connections are usually from theGOOSEXLNRCV function (see Figure 76 and Figure 77).

IEC16000071 V1 EN

Figure 76: Configuration with XLNPROXY and GOOSEXLNRCV where all theIEC 61850 modelled data is used, including selection

Section 12 1MRK 506 375-UEN -Control

242 Railway application RER670 2.2 IECApplication manual

Page 249: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000072 V1 EN

Figure 77: Configuration with XLNPROXY and GOOSEXLNRCV where only themandatory data in the IEC 61850 modelling is used

All the information from the XLNPROXY to the SCSWI about command followingstatus, causes for failed command and selection status is transferred in the outputXPOS. The other outputs may be used by other functions in the same way as thecorresponding outputs of the SXCBR and SXSWI function.

When a command has been issued from the connected SCSWI function, theXLNPROXY function awaits the response on it from the represented switch throughthe inputs POSVAL and OPOK. While waiting for the switch to start moving, itchecks if the switch is blocked for the operation. When the switch has started movingand no blocking condition has been detected, XLNPROXY issues a response to theSCSWI function that the command has started. If OPOK is used, this response is givenwhen XLNPROXY receives the signal.

If no movement of the switch is registered within the limit tStartMove, the commandis considered failed, and the cause of the failure is evaluated. In the evaluation, thefunction checks if the state of the represented switch is indicating that the commandis blocked in any way during the command, and gives the appropriate cause to theSCSWI function. This cause is also shown on the output L_CAUSE as indicated in thefollowing table:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 243Application manual

Page 250: Railway application RER670 Version 2.2 IEC ... - ABB

Table 27: Possible cause values from XLNPROXY

CauseNo

Cause Description Conditions

8 Blocked-by-Mode The BEH input is 5.

2 Blocked-by-switching-hierarchy The LOC input indicates that only local commands areallowed for the breaker IED function.

-24 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is blockedfor open commands.

-25 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is blockedfor close commands.

9 Blocked-by-process If the Blk input is connected and active indicating that theswitch is dynamically blocked. Or if the OPCAP input isconnected, it indicates that the operation capability of theswitch is not enough to perform the command.

5 Position-reached Switch is already in the intended position.

-31 Switch-not-start-moving Switch did not start moving within tStartMove.

-32 Persistent-intermediate-state The switch stopped in intermediate state for longer thantIntermediate.

-33 Switch-returned-to-init-pos Switch returned to the initial position.

-34 Switch-in-bad-state Switch is in a bad position.

-35 Not-expected-final-position Switch did not reach the expected final position.

The OPCAP input and output are used for the CBOpCap data of aXCBR respectively SwOpCap for a XSWI. The interpretation for thecommand following is controlled through the setting SwitchType.

12.3.1.5 Reservation function (QCRSV and RESIN)

The purpose of the reservation function is primarily to transfer interlockinginformation between IEDs in a safe way and to prevent double operation in a bay,switchyard part, or complete substation.

For interlocking evaluation in a substation, the position information from switchingdevices, such as circuit breakers, disconnectors and earthing switches can be requiredfrom the same bay or from several other bays. When information is needed from otherbays, it is exchanged over the station bus between the distributed IEDs. The problemthat arises, even at a high speed of communication, is a space of time during which theinformation about the position of the switching devices are uncertain. Theinterlocking function uses this information for evaluation, which means that also theinterlocking conditions are uncertain.

To ensure that the interlocking information is correct at the time of operation, a uniquereservation method is available in the IEDs. With this reservation method, the bay thatwants the reservation sends a reservation request to other bays and then waits for areservation granted signal from the other bays. Actual position indications from these

Section 12 1MRK 506 375-UEN -Control

244 Railway application RER670 2.2 IECApplication manual

Page 251: Railway application RER670 Version 2.2 IEC ... - ABB

bays are then transferred over the station bus for evaluation in the IED. After theevaluation the operation can be executed with high security.

This functionality is realized over the station bus by means of the function blocksQCRSV and RESIN. The application principle is shown in Figure 78.

The function block QCRSV handles the reservation. It sends out either the reservationrequest to other bays or the acknowledgement if the bay has received a request fromanother bay.

The other function block RESIN receives the reservation information from other bays.The number of instances is the same as the number of involved bays (up to 60instances are available). The received signals are either the request for reservationfrom another bay or the acknowledgment from each bay respectively, which havereceived a request from this bay. Also the information of valid transmission over thestation bus must be received.

en05000117.vsd

IEDIED

From otherSCSWI inthe bay To other

SCSWIin thebay

3

Station bus

. . .

. . .

. . .

3

RESIN

EXCH_OUTEXCH_IN

RESIN

EXCH_OUTEXCH_IN

..

SCSWI

RES_RQRES_GRT

RES_DATA

QCRSV

RES_RQ1

RES_RQ8

RES_GRT1

RES_GRT8

..

2

IEC05000117 V2 EN

Figure 78: Application principles for reservation over the station bus

The reservation can also be realized with external wiring according to the applicationexample in Figure 79. This solution is realized with external auxiliary relays and extrabinary inputs and outputs in each IED, but without use of function blocks QCRSV andRESIN.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 245Application manual

Page 252: Railway application RER670 Version 2.2 IEC ... - ABB

SCSWI

SELECTEDRES_EXT

+

IED

BI BO

IED

BI BO

OROther SCSWI in the bay

en05000118.vsd

IEC05000118 V2 EN

Figure 79: Application principles for reservation with external wiring

The solution in Figure 79 can also be realized over the station bus according to theapplication example in Figure 80. The solutions in Figure 79 and Figure 80 do not havethe same high security compared to the solution in Figure 78, but instead have a higheravailability, since no acknowledgment is required.

SCSWI

SELECTED

RES_EXT

IEDIED

OROther SCWI inthe bay

Station bus. . .

SPGAPCIN

RESGRANT

IntlReceive

. . .

. . .

RESGRANT

IntlReceive

IEC05000178-3-en.vsd

IEC05000178 V3 EN

Figure 80: Application principle for an alternative reservation solution

12.3.2 Interaction between modules

A typical bay with apparatus control function consists of a combination of logicalnodes or functions that are described here:

Section 12 1MRK 506 375-UEN -Control

246 Railway application RER670 2.2 IECApplication manual

Page 253: Railway application RER670 Version 2.2 IEC ... - ABB

• The Switch controller (SCSWI) initializes all operations for one apparatus. It isthe command interface of the apparatus. It includes the position reporting as wellas the control of the position

• The Circuit breaker (SXCBR) is the process interface to the circuit breaker for theapparatus control function.

• The Circuit switch (SXSWI) is the process interface to the disconnector or theearthing switch for the apparatus control function.

• The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,such as operator place selection and blockings for the complete bay.

• The Reservation (QCRSV) deals with the reservation function.• The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or more

protection functions to a common "trip" to be transmitted to SXCBR.• The Autorecloser (SMBRREC) consists of the facilities to automatically close a

tripped breaker with respect to a number of configurable conditions.• The logical node Interlocking (SCILO) provides the information to SCSWI

whether it is permitted to operate due to the switchyard topology. Theinterlocking conditions are evaluated with separate logic and connected toSCILO .

• The Synchrocheck, energizing check, and synchronizing (SESRSYN) calculatesand compares the voltage phasor difference from both sides of an open breakerwith predefined switching conditions (synchrocheck). Also the case that one sideis dead (energizing-check) is included.

• The Generic Automatic Process Control function, GAPC, handles genericcommands from the operator to the system.

The overview of the interaction between these functions is shown in Figure 81 below.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 247Application manual

Page 254: Railway application RER670 Version 2.2 IEC ... - ABB

SXCBR

(Circuit breaker)

Interlocking

functionblock

(Not a LN)

SCSWI

(Switching control)

QCBAY

(Bay control)

SMBRREC

(Auto-

reclosure)I/O

Trip

Close rel.

Res. req.

Sta

rt A

R

Close CB

Position

Res. granted

Operator placeselection

SCSWI

(Switching control)

SXSWI

(Disconnector)

Open cmd

Close cmd

Position

SESRSYN

(Synchrocheck & Synchronizer)

SCILO

(Interlocking)

QCRSV

(Reservation) Res. req.

Res.

grantedGAPC

(Generic

Automatic

Process

Control) Open/Close

Open/Close

Enable

close

Enable

open

Open rel.

Close rel.

Open rel.

SMPPTRC

(Trip logic)

Position

Po

s. fr

om

oth

er

ba

ys

I/O

Open cmd

Close cmd

Synchronizing OK

Syn

ch

roch

eck

OK

Sta

rt

Syn

ch

ron

izin

g

Syn

ch

ron

izin

g

in p

rog

ress

SCILO

(Interlocking)

En

ab

leo

pe

n

En

ab

leclo

se

IEC05000120-3-EN.vsdx

IEC05000120 V3 EN

Figure 81: Example overview of the interactions between functions in a typicalbay

12.3.3 Setting guidelines

The setting parameters for the apparatus control function are set via the local HMI orPCM600.

Section 12 1MRK 506 375-UEN -Control

248 Railway application RER670 2.2 IECApplication manual

Page 255: Railway application RER670 Version 2.2 IEC ... - ABB

12.3.3.1 Bay control (QCBAY)

If the parameter AllPSTOValid is set to No priority, all originators from local andremote are accepted without any priority.

If the parameter RemoteIncStation is set to Yes, commands from IEC 61850-8-1clients at both station and remote level are accepted, when the QCBAY function is inRemote. If set to No, the command LocSta controls which operator place is acceptedwhen QCBAY is in Remote. If LocSta is true, only commands from station level areaccepted, otherwise only commands from remote level are accepted.

The parameter RemoteIncStation has only effect on the IEC61850-8-1 communication. Further, when using IEC 61850 edition 1communication, the parameter should be set to Yes, since thecommand LocSta is not defined in IEC 61850-8-1 edition 1.

12.3.3.2 Switch controller (SCSWI)

The parameter CtlModel specifies the type of control model according to IEC 61850.The default for control of circuit breakers, disconnectors and earthing switches thecontrol model is set to SBO Enh (Select-Before-Operate) with enhanced security.

When the operation shall be performed in one step, and no monitoring of the result ofthe command is desired, the model direct control with normal security is used.

At control with enhanced security there is an additional supervision of the status valueby the control object, which means that each command sequence must be terminatedby a termination command.

The parameter PosDependent gives permission to operate depending on the positionindication, that is, at Always permitted it is always permitted to operate independentof the value of the position. At Not perm at 00/11 it is not permitted to operate if theposition is in bad or intermediate state.

tSelect is the maximum allowed time between the select and the execute commandsignal, that is, the time the operator has to perform the command execution after theselection of the object to operate. When the time has expired, the selected output signalis set to false and a cause-code is given.

The time parameter tResResponse is the allowed time from reservation request to thefeedback reservation granted from all bays involved in the reservation function. Whenthe time has expired, the control function is reset, and a cause-code is given.

tSynchrocheck is the allowed time for the synchrocheck function to fulfill the closeconditions. When the time has expired, the function tries to start the synchronizingfunction. If tSynchrocheck is set to 0, no synchrocheck is done, before starting thesynchronizing function.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 249Application manual

Page 256: Railway application RER670 Version 2.2 IEC ... - ABB

The timer tSynchronizing supervises that the signal synchronizing in progress isobtained in SCSWI after start of the synchronizing function. The start signal for thesynchronizing is set if the synchrocheck conditions are not fulfilled. When the timehas expired, the control function is reset, and a cause-code is given. If nosynchronizing function is included, the time is set to 0, which means no start of thesynchronizing function is done, and when tSynchrocheck has expired, the controlfunction is reset and a cause-code is given.

tExecutionFB is the maximum time between the execute command signal and thecommand termination. When the time has expired, the control function is reset and acause-code is given.

tPoleDiscord is the allowed time to have discrepancy between the poles at control ofthree one-phase breakers. At discrepancy an output signal is activated to be used fortrip or alarm, and during a command, the control function is reset, and a cause-code isgiven.

SuppressMidPos when On suppresses the mid-position during the time tIntermediateof the connected switches.

The parameter InterlockCheck decides if interlock check should be done at both selectand operate, Sel & Op phase, or only at operate, Op phase.

12.3.3.3 Switch (SXCBR/SXSWI)

tStartMove is the supervision time for the apparatus to start moving after a commandexecution is done from the SCSWI function. When the time has expired, the commandsupervision is reset, and a cause-code is given.

During the tIntermediate time, the position indication is allowed to be in anintermediate (00) state. When the time has expired, the command supervision is reset,and a cause-code is given. The indication of the mid-position at SCSWI is suppressedduring this time period when the position changes from open to close or vice-versa ifthe parameter SuppressMidPos is set to On in the SCSWI function.

If the parameter AdaptivePulse is set to Adaptive the command output pulse resetswhen a new correct end position is reached. If the parameter is set to Not adaptive thecommand output pulse remains active until the timer tOpenPulsetClosePulse haselapsed.

tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set toAdaptive, it is the maximum length of the output pulse for an open command. Thedefault length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for adisconnector (SXSWI).

tClosePulse is the output pulse length for a close command. If AdaptivePulse is set toAdaptive, it is the maximum length of the output pulse for an open command. Thedefault length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for adisconnector (SXSWI).

Section 12 1MRK 506 375-UEN -Control

250 Railway application RER670 2.2 IECApplication manual

Page 257: Railway application RER670 Version 2.2 IEC ... - ABB

12.3.3.4 Proxy for signals from switching device via GOOSE XLNPROXY

The SwitchType setting controls the evaluation of the operating capability. IfSwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breakeroperating capability, otherwise it is interpreted as a switch operating capability.

Table 28: Operating capability values for breaker/switches

Value Breaker operating capability, CbOpCap Switch operating capability, SwOpCap1 None None

2 Open Open

3 Close – Open Close

4 Open – Close – Open Close and Open

5 Close – Open – Close – Open Larger values handled as 4, both Close andOpen

6 Open – Close – Open – Close – Open

7 more

tStartMove is the supervision time for the apparatus to start moving after a commandexecution is done from the SCSWI function. When the time has expired, the commandsupervision is reset, and a cause-code is given.

During the tIntermediate time, the position indication is allowed to be in anintermediate (00) state. When the time has expired, the command supervision is reset,and a cause-code is given. The indication of the mid-position at SCSWI is suppressedduring this time period when the position changes from open to close or vice-versa ifthe parameter SuppressMidPos is set to On in the SCSWI function.

In most cases, the same value can be used for both tStartMove and tIntermediate as inthe source function. However, tStartMove may need to be increased to accommodatefor the communication delays, mainly when representing a circuit breaker.

12.3.3.5 Bay Reserve (QCRSV)

The timer tCancelRes defines the supervision time for canceling the reservation, whenthis cannot be done by requesting bay due to for example communication failure.

When the parameter ParamRequestx (x=1-8) is set to Only own bay res. individuallyfor each apparatus (x) in the bay, only the own bay is reserved, that is, the output forreservation request of other bays (RES_BAYS) will not be activated at selection ofapparatus x.

12.3.3.6 Reservation input (RESIN)

With the FutureUse parameter set to Bay future use the function can handle bays notyet installed in the SA system.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 251Application manual

Page 258: Railway application RER670 Version 2.2 IEC ... - ABB

12.4 Interlocking

The main purpose of switchgear interlocking is:

• To avoid the dangerous or damaging operation of switchgear• To enforce restrictions on the operation of the substation for other reasons for

example, load configuration. Examples of the latter are to limit the number ofparallel transformers to a maximum of two or to ensure that energizing is alwaysfrom one side, for example, the high voltage side of a transformer.

This section only deals with the first point, and only with restrictions caused byswitching devices other than the one to be controlled. This means that switchinterlock, because of device alarms, is not included in this section.

Disconnectors and earthing switches have a limited switching capacity.Disconnectors may therefore only operate:

• With basically zero current. The circuit is open on one side and has a smallextension. The capacitive current is small (for example, < 5A) and powertransformers with inrush current are not allowed.

• To connect or disconnect a parallel circuit carrying load current. The switchingvoltage across the open contacts is thus virtually zero, thanks to the parallel circuit(for example, < 1% of rated voltage). Paralleling of power transformers is notallowed.

Earthing switches are allowed to connect and disconnect earthing of isolated points.Due to capacitive or inductive coupling there may be some voltage (for example <40% of rated voltage) before earthing and some current (for example < 100A) afterearthing of a line.

Circuit breakers are usually not interlocked. Closing is only interlocked againstrunning disconnectors in the same bay, and the bus-coupler opening is interlockedduring a busbar transfer.

The positions of all switching devices in a bay and from some other bays determine theconditions for operational interlocking. Conditions from other stations are usually notavailable. Therefore, a line earthing switch is usually not fully interlocked. Theoperator must be convinced that the line is not energized from the other side beforeclosing the earthing switch. As an option, a voltage indication can be used forinterlocking. Take care to avoid a dangerous enable condition at the loss of a VTsecondary voltage, for example, because of a blown fuse.

The switch positions used by the operational interlocking logic are obtained fromauxiliary contacts or position sensors. For each end position (open or closed) a trueindication is needed - thus forming a double indication. The apparatus control functioncontinuously checks its consistency. If neither condition is high (1 or TRUE), theswitch may be in an intermediate position, for example, moving. This dynamic statemay continue for some time, which in the case of disconnectors may be up to 10

Section 12 1MRK 506 375-UEN -Control

252 Railway application RER670 2.2 IECApplication manual

Page 259: Railway application RER670 Version 2.2 IEC ... - ABB

seconds. Should both indications stay low for a longer period, the position indicationwill be interpreted as unknown. If both indications stay high, something is wrong, andthe state is again treated as unknown.

In both cases an alarm is sent to the operator. Indications from position sensors shallbe self-checked and system faults indicated by a fault signal. In the interlocking logic,the signals are used to avoid dangerous enable or release conditions. When theswitching state of a switching device cannot be determined operation is not permitted.

For switches with an individual operation gear per phase, the evaluation must considerpossible phase discrepancies. This is done with the aid of an AND-function for bothtwo phases in each apparatus for both open and close indications. Phase discrepancieswill result in an unknown double indication state.

12.4.1 Configuration guidelines

The following sections describe how the interlocking for a certain switchgearconfiguration can be realized in the IED by using standard interlocking modules andtheir interconnections. They also describe the configuration settings. The inputs fordelivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, exceptin the following cases:

• QB9_EX2 and QB9_EX4 in modules BH_LINE_A and BH_LINE_B• QA1_EX3 in module AB_TRAFO

when they are set to 0=FALSE.

12.4.2 Interlocking for line bay ABC_LINE

12.4.2.1 Application

The interlocking for line bay (ABC_LINE) function is used for a line connected to adouble busbar arrangement with a transfer busbar according to figure 82. The functioncan also be used for a double busbar arrangement without transfer busbar or a singlebusbar arrangement with/without transfer busbar.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 253Application manual

Page 260: Railway application RER670 Version 2.2 IEC ... - ABB

QB1 QB2QC1

QA1

QC2

QB9QC9

WA1 (A)

WA2 (B)

WA7 (C)

QB7

en04000478.vsdIEC04000478 V1 EN

Figure 82: Switchyard layout ABC_LINE

The signals from other bays connected to the module ABC_LINE are describedbelow.

12.4.2.2 Signals from bypass busbar

To derive the signals:

Signal BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.

VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.

EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7

These signals from each line bay (ABC_LINE) except that of the own bay are needed:

Signal QB7OPTR Q7 is open

VPQB7TR The switch status for QB7 is valid.

EXDU_BPB No transmission error from the bay that contains the above information.

For bay n, these conditions are valid:

Section 12 1MRK 506 375-UEN -Control

254 Railway application RER670 2.2 IECApplication manual

Page 261: Railway application RER670 Version 2.2 IEC ... - ABB

QB7OPTR (bay 1)QB7OPTR (bay 2)

. . .

. . .QB7OPTR (bay n-1)

& BB7_D_OP

VPQB7TR (bay 1)VPQB7TR (bay 2)

. . .

. . .VPQB7TR (bay n-1)

& VP_BB7_D

EXDU_BPB (bay 1)EXDU_BPB (bay 2)

. . .

. . .EXDU_BPB (bay n-1)

& EXDU_BPB

en04000477.vsd

IEC04000477 V1 EN

Figure 83: Signals from bypass busbar in line bay n

12.4.2.3 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus section.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINE ABC_BCABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000479.vsd

IEC04000479 V1 EN

Figure 84: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

BC_17_OP No bus-coupler connection between busbar WA1 and WA7.

BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.

BC_27_OP No bus-coupler connection between busbar WA2 and WA7.

BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.

VP_BC_12 The switch status of BC_12 is valid.

VP_BC_17 The switch status of BC_17 is valid.

VP_BC_27 The switch status of BC_27 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 255Application manual

Page 262: Railway application RER670 Version 2.2 IEC ... - ABB

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA7.

BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA7.

BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 andWA7.

BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2and WA7.

VPBC12TR The switch status of BC_12 is valid.

VPBC17TR The switch status of BC_17 is valid.

VPBC27TR The switch status of BC_27 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a line bay in section 1, these conditions are valid:

Section 12 1MRK 506 375-UEN -Control

256 Railway application RER670 2.2 IECApplication manual

Page 263: Railway application RER670 Version 2.2 IEC ... - ABB

BC12CLTR (sect.1)

DCCLTR (A1A2)DCCLTR (B1B2)

>1&

BC12CLTR (sect.2)

&VPBC12TR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

>1&

BC17OPTR (sect.1)

DCOPTR (A1A2)BC17OPTR (sect.2)

>1&

BC17CLTR (sect.1)

DCCLTR (A1A2)BC17CLTR (sect.2)

&VPBC17TR (sect.1)

VPDCTR (A1A2)VPBC17TR (sect.2)

>1&

>1&

&

&

BC27OPTR (sect.1)

DCOPTR (B1B2)BC27OPTR (sect.2)

BC27CLTR (sect.1)

DCCLTR (B1B2)BC27CLTR (sect.2)

VPBC27TR (sect.1)VPDCTR (B1B2)

VPBC27TR (sect.2)

EXDU_BC (sect.1)EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

BC_12_CL

VP_BC_12

BC_17_OP

BC_17_CL

VP_BC_17

BC_27_OP

BC_27_CL

VP_BC_27

EXDU_BC

en04000480.vsd

IEC04000480 V1 EN

Figure 85: Signals to a line bay in section 1 from the bus-coupler bays in eachsection

For a line bay in section 2, the same conditions as above are valid by changing section1 to section 2 and vice versa.

12.4.2.4 Configuration setting

If there is no bypass busbar and therefore no QB7 disconnector, then the interlockingfor QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to open

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 257Application manual

Page 264: Railway application RER670 Version 2.2 IEC ... - ABB

by setting the appropriate module inputs as follows. In the functional block diagram,0 and 1 are designated 0=FALSE and 1=TRUE:

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

• BB7_D_OP = 1

• BC_17_OP = 1• BC_17_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• EXDU_BPB = 1

• VP_BB7_D = 1• VP_BC_17 = 1• VP_BC_27 = 1

If there is no second busbar WA2 and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• VP_BC_12 = 1

12.4.3 Interlocking for bus-coupler bay ABC_BC

Section 12 1MRK 506 375-UEN -Control

258 Railway application RER670 2.2 IECApplication manual

Page 265: Railway application RER670 Version 2.2 IEC ... - ABB

12.4.3.1 Application

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-couplerbay connected to a double busbar arrangement according to figure 86. The functioncan also be used for a single busbar arrangement with transfer busbar or double busbararrangement without transfer busbar.

QB1 QB2

QC1

QA1

WA1 (A)

WA2 (B)

WA7 (C)

QB7QB20

QC2

en04000514.vsdIEC04000514 V1 EN

Figure 86: Switchyard layout ABC_BC

12.4.3.2 Configuration

The signals from the other bays connected to the bus-coupler module ABC_BC aredescribed below.

12.4.3.3 Signals from all feeders

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-coupler.

VP_BBTR The switch status is valid for all apparatuses involved in the busbar transfer.

EXDU_12 No transmission error from any bay connected to the WA1/WA2 busbars.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:

Signal QQB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 259Application manual

Page 266: Railway application RER670 Version 2.2 IEC ... - ABB

For bus-coupler bay n, these conditions are valid:

QB12OPTR (bay 1)QB12OPTR (bay 2)

. . .

. . .QB12OPTR (bay n-1)

& BBTR_OP

VPQB12TR (bay 1)VPQB12TR (bay 2)

. . .

. . .VPQB12TR (bay n-1)

& VP_BBTR

EXDU_12 (bay 1)EXDU_12 (bay 2)

. . .

. . .EXDU_12 (bay n-1)

& EXDU_12

en04000481.vsd

IEC04000481 V1 EN

Figure 87: Signals from any bays in bus-coupler bay n

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBBTR are connected in parallel - if both bus-section disconnectors are closed. So forthe basic project-specific logic for BBTR above, add this logic:

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000482.vsd

AB_TRAFO

IEC04000482 V1 EN

Figure 88: Busbars divided by bus-section disconnectors (circuit breakers)

The following signals from each bus-section disconnector bay (A1A2_DC) areneeded. For B1B2_DC, corresponding signals from busbar B are used. The same typeof module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay

Section 12 1MRK 506 375-UEN -Control

260 Railway application RER670 2.2 IECApplication manual

Page 267: Railway application RER670 Version 2.2 IEC ... - ABB

(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-coupler bay in section 1, these conditions are valid:

BBTR_OP (sect.1)

DCOPTR (A1A2)DCOPTR (B1B2)

BBTR_OP (sect.2)

&VP_BBTR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VP_BBTR (sect.2)

EXDU_12 (sect.1)

EXDU_DC (B1B2)EXDU_12 (sect.2)

VP_BBTR

EXDU_12

en04000483.vsd

&EXDU_DC (A1A2)

BBTR_OP

>1&

IEC04000483 V1 EN

Figure 89: Signals to a bus-coupler bay in section 1 from any bays in eachsection

For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

12.4.3.4 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBC_12 from the busbar coupler of the other busbar section must be transmitted to theown busbar coupler if both disconnectors are closed.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_BCABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000484.vsd

IEC04000484 V1 EN

Figure 90: Busbars divided by bus-section disconnectors (circuit breakers)

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 261Application manual

Page 268: Railway application RER670 Version 2.2 IEC ... - ABB

To derive the signals:

Signal BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal S1S2CLTR A bus-section coupler connection exists between bus sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay containing the above information.

For a bus-coupler bay in section 1, these conditions are valid:

Section 12 1MRK 506 375-UEN -Control

262 Railway application RER670 2.2 IECApplication manual

Page 269: Railway application RER670 Version 2.2 IEC ... - ABB

DCCLTR (A1A2)DCCLTR (B1B2)

BC12CLTR (sect.2)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

& BC_12_CL

VP_BC_12

EXDU_BC

en04000485.vsd

&

&

IEC04000485 V1 EN

Figure 91: Signals to a bus-coupler bay in section 1 from a bus-coupler bay inanother section

For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

12.4.3.5 Configuration setting

If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then theinterlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then theinterlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,BC_12, BBTR are set to open by setting the appropriate module inputs as follows. Inthe functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB20_OP = 1• QB20_CL = 0

• QC21_OP = 1• QC21_CL = 0

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 263Application manual

Page 270: Railway application RER670 Version 2.2 IEC ... - ABB

• BC_12_CL = 0• VP_BC_12 = 1

• BBTR_OP = 1• VP_BBTR = 1

12.4.4 Interlocking for transformer bay AB_TRAFO

12.4.4.1 Application

The interlocking for transformer bay (AB_TRAFO) function is used for a transformerbay connected to a double busbar arrangement according to figure 92. The function isused when there is no disconnector between circuit breaker and transformer.Otherwise, the interlocking for line bay (ABC_LINE) function can be used. Thisfunction can also be used in single busbar arrangements.

QB1 QB2QC1

QA1

QC2

WA1 (A)

WA2 (B)

QA2

QC3

T

QC4

QB4QB3

QA2 and QC4 are notused in this interlocking

AB_TRAFO

en04000515.vsdIEC04000515 V1 EN

Figure 92: Switchyard layout AB_TRAFO

The signals from other bays connected to the module AB_TRAFO are describedbelow.

Section 12 1MRK 506 375-UEN -Control

264 Railway application RER670 2.2 IECApplication manual

Page 271: Railway application RER670 Version 2.2 IEC ... - ABB

12.4.4.2 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus-section.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_BCAB_TRAFO ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000487.vsd

IEC04000487 V1 EN

Figure 93: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic for input signals concerning bus-coupler are the same as thespecific logic for the line bay (ABC_LINE):

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from bus-coupler bay (BC).

The logic is identical to the double busbar configuration “Signals from bus-coupler“.

12.4.4.3 Configuration setting

If there are no second busbar B and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to open bysetting the appropriate module inputs as follows. In the functional block diagram, 0and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

If there is no second busbar B at the other side of the transformer and therefore no QB4disconnector, then the state for QB4 is set to open by setting the appropriate moduleinputs as follows:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 265Application manual

Page 272: Railway application RER670 Version 2.2 IEC ... - ABB

• QB4_OP = 1• QB4_CL = 0

12.4.5 Interlocking for bus-section breaker A1A2_BS

12.4.5.1 Application

The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit breaker between section 1 and 2 according to figure 94. The functioncan be used for different busbars, which includes a bus-section circuit breaker.

QA1

WA1 (A1)

QB2

QC4

QB1

QC3

WA2 (A2)

en04000516.vsd

QC2QC1

A1A2_BS

IEC04000516 V1 EN

Figure 94: Switchyard layout A1A2_BS

The signals from other bays connected to the module A1A2_BS are described below.

12.4.5.2 Signals from all feeders

If the busbar is divided by bus-section circuit breakers into bus-sections and bothcircuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists between busbars on one bus-section side and if on the otherbus-section side a busbar transfer is in progress:

Section 1 Section 2

A1A2_BSB1B2_BS

ABC_LINEABC_BC

ABC_LINEABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000489.vsd

AB_TRAFOAB_TRAFO

IEC04000489 V1 EN

Figure 95: Busbars divided by bus-section circuit breakers

Section 12 1MRK 506 375-UEN -Control

266 Railway application RER670 2.2 IECApplication manual

Page 273: Railway application RER670 Version 2.2 IEC ... - ABB

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-section.

VP_BBTR The switch status of BBTR is valid.

EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC) are needed:

Signal QB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and

WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) areneeded.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-section circuit breaker between A1 and A2 section busbars, these conditionsare valid:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 267Application manual

Page 274: Railway application RER670 Version 2.2 IEC ... - ABB

S1S2OPTR (B1B2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (B1B2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000490.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (B1B2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12 (bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12(bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (B1B2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000490 V1 EN

Figure 96: Signals from any bays for a bus-section circuit breaker betweensections A1 and A2

For a bus-section circuit breaker between B1 and B2 section busbars, these conditionsare valid:

Section 12 1MRK 506 375-UEN -Control

268 Railway application RER670 2.2 IECApplication manual

Page 275: Railway application RER670 Version 2.2 IEC ... - ABB

S1S2OPTR (A1A2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (A1A2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000491.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (A1A2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12(bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12 (bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (A1A2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000491 V1 EN

Figure 97: Signals from any bays for a bus-section circuit breaker betweensections B1 and B2

12.4.5.3 Configuration setting

If there is no other busbar via the busbar loops that are possible, then either theinterlocking for the QA1 open circuit breaker is not used or the state for BBTR is setto open. That is, no busbar transfer is in progress in this bus-section:

• BBTR_OP = 1• VP_BBTR = 1

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 269Application manual

Page 276: Railway application RER670 Version 2.2 IEC ... - ABB

12.4.6 Interlocking for bus-section disconnector A1A2_DC

12.4.6.1 Application

The interlocking for bus-section disconnector (A1A2_DC) function is used for onebus-section disconnector between section 1 and 2 according to figure 98. A1A2_DCfunction can be used for different busbars, which includes a bus-section disconnector.

WA1 (A1) WA2 (A2)

QB

QC1 QC2

A1A2_DC en04000492.vsd

IEC04000492 V1 EN

Figure 98: Switchyard layout A1A2_DC

The signals from other bays connected to the module A1A2_DC are described below.

12.4.6.2 Signals in single breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition no otherdisconnector connected to the bus-section must be made by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B3A3

en04000493.vsd

AB_TRAFOAB_TRAFO

A2B2

IEC04000493 V1 EN

Figure 99: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Section 12 1MRK 506 375-UEN -Control

270 Railway application RER670 2.2 IECApplication manual

Page 277: Railway application RER670 Version 2.2 IEC ... - ABB

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE).

QB220OTR QB2 and QB20 are open (ABC_BC).

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2 and QB20 are valid.

EXDU_BB No transmission error from the bay that contains the above information.

If there is an additional bus-section disconnector, the signal from the bus-sectiondisconnector bay (A1A2_DC) must be used:

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If there is an additional bus-section circuit breaker rather than an additional bus-section disconnector the signals from the bus-section, circuit-breaker bay (A1A2_BS)rather than the bus-section disconnector bay (A1A2_DC) must be used:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 271Application manual

Page 278: Railway application RER670 Version 2.2 IEC ... - ABB

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000494.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_BB (bay 1/sect.A1)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000494 V1 EN

Figure 100: Signals from any bays in section A1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000495.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A2/A3)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A2/A3)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A2/A3)IEC04000495 V1 EN

Figure 101: Signals from any bays in section A2 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

Section 12 1MRK 506 375-UEN -Control

272 Railway application RER670 2.2 IECApplication manual

Page 279: Railway application RER670 Version 2.2 IEC ... - ABB

QB2OPTR (QB220OTR)(bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000496.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (VQB220TR)(bay 1/sect.B1)

VPQB2TR (VQB220TR)(bay n/sect.B1)

EXDU_BB (bay 1/sect.B1)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

IEC04000496 V1 EN

Figure 102: Signals from any bays in section B1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (QB220OTR)(bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000497.vsd

QB2OPTR (QB220OTR)(bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B2/B3)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B2/B3)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B2/B3)IEC04000497 V1 EN

Figure 103: Signals from any bays in section B2 to a bus-section disconnector

12.4.6.3 Signals in double-breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 273Application manual

Page 280: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

DB_BUS DB_BUSDB_BUS DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000498.vsd

IEC04000498 V1 EN

Figure 104: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from double-breaker bay (DB) that contains the aboveinformation.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration “Signals in single breakerarrangement”.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

Section 12 1MRK 506 375-UEN -Control

274 Railway application RER670 2.2 IECApplication manual

Page 281: Railway application RER670 Version 2.2 IEC ... - ABB

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000499.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_DB (bay 1/sect.A1)

EXDU_DB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000499 V1 EN

Figure 105: Signals from double-breaker bays in section A1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000500.vsd

&

&

&

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)

EXDU_DB (bay 1/sect.A2)

EXDU_DB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000500 V1 EN

Figure 106: Signals from double-breaker bays in section A2 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 275Application manual

Page 282: Railway application RER670 Version 2.2 IEC ... - ABB

QB2OPTR (bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000501.vsd

&

&

&

QB2OPTR (bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B1)

VPQB2TR (bay n/sect.B1)

EXDU_DB (bay 1/sect.B1)

EXDU_DB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000501 V1 EN

Figure 107: Signals from double-breaker bays in section B1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000502.vsd

&

&

&

QB2OPTR (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B2)

VPQB2TR (bay n/sect.B2)

EXDU_DB (bay 1/sect.B2)

EXDU_DB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000502 V1 EN

Figure 108: Signals from double-breaker bays in section B2 to a bus-sectiondisconnector

12.4.6.4 Signals in 1 1/2 breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 12 1MRK 506 375-UEN -Control

276 Railway application RER670 2.2 IECApplication manual

Page 283: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000503.vsd

BH_LINE BH_LINE BH_LINE

IEC04000503 V1 EN

Figure 109: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic is the same as for the logic for the double-breakerconfiguration.

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from breaker and a half (BH) that contains the aboveinformation.

12.4.7 Interlocking for busbar earthing switch BB_ES

12.4.7.1 Application

The interlocking for busbar earthing switch (BB_ES) function is used for one busbarearthing switch on any busbar parts according to figure 110.

QC

en04000504.vsd

IEC04000504 V1 EN

Figure 110: Switchyard layout BB_ES

The signals from other bays connected to the module BB_ES are described below.

12.4.7.2 Signals in single breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 277Application manual

Page 284: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_LINEBB_ES

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000505.vsd

BB_ESABC_BC

IEC04000505 V1 EN

Figure 111: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnector on this part of the busbar is valid.

EXDU_BB No transmission error from any bay containing the above information.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)

QB220OTR QB2 and QB20 are open (ABC_BC)

QB7OPTR QB7 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2and QB20 is valid.

VPQB7TR The switch status of QB7 is valid.

EXDU_BB No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DCare set to 1 (TRUE).

Section 12 1MRK 506 375-UEN -Control

278 Railway application RER670 2.2 IECApplication manual

Page 285: Railway application RER670 Version 2.2 IEC ... - ABB

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS) rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a busbar earthing switch, these conditions from the A1 busbar section are valid:

QB1OPTR (bay 1/sect.A1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000506.vsd

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A1)

EXDU_DC (A1/A2)

IEC04000506 V1 EN

Figure 112: Signals from any bays in section A1 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the A2 busbar section are valid:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 279Application manual

Page 286: Railway application RER670 Version 2.2 IEC ... - ABB

QB1OPTR (bay 1/sect.A2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000507.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A1/A2)

IEC04000507 V1 EN

Figure 113: Signals from any bays in section A2 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the B1 busbar section are valid:

QB2OPTR(QB220OTR)(bay 1/sect.B1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000508.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B1)

VPQB2TR(VQB220TR) (bay n/sect.B1)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B1)

EXDU_DC (B1/B2)

IEC04000508 V1 EN

Figure 114: Signals from any bays in section B1 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the B2 busbar section are valid:

Section 12 1MRK 506 375-UEN -Control

280 Railway application RER670 2.2 IECApplication manual

Page 287: Railway application RER670 Version 2.2 IEC ... - ABB

QB2OPTR(QB220OTR) (bay 1/sect.B2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000509.vsd

QB2OPTR(QB220OTR) (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B1/B2)

IEC04000509 V1 EN

Figure 115: Signals from any bays in section B2 to a busbar earthing switch in thesame section

For a busbar earthing switch on bypass busbar C, these conditions are valid:

QB7OPTR (bay 1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000510.vsd

&

&

&

QB7OPTR (bay n)

. . .

. . .

. . .

VPQB7TR (bay 1)

VPQB7TR (bay n)

EXDU_BB (bay 1)

EXDU_BB (bay n)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000510 V1 EN

Figure 116: Signals from bypass busbar to busbar earthing switch

12.4.7.3 Signals in double-breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bussection are open.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 281Application manual

Page 288: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000511.vsd

DB_BUS

IEC04000511 V1 EN

Figure 117: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal BB_DC_OP All disconnectors of this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar are valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration described in section “Signalsin single breaker arrangement”.

12.4.7.4 Signals in 1 1/2 breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

Section 12 1MRK 506 375-UEN -Control

282 Railway application RER670 2.2 IECApplication manual

Page 289: Railway application RER670 Version 2.2 IEC ... - ABB

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000512.vsdBH_LINE

IEC04000512 V1 EN

Figure 118: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic are the same as for the logic for the double busbarconfiguration described in section “Signals in single breaker arrangement”.

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.

EXDU_BB No transmission error from any bay that contains the above information.

12.4.8 Interlocking for double CB bay DB

12.4.8.1 Application

The interlocking for a double busbar double circuit breaker bay includingDB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to adouble busbar arrangement according to figure 119.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 283Application manual

Page 290: Railway application RER670 Version 2.2 IEC ... - ABB

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB61

QB9

QB2QC4

QA2

QC5

QC3

QB62

DB_BUS_B

DB_LINE

DB_BUS_A

en04000518.vsdIEC04000518 V1 EN

Figure 119: Switchyard layout double circuit breaker

For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE andDB_BUS_B must be used.

12.4.8.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

Section 12 1MRK 506 375-UEN -Control

284 Railway application RER670 2.2 IECApplication manual

Page 291: Railway application RER670 Version 2.2 IEC ... - ABB

12.4.9 Interlocking for 1 1/2 CB BH

12.4.9.1 Application

The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameteraccording to figure 120.

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB6

QB9

QB2QC1

QA1

QC2

QC3

QB6

QC3

QB62QB61 QA1

QC1 QC2QC9

QB9

BH_LINE_A BH_LINE_B

BH_CONNen04000513.vsd

IEC04000513 V1 EN

Figure 120: Switchyard layout 1 1/2 breaker

Three types of interlocking modules per diameter are defined. BH_LINE_A andBH_LINE_B are the connections from a line to a busbar. BH_CONN is theconnection between the two lines of the diameter in the 1 1/2 breaker switchyardlayout.

For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN andBH_LINE_B must be used.

12.4.9.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 285Application manual

Page 292: Railway application RER670 Version 2.2 IEC ... - ABB

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

12.5 Logic rotating switch for function selection and LHMIpresentation SLGAPC

12.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic rotating switch for functionselection and LHMI presentation

SLGAPC - -

12.5.2 Application

The logic rotating switch for function selection and LHMI presentation function(SLGAPC) (or the selector switch function block, as it is also known) is used to get aselector switch functionality similar with the one provided by a hardware multi-position selector switch. Hardware selector switches are used extensively by utilities,in order to have different functions operating on pre-set values. Hardware switches arehowever sources for maintenance issues, lower system reliability and extendedpurchase portfolio. The virtual selector switches eliminate all these problems.

SLGAPC function block has two operating inputs (UP and DOWN), one blockinginput (BLOCK) and one operator position input (PSTO).

SLGAPC can be activated both from the local HMI and from external sources(switches), via the IED binary inputs. It also allows the operation from remote (like thestation computer). SWPOSN is an integer value output, giving the actual output

Section 12 1MRK 506 375-UEN -Control

286 Railway application RER670 2.2 IECApplication manual

Page 293: Railway application RER670 Version 2.2 IEC ... - ABB

number. Since the number of positions of the switch can be established by settings (seebelow), one must be careful in coordinating the settings with the configuration (if onesets the number of positions to x in settings – for example, there will be only the firstx outputs available from the block in the configuration). Also the frequency of the (UPor DOWN) pulses should be lower than the setting tPulse.

From the local HMI, the selector switch can be operated from Single-line diagram(SLD).

12.5.3 Setting guidelines

The following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGAPC) function:

Operation: Sets the operation of the function On or Off.

NrPos: Sets the number of positions in the switch (max. 32).

OutType: Steady or Pulsed.

tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).

tDelay: The delay between the UP or DOWN activation signal positive front and theoutput activation.

StopAtExtremes: Sets the behavior of the switch at the end positions – if set toDisabled, when pressing UP while on first position, the switch will jump to the lastposition; when pressing DOWN at the last position, the switch will jump to the firstposition; when set to Enabled, no jump will be allowed.

12.6 Selector mini switch VSGAPC

12.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Selector mini switch VSGAPC - 43

12.6.2 Application

Selector mini switch (VSGAPC) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGAPC can be used for both acquiring an external switch position (throughthe IPOS1 and the IPOS2 inputs) and represent it through the single line diagramsymbols (or use it in the configuration through the outputs POS1 and POS2) as well

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 287Application manual

Page 294: Railway application RER670 Version 2.2 IEC ... - ABB

as, a command function (controlled by the PSTO input), giving switching commandsthrough the CMDPOS12 and CMDPOS21 outputs.

The output POSITION is an integer output, showing the actual position as an integernumber 0 – 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.

An example where VSGAPC is configured to switch Autorecloser on–off from abutton symbol on the local HMI is shown in figure121. The I and O buttons on thelocal HMI are normally used for on–off operations of the circuit breaker.

IEC07000112-3-en.vsd

PSTO

CMDPOS12

IPOS1

NAM_POS1NAM_POS2

IPOS2

CMDPOS21OFFON

VSGAPC

SMBRRECONOFF

SETON

INTONE

INVERTERINPUT OUT

IEC07000112 V3 EN

Figure 121: Control of Autorecloser from local HMI through Selector mini switch

VSGAPC is also provided with IEC 61850 communication so it can be controlledfrom SA system as well.

12.6.3 Setting guidelines

Selector mini switch (VSGAPC) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the length ofthe pulse can be set using the tPulse parameter. Also, being accessible on the singleline diagram (SLD), this function block has two control modes (settable throughCtlModel): Dir Norm and SBO Enh.

12.7 Generic communication function for Double Pointindication DPGAPC

12.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Generic communication function forDouble Point indication

DPGAPC - -

Section 12 1MRK 506 375-UEN -Control

288 Railway application RER670 2.2 IECApplication manual

Page 295: Railway application RER670 Version 2.2 IEC ... - ABB

12.7.2 Application

Generic communication function for Double Point indication (DPGAPC) functionblock is used to send double point position indication to other systems, equipment orfunctions in the substation through IEC 61850-8-1 or other communication protocols.It is especially intended to be used in the interlocking station-wide logics. To be ableto get the signals into other systems, equipment or functions, one must use other tools,described in the Engineering manual, and define which function block in whichsystems, equipment or functions should receive this information.

More specifically, DPGAPC function reports a combined double point positionindication output POSITION, by evaluating the value and the timestamp attributes ofthe inputs OPEN and CLOSE, together with the logical input signal VALID.

When the input signal VALID is active, the values of the OPEN and CLOSE inputsdetermine the two-bit integer value of the output POSITION. The timestamp of theoutput POSITION will have the latest updated timestamp of the inputs OPEN andCLOSE.

When the input signal VALID is inactive, DPGAPC function forces the position tointermediated state.

When the value of the input signal VALID changes, the timestamp of the outputPOSITION will be updated as the time when DPGAPC function detects the change.

Refer to Table 29 for the description of the input-output relationship in terms of thevalue and the quality attributes.

Table 29: Description of the input-output relationship

VALID OPEN CLOSE POSITIONValue Description

0 - - 0 Intermediate

1 0 0 0 Intermediate

1 1 0 1 Open

1 0 1 2 Closed

1 1 1 3 Bad State

12.7.3 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

12.8 Single point generic control 8 signals SPC8GAPC

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 289Application manual

Page 296: Railway application RER670 Version 2.2 IEC ... - ABB

12.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Single point generic control 8 signals SPC8GAPC - -

12.8.2 Application

The Single point generic control 8 signals (SPC8GAPC) function block is a collectionof 8 single point commands that can be used for direct commands for example reset ofLED's or putting IED in "ChangeLock" state from remote. In this way, simplecommands can be sent directly to the IED outputs, without confirmation.Confirmation (status) of the result of the commands is supposed to be achieved byother means, such as binary inputs and SPGAPC function blocks.

PSTO is the universal operator place selector for all control functions.Even if PSTO can be configured to allow LOCAL or ALL operatorpositions, the only functional position usable with the SPC8GAPCfunction block is REMOTE.

12.8.3 Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GAPC) functionare set via the local HMI or PCM600.

Operation: turning the function operation On/Off.

There are two settings for every command output (totally 8):

PulseModex: decides if the command signal for output x is Latched (steady) orPulsed.

tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (inseconds).

12.9 AutomationBits, command function for DNP3.0AUTOBITS

12.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

AutomationBits, command function forDNP3 AUTOBITS - -

Section 12 1MRK 506 375-UEN -Control

290 Railway application RER670 2.2 IECApplication manual

Page 297: Railway application RER670 Version 2.2 IEC ... - ABB

12.9.2 Application

Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600in order to get into the configuration the commands coming through the DNP3.0protocol.The AUTOBITS function plays the same role as functions GOOSEBINRCV(for IEC 61850) and MULTICMDRCV (for LON).AUTOBITS function block have32 individual outputs which each can be mapped as a Binary Output point in DNP3.The output is operated by a "Object 12" in DNP3. This object contains parameters forcontrol-code, count, on-time and off-time. To operate an AUTOBITS output point,send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. Theremaining parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.

For description of the DNP3 protocol implementation, refer to the Communicationmanual.

12.9.3 Setting guidelines

AUTOBITS function block has one setting, (Operation: On/Off) enabling or disablingthe function. These names will be seen in the DNP3 communication management toolin PCM600.

12.10 Single command, 16 signals SINGLECMD

12.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Single command, 16 signals SINGLECMD - -

12.10.2 Application

Single command, 16 signals (SINGLECMD) is a common function and alwaysincluded in the IED.

The IEDs may be provided with a function to receive commands either from asubstation automation system or from the local HMI. That receiving function blockhas outputs that can be used, for example, to control high voltage apparatuses inswitchyards. For local control functions, the local HMI can also be used. Togetherwith the configuration logic circuits, the user can govern pulses or steady outputsignals for control purposes within the IED or via binary outputs.

Figure 122 shows an application example of how the user can connect SINGLECMDvia configuration logic circuit to control a high-voltage apparatus. This type of

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 291Application manual

Page 298: Railway application RER670 Version 2.2 IEC ... - ABB

command control is normally carried out by sending a pulse to the binary outputs ofthe IED. Figure 122 shows a close operation. An open breaker operation is performedin a similar way but without the synchro-check condition.

SinglecommandfunctionSINGLECMD

CMDOUTy

OUTy

Close CB1

&User-definedconditionsSynchro-check

Configuration logic circuits

en04000206.vsdIEC04000206 V2 EN

Figure 122: Application example showing a logic diagram for control of a circuitbreaker via configuration logic circuits

Figure 123 and figure 124 show other ways to control functions, which require steadyOn/Off signals. Here, the output is used to control built-in functions or externaldevices.

Section 12 1MRK 506 375-UEN -Control

292 Railway application RER670 2.2 IECApplication manual

Page 299: Railway application RER670 Version 2.2 IEC ... - ABB

SinglecommandfunctionSINGLECMD

CMDOUTy

OUTy

Function n

en04000207.vsd

Function n

IEC04000207 V2 EN

Figure 123: Application example showing a logic diagram for control of built-infunctions

Singlecommandfunction

SINGLESMD

CMDOUTy

OUTy

Device 1

User-definedconditions

Configuration logic circuits

en04000208.vsd

&

IEC04000208 V2 EN

Figure 124: Application example showing a logic diagram for control of externaldevices via configuration logic circuits

12.10.3 Setting guidelines

The parameters for Single command, 16 signals (SINGLECMD) are set via the localHMI or PCM600.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 293Application manual

Page 300: Railway application RER670 Version 2.2 IEC ... - ABB

Parameters to be set are MODE, common for the whole block, and CMDOUTy whichincludes the user defined name for each output signal. The MODE input sets theoutputs to be one of the types Off, Steady, or Pulse.

• Off, sets all outputs to 0, independent of the values sent from the station level, thatis, the operator station or remote-control gateway.

• Steady, sets the outputs to a steady signal 0 or 1, depending on the values sentfrom the station level.

• Pulse, gives a pulse with 100 ms duration, if a value sent from the station level ischanged from 0 to 1. That means the configured logic connected to the commandfunction block may not have a cycle time longer than the cycle time for thecommand function block.

12.11 Transformer energizing control XENCPOW

12.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Transformer Energizing Control XENCPOW

0->1T

IEC15000180 V1 EN

25T

12.11.2 Application

The transformer core may become saturated due to an abrupt change in the voltageapplied to it. This may be caused by:

• Switching transients• Out-of-phase synchronization of a generator• Clearing of an external fault

When saturated, a transformer absorbs a magnetization current, also known as inrushcurrent, which can reach several times the nominal current of the transformer.Energization of a transformer from the network by uncontrolled/random closing by aswitching device produces inrush currents since the flux in the core can reach amaximum theoretical value of 2 to 3 times the rated peak flux. This can haveundesirable consequences.

The flux-linkage/current relation is non-linear, as shown in Figure 125, and it isdetermined by the saturation curve of a transformer. Therefore, the magnetizationcurrent of the transformer contains harmonics.

When a transformer is energized, the initial value of the flux may differ from theprospective flux. This causes a DC offset of the flux-linkage and a higher-than-rated

Section 12 1MRK 506 375-UEN -Control

294 Railway application RER670 2.2 IECApplication manual

Page 301: Railway application RER670 Version 2.2 IEC ... - ABB

peak value. The result is an inrush current that may be several times the value of thenominal current. Due to the low relative permeability of the ferromagnetic material insaturation, a marginal increase in the peak of the flux-linkage results in amagnification of the inrush current as shown in Figure 125.

Time

Vo

ltag

e &

Flu

x

Tim

e

Current

Voltage

Flux

Current when Voltage Zero switching

Current when Voltage Peak Switching

Saturation Curve

IEC15000177.vsd

IEC15000177 V1 EN

Figure 125: Flux-linkage/current relation

The transformer energization control function (XENCPOW) is used to minimizeinrush currents by energizing the transformer near the voltage peak. Energizing thetransformer at a voltage zero crossing results in the most severe inrush current.Energizing the transformer at voltage peak results in no DC offset other than thatcaused by the initial residual flux.

12.11.3 Setting guidelines

The controlled close operation of a transformer from the XENCPOW function isbased on the voltage waveform and circuit breaker operating time. The voltagewaveform is traced using the input signal fed to the function, and the breaker operatetime is taken from the setting. Incorrect operation may occur if the tBreaker setting isset incorrectly. Hence the operation accuracy of the XENCPOW function dependsstrongly on the accuracy of the breaker operate time setting.

The parameters for the XENCPOW function are set via the local HMI or PCM600.

1MRK 506 375-UEN - Section 12Control

Railway application RER670 2.2 IEC 295Application manual

Page 302: Railway application RER670 Version 2.2 IEC ... - ABB

The common base IED values for primary current IBase and primary voltage UBaseare set in the global base values for settings function GBASVAL.

GlobalBaseSel: This setting is used to select the GBASVAL function for the referenceof base values.

Operation: On or Off.

ULowLimit: This setting is used to set the voltage range where the transformer can beenergized without looking the voltage peak once the START input is activated. Thetypical setting is 20 % of UBase.

UHighLimit: This setting is used to set the voltage range where the transformer shouldnot be energized even when the START input is activated. The typical setting is 120 %of UBase.

tBreaker: It should be set to match the total closing time of the circuit breaker and itshould also include possible auxiliary relays in the closing circuit. A typical setting is80-150 ms.

tPulse: This setting is used to set the close command pulse duration. The setting mustbe grater than the critical impulse time of the circuit breakers to be closed from thetransformer energizing control function. The typical setting is 200 ms.

12.11.3.1 Setting examples

Refer to the transformer manufacturer’s operating requirements for the UHighLimitand ULowLimit settings.

Refer to the transformer circuit breaker manufacturer’s operating requirements for thetBreaker and tPulse settings.

Section 12 1MRK 506 375-UEN -Control

296 Railway application RER670 2.2 IECApplication manual

Page 303: Railway application RER670 Version 2.2 IEC ... - ABB

Section 13 Scheme communication

13.1 Scheme communication logic for distance orovercurrent protection ZCPSCH

13.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Scheme communication logic fordistance or overcurrent protection

ZCPSCH - 85

13.1.2 Application

To achieve fast clearing of a fault on the part of the line not covered by theinstantaneous zone 1, the stepped distance protection function can be supported withlogic that uses a communication channel.

One communication channel in each direction, which can transmit an on/off signal isrequired. The performance and security of this function is directly related to thetransmission channel speed and security against false or lost signals. Communicationspeed, or minimum time delay, is always of utmost importance because the purpose ofusing communication is to improve the tripping speed of the scheme.

To avoid false signals that could cause false tripping, it is necessary to pay attentionto the security of the communication channel. At the same time it is important to payattention to the communication channel dependability to ensure that proper signals arecommunicated during power system faults, the time during which the protectionschemes must perform their tasks flawlessly.

The logic supports the following communications schemes:

• blocking scheme (blocking)• permissive schemes (overreaching and underreaching)• unblocking scheme and direct intertrip

A permissive scheme is inherently faster and has better security against false trippingthan a blocking scheme. On the other hand, a permissive scheme depend on a receivedCR signal for a fast trip, so its dependability is lower than that of a blocking scheme.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 297Application manual

Page 304: Railway application RER670 Version 2.2 IEC ... - ABB

13.1.2.1 Blocking schemes

In a blocking scheme a reverse looking zone is used to send a block signal to theremote end to block an overreaching zone.

Since the scheme is sending the blocking signal during conditions where the protectedline is healthy, it is common to use the line itself as communication media (PLC). Thescheme can be used on all line lengths.

The blocking scheme is very dependable because it will operate for faults anywhereon the protected line if the communication channel is out of service. On the other hand,it is less secure than permissive schemes because it will trip for external faults withinthe reach of the tripping function if the communication channel is out of service.

Inadequate speed or dependability can cause spurious tripping for external faults.Inadequate security can cause delayed tripping for internal faults.

To secure that the send signal will arrive before the zone used in the communicationscheme will trip, the trip is released first after the time delay tCoord has elapsed. Thesetting of tCoord must be set longer than the maximal transmission time of thechannel. A security margin of at least 10 ms should be considered.

The timer tSendMin for prolonging the send signal is proposed to set to zero.

A B

ORB

Z revA

Z revA CSA TRIPB = ORB+ tCoord+ CR IEC09000015_2_en.vsd

IEC09000015 V2 EN

Figure 126: Principle of blocking scheme

OR: Overreaching

CR: Communication signal received

CS: Communication signal send

Z revA: Reverse zone

13.1.2.2 Permissive schemes

In permissive schemes, the permission to trip is sent from the local end to the remoteend(s), when the protection at the local end has detected a fault on the protected object.

Section 13 1MRK 506 375-UEN -Scheme communication

298 Railway application RER670 2.2 IECApplication manual

Page 305: Railway application RER670 Version 2.2 IEC ... - ABB

The received signal(s) is combined with an overreaching zone and gives aninstantaneous trip if the received signal is present during the time the chosen zone hasdetected a fault.

Either end may send a permissive (or command) signal to trip to the other end(s), andthe teleprotection equipment needs to be able to receive while transmitting.

A general requirement on permissive schemes is that it shall be fast and secure.

If the sending signal(s) is issued by underreaching or overreaching zone, it is dividedinto a permissive underreach or permissive overreach scheme.

Permissive underreaching schemePermissive underreaching scheme is not suitable to use on short line length due todifficulties for distance protection measurement in general to distinguish betweeninternal and external faults in those applications.

The underreaching zones at the local and remote end(s) must overlap in reach toprevent a gap between the protection zones where faults would not be detected. If theunderreaching zone do not meet the required sensitivity due to for instance fault infeedfrom the remote end, a blocking or permissive overreaching scheme should beconsidered.

The received signal (CR) must be received when the overreaching zone is activated toachieve an instantaneous trip. In some cases, due to the fault current distribution, theoverreaching zone can operate only after the fault has been cleared at the terminalnearest to the fault. There is a certain risk that in case of a trip from an independenttripping zone, the zone issuing the send signal (CS) resets before the overreachingzone has started at the remote terminal. To assure a sufficient duration of the receivedsignal (CR), the send signal (CS) can be prolonged by a tSendMin reset timer. Therecommended setting of tSendMin is 100 ms.

Since the received communication signal is combined with the output from anoverreaching zone, there is less concern about a false signal causing an incorrect trip.Therefore set the timer tCoord to zero.

Failure of the communication channel does not affect the selectivity, but delaystripping at one end(s) for certain fault locations.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 299Application manual

Page 306: Railway application RER670 Version 2.2 IEC ... - ABB

A B

ORA

ORB

URB

CSB

URA

CSA

TRIP: UR or OR+CRIEC09000013-2-en.vsd

IEC09000013 V2 EN

Figure 127: Principle of Permissive underreaching scheme

UR: Underreaching

OR: Overreaching

CR: Communication signal received

CS: Communication signal send

Permissive overreaching schemeIn a permissive overreaching scheme there is an overreaching zone that issues the sendsignal. At the remote end the received signal together with the start of an overreachingzone will give an instantaneous trip. The scheme can be used for all line lengths.

In permissive overreaching schemes, the communication channel plays an essentialroll to obtain fast tripping at both ends. Failure of the communication channel mayaffect the selectivity and delay the tripping at one end at least, for faults anywherealong the protected circuit.

Teleprotection, operating in permissive overreaching scheme, must consider besidesthe general requirement of fast and secure operation also consider requirement on thedependability. Inadequate security can cause unwanted tripping for external faults.Inadequate speed or dependability can cause delayed tripping for internal faults oreven unwanted operations.

This scheme may use virtually any communication media that is not adverselyaffected by electrical interference from fault generated noise or by electricalphenomena, such as lightning. Communication media that uses metallic paths areparticularly subjected to this type of interference, therefore they must be properlyshielded or otherwise designed to provide an adequate communication signal duringpower system faults.

The send signal (CS) might be issued in parallel both from an overreaching zone andan underreaching, independent tripping zone. The CS signal from the overreachingzone must not be prolonged while the CS signal from zone 1 can be prolonged.

Section 13 1MRK 506 375-UEN -Scheme communication

300 Railway application RER670 2.2 IECApplication manual

Page 307: Railway application RER670 Version 2.2 IEC ... - ABB

To secure correct operations of current reversal logic in case of parallel lines the sendsignal CS shall not be prolonged. Set the tSendMin to zero in this case.

There is no need to delay the trip at receipt of the signal, so set the timer tCoord to zero.

A B

ORA

ORB

ORA CSA TRIPB = ORB+ CRB , ORB+ T2

IEC09000014-1-en.vsd

IEC09000014 V1 EN

Figure 128: Principle of Permissive overreaching scheme

OR: Overreaching

CR: Communication signal received

CS: Communication signal send

T2: Timer step 2

Unblocking schemeMetallic communication paths adversely affected by fault generated noise may not besuitable for conventional permissive schemes that rely on a signal transmitted duringa protected line fault. With power line carrier for example, the communication signalmay be attenuated by the fault, especially when the fault is close to the line end,thereby disabling the communication channel.

To overcome the lower dependability in permissive schemes, an unblocking functioncan be used. Use this function at older, less reliable, power-line carrier (PLC)communication, where the signal has to be sent through the primary fault. Theunblocking function uses a guard signal CRG, which must always be present, evenwhen no CR signal is received. The absence of the CRG signal for minimum of thesecurity time duration is considered as a CR signal. This also enables a permissivescheme to operate when the line fault blocks the signal transmission. Set the tSecurityto 35 ms.

13.1.2.3 Intertrip scheme

In some power system applications, there is a need to trip the remote end breakerimmediately from local protections. This applies for instance when transformers orreactors are connected to the system without circuit-breakers or for remote trippingfollowing operation of breaker failure protection.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 301Application manual

Page 308: Railway application RER670 Version 2.2 IEC ... - ABB

In an intertrip scheme, the send signal is initiated by an underreaching zone or from anexternal protection (transformer or reactor protection). At the remote end, the receivedsignals initiate a trip without any further protection criteria. To limit the risk for anunwanted trip due to the spurious sending of signals, the timer tCoord should be set to10-30 ms dependant on the type of communication channel.

The general requirement for teleprotection equipment operating in intertrippingapplications is that it should be very secure and very dependable, since bothinadequate security and dependability may cause unwanted operation. In someapplications the equipment shall be able to receive while transmitting, and commandsmay be transmitted over longer time period than for other teleprotection systems.

13.1.3 Setting guidelines

The parameters for the scheme communication logic function are set via the local HMIor PCM600.

Configure the zones used for the CS send and for scheme communication tripping byusing the ACT configuration tool.

The recommended settings of tCoord timer are based on maximal recommendedtransmission time for analogue channels according to IEC 60834-1. It isrecommended to coordinate the proposed settings with actual performance for theteleprotection equipment to get optimized settings.

13.1.3.1 Blocking scheme

Set Operation On

Set SchemeType Blocking

Set tCoord 25 ms (10 ms + maximal transmission time)

Set tSendMin 0 s

Set Unblock Off(Set to NoRestart if Unblocking scheme with no alarm for loss of guard is to be used.Set to Restart if Unblocking scheme with alarm for loss of guard is to be used)

Set tSecurity 0.035 s

13.1.3.2 Permissive underreaching scheme

Set Operation = On

Set SchemeType = Permissive UR

Set tCoord = 0 ms

Set tSendMin = 0.1 s

Set Unblock = Off

Set tSecurity = 0.035 s

Section 13 1MRK 506 375-UEN -Scheme communication

302 Railway application RER670 2.2 IECApplication manual

Page 309: Railway application RER670 Version 2.2 IEC ... - ABB

13.1.3.3 Permissive overreaching scheme

Set Operation = On

Set Scheme type = Permissive OR

Set tCoord = 0 ms

Set tSendMin = 0.1 s (0 s in parallel line applications)

Set Unblock = Off

Set tSecurity = 0.035 s

13.1.3.4 Unblocking scheme

Set Unblock = Restart(Loss of guard signal will give both trip and alarmChoose NoRestart if only trip is required)

Set tSecurity = 0.035 s

13.1.3.5 Intertrip scheme

Set Operation = On

Set SchemeType = Intertrip

Set tCoord = 50 ms (10 ms + maximal transmission time)

Set tSendMin = 0.1 s (0 s in parallel line applications)

Set Unblock = Off

Set tSecurity = 0.015 s

13.2 Current reversal and Weak-end infeed logic fordistance protection 2-phase ZCRWPSCH

13.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Current reversal and weak-end infeedlogic for distance protection 2-phase

ZCRWPSCH - 85

13.2.2 Application

13.2.2.1 Current reversal logic

In the case of parallel lines, overreaching permissive communication schemes cancause unwanted tripping due to current reversal. The unwanted tripping affects the

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 303Application manual

Page 310: Railway application RER670 Version 2.2 IEC ... - ABB

healthy line when a fault is cleared on the parallel line. This lack of security results ina total disconnection between the two buses.

To avoid this kind of disturbances, a fault current reversal logic (transient blockinglogic) can be used.

The unwanted operations that might occur can be explained by looking intoFigure 129 and Figure 130. Initially the protection A2 at A side will detect a fault inforward direction and send a communication signal to the protection B2 at remote end,which is measuring a fault in reverse direction.

L1

L2

A1

A2

B1

B2

IEC9900043-2.vsd

IEC99000043 V3 EN

Figure 129: Current distribution for a fault close to B side when all breakers areclosed

When the breaker B1 opens for clearing the fault, the fault current through B2 bay willinvert. If the communication signal has not reset at the same time as the distanceprotection function used in the teleprotection scheme has switched on to forwarddirection, we will have an unwanted operation of breaker B2 at B side.

L1

L2

A1

A2

B1

B2

IEC99000044-2.vsd

IEC99000044 V3 EN

Figure 130: Current distribution for a fault close to B side when breaker B1 hasopened

To handle this the send signal CS or CSLn from B2 is held back until the reverse zoneIRVLn has reset and the tDelayRev time has been elapsed. To achieve this the reversezone on the distance protection shall be connected to input IRV and the output IRVLshall be connected to input BLKCS on the communication function block ZCPSCH.

The function can be blocked by activating the input IRVBLK or the general BLOCKinput.

13.2.2.2 Weak-end infeed logic

Permissive communication schemes can basically operate only when the protection inthe remote IED can detect the fault. The detection requires a sufficient minimum fault

Section 13 1MRK 506 375-UEN -Scheme communication

304 Railway application RER670 2.2 IECApplication manual

Page 311: Railway application RER670 Version 2.2 IEC ... - ABB

current, normally >20% of Ir. The fault current can be too low due to an open breakeror low short-circuit power of the source. To overcome these conditions, weak-endinfeed (WEI) echo logic is used. The fault current can also be initially too low due tothe fault current distribution. Here, the fault current increases when the breaker opensat the strong terminal, and a sequential tripping is achieved. This requires a detectionof the fault by an independent tripping zone 1. To avoid sequential tripping asdescribed, and when zone 1 is not available, weak-end infeed tripping logic is used.The weak end infeed function only works together with permissive overreachcommunication schemes as the carrier send signal must cover the complete linelength.

The WEI function sends back (echoes) the received signal under the condition that nofault has been detected on the weak-end by different fault detection elements (distanceprotection in forward and reverse direction).

Also, the WEI function can be extended to trip the breaker in the weak side. The tripis achieved when one or more phase voltages are low during an echo function.

Together with the blocking teleprotection scheme some limitations apply:

• Only the trip part of the function can be used together with the blocking scheme.It is not possible to use the echo function to send the echo signal to the remote lineIED. The echo signal would block the operation of the distance protection at theremote line end and in this way prevents the correct operation of a completeprotection scheme.

• A separate direct intertrip channel must be arranged from remote end when a tripor accelerated trip is given there. The intertrip receive signal is connect to inputCRL.

• The WEI function shall be set to WEI=Echo&Trip. The WEI function block willthen give phase selection and trip the local breaker.

Avoid using WEI function at both line ends. It shall only be activated at the weak-end.

13.2.3 Setting guidelines

The parameters for the current reversal logic and the weak-end infeed logic (WEI)function are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

13.2.3.1 Current reversal logic

Set CurrRev to On to activate the function.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 305Application manual

Page 312: Railway application RER670 Version 2.2 IEC ... - ABB

Set tDelayRev timer at the maximum reset time for the communication equipment thatgives the carrier receive (CRL) signal plus 30 ms. A minimum setting of 40 ms isrecommended, typical 60 ms.

A long tDelayRev setting increases security against unwanted tripping, but delay thefault clearing in case of a fault developing from one line that evolves to the other one.The probability of this type of fault is small. Therefore set tDelayRev with a goodmargin.

Set the pick-up delay tPickUpRev to <80% of the minimum sum of breaker operatetime + communication delay time, but with a minimum of 20 ms.

13.2.3.2 Weak-end infeed logic

Set WEI to Echo, to activate the weak-end infeed function with only echo function.

Set WEI to Echo&Trip to obtain echo with trip.

Set tPickUpWEI to 10 ms, a short delay is recommended to avoid that spurious carrierreceived signals will activate WEI and cause unwanted carrier send (ECHO) signals.

Set the voltage criterion UPP< and UPN< for the weak-end trip to 70% of the systembase voltage UBase. The setting should be below the operate voltage of the system butabove the voltage that occurs for fault on the protected line.

13.3 Scheme communication logic for residualovercurrent protection ECPSCH

13.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Scheme communication logic forresidual overcurrent protection

ECPSCH - 85

13.3.2 Application

To achieve fast fault clearance of earth faults on the part of the line not covered by theinstantaneous step of the residual overcurrent protection, the directional residualovercurrent protection can be supported with a logic that uses communicationchannels.

One communication channel is used in each direction, which can transmit an on/offsignal if required. The performance and security of this function is directly related tothe transmission channel speed and security against false or lost signals.

Section 13 1MRK 506 375-UEN -Scheme communication

306 Railway application RER670 2.2 IECApplication manual

Page 313: Railway application RER670 Version 2.2 IEC ... - ABB

In the directional scheme, information of the fault current direction must betransmitted to the other line end.

With directional comparison in permissive schemes, a short operate time of theprotection including a channel transmission time, can be achieved. This short operatetime enables rapid autoreclosing function after the fault clearance.

The communication logic module enables blocking as well as permissive under/overreaching schemes. The logic can also be supported by additional logic for weak-end infeed and current reversal, included in the Current reversal and weak-end infeedlogic for residual overcurrent protection (ECRWPSCH) function.

Metallic communication paths adversely affected by fault generated noise may not besuitable for conventional permissive schemes that rely on signal transmitted during aprotected line fault. With power line carrier, for example, the communication signalmay be attenuated by the fault, especially when the fault is close to the line end,thereby disabling the communication channel.

To overcome the lower dependability in permissive schemes, an unblocking functioncan be used. Use this function at older, less reliable, power line carrier (PLC)communication, where the signal has to be sent through the primary fault. Theunblocking function uses a guard signal CRG, which must always be present, evenwhen no CR signal is received. The absence of the CRG signal during the security timeis used as a CR signal. This also enables a permissive scheme to operate when the linefault blocks the signal transmission. Set the tSecurity to 35 ms.

13.3.3 Setting guidelines

The parameters for the scheme communication logic for residual overcurrentprotection function are set via the local HMI or PCM600.

The following settings can be done for the scheme communication logic for residualovercurrent protection function:

Operation: Off or On.

SchemeType: This parameter can be set to Off , Intertrip, Permissive UR, PermissiveOR or Blocking.

tCoord: Delay time for trip from ECPSCH function. For Permissive under/overreaching schemes, this timer shall be set to at least 20 ms plus maximum reset timeof the communication channel as a security margin. For Blocking scheme, the settingshould be > maximum signal transmission time +10 ms.

Unblock: Select Off if unblocking scheme with no alarm for loss of guard is used. Setto Restart if unblocking scheme with alarm for loss of guard is used.

tSendMin: Time duration, the carrier send signal is prolonged.

tSecurity: The absence of CRG signal for a time duration of tSecurity is considered asCR signal.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 307Application manual

Page 314: Railway application RER670 Version 2.2 IEC ... - ABB

13.4 Current reversal and weak-end infeed logic forresidual overcurrent protection ECRWPSCH

13.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Current reversal and weak-end infeedlogic for residual overcurrent protection

ECRWPSCH - 85

13.4.2 Application

13.4.2.1 Fault current reversal logic

Figure 131 and figure 132 show a typical system condition, which can result in a faultcurrent reversal.

Assume that fault is near the B1 breaker. B1 Relay sees the fault in Zone1 and A1 relayidentifies the fault in Zone2.

Note that the fault current is reversed in line L2 after the breaker B1 opening.

It can cause an unselective trip on line L2 if the current reversal logic does not blockthe permissive overreaching scheme in the IED at B2.

L1

L2

A1

A2

B1

B2

IEC9900043-2.vsd

IEC99000043 V3 EN

Figure 131: Current distribution for a fault close to B side when all breakers areclosed

L1

L2

A1

A2

B1

B2

IEC99000044-2.vsd

IEC99000044 V3 EN

Figure 132: Current distribution for a fault close to B side when breaker at B1 isopened

Section 13 1MRK 506 375-UEN -Scheme communication

308 Railway application RER670 2.2 IECApplication manual

Page 315: Railway application RER670 Version 2.2 IEC ... - ABB

When the breaker on the parallel line operates, the fault current on the healthy line isreversed. The IED at B2 recognizes the fault in forward direction from reversedirection before breaker operates. As IED at B2 already received permissive signalfrom A2 and IED at B2 is now detecting the fault as forward fault, it will immediatelytrip breaker at B2. To ensure that tripping at B2 should not occur, the permissiveoverreaching function at B2 needs to be blocked by IRVL till the received permissivesignal from A2 is reset.

The IED at A2, where the forward direction element was initially activated, must resetbefore the send signal is initiated from B2. The delayed reset of output signal IRVLalso ensures the send signal from IED B2 is held back till the forward directionelement is reset in IED A2.

13.4.2.2 Weak-end infeed logic

Figure 133 shows a typical system condition that can result in a missing operation.Note that there is no fault current from node B. This causes that the IED at B cannotdetect the fault and trip the breaker in B. To cope with this situation, a selectable weak-end infeed logic is provided for the permissive overreaching scheme.

A B

IEC99000054-3-en.vsd

Strongsource

Weaksource

IEC99000054 V3 EN

Figure 133: Initial condition for weak-end infeed

13.4.3 Setting guidelines

The parameters for the current reversal and weak-end infeed logic for residualovercurrent protection function are set via the local HMI or PCM600.

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

13.4.3.1 Current reversal

The current reversal function is set on or off by setting the parameter CurrRev to On orOff. Time delays shall be set for the timers tPickUpRev and tDelayRev.

tPickUpRev is chosen shorter (<80%) than the breaker opening time, but minimum 20ms.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 309Application manual

Page 316: Railway application RER670 Version 2.2 IEC ... - ABB

tDelayRev is chosen at a minimum to the sum of protection reset time and thecommunication reset time. A minimum tDelayRev setting of 40 ms is recommended.

The reset time of the directional residual overcurrent protection (EF4PTOC) istypically 25 ms. If other type of residual overcurrent protection is used in the remoteline end, its reset time should be used.

The signal propagation time is in the range 3 – 10 ms/km for most types ofcommunication media. In communication networks small additional time delays areadded in multiplexers and repeaters. Theses delays are less than 1 ms per process. Itis often stated that the total propagation time is less than 5 ms.

When a signal picks-up or drops out there is a decision time to be added. This decisiontime is highly dependent on the interface between communication and protectionused. In many cases an external interface (teleprotection equipment) is used. Thisequipment makes a decision and gives a binary signal to the protection device. In caseof analog teleprotection equipment typical decision time is in the range 10 – 30 ms. Fordigital teleprotection equipment this time is in the range 2 – 10 ms.

If the teleprotection equipment is integrated in the protection IED the decision timecan be slightly reduced.

The principle time sequence of signaling at current reversal is shown.

Protection Function

Protection Function

Tele-ProtectionEquipment

Tele-ProtectionEquipment

Tele-communication

System

CS from the protection

function, operateand reset time

CS initiation to the

communicationsystem, operate and reset time

CS propagation, propagation

CR selection and decision, operate

and reset time

CR to the protection

function, operateand reset time

Time

Faultoccurs

Protectionpick-up CS initiation

CR to teleprot.

eq.

CR to prot.func

Fault current reversal

Sendingprotection

reset

CS to communication

drop

CRreception

dropCR to prot. funcdrop

Minimum setting of tDelay IEC05000536-2-en.vsd

IEC05000536 V2 EN

Figure 134: Time sequence of signaling at current reversal

Section 13 1MRK 506 375-UEN -Scheme communication

310 Railway application RER670 2.2 IECApplication manual

Page 317: Railway application RER670 Version 2.2 IEC ... - ABB

13.4.3.2 Weak-end infeed

The weak-end infeed can be set by setting the parameter WEI to Off, Echo or Echo &Trip. Operating zero sequence voltage when parameter WEI is set to Echo & Trip isset with 2U0>.

The zero sequence voltage for a fault at the remote line end and appropriate faultresistance is calculated.

To avoid unwanted trip from the weak-end infeed logic (if spurious signals shouldoccur), set the operate value of the broken delta voltage level detector (2U0) higherthan the maximum false network frequency residual voltage that can occur duringnormal service conditions. The recommended minimum setting is two times the falsezero-sequence voltage during normal service conditions.

1MRK 506 375-UEN - Section 13Scheme communication

Railway application RER670 2.2 IEC 311Application manual

Page 318: Railway application RER670 Version 2.2 IEC ... - ABB

312

Page 319: Railway application RER670 Version 2.2 IEC ... - ABB

Section 14 Logic

14.1 Tripping logic SMPPTRC

14.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Tripping logic SMPPTRC

1 -> 0

IEC15000314 V1 EN

94

14.1.2 Application

All trip signals from the different protection functions shall be routed through the triplogic. In its simplest form, the trip logic will only link the TRIP signal to a binaryoutput and make sure that the trip duration is sufficient.

Tripping logic SMPPTRC can be used in single-phase and two-phase railway supplysystems.

One SMPPTRC function block should be used per each breaker.

To prevent closing of a circuit breaker after a trip, the function offers a lockoutfunction.

14.1.2.1 Tripping

A simple application with tripping utilizes part of the function block. Connect theinputs from the protection function blocks to the input TRIN to combine the differentfunction outputs to this input. Connect the output TRIP to the binary outputs on the IOboard.

This signal can also be used for other purposes internally in the IED. An examplecould be the starting of breaker failure protection.

Set the required length of the trip pulse to for example, tTripMin = 150ms.

For special applications such as lockout refer to the separate section below. Thetypical connection is shown below in figure 135. Signals that are not used are dimmed.

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 313Application manual

Page 320: Railway application RER670 Version 2.2 IEC ... - ABB

BLOCK

TRIN

SETLKOUT

RSTLKOUT

SMPPTRC

TRIP

CLLKOUT

Impedance protection zone 1 TRIP

EF4PTOC TRIP

IEC16000184-1-en.vsd

Impedance protection zone 3 TRIP

Impedance protection zone 2 TRIPTMAGAPC

STDIR

START

STL1

STL2

FW

REV

IEC16000184 V1 EN

Figure 135: Tripping logic SMPPTRC is used for a simple tripping application

14.1.2.2 Lock-out

The function block is provided with possibilities to initiate lockout. The lockout canbe set to only activate the block closing output CLLKOUT or initiate the block closingoutput and also maintain the trip output signal TRIP (latched trip), by settingTripLockout=On.

The lockout can then be manually reset after checking the primary fault by activatingthe reset input RSTLKOUT. Note that the activation of the RSTLKOUT input willinitiate a short pulse of 3 ms. A new reset needs a new activation of the RSTLKOUTinput.

If external conditions are required to initiate a lockout but not initiate a trip, this canbe achieved by activating input SETLKOUT. The setting AutoLock = Off means thatthe internal trip will not activate lockout so only initiation of the input SETLKOUTwill result in lockout. This is normally the case for overhead line protection wheremost faults are transient. Unsuccessful autoreclose and back-up zone tripping can insuch cases be connected to initiate lockout by activating the input SETLKOUT.

14.1.2.3 Example of directional data

An example how to connect the directional data from different application functionsto the trip function is given below, see Figure 136:

Section 14 1MRK 506 375-UEN -Logic

314 Railway application RER670 2.2 IECApplication manual

Page 321: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000182-1-en.vsdx

BLOCK

START

FW

REV

STL1

FWL1

REVL1

STL2

FWL2

REVL2

STDIR

STARTCOMB

BLOCK

START

FW

REV

STL1

FWL1

REVL1

STL2

FWL2

REVL2

STDIR

STARTCOMB

BLOCK

STDIR1

STDIR2

STDIR3

STDIR4

STDIR5

STDIR6

STDIR7

STDIR8

STDIR9

STDIR10

STDIR11

STDIR12

STDIR13

STDIR14

STDIR15

STDIR16

STDIR

SMAGAPC

START

FW

REV

PROTECTION 1

STL1

FWL1

REVL1

STL2

FWL2

REVL2

PROTECTION 2

STDIR

PROTECTION 3

-

-

-

BLOCKTRIN

SETLKOUT

RSTLKOUT

STDIR

TRIP

SMPPTRC

CLLKOUT

START

STL1

STL2

FW

REV

IEC16000182 V1 EN

Figure 136: Example of the connection of directional start logic.

Protection functions connect the directional data via the start combinator functionSTARTCOMB to the start matrix function SMAGAPC and then to the trip functionSMPPTRC, or directly to SMAGAPC and then to the SMPPTRC.

The SMAGAPC merge start and directional output signals from different applicationfunctions and create a common directional output signal STDIR to be connected toSMPPTRC.

The trip function SMPPTRC splits up the directional data as general output data forSTART, STL1, STL2, FW and REV.

All start and directional outputs are mapped to the 61850 logical node data model ofthe trip function and provided via the 61850 dirGeneral, dirPhsA and dirPhsB dataattributes.

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 315Application manual

Page 322: Railway application RER670 Version 2.2 IEC ... - ABB

14.1.2.4 Blocking of the function block

Total block of the trip function is done by activating the input BLOCK and can be usedto disable the outputs of the trip logic in the event of internal failures.

14.1.3 Setting guidelines

The parameters for tripping logic SMPPTRC are set via the local HMI or PCM600.

The following trip parameters can be set to regulate tripping.

Operation: Sets the mode of operation. Off switches the tripping off. The normalselection is On.

TripLockout: Sets the scheme for lockout. Off only activates the lockout output whenthe input SETLKOUT is activated. On activates the lockout output and latches theoutput TRIP when the input SETLKOUT is activated. The normal selection is Off.

AutoLock: Sets the scheme for lockout. Off only activates lockout through the inputSETLKOUT. On additionally allows activation of lockout from the trip functionitself. The normal selection is Off.

tTripMin: Sets the required minimum duration of the trip pulse. It should be set toensure that the circuit breaker is tripped correctly. Normal setting is 0.150s.

14.2 Trip matrix logic TMAGAPC

14.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Trip matrix logic TMAGAPC - -

14.2.2 Application

The trip matrix logic TMAGAPC function is used to route trip signals and otherlogical output signals to different output contacts on the IED.

The trip matrix logic function has 3 output signals and these outputs can be connectedto physical tripping outputs according to the specific application needs for settablepulse or steady output.

14.2.3 Setting guidelines

Operation: Operation of function On/Off.

Section 14 1MRK 506 375-UEN -Logic

316 Railway application RER670 2.2 IECApplication manual

Page 323: Railway application RER670 Version 2.2 IEC ... - ABB

PulseTime: Defines the pulse time when in Pulsed mode. When used for directtripping of circuit breaker(s) the pulse time delay shall be set to approximately 0.150seconds in order to obtain satisfactory minimum duration of the trip pulse to the circuitbreaker trip coils.

OnDelay: Used to prevent output signals to be given for spurious inputs. Normally setto 0 or a low value.

OffDelay: Defines a delay of the reset of the outputs after the activation conditions nolonger are fulfilled. It is only used in Steady mode. When used for direct tripping ofcircuit breaker(s) the off delay time shall be set to at least 0.150 seconds in order toobtain a satisfactory minimum duration of the trip pulse to the circuit breaker tripcoils.

ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed.

14.3 Logic for group alarm ALMCALH

14.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic for group alarm ALMCALH - -

14.3.2 Application

Group alarm logic function ALMCALH is used to route alarm signals to differentLEDs and/or output contacts on the IED.

ALMCALH output signal and the physical outputs allows the user to adapt the alarmsignal to physical tripping outputs according to the specific application needs.

14.3.3 Setting guidelines

Operation: On or Off

14.4 Logic for group alarm WRNCALH

14.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic for group warning WRNCALH - -

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 317Application manual

Page 324: Railway application RER670 Version 2.2 IEC ... - ABB

14.4.1.1 Application

Group warning logic function WRNCALH is used to route warning signals to LEDsand/or output contacts on the IED.

WRNCALH output signal WARNING and the physical outputs allows the user toadapt the warning signal to physical tripping outputs according to the specificapplication needs.

14.4.1.2 Setting guidelines

OperationOn or Off

14.5 Logic for group indication INDCALH

14.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic for group indication INDCALH - -

14.5.1.1 Application

Group indication logic function INDCALH is used to route indication signals todifferent LEDs and/or output contacts on the IED.

INDCALH output signal IND and the physical outputs allows the user to adapt theindication signal to physical outputs according to the specific application needs.

14.5.1.2 Setting guidelines

Operation: On or Off

14.6 Configurable logic blocks

The configurable logic blocks are available in two categories:

• Configurable logic blocks that do not propagate the time stamp and the quality ofsignals. They do not have the suffix QT at the end of their function block name,for example, SRMEMORY. These logic blocks are also available as part of anextension logic package with the same number of instances.

• Configurable logic blocks that propagate the time stamp and the quality ofsignals. They have the suffix QT at the end of their function block name, forexample, SRMEMORYQT.

Section 14 1MRK 506 375-UEN -Logic

318 Railway application RER670 2.2 IECApplication manual

Page 325: Railway application RER670 Version 2.2 IEC ... - ABB

14.6.1 Application

A set of standard logic blocks, like AND, OR etc, and timers are available for adaptingthe IED configuration to the specific application needs.

14.6.2 Setting guidelines

There are no settings for AND gates, OR gates, inverters or XOR gates.

For normal On/Off delay and pulse timers the time delays and pulse lengths are setfrom the local HMI or via the PST tool.

Both timers in the same logic block (the one delayed on pick-up and the one delayedon drop-out) always have a common setting value.

For controllable gates, settable timers and SR flip-flops with memory, the settingparameters are accessible via the local HMI or via the PST tool.

14.6.2.1 Configuration

Logic is configured using the ACT configuration tool in PCM600.

Execution of functions as defined by the configurable logic blocks runs according toa fixed sequence with different cycle times.

For each cycle time, the function block is given an serial execution number. This isshown when using the ACT configuration tool with the designation of the functionblock and the cycle time, see example below.

IEC09000695_2_en.vsd

IEC09000695 V2 EN

Figure 137: Example designation, serial execution number and cycle time forlogic function

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 319Application manual

Page 326: Railway application RER670 Version 2.2 IEC ... - ABB

IEC09000310-2-en.vsd

IEC09000310 V2 EN

Figure 138: Example designation, serial execution number and cycle time forlogic function that also propagates timestamp and quality of inputsignals

The execution of different function blocks within the same cycle is determined by theorder of their serial execution numbers. Always remember this when connecting twoor more logical function blocks in series.

Always be careful when connecting function blocks with a fast cycletime to function blocks with a slow cycle time.Remember to design the logic circuits carefully and always check theexecution sequence for different functions. In other cases, additionaltime delays must be introduced into the logic schemes to preventerrors, for example, race between functions.

14.7 Fixed signal function block FXDSIGN

14.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fixed signals FXDSIGN - -

14.7.2 Application

The Fixed signals function (FXDSIGN) has nine pre-set (fixed) signals that can beused in the configuration of an IED, either for forcing the unused inputs in otherfunction blocks to a certain level/value, or for creating certain logic. Boolean, integer,floating point, string types of signals are available.

One FXDSIGN function block is included in all IEDs.

Section 14 1MRK 506 375-UEN -Logic

320 Railway application RER670 2.2 IECApplication manual

Page 327: Railway application RER670 Version 2.2 IEC ... - ABB

Example for use of GRP_OFF signal in FXDSIGNThe Restricted earth fault function REFPDIF can be used both for auto-transformersand normal transformers.

When used for auto-transformers, information from both windings parts, togetherwith the neutral point current, needs to be available to the function. This means thatthree inputs are needed.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

IEC09000619_3_en.vsd

IEC09000619 V3 EN

Figure 139: REFPDIF function inputs for autotransformer application

For normal transformers only one winding and the neutral point is available. Thismeans that only two inputs are used. Since all group connections are mandatory to beconnected, the third input needs to be connected to something, which is the GRP_OFFsignal in FXDSIGN function block.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

GRP_OFFFXDSIGN

IEC09000620_3_en.vsd

IEC09000620 V3 EN

Figure 140: REFPDIF function inputs for normal transformer application

14.8 Boolean 16 to Integer conversion B16I

14.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean 16 to integer conversion B16I - -

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 321Application manual

Page 328: Railway application RER670 Version 2.2 IEC ... - ABB

14.8.2 Application

Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary(logical) signals into an integer. It can be used – for example, to connect logical outputsignals from a function (like distance protection) to integer inputs from anotherfunction (like line differential protection). B16I does not have a logical node mapping.

The Boolean 16 to integer conversion function (B16I) will transfer a combination ofup to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a valueaccording to the table below from 0 to 32768. This follows the general formula: INx= 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be availableon the output OUT as a sum of the values of all the inputs INx that are activated. OUTis an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 itcorresponds to that integer 65535 is available on the output OUT. B16I function isdesigned for receiving up to 16 booleans input locally. If the BLOCK input isactivated, it will freeze the output at the last value.

Values of each of the different OUTx from function block B16I for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block B16I.

Name of input Type Default Description Value whenactivated

Value whendeactivated

IN1 BOOLEAN 0 Input 1 1 0

IN2 BOOLEAN 0 Input 2 2 0

IN3 BOOLEAN 0 Input 3 4 0

IN4 BOOLEAN 0 Input 4 8 0

IN5 BOOLEAN 0 Input 5 16 0

IN6 BOOLEAN 0 Input 6 32 0

IN7 BOOLEAN 0 Input 7 64 0

IN8 BOOLEAN 0 Input 8 128 0

IN9 BOOLEAN 0 Input 9 256 0

IN10 BOOLEAN 0 Input 10 512 0

IN11 BOOLEAN 0 Input 11 1024 0

IN12 BOOLEAN 0 Input 12 2048 0

IN13 BOOLEAN 0 Input 13 4096 0

IN14 BOOLEAN 0 Input 14 8192 0

IN15 BOOLEAN 0 Input 15 16384 0

IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the B16I function block.

Section 14 1MRK 506 375-UEN -Logic

322 Railway application RER670 2.2 IECApplication manual

Page 329: Railway application RER670 Version 2.2 IEC ... - ABB

14.9 Boolean to integer conversion with logical noderepresentation, 16 bit BTIGAPC

14.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean to integer conversion withlogical node representation, 16 bit

BTIGAPC - -

14.9.2 Application

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) isused to transform a set of 16 binary (logical) signals into an integer. BTIGAPC has alogical node mapping in IEC 61850.

The BTIGAPC function will transfer a combination of up to 16 binary inputs INxwhere 1≤x≤16 to an integer. Each INx represents a value according to the table belowfrom 0 to 32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sumof all the values on the activated INx will be available on the output OUT as a sum ofthe values of all the inputs INx that are activated. OUT is an integer. When all INxwhere 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535 isavailable on the output OUT. BTIGAPC function is designed for receiving up to 16booleans input locally. If the BLOCK input is activated, it will freeze the output at thelast value.

Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block BTIGAPC.

Name of input Type Default Description Value whenactivated

Value whendeactivated

IN1 BOOLEAN 0 Input 1 1 0

IN2 BOOLEAN 0 Input 2 2 0

IN3 BOOLEAN 0 Input 3 4 0

IN4 BOOLEAN 0 Input 4 8 0

IN5 BOOLEAN 0 Input 5 16 0

IN6 BOOLEAN 0 Input 6 32 0

IN7 BOOLEAN 0 Input 7 64 0

IN8 BOOLEAN 0 Input 8 128 0

IN9 BOOLEAN 0 Input 9 256 0

IN10 BOOLEAN 0 Input 10 512 0

Table continues on next page

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 323Application manual

Page 330: Railway application RER670 Version 2.2 IEC ... - ABB

Name of input Type Default Description Value whenactivated

Value whendeactivated

IN11 BOOLEAN 0 Input 11 1024 0

IN12 BOOLEAN 0 Input 12 2048 0

IN13 BOOLEAN 0 Input 13 4096 0

IN14 BOOLEAN 0 Input 14 8192 0

IN15 BOOLEAN 0 Input 15 16384 0

IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the BTIGAPC function block.

14.10 Integer to Boolean 16 conversion IB16

14.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion IB16 - -

14.10.2 Application

Integer to boolean 16 conversion function (IB16) is used to transform an integer intoa set of 16 binary (logical) signals. It can be used – for example, to connect integeroutput signals from one function to binary (logical) inputs to another function. IB16function does not have a logical node mapping.

The Boolean 16 to integer conversion function (IB16) will transfer a combination ofup to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a valueaccording to the table below from 0 to 32768. This follows the general formula: INx= 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be availableon the output OUT as a sum of the values of all the inputs INx that are activated. OUTis an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 itcorresponds to that integer 65535 is available on the output OUT. IB16 function isdesigned for receiving up to 16 booleans input locally. If the BLOCK input isactivated, it will freeze the output at the last value.

Values of each of the different OUTx from function block IB16 for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block IB16.

Section 14 1MRK 506 375-UEN -Logic

324 Railway application RER670 2.2 IECApplication manual

Page 331: Railway application RER670 Version 2.2 IEC ... - ABB

Name of input Type Default Description Value whenactivated

Value whendeactivated

IN1 BOOLEAN 0 Input 1 1 0

IN2 BOOLEAN 0 Input 2 2 0

IN3 BOOLEAN 0 Input 3 4 0

IN4 BOOLEAN 0 Input 4 8 0

IN5 BOOLEAN 0 Input 5 16 0

IN6 BOOLEAN 0 Input 6 32 0

IN7 BOOLEAN 0 Input 7 64 0

IN8 BOOLEAN 0 Input 8 128 0

IN9 BOOLEAN 0 Input 9 256 0

IN10 BOOLEAN 0 Input 10 512 0

IN11 BOOLEAN 0 Input 11 1024 0

IN12 BOOLEAN 0 Input 12 2048 0

IN13 BOOLEAN 0 Input 13 4096 0

IN14 BOOLEAN 0 Input 14 8192 0

IN15 BOOLEAN 0 Input 15 16384 0

IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the IB16 function block.

14.11 Integer to Boolean 16 conversion with logic noderepresentation ITBGAPC

14.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion withlogic node representation

ITBGAPC - -

14.11.2 Application

Integer to boolean 16 conversion with logic node representation function (ITBGAPC)is used to transform an integer into a set of 16 boolean signals. ITBGAPC function canreceive an integer from a station computer – for example, over IEC 61850–8–1. Thisfunction is very useful when the user wants to generate logical commands (for selector

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 325Application manual

Page 332: Railway application RER670 Version 2.2 IEC ... - ABB

switches or voltage controllers) by inputting an integer number. ITBGAPC functionhas a logical node mapping in IEC 61850.

The Integer to Boolean 16 conversion with logic node representation function(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicatedvia IEC 61850 and connected to the ITBGAPC function block to a combination ofactivated outputs OUTx where 1≤x≤16.

The values of the different OUTx are according to the Table 30.

If the BLOCK input is activated, it freezes the logical outputs at the last value.

Table 30: Output signals

Name of OUTx Type Description Value whenactivated

Value whendeactivated

OUT1 BOOLEAN Output 1 1 0

OUT2 BOOLEAN Output 2 2 0

OUT3 BOOLEAN Output 3 4 0

OUT4 BOOLEAN Output 4 8 0

OUT5 BOOLEAN Output 5 16 0

OUT6 BOOLEAN Output 6 32 0

OUT7 BOOLEAN Output 7 64 0

OUT8 BOOLEAN Output 8 128 0

OUT9 BOOLEAN Output 9 256 0

OUT10 BOOLEAN Output 10 512 0

OUT11 BOOLEAN Output 11 1024 0

OUT12 BOOLEAN Output 12 2048 0

OUT13 BOOLEAN Output 13 4096 0

OUT14 BOOLEAN Output 14 8192 0

OUT15 BOOLEAN Output 15 16384 0

OUT16 BOOLEAN Output 16 32768 0

The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)are active equals 65535. This is the highest integer that can be converted by theITBGAPC function block.

14.12 Elapsed time integrator with limit transgression andoverflow supervision TEIGAPC

14.12.1 IdentificationFunction Description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2 devicenumber

Elapsed time integrator TEIGAPC - -

Section 14 1MRK 506 375-UEN -Logic

326 Railway application RER670 2.2 IECApplication manual

Page 333: Railway application RER670 Version 2.2 IEC ... - ABB

14.12.2 Application

The function TEIGAPC is used for user-defined logics and it can also be used fordifferent purposes internally in the IED. An application example is the integration ofelapsed time during the measurement of neutral point voltage or neutral current atearth-fault conditions.

Settable time limits for warning and alarm are provided. The time limit for overflowindication is fixed to 999999.9 seconds.

14.12.3 Setting guidelines

The settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.

A resolution of 10 ms can be achieved when the settings are defined within the range

1.00 second ≤ tAlarm ≤ 99 999.99 seconds

1.00 second ≤ tWarning ≤ 99 999.99 seconds.

If the values are above this range, the resolution becomes lower due to the 32 bit floatrepresentation

99 999.99 seconds < tAlarm ≤ 999 999.0 seconds

99 999.99 seconds < tWarning ≤ 999 999.0 seconds

Note that tAlarm and tWarning are independent settings, that is, thereis no check if tAlarm > tWarning.

The limit for the overflow supervision is fixed at 999999.9 seconds.

14.13 Comparator for integer inputs - INTCOMP

14.13.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Comparison of integer values INTCOMP Int<=>

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 327Application manual

Page 334: Railway application RER670 Version 2.2 IEC ... - ABB

14.13.2 Application

The function gives the possibility to monitor the level of integer values in the systemrelative to each other or to a fixed value. It is a basic arithmetic function that can beused for monitoring, supervision, interlocking and other logics.

14.13.3 Setting guidelines

For proper operation of comparison the set value should be set within the range of ± 2×109.

Setting procedure on the IED:

EnaAbs: This setting is used to select the comparison type between signed andabsolute values.

• Absolute: Comparison is performed on absolute values of input and referencevalues

• Signed: Comparison is performed on signed values of input and reference values.

RefSource: This setting is used to select the reference source between input and settingfor comparison.

• Input REF: The function will take reference value from input REF• Set Value: The function will take reference value from setting SetValue

SetValue: This setting is used to set the reference value for comparison when settingRefSource is selected as SetValue.

14.13.4 Setting example

For absolute comparison between inputs:

Set the EnaAbs = Absolute

Set the RefSource = Input REF

Similarly for Signed comparison between inputs

Set the EnaAbs = Signed

Set the RefSource =Input REF

For absolute comparison between input and setting

Set the EnaAbs = Absolute

Set the RefSource = Set Value

Section 14 1MRK 506 375-UEN -Logic

328 Railway application RER670 2.2 IECApplication manual

Page 335: Railway application RER670 Version 2.2 IEC ... - ABB

SetValue shall be set between -2000000000 to 2000000000

Similarly for signed comparison between input and setting

Set the EnaAbs = Signed

Set the RefSource = Set Value

SetValue shall be set between -2000000000 to 2000000000

14.14 Comparator for real inputs - REALCOMP

14.14.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Comparator for real inputs REALCOMP Real<=>

14.14.2 Application

The function gives the possibility to monitor the level of real values in the systemrelative to each other or to a fixed value. It is a basic arithmetic function that can beused for monitoring, supervision, interlocking and other logics.

14.14.3 Setting guidelines

Setting procedure on the IED:

EnaAbs: This setting is used to select the comparison type between signed andabsolute values.

• Absolute: Comparison is performed with absolute values of input and reference.• Signed: Comparison is performed with signed values of input and reference.

RefSource: This setting is used to select the reference source between input and settingfor comparison.

• Input REF: The function will take reference value from input REF• Set Value: The function will take reference value from setting SetValue

SetValue: This setting is used to set the reference value for comparison when settingRefSource is selected as Set Value. If this setting value is less than 0.2% of the set unitthen the output INLOW will never pickup.

1MRK 506 375-UEN - Section 14Logic

Railway application RER670 2.2 IEC 329Application manual

Page 336: Railway application RER670 Version 2.2 IEC ... - ABB

RefPrefix: This setting is used to set the unit of the reference value for comparisonwhen setting RefSource is selected as SetValue. It has 5 unit selections and they areMilli, Unity, Kilo, Mega and Giga.

EqualBandHigh: This setting is used to set the equal condition high band limit in % ofreference value. This high band limit will act as reset limit for INHIGH output whenINHIGH.

EqualBandLow: This setting is used to set the equal condition low band limit in % ofreference value. This low band limit will act as reset limit for INLOW output whenINLOW.

14.14.4 Setting example

Let us consider a comparison is to be done between current magnitudes in the rangeof 90 to 110 with nominal rating is 100 and the order is kA.

For the above condition the comparator can be designed with settings as follows,

EnaAbs = Absolute

RefSource = Set Value

SetValue = 100

RefPrefix = Kilo

EqualBandHigh = 5.0 % of reference value

EqualBandLow = 5.0 % of reference value

Operation

The function will set the outputs for the following conditions,

INEQUAL will set when the INPUT is between the ranges of 95 to 105 kA.

INHIGH will set when the INPUT crosses above 105 kA.

INLOW will set when the INPUT crosses below 95 kA.

If the comparison should be done between two current magnitudes then those currentsignals need to be connected to function inputs, INPUT and REF. Then the settingsshould be adjusted as below,

EnaAbs = Absolute

RefSource = Input REF

EqualBandHigh = 5.0 % of reference value

EqualBandLow = 5.0 % of reference value.

Section 14 1MRK 506 375-UEN -Logic

330 Railway application RER670 2.2 IECApplication manual

Page 337: Railway application RER670 Version 2.2 IEC ... - ABB

Section 15 Monitoring

15.1 Measurement

15.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measurements CVMMXN

P_Q

IEC15000112 V1 EN

-

Phase current measurement CMMXU

I

IEC15000116 V1 EN

-

Phase-phase voltage measurement VMMXU

U

IEC15000117 V1 EN

-

Current sequence componentmeasurement

CMSQI

Isqi

IEC15000113 V1 EN

-

Voltage sequence componentmeasurement

VMSQI

Usqi

IEC15000114 V1 EN

-

Phase-neutral voltage measurement VNMMXU

UN

IEC15000115 V1 EN

-

15.1.2 Application

Measurement functions are used for power system measurement and supervision, forreporting to the local HMI, the monitoring tool within PCM600 or to station level forexample, via IEC 61850. The measurement functions operates properly for 16.7Hz,50Hz and 60Hz railway power supply systems. The possibility to continuouslymonitor measured values of active power, reactive power, currents, voltages,frequency, power factor etc. is vital for efficient production, transmission and

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 331Application manual

Page 338: Railway application RER670 Version 2.2 IEC ... - ABB

distribution of electrical energy. It provides to the system operator fast and easyoverview of the present status of the power system. Additionally, it can be used duringtesting and commissioning of protection and control IEDs in order to verify properoperation and connection of instrument transformers (CTs and VTs). During normalservice by periodic comparison of the measured value from the IED with otherindependent meters the proper operation of the IED analog measurement chain can beverified. Finally, it can be used to verify proper direction orientation for distance ordirectional overcurrent protection function.

Several instances of each type of measurement function blocks areavailable in the IED. The actual reported values from the IED aredependent on the logic configuration made in PCM600.

All measured values can be supervised with four settable limits:

• low-low limit• low limit• high limit• high-high limit

A zero clamping reduction is also supported, that is, the measured value below asettable limit is forced to zero which reduces the impact of noise in the inputs.

Dead-band supervision can be used to report the measured signal value to the stationlevel when a change in the measured value is above the set threshold limit or timeintegral of all changes since the last time value updating exceeds the threshold limit.The measure value can also be based on periodic reporting.

All measurement functions uses fundamental frequency phasors (i.e. DFT filtering)for internal calculations and for reporting of measured values. However, from thefollowing three measurement functions CMMXU, VMMXU and VNMMXU it is alsopossible to report the total measured quantity (i.e. true RMS filtering). By selecting theRMS mode, the reported value will in addition to the fundamental magnitude alsoinclude harmonics. The RMS measurement is often required for railway powersystems which are typically polluted by harmonics.

The measurement function CVMMXN is located under: Main menu/Measurement/Monitoring/Service values/CVMMXN

CVMMXN provides the following power system quantities:

• P, Q and S: two or single phase active, reactive and apparent power• PF: power factor• F: power system frequency

The CVMMXN function calculates two-phase power quantities by using fundamentalfrequency phasors (DFT values) of the measured current respectively voltage signals.The measured power quantities are available either, as instantaneously calculated

Section 15 1MRK 506 375-UEN -Monitoring

332 Railway application RER670 2.2 IECApplication manual

Page 339: Railway application RER670 Version 2.2 IEC ... - ABB

quantities or, averaged values over a period of time (low pass filtered) depending onthe selected settings.

The measuring functions CMMXU, VMMXU and VNMMXU are located under:

Main menu/Measurement/Monitoring/CurrentPhasors(I)/CMMXU

Main menu/Measurement/Monitoring/VoltagePhasors, phase-phase(U)/VMMXU

Main menu/Measurement/Monitoring/VoltagePhasors, phase-neutral(UN)/VNMMXU

CMMXU, VMMXU and VNMMXU provide physical quantities:

• I: phase currents (amplitude and angle) (CMMXU)• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)

(VMMXU, VNMMXU)

Fundamental frequency filtered values (DFT) or true RMS values can be selected asa measurement type in CMMXU, VMMXU and VNMMXU functions.

The measuring functions CMSQI and VMSQI are located under:

Main menu/Measurement/Monitoring/CurrentSequenceComponents(Isqi)/CMSQI

Main menu/Measurement/Monitoring/VoltageSequenceComponents(Usqi)/VMSQI

CMSQI and VMSQI provide sequence component quantities:

• I: sequence currents (positive and zero sequence, amplitude and angle)• U: sequence voltages (positive and zero sequence, amplitude and angle).

It is possible to calibrate the measuring function to get better than class 0.5presentation. This is accomplished by angle and amplitude compensation at 5%, 30%and 100% of the rated current and at 100% of the rated voltage.

15.1.3 Zero clamping

Measuring functions CVMMXN, CMMXU, VMMXU and VNMMXU have nointerconnections regarding any settings or parameters.

Zero clampings are also handled entirely by ZeroDb separately for each function'severy output signal. For example, zero clamping of U12 is handled by UL12ZeroDbin VMMXU, zero clamping of I1 is handled by IL1ZeroDb in CMMXU, and so on.

Example of CVMMXN operation

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 333Application manual

Page 340: Railway application RER670 Version 2.2 IEC ... - ABB

Outputs seen on the local HMI under Main menu/Measurements/Monitoring/Servicevalues(P_Q)/CVMMXN(P_Q):

S Apparent three-phase power

P Active three-phase power

Q Reactive three-phase power

PF Power factor

ILAG I lagging U

ILEAD I leading U

U System mean voltage, calculated according to selected mode

I System mean current, calculated according to selected mode

F Frequency

Relevant settings and their values on the local HMI under Main menu/Settings/IEDsettings/Monitoring/Servicevalues(P_Q)/CVMMXN(P_Q):

• When system voltage falls below UGenZeroDB, values for S, P, Q, PF, U and Fare forced to zero.

• When system current falls below IGenZeroDB, values for S, P, Q, PF, U and F areforced to zero.

• When the value of a single signal falls below its set deadband, the value is forcedto zero. For example, if the apparent three-phase power falls below SZeroDb, thevalue for S is forced to zero.

15.1.4 Setting guidelines

The available setting parameters of the measurement function CVMMXN, CMMXU,VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actual hardware(TRM) and the logic configuration made in PCM600.

The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.

GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.

Operation: Off/On. Every function instance (CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation(Off).

The following general settings can be set for the Measurement function(CVMMXN):

k: Low pass filter coefficient for power measurement.

Parameters IBase, Ubase and SBase have been implemented as asettings instead of a parameters, which means that if the values of the

Section 15 1MRK 506 375-UEN -Monitoring

334 Railway application RER670 2.2 IECApplication manual

Page 341: Railway application RER670 Version 2.2 IEC ... - ABB

parameters are changed there will be no restart of the application. Asrestart is required to activate new parameters values, the IED must berestarted in some way. Either manually or by changing some otherparameter at the same time.

The following general settings can be set for the Phase current measurement(CMMXU):

IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.

IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, whereY is equal to 5, 30 or 100.

MeasurementType: This default setting is DFT, which gives fundamental frequencyamplitude and angle. It can be set as RMS, if true RMS value over one cycle isrequired.

The following general settings can be set for the Phase-phase voltage measurement(VMMXU):

UAmpComp100: Amplitude compensation to calibrate voltage measurements at100% of Ur.

MeasurementType: This default setting is DFT, which gives fundamental frequencyamplitude and angle. It can be set as RMS, if true RMS value over one cycle isrequired.

The following general settings can be set for all monitored quantities included in thefunctions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X insetting names below equals S, P, Q, PF, F, IL1-2, UL1-2, UL12, I1, 2I0, U1 or 2U0.

Xmin: Minimum value for analog signal X set directly in applicable measuring unit.

Xmax: Maximum value for analog signal X.

XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.

Observe the related zero point clamping settings in Setting group N for CVMMXN.If measured value is below 5% of UBase and/or 5% of IBase calculated S, P, Q and PFwill be zero and these settings will override XZeroDb.

XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) orintegral deadband (Int deadband). The reporting interval is controlled by theparameter XDbRepInt.

XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and isreporting interval in seconds. Amplitude deadband is the setting value in % ofmeasuring range. Integral deadband setting is the integral area, that is, measured valuein % of measuring range multiplied by the time between two measured values.

XHiHiLim: High-high limit. Set in applicable measuring unit.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 335Application manual

Page 342: Railway application RER670 Version 2.2 IEC ... - ABB

XHiLim: High limit.

XLowLim: Low limit.

XLowLowLim: Low-low limit.

XLimHyst: Hysteresis value in % of range and is common for all limits.

All phase angles are presented in relation to defined reference channel. The parameterPhaseAngleRef defines the reference, see Section “Analog inputs”.

Calibration curvesIt is possible to calibrate the functions (CMMXU, VMMXU and VNMMXU) to getclass 0.5 presentations of currents and voltages. This is accomplished by amplitudeand angle compensation at 5, 30 and 100% of rated current and voltage. Thecompensation curve will have the characteristic for amplitude and anglecompensation of currents as shown in figure 141 (example). The first phase will beused as reference channel and compared with the curve for calculation of factors. Thefactors will then be used for all related channels.

IEC05000652 V2 EN

Figure 141: Calibration curves

Section 15 1MRK 506 375-UEN -Monitoring

336 Railway application RER670 2.2 IECApplication manual

Page 343: Railway application RER670 Version 2.2 IEC ... - ABB

15.1.4.1 Setting examples

Three setting examples, in connection to Measurement function (CVMMXN), areprovided:

• Measurement function (CVMMXN) application for a OHL• Measurement function (CVMMXN) application on the secondary side of a

transformer

For each of them detail explanation and final list of selected setting parameters valueswill be provided.

Several instances of each type of measurement function blocks areavailable in the IED. The actual reported values from the IED aredependent on the logic configuration made in PCM600.

Measurement function application for a 110kV OHLSingle line diagram for this application is given in figure 142:

110kV Busbar

110kV OHL

P Q

600/1 A

IEC16000124-1-en.vsdx

IED110 0,1kV

IEC16000124 V1 EN

Figure 142: Single line diagram for 110kV OHL application

In order to monitor, supervise and calibrate the active and reactive power as indicatedin figure 142 it is necessary to do the following:

1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRefusing PCM600 for analog input channels

2. Connect, in PCM600, measurement function to two-phase CT and VT inputs3. Set under General settings parameters for the Measurement function:

• general settings as shown in table 31.• level supervision of active power as shown in table 32.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 337Application manual

Page 344: Railway application RER670 Version 2.2 IEC ... - ABB

Table 31: General settings parameters for the Measurement function

Setting Short Description Selectedvalue

Comments

Operation Operation Off/On On Function must be On

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

UGenZeroDb Zero point clamping in % ofUbase

25 Set minimum voltage level to25%. Voltage below 25% will forceS, P and Q to zero.

IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%.Current below 3% will force S, Pand Q to zero.

UBase (set inGlobal base)

Base setting for voltage level inkV

110.00 Set rated OHL phase-to-phasevoltage

IBase (set inGlobal base)

Base setting for current level in A 600 Set rated primary CT current usedfor OHL

SBase (set inGlobal base)

Base setting for power level inMVA

66 Set rated apparent two-phasepower which correspond to 110kVand 600A

Table 32: Settings parameters for level supervision

Setting Short Description Selectedvalue

Comments

PMin Minimum value -100 Minimum expected load

PMax Maximum value 100 Maximum expected load

PZeroDb Zero point clamping in 0.001% ofrange

1000 Set zero point clamping to 0,66MW that is, 1% of 66 MW

PRepTyp Reporting type db Select amplitude deadbandsupervision

PDbRepInt Cycl: Report interval (s), Db: In %of range, Int Db: In %s

5 Set ±Δdb=1,3 MW that is, 2%(larger changes than 1,3 MW willbe reported)

PHiHiLim High High limit (physical value) 120 High alarm limit that is, extremeoverload alarm

PHiLim High limit (physical value) 100 High warning limit that is, overloadwarning

PLowLim Low limit (physical value) -100 Low warning limit. Not active

PLowLowlLim Low Low limit (physical value) -120 Low alarm limit. Not active

PLimHyst Hysteresis value in % of range(common for all limits)

2 Set ±Δ Hysteresis MW that is, 2%

Measurement function application for a power transformerSingle line diagram for this application is given in Figure 143.

Section 15 1MRK 506 375-UEN -Monitoring

338 Railway application RER670 2.2 IECApplication manual

Page 345: Railway application RER670 Version 2.2 IEC ... - ABB

110kV Busbar

200/1

15kV Busbar

600/5

P Q

8,0 MVA

110/15kV

UL1 & UL2

IEC16000125-1-en.vsdx

IED

15/0,1kV

IEC16000125 V1 EN

Figure 143: Single line diagram for transformer application

In order to measure the active and reactive power as indicated in figure 143, it isnecessary to do the following:

1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRefdata using PCM600 for analog input channels

2. Connect, in PCM600, measurement function to LV side CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in table

33.

The power P&Q measurement is needed towards busbar (not towards IED, as default).Proper inversion of current should be done in SMAI block for the current channels inorder to get correct direction of P&Q. Note that, in such case this SMAI block shallonly be used for the measurement functions.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 339Application manual

Page 346: Railway application RER670 Version 2.2 IEC ... - ABB

Table 33: General settings parameters for the Measurement function

Setting Short description Selectedvalue

Comment

Operation Operation Off/On On Function must be On

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

UGenZeroDb Zero point clamping in % ofUbase

25 Set minimum voltage level to 25%

IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%

UBase (set inGlobal base)

Base setting for voltage level inkV

15.00 Set LV side rated phase-to-phasevoltage

IBase (set inGlobal base)

Base setting for current level in A 533A Set transformer LV winding ratedcurrent

SBase (set inGlobal base)

Base setting for power level inMVA

8 Set rated apparent power of thetransformer

15.2 Gas medium supervision SSIMG

15.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation gas monitoring function SSIMG - 63

15.2.2 Application

Gas medium supervision (SSIMG) is used for monitoring the circuit breakercondition. Proper arc extinction by the compressed gas in the circuit breaker is veryimportant. When the pressure becomes too low compared to the required value, thecircuit breaker operation shall be blocked to minimize the risk of internal failure.Binary information based on the gas pressure in the circuit breaker is used as an inputsignal to the function. The function generates alarms based on the receivedinformation.

15.2.3 Setting guidelines

The parameters for Gas medium supervision SSIMG can be set via local HMI orProtection and Control Manager PCM600.

Operation: This is used to disable/enable the operation of gas medium supervision i.e.Off/On.

PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuitbreaker.

Section 15 1MRK 506 375-UEN -Monitoring

340 Railway application RER670 2.2 IECApplication manual

Page 347: Railway application RER670 Version 2.2 IEC ... - ABB

PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuitbreaker.

TempAlarmLimit: This is used to set the limit for a temperature alarm condition in thecircuit breaker.

TempLOLimit: This is used to set the limit for a temperature lockout condition in thecircuit breaker.

tPressureAlarm: This is used to set the time delay for a pressure alarm indication,given in s.

tPressureLO: This is used to set the time delay for a pressure lockout indication, givenin s.

tTempAlarm: This is used to set the time delay for a temperature alarm indication,given in s.

tTempLockOut: This is used to set the time delay for a temperature lockout indication,given in s.

tResetPressAlm: This is used for the pressure alarm indication to reset after a set timedelay in s.

tResetPressLO: This is used for the pressure lockout indication to reset after a set timedelay in s.

tResetTempLO: This is used for the temperature lockout indication to reset after a settime delay in s.

tResetTempAlm: This is used for the temperature alarm indication to reset after a settime delay in s.

15.3 Liquid medium supervision SSIML

15.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation liquid monitoring function SSIML - 71

15.3.2 Application

Liquid medium supervision (SSIML) is used for monitoring the transformers and tapchangers. When the level becomes too low compared to the required value, theoperation is blocked to minimize the risk of internal failures. Binary informationbased on the oil level in the transformer and the tap changer is used as input signals to

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 341Application manual

Page 348: Railway application RER670 Version 2.2 IEC ... - ABB

the function. In addition to that, the function generates alarms based on receivedinformation.

15.3.3 Setting guidelines

The parameters for Liquid medium supervision SSIML can be set via local HMI orProtection and Control Manager PCM600.

Operation: This is used to disable/enable the operation of liquid medium supervisioni.e. Off/On.

LevelAlmLimit: This is used to set the limit for a level alarm condition in thetransformer.

LevelLOLimit: This is used to set the limit for a level lockout condition in thetransformer.

TempAlarmLimit: This is used to set the limit for a temperature alarm condition in thetransformer.

TempLOLimit: This is used to set the limit for a temperature lockout condition in thetransformer.

tLevelAlarm: This is used to set the time delay for a level alarm indication, given in s.

tLevelLockOut: This is used to set the time delay for a level lockout indication, givenin s.

tTempAlarm: This is used to set the time delay for a temperature alarm indication,given in s.

tTempLockOut: This is used to set the time delay for a temperature lockout indication,given in s.

tResetLevelAlm: This is used for the level alarm indication to reset after a set timedelay in s.

tResetLevelLO: This is used for the level lockout indication to reset after a set timedelay in s.

tResetTempLO: This is used for the temperature lockout indication to reset after a settime delay in s.

tResetTempAlm: This is used for the temperature alarm indication to reset after a settime delay in s.

15.4 Breaker monitoring SSCBR

15.4.1 Identification

Section 15 1MRK 506 375-UEN -Monitoring

342 Railway application RER670 2.2 IECApplication manual

Page 349: Railway application RER670 Version 2.2 IEC ... - ABB

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Breaker monitoring SSCBR - -

15.4.2 Application

The circuit breaker maintenance is usually based on regular time intervals or thenumber of operations performed. This has some disadvantages because there could bea number of abnormal operations or few operations with high-level currents within thepredetermined maintenance interval. Hence, condition-based maintenancescheduling is an optimum solution in assessing the condition of circuit breakers.

Circuit breaker contact travel timeAuxiliary contacts provide information about the mechanical operation, opening timeand closing time of a breaker. Detecting an excessive traveling time is essential toindicate the need for maintenance of the circuit breaker mechanism. The excessivetravel time can be due to problems in the driving mechanism or failures of the contacts.

Circuit breaker statusMonitoring the breaker status ensures proper functioning of the features within theprotection relay such as breaker control, breaker failure and autoreclosing. Thebreaker status is monitored using breaker auxiliary contacts. The breaker status isindicated by the binary outputs. These signals indicate whether the circuit breaker isin an open, closed or error state.

Remaining life of circuit breakerEvery time the breaker operates, the circuit breaker life reduces due to wear. The wearin a breaker depends on the interrupted current. For breaker maintenance orreplacement at the right time, the remaining life of the breaker must be estimated. Theremaining life of a breaker can be estimated using the maintenance curve provided bythe circuit breaker manufacturer.

Circuit breaker manufacturers provide the number of make-break operations possibleat various interrupted currents. An example is shown in figure 144.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 343Application manual

Page 350: Railway application RER670 Version 2.2 IEC ... - ABB

Num

ber o

f mak

e-br

eak

oper

atio

ns (

n)

Interrupted current (kA)

P1

P2

100000

50000

20000

10000

2000

5000

1000

100

200

500

10

20

50

0.1 0.2 0.5 1 2 5 10 20 50 100

IEC12000623_1_en.vsd

IEC12000623 V1 EN

Figure 144: An example for estimating the remaining life of a circuit breaker

Calculation for estimating the remaining life

The graph shows that there are 10000 possible operations at the rated operating currentand 900 operations at 10 kA and 50 operations at rated fault current. Therefore, if theinterrupted current is 10 kA, one operation is equivalent to 10000/900 = 11 operationsat the rated current. It is assumed that prior to tripping, the remaining life of a breakeris 10000 operations. Remaining life calculation for three different interrupted currentconditions is explained below.

• Breaker interrupts at and below the rated operating current, that is, 2 kA, theremaining life of the CB is decreased by 1 operation and therefore, 9999operations remaining at the rated operating current.

• Breaker interrupts between rated operating current and rated fault current, that is,10 kA, one operation at 10kA is equivalent to 10000/900 = 11 operations at the

Section 15 1MRK 506 375-UEN -Monitoring

344 Railway application RER670 2.2 IECApplication manual

Page 351: Railway application RER670 Version 2.2 IEC ... - ABB

rated current. The remaining life of the CB would be (10000 – 10) = 9989 at therated operating current after one operation at 10 kA.

• Breaker interrupts at and above rated fault current, that is, 50 kA, one operationat 50 kA is equivalent to 10000/50 = 200 operations at the rated operating current.The remaining life of the CB would become (10000 – 200) = 9800 operations atthe rated operating current after one operation at 50 kA.

Accumulated energyMonitoring the contact erosion and interrupter wear has a direct influence on therequired maintenance frequency. Therefore, it is necessary to accurately estimate theerosion of the contacts and condition of interrupters using cumulative summation ofIy. The factor "y" depends on the type of circuit breaker. The energy values wereaccumulated using the current value and exponent factor for CB contact openingduration. When the next CB opening operation is started, the energy is accumulatedfrom the previous value. The accumulated energy value can be reset to initialaccumulation energy value by using the Reset accumulating energy input, RSTIPOW.

Circuit breaker operation cyclesRoutine breaker maintenance like lubricating breaker mechanism is based on thenumber of operations. A suitable threshold setting helps in preventive maintenance.This can also be used to indicate the requirement for oil sampling for dielectric testingin case of an oil circuit breaker.

Circuit breaker operation monitoringBy monitoring the activity of the number of operations, it is possible to calculate thenumber of days the breaker has been inactive. Long periods of inactivity degrade thereliability for the protection system.

Circuit breaker spring charge monitoringFor normal circuit breaker operation, the circuit breaker spring should be chargedwithin a specified time. Detecting a long spring charging time indicates the time forcircuit breaker maintenance. The last value of the spring charging time can be givenas a service value.

Circuit breaker gas pressure indicationFor proper arc extinction by the compressed gas in the circuit breaker, the pressure ofthe gas must be adequate. Binary input available from the pressure sensor is based onthe pressure levels inside the arc chamber. When the pressure becomes too lowcompared to the required value, the circuit breaker operation is blocked.

15.4.3 Setting guidelines

The breaker monitoring function is used to monitor different parameters of the circuitbreaker. The breaker requires maintenance when the number of operations hasreached a predefined value. For proper functioning of the circuit breaker, it is alsoessential to monitor the circuit breaker operation, spring charge indication or breaker

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 345Application manual

Page 352: Railway application RER670 Version 2.2 IEC ... - ABB

wear, travel time, number of operation cycles and accumulated energy during arcextinction.

15.4.3.1 Setting procedure on the IED

The parameters for breaker monitoring (SSCBR) can be set using the local HMI orProtection and Control Manager (PCM600).

Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in Global base values for settings function GBASVAL.

GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.

Operation: On or Off.

OpenTimeCorr: Correction factor for circuit breaker opening travel time.

CloseTimeCorr: Correction factor for circuit breaker closing travel time.

tTrOpenAlm: Setting of alarm level for opening travel time.

tTrCloseAlm: Setting of alarm level for closing travel time.

OperAlmLevel: Alarm limit for number of mechanical operations.

OperLOLevel: Lockout limit for number of mechanical operations.

CurrExponent: Current exponent setting for energy calculation. It varies for differenttypes of circuit breakers. This factor ranges from 0.5 to 3.0.

AccStopCurr: RMS current setting below which calculation of energy accumulationstops. It is given as a percentage of IBase.

ContTrCorr: Correction factor for time difference in auxiliary and main contacts'opening time.

AlmAccCurrPwr: Setting of alarm level for accumulated energy.

LOAccCurrPwr: Lockout limit setting for accumulated energy.

SpChAlmTime: Time delay for spring charging time alarm.

tDGasPresAlm: Time delay for gas pressure alarm.

tDGasPresLO: Time delay for gas pressure lockout.

DirCoef: Directional coefficient for circuit breaker life calculation.

RatedOperCurr: Rated operating current of the circuit breaker.

RatedFltCurr: Rated fault current of the circuit breaker.

OperNoRated: Number of operations possible at rated current.

Section 15 1MRK 506 375-UEN -Monitoring

346 Railway application RER670 2.2 IECApplication manual

Page 353: Railway application RER670 Version 2.2 IEC ... - ABB

OperNoFault: Number of operations possible at rated fault current.

CBLifeAlmLevel: Alarm level for circuit breaker remaining life.

AccSelCal: Selection between the method of calculation of accumulated energy.

OperTimeDelay: Time delay between change of status of trip output and start of maincontact separation.

15.5 Event function EVENT

15.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Event function EVENT

S00946 V1 EN

-

15.5.2 Application

When using a Substation Automation system with LON or SPA communication,time-tagged events can be sent at change or cyclically from the IED to the station level.These events are created from any available signal in the IED that is connected to theEvent function (EVENT). The EVENT function block is used for LON and SPAcommunication.

Analog, integer and double indication values are also transferred through the EVENTfunction.

15.5.3 Setting guidelines

The input parameters for the Event function (EVENT) can be set individually via thelocal HMI (Main Menu/Settings / IED Settings / Monitoring / Event Function) orvia the Parameter Setting Tool (PST).

EventMask (Ch_1 - 16)The inputs can be set individually as:

• NoEvents• OnSet, at pick-up of the signal• OnReset, at drop-out of the signal• OnChange, at both pick-up and drop-out of the signal• AutoDetect, the EVENT function makes the reporting decision (reporting criteria

for integers have no semantic, prefer to be set by the user)

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 347Application manual

Page 354: Railway application RER670 Version 2.2 IEC ... - ABB

LONChannelMask or SPAChannelMaskDefinition of which part of the event function block that shall generate events:

• Off• Channel 1-8• Channel 9-16• Channel 1-16

MinRepIntVal (1 - 16)A time interval between cyclic events can be set individually for each input channel.This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, thatis, no cyclic communication.

It is important to set the time interval for cyclic events in an optimizedway to minimize the load on the station bus.

15.6 Disturbance report DRPRDRE

15.6.1 IdentificationFunction description IEC 61850 identification IEC 60617

identificationANSI/IEEE C37.2device number

Disturbance report DRPRDRE - -

Disturbance report A1RADR - A4RADR - -

Disturbance report B1RBDR - B22RBDR - -

15.6.2 Application

To get fast, complete and reliable information about disturbances in the primary and/or in the secondary system it is very important to gather information on fault currents,voltages and events. It is also important having a continuous event-logging to be ableto monitor in an overview perspective. These tasks are accomplished by thedisturbance report function DRPRDRE and facilitate a better understanding of thepower system behavior and related primary and secondary equipment during and aftera disturbance. An analysis of the recorded data provides valuable information that canbe used to explain a disturbance, basis for change of IED setting plan, improveexisting equipment, and so on. This information can also be used in a longerperspective when planning for and designing new installations, that is, a disturbancerecording could be a part of Functional Analysis (FA).

Disturbance report DRPRDRE, always included in the IED, acquires sampled data ofall selected analog and binary signals connected to the function blocks that is,

Section 15 1MRK 506 375-UEN -Monitoring

348 Railway application RER670 2.2 IECApplication manual

Page 355: Railway application RER670 Version 2.2 IEC ... - ABB

• Maximum 30 external analog signals,• 10 internal derived analog signals, and• 352 binary signals

Disturbance report function is a common name for several functions; Indications(IND), Event recorder (ER), Event list (EL), Trip value recorder (TVR), Disturbancerecorder (DR) and Fault locator (FL).

Disturbance report function is characterized by great flexibility as far asconfiguration, starting conditions, recording times, and storage capacity areconcerned. Thus, disturbance report is not dependent on the operation of protectivefunctions, and it can record disturbances that were not discovered by protectivefunctions for one reason or another. Disturbance report can be used as an advancedstand-alone disturbance recorder.

Every disturbance report recording is saved in the IED. The same applies to all events,which are continuously saved in a ring-buffer. Local HMI can be used to getinformation about the recordings, and the disturbance report files may be uploaded inthe PCM600 using the Disturbance handling tool, for report reading or further analysis(using WaveWin, that can be found on the PCM600 installation CD). The user canalso upload disturbance report files using FTP or MMS (over 61850–8–1) clients.

If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder(record made and fault number) and the fault locator information are available. Thesame information is obtainable if IEC 60870-5-103 is used.

15.6.3 Setting guidelines

The setting parameters for the Disturbance report function DRPRDRE are set via thelocal HMI or PCM600.

It is possible to handle up to 40 analog and 352 binary signals, either internal signalsor signals coming from external inputs. The binary signals are identical in all functionsthat is, Disturbance recorder (DR), Event recorder (ER), Indication (IND), Trip valuerecorder (TVR) and Event list (EL) function.

User-defined names of binary and analog input signals is set using PCM600. Theanalog and binary signals appear with their user-defined names. The name is used inall related functions (Disturbance recorder (DR), Event recorder (ER), Indication(IND), Trip value recorder (TVR) and Event list (EL)).

Figure 145 shows the relations between Disturbance report, included functions andfunction blocks. Event list (EL), Event recorder (ER) and Indication (IND) usesinformation from the binary input function blocks (BxRBDR). Trip value recorder(TVR) uses analog information from the analog input function blocks (AxRADR),which is used by Fault locator (FL) after estimation by Trip Value Recorder (TVR).Disturbance report function acquires information from both AxRADR and BxRBDR.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 349Application manual

Page 356: Railway application RER670 Version 2.2 IEC ... - ABB

Trip value rec Fault locator

Event list

Event recorder

Indications

Disturbancerecorder

Disturbance Report

Binary signals

Analog signals

DRPRDRE FL

IEC09000336-3-en.vsdx

AxRADR

BxRBDR

IEC09000336 V3 EN

Figure 145: Disturbance report functions and related function blocks

For Disturbance report function there are a number of settings which also influencesthe sub-functions.

Three LED indications placed above the LCD screen makes it possible to get quickstatus information about the IED.

Green LED:

Steady light In Service

Flashing light Internal failure

Dark No power supply

Yellow LED:

Steady light Triggered on binary signal N with SetLEDx = Start (or Start andTrip)

Flashing light The IED is in test mode

Red LED:

Steady light Triggered on binary signal N with SetLEDx = Trip (or Start andTrip)

Flashing The IED is in configuration mode

Section 15 1MRK 506 375-UEN -Monitoring

350 Railway application RER670 2.2 IECApplication manual

Page 357: Railway application RER670 Version 2.2 IEC ... - ABB

OperationThe operation of Disturbance report function DRPRDRE has to be set On or Off. If Offis selected, note that no disturbance report is registered, and none sub-function willoperate (the only general parameter that influences Event list (EL)).

Operation = Off:

• Disturbance reports are not stored.• LED information (yellow - start, red - trip) is not stored or changed.

Operation = On:

• Disturbance reports are stored, disturbance data can be read from the local HMIand from a PC for example using PCM600.

• LED information (yellow - start, red - trip) is stored.

Every recording will get a number (0 to 999) which is used as identifier (local HMI,disturbance handling tool and IEC 61850). An alternative recording identification isdate, time and sequence number. The sequence number is automatically increased byone for each new recording and is reset to zero at midnight. The maximum number ofrecordings stored in the IED is 100. The oldest recording will be overwritten when anew recording arrives (FIFO).

To be able to delete disturbance records, Operation parameter has tobe On.

The maximum number of recordings depend on each recordings totalrecording time. Long recording time will reduce the number ofrecordings to less than 100.

The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of diskspace.

15.6.3.1 Recording times

The different recording times for Disturbance report are set (the pre-fault time, post-fault time, and limit time). These recording times affect all sub-functions more or lessbut not the Event list (EL) function.

Prefault recording time (PreFaultRecT) is the recording time before the starting pointof the disturbance. The setting should be at least 0.1 s to ensure enough samples for theestimation of pre-fault values in the Trip value recorder (TVR) function.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 351Application manual

Page 358: Railway application RER670 Version 2.2 IEC ... - ABB

Postfault recording time (PostFaultRecT) is the maximum recording time after thedisappearance of the trig-signal (does not influence the Trip value recorder (TVR)function).

Recording time limit (TimeLimit) is the maximum recording time after trig. Theparameter limits the recording time if some trigging condition (fault-time) is very longor permanently set (does not influence the Trip value recorder (TVR) function).

Operation in test modeIf the IED is in test mode and OpModeTest = Off. Disturbance report function does notsave any recordings and no LED information is displayed.

If the IED is in test mode and OpModeTest = On. Disturbance report function worksin normal mode and the status is indicated in the saved recording.

Post RetriggerDisturbance report function does not automatically respond to any new trig conditionduring a recording, after all signals set as trigger signals have been reset. However,under certain circumstances the fault condition may reoccur during the post-faultrecording, for instance by automatic reclosing to a still faulty power line.

In order to capture the new disturbance it is possible to allow retriggering (PostRetrig= On) during the post-fault time. In this case a new, complete recording will start and,during a period, run in parallel with the initial recording.

When the retrig parameter is disabled (PostRetrig = Off), a new recording will not startuntil the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a new trigoccurs during the post-fault period and lasts longer than the proceeding recording anew complete recording will be started.

Disturbance report function can handle a maximum of 3 simultaneous disturbancerecordings.

15.6.3.2 Binary input signals

Up to 352 binary signals can be selected among internal logical and binary inputsignals. The configuration tool is used to configure the signals.

For each of the 352 signals, it is also possible to select if the signal is to be used as atrigger for the start of the Disturbance report and if the trigger should be activated onpositive (1) or negative (0) slope.

OperationN: Disturbance report may trig for binary input N (On) or not (Off).

TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary inputN.

Func103N: Function type number (0-255) for binary input N according toIEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection, 176:transformer differential protection and 192: line differential protection.

Section 15 1MRK 506 375-UEN -Monitoring

352 Railway application RER670 2.2 IECApplication manual

Page 359: Railway application RER670 Version 2.2 IEC ... - ABB

Info103N: Information number (0-255) for binary input N according toIEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.

See also description in the chapter IEC 60870-5-103.

15.6.3.3 Analog input signals

Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.

For retrieving remote data from LDCM module, the Disturbancereport function should be connected to a 8 ms SMAI function block ifthis is the only intended use for the remote data.

The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).

If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

NomValueM: Nominal value for input M.

OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).

OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relativenominal value for analog input M in percent of nominal value.

15.6.3.4 Sub-function parameters

All functions are in operation as long as Disturbance report is in operation.

IndicationsIndicationMaN: Indication mask for binary input N. If set (Show), a status change ofthat particular input, will be fetched and shown in the disturbance summary on localHMI. If not set (Hide), status change will not be indicated.

SetLEDN: Set red LED on local HMI in front of the IED if binary input N changesstatus.

Disturbance recorderOperationM: Analog channel M is to be recorded by the disturbance recorder (On) ornot (Off).

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 353Application manual

Page 360: Railway application RER670 Version 2.2 IEC ... - ABB

If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

Event recorderEvent recorder (ER) function has no dedicated parameters.

Trip value recorderZeroAngleRef: The parameter defines which analog signal that will be used as phaseangle reference for all other analog input signals. This signal will also be used forfrequency measurement and the measured frequency is used when calculating tripvalues. It is suggested to point out a sampled voltage input signal, for example, a lineor busbar phase voltage (channel 1-30).

Event listEvent list (EL) (SOE) function has no dedicated parameters.

15.6.3.5 Consideration

The density of recording equipment in power systems is increasing, since the numberof modern IEDs, where recorders are included, is increasing. This leads to a vastnumber of recordings at every single disturbance and a lot of information has to behandled if the recording functions do not have proper settings. The goal is to optimizethe settings in each IED to be able to capture just valuable disturbances and tomaximize the number that is possible to save in the IED.

The recording time should not be longer than necessary (PostFaultrecT andTimeLimit).

• Should the function record faults only for the protected object or cover more?• How long is the longest expected fault clearing time?• Is it necessary to include reclosure in the recording or should a persistent fault

generate a second recording (PostRetrig)?

Minimize the number of recordings:

• Binary signals: Use only relevant signals to start the recording that is, protectiontrip, carrier receive and/or start signals.

• Analog signals: The level triggering should be used with great care, sinceunfortunate settings will cause enormously number of recordings. If neverthelessanalog input triggering is used, chose settings by a sufficient margin from normaloperation values. Phase voltages are not recommended for trigging.

There is a risk of flash wear out if the disturbance report triggers toooften.

Section 15 1MRK 506 375-UEN -Monitoring

354 Railway application RER670 2.2 IECApplication manual

Page 361: Railway application RER670 Version 2.2 IEC ... - ABB

Remember that values of parameters set elsewhere are linked to the information on areport. Such parameters are, for example, station and object identifiers, CT and VTratios.

15.7 Logical signal status report BINSTATREP

15.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logical signal status report BINSTATREP - -

15.7.2 Application

The Logical signal status report (BINSTATREP) function makes it possible to pollsignals from various other function blocks.

BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs andcan be read from the local HMI or via SPA communication.

When an input is set, the respective output is set for a user defined time. If the inputsignal remains set for a longer period, the output will remain set until the input signalresets.

t t

INPUTn

OUTPUTn

IEC09000732-1-en.vsdIEC09000732 V1 EN

Figure 146: BINSTATREP logical diagram

15.7.3 Setting guidelines

The pulse time t is the only setting for the Logical signal status report(BINSTATREP). Each output can be set or reset individually, but the pulse time willbe the same for all outputs in the entire BINSTATREP function.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 355Application manual

Page 362: Railway application RER670 Version 2.2 IEC ... - ABB

15.8 Limit counter L4UFCNT

15.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Limit counter L4UFCNT -

15.8.2 Application

Limit counter (L4UFCNT) is intended for applications where positive and/or negativeflanks on a binary signal need to be counted.

The limit counter provides four independent limits to be checked against theaccumulated counted value. The four limit reach indication outputs can be utilized toinitiate proceeding actions. The output indicators remain high until the reset of thefunction.

It is also possible to initiate the counter from a non-zero value by resetting the functionto the wanted initial value provided as a setting.

If applicable, the counter can be set to stop or rollover to zero and continue countingafter reaching the maximum count value. The steady overflow output flag indicatesthe next count after reaching the maximum count value. It is also possible to set thecounter to rollover and indicate the overflow as a pulse, which lasts up to the first countafter rolling over to zero. In this case, periodic pulses will be generated at multipleoverflow of the function.

15.8.3 Setting guidelines

The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.

15.9 Running hour-meter TEILGAPC

15.9.1 IdentificationFunction Description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2 devicenumber

Running hour-meter TEILGAPC - -

Section 15 1MRK 506 375-UEN -Monitoring

356 Railway application RER670 2.2 IECApplication manual

Page 363: Railway application RER670 Version 2.2 IEC ... - ABB

15.9.2 Application

The function is used for user-defined logics and it can also be used for differentpurposes internally in the IED. An application example is to accumulate the totalrunning/energized time of the generator, transformer, reactor, capacitor bank or evenline.

Settable time limits for warning and alarm are provided. The time limit for overflowindication is fixed to 99999.9 hours. At overflow the accumulated time resets and theaccumulation starts from zero again.

15.9.3 Setting guidelines

The settings tAlarm and tWarning are user settable limits defined in hours. Theachievable resolution of the settings is 0.1 hours (6 minutes).

tAlarm and tWarning are independent settings, that is, there is nocheck if tAlarm > tWarning.

The limit for the overflow supervision is fixed at 99999.9 hours.

The setting tAddToTime is a user settable time parameter in hours.

15.10 Fault locator RWRFLO

15.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fault locator RWRFLO -

15.10.2 Application

The main purpose of line protection and monitoring IEDs is to provide fast, selectiveand reliable operation regarding faults on a protected line section.

Information on distance-to-fault is more important for those involved in operation andmaintenance. Reliable information on fault location greatly decreases the downtimeof protected lines, and increases the total availability of the power system.

Transmission lines are typically made of single type of conductor. If a transmissionline is made of more than one section, the line parameters are different for eachsection, and the set-up cannot be considered as one single line. Fault locationalgorithms for a single line will thus not meet accuracy requirements in railway supply

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 357Application manual

Page 364: Railway application RER670 Version 2.2 IEC ... - ABB

system. This can be explained by considering an example of transmission line with 3sections as shown in the figure 147:

Source A

1 2 3

RFLO

Source B

IEC15000299-1-en.vsdx

IEC15000299 V1 EN

Figure 147: Single line diagram with three line sections

For example, consider a case where the line angle of line 1 is 70 degrees, line 2 is 55degrees and line 3 is 45 degrees. The area that remains between line sections 1, 2, 3 andthe sum of the three line sections denotes inaccuracy (see figure 148). Thus summingup of the line parameters and considering it as one line should not be done for faultlocation algorithm.

R(Ohm)

X(O

hm

)

1+2+

3

2

1

3

IEC15000300-1-en.vsdx

IEC15000300 V1 EN

Figure 148: R-X diagram showing positive sequence impedances of three linesections

The fault locator (RWRFLO) is started with the input CALCDIST to which trip signalsindicating in-line faults are connected, typically distance protection zone 1 andaccelerating zone or the line differential protection. Disturbance report must also be

Section 15 1MRK 506 375-UEN -Monitoring

358 Railway application RER670 2.2 IECApplication manual

Page 365: Railway application RER670 Version 2.2 IEC ... - ABB

started for the same faults since the function uses pre-fault and fault information fromthe trip value recorder function (TVR).

Besides this, the function must be informed about faulted phases for correct loopselection (phase-selective outputs from distance protections, directional over-currentprotection and so on). The following loops are used for different types of faults:

• For two-phase faults: loop L1-L2• For phase-to-earth faults: L1N, L2N : phase-to-earth loop

RWRFLO function indicates distance-to-faults as a percentage of the line length andin kilometres. The calculated distance-to-fault is stored together with the recordeddisturbances. Information can be read on the local HMI or uploaded to PCM600. Isalso available on the station bus according to IEC 61850-8-1.

Distance-to-fault can be recalculated on the local HMI by using the measuringalgorithm for different fault loops.

15.10.3 Setting guidelines

In RWRFLO, the setting NrOfSections is set according to the number of sectionsavailable in the transmission line. The maximum number of sections in the faultlocator is ten.

The setting parameters are:

LineLength1 Set with length of section 1 in km

RL1 Set with positive sequence resistance of section 1 per phase

XL1 Set with positive sequence reactance of section 1 per phase

REOverRL1 Set with ratio of RE by RL of section 1, this can be derived from positive and zerosequences impedances as:

1*2

1011

RL

RLRREOverRL

IECEQUATION15082 V1 EN

Where R01 is zero sequence resistance of section 1 per phase.

XEOverXL1 Set with ratio of XE by XL of section 1, this can be derived from positive and zerosequences impedances as:

1*2

1011

XL

XLXXEOverXL

IECEQUATION15083 V1 EN

Where X01 is zero sequence reactance of section 1 per phase.

The settings are set in the same way for line sections 2, 3 and so on.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 359Application manual

Page 366: Railway application RER670 Version 2.2 IEC ... - ABB

15.10.3.1 Setting example

Consider a 110kV/16.7Hz system with three transmission line sections (see Figure149).

Source A

1 2 3

RFLO

Source B

IEC15000299-1-en.vsdx

IEC15000299 V1 EN

Figure 149: Single line diagram with three line sections

RWRFLO function should set for the NrOfSections. Since number of transmissionline sections is three, the NrOfSections should also be set to three (3). Table 34provides the system line specifications for three transmission lines.

Table 34: Line specifications for three transmission line sections

Parameter Line section 1 Line section 2 Line section 3LineLength(km) 4.8 40.3 18.2

RL Positive sequenceresistance (Ohm/Ph.)

RL1 = 0.575 RL2= 11.122 RL3= 5.609

XL Positive sequencereactance (Ohm/Ph.)

XL1 = 1.206 XL2= 10.034 XL3= 4.765

R0 Zero sequenceresistance (Ohm/Ph.)

R01 = 0.543 R02 = 8.293 R03 = 3.752

X0 Zero sequencereactance (Ohm/Ph.)

X01 = 1.284 X02 = 12.429 X03 = 6.858

Setting related to line section 1

1*2

1011

RL

RLRREOverRL

IECEQUATION15082 V1 EN (Equation 72)

REOverRL1 = The positive sequence resistance. REOverRL1 should be set as-0.02783.

1*2

1011

XL

XLXXEOverXL

IECEQUATION15083 V1 EN (Equation 73)

XEOverXL1 = The positive sequence reactance. REOverRL1 should be set as 0.0323.

Section 15 1MRK 506 375-UEN -Monitoring

360 Railway application RER670 2.2 IECApplication manual

Page 367: Railway application RER670 Version 2.2 IEC ... - ABB

Setting related to line section 2

2*2

2022

RL

RLRREOverRL

IECEQUATION15112 V1 EN (Equation 74)

REOverRL2 = The positive sequence resistance. REOverRL2 should be set as -0.1272.

2*2

2022

XL

XLXXEOverXL

IECEQUATION15113 V1 EN (Equation 75)

XEOverXL2 = The positive sequence reactance. REOverRL2 should be set as 0.1193.

Setting related to line section 3

3*2

3033

RL

RLRREOverRL

IECEQUATION15114 V1 EN (Equation 76)

REOverRL3 = The positive sequence resistance. REOverRL3 should be set as-0.16554.

3*2

3033

XL

XLXXEOverXL

IECEQUATION15115 V1 EN (Equation 77)

XEOverXL3 = The positive sequence reactance. REOverRL3 should be set as 0.219.

1MRK 506 375-UEN - Section 15Monitoring

Railway application RER670 2.2 IEC 361Application manual

Page 368: Railway application RER670 Version 2.2 IEC ... - ABB

362

Page 369: Railway application RER670 Version 2.2 IEC ... - ABB

Section 16 Metering

16.1 Pulse-counter logic PCFCNT

16.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Pulse-counter logic PCFCNT

S00947 V1 EN

-

16.1.2 Application

Pulse-counter logic (PCFCNT) function counts externally generated binary pulses,for instance pulses coming from an external energy meter, for calculation of energyconsumption values. The pulses are captured by the binary input module (BIM), andread by the PCFCNT function. The number of pulses in the counter is then reported viathe station bus to the substation automation system or read via the station monitoringsystem as a service value. When using IEC 61850–8–1, a scaled service value isavailable over the station bus.

The normal use for this function is the counting of energy pulses from external energymeters. An optional number of inputs from an arbitrary input module in IED can beused for this purpose with a frequency of up to 40 Hz. The pulse-counter logicPCFCNT can also be used as a general purpose counter.

16.1.3 Setting guidelines

Parameters that can be set individually for each pulse counter from PCM600:

• Operation: Off/On• tReporting: 0-3600s• EventMask: NoEvents/ReportEvents

Configuration of inputs and outputs of PCFCNT is made via PCM600.

1MRK 506 375-UEN - Section 16Metering

Railway application RER670 2.2 IEC 363Application manual

Page 370: Railway application RER670 Version 2.2 IEC ... - ABB

On the Binary input module (BIM), the debounce filter default time is set to 1 ms, thatis, the counter suppresses pulses with a pulse length less than 1 ms. The inputoscillation blocking frequency is preset to 40 Hz meaning that the counter detects theinput to oscillate if the input frequency is greater than 40 Hz. Oscillation suppressionis released at 30 Hz. Block/release values for oscillation can be changed on the localHMI and PCM600 under Main menu/Configuration/I/O modules.

The setting is common for all input channels on BIM, that is, if limitchanges are made for inputs not connected to the pulse counter, thesetting also influences the inputs on the same board used for pulsecounting.

16.2 Function for energy calculation and demand handlingETPMMTR

16.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Function for energy calculation anddemand handling

ETPMMTR W_Varh -

16.2.2 Application

Energy calculation and demand handling function (ETPMMTR) is intended forstatistics of the forward and reverse active and reactive energy. It has a high accuracybasically given by the measurements function (CVMMXN). This function has a sitecalibration possibility to further increase the total accuracy.

The function is connected to the instantaneous outputs of (CVMMXN) as shown infigure 150.

Section 16 1MRK 506 375-UEN -Metering

364 Railway application RER670 2.2 IECApplication manual

Page 371: Railway application RER670 Version 2.2 IEC ... - ABB

CVMMXN

P_INST

Q_INST

ETPMMTR

P

Q

RSTACC

RSTDMD

STARTACC

STOPACC

IEC13000190-2-en.vsdx

IEC13000190 V2 EN

Figure 150: Connection of energy calculation and demand handling functionETPMMTR to the measurements function (CVMMXN)

The energy values can be read through communication in MWh and MVArh inmonitoring tool of PCM600 and/or alternatively the values can be presented on thelocal HMI. The local HMI graphical display is configured with PCM600 GraphicalDisplay Editor tool (GDE) with a measuring value which is selected to the active andreactive component as preferred. Also all Accumulated Active Forward, ActiveReverse, Reactive Forward and Reactive Reverse energy values can be presented.

Maximum demand values are presented in MWh or MVArh in the same way.

Alternatively, the energy values can be presented with use of the pulse countersfunction (PCGGIO). The output energy values are scaled with the pulse output settingvalues EAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERVAccPlsQty of theenergy metering function and then the pulse counter can be set-up to present thecorrect values by scaling in this function. Pulse counter values can then be presentedon the local HMI in the same way and/or sent to the SA (Substation Automation)system through communication where the total energy then is calculated bysummation of the energy pulses. This principle is good for very high values of energyas the saturation of numbers else will limit energy integration to about one year with50 kV and 3000 A. After that the accumulation will start on zero again.

16.2.3 Setting guidelines

The parameters are set via the local HMI or PCM600.

The following settings can be done for the energy calculation and demand handlingfunction ETPMMTR:

GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.

Operation: Off/On

1MRK 506 375-UEN - Section 16Metering

Railway application RER670 2.2 IEC 365Application manual

Page 372: Railway application RER670 Version 2.2 IEC ... - ABB

EnaAcc: Off/On is used to switch the accumulation of energy on and off.

tEnergy: Time interval when energy is measured.

tEnergyOnPls: gives the pulse length ON time of the pulse. It should be at least 100ms when connected to the Pulse counter function block. Typical value can be 100 ms.

tEnergyOffPls: gives the OFF time between pulses. Typical value can be 100 ms.

EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It should beselected together with the setting of the Pulse counter (PCGGIO) settings to give thecorrect total pulse value.

ERFAccPlsQty and ERVAccPlsQty : gives the MVArh value in each pulse. It shouldbe selected together with the setting of the Pulse counter (PCGGIO) settings to givethe correct total pulse value.

For the advanced user there are a number of settings for direction, zero clamping, maxlimit, and so on. Normally, the default values are suitable for these parameters.

Section 16 1MRK 506 375-UEN -Metering

366 Railway application RER670 2.2 IECApplication manual

Page 373: Railway application RER670 Version 2.2 IEC ... - ABB

Section 17 Ethernet-based communication

17.1 Access point

17.1.1 Application

The access points are used to connect the IED to the communication buses (like thestation bus) that use communication protocols. The access point can be used for singleand redundant data communication. The access points are also used forcommunication with the merging units and for time synchronization using PrecisionTime Protocol (PTP).

17.1.2 Setting guidelines

The physical ports allocated to access points 2–6 have to be added inthe hardware tool in PCM600 before the access points can beconfigured. The factory setting only includes the physical portsallocated to the front port and access point 1.

The settings for the access points are configured using the Ethernet configuration tool(ECT) in PCM600.

The access point is activated if the Operation checkbox is checked for the respectiveaccess point and a partial or common write to IED is performed.

To increase security, it is recommended to deactivate the access pointwhen it is not in use.

Redundancy and PTP cannot be set for the front port (Access point 0) as redundantcommunication and PTP are only available for the rear optical Ethernet ports.

Subnetwork shows the SCL subnetwork to which the access point is connected. Thiscolumn shows the SCL subnetworks available in the PCM600 project. SCLsubnetworks can be created/deleted in the Subnetworks tab of IEC 61850Configuration tool in PCM600.

When saving the ECT configuration after selecting a subnetwork,ECT creates the access point in the SCL model. Unselecting thesubnetwork removes the access point from the SCL model. Thiscolumn is editable for IEC61850 Ed2 IEDs and not editable for

1MRK 506 375-UEN - Section 17Ethernet-based communication

Railway application RER670 2.2 IEC 367Application manual

Page 374: Railway application RER670 Version 2.2 IEC ... - ABB

IEC61850 Ed1 IEDs because in IEC61850 Ed1 only one access pointcan be modelled in SCL.

The IP address can be set in IP address. ECT validates the value, the access pointshave to be on separate subnetworks.

The subnetwork mask can be set in Subnet mask. This field will be updated to the SCLmodel based on the Subnetwork selection.

To select which communication protocols can be run on the respective access points,check or uncheck the check box for the relevant protocol. The protocols are notactivated/deactivated in ECT, only filtered for the specific access point. Forinformation on how to activate the individual communication protocols, see thecommunication protocol chapters.

To increase security it is recommended to uncheck protocols that arenot used on the access point.

The default gateway can be selected by entering the IP address in Default gateway.The default gateway is the router that is used to communicate with the devices in theother subnetwork. By default this is set to 0.0.0.0 which means that no default gatewayis selected. ECT validates the entered value, but the default gateway has to be in thesame subnetwork as the access point. The default gateway is the router that is beingused as default, that is when no route has been set up for the destination. Ifcommunication with a device in another subnetwork is needed, a route has to be set up.For more information on routes, see the Routes chapter in the Technical manual andthe Application manual.

DHCP can be activated for the front port from the LHMI in Main menu/Configuration/Communication/Ethernet configuration/Front port/DHCP:1

17.2 Redundant communication

17.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 62439-3 Parallel redundancyprotocol

PRP - -

IEC 62439-3 High-availability seamlessredundancy

HSR - -

Access point diagnostic for redundantEthernet ports

RCHLCCH - -

Section 17 1MRK 506 375-UEN -Ethernet-based communication

368 Railway application RER670 2.2 IECApplication manual

Page 375: Railway application RER670 Version 2.2 IEC ... - ABB

17.2.2 Application

Dynamic access point diagnostic (RCHLCCH) is used to supervise and assureredundant Ethernet communication over two channels. This will secure data transfereven though one communication channel might not be available for some reason

Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy(HSR) provides redundant communication over station bus running the availablecommunication protocols. The redundant communication uses two Ethernet ports.

IEC09000758-4-en.vsd

Switch A

AP1 PhyPortB PhyPortA

AP1 PhyPortA PhyPortB

AP1

PhyPortB PhyPortA

AP1

PhyPortA PhyPortB

Switch B

Device 1 Device 2

Device 3 Device 4

IEC09000758 V4 EN

Figure 151: Parallel Redundancy Protocol (PRP)

1MRK 506 375-UEN - Section 17Ethernet-based communication

Railway application RER670 2.2 IEC 369Application manual

Page 376: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000038-1-en.vsdx

AP1 PhyPortB PhyPortA

AP1 PhyPortA PhyPortB

AP1

PhyPortA PhyPortB

AP1

PhyPortB PhyPortA

Device 1 Device 2

Device 3 Device 4

IEC16000038 V1 EN

Figure 152: High-availability Seamless Redundancy (HSR)

17.2.3 Setting guidelines

Redundant communication is configured with the Ethernet configuration tool inPCM600.

Redundancy: redundant communication is activated when the parameter is set toPRP-0, PRP-1 or HSR. The settings for the next access point will be hidden andPhyPortB will show the second port information. Redundant communication isactivated after a common write to IED is done.

PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-networks. PRP-1 and HSR can be combined in a mixed network.

If the access point is not taken into operation, the write option in EthernetConfiguration Tool can be used to activate the access point.

Section 17 1MRK 506 375-UEN -Ethernet-based communication

370 Railway application RER670 2.2 IECApplication manual

Page 377: Railway application RER670 Version 2.2 IEC ... - ABB

IEC16000039-1-en.vsdx

IEC16000039 V1 EN

Figure 153: ECT screen with Redundancy set to PRP-1 on Access point 1 andHSR Access point 3

17.3 Merging unit

17.3.1 Application

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED tocommunicate with devices providing measured values in digital format, commonlyknown as Merging Units (MU). The rear access points are used for thecommunication.

The merging units (MU) are called so because they can gather analog values from oneor more measuring transformers, sample the data and send the data over process busto other clients (or subscribers) in the system. Some merging units are able to get datafrom classical measuring transformers, others from non-conventional measuringtransducers and yet others can pick up data from both types.

When configuring RER670 for 9-2LE streams in a 16.7Hz system, theIED shall be set to 16.7Hz and the MU to 50Hz (4kHz sampling).

1MRK 506 375-UEN - Section 17Ethernet-based communication

Railway application RER670 2.2 IEC 371Application manual

Page 378: Railway application RER670 Version 2.2 IEC ... - ABB

IEC17000044-1-en.vsdx

IEC17000044 V1 EN

Figure 154: Merging unit

17.3.2 Setting guidelines

For information on the merging unit setting guidelines, see section IEC/UCA61850-9-2LE communication protocol.

17.4 Routes

17.4.1 Application

Setting up a route enables communication to a device that is located in anothersubnetwork. Routing is used when the destination device is not in the samesubnetwork as the default gateway.

The route specifies that when a package is sent to the destination device it should besent through the selected router. If no route is specified the source device will not findthe destination device.

17.4.2 Setting guidelines

Routes are configured using the Ethernet configuration tool in PCM600.

Operation for the route can be set to On/Off by checking and unchecking the check-box in the operation column.

Gateway specifies the address of the gateway.

Destination specifies the destination.

Destination subnet mask specifies the subnetwork mask of the destination.

Section 17 1MRK 506 375-UEN -Ethernet-based communication

372 Railway application RER670 2.2 IECApplication manual

Page 379: Railway application RER670 Version 2.2 IEC ... - ABB

Section 18 Station communication

18.1 Communication protocols

Each IED is provided with several communication interfaces enabling it to connect toone or many substation level systems or equipment, either on the SubstationAutomation (SA) bus or Substation Monitoring (SM) bus.

Available communication protocols are:

• IEC 61850-8-1 communication protocol• IEC/UCA 61850-9-2LE communication protocol• LON communication protocol• SPA communication protocol• IEC 60870-5-103 communication protocol• DNP 3.0 communication protocol

Several protocols can be combined in the same IED.

18.2 IEC 61850-8-1 communication protocol

18.2.1 Application IEC 61850-8-1

IEC 61850-8-1 communication protocol allows vertical communication to HSIclients and allows horizontal communication between two or more intelligentelectronic devices (IEDs) from one or several vendors to exchange information and touse it in the performance of their functions and for correct co-operation.

GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard, allows the IEDs to communicate state and control information amongstthemselves, using a publish-subscribe mechanism. That is, upon detecting an event,the IED(s) use a multi-cast transmission to notify those devices that have registered toreceive the data. An IED can, by publishing a GOOSE message, report its status. It canalso request a control action to be directed at any device in the network.

Figure 155 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1specifies only the interface to the substation LAN. The LAN itself is left to the systemintegrator.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 373Application manual

Page 380: Railway application RER670 Version 2.2 IEC ... - ABB

KIOSK 2 KIOSK 3

Station HSIBase System

EngineeringWorkstation

SMSGateway

Printer

CC

IEC09000135_en.vsd

KIOSK 1

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IEC09000135 V1 EN

Figure 155: SA system with IEC 61850–8–1

Figure156 shows the GOOSE peer-to-peer communication.

Control Protection Control ProtectionControl and protection

GOOSE

en05000734.vsd

Station HSIMicroSCADA

Gateway

IEDA

IEDA

IEDA

IEDA

IEDA

IEC05000734 V1 EN

Figure 156: Example of a broadcasted GOOSE message

Section 18 1MRK 506 375-UEN -Station communication

374 Railway application RER670 2.2 IECApplication manual

Page 381: Railway application RER670 Version 2.2 IEC ... - ABB

18.2.2 Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:

Operation: User can set IEC 61850 communication to On or Off.

GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sentand received. This is only valid for Edition 1 and can be ignored if Edition 2 is used.For Edition 2, the Ethernet link selection is done with the Ethernet Configuration Tool(ECT) in PCM600.

18.2.3 Horizontal communication via GOOSE

18.2.3.1 Sending data

In addition to the data object and data attributes of the logical nodes, it is possible tosend the outputs of the function blocks using the generic communication blocks. Theoutputs of this function can be set in a dataset and be sent in a GOOSE Control Blockto other subscriber IEDs. There are different function blocks for different type ofsending data.

Generic communication function for Single Point indication SPGAPC,SP16GAPC

ApplicationGeneric communication function for Single Point Value (SPGAPC) function is usedto send one single logical output to other systems or equipment in the substation.SP16GAPC can be used to send up to 16 single point values from the applicationfunctions running in the same cycle time. SPGAPC has one visible input andSPGAPC16 has 16 visible inputs that should be connected in the ACT tool.

Setting guidelinesThere are no settings available for the user for SPGAPC.

Generic communication function for Measured Value MVGAPC

ApplicationGeneric communication function for measured values (MVGAPC) function is used tosend the instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to ananalog value and to permit measurement supervision on that value.

Setting guidelinesThe settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband forthe monitored signal. Values within the zero deadband are considered as zero.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 375Application manual

Page 382: Railway application RER670 Version 2.2 IEC ... - ABB

The high and low limit settings provides limits for the high-high-, high, normal, lowand low-low ranges of the measured value. The actual range of the measured value isshown on the range output of MVGAPC function block. When a Measured valueexpander block (RANGE_XP) is connected to the range output, the logical outputs ofthe RANGE_XP are changed accordingly.

18.2.3.2 Receiving data

The GOOSE data must be received at function blocks. There are different GOOSEreceiving function blocks depending on the type of the received data. Refer to theEngineering manual for more information about how to configure GOOSE.

Function block type Data TypeGOOSEBINRCV 16 single point

GOOSEINTLKRCV 2 single points16 double points

GOOSEDPRCV Double point

GOOSEINTRCV Integer

GOOSEMVRCV Analog value

GOOSESPRCV Single point

GOOSEXLNRCV Switch status

ApplicationThe GOOSE receive function blocks are used to receive subscribed data from theGOOSE protocol. The validity of the data value is exposed as outputs of the functionblock as well as the validity of the communication. It is recommended to use theseoutputs to ensure that only valid data is handled on the subscriber IED. An examplecould be to control the external reservation before operating on a bay. In the figurebelow, the GOOSESPRCV is used to receive the status of the bay reservation. Thevalidity of the received data is used in additional logic to guarantee that the value hasgood quality before operation on that bay.

GOOSESPRCV

Block Spout DataValid CommValid Test

AND AND

Input1 outInput2 NoputInput3Input4

Input1 outInput2 NoputInput3Input4

Ext_Res_OK_To_Operate

IEC16000082=1=en.vsdIEC16000082 V1 EN

Figure 157: GOOSESPRCV and AND function blocks - checking the validity ofthe received data

Section 18 1MRK 506 375-UEN -Station communication

376 Railway application RER670 2.2 IECApplication manual

Page 383: Railway application RER670 Version 2.2 IEC ... - ABB

18.3 IEC/UCA 61850-9-2LE communication protocol

18.3.1 Introduction

Every IED can be provided with communication interfaces enabling it to connect tothe process buses in order to get data from analog data acquisition units close to theprocess (primary apparatus), commonly known as Merging Units (MU). The protocolused in this case is the IEC/UCA 61850-9-2LE communication protocol.

The IEC/UCA 61850-9-2LE standard does not specify the quality of the sampledvalues. Thus, the accuracy of the current and voltage inputs to the merging unit and theinaccuracy added by the merging unit must be coordinated with the requirement forthe actual type of protection function.

Factors influencing the accuracy of the sampled values from the merging unit are, forexample, anti aliasing filters, frequency range, step response, truncating, A/Dconversion inaccuracy, time tagging accuracy etc.

In principle, the accuracy of the current and voltage transformers, together with themerging unit, will have the same quality as the direct input of currents and voltages.

The process bus physical layout can be arranged in several ways, described in AnnexB of the standard, depending on what are the needs for sampled data in a substation.

IEC06000537 V1 EN

Figure 158: Example of a station configuration with separated process bus andstation bus

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 377Application manual

Page 384: Railway application RER670 Version 2.2 IEC ... - ABB

The IED can get analog values simultaneously from a classical CT or VT and from aMerging Unit, like in this example:

The merging units (MU) are called so because they can gather analog values from oneor more measuring transformers, sample the data and send the data over process busto other clients (or subscribers) in the system. Some merging units are able to get datafrom classical measuring transformers, others from non-conventional measuringtransducers and yet others can pick up data from both types. The electronic part of anon-conventional measuring transducer (like a Rogowski coil or a capacitive divider)can represent a MU by itself as long as it can send sampled data over process bus.

Section 18 1MRK 506 375-UEN -Station communication

378 Railway application RER670 2.2 IECApplication manual

Page 385: Railway application RER670 Version 2.2 IEC ... - ABB

CTCT

ABBMerging

Unit

Ethernet Switch

IED

CombiSensor

Conventional VT

IEC61850-9-2LE

IEC61850-9-2LE

SplitterElectrical-to-

Optical Converter

1PPS

1PPS

110 V1 A1 A

IEC61850-8-1

Station Wide SCADA System

Station Wide GPS Clock

Other Relays

IEC61850-8-1

en08000069-3.vsd

IEC08000069 V2 EN

Figure 159: Example of a station configuration with the IED receiving analogvalues from both classical measuring transformers and mergingunits.

18.3.2 Setting guidelines

Merging Units (MUs) have several settings on local HMI under:

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 379Application manual

Page 386: Railway application RER670 Version 2.2 IEC ... - ABB

• Main menu/Configuration/Analog modules/MUx:92xx. The correspondingsettings are also available in PST (PCM600).

• Main menu/Configuration/Communication/Merging units configuration/MUx:92xx. The corresponding settings are also available in ECT (PCM600).

XX can take value 01–12.

18.3.2.1 Specific settings related to the IEC/UCA 61850-9-2LE communication

The process bus communication IEC/UCA 61850-9-2LE has specific settings, similarto the analog inputs modules.

If there are more than one sample group involved, time synch is mandatory. If there isno time synchronization, the protection functions will be blocked due to conditionblocking.

CTStarPointx: These parameters specify the direction to or from object. See alsosection "Setting of current channels".

SyncLostMode: If this parameter is set to Block and the IED hardware timesynchronization is lost or the synchronization to the MU time is lost, the protectionfunctions in the list 35 will be blocked due to conditional blocking. If this parameteris set to BlockOnLostUTC, the protection functions in list 35 are blocked if the IEDhardware time synchronization is lost or the synchronization of the MU time is lost orthe IED has lost global common synchronization (i.e. GPS, IRIG-B or PTP). SYNCHoutput will be set if IED hardware time synchronization is lost. MUSYNCH output willbe set if either of MU or IED hardware time synchronization is lost.

18.3.2.2 Loss of communication when used with LDCM

If IEC/UCA 61850-9-2LE communication is lost, see examples in figures 160, 161and 162, the protection functions in table 35 are blocked as per graceful degradation.

Case 1:

IEC13000298-2-en.vsd

IEDIED

MU

OK

OK

Direct transfer trip (DTT) local remote

IEC13000298 V2 EN

Figure 160: Normal operation

Section 18 1MRK 506 375-UEN -Station communication

380 Railway application RER670 2.2 IECApplication manual

Page 387: Railway application RER670 Version 2.2 IEC ... - ABB

Case 2:

Failure of the MU (sample lost) blocks the sending of binary signals through LDCM.The received binary signals are not blocked and processd normally.

→DTT from the remote end is still processed.

IEC13000299-2-en.vsd

Direct transfer trip (DTT) local remote

IEDIED

MU

Not OK

OK

IEC13000299 V2 EN

Figure 161: MU failed, mixed system

Case 3:

Failure of one MU (sample lost) blocks the sending and receiving of binary signalsthrough LDCM.

→DTT from the remote end is not working.

IEC13000300-2-en.vsd

Direct transfer trip (DTT) local remote

IEDIED

MU

Not OK

Not OK

MU

IEC13000300 V2 EN

Figure 162: MU failed, 9-2 system

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 381Application manual

Page 388: Railway application RER670 Version 2.2 IEC ... - ABB

Table 35: Blocked protection functions if IEC/UCA 61850-9-2LE communication is interruptedand functions are connected to specific MUs

Function description IEC 61850 identification Function description IEC 61850 identificationAccidental energizingprotection forsynchronous generator

AEGPVOC Two step overvoltageprotection

O2RWPTOV

Overcurrent protectionwith binary release

BRPTOC Four step single phaseovercurrent protection

PH4SPTOC

Capacitor bankprotection

CBPGAPC Radial feederprotection

PAPGAPC

Pole discordanceprotection

CCPDSC Instantaneous phaseovercurrent protection

PHPIOC

Breaker failureprotection

CCRWRBRF PoleSlip/Out-of-stepprotection

PSPPPAM

Breaker failureprotection, singlephase version

CCSRBRF Restricted earth faultprotection, lowimpedance

REFPDIF

Current circuitsupervison

CCSSPVC Two step residualovervoltage protection

ROV2PTOV

Compensated over-and undervoltageprotection

COUVGAPC Rate-of-changefrequency protection

SAPFRC

General currrent andvoltage protection

CVGAPC Overfrequencyprotection

SAPTOF

Current reversal andweakend infeed logicfor residual overcurrentprotection

ECRWPSCH Underfrequencyprotection

SAPTUF

Two step residualovercurrent protection

EF2PTOC Sudden change incurrent variation

SCCVPTOC

Instantaneous residualovercurrent protection

EFRWPIOC Sensitive Directionalresidual over currentand power protetcion

SDEPSDE

Phase selection,quadrilateralcharacteristic with fixedangle

FDPSPDIS Synchrocheck,energizing check, andsynchronizing

SESRSYN

Faulty phaseidentification with loadenchroachment

FMPSPDIS Circuit breakercondition monitoring

SSCBR

Phase selection,quadrilateralcharacteristic withsettable angle

FRPSPDIS Insulation gasmonitoring

SSIMG

Frequency timeaccumulationprotection

FTAQFVR Insulation liquidmonitoring

SSIML

Fuse failuresupervision

FRWSPVC Stub protection STBPTOC

Generator differentialprotection

GENPDIF Transformer differentialprotection, two winding

T1PPDIF

Table continues on next page

Section 18 1MRK 506 375-UEN -Station communication

382 Railway application RER670 2.2 IECApplication manual

Page 389: Railway application RER670 Version 2.2 IEC ... - ABB

Function description IEC 61850 identification Function description IEC 61850 identificationDirectional Overpowerprotection

GOPPDOP Transformer differentialprotection, threewinding

T3WPDIF

Generator rotoroverload protection

GRPTTR Automatic voltagecontrol for tapchanger,single control

TR1ATCC

Generator statoroverload protection

GSPTTR Automatic voltagecontrol for tapchanger,parallel control

TR8ATCC

DirectionalUnderpower protection

GUPPDUP Thermal overloadprotection, two timeconstants

TRPTTR

1Ph High impedancedifferential protection

HZPDIF Two step undervoltageprotection

U2RWPTUV

Line differentialprotection, 3 CT sets,2-3 line ends

L3CPDIF Voltage differentialprotection

VDCPTOV

Line differentialprotection, 6 CT sets,3-5 line ends

L6CPDIF Fuse failuresupervision

VDRFUF

Low active power andpower factor protection

LAPPGAPC Voltage-restrained timeovercurrent protection

VRPVOC

Negative sequenceovercurrent protection

LCNSPTOC Local acceleration logic ZCLCPSCH

Negative sequenceovervoltage protection

LCNSPTOV Schemecommunication logicfor distance orovercurrent protection

ZCPSCH

Three phaseovercurrent

LCP3PTOC Current reversal andweak-end infeed logicfor distance protection

ZCRWPSCH

Three phaseundercurrent

LCP3PTUC Automatic switch ontofault logic, voltage andcurrent based

ZCVPSOF

Thermal overloadprotection, one timeconstant

LCPTTR Underimpedanceprotection forgenerators andtransformers

ZGTPDIS

Zero sequenceovercurrent protection

LCZSPTOC Fast distanceprotection

ZMFCPDIS

Zero sequenceovervoltage protection

LCZSPTOV High speed distanceprotection

ZMFPDIS

Line differentialcoordination

LDLPSCH Distance measuringzone, quadrilateralcharacteristic for seriescompensated lines

ZMCAPDIS

Additional securitylogic for differentialprotection

LDRGFC Distance measuringzone, quadrilateralcharacteristic for seriescompensated lines

ZMCPDIS

Loss of excitation LEXPDIS Fullscheme distanceprotection, mhocharacteristic

ZMHPDIS

Table continues on next page

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 383Application manual

Page 390: Railway application RER670 Version 2.2 IEC ... - ABB

Function description IEC 61850 identification Function description IEC 61850 identificationThermal overloadprotection, one timeconstant

LFPTTR Fullscheme distanceprotection,quadrilateral for earthfaults

ZMMAPDIS

Loss of voltage check LOVPTUV Fullscheme distanceprotection,quadrilateral for earthfaults

ZMMPDIS

Line differentialprotection 3 CT sets,with inzonetransformers, 2-3 lineends

LT3CPDIF Distance protectionzone, quadrilateralcharacteristic

ZMQAPDIS

Line differentialprotection 6 CT sets,with inzonetransformers, 3-5 lineends

LT6CPDIF Distance protectionzone, quadrilateralcharacteristic

ZMQPDIS

Negativ sequence timeovercurrent protectionfor machines

NS2PTOC Distance protectionzone, quadrilateralcharacteristic, separatesettings

ZMRAPDIS

Four step directionalnegative phasesequence overcurrentprotection

NS4PTOC Distance protectionzone, quadrilateralcharacteristic, separatesettings

ZMRPDIS

Four step phaseovercurrent protection

OC4PTOC Power swing detection ZMRPSB

Overexcitationprotection

OEXPVPH Mho Impedancesupervision logic

ZSMGAPC

Out-of-step protection OOSPPAM Transformer tankovercurrent protection

TPPIOC

Transformerenergization control

XENCPOW Fault locator, multisection

RWRFLO

Two steps directionalphase overcurrentprotection

D2PTOC Distance protection,quadrilateralcharacteristic

ZRWPDIS

18.3.2.3 Setting examples for IEC/UCA 61850-9-2LE and time synchronization

The IED and the Merging Units (MU) should use the same time reference especiallyif analog data is used from several sources, for example from an internal TRM and anMU, or if several physical MUs are used. Having the same time reference is importantto correlate data so that channels from different sources refer to the correct phaseangle.

When only one MU is used as an analog source, it is theoretically possible to dowithout time synchronization. However, this would mean that timestamps for analogand binary data/events become uncorrelated. If the IED has no time synchronizationsource configured, then the binary data/events will be synchronized with the mergingunit. However, the global/complete time might not be correct. Disturbance recordingsthen appear incorrect since analog data is timestamped by MU, and binary events use

Section 18 1MRK 506 375-UEN -Station communication

384 Railway application RER670 2.2 IECApplication manual

Page 391: Railway application RER670 Version 2.2 IEC ... - ABB

the internal IED time. It is thus recommended to use time synchronization also whenanalog data emanate from only one MU.

An external time source can be used to synchronize both the IED and the MU. It is alsopossible to use the MU as a clock master to synchronize the IED from the MU. Whenusing an external clock, it is possible to set the IED to be synchronized via PPS, IRIG-B or PTP. It is also possible to use an internal GPS receiver in the IED (if the externalclock is using GPS).

Using PTP for synchronizing the MU

SAM600 VT SAM600 CT

SAM600 TS

IED

PTP9-2

IEC17000040-1-en.vsdx

IEC17000040 V1 EN

Figure 163: Setting example with PTP synchronization

Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 385Application manual

Page 392: Railway application RER670 Version 2.2 IEC ... - ABB

• HwSyncSrc: is not used as the SW-time and HW-time are connected with eachother due to PTP

• SyncLostMode : set to Block to block protection functions if time synchronizationis lost or set to BlockOnLostUTC if the protection functions are to be blockedwhen global common synchronization is lost

• SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase angleerror of 0.018 degrees at 50Hz

Settings on the local HMI under Main menu/Configuration/Communication/Ethernet configuration/Access point/AP_X:

• Operation: On• PTP: On

Two status monitoring signals can be:

• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED

• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.

Using MU for time synchronization via PPS

This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.

IED

MU

Analog data

PPS

IEC/UCA 61850-9-2LE

Synchronization

IEC10000061=2=en=Original.vsd

IEC10000061 V2 EN

Figure 164: Setting example when MU is the synchronizing source

Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:

Section 18 1MRK 506 375-UEN -Station communication

386 Railway application RER670 2.2 IECApplication manual

Page 393: Railway application RER670 Version 2.2 IEC ... - ABB

• HwSyncSrc: set to PPS as generated by the MU (ABB MU)• SyncLostMode : set to Block to block protection functions if time synchronization

is lost• SyncAccLevel: can be set to 4μs since this corresponds to a maximum phase angle

error of 0.072 degrees at 50Hz

Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/General:

• fineSyncSource can be set to something different to correlate events and data toother IEDs in the station.

Two status monitoring signals can be:

• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED.

• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.

SMPLLOST indicates that merging unit data are generated by internal substitution orone/more channel's Quality is not good or merging unit is in Testmode/detailedquality=Test, IED is not in test mode.

Using external clock for time synchronization

This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.

IED

MU

data

PPS

IEC/UCA 61850-9-2LE

PPS / IRIG-B

STATIONCLOCK

IEC10000074=2=en=Original.vsd

IEC10000074 V2 EN

Figure 165: Setting example with external synchronization

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 387Application manual

Page 394: Railway application RER670 Version 2.2 IEC ... - ABB

Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:

• HwSyncSrc: set to PPS/IRIG-B depending on available outputs on the clock• SyncLostMode: set to Block to block protection functions if time synchronization

is lost• SyncAccLevel: can be set to 4μs since this corresponds to a maximum phase angle

error of 0.072 degrees at 50Hz• fineSyncSource: should be set to IRIG-B if available from the clock. If PPS is used

for HWSyncSrc , “full-time” has to be acquired from another source. If stationclock is on the local area network (LAN) and has an sntp-server, this is one option.

Two status monitoring signals can be:

• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED (that is loss of thehardware synchSrc).

• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.

No time synchronization

This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.

IEC/UCA 61850-9-2LE

Data

MU

IED

IEC10000075=2=en=Original.vsd

IEC10000075 V2 EN

Figure 166: Setting example without time synchronization

It is also possible to use IEC/UCA 61850-9-2LE communication without timesynchronization.

Section 18 1MRK 506 375-UEN -Station communication

388 Railway application RER670 2.2 IECApplication manual

Page 395: Railway application RER670 Version 2.2 IEC ... - ABB

Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:

• HwSyncSrc: set to Off• SyncLostMode: set to No block to indicate that protection functions are not

blocked• SyncAccLevel: set to unspecified

Two status monitoring signals with no time synchronization:

• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED. SinceSyncLostMode is set to No block, this signal is not set.

• MUSYNCH signal on the MUx function block is set if the datastream indicatestime synchronization loss. However, protection functions are not blocked.

To get higher availability in protection functions, it is possible to avoid blockingduring time synchronization loss if there is a single source of analog data. This meansthat if there is only one physical MU and no TRM, parameter SyncLostMode is set toNo block but parameter HwSyncSrc is still set to PPS. This maintains analog andbinary data correlation in disturbance recordings without blocking protectionfunctions if PPS is lost.

18.3.3 IEC 61850 quality expander QUALEXP

The quality expander component is used to display the detailed quality of anIEC/UCA 61850-9-2LE analog channel. The component expands the channel qualityoutput of a Merging Unit analog channel received in the IED as per the IEC 61850-7-3standard. This component can be used during the ACT monitoring to get the particularchannel quality of the Merging Unit.

Figure 167 depicts the usage of the quality expander block in ACT.

IEC16000073-1-en.vsdx

IEC16000073 V1 EN

Figure 167: Quality expander block in ACT

The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard.When written to IED, the configuration will show the expanded form of the respectiveMU channel quality information during the online monitoring in the ACT.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 389Application manual

Page 396: Railway application RER670 Version 2.2 IEC ... - ABB

The quality expander function is intended for monitoring purposes,not for being used in a logic controlling the behaviour of the protectionor control functions in the IED. The function outputs are updated onceevery second and, therefore, do not reflect the quality bits in real time.

18.4 LON communication protocol

18.4.1 Application

Control Center

IED IEDIED

Gateway

Star couplerRER 111

Station HSIMicroSCADA

IEC05000663-1-en.vsd

IEC05000663 V2 EN

Figure 168: Example of LON communication structure for a substationautomation system

An optical network can be used within the substation automation system. This enablescommunication with the IEDs through the LON bus from the operator’s workplace,from the control center and also from other IEDs via bay-to-bay horizontalcommunication. For LON communication an SLM card should be ordered for theIEDs.

The fibre optic LON bus is implemented using either glass core or plastic core fibreoptic cables.

Section 18 1MRK 506 375-UEN -Station communication

390 Railway application RER670 2.2 IECApplication manual

Page 397: Railway application RER670 Version 2.2 IEC ... - ABB

Table 36: Specification of the fibre optic connectors

Glass fibre Plastic fibreCable connector ST-connector snap-in connector

Cable diameter 62.5/125 m 1 mm

Max. cable length 1000 m 10 m

Wavelength 820-900 nm 660 nm

Transmitted power -13 dBm (HFBR-1414) -13 dBm (HFBR-1521)

Receiver sensitivity -24 dBm (HFBR-2412) -20 dBm (HFBR-2521)

The LON ProtocolThe LON protocol is specified in the LonTalkProtocol Specification Version 3 fromEchelon Corporation. This protocol is designed for communication in controlnetworks and is a peer-to-peer protocol where all the devices connected to the networkcan communicate with each other directly. For more information of the bay-to-baycommunication, refer to the section Multiple command function.

Hardware and software modulesThe hardware needed for applying LON communication depends on the application,but one very central unit needed is the LON Star Coupler and optical fibres connectingthe star coupler to the IEDs. To interface the IEDs from the MicroSCADA withClassic Monitor, application library LIB520 is required.

The HV Control 670 software module is included in the LIB520 high-voltage processpackage, which is a part of the Application Software Library in MicroSCADAapplications.

The HV Control 670 software module is used for control functions in the IEDs. Themodule contains a process picture, dialogues and a tool to generate a process databasefor the control application in MicroSCADA.

When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB isused together with 670 series Object Type files.

The HV Control 670 software module and 670 series Object Typefiles are used with both 650 and 670 series IEDs.

Use the LON Network Tool (LNT) to set the LON communication. This is a softwaretool applied as one node on the LON bus. To communicate via LON, the IEDs needto know

• The node addresses of the other connected IEDs.• The network variable selectors to be used.

This is organized by LNT.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 391Application manual

Page 398: Railway application RER670 Version 2.2 IEC ... - ABB

The node address is transferred to LNT via the local HMI by setting the parameterServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNT canscan the network for new nodes.

The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This canbe changed by LNT.

18.4.2 MULTICMDRCV and MULTICMDSND

18.4.2.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Multiple command and receive MULTICMDRCV - -

Multiple command and send MULTICMDSND - -

18.4.2.2 Application

The IED provides two function blocks enabling several IEDs to send and receivesignals via the interbay bus. The sending function block, MULTICMDSND, takes 16binary inputs. LON enables these to be transmitted to the equivalent receivingfunction block, MULTICMDRCV, which has 16 binary outputs.

18.4.2.3 Setting guidelines

SettingsThe parameters for the multiple command function are set via PCM600.

The Mode setting sets the outputs to either a Steady or Pulsed mode.

18.5 SPA communication protocol

18.5.1 Application

SPA communication protocol is an alternative to IEC 60870-5-103, and they use thesame rear communication port.

When communicating with a PC connected to the utility substation LAN via WANand the utility office LAN (see Figure 169), and when using the rear optical Ethernetport, the only hardware required for a station monitoring system is:

• Optical fibres from the IED to the utility substation LAN• PC connected to the utility office LAN

Section 18 1MRK 506 375-UEN -Station communication

392 Railway application RER670 2.2 IECApplication manual

Page 399: Railway application RER670 Version 2.2 IEC ... - ABB

IED IEDIED

Substation LAN

IEC05000715-4-en.vsd

Remote monitoring

Utility LAN

WAN

IEC05000715 V4 EN

Figure 169: SPA communication structure for a remote monitoring system via asubstation LAN, WAN and utility LAN

SPA communication is mainly used for the Station Monitoring System. It can includedifferent IEDs with remote communication possibilities. Connection to a PC can bemade directly (if the PC is located in the substation), via a telephone modem througha telephone network with ITU (former CCITT) characteristics or via a LAN/WANconnection.

glass <1000 m according to optical budget

plastic <25 m (inside cubicle) according to optical budget

FunctionalityThe SPA protocol V2.5 is an ASCII-based protocol for serial communication. Thecommunication is based on a master-slave principle, where the IED is a slave and thePC is the master. Only one master can be applied on each fibre optic loop. A programis required in the master computer for interpretation of the SPA-bus codes and fortranslation of the data that should be sent to the IED.

For the specification of the SPA protocol V2.5, refer to SPA-bus CommunicationProtocol V2.5.

18.5.2 Setting guidelines

SPA, IEC 60870-5-103 and DNP3 use the same rear communication port. This portcan be set for SPA use on the local HMI under Main menu /Configuration /Communication /Station communication/Port configuration/SLM optical serialport/PROTOCOL:1. When the communication protocol is selected, the IED isautomatically restarted, and the port then operates as a SPA port.

The SPA communication setting parameters are set on the local HMI under Mainmenu/Configuration/Communication/Station communication/SPA/SPA:1.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 393Application manual

Page 400: Railway application RER670 Version 2.2 IEC ... - ABB

The most important SPA communication setting parameters are SlaveAddress andBaudRate. They are essential for all communication contact to the IED. SlaveAddressand BaudRate can be set only on the local HMI for rear and front channelcommunication.

SlaveAddress can be set to any value between 1–899 as long as the slave number isunique within the used SPA loop. BaudRate (communication speed) can be setbetween 300–38400 baud. BaudRate should be the same for the whole stationalthough different communication speeds in a loop are possible. If differentcommunication speeds are used in the same fibre optical loop or RS485 network, takethis into account when making the communication setup in the communication master(the PC).

With local fibre optic communication, communication speed is usually set to 19200 or38400 baud. With telephone communication, the speed setting depends on the qualityof the connection and the type of modem used. Refer to technical data to determine therated communication speed for the selected communication interfaces.

The IED does not adapt its speed to the actual communicationconditions because the communication speed is set on the local HMI.

Section 18 1MRK 506 375-UEN -Station communication

394 Railway application RER670 2.2 IECApplication manual

Page 401: Railway application RER670 Version 2.2 IEC ... - ABB

18.6 IEC 60870-5-103 communication protocol

18.6.1 Application

TCP/IP

Control Center

IED IEDIED

Gateway

Star coupler

Station HSI

IEC05000660-4-en.vsdIEC05000660 V4 EN

Figure 170: Example of IEC 60870-5-103 communication structure for asubstation automation system

IEC 60870-5-103 communication protocol is mainly used when a protection IEDcommunicates with a third party control or monitoring system. This system must havesoftware that can interpret the IEC 60870-5-103 communication messages.

When communicating locally in the station using a Personal Computer (PC) or aRemote Terminal Unit (RTU) connected to the Communication and processingmodule, the only hardware needed is optical fibres and an opto/electrical converter forthe PC/RTU, or a RS-485 connection depending on the used IED communicationinterface.

18.6.1.1 Functionality

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information with a control system. In IEC terminology aprimary station is a master and a secondary station is a slave. The communication isbased on a point-to-point principle. The master must have software that can interpretthe IEC 60870-5-103 communication messages. For detailed information about IEC60870-5-103, refer to IEC 60870 standard part 5: Transmission protocols, and to the

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 395Application manual

Page 402: Railway application RER670 Version 2.2 IEC ... - ABB

section 103, Companion standard for the informative interface of protectionequipment.

18.6.1.2 Design

GeneralThe protocol implementation consists of the following functions:

• Event handling• Report of analog service values (measurands)• Fault location• Command handling

• Autorecloser ON/OFF• Teleprotection ON/OFF• Protection ON/OFF• LED reset• Characteristics 1 - 4 (Setting groups)

• File transfer (disturbance files)• Time synchronization

HardwareWhen communicating locally with a Personal Computer (PC) or a Remote TerminalUnit (RTU) in the station, using the SPA/IEC port, the only hardware needed is:·Optical fibres, glass/plastic· Opto/electrical converter for the PC/RTU· PC/RTU

CommandsThe commands defined in the IEC 60870-5-103 protocol are represented in dedicatedfunction blocks. These blocks have output signals for all available commandsaccording to the protocol. For more information, refer to the Communication protocolmanual, IEC 60870-5-103.

• IED commands in control direction

Function block with defined IED functions in control direction, I103IEDCMD. Thisblock use PARAMETR as FUNCTION TYPE, and INFORMATION NUMBERparameter is defined for each output signal.

• Function commands in control direction

Function block with pre-defined functions in control direction, I103CMD. This blockincludes the FUNCTION TYPE parameter, and the INFORMATION NUMBERparameter is defined for each output signal.

• Function commands in control direction

Section 18 1MRK 506 375-UEN -Station communication

396 Railway application RER670 2.2 IECApplication manual

Page 403: Railway application RER670 Version 2.2 IEC ... - ABB

Function block with user defined functions in control direction, I103UserCMD. Thesefunction blocks include the FUNCTION TYPE parameter for each block in the privaterange, and the INFORMATION NUMBER parameter for each output signal.

Status

For more information on the function blocks below, refer to theCommunication protocol manual, IEC 60870-5-103.

The events created in the IED available for the IEC 60870-5-103 protocol are basedon the:

• IED status indication in monitor direction

Function block with defined IED functions in monitor direction, I103IED. This blockuse PARAMETER as FUNCTION TYPE, and INFORMATION NUMBERparameter is defined for each input signal.

• Function status indication in monitor direction, user-defined

Function blocks with user defined input signals in monitor direction, I103UserDef.These function blocks include the FUNCTION TYPE parameter for each block in theprivate range, and the INFORMATION NUMBER parameter for each input signal.

• Supervision indications in monitor direction

Function block with defined functions for supervision indications in monitordirection, I103Superv. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.

• Earth fault indications in monitor direction

Function block with defined functions for earth fault indications in monitor direction,I103EF. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.

• Fault indications in monitor direction

Function block with defined functions for fault indications in monitor direction,I103FLTPROT. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each input signal.

This block is suitable for distance protection, line differential, transformerdifferential, over-current and earth-fault protection functions.

• Autorecloser indications in monitor direction

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 397Application manual

Page 404: Railway application RER670 Version 2.2 IEC ... - ABB

Function block with defined functions for autorecloser indications in monitordirection, I103AR. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.

MeasurandsThe measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to thestandard.

• Measurands in public range

Function block that reports all valid measuring types depending on connected signals,I103Meas.

• Measurands in private range

Function blocks with user defined input measurands in monitor direction,I103MeasUsr. These function blocks include the FUNCTION TYPE parameter foreach block in the private range, and the INFORMATION NUMBER parameter foreach block.

Fault locationThe fault location is expressed in reactive ohms. In relation to the line length inreactive ohms, it gives the distance to the fault in percent. The data is available andreported when the fault locator function is included in the IED.

Disturbance recordings

• The transfer functionality is based on the Disturbance recorder function. Theanalog and binary signals recorded will be reported to the master by polling. Theeight last disturbances that are recorded are available for transfer to the master. Afile that has been transferred and acknowledged by the master cannot betransferred again.

• The binary signals that are included in the disturbance recorder are those that areconnected to the disturbance function blocks B1RBDR to B22RBDR. Thesefunction blocks include the function type and the information number for eachsignal. For more information on the description of the Disturbance report in theTechnical reference manual. The analog channels, that are reported, are thoseconnected to the disturbance function blocks A1RADR to A4RADR. The eightfirst ones belong to the public range and the remaining ones to the private range.

18.6.2 Settings

Section 18 1MRK 506 375-UEN -Station communication

398 Railway application RER670 2.2 IECApplication manual

Page 405: Railway application RER670 Version 2.2 IEC ... - ABB

18.6.2.1 Settings for RS485 and optical serial communication

General settingsSPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM opticalserial port while DNP and IEC 60870-5-103 additionally can utilize the RS485 port.A single protocol can be active on a given physical port at any time.

Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.

1. The port specific IEC 60870-5-103 protocol parameters are configured under:Main menu/Configuration/Communication/Station Communication/IEC60870-5-103/• <config-selector>• SlaveAddress• BaudRate• RevPolarity (optical channel only)• CycMeasRepTime• MasterTimeDomain• TimeSyncMode• EvalTimeAccuracy• EventRepMode• CmdMode• RepIntermediatePos

<config-selector> is:• “OPTICAL103:1” for the optical serial channel on the SLM• “RS485103:1” for the RS485 port

2. The protocol to activate on a physical port is selected under:Main menu/Configuration/Communication/Station Communication/Portconfiguration/• RS485 port

• RS485PROT:1 (off, DNP, IEC103)• SLM optical serial port

• PROTOCOL:1 (off, DNP, IEC103, SPA)

GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN

GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN

Figure 171: Settings for IEC 60870-5-103 communication

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 399Application manual

Page 406: Railway application RER670 Version 2.2 IEC ... - ABB

The general settings for IEC 60870-5-103 communication are the following:

• SlaveAddress and BaudRate: Settings for slave number and communicationspeed (baud rate).The slave number can be set to any value between 1 and 254. The communicationspeed, can be set either to 9600 bits/s or 19200 bits/s.

• RevPolarity: Setting for inverting the light (or not). Standard IEC 60870-5-103setting is On.

• CycMeasRepTime: See I103MEAS function block for more information.• EventRepMode: Defines the mode for how events are reported. The event buffer

size is 1000 events.

Event reporting modeIf EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in theorder they were generated by BSW. The most recent value is the latest value delivered.All GI data from a single block will come from the same cycle.

If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GIevent. To prevent old GI data from being delivered after a new spontaneous event, thepending GI event is modified to contain the same value as the spontaneous event. Asa result, the GI dataset is not time-correlated.

18.6.2.2 Settings from PCM600

I103USEDEFFor each input of the I103USEDEF function there is a setting for the informationnumber of the connected signal. The information number can be set to any valuebetween 0 and 255. To get proper operation of the sequence of events the event masksin the event function is to be set to ON_CHANGE. For single-command signals, theevent mask is to be set to ON_SET.

In addition there is a setting on each event block for function type. Refer to descriptionof the Main Function type set on the local HMI.

CommandsAs for the commands defined in the protocol there is a dedicated function block witheight output signals. Use PCM600 to configure these signals. To realize theBlockOfInformation command, which is operated from the local HMI, the outputBLKINFO on the IEC command function block ICOM has to be connected to an inputon an event function block. This input must have the information number 20 (monitordirection blocked) according to the standard.

Disturbance RecordingsFor each input of the Disturbance recorder function there is a setting for theinformation number of the connected signal. The function type and the informationnumber can be set to any value between 0 and 255. To get INF and FUN for therecorded binary signals, there are parameters on the disturbance recorder for each

Section 18 1MRK 506 375-UEN -Station communication

400 Railway application RER670 2.2 IECApplication manual

Page 407: Railway application RER670 Version 2.2 IEC ... - ABB

input. The user must set these parameters to whatever he connects to thecorresponding input.

Refer to description of Main Function type set on the local HMI.

Recorded analog channels are sent with ASDU26 and ASDU31. One informationelement in these ASDUs is called ACC, and it indicates the actual channel to beprocessed. The channels on disturbance recorder are sent with an ACC as shown inTable 37.

Table 37: Channels on disturbance recorder sent with a given ACC

DRA#-Input ACC IEC 60870-5-103 meaning1 1 IL1

2 2 IL2

3 3 IL3

4 4 IN

5 5 UL1

6 6 UL2

7 7 UL3

8 8 UN

9 64 Private range

10 65 Private range

11 66 Private range

12 67 Private range

13 68 Private range

14 69 Private range

15 70 Private range

16 71 Private range

17 72 Private range

18 73 Private range

19 74 Private range

20 75 Private range

21 76 Private range

22 77 Private range

23 78 Private range

24 79 Private range

25 80 Private range

26 81 Private range

27 82 Private range

28 83 Private range

29 84 Private range

30 85 Private range

31 86 Private range

Table continues on next page

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 401Application manual

Page 408: Railway application RER670 Version 2.2 IEC ... - ABB

DRA#-Input ACC IEC 60870-5-103 meaning32 87 Private range

33 88 Private range

34 89 Private range

35 90 Private range

36 91 Private range

37 92 Private range

38 93 Private range

39 94 Private range

40 95 Private range

18.6.3 Function and information types

Product type IEC103mainFunType value Comment:

REL 128 Compatible range

REC 242 Private range, use default

RED 192 Compatible range

RET 176 Compatible range

REB 207 Private range

REG 150 Private range

REQ 245 Private range

RER 152 Private range

RES 118 Private range

Refer to the tables in the Technical reference manual /Station communication,specifying the information types supported by the communication protocol IEC60870-5-103.

To support the information, corresponding functions must be included in theprotection IED.

There is no representation for the following parts:

• Generating events for test mode• Cause of transmission: Info no 11, Local operation

Glass or plastic fibre should be used. BFOC/2.5 is the recommended interface to use(BFOC/2.5 is the same as ST connectors). ST connectors are used with the opticalpower as specified in standard.

Section 18 1MRK 506 375-UEN -Station communication

402 Railway application RER670 2.2 IECApplication manual

Page 409: Railway application RER670 Version 2.2 IEC ... - ABB

For more information, refer to IEC standard IEC 60870-5-103.

18.7 DNP3 Communication protocol

18.7.1 Application

For more information on the application and setting guidelines for the DNP3communication protocol refer to the DNP3 Communication protocol manual.

1MRK 506 375-UEN - Section 18Station communication

Railway application RER670 2.2 IEC 403Application manual

Page 410: Railway application RER670 Version 2.2 IEC ... - ABB

404

Page 411: Railway application RER670 Version 2.2 IEC ... - ABB

Section 19 Remote communication

19.1 Binary signal transfer

19.1.1 IdentificationFunction description IEC 61850 identification IEC 60617

identificationANSI/IEEE C37.2device number

Binary signal transfer, receiveBinSignRec1_1BinSignRec1_2BinSignReceive2

- -

Binary signal transfer, 2Mbitreceive

BinSigRec1_12MBinSigRec1_22M - -

Binary signal transfer,transmit

BinSignTrans1_1BinSignTrans1_2BinSignTransm2

- -

Binary signal transfer, 2Mbittransmit

BinSigTran1_12MBinSigTran1_22M - -

19.1.2 Application

The IEDs can be equipped with communication devices for line differentialcommunication (not applicable for RER670) and/or communication of binary signalsbetween IEDs. The same communication hardware is used for both purposes.

Sending of binary signals between two IEDs is used in teleprotection schemes and fordirect transfer trips. In addition to this, there are application possibilities, for example,blocking/enabling functionality in the remote substation, changing setting group inthe remote IED depending on the switching situation in the local substation and so on.

If equipped with a 64kbit/s LDCM module, the IED can be configured to send either192 binary signals or 3 analog and 8 binary signals to a remote IED. If equipped witha 2Mbps LDCM module, the IED can send 9 analog channels and 192 binary channelsto a remote IED.

Link forwardingIf it is not possible to have a communication link between each station, the solution hasbeen to set the protection up in a slave-master-slave configuration. This means that inFigure 172, only IED-B has access to all currents and, therefore, this is the only placewhere the differential current is evaluated. If the evaluation results in a trip, the tripsignal will be sent over the two communication links.

1MRK 506 375-UEN - Section 19Remote communication

Railway application RER670 2.2 IEC 405Application manual

Page 412: Railway application RER670 Version 2.2 IEC ... - ABB

IED-A IED-B IED-C

IEC16000077-1-en.vsd

3-end differential protection with two communication links

Ldcm312

Ldcm312

Ldcm313

Ldcm312

IEC16000077 V1 EN

Figure 172: Three-end differential protection with two communication links

If the LDCM is in 2Mbit mode, you can send the three local currents as well as thethree remote currents from the other links by configuring the transmitters in IED-B:

1. Ldcm312 transmitter sends the local currents and the three currents received byLdcm313.

2. Ldcm313 transmitter sends the three local currents and the three currents receivedfrom Ldcm312.

As a result, six currents are received in IED-A and IED-C. These currents can beconnected to the protection function together with the local three currents.

In order to forward the logic signals (for example, inter-trip or inter-block) between IED-A and IED-C, the setting LinkForwarded shouldbe defined. In IED-B, it is set to LDCM313 for Ldcm312 and toLDCM312 for ldcm313.

This setup results in a master-master-master configuration, but without the benefit ofreverting to a slave-master-slave configuration in case of a communication linkinterruption. In case of a communication link interruption, all three IEDs would beblocked.

19.1.2.1 Communication hardware solutions

The LDCM (Line Data Communication Module) has an optical connection such thattwo IEDs can be connected over a direct fibre, as shown in figure 173. The distanceto be covered with this solution is up to typical 3km (SR), 80km (MR) and 110km(LR).

Section 19 1MRK 506 375-UEN -Remote communication

406 Railway application RER670 2.2 IECApplication manual

Page 413: Railway application RER670 Version 2.2 IEC ... - ABB

LDCM

LDCM

LDCM

LDCMLDCM

LDCMLDCMLDCM

LDCMLDCM

LDCM

LDCMLD

CMLD

CM

LDCMLDCM

en06000519-2.vsdIEC06000519 V2 EN

Figure 173: Direct fibre optical connection between two IEDs with LDCM

The LDCM can also be used together with an external optical to galvanic G.703converter as shown in figure 174. These solutions are aimed for connections to amultiplexer, which in turn is connected to a telecommunications transmissionnetwork (for example PDH).

Telecom. Network

*) *)

Multiplexer Multiplexer

en05000527-2.vsd*) Converting optical to galvanic G.703

IEC05000527 V2 EN

Figure 174: LDCM with an external optical to galvanic converter and a multiplexer

When an external modem G.703 is used, the connection between LDCM and themodem is made with a multimode fibre of max. 3 km length. The IEEE/ANSI C37.94protocol is always used between LDCM and the modem.

19.1.3 Setting guidelines

64 kbit and 2 Mbit mode common settings

ChannelMode defines how an IED discards the LDCM information when one of theIEDs in the system is out of service: it can either be done on the IED out of service bysetting all local LDCMs to channel mode OutOfService or at the remote end by setting

1MRK 506 375-UEN - Section 19Remote communication

Railway application RER670 2.2 IEC 407Application manual

Page 414: Railway application RER670 Version 2.2 IEC ... - ABB

the corresponding LDCM to channel mode Blocked. If OutOfService is selected, theIED should have active communication to the remote end during the wholemaintenance process, that is, no restart or removal of the fibre can be done.

This setting does not apply to two-end communication.

Blocked IED does not use data from the LDCM

OutOfService IED informs the remote end that it is out of service

TerminalNo is used to assign a unique address to each LDCM in all current differentialIEDs. Up to 256 LDCMs can be assigned a unique number. For example, in a localIED with two LDCMs:

• LDCM for slot 305: set TerminalNo to 1 and RemoteTermNo to 2• LDCM for slot 306: set TerminalNo to 3 and RemoteTermNo to 4

In multiterminal current differential applications,with 4 LDCMs in each IED, up to 20unique addresses must be set.

A unique address is necessary to give high security against incorrectaddressing in the communication system. If the same number is usedfor TerminalNo in some of the LDCMs, a loop-back test in thecommunication system can give an incorrect trip.

RemoteTermNo is used to assign a number to each related LDCM in the remote IED.For each LDCM, RemoteTermNo is set to a different value than TerminalNo, but equalto the TerminalNo of the remote end LDCM. In the remote IED, TerminalNo andRemoteTermNo are reversed as follows:

• LDCM for slot 305: set TerminalNo to 2 and RemoteTermNo to 1• LDCM for slot 306: set TerminalNo to 4 and RemoteTermNo to 3

The redundant channel is always configured to the lower position, forexample:

• Slot 305: main channel• Slot 306: redundant channel

The same is applicable for slot 312-313 and slot 322-323.

DiffSync defines the method of time synchronization for the line differential function:Echo or GPS.

Section 19 1MRK 506 375-UEN -Remote communication

408 Railway application RER670 2.2 IECApplication manual

Page 415: Railway application RER670 Version 2.2 IEC ... - ABB

Using Echo in this case is safe only if there is no risk of varyingtransmission asymmetry.

GPSSyncErr: when GPS synchronization is lost, synchronization of the linedifferential function continues for 16 s based on the stability in the local IED clocks.After that, setting Block blocks the line differential function or setting Echo keeps iton by using the Echo synchronization method.

Using Echo in this case is safe only if there is no risk of varyingtransmission asymmetry.

CommSync defines the Master and Slave relation in the communication system, andshould not be mistaken for the synchronization of line differential current samples.When direct fibre is used, one LDCM is set as Master and the other as Slave. When amodem and multiplexer is used, the IED is always set as Slave because thetelecommunication system provides the clock master.

OptoPower has two settings: LowPower is used for fibres 0 – 1 km and HighPower forfibres >1 km.

ComAlarmDel defines the time delay for communication failure alarm. Incommunication systems, route switching can sometimes cause interruptions with aduration of up to 50 ms. Too short a time delay can thus cause nuisance alarms.

ComAlrmResDel defines the time delay for communication failure alarm reset.

RedChSwTime defines the time delay before switching over to a redundant channel incase of primary channel failure.

RedChRturnTime defines the time delay before switching back to the primary channelafter channel failure.

AsymDelay denotes asymmetry which is defined as transmission delay minus receivedelay. If fixed asymmetry is known, Echo synchronization method can be used,provided that AsymDelay is properly set. From the definition follows that asymmetryis always positive at one end and negative at the other end.

MaxTransmDelay indicates maximum transmission delay. Data for maximum 40 mstransmission delay can be buffered up. Delay times in the range of some ms arecommon. If data arrive in wrong order, the oldest data is disregarded.

MaxtDiffLevel indicates the maximum time difference allowed between internalclocks in respective line ends.

64 kbit mode specific settings

TransmCurr is used to select among the following:

1MRK 506 375-UEN - Section 19Remote communication

Railway application RER670 2.2 IEC 409Application manual

Page 416: Railway application RER670 Version 2.2 IEC ... - ABB

• one of the two possible local currents is transmitted• sum of the two local currents is transmitted• channel is used as a redundant backup channel

1½ breaker arrangement has two local currents, and the Current Transformer (CT)earthing for those can differ. CT-SUM transmits the sum of the two CT groups. CT-DIFF1 transmits CT group 1 minus CT group 2 and CT-DIFF2 transmits CT group 2minus CT group 1.

CT-GRP1 and CT-GRP2 transmit the respective CT groups, and settingRedundantChannel determines that the channel is used as a redundant backupchannel. The redundant channel takes the CT group setting of the main channel.

RemAinLatency corresponds to LocAinLatency set in the remote IED.

AnalogLatency specifies the time delay (number of samples) between actual samplingand the time the sample reaches LDCM. The value is set to 2 when transmitting analogdata. When a merging unit according to IEC 61850-9-2 is used instead of the TRM,this parameter shall be set to 5.

CompRange value indicates the current peak value over which truncation is made. Toset this value, knowledge of fault current levels is required. It is recommended to setthe minimum range that will cover the expected fault current value. For example, if a40kA fault level is expected on the network, the 0-50kA settings range should bechosen.

2 Mbit mode specific settings

RedundantCh is used to set the channel as a redundant backup channel. The redundantchannel takes the CT group setting of the main channel, and ignores the CT groupconfigured in its own transmit block.

LinkForwarded is used to configure the LDCM to merge the inter-trip and blocksignals from another LDCM-receiver. This is used when the analog signals for theLDCM-transmitter is connected to the receiver of another LDCM.

Section 19 1MRK 506 375-UEN -Remote communication

410 Railway application RER670 2.2 IECApplication manual

Page 417: Railway application RER670 Version 2.2 IEC ... - ABB

Section 20 Security

20.1 Authority status ATHSTAT

20.1.1 Application

Authority status (ATHSTAT) function is an indication function block, which informsabout two events related to the IED and the user authorization:

• the fact that at least one user has tried to log on wrongly into the IED and it wasblocked (the output USRBLKED)

• the fact that at least one user is logged on (the output LOGGEDON)

The two outputs of ATHSTAT function can be used in the configuration for differentindication and alarming reasons, or can be sent to the station control for the samepurpose.

20.2 Self supervision with internal event list INTERRSIG

20.2.1 Application

The protection and control IEDs have many functions included. The included self-supervision with internal event list function block provides good supervision of theIED. The fault signals make it easier to analyze and locate a fault.

Both hardware and software supervision is included and it is also possible to indicatepossible faults through a hardware contact on the power supply module and/orthrough the communication.

Internal events are generated by the built-in supervisory functions. The supervisoryfunctions supervise the status of the various modules in the IED and, in case of failure,a corresponding event is generated. Similarly, when the failure is corrected, acorresponding event is generated.

Apart from the built-in supervision of the various modules, events are also generatedwhen the status changes for the:

• built-in real time clock (in operation/out of order).• external time synchronization (in operation/out of order).

1MRK 506 375-UEN - Section 20Security

Railway application RER670 2.2 IEC 411Application manual

Page 418: Railway application RER670 Version 2.2 IEC ... - ABB

Events are also generated:

• whenever any setting in the IED is changed.

The internal events are time tagged with a resolution of 1 ms and stored in a list. Thelist can store up to 40 events. The list is based on the FIFO principle, that is, when itis full, the oldest event is overwritten. The list contents cannot be modified, but thewhole list can be cleared using the Reset menu in the LHMI.

The list of internal events provides valuable information, which can be used duringcommissioning and fault tracing.

The information can, in addition to be viewed on the built in HMI, also be retrievedwith the aid of a PC with PCM600 installed and by using the Event Monitoring Tool.The PC can either be connected to the front port, or to the port at the back of the IED.

20.3 Change lock CHNGLCK

20.3.1 Application

Change lock function CHNGLCK is used to block further changes to the IEDconfiguration once the commissioning is complete. The purpose is to make itimpossible to perform inadvertent IED configuration and setting changes.

However, when activated, CHNGLCK will still allow the following actions that doesnot involve reconfiguring of the IED:

• Monitoring• Reading events• Resetting events• Reading disturbance data• Clear disturbances• Reset LEDs• Reset counters and other runtime component states• Control operations• Set system time• Enter and exit from test mode• Change of active setting group

The binary input controlling the function is defined in ACT or SMT. The CHNGLCKfunction is configured using ACT.

LOCK Binary input signal that will activate/deactivate the function, defined in ACT orSMT.

Section 20 1MRK 506 375-UEN -Security

412 Railway application RER670 2.2 IECApplication manual

Page 419: Railway application RER670 Version 2.2 IEC ... - ABB

When CHNGLCK has a logical one on its input, then all attempts tomodify the IED configuration and setting will be denied and themessage "Error: Changes blocked" will be displayed on the localHMI; in PCM600 the message will be "Operation denied by activeChangeLock". The CHNGLCK function should be configured so thatit is controlled by a signal from a binary input card. This guaranteesthat by setting that signal to a logical zero, CHNGLCK is deactivated.If any logic is included in the signal path to the CHNGLCK input, thatlogic must be designed so that it cannot permanently issue a logicalone to the CHNGLCK input. If such a situation would occur in spiteof these precautions, then please contact the local ABB representativefor remedial action.

20.4 Denial of service SCHLCCH/RCHLCCH

20.4.1 Application

The denial of service functionality is designed to limit the CPU load that can beproduced by Ethernet network traffic on the IED. The communication facilities mustnot be allowed to compromise the primary functionality of the device. All inboundnetwork traffic will be quota controlled so that too heavy network loads can becontrolled. Heavy network load might for instance be the result of malfunctioningequipment connected to the network.

The functions Access point diagnostics function block measure the IED load fromcommunication and, if necessary, limit it for not jeopardizing the IEDs control andprotection functionality due to high CPU load. The function has the following denialof service related outputs:

• LINKSTS indicates the Ethernet link status for the rear ports (singlecommunication)

• CHALISTS and CHBLISTS indicates the Ethernet link status for the rear portschannel A and B (redundant communication)

• LinkStatus indicates the Ethernet link status for the front port

20.4.2 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

1MRK 506 375-UEN - Section 20Security

Railway application RER670 2.2 IEC 413Application manual

Page 420: Railway application RER670 Version 2.2 IEC ... - ABB

414

Page 421: Railway application RER670 Version 2.2 IEC ... - ABB

Section 21 Basic IED functions

21.1 IED identifiers TERMINALID

21.1.1 Application

IED identifiers (TERMINALID) function allows the user to identify the individualIED in the system, not only in the substation, but in a whole region or a country.

Use only characters A-Z, a-z and 0-9 in station, object and unit names.

21.2 Product information PRODINF

21.2.1 Application

Product information contains unchangeable data that uniquely identifies the IED.

Product information data is visible on the local HMI under Main menu/Diagnostics/IED status/Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers:

• ProductVer• ProductDef• FirmwareVer• SerialNo• OrderingNo• ProductionDate• IEDProdType

This information is very helpful when interacting with ABB product support (forexample during repair and maintenance).

21.2.2 Factory defined settings

The factory defined settings are very useful for identifying a specific version and veryhelpful in the case of maintenance, repair, interchanging IEDs between differentSubstation Automation Systems and upgrading. The factory made settings can not be

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 415Application manual

Page 422: Railway application RER670 Version 2.2 IEC ... - ABB

changed by the customer. They can only be viewed. The settings are found in the localHMI under Main menu/Diagnostics/IED status/Product identifiers

The following identifiers are available:

• IEDProdType• Describes the type of the IED. Example: REL670

• ProductDef• Describes the release number from the production. Example: 2.1.0

• FirmwareVer• Describes the firmware version.• The firmware version can be checked from Main menu/Diagnostics/IED

status/Product identifiers• Firmware version numbers run independently from the release production

numbers. For every release number there can be one or more firmwareversions depending on the small issues corrected in between releases.

• ProductVer• Describes the product version. Example: 2.1.0

1 is the Major version of the manufactured product this means, new platform of theproduct

2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product

3 is the Major revision of the manufactured product this means, functions or hardware iseither changed or enhanced in the product

• IEDMainFunType• Main function type code according to IEC 60870-5-103. Example: 128

(meaning line protection).• SerialNo• OrderingNo• ProductionDate

21.3 Measured value expander block RANGE_XP

21.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measured value expander block RANGE_XP - -

Section 21 1MRK 506 375-UEN -Basic IED functions

416 Railway application RER670 2.2 IECApplication manual

Page 423: Railway application RER670 Version 2.2 IEC ... - ABB

21.3.2 Application

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXUand VNMMXU), current and voltage sequence measurement functions (CMSQI andVMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) areprovided with measurement supervision functionality. All measured values can besupervised with four settable limits, that is low-low limit, low limit, high limit andhigh-high limit. The measure value expander block ( RANGE_XP) has beenintroduced to be able to translate the integer output signal from the measuringfunctions to 5 binary signals, that is below low-low limit, below low limit, normal,above high-high limit or above high limit. The output signals can be used as conditionsin the configurable logic.

21.3.3 Setting guidelines

There are no settable parameters for the measured value expander block function.

21.4 Parameter setting groups

21.4.1 Application

Six sets of settings are available to optimize IED operation for different power systemconditions. By creating and switching between fine tuned setting sets, either from thelocal HMI or configurable binary inputs, results in a highly adaptable IED that cancope with a variety of power system scenarios.

Different conditions in networks with different voltage levels require highly adaptableprotection and control units to best provide for dependability, security and selectivityrequirements. Protection units operate with a higher degree of availability, especially,if the setting values of their parameters are continuously optimized according to theconditions in the power system.

Operational departments can plan for different operating conditions in the primaryequipment. The protection engineer can prepare the necessary optimized and pre-tested settings in advance for different protection functions. Six different groups ofsetting parameters are available in the IED. Any of them can be activated through thedifferent programmable binary inputs by means of external or internal control signals.

A function block, SETGRPS, defines how many setting groups are used. Setting isdone with parameter MAXSETGR and shall be set to the required value for each IED.Only the number of setting groups set will be available in the Parameter Setting toolfor activation with the ActiveGroup function block.

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 417Application manual

Page 424: Railway application RER670 Version 2.2 IEC ... - ABB

21.4.2 Setting guidelines

The setting ActiveSetGrp, is used to select which parameter group to be active. Theactive group can also be selected with configured input to the function blockSETGRPS.

The length of the pulse, sent out by the output signal SETCHGD when an active grouphas changed, is set with the parameter t.

The parameter MAXSETGR defines the maximum number of setting groups in use toswitch between. Only the selected number of setting groups will be available in theParameter Setting tool (PST) for activation with the ActiveGroup function block.

21.5 Rated system frequency PRIMVAL

21.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Primary system values PRIMVAL - -

21.5.2 Application

The rated system frequency and phase rotation direction are set under Main menu/Configuration/ Power system/ Primary Values in the local HMI and PCM600parameter setting tree.

21.5.3 Setting guidelines

Set the system rated frequency. Refer to section "Signal matrix for analog inputsSMAI" for description on frequency tracking.

21.6 Global base values GBASVAL

21.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Global base values GBASVAL - -

Section 21 1MRK 506 375-UEN -Basic IED functions

418 Railway application RER670 2.2 IECApplication manual

Page 425: Railway application RER670 Version 2.2 IEC ... - ABB

21.6.2 Application

Global base values function (GBASVAL) is used to provide global values, commonfor all applicable functions within the IED. One set of global values consists of valuesfor current, voltage and apparent power and it is possible to have twelve different sets.

This is an advantage since all applicable functions in the IED use a single source ofbase values. This facilitates consistency throughout the IED and also facilitates asingle point for updating values when necessary.

Each applicable function in the IED has a parameter, GlobalBaseSel, defining one outof the twelve sets of GBASVAL functions.

21.6.3 Setting guidelines

UBase: Phase-to-phase voltage value to be used as a base value for applicablefunctions throughout the IED.

IBase: Phase current value to be used as a base value for applicable functionsthroughout the IED.

SBase: Standard apparent power value to be used as a base value for applicablefunctions throughout the IED, typically SBase=UBase·IBase.

21.7 Signal matrix for binary inputs SMBI

21.7.1 Application

The Signal matrix for binary inputs function SMBI is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMBI represents theway binary inputs are brought in for one IED configuration.

21.7.2 Setting guidelines

There are no setting parameters for the Signal matrix for binary inputs SMBI availableto the user in Parameter Setting tool. However, the user shall give a name to SMBIinstance and the SMBI inputs, directly in the Application Configuration tool. Thesenames will define SMBI function in the Signal Matrix tool. The user defined name forthe input or output signal will also appear on the respective output or input signal.

21.8 Signal matrix for binary outputs SMBO

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 419Application manual

Page 426: Railway application RER670 Version 2.2 IEC ... - ABB

21.8.1 Application

The Signal matrix for binary outputs function SMBO is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMBO represents theway binary outputs are sent from one IED configuration.

21.8.2 Setting guidelines

There are no setting parameters for the Signal matrix for binary outputs SMBOavailable to the user in Parameter Setting tool. However, the user must give a name toSMBO instance and SMBO outputs, directly in the Application Configuration tool.These names will define SMBO function in the Signal Matrix tool.

21.9 Signal matrix for mA inputs SMMI

21.9.1 Application

The Signal matrix for mA inputs function SMMI is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMMI represents theway milliamp (mA) inputs are brought in for one IED configuration.

21.9.2 Setting guidelines

There are no setting parameters for the Signal matrix for mA inputs SMMI availableto the user in the Parameter Setting tool. However, the user must give a name to SMMIinstance and SMMI inputs, directly in the Application Configuration tool.

21.10 Signal matrix for analog inputs SMAI

21.10.1 Application

Signal matrix for analog inputs (SMAI), also known as the preprocessor functionblock, analyses the connected four analog signals (two Ph-N inputs, one Ph-Ph inputand neutral) and calculates all relevant information from them such as the phasormagnitude, phase angle, frequency, true RMS value, harmonics, sequencecomponents and so on. This information is then used by the respective functionsconnected to this SMAI block in the ACT (for example protection, measurement ormonitoring functions).

Section 21 1MRK 506 375-UEN -Basic IED functions

420 Railway application RER670 2.2 IECApplication manual

Page 427: Railway application RER670 Version 2.2 IEC ... - ABB

21.10.2 Frequency values

A valid input voltage signal level for frequency measurement can be set with SMAIsetting MinValFreqMeas in % of UBase. If the input signal level (positive sequenceor single phase voltage) is lower than the MinValFreqMeas level, then the frequencyoutput is invalid and the connected frequency functions will be blocked.

21.10.3 Setting guidelines

The parameters for the signal matrix for analog inputs (SMAI) functions are set via thelocal HMI or PCM600.

Application functions should be connected to a SMAI block with same task cycle asthe application function, except for e.g. measurement functions that run in slow cycletasks.

Negation: If the user wants to negate the 2ph signal, it is possible to choose to negateonly the phase signals Negate2Ph, only the neutral signal NegateN or both Negate2Ph+N. Negation means rotation with 180° of the vectors.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

MinValFreqMeas: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase (for each instance n).

A valid input voltage signal level for frequency measurement can be set with SMAIsetting MinValFreqMeas in % of UBase. If the input signal level (positive sequenceor single phase voltage) is lower than the MinValFreqMeas level, then the frequencyoutput is invalid and the connected frequency functions will be blocked.

Even if the user sets the AnalogInputType of a SMAI block to“Current”, the MinValFreqMeas is still visible. However, using thecurrent channel values as base for frequency measurement is notrecommendable for a number of reasons, not last among them beingthe low level of currents that one can have in normal operatingconditions.

The preprocessing block shall only be used to feed functions withinthe same execution cycles. The only exceptions are the measurementfunctions (CVMMXN, CMMXU,VMMXU, etc.).

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 421Application manual

Page 428: Railway application RER670 Version 2.2 IEC ... - ABB

21.11 Test mode functionality TESTMODE

21.11.1 Application

The protection and control IEDs may have a complex configuration with manyincluded functions. To make the testing procedure easier, the IEDs include the featurethat allows individual blocking of a single-, several-, or all functions.

This means that it is possible to see when a function is activated or trips. It also enablesthe user to follow the operation of several related functions to check correctfunctionality and to check parts of the configuration, and so on.

21.11.1.1 IEC 61850 protocol test mode

The IEC 61850 Test Mode has improved testing capabilities for IEC 61850 systems.Operator commands sent to the IEC 61850 Mod determine the behavior of thefunctions. The command can be given from the LHMI under the Main menu/Test/Function test modes menu or remotely from an IEC 61850 client. The possible valuesof IEC 61850 Mod are described in Communication protocol manual, IEC 61850Edition 1 and Edition 2.

To be able to set the IEC 61850 Mod the parameter remotely, the PSTsetting RemoteModControl may not be set to Off. The possible valuesare Off, Maintenance or All levels. The Off value denies all access todata object Mod from remote, Maintenance requires that the categoryof the originator (orCat) is Maintenance and All levels allow anyorCat.

The mod of the Root LD.LNN0 can be configured under Main menu/Test/Functiontest modes/Communication/Station communication/IEC61850 LD0 LLN0/LD0LLN0:1

When the Mod is changed at this level, all components under the logical device updatetheir own behavior according to IEC 61850-7-4. The supported values of IEC 61850Mod are described in Communication protocol manual, IEC 61850 Edition 2. TheIEC 61850 test mode is indicated with the Start LED on the LHMI.

The mod of an specific component can be configured under Main menu/Test/Function test modes/Communication/Station Communication

It is possible that the behavior is also influenced by other sources as well, independentof the mode, such as the insertion of the test handle, loss of SV, and IED configurationor LHMI. If a function of an IED is set to Off, the related Beh is set to Off as well. Therelated mod keeps its current state.

Section 21 1MRK 506 375-UEN -Basic IED functions

422 Railway application RER670 2.2 IECApplication manual

Page 429: Railway application RER670 Version 2.2 IEC ... - ABB

When the setting Operation is set to Off, the behavior is set to Off and it is not possibleto override it. When a behavior of a function is Offthe function will not execute.

When IEC 61850 Mod of a function is set to Off or Blocked, the StartLED on the LHMI will be set to flashing to indicate the abnormaloperation of the IED.

The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode andother states of mode and behavior.

• When the Beh of a component is set to Test, the component is not blocked and allcontrol commands with a test bit are accepted.

• When the Beh of a component is set to Test/blocked, all control commands witha test bit are accepted. Outputs to the process via a non-IEC 61850 link data areblocked by the LN. Only process-related outputs on LNs related to primaryequipment are blocked. If there is an XCBR, the outputs EXC_Open andEXC_Close are blocked.

• When the Beh of a component is set to Blocked, all control commands with a testbit are accepted. Outputs to the process via a non-IEC 61850 link data are blockedby the LN. In addition, the components can be blocked when their Beh isblocked. This can be done if the component has a block input. The block status ofa component is shown as the Blk output under the Test/Function status menu. Ifthe Blk output is not shown, the component cannot be blocked.

21.11.2 Setting guidelines

There are two possible ways to place the IED in the TestMode= On” state. If, the IEDis set to normal operation (TestMode = Off), but the functions are still shown being inthe test mode, the input signal INPUT on the TESTMODE function block might beactivated in the configuration.

Forcing of binary input and output signals is only possible when the IED is in IED testmode.

21.12 Time synchronization TIMESYNCHGEN

21.12.1 Application

Use time synchronization to achieve a common time base for the IEDs in a protectionand control system. This makes it possible to compare events and disturbance databetween all IEDs in the system. If a global common source (i.e. GPS) is used indifferent substations for the time synchronization, also comparisons and analysisbetween recordings made at different locations can be easily performed and a moreaccurate view of the actual sequence of events can be obtained.

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 423Application manual

Page 430: Railway application RER670 Version 2.2 IEC ... - ABB

Time-tagging of internal events and disturbances are an excellent help whenevaluating faults. Without time synchronization, only the events within one IED canbe compared with each other. With time synchronization, events and disturbanceswithin the whole network, can be compared and evaluated.

In the IED, the internal time can be synchronized from the following sources:

• GPS• IRIG-B• IEEE 1588 (PTP)

For IEDs using IEC/UCA 61850-9-2LE in "mixed mode" a time synchronizationfrom an external clock is recommended to the IED and all connected merging units.The time synchronization from the clock to the IED can be PTP, optical PPS or IRIG-B. For IEDs using IEC/UCA 61850-9-2LE from one single MU as analog data source,the MU and IED still need to be synchronized to each other. This could be done byletting the MU supply a PPS signal to the IED or by supplying a PPS signal from theIED to the MU, by using a GTM.

The selection of the time source is done via the corresponding setting.

It is possible to set a backup time-source for GPS signal, for instance SNTP. In thiscase, when the GPS signal quality is bad, the IED will automatically choose SNTP asthe time-source. At a given point in time, only one time-source will be used.

If PTP is activated, the device with the best accuracy within the synchronizing groupwill be selected as the source. For more information about PTP, see the Technicalmanual.

IEEE 1588 (PTP)PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3for power utility automation is a synchronization method that can be used to maintaina common time within a station. This time can be synchronized to the global timeusing, for instance, a GPS receiver. If PTP is enabled on the IEDs and the switches thatconnect the station are compatible with IEEE 1588, the station will becomesynchronized to one common time with an accuracy of under 1us. Using an IED as aboundary clock between several networks will keep 1us accuracy on three levels orwhen using an HSR, 15 IEDs can be connected in a ring without losing a singlemicrosecond in accuracy.

21.12.2 Setting guidelines

All the parameters related to time are divided into two categories: System time andSynchronization.

Section 21 1MRK 506 375-UEN -Basic IED functions

424 Railway application RER670 2.2 IECApplication manual

Page 431: Railway application RER670 Version 2.2 IEC ... - ABB

21.12.2.1 System time

21.12.2.2 Synchronization

The setting parameters for the real-time clock with external time synchronization areset via local HMI or PCM600. The path for Time Synchronization parameters on localHMI is Main menu/Configuration/Time/Synchronization. The parameters arecategorized as Time Synchronization (TIMESYNCHGEN) and IRIG-B settings(IRIG-B:1) in case that IRIG-B is used as the external time synchronization source.

IEEE 1588 (PTP)Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configurationtool /ECT) in PCM600.

PTP can be set to On,Off or Slave only. When set to Slave only the IED is connectedto the PTP-group and will synchronize to the grandmaster but cannot function as thegrandmaster.

A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To setone IED as the grandmaster change Priority2 to 127 instead of the default 128.

IEC16000093-1-en.vsdx

IEC16000093 V1 EN

Figure 175: Enabling PTP in ECT

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 425Application manual

Page 432: Railway application RER670 Version 2.2 IEC ... - ABB

Setting example

9-2

REC

PTP

PTP

Station bus

GPS

SAM600-TS

SAM600-CT

SAM600-VT

PTP

PTP

9-2

PTP

REL

MU

GTM

PPS

IEC16000167-1-en.vsdx

9-2

9-2 9-2

Process bus

IEC16000167 V1 EN

Figure 176: Example system

Figure 176 describes an example system. The REC and REL are both using the 9-2stream from the SAM600, and gets its synch from the GPS. Moreover, the REL andREC both acts as a boundary clock to provide synch to the SAM600. The RELcontains a GTM card, which has a PPS output that is used to synchronize mergingunits that are not PTP compliant. As a side effect, the GTM contains a GPS receiverand the REL acts as a backup of the GPS on the station bus.

On all access points, the PTP parameter is “ON”.

On the REL, the parameter FineSyncSource (under Configuration/Time/Synchronization/TIMESYNCHGEN:1/General) is set to “GPS” if there is a GPSantenna attached.

If the GTM is used as a PPS output only, the FineSynchSource is not set.

21.12.2.3 Process bus IEC/UCA 61850-9-2LE synchronization

When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it isessential that the merging units are synchronized with the hardware time of the IED(see Technical manual, section Design of the time system (clock synchronization) ). Toachieve this, PTP, PPS or IRIG-B can be used depending of the facilities of themerging unit.

If the merging unit supports PTP, use PTP. If PTP is used in the IED and the mergingunit is not PTP capable, then synchronize the merging unit from the IED via a PPS out

Section 21 1MRK 506 375-UEN -Basic IED functions

426 Railway application RER670 2.2 IECApplication manual

Page 433: Railway application RER670 Version 2.2 IEC ... - ABB

from the GTM. If PTP is used in the IED and the merging unit cannot be synchronizedfrom the IED, then use GPS-based clocks to provide PTP synch as well as sync to themerging unit.

If synchronization of the IED and the merging unit is based on GPS, set the parameterLostSyncMode to BlockOnLostUTC in order to provide a block of protection functionswhenever the global common time is lost.

If PTP is not used, use the same synchronization method for the HwSyncSrc as themerging unit provides. For instance, if the merging unit provides PPS assynchronization, use PPS as HwSyncSrc. If either PMU or LDCM in GPS-mode isused, that is, the hardware and software clocks are connected to each other,HwSyncSrc is not used and other means to synchronize the merging unit to the IED isrequired. Either FineSyncSource is set to the same source that the merging unit uses,or the PPS output from the GTM module is used to synchronize the merging unit. Ifthe PPS output from the GTM module is used to synchronize the merging unit and PTPis not used, the IED does not know how the merging unit is synchronized and theparameter LostSyncMode must be set to NoBlock.

1MRK 506 375-UEN - Section 21Basic IED functions

Railway application RER670 2.2 IEC 427Application manual

Page 434: Railway application RER670 Version 2.2 IEC ... - ABB

428

Page 435: Railway application RER670 Version 2.2 IEC ... - ABB

Section 22 Requirements

22.1 Current transformer requirements

The performance of a protection function will depend on the quality of the measuredcurrent signal. Saturation of the current transformers (CTs) will cause distortion of thecurrent signals and can result in a failure to operate or cause unwanted operations ofsome functions. Consequently CT saturation can have an influence on both thedependability and the security of the protection. This protection IED has beendesigned to permit heavy CT saturation with maintained correct operation.

22.1.1 Current transformer basic classification and requirements

To guarantee correct operation, the current transformers (CTs) must be able tocorrectly reproduce the current for a minimum time before the CT will begin tosaturate. To fulfill the requirement on a specified time to saturation the CTs mustfulfill the requirements of a minimum secondary e.m.f. that is specified below.

CTs are specified according to many different classes and standards. In principle,there are three different types of protection CTs. These types are related to the designof the iron core and the presence of airgaps. Airgaps affects the properties of theremanent flux.

The following three different types of protection CTs have been specified:

• The High Remanence type with closed iron core and no specified limit of theremanent flux

• The Low Remanence type with small airgaps in the iron core and the remanentflux limit is specified to be maximum 10% of the saturation flux

• The Non Remanence type with big airgaps in the iron core and the remanent fluxcan be neglected

Even though no limit of the remanent flux is specified in the IEC standard for closedcore CTs, it is a common opinion that the remanent flux is normally limited tomaximum 75 - 80 % of the saturation flux.

Since approximately year 2000 some CT manufactures have introduced new corematerials that gradually have increased the possible maximum levels of remanent fluxeven up to 95 % related to the hysteresis curve. Corresponding level of actualremanent flux is 90 % of the saturation flux (Ψsat). As the present CT standards haveno limitation of the level of remanent flux, these CTs are also classified as forexample, class TPX, P and PX according to IEC. The IEC TR 61869-100, Edition 1.02017-01, Instrument transformers – Guidance for application of current transformers

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 429Application manual

Page 436: Railway application RER670 Version 2.2 IEC ... - ABB

in power system protection, is the first official document that highlighted thisdevelopment. So far remanence factors of maximum 80% have been considered whenCT requirements have been decided for ABB IEDs. Even in the future this level ofremanent flux probably will be the maximum level that will be considered whendecided the CT requirements. If higher remanence levels should be considered, itshould often lead to unrealistic CT sizes.

Thus, now there is a need to limit the acceptable level of remanent flux. To be able toguarantee the performance of protection IEDs, we need to introduce the followingclassification of CTs.

There are many different standards and a lot of classes but fundamentally there arefour different types of CTs:

• Very High Remanence type CT• High Remanence type CT• Low Remanence type CT• Non Remanence type CT

The Very High Remanence (VHR) type is a CT with closed iron core (for example.protection classes TPX, P, PX according to IEC, class C, K according to ANSI/IEEE)and with an iron core material (new material, typically new alloy based magneticmaterials) that gives a remanent flux higher than 80 % of the saturation flux.

The High Remanence (HR) type is a CT with closed iron core (for example,protection classes TPX, P, PX according to IEC, class C, K according to ANSI/IEEE)but with an iron core material (traditional material) that gives a remanent flux that islimited to maximum 80 % of the saturation flux.

The Low Remanence (LR) type is a CT with small airgaps in the iron core (forexample, TPY, PR, PXR according to IEC) and the remanent flux limit is specified tobe maximum 10% of the saturation flux.

The Non Remanence (NR) type is a CT with big airgaps in the core (for example,TPZ according to IEC) and the remanent flux can be neglected.

It is also possible that different CT classes of HR and LR type may be mixed.

CT type VHR (using new material) should not be used for protection CT cores. Thismeans that it is important to specify that the remanence factor must not exceed 80 %when ordering for example, class P, PX or TPX CTs. If CT manufacturers are usingnew core material and are not able to fulfill this requirement, the CTs shall be specifiedwith small airgaps and therefore will be CTs of LR type (for example, class PR, TPYor PXR). Very high remanence level in a protection core CT can cause the followingproblems for protection IEDs:

1. Unwanted operation of differential (i.e. unit) protections for external faults2. Unacceptably delayed or even missing operation of all types of protections (for

example, distance, differential, overcurrent, etc.) which can result in loosingprotection selectivity in the network

Section 22 1MRK 506 375-UEN -Requirements

430 Railway application RER670 2.2 IECApplication manual

Page 437: Railway application RER670 Version 2.2 IEC ... - ABB

No information is available about how frequent the use of the new iron core materialis for protection CT cores, but it is known that some CT manufacturers are using thenew material while other manufacturers continue to use the old traditional corematerial for protection CT cores. In a case where VHR type CTs have been alreadyinstalled, the calculated values of Eal for HR type CTs, for which the formulas aregiven in this document, must be multiplied by factor two-and-a-half in order for VHRtype CTs (i.e. with new material) to be used together with ABB protection IEDs.However, this may result in unacceptably big CT cores, which can be difficult tomanufacture and fit in available space.

Different standards and classes specify the saturation e.m.f. in different ways but it ispossible to approximately compare values from different classes. The rated equivalentlimiting secondary e.m.f. Eal according to the IEC 61869–2 standard is used to specifythe CT requirements for the IED. The requirements are also specified according toother standards.

22.1.2 Conditions

The requirements are a result of investigations performed in our network simulator.The current transformer models are representative for current transformers of highremanence and low remanence type. The results may not always be valid for nonremanence type CTs (TPZ).

The performances of the protection functions have been checked in the range fromsymmetrical to fully asymmetrical fault currents. Primary time constants of at least120 ms have been considered at the tests. The current requirements below are thusapplicable both for symmetrical and asymmetrical fault currents.

Depending on the protection function phase-to-earth, phase-to-phase and three-phasefaults have been tested for different relevant fault positions for example, close inforward and reverse faults, zone 1 reach faults, internal and external faults. Thedependability and security of the protection was verified by checking for example,time delays, unwanted operations, directionality, overreach and stability.

The remanence in the current transformer core can cause unwanted operations orminor additional time delays for some protection functions. As unwanted operationsare not acceptable at all maximum remanence has been considered for fault casescritical for the security, for example, faults in reverse direction and external faults.Because of the almost negligible risk of additional time delays and the non-existentrisk of failure to operate the remanence have not been considered for the dependabilitycases. The requirements below are therefore fully valid for all normal applications.

It is difficult to give general recommendations for additional margins for remanenceto avoid the minor risk of an additional time delay. They depend on the performanceand economy requirements. When current transformers of low remanence type (forexample, TPY, PR) are used, normally no additional margin is needed. For currenttransformers of high remanence type (for example, P, PX, TPX) the small probabilityof fully asymmetrical faults, together with high remanence in the same direction as theflux generated by the fault, has to be kept in mind at the decision of an additional

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 431Application manual

Page 438: Railway application RER670 Version 2.2 IEC ... - ABB

margin. Fully asymmetrical fault current will be achieved when the fault occurs atapproximately zero voltage (0°). Investigations have shown that 95% of the faults inthe network will occur when the voltage is between 40° and 90°. In addition fullyasymmetrical fault current will not exist in all phases at the same time.

22.1.3 Fault current

The current transformer requirements are based on the maximum fault current forfaults in different positions. Maximum fault current will occur for three-phase faultsor single phase-to-earth faults. The current for a single phase-to-earth fault will exceedthe current for a three-phase fault when the zero sequence impedance in the total faultloop is less than the positive sequence impedance.

When calculating the current transformer requirements, maximum fault current forthe relevant fault position should be used and therefore both fault types have to beconsidered.

22.1.4 Secondary wire resistance and additional load

The voltage at the current transformer secondary terminals directly affects the currenttransformer saturation. This voltage is developed in a loop containing the secondarywires and the burden of all relays in the circuit. For earth faults the loop includes thephase and neutral wire, normally twice the resistance of the single secondary wire. Forthree-phase faults the neutral current is zero and it is just necessary to consider theresistance up to the point where the phase wires are connected to the common neutralwire. The most common practice is to use four wires secondary cables so it normallyis sufficient to consider just a single secondary wire for the three-phase case.

The conclusion is that the loop resistance, twice the resistance of the single secondarywire, must be used in the calculation for phase-to-earth faults and the phase resistance,the resistance of a single secondary wire, may normally be used in the calculation forthree-phase faults.

As the burden can be considerable different for three-phase faults and phase-to-earthfaults it is important to consider both cases. Even in a case where the phase-to-earthfault current is smaller than the three-phase fault current the phase-to-earth fault canbe dimensioning for the CT depending on the higher burden.

In isolated or high impedance earthed systems the phase-to-earth fault is not thedimensioning case. Therefore, the resistance of the single secondary wire can alwaysbe used in the calculation for this kind of power systems.

22.1.5 General current transformer requirements

The current transformer ratio is mainly selected based on power system data forexample, maximum load and/or maximum fault current. It should be verified that thecurrent to the protection is higher than the minimum operating value for all faults that

Section 22 1MRK 506 375-UEN -Requirements

432 Railway application RER670 2.2 IECApplication manual

Page 439: Railway application RER670 Version 2.2 IEC ... - ABB

are to be detected with the selected CT ratio. It should also be verified that themaximum possible fault current is within the limits of the IED.

The current error of the current transformer can limit the possibility to use a verysensitive setting of a sensitive residual overcurrent protection. If a very sensitivesetting of this function will be used it is recommended that the current transformershould have an accuracy class which have an current error at rated primary current thatis less than ±1% (for example, 5P). If current transformers with less accuracy are usedit is advisable to check the actual unwanted residual current during thecommissioning.

22.1.6 Rated equivalent secondary e.m.f. requirements

With regard to saturation of the current transformer all current transformers of highremanence and low remanence type that fulfill the requirements on the ratedequivalent limiting secondary e.m.f. Eal below can be used. The characteristic of thenon remanence type CT (TPZ) is not well defined as far as the phase angle error isconcerned. If no explicit recommendation is given for a specific function we thereforerecommend contacting ABB to confirm that the non remanence type can be used.

The CT requirements for the different functions below are specified as a ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard.Requirements for CTs specified according to other classes and standards are given atthe end of this section.

22.1.6.1 Breaker failure protection

The CTs must have a rated equivalent limiting secondary e.m.f. Eal that is larger thanor equal to the required rated equivalent limiting secondary e.m.f. Ealreq below:

sr Ral alreq op ct L 2

pr r

I SE E 5 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1380 V2 EN (Equation 78)

where:

Iop The primary operate value (A)

Ipr The rated primary CT current (A)

Isr The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

Rct The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistance containingthe phase and neutral wires, must be used for faults in solidly earthed systems. The resistanceof a single secondary wire should be used for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir=1 A and SR=0.150VA/channel for Ir=5 A

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 433Application manual

Page 440: Railway application RER670 Version 2.2 IEC ... - ABB

22.1.6.2 Restricted earth fault protection (low impedance differential)

The requirements are specified separately for solidly earthed and impedance earthedtransformers. For impedance earthed transformers the requirements for the phase CTsare depending whether it is three individual CTs connected in parallel or it is a cableCT enclosing all three phases.

Neutral CTs and phase CTs for solidly earthed transformersThe neutral CT and the phase CTs must have a rated equivalent limiting secondarye.m.f. Eal that is larger than or equal to the maximum of the required rated equivalentlimiting secondary e.m.f. Ealreq below:

230 sr Ral alreq rt ct L

pr r

I SE E I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION2237 V2 EN (Equation 79)

22 sr Ral alreq etf ct L

pr r

I SE E I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION2238 V2 EN (Equation 80)

Where:

Irt The rated primary current of the power transformer (A)

Ietf Maximum primary fundamental frequency phase-to-earth fault current that passes theCTs and the power transformer neutral (A)

Ipr The rated primary CT current (A)

Isr The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

Rct The secondary resistance of the CT (Ω)

RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.

SR The burden of a REx670 current input channel (VA). SR=0.020 VA / channel for IR = 1A and SR = 0.150 VA / channel for IR = 5 A

In substations with breaker-and-a-half or double-busbar double-breaker arrangement,the fault current may pass two main phase CTs for the restricted earth fault protectionwithout passing the power transformer. In such cases and if both main CTs have equalratios and magnetization characteristics the CTs must satisfy Requirement 79 and theRequirement 80:

2sr R

al alreq ef ct Lpr r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION2239 V2 EN (Equation 81)

Section 22 1MRK 506 375-UEN -Requirements

434 Railway application RER670 2.2 IECApplication manual

Page 441: Railway application RER670 Version 2.2 IEC ... - ABB

Where:

Ief Maximum primary fundamental frequency phase-to-earth fault current that passes twomain CTs without passing the power transformer neutral (A)

Neutral CTs and phase CTs for impedance earthed transformersThe neutral CT and phase CTs must have a rated equivalent limiting secondary e.m.f.Eal that is larger than or equal to the required rated equivalent limiting secondary e.m.f.Ealreq below:

23 sr Ral alreq etf ct L

pr r

I SE E I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION2240 V2 EN (Equation 82)

Where:

Ietf Maximum primary fundamental frequency phase-to-earth fault current that passesthe CTs and the power transformer neutral (A)

Ipr The rated primary CT current (A)

Isr The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

Rct The secondary resistance of the CT (Ω)

RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.

SR The burden of a REx670 current input channel (VA). SR = 0.020 VA / channel for Ir= 1 A and SR = 0.150 VA / channel for Ir = 5 A

In case of three individual CTs connected in parallel (Holmgren connection) on thephase side the following additional requirements must also be fulfilled.

The three individual phase CTs must have a rated equivalent limiting secondary e.m.f.Eal that is larger than or equal to the maximum of the required rated equivalent limitingsecondary e.m.f. Ealreq below:

22 sr Ral alreq tf ct Lsw

pr r

I SE E I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION2241 V2 EN (Equation 83)

Where:

Itf Maximum primary fundamental frequency three-phase fault current that passes theCTs and the power transformer (A).

RLsw The resistance of the single secondary wire and additional load (Ω).

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 435Application manual

Page 442: Railway application RER670 Version 2.2 IEC ... - ABB

In impedance earthed systems the phase-to-earth fault currents often are relativelysmall and the requirements might result in small CTs. However, in applications wherethe zero sequence current from the phase side of the transformer is a summation ofcurrents from more than one CT (cable CTs or groups of individual CTs in Holmgrenconnection) for example, in substations with breaker-and-a-half or double-busbardouble-breaker arrangement or if the transformer has a T-connection to differentbusbars, there is a risk that the CTs can be exposed for higher fault currents than theconsidered phase-to-earth fault currents above. Examples of such cases can be cross-country faults or phase-to-phase faults with high fault currents and unsymmetricaldistribution of the phase currents between the CTs. The zero sequence fault currentlevel can differ much and is often difficult to calculate or estimate for different cases.To cover these cases, with summation of zero sequence currents from more than oneCT, the phase side CTs must fulfill the Requirement 84 below:

2sr R

al alreq f ct Lpr r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION2242 V2 EN (Equation 84)

Where:

If Maximum primary fundamental frequency three-phase fault current that passes theCTs (A)

RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.

22.1.7 Current transformer requirements for CTs according to otherstandards

All kinds of conventional magnetic core CTs are possible to use with the IEDs if theyfulfill the requirements corresponding to the above specified expressed as the ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard. Fromdifferent standards and available data for relaying applications it is possible toapproximately calculate a secondary e.m.f. of the CT comparable with Eal. Bycomparing this with the required rated equivalent limiting secondary e.m.f. Ealreq it ispossible to judge if the CT fulfills the requirements. The requirements according tosome other standards are specified below.

22.1.7.1 Current transformers according to IEC 61869-2, class P, PR

A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. EALF.The value of the EALF is approximately equal to the corresponding Eal. Therefore, theCTs according to class P and PR must have a secondary limiting e.m.f. EALF thatfulfills the following:

Section 22 1MRK 506 375-UEN -Requirements

436 Railway application RER670 2.2 IECApplication manual

Page 443: Railway application RER670 Version 2.2 IEC ... - ABB

ALF alreqE maxE

EQUATION1383 V4 EN (Equation 85)

22.1.7.2 Current transformers according to IEC 61869-2, class PX, PXR (andold IEC 60044-6, class TPS and old British Standard, class X)

CTs according to these classes are specified approximately in the same way by a ratedknee point e.m.f. Eknee (Ek for class PX and PXR, EkneeBS for class X and the limitingsecondary voltage Ual for TPS). The value of the Eknee is lower than the correspondingEal according to IEC 61869-2. It is not possible to give a general relation between theEknee and the Eal but normally the Eknee is approximately 80 % of the Eal. Therefore,the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f.Eknee that fulfills the following:

( )knee k kneeBS al alreqE E E U 0.8 maximum of E» » » > ×

EQUATION2100 V2 EN (Equation 86)

22.1.7.3 Current transformers according to ANSI/IEEE

Current transformers according to ANSI/IEEE are partly specified in different ways.A rated secondary terminal voltage UANSI is specified for a CT of class C. UANSI is thesecondary terminal voltage the CT will deliver to a standard burden at 20 times ratedsecondary current without exceeding 10 % ratio correction. There are a number ofstandardized UANSI values for example, UANSI is 400 V for a C400 CT. Acorresponding rated equivalent limiting secondary e.m.f. EalANSI can be estimated asfollows:

alANSI sr ct ANSI sr ct sr bANSIE 20 I R U 20 I R 20 I Z= × × + = × × + × ×

EQUATION971 V2 EN (Equation 87)

where:

ZbANSI The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific Cclass (W)

UANSI The secondary terminal voltage for the specific C class (V)

The CTs according to class C must have a calculated rated equivalent limitingsecondary e.m.f. EalANSI that fulfils the following:

alANSI alreqE maximum of E>

EQUATION1384 V2 EN (Equation 88)

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 437Application manual

Page 444: Railway application RER670 Version 2.2 IEC ... - ABB

A CT according to ANSI/IEEE is also specified by the knee point voltage UkneeANSIthat is graphically defined from an excitation curve. The knee point voltage UkneeANSInormally has a lower value than the knee-point e.m.f. according to IEC and BS.UkneeANSI can approximately be estimated to 75 % of the corresponding Eal accordingto IEC 61869-2. Therefore, the CTs according to ANSI/IEEE must have a knee pointvoltage UkneeANSI that fulfills the following:

kneeANSI alreqV 0.75 (max imum of E )> ×EQUATION2101 V2 EN (Equation 89)

22.2 Voltage transformer requirements

The performance of a protection function will depend on the quality of the measuredinput signal. Transients caused by capacitive voltage transformers (CVTs) can affectsome protection functions.

Magnetic or capacitive voltage transformers can be used.

The capacitive voltage transformers (CVTs) should fulfill the requirements accordingto the IEC 61869-5 standard regarding ferro-resonance and transients. The ferro-resonance requirements of the CVTs are specified in chapter 6.502 of the standard.

The transient responses for three different standard transient response classes, T1, T2and T3 are specified in chapter 6.503 of the standard. CVTs according to all classescan be used.

The protection IED has effective filters for these transients, which gives secure andcorrect operation with CVTs.

22.3 SNTP server requirements

The SNTP server to be used is connected to the local network, that is not more than 4-5switches or routers away from the IED. The SNTP server is dedicated for its task, orat least equipped with a real-time operating system, that is not a PC with SNTP serversoftware. The SNTP server should be stable, that is, either synchronized from a stablesource like GPS, or local without synchronization. Using a local SNTP server withoutsynchronization as primary or secondary server in a redundant configuration is notrecommended.

Section 22 1MRK 506 375-UEN -Requirements

438 Railway application RER670 2.2 IECApplication manual

Page 445: Railway application RER670 Version 2.2 IEC ... - ABB

22.4 PTP requirements

For PTP to perform properly, the Ethernet equipment that is used needs to becompliant with IEEE1588. The clocks used must follow the IEEE1588 standard BMC(Best Master Algorithm) and shall, for instance, not claim class 7 for a longer timethan it can guarantee 1us absolute accuracy.

22.5 Sample specification of communication requirementsfor the protection and control terminals in digitaltelecommunication networks

The communication requirements are based on echo timing.

Bit Error Rate (BER) according to ITU-T G.821, G.826 and G.828

• <10-6 according to the standard for data and voice transfer

Bit Error Rate (BER) for high availability of the differential protection

• <10-8-10-9 during normal operation• <10-6 during disturbed operation

During disturbed conditions, the trip security function can cope with high bit errorrates up to 10-5 or even up to 10-4. The trip security can be configured to beindependent of COMFAIL from the differential protection communicationsupervision, or blocked when COMFAIL is issued after receive error >100ms.(Default).

Synchronization in SDH systems with G.703 E1 or IEEE C37.94

The G.703 E1, 2 Mbit shall be set according to ITU-T G.803, G.810-13

• One master clock for the actual network• The actual port Synchronized to the SDH system clock at 2048 kbit• Synchronization; bit synchronized, synchronized mapping• Maximum clock deviation <±50 ppm nominal, <±100 ppm operational• Jitter and Wander according to ITU-T G.823 and G.825• Buffer memory <250 μs, <100 μs asymmetric difference• Format.G 704 frame, structured etc.Format.• No CRC-check

Synchronization in PDH systems connected to SDH systems

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 439Application manual

Page 446: Railway application RER670 Version 2.2 IEC ... - ABB

• Independent synchronization, asynchronous mapping• The actual SDH port must be set to allow transmission of the master clock from

the PDH-system via the SDH-system in transparent mode.• Maximum clock deviation <±50 ppm nominal, <±100 ppm operational• Jitter and Wander according to ITU-T G.823 and G.825• Buffer memory <100 μs• Format: Transparent• Maximum channel delay• Loop time <40 ms continuous (2 x 20 ms)

IED with echo synchronization of differential clock (without GPS clock)

• Both channels must have the same route with maximum asymmetry of 0,2-0,5ms, depending on set sensitivity of the differential protection.

• A fixed asymmetry can be compensated (setting of asymmetric delay in built inHMI or the parameter setting tool PST).

IED with GPS clock

• Independent of asymmetry.

22.6 IEC/UCA 61850-9-2LE Merging unit requirements

The merging units that supply the IED with measured values via the process bus mustfulfill the IEC/UCA 61850-9-2LE standard.

This part of the IEC 61850 is specifying “Communication Service Mapping (SCSM)– Sampled values over ISO/IEC 8802”, in other words – sampled data over Ethernet.The 9-2 part of the IEC 61850 protocol uses also definitions from 7-2, “Basiccommunication structure for substation and feeder equipment – Abstractcommunication service interface (ACSI)”. The set of functionality implemented inthe IED (IEC/UCA 61850-9-2LE) is a subset of the IEC 61850-9-2. For example theIED covers the client part of the standard, not the server part.

The standard does not define the sample rate for data, but in the UCA users grouprecommendations there are indicated sample rates that are adopted, by consensus, inthe industry.

There are two sample rates defined: 80 samples/cycle (4000 samples/sec. at 50Hz or4800 samples/sec. at 60 Hz) for a merging unit “type1” and 256 samples/cycle for amerging unit “type2”. The IED can receive data rates of 80 samples/cycle.

Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of thesampled values, only the transportation. Thus, the accuracy of the current and voltageinputs to the merging unit and the inaccuracy added by the merging unit must becoordinated with the requirement for actual type of protection function.

Section 22 1MRK 506 375-UEN -Requirements

440 Railway application RER670 2.2 IECApplication manual

Page 447: Railway application RER670 Version 2.2 IEC ... - ABB

Factors influencing the accuracy of the sampled values from the merging unit are forexample anti aliasing filters, frequency range, step response, truncating, A/Dconversion inaccuracy, time tagging accuracy etc.

In principle the accuracy of the current and voltage transformers, together with themerging unit, shall have the same quality as direct input of currents and voltages.

1MRK 506 375-UEN - Section 22Requirements

Railway application RER670 2.2 IEC 441Application manual

Page 448: Railway application RER670 Version 2.2 IEC ... - ABB

442

Page 449: Railway application RER670 Version 2.2 IEC ... - ABB

Section 23 Glossary

AC Alternating current

ACC Actual channel

ACT Application configuration tool within PCM600

A/D converter Analog-to-digital converter

ADBS Amplitude deadband supervision

ADM Analog digital conversion module, with timesynchronization

AI Analog input

ANSI American National Standards Institute

AR Autoreclosing

ASCT Auxiliary summation current transformer

ASD Adaptive signal detection

ASDU Application service data unit

AWG American Wire Gauge standard

BBP Busbar protection

BFOC/2,5 Bayonet fibre optic connector

BFP Breaker failure protection

BI Binary input

BIM Binary input module

BOM Binary output module

BOS Binary outputs status

BR External bistable relay

BS British Standards

BSR Binary signal transfer function, receiver blocks

BST Binary signal transfer function, transmit blocks

C37.94 IEEE/ANSI protocol used when sending binary signalsbetween IEDs

CAN Controller Area Network. ISO standard (ISO 11898) forserial communication

CB Circuit breaker

CBM Combined backplane module

1MRK 506 375-UEN - Section 23Glossary

Railway application RER670 2.2 IEC 443Application manual

Page 450: Railway application RER670 Version 2.2 IEC ... - ABB

CCITT Consultative Committee for International Telegraph andTelephony. A United Nations-sponsored standards bodywithin the International Telecommunications Union.

CCM CAN carrier module

CCVT Capacitive Coupled Voltage Transformer

Class C Protection Current Transformer class as per IEEE/ ANSI

CMPPS Combined megapulses per second

CMT Communication Management tool in PCM600

CO cycle Close-open cycle

Codirectional Way of transmitting G.703 over a balanced line. Involvestwo twisted pairs making it possible to transmit informationin both directions

COM Command

COMTRADE Standard Common Format for Transient Data Exchangeformat for Disturbance recorder according to IEEE/ANSIC37.111, 1999 / IEC 60255-24

Contra-directional Way of transmitting G.703 over a balanced line. Involvesfour twisted pairs, two of which are used for transmittingdata in both directions and two for transmitting clocksignals

COT Cause of transmission

CPU Central processing unit

CR Carrier receive

CRC Cyclic redundancy check

CROB Control relay output block

CS Carrier send

CT Current transformer

CU Communication unit

CVT or CCVT Capacitive voltage transformer

DAR Delayed autoreclosing

DARPA Defense Advanced Research Projects Agency (The USdeveloper of the TCP/IP protocol etc.)

DBDL Dead bus dead line

DBLL Dead bus live line

DC Direct current

DFC Data flow control

DFT Discrete Fourier transform

Section 23 1MRK 506 375-UEN -Glossary

444 Railway application RER670 2.2 IECApplication manual

Page 451: Railway application RER670 Version 2.2 IEC ... - ABB

DHCP Dynamic Host Configuration Protocol

DIP-switch Small switch mounted on a printed circuit board

DI Digital input

DLLB Dead line live bus

DNP Distributed Network Protocol as per IEEE Std 1815-2012

DR Disturbance recorder

DRAM Dynamic random access memory

DRH Disturbance report handler

DSP Digital signal processor

DTT Direct transfer trip scheme

ECT Ethernet configuration tool

EHV network Extra high voltage network

EIA Electronic Industries Association

EMC Electromagnetic compatibility

EMF Electromotive force

EMI Electromagnetic interference

EnFP End fault protection

EPA Enhanced performance architecture

ESD Electrostatic discharge

F-SMA Type of optical fibre connector

FAN Fault number

FCB Flow control bit; Frame count bit

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signals

FOX 512/515 Access multiplexer

FOX 6Plus Compact time-division multiplexer for the transmission ofup to seven duplex channels of digital data over opticalfibers

FPN Flexible product naming

FTP File Transfer Protocol

FUN Function type

G.703 Electrical and functional description for digital lines usedby local telephone companies. Can be transported overbalanced and unbalanced lines

GCM Communication interface module with carrier of GPSreceiver module

1MRK 506 375-UEN - Section 23Glossary

Railway application RER670 2.2 IEC 445Application manual

Page 452: Railway application RER670 Version 2.2 IEC ... - ABB

GDE Graphical display editor within PCM600

GI General interrogation command

GIS Gas-insulated switchgear

GOOSE Generic object-oriented substation event

GPS Global positioning system

GSAL Generic security application

GSE Generic substation event

HDLC protocol High-level data link control, protocol based on the HDLCstandard

HFBR connector type Plastic fiber connector

HMI Human-machine interface

HSAR High speed autoreclosing

HSR High-availability Seamless Redundancy

HV High-voltage

HVDC High-voltage direct current

IDBS Integrating deadband supervision

IEC International Electrical Committee

IEC 60044-6 IEC Standard, Instrument transformers – Part 6:Requirements for protective current transformers fortransient performance

IEC 60870-5-103 Communication standard for protection equipment. A serialmaster/slave protocol for point-to-point communication

IEC 61850 Substation automation communication standard

IEC 61850–8–1 Communication protocol standard

IEEE Institute of Electrical and Electronics Engineers

IEEE 802.12 A network technology standard that provides 100 Mbits/son twisted-pair or optical fiber cable

IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules.References the CMC (IEEE P1386, also known as CommonMezzanine Card) standard for the mechanics and the PCIspecifications from the PCI SIG (Special Interest Group) forthe electrical EMF (Electromotive force).

IEEE 1686 Standard for Substation Intelligent Electronic Devices(IEDs) Cyber Security Capabilities

IED Intelligent electronic device

IET600 Integrated engineering tool

I-GIS Intelligent gas-insulated switchgear

Section 23 1MRK 506 375-UEN -Glossary

446 Railway application RER670 2.2 IECApplication manual

Page 453: Railway application RER670 Version 2.2 IEC ... - ABB

IOM Binary input/output module

Instance When several occurrences of the same function areavailable in the IED, they are referred to as instances of thatfunction. One instance of a function is identical to another ofthe same kind but has a different number in the IED userinterfaces. The word "instance" is sometimes defined as anitem of information that is representative of a type. In thesame way an instance of a function in the IED isrepresentative of a type of function.

IP 1. Internet protocol. The network layer for the TCP/IPprotocol suite widely used on Ethernet networks. IP is aconnectionless, best-effort packet-switching protocol. Itprovides packet routing, fragmentation and reassemblythrough the data link layer.2. Ingression protection, according to IEC 60529

IP 20 Ingression protection, according to IEC 60529, level 20

IP 40 Ingression protection, according to IEC 60529, level 40

IP 54 Ingression protection, according to IEC 60529, level 54

IRF Internal failure signal

IRIG-B: InterRange Instrumentation Group Time code format B,standard 200

ITU International Telecommunications Union

LAN Local area network

LIB 520 High-voltage software module

LCD Liquid crystal display

LDCM Line data communication module

LDD Local detection device

LED Light-emitting diode

LNT LON network tool

LON Local operating network

MCB Miniature circuit breaker

MCM Mezzanine carrier module

MIM Milli-ampere module

MPM Main processing module

MVAL Value of measurement

MVB Multifunction vehicle bus. Standardized serial busoriginally developed for use in trains.

NCC National Control Centre

1MRK 506 375-UEN - Section 23Glossary

Railway application RER670 2.2 IEC 447Application manual

Page 454: Railway application RER670 Version 2.2 IEC ... - ABB

NOF Number of grid faults

NUM Numerical module

OCO cycle Open-close-open cycle

OCP Overcurrent protection

OEM Optical Ethernet module

OLTC On-load tap changer

OTEV Disturbance data recording initiated by other event thanstart/pick-up

OV Overvoltage

Overreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is overreachingwhen the impedance presented to it is smaller than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhapsit should not have seen it.

PCI Peripheral component interconnect, a local data bus

PCM Pulse code modulation

PCM600 Protection and control IED manager

PC-MIP Mezzanine card standard

PMC PCI Mezzanine card

POR Permissive overreach

POTT Permissive overreach transfer trip

Process bus Bus or LAN used at the process level, that is, in nearproximity to the measured and/or controlled components

PRP Parallel redundancy protocol

PSM Power supply module

PST Parameter setting tool within PCM600

PTP Precision time protocol

PT ratio Potential transformer or voltage transformer ratio

PUTT Permissive underreach transfer trip

RASC Synchrocheck relay, COMBIFLEX

RCA Relay characteristic angle

RISC Reduced instruction set computer

RMS value Root mean square value

RS422 A balanced serial interface for the transmission of digitaldata in point-to-point connections

RS485 Serial link according to EIA standard RS485

Section 23 1MRK 506 375-UEN -Glossary

448 Railway application RER670 2.2 IECApplication manual

Page 455: Railway application RER670 Version 2.2 IEC ... - ABB

RTC Real-time clock

RTU Remote terminal unit

SA Substation Automation

SBO Select-before-operate

SC Switch or push button to close

SCL Short circuit location

SCS Station control system

SCADA Supervision, control and data acquisition

SCT System configuration tool according to standard IEC 61850

SDU Service data unit

SFP Small form-factor pluggable (abbreviation)Optical Ethernet port (explanation)

SLM Serial communication module.

SMA connector Subminiature version A, A threaded connector withconstant impedance.

SMT Signal matrix tool within PCM600

SMS Station monitoring system

SNTP Simple network time protocol – is used to synchronizecomputer clocks on local area networks. This reduces therequirement to have accurate hardware clocks in everyembedded system in a network. Each embedded node caninstead synchronize with a remote clock, providing therequired accuracy.

SOF Status of fault

SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocol for point-to-point and ring communication.

SRY Switch for CB ready condition

ST Switch or push button to trip

Starpoint Neutral point of transformer or generator

SVC Static VAr compensation

TC Trip coil

TCS Trip circuit supervision

TCP Transmission control protocol. The most common transportlayer protocol used on Ethernet and the Internet.

TCP/IP Transmission control protocol over Internet Protocol. Thede facto standard Ethernet protocols incorporated into4.2BSD Unix. TCP/IP was developed by DARPA for

1MRK 506 375-UEN - Section 23Glossary

Railway application RER670 2.2 IEC 449Application manual

Page 456: Railway application RER670 Version 2.2 IEC ... - ABB

Internet working and encompasses both network layer andtransport layer protocols. While TCP and IP specify twoprotocols at specific protocol layers, TCP/IP is often used torefer to the entire US Department of Defense protocol suitebased upon these, including Telnet, FTP, UDP and RDP.

TEF Time delayed earth-fault protection function

TLS Transport Layer Security

TM Transmit (disturbance data)

TNC connector Threaded Neill-Concelman, a threaded constant impedanceversion of a BNC connector

TP Trip (recorded fault)

TPZ, TPY, TPX, TPS Current transformer class according to IEC

TRM Transformer Module. This module transforms currents andvoltages taken from the process into levels suitable forfurther signal processing.

TYP Type identification

UMT User management tool

Underreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is underreachingwhen the impedance presented to it is greater than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay does not “see” the fault butperhaps it should have seen it. See also Overreach.

UTC Coordinated Universal Time. A coordinated time scale,maintained by the Bureau International des Poids etMesures (BIPM), which forms the basis of a coordinateddissemination of standard frequencies and time signals.UTC is derived from International Atomic Time (TAI) bythe addition of a whole number of "leap seconds" tosynchronize it with Universal Time 1 (UT1), thus allowingfor the eccentricity of the Earth's orbit, the rotational axis tilt(23.5 degrees), but still showing the Earth's irregularrotation, on which UT1 is based. The CoordinatedUniversal Time is expressed using a 24-hour clock, and usesthe Gregorian calendar. It is used for aeroplane and shipnavigation, where it is also sometimes known by themilitary name, "Zulu time." "Zulu" in the phonetic alphabetstands for "Z", which stands for longitude zero.

UV Undervoltage

WEI Weak end infeed logic

VT Voltage transformer

Section 23 1MRK 506 375-UEN -Glossary

450 Railway application RER670 2.2 IECApplication manual

Page 457: Railway application RER670 Version 2.2 IEC ... - ABB

X.21 A digital signalling interface primarily used for telecomequipment

3IO Three times zero-sequence current.Often referred to as theresidual or the earth-fault current

3UO Three times the zero sequence voltage. Often referred to asthe residual voltage or the neutral point voltage

1MRK 506 375-UEN - Section 23Glossary

Railway application RER670 2.2 IEC 451Application manual

Page 458: Railway application RER670 Version 2.2 IEC ... - ABB

452

Page 459: Railway application RER670 Version 2.2 IEC ... - ABB

453

Page 460: Railway application RER670 Version 2.2 IEC ... - ABB

—ABB AB Grid Automation Products721 59 Västerås, SwedenPhone: +46 (0) 21 32 50 00

abb.com/protection-control

© Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. 1M

RK

50

6 3

75-U

EN