RELION® 670 SERIES — Railway application RER670 Version 2.2 IEC Application manual
Document ID: 1MRK 506 375-UENIssued: May 2017
Revision: -Product version: 2.2
© Copyright 2017 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license andmay be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographicsoftware written/developed by: Eric Young ([email protected]) and Tim Hudson([email protected]).
TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.
WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandard EN 60255-26 for the EMC directive, and with the product standards EN60255-1 and EN 60255-27 for the low voltage directive. The product is designed inaccordance with the international standards of the IEC 60255 series.
Table of contents
Section 1 Introduction.....................................................................17This manual...................................................................................... 17Intended audience............................................................................ 17Product documentation.....................................................................18
Product documentation set..........................................................18Document revision history........................................................... 19Related documents......................................................................19
Document symbols and conventions................................................20Symbols.......................................................................................20Document conventions................................................................21
IEC 61850 edition 1 / edition 2 mapping...........................................22
Section 2 Application......................................................................25General IED application....................................................................25Main protection functions..................................................................26Back-up protection functions............................................................ 27Control and monitoring functions......................................................28Communication.................................................................................33Basic IED functions.......................................................................... 35
Section 3 Configuration..................................................................37Description of configuration RER670............................................... 37
Introduction..................................................................................37Description of configuration – transformer protectionapplication in compensated networks.................................... 38Description of configuration – transformer protectionapplication in solidly earthed networks...................................39Description of configuration – line protection application incompensated networks.......................................................... 40Description of configuration – line protection application insolidly earthed networks.........................................................41
Section 4 Analog inputs..................................................................43Introduction.......................................................................................43Setting guidelines............................................................................. 43
Setting of the phase reference channel.......................................44Example................................................................................. 44
Setting of current channels..........................................................44Example 1.............................................................................. 45Example 2.............................................................................. 45Example 3.............................................................................. 46
Table of contents
Railway application RER670 2.2 IEC 1Application manual
Examples on how to connect, configure and set CT inputsfor most commonly used CT connections.............................. 48Example on how to connect a star connected two-phaseCT set to the IED....................................................................50Example how to connect single-phase CT to the IED............ 53
Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protection IED.. 54Setting of voltage channels......................................................... 55
Example................................................................................. 55Examples how to connect, configure and set VT inputs formost commonly used VT connections....................................55Examples on how to connect a two phase-to-earthconnected VT to the IED........................................................ 56Example on how to connect a residually connected IED....... 57Example on how to connect a neutral point VT to the IED.....59
Section 5 Local HMI....................................................................... 61Display..............................................................................................62LEDs.................................................................................................64Keypad............................................................................................. 65Local HMI functionality..................................................................... 67
Protection and alarm indication................................................... 67Parameter management .............................................................68Front communication...................................................................69
Section 6 Differential protection..................................................... 71Low impedance restricted earth fault protection REFPDIF ............. 71
Identification................................................................................ 71Application...................................................................................71
Transformer winding, solidly earthed..................................... 72CT earthing direction.............................................................. 73Railway specific applications for REFPDIF function...............73
Setting guidelines........................................................................ 73Setting and configuration........................................................73Settings.................................................................................. 74
Single-phase railway power transformer differential protectionT1PPDIF...........................................................................................74
Identification................................................................................ 74Application...................................................................................74Setting guidelines........................................................................ 75
Restrained and unrestrained differential protection................75Elimination of zero sequence currents................................... 78Inrush restraint methods.........................................................78Overexcitation restraint method............................................. 78Protections based on the directional criterion........................ 79
Table of contents
2 Railway application RER670 2.2 IECApplication manual
Setting examples.........................................................................79Application examples............................................................. 81How to wire the transformer differential protection to theIED using CTs........................................................................ 86
Section 7 Impedance protection.....................................................91Automatic switch onto fault logic ZCVPSOF ................................... 91
Identification................................................................................ 91Application...................................................................................91Setting guidelines........................................................................ 91
Distance protection, quadrilateral characteristic ZRWPDIS............. 93Identification................................................................................ 93Application...................................................................................93
Compensated earthing systems.............................................94Solidly earthed systems....................................................... 109High impedance earthing systems....................................... 120
Setting examples.......................................................................131Compensated earthed systems............................................131Solidly earthed systems....................................................... 138
Underimpedance protection for railway transformers ZGTPDIS.... 145Identification.............................................................................. 145Application.................................................................................145
Zone 1 operation.................................................................. 147Zone 2 operation.................................................................. 147Zone 3 operation.................................................................. 147
Setting guidelines...................................................................... 148Catenary Protection...................................................................150Wrong phase coupling protection..............................................150
Section 8 Current protection.........................................................153Instantaneous phase overcurrent protection 2-phase outputPHPIOC..........................................................................................153
Identification.............................................................................. 153Application.................................................................................153Setting guidelines...................................................................... 153
Meshed network without parallel line................................... 154Two-step directional phase overcurrent protection D2PTOC......... 156
Identification.............................................................................. 156Application.................................................................................156Setting guidelines...................................................................... 157
Settings for step 1................................................................ 160Settings for step 2................................................................ 162
Instantaneous residual overcurrent protection EFRWPIOC........... 162Identification.............................................................................. 162
Table of contents
Railway application RER670 2.2 IEC 3Application manual
Application.................................................................................163Setting guidelines...................................................................... 163
Two step residual overcurrent protection EF2PTOC......................166Identification.............................................................................. 166Application.................................................................................166Setting guidelines...................................................................... 167
Settings for each step (x = 1 and 2)..................................... 167Common settings................................................................. 1692nd harmonic restrain...........................................................170
Sensitive directional residual overcurrent and power protectionSDEPSDE ..................................................................................... 170
Identification.............................................................................. 170Application.................................................................................170Setting guidelines...................................................................... 172
Thermal overload protection, one time constant, Celsius LPTTR.. 180Identification.............................................................................. 181Application.................................................................................181Setting guideline........................................................................182
Breaker failure protection CCRWRBRF......................................... 184Application.................................................................................184Setting guidelines...................................................................... 184
Overcurrent protection with binary release BRPTOC.....................187Identification.............................................................................. 187Application.................................................................................187Setting guidelines...................................................................... 187
Tank overcurrent protection TPPIOC............................................. 188Identification.............................................................................. 188Application.................................................................................188Setting guidelines...................................................................... 190
Section 9 Voltage protection........................................................ 193Two step undervoltage protection U2RWPTUV............................. 193
Identification.............................................................................. 193Application.................................................................................193Setting guidelines...................................................................... 194
Disconnected equipment detection...................................... 194Power supply quality ........................................................... 194Voltage instability mitigation................................................. 194Backup protection for power system faults...........................194Settings for two step undervoltage protection...................... 194
Two step overvoltage protection O2RWPTOV............................... 196Identification.............................................................................. 196Application.................................................................................196Setting guidelines...................................................................... 197
Table of contents
4 Railway application RER670 2.2 IECApplication manual
Equipment protection, transformers..................................... 197Power supply quality............................................................ 197The following settings can be done for the two stepovervoltage protection.......................................................... 197
Two step residual overvoltage protection ROV2PTOV ................. 199Identification.............................................................................. 199Application.................................................................................199Setting guidelines...................................................................... 199
High impedance earthed systems........................................ 199Solidly earthed systems....................................................... 200Settings for two step residual overvoltage protection...........200
Section 10 Frequency protection....................................................203Underfrequency protection SAPTUF ............................................. 203
Identification.............................................................................. 203Application.................................................................................203Setting guidelines...................................................................... 203
Section 11 Secondary system supervision.....................................205Current circuit supervision CCSSPVC............................................205
Identification.............................................................................. 205Application.................................................................................205Setting guidelines...................................................................... 206
Fuse failure supervision FRWSPVC...............................................206Identification.............................................................................. 206Application.................................................................................206Setting guidelines...................................................................... 207
DeltaU and DeltaI detection................................................. 207Dead line detection...............................................................208
Sudden current and voltage change..........................................208
Section 12 Control..........................................................................209Synchrocheck, energizing check, and synchronizing SESRSYN...209
Identification.............................................................................. 209Application.................................................................................209
Synchronizing.......................................................................209Synchrocheck.......................................................................211Energizing check.................................................................. 213External fuse failure..............................................................214
Application examples.................................................................215Single circuit breaker with single busbar.............................. 216
Setting guidelines...................................................................... 216Autoreclosing for railway system SMBRREC ................................ 221
Identification.............................................................................. 221
Table of contents
Railway application RER670 2.2 IEC 5Application manual
Application.................................................................................221Auto reclosing operation Off and On.................................... 224Start auto reclosing and conditions for start of a reclosingcycle..................................................................................... 224Start auto reclosing from circuit breaker open information...224Blocking of the auto recloser................................................ 225Control of the auto reclosing dead time for shot 1................225Long trip signal..................................................................... 225Maximum number of reclosing shots....................................225Auto reclosing reclaim timer................................................. 225Pulsing of the circuit breaker closing command and counter226Transient fault.......................................................................226Permanent fault and reclosing unsuccessful signal............. 226Lock-out initiation................................................................. 226Thermal overload protection holding the auto recloser back228
Setting guidelines...................................................................... 228Configuration........................................................................ 228Auto recloser settings...........................................................232
Apparatus control APC................................................................... 235Application.................................................................................235
Bay control QCBAY..............................................................239Switch controller SCSWI...................................................... 240Switches SXCBR/SXSWI..................................................... 241Proxy for signals from switching device via GOOSEXLNPROXY..........................................................................242Reservation function (QCRSV and RESIN)......................... 244
Interaction between modules.....................................................246Setting guidelines...................................................................... 248
Bay control (QCBAY)........................................................... 249Switch controller (SCSWI)....................................................249Switch (SXCBR/SXSWI)...................................................... 250Proxy for signals from switching device via GOOSEXLNPROXY..........................................................................251Bay Reserve (QCRSV).........................................................251Reservation input (RESIN)................................................... 251
Interlocking .................................................................................... 252Configuration guidelines............................................................253Interlocking for line bay ABC_LINE .......................................... 253
Application............................................................................253Signals from bypass busbar................................................. 254Signals from bus-coupler......................................................255Configuration setting............................................................ 257
Interlocking for bus-coupler bay ABC_BC ................................ 258Application............................................................................259
Table of contents
6 Railway application RER670 2.2 IECApplication manual
Configuration........................................................................ 259Signals from all feeders........................................................259Signals from bus-coupler......................................................261Configuration setting............................................................ 263
Interlocking for transformer bay AB_TRAFO ............................ 264Application............................................................................264Signals from bus-coupler......................................................265Configuration setting............................................................ 265
Interlocking for bus-section breaker A1A2_BS..........................266Application............................................................................266Signals from all feeders........................................................266Configuration setting............................................................ 269
Interlocking for bus-section disconnector A1A2_DC ................ 270Application............................................................................270Signals in single breaker arrangement.................................270Signals in double-breaker arrangement............................... 273Signals in 1 1/2 breaker arrangement.................................. 276
Interlocking for busbar earthing switch BB_ES .........................277Application............................................................................277Signals in single breaker arrangement.................................277Signals in double-breaker arrangement............................... 281Signals in 1 1/2 breaker arrangement.................................. 282
Interlocking for double CB bay DB ........................................... 283Application............................................................................283Configuration setting............................................................ 284
Interlocking for 1 1/2 CB BH .....................................................285Application............................................................................285Configuration setting............................................................ 285
Logic rotating switch for function selection and LHMIpresentation SLGAPC.................................................................... 286
Identification.............................................................................. 286Application.................................................................................286Setting guidelines...................................................................... 287
Selector mini switch VSGAPC........................................................287Identification.............................................................................. 287Application.................................................................................287Setting guidelines...................................................................... 288
Generic communication function for Double Point indicationDPGAPC........................................................................................ 288
Identification.............................................................................. 288Application.................................................................................289Setting guidelines...................................................................... 289
Single point generic control 8 signals SPC8GAPC........................ 289Identification.............................................................................. 290
Table of contents
Railway application RER670 2.2 IEC 7Application manual
Application.................................................................................290Setting guidelines...................................................................... 290
AutomationBits, command function for DNP3.0 AUTOBITS.......... 290Identification.............................................................................. 290Application.................................................................................291Setting guidelines...................................................................... 291
Single command, 16 signals SINGLECMD.................................... 291Identification.............................................................................. 291Application.................................................................................291Setting guidelines...................................................................... 293
Transformer energizing control XENCPOW................................... 294Identification.............................................................................. 294Application.................................................................................294Setting guidelines...................................................................... 295
Setting examples..................................................................296
Section 13 Scheme communication...............................................297Scheme communication logic for distance or overcurrentprotection ZCPSCH........................................................................ 297
Identification.............................................................................. 297Application.................................................................................297
Blocking schemes................................................................ 298Permissive schemes............................................................ 298Intertrip scheme....................................................................301
Setting guidelines...................................................................... 302Blocking scheme.................................................................. 302Permissive underreaching scheme...................................... 302Permissive overreaching scheme........................................ 303Unblocking scheme.............................................................. 303Intertrip scheme....................................................................303
Current reversal and Weak-end infeed logic for distanceprotection 2-phase ZCRWPSCH.................................................... 303
Identification.............................................................................. 303Application.................................................................................303
Current reversal logic........................................................... 303Weak-end infeed logic..........................................................304
Setting guidelines...................................................................... 305Current reversal logic........................................................... 305Weak-end infeed logic..........................................................306
Scheme communication logic for residual overcurrent protectionECPSCH ........................................................................................306
Identification.............................................................................. 306Application.................................................................................306Setting guidelines...................................................................... 307
Table of contents
8 Railway application RER670 2.2 IECApplication manual
Current reversal and weak-end infeed logic for residualovercurrent protection ECRWPSCH...............................................308
Identification.............................................................................. 308Application.................................................................................308
Fault current reversal logic................................................... 308Weak-end infeed logic..........................................................309
Setting guidelines...................................................................... 309Current reversal....................................................................309Weak-end infeed.................................................................. 311
Section 14 Logic.............................................................................313Tripping logic SMPPTRC ...............................................................313
Identification.............................................................................. 313Application.................................................................................313
Tripping................................................................................ 313Lock-out................................................................................314Example of directional data.................................................. 314Blocking of the function block...............................................316
Setting guidelines...................................................................... 316Trip matrix logic TMAGAPC........................................................... 316
Identification.............................................................................. 316Application.................................................................................316Setting guidelines...................................................................... 316
Logic for group alarm ALMCALH....................................................317Identification.............................................................................. 317Application.................................................................................317Setting guidelines...................................................................... 317
Logic for group alarm WRNCALH.................................................. 317Identification.............................................................................. 317
Application............................................................................318Setting guidelines................................................................. 318
Logic for group indication INDCALH...............................................318Identification.............................................................................. 318
Application............................................................................318Setting guidelines................................................................. 318
Configurable logic blocks................................................................318Application.................................................................................319Setting guidelines...................................................................... 319
Configuration........................................................................ 319Fixed signal function block FXDSIGN............................................ 320
Identification.............................................................................. 320Application.................................................................................320
Boolean 16 to Integer conversion B16I.......................................... 321Identification.............................................................................. 321
Table of contents
Railway application RER670 2.2 IEC 9Application manual
Application.................................................................................322Boolean to integer conversion with logical node representation,16 bit BTIGAPC.............................................................................. 323
Identification.............................................................................. 323Application.................................................................................323
Integer to Boolean 16 conversion IB16.......................................... 324Identification.............................................................................. 324Application.................................................................................324
Integer to Boolean 16 conversion with logic node representationITBGAPC........................................................................................325
Identification.............................................................................. 325Application.................................................................................325
Elapsed time integrator with limit transgression and overflowsupervision TEIGAPC.....................................................................326
Identification.............................................................................. 326Application.................................................................................327Setting guidelines...................................................................... 327
Comparator for integer inputs - INTCOMP..................................... 327Identification.............................................................................. 327Application.................................................................................328Setting guidelines...................................................................... 328Setting example.........................................................................328
Comparator for real inputs - REALCOMP...................................... 329Identification.............................................................................. 329Application.................................................................................329Setting guidelines...................................................................... 329Setting example.........................................................................330
Section 15 Monitoring.....................................................................331Measurement..................................................................................331
Identification.............................................................................. 331Application.................................................................................331Zero clamping............................................................................333Setting guidelines...................................................................... 334
Setting examples..................................................................337Gas medium supervision SSIMG................................................... 340
Identification.............................................................................. 340Application.................................................................................340Setting guidelines...................................................................... 340
Liquid medium supervision SSIML................................................. 341Identification.............................................................................. 341Application.................................................................................341Setting guidelines...................................................................... 342
Breaker monitoring SSCBR............................................................342
Table of contents
10 Railway application RER670 2.2 IECApplication manual
Identification.............................................................................. 342Application.................................................................................343Setting guidelines...................................................................... 345
Setting procedure on the IED............................................... 346Event function EVENT....................................................................347
Identification.............................................................................. 347Application.................................................................................347Setting guidelines...................................................................... 347
Disturbance report DRPRDRE....................................................... 348Identification.............................................................................. 348Application.................................................................................348Setting guidelines...................................................................... 349
Recording times................................................................... 351Binary input signals.............................................................. 352Analog input signals............................................................. 353Sub-function parameters...................................................... 353Consideration....................................................................... 354
Logical signal status report BINSTATREP..................................... 355Identification.............................................................................. 355Application.................................................................................355Setting guidelines...................................................................... 355
Limit counter L4UFCNT..................................................................356Identification.............................................................................. 356Application.................................................................................356Setting guidelines...................................................................... 356
Running hour-meter TEILGAPC.....................................................356Identification.............................................................................. 356Application.................................................................................357Setting guidelines...................................................................... 357
Fault locator RWRFLO................................................................... 357Identification.............................................................................. 357Application.................................................................................357Setting guidelines...................................................................... 359
Setting example....................................................................360
Section 16 Metering....................................................................... 363Pulse-counter logic PCFCNT......................................................... 363
Identification.............................................................................. 363Application.................................................................................363Setting guidelines...................................................................... 363
Function for energy calculation and demand handling ETPMMTR 364Identification.............................................................................. 364Application.................................................................................364Setting guidelines...................................................................... 365
Table of contents
Railway application RER670 2.2 IEC 11Application manual
Section 17 Ethernet-based communication....................................367Access point................................................................................... 367
Application.................................................................................367Setting guidelines...................................................................... 367
Redundant communication.............................................................368Identification.............................................................................. 368Application.................................................................................369Setting guidelines...................................................................... 370
Merging unit....................................................................................371Application.................................................................................371Setting guidelines...................................................................... 372
Routes............................................................................................ 372Application.................................................................................372Setting guidelines...................................................................... 372
Section 18 Station communication.................................................373Communication protocols............................................................... 373IEC 61850-8-1 communication protocol......................................... 373
Application IEC 61850-8-1.........................................................373Setting guidelines...................................................................... 375Horizontal communication via GOOSE..................................... 375
Sending data........................................................................ 375Receiving data......................................................................376
IEC/UCA 61850-9-2LE communication protocol............................ 377Introduction................................................................................377Setting guidelines...................................................................... 379
Specific settings related to the IEC/UCA 61850-9-2LEcommunication..................................................................... 380Loss of communication when used with LDCM....................380Setting examples for IEC/UCA 61850-9-2LE and timesynchronization.................................................................... 384
IEC 61850 quality expander QUALEXP.................................... 389LON communication protocol......................................................... 390
Application.................................................................................390MULTICMDRCV and MULTICMDSND..................................... 392
Identification......................................................................... 392Application............................................................................392Setting guidelines................................................................. 392
SPA communication protocol......................................................... 392Application.................................................................................392Setting guidelines...................................................................... 393
IEC 60870-5-103 communication protocol..................................... 395Application.................................................................................395
Table of contents
12 Railway application RER670 2.2 IECApplication manual
Functionality......................................................................... 395Design.................................................................................. 396
Settings......................................................................................398Settings for RS485 and optical serial communication.......... 399Settings from PCM600......................................................... 400
Function and information types................................................. 402DNP3 Communication protocol...................................................... 403
Application.................................................................................403
Section 19 Remote communication................................................405Binary signal transfer......................................................................405
Identification.............................................................................. 405Application.................................................................................405
Communication hardware solutions..................................... 406Setting guidelines...................................................................... 407
Section 20 Security........................................................................ 411Authority status ATHSTAT............................................................. 411
Application.................................................................................411Self supervision with internal event list INTERRSIG...................... 411
Application.................................................................................411Change lock CHNGLCK................................................................. 412
Application.................................................................................412Denial of service SCHLCCH/RCHLCCH ....................................... 413
Application.................................................................................413Setting guidelines...................................................................... 413
Section 21 Basic IED functions...................................................... 415IED identifiers TERMINALID.......................................................... 415
Application.................................................................................415Product information PRODINF....................................................... 415
Application.................................................................................415Factory defined settings............................................................ 415
Measured value expander block RANGE_XP................................ 416Identification.............................................................................. 416Application.................................................................................417Setting guidelines...................................................................... 417
Parameter setting groups............................................................... 417Application.................................................................................417Setting guidelines...................................................................... 418
Rated system frequency PRIMVAL................................................ 418Identification.............................................................................. 418Application.................................................................................418Setting guidelines...................................................................... 418
Table of contents
Railway application RER670 2.2 IEC 13Application manual
Global base values GBASVAL....................................................... 418Identification.............................................................................. 418Application.................................................................................419Setting guidelines...................................................................... 419
Signal matrix for binary inputs SMBI.............................................. 419Application.................................................................................419Setting guidelines...................................................................... 419
Signal matrix for binary outputs SMBO ......................................... 419Application.................................................................................420Setting guidelines...................................................................... 420
Signal matrix for mA inputs SMMI.................................................. 420Application.................................................................................420Setting guidelines...................................................................... 420
Signal matrix for analog inputs SMAI............................................. 420Application.................................................................................420Frequency values...................................................................... 421Setting guidelines...................................................................... 421
Test mode functionality TESTMODE..............................................422Application.................................................................................422
IEC 61850 protocol test mode..............................................422Setting guidelines...................................................................... 423
Time synchronization TIMESYNCHGEN........................................423Application.................................................................................423Setting guidelines...................................................................... 424
System time..........................................................................425Synchronization....................................................................425Process bus IEC/UCA 61850-9-2LE synchronization.......... 426
Section 22 Requirements...............................................................429Current transformer requirements.................................................. 429
Current transformer basic classification and requirements....... 429Conditions..................................................................................431Fault current.............................................................................. 432Secondary wire resistance and additional load......................... 432General current transformer requirements................................ 432Rated equivalent secondary e.m.f. requirements......................433
Breaker failure protection..................................................... 433Restricted earth fault protection (low impedance differential)434
Current transformer requirements for CTs according to otherstandards...................................................................................436
Current transformers according to IEC 61869-2, class P, PR436Current transformers according to IEC 61869-2, class PX,PXR (and old IEC 60044-6, class TPSand old British Standard, class X)........................................ 437
Table of contents
14 Railway application RER670 2.2 IECApplication manual
Current transformers according to ANSI/IEEE..................... 437Voltage transformer requirements.................................................. 438SNTP server requirements............................................................. 438PTP requirements...........................................................................439Sample specification of communication requirements for theprotection and control terminals in digital telecommunicationnetworks......................................................................................... 439IEC/UCA 61850-9-2LE Merging unit requirements ....................... 440
Section 23 Glossary....................................................................... 443
Table of contents
Railway application RER670 2.2 IEC 15Application manual
Section 1 Introduction
1.1 This manual
The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provide assistance forcalculating settings.
1.2 Intended audience
This manual addresses the protection and control engineer responsible for planning,pre-engineering and engineering.
The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand communication principles.
1MRK 506 375-UEN - Section 1Introduction
Railway application RER670 2.2 IEC 17Application manual
1.3 Product documentation
1.3.1 Product documentation set
IEC07000220-4-en.vsd
Pla
nnin
g &
pur
chas
e
Eng
inee
ring
Inst
allin
g
Com
mis
sion
ing
Ope
ratio
n
Mai
nten
ance
Dec
omm
issi
onin
gD
eins
talli
ng &
dis
posa
l
Application manual
Operation manual
Installation manual
Engineering manual
Communication protocol manual
Cyber security deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN
Figure 1: The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using thevarious tools available within the PCM600 software. The manual providesinstructions on how to set up a PCM600 project and insert IEDs to the projectstructure. The manual also recommends a sequence for the engineering of protectionand control functions, LHMI functions as well as communication engineering for IEC60870-5-103, IEC 61850, DNP3, LON and SPA.
The installation manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in the chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for the checkingof external circuitry and energizing the IED, parameter setting and configuration as
Section 1 1MRK 506 375-UEN -Introduction
18 Railway application RER670 2.2 IECApplication manual
well as verifying settings by secondary injection. The manual describes the process oftesting an IED in a substation which is not in service. The chapters are organized in thechronological order in which the IED should be commissioned. The relevantprocedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for the monitoring, controlling andsetting of the IED. The manual also describes how to identify disturbances and how toview calculated and measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provide assistance forcalculating settings.
The technical manual contains operation principle descriptions, and lists functionblocks, logic diagrams, input and output signals, setting parameters and technicaldata, sorted per function. The manual can be used as a technical reference during theengineering phase, installation and commissioning phase, and during normal service.
The communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.
The point list manual describes the outlook and properties of the data points specificto the IED. The manual should be used in conjunction with the correspondingcommunication protocol manual.
The cyber security deployment guideline describes the process for handling cybersecurity when communicating with the IED. Certification, Authorization with rolebased access control, and product engineering for cyber security related events aredescribed and sorted by function. The guideline can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.
1.3.2 Document revision historyDocument revision/date History–/May 2017 First release
1.3.3 Related documentsDocuments related to RER670 Document numbersApplication manual 1MRK 506 375-UEN
Commissioning manual 1MRK 506 377-UEN
Product guide 1MRK 506 378-BEN
Technical manual 1MRK 506 376-UEN
Type test certificate 1MRK 506 378-TEN
1MRK 506 375-UEN - Section 1Introduction
Railway application RER670 2.2 IEC 19Application manual
670 series manuals Document numbersOperation manual 1MRK 500 127-UEN
Engineering manual 1MRK 511 398-UEN
Installation manual 1MRK 514 026-UEN
Communication protocol manual, DNP3 1MRK 511 391-UUS
Communication protocol manual, IEC60870-5-103
1MRK 511 394-UEN
Communication protocol manual, IEC 61850Edition 2
1MRK 511 393-UEN
Communication protocol manual, LON 1MRK 511 395-UEN
Communication protocol manual, SPA 1MRK 511 396-UEN
Point list manual, DNP3 1MRK 511 397-UUS
Accessories guide 1MRK 514 012-BEN
Cyber security deployment guideline 1MRK 511 399-UEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN
Application guide, Communication set-up 1MRK 505 382-UEN
1.4 Document symbols and conventions
1.4.1 Symbols
The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.
The warning icon indicates the presence of a hazard which couldresult in personal injury.
The caution hot surface icon indicates important information orwarning about the temperature of product surfaces.
Class 1 Laser product. Take adequate measures to protect the eyes anddo not view directly with optical instruments.
The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence of
Section 1 1MRK 506 375-UEN -Introduction
20 Railway application RER670 2.2 IECApplication manual
a hazard which could result in corruption of software or damage toequipment or property.
The information icon alerts the reader of important facts andconditions.
The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. It is importantthat the user fully complies with all warning and cautionary notices.
1.4.2 Document conventions
• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using thepush button icons.For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.For example, to save the changes in non-volatile memory, select Yes and press
.• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that thesignal name may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must beconnected to another function block in the application configuration toachieve a valid application configuration.
• Logic diagrams describe the signal logic inside the function block and arebordered by dashed lines.• Signals in frames with a shaded area on their right hand side represent
setting parameter signals that are only settable via the PST, ECT or LHMI.• If an internal signal path cannot be drawn with a continuous line, the suffix
-int is added to the signal name to indicate where the signal starts andcontinues.
• Signal paths that extend beyond the logic diagram and continue in anotherdiagram have the suffix ”-cont.”
1MRK 506 375-UEN - Section 1Introduction
Railway application RER670 2.2 IEC 21Application manual
Illustrations are used as an example and might show other productsthan the one the manual describes. The example that is illustrated isstill valid.
1.5 IEC 61850 edition 1 / edition 2 mapping
Function block names are used in ACT and PST to identify functions. Respectivefunction block names of Edition 1 logical nodes and Edition 2 logical nodes are shownin the table below.
Table 1: IEC 61850 edition 1 / edition 2 mapping
Function block name Edition 1 logical nodes Edition 2 logical nodesAGSAL AGSAL
SECLLN0AGSAL
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BRPTOC BRPTOC BRPTOC
BTIGAPC B16IFCVI BTIGAPC
CCRWRBRF CCRWRBRF CCRWRBRF
CCSSPVC CCSRDIF CCSSPVC
CMMXU CMMXU CMMXU
CMSQI CMSQI CMSQI
CVMMXN CVMMXN CVMMXN
D2PTOC D2LLN0D2PTOCPH1PTRC
D2PTOCPH1PTRC
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
ECPSCH ECPSCH ECPSCH
ECRWPSCH ECRWPSCH ECRWPSCH
EF2PTOC EF2LLN0EF2PTRCEF2RDIRGEN2PHARPH1PTOC
EF2PTRCEF2RDIRGEN2PHARPH1PTOC
EFPIOC EFPIOC EFPIOC
ETPMMTR ETPMMTR ETPMMTR
ITBGAPC IB16FCVB ITBGAPC
L4UFCNT L4UFCNT L4UFCNT
LPHD LPHD -
Table continues on next page
Section 1 1MRK 506 375-UEN -Introduction
22 Railway application RER670 2.2 IECApplication manual
Function block name Edition 1 logical nodes Edition 2 logical nodesLPTTR LPTTR LPTTR
MVGAPC MVGGIO MVGAPC
O2RWPTOV GEN2LLN0O2RWPTOVPH1PTRC
O2RWPTOVPH1PTRC
PHPIOC PHPIOC PHPIOC
QCBAY QCBAY BAY/LLN0
QCRSV QCRSV QCRSV
RCHLCCH RCHLCCH RCHLCCH
REFPDIF REFPDIF REFPDIF
ROV2PTOV GEN2LLN0PH1PTRCROV2PTOV
PH1PTRCROV2PTOV
RWRFLO - RWRFLO
SAPTUF SAPTUF SAPTUF
SCHLCCH SCHLCCH SCHLCCH
SCILO SCILO SCILO
SCSWI SCSWI SCSWI
SDEPSDE SDEPSDE SDEPSDESDEPTOCSDEPTOVSDEPTRC
SESRSYN RSY1LLN0AUT1RSYNMAN1RSYNSYNRSYN
AUT1RSYNMAN1RSYNSYNRSYN
SLGAPC SLGGIO SLGAPC
SMBRREC SMBRREC SMBRREC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
T1PPDIF - T1PPDIFT1PPHART1PPTRC
TEIGAPC TEIGGIO TEIGAPCTEIGGIO
TEILGAPC TEILGGIO TEILGAPC
TMAGAPC TMAGGIO TMAGAPC
Table continues on next page
1MRK 506 375-UEN - Section 1Introduction
Railway application RER670 2.2 IEC 23Application manual
Function block name Edition 1 logical nodes Edition 2 logical nodesTPPIOC TPPIOC TPPIOC
U2RWPTUV GEN2LLN0PH1PTRCU2RWPTUV
PH1PTRCU2RWPTUV
VMMXU VMMXU VMMXU
VMSQI VMSQI VMSQI
VNMMXU VNMMXU VNMMXU
VSGAPC VSGGIO VSGAPC
WRNCALH WRNCALH WRNCALH
XENCPOW - XENCPOW
ZCPSCH ZCPSCH ZCPSCH
ZCRWPSCH ZCRWPSCH ZCRWPSCH
ZCVPSOF ZCVPSOF ZCVPSOF
ZGTPDIS ZGTLLN0ZGPDISZGPTRC
ZGPDISZGPTRC
ZRWPDIS - PSRWPDISZRWPDISZRWPTRC
Section 1 1MRK 506 375-UEN -Introduction
24 Railway application RER670 2.2 IECApplication manual
Section 2 Application
2.1 General IED application
RER670 is used for the protection, control and monitoring of transmission lines,catenary lines or transformers in two- and single-phase 16.7Hz, 50Hz and 60Hzrailway applications. It supports isolated, compensated and solidly earthed networks.
The line protection covers distance protection functions with quadrilateral or circularstarting characteristic. The six zones have fully independent measuring and settingwhich gives high flexibility for all types of lines. Load encroachment and adaptivereach compensation are included.
Communication to the remote ends can be used for even more selective protection.Backup functions like directional earth fault or overcurrent as well as breaker failureprotection are equally available as autoreclosure and synchrocheck functions.
A line fault locator for up to 10 line segments supports efficient remedial actions afterfaults on the transmission line.
The transformer protection covers transformer differential protection for two-phase totwo-phase as well as two-phase to one-phase transformers. Besides the transformerdifferential protection, a wide range of backup functions are available.
A very fast transformer tank protection helps to avoid damages in case of short circuitsto the transformer tank.
The transformer energizing functions allow smooth energizing of transformers tominimize stress on equipment and power system which operate at 16.7Hz.
The control functionality can be combined backup, line or transformer protection touse RER670 as protection, control or combined protection and control IED.
The autorecloser co-operates with the synchrocheck function with high-speed ordelayed reclosing.
Logic is prepared with a graphical tool. The advanced logic capability allows, forexample, to combine protection functions with logic gates or to create customsolutions.
Disturbance recording is available to allow post-fault analysis after primarydisturbances.
RER670 provides IEC 60870-5-103 as well as IEC 61850 communication to asubstation automation system or, in case of IEC 61850, also for horizontalcommunication between IEDs. Redundant communication is obtained through the
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 25Application manual
built-in PRP and HSR features which can be used in star or ringbus architectures.Further, also communication between IEDs in different substations is supported usingthe IEEE C37.94 standard. Up to 192 channels for intertrip and binary signals areavailable per LDCM communication module in the communication between theIEDs.
The IED can be used in applications with the IEC/UCA 61850-9-2LE process bus withup to eight Merging Units (MU). Each MU has eight analogue channels, four currentand four voltages. Conventional input transformer module and Merging Unit channelscan be mixed freely in your application.
RER670 can be ordered with three functional packages:
• A50: Transformer protection (main and backup functions)• B60: Line distance protection (main and backup functions)• H50: Control
The packages A50 and B60 contain all main and backup protection functions fortransformer or line protection. Only one of them can be ordered for a single IED. Bothpackages can be extended with additional functions like synchrocheck (H51) andautoreclosure (H52). Also full control functionality can be added to these packages.
The package H50 describes a control IED, which can be extended with synchrocheck,autoreclosure and backup protection (C60).
More optional functions can be added as described in the next chapter.
The number and type of analog inputs and binary input/output as well as the mA inputand communication modules can be selected when ordering.
The following tables list all the functions available in the IED. Thosefunctions that are not exposed to the user or do not need to beconfigured are not described in this manual.
2.2 Main protection functions
Table 2: Example of quantities
2 = number of basic instances0-3 = option quantities3-A03 = optional function included in packages A03 (refer to ordering details)
Section 2 1MRK 506 375-UEN -Application
26 Railway application RER670 2.2 IECApplication manual
IEC 61850 orfunction name
ANSI Function description Railway
RER670
Differential protection
REFPDIF 87N Restricted earth fault protection, low impedance 2-A501-B60
T1PPDIF 87T Transformer differential protection, two windings 2-A50
Impedance protection
ZCVPSOF Automatic switch onto fault logic, voltage and current based 1-B60
ZGTPDIS 21T Underimpedance protection for generators and transformers 2-A501-B60
ZRWPDIS 21 Distance protection, quadrilateral characteristic 1-B60
2.3 Back-up protection functions
IEC 61850 orfunction name
ANSI Function description Railway
RER670
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection 2-C60
D2PTOC 51_67 Directional phase overcurrent protection, two steps 8-C60
EFRWPIOC 50N Instantaneous residual overcurrent protection 1-C60
EF2PTOC 51N67N1)
Directional residual overcurrent protection, two steps 3-C60
SDEPSDE 67N Sensitive directional residual overcurrent and powerprotection
1-C60
LPTTR 26 Thermal overload protection, one time constant 2-C60
CCRWRBRF 50BF Breaker failure protection 2-C60
BRPTOC 50 Overcurrent protection with binary release 8-C60
TPPIOC 64 Transformer tank overcurrent protection 1-A501-B60
Voltage protection
U2RWPTUV 27 Undervoltage protection, two steps 2-C60
O2RWPTOV 59 Overvoltage protection, two steps 2-C60
ROV2PTOV 59N Two step residual overvoltage protection 2-C60
Frequency protection
SAPTUF 81L Underfrequency protection 2-C60
1) 67N requires voltage
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 27Application manual
2.4 Control and monitoring functions
IEC 61850 orfunction name
ANSI Function description Railway
RER670
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing 1-H51
SMBRREC 79 Autorecloser 1-H52
APC10 3 Control functionality for a single bay, max 10 objects(1CB), including interlocking (see Table 4)
1-H37
APC15 3 Control functionality for a single bay, max 15 objects(2CB), including interlocking (see Table 5)
1-H38
QCBAY Bay control 1
LOCREM Handling of LR-switch positions 1
LOCREMCTRL LHMI control of PSTO 1
SXCBR Circuit breaker 6
TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 1-H53
TCLYLTC 84 Tap changer control and supervision, 32 binaryinputs
1-H54
SLGAPC Logic rotating switch for function selection and LHMIpresentation
15
VSGAPC Selector mini switch 30
DPGAPC Generic communication function for Double Pointindication
16
SPC8GAPC Single point generic control function 8 signals 5
AUTOBITS Automation bits, command function for DNP3.0 2
SINGLECMD Single command, 16 signals 4
I103CMD Function commands for IEC 60870-5-103 1
I103GENCMD Function commands generic for IEC 60870-5-103 35
I103POSCMD IED commands with position and select for IEC60870-5-103
50
I103POSCMDV IED direct commands with position for IEC60870-5-103
50
I103IEDCMD IED commands for IEC 60870-5-103 1
I103USRCMD Function commands user defined for IEC60870-5-103
3
XENCPOW 25T Transformer energization control 1-A50/1-H55
Secondary systemsupervision
CCSSPVC 87 Current circuit supervision 3-G04
FRWSPVC Fuse failure supervision 3-C60
Logic
SMPPTRC 94 Tripping logic 8-C60
Table continues on next page
Section 2 1MRK 506 375-UEN -Application
28 Railway application RER670 2.2 IECApplication manual
IEC 61850 orfunction name
ANSI Function description Railway
RER670
SMAGAPC General start matrix block 12-C60
STARTCOMB Start combinator 32
TMAGAPC Trip matrix logic 6
ALMCALH Logic for group alarm 5
WRNCALH Logic for group warning 5
INDCALH Logic for group indication 5
AND, GATE, INV,LLD, OR,PULSETIMER,RSMEMORY,SRMEMORY,TIMERSET, XOR
Basic configurable logic blocks (see Table 3) 40-420
ANDQT,INDCOMBSPQT,INDEXTSPQT,INVALIDQT,INVERTERQT,ORQT,PULSETIMERQT,RSMEMORYQT,SRMEMORYQT,TIMERSETQT,XORQT
Configurable logic blocks Q/T (see Table 6) 1-L01
AND, GATE, INV,LLD, OR,PULSETIMER,RSMEMORY,SLGAPC,SRMEMORY,TIMERSET,VSGAPC, XOR
Extension logic package (see Table 7) 1-L02
FXDSIGN Fixed signal function block 1
B16I Boolean to integer conversion, 16 bit 18
BTIGAPC Boolean to integer conversion with logical noderepresentation, 16 bit
16
IB16 Integer to Boolean 16 conversion 14
ITBGAPC Integer to Boolean 16 conversion with Logic Noderepresentation
16
TEIGAPC Elapsed time integrator with limit transgression andoverflow supervision
12
INTCOMP Comparator for integer inputs 30
REALCOMP Comparator for real inputs 30
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 29Application manual
Table 3: Total number of instances for basic configurable logic blocks
Basic configurable logic block Total number of instancesAND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
Table 4: Number of function instances in APC10
Function name Function description Total number of instancesSCILO Interlocking 10
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
SCSWI Switch controller 10
SXSWI Circuit switch 9
QCRSV Apparatus control 2
RESIN1 1
RESIN2 59
POS_EVAL Evaluation of position indication 10
XLNPROXY Proxy for signals from switchingdevice via GOOSE
12
GOOSEXLNRCV GOOSE function block toreceive a switching device
12
Section 2 1MRK 506 375-UEN -Application
30 Railway application RER670 2.2 IECApplication manual
Table 5: Number of function instances in APC15
Function name Function description Total number of instancesSCILO Interlocking 15
BB_ES 3
A1A2_BS 2
A1A2_DC 3
ABC_BC 1
BH_CONN 1
BH_LINE_A 1
BH_LINE_B 1
DB_BUS_A 1
DB_BUS_B 1
DB_LINE 1
ABC_LINE 1
AB_TRAFO 1
SCSWI Switch controller 15
SXSWI Circuit switch 14
QCRSV Apparatus control 2
RESIN1 1
RESIN2 59
POS_EVAL Evaluation of position indication 15
XLNPROXY Proxy for signals from switchingdevice via GOOSE
20
GOOSEXLNRCV GOOSE function block toreceive a switching device
20
Table 6: Total number of instances for configurable logic blocks Q/T
Configurable logic blocks Q/T Total number of instancesANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 31Application manual
Table 7: Total number of instances for extended logic package
Extended configurable logic block Total number of instancesAND 180
GATE 49
INV 180
LLD 49
OR 180
PULSETIMER 89
RSMEMORY 40
SLGAPC 74
SRMEMORY 130
TIMERSET 109
VSGAPC 120
XOR 89
IEC 61850 orfunction name
ANSI Function description Railway
RER670
Monitoring
CVMMXN Power system measurement 6
CMMXU Current measurement 10
VMMXU Voltage measurement phase-phase 6
CMSQI Current sequence measurement 6
VMSQI Voltage sequence measurement 6
VNMMXU Voltage measurement phase-earth 6
AISVBAS General service value presentation of analog inputs 1
EVENT Event function 14
DRPRDRE,A1RADR-A4RADR,B1RBDR-B22RBDR
Disturbance report 1
SPGAPC Generic communication function for Single Pointindication
64
SP16GAPC Generic communication function for Single Pointindication 16 inputs
16
MVGAPC Generic communication function for measuredvalues
24
BINSTATREP Logical signal status report 3
RANGE_XP Measured value expander block 66
SSIMG 63 Insulation supervision for gas medium 21
SSIML 71 Insulation supervision for liquid medium 3
SSCBR Circuit breaker condition monitoring 6-M15
Table continues on next page
Section 2 1MRK 506 375-UEN -Application
32 Railway application RER670 2.2 IECApplication manual
IEC 61850 orfunction name
ANSI Function description Railway
RER670
RWRFLO Fault locator, multi section 1-B60
I103MEAS Measurands for IEC 60870-5-103 1
I103MEASUSR Measurands user defined signals for IEC60870-5-103
3
I103AR Function status auto-recloser for IEC 60870-5-103 1
I103EF Function status earth-fault for IEC 60870-5-103 1
I103FLTPROT Function status fault protection for IEC 60870-5-103 1
I103IED IED status for IEC 60870-5-103 1
I103SUPERV Supervison status for IEC 60870-5-103 1
I103USRDEF Status for user defined signals for IEC 60870-5-103 14
L4UFCNT Event counter with limit supervision 30
TEILGAPC Running hour meter 6
Metering
PCFCNT Pulse-counter logic 16
ETPMMTR Function for energy calculation and demandhandling
6
2.5 Communication
IEC 61850 or functionname
ANSI Function description Railway
RER670 Station communication
LONSPA, SPA SPA communication protocol 1
ADE LON communication protocol 1
HORZCOMM Network variables via LON 1
RS485GEN RS485 1
DNPGEN DNP3.0 communication general protocol 1
CHSERRS485 DNP3.0 for EIA-485 communication protocol 1
CH1TCP, CH2TCP,CH3TCP, CH4TCP
DNP3.0 for TCP/IP communication protocol 1
CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol 1
MSTSER DNP3.0 serial master 1
MST1TCP,MST2TCP,MST3TCP,MST4TCP
DNP3.0 for TCP/IP communication protocol 1
DNPFREC DNP3.0 fault records for TCP/IP and EIA-485communication protocol
1
IEC 61850-8-1 IEC 61850 1
Table continues on next page
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 33Application manual
IEC 61850 or functionname
ANSI Function description Railway
RER670
GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59
GOOSEBINRCV GOOSE binary receive 11
GOOSEDPRCV GOOSE function block to receive a double point value 40
GOOSEINTRCV GOOSE function block to receive an integer value 24
GOOSEMVRCV GOOSE function block to receive a measurand value 56
GOOSESPRCV GOOSE function block to receive a single point value 40
MULTICMDRCV,MULTICMDSND
Multiple command and transmit 60/10
OPTICAL103 IEC 60870-5-103 Optical serial communication 1
RS485103 IEC 60870-5-103 serial communication for RS485 1
AGSAL Generic security application component 1
LD0LLN0 IEC 61850 LD0 LLN0 1
SYSLLN0 IEC 61850 SYS LLN0 1
LPHD Physical device information 1
PCMACCS IED configuration protocol 1
SECALARM Component for mapping security events on protocols suchas DNP3 and IEC103
1
FSTACCS Field service tool access 1
IEC 61850-9-2 Process bus communication, 8 mergingunits
1-P30
ACTIVLOG Activity logging 1
ALTRK Service tracking 1
PRP IEC 62439-3 Parallel redundancy protocol 1-P23
HSR IEC 62439-3 High-availability seamless redundancy 1-P24
PTP Precision time protocol 1
FRONTSTATUS Access point diagnostic for front Ethernet port 1
SCHLCCH Access point diagnostic for non-redundant Ethernet port 6
RCHLCCH Access point diagnostic for redundant Ethernet ports 3
DHCP DHCP configuration for front access point 1
QUALEXP IEC 61850 quality expander 96
Remote communication
BinSignRec1_1BinSignRec1_2BinSignReceive2
Binary signal transfer receive 3/3/6
BinSignTrans1_1BinSignTrans1_2BinSignTransm2
Binary signal transfer transmit 3/3/6
BinSigRec1_12MBinSigRec1_22MBinSigTran1_12MBinSigTran1_22M
Binary signal transfer, 2Mbit receive/transmit 3
LDCMTRN Transmission of analog data from LDCM 1
Table continues on next page
Section 2 1MRK 506 375-UEN -Application
34 Railway application RER670 2.2 IECApplication manual
IEC 61850 or functionname
ANSI Function description Railway
RER670
LDCMTRN_2M Transmission of analog data from LDCM, 2Mbit 6
LDCMRecBinStat1LDCMRecBinStat2LDCMRecBinStat3
Receive binary status from remote LDCM 6/3/3
LDCMRecBinS2_2M Receive binary status from LDCM, 2Mbit 3
LDCMRecBinS3_2M Receive binary status from remote LDCM, 2Mbit 3
Scheme communication
ZCPSCH 85 Scheme communication logic for distance or overcurrentprotection
1-B60
ZCRWPSCH 85 Current reversal and weak-end infeed logic for distanceprotection
1-B60
ECPSCH 85 Scheme communication logic for residual overcurrentprotection
1-B60
ECRWPSCH 85 Current reversal and weak-end infeed logic for residualovercurrent protection
1-B60
2.6 Basic IED functions
Table 8: Basic IED functions
IEC 61850 or functionname
Description
INTERRSIG Self supervision with internal event list
TIMESYNCHGEN Time synchronization module
BININPUT,SYNCHCAN,SYNCHGPS,SYNCHCMPPS,SYNCHLON,SYNCHPPH,SYNCHPPS, SNTP,SYNCHSPA
Time synchronization
PTP Precision time protocol
TIMEZONE Time synchronization
IRIG-B Time synchronization
SETGRPS Number of setting groups
ACTVGRP Parameter setting groups
TESTMODE Test mode functionality
CHNGLCK Change lock function
SMBI Signal matrix for binary inputs
SMBO Signal matrix for binary outputs
SMMI Signal matrix for mA inputs
Table continues on next page
1MRK 506 375-UEN - Section 2Application
Railway application RER670 2.2 IEC 35Application manual
IEC 61850 or functionname
Description
SMAI1 - SMAI12 Signal matrix for analog inputs
ATHSTAT Authority status
ATHCHCK Authority check
AUTHMAN Authority management
FTPACCS FTP access with password
GBASVAL Global base values for settings
ALTMS Time master supervision
ALTIM Time management
COMSTATUS Protocol diagnostic
Table 9: Local HMI functions
IEC 61850 or functionname
ANSI Description
LHMICTRL Local HMI signals
LANGUAGE Local human machine language
SCREEN Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5FNKEYMD1–FNKEYMD5
Parameter setting function for HMI in PCM600
LEDGEN General LED indication part for LHMI
OPENCLOSE_LED LHMI LEDs for open and close keys
GRP1_LED1–GRP1_LED15GRP2_LED1–GRP2_LED15GRP3_LED1–GRP3_LED15
Basic part for CP HW LED indication module
Section 2 1MRK 506 375-UEN -Application
36 Railway application RER670 2.2 IECApplication manual
Section 3 Configuration
3.1 Description of configuration RER670
3.1.1 Introduction
All IEDs shall be configured with the help of the application configuration tool inPCM600. The IED can be adapted to special applications and special logic can bedeveloped, such as logic for automatic opening of disconnectors and closing of ringbays, automatic load transfer from one busbar to the other, and so on.
On request, ABB is available to support the configuration work, either directly or todo the design checking. Example configurations are given in following sections as aguide what can be achieved using RER670.
1MRK 506 375-UEN - Section 3Configuration
Railway application RER670 2.2 IEC 37Application manual
3.1.1.1 Description of configuration – transformer protection application incompensated networks
QB1
W1-QA1
WA1RER670 V 2.2 – Application for Transformer Protection
¾-19“-Casing, 1xBIM, 1xSOM, 1xMIM 12AI (7I+5U)
CT
VT
BR PTOC
51 IBR>
SMP PTRC
94 1→0
VN MMXU
MET UN
FRW SPVC
U>/I<
L PTTR
26 θ>
CCRW RBRF
50BF 2I>BF
Temp.-Sensor
Other Functions available from the function library
optional Functions
ROV2 PTOV
59N 2(U0>)
S CSWI
3 Control
S XSWI
3 Control
S XCBR
3 Control
Q CRSV
3 Control
S CILO
3 Control
PH PIOC
50 2I>>
EFRW PIOC
50N IN>>
O2RW PTOV
59 2(2U>)
Q CBAY
3 Control
S SIML
71
W2-QA1
L2
VT
L1-L2
ZGT PDIS
21 Z<
C MSQI
MET Isqi
W1
W2
T1P PDIF
87T Id/I>
Transducer
D2 PTOC
51_67 2(2I>)
D2 PTOC
51_67 2(2I>)
L1, nicht benutzt
C MMXU
MET I
SA PTUF
81 f<
L2
CT
L2CV MMXN
MET P/Q
TP PIOC
64 IN>>>
BF Prot.
C MMXU
MET I
D2 PTOC
51_67 2(2I>)
D2 PTOC
51_67 2(2I>)
FRW SPVC
U>/I<
CCRW RBRF
50BF 2I>BF
EF2 PTOC
51N_67N 2(IN>)
CV MMXN
MET P/Q
I> ASY
SA PTUF
81 f<
U2RW PTUV
27 2(2U<)
V MMXU
MET U
V MSQI
MET Usqi
VN MMXU
MET UN
SMP PTRC
94 1→0
SMP PTRC
94 1→0
SMP PTRC
94 1→0
SMP PTRC
94 1→0
SMP PTRC
94 1→0
Trip 1 HV Trip 2 HV Trip to BBP
Trip 1 LV Trip 2 LV Back-up prot.
4-20 mA
XENC POW
25T POW
67N
SDE PSDE
IN>
REF PDIF
87N IdN/I
L1 L2
T1P PDIF
87T Id/I>
long. Diff Prottransv. Diff Prot.
IEC17000009-1-en.vsdx
IEC17000009 V1 EN
Figure 2: Configuration diagram for transformer protection application incompensated networks
Section 3 1MRK 506 375-UEN -Configuration
38 Railway application RER670 2.2 IECApplication manual
3.1.1.2 Description of configuration – transformer protection application insolidly earthed networks
QB1
W1-QA1
WA1RER670 V2.1 – Application for Transformer Protection
½-19“-casing, 1xIOM, 1xBOM, 1xMIM 12AI (7I+5U)
CT
VT
IEC17000010-1-en.vsdx
BR PTOC
51 IBR>
SMP PTRC
94 1→0
VN MMXU
MET UN
FRW SPVC
U>/I<
L PTTR
26 θ>
CCRW RBRF
50BF 2I>BF
Temp.-Sensor
Other Functions available from the function library
Optional functions
ROV2 PTOV
59N 2(U0>)
S CSWI
3 Control
S XSWI
3 Control
S XCBR
3 Control
Q CRSV
3 Control
S CILO
3 Control
PH PIOC
50 2I>>
EFRW PIOC
50N IN>>
O2RW PTOV
59 2(2U>)
Q CBAY
3 Control
S SIML
71
W2-QA1
L2
VT
L1-L2
ZGT PDIS
21 Z<
C MSQI
MET Isqi
W1
W2
T1P PDIF
87T Id/I>Transducer
D2 PTOC
51_67 2(2I>)
C MMXU
MET I
SA PTUF
81 f<
L2
CT
L2CV MMXN
MET P/Q
TP PIOC
64 IN>>>
BF Logic
C MMXU
MET I
D2 PTOC
51_67 2(2I>)
FRW SPVC
U>/I<
CCRW RBRF
50BF 2I>BF
EF2 PTOC
51N_67N 2(IN>)
CV MMXN
MET P/Q
I> ASY
SA PTUF
81 f<
U2RW PTUV
27 2(2U<)
V MMXU
MET U
V MSQI
MET Usqi
VN MMXU
MET UN
SMP PTRC
94 1→0
Trip 1 HV-side
Trip 1 LV-side
4-20 mA
XENC POW
25T POW
67N
SDE PSDE
IN>
REF PDIF
87N IdN/I
D2 PTOC
51_67 2(2I>)
T1P PDIF
87T Id/I>
D2 PTOC
51_67 2(2I>)
IEC17000010 V1 EN
Figure 3: Configuration diagram for transformer protection application insolidly earthed networks
1MRK 506 375-UEN - Section 3Configuration
Railway application RER670 2.2 IEC 39Application manual
3.1.1.3 Description of configuration – line protection application incompensated networks
QB1
QA1
QB9
QC9
WA1RER670 V2.1 – Application for Line Protection
¾-19“-Casing, 1xBIM, 1xBOM, 12AI (7I+5U)
VT
CT
VT
SMB RREC
79 5(0→1)
IEC17000011-1-en.vsdx
RW RFLO
21FL FL
ZCRW PSCH
85
67N
SDE PSDE
IN>
SES RSYN
25 SC/VC
BR PTOC
51 IBR>
BR PTOC
51 IBR>
Emergency OC
CCS SPVC
∆I
SMP PTRC
94 1→0
ZC PSCH
85
VN MMXU
MET UN
V MSQI
MET Usqi
V MMXU
MET U
CV MMXN
MET P/Q
S SCBR
FRW SPVC
U>/I<
EF2 PTOC
51N(67N) 2(IN>)
L PTTR
26 θ>
CCRW RBRF
50BF 2I>BF
ZRW PDIS
21 2Z<
ZCV PSOF
Temp.-Sensor
Other Functions available from the function library
Optional functions
ROV2 PTOV
59N 2(U0>)
S CSWI
3 Control
S XSWI
3 Control
S XCBR
3 Control
Q CRSV
3 Control
S CILO
3 Control
PH PIOC
50 2I>>
EFRW PIOC
50N IN>>
O2RW PTOV
59 2(2U>)
U2RW PTUV
27 2(2U<)
Q CBAY
3 Control
S SIML
71
GOOSE
IEC17000011 V1 EN
Figure 4: Configuration diagram for line protection application in compensatednetworks
Section 3 1MRK 506 375-UEN -Configuration
40 Railway application RER670 2.2 IECApplication manual
3.1.1.4 Description of configuration – line protection application in solidlyearthed networks
QB1
QA1
QB9
QC9
WA1RER670 V2.1 – Application for Line Protection
1/2-19“-Casing, 1xBIM, 1xBOM, 1xMIM, 12AI (7I+5U)
VT
CT
VT
SMB RREC
79 5(0→1)
IEC17000012-1-en.vsdx
RW RFLO
21FL FL
ZCRW PSCH
85
67N
SDE PSDE
IN>
SES RSYN
25 SC/VC
BR PTOC
51 IBR>
BR PTOC
51 IBR>
Emergency OC
CCS SPVC
∆I
SMP PTRC
94 1→0
ZC PSCH
85
VN MMXU
MET UN
V MSQI
MET Usqi
V MMXU
MET U
CV MMXN
MET P/Q
S SCBR
FRW SPVC
U>/I<
EF2 PTOC
51N(67N) 2(IN>)
L PTTR
26 θ>
CCRW RBRF
50BF 2I>BF
ZRW PDIS
21 2Z<
ZCV PSOF
Other Functions available from the function library
Optional functions
ROV2 PTOV
59N 2(U0>)
S CSWI
3 Control
S XSWI
3 Control
S XCBR
3 Control
Q CRSV
3 Control
S CILO
3 Control
PH PIOC
50 2I>>
EFRW PIOC
50N IN>>
O2RW PTOV
59 2(2U>)
U2RW PTUV
27 2(2U<)
Q CBAY
3 Control
S SIML
71
4-20mAAmb. temp sens.Transducer
EF2 PTOC
51N(67N) 2(IN>)
IEC17000012 V1 EN
Figure 5: Configuration diagram for line protection application in solidlyearthed networks
1MRK 506 375-UEN - Section 3Configuration
Railway application RER670 2.2 IEC 41Application manual
Section 4 Analog inputs
4.1 Introduction
Analog input channels must be configured and set properly in order to get correctmeasurement results and correct protection operations. For power measuring, alldirectional and differential functions, the directions of the input currents must bedefined in order to reflect the way the current transformers are installed/connected inthe field ( primary and secondary connections ). Measuring and protection algorithmsin the IED use primary system quantities. Setting values are in primary quantities aswell and it is important to set the data about the connected current and voltagetransformers properly.
Under the Logical Node AISVBAS, the TRM channel for phase angle referencePhaseAngleRef can be defined to facilitate service values reading. This TRMchannel's phase angle will always be forced to zero degrees and remaining analogchannel's phase angle information will be shown in relation to this channel. Duringtesting and commissioning of the IED, the reference channel can be changed tofacilitate testing and service values reading.
The IED has the ability to receive analog values from primaryequipment, that are sampled by Merging units (MU) connected to aprocess bus, via the IEC 61850-9-2 LE protocol.
In RER670 7I+5U TRM is always used. However several variantsexist in order to cover 1A and/or 5A main CTs.
4.2 Setting guidelines
The available setting parameters related to analog inputs aredepending on the actual hardware (TRM) and the logic configurationmade in PCM600.
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 43Application manual
4.2.1 Setting of the phase reference channel
All phase angles are calculated in relation to a defined reference. An appropriateanalog input channel is selected and used as phase reference. The parameterPhaseAngleRef defines the analog channel that is used as phase angle reference.
4.2.1.1 Example
Usually the L1 phase-to-earth voltage connected to the first VT channel number of thetransformer input module (TRM) is selected as the phase reference. The first VTchannel number depends on the type of transformer input module.
For a TRM with 7 current and 5 voltage inputs the first VT channel is 8. The settingPhaseAngleRef=8 shall be used if the phase reference voltage is connected to thatchannel.
4.2.2 Setting of current channels
The direction of a current to the IED is depending on the connection of the CT. Unlessindicated otherwise, the main CTs are supposed to be star connected and can beconnected with the earthing point to the object or from the object. This informationmust be set in the IED. The convention of the directionality is defined as follows: Apositive value of current, power, and so on means that the quantity has the directioninto the object and a negative value means direction out from the object. Fordirectional functions the direction into the object is defined as Forward and thedirection out from the object is defined as Reverse. See Figure 6
A positive value of current, power, and so on (forward) means that the quantity flowstowards the object. A negative value of current, power, and so on (reverse) means thatthe quantity flows away from the object. See Figure 6.
Protected ObjectLine, transformer, etc
ForwardReverse
Definition of directionfor directional functions
Measured quantity ispositive when flowing
towards the object
e.g. P, Q, I
ReverseForward
Definition of directionfor directional functions
e.g. P, Q, IMeasured quantity ispositive when flowing
towards the object
Set parameterCTStarPoint
Correct Setting is"ToObject"
Set parameterCTStarPoint
Correct Setting is"FromObject" en05000456.vsd
IEC05000456 V1 EN
Figure 6: Internal convention of the directionality in the IED
Section 4 1MRK 506 375-UEN -Analog inputs
44 Railway application RER670 2.2 IECApplication manual
With correct setting of the primary CT direction, CTStarPoint set to FromObject orToObject, a positive quantities always flowing towards the protected object and adirection defined as Forward always is looking towards the protected object. Thefollowing examples show the principle.
4.2.2.1 Example 1
Two IEDs used for protection of two objects.
Transformer
protection
Transformer
Line
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
ForwardReverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
IsIs
Ip Ip Ip
IED IED
IEC05000753 V2 EN
Figure 7: Example how to set CTStarPoint parameters in the IED
Figure 7 shows the normal case where the objects have their own CTs. The settings forCT direction shall be done according to the figure. To protect the line, direction of thedirectional functions of the line protection shall be set to Forward. This means that theprotection is looking towards the line.
4.2.2.2 Example 2
Two IEDs used for protection of two objects and sharing a CT.
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 45Application manual
Transformer
protection
Transformer
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
ForwardReverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED IED
IEC05000460 V2 EN
Figure 8: Example how to set CTStarPoint parameters in the IED
This example is similar to example 1, but here the transformer is feeding just one lineand the line protection uses the same CT as the transformer protection does. The CTdirection is set with different reference objects for the two IEDs though it is the samecurrent from the same CT that is feeding the two IEDs. With these settings, thedirectional functions of the line protection shall be set to Forward to look towards theline.
4.2.2.3 Example 3
One IED used to protect two objects.
Section 4 1MRK 506 375-UEN -Analog inputs
46 Railway application RER670 2.2 IECApplication manual
Transformer and
Line protection
Transformer
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
ReverseForward
Definition of direction
for directional
line functions
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IED
IEC05000461 V2 EN
Figure 9: Example how to set CTStarPoint parameters in the IED
In this example, one IED includes both transformer and line protections and the lineprotection uses the same CT as the transformer protection does. For both current inputchannels, the CT direction is set with the transformer as reference object. This meansthat the direction Forward for the line protection is towards the transformer. To looktowards the line, the direction of the directional functions of the line protection mustbe set to Reverse. The direction Forward/Reverse is related to the reference object thatis the transformer in this case.
If the IED has sufficient number of analog current inputs, an alternative solution isshown in Figure 10. The same currents are fed to two separate groups of inputs and theline and transformer protection functions are configured to the different inputs. TheCT direction for the current channels to the line protection is set with the line asreference object and the directional functions of the line protection shall be set toForward to protect the line.
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 47Application manual
Transformer and
Line protection
Transformer
Line
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
ForwardReverse
Definition of direction
for directional
line functions
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IEC05000462 V2 EN
Figure 10: Example how to set CTStarPoint parameters in the IED
4.2.2.4 Examples on how to connect, configure and set CT inputs for mostcommonly used CT connections
Figure 11 defines the marking of current transformer terminals commonly usedaround the world:
In the SMAI function block, you have to set if the SMAI block ismeasuring current or voltage. This is done with the parameter:AnalogInputType: Current/Voltage. The ConnectionType: phase -phase/phase-earth and GlobalBaseSel.
Section 4 1MRK 506 375-UEN -Analog inputs
48 Railway application RER670 2.2 IECApplication manual
ISec
I Pri
S1 (X1)
P1(H1)
P2(H2)
S2 (X2)
P2(H2)
P1(H1)
x x
a) b) c)
en06000641.vsd
S2 (X2) S1 (X1)
IEC06000641 V1 EN
Figure 11: Commonly used markings of CT terminals
Where:
a) is symbol and terminal marking used in this document. Terminals marked with a squareindicates the primary and secondary winding terminals with the same (that is, positive) polarity
b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that forthese two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices, the ratedsecondary current of a CT has typically one of the following values:
• 1A• 5A
However, in some cases, the following rated secondary currents are used as well:
• 2A• 10A
The IED fully supports all of these rated secondary values.
It is recommended to:
• use 1A rated CT input into the IED in order to connect CTs with1A and 2A secondary rating
• use 5A rated CT input into the IED in order to connect CTs with5A and 10A secondary rating
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 49Application manual
4.2.2.5 Example on how to connect a star connected two-phase CT set to theIED
Figure 12 gives an example about the wiring of a star connected two-phase CT set tothe IED. It gives an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within the IEDas well.
For correct terminal designations, see the connection diagrams validfor the delivered IED.
L1
IL1
IL2
L2
Protected Object
CT 600/5A
Star Connected
IL1
IL2
IED
IEC16000136-1-en.vsdx
1 2
3
4
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
IN
IEC16000136 V1 EN
Figure 12: Star connected two-phase CT set with star point towards theprotected object
Where:
1) Shows how to connect two individual phase currents from a star connected two-phase CT setto the two CT inputs of the IED.
2) The current inputs are located in the TRM. It shall be noted that for all these current inputs thefollowing setting values shall be entered for the example shown in Figure 12.
• CTprim=600A• CTsec=5A• CTStarPoint=ToObject
Ratio of the first two parameters is only used inside the IED. The third parameter(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.In other words, currents are already measured towards the protected object.
Table continues on next page
Section 4 1MRK 506 375-UEN -Analog inputs
50 Railway application RER670 2.2 IECApplication manual
3) These two connections are the links between the two phase current inputs and the two inputchannels of the preprocessing function block 4).
4) The preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:
• fundamental frequency phasors for the two input channels• harmonic content for the two input channels• positive and zero sequence quantities by using the fundamental frequency phasors for
the first two input channels (channel one taken as reference for sequence quantities)
These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For this applicationmost of the preprocessing settings can be left to the default values.
5) AI2P in the SMAI function block is a grouped signal which contains all the data about thephases L1, L2, L1–L2, and neutral quantity; in particular the data about fundamentalfrequency phasors, harmonic content, positive sequence and zero sequence quantities areavailable.AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain thefundamental frequency phasors and the harmonic content of the corresponding inputchannels of the preprocessing function block.AIN is the signal which contains the fundamental frequency phasors and the harmoniccontent of the neutral quantity. In this example, GRP2N is not connected so this data iscalculated by the preprocessing function block on the basis of the inputs GRPL1 and GRPL2.If GRP2N is connected, the data reflects the measured value of GRP2N.
Another alternative is to have the star point of the two-phase CT set as shown in Figure13:
L1
IL1
IL2
L2
Protected Object
IL1
IL2
IED
IEC16000137-1-en.vsdx
4 1
2
3IN
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5CT 600/5A
Star Connected
IEC16000137 V1 EN
Figure 13: Star connected two-phase CT set with its star point away from theprotected object
In the example, everything is done in a similar way as in the above described example(Figure 12). The only difference is the setting of the parameter CTStarPoint of theused current inputs on the TRM (item 2 in Figure 12 and 13):
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 51Application manual
• CTprim=600A• CTsec=5A• CTStarPoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameteras set in this example will negate the measured currents in order to ensure that thecurrents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the two-phase CT setconnected to the IED as shown in Figure 14.
L1
IL1
IL2
L2
Protected Object
CT 600/5A
Star ConnectedIL1
IL2
IN
IED
1
3
4
2
IEC16000138-1-en.vsdx
6
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
5
IEC16000138 V1 EN
Figure 14: Star connected two-phase CT set with its star point away from theprotected object and the residual/neutral current connected to theIED
Where:
1) Shows how to connect two individual phase currents from a star connected two-phase CT setto the two CT inputs of the IED.
2) Shows how to connect residual/neutral current from the two-phase CT set to the fourth inputin the IED. It shall be noted that if this connection is not made, the IED will still calculate thiscurrent internally by vectorial summation of the two individual phase currents.
3) Is the TRM where these current inputs are located. It shall be noted that for all these currentinputs the following setting values shall be entered.
• CTprim=600A• CTsec=5A• CTStarPoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameteras set inthis example will negate the measured currents in order to ensure that the currents aremeasured towards the protected object within the IED.
Table continues on next page
Section 4 1MRK 506 375-UEN -Analog inputs
52 Railway application RER670 2.2 IECApplication manual
4) Are two connections made in the Signal Matrix tool (SMT) and Application configuration tool(ACT) which connects these two phase current inputs to the first two input channels on thepreprocessing function block 6).
5) Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool(ACT), which connects the residual/neutral current input to the fourth input channel of thepreprocessing function block 6). Note that this connection in SMT shall not be done if theresidual/neutral current is not connected to the IED.
6) Is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:
• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive and zero sequence quantities by using the fundamental frequency phasors of
the first two input channels (channel one taken as reference for sequence quantities)
These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application, most of the preprocessing settings can be left to the default values.
4.2.2.6 Example how to connect single-phase CT to the IED
Figure 15 gives an example how to connect the single-phase CT to the IED. It givesan overview of the required actions by the user in order to make this measurementavailable to the built-in protection and control functions within the IED as well.
For correct terminal designations, see the connection diagrams validfor the delivered IED.
Protected Object
L1 L2
IED
INP
INS
INS
2
IEC16000139-1-en.vsdx
4
3
CT
600
/1A
a)
b)
(+)
(+)
(-)
(-)(+)
(-)
1SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
IEC16000139 V1 EN
Figure 15: Connections for single-phase CT input
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 53Application manual
Where:
1) shows how to connect single-phase CT input in the IED.
2) is TRM where these current inputs are located. It shall be noted that for all these currentinputs the following setting values shall be entered.For connection (a) shown in Fgure 15:CTprim= 600 ACTsec= 1ACTStarPoint=ToObject For connection (b) shown in Figure 15:CTprim= 600 ACTsec= 1ACTStarPoint=FromObject
3) shows the connection made in SMT tool, which connect this CT input to the fourth inputchannel of the preprocessing function block 4).
4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate values. The calculated values are then available for all built-in protection andcontrol functions within the IED, which are connected to this preprocessing function block.
4.2.3 Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protectionIED
Note that for all line protection applications the parameter Base Current (i.e. IBasesetting in the IED) used by the relevant protection function, shall always be set equalto the largest rated CT primary current among all CTs involved in the protectionscheme. The rated CT primary current value is set as parameter CTPrim under the IEDTRM settings.
For all other protection applications (e.g. transformer protection) it is typicallydesirable to set IBase parameter equal to the rated current of the protected object.However this is only recommended to do if the rated current of the protected object iswithin the range of 40% to 120% of the selected CT rated primary current. If for anyreason (e.g. high maximum short circuit current) the rated current of the protectedobject is less than 40% of the rated CT primary current, it is strongly recommended toset the parameter IBase in the IED to be equal to the largest rated CT primary currentamong all CTs involved in the protection scheme and installed on the same voltagelevel. This will effectively make the protection scheme less sensitive; however, suchmeasures are necessary in order to avoid possible problems with loss of themeasurement accuracy in the IED.
Regardless of the applied relationship between the IBase parameter and the rated CTprimary current, the corresponding minimum pickup of the function on the CTsecondary side must always be verified. It is strongly recommended that the minimumpickup of any instantaneous protection function (e.g. differential, restricted earthfault, distance, instantaneous overcurrent, etc.) shall under no circumstances be lessthan 4% of the used IED CT input rating (i.e. 1A or 5A). This corresponds to 40mAsecondary for IED 1A rated inputs and to 200mA secondary for IED 5A rated inputsused by the function. This shall be individually verified for all current inputs involvedin the protection scheme.
Section 4 1MRK 506 375-UEN -Analog inputs
54 Railway application RER670 2.2 IECApplication manual
4.2.4 Setting of voltage channels
As the IED uses primary system quantities, the main VT ratios must be known to theIED. This is done by setting the two parameters VTsec and VTprim for each voltagechannel. The phase-to-phase value can be used even if each channel is connected to aphase-to-earth voltage from the VT.
4.2.4.1 Example
Consider a VT with the following data:
110 100/
2 2
kV V
IECEQUATION16054 V1 EN (Equation 1)
The following setting should be used: VTprim=110 (value in kV) VTsec=100 (valuein V)
4.2.4.2 Examples how to connect, configure and set VT inputs for mostcommonly used VT connections
Figure 16 defines the marking of voltage transformer terminals commonly usedaround the world.
A(H1)
B(H2)
b(X2)
a(X1)
A(H1)
N(H2)
n(X2)
a(X1)
b) c)
A(H1)
N(H2)
dn(X2)
da(X1)
d)
UPri
+ +USec
a)
en06000591.vsd
IEC06000591 V1 EN
Figure 16: Commonly used markings of VT terminals
Where:
a) is the symbol and terminal marking used in this document. Terminals marked with a squareindicate the primary and secondary winding terminals with the same (positive) polarity
b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth connected VTs
c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open deltaconnected VTs
d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs
It shall be noted that depending on national standard and utility practices the ratedsecondary voltage of a VT has typically one of the following values:
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 55Application manual
• 100 V• 110 V
The IED fully supports all of these values and most of them will be shown in thefollowing examples.
4.2.4.3 Examples on how to connect a two phase-to-earth connected VT to theIED
Figure 17 gives an example on how to connect a two phase-to-earth connected VT tothe IED. It gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.
For correct terminal designations, see the connection diagrams validfor the delivered IED.
L1
IED L2
132
2110
2
kV
V
1
3
2
132
2110
2
kV
V
IEC16000140-1-en.vsdx
4
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
IEC16000140 V1 EN
Figure 17: A two phase-to-earth connected VT
Where:
1) shows how to connect two secondary phase-to-earth voltages to two VT inputs on the IED
2) is the TRM where these voltage inputs are located. For these voltage inputs, the followingsetting values shall be entered:VTprim =132 kVVTsec = 110 VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.
132 / 2132 /110
110 / 2
kk
IECEQUATION16055 V1 EN (Equation 2)
Table continues on next page
Section 4 1MRK 506 375-UEN -Analog inputs
56 Railway application RER670 2.2 IECApplication manual
3) are two connections made in Signal Matrix Tool (SMT), which connect these two voltageinputs to first two input channels of the preprocessing function block 5). Depending on thetype of functions which need this voltage information, more than one preprocessing blockmight be connected in parallel to these VT inputs.
4) shows that in this example the fourth (that is, residual) input channel of the preprocessingblock is not connected in SMT tool. Thus the preprocessing block will automaticallycalculate 2Uo inside by vectorial sum from the two phase to earth voltages connected tothe first two input channels of the same preprocessing block. Alternatively, the fourth inputchannel can be connected to open delta VT input, as shown in Figure 18.
5) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:
• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive and zero sequence quantities by using the fundamental frequency phasors
for the first two input channels (channel one taken as reference for sequence
These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values. However the following settings shall be set as shown here:UBase=132 kV (that is, rated Ph-Ph voltage)
4.2.4.4 Example on how to connect a residually connected IED
Figure 18 gives an example about the wiring of a residually connected VT to the IED.It shall be noted that this type of VT connection presents a secondary voltageproportional to 2U0 to the IED.
The primary rated voltage of an open Delta VT is always equal to UPh-E. Two seriesconnected VT secondary windings gives a secondary voltage equal to the sum of thetwo phase voltages. Thus the secondary windings of open deltaVTs may have asecondary rating of 110/2V.
Figure 18 gives overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IEDas well.
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 57Application manual
L1
IED L2
+2Uo
132
2100
2
kV
V
132
2100
2
kV
V
1
2
4
3
5
IEC16000152-1-en.vsdx
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
IEC16000152 V1 EN
Figure 18: Residually connected VT in two-phase power system
Where:
1) shows how to connect the secondary side of the residually connected VT to one VT inputon the IED.
+2U0 shall be connected to the IED
2) is the TRM where this voltage input is located. It shall be noted that for this voltage input thefollowing setting values shall be entered:VTprim=132kVVTsec=100VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.
3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool or ACT tool.
4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool(ACT), which connect this voltage input to the fourth input channel of the preprocessingfunction block 5).
5) is a Preprocessing block that has the task to digitally filter the connected analog input andcalculate:
• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• zero sequence quantities by using the fundamental frequency phasors for the fourth
input channel
These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values.
Section 4 1MRK 506 375-UEN -Analog inputs
58 Railway application RER670 2.2 IECApplication manual
4.2.4.5 Example on how to connect a neutral point VT to the IED
Figure 19 gives an example on how to connect a neutral point VT to the IED. This typeof VT connection presents secondary voltage proportional to U0 to the IED.
In case of a solid earth fault in high impedance earthed or unearthed systems theprimary value of Uo voltage will be equal to:
02
Ph PhPh N
UU U
IECEQUATION16056 V1 EN (Equation 4)
Figure 19 gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.
L1 L2
IED
6.6
2100
kV
V
RUo
IEC16000141-1-en.vsdx
Protected Object
1
2
3
4
SMAI2BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
IEC16000141 V1 EN
Figure 19: Neutral point connected VT
1MRK 506 375-UEN - Section 4Analog inputs
Railway application RER670 2.2 IEC 59Application manual
Where:
1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.
U0 shall be connected to the IED.
2) is the TRM or AIM where this voltage input is located. For this voltage input the followingsetting values shall be entered:
6.63.3
2VTprim kV
IECEQUATION16057 V1 EN (Equation 6)
sec 100VT V
EQUATION1934 V2 EN (Equation 7)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of the neutral point VT.
3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool or ACT tool.
4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool(ACT), which connects this voltage input to the fourth input channel of the preprocessingfunction block 5).
5) is a preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:
• fundamental frequency phasors for all the fourth input channels• harmonic content for all the fourth input channels
• zero sequence quantities by using the fundamental frequency phasors
These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application, most of the preprocessing settings can be left to the default values.
Section 4 1MRK 506 375-UEN -Analog inputs
60 Railway application RER670 2.2 IECApplication manual
Section 5 Local HMI
IEC13000239-3-en.vsd
IEC13000239 V3 EN
Figure 20: Local human-machine interface
The LHMI of the IED contains the following elements:
• Keypad• Display (LCD)• LED indicators• Communication port for PCM600
1MRK 506 375-UEN - Section 5Local HMI
Railway application RER670 2.2 IEC 61Application manual
The LHMI is used for setting, monitoring and controlling.
5.1 Display
The LHMI includes a graphical monochrome liquid crystal display (LCD) with aresolution of 320 x 240 pixels. The character size can vary. The amount of charactersand rows fitting the view depends on the character size and the view that is shown.
The display view is divided into four basic areas.
IEC15000270-1-en.vsdx
IEC15000270 V1 EN
Figure 21: Display layout
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
The function key button panel shows on request what actions are possible with thefunction buttons. Each function button has a LED indication that can be used as a
Section 5 1MRK 506 375-UEN -Local HMI
62 Railway application RER670 2.2 IECApplication manual
feedback signal for the function button control action. The LED is connected to therequired signal with PCM600.
IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN
Figure 22: Function button panel
The indication LED panel shows on request the alarm text labels for the indicationLEDs. Three indication LED pages are available.
IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN
Figure 23: Indication LED panel
The function button and indication LED panels are not visible at the same time. Eachpanel is shown by pressing one of the function buttons or the Multipage button.Pressing the ESC button clears the panel from the display. Both panels have a dynamicwidth that depends on the label string length.
1MRK 506 375-UEN - Section 5Local HMI
Railway application RER670 2.2 IEC 63Application manual
5.2 LEDs
The LHMI includes three status LEDs above the display: Ready, Start and Trip.
There are 15 programmable indication LEDs on the front of the LHMI. Each LED canindicate three states with the colors: green, yellow and red. The texts related to eachthree-color LED are divided into three panels.
There are 3 separate panels of LEDs available. The 15 physical three-color LEDs inone LED group can indicate 45 different signals. Altogether, 135 signals can beindicated since there are three LED groups. The LEDs are lit according to priority,with red being the highest and green the lowest priority. For example, if on one panelthere is an indication that requires the green LED to be lit, and on another panel thereis an indication that requires the red LED to be lit, the red LED takes priority and is lit.The LEDs can be configured with PCM600 and the operation mode can be selectedwith the LHMI or PCM600.
Information panels for the indication LEDs are shown by pressing the Multipagebutton. Pressing that button cycles through the three pages. A lit or un-acknowledgedLED is indicated with a highlight. Such lines can be selected by using the Up/Downarrow buttons. Pressing the Enter key shows details about the selected LED. Pressingthe ESC button exits from information pop-ups as well as from the LED panel as such.
The Multipage button has a LED. This LED is lit whenever any LED on any panel islit. If there are un-acknowledged indication LEDs, then the Multipage LED blinks. Toacknowledge LEDs, press the Clear button to enter the Reset menu (refer todescription of this menu for details).
There are two additional LEDs which are next to the control buttons and .These LEDs can indicate the status of two arbitrary binary signals by configuring theOPENCLOSE_LED function block. For instance, OPENCLOSE_LED can beconnected to a circuit breaker to indicate the breaker open/close status on the LEDs.
IEC16000076-1-en.vsd
IEC16000076 V1 EN
Figure 24: OPENCLOSE_LED connected to SXCBR
Section 5 1MRK 506 375-UEN -Local HMI
64 Railway application RER670 2.2 IECApplication manual
5.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either asmenu shortcut or control buttons.
1MRK 506 375-UEN - Section 5Local HMI
Railway application RER670 2.2 IEC 65Application manual
1
18
19
7
6
5
4
3
2
8
20
21
22
17161514131211109
23
24
IEC15000157-2-en.vsd
IEC15000157 V2 EN
Figure 25: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port
1...5 Function button
6 Close
7 Open
8 Escape
9 Left
10 Down
11 Up
12 Right
13 Key
14 Enter
15 Remote/Local
16 Uplink LED
17 Not in use
18 Multipage
Section 5 1MRK 506 375-UEN -Local HMI
66 Railway application RER670 2.2 IECApplication manual
19 Menu
20 Clear
21 Help
22 Communication port
23 Programmable indication LEDs
24 IED status LEDs
5.4 Local HMI functionality
5.4.1 Protection and alarm indication
Protection indicatorsThe protection indicator LEDs are Ready, Start and Trip.
The start and trip LEDs are configured via the disturbance recorder.The yellow and red status LEDs are configured in the disturbancerecorder function, DRPRDRE, by connecting a start or trip signalfrom the actual function to a BxRBDR binary input function blockusing the PCM600 and configure the setting to Off, Start or Trip forthat particular signal.
Table 10: Ready LED (green)
LED state DescriptionOff Auxiliary supply voltage is disconnected.
On Normal operation.
Flashing Internal fault has occurred.
Table 11: Start LED (yellow)
LED state DescriptionOff Normal operation.
On A protection function has started and an indication message is displayed.The start indication is latching and must be reset via communication, LHMIor binary input on the LEDGEN component. To open the reset menu on theLHMI, press .
Flashing The IED is in test mode and protection functions are blocked, or theIEC61850 protocol is blocking one or more functions.The indication disappears when the IED is no longer in test mode andblocking is removed. The blocking of functions through the IEC61850protocol can be reset in Main menu/Test/Reset IEC61850 Mod. The yellowLED changes to either On or Off state depending on the state of operation.
1MRK 506 375-UEN - Section 5Local HMI
Railway application RER670 2.2 IEC 67Application manual
Table 12: Trip LED (red)
LED state DescriptionOff Normal operation.
On A protection function has tripped. An indication message is displayed if theauto-indication feature is enabled in the local HMI.The trip indication is latching and must be reset via communication, LHMI orbinary input on the LEDGEN component. To open the reset menu on theLHMI, press .
Flasing Configuration mode.
Alarm indicatorsThe 15 programmable three-color LEDs are used for alarm indication. An individualalarm/status signal, connected to any of the LED function blocks, can be assigned toone of the three LED colors when configuring the IED.
Table 13: Alarm indications
LED state DescriptionOff Normal operation. All activation signals are off.
On • Follow-S sequence: The activation signal is on.• LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.• LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.• LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.• LatchedReset-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
Flashing • Follow-F sequence: The activation signal is on.• LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.• LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.
5.4.2 Parameter management
The LHMI is used to access the relay parameters. Three types of parameters can beread and written.
• Numerical values• String values• Enumerated values
Numerical values are presented either in integer or in decimal format with minimumand maximum values. Character strings can be edited character by character.Enumerated values have a predefined set of selectable values.
Section 5 1MRK 506 375-UEN -Local HMI
68 Railway application RER670 2.2 IECApplication manual
5.4.3 Front communication
The RJ-45 port in the LHMI enables front communication.
• The green uplink LED on the left is lit when the cable is successfully connectedto the port.
• The yellow LED is not used; it is always off.
IEC13000280-1-en.vsd
1
2
GUID-AACFC753-BFB9-47FE-9512-3C4180731A1B V1 EN
Figure 26: RJ-45 communication port and green indicator LED
1 RJ-45 connector
2 Green indicator LED
The default IP address for the IED front port is 10.1.150.3 and the correspondingsubnetwork mask is 255.255.254.0. It can be set through the local HMI path Mainmenu/Configuration/Communication/Ethernet configuration/FRONT port/AP_FRONT.
Do not connect the IED front port to a LAN. Connect only a singlelocal PC with PCM600 to the front port. It is only intended fortemporary use, such as commissioning and testing.
1MRK 506 375-UEN - Section 5Local HMI
Railway application RER670 2.2 IEC 69Application manual
Section 6 Differential protection
6.1 Low impedance restricted earth fault protectionREFPDIF
6.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Restricted earth fault protection, lowimpedance
REFPDIF
IdN/I
SYMBOL-AA V1 EN
87N
6.1.2 Application
A breakdown of the insulation between a transformer winding and the core or the tankmay result in a large fault current which causes severe damage to the windings and thetransformer core. A high gas pressure may develop, damaging the transformer tank.
Fast and sensitive detection of earth faults in a power transformer winding can beobtained in solidly earthed or low impedance earthed networks by the restricted earthfault protection. The only requirement is that the power transformer winding isconnected to earth in the star point (in case of star-connected windings).
The low impedance restricted earth fault protection REFPDIF is a winding protectionfunction. It protects the power transformer winding against faults involving earth.Observe that single phase-to-earth faults are the most common fault types intransformers. Therefore, a sensitive earth fault protection is desirable.
A restricted earth fault protection is the fastest and the most sensitive protection, apower transformer winding can have and will detect faults such as:
• earth faults in the transformer winding when the network is earthed through animpedance
• earth faults in the transformer winding in solidly earthed network when the pointof the fault is close to the winding star point.
The restricted earth fault protection is not affected, as a differential protection, withthe following power transformer related phenomena:
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 71Application manual
• magnetizing inrush currents• overexcitation magnetizing currents• load tap changer• external and internal phase faults which do not involve earth• symmetrical overload conditions
Due to its features, REFPDIF is often used as a main protection of the transformerwinding for all faults involving earth.
6.1.2.1 Transformer winding, solidly earthed
The most common application is on a solidly earthed transformer winding. Theconnection is shown in Figure 27.
IEC16000117-1-en.vsdx
REFPDIF
I2P
ISI
IdN/I
Protected
winding
IEC16000117 V1 EN
Figure 27: Connection of the low impedance Restricted earth fault functionREFPDIF for a directly (solidly) earthed transformer winding
Section 6 1MRK 506 375-UEN -Differential protection
72 Railway application RER670 2.2 IECApplication manual
6.1.2.2 CT earthing direction
To make the restricted earth fault protection REFPDIF operate correctly, the mainCTs are always supposed to be star -connected. The main CT's neutral (star) formationcan be positioned in either way, ToObject or FromObject. However, internallyREFPDIF always uses reference directions towards the protected transformers, asshown in Figure 27. Thus the IED always measures the primary currents on all sidesand in the neutral of the power transformer with the same reference direction towardsthe power transformer windings.
The main CT's connection type can be freely selected for each of the involved currenttransformers.
6.1.2.3 Railway specific applications for REFPDIF function
If appropriate configuration and settings are applied, the REFPDIF function can alsobe used for the following special applications in the railway supply system:
• Defrost protection, when a single phase differential protection is temporaryarranged among two CTs during de-icing operation of the catenary contact linewires.
• Single phase differential protection applied across one winding (i.e. either overone single-phase transformer winding or a generator winding).
6.1.3 Setting guidelines
6.1.3.1 Setting and configuration
Recommendation for analog inputsISI: Neutral current input.
I2P: Phase currents from winding HV side current transformer set.
Recommendation for Binary input signalsBLOCK: The input will block the operation of the function. It can be used, forexample, to block the operation during special service conditions for a limited time.
Recommendation for output signalsSTART: The start output indicates that Idiff is in the operate region of the operate-restraint characteristic.
TRIP: The trip output is activated when all operating criteria are fulfilled.
DIROK: The output is activated when the directional criteria has been fulfilled.
BLK2H: The output is activated when the function is blocked due to high level ofsecond harmonic.
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 73Application manual
6.1.3.2 Settings
The parameters for the restricted earth fault protection, low impedance functionREFPDIF are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
Operation: The operation of REFPDIF can be switched On/Off.
IdMin: The setting gives the minimum operation value. The setting is in percent of theIBase value of the chosen GlobalBaseSel. For function operation, the neutral currentmust be larger than half of this value. A recommended setting is 30% of powertransformer-winding rated current for a solidly earthed winding.
ROA: Relay operate angle for zero sequence directional feature. It is used todifferentiate an internal fault and an external fault based on measured zero sequencecurrent and neutral current. Default value of 60 deg is recommended.
6.2 Single-phase railway power transformer differentialprotection T1PPDIF
6.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Single-phase railway power transformerdifferential protection
T1PPDIF
Id/I>
IEC15000166 V1 EN
87T
6.2.2 Application
The railway transformer differential protection is a unit protection. The function isdesigned to operate properly for 16.7Hz, 50Hz and 60Hz railway power transformers.It serves as the main protection of railway power transformers in case of windingfailure. Internal electrical faults are very serious and will cause immediate damage.Short circuits and earth faults in windings and terminals will normally be detected bythe differential protection. It is possible to detect inter-turn faults if a sufficientnumber of turns is short-circuited. Inter-turn faults are the most difficult transformerwinding fault to detect with electrical protections.
It is important that the faulty power transformer can be disconnected as fast aspossible. As the differential protection is a unit protection, it can be designed for fast
Section 6 1MRK 506 375-UEN -Differential protection
74 Railway application RER670 2.2 IECApplication manual
tripping, thus providing selective disconnection of the faulty railway powertransformer. The differential protection should never operate on faults outside theprotective zone. A transformer differential protection compares the current flowinginto the transformer with the current leaving the transformer.
The differential current should be zero during normal load or external faults if the turn-ratio and the phase shift are correctly compensated. However, there are severalphenomena other than internal faults that will cause unwanted and false differentialcurrents. The main reasons for unwanted differential currents are:
• different characteristics, loads and operating conditions of the currenttransformers
• zero sequence currents that flow only on one side of the power transformer• normal magnetizing currents• magnetizing inrush currents• overexcitation magnetizing currents
6.2.3 Setting guidelines
The parameters for the transformer differential protection T1PPDIF function are setvia the local HMI or Protection and Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: This is used for transformer differential protection Off/On.
6.2.3.1 Restrained and unrestrained differential protection
To make a differential IED as sensitive and stable as possible, restrained differentialprotections have been developed and are now adopted as the general practice in theprotection of power transformers. The protection should be provided with aproportional bias, which makes the protection operate for a certain percentagedifferential current related to the current flowing through the transformer. Thisstabilizes the protection under through-fault conditions while still permitting the relayto have good basic sensitivity.
The bias current should be defined as the highest power transformer current becausethis will reflect the difficulties met by the current transformers much better. Thedifferential protection function uses the highest differential current contribution fromthe two sides as bias current. The principle with the operate-bias characteristic is toincrease the pick-up level when the current transformers have difficult operatingconditions.
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 75Application manual
The usual practice for transformer protection is to set the bias characteristic to a valueof at least twice the value of the expected spill current under through-fault conditions.These criteria can vary considerably from application to application.
The default settings for the operating characteristic with IdMin = 30% of the railwaypower transformer rated current can be recommended in normal applications. If theconditions are known in more detail, a higher or a lower sensitivity can be chosen. Insuch cases, the selection of the suitable characteristic should be based on the class ofthe current transformers, the short-circuit power of the systems, and so on.
The second section of the restrain characteristic has an increased slope in order to dealwith the increased differential current during heavy loading of the transformer andexternal fault currents.
The third section of the restrain characteristic further decreases the sensitivity of therestrained differential function in order to cope with CT saturation during heavythrough faults.
The unrestrained operation level has a default value of IdUnre = 800% of the railwaypower transformer rated current, which is typically acceptable for most of the standardapplications. The overall operating characteristic of the transformer differentialprotection is shown in Figure 28:
Section 6 1MRK 506 375-UEN -Differential protection
76 Railway application RER670 2.2 IECApplication manual
Unrestrained Limit IdUnre
Restrain
Restrain current [%]
(bias current)
Operate
unconditionally
Operate
conditionally
Section 1 Section 2 Section 3
SlopeSection 2
SlopeSection 3
EndSection 1
EndSection2
Operate current [%]
(differential current)
IdMin
IEC15000390-2-en.vsdx
IEC15000390 V2 EN
Figure 28: Operate-restrain characteristic
The operate-restrained characteristic is determined by five parameter settings:
• IdMin• EndSection1• EndSection2• SlopeSection2• SlopeSection3
The slope is relative to the characteristic breakpoint.
%100
BIAS
DIFF
I
Islope
IECEQUATION15054 V1 EN (Equation 8)
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 77Application manual
6.2.3.2 Elimination of zero sequence currents
To avoid unwanted trips for external earth faults, zero sequence currents should besubtracted on the side of the protected railway power transformer where they can flowduring external earth faults.
Eliminating the zero sequence component is necessary when:
• the protected railway power transformer cannot transform the zero sequencecurrents to the other side.
• the zero sequence currents can only flow on one side of the protected railwaypower transformer.
If zero sequence current reduction is not done, it can cause false differential currentsconsisting exclusively of the zero sequence currents. If high enough, these falsedifferential currents can cause an unwanted disconnection of a healthy railway powertransformer.
Removing zero sequence currents is important for the stability of T1PPDIF againstexternal earth faults.
The disadvantage of eliminating the zero sequence current is that T1PPDIF becomesless sensitive to the single-phase earth faults within the protected zone. To counteractfor this effect to some degree, the zero sequence current is subtracted not only from thefundamental frequency differential current, but also from the bias current (seeTransformer connection types in Technical Manual). For a railway power transformerwinding, the zero sequence current is subtracted when for the phase selectionparameter on the respective side the value (L1-L2)/2 is selected. For a detailedexplanation, see the calculations done in Solution 1 in section Setting example in thismanual.
6.2.3.3 Inrush restraint methods
With a combination of the 2nd harmonic restraint and the waveform restraint methodsit is possible to get a protection with high security and stability against inrush effectsand, at the same time, maintain high performance in case of heavy internal faults evenif the current transformers are saturated. Both these restraint methods are used by theT1PPDIF function. The 2nd harmonic restraint function has a settable level. If the ratioof the 2nd harmonic to the fundamental in the differential current is above the settablelimit, the operation of the differential protection is blocked. It is recommended to setparameter I2/I1Ratio = 15% as default value if there are no reasons to choose anothervalue.
6.2.3.4 Overexcitation restraint method
In case of an overexcited transformer, the winding currents contain odd harmoniccomponents because the current waveform is symmetrical to the time axis. Thedifferential protection function is provided with a 5th harmonic restraint to prevent the
Section 6 1MRK 506 375-UEN -Differential protection
78 Railway application RER670 2.2 IECApplication manual
protection from operating during an overexcitation condition of a power transformer.If the ratio of the 5th harmonic to the fundamental in the differential current is abovea settable limit, the operation is restrained. It is recommended to use I5/I1Ratio = 25%as default value if there are no special reasons to choose another setting.
6.2.3.5 Protections based on the directional criterion
Two kinds of protections based on the directional criterion are integrated into therailway differential protection function:
• The directional unrestrained differential protection• The directional sensitive differential protection
These two subfunctions are based on the internal-external fault discriminator, whichis a supplementary criterion to the traditional differential protection. The internal/external fault discriminator detects even minor faults, with a high sensitivity and athigh speed and, at the same time, discriminates between internal and external faultswith a high degree of dependability. The goal is to be able to quickly switch off thefaulty power transformer before the fault develops into a severe one (for example, afault involving the iron core). This feature should always be used when protecting arailway power transformer (by setting DirDiffEn = On).
6.2.4 Setting examples
For the transformer in Figure 29, there are two solutions for balancing the transformerdifferential protection.
IEC16000067-1-en.vsd
15kV132kV
I
U
v
IU
IsSV
R
IEC16000067 V1 EN
Figure 29: A railway transformer with rating 16MVA, 132/15kV
Solution 1 (see Figure 35 for CT connections and ACT configuration):
Connection to the preprocessing blocks:
HV side: IL1=IV; IL2=IU
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 79Application manual
LV side: IL1=IS, IL2= 0
Settings within the transformer differential protection:
PhSelW1 = (IL1-IL2)/2
PhSelW2 = IL1
InvW2Curr = No
Solution 2 (see Figure 36 for CT connections and ACT configuration):
Connection to the preprocessing blocks:
HV side: IL1=IU; IL2=IV
LV side: IL1=0, IL2= IS
Settings within the transformer differential protection:
PhSelW1 = (IL1-IL2)/2
PhSelW2 = IL2
InvW2Curr = Yes
Base current
The base current is calculated for each side (winding 1 and winding 2) of the powertransformer:
1
10001 121
W
SBaseIBaseW A
UBase
IECEQUATION16075 V1 EN (Equation 9)
2
10002 1067
W
SBaseIBaseW A
UBase
IECEQUATION16076 V1 EN (Equation 10)
where:
SBase Rated power of transformer [MVA]
UBaseW1 Rated phase-to-phase voltage of winding 1 [kV]
UBaseW2 Rated phase-to-phase voltage of winding 2 [kV]
The base currents for T1PPDIF functions are set under Global Base Values inParameter Setting tool.
Section 6 1MRK 506 375-UEN -Differential protection
80 Railway application RER670 2.2 IECApplication manual
6.2.4.1 Application examples
Five examples of railway power transformer connections are presented here. Othertransformer connections may also be protected using the single-phase T1PPDIFfunction.
Transformer connection – example 1
In all the following figures the phases are indicated as U and V on theHV side and R and S on the LV side of the transformer. Equivalentwinding ends are U & R and V & S.
IEC15000170-3-en.vsdx
132/15kV
15kV132kV
I
U
v
IU
Is
SV
R
IEC15000170 V3 EN
Figure 30: Transformer connection – example 1
Base current calculation:
kVU
MVASI
WxPhPh
WxBase
__
_
1000
IECEQUATION058 V1 EN (Equation 11)
The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV current Is shall beconnected as IL1 current for the winding 2 side towards the T1PPDIF function.
Zero sequence current calculation on the HV side:
02U VI I I IECEQUATION200 V2 EN (Equation 12)
Removal of zero sequence current from the V phase:
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 81Application manual
0 2 2
U V V UV V
I I I II I I
IECEQUATION201 V2 EN (Equation 13)
The phase selection settings for the T1PPDIF function shall be:
PhSelW1=(L1-L2)/2
PhSelW2=L1
InvW2Curr=No
Calculation of differential and bias currents:
1 2
1 2
100 100% 1 2
2
100 100% 1 , 2 ,
2
V UDiff S
BaseW BaseW
V UBias S
BaseW BaseW
I II IDLW IDLW I
I I
I II IDLW IDLW Max I
I I
IECEQUATION202 V2 EN (Equation 14)
Transformer connection – example 2
IEC15000171-3-en.vsdx
66/15kV
15kV66kV
I
U
v
IU
Is
SV
R
IEC15000171 V3 EN
Figure 31: Transformer connection – example 2
The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV current Is shall beconnected as IL1 current for the winding 2 side towards the T1PPDIF function.
Zero-sequence current removal is not necessary in this arrangement.
The phase selection settings for the first instance of the T1PPDIF function shall be:
PhSelW1=L1
PhSelW2=L1
Section 6 1MRK 506 375-UEN -Differential protection
82 Railway application RER670 2.2 IECApplication manual
InvW2Curr=No
Then the internal calculations will be:
1
1 2
1
1 2
100 100% IDLW1 IDLW2
100 100% 1 , 2 ,
Diff V S
BaseW BaseW
Bias V S
BaseW BaseW
I I II I
I Max IDLW IDLW Max I II I
IECEQUATION203 V2 EN (Equation 15)
The phase selection settings for the second instance of the T1PPDIF function shall be:
PhSelW1=L2
PhSelW2=L1
InvW2Curr=Yes
Then the internal calculations will be:
2
1 2
2
1 2
100 100% IDLW1 IDLW2
100 100% 1 , 2 ,
Diff U S
BaseW BaseW
Bias U S
BaseW BaseW
I I II I
I Max IDLW IDLW Max I II I
IECEQUATION204 V2 EN (Equation 16)
Transformer connection – example 3
IEC15000172-2-en.vsdx
132/66kV
66kV132kV
I
U
v
IU
IS
SV
IR
R
IEC15000172 V2 EN
Figure 32: Transformer connection – example 3
The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV currents IS and IR shallbe connected as IL1 and IL2 currents, respectively, for the winding 2 side towards theT1PPDIF function.
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 83Application manual
To calculate the zero sequence current reduction for U and V phases, see connectionexample 1.
The phase selection settings for the first instance of the T1PPDIF function shall be:
PhSelW1=(L1-L2)/2
PhSelW2=L1
InvW2Curr=No
Then the internal calculations will be:
1
1 2
1
1 2
100 100% IDLW1 IDLW2
2
100 100% 1 , 2 ,
2
V UDiff S
BaseW BaseW
V UBias S
BaseW BaseW
I II I
I I
I II Max IDLW IDLW Max I
I I
IECEQUATION205 V2 EN (Equation 17)
The phase selection settings for the second instance of the T1PPDIF function shall be:
PhSelW1=(L1-L2)/2
PhSelW2=L2
InvW2Curr=Yes
Then the internal calculations will be:
2
1 2
2
1 2
100 100% IDLW1 IDLW2
2
100 100% 1 , 2 ,
2
V UDiff R
BaseW BaseW
V UBias R
BaseW BaseW
I II I
I I
I II Max IDLW IDLW Max I
I I
IECEQUATION206 V2 EN (Equation 18)
Section 6 1MRK 506 375-UEN -Differential protection
84 Railway application RER670 2.2 IECApplication manual
Transformer connection – example 4
IEC15000173-2-en.vsdx
132/110kV
110kV132kV
I
U
v
IU
IS
SV
IR
R
IEC15000173 V2 EN
Figure 33: Transformer connection – example 4
The HV currents IV and IU shall be connected as IL1 and IL2 currents, respectively,for the winding 1 side towards the T1PPDIF function. The LV currents IS and IR shallbe connected as IL1 and IL2 currents, respectively, for the winding 2 side towardsT1PPDIF function.
To calculate zero sequence current reduction for U, V, R and S phases, see connectionexample 1.
The phase selection settings for the first instance of the T1PPDIF function shall be:
PhSelW1=(L1-L2)/2
PhSelW2=(L1-L2)/2
InvW2Curr=No
Then the internal calculations will be:
1 2
1 2
100 100% IDLW1 IDLW2
2 2
100 100% 1 , 2 ,
2 2
V U S RDiff
BaseW BaseW
V U S RBias
BaseW BaseW
I I I II
I I
I I I II Max IDLW IDLW Max
I I
IECEQUATION207 V2 EN (Equation 19)
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 85Application manual
Transformer connection – example 5
IU
Iv Is
110kV 15kV
U
SV
110/15kV
IEC15000174-3-en.vsdx
R
IEC15000174 V3 EN
Figure 34: Transformer connection – example 5
The starpoint of the 110/15kV railway transformer can either be earthed (via coil) orisolated.
For information on how to arrange the differential protection for this transformer, seeexample 2.
6.2.4.2 How to wire the transformer differential protection to the IED using CTs
Here are two examples of how to wire and connect a star-connected, two-phase CT (onthe high-voltage side) and a one-phase CT (on the low-voltage side) to the IED forprotection of a railway power transformer (shown in Figure 29) using the T1PPDIFfunction.
For the correct terminal designations, see the connection diagramsvalid for the delivered IED.
Section 6 1MRK 506 375-UEN -Differential protection
86 Railway application RER670 2.2 IECApplication manual
Solution 1
V U
S
I V I U
IV
IU
IS
HV-side
LV-side
16MVA132/15kV
T1PPDIFI2PW1
BLOCKBLKRES
TRIPI2PW2
BLKUNRESBLKDRUNRBLKDRSEN
TRRESTRUNRESTRDRUNRTRDRSEN
STARTIDALARM
ST2NDHRMST5THHRMSTWAVDET
IDLIDLMAG
IBIAS
SMAI2BLOCKGRP2L1GRP2L2GRP2L1L2GRP2N
G2AI2PG2AI1G2AI2G2AI3G2AI4
G2N
SMAI1BLOCKGRP1L1GRP1L2GRP1L1L2GRP1N
G1AI2PG1AI1G1AI2G1AI3G1AI4
G1N
IED
1
2
2
3
3
4
4
5
CT
20
0/1
Star
co
nn
ecte
dC
T 1
60
0/1
I S
1
IEC16000064-1-en-original.vsd
IN
IEC16000064 V1 EN
Figure 35: CT wiring, pre-processing blocks and T1PPDIF connections for theproposed Solution 1
1 HV side: Two individual phase currents from a star-connected two-phase CT set are connected to twoCT inputs in the IEDLV side: A single phase current from the one-phase CT is connected to a third CT input in the IED
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 87Application manual
2 The current inputs are located in the TRM. The following settings shall be used for the current inputsin this example:HV side (two inputs):
• CTprim = 200A• CTsec = 1A• CTStarPoint = ToObject
LV side (one input):
• CTprim = 1200A• CTsec = 1A• CTStarPoint = ToObject
Inside the IED, only the ratio of the first two parameters is used. The third parameter (CTStarPoint =ToObject) causes no change on the measured currents. In other words, currents are alreadymeasured towards the protected object.
3 These connections are the links between the current inputs and the input channels of the twopreprocessing function blocks. The preprocessing block digitally filters the connected currents andcalculates:
• fundamental frequency phasors for all input channels• harmonic content for all input channels• positive- and zero-sequence quantities by using the fundamental frequency phasors (phase L1
taken as reference for sequence quantities)
These calculated values are then available for all built-in protection and control functions within theIED that are connected to this preprocessing function block. For this application most of thepreprocessing settings can be left to the default values.
4 GxAI2P output on the SMAI function block is a grouped signal which contains all the data about thephase L1, phase L2 and the neutral quantity; in particular, the data about fundamental frequencyphasors, harmonic content, positive sequence and zero sequence quantities are available.
5 Two group signals (G1AI2P and G2AI2P) in the preprocessing blocks SMAI1 and SMAI2 areconnected to the inputs I2PW1 and I2PW2 in T1PPDIF.Phase selection settings for the measured currents in T1PPDIF:
• PhSelW1 = (IL1-IL2)/2• PhSelW2 = IL1• InvW2Curr = No
Section 6 1MRK 506 375-UEN -Differential protection
88 Railway application RER670 2.2 IECApplication manual
Solution 2
V U
S
I V I U
IU
IV
IS
HV-side
LV-side
16MVA132/15kV
T1PPDIFI2PW1
BLOCKBLKRES
TRIPI2PW2
BLKUNRESBLKDRUNRBLKDRSEN
TRRESTRUNRESTRDRUNRTRDRSEN
STARTIDALARM
ST2NDHRMST5THHRMSTWAVDET
IDLIDLMAG
IBIAS
SMAI2BLOCKGRP2L1GRP2L2GRP2L1L2GRP2N
G2AI2PG2AI1G2AI2G2AI3G2AI4
G2N
SMAI1BLOCKGRP1L1GRP1L2GRP1L1L2GRP1N
G1AI2PG1AI1G1AI2G1AI3G1AI4
G1N
IED
1
2
2
3
3
4
4
5
CT
20
0/1
Star
co
nn
ect
edC
T 1
60
0/1
I S
1
=IEC16000065=1=en=Original.vsd
IN
IEC16000065 V1 EN
Figure 36: CT wiring, pre-processing blocks and T1PPDIF connections for theproposed Solution 2
This solution is similar to Solution 1. The only differences are the following:
1. In point 5 the settings in T1PPDIF are the following:• PhSelW1 = (IL1-IL2)/2• PhSelW2 = IL2• InvW2Curr = Yes
2. The sequence of the HV currents is swapped by wiring towards the IED.3. LV current is connected as phase L2 on the preprocessing function block.
1MRK 506 375-UEN - Section 6Differential protection
Railway application RER670 2.2 IEC 89Application manual
Section 7 Impedance protection
7.1 Automatic switch onto fault logic ZCVPSOF
7.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Automatic switch onto fault logic ZCVPSOF - -
7.1.2 Application
Automatic switch onto fault logic, voltage- and current-based function ZCVPSOF isa complementary function to impedance measuring functions, but may use theinformation from such functions.
With ZCVPSOF, a fast trip is achieved for a fault on the whole line when the line isbeing energized. The ZCVPSOF tripping is generally non-directional to secure a tripat fault situations where directional information cannot be established, for example,due to lack of polarizing voltage when a line potential transformer is used.
Automatic activation based on dead-line detection can only be used when the voltagetransformer is situated on the line side of a circuit breaker.
When line side voltage transformers are used, the use of the nondirectional distancezones secures switch onto fault tripping for close-in three-phase short circuits. The useof the nondirectional distance zones also gives a fast fault clearance when energizinga bus from the line with a short circuit fault on the bus.
Other protection functions like time-delayed phase and zero-sequence overcurrentfunction can be connected to ZCVPSOF to increase the dependability in the scheme.
When the voltage transformers are situated on the bus side, the automatic switch ontofault detection based on dead-line detection is not possible. In such cases the switchonto fault logic is activated using the binary input BC.
7.1.3 Setting guidelines
The parameters for automatic switch onto fault logic, voltage- and current-basedfunction ZCVPSOF are set via the local HMI or Protection and Control ManagerPCM600.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 91Application manual
The distance protection zone used for instantaneous trip by ZCVPSOF has to be set tocover the entire protected line with a safety margin of minimum 20%.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel is used to select GBASVAL for reference of base values.
Operation: The operation of ZCVPSOF is by default set to On. The parameter must beset to Off if ZCVPSOF is not to be used.
IPh< is used to set the current level for the detection of a dead line. IPh< is, by default,set to 20% of IBase. It shall be set with a sufficient margin (15–20%) below theminimum expected load current. In many cases, the minimum load current of a line isclose to zero and even can be zero. The operating value must exceed the maximumcharging current of an overhead line when only one phase is disconnected (mutualcoupling in the other phases).
UPh< is used to set the voltage level for the detection of a dead line. UPh< is, bydefault, set to 70% of UBase. This is a suitable setting in most cases, but it isrecommended to check the suitability in the actual application.
AutoInitMode: automatic activating of ZCVPSOF is, by default, set to DLD disabled,which means the dead-line logic detection is disabled. If an automatic activation of thedead-line detection is required, the parameter AutoInitMode has to be set to eitherVoltage, Current or Current & Voltage.
When AutoInitMode is set to Voltage, the dead-line detection logic checks that thetwo-phase voltages are lower than the set UPh< level.
When AutoInitMode is set to Current, the dead-line detection logic checks if the two-phase currents are lower than the set IPh< level.
When AutoInitMode is set to Current & Voltage, the dead-line detection logic checksthat both two-phase currents and two-phase voltages are lower than the set IPh< andUPh< levels.
Otherwise, the logic is activated by an external BC input.
tSOTF: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is suitablefor most applications.
tDLD: The time delay for activating ZCVPSOF by the internal dead-line detection is,by default, set to 0.2 seconds. It is suitable in most applications. The delay shall not beset too short to avoid unwanted activations during transients in the system.
Mode: The operation of ZCVPSOF has three modes for defining the criteria fortripping. The setting of Mode is, by default, UILevel, which means that the trippingcriterion is based on the setting of IPh< and UPh<. The choice of UILevel gives afaster and more sensitive operation of the function, which is important for reducing the
Section 7 1MRK 506 375-UEN -Impedance protection
92 Railway application RER670 2.2 IECApplication manual
stress that might occur when energizing onto a fault. However, the voltage recoverycan be slow in some systems when energizing the line. Therefore, if the timertDuration is set too short, ZCVPSOF can interpret this as a fault and release a trip.
When Mode is set to Impedance, the operate criterion is based on the BC input (breakerclosing), which can be the start of the overreaching zone from the impedance zonemeasurement. A nondirectional output signal should be used from an overreachingzone. The selection of the Impedance mode gives increased security.
When Mode is set to UILvl&Imp, the condition for tripping is an ORed betweenUILevel and Impedance.
tDuration: The setting of the timer for the release of UILevel is, by default, 0.02seconds, which has proven to be suitable in most cases from field experience. If ashorter time delay is to be set, it is necessary to consider the voltage recovery timeduring line energization.
7.2 Distance protection, quadrilateral characteristicZRWPDIS
7.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEEidentification
Distance protection, quadrilateralcharacteristic
ZRWPDISZ<
IEC15000305 V1 EN
21
7.2.2 Application
The distance protection, quadrilateral characteristic ZRWPDIS function is applicablefor all earthing types in 2-phase power networks. The SystemEarthing setting isprovided in order to have the distance protection function suitable for a specific typeof earthing system.
The ZRWPDIS application function is designed to detect and clear the faultsmentioned in Table 14 with reliability in order to maintain the system stability.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 93Application manual
Table 14: Earthing systems and possible faults
Earthing system Types of faultCompensated earthing systems • Single phase earth fault of short duration
• Sustained single phase earth fault• Cross country double earth faults• Two phase short circuit with and without
earth connection
Solidly earthing systems • Single phase earth fault• Two phase short circuit with and without
earth connection
High impedance earthing systems • Single phase earth fault• Cross country double earth faults• Two phase short circuit with and without
earth connection
7.2.2.1 Compensated earthing systems
In compensated grids, a distinction must be made between the following types offaults:
• Single earth fault, short-term (< 5sec)• Single earth fault, sustained (> 5sec) (= sustained earth fault)• Double cross country line-to-earth faults with separate earth contact points• Phase-to-phase short-circuit, earthed and unearthed
When the single earth faults occurs, the fault currents are reduced by the earth-faultneutralizers or the active compensation facility level decreases until the flashovers areneutralized automatically. The concerned phase is not to be tripped. However, thefaulty phase has to be identified and indicated (earth-fault protection/determination ofthe earth fault direction).
When the cross country phase-to-earth faults occurs, the two phases have to behandled with different time grading so that a delayed disconnection of the L2 phaseenables elimination of the fault via the earth-fault neutralizing function. The L2 phaseis tripped only if the neutralization after a cross country line-to-earth fault and a tripof the L1 phase has failed.
Phase preference logicIn compensated earthing systems, phase preference logic is used to achieve the correctphase selective tripping during two simultaneous single phase earth faults in differentphases on different line sections.
Due to compensated earthing, the earth faults in these systems involve very low faultcurrents, typically below 25A. At the same time, the system voltage on the healthyphase increases to phase-to-phase voltage level since the neutral displacement is equalto the phase voltage level at a fully developed earth fault. Increase of the healthy phase
Section 7 1MRK 506 375-UEN -Impedance protection
94 Railway application RER670 2.2 IECApplication manual
voltage together with slow tripping increases the risk a second fault in a healthy phaseand the second fault can occur at any location.
UL1'UL2'
IEC15000382-2-en.vsdx
2U0
UL2 UL1
IEC15000382 V2 EN
Figure 37: Phase preference logic
The phase preference logic is mainly used in systems where the single phase-to-earthfaults are not automatically cleared, only alarm is given and the fault remains until asuitable time to send people to track down and repair the fault. When the cross countryfault occurs, the practice is to trip only one of the faulty lines. Alternatively, theresidual earth fault protection is used to trip both lines. But due to the low faultcurrents, long tripping times are used.
Phase preference logic is used to decide the tripping mode for distance protection andthe following two selection modes are provided:
• Equal priority• L1 before L2
The typical waveform of recovery voltage following arc extinction (earth faults) incompensated earthing systems is shown in Figure 38. The resonance establishedbetween the capacitance of system and inductance of Petersen coil delays the recoveryvoltage build up after arc extinction. The resonance enables the dielectric strength ofthe insulation at the point of fault to recover and prevent restriking of the arc. Hence,special care has to be taken in clearing earth faults in compensated earthed systems.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 95Application manual
IEC15000383-1-en.vsdx
10
5
0
- 5
- 10
0 50 100 150 200 250
Time (mS) Time (mS)
IEC15000383 V1 EN
Figure 38: Recovery voltage after arc extinction
Three situations are possible when a cross country double earth fault occurs in thesystem:
• Line L1 is tripped, voltage on line L2 recovers after a while, the distance andresidual current protections reset.
• Line L1 is tripped, voltage on line L2 recovers after a while, the distance andresidual current protections reset, line L2 restrikes immediately after the reset.
• Line L1 is tripped, voltage on line L2 does not recover, the distance and/orresidual current protections does not reset.
After tripping the line with fault on phase L1, wait for a while to make sure that thevoltage on L2 has recovered and the distance and residual protection functions havereset, refer to Figure 38. The time delay to detect cross country fault is normally (0.1- 0.15)s.
After the above event, another restrike occurs on L2, the voltage on L1 increases andthe distance or residual current protection operates again. To confirm that the faultexists on phase L2, phase-to-earth voltage of L1 will be checked. Normally in acompensated earthing system, the change in measured voltage is big if fault persistson L2 and is typically 70% UB.
The voltage function has a reset drop-off about 0.1s to ensure the correct functionwithout timing problems.
Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that hasbeen set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.
Section 7 1MRK 506 375-UEN -Impedance protection
96 Railway application RER670 2.2 IECApplication manual
The default values given should be validated for each application and adopt theappropriate setting values.
The parameters for ZRWPDIS are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.
General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).
Operation: Sets the protection to On or Off.
System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).
LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.
IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.
RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:
max
2
min8.0P
URLd
IECEQUATION15051 V1 EN (Equation 20)
Where,
Pmax is the maximum exporting power
Umin is the minimum voltage for which Pmax can occur
0.8 is security factor.
ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 97Application manual
OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.
OpModetEnd1: It is used to select operation On or Off of the end zone 1.
OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.
tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.
OpModetEnd2: This is used to select the operation On or Off of the end zone 2.
OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.
tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.
OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.
ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.
StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).
Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.
X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.
RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.
RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.
Section 7 1MRK 506 375-UEN -Impedance protection
98 Railway application RER670 2.2 IECApplication manual
I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.
REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.
ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.
Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.
DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.
LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.
X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.
X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.
REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 99Application manual
RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.
RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.
RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.
RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.
TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.
tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.
OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.
tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.
Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.
DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.
LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.
Section 7 1MRK 506 375-UEN -Impedance protection
100 Railway application RER670 2.2 IECApplication manual
X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.
X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.
REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.
RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.
tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.
tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.
DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 101Application manual
PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.
LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.
X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.
X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.
REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.
RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.
tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.
Section 7 1MRK 506 375-UEN -Impedance protection
102 Railway application RER670 2.2 IECApplication manual
tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.
DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.
PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.
LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.
X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.
X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.
RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.
RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus fault
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 103Application manual
resistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.
tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.
OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.
tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.
Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.
DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.
LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.
X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.
X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.
REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
Section 7 1MRK 506 375-UEN -Impedance protection
104 Railway application RER670 2.2 IECApplication manual
RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.
RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.
RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.
TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.
tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.
tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.
DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.
LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due toremote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.
X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 105Application manual
X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.
RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.
RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.
tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.
tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
Phase SelectionModePhSelKI: This setting is used to enable/disable current ratio of the phasecurrents. The default setting is Off.
KI: The current ratio of phase currents used for phase selection. The recommendedsetting is 2.0.
tI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.
If magnitude of the phase L1 current is more than KI times magnitude of phase L2current together with delayed residual overcurrent start signal and ModePhSelKI is set
Section 7 1MRK 506 375-UEN -Impedance protection
106 Railway application RER670 2.2 IECApplication manual
to Off, the L1E loop will be released for distance measuring. This is valid for phase L2as well.
Phase selection based on residual overcurrent start is done only if the stub mode is notselected. This means that the setting ModeStubline is set to Off and there are no outputsfrom the underimpedance starting loops.
I01: This setting is used to detect the high short circuit current during the blocking timetI01 when starting element impedance loop has picked up. A default setting of 300%IB is used.
tI01: This is used as the blocking time of distance measuring for the transient earthfault. A default setting of 0.1s is used.
The underimpedance start and residual overcurrent start operates in the event of anearth fault. Once the earth fault is detected, it is blocked for a set time delay tI01 toavoid tripping in any of the transient earth fault conditions. However, if the measuredcurrent in a phase exceeds the set value I01 and the respective underimpedance loophas also picked up, the distance measuring loop of that loop is released immediately.This is done in order to clear the high current faults instantaneously. Phase-to-phasefault loop is released if there is output from the under impedance starting and there isno residual overcurrent start output.
I0MinPhSel: This is the minimum current that should be present to detect a phase-to-phase fault. The recommended setting is 4.0% IB.
ModeI0StRel: This is used to release the L1E & L2E / L1L2 distance measuring loopsusing the residual overcurrent start. The default setting is L1E & L2E.
If magnitudes of both phase currents (IL1 and IL2) are almost equal or less than the setvalue I0MinPhSel, it indicates that a phase-to-phase fault has occurred in the system.At this condition, the measuring loops are enabled based on the setting modeModeI0StRel and the respective loops will be released for distance measuring.
Phase preference
The time steps from t0L2 to t6L2 listed below can be selected bysettings OpModet0L2 to OpModet6L2 for stub line and each distancezone 1 to zone 6 respectively.
For faults on phase L2, after distance and direction decision is fulfilled, an alarm willappear and the additional timers t1L2 to t6L2 will start. If the starting element is resetbefore the expiry of (and therefore before trip) the zone timers tPEZx plus basic timetGL2, the UL1E will be checked against a set limit UL1E < U0Min at the end of 100msafter the reset of starting element.
The basic time tGL2 is effective only during the underimpedance or residualovercurrent start. If the voltage UL1E is greater than the set limit U0Min, the startsignal is maintained. A trip will occur if the voltage UL1E does not fall below the setlimit by the end of extra time t1L2 to t6L2 that are assigned to the respective zones.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 107Application manual
ModePhPref: In compensated earthed systems, phase L2 will be specially treated.Two operation modes i.e. Equal priority and L1 before L2 of phase preference variantsare implemented. The default is set to Equal priority.
OpModet0L2: This is used for Off/On operation of the t0L2 timer if phase preferenceis set.
t0L2: This is an additional time delay to the trip phase L2 in stub line.
OpModet1L2: This is used for Off/On operation of the t1L2 timer if phase preferenceis selected. The default setting is On.
t1L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 1. The default setting is 1.5s.
OpModet2L2: This is used for Off/On operation of the t2L2 timer if phase preferenceis selected. The default setting is Off.
t2L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 2. The default setting is 2.5s.
OpModet3L2: This is used for Off/On operation of the t3L2 timer if phase preferenceis selected. The default setting is Off.
t3L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 3. The default setting is 0.0s.
OpModet4L2: This is used for Off/On operation of the t4L2 timer if phase preferenceis selected. The default setting is Off.
t4L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 4. The default setting is 0.0s.
OpModet5L2: This is used for Off/On operation of the t5L2 timer if phase preferenceis selected. The default setting is Off.
t5L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 5. The default setting is 0.0s.
OpModet6L2: This is used for Off/On operation of the t6L2 timer if phase preferenceis selected. The default setting is Off.
t6L2: This is an additional time delay to trip phase L2 if the phase preference is set totrip phase L2 in zone 6. The default setting is 0.0s.
U0Min: This is used to check the minimum residual voltage on phase L1 if the startsignal falls back, and indicates the fault on phase L2 is cleared successfully. Thedefault value is 50% UBase.
tVL2: This is used to extend the time for phase L2 to check the voltage shift. For thetimes from t0L2 to t6L2, a settable time tVL2 (operation time extension L2) is added.
Section 7 1MRK 506 375-UEN -Impedance protection
108 Railway application RER670 2.2 IECApplication manual
When a cross country fault occurs and the phase L1 has tripped, wait for some time toensure that:
• The fault on phase L2 is cleared successfully• The voltage on phase L2 has recovered• The distance and residual protection functions have reset.
OpModetGL2: This is used for Off/On operation of an additional timer tGL2 used inthe compensated earthed network. The default setting is On.
tGL2: This is an additional time delay to trip L2 in compensated earthing. If the startsignal continues to be active, trip is given after expiration tPEZx plus tGL2. Thedefault setting is 0.6s.
dUOverdt: This is the rate of change of voltage for phase L1 and phase L2. When thepriority L1 before L2 is selected, the time steps t1L2, t2L2, t3L2, t4L2, t5L2 and t6L2are extended by tVL2. During trip time of the corresponding zone, a normalization ofthe supply voltage can be identified (i.e. dUL1/dt < dUOverdt and dUL2/dt>dUOverdt). If a restrike of the earth fault is detected during the tVL2 time (i.e. dUL1/dt > dUOverdt, dUL2/dt < dUOverdt), an instantaneous trip will be issued.Calculation of algorithm for both voltage step functions dUL1/dt and dUL2/dt is setwith a common parameter dUOverdt. The default setting is 100 V/s.
Stub lineModeStubLine: This is used to enable/disable the compensated network contains astub line.
UPPMin: This is the minimum phase-to-phase voltage in %UB in case of a stub line.This is considered before deciding to trip the line that has lower phase-to-earthvoltage. The default setting is 80% UB.
tI0Stub: Time delay to trip for residual current in case of a stub line. The default settingis 0.2s.
KU: This is the phase-to-earth voltage ratio in case of a stub line.
7.2.2.2 Solidly earthed systems
In directly earthed networks, a distinction is made between the following types offaults:
• Double phase-to-phase fault, earthed or unearthed• Single phase-to-earth fault
The fault currents are high during all short circuit events. In the event of high-resistance earth faults, e.g. through trees, the earth current is low. These types of faultsshall be detected and tripped selectively by a sensitive earth-fault detection device inconjunction with protection signaling devices.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 109Application manual
Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that hasbeen set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.
The default values given should be validated for each application and adopt theappropriate setting values.
The parameters for ZRWPDIS are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.
General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).
Operation: Sets the protection to On or Off.
System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).
LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.
IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.
RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:
max
2
min8.0P
URLd
IECEQUATION15051 V1 EN (Equation 21)
Where,
Pmax is the maximum exporting power
Umin is the minimum voltage for which Pmax can occur
Section 7 1MRK 506 375-UEN -Impedance protection
110 Railway application RER670 2.2 IECApplication manual
0.8 is security factor.
ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.
OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.
OpModetEnd1: It is used to select operation On or Off of the end zone 1.
OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.
tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.
OpModetEnd2: This is used to select the operation On or Off of the end zone 2.
OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.
tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.
OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.
ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.
StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).
Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.
X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.
RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 111Application manual
RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.
I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.
REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.
ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.
Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.
DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.
LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.
X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.
X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.
Section 7 1MRK 506 375-UEN -Impedance protection
112 Railway application RER670 2.2 IECApplication manual
REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.
RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.
RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.
RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.
TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.
tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.
OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.
tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.
Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.
DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 113Application manual
LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.
X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.
X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.
REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.
RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.
tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.
tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
Section 7 1MRK 506 375-UEN -Impedance protection
114 Railway application RER670 2.2 IECApplication manual
Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.
DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.
LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.
X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.
X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.
REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.
RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 115Application manual
tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.
tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.
DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.
PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.
LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.
X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.
X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.
RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus fault
Section 7 1MRK 506 375-UEN -Impedance protection
116 Railway application RER670 2.2 IECApplication manual
resistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.
RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.
tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.
OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.
tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.
Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.
DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.
LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.
X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.
X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 117Application manual
REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.
RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.
RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.
TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.
tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.
tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.
DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.
LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due to
Section 7 1MRK 506 375-UEN -Impedance protection
118 Railway application RER670 2.2 IECApplication manual
remote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.
X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.
X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.
RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.
RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.
tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.
tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
Phase selectiontI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 119Application manual
7.2.2.3 High impedance earthing systems
In isolated/high impedance networks, following types of errors can be anticipated:
• 2-phase short circuit, with or without earth connection• Single phase-to-earth fault• cross country double earth faults
For double earth faults, the disconnection by the distance measurement should beselective.
For single phase earth fault in isolated systems, voltage shifts occur and a smallcapacitive current generates. Trip will occur after a time delay. In an isolated neutralsystem, the neutral has no intentional connection to earth. The system is connected toearth through the phase-to-earth capacitances. Single phase-to-earth faults will shiftthe system neutral voltage.
Earth fault
IEC15000384-1-en.vsdx
IEC15000384 V1 EN
Figure 39: Earth fault in isolated systems
Two major earth fault-current limiting factors are possible for the isolated earthingsystems; the zero sequence phase-to-earth capacitance and fault resistance. Since thevoltage and their phase angles are relatively undisturbed, these systems can remainoperational during the sustained low magnitude faults.
Self-extinction of earth faults in the overhead lines is possible for the low values ofearth fault current. At higher magnitudes of fault current, faults are unlikely to self-extinguish at the natural zero crossing of fault current because of the high transientrecovery voltage.
The zero sequence voltage relays can detect earth faults in the isolated systems. Thismethod of fault detection is not selective and requires sequential disconnection orisolation of the feeders to determine the faulted feeder.
Setting guidelinesThe settings for 2-phase Distance protection zones, quadrilateral characteristic(ZRWPDIS) are done in primary values. The instrument transformer ratio that has
Section 7 1MRK 506 375-UEN -Impedance protection
120 Railway application RER670 2.2 IECApplication manual
been set for the analog input card is used to automatically convert the measuredsecondary input signals to primary values used in ZRWPDIS.
The default values given should be validated for each application and adopt theappropriate setting values.
The parameters for ZRWPDIS are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a global base values for settings functionGBASVAL.
General settingsGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).
Operation: Sets the protection to On or Off.
System Earthing: It is used to select the type of system earthing (i.e. Compensated,Solidly and High impedance).
LineAng: This is to used set the distance protection characteristic angle. It should beset to line angle of the protected transmission line. The default value is 75 deg.
IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. If the minimum current is exceeded, the distance protection calculates theimpedance. The default setting is 10% IB.
OpLoadEnch: This setting is used to select the load discrimination characteristicoperation to On or Off. The default value is Off.
RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. This setting can be calculated according to equation:
max
2
min8.0P
URLd
IECEQUATION15051 V1 EN (Equation 22)
Where,
Pmax is the maximum exporting power
Umin is the minimum voltage for which Pmax can occur
0.8 is security factor.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 121Application manual
ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. The default value is set at 30 deg.
OpModeI0: This is used to select the operation On or Off of the end zone timer logicusing residual overcurrent start to provide a remote backup.
OpModetEnd1: It is used to select operation On or Off of the end zone 1.
OpDirEnd1: This is used to select the direction mode of end zone 1. It can be set toNon-directional, Forward and Reverse. It is recommended to set as Forward.
tEnd1: This is used to set time delay for the first stage remote backup. The settingshould allow the farthest zone to operate. The default setting is 2.5s.
OpModetEnd2: This is used to select the operation On or Off of the end zone 2.
OpDirEnd2: This is used to select the direction mode of the end zone 2. It can be set toNon-directional, Forward and Reverse. It is recommended to set this as Non-directional.
tEnd2: This is used to set the time delay for the second stage trip. It should be set incoordination with the tEnd1 timer. The default setting is 3.0s.
OpModeGenSt: This is used to select On or Off of zone timers start by general startsignal. The default value is Off.
ZoneCharSym: This is used to select measuring zone Symmetry/Nonsymmetry aroundR – X plane and it is set by default to Symmetry. With this default value, it is notpossible to set resistive and reactance reaches in reverse direction. However, if it isneeded to specify the reverse reaches depending on the application, it is recommendedto set this parameter to Nonsymmetry.
StartCharStartZ<: It is used to select the underimpedance start characteristic (i.e. Circularand Quadrilateral).
Z1CircleStart: This is used to set a positive sequence impedance reach in Ohm of thestarting element circular characteristic. It will be set to operate for all faults within theprotected area. Therefore, it should be set beyond the reach of the farthest zone.
X1Start: This is to set positive sequence reactance reach in Ohm of starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea. Therefore, it should be set beyond the reach of the farthest zone.
RFPEStart: This is used to set the forward and reverse resistive reach in Ohm for PEstarting element when the quadrilateral characteristic is selected. It will be set to avalue greater than the resistive reach of the farthest zone.
RFPPStart: This is used to set the forward and reverse resistive reach in Ohm for PPstarting element when the quadrilateral characteristic is selected. It will be set to a
Section 7 1MRK 506 375-UEN -Impedance protection
122 Railway application RER670 2.2 IECApplication manual
value greater than the resistive reach of the farthest zone. It is not applicable forcompensated and high impedance earthed systems.
I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. It should be set to detect all earth faults, but above any continuous residualcurrent under normal operating conditions. The default value is 10% IB.
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. The default setting is 0.8.
REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element. It is not applicable for compensated and high impedanceearthed systems.
DirectionArgNegRes: This is the angle for blinder in the second quadrant. The default setting is120 deg and it should not be changed unless system studies show the necessity.
ArgDir: This is the angle of setting in the fourth quadrant. The default setting is 15 degand it should not be changed unless system studies show the necessity.
Zone 1OpZ1: This is used for the Off/On operation of zone 1 and it is set to On by default.
DirModeZ1: This is used to set the zone 1 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ1: This is used to enable the measuring loops of zone 1. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.The default setting is Off.
LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. The default setting is Off.
X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. It should be set so that it never overreaches the protected line. Therecommended setting is 80% of the protected line length.
X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. It may be set identical to X1FwZ1.
REoverRLZ1: This is used to set the earth return compensation factor for resistance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 123Application manual
XEoverXLZ1: This is used to set the earth return compensation factor for reactance ofzone 1. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ1: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 1. It should be set to give maximum coverage consideringthe line resistance, arc resistance and tower footing resistance. In general, resistivereach should be set to give maximum coverage subject to check possibility againstload point encroachment considering minimum expected voltage and maximum load.In case of short lines, consideration has to be given to overreach due to remote endinfeed and reach in resistance direction is restricted.
RFPERvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 1. It may be set identical to RFPEFwZ1.
RFPPFwZ1: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It should be set to cover the arc resistance for phase-to-phasefaults.
RFPPRvZ1: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 1. It may be set identical to RFPPFwZ1.
TimerSelZ1: This is used to set the zone timer selection mode of zone 1. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ1: This is used to set the Off/On operation of the phase-to-earth timer ofzone 1. The default setting is Off.
tPEZ1: This is used to set the time delay to trip for phase-to-earth faults in zone 1. Thedefault setting is 0.0s.
OpModetPPZ1: This is used to set the Off/On operation of the phase-to-phase timer ofzone 1. The default setting is Off.
tPPZ1: This is used to set the time delay to trip for phase-to-phase faults in zone 1. Thedefault setting is 0.0s.
Zone 2OpZ2: This is used for the Off/On operation of zone 2 and it is set to Off by default.
DirModeZ2: This is used to set the zone 2 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ2: This is used to enable the measuring loops of zone 2. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.The default setting is Off.
LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. It avoids overreaching of the zone in to the next section in case of resistive fault
Section 7 1MRK 506 375-UEN -Impedance protection
124 Railway application RER670 2.2 IECApplication manual
due to remote end feed. Generally, this setting is not needed for zone 2. The defaultsetting is Off.
X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. The zone should never underreach the next section. The recommendedsetting is 120% of the protected line length. Impact of the mutual coupling should beconsidered for the double circuit lines.
X1RvZ2: This is used to set the reverse positive sequence impedance reach of zone 2in Ohm/p. It may be set identical to X1FwZ2.
REoverRLZ2: This is used to set the earth return compensation factor for resistance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ2: This is used to set the earth return compensation factor for reactance ofzone 2. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ2: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 2. This may be set identical to zone 1 setting.
RFPPFwZ2: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
RFPPRvZ2: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ2: This is used to set the Off/On operation of the phase-to- earth timer ofzone 2. The default setting is Off.
tPEZ2: This is used to set the time delay to trip for phase-to-earth faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
OpModetPPZ2: This is used to set the Off/On operation of the phase-to-phase timer ofzone 2. The default setting is Off.
tPPZ2: This is used to set the time delay to trip for phase-to-phase faults in zone 2. Itshould be set to coordinate with the clearance of adjacent circuit fault with in reach bythe intended main protection or breaker fail protection. The default setting is 0.4 s.
Zone 3OpZ3: This is used for the Off/On operation of zone 3 and it is set to Off by default.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 125Application manual
DirModeZ3: This is used to set the zone 3 direction mode. It can be set to Non-directional, Forward and Reverse. The Forward direction mode is set by default.
PhSelModeZ3: This is used to enable the measuring loops of zone 3. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.The default setting is Off.
LCModeZ3: This is used to enable/disable the adaptive load compensation mode ofzone 3. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 3. The defaultsetting is Off.
X1FwZ3: This is used to set the forward positive sequence reactance reach of zone 3in Ohm/p. It should be set to overreach the remote terminal of the longest adjacent lineby 20% for all fault conditions.
X1RvZ3: This is used to set the reverse positive sequence impedance reach of zone 3in Ohm/p. It may be set identical to X1FwZ3.
REoverRLZ3: This is used to set the earth return compensation factor for resistance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ3: This is used to set the earth return compensation factor for reactance ofzone 3. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ3: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistivereach.
RFPERvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-earth faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPFwZ3: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
RFPPRvZ3: This is used to set the reverse fault resistive reach in Ohm/p for phase-to-phase faults in zone 3. This may be set identical to zone 2 setting resistive reach.
TimerSelZ3: This is used to set the zone timer selection mode of zone 3. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ3: This is used to set the Off/On operation of the phase-to-earth timer ofzone 3. The default setting is Off.
tPEZ3: This is used to set the time delay to trip for phase-to-earth faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
Section 7 1MRK 506 375-UEN -Impedance protection
126 Railway application RER670 2.2 IECApplication manual
OpModetPPZ3: This is used to set the Off/On operation of the phase-to-phase timer ofzone 3. The default setting is Off.
tPPZ3: This is used to set the time delay to trip for phase-to-phase faults in zone 3. Itshould be set so that it provides discrimination with the operating time of relaysprovided in subsequent sections which zone 3 reach of relay being set, overlaps. Thedefault setting is 0.7 s.
Zone 4OpZ4: This is used for the Off/On operation of zone 4 and it is set to Off by default. Thiscan be used as reverse zone.
DirModeZ4: This is used to set the zone 4 direction mode. It can be set to Non-directional, Forward and Reverse.
PhSelModeZ4: This is used to enable the measuring loops of zone 4. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ4: This is used to operate the load discrimination characteristic of zone 4.The default setting is Off.
LCModeZ4: This is used to enable/disable the adaptive load compensation mode ofzone 4. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 4. The defaultsetting is Off.
X1FwZ4: This is used to set the forward positive sequence reactance reach of zone 4in Ohm/p. It may be set identical to X1RvZ4.
X1RvZ4: This is used to set the reverse positive sequence impedance reach of zone 4in Ohm/p. It should be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ4: This is used to set the earth return compensation factor for resistance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ4: This is used to set the earth return compensation factor for reactance ofzone 4. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ4: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 4. This may be set identical to RFPERVZ4.
RFPERvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should cover apparent phase-to-earth bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
RFPPFwZ4: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 4. This may be set identical to RFPPRVZ4.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 127Application manual
RFPPRvZ4: This is used to cover the zone 4 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase bus faultresistance allowing for multiple infeed from other circuits. Therefore, it should be setidentical to zone 3 resistive reach setting.
TimerSelZ4: This is used to set the zone timer selection mode of zone 4. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ4: This is used to set the Off/On operation of the phase-to-earth timer ofzone 4. The default setting is Off.
tPEZ4: This is used to set the time delay to trip for phase-to-earth faults in zone 4. Itshould be set identical to zone 2 timer setting.
OpModetPPZ4: This is used to set the Off/On operation of the phase-to-phase timer ofzone 4. The default setting is Off.
tPPZ4: This is used to set the time delay to trip for phase-to-phase faults in zone 4. Itshould be set identical to zone 2 timer setting.
Zone 5OpZ5: This is used for the Off/On operation of zone 5 and it is set to Off by default. ThisZone can be used for the permissive overreach scheme along with a communicationchannel.
DirModeZ5: This is used to set the zone 5 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ5: This is used to enable the measuring loops of zone 5. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ5: This is used to operate the load discrimination characteristic of zone 5.The default setting is Off.
LCModeZ5: This is used to enable/disable the adaptive load compensation mode ofzone 5. It avoids overreaching of the zone in to the next section in case of resistive faultdue to remote end feed. Generally, this setting is not needed for zone 5. The defaultsetting is Off.
X1FwZ5: This is used to set the forward positive sequence reactance reach of zone 5in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.
X1RvZ5: This is used to set the reverse positive sequence impedance reach of zone 5in Ohm/p. It may be set identical to X1FwZ5.
REoverRLZ5: This is used to set the earth return compensation factor for resistance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ5: This is used to set the earth return compensation factor for reactance ofzone 5. It provides zero sequence compensation for phase-to-earth faults.
Section 7 1MRK 506 375-UEN -Impedance protection
128 Railway application RER670 2.2 IECApplication manual
RFPEFwZ5: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults in zone 5. This may be set identical to zone 1 setting. In case ofpermissive overreach schemes used for short lines, this has to be set higher than zone1 resistive reach.
RFPERvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It may be set identical to zone 1 setting.
RFPPFwZ5: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults in zone 5. It may be set identical to zone 1 setting.
RFPPRvZ5: This is used to cover the zone 5 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It may be set identical to zone 1 setting.
TimerSelZ5: This is used to set the zone timer selection mode of zone 5. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ5: This is used to set the Off/On operation of the phase-to-earth timer ofzone 5. The default setting is Off.
tPEZ5: This is used to set the time delay to trip for phase-to-earth faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
OpModetPPZ5: This is used to set the Off/On operation of the phase-to-phase timer ofzone 5. The default setting is Off.
tPPZ5: This is used to set the time delay to trip for phase-to-phase faults in zone 5. Itshould be set identical to zone 2/zone 3 timer setting.
zone 6OpZ6: This is used for the Off/On operation of zone 6 and it is set to Off by default. Thiszone can be used to provide switch on to fault protection.
DirModeZ6: This is used to set the zone 6 direction mode. It can be set to Non-directional, Forward and Reverse. The default setting is Forward direction mode.
PhSelModeZ6: This is used to enable the measuring loops of zone 6. It can be set toPhsel logic, Release L1E, ReleaseL2E, Release PE, Release L1L2 and ReleasePE&PP modes. The default setting is Phsel logic mode.
LEModeZ6: This is used to operate the load discrimination characteristic of zone 6.The default setting is Off.
LCModeZ6: This is used to Off/On the adaptive load compensation mode of zone 6. Itavoids overreaching of the zone in to the next section in case of resistive fault due toremote end feed. Generally, this setting is not needed for zone 6. The default setting isOff.
X1FwZ6: This is used to set the forward positive sequence reactance reach of zone 6in Ohm/p. It may be set identical to zone 2 reach setting.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 129Application manual
X1RvZ6: This is used to set the reverse positive sequence impedance reach of zone 6in Ohm/p. It may be set less than zone 1 reach of distance protection for the shortestline in the reverse direction.
REoverRLZ6: This is used to set the earth return compensation factor for resistance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ6: This is used to set the earth return compensation factor for reactance ofzone 6. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ6: This is used to set the forward fault resistive reach in Ohm/p for thephase-to-earth faults of zone 6. It may be set identical to zone 2 resistive reach setting.
RFPERvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-earth faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
RFPPFwZ6: This is used to set the forward fault resistive reach in Ohm/p for phase-to-phase faults of zone 6. It should be set identical to zone 2 resistive reach setting.
RFPPRvZ6: This is used to cover the zone 6 fault resistive reach in Ohm/p for phase-to-phase faults in reverse direction. It should be set identical to zone 2 resistive reachsetting.
TimerSelZ6: This is used to set the zone timer selection mode of zone 6. i.e. Timersseparated, Timers linked, General start, PhSel start, Internal start and External start.The default setting is Timers separated.
OpModetPEZ6: This is used to set the Off/On operation of the phase-to-earth timer ofzone 6. The default setting is Off.
tPEZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
OpModetPPZ6: This is used to set the Off/On operation of the phase-to-phase timer ofzone 6. The default setting is Off.
tPPZ6: This is used to set the time delay to trip for phase-to-earth faults in zone 6. Itshould be set to 0.0 s.
Phase SelectiontI0: Delay time for the residual overcurrent start. Residual overcurrent start is delayedby settable time delay tI0. The default setting is 0.2s.
ModeU0DetMin: This is used to enable/disable the neutral voltage shift protection.The default setting is Off.
U0DetMin: This is used to set the minimum operate value for the neutral voltage shift.The default value is 20% UB.
Section 7 1MRK 506 375-UEN -Impedance protection
130 Railway application RER670 2.2 IECApplication manual
UDispOpModeU0: This is used for the Off/On operation of the neutral voltage displacementlogic. The default value is Off.
UMinDisp: This is used to check the neutral voltage displacement for single phase-earth-faults occur in the system. The default setting is 150% UB.
tU0: This is the time delay to trip for the neutral voltage displacement start. The defaultvalue is 5.0s.
7.2.3 Setting examples
7.2.3.1 Compensated earthed systems
Example in Figure 40 illustrates how the distance protection ZRWPDIS protects a110kV overhead transmission line. The earthing considered is compensated earthedsystem.
Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 areconsidered in this example. Zones 4, 5 and 6 can be set on similar lines depending onthe application they are being used.
All the settings for impedance are in Ohms Primary.
Z<
A B C
Line 1 Line 2
IEC15000385-1-en.vsdx
IEC15000385 V1 EN
Figure 40: Considered single line diagram
Table 15: System Data
Parameter ValueSystem Voltage 110kV
System Frequency 16.7Hz
Full load 50MVA
Short time maximum Power 250% of Full load
Minimum operating voltage 90% of rated voltage
PT Ratio 110kV/110V
CT Ratio 600/1A
Line length A-B 50km
Line length B-C 100km
Positive sequence impedance of line 0.097 + j0.112 Ohm/km = 0.1481 ∟ 49.3° Ohm/km
Table continues on next page
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 131Application manual
Parameter ValueZero sequence impedance of line 0.151 + j0.298 Ohm/km = 0.334 ∟ 63.13° Ohm/km
Arc resistance 2 Ohm
Tower footing resistance 10 Ohm
GeneralCommon base IED values for primary current (IBase) and primary voltage (UBase)are set in a Global base values for settings function GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
IBase: Sets the base current in primary ampere. This is 50MVA/110kV = 454.54A.
UBase: Sets the base voltage in kV. This is 110.0kV.
Operation: Sets the protection to On/Off. Set this to On.
System Earthing: It is used to select the type of system earthing. Select theCompensated.
LineAng: Set it to 50 deg.
IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. Set this to 10% IB.
IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. Set this to 10% IB.
OpLoadEnch: This setting is used to select the load discrimination characteristic. Setthis to On.
RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. RLd can be calculated according to equation:
max
2
min8.0P
URLd
IECEQUATION15051 V1 EN (Equation 23)
Where,
Pmax is the maximum exporting power = 2.5 times the rated power of 50MVA.
Umin is the minimum voltage which can be taken as 90% of 110.0kV which is equalto 99kV.
0.8 is security factor.
Therefore RLd = 0.8 (99.0)2 /2.5 x 50.0 = 62.7 Ohm.
Section 7 1MRK 506 375-UEN -Impedance protection
132 Railway application RER670 2.2 IECApplication manual
ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. Set this to 30 deg.
OpModetEnd1: It is used to select the On/Off operation of the first stage timer tEnd1.Set this to On.
OpDirEnd1: This is used to select the direction mode of end zone 1. Set this toForward.
tEnd1: This is used to set time delay for the first stage remote backup. Set this higherthan zone 3 time delay of 0.7s plus additional delays provided. Set this to the default2.5s.
OpModetEnd2: This is used to select the operation On/Off of the second stage timertEnd2. Set this to On.
OpDirEnd2: This is used to select the direction mode of the end zone 2. Set this toNon-directional.
tEnd2: This is used to set the time delay for the second stage trip. Set this after thetEnd1 has operated. Since the tEnd1 is set to 2.5s, set it to 3.0s.
OpModeGenSt: This is used to select On/Off of zone timers start by general startsignal. Set this to On.
ZoneCharSym: This is used to set On/Off of the zone symmetry. Set this to Symmetry.
StartCharStartZ<: It is used to select the underimpedance start characteristic. Set this toQuadrilateral.
X1Start: This is to set positive sequence reactance reach of the starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea.
Therefore, set the X1Start to 150% of zone 3 reach. Zone 3 reach being 20.16 Ohm, setX1Start to 1.5 x 20.16 = 30.24 Ohm.
RFPEStart: This is used to set the forward and reverse resistive reach for PE startingelement. It will be set to operate for all faults within the protected area. To providemaximum coverage for the high resistive faults, it may be set as high as possiblesubject to check of possibility against load point encroachment.
Therefore, set this to 80% of the setting RLd resistive reach of the starter. The settingRLd being 62.7 Ohm, the RFPEStart can be set to 0.8 x 62.7 = 50.16 Ohm.
I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. Set this to 10% IB.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 133Application manual
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. Set this to 0.8.
DirectionArgNegRes: This is the angle for blinder in the second quadrant. Set this to 120 deg.
ArgDir: This is the angle of setting in the fourth quadrant. Set this to 15 deg.
Zone 1OpZ1: Set this to On.
DirModeZ1: This is used to set the zone 1 direction mode. Set this to Forward.
PhSelModeZ1: This is used to enable the measuring loops of zone 1. Set this to Phsellogic.
LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.Set this to On.
LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. Set this to On.
X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. The recommended setting is 90% of the protected line length.
Therefore, set the X1FwZ1 to 0.9 x 50.0 x 0.112 = 5.6 Ohm.
REoverRLZ1: It provides zero sequence compensation for phase-to-earth faults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 24)
Therefore, set this to 0.28.
XEoverXLZ1: It provides zero sequence compensation for phase-to-earth faults.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 25)
Therefore, set this to 0.83.
RFPEFwZ1: It should be set to give maximum coverage considering the arc resistanceand tower footing resistance.
Arc resistance = 2 Ohm primary and Tower footing resistance = 10 Ohm Primary.Therefore, RFPEFwZ1 should be minimum of 12 Ohm.
Since the RFPEStart is set to 50.16 Ohm to give more resistive coverage, RFPEFwZ1can be set at 0.8 x 50.16 = 40.13 Ohm. However, to avoid overreach due to the remote
Section 7 1MRK 506 375-UEN -Impedance protection
134 Railway application RER670 2.2 IECApplication manual
end infeed, it is recommended that the resistive reach does not exceed 4.5 timesreactive reach.
Therefore, RFPEFwZ1 may be set to 4.5 x X1FwZ1 = 4.5 x 5.6 = 25.52 Ohm.
RFPPFwZ1: It should be set to cover the arc resistance for phase-to-phase faults. Itmay be set identical to RFPEFwZ1, which is 25.52 Ohm.
TimerSelZ1: This is used to set the zone timer selection mode of zone 1. Set this toTimers Separated.
OpModetPEZ1: Set this to On.
tPEZ1: Set this to 0.0s.
OpModetPPZ1: Set this to On.
tPPZ1: Set this to 0.0s.
Zone 2OpZ2: Set this to On.
DirModeZ2: This is used to set the zone 2 direction mode. Set this to Forward.
PhSelModeZ2: This is used to enable the measuring loops of zone 2. Set this to Phsellogic.
LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.Set this to On.
LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. Set this to Off.
X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. This should be set to 120% of line 1 reactance.
Therefore, set the X1FwZ2 to 1.2 x 50 x 0.112 = 6.72 Ohm.
REoverRLZ2: It provides zero sequence compensation for phase-to-earth faults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 26)
Therefore, set this to 0.28.
XEoverXLZ2: It provides zero sequence compensation for phase-to-earth faults.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 27)
Therefore, set this to 0.83.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 135Application manual
RFPEFwZ2: It should be set to give maximum coverage considering the maximumpermissible load.
Since the RFPEFwStart is set to 50.16 Ohm to give more resistive coverage,RFPEFwZ2 can be set at 0.8 x 50.16 = 40.13 Ohm.
RFPPFwZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. Set this toTimers Separated.
OpModetPEZ2: Set this to On.
tPEZ2: Choose a time delay for zone 2 with margin to assure selectivity to zone 1 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient.Therefore, the time delay for zone 2 can be set to 0.4s.
OpModetPPZ2: Set this to On.
tPPZ2: Set this identical to tPEZ2, which is 0.4s.
Zone 3OpZ3: This is for operation Off/On of zone 3. Set this to On.
DirModeZ3: This is used to set the zone 3 direction mode. Set this to Forward.
PhSelModeZ3: This is used to enable the zone 3 measuring loops. Set this to Phsellogic.
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.Set this to On.
LCModeZ3: This is used to enable/disable load compensation mode for zone 3. Setthis to Off.
X1FwZ3: This is used to set the forward positive sequence reactance reach for zone 3in Ohm/p. This should be set to 120% of reactance of (Line 1 + Line 2).
Therefore, set X1FwZ3 to 1.2 x (50 +100) x 0.112 = 20.16 Ohm.
REoverRLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 28)
Therefore, set this to 0.28.
XEoverXLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.
Section 7 1MRK 506 375-UEN -Impedance protection
136 Railway application RER670 2.2 IECApplication manual
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 29)
Therefore, set this to 0.83.
RFPEFwZ3: This may be set identical to setting RFPEFwZ2 which is 40.13 Ohm.
RFPPFwZ3: This may be set identical to setting RFPEFwZ3 which is 40.13 Ohm.
TimerSelZ3: This is used for Zone timer selection mode of zone 3. Set this to Timersseparated.
OpModetPEZ3: Set this to On.
tPEZ3: Choose a time delay for zone 3 with a margin to assure selectivity to zone 2 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient. Thetime delay for zone 3 therefore can be set to 0.8s.
OpModetPPZ3: Set this to On.
tPPZ3: Set this identical to tPPZ3 = 0.8s.
Zones 4, 5 and 6 can be set on similar lines based on the application.
Phase selectionModePhSelKI: Set this to Off.
KI: Set this to 1.2.
I01: This setting is used to detect high short circuit current during blocking time tI01when starting element impedance loop has picked up. Set at 400% IB.
ModeI0StRel: Set this to L1E and L2E
I0MinPhSel: Set this to 4% IB.
tI0: This is delay time for residual overcurrent start. Residual overcurrent start isdelayed by settable time delay tI0. Set this to 0.2s.
tI01: This is blocking time of distance measuring for transient earth fault. Set this to0.1s.
Phase preferenceModePhPref: Set this to L1 before L2.
OpModet1L2: Set this to On.
t1L2: Set this to 1.0s.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 137Application manual
OpModet2L2: Set this to On.
t2L2: Set this to 2.0s.
OpModet3L2: Set this to On.
t3L2: Set this to 3.0s.
U0Min: This is used to check minimum residual voltage if start signal falls back. Setthis to 50% UB.
tVL2: This is used to extend the time for phase L2 to check the voltage shift. To timet0L2 to t6L2 is a settable time tVL2 (operation time extension L2) added. Set this to0.5s.
OpModetGL2: Set this to On.
tGL2: This is an additional time delay to trip L2 in compensated earthing. If the startsignal continues to be active, trip is given after expiration tPEZx plus tGL2. Set this to0.6s.
dUOverdt: Set this to 100V/s.
Stub lineModeStubLine: Set this to Off.
7.2.3.2 Solidly earthed systems
Example in Figure 41 illustrates how the distance protection ZRWPDIS protects a110kV overhead transmission line. The earthing considered is solidly earthed system.
Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 areconsidered in this example. Zones 4, 5 and 6 can be set on similar lines depending onthe application they are being used.
All the settings for impedance are in Ohms Primary.
Z<
A B C
Line 1 Line 2
IEC15000385-1-en.vsdx
IEC15000385 V1 EN
Figure 41: Considered single line diagram
Section 7 1MRK 506 375-UEN -Impedance protection
138 Railway application RER670 2.2 IECApplication manual
Table 16: System Data
Parameter ValueSystem Voltage 110kV
System Frequency 16.7Hz
Full load 50MVA
Short time maximum Power 250% of Full load
Minimum operating voltage 90% of rated voltage
PT Ratio 110kV/110V
CT Ratio 600/1A
Line length A-B 50km
Line length B-C 100km
Positive sequence impedance of line 0.097 + j0.112 Ohm/km = 0.1481 ∟ 49.3° Ohm/km
Zero sequence impedance of line 0.151 + j0.298 Ohm/km = 0.334 ∟ 63.13° Ohm/km
Arc resistance 2 Ohm
Tower footing resistance 10 Ohm
GeneralCommon base IED values for primary current (IBase) and primary voltage (UBase)are set in a Global base values for settings function GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
IBase: Sets the base current in primary ampere. This is 50MVA/110kV = 454.54A.
UBase: Sets the base voltage in kV. This is 110.0kV.
Operation: Sets the protection to On/Off. Set this to On.
System Earthing: It is used to select the type of system earthing. Select theCompensated.
LineAng: Set it to 50 deg.
IMinOpPE: It is used to select the minimum operating current for the phase-to-earthloops. Set this to 10% IB.
IMinOpPP: It is used to select the minimum operating current for the phase-to-phaseloops. Set this to 10% IB.
OpLoadEnch: This setting is used to select the load discrimination characteristic. Setthis to On.
RLd: It is used to set the resistive reach within the load impedance of loaddiscrimination characteristic. RLd can be calculated according to equation:
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 139Application manual
max
2
min8.0P
URLd
IECEQUATION15051 V1 EN (Equation 30)
Where,
Pmax is the maximum exporting power = 2.5 times the rated power of 50MVA.
Umin is the minimum voltage which can be taken as 90% of 110.0kV which is equalto 99kV.
0.8 is security factor.
Therefore RLd = 0.8 (99.0)2 /2.5 x 50.0 = 62.7 Ohm.
ArgLd: This is used to set the load angle determining the load impedance area of theload discrimination characteristic. Set the parameter to the maximum possible loadangle at maximum possible load. Set this to 30 deg.
OpModetEnd1: It is used to select the On/Off operation of the first stage timer tEnd1.Set this to On.
OpDirEnd1: This is used to select the direction mode of end zone 1. Set this toForward.
tEnd1: This is used to set time delay for the first stage remote backup. Set this higherthan zone 3 time delay of 0.7s plus additional delays provided. Set this to the default2.5s.
OpModetEnd2: This is used to select the operation On/Off of the second stage timertEnd2. Set this to On.
OpDirEnd2: This is used to select the direction mode of the end zone 2. Set this toNon-directional.
tEnd2: This is used to set the time delay for the second stage trip. Set this after thetEnd1 has operated. Since the tEnd1 is set to 2.5s, set it to 3.0s.
OpModeGenSt: This is used to select On/Off of zone timers start by general startsignal. Set this to On.
ZoneCharSym: This is used to set On/Off of the zone symmetry. Set this toNonsymmetry.
StartCharStartZ<: It is used to select the underimpedance start characteristic. Set this toQuadrilateral.
X1Start: This is to set positive sequence reactance reach of the starting elementquadrilateral characteristic. It will be set to operate for all faults within the protectedarea.
Section 7 1MRK 506 375-UEN -Impedance protection
140 Railway application RER670 2.2 IECApplication manual
Therefore, set the X1Start to 150% of zone 3 reach. Zone 3 reach being 20.16 Ohm, setX1Start to 1.5 x 20.16 = 30.24 Ohm.
RFPEStart: This is used to set the forward and reverse resistive reach for PE startingelement. It will be set to operate for all faults within the protected area. To providemaximum coverage for the high resistive faults, it may be set as high as possiblesubject to check of possibility against load point encroachment.
Therefore, set this to 80% of the setting RLd resistive reach of the starter. The settingRLd being 62.7 Ohm, the RFPEStart can be set to 0.8 x 62.7 = 50.16 Ohm.
RFPPStart: This is used to set the forward and reverse resistive reach for PP startingelement. This may be set equal to RFPEStart, which is 50.16 Ohm.
I0MinOp: This is the minimum operating current of residual overcurrent start as % ofIBase. Set this to 10% IB.
KI0Stab: The stabilizing factor to prevent operation of the residual overcurrent startcaused by an unbalance or dissimilar CT behaviour in the event of high short circuitcurrents. Set this to 0.8.
REOverRLStart: This is used to set the earth return compensation factor for resistanceof the starting element.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 31)
XEOverXLStart: This is used to set the earth return compensation factor for reactanceof the starting element.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 32)
DirectionArgNegRes: This is the angle for blinder in the second quadrant. Set this to 120 deg.
ArgDir: This is the angle of setting in the fourth quadrant. Set this to 15 deg.
Zone 1OpZ1: Set this to On.
DirModeZ1: This is used to set the zone 1 direction mode. Set this to Forward.
PhSelModeZ1: This is used to enable the measuring loops of zone 1. Set this to Phsellogic.
LEModeZ1: This is used to operate the load discrimination characteristic of zone 1.Set this to On.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 141Application manual
LCModeZ1: This is used to enable/disable the adaptive load compensation mode ofzone 1. Set this to On.
X1FwZ1: This is used to set the forward positive sequence reactance reach of zone 1in Ohm/p. The recommended setting is 90% of the protected line length.
Therefore, set the X1FwZ1 to 0.9 x 50.0 x 0.112 = 5.6 Ohm.
X1RvZ1: This is used to set the reverse positive sequence impedance reach of zone 1in Ohm/p. Set this to 5.6 Ohm.
REoverRLZ1: It provides zero sequence compensation for phase-to-earth faults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 33)
Therefore, set this to 0.28.
XEoverXLZ1: It provides zero sequence compensation for phase-to-earth faults.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 34)
Therefore, set this to 0.83.
RFPEFwZ1: It should be set to give maximum coverage considering the arc resistanceand tower footing resistance.
Arc resistance = 2 Ohm primary and Tower footing resistance = 10 Ohm Primary.Therefore, RFPEFwZ1 should be minimum of 12 Ohm.
Since the RFPEStart is set to 50.16 Ohm to give more resistive coverage, RFPEFwZ1can be set at 0.8 x 50.16 = 40.13 Ohm. However, to avoid overreach due to the remoteend infeed, it is recommended that the resistive reach does not exceed 4.5 timesreactive reach.
Therefore, RFPEFwZ1 may be set to 4.5 x X1FwZ1 = 4.5 x 5.6 = 25.52 Ohm.
RFPERvZ1: It may be set identical to RFPEFwZ1, which is 25.52 Ohm.
RFPPFwZ1: It should be set to cover the arc resistance for phase-to-phase faults. Itmay be set identical to RFPEFwZ1, which is 25.52 Ohm.
RFPPRvZ1: It may be set identical to RFPPFwZ1, which is 25.52 Ohm.
TimerSelZ1: This is used to set the zone timer selection mode of zone 1. Set this toTimers Separated.
OpModetPEZ1: Set this to On.
tPEZ1: Set this to 0.0s.
Section 7 1MRK 506 375-UEN -Impedance protection
142 Railway application RER670 2.2 IECApplication manual
OpModetPPZ1: Set this to On.
tPPZ1: Set this to 0.0s.
Zone 2OpZ2: Set this to On.
DirModeZ2: This is used to set the zone 2 direction mode. Set this to Forward.
PhSelModeZ2: This is used to enable the measuring loops of zone 2. Set this to Phsellogic.
LEModeZ2: This is used to operate the load discrimination characteristic of zone 2.Set this to On.
LCModeZ2: This is used to enable/disable the adaptive load compensation mode ofzone 2. Set this to Off.
X1FwZ2: This is used to set the forward positive sequence reactance reach of zone 2in Ohm/p. This should be set to 120% of line 1 reactance.
Therefore, set the X1FwZ2 to 1.2 x 50 x 0.112 = 6.72 Ohm.
X1RvZ2: Set this identical to X1FwZ2 which is 6.72 Ohm.
REoverRLZ2: It provides zero sequence compensation for phase-to-earth faults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 35)
Therefore, set this to 0.28.
XEoverXLZ2: It provides zero sequence compensation for phase-to-earth faults.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 36)
Therefore, set this to 0.83.
RFPEFwZ2: It should be set to give maximum coverage considering the maximumpermissible load.
Since the RFPEFwStart is set to 50.16 Ohm to give more resistive coverage,RFPEFwZ2 can be set at 0.8 x 50.16 = 40.13 Ohm.
RFPERvZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.
RFPPFwZ2: It may be set identical to RFPEFwZ2, which is 40.13 Ohm.
RFPPRvZ2: It may be set identical to RFPPFwZ2, which is 40.13 Ohm.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 143Application manual
TimerSelZ2: This is used to set the zone timer selection mode of zone 2. Set this toTimers Separated.
OpModetPEZ2: Set this to On.
tPEZ2: Choose a time delay for zone 2 with margin to assure selectivity to zone 1 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient.Therefore, the time delay for zone 2 can be set to 0.4s.
OpModetPPZ2: Set this to On.
tPPZ2: Set this identical to tPEZ2, which is 0.4s.
Zone 3OpZ3: This is for operation Off/On of zone 3. Set this to On.
DirModeZ3: This is used to set the zone 3 direction mode. Set this to Forward.
PhSelModeZ3: This is used to enable the zone 3 measuring loops. Set this to Phsellogic.
LEModeZ3: This is used to operate the load discrimination characteristic of zone 3.Set this to On.
LCModeZ3: This is used to enable/disable load compensation mode for zone 3. Setthis to Off.
X1FwZ3: This is used to set the forward positive sequence reactance reach for zone 3in Ohm/p. This should be set to 120% of reactance of (Line 1 + Line 2).
Therefore, set X1FwZ3 to 1.2 x (50 +100) x 0.112 = 20.16 Ohm.
X1RvZ3: Set this identical to X1FwZ3 which is 20.16 Ohm.
REoverRLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.
28.01097.0
151.0
2
11
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN (Equation 37)
Therefore, set this to 0.28.
XEoverXLZ3: This is used to provide zero sequence compensation for phase-to-earthfaults.
83.01112.0
298.0
2
11
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN (Equation 38)
Therefore, set this to 0.83.
Section 7 1MRK 506 375-UEN -Impedance protection
144 Railway application RER670 2.2 IECApplication manual
RFPEFwZ3: This may be set identical to setting RFPEFwZ2 which is 40.13 Ohm.
RFPERvZ3: It is set identical to setting RFPEFwZ3 which is 40.13 Ohm.
RFPPFwZ3: This may be set identical to setting RFPEFwZ3 which is 40.13 Ohm.
RFPPRvZ3: It is set identical to setting RFPEFwZ3 which is 40.13 Ohm.
TimerSelZ3: This is used for Zone timer selection mode of zone 3. Set this to Timersseparated.
OpModetPEZ3: Set this to On.
tPEZ3: Choose a time delay for zone 3 with a margin to assure selectivity to zone 2 ofadjacent lines. A delay time difference of 0.4s between the zones is sufficient. Thetime delay for zone 3 therefore can be set to 0.8s.
OpModetPPZ3: Set this to On.
tPPZ3: Set this identical to tPPZ3 = 0.8s.
Zones 4, 5 and 6 can be set on similar lines based on the application.
Phase selectiontI0: It is strongly recommended not to use residual overcurrent based phase selectionincase of solidly earthed systems. Hence, set this to 60.0s.
7.3 Underimpedance protection for railway transformersZGTPDIS
7.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEEidentification
Underimpedance protection for railwaytransformers
ZGTPDISZ<
IEC15000305 V1 EN
21T
7.3.2 Application
ZGTPDIS is generally used as backup protection for faults on the transformer and theassociated transmission lines. These transformers can be classified in two basiccategories:
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 145Application manual
• 2-phase to 2-phase Interconnecting transformers• 2-phase to 1-phase Interconnecting transformers
IEC15000302-1-en.vsdx
Trafo 132/15kV
15kV132kV
U
VV
2-phase to 1-phase interconnectionIEC15000302 V2 EN
IEC15000304-2-en.vsdx
Trafo 132/66kV
66kV132kV
U
VV
U
2-phase to 2-phase interconnectionIEC15000304 V2 EN
Figure 42: Railway transformers connection examples
ZGTPDIS function can be used as primary protection as well as backup protection forthe transformer. It protects both HV and LV side of the transformer. The protection isdesigned to operate for earth faults and phase faults in the transformer and theassociated lines.
Zone 1 can be used to provide high-speed protection for faults in the HV winding ofthe transformer. Zone 2 can be used to cover the entire transformer and substation LVbusbar. Zone 3 can be used to cover power system faults beyond the LV busbar.
Section 7 1MRK 506 375-UEN -Impedance protection
146 Railway application RER670 2.2 IECApplication manual
Backup impedance protection characteristicsThe characteristics of zone 1, zone 2 and zone 3 are shown in Figure 43. All zones haveeither offset mho or non-directional quadrilateral characteristics with adjustable reachin forward and reverse direction. Quadrilateral characteristics have additionalresistive blinders in forward and reverse direction. The quadrilateral characteristiclimits the resistive reach and helps to avoid incorrect operations due to loadencroachment. All three zones have the same characteristic angle which can beadjusted using ImpCharAng setting.
IEC15000196-2-en.vsdx
RFRevZxRFFwZx
ImpCharAng
RFFwZx
RFRevZx RFFwZx
R(Ω)
jX(Ω)
R (Ω)
ZxFwd
ImpCharAng
ZxRev
jX(Ω)
IEC15000196 V2 EN
Figure 43: Non-directional quadrilateral and mho offset characteristic forZGTPDIS
7.3.2.1 Zone 1 operation
For transformer applications, the zone 1 element is typically set to see 70% of thetransformer impedance.
7.3.2.2 Zone 2 operation
Zone 2 can be used to cover the LV side of the transformer and the associated busbar.It is usually set to cover 125% of the transformer impedance. The time to trip must beprovided in order to coordinate with the zone 1 element on the shortest outgoing linefrom the bus.
7.3.2.3 Zone 3 operation
Zone 3 covers the whole of the transformer, the interconnecting station bus to thenetwork and outgoing lines. Within its operating zone, the tripping time for this relayshould be coordinated with the longest time delay of the distance relays on theoutgoing LV lines.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 147Application manual
7.3.3 Setting guidelines
Settings for underimpedance protection for transformers (ZGTPDIS) are done inprimary values. The instrument transformer ratio that has been set for the analog inputcard is used to automatically convert the measured secondary input signals to primaryvalues used in ZGTPDIS.
Default values mentioned below should be validated for each application andappropriate setting values should be adopted.
Parameters for ZGTPDIS application function are set via local HMI or Protection andControl Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: This is used for underimpedance protection Off/On.
ImpCharAng: This is to set the common characteristic angle for all three zones ofunderimpedance element. ImpCharAng should match the associated transformerimpedance angle.
IMinOp: This is to select the minimum operating current for underimpedance element.If the minimum current is exceeded, underimpedance protection calculates theimpedance. A default setting of 10% of IB is recommended.
Zone 1
OpModeZ1: This is to select the operating characteristic of zone 1 underimpedanceelement. This can be selected as Off/Mho offset/Quad non-dir.
Z1Fwd: This is to set the zone 1 forward positive sequence impedance reach in ohm/p. It is recommended to set this to 70% of transformer impedance.
Z1Rev: This is to set the zone 1 reverse positive sequence impedance reach in ohm/p.This should be set as 1% of transformer impedance or lower for better security in caseof reverse faults.
RFFwZ1: This is to set the zone 1 forward fault resistive reach in ohm/p whenquadrilateral characteristic is chosen. It should be set to give maximum coverage offault resistance and the load encroachment (RLdmax).
max
minmax
I
URLd
IECEQUATION226 V2 EN (Equation 39)
Section 7 1MRK 506 375-UEN -Impedance protection
148 Railway application RER670 2.2 IECApplication manual
RFRevZ1: This is to set the zone 1 reverse fault resistive reach in ohm/p whenquadrilateral characteristic is chosen. It may be set identical to RFFwZ1.
tZ1: This is to set the zone 1 time delay to trip. Default setting is 0.0s.
Zone 2
OpModeZ2: This is to select the operating characteristic of zone 2 distance element.This can be selected as Off/Mho offset/Quad non-dir.
Z2Fwd: This is to set the zone 2 forward positive sequence impedance reach in ohm/p. It is recommended to set this to 125% of transformer impedance.
Z2Rev: This is to set the zone 2 reverse positive sequence impedance reach in ohm/p.The recommended setting is 80% of shortest outgoing line in the reverse direction inorder to cover the bus faults.
RFFwZ2: This is to set the zone 2 forward fault resistive reach in ohm/p ifquadrilateral characteristic is selected. It should be set to give maximum coverage offault resistance and the load encroachment (RLdmax).
RFRevZ2: This is to set the zone 2 reverse fault resistive reach in ohm/p if quadrilateralcharacteristic is selected. It may be set identical to RFFwZ2.
tZ2: This is to set the zone 2 time delay to trip. The default setting is 0.5s. It should beset to coordinate with clearance of adjacent circuit fault within reach by the intendedmain protection or breaker fail protection.
Zone 3
OpModeZ3: This is to select the operating characteristic of the zone 3 distanceelement. This can be selected as Off/Mho offset/Quad non-dir.
Z3Fwd: This is to set the zone 3 forward positive sequence impedance reach in ohm/p. It should be set to overreach the remote terminal of the longest adjacent line about20% for all fault conditions.
Z3Rev: This is to set the zone 3 reverse positive sequence impedance reach in ohm/p.This may be set identical to Z2Rev.
RFFwZ3: This is to set the zone 3 forward fault resistive reach in ohm/p ifquadrilateral characteristic is chosen. It should be set to give maximum coverage ofthe fault resistance and load encroachment.
RFRevZ3: This is to set the zone 3 reverse fault resistive reach in ohm/p if quadrilateralcharacteristic is chosen. It may be set identical to RFFwZ3.
tZ3: This is to set the zone 3 time delay to trip. Time delay is used to coordinate withthe slowest circuit backup protection or slowest local backup for faults within zone 3reach. The default setting is 1.5s.
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 149Application manual
7.3.4 Catenary Protection
The ZGTPDIS function can also be utilized for catenary line protection. By using it asimple, three-zone underimpedance protection with independent reach in forward andreverse direction can be easily achieved. Consider the following:
• ZGTPDIS function is using full cycle DFT filtering. Thus, all higher harmonicsare effectively suppressed in measured current and voltage signals.
• The start time of the individual underimpedance zones is typically slightly biggerthan one fundamental power system cycle.
• If directional operation is required (e.g. operation for faults in forward directiononly), the operation of the individual underimpedance zones can be supervised byforward start of the directional overcurrent function D2PTOC. Several instancesof this function are readily available in the IED.
• Second harmonic blocking feature may be required for catenary protection. Forthis purpose, second harmonic blocking feature available in D2PTOC functioncan be utilized.
• Sometimes supervision by sudden change in current and/or voltage signals isrequired for catenary protection. For this purpose, individual zones can besupervised by outputs STDI and STDU from the FRWSPVC function. Severalinstances of FRWSPVC function are readily available in the IED.
• To achieve any of the above mentioned supervisions, correspondingconfiguration logic and appropriate setting in the PCM600 tool shall be done.
• For external supervision from any additional logic input BLKZx on theZGTPDIS function shall be used in the IED configuration.
7.3.5 Wrong phase coupling protection
The ZGTPDIS function in combination with directional overcurrent functionD2PTOC and associated configuration logic can be utilized for wrong phase couplingprotection. The operating characteristic as shown in Figure 44 can be easily achieved.To achieve such application, a simple configuration logic and appropriate setting inthe PCM600 tool shall be done.
Section 7 1MRK 506 375-UEN -Impedance protection
150 Railway application RER670 2.2 IECApplication manual
IEC16000116-1-en.vsdx
R
X
Z2
Z1
WrongPhase
Coupling
IEC16000116 V1 EN
Figure 44: Wrong phase coupling protection
1MRK 506 375-UEN - Section 7Impedance protection
Railway application RER670 2.2 IEC 151Application manual
Section 8 Current protection
8.1 Instantaneous phase overcurrent protection 2-phaseoutput PHPIOC
8.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Instantaneous phase overcurrentprotection 2-phase output
PHPIOC
2I>>
IEC15000110 V1 EN
50
8.1.2 Application
The transient stability of a power system depends mostly on three parameters (atconstant amount of transmitted electric power):
• The type of the fault. Two-phase faults are the most dangerous, because no powercan be transmitted through the fault point during fault conditions.
• The magnitude of the fault current. A high fault current indicates that the decreaseof transmitted power is high.
• The total fault clearing time. The phase angles between the EMFs of thegenerators on both sides of the transmission line increase over the permittedstability limits if the total fault clearing time, which consists of the protectionoperating time and the breaker opening time, is too long.
The fault current on railway lines depends mostly on the fault position and decreaseswith the distance from the infeed point. For this reason the protection must operatevery quickly for faults very close to the relay point, for which very high fault currentsare characteristic.
The instantaneous phase overcurrent protection PHPIOC can operate in one-half ofthe fundamental power system cycle for faults characterized by very high currents.
8.1.3 Setting guidelines
The parameters for instantaneous phase overcurrent protection PHPIOC are set via thelocal HMI or PCM600.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 153Application manual
This protection function must operate only in a selective way. So check all system andtransient conditions that could cause its unwanted operation.
Only detailed network studies can determine the operating conditions under which thehighest possible fault current is expected on the line. In most cases, this currentappears during two-phase fault conditions. But also examine single-phase-to-earthcondition.
Also study transients that could cause a high increase of the line current for shorttimes. A typical example is a line with a power transformer at the remote end, whichcan cause high inrush current when connected to the network and can thus also causethe operation of the built-in, instantaneous, overcurrent protection.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: Set the protection to On/Off.
IP>>: Set operate current in % of IB.
IP>>Max and IP>>Min should only be changed if remote setting of operation currentlevel, IP>>, is used. The limits are used for decreasing the used range of the IP>>setting. If IP>> is set outside IP>>Max and IP>>Min, the closest of the limits toIP>> is used by the function. If IP>>Max is smaller than IP>>Min, the limits areswapped.
IP>>MinEd2Set: Minimum settable operate phase current level in % of IBase, forIEC 61850 Ed. 2 settings.
IP>>MaxEd2Set: Maximum settable operate phase current level in % of IBase, forIEC 61850 Ed. 2 settings.
8.1.3.1 Meshed network without parallel line
The following fault calculations have to be done for two-phase and single-phase-to-earth faults. With reference to Figure 45, apply a fault in B and then calculate thethrough-fault phase current IfB. The calculation should be done using the minimumsource impedance values for ZA and the maximum source impedance values for ZB inorder to get the maximum through fault current from A to B.
Section 8 1MRK 506 375-UEN -Current protection
154 Railway application RER670 2.2 IECApplication manual
~ ~ZA ZBZ L
A B
IED
I fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN
Figure 45: Through fault current from A to B: IfB
Then a fault in A has to be applied and the through fault current IfA has to be calculated,Figure 46. In order to get the maximum through fault current, the minimum value forZB and the maximum value for ZA have to be considered.
IEC09000023-1-en.vsd
~ ~ZA ZBZ L
A B
IED
I fA
Fault
IEC09000023 V1 EN
Figure 46: Through fault current from B to A: IfA
The IED must not trip for any of the two through-fault currents. Hence the minimumtheoretical current setting (Imin) will be:
Imin MAX IfA IfB,( )³
EQUATION78 V1 EN (Equation 40)
A safety margin of 5% for the maximum protection static inaccuracy and a safetymargin of 5% for the maximum possible transient overreach have to be introduced. Anadditional 20% is suggested due to the inaccuracy of the instrument transformersunder transient conditions and inaccuracy in the system data.
The minimum primary setting (Is) for the instantaneous phase overcurrent protectionis then:
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 155Application manual
min1.3sI I³ ×
EQUATION79 V3 EN (Equation 41)
The protection function can be used for the specific application only if this settingvalue is equal to or less than the maximum fault current that the IED has to clear, IF inFigure 47.
IEC09000024-1-en.vsd
~ ~ZA ZBZ L
A B
IED
I F
Fault
IEC09000024 V1 EN
Figure 47: Fault current: IF
100Is
IPIBase
>>= ×
EQUATION1147 V3 EN (Equation 42)
8.2 Two-step directional phase overcurrent protectionD2PTOC
8.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Directional phase overcurrentprotection, two steps
D2PTOC2(2I>)
2
2alt
IEC15000155 V2 EN
51_67
8.2.2 Application
The two-step directional phase overcurrent protection D2PTOC is used in severalapplications in the power system. Some applications are:
Section 8 1MRK 506 375-UEN -Current protection
156 Railway application RER670 2.2 IECApplication manual
• Short circuit protection of feeders.• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers.
In many applications several steps with different current pickup levels and time delaysare needed. D2PTOC can have one or two, individually settable steps. The followingoptions are possible:
Non-directional / Directional function: In most applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed from theprotected object itself. In order to achieve both selectivity and fast fault clearance, thedirectional function can be necessary.
If VT inputs are not available or not connected, the setting parameterDirModex (x = step 1, 2) shall be left to the default value Non-directional.
Choice of time delay characteristics: There are several types of time delaycharacteristics available such as definite time delay and different types of inverse timedelay characteristics. The selectivity between different overcurrent protections isnormally enabled by co-ordination between the function time delays of the differentprotections. To enable optimal co-ordination between all overcurrent protections,they should have the same time delay characteristic. Therefore, several inverse timecharacteristics are available within D2PTOC function.
Normally, it is required that the phase overcurrent protection shall reset as fast aspossible when the current level gets lower than the operation level.
Power transformers can have a large inrush current, when being energized. Thisphenomenon is due to saturation of the transformer magnetic core during parts of theperiod. There is a risk that inrush current will reach levels above the pick-up currentof the phase overcurrent protection. The inrush current has a large 2nd harmoniccontent. This can be used to avoid unwanted operation of the protection function.Therefore, D2PTOC has a possibility of 2nd harmonic restrain if the level of 2nd
harmonic component reaches a value above a set percent of the fundamentalfrequency current.
8.2.3 Setting guidelines
When inverse time overcurrent characteristic is selected, the operatetime of the stage will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that stage to zero.
The parameters for two-step directional phase overcurrent protection D2PTOC are setvia the local HMI or Protection and Control Manager PCM600.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 157Application manual
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
The parameter settings for the base quantities, which represent the base (100%) forpickup levels of all measuring stages, shall be entered as setting parameters for everyD2PTOC function.
For two-phase railway supply system, IBase shall be entered as:
• Rated phase current of the protected object in primary amperes, when themeasured current quantity is selected other than phase1-phase2, which is shownin Table 17.
• Rated phase current of the protected object in primary amperes multiplied by 2.0(i.e. 2.0*Iphase), when the measured current quantity is selected as phase1-phase2, which is shown in Table 17.
For two-phase railway supply system, UBase shall be entered as:
• Rated phase-to-earth voltage of the protected object in primary kV, when themeasured voltage quantity is selected other than phase1-phase2, which is shownin Table 18.
• Rated phase-to-phase voltage of the protected object in primary kV, when themeasured voltage quantity is selected as phase1-phase2, which is shown in Table18.
Operation: This is used for two-step directional phase overcurrent protection Off/On.
CurrentInput: This is used to select the type of energizing quantity (i.e. phasor) forcurrent and will be used as operating quantity for operation of both overcurrent steps.
Table 17: Current selection for D2PTOC function
Set value for the parameter CurrentInput Commentphase1 D2PTOC function will measure the phase L1
current
phase2 D2PTOC function will measure the phase L2current
posSeq D2PTOC function will measure internallycalculated positive sequence current 1 2 / 2IL IL
Table continues on next page
Section 8 1MRK 506 375-UEN -Current protection
158 Railway application RER670 2.2 IECApplication manual
Set value for the parameter CurrentInput Comment
MaxPh1) D2PTOC function will measure current of thephase with maximum magnitude
phase1-phase2 D2PTOC function will measure the currentinternally calculated as the vector differencebetween the phase L1 current and phase L2current IL IL
1) = Note that MaxPh current selection shall not be used when D2PTOC function is used as directional.It shall be only used when function is used for non-directional operation.
VoltageInput: This is used to select the type of energizing quantity (i.e. phasor) forvoltage and will be used as polarizing signal to detect the direction of faults if any ofthe two steps is set for Forward/Reverse mode of operation.
Table 18: Voltage selection for D2PTOC function
Set value for the parameter VoltageInput Commentphase1 D2PTOC function will measure the phase L1
voltage
phase2 D2PTOC function will measure the phase L2voltage
PosSeq D2PTOC function will measure internallycalculated positive sequence voltage 1 2 / 2UL UL
phase1-phase2 D2PTOC function will measure the voltageinternally calculated as the vector differencebetween the phase L1 voltage and phase L2voltage UL UL
For directional operation of the D2PTOC function, the identicalvalues for current and voltage measurement selection shall be set (e.g.both set to PosSeq, or both set to phase1).
OperHarmRestr: This is used to Off/On the 2nd harmonic restrain feature for theD2PTOC function.
I_2nd/I_fund: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 10.0 - 50.0% in steps of 1%. The defaultsetting is 20%.
RCADir: Relay characteristic angle set in degrees. It defines the middle line of theforward operating sector in the directional plane.
ROADir: Relay operate angle value, given in degrees, to define the width of theforward operating sector in the directional plane, shown in Figure 48.
LowVolt: This is used to set low-voltage level in % of UBase for the directiondetection. If measure voltage is below this set level, the setting ActLowVoltx (wherex = 1 & 2) decides the function behavior.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 159Application manual
Uref
Idir
IEC09000636_2_vsd
1
2
2
3
4
IEC09000636 V2 EN
Figure 48: Directional function characteristic
1. RCA = Relay characteristic angle2. ROA = Relay operating angle3. Reverse4. Forward
8.2.3.1 Settings for step 1
Operation1: This is used to Off/On the operation of step 1.
StartCurr1: This is used to set operate current level for step 1 given in % of IBase.
CurveType1: Selection of time characteristic for step 1. Definite time delay anddifferent types of inverse time characteristics are available according to Table 19.
Section 8 1MRK 506 375-UEN -Current protection
160 Railway application RER670 2.2 IECApplication manual
Table 19: Inverse time characteristics
Curve nameIEC Normal Inverse
IEC Very Inverse
IEC Extremely Inverse
IEC Definite Time
ASEA RI type
tDef1: Definite time delay for step 1. The definite time tDef1 is added to the inversetime when inverse time characteristic is selected. Note that the value set is the timebetween activation of the start and the trip outputs.
k1: Time multiplier for inverse time delay for step 1.
IMin1: Minimum operate current for step 1 in % of IBase.
tMin1: Minimum operate time for all inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter, the operation time of the step can never be shorter than the setting. Settingrange: 0.000 - 60.000s in steps of 0.001s.
Operate
time
Current
tDef1
tMin1
IMin1
IEC16000212-1-en.vsdx
IEC16000212 V1 EN
Figure 49: Minimum operate current and operate time for inverse timecharacteristics
In order to fully comply with the definition of the curve, the setting parameter tMin1shall be set to a value equal to the operating time of the selected inverse curve fortwenty times the set current pickup value. Note that the operate time is dependent onthe selected time multiplier setting k1.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 161Application manual
HarmRestr1: This is used to block the operation of step1 from the 2nd harmonicrestrain function. This function should be used when there is a risk of an unwanted tripcaused by power transformer inrush currents. It can be set to Off/On.
DirMode1: This is used to set the directional mode of step 1. The possible modes areNon-directional/Forward/Reverse.
ActLowVolt1: This is used to define directional step behavior when the measuredvoltage is below set LowVolt level. The possible modes of operation are Non-directional/block/Memory. It is set to Memory by default.
8.2.3.2 Settings for step 2
Operation2: This is used to Off/On the operation of step 2.
StartCurr2: This is used to set operate phase current level for step 2 given in % ofIBase.
tDef2: Definite time delay for step 2. Note that the value set is the time betweenactivation of the start and the trip outputs.
HarmRestrain2: This is used to block the operation of step 2 from the 2nd harmonicrestrain function. This function should be used when there is a risk if powertransformer inrush currents might cause unwanted trip. It can be set Off/On.
DirMode2: This is used to set the directional mode of step 2. The possible modes areNon-directional/Forward/Reverse.
ActLowVolt2: This is used to define directional step behavior when the measuredvoltage is below set LowVolt level. The possible modes of operation are Non-directional/block/Memory. It is set to Memory by default.
8.3 Instantaneous residual overcurrent protectionEFRWPIOC
8.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Instantaneous residual overcurrentprotection
EFRWPIOC
IN>>
IEF V1 EN
50N
Section 8 1MRK 506 375-UEN -Current protection
162 Railway application RER670 2.2 IECApplication manual
8.3.2 Application
In many applications, when fault current is limited to a defined value by the objectimpedance, an instantaneous earth-fault protection can provide fast and selectivetripping.
8.3.3 Setting guidelines
The parameters for the Instantaneous residual overcurrent protection EFRWPIOC areset via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
The basic requirement is to assure selectivity, that is EFRWPIOC shall not be allowedto operate for faults at other objects than the protected object (line).
For a normal line in a meshed system single phase-to-earth faults and phase-to-phase-to-earth faults shall be calculated as shown in Figure 50 and Figure 51. The residualcurrents (3I0) to the protection are calculated. For a fault at the remote line end thisfault current is IfB. In this calculation the operational state with high source impedanceZA and low source impedance ZB should be used. For the fault at the home busbar thisfault current is IfA. In this calculation the operational state with low source impedanceZA and high source impedance ZB should be used.
~ ~ZA ZBZ L
A B
IED
I fB
Fault
IEC09000022-1-en.vsd
IEC09000022 V1 EN
Figure 50: Through fault current from A to B: IfB
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 163Application manual
IEC09000023-1-en.vsd
~ ~ZA ZBZ L
A B
IED
I fA
Fault
IEC09000023 V1 EN
Figure 51: Through fault current from B to A: IfA
The function shall not operate for any of the calculated currents to the protection. Theminimum theoretical current setting (Imin) will be:
Im ,fA fBin MAX I I
EQUATION284 V2 EN (Equation 43)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%for maximum possible transient overreach have to be introduced. An additional 20%is suggested due to inaccuracy of instrument transformers under transient conditionsand inaccuracy in the system data.
The minimum primary current setting (Is) is:
Is = 1.3 × Imin EQUATION285 V3 EN (Equation 44)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,as shown in Figure 52, should be calculated.
Section 8 1MRK 506 375-UEN -Current protection
164 Railway application RER670 2.2 IECApplication manual
IEC09000025-1-en.vsd
~ ~ZA ZB
ZL1A B
I M
Fault
IED
ZL2
M
CLine 1
Line 2
IEC09000025 V1 EN
Figure 52: Two parallel lines. Influence from parallel line to the through faultcurrent: IM
The minimum theoretical current setting (Imin) will in this case be:
I m in M AX IfA I fB IM, ,( )³
EQUATION287 V1 EN (Equation 45)
Where:
IfA and IfB have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
Is = 1.3 × Imin EQUATION288 V3 EN (Equation 46)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (IBase).
Operation: set the protection to On or Off.
IN>>: Set operate current in % of IB.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 165Application manual
8.4 Two step residual overcurrent protection EF2PTOC
8.4.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Two step residual overcurrent protection EF2PTOC
2(IN>)
IEC15000229 V1 EN
51N_67N
8.4.2 Application
The two step residual overcurrent protection EF2PTOC is used in several applicationsin the power system. Some applications are:
• Earth-fault protection of feeders in effectively earthed two-phase railway supplysystem. Normally these feeders have radial structure.
• Back-up earth-fault protection of transmission lines.• Sensitive earth-fault protection of transmission lines. EF2PTOC can have better
sensitivity to detect resistive phase-to-earth-faults compared to distanceprotection.
• Back-up earth-fault protection of power transformers.• Earth-fault protection of different kinds of equipment connected to the power
system such as shunt capacitor banks and others.
In many applications, several steps with different current operating levels and timedelays are needed. EF2PTOC can have up to two, individual settable steps. Theflexibility of each step of EF2PTOC is great. The following options are possible:
Non-directional/Directional: In some applications the non-directional functionality isused. This is mostly the case when no fault current can be fed from the protected objectitself. In order to achieve both selectivity and fast fault clearance, the directionalfunctionality may be necessary. Note that for directional operation additional logic inthe IED configuration tool is needed.
Choice of time characteristics: There are several types of time characteristicsavailable such as definite time delay and different types of inverse timecharacteristics. The selectivity between different overcurrent protections is normallyenabled by co-ordination between the operate time of the different protections. Toenable optimal co-ordination all overcurrent protections, to be co-ordinated againsteach other, should have the same time characteristic.
Section 8 1MRK 506 375-UEN -Current protection
166 Railway application RER670 2.2 IECApplication manual
Table 20: Time characteristics
Curve nameIEC Normal Inverse
IEC Very Inverse
IEC Extremely Inverse
IEC Definite Time
ASEA RI
Normally it is required that EF2PTOC shall reset as fast as possible when the currentlevel gets lower than the operation level.
8.4.3 Setting guidelines
When inverse time overcurrent characteristic is selected, the operatetime of the step will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that step to zero.
The parameters for the two step residual overcurrent protection, zero sequencedirection EF2PTOC is set via the local HMI or PCM600.
The following settings can be done for the two step residual overcurrent protection.
GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.
Operation: Sets the protection to On or Off.
8.4.3.1 Settings for each step (x = 1 and 2)
DirModex: The directional mode of step x. Possible settings are Off/Non-directional.
Characterist1: Selection of time characteristic for step 1. Definite time delay anddifferent types of inverse time characteristics are available.
Inverse time characteristic enables fast fault clearance of high current faults at thesame time as selectivity to other inverse time phase overcurrent protections can beassured. This is mainly used in radial fed networks but can also be used in meshednetworks. In meshed networks the settings must be based on network faultcalculations.
To assure selectivity between different protections, in the radial network, there haveto be a minimum time difference Dt between the time delays of two protections. Theminimum time difference can be determined for different cases. To determine theshortest possible time difference, the operation time of protections, breaker openingtime and protection resetting time must be known. These time delays can vary
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 167Application manual
significantly between different protective equipment. The following time delays canbe estimated:
Protection operate time: 15-60 ms
Protection resetting time: 15-60 ms
Breaker opening time: 20-120 ms
The different characteristics are described in the technical reference manual.
INx>: Operate residual current level for step x given in % of IBase.
kx: Time multiplier for the dependent (inverse) characteristic for step x.
IN1Min: Minimum operate current for step 1 in % of IBase.
t1Min: Minimum operating time for inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter the operation time of the step can never be shorter than the setting.
Current
Operatetime
IN1Min
t1Min
IEC15000250-1-en.vsdx
IEC15000250 V1 EN
Figure 53: Minimum operate current and operate time for inverse timecharacteristics
In order to fully comply with curves definition the setting parameter t1Min shall be setto the value which is equal to the operate time of the selected IEC inverse curve for
Section 8 1MRK 506 375-UEN -Current protection
168 Railway application RER670 2.2 IECApplication manual
measured current of twenty times the set current pickup value. Note that the operatetime value is dependent on the selected setting value for time multiplier k1.
8.4.3.2 Common settings
tx: Definite time delay for step x. Used if definite time characteristic is chosen.
AngleRCA: Relay characteristic angle given in degree. This angle is defined as shownin Figure 54. The angle is defined positive when the residual current lags the referencevoltage (Upol = -2U0)
Upol = -2U0
I>Dir
RCA
Operation
IEC16000027-1-en.vsdx
IEC16000027 V1 EN
Figure 54: Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°.
Normally voltage polarizing from the internally calculated residual sum or an externalopen delta is used.
UPolMin: Minimum polarization (reference) polarizing voltage for the directionalfunction, given in % of UBase/2.
I>Dir: Operate residual current release level in % of IB for directional stage. Thesetting is given in % of IB. The output signals, STFW and STRV can be used in ateleprotection scheme. The appropriate signal should be configured to thecommunication scheme block.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 169Application manual
8.4.3.3 2nd harmonic restrain
If a power transformer is energized there is a risk that the current transformer core willsaturate during part of the period, resulting in a transformer inrush current. This willgive a declining residual current in the network, as the inrush current is deviatingbetween the phases. There is a risk that the residual overcurrent function will give anunwanted trip. The inrush current has a relatively large ratio of 2nd harmoniccomponent. This component can be used to create a restrain signal to prevent thisunwanted function.
At current transformer saturation a false residual current can be measured by theprotection. Here the 2nd harmonic restrain can prevent unwanted operation as well.
2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal. The setting is given in % of the fundamental frequencyresidual current.
8.5 Sensitive directional residual overcurrent and powerprotection SDEPSDE
8.5.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Sensitive directional residual overcurrent and power protection
SDEPSDEIN>
IEC15000260 V1 EN
67N
8.5.2 Application
In networks with high impedance earthing, the phase-to-earth fault current issignificantly smaller than the short circuit currents. Another difficulty for earth faultprotection is that the magnitude of the phase-to-earth fault current is almostindependent of the fault location in the network.
Directional residual current can be used to detect and give selective trip of phase-to-earth faults in high impedance earthed networks. The protection uses the residualcurrent component 2I0 · cos φ, where φ is the angle between the residual current andthe residual voltage (-2U0), compensated with a characteristic angle. Alternatively,the function can be set to strict 2I0 level with a check of angle φ.
Directional residual power can also be used to detect and give selective trip of phase-to-earth faults in high impedance earthed networks. The protection uses the residual
Section 8 1MRK 506 375-UEN -Current protection
170 Railway application RER670 2.2 IECApplication manual
power component 2I0 · 2U0 · cos φ, where φ is the angle between the residual currentand the reference residual voltage, compensated with a characteristic angle.
A normal non-directional residual current function can also be used with definite orinverse time delay.
A backup neutral point voltage function is also available for non-directional residualovervoltage protection.
In an isolated network, that is, the network is only coupled to earth via the capacitancesbetween the phase conductors and earth, the residual current always has -90º phaseshift compared to the residual voltage (2U0). The characteristic angle is chosen to -90ºin such a network.
In resistance earthed networks or in Petersen coil earthed, with a parallel resistor, theactive residual current component (in phase with the residual voltage) should be usedfor the earth fault detection. In such networks, the characteristic angle is chosen to 0º.
As the amplitude of the residual current is independent of the fault location, theselectivity of the earth fault protection is achieved by time selectivity.
When should the sensitive directional residual overcurrent protection be used andwhen should the sensitive directional residual power protection be used? Consider thefollowing:
• Sensitive directional residual overcurrent protection gives possibility for bettersensitivity. The setting possibilities of this function are down to 0.25 % of IBase,1 A or 5 A. This sensitivity is in most cases sufficient in high impedance networkapplications, if the measuring CT ratio is not too high.
• Sensitive directional residual power protection gives possibility to use inversetime characteristics. This is applicable in large high impedance earthed networks,with large capacitive earth fault currents. In such networks, the active faultcurrent would be small and by using sensitive directional residual powerprotection, the operating quantity is elevated. Therefore, better possibility todetect earth faults. In addition, in low impedance earthed networks, the inversetime characteristic gives better time-selectivity in case of high zero-resistive faultcurrents.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 171Application manual
Phase
currentsIN
Phase-earth
voltagesUN
IEC16000210-1-en.vsdx
IEC16000210 V1 EN
Figure 55: Connection of SDEPSDE to analog preprocessing function block
Overcurrent functionality uses true 2I0, i.e. sum of GRPxL1 and GRPxL2. For 2I0 tobe calculated, connection is needed to both two phase inputs.
Directional and power functionality uses IN and UN. If a connection is made toGRPxN this signal is used, else if connection is made only to inputs GRPxL1 andGRPxL2 the internally calculated sum of these inputs (2I0 and 2U0) will be used.
8.5.3 Setting guidelines
The sensitive earth fault protection is intended to be used in high impedance earthedsystems, or in systems with resistive earthing where the neutral point resistor gives anearth fault current larger than what normal high impedance gives but smaller than thephase-to-phase short circuit current.
In a high impedance system the fault current is assumed to be limited by the systemzero sequence shunt impedance to earth and the fault resistance only. All the seriesimpedances in the system are assumed to be zero.
In the setting of earth fault protection, in a high impedance earthed system, the neutralpoint voltage (zero sequence voltage) and the earth fault current will be calculated atthe desired sensitivity (fault resistance). The complex neutral point voltage (zerosequence) can be calculated as:
Section 8 1MRK 506 375-UEN -Current protection
172 Railway application RER670 2.2 IECApplication manual
0
0
21
phase
f
UU
R
Z
IECEQUATION16029 V1 EN (Equation 47)
Where
Uphase is the phase voltage in the fault point before the fault,
Rf is the resistance to earth in the fault point and
Z0 is the system zero sequence impedance to earth
The fault current, in the fault point, can be calculated as:
00
22
2phase
jf
UI I
Z R
IECEQUATION16030 V1 EN (Equation 48)
The impedance Z0 is dependent on the system earthing. In an isolated system (withoutneutral point apparatus) the impedance is equal to the capacitive coupling between thephase conductors and earth:
0
2 phasec
j
UZ jX j
I
IECEQUATION16031 V1 EN (Equation 49)
Where
Ij is the capacitive earth fault current at a non-resistive phase-to-earth fault
Xc is the capacitive reactance to earth
In a system with a neutral point resistor (resistance earthed system) the impedance Z0can be calculated as:
0
2
2c n
c n
jX RZ
jX R
IECEQUATION16032 V1 EN (Equation 50)
Where
Rn is the resistance of the neutral point resistor
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 173Application manual
In many systems there is also a neutral point reactor (Petersen coil) connected to oneor more transformer neutral points. In such a system the impedance Z0 can becalculated as:
0
4/ /2 / / 2
2 2 2n n c
c n nn c n n c
R X XZ jX R j X
X X j R X X
IECEQUATION16033 V1 EN (Equation 51)
Where
Xn is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 2Xn = Xc In thiscase the impedance Z0 will be: Z0 = 2Rn
Now consider a system with an earthing via a resistor giving higher earth fault currentthan the high impedance earthing. The series impedances in the system can no longerbe neglected. The system with a single phase to earth fault can be described as inFigure 56.
Substation A
Substation B
ZlineAB,1 (pos. seq) ZlineAB,0 (zero seq)
Zl ineBC,1 (pos. seq) Zl ineBC,0 (zero seq)
U0A
U0B
2I0
Phase to earth fault
RN
ZT,1 (pos. seq) ZT,0 (zero seq)
Source impedance Zsc (pos. seq)
IEC16000126-1-en.vsdx
IEC16000126 V1 EN
Figure 56: Equivalent of power system for calculation of setting
The residual fault current can be written:
Section 8 1MRK 506 375-UEN -Current protection
174 Railway application RER670 2.2 IECApplication manual
01 0
22
2 2phase
f
UI
Z Z R
IECEQUATION16034 V1 EN (Equation 52)
Where
Uphase is the phase voltage in the fault point before the fault
Z1 is the total positive sequence impedance to the fault point. Z1 = Zsc+ZT,1+ZlineAB,1+ZlineBC,1
Z0 is the total zero sequence impedance to the fault point. Z0 = ZT,0+2RN+ZlineAB,0+ZlineBC,0
Rf is the fault resistance.
The residual voltages in stations A and B can be written:
0 0 ,02 2A T NU I Z R IECEQUATION16097 V1 EN (Equation 53)
0 0 ,0 ,02 2B T N lineABU I Z R Z IECEQUATION16098 V1 EN (Equation 54)
The residual power, measured by the sensitive earth fault protections in A and B willbe:
0 0 02 2A AS U I IECEQUATION16099 V1 EN (Equation 55)
0 0 02 2B BS U I IECEQUATION16100 V1 EN (Equation 56)
The residual power is a complex quantity. The protection will have a maximumsensitivity in the characteristic angle RCA. The apparent residual power componentin the characteristic angle, measured by the protection, can be written:
0 , 0 02 2 cosA prot A AS U I IECEQUATION16101 V1 EN (Equation 57)
0 , 0 02 2 cosB prot B BS U I IECEQUATION16102 V1 EN (Equation 58)
The angles φA and φB are the phase angles between the residual current and theresidual voltage in the station compensated with the characteristic angle RCA.
The protection will use the power components in the characteristic angle direction formeasurement, and as base for the inverse time delay.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 175Application manual
The inverse time delay is defined as:
0 02 2 cosinv
kSN Sreft
I U measured
IECEQUATION16103 V1 EN (Equation 59)
The function can be set On/Off with the setting of Operation.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
RotResU: It is a setting for rotating the polarizing quantity ( 2U0) by 0 or 180 degrees.This parameter is set to 180 degrees by default in order to inverse the residual voltage( 2U0) to calculate the reference voltage (-2U0 e-jRCADir). Since the reference voltageis used as the polarizing quantity for directionality, it is important to set this parametercorrectly.
With the setting OpMode the principle of directional function is chosen.
With OpMode set to 2I0cosfi the current component in the direction equal to thecharacteristic angleRCADir has the maximum sensitivity. The characteristic forRCADir is equal to 0° is shown in Figure 57.
0 , 90RCADir ROADir
02I
0 refang(2I ) ang(2U )
0 ref2U U 02I cos
IEC16000127-1-en.vsdx
IEC16000127 V1 EN
Figure 57: Characteristic for RCADir equal to 0°
The characteristic is for RCADir equal to -90° is shown in Figure 58.
Section 8 1MRK 506 375-UEN -Current protection
176 Railway application RER670 2.2 IECApplication manual
IEC16000128-1-en.vsdx
refU
90 , 90RCADir ROADir
02I
02I cos
0(2 ) ( )refang I ang U
02U
IEC16000128 V1 EN
Figure 58: Characteristic for RCADir equal to -90°
When OpMode is set to 2U02I0cosfi the apparent residual power component in thedirection is measured.
When OpMode is set to 2I0 and fi the function will operate if the residual current islarger than the setting INDir> and the residual current angle is within the sectorRCADir ± ROADir.
The characteristic for this OpMode when RCADir = 0° and ROADir = 80° is shown inFigure 59.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 177Application manual
-2U0
Operate area
2I0
RCADir = 0º
ROADir = 80º
IEC16000129-1-en.vsdx
IEC16000129 V1 EN
Figure 59: Characteristic for RCADir = 0° and ROADir = 80°
DirMode is set Forward or Reverse to set the direction of the operation for thedirectional function selected by the OpMode.
All the directional protection modes have a residual current release level settingINRel> which is set in % of IBase. This setting should be chosen smaller than or equalto the lowest fault current to be detected.
All the directional protection modes have a residual voltage release level settingUNRel> which is set in % of UBase. This setting should be chosen smaller than orequal to the lowest fault residual voltage to be detected.
tDef is the definite time delay, given in s, for the directional residual currentprotection.
tReset is the time delay before the definite timer gets reset, given in s. With a tResettime of few cycles, there is an increased possibility to clear intermittent earth faultscorrectly. The setting shall be much shorter than the set trip delay. In case ofintermittent earth faults, the fault current is intermittently dropping below the set valueduring consecutive cycles. Therefore the definite timer should continue for a certaintime equal to tReset even though the fault current has dropped below the set value.
The characteristic angle of the directional functions RCADir is set in degrees. RCADiris normally set equal to 0° in a high impedance earthed network with a neutral pointresistor as the active current component is appearing out on the faulted feeder only.RCADir is set equal to -90° in an isolated network as all currents are mainly capacitive.
Section 8 1MRK 506 375-UEN -Current protection
178 Railway application RER670 2.2 IECApplication manual
ROADir is Relay Operating Angle. ROADir is identifying a window around thereference direction in order to detect directionality. ROADir is set in degrees. Forangles differing more than ROADir from RCADir the function is blocked. The settingcan be used to prevent unwanted operation for non-faulted feeders, with largecapacitive earth fault current contributions, due to CT phase angle error.
INCosPhi> is the operate current level for the directional function when OpMode isset 2I0Cosfi. The setting is given in % of IBase. The setting should be based oncalculation of the active or capacitive earth fault current at required sensitivity of theprotection.
SN> is the operate power level for the directional function when OpMode is set2I02U0Cosfi. The setting is given in % of SBase. The setting should be based oncalculation of the active or capacitive earth fault residual power at required sensitivityof the protection.
The input transformer for the Sensitive directional residual over current and powerprotection function has the same short circuit capacity as the phase currenttransformers. Hence, there is no specific requirement for the external CT core, i.e. anyCT core can be used.
If the time delay for residual power is chosen the delay time is dependent on twosetting parameters. SRef is the reference residual power, given in % of SBase. kSN isthe time multiplier. The time delay will follow the following expression:
0 02 2 cosinv
kSN Sreft
I U measured
IECEQUATION16103 V1 EN (Equation 60)
INDir> is the operate current level for the directional function when OpMode is set2I0 and fi. The setting is given in % of IBase. The setting should be based oncalculation of the earth fault current at required sensitivity of the protection.
OpINNonDir> is set On to activate the non-directional residual current protection.
INNonDir> is the operate current level for the non-directional function. The setting isgiven in % of IBase. This function can be used for detection and clearance of cross-country faults in a shorter time than for the directional function. The current settingshould be larger than the maximum single-phase residual current on the protected line.
TimeChar is the selection of time delay characteristic for the non-directional residualcurrent protection. Definite time delay and different types of inverse timecharacteristics are available:
Table 21: Inverse time characteristics
Curve nameANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
Table continues on next page
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 179Application manual
Curve nameANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
See chapter “Inverse time characteristics” in Technical Manual for the description ofdifferent characteristics
tPCrv, tACrv, tBCrv, tCCrv: Parameters for customer creation of inverse timecharacteristic curve (Curve type = 17). The time characteristic equation is:
[ ] = + ×
->
æ öç ÷ç ÷ç ÷æ öç ÷ç ÷è øè ø
p
At s B InMult
iC
inEQUATION1958 V1 EN (Equation 61)
tINNonDir is the definite time delay for the non directional earth fault currentprotection, given in s.
OpUN> is set On to activate the trip function of the residual over voltage protection.
tUN is the definite time delay for the trip function of the residual voltage protection,given in s.
8.6 Thermal overload protection, one time constant,Celsius LPTTR
Section 8 1MRK 506 375-UEN -Current protection
180 Railway application RER670 2.2 IECApplication manual
8.6.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Thermal overload protection, one timeconstant, Celsius
LPTTR
θ>
26
8.6.2 Application
Equipment in the power system is designed for a certain maximum load current level.If the current exceeds this level the losses will be higher than expected. As aconsequence the temperature of the conductors will increase. If temperature of theequipment reaches too high values, the equipment might be damaged:
• The sag of overhead lines can reach unacceptable value.• If the temperature of conductors, for example aluminium conductors, gets too
high the material will be destroyed.• In cables the insulation can be damaged as a consequence of the overtemperature.
As a consequence of this phase to phase or phase to earth faults can occur.• The paper insulation used inside a power transformer will deteriorate quicker and
expected life of the transformer will be shortened. Even an internal flash-overmay occur.
In stressed situations in the power system it can be required to overload lines andtransformers for a limited time. This should be done while managing the risks safely.
The thermal overload protection provides information that makes a temporaryoverloading possible. The thermal overload protection estimates the conductortemperature continuously in Celsius. This estimation is made by using a thermalmodel based on the current measurement.
If the temperature of the protected object reaches a set alarm level AlarmTemp, asignal ALARM can be given to the operator. This enables actions in the power systemto be taken before dangerous temperatures are reached. If the temperature continuesto increase to the trip value TripTemp, the protection initiates trip of the protectedobject.
The following applications are possible by using thermal overload protection functionwith one time constant LPTTR:
• Thermal overload protection of overhead lines where the outside air temperatureis given as the ambient temperature to the function. Alternatively, an averageoutside air temperature can be given as a setting value. Note that for suchapplication, the primary conductor heating time constant shall be used. Thereference temperature TRef shall be set as primary conductor temperature raiseabove the ambient temperature for the set reference current. The trip temperature
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 181Application manual
TripTemp shall be set as maximum permissible primary conductor temperature indegrees Centigrade.
• Thermal overload protection of power cables. Note that for such application, theambient temperature shall actually represent the soil temperature. Note that forsuch application, the overall cable heating time constant shall be used. Thereference temperature TRef shall be set as primary conductor temperature raiseabove the soil temperature for the set reference current. The trip temperatureTripTemp shall be set as maximum permissible cable temperature in degreesCentigrade.
• Thermal overload protection of power transformer where the outside airtemperature is given as the ambient temperature to the function. Alternatively, anaverage outside air temperature can be given as a setting value. Note that for suchapplication, the power transformer oil heating time constant, which is typicallyavailable from transformer heat run test (i.e. transformer temperature rise test)shall be used. The reference temperature TRef shall be set as top oil temperatureraise above the ambient for the set reference current of 100% (i.e. 60°C inaccordance with IEC 60076-2). The trip temperature TripTemp shall be set asmaximum permissible top oil temperature in degrees Centigrade. For powertransformer manufactured by ABB, a trip value of 105°C is recommended. Thesame value is also recommended in IEC 60076-7 published in 2005.
• Thermal overload protection of power transformers where the top oil temperatureis measured using a sensor and provided to the function as ambient temperature.Note that for such application, the power transformer winding to oil heating timeconstant (i.e. typically much shorter than the power transformer oil heating timeconstant) shall be used. Some typical values of this time constant is around fiveminutes. The reference temperature TRef shall be set as hot-spot windingtemperature rise above the top oil temperature for the set reference current of100% (e.g. 18°C in accordance with IEC 60076-2 published in 2011). If required,additional safety factor (e.g. 1.3) can be used to increase the TRef value. The triptemperature TripTemp shall be set as maximum permissible winding hot-spottemperature in degrees Centigrade. The conservative trip value, in accordancewith IEC 60076-7 published in 2005, is 98°C or 110°C depending on type ofpaper insulation used. Note that higher value can be used if higher relative ageingrates for the power transformer are allowed. For power transformer manufacturedby ABB, the trip value for hot-spot temperature of 130°C is recommended.
• Any of the above four application where additional configuration logic is usedbased on LCPPTR function output TEMP (i.e. estimated protected objecttemperature in degrees Celsius) and associated comparator (i.e. REALCOMP)and timer (i.e. TIMERSET) function blocks. By using such additional logic, forexample, an automatic control of power transformer cooling fans can beengineered within the IED.
8.6.3 Setting guideline
The parameters for the Thermal overload protection, one time constant, CelsiusLPTTR are set via the local HMI or PCM600.
tPulse: Trip signal pulse length.
Section 8 1MRK 506 375-UEN -Current protection
182 Railway application RER670 2.2 IECApplication manual
SensAvailable: Indication for external temperature sensor availability.
DefaultAmbTemp: Default ambient temperature used when external ambienttemperature sensor is set to off or invalid.
DefaultTemp: Initial temperature raise above ambient temperature during startup.
SensMinTemp: Minimum ambient temperature used for limit check.
SensMaxTemp: Maximum ambient temperature used for limit check.
SenInvRstTim: Sensor invalid signal reset time delay.
TmpAmbMin: Ambient temperature minimum value considered for calculation.
The following settings can be done for the thermal overload protection.
Operation: Off/On
GlobalBaseSel is used to select a GBASVAL function for reference of base values,primary current (IBase), primary voltage (UBase) and primary power (SBase).
Imult: Enter the number of lines in case the protection function is applied on multipleparallel lines sharing one CT.
IRef: Reference, steady state current, given in % of IBase that will give a steady state(end) temperature rise TRef. It is suggested to set this current to the maximum steadystate current allowed for the line/cable under emergency operation (a few hours peryear). For power transformer application, the IRef parameter is typically set to 100%(e.g. equal to the rated current) because the heat run tests are typically conducted insuch way.
TRef: Reference temperature rise (end temperature) corresponding to the steady statecurrent IRef. From cable manuals current values with corresponding conductortemperature are often given. These values are given for conditions such as earthtemperature, ambient air temperature, way of laying of cable and earth thermalresistivity. From manuals for overhead conductor temperatures and correspondingcurrent is given. For power transformers, this value is typically available from thepower transformer manual or from the heat run test report.
Tau: The thermal time constant of the protected circuit given in minutes. Please referto equipment manufacturer manuals for details.
TripTemp: Temperature value for trip of the protected circuit. For cables, a maximumallowed conductor temperature is often stated to be 90°C. For overhead lines, thecritical temperature for aluminium conductor is about 90 - 100°C. However, forrailway catenary lines, the critical temperature can be as low as 48°C. For a copperconductor a normal figure is 70°C. For power transformers, it depends on theapplication and used type of paper insulation. Some typical value is around 100°C.
AlarmTemp: Temperature level for alarm of the protected circuit. ALARM signal canbe used as a warning before the circuit is tripped. Therefore the setting shall be lower
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 183Application manual
than the trip level. It shall at the same time be higher than the maximum conductortemperature at normal operation. A suitable setting can be about 15°C below the tripvalue.
ReclTemp: Temperature where lockout signal LOCKOUT from the protection isreleased. When the thermal overload protection trips, a lock-out signal is activated.This signal is intended to block switch in of the protected circuit as long as theconductor temperature is high. The signal is released when the estimated temperatureis below the set value. This temperature value should be chosen below the alarmtemperature.
8.7 Breaker failure protection CCRWRBRF
8.7.1 Application
In the design of the fault clearance system the N-1 criterion is often used. This meansthat a fault needs to be cleared even if any component in the fault clearance system isfaulty. One necessary component in the fault clearance system is the circuit breaker.It is from practical and economical reason not feasible to duplicate the circuit breakerfor the protected object. Instead a breaker failure protection is used.
Breaker failure protection (CCRWRBRF) will issue a back-up trip command to theadjacent circuit breakers in case of failure to trip of the “normal” circuit breaker for theprotected object. The detection of failure to break the current through the breaker ismade by means of either current measurement or status of CB axillary contact.
CCRWRBRF can also give a re-trip. This means that a separate trip signal is sent tothe protected circuit breaker first. The re-trip function can be used to increase theprobability of operation of the breaker, or it can be used to avoid back-up trip of manybreakers in case of mistakes during relay maintenance and testing.
8.7.2 Setting guidelines
The parameters for Breaker failure protection CCRWRBRF application function areset via the local HMI or Protection and Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: This is used for breaker failure protection Off/On.
Section 8 1MRK 506 375-UEN -Current protection
184 Railway application RER670 2.2 IECApplication manual
FunctionMode: This parameter defines the way the detection of failure of the breakeris performed. In the mode Current the current measurement is used for the detection.In the mode Contact the status of breaker auxiliary contact is used as indicator offailure of the breaker. The mode Current/Contact means that either criterion ofdetections can be activated. Contact mode will then be used in situation where thefault current through the circuit breaker is small at the moment when function isinitiated (current level determined by parameter I>BlkCont). This can be the case forsome generator protection application (for example reverse power protection) or incase of line ends with weak end infeed.
RetripMode: This setting states how the re-trip function shall operate. Retrip Offmeans that the re-trip function is not activated. CB Pos Check (circuit breaker positioncheck) and Current means that a phase current must be larger than the operate level toallow re-trip. CB Pos Check (circuit breaker position check) and Contact means re-tripis done when circuit breaker is closed (breaker position is used). No CBPos Checkmeans re-trip is done without any check of breaker position.
Table 22: Dependencies between parameters RetripMode and FunctionMode
RetripMode FunctionMode DescriptionRetrip Off N/A the re-trip function is not
activated
CB Pos Check Current re-trip is done if the phasecurrent is larger than the operatelevel after re-trip time haselapsed
Contact re-trip is done when auxiliarycontact position indicates thatbreaker is still closed after re-triptime has elapsed
Current/Contact both methods according toabove are used but taken intoaccount also I>BlkCont
No CBPos Check Current re-trip is done without check ofcurrent level
Contact re-trip is done without check ofauxiliary contact position
Current/Contact re-trip is done without check ofcurrent level or auxiliary contactposition
IP>: Current level for detection of breaker failure, set in % of IBase. This parametershould be set so that faults with small fault current can be detected. The setting can bechosen in accordance with the most sensitive protection function to start the breakerfailure protection. Typical setting is 10% of IBase.
I>BlkCont: If contact based detection for breaker failure is used, this feature can beblocked if any phase current is larger than this setting level. If the FunctionMode is setCurrent/Contact breaker failure for high current faults are safely detected by thecurrent measurement function. To increase security the contact based measurement
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 185Application manual
should be enabled only for small currents. The setting can be given within the range5 – 200% of IBase.
t1: Time delay of the re-trip. The setting can be given within the range 0 – 60s in stepsof 0.001 s. Typical setting is 0 – 50ms.
t2: Time delay of the back-up trip. The choice of this setting is made as short aspossible at the same time as unwanted operation must be avoided. Typical setting is 90– 200ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
_2 1³ + + +cbopen BFP reset margint t t t tEQUATION1430 V1 EN (Equation 62)
where:
tcbopen is the maximum opening time for the circuit breaker
tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)
tmargin is a safety margin
It is often required that the total fault clearance time shall be less than a given criticaltime. This time is often dependent of the ability to maintain transient stability in caseof a fault close to a power plant.
Time
The fault
occurs
Protection
operate time
Trip and Start
CCRWRBRF
Normal tcbopen
Margin
Retrip delay t1 tcbopen after re-trip
tBFPreset
Minimum back-up trip delay t2
Critical fault clearance time for stability
IEC15000141-1-en.vsdx
IEC15000141 V1 EN
Figure 60: Time sequence
Section 8 1MRK 506 375-UEN -Current protection
186 Railway application RER670 2.2 IECApplication manual
tCBAlarm: Time delay for alarm in case of indication of faulty circuit breaker. Thereis a binary input CBFLT from the circuit breaker. This signal is activated wheninternal supervision in the circuit breaker detect that the circuit breaker is unable toclear fault. This could be the case when gas pressure is low in a SF6 circuit breaker.After the set time an alarm is given, so that actions can be done to repair the circuitbreaker. The time delay for back-up trip is bypassed when the CBFLT is active.Typical setting is 2.0 seconds.
tPulse: Trip pulse duration. This setting must be larger than the critical impulse timeof circuit breakers to be tripped from the breaker failure protection. Typical setting is200 ms.
8.8 Overcurrent protection with binary release BRPTOC
8.8.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Overcurrent protection with binaryrelease
BRPTOC2I>
IEC16000104 V1 EN
50
8.8.2 Application
Overcurrent protection with binary release (BRPTOC) is a simple, non-directionaltwo-phase overcurrent protection function with definite time delay. A single step isavailable within the function. The current pickup level and definite time delay can beset independently. It is possible to release the function operation via a binary signal.If the binary signal is not connected, the function will automatically operate in acontinuous mode of operation. Several function instances are available.
BRPTOC can be used for different line and transformer railway protectionapplications. If required, it can also be used to supervise on-load tap-changeroperation.
The function can be used in 16.7Hz, 50Hz and 60Hz railway supply systems. Thefunction is a two-phase design but it can be used in a single-phase railway supplysystems as well.
8.8.3 Setting guidelines
The parameters for Overcurrent protection with binary release BRPTOC are set viathe local HMI or PCM600.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 187Application manual
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select GBASVAL function for reference of base values.
Operation: By using this setting the function can be set On/Off.
I>: Current pickup level, set in % of IBase.
tDelay: Time delay of the operation.
8.9 Tank overcurrent protection TPPIOC
8.9.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Tank overcurrent protection TPPIOC
IN>>>
IEC15000111 V1 EN
64
8.9.2 Application
The transformer is placed on an insulated platform using the rails. The rails are cut ateach end and insulated with respect to ground by setting the holding-down bolts in theconcrete foundation without any contact to the reinforcement or by fixing the rails onwooden ties.
The tank is grounded at a certain location by a conductor where a CT measures the tankto ground current as shown in Figure 61.
The transformer tank protection function measures the current in the tank earthconductor and give an instantaneous trip signal in case of an insulation break downbetween a winding or terminal and the tank.
Section 8 1MRK 506 375-UEN -Current protection
188 Railway application RER670 2.2 IECApplication manual
IEC15000105-1-en.vsdx
~ ZG
I>
IF,i
IEC15000105 V1 EN
Figure 61: Transformer tank and grounding arrangement
Transformer tank protection function is used to sense the tank leakage current andoperates if the current is above the set level.
In the case of grounded neutral systems, protection can be provided by insulating thetransformer tank from ground apart from a connection to ground through a CT whosesecondary energizes an overcurrent relay. Such an arrangement gives sensitiveprotection for arc-overs to the tank or to the core, but it will not respond to turn faultsor to faults in the leads to the transformer.
The protection scheme should not initiate a trip in case of an external phase to groundfault. Figure 62 illustrates the different elements that are involved in that case.
The neutral displacement voltage that appears in case of an external phase to groundfault is the source voltage for current flowing through the protection circuit. Theamount of this current is proportional to the ratio given by the ground contactresistance RG,C to the leakage resistance RG,I of the tank as explained in Figure 62.
IEC15000106-1-en.vsdx
~ ZG
I>
IF,e
RG,I RG,cVNG
ING
IEC15000106 V1 EN
Figure 62: Behaviour of ground fault protection during an external fault
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 189Application manual
where:
RG,I Leakage resistance of the tank
RG,C Ground contact resistance
ZG Neutral grounding impedance
ING is described as:
IGCGG
NGNG
RRZ
VI
,,
IECEQUATION051 V2 EN (Equation 63)
IFe RG,I is described as:
CGFeNGIGFe RIIRI ,, )(
IECEQUATION052 V2 EN (Equation 64)
For
CGIGG RRZ ,,,
IECEQUATION053 V2 EN (Equation 65)
IFe is described as:
IG
CG
G
NGFe
R
R
Z
VI
,
,
IECEQUATION054 V2 EN (Equation 66)
The current flow in case of an external phase to ground fault should not operate thetank protection. Therefore, start value is set above the absolute value of this current.In other words, the ratio of ground contact resistance RG,C to leakage resistance RG,Ishould not exceed a certain value regardless of atmospheric conditions.
8.9.3 Setting guidelines
The parameters for transformer tank protection TPPIOC are set via the local HMI orPCM600.
The setting parameters for the transformer tank protection TPPIOC are describedbelow:
Common base IED values for primary current (setting IBase) is set in a Global basevalues for settings function GBASVAL setting.
GlobalBaseSel: Selects the global base value group used by the function to define(IBase).
Section 8 1MRK 506 375-UEN -Current protection
190 Railway application RER670 2.2 IECApplication manual
I>: Instantaneous peak current start value in % of IBase.
1MRK 506 375-UEN - Section 8Current protection
Railway application RER670 2.2 IEC 191Application manual
Section 9 Voltage protection
9.1 Two step undervoltage protection U2RWPTUV
9.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Undervoltage protection, two steps U2RWPTUV
2(2U<)
IEC15000109 V1 EN
27
9.1.2 Application
Two-step undervoltage protection function (U2RWPTUV) is applicable in allsituations, where reliable detection of low phase voltages is necessary. It is also usedas a supervision and fault detection function for other protection functions to increasethe security of a complete protection system.
U2RWPTUV is applied to transformers and power lines in order to detect low voltageconditions. Low voltage conditions are caused by abnormal operation or fault in thepower system. U2RWPTUV is used in combination with overcurrent protections,either as restraint or in logic "and gates" of the trip signals issued by the two functions.Other applications are the detection of "no voltage" condition, for example, before theenergization of a HV line or for automatic breaker trip in case of a blackout.
U2RWPTUV is used to disconnect apparatuses which will be damaged when subjectto service under low voltage conditions. U2RWPTUV deals with low voltageconditions at power system frequency, which can be caused by the following reasons:
1. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).
2. Overload (symmetrical voltage decrease).3. Short circuits, often as phase-to-earth faults (unsymmetrical voltage decrease).
U2RWPTUV prevents sensitive equipment from running under conditions that couldcause overheating and thus shorten their life time expectancy. In many cases, it is auseful function in circuits for local or remote automation processes in the powersystem.
1MRK 506 375-UEN - Section 9Voltage protection
Railway application RER670 2.2 IEC 193Application manual
9.1.3 Setting guidelines
All the voltage conditions in the system where U2RWPTUV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.
There are wide applications where general undervoltage functions are used. Allvoltage related settings are made as a percentage of the global base value UBase andbase current IBase, which normally is set to the primary rated voltage level (phase-to-phase) of the power system or the high voltage equipment under consideration.
The setting for U2RWPTUV is normally not critical, since there must be enough timeavailable for the main protection to clear short circuits and earth faults.
Some applications and related setting guidelines for the voltage level are described inthe following sections.
9.1.3.1 Disconnected equipment detection
The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage, caused by inductive or capacitive coupling, when theequipment is disconnected.
9.1.3.2 Power supply quality
The setting must be below the lowest occurring "normal" voltage and above the lowestacceptable voltage, due to regulation, good practice or other agreements.
9.1.3.3 Voltage instability mitigation
This setting is very much dependent on the power system characteristics, andthorough studies have to be made to find the suitable levels.
9.1.3.4 Backup protection for power system faults
The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage during the fault conditions under consideration.
9.1.3.5 Settings for two step undervoltage protection
Parameters for U2RWPTUV application function are set via local HMI or Protectionand Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
Section 9 1MRK 506 375-UEN -Voltage protection
194 Railway application RER670 2.2 IECApplication manual
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
ConnType: Sets whether the measurement shall be phase-to-earth fundamental value,phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phaseRMS value.
Operation: This is used for undervoltage protection Off/On.
UBase (given in GlobalBaseSel): Set as rated phase-to-phase voltage in primary kV.This voltage is used as reference for voltage setting. U2RWPTUV measuresselectively phase-to-earth voltages, or phase-to-phase voltage chosen by the settingConnType. The function will operate if the voltage becomes lower than the setpercentage of UBase. When ConnType is set to PhN DFT or PhN RMS, the IEDautomatically divides set value for UBase by 2. UBase is used as set when ConnTypeis set to PhPh DFT or PhPh RMS. Therefore, always set UBase as rated primaryphase-to-phase voltage of the protected object. This means operation for phase-to-earth voltage under:
2/)((%) kVUBaseU
IECEQUATION048 V1 EN (Equation 67)
and operation for phase-to-phase voltage under:
U (%) UBase(kV)< ×EQUATION1990 V1 EN (Equation 68)
Thus, for any selected measuring type setting of 100% corresponds to the ratedprimary voltage.
The below described setting parameters are identical for the two steps (n = 1 and 2).Therefore, the setting parameters are described only once.
OperationStepn: This is used to on/off the operation of step n.
OpModen: This parameter describes how many of the two measured voltages shouldbe below the set level to give operation for step n. The setting can be Any phase or Allphases.
Un<: It is used to set undervoltage operation value for step n, given as %UB. Thesetting is highly dependent on the protection application.
tn: time delay of step n, given in s. This setting is dependent on the protectionapplication. In many applications the protection function shall not directly trip whenthere is a short circuit or earth faults in the system. The time delay must be coordinatedto the other short circuit protections.
1MRK 506 375-UEN - Section 9Voltage protection
Railway application RER670 2.2 IEC 195Application manual
9.2 Two step overvoltage protection O2RWPTOV
9.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617 identification ANSI/IEEE C37.2
device numberOvervoltage protection, two steps O2RWPTOV
2(2U>)
IEC15000214 V1 EN
59
9.2.2 Application
Two step overvoltage protection O2RWPTOV is applicable in situations wherereliable detection of high voltage is necessary. O2RWPTOV is used for supervisionand detection of abnormal conditions, which in combination with other protectionfunctions, to increase the security of a complete protection system.
High overvoltage conditions are caused by abnormal situations in the power system.O2RWPTOV is applied to transformers and power lines in order to detect high voltageconditions. O2RWPTOV is used in combination with low current signals to identifya transmission line open in the remote end.
O2RWPTOV is used to disconnect apparatuses which will be damaged when subjectto service under high voltage conditions. It deals with high voltage conditions atpower system frequency, which can be caused by:
1. Different kinds of faults, where a too high voltage appears in a certain powersystem, like metallic connection to a higher voltage level (broken conductorfalling down to a crossing overhead line, transformer flash over fault from thehigh voltage winding to the low voltage winding and so on).
2. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).
3. Low load compared to the reactive power generation (symmetrical voltagedecrease).
4. Earth-faults in high impedance earthed systems causes, beside the high voltage inthe neutral, high voltages in the non-faulted phase, (unsymmetrical voltageincrease).
O2RWPTOV prevents sensitive equipment from running under conditions that couldcause their overheating or stress of insulation material, and, thus, shorten their lifetime expectancy. In many cases, it is a useful function in circuits for local or remoteautomation processes in the power system.
Section 9 1MRK 506 375-UEN -Voltage protection
196 Railway application RER670 2.2 IECApplication manual
9.2.3 Setting guidelines
The parameters for two step overvoltage protection (O2RWPTOV) are set via thelocal HMI or Protection and Control Manager PCM600.
All the voltage conditions in the system where O2RWPTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.
There are wide applications where general overvoltage functions are used. All voltagerelated settings are made as a percentage of a settable base primary voltage, which isnormally set to the nominal voltage level (phase-to-phase) of the power system.
The time delay for the O2RWPTOV can sometimes be critical and related to the sizeof the overvoltage - a power system or a high voltage component can withstandsmaller overvoltages for some time, but in case of large overvoltages the relatedequipment should be disconnected more rapidly.
Some applications and related setting guidelines for the voltage level are given below:
9.2.3.1 Equipment protection, transformers
High voltage will cause overexcitation of the core and deteriorate the windinginsulation. The setting has to be well above the highest occurring "normal" voltageand well below the highest acceptable voltage for the equipment.
9.2.3.2 Power supply quality
The setting has to be well above the highest occurring "normal" voltage and below thehighest acceptable voltage, due to regulation, good practice or other agreements.
9.2.3.3 The following settings can be done for the two step overvoltageprotection
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
ConnType: This is used to set whether the measurement shall be phase-to-earthfundamental value, phase-to-phase fundamental value, phase-to-earth true RMSvalue or phase-to-phase true RMS value.
Operation: This is used for two step overvoltage protection Off/On.
UBase (given in GlobalBaseSel): Set as rated phase-to-phase voltage in primary kV.This voltage is used as reference for voltage setting. O2RWPTOV measures
1MRK 506 375-UEN - Section 9Voltage protection
Railway application RER670 2.2 IEC 197Application manual
selectively phase-to-earth voltages, or phase-to-phase voltage chosen by the settingConnType. The function will operate if the voltage gets higher than the set percentageof UBase. When ConnType is set to PhN DFT or PhN RMS, the IED automaticallydivides set value of UBase by 2. When ConnType is set to PhPh DFT or PhPh RMS,set value of UBase is used. Therefore, always set UBase as rated primary phase-to-phase voltage of the protected object. This means operation for phase-to-earth voltageover:
and operation for phase-to-phase voltage over:
U (%) UBase(kV)> ×EQUATION1993 V1 EN (Equation 70)
Thus, for any selected measuring type setting of 100% corresponds to the ratedprimary voltage.
The below described setting parameters are identical for the two steps (n = 1 and 2).Therefore the setting parameters are described only once.
OperationStepn: This is used to enable/disable the operation of step n.
OpModen: This parameter describes how many of the two measured voltages thatshould be above the set level to give operation. The setting can be Any phase or Allphases. In most applications it is sufficient that one phase voltage is high to giveoperation. If the function shall be insensitive for single phase-to-earth faults Allphases can be chosen, because the voltage will normally rise in the non-faulted phasesat single phase-to-earth faults.
Un>: This is used to set operate overvoltage operation value for step n, given as % ofUBase. The setting is highly dependent of the protection application. Here, it isessential to consider the maximum voltage at non-faulted situations. In general, thisvoltage is less than 110% of nominal voltage.
tn: time delay of step n, given in s. The setting is highly dependent of the protectionapplication. In many applications the protection function is used to prevent damagesto the protected object. The speed might be important for example in case of protectionof transformer that might be overexcited. The time delay must be co-ordinated withother automated actions in the system.
Section 9 1MRK 506 375-UEN -Voltage protection
198 Railway application RER670 2.2 IECApplication manual
9.3 Two step residual overvoltage protectionROV2PTOV
9.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Two step residual overvoltageprotection
ROV2PTOV
2(U0>)
IEC15000108 V1 EN
59N
9.3.2 Application
The residual voltage will increase in case of any single phase earth-fault occurred inisolated or compensated two-phase railway supply systems. Depending on the type offault and fault resistance, the residual voltage will reach different values. The highestresidual voltage, equal to two times the phase-to-earth voltage, is achieved for a solidsingle phase-to-earth fault. The residual voltage increases approximately to the samelevel in the whole system and does not provide any guidance in finding the faultedcomponent. Therefore, ROV2PTOV is often used as a backup protection or as arelease signal for the feeder earth-fault protection.
9.3.3 Setting guidelines
All the voltage conditions in the system where ROV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltagewithstand capability and time characteristic.
All voltage-related settings are made as a percentage of a settable base voltage, whichshall be set to the primary nominal voltage (phase-phase) level of the power system.
The time delay for ROV2PTOV is seldom critical, since residual voltage is related toearth faults in a high-impedance earthed system, and enough time must normally begiven for the primary protection to clear the fault. In some more specific situations,where the residual overvoltage protection is used to protect some specific equipment,the time delay is shorter.
Some applications and related setting guidelines for the residual voltage level aregiven below.
9.3.3.1 High impedance earthed systems
In high impedance earthed systems, an earth fault on one phase will cause a voltagecollapse in that phase. However, the other healthy phase voltage will raise to full
1MRK 506 375-UEN - Section 9Voltage protection
Railway application RER670 2.2 IEC 199Application manual
phase-to-phase voltage value. The residual voltage sum 2U0 will raise to the samephase-to-phase value during earth fault.
9.3.3.2 Solidly earthed systems
In solidly earthed systems, an earth fault on one phase is indicated by voltage collapsein that phase. The other healthy phase will still have normal phase-to-earth voltage.The residual sum 2U0 will have the same value as the remaining phase-to-earthvoltage.
9.3.3.3 Settings for two step residual overvoltage protection
Parameters for ROV2PTOV application function are set via the local HMI orProtection and Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: This is used for residual overvoltage protection Off/On.
UBase (given in GlobalBaseSel) is used as voltage reference for the set pickup values.UBase shall be set equal to rated phase-to-phase voltage. Note that the set value forUBase will be multiplied by factor 0.5 within the ROV2PTOV function. The voltagecan be fed to the IED in different ways:
1. The IED is fed from two VTs connected phase-to-ground, where the residualvoltage 2U0 is calculated internally within the protection.
2. The IED is fed from a single voltage transformer connected to the neutral point ofa power transformer in the power system. In this connection the protection is fedby the voltage UN=U0 (single input). Section Analog inputs in the Applicationmanual explains how the analog input needs to be set.
The setting parameters described below are identical for the two steps (n = step 1 and2). Therefore the setting parameters are described only once.
OperationStepn: This is to enable/disable operation of step n.
Un>: Set operate overvoltage operation value for step n, given as % of residualvoltage corresponding to UBase:
(%) ( ) / 2Un UBase kV IECEQUATION050 V2 EN (Equation 71)
Section 9 1MRK 506 375-UEN -Voltage protection
200 Railway application RER670 2.2 IECApplication manual
The setting depends on the required sensitivity of the protection and the type of systemearthing. In high impedance earthed systems, the residual voltage can be at maximumrated phase-to-phase voltage, which should correspond to 200%.
In solidly earthed systems, this value depends on the ratio Z0/Z1. The required settingto detect high resistive earth faults must be based on network calculations. Typicallyit shall be lesser than 100%.
tn: time delay of step n, given in s. The setting is highly dependent on the protectionapplication. The time delay must be co-ordinated with other automated actions in thesystem.
1MRK 506 375-UEN - Section 9Voltage protection
Railway application RER670 2.2 IEC 201Application manual
Section 10 Frequency protection
10.1 Underfrequency protection SAPTUF
10.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Underfrequency protection SAPTUF
f <
SYMBOL-P V1 EN
81L
10.1.2 Application
Underfrequency protection SAPTUF is applicable in all situations, where reliabledetection of low fundamental power system frequency is needed. The power systemfrequency, and the rate of change of frequency, is a measure of the unbalance betweenthe actual generation and the load demand. Low fundamental frequency in a powersystem indicates that the available generation is too low to fully supply the powerdemanded by the load connected to the power grid. SAPTUF detects such situationsand provides an output signal, suitable for load shedding, generator boosting, HVDC-set-point change, gas turbine start up and so on. Sometimes shunt reactors areautomatically switched in due to low frequency, in order to reduce the power systemvoltage and hence also reduce the voltage dependent part of the load.
SAPTUF is very sensitive and accurate and is used to alert operators that frequencyhas slightly deviated from the set-point, and that manual actions might be enough. Theunderfrequency signal is also used for overexcitation detection. This is especiallyimportant for generator step-up transformers, which might be connected to thegenerator but disconnected from the grid, during a roll-out sequence. If the generatoris still energized, the system will experience overexcitation, due to the low frequency.
10.1.3 Setting guidelines
All the frequency and voltage magnitude conditions in the system where SAPTUFperforms its functions should be considered. The same also applies to the associatedequipment, its frequency and time characteristic.
There are two specific application areas for SAPTUF:
1MRK 506 375-UEN - Section 10Frequency protection
Railway application RER670 2.2 IEC 203Application manual
1. to protect equipment against damage due to low frequency, such as generators,transformers, and motors. Overexcitation is also related to low frequency
2. to protect a power system, or a part of a power system, against breakdown, byshedding load, in generation deficit situations.
The under frequency start value is set in Hz. All voltage magnitude related settings aremade as a percentage of a global base voltage parameter. The UBase value should beset as a primary phase-to-phase value.
Some applications and related setting guidelines for the frequency level are givenbelow:
Equipment protection, such as for motors and generatorsThe setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.
Power system protection, by load sheddingThe setting has to be below the lowest occurring "normal" frequency and well abovethe lowest acceptable frequency for power stations, or sensitive loads. The settinglevel, the number of levels and the distance between two levels (in time and/or infrequency) depends very much on the characteristics of the power system underconsideration. The size of the "largest loss of production" compared to "the size of thepower system" is a critical parameter. In large systems, the load shedding can be setat a fairly high frequency level, and the time delay is normally not critical. In smallersystems the frequency start level has to be set at a lower value, and the time delay mustbe rather short.
The voltage related time delay is used for load shedding. The settings of SAPTUFcould be the same all over the power system. The load shedding is then performedfirstly in areas with low voltage magnitude, which normally are the most problematicareas, where the load shedding also is most efficient.
Section 10 1MRK 506 375-UEN -Frequency protection
204 Railway application RER670 2.2 IECApplication manual
Section 11 Secondary system supervision
11.1 Current circuit supervision CCSSPVC
11.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Current circuit supervision CCSSPVCINd/I
IEC15000306 V1 EN
87
11.1.2 Application
Open or short circuited current transformer cores can cause unwanted operation ofmany protection functions such as differential and earth-fault current functions. Whencurrents from two independent two-phase sets of CTs, or CT cores, measuring thesame primary currents are available, reliable current circuit supervision can bearranged by comparing the currents from the two sets. If an error in any CT circuit isdetected, the protection functions concerned can be blocked and an alarm will begiven.
In case of large currents, unequal transient saturation of CT cores with differentremanence or different saturation factor may result in differences in the secondarycurrents from the two CT sets. Unwanted blocking of protection functions during thetransient stage must then be avoided.
Current circuit supervision CCSSPVC must be sensitive and have short operate timein order to prevent unwanted tripping from fast-acting, sensitive numericalprotections in case of faulty CT secondary circuits.
Open CT circuits creates extremely high voltages in the circuits whichis extremely dangerous for the personnel. It can also damage theinsulation and cause new problems. The application shall, thus, bedone with this in consideration, especially if the protection functionsare blocked.
1MRK 506 375-UEN - Section 11Secondary system supervision
Railway application RER670 2.2 IEC 205Application manual
11.1.3 Setting guidelines
The parameters for Current circuit supervision CCSSPVC are set via local HMI orProtection and Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select GBASVAL function for reference of base values.
Operation: This is used for current circuit supervision function Off/On.
Current circuit supervision CCSSPVC compares the residual current from a two-phase set of current transformer cores with the neutral point current on a separate inputtaken from another set of cores on the same current transformer.
IMinOp: It must be set as a minimum to twice the residual current in the supervised CTcircuits under normal service conditions and rated primary current.
Ip>Block: It is normally set at 150% to block the function during transient conditions.
The FAIL output is connected to the blocking input of the protection function to beblocked at faulty CT secondary circuits.
11.2 Fuse failure supervision FRWSPVC
11.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Fuse failure supervision FRWSPVC - -
11.2.2 Application
Different protection functions within the protection IED, operates on the basis of themeasured voltage at the relay point. Examples are:
• Impedance protection functions• Undervoltage function• Energizing check function and voltage check for the weak infeed logic
These functions can operate unintentionally if a fault occurs in the secondary circuitsbetween the voltage instrument transformers and the IED.
It is possible to use different measures to prevent such unwanted operations. Miniaturecircuit breakers in the voltage measuring circuits should be located as close as possible
Section 11 1MRK 506 375-UEN -Secondary system supervision
206 Railway application RER670 2.2 IECApplication manual
to the voltage instrument transformers, and shall be equipped with auxiliary contactsthat are wired to the IEDs. Separate fuse-failure monitoring IEDs or elements withinthe protection and monitoring devices are another possibilities. These solutions arecombined to get the best possible effect in the fuse failure supervision function(FRWSPVC).
FRWSPVC function built into the IED products can operate on the basis of externalbinary signals from the miniature circuit breaker or from the line disconnector. Thefirst case influences the operation of all voltage-dependent and underimpedanceprotection functions while the second one does not affect the impedance measuringfunctions.
In the event of failure of measuring circuit voltage, the underimpedance protectionfunction will be blocked for a set time if residual current exists during the blockingtime.
A criterion based on delta current and delta voltage measurements is used as the fusefailure supervision function in order to detect a fuse failure.
11.2.3 Setting guidelines
The parameters for fuse failure supervision FRWSPVC are set via the local HMI orProtection and Control Manager PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in the global base values for settings functionGBASVAL.
GlobalBaseSel: This is used to select GBASVAL function for reference of basevalues.
Operation: This is used for fuse failure supervision Off/On.
11.2.3.1 DeltaU and DeltaI detection
To avoid unwanted operation due to the normal switching conditions in the network,the DU> setting should be set high (approximately 60% of UBase) and the currentthreshold DI< setting should be set low (approximately 10% of IBase).
If USetprim is the primary voltage for dU/dt operation:
UBaseUSetDU prim /)100(
IECEQUATION215 V1 EN
If ISetprim is the primary current for dI/dt operation:
IBaseISetDI prim /)100(
IECEQUATION216 V1 EN
1MRK 506 375-UEN - Section 11Secondary system supervision
Railway application RER670 2.2 IEC 207Application manual
The voltage threshold UPh> is used to identify low voltage condition in the system.Set UPh> below the minimum operating voltage during emergency conditions. Asafety margin of approximately 70% of UBase is recommended.
The current threshold IPh> should be set lower than the IMinOp for the distanceprotection function. A safety margin of 5–10% lower value is recommended.
The setting INDeblock is used to block or deblock the underimpedance protection ifresidual current exists during fuse failure conditions in the voltage measuring circuit.
The residual current threshold 2I0< should be set above the maximum occurringresidual current during normal loading conditions.
The timer tIN is used to delay the deblocking of underimpedance protection functionsif required. A default value of 5.0 s is given.
11.2.3.2 Dead line detection
The condition for operation of the dead line detection is set by the parameters IDLD<for the current threshold and UDLD< for the voltage threshold.
Set the IDLD< with a sufficient margin below the minimum expected load current. Asafety margin of at least 15-20% is recommended. The operate value must howeverexceed the maximum charging current of an overhead line, when only one phase isdisconnected (mutual coupling to the other phases).
Set the UDLD< with a sufficient margin below the minimum expected operatingvoltage. A safety margin of at least 15% is recommended.
11.2.4 Sudden current and voltage change
Several instances of FRWSPVC function are available. Therefore if required byapplication, one instance of this function can also be used for sudden current andvoltage change detection. This information, for example, can be used in IEDconfiguration logic to enable higher distance protection zones for catenaryapplications.
Section 11 1MRK 506 375-UEN -Secondary system supervision
208 Railway application RER670 2.2 IECApplication manual
Section 12 Control
12.1 Synchrocheck, energizing check, and synchronizingSESRSYN
12.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Synchrocheck, energizing check, andsynchronizing
SESRSYN
sc/vc
SYMBOL-M V1 EN
25
12.1.2 Application
12.1.2.1 Synchronizing
To allow closing of breakers between asynchronous networks, a synchronizingfeature is provided. The breaker close command is issued at the optimum time whenconditions across the breaker are satisfied in order to avoid stress on the network andits components.
The systems are defined as asynchronous when the frequency difference between busand line is larger than an adjustable parameter. If the frequency difference is less thanthis threshold value the system is defined to have a parallel circuit and thesynchrocheck function is used.
The synchronizing function measures the difference between the U-Line and the U-Bus. It operates and enables a closing command to the circuit breaker when thecalculated closing angle is equal to the measured phase angle and the followingconditions are simultaneously fulfilled:
• The voltages U-Line and U-Bus are higher than the set values forUHighBusSynch and UHighLineSynch of the respective base voltagesGblBaseSelBus and GblBaseSelLine.
• The difference in the voltage is smaller than the set value of UDiffSynch.• The difference in frequency is less than the set value of FreqDiffMax and larger
than the set value of FreqDiffMin. If the frequency is less than FreqDiffMin thesynchrocheck is used and the value of FreqDiffMin must thus be identical to thevalue FreqDiffM resp FreqDiffA for synchrocheck function. The bus and line
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 209Application manual
frequencies must also be within a range of ±10% from the rated frequency. Whenthe synchronizing option is included also for autoreclose there is no reason tohave different frequency setting for the manual and automatic reclosing and thefrequency difference values for synchronism check should be kept low.
• The frequency rate of change is less than set value for both U-Bus and U-Line.• The difference in the phase angle is smaller than the set value of CloseAngleMax.• The closing angle is decided by the calculation of slip frequency and required pre-
closing time.
The synchronizing function compensates for the measured slip frequency as well asthe circuit breaker closing delay. The phase angle advance is calculated continuously.The calculation of the operation pulse sent in advance is using the measuredSlipFrequency and the set tBreaker time. To prevent incorrect closing pulses, amaximum closing angle between bus and line is set with CloseAngleMax. Table 23below shows the maximum settable value for tBreaker when CloseAngleMax is set to15 or 30 degrees, at different allowed slip frequencies for synchronizing. To minimizethe moment stress when synchronizing near a power station, a narrower limit for theCloseAngleMax needs to be used.
Table 23: Dependencies between tBreaker and SlipFrequency with different CloseAngleMaxvalues
tBreaker [s] (max settable value)with CloseAngleMax = 15degrees [default value]
tBreaker [s] (max settable value)with CloseAngleMax = 30 degrees[max value]
SlipFrequency [Hz](BusFrequency -LineFrequency)
0.040 0.080 1.000
0.050 0.100 0.800
0.080 0.160 0.500
0.200 0.400 0.200
0.400 0.810 0.100
1.000 0.080
0.800 0.050
1.000 0.040
The reference voltage can be phase-neutral L1, L2 or positive sequence. By setting thephases used for SESRSYN, with the settings SelPhaseBus and SelPhaseLine, acompensation has to be made for the phase angle difference caused if different settingvalues are selected for the two sides of the breaker. This compensation has to be donewith the PhaseShift setting according to Table 24.
Section 12 1MRK 506 375-UEN -Control
210 Railway application RER670 2.2 IECApplication manual
Table 24: Selection of phase shift for different combinations of SelPhaseBus and SelPhaseLine
SelPhase Bus SelPhase Line PhaseShift in degreesPhase L1 or Positive sequence Phase L1 or Positive sequence 0
Phase L1 or Positive sequence Phase L2 180
Phase L2 Phase L1 or Positive sequence 180
Phase L2 Phase L2 0
12.1.2.2 Synchrocheck
The main purpose of the synchrocheck function is to provide control over closingcircuit breakers in power networks. The purpose for providing control is to prevent theclosing if the conditions of synchronism are not detected. It is also used to prevent re-connection of two systems, which are divided after islanding/after a two polereclosing.
Sometimes first shot in the auto-reclosing cycle shall be performedwithout using synchrocheck for railway applications. For such caseshigh-speed shot within the auto-reclosing function shall be used.
SESRSYN function block includes both the synchrocheck and the energizingfeatures. The energizing function allows closing when one side of the breaker is dead.
IEC16000121-1-en.vsdx
IEC16000121 V1 EN
Figure 63: Two interconnected power systems
Figure 63 shows two interconnected power systems. The cloud means that theinterconnection can be further away, that is, a weak connection through other stations.The need for a check of synchronization increases if the meshed system decreasessince the risk of the two networks being out of synchronization at manual or automaticclosing is greater.
The synchrocheck function measures the conditions across the circuit breaker andcompares against the set limits. Output is generated only when all measuredconditions are within the respective set limits simultaneously. The check consists of:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 211Application manual
• Live line and live bus.• Voltage level difference.• Frequency difference (slip). The bus and line frequency must also be within a
range of ±10% deviated from rated frequency.• Phase angle difference.
A time delay is available to ensure that the conditions are fulfilled for a minimumperiod of time.
In stable power systems, the frequency difference is insignificant or zero for manuallyinitiated closing or closing by automatic restoration. In steady conditions, a biggerphase angle difference can be allowed as this is sometimes the case in a long andloaded parallel power line. For this application we accept a synchrocheck with a longoperation time and high sensitivity regarding the frequency difference. The phaseangle difference setting can be set for steady state conditions.
Another example is the operation of a power network that is disturbed due to a faultevent: After the fault clearance a highspeed auto-reclosing takes place. This can causea power swing in the network and the phase angle difference may begin to oscillate.Generally, the frequency difference is the time derivative of the phase angle differenceand typically oscillates between positive and negative values. When the circuitbreaker needs to be closed by auto-reclosing after fault-clearance some frequencydifference should be tolerated. But if a big and increasing phase angle difference isallowed at the same time, there is some risk in auto-reclosing. In this case it is safer toclose when the phase angle difference is smaller.
To fulfill the requirements above, the synchrocheck function is provided with separatesettings for steady (Manual) conditions and operation under disturbed conditions(Auto).
Section 12 1MRK 506 375-UEN -Control
212 Railway application RER670 2.2 IECApplication manual
SynchroCheck
UHighBusSC > 10 - 120 % of GblBaseSelBus
UHighLineSC > 10 - 120 % of GblBaseSelLine
UDiffSC < 0.02 – 0.50 p.u.
PhaseDiffM < 5 - 90 degrees
PhaseDiffA < 5 - 90 degrees
FreqDiffM < 3 - 1000 mHz
FreqDiffA < 3 - 1000 mHz
Fuse fail
Fuse fail
Line voltage Linereferencevoltage
Bus voltage
IEC16000122-1-en.vsdx
IEC16000122 V1 EN
Figure 64: Principle for the synchrocheck function
12.1.2.3 Energizing check
The main purpose of the energizing check function is to facilitate the controlled re-connection of disconnected lines and buses to energized buses and lines.
The energizing check function measures the bus and line voltages and compares themto both high and low threshold values. The output is given only when the actualmeasured conditions match the set conditions. Figure 65 shows two substations,where one (1) is energized and the other (2) is not energized. The line between CB Aand CB B is energized (DLLB) from substation 1 via the circuit breaker A andenergization of station 2 is done by CB B energization check device for that breakerDBLL. (or Both).
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 213Application manual
~
1 2 A
EnergizingCheckUHighBusEnerg > 10 - 120 % of GblBaseSelBus
UHighLineEnerg > 10 - 120 % of GblBaseSelLine
ULowBusEnerg < 10 - 80 % of GblBaseSelBus
ULowLineEnerg < 10 - 80 % of GblBaseSelLine
UMaxEnerg < 50 - 180 % of GblBaseSelBus and/or
GblBaseSelLine
Line voltageBus voltage
IEC17000008-1-en.vsdx
B
IEC17000008 V1 EN
Figure 65: Principle for the energizing check function
The energizing operation can operate in the dead line live bus (DLLB) direction, deadbus live line (DBLL) direction, or in both directions over the circuit breaker.Energizing from different directions can be different for automatic reclosing andmanual closing of the circuit breaker. For manual closing it is also possible to allowclosing when both sides of the breaker are dead, Dead Bus Dead Line (DBDL).
The equipment is considered energized (Live) if the voltage is above the set value forUHighBusEnerg or UHighLineEnerg of the base voltages GblBaseSelBus andGblBaseSelLine, which are defined in the Global Base Value groups; in a similar way,the equipment is considered non-energized (Dead) if the voltage is below the set valuefor ULowBusEnerg or ULowLineEnerg of the respective Global Base Value groups.A disconnected line can have a considerable potential due to factors such as inductionfrom a line running in parallel, or feeding via extinguishing capacitors in the circuitbreakers. This voltage can be as high as 50% or more of the base voltage of the line.Normally, for breakers with single breaking elements (<330 kV) the level is wellbelow 30%.
When the energizing direction corresponds to the settings, the situation has to remainconstant for a certain period of time before the close signal is permitted. The purposeof the delayed operate time is to ensure that the dead side remains de-energized andthat the condition is not due to temporary interference.
12.1.2.4 External fuse failure
Either external fuse-failure signals or signals from a tripped miniature circuit breakerare connected to HW binary inputs of the IED; these signals are connected to inputsof SESRSYN function in the application configuration tool of PCM600. The internalfuse failure supervision function can also be used if a two-phase voltage is present.The signal BLKU, from the internal fuse failure supervision function, is then used andconnected to the fuse supervision inputs of the SESRSYN function block. In case ofa fuse failure, the SESRSYN energizing function shall be blocked.
Section 12 1MRK 506 375-UEN -Control
214 Railway application RER670 2.2 IECApplication manual
The UBOK and UBFF inputs are related to the busbar voltage and the ULNOK andULNFF inputs are related to the line voltage.
External selection of energizing directionThe energizing can be selected by use of the available logic function blocks. Below isan example where the choice of mode is done from a symbol ,created in the GraphicalDesign Editor (GDE) tool on the local HMI, through selector switch function block,but alternatively there can for example, be a physical selector switch on the front of thepanel which is connected to a binary to integer function block (B16I).
If the PSTO input is used, connected to the Local-Remote switch on the local HMI, thechoice can also be from the station HMI system, typically ABB Microscada throughIEC 61850–8–1 communication.
The connection example for selection of the manual energizing mode is shown infigure 66. Selected names are just examples but note that the symbol on the local HMIcan only show the active position of the virtual selector.
IEC17000001-1-en.vsdx
SESRSYNU2PBB*
U2PLN*
BLOCK
BLKSYNCH
BLKSC
BLKENERG
UBOK
UBFF
ULNOK
ULNFF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
USELFAIL
SYNPROGR
SYNFAIL
UOKSYN
UDIFFSYN
FRDIFSYN
FRDIFFOK
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
SLGAPCBLOCK
PSTO
UP
DOWN
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
P22
P23
P24
P25
P26
P27
P28
P29
P30
P31
P32
SWPOSN
INTONE
U2PBB
U2PLN
IEC17000001 V1 EN
Figure 66: Selection of the energizing direction from a local HMI symbol througha selector switch function block.
12.1.3 Application examples
The synchronizing function block can be used in different switchyard arrangements,but with different parameter settings. An example is given below.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 215Application manual
The input used below in example are typical and can be changed byuse of configuration and signal matrix tools.
12.1.3.1 Single circuit breaker with single busbar
WA1_MCB
LINE
WA1
QB1
QA1
IEC16000123-1-en.vsdx
LINE_VT
LINE_MCB
WA1_MCB
SESRSYNU2PBB*
U2PLN*
UBOK
UBFF
ULOK
ULFF
WA1_VT
WA1_VT
LINE_VT
LINE_MCB
WA1_MCB
IEC16000123 V1 EN
Figure 67: Connection of SESRSYN function block in a single busbararrangement
Figure 67 illustrates connection principles for a single busbar. For the SESRSYNfunction there is one voltage transformer on each side of the circuit breaker. Thevoltage transformer circuit connections are straightforward; no special voltageselection is necessary.
The voltage from busbar VT is connected to U2PBB and the voltage from the line VTis connected to U2PLN. The conditions of the VT fuses shall also be connected asshown above.
12.1.4 Setting guidelines
The setting parameters for the Synchronizing, synchrocheck and energizing checkfunction SESRSYN are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN function via the LHMI.
Common base IED value for primary voltage ( UBase ) is set in a Global base valuefunction, GBASVAL, found under Main menu//Configuration/Power system/GlobalBaseValue/GBASVAL_X/UBase. The SESRSYN function has one settingfor the bus reference voltage (GblBaseSelBus) and one setting for the line referencevoltage (GblBaseSelLine) which independently of each other can be set to select oneof the twelve GBASVAL functions used for reference of base values (e.g. when apower transformer is installed in-between two VTs used for the function). This means
Section 12 1MRK 506 375-UEN -Control
216 Railway application RER670 2.2 IECApplication manual
that the reference voltage of bus and line can be set to different values. The settings forthe SESRSYN function are found under Main menu/Settings/IED Settings/Control/Synchronizing(25,SC/VC)/SESRSYN(25,SC/VC):X has been dividedinto four different setting groups: General, Synchronizing, Synchrocheck andEnergizingcheck.
General settingsOperation: The operation mode can be set On or Off. The setting Off disables thewhole function.
GblBaseSelBus and GblBaseSelLine
These configuration settings are used for selecting one of twelve GBASVALfunctions, which then is used as base value reference voltage, for bus and linerespectively.
SelPhaseBus
Configuration parameters for selecting the measuring phase of the voltage for busbar,which can be a single-phase (phase-neutral) or a positive sequence voltage.
SelPhaseLine
Configuration parameters for selecting the measuring phase of the voltage for line,which can be a single-phase (phase-neutral) or a positive sequence voltage.
PhaseShift
This setting is used to compensate the phase shift between the measured bus voltageand line voltage when:
• different phase-neutral voltages are selected (for example UL1 for bus and UL2for line);
• one available voltage is positive sequence and the other one is phase-neutral (forexample Pos. Seq. for bus and UL2 for line).
The set value is added to the measured line phase angle. The bus voltage is referencevoltage.
Synchronizing settingsOperationSynch
The setting Off disables the Synchronizing function. With the setting On, the functionis in the service mode and the output signal depends on the input conditions.
UHighBusSynch and UHighLineSynch
The voltage level settings shall be chosen in relation to the bus/line network voltage.The threshold voltages UHighBusSynch and UHighLineSynch have to be set lower
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 217Application manual
than the value where the network is expected to be synchronized. A typical value is80% of the rated voltage.
UDiffSynch
Setting of the voltage difference between the line voltage and the bus voltage. Thedifference is set depending on the network configuration and expected voltages in thetwo networks running asynchronously. A normal setting is 0.10-0.15 p.u.
FreqDiffMin
The setting FreqDiffMin is the minimum frequency difference where the systems aredefined to be asynchronous. For frequency differences lower than this value, thesystems are considered to be in parallel. A typical value for FreqDiffMin is 10 mHz.Generally, the value should be low if both synchronizing and synchrocheck functionsare provided, and it is better to let the synchronizing function close, as it will close atexactly the right instance if the networks run with a frequency difference.
To avoid overlapping of the synchronizing function and thesynchrocheck function the setting FreqDiffMin must be set to a highervalue than used setting FreqDiffM, respective FreqDiffA used forsynchrocheck.
FreqDiffMax
The setting FreqDiffMax is the maximum slip frequency at which synchronizing isaccepted. 1/FreqDiffMax shows the time for the vector to move 360 degrees, one turnon the synchronoscope, and is called Beat time. A typical value for FreqDiffMax is200-250 mHz, which gives beat times on 4-5 seconds. Higher values should beavoided as the two networks normally are regulated to nominal frequencyindependent of each other, so the frequency difference shall be small.
FreqRateChange
The maximum allowed rate of change for the frequency.
CloseAngleMax
The setting CloseAngleMax is the maximum closing angle between bus and line atwhich synchronizing is accepted. To minimize the moment stress when synchronizingnear a power station, a narrower limit should be used. A typical value is 15 degrees.
tBreaker
The tBreaker shall be set to match the closing time for the circuit breaker and shouldalso include the possible auxiliary relays in the closing circuit. It is important to checkthat no slow logic function blocks (e.g. in 100ms loop) are used in the configurationof the IED as there then can be big variations in closing time due to those components.Typical setting is 80-150 ms depending on the breaker closing time.
Section 12 1MRK 506 375-UEN -Control
218 Railway application RER670 2.2 IECApplication manual
tClosePulse
The setting for the duration of the breaker close pulse.
tMaxSynch
The setting tMaxSynch is set to reset the operation of the synchronizing function if theoperation does not take place within this time. The setting must allow for the setting ofFreqDiffMin, which will decide how long it will take maximum to reach phaseequality. At the setting of 10 mHz, the beat time is 100 seconds and the setting wouldthus need to be at least tMinSynch plus 100 seconds. If the network frequencies areexpected to be outside the limits from the start, a margin needs to be added. A typicalsetting is 600 seconds.
tMinSynch
The setting tMinSynch is set to limit the minimum time at which the synchronizingclosing attempt is given. The synchronizing function will not give a closing commandwithin this time, from when the synchronizing is started, even if a synchronizingcondition is fulfilled. A typical setting is 200 ms.
Synchrocheck settingsOperationSC
The OperationSC setting Off disables the synchrocheck function and sets the outputsAUTOSYOK, MANSYOK, TSTAUTSY and TSTMANSY to low. With the settingOn, the function is in the service mode and the output signal depends on the inputconditions.
UHighBusSC and UHighLineSC
The voltage level settings must be chosen in relation to the bus or line network voltage.The threshold voltages UHighBusSC and UHighLineSC have to be set lower than thevalue at which the breaker is expected to close with the synchronism check. A typicalvalue can be 80% of the base voltages.
UDiffSC
The setting for voltage difference between line and bus in p.u. This setting in p.u. isdefined as (U-Bus/GblBaseSelBus) - (U-Line/GblBaseSelLine). A normal setting is0,10-0,15 p.u.
FreqDiffM and FreqDiffA
The frequency difference level settings, FreqDiffM and FreqDiffA, shall be chosendepending on the condition in the network. At steady conditions a low frequencydifference setting is needed, where the FreqDiffM setting is used. For autoreclosing abigger frequency difference setting is preferable, where the FreqDiffA setting is used.A typical value for FreqDiffM can be10 mHz, and a typical value for FreqDiffA canbe 100-200 mHz.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 219Application manual
PhaseDiffM and PhaseDiffA
The phase angle difference level settings, PhaseDiffM and PhaseDiffA, shall also bechosen depending on conditions in the network. The phase angle setting must bechosen to allow closing under maximum load condition. A typical maximum value inheavy-loaded networks can be 45 degrees, whereas in most networks the maximumoccurring angle is below 25 degrees. The PhaseDiffM setting is a limitation toPhaseDiffA setting. Fluctuations occurring at high speed autoreclosing limitPhaseDiffA setting.
tSCM and tSCA
The purpose of the timer delay settings, tSCM and tSCA, is to ensure that thesynchrocheck conditions remains constant and that the situation is not due to atemporary interference. Should the conditions not persist for the specified time, thedelay timer is reset and the procedure is restarted when the conditions are fulfilledagain. Circuit breaker closing is thus not permitted until the synchrocheck situationhas remained constant throughout the set delay setting time. Manual closing isnormally under more stable conditions and a longer operation time delay setting isneeded, where the tSCM setting is used. During auto-reclosing, a shorter operationtime delay setting is preferable, where the tSCA setting is used. A typical value fortSCM can be 1 second and a typical value for tSCA can be 0.1 seconds.
Energizingcheck settingsAutoEnerg and ManEnerg
Two different settings can be used for automatic and manual closing of the circuitbreaker. The settings for each of them are:
• Off, the energizing function is disabled.• DLLB, Dead Line Live Bus, the line voltage is below set value of
ULowLineEnerg and the bus voltage is above set value of UHighBusEnerg.• DBLL, Dead Bus Live Line, the bus voltage is below set value of ULowBusEnerg
and the line voltage is above set value of UHighLineEnerg.• Both, energizing can be done in both directions, DLLB or DBLL.
ManEnergDBDL
If the parameter is set to On, manual closing is also enabled when both line voltage andbus voltage are below ULowLineEnerg and ULowBusEnerg respectively, andManEnerg is set to DLLB, DBLL or Both.
UHighBusEnerg and UHighLineEnerg
The voltage level settings must be chosen in relation to the bus or line network voltage.The threshold voltages UHighBusEnerg and UHighLineEnerg have to be set lowerthan the value at which the network is considered to be energized. A typical value canbe 80% of the base voltages.
ULowBusEnerg and ULowLineEnerg
Section 12 1MRK 506 375-UEN -Control
220 Railway application RER670 2.2 IECApplication manual
The threshold voltages ULowBusEnerg and ULowLineEnerg, have to be set to a valuegreater than the value where the network is considered not to be energized. A typicalvalue can be 40% of the base voltages.
A disconnected line can have a considerable potential due to, forinstance, induction from a line running in parallel, or by being fed viathe extinguishing capacitors in the circuit breakers. This voltage canbe as high as 30% or more of the base line voltage.
Because the setting ranges of the threshold voltages UHighBusEnerg/UHighLineEnerg and ULowBusEnerg/ULowLineEnerg partly overlap each other, thesetting conditions may be such that the setting of the non-energized threshold value ishigher than that of the energized threshold value. The parameters must therefore be setcarefully to avoid overlapping.
UMaxEnerg
This setting is used to block the closing when the voltage on the live side is above theset value of UMaxEnerg.
tAutoEnerg and tManEnerg
The purpose of the timer delay settings, tAutoEnerg and tManEnerg, is to ensure thatthe dead side remains de-energized and that the condition is not due to a temporaryinterference. Should the conditions not persist for the specified time, the delay timeris reset and the procedure is restarted when the conditions are fulfilled again. Circuitbreaker closing is thus not permitted until the energizing condition has remainedconstant throughout the set delay setting time.
12.2 Autoreclosing for railway system SMBRREC
12.2.1 IdentificationFunction Description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Autoreclosing for railway system SMBRREC
5(0 -->1)
IEC15000204 V1 EN
79
12.2.2 Application
Automatic reclosing is a well-established method for the restoration of service in apower system after a transient line fault. The majority of line faults are flashovers,
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 221Application manual
which are transient by nature. When the power line is switched off by the operation ofline protection and line breakers, the arc de-ionizes and recovers its ability towithstand voltage at a somewhat variable rate. Thus, a certain dead time with a de-energized line is necessary. Line service can then be resumed by automatic reclosingof the line breakers. The dead time selected should be long enough to ensure a highprobability of arc de-ionization and successful reclosing.
For individual line breakers, auto reclosing equipment, the required circuit breakerdead time is used to determine the “dead time” setting value. When simultaneoustripping and reclosing at the two line ends occurs, line dead time is approximatelyequal to the auto recloser “dead time”. If the auto reclosing dead time and line “deadtime” differ then, the line will be energized until the breakers at both ends haveopened.
Open
Closed
Operate time
Line
protection
Circuit
breaker
Break time
Tri
p c
om
man
d
Conta
cts s
ep
ara
ted
Arc
extin
gu
ish
ers
Fault duration Circuit breaker open time Fault duration
Resets
Insta
nt
of
fault
Op
era
tes
Break timeClosing time
Operate time
Fa
ult
Op
era
tes
Resets
Clo
se c
om
ma
nd
Conta
ct c
lose
d
Set AR dead time Reclaim timeAuto-reclosing
function
Sta
rt A
R
Reclo
sin
g
com
ma
nd
AR
reset
IEC04000146-3-en.vsd
IEC04000146 V3 EN
Figure 68: Single-shot automatic reclosing at a permanent fault
Automatic reclosing can be performed with or without the use of synchrocheck.
For the individual line breakers and auto reclosing equipment, the auto reclosing deadtime expression is used. This is the dead time setting for the auto recloser. Duringsimultaneous tripping and reclosing at the two line ends, auto reclosing dead time isapproximately equal to the line dead time. Otherwise these two times may differ asone line end might have a slower trip than the other end which means that the line willnot be dead until both ends have opened.
Section 12 1MRK 506 375-UEN -Control
222 Railway application RER670 2.2 IECApplication manual
If the fault is permanent, the line protection will trip again when reclosing is attemptedin order to clear the fault.
It is common to use one automatic reclosing function per line circuit breaker (CB).When one CB per line end is used, then there is one auto- recloser per line end. If autoreclosers are included in duplicated line protection, which means two auto reclosersper CB, one should take measures to avoid uncoordinated reclosing commands.
The auto recloser can be selected to perform multiple shots. The auto reclosing deadtime can be set to give either High-Speed Automatic Reclosing (HSAR) or DelayedAutomatic Reclosing (DAR). HSAR usually means a dead time of less than 1 second.
The mode of automatic reclosing varies. Single-shot and multi-shot are in use. Thefirst shot can have a short delay, HSAR, or a longer delay, DAR. The second andfollowing reclosing shots have a rather long delay. When multiple shots are used thedead time must harmonize with the breaker duty-cycle capacity.
Automatic reclosing is usually started by the line protection and in particular byinstantaneous tripping of such protection. The auto recloser can be inhibited (blocked)when certain protection functions detecting permanent faults (e.g. thermal overloadprotection). Back-up protection zones indicating faults outside the own line aretypically connected to inhibit the auto recloser.
Automatic reclosing should not be attempted when closing a CB and energizing a lineonto a fault (SOTF), except when multiple-shots are used where shots 2 etc. will bestarted at SOTF. Auto reclosing is often combined with a release condition fromsynchrocheck and dead line or dead busbar check.
Protection systems are usually sub-divided and provided with two redundantprotection IEDs. In such systems it is common to provide auto reclosing in only oneof the sub-systems as the requirement is for fault clearance and a failure to reclosebecause of the auto recloser being out of service is not considered a major disturbance.If two auto reclosers are provided on the same breaker, the application must becarefully checked and normally one must be the master and be connected to inhibit theother auto recloser if it has started. This inhibit can, for example, be done from an autorecloser by using operation in progress signal.
A permanent fault will cause the line protection to trip again when it recloses in anattempt to energize the line.
The auto reclosing function allows a number of parameters to be adjusted.
Examples:
• number of auto reclosing shots• auto reclosing dead times for each shot
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 223Application manual
12.2.2.1 Auto reclosing operation Off and On
Operation of the automatic recloser can be set to Off and On by a setting parameter orby external control. The setting parameter Operation = Off, or On sets the function toOff or On. With the settings Operation = On and ExternalCtrl = On , the control ismade by input signal pulses to the inputs On and Off, for example, from a controlsystem or by a control switch.
When the auto recloser is set On, the SETON output is set, and the auto recloserbecomes operative if other conditions such as circuit breaker is closed and circuitbreaker is ready are also fulfilled, the READY output is activated (high). Then the autorecloser is ready to accept a start.
12.2.2.2 Start auto reclosing and conditions for start of a reclosing cycle
The usual way to start an auto reclosing cycle, or sequence, is to start it at selectivetripping by line protection by applying a signal to the START input. Starting signalscan be either, general trip signals or, only the conditions for differential, distanceprotection zone 1 and distance protection aided trip. In some cases also directionalearth fault protection aided trip can be connected to start an auto reclose attempt. Ifgeneral trip is used to start the auto recloser it is important to block it from otherfunctions that should not start an auto reclosing sequence.
In cases where one wants to differentiate auto reclosing dead time, for different powersystem configuration or at tripping by different protection stages, one can also use theSTARTHS input (start high-speed reclosing). When initiating STARTHS, the autoreclosing dead time for high-speed shot 1, t1_HS is used and the closing is donewithout checking the synchrocheck condition.
A number of conditions need to be fulfilled for the start to be accepted and a new autoreclosing cycle to be started. They are linked to dedicated inputs. The inputs are:
• CBREADY, circuit breaker ready for a reclosing cycle, for example, chargedoperating gear.
• CBCLOSED to ensure that the circuit breaker was closed when the line faultoccurred and start was applied.
• No signal at INHIBIT input that is, no blocking or inhibit signal present. After thestart has been accepted, it is latched in and an internal signal “start” is set. It canbe interrupted by certain events, like an “inhibit” signal.
12.2.2.3 Start auto reclosing from circuit breaker open information
If a user wants to initiate auto reclosing from the circuit breaker open position insteadof from protection trip signals, the function offers such a possibility. This startingmode is selected with the setting parameter StartByCBOpen=On. Typically a circuitbreaker auxiliary contact of type NO (normally open) is connected to CBCLOSED andSTART. When the signal changes from circuit breaker closed to circuit breaker openan auto reclosing start pulse is generated and latched in the function, subject to the
Section 12 1MRK 506 375-UEN -Control
224 Railway application RER670 2.2 IECApplication manual
usual checks. The auto reclosing sequence continues then as usual. Signals frommanual tripping and other functions, which shall prevent auto reclosing, need to beconnected to the INHIBIT input.
12.2.2.4 Blocking of the auto recloser
Auto reclose attempts are expected to take place only for faults on the own line. Theauto recloser must be blocked by activating the INHIBIT input for the followingconditions:
• Tripping from delayed distance protection zones• Tripping from back-up protection functions• Tripping from breaker failure function• Intertrip received from remote end circuit breaker failure function• Busbar protection tripping
Depending of the starting principle (general trip or only instantaneous trip) adoptedabove the delayed and back-up zones might not be required. Breaker failure trip localand remote must however always be connected.
12.2.2.5 Control of the auto reclosing dead time for shot 1
For the first shot, there is a separate setting for the dead time, t1. If no particular inputsignal is applied, the auto reclosing dead time t1 will be used. There is also a separatetime setting facility for high-speed auto reclosing without synchrocheck, t1_HS,available for use when required. It is activated by the STARTHS input.
12.2.2.6 Long trip signal
When start pulse duration signal is longer than set maximum start pulse duration, theauto reclosing sequence interrupts in the same way as for a signal to the INHIBITinput.
12.2.2.7 Maximum number of reclosing shots
The maximum number of auto reclosing shots in an auto reclosing cycle is selected bythe setting NoOfShots. A maximum of five shots can be done.
12.2.2.8 Auto reclosing reclaim timer
The tReclaim timer defines the time it takes from issue of the breaker closingcommand, until the auto recloser resets. Should a new trip occur during this time, it istreated as a continuation of the first fault. The reclaim timer is started when the circuitbreaker closing command is given.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 225Application manual
12.2.2.9 Pulsing of the circuit breaker closing command and counter
The circuit breaker closing command, CLOSECB is given as a pulse with a durationset by the tPulse setting. For circuit breakers without an anti-pumping function, closepulse cutting can be used. It is selected by the CutPulse setting. In case of a new startpulse (trip), the breaker closing command pulse is then cut (interrupted). Theminimum breaker closing command pulse length is always 50ms. At the issue of thebreaker closing command, the appropriate auto recloser operation counter isincremented. There is a counter for each type of auto reclosing command and one forthe total number of auto reclosing commands.
12.2.2.10 Transient fault
After the breaker closing command the reclaim timer keeps running for the settReclaim time. If no start (trip) occurs within this time, the auto recloser will reset. Thecircuit breaker remains closed and the operating gear recharges. The CBCLOSED andCBREADY input signals will be set.
12.2.2.11 Permanent fault and reclosing unsuccessful signal
If a new start occurs, and the number of auto reclosing shots is set to 1, and a newSTART or TRSOTF input signal appears, after the circuit breaker closing command,the UNSUCCL output (unsuccessful reclosing) is set high. The timer for the first shotcan no longer be started. Depending on the set number of auto reclosing shots furthershots may be made or the auto reclosing sequence is ended. After reclaim timer time-out the auto recloser resets, but the circuit breaker remains open. The circuit breakerclosed information through the CBCLOSED input is missing. Thus, the auto recloseris not ready for a new auto reclosing cycle. Normally, the UNSUCCL output appearswhen a new start is received after the last auto reclosing shot has been made and theauto recloser is inhibited. The output signal resets after reclaim time. The UNSUCCLoutput can for example, be used in multi-breaker arrangement to cancel the autoreclosing for the second circuit breaker, if the first circuit breaker closed onto apersistent fault. It can also be used to generate a lock-out of manual circuit breakerclosing until the operator has reset the lock-out, see separate section.
12.2.2.12 Lock-out initiation
In many cases there is a requirement that a lock-out is generated when the autoreclosing attempt fails. This is done with logic connected to the in- and outputs of theauto recloser and connected to binary I/O as required. Many alternative ways ofperforming the logic exist depending on whether manual circuit breaker closing isinterlocked in the IED, whether an external physical lock-out relay exists and whetherthe reset is hardwired, or carried out by means of communication. There are alsodifferent alternatives regarding what shall generate lock-out. Examples of questionsare:
Section 12 1MRK 506 375-UEN -Control
226 Railway application RER670 2.2 IECApplication manual
• shall back-up time delayed trip give lock-out (normally yes)• shall lock-out be generated when closing onto a fault (mostly)• shall lock-out be generated when the auto recloser is Off at the fault• shall lock-out be generated if the circuit breaker did not have sufficient operating
power for an auto reclosing sequence (normally not as no auto closing attempt hasbeen given)
In Figures 69 and 70 the logic shows how a closing lock-out logic can be designed withthe lock-out relay as an external relay alternatively with the lock-out created internallywith the manual closing going through the synchrocheck function. An example oflock-out logic.
Lock-out RXMD1
11
1221
MAIN ZAK CLOSE CLOSE COMMAND
SMBO
OR
SMBRREC
OR
CCRBRF
BU-TRIP
ZCVPSOF-TRIP INHIBIT
UNSUCCL
TRBU
IEC05000315-4-en.vsdIEC05000315-WMF V4 EN
Figure 69: Lock-out arranged with an external lock-out relay
CLOSE COMMAND
OR
SMBRREC
OR
CCRBRF
BU-TRIP
ZCVPSOF-TRIP INHIBIT
UNSUCCL
TRBU
SMPPTRC
AND
RESET LOCK-OUT
OR
OR
SESRSYN
Functional key,
SOFTWARE
OR IO RESET
MANSYOK
MAN CLOSE
SMBRREC CLOSE
CLLKOUT
RSTLKOUT
SETLKOUT
IEC05000316-4-en.vsdx
SMBO
MANENOK
IEC05000316-WMF V4 EN
Figure 70: Lock-out arranged with internal logic with manual closing goingthrough in IED
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 227Application manual
12.2.2.13 Thermal overload protection holding the auto recloser back
If the THOLHOLD input (thermal overload protection holding auto reclosing back) isactivated, it will keep the auto recloser on a hold until it is reset. There may thus be aconsiderable delay between start of the auto recloser and the breaker closingcommand to the circuit breaker. An external logic limiting the time and sending aninhibit to the INHIBIT input can be used. The input can also be used to set the autorecloser on hold for a longer or shorter period.
12.2.3 Setting guidelines
12.2.3.1 Configuration
Use the PCM600 configuration tool to configure signals.
Auto recloser function parameters are set via the local HMI or Parameter Setting Tool(PST). Parameter Setting Tool is a part of PCM600.
Recommendations for input signalsPlease see Figure 71 and default factory configuration for examples.
BLKOFFUsed to unblock the auto recloser when it has been blocked due to activating BLKONinput or by an unsuccessful auto reclosing attempt if the BlockByUnsucCl setting is setto On.
BLKONUsed to block the auto recloser, for example, when certain special service conditionsarise. When used, blocking must be reset with BLKOFF.
CBCLOSED and CBREADYThese binary inputs should pick-up information from the circuit breaker. At threeoperating gears in the circuit breaker (single pole operated circuit breakers) theconnection should be “All poles closed” (series connection of the NO contacts) or “Atleast one pole open” (parallel connection of NC contacts). The CBREADY is a signalmeaning that the circuit breaker is ready for an auto reclosing operation, either Close-Open (CO), or Open-Close-Open (OCO). If the available signal is of type “circuitbreaker not charged” or “not ready”, an inverter can be inserted in front of theCBREADY input.
INHIBITTo this input shall be connected signals that interrupt an auto reclosing cycle orprevent a start from being accepted. Such signals can come from protection for a lineconnected shunt reactor, from transfer trip receive, from back-up protection functions,busbar protection trip or from breaker failure protection. When the circuit breakeropen position is set to start the auto recloser, then manual opening must also be
Section 12 1MRK 506 375-UEN -Control
228 Railway application RER670 2.2 IECApplication manual
connected here. The inhibit is often a combination of signals from external IEDs viathe I/O and internal functions. An OR-gate is then used for the combination.
ON and OFFThese inputs can be connected to binary inputs or to a communication interface blockfor external control.
RESETUsed to reset the auto recloser to start conditions. Possible hold by thermal overloadprotection will be reset. Circuit breaker position will be checked and time settings willbe restarted with their set times.
RSTCOUNTThere is a counter for each type of auto reclosing and one for the total number of circuitbreaker close commands issued. All counters are reset with the RSTCOUNT input orby an IEC 61850 command.
SKIPHSThe high-speed auto reclosing sequence can be skipped and be replaced by normalauto reclosing sequence by activating SKIPHS input before the STARTHS high-speedstart input is activated. The replacement is done for the 1st shot.
STARTThe START input should be connected to the trip function (SMPPTRC) output, whichstarts the auto recloser operation. It can also be connected to a binary input for startfrom an external contact. A logical OR-gate can be used to combine the number ofstart sources.
If StartByCBOpen is used, the circuit breaker open condition shallalso be connected to the START input.
STARTHS, Start high-speed auto reclosingIt may be used when one wants to use two different dead times in different protectiontrip operations. This input starts the dead time t1_HS. High-speed reclosing shot 1started by this input is without a synchronization check.
SYNCThis input is connected to the internal synchrocheck function when required or to anexternal device for synchronism. If neither internal nor external synchronism orenergizing check is required, it can be connected to a permanently high source, TRUE.The signal is required for shots 1-5 to proceed (Note! Not the high-speed step).
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 229Application manual
THOLHOLDSignal “Thermal overload protection holding back auto reclosing”. It can beconnected to a thermal overload protection trip signal which resets only when thethermal content has fallen to an acceptable level, for example, 70%. As long as thesignal is high, indicating that the line is hot, the auto reclosing is held back. When thesignal resets, a reclosing cycle will continue. Observe that this have a considerabledelay. Input can also be used for other purposes if for some reason the auto reclosingshot needs to be halted.
TRSOTFThis is the signal “Trip by Switch Onto Fault”. It is usually connected to the “switchonto fault” output of line protection if multi-shot auto reclosing attempts are used. Theinput will start the shots two to five.
Recommendations for output signalsPlease see Figure 71 and default factory configuration for examples.
IPT1, IPT2, IPT3, IPT4 and IPT5Indicates that auto reclosing shots one to five are in progress. The signals can be usedas an indication of progress or for own logic.
ABORTEDThe ABORTED output indicates that the auto recloser is inhibited while it is in one ofthe following internal states:
• inProgress: auto recloser is started and dead time is in progress• reclaimTimeStarted: the circuit breaker closing command has started the reclaim
timer
ACTIVEIndicates that the auto recloser is active, from start until end of reclaim time.
BLOCKEDIndicates that auto recloser is temporarily or permanently blocked.
CLOSECBConnect to a binary output for circuit breaker closing command.
COUNTT1, COUNTT2, COUNTT3, COUNTT4 and COUNTT5Indicates the number of auto reclosing shots made for respective shot.
COUNTARIndicates the total number of auto reclosing shots made.
Section 12 1MRK 506 375-UEN -Control
230 Railway application RER670 2.2 IECApplication manual
INHIBOUTIf the INHIBIT input is activated it is reported on the INHIBOUT output.
INPROGRIndicates that an auto recloser sequence is in progress, from start until circuit breakerclose command.
READYIndicates that the auto recloser is ready for a new and complete auto reclosingsequence. It can be connected to the zone extension if a line protection should haveextended zone reach before auto reclosing.
SETONIndicates that auto recloser is switched on and operative.
SUCCLIf the circuit breaker closing command is given and the circuit breaker is closed withinthe set time interval tUnsucCl, the SUCCL output is activated after the set time intervaltSuccessful.
SYNCFAILThe SYNCFAIL output indicates that the auto recloser is inhibited because thesynchrocheck or energizing check condition has not been fulfilled within the set timeinterval, tSync. Also ABORTED output will be activated.
UNSUCCLIndicates unsuccessful reclosing.
Connection and setting examplesFigure 71 shows an example of how to connect the auto recloser.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 231Application manual
ON
OFF
BLKON
BLKOFF
INHIBIT
BLOCKED
SETON
INPROGR
ACTIVE
UNSUCCL
SUCCL
CLOSECB
CBREADY
CBCLOSED
RESET
START
THOLHOLD
READY
TRSOTF
SYNC
INPUT
xx
xx
xx
xx
xx
xx
xx
xx
xx
OR
OUTPUT
xx
xx
xx
xx
xx
xx
xx
xx
xx
xx
PROTECTION
xxxx-TRIP
ZCVPSOF-TRIP
SESRSYN-AUTOOK
BIM BOM
SMBRREC
STARTHS
SKIPHS
RSTCOUNT
IPT1
IPT2
IPT3
IPT4
IPT5
IEC17000005-1-en.vsdx
IEC17000005 V1 EN
Figure 71: Example of I/O-signal connections at an auto reclosing sequence
12.2.3.2 Auto recloser settings
The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.
This setting guideline describes the settings of the auto recloser using the LHMI.
The settings for the auto recloser are found under Main menu/Settings/IED Settings/Control/AutoRecloser(79,5(0->1))/SMBRREC(79,5(0->)):X and have beendivided into four different setting groups: General, CircuitBreaker, DeadTime andMasterSlave.
General settingsOperation: The operation of the auto recloser can be switched On or Off.
ExternalCtrl: This setting makes it possible to switch the auto recloser On or Off usingan external switch via IO or communication ports.
StartByCBOpen: The normal setting Off is used when the function is started byprotection trip signals. If set On the start of the auto recloser is controlled by an circuitbreaker auxiliary contact.
LongStartInhib: Usually the protection trip command, used as an auto reclosing startsignal, resets quickly as the fault is cleared. A prolonged trip command may depend
Section 12 1MRK 506 375-UEN -Control
232 Railway application RER670 2.2 IECApplication manual
on a circuit breaker failing to clear the fault. A protection trip signal present when thecircuit breaker is reclosed will result in a new trip. The user can set a maximum startpulse duration time tLongStartInh. This start pulse duration time is controlled by theLongStartInhib setting. When the start pulse duration signal is longer than setmaximum start pulse duration, the auto reclosing sequence interrupts in the same wayas for a signal to the INHIBIT input.
tLongStartInh: The user can set a maximum start pulse duration time tLongStartInh.At a set time somewhat longer than the auto reclosing dead time, this facility will notinfluence the auto reclosing. A typical setting of tLongStartInh could be close to theauto reclosing dead time.
tInhibit: To ensure reliable interruption and temporary blocking of the auto recloser aresetting time delay tInhibit is used. The auto recloser will be blocked this time afterthe deactivation of the INHIBIT input. A typical resetting delay is 5.0 s.
CircuitBreaker settingsCBReadyType: The selection depends on the type of performance available from thecircuit breaker operating gear. At setting OCO (circuit breaker ready for an Open –Close – Open cycle), the condition is checked only at the start of the auto reclosingcycle. The signal will disappear after tripping, but the circuit breaker will still be ableto perform the C-O sequence. For the selection CO (circuit breaker ready for a Close– Open cycle) the condition is also checked after the set auto reclosing dead time. Thisselection has a value first of all at multi-shot auto reclosing to ensure that the circuitbreaker is ready for a C-O sequence at shot two and further shots. During single-shotauto reclosing, the OCO selection can be used. A breaker shall according to its dutycycle always have storing energy for a CO operation after the first trip. (IEC 56 dutycycle is O – 0.3sec – CO – 3min – CO).
FollowCB: The usual setting is Follow CB = Off. The setting On can be used fordelayed auto reclosing with long delay, to cover the case when a circuit breaker isbeing manually closed during the auto reclosing dead time before the auto recloser hasissued its breaker close command.
BlockByUnsucCl: Setting of whether an unsuccessful auto reclosing attempt shall setthe auto recloser in blocked status. If used the BLKOFF input must be configured tounblock the function after an unsuccessful auto reclosing attempt. Normal setting isOff.
CutPulse: In circuit breakers without anti-pumping relays, the setting CutPulse = Oncan be used to avoid repeated closing operation when reclosing onto a fault. A newstart will then cut the ongoing pulse.
tPulse: The circuit breaker closing command should be long enough to ensure reliableoperation of the circuit breaker. The circuit breaker closing command pulse has aduration set by the tPulse setting. A typical setting may be tPulse = 200 ms. A longerpulse setting may facilitate dynamic indication at testing, for example, in debug modeof the Application Configuration Tool (ACT) in PCM600. In circuit breakers without
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 233Application manual
anti-pumping relays, the setting CutPulse = On can be used to avoid repeated closingoperations when reclosing onto a fault. A new start will then cut the ongoing pulse.
tReclaim: The reclaim time sets the time for resetting the function to its original state,after which a line fault and tripping will be treated as an independent new case with anew auto reclosing cycle. One may consider a nominal CB duty cycle of for instance,O – 0.3sec – CO – 3min – CO. However the 3 minute (180 s) recovery time is usuallynot critical as fault levels are mostly lower than rated value and the risk of a new faultwithin a short time is negligible. A typical time may be tReclaim = 60 or 180 sdependent on the fault level and circuit breaker duty cycle.
tSync: Maximum wait time for fulfilled synchrocheck conditions. The time windowshould be coordinated with the operate time and other settings of the synchrocheckfunction. Attention should also be paid to the possibility of a power swing whenreclosing after a line fault. Too short a time may prevent a potentially successful autoreclosing.
tCBClosedMin: A typical setting is 5.0 s. If the circuit breaker has not been closed forat least this minimum time, an auto reclosing start will not be accepted.
tSuccessful: If the circuit breaker closing command is given and the circuit breaker isclosed within the set time interval tUnsucCl, the SUCCL output is activated after theset time interval tSuccessful.
tUnsucCl: The reclaim timer, tReclaim, is started each time a circuit breaker closingcommand is given. If no start occurs within this time, the auto recloser will reset. Anew start received in “reclaim time” status will reenter the auto recloser to “inprogress” status as long as the final shot is not reached. The auto recloser will reset andenter “inactive” status if a new start is given during the final reclaim time. The autoreclosing sequence is considered unsuccessful and the UNSUCCL output is activated.
DeadTime settingsNoOfShots: In power transmission one shot is mostly used. In most cases one autoreclosing shot is sufficient as the majority of arcing faults will cease after the first autoreclosing shot. In power systems with many other types of faults caused by otherphenomena, for example wind, a greater number of auto reclosing attempts (shots) canbe motivated.
t1: There is a separate setting for the first shot auto reclosing dead time. Different localphenomena, such as moisture, salt, pollution, can influence the required dead time.Some users apply Delayed Auto Reclosing (DAR) with delays of 10s or more.
t1_HS: There is also a separate time setting facility for high-speed auto reclosing,t1_HS. This high-speed auto reclosing is activated by the STARTHS input and is usedwhen auto reclosing is done without the requirement of synchrocheck conditions to befulfilled. A typical dead time is 400ms.
t2 , t3, t4, t5: The delay of auto reclosing shot two and possible later shots are usuallyset at 30s or more. A check that the circuit breaker duty cycle can manage the selectedsetting must be done. The setting can in some cases be restricted by national
Section 12 1MRK 506 375-UEN -Control
234 Railway application RER670 2.2 IECApplication manual
regulations. For multiple shots the setting of shots two to five must be longer than thecircuit breaker duty cycle time.
12.3 Apparatus control APC
12.3.1 Application
The apparatus control is a functionality for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is given afterevaluation of conditions from other functions such as interlocking, synchrocheck,operator place selection and external or internal blockings.
The complete apparatus control function is not included in thisproduct, and the information below is included for understanding ofthe principle for the use of QCBAY, LOCREM, LOCREMCTRL andSXCBR.
Figure 72 shows from which places the apparatus control function receivescommands. The commands to an apparatus can be initiated from the Control Centre(CC), the station HMI or the local HMI on the IED front.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 235Application manual
Station HMI
GW
cc
Station bus
breakers disconnectors earthing switchesIEC08000227.vsd
ApparatusControl
IED
I/O
Local HMI
ApparatusControl
IED
I/O
ApparatusControl
IED
I/O
Local HMI
Local HMI
IEC08000227 V1 EN
Figure 72: Overview of the apparatus control functions
Features in the apparatus control function:
• Operation of primary apparatuses• Select-Execute principle to give high security• Selection and reservation function to prevent simultaneous operation• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Pole discordance supervision• Operation counter• Suppression of mid position
The apparatus control function is realized by means of a number of function blocksdesignated:
• Switch controller SCSWI• Circuit breaker SXCBR• Circuit switch SXSWI• Bay control QCBAY• Bay reserve QCRSV
Section 12 1MRK 506 375-UEN -Control
236 Railway application RER670 2.2 IECApplication manual
• Reservation input RESIN• Local remote LOCREM• Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 73. To realize thereservation function, the function blocks Reservation input (RESIN) and Bay reserve(QCRSV) also are included in the apparatus control function. The applicationdescription for all these functions can be found below. The function SCILO in theFigure below is the logical node for interlocking.
When the circuit breaker or switch is located in a breaker IED, two more functions areadded:
• GOOSE receive for switching device GOOSEXLNRCV• Proxy for signals from switching device via GOOSE XLNPROXY
The extension of the signal flow and the usage of the GOOSE communication areshown in Figure 74.
en05000116.vsd
IEC 61850
IEC05000116 V2 EN
Figure 73: Signal flow between apparatus control function blocks when allfunctions are situated within the IED
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 237Application manual
Merging Unit
Bay level IED
XCBRXCBR
XCBR
SCSWI
IEC 61850 on station bus
XSWI
QCBAY
SCILO
SCSWI
GOOSEXLNRCV
SCILO
XLNPROXY
GOOSEXLNRCV XLNPROXY
-QA1
-QB1
-QB9
GOOSE over process bus
IEC16000070-1-EN.vsdx
IEC16000070 V1 EN
Figure 74: Signal flow between apparatus control functions with XCBR andXSWI located in a breaker IED
Control operation can be performed from the local IED HMI. If users are defined inthe IED, then the local/remote switch is under authority control, otherwise the defaultuser can perform control operations from the local IED HMI without logging in. Thedefault position of the local/remote switch is on remote.
Section 12 1MRK 506 375-UEN -Control
238 Railway application RER670 2.2 IECApplication manual
Accepted originator categories for PSTOIf the requested command is accepted by the authority control, the value will change.Otherwise the attribute blocked-by-switching-hierarchy is set in the cause signal. Ifthe PSTO value is changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in Table 25.
Table 25: Accepted originator categories for each PSTO
Permitted Source To Operate Originator (orCat)
0 = Off 4,5,6
1 = Local 1,4,5,6
2 = Remote 2,3,4,5,6
3 = Faulty 4,5,6
4 = Not in use 4,5,6
5 = All 1,2,3,4,5,6
6 = Station 2,4,5,6
7 = Remote 3,4,5,6
PSTO = All, then it is no priority between operator places. All operator places areallowed to operate.
According to IEC 61850 standard the orCat attribute in originator category aredefined in Table 26
Table 26: orCat attribute according to IE C61850
Value Description
0 not-supported
1 bay-control
2 station-control
3 remote-control
4 automatic-bay
5 automatic-station
6 automatic-remote
7 maintenance
8 process
12.3.1.1 Bay control QCBAY
The Bay control (QCBAY) is used to handle the selection of the operator place perbay. The function gives permission to operate from two main types of locations eitherfrom Remote (for example, control centre or station HMI) or from Local (local HMIon the IED) or from all (Local and Remote). The Local/Remote switch position can
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 239Application manual
also be set to Off, which means no operator place selected that is, operation is notpossible either from local or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set todiscriminate between commands with orCat station and remote (2 and 3). Theselection is then done through the IEC 61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to differentapparatuses within the bay. There are two different blocking alternatives:
• Blocking of update of positions• Blocking of commands
IEC13000016-2-en.vsd
IEC13000016 V2 EN
Figure 75: APC - Local remote function block
12.3.1.2 Switch controller SCSWI
After the selection of an apparatus and before the execution, the switch controllerperforms the following checks and actions:
Section 12 1MRK 506 375-UEN -Control
240 Railway application RER670 2.2 IECApplication manual
• A request initiates to reserve other bays to prevent simultaneous operation.• Actual position inputs for interlocking information are read and evaluated if the
operation is permitted.• The synchrocheck/synchronizing conditions are read and checked, and performs
operation upon positive response.• The blocking conditions are evaluated• The position indications are evaluated according to given command and its
requested direction (open or closed).
The command sequence is supervised regarding the time between:
• Select and execute.• Select and until the reservation is granted.• Execute and the final end position of the apparatus.• Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
The switch controller is not dependent on the type of switching device SXCBR orSXSWI. The switch controller represents the content of the SCSWI logical node(according to IEC 61850) with mandatory functionality.
12.3.1.3 Switches SXCBR/SXSWI
Switches are functions used to close and interrupt an ac power circuit under normalconditions, or to interrupt the circuit under fault, or emergency conditions. Theintention with these functions is to represent the lowest level of a power-switchingdevice with or without short circuit breaking capability, for example, circuit breakers,disconnectors, earthing switches etc.
The purpose of these functions is to provide the actual status of positions and toperform the control operations, that is, pass all the commands to the primary apparatusvia output boards and to supervise the switching operation and position.
Switches have the following functionalities:
• Local/Remote switch intended for the switchyard• Block/deblock for open/close command respectively• Update block/deblock of position indication• Substitution of position indication• Supervision timer that the primary device starts moving after a command• Supervision of allowed time for intermediate position• Definition of pulse duration for open/close command respectively
The realizations of these functions are done with SXCBR representing a circuitbreaker and with SXSWI representing a circuit switch that is, a disconnector or anearthing switch.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 241Application manual
The content of this function is represented by the IEC 61850 definitions for the logicalnodes Circuit breaker (SXCBR) and Circuit switch (SXSWI) with mandatoryfunctionality.
12.3.1.4 Proxy for signals from switching device via GOOSE XLNPROXY
The purpose of the proxy for signals from switching device via GOOSE(XLNPROXY) is to give the same internal representation of the position status andcontrol response for a switch modeled in a breaker IED as if represented by a SXCBRor SXSWI function.
The command response functionality is dependent on the connection of the executioninformation, XIN, from the SCSWI function controlling the represented switch.Otherwise, the function only reflects the current status of the switch, such as blocking,selection, position, operating capability and operation counter.
Since different switches are represented differently on IEC 61850, the data that ismandatory to model in IEC 61850 is mandatory inputs and the other useful data for thecommand and status following is optional. To make it easy to choose which data to usefor the XLNPROXY function, their usage is controlled by the connection of eachdata’s signal input and valid input. These connections are usually from theGOOSEXLNRCV function (see Figure 76 and Figure 77).
IEC16000071 V1 EN
Figure 76: Configuration with XLNPROXY and GOOSEXLNRCV where all theIEC 61850 modelled data is used, including selection
Section 12 1MRK 506 375-UEN -Control
242 Railway application RER670 2.2 IECApplication manual
IEC16000072 V1 EN
Figure 77: Configuration with XLNPROXY and GOOSEXLNRCV where only themandatory data in the IEC 61850 modelling is used
All the information from the XLNPROXY to the SCSWI about command followingstatus, causes for failed command and selection status is transferred in the outputXPOS. The other outputs may be used by other functions in the same way as thecorresponding outputs of the SXCBR and SXSWI function.
When a command has been issued from the connected SCSWI function, theXLNPROXY function awaits the response on it from the represented switch throughthe inputs POSVAL and OPOK. While waiting for the switch to start moving, itchecks if the switch is blocked for the operation. When the switch has started movingand no blocking condition has been detected, XLNPROXY issues a response to theSCSWI function that the command has started. If OPOK is used, this response is givenwhen XLNPROXY receives the signal.
If no movement of the switch is registered within the limit tStartMove, the commandis considered failed, and the cause of the failure is evaluated. In the evaluation, thefunction checks if the state of the represented switch is indicating that the commandis blocked in any way during the command, and gives the appropriate cause to theSCSWI function. This cause is also shown on the output L_CAUSE as indicated in thefollowing table:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 243Application manual
Table 27: Possible cause values from XLNPROXY
CauseNo
Cause Description Conditions
8 Blocked-by-Mode The BEH input is 5.
2 Blocked-by-switching-hierarchy The LOC input indicates that only local commands areallowed for the breaker IED function.
-24 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is blockedfor open commands.
-25 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is blockedfor close commands.
9 Blocked-by-process If the Blk input is connected and active indicating that theswitch is dynamically blocked. Or if the OPCAP input isconnected, it indicates that the operation capability of theswitch is not enough to perform the command.
5 Position-reached Switch is already in the intended position.
-31 Switch-not-start-moving Switch did not start moving within tStartMove.
-32 Persistent-intermediate-state The switch stopped in intermediate state for longer thantIntermediate.
-33 Switch-returned-to-init-pos Switch returned to the initial position.
-34 Switch-in-bad-state Switch is in a bad position.
-35 Not-expected-final-position Switch did not reach the expected final position.
The OPCAP input and output are used for the CBOpCap data of aXCBR respectively SwOpCap for a XSWI. The interpretation for thecommand following is controlled through the setting SwitchType.
12.3.1.5 Reservation function (QCRSV and RESIN)
The purpose of the reservation function is primarily to transfer interlockinginformation between IEDs in a safe way and to prevent double operation in a bay,switchyard part, or complete substation.
For interlocking evaluation in a substation, the position information from switchingdevices, such as circuit breakers, disconnectors and earthing switches can be requiredfrom the same bay or from several other bays. When information is needed from otherbays, it is exchanged over the station bus between the distributed IEDs. The problemthat arises, even at a high speed of communication, is a space of time during which theinformation about the position of the switching devices are uncertain. Theinterlocking function uses this information for evaluation, which means that also theinterlocking conditions are uncertain.
To ensure that the interlocking information is correct at the time of operation, a uniquereservation method is available in the IEDs. With this reservation method, the bay thatwants the reservation sends a reservation request to other bays and then waits for areservation granted signal from the other bays. Actual position indications from these
Section 12 1MRK 506 375-UEN -Control
244 Railway application RER670 2.2 IECApplication manual
bays are then transferred over the station bus for evaluation in the IED. After theevaluation the operation can be executed with high security.
This functionality is realized over the station bus by means of the function blocksQCRSV and RESIN. The application principle is shown in Figure 78.
The function block QCRSV handles the reservation. It sends out either the reservationrequest to other bays or the acknowledgement if the bay has received a request fromanother bay.
The other function block RESIN receives the reservation information from other bays.The number of instances is the same as the number of involved bays (up to 60instances are available). The received signals are either the request for reservationfrom another bay or the acknowledgment from each bay respectively, which havereceived a request from this bay. Also the information of valid transmission over thestation bus must be received.
en05000117.vsd
IEDIED
From otherSCSWI inthe bay To other
SCSWIin thebay
3
Station bus
. . .
. . .
. . .
3
RESIN
EXCH_OUTEXCH_IN
RESIN
EXCH_OUTEXCH_IN
..
SCSWI
RES_RQRES_GRT
RES_DATA
QCRSV
RES_RQ1
RES_RQ8
RES_GRT1
RES_GRT8
..
2
IEC05000117 V2 EN
Figure 78: Application principles for reservation over the station bus
The reservation can also be realized with external wiring according to the applicationexample in Figure 79. This solution is realized with external auxiliary relays and extrabinary inputs and outputs in each IED, but without use of function blocks QCRSV andRESIN.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 245Application manual
SCSWI
SELECTEDRES_EXT
+
IED
BI BO
IED
BI BO
OROther SCSWI in the bay
en05000118.vsd
IEC05000118 V2 EN
Figure 79: Application principles for reservation with external wiring
The solution in Figure 79 can also be realized over the station bus according to theapplication example in Figure 80. The solutions in Figure 79 and Figure 80 do not havethe same high security compared to the solution in Figure 78, but instead have a higheravailability, since no acknowledgment is required.
SCSWI
SELECTED
RES_EXT
IEDIED
OROther SCWI inthe bay
Station bus. . .
SPGAPCIN
RESGRANT
IntlReceive
. . .
. . .
RESGRANT
IntlReceive
IEC05000178-3-en.vsd
IEC05000178 V3 EN
Figure 80: Application principle for an alternative reservation solution
12.3.2 Interaction between modules
A typical bay with apparatus control function consists of a combination of logicalnodes or functions that are described here:
Section 12 1MRK 506 375-UEN -Control
246 Railway application RER670 2.2 IECApplication manual
• The Switch controller (SCSWI) initializes all operations for one apparatus. It isthe command interface of the apparatus. It includes the position reporting as wellas the control of the position
• The Circuit breaker (SXCBR) is the process interface to the circuit breaker for theapparatus control function.
• The Circuit switch (SXSWI) is the process interface to the disconnector or theearthing switch for the apparatus control function.
• The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,such as operator place selection and blockings for the complete bay.
• The Reservation (QCRSV) deals with the reservation function.• The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or more
protection functions to a common "trip" to be transmitted to SXCBR.• The Autorecloser (SMBRREC) consists of the facilities to automatically close a
tripped breaker with respect to a number of configurable conditions.• The logical node Interlocking (SCILO) provides the information to SCSWI
whether it is permitted to operate due to the switchyard topology. Theinterlocking conditions are evaluated with separate logic and connected toSCILO .
• The Synchrocheck, energizing check, and synchronizing (SESRSYN) calculatesand compares the voltage phasor difference from both sides of an open breakerwith predefined switching conditions (synchrocheck). Also the case that one sideis dead (energizing-check) is included.
• The Generic Automatic Process Control function, GAPC, handles genericcommands from the operator to the system.
The overview of the interaction between these functions is shown in Figure 81 below.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 247Application manual
SXCBR
(Circuit breaker)
Interlocking
functionblock
(Not a LN)
SCSWI
(Switching control)
QCBAY
(Bay control)
SMBRREC
(Auto-
reclosure)I/O
Trip
Close rel.
Res. req.
Sta
rt A
R
Close CB
Position
Res. granted
Operator placeselection
SCSWI
(Switching control)
SXSWI
(Disconnector)
Open cmd
Close cmd
Position
SESRSYN
(Synchrocheck & Synchronizer)
SCILO
(Interlocking)
QCRSV
(Reservation) Res. req.
Res.
grantedGAPC
(Generic
Automatic
Process
Control) Open/Close
Open/Close
Enable
close
Enable
open
Open rel.
Close rel.
Open rel.
SMPPTRC
(Trip logic)
Position
Po
s. fr
om
oth
er
ba
ys
I/O
Open cmd
Close cmd
Synchronizing OK
Syn
ch
roch
eck
OK
Sta
rt
Syn
ch
ron
izin
g
Syn
ch
ron
izin
g
in p
rog
ress
SCILO
(Interlocking)
En
ab
leo
pe
n
En
ab
leclo
se
IEC05000120-3-EN.vsdx
IEC05000120 V3 EN
Figure 81: Example overview of the interactions between functions in a typicalbay
12.3.3 Setting guidelines
The setting parameters for the apparatus control function are set via the local HMI orPCM600.
Section 12 1MRK 506 375-UEN -Control
248 Railway application RER670 2.2 IECApplication manual
12.3.3.1 Bay control (QCBAY)
If the parameter AllPSTOValid is set to No priority, all originators from local andremote are accepted without any priority.
If the parameter RemoteIncStation is set to Yes, commands from IEC 61850-8-1clients at both station and remote level are accepted, when the QCBAY function is inRemote. If set to No, the command LocSta controls which operator place is acceptedwhen QCBAY is in Remote. If LocSta is true, only commands from station level areaccepted, otherwise only commands from remote level are accepted.
The parameter RemoteIncStation has only effect on the IEC61850-8-1 communication. Further, when using IEC 61850 edition 1communication, the parameter should be set to Yes, since thecommand LocSta is not defined in IEC 61850-8-1 edition 1.
12.3.3.2 Switch controller (SCSWI)
The parameter CtlModel specifies the type of control model according to IEC 61850.The default for control of circuit breakers, disconnectors and earthing switches thecontrol model is set to SBO Enh (Select-Before-Operate) with enhanced security.
When the operation shall be performed in one step, and no monitoring of the result ofthe command is desired, the model direct control with normal security is used.
At control with enhanced security there is an additional supervision of the status valueby the control object, which means that each command sequence must be terminatedby a termination command.
The parameter PosDependent gives permission to operate depending on the positionindication, that is, at Always permitted it is always permitted to operate independentof the value of the position. At Not perm at 00/11 it is not permitted to operate if theposition is in bad or intermediate state.
tSelect is the maximum allowed time between the select and the execute commandsignal, that is, the time the operator has to perform the command execution after theselection of the object to operate. When the time has expired, the selected output signalis set to false and a cause-code is given.
The time parameter tResResponse is the allowed time from reservation request to thefeedback reservation granted from all bays involved in the reservation function. Whenthe time has expired, the control function is reset, and a cause-code is given.
tSynchrocheck is the allowed time for the synchrocheck function to fulfill the closeconditions. When the time has expired, the function tries to start the synchronizingfunction. If tSynchrocheck is set to 0, no synchrocheck is done, before starting thesynchronizing function.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 249Application manual
The timer tSynchronizing supervises that the signal synchronizing in progress isobtained in SCSWI after start of the synchronizing function. The start signal for thesynchronizing is set if the synchrocheck conditions are not fulfilled. When the timehas expired, the control function is reset, and a cause-code is given. If nosynchronizing function is included, the time is set to 0, which means no start of thesynchronizing function is done, and when tSynchrocheck has expired, the controlfunction is reset and a cause-code is given.
tExecutionFB is the maximum time between the execute command signal and thecommand termination. When the time has expired, the control function is reset and acause-code is given.
tPoleDiscord is the allowed time to have discrepancy between the poles at control ofthree one-phase breakers. At discrepancy an output signal is activated to be used fortrip or alarm, and during a command, the control function is reset, and a cause-code isgiven.
SuppressMidPos when On suppresses the mid-position during the time tIntermediateof the connected switches.
The parameter InterlockCheck decides if interlock check should be done at both selectand operate, Sel & Op phase, or only at operate, Op phase.
12.3.3.3 Switch (SXCBR/SXSWI)
tStartMove is the supervision time for the apparatus to start moving after a commandexecution is done from the SCSWI function. When the time has expired, the commandsupervision is reset, and a cause-code is given.
During the tIntermediate time, the position indication is allowed to be in anintermediate (00) state. When the time has expired, the command supervision is reset,and a cause-code is given. The indication of the mid-position at SCSWI is suppressedduring this time period when the position changes from open to close or vice-versa ifthe parameter SuppressMidPos is set to On in the SCSWI function.
If the parameter AdaptivePulse is set to Adaptive the command output pulse resetswhen a new correct end position is reached. If the parameter is set to Not adaptive thecommand output pulse remains active until the timer tOpenPulsetClosePulse haselapsed.
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set toAdaptive, it is the maximum length of the output pulse for an open command. Thedefault length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for adisconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set toAdaptive, it is the maximum length of the output pulse for an open command. Thedefault length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for adisconnector (SXSWI).
Section 12 1MRK 506 375-UEN -Control
250 Railway application RER670 2.2 IECApplication manual
12.3.3.4 Proxy for signals from switching device via GOOSE XLNPROXY
The SwitchType setting controls the evaluation of the operating capability. IfSwitchType is set to Circuit Breaker, the input OPCAP is interpreted as a breakeroperating capability, otherwise it is interpreted as a switch operating capability.
Table 28: Operating capability values for breaker/switches
Value Breaker operating capability, CbOpCap Switch operating capability, SwOpCap1 None None
2 Open Open
3 Close – Open Close
4 Open – Close – Open Close and Open
5 Close – Open – Close – Open Larger values handled as 4, both Close andOpen
6 Open – Close – Open – Close – Open
7 more
tStartMove is the supervision time for the apparatus to start moving after a commandexecution is done from the SCSWI function. When the time has expired, the commandsupervision is reset, and a cause-code is given.
During the tIntermediate time, the position indication is allowed to be in anintermediate (00) state. When the time has expired, the command supervision is reset,and a cause-code is given. The indication of the mid-position at SCSWI is suppressedduring this time period when the position changes from open to close or vice-versa ifthe parameter SuppressMidPos is set to On in the SCSWI function.
In most cases, the same value can be used for both tStartMove and tIntermediate as inthe source function. However, tStartMove may need to be increased to accommodatefor the communication delays, mainly when representing a circuit breaker.
12.3.3.5 Bay Reserve (QCRSV)
The timer tCancelRes defines the supervision time for canceling the reservation, whenthis cannot be done by requesting bay due to for example communication failure.
When the parameter ParamRequestx (x=1-8) is set to Only own bay res. individuallyfor each apparatus (x) in the bay, only the own bay is reserved, that is, the output forreservation request of other bays (RES_BAYS) will not be activated at selection ofapparatus x.
12.3.3.6 Reservation input (RESIN)
With the FutureUse parameter set to Bay future use the function can handle bays notyet installed in the SA system.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 251Application manual
12.4 Interlocking
The main purpose of switchgear interlocking is:
• To avoid the dangerous or damaging operation of switchgear• To enforce restrictions on the operation of the substation for other reasons for
example, load configuration. Examples of the latter are to limit the number ofparallel transformers to a maximum of two or to ensure that energizing is alwaysfrom one side, for example, the high voltage side of a transformer.
This section only deals with the first point, and only with restrictions caused byswitching devices other than the one to be controlled. This means that switchinterlock, because of device alarms, is not included in this section.
Disconnectors and earthing switches have a limited switching capacity.Disconnectors may therefore only operate:
• With basically zero current. The circuit is open on one side and has a smallextension. The capacitive current is small (for example, < 5A) and powertransformers with inrush current are not allowed.
• To connect or disconnect a parallel circuit carrying load current. The switchingvoltage across the open contacts is thus virtually zero, thanks to the parallel circuit(for example, < 1% of rated voltage). Paralleling of power transformers is notallowed.
Earthing switches are allowed to connect and disconnect earthing of isolated points.Due to capacitive or inductive coupling there may be some voltage (for example <40% of rated voltage) before earthing and some current (for example < 100A) afterearthing of a line.
Circuit breakers are usually not interlocked. Closing is only interlocked againstrunning disconnectors in the same bay, and the bus-coupler opening is interlockedduring a busbar transfer.
The positions of all switching devices in a bay and from some other bays determine theconditions for operational interlocking. Conditions from other stations are usually notavailable. Therefore, a line earthing switch is usually not fully interlocked. Theoperator must be convinced that the line is not energized from the other side beforeclosing the earthing switch. As an option, a voltage indication can be used forinterlocking. Take care to avoid a dangerous enable condition at the loss of a VTsecondary voltage, for example, because of a blown fuse.
The switch positions used by the operational interlocking logic are obtained fromauxiliary contacts or position sensors. For each end position (open or closed) a trueindication is needed - thus forming a double indication. The apparatus control functioncontinuously checks its consistency. If neither condition is high (1 or TRUE), theswitch may be in an intermediate position, for example, moving. This dynamic statemay continue for some time, which in the case of disconnectors may be up to 10
Section 12 1MRK 506 375-UEN -Control
252 Railway application RER670 2.2 IECApplication manual
seconds. Should both indications stay low for a longer period, the position indicationwill be interpreted as unknown. If both indications stay high, something is wrong, andthe state is again treated as unknown.
In both cases an alarm is sent to the operator. Indications from position sensors shallbe self-checked and system faults indicated by a fault signal. In the interlocking logic,the signals are used to avoid dangerous enable or release conditions. When theswitching state of a switching device cannot be determined operation is not permitted.
For switches with an individual operation gear per phase, the evaluation must considerpossible phase discrepancies. This is done with the aid of an AND-function for bothtwo phases in each apparatus for both open and close indications. Phase discrepancieswill result in an unknown double indication state.
12.4.1 Configuration guidelines
The following sections describe how the interlocking for a certain switchgearconfiguration can be realized in the IED by using standard interlocking modules andtheir interconnections. They also describe the configuration settings. The inputs fordelivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, exceptin the following cases:
• QB9_EX2 and QB9_EX4 in modules BH_LINE_A and BH_LINE_B• QA1_EX3 in module AB_TRAFO
when they are set to 0=FALSE.
12.4.2 Interlocking for line bay ABC_LINE
12.4.2.1 Application
The interlocking for line bay (ABC_LINE) function is used for a line connected to adouble busbar arrangement with a transfer busbar according to figure 82. The functioncan also be used for a double busbar arrangement without transfer busbar or a singlebusbar arrangement with/without transfer busbar.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 253Application manual
QB1 QB2QC1
QA1
QC2
QB9QC9
WA1 (A)
WA2 (B)
WA7 (C)
QB7
en04000478.vsdIEC04000478 V1 EN
Figure 82: Switchyard layout ABC_LINE
The signals from other bays connected to the module ABC_LINE are describedbelow.
12.4.2.2 Signals from bypass busbar
To derive the signals:
Signal BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7
These signals from each line bay (ABC_LINE) except that of the own bay are needed:
Signal QB7OPTR Q7 is open
VPQB7TR The switch status for QB7 is valid.
EXDU_BPB No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
Section 12 1MRK 506 375-UEN -Control
254 Railway application RER670 2.2 IECApplication manual
QB7OPTR (bay 1)QB7OPTR (bay 2)
. . .
. . .QB7OPTR (bay n-1)
& BB7_D_OP
VPQB7TR (bay 1)VPQB7TR (bay 2)
. . .
. . .VPQB7TR (bay n-1)
& VP_BB7_D
EXDU_BPB (bay 1)EXDU_BPB (bay 2)
. . .
. . .EXDU_BPB (bay n-1)
& EXDU_BPB
en04000477.vsd
IEC04000477 V1 EN
Figure 83: Signals from bypass busbar in line bay n
12.4.2.3 Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus section.
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
ABC_LINE ABC_BCABC_LINE ABC_BC
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000479.vsd
IEC04000479 V1 EN
Figure 84: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.
BC_17_OP No bus-coupler connection between busbar WA1 and WA7.
BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.
BC_27_OP No bus-coupler connection between busbar WA2 and WA7.
BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.
VP_BC_12 The switch status of BC_12 is valid.
VP_BC_17 The switch status of BC_17 is valid.
VP_BC_27 The switch status of BC_27 is valid.
EXDU_BC No transmission error from any bus-coupler bay (BC).
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 255Application manual
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA7.
BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA7.
BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 andWA7.
BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2and WA7.
VPBC12TR The switch status of BC_12 is valid.
VPBC17TR The switch status of BC_17 is valid.
VPBC27TR The switch status of BC_27 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.
Signal DCOPTR The bus-section disconnector is open.
DCCLTR The bus-section disconnector is closed.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.
S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay that contains the above information.
For a line bay in section 1, these conditions are valid:
Section 12 1MRK 506 375-UEN -Control
256 Railway application RER670 2.2 IECApplication manual
BC12CLTR (sect.1)
DCCLTR (A1A2)DCCLTR (B1B2)
>1&
BC12CLTR (sect.2)
&VPBC12TR (sect.1)
VPDCTR (A1A2)VPDCTR (B1B2)
VPBC12TR (sect.2)
>1&
BC17OPTR (sect.1)
DCOPTR (A1A2)BC17OPTR (sect.2)
>1&
BC17CLTR (sect.1)
DCCLTR (A1A2)BC17CLTR (sect.2)
&VPBC17TR (sect.1)
VPDCTR (A1A2)VPBC17TR (sect.2)
>1&
>1&
&
&
BC27OPTR (sect.1)
DCOPTR (B1B2)BC27OPTR (sect.2)
BC27CLTR (sect.1)
DCCLTR (B1B2)BC27CLTR (sect.2)
VPBC27TR (sect.1)VPDCTR (B1B2)
VPBC27TR (sect.2)
EXDU_BC (sect.1)EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)
BC_12_CL
VP_BC_12
BC_17_OP
BC_17_CL
VP_BC_17
BC_27_OP
BC_27_CL
VP_BC_27
EXDU_BC
en04000480.vsd
IEC04000480 V1 EN
Figure 85: Signals to a line bay in section 1 from the bus-coupler bays in eachsection
For a line bay in section 2, the same conditions as above are valid by changing section1 to section 2 and vice versa.
12.4.2.4 Configuration setting
If there is no bypass busbar and therefore no QB7 disconnector, then the interlockingfor QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to open
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 257Application manual
by setting the appropriate module inputs as follows. In the functional block diagram,0 and 1 are designated 0=FALSE and 1=TRUE:
• QB7_OP = 1• QB7_CL = 0
• QC71_OP = 1• QC71_CL = 0
• BB7_D_OP = 1
• BC_17_OP = 1• BC_17_CL = 0• BC_27_OP = 1• BC_27_CL = 0
• EXDU_BPB = 1
• VP_BB7_D = 1• VP_BC_17 = 1• VP_BC_27 = 1
If there is no second busbar WA2 and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
• QB2_OP = 1• QB2_CL = 0
• QC21_OP = 1• QC21_CL = 0
• BC_12_CL = 0• BC_27_OP = 1• BC_27_CL = 0
• VP_BC_12 = 1
12.4.3 Interlocking for bus-coupler bay ABC_BC
Section 12 1MRK 506 375-UEN -Control
258 Railway application RER670 2.2 IECApplication manual
12.4.3.1 Application
The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-couplerbay connected to a double busbar arrangement according to figure 86. The functioncan also be used for a single busbar arrangement with transfer busbar or double busbararrangement without transfer busbar.
QB1 QB2
QC1
QA1
WA1 (A)
WA2 (B)
WA7 (C)
QB7QB20
QC2
en04000514.vsdIEC04000514 V1 EN
Figure 86: Switchyard layout ABC_BC
12.4.3.2 Configuration
The signals from the other bays connected to the bus-coupler module ABC_BC aredescribed below.
12.4.3.3 Signals from all feeders
To derive the signals:
Signal BBTR_OP No busbar transfer is in progress concerning this bus-coupler.
VP_BBTR The switch status is valid for all apparatuses involved in the busbar transfer.
EXDU_12 No transmission error from any bay connected to the WA1/WA2 busbars.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:
Signal QQB12OPTR QB1 or QB2 or both are open.
VPQB12TR The switch status of QB1 and QB2 are valid.
EXDU_12 No transmission error from the bay that contains the above information.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 259Application manual
For bus-coupler bay n, these conditions are valid:
QB12OPTR (bay 1)QB12OPTR (bay 2)
. . .
. . .QB12OPTR (bay n-1)
& BBTR_OP
VPQB12TR (bay 1)VPQB12TR (bay 2)
. . .
. . .VPQB12TR (bay n-1)
& VP_BBTR
EXDU_12 (bay 1)EXDU_12 (bay 2)
. . .
. . .EXDU_12 (bay n-1)
& EXDU_12
en04000481.vsd
IEC04000481 V1 EN
Figure 87: Signals from any bays in bus-coupler bay n
If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBBTR are connected in parallel - if both bus-section disconnectors are closed. So forthe basic project-specific logic for BBTR above, add this logic:
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
ABC_LINEABC_BC
ABC_LINE ABC_BC
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000482.vsd
AB_TRAFO
IEC04000482 V1 EN
Figure 88: Busbars divided by bus-section disconnectors (circuit breakers)
The following signals from each bus-section disconnector bay (A1A2_DC) areneeded. For B1B2_DC, corresponding signals from busbar B are used. The same typeof module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.
Signal DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay
Section 12 1MRK 506 375-UEN -Control
260 Railway application RER670 2.2 IECApplication manual
(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay that contains the above information.
For a bus-coupler bay in section 1, these conditions are valid:
BBTR_OP (sect.1)
DCOPTR (A1A2)DCOPTR (B1B2)
BBTR_OP (sect.2)
&VP_BBTR (sect.1)
VPDCTR (A1A2)VPDCTR (B1B2)
VP_BBTR (sect.2)
EXDU_12 (sect.1)
EXDU_DC (B1B2)EXDU_12 (sect.2)
VP_BBTR
EXDU_12
en04000483.vsd
&EXDU_DC (A1A2)
BBTR_OP
>1&
IEC04000483 V1 EN
Figure 89: Signals to a bus-coupler bay in section 1 from any bays in eachsection
For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.
12.4.3.4 Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBC_12 from the busbar coupler of the other busbar section must be transmitted to theown busbar coupler if both disconnectors are closed.
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
ABC_BCABC_BC
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000484.vsd
IEC04000484 V1 EN
Figure 90: Busbars divided by bus-section disconnectors (circuit breakers)
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 261Application manual
To derive the signals:
Signal BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
VPBC12TR The switch status of BC_12 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.
Signal DCCLTR The bus-section disconnector is closed.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal S1S2CLTR A bus-section coupler connection exists between bus sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay containing the above information.
For a bus-coupler bay in section 1, these conditions are valid:
Section 12 1MRK 506 375-UEN -Control
262 Railway application RER670 2.2 IECApplication manual
DCCLTR (A1A2)DCCLTR (B1B2)
BC12CLTR (sect.2)
VPDCTR (A1A2)VPDCTR (B1B2)
VPBC12TR (sect.2)
EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)
& BC_12_CL
VP_BC_12
EXDU_BC
en04000485.vsd
&
&
IEC04000485 V1 EN
Figure 91: Signals to a bus-coupler bay in section 1 from a bus-coupler bay inanother section
For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.
12.4.3.5 Configuration setting
If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then theinterlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
• QB2_OP = 1• QB2_CL = 0
• QB7_OP = 1• QB7_CL = 0
• QC71_OP = 1• QC71_CL = 0
If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then theinterlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,BC_12, BBTR are set to open by setting the appropriate module inputs as follows. Inthe functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:
• QB2_OP = 1• QB2_CL = 0
• QB20_OP = 1• QB20_CL = 0
• QC21_OP = 1• QC21_CL = 0
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 263Application manual
• BC_12_CL = 0• VP_BC_12 = 1
• BBTR_OP = 1• VP_BBTR = 1
12.4.4 Interlocking for transformer bay AB_TRAFO
12.4.4.1 Application
The interlocking for transformer bay (AB_TRAFO) function is used for a transformerbay connected to a double busbar arrangement according to figure 92. The function isused when there is no disconnector between circuit breaker and transformer.Otherwise, the interlocking for line bay (ABC_LINE) function can be used. Thisfunction can also be used in single busbar arrangements.
QB1 QB2QC1
QA1
QC2
WA1 (A)
WA2 (B)
QA2
QC3
T
QC4
QB4QB3
QA2 and QC4 are notused in this interlocking
AB_TRAFO
en04000515.vsdIEC04000515 V1 EN
Figure 92: Switchyard layout AB_TRAFO
The signals from other bays connected to the module AB_TRAFO are describedbelow.
Section 12 1MRK 506 375-UEN -Control
264 Railway application RER670 2.2 IECApplication manual
12.4.4.2 Signals from bus-coupler
If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus-section.
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
AB_TRAFO ABC_BCAB_TRAFO ABC_BC
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000487.vsd
IEC04000487 V1 EN
Figure 93: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as thespecific logic for the line bay (ABC_LINE):
Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration “Signals from bus-coupler“.
12.4.4.3 Configuration setting
If there are no second busbar B and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to open bysetting the appropriate module inputs as follows. In the functional block diagram, 0and 1 are designated 0=FALSE and 1=TRUE:
• QB2_OP = 1• QB2QB2_CL = 0
• QC21_OP = 1• QC21_CL = 0
• BC_12_CL = 0• VP_BC_12 = 1
If there is no second busbar B at the other side of the transformer and therefore no QB4disconnector, then the state for QB4 is set to open by setting the appropriate moduleinputs as follows:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 265Application manual
• QB4_OP = 1• QB4_CL = 0
12.4.5 Interlocking for bus-section breaker A1A2_BS
12.4.5.1 Application
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit breaker between section 1 and 2 according to figure 94. The functioncan be used for different busbars, which includes a bus-section circuit breaker.
QA1
WA1 (A1)
QB2
QC4
QB1
QC3
WA2 (A2)
en04000516.vsd
QC2QC1
A1A2_BS
IEC04000516 V1 EN
Figure 94: Switchyard layout A1A2_BS
The signals from other bays connected to the module A1A2_BS are described below.
12.4.5.2 Signals from all feeders
If the busbar is divided by bus-section circuit breakers into bus-sections and bothcircuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists between busbars on one bus-section side and if on the otherbus-section side a busbar transfer is in progress:
Section 1 Section 2
A1A2_BSB1B2_BS
ABC_LINEABC_BC
ABC_LINEABC_BC
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000489.vsd
AB_TRAFOAB_TRAFO
IEC04000489 V1 EN
Figure 95: Busbars divided by bus-section circuit breakers
Section 12 1MRK 506 375-UEN -Control
266 Railway application RER670 2.2 IECApplication manual
To derive the signals:
Signal BBTR_OP No busbar transfer is in progress concerning this bus-section.
VP_BBTR The switch status of BBTR is valid.
EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC) are needed:
Signal QB12OPTR QB1 or QB2 or both are open.
VPQB12TR The switch status of QB1 and QB2 are valid.
EXDU_12 No transmission error from the bay that contains the above information.
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA2.
VPBC12TR The switch status of BC_12 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) areneeded.
Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR The switch status of bus-section coupler BS is valid.
EXDU_BS No transmission error from the bay that contains the above information.
For a bus-section circuit breaker between A1 and A2 section busbars, these conditionsare valid:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 267Application manual
S1S2OPTR (B1B2)BC12OPTR (sect.1)
QB12OPTR (bay 1/sect.2)
QB12OPTR (bay n/sect.2)
S1S2OPTR (B1B2)BC12OPTR (sect.2)
QB12OPTR (bay 1/sect.1)
QB12OPTR (bay n /sect.1)
BBTR_OP
VP_BBTR
EXDU_12
en04000490.vsd
>1&
>1&
. . .
. . .
. . .
. . .
&
&
VPS1S2TR (B1B2)VPBC12TR (sect.1)
VPQB12TR (bay 1/sect.2)
VPQB12TR (bay n/sect.1). . .. . .
VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)
VPQB12TR (bay n/sect.1)
. . .
. . .
&
EXDU_12 (bay 1/sect.2)
EXDU_12 (bay n /sect.2)
EXDU_12(bay 1/sect.1)
EXDU_12 (bay n /sect.1)
EXDU_BS (B1B2)EXDU_BC (sect.1)
EXDU_BC (sect.2)
. . .
. . .
. . .
. . .
IEC04000490 V1 EN
Figure 96: Signals from any bays for a bus-section circuit breaker betweensections A1 and A2
For a bus-section circuit breaker between B1 and B2 section busbars, these conditionsare valid:
Section 12 1MRK 506 375-UEN -Control
268 Railway application RER670 2.2 IECApplication manual
S1S2OPTR (A1A2)BC12OPTR (sect.1)
QB12OPTR (bay 1/sect.2)
QB12OPTR (bay n/sect.2)
S1S2OPTR (A1A2)BC12OPTR (sect.2)
QB12OPTR (bay 1/sect.1)
QB12OPTR (bay n /sect.1)
BBTR_OP
VP_BBTR
EXDU_12
en04000491.vsd
>1&
>1&
. . .
. . .
. . .
. . .
&
&
VPS1S2TR (A1A2)VPBC12TR (sect.1)
VPQB12TR (bay 1/sect.2)
VPQB12TR (bay n/sect.1). . .. . .
VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)
VPQB12TR (bay n/sect.1)
. . .
. . .
&
EXDU_12(bay 1/sect.2)
EXDU_12 (bay n /sect.2)
EXDU_12 (bay 1/sect.1)
EXDU_12 (bay n /sect.1)
EXDU_BS (A1A2)EXDU_BC (sect.1)
EXDU_BC (sect.2)
. . .
. . .
. . .
. . .
IEC04000491 V1 EN
Figure 97: Signals from any bays for a bus-section circuit breaker betweensections B1 and B2
12.4.5.3 Configuration setting
If there is no other busbar via the busbar loops that are possible, then either theinterlocking for the QA1 open circuit breaker is not used or the state for BBTR is setto open. That is, no busbar transfer is in progress in this bus-section:
• BBTR_OP = 1• VP_BBTR = 1
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 269Application manual
12.4.6 Interlocking for bus-section disconnector A1A2_DC
12.4.6.1 Application
The interlocking for bus-section disconnector (A1A2_DC) function is used for onebus-section disconnector between section 1 and 2 according to figure 98. A1A2_DCfunction can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1) WA2 (A2)
QB
QC1 QC2
A1A2_DC en04000492.vsd
IEC04000492 V1 EN
Figure 98: Switchyard layout A1A2_DC
The signals from other bays connected to the module A1A2_DC are described below.
12.4.6.2 Signals in single breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition no otherdisconnector connected to the bus-section must be made by a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
ABC_LINEABC_BC
ABC_LINE
(WA1)A1(WA2)B1(WA7)C C
B3A3
en04000493.vsd
AB_TRAFOAB_TRAFO
A2B2
IEC04000493 V1 EN
Figure 99: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Section 12 1MRK 506 375-UEN -Control
270 Railway application RER670 2.2 IECApplication manual
Signal S1DC_OP All disconnectors on bus-section 1 are open.
S2DC_OP All disconnectors on bus-section 2 are open.
VPS1_DC The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB No transmission error from any bay that contains the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE).
QB220OTR QB2 and QB20 are open (ABC_BC).
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
VQB220TR The switch status of QB2 and QB20 are valid.
EXDU_BB No transmission error from the bay that contains the above information.
If there is an additional bus-section disconnector, the signal from the bus-sectiondisconnector bay (A1A2_DC) must be used:
Signal DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If there is an additional bus-section circuit breaker rather than an additional bus-section disconnector the signals from the bus-section, circuit-breaker bay (A1A2_BS)rather than the bus-section disconnector bay (A1A2_DC) must be used:
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.
For a bus-section disconnector, these conditions from the A1 busbar section are valid:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 271Application manual
QB1OPTR (bay 1/sect.A1) S1DC_OP
VPS1_DC
EXDU_BB
en04000494.vsd
&
&
&
QB1OPTR (bay n/sect.A1)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A1)
VPQB1TR (bay n/sect.A1)
EXDU_BB (bay 1/sect.A1)
EXDU_BB (bay n/sect.A1)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000494 V1 EN
Figure 100: Signals from any bays in section A1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the A2 busbar section are valid:
QB1OPTR (bay 1/sect.A2) S2DC_OP
VPS2_DC
EXDU_BB
en04000495.vsd
QB1OPTR (bay n/sect.A2)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A2)
VPQB1TR (bay n/sect.A2)VPDCTR (A2/A3)
EXDU_BB (bay n/sect.A2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (A2/A3)
EXDU_BB (bay 1/sect.A2)
EXDU_DC (A2/A3)IEC04000495 V1 EN
Figure 101: Signals from any bays in section A2 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
Section 12 1MRK 506 375-UEN -Control
272 Railway application RER670 2.2 IECApplication manual
QB2OPTR (QB220OTR)(bay 1/sect.B1) S1DC_OP
VPS1_DC
EXDU_BB
en04000496.vsd
QB2OPTR (QB220OTR)(bay n/sect.B1)
. . .
. . .
. . .
VPQB2TR (VQB220TR)(bay 1/sect.B1)
VPQB2TR (VQB220TR)(bay n/sect.B1)
EXDU_BB (bay 1/sect.B1)
EXDU_BB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
IEC04000496 V1 EN
Figure 102: Signals from any bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
QB2OPTR (QB220OTR)(bay 1/sect.B2) S2DC_OP
VPS2_DC
EXDU_BB
en04000497.vsd
QB2OPTR (QB220OTR)(bay n/sect.B2)
. . .
. . .
. . .
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B2/B3)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (B2/B3)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B2/B3)IEC04000497 V1 EN
Figure 103: Signals from any bays in section B2 to a bus-section disconnector
12.4.6.3 Signals in double-breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 273Application manual
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
DB_BUS DB_BUSDB_BUS DB_BUS
(WA1)A1(WA2)B1 B2
A2
en04000498.vsd
IEC04000498 V1 EN
Figure 104: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal S1DC_OP All disconnectors on bus-section 1 are open.
S2DC_OP All disconnectors on bus-section 2 are open.
VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.
VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.
EXDU_BB No transmission error from double-breaker bay (DB) that contains the aboveinformation.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
EXDU_DB No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration “Signals in single breakerarrangement”.
For a bus-section disconnector, these conditions from the A1 busbar section are valid:
Section 12 1MRK 506 375-UEN -Control
274 Railway application RER670 2.2 IECApplication manual
QB1OPTR (bay 1/sect.A1) S1DC_OP
VPS1_DC
EXDU_BB
en04000499.vsd
&
&
&
QB1OPTR (bay n/sect.A1)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A1)
VPQB1TR (bay n/sect.A1)
EXDU_DB (bay 1/sect.A1)
EXDU_DB (bay n/sect.A1)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000499 V1 EN
Figure 105: Signals from double-breaker bays in section A1 to a bus-sectiondisconnector
For a bus-section disconnector, these conditions from the A2 busbar section are valid:
QB1OPTR (bay 1/sect.A2) S2DC_OP
VPS2_DC
EXDU_BB
en04000500.vsd
&
&
&
QB1OPTR (bay n/sect.A2)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A2)
VPQB1TR (bay n/sect.A2)
EXDU_DB (bay 1/sect.A2)
EXDU_DB (bay n/sect.A2)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000500 V1 EN
Figure 106: Signals from double-breaker bays in section A2 to a bus-sectiondisconnector
For a bus-section disconnector, these conditions from the B1 busbar section are valid:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 275Application manual
QB2OPTR (bay 1/sect.B1) S1DC_OP
VPS1_DC
EXDU_BB
en04000501.vsd
&
&
&
QB2OPTR (bay n/sect.B1)
. . .
. . .
. . .
VPQB2TR (bay 1/sect.B1)
VPQB2TR (bay n/sect.B1)
EXDU_DB (bay 1/sect.B1)
EXDU_DB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000501 V1 EN
Figure 107: Signals from double-breaker bays in section B1 to a bus-sectiondisconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
QB2OPTR (bay 1/sect.B2) S2DC_OP
VPS2_DC
EXDU_BB
en04000502.vsd
&
&
&
QB2OPTR (bay n/sect.B2)
. . .
. . .
. . .
VPQB2TR (bay 1/sect.B2)
VPQB2TR (bay n/sect.B2)
EXDU_DB (bay 1/sect.B2)
EXDU_DB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000502 V1 EN
Figure 108: Signals from double-breaker bays in section B2 to a bus-sectiondisconnector
12.4.6.4 Signals in 1 1/2 breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.
Section 12 1MRK 506 375-UEN -Control
276 Railway application RER670 2.2 IECApplication manual
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
BH_LINE
(WA1)A1(WA2)B1 B2
A2
en04000503.vsd
BH_LINE BH_LINE BH_LINE
IEC04000503 V1 EN
Figure 109: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breakerconfiguration.
Signal S1DC_OP All disconnectors on bus-section 1 are open.
S2DC_OP All disconnectors on bus-section 2 are open.
VPS1_DC The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB No transmission error from breaker and a half (BH) that contains the aboveinformation.
12.4.7 Interlocking for busbar earthing switch BB_ES
12.4.7.1 Application
The interlocking for busbar earthing switch (BB_ES) function is used for one busbarearthing switch on any busbar parts according to figure 110.
QC
en04000504.vsd
IEC04000504 V1 EN
Figure 110: Switchyard layout BB_ES
The signals from other bays connected to the module BB_ES are described below.
12.4.7.2 Signals in single breaker arrangement
The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 277Application manual
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS)
AB_TRAFO ABC_LINEBB_ES
ABC_LINE
(WA1)A1(WA2)B1(WA7)C C
B2A2
en04000505.vsd
BB_ESABC_BC
IEC04000505 V1 EN
Figure 111: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal BB_DC_OP All disconnectors on this part of the busbar are open.
VP_BB_DC The switch status of all disconnector on this part of the busbar is valid.
EXDU_BB No transmission error from any bay containing the above information.
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)
QB220OTR QB2 and QB20 are open (ABC_BC)
QB7OPTR QB7 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
VQB220TR The switch status of QB2and QB20 is valid.
VPQB7TR The switch status of QB7 is valid.
EXDU_BB No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.
Signal DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DCare set to 1 (TRUE).
Section 12 1MRK 506 375-UEN -Control
278 Railway application RER670 2.2 IECApplication manual
If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS) rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.
For a busbar earthing switch, these conditions from the A1 busbar section are valid:
QB1OPTR (bay 1/sect.A1) BB_DC_OP
VP_BB_DC
EXDU_BB
en04000506.vsd
QB1OPTR (bay n/sect.A1)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A1)
VPQB1TR (bay n/sect.A1)VPDCTR (A1/A2)
EXDU_BB (bay n/sect.A1)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (A1/A2)
EXDU_BB (bay 1/sect.A1)
EXDU_DC (A1/A2)
IEC04000506 V1 EN
Figure 112: Signals from any bays in section A1 to a busbar earthing switch in thesame section
For a busbar earthing switch, these conditions from the A2 busbar section are valid:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 279Application manual
QB1OPTR (bay 1/sect.A2) BB_DC_OP
VP_BB_DC
EXDU_BB
en04000507.vsd
QB1OPTR (bay n/sect.A2)
. . .
. . .
. . .
VPQB1TR (bay 1/sect.A2)
VPQB1TR (bay n/sect.A2)VPDCTR (A1/A2)
EXDU_BB (bay n/sect.A2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (A1/A2)
EXDU_BB (bay 1/sect.A2)
EXDU_DC (A1/A2)
IEC04000507 V1 EN
Figure 113: Signals from any bays in section A2 to a busbar earthing switch in thesame section
For a busbar earthing switch, these conditions from the B1 busbar section are valid:
QB2OPTR(QB220OTR)(bay 1/sect.B1) BB_DC_OP
VP_BB_DC
EXDU_BB
en04000508.vsd
QB2OPTR (QB220OTR)(bay n/sect.B1)
. . .
. . .
. . .
VPQB2TR(VQB220TR) (bay 1/sect.B1)
VPQB2TR(VQB220TR) (bay n/sect.B1)VPDCTR (B1/B2)
EXDU_BB (bay n/sect.B1)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (B1/B2)
EXDU_BB (bay 1/sect.B1)
EXDU_DC (B1/B2)
IEC04000508 V1 EN
Figure 114: Signals from any bays in section B1 to a busbar earthing switch in thesame section
For a busbar earthing switch, these conditions from the B2 busbar section are valid:
Section 12 1MRK 506 375-UEN -Control
280 Railway application RER670 2.2 IECApplication manual
QB2OPTR(QB220OTR) (bay 1/sect.B2) BB_DC_OP
VP_BB_DC
EXDU_BB
en04000509.vsd
QB2OPTR(QB220OTR) (bay n/sect.B2)
. . .
. . .
. . .
VPQB2TR(VQB220TR) (bay 1/sect.B2)
VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B1/B2)
EXDU_BB (bay n/sect.B2)
. . .
. . .
. . .
. . .
. . .
. . .
&
&
&
DCOPTR (B1/B2)
EXDU_BB (bay 1/sect.B2)
EXDU_DC (B1/B2)
IEC04000509 V1 EN
Figure 115: Signals from any bays in section B2 to a busbar earthing switch in thesame section
For a busbar earthing switch on bypass busbar C, these conditions are valid:
QB7OPTR (bay 1) BB_DC_OP
VP_BB_DC
EXDU_BB
en04000510.vsd
&
&
&
QB7OPTR (bay n)
. . .
. . .
. . .
VPQB7TR (bay 1)
VPQB7TR (bay n)
EXDU_BB (bay 1)
EXDU_BB (bay n)
. . .
. . .
. . .
. . .
. . .
. . .
IEC04000510 V1 EN
Figure 116: Signals from bypass busbar to busbar earthing switch
12.4.7.3 Signals in double-breaker arrangement
The busbar earthing switch is only allowed to operate if all disconnectors of the bussection are open.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 281Application manual
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES
DB_BUS
(WA1)A1(WA2)B1 B2
A2
en04000511.vsd
DB_BUS
IEC04000511 V1 EN
Figure 117: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal BB_DC_OP All disconnectors of this part of the busbar are open.
VP_BB_DC The switch status of all disconnectors on this part of the busbar are valid.
EXDU_BB No transmission error from any bay that contains the above information.
These signals from each double-breaker bay (DB_BUS) are needed:
Signal QB1OPTR QB1 is open.
QB2OPTR QB2 is open.
VPQB1TR The switch status of QB1 is valid.
VPQB2TR The switch status of QB2 is valid.
EXDU_DB No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.
Signal DCOPTR The bus-section disconnector is open.
VPDCTR The switch status of bus-section disconnector DC is valid.
EXDU_DC No transmission error from the bay that contains the above information.
The logic is identical to the double busbar configuration described in section “Signalsin single breaker arrangement”.
12.4.7.4 Signals in 1 1/2 breaker arrangement
The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.
Section 12 1MRK 506 375-UEN -Control
282 Railway application RER670 2.2 IECApplication manual
Section 1 Section 2
A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES
BH_LINE
(WA1)A1(WA2)B1 B2
A2
en04000512.vsdBH_LINE
IEC04000512 V1 EN
Figure 118: Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic are the same as for the logic for the double busbarconfiguration described in section “Signals in single breaker arrangement”.
Signal BB_DC_OP All disconnectors on this part of the busbar are open.
VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB No transmission error from any bay that contains the above information.
12.4.8 Interlocking for double CB bay DB
12.4.8.1 Application
The interlocking for a double busbar double circuit breaker bay includingDB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to adouble busbar arrangement according to figure 119.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 283Application manual
WA1 (A)
WA2 (B)
QB1QC1
QA1
QC2
QC9
QB61
QB9
QB2QC4
QA2
QC5
QC3
QB62
DB_BUS_B
DB_LINE
DB_BUS_A
en04000518.vsdIEC04000518 V1 EN
Figure 119: Switchyard layout double circuit breaker
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE andDB_BUS_B must be used.
12.4.8.2 Configuration setting
For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:
• QB9_OP = 1• QB9_CL = 0
• QC9_OP = 1• QC9_CL = 0
If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:
• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
• VOLT_OFF = 1• VOLT_ON = 0
Section 12 1MRK 506 375-UEN -Control
284 Railway application RER670 2.2 IECApplication manual
12.4.9 Interlocking for 1 1/2 CB BH
12.4.9.1 Application
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameteraccording to figure 120.
WA1 (A)
WA2 (B)
QB1QC1
QA1
QC2
QC9
QB6
QB9
QB2QC1
QA1
QC2
QC3
QB6
QC3
QB62QB61 QA1
QC1 QC2QC9
QB9
BH_LINE_A BH_LINE_B
BH_CONNen04000513.vsd
IEC04000513 V1 EN
Figure 120: Switchyard layout 1 1/2 breaker
Three types of interlocking modules per diameter are defined. BH_LINE_A andBH_LINE_B are the connections from a line to a busbar. BH_CONN is theconnection between the two lines of the diameter in the 1 1/2 breaker switchyardlayout.
For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN andBH_LINE_B must be used.
12.4.9.2 Configuration setting
For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 285Application manual
• QB9_OP = 1• QB9_CL = 0
• QC9_OP = 1• QC9_CL = 0
If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:
• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
• VOLT_OFF = 1• VOLT_ON = 0
12.5 Logic rotating switch for function selection and LHMIpresentation SLGAPC
12.5.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Logic rotating switch for functionselection and LHMI presentation
SLGAPC - -
12.5.2 Application
The logic rotating switch for function selection and LHMI presentation function(SLGAPC) (or the selector switch function block, as it is also known) is used to get aselector switch functionality similar with the one provided by a hardware multi-position selector switch. Hardware selector switches are used extensively by utilities,in order to have different functions operating on pre-set values. Hardware switches arehowever sources for maintenance issues, lower system reliability and extendedpurchase portfolio. The virtual selector switches eliminate all these problems.
SLGAPC function block has two operating inputs (UP and DOWN), one blockinginput (BLOCK) and one operator position input (PSTO).
SLGAPC can be activated both from the local HMI and from external sources(switches), via the IED binary inputs. It also allows the operation from remote (like thestation computer). SWPOSN is an integer value output, giving the actual output
Section 12 1MRK 506 375-UEN -Control
286 Railway application RER670 2.2 IECApplication manual
number. Since the number of positions of the switch can be established by settings (seebelow), one must be careful in coordinating the settings with the configuration (if onesets the number of positions to x in settings – for example, there will be only the firstx outputs available from the block in the configuration). Also the frequency of the (UPor DOWN) pulses should be lower than the setting tPulse.
From the local HMI, the selector switch can be operated from Single-line diagram(SLD).
12.5.3 Setting guidelines
The following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGAPC) function:
Operation: Sets the operation of the function On or Off.
NrPos: Sets the number of positions in the switch (max. 32).
OutType: Steady or Pulsed.
tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).
tDelay: The delay between the UP or DOWN activation signal positive front and theoutput activation.
StopAtExtremes: Sets the behavior of the switch at the end positions – if set toDisabled, when pressing UP while on first position, the switch will jump to the lastposition; when pressing DOWN at the last position, the switch will jump to the firstposition; when set to Enabled, no jump will be allowed.
12.6 Selector mini switch VSGAPC
12.6.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Selector mini switch VSGAPC - 43
12.6.2 Application
Selector mini switch (VSGAPC) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGAPC can be used for both acquiring an external switch position (throughthe IPOS1 and the IPOS2 inputs) and represent it through the single line diagramsymbols (or use it in the configuration through the outputs POS1 and POS2) as well
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 287Application manual
as, a command function (controlled by the PSTO input), giving switching commandsthrough the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integernumber 0 – 3, where 0 = MidPos, 1 = Open, 2 = Closed and 3 = Error.
An example where VSGAPC is configured to switch Autorecloser on–off from abutton symbol on the local HMI is shown in figure121. The I and O buttons on thelocal HMI are normally used for on–off operations of the circuit breaker.
IEC07000112-3-en.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1NAM_POS2
IPOS2
CMDPOS21OFFON
VSGAPC
SMBRRECONOFF
SETON
INTONE
INVERTERINPUT OUT
IEC07000112 V3 EN
Figure 121: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlledfrom SA system as well.
12.6.3 Setting guidelines
Selector mini switch (VSGAPC) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the length ofthe pulse can be set using the tPulse parameter. Also, being accessible on the singleline diagram (SLD), this function block has two control modes (settable throughCtlModel): Dir Norm and SBO Enh.
12.7 Generic communication function for Double Pointindication DPGAPC
12.7.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Generic communication function forDouble Point indication
DPGAPC - -
Section 12 1MRK 506 375-UEN -Control
288 Railway application RER670 2.2 IECApplication manual
12.7.2 Application
Generic communication function for Double Point indication (DPGAPC) functionblock is used to send double point position indication to other systems, equipment orfunctions in the substation through IEC 61850-8-1 or other communication protocols.It is especially intended to be used in the interlocking station-wide logics. To be ableto get the signals into other systems, equipment or functions, one must use other tools,described in the Engineering manual, and define which function block in whichsystems, equipment or functions should receive this information.
More specifically, DPGAPC function reports a combined double point positionindication output POSITION, by evaluating the value and the timestamp attributes ofthe inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputsdetermine the two-bit integer value of the output POSITION. The timestamp of theoutput POSITION will have the latest updated timestamp of the inputs OPEN andCLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position tointermediated state.
When the value of the input signal VALID changes, the timestamp of the outputPOSITION will be updated as the time when DPGAPC function detects the change.
Refer to Table 29 for the description of the input-output relationship in terms of thevalue and the quality attributes.
Table 29: Description of the input-output relationship
VALID OPEN CLOSE POSITIONValue Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State
12.7.3 Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
12.8 Single point generic control 8 signals SPC8GAPC
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 289Application manual
12.8.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Single point generic control 8 signals SPC8GAPC - -
12.8.2 Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collectionof 8 single point commands that can be used for direct commands for example reset ofLED's or putting IED in "ChangeLock" state from remote. In this way, simplecommands can be sent directly to the IED outputs, without confirmation.Confirmation (status) of the result of the commands is supposed to be achieved byother means, such as binary inputs and SPGAPC function blocks.
PSTO is the universal operator place selector for all control functions.Even if PSTO can be configured to allow LOCAL or ALL operatorpositions, the only functional position usable with the SPC8GAPCfunction block is REMOTE.
12.8.3 Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) functionare set via the local HMI or PCM600.
Operation: turning the function operation On/Off.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) orPulsed.
tPulsex: if PulseModex is set to Pulsed, then tPulsex will set the length of the pulse (inseconds).
12.9 AutomationBits, command function for DNP3.0AUTOBITS
12.9.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
AutomationBits, command function forDNP3 AUTOBITS - -
Section 12 1MRK 506 375-UEN -Control
290 Railway application RER670 2.2 IECApplication manual
12.9.2 Application
Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600in order to get into the configuration the commands coming through the DNP3.0protocol.The AUTOBITS function plays the same role as functions GOOSEBINRCV(for IEC 61850) and MULTICMDRCV (for LON).AUTOBITS function block have32 individual outputs which each can be mapped as a Binary Output point in DNP3.The output is operated by a "Object 12" in DNP3. This object contains parameters forcontrol-code, count, on-time and off-time. To operate an AUTOBITS output point,send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. Theremaining parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.
For description of the DNP3 protocol implementation, refer to the Communicationmanual.
12.9.3 Setting guidelines
AUTOBITS function block has one setting, (Operation: On/Off) enabling or disablingthe function. These names will be seen in the DNP3 communication management toolin PCM600.
12.10 Single command, 16 signals SINGLECMD
12.10.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Single command, 16 signals SINGLECMD - -
12.10.2 Application
Single command, 16 signals (SINGLECMD) is a common function and alwaysincluded in the IED.
The IEDs may be provided with a function to receive commands either from asubstation automation system or from the local HMI. That receiving function blockhas outputs that can be used, for example, to control high voltage apparatuses inswitchyards. For local control functions, the local HMI can also be used. Togetherwith the configuration logic circuits, the user can govern pulses or steady outputsignals for control purposes within the IED or via binary outputs.
Figure 122 shows an application example of how the user can connect SINGLECMDvia configuration logic circuit to control a high-voltage apparatus. This type of
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 291Application manual
command control is normally carried out by sending a pulse to the binary outputs ofthe IED. Figure 122 shows a close operation. An open breaker operation is performedin a similar way but without the synchro-check condition.
SinglecommandfunctionSINGLECMD
CMDOUTy
OUTy
Close CB1
&User-definedconditionsSynchro-check
Configuration logic circuits
en04000206.vsdIEC04000206 V2 EN
Figure 122: Application example showing a logic diagram for control of a circuitbreaker via configuration logic circuits
Figure 123 and figure 124 show other ways to control functions, which require steadyOn/Off signals. Here, the output is used to control built-in functions or externaldevices.
Section 12 1MRK 506 375-UEN -Control
292 Railway application RER670 2.2 IECApplication manual
SinglecommandfunctionSINGLECMD
CMDOUTy
OUTy
Function n
en04000207.vsd
Function n
IEC04000207 V2 EN
Figure 123: Application example showing a logic diagram for control of built-infunctions
Singlecommandfunction
SINGLESMD
CMDOUTy
OUTy
Device 1
User-definedconditions
Configuration logic circuits
en04000208.vsd
&
IEC04000208 V2 EN
Figure 124: Application example showing a logic diagram for control of externaldevices via configuration logic circuits
12.10.3 Setting guidelines
The parameters for Single command, 16 signals (SINGLECMD) are set via the localHMI or PCM600.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 293Application manual
Parameters to be set are MODE, common for the whole block, and CMDOUTy whichincludes the user defined name for each output signal. The MODE input sets theoutputs to be one of the types Off, Steady, or Pulse.
• Off, sets all outputs to 0, independent of the values sent from the station level, thatis, the operator station or remote-control gateway.
• Steady, sets the outputs to a steady signal 0 or 1, depending on the values sentfrom the station level.
• Pulse, gives a pulse with 100 ms duration, if a value sent from the station level ischanged from 0 to 1. That means the configured logic connected to the commandfunction block may not have a cycle time longer than the cycle time for thecommand function block.
12.11 Transformer energizing control XENCPOW
12.11.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Transformer Energizing Control XENCPOW
0->1T
IEC15000180 V1 EN
25T
12.11.2 Application
The transformer core may become saturated due to an abrupt change in the voltageapplied to it. This may be caused by:
• Switching transients• Out-of-phase synchronization of a generator• Clearing of an external fault
When saturated, a transformer absorbs a magnetization current, also known as inrushcurrent, which can reach several times the nominal current of the transformer.Energization of a transformer from the network by uncontrolled/random closing by aswitching device produces inrush currents since the flux in the core can reach amaximum theoretical value of 2 to 3 times the rated peak flux. This can haveundesirable consequences.
The flux-linkage/current relation is non-linear, as shown in Figure 125, and it isdetermined by the saturation curve of a transformer. Therefore, the magnetizationcurrent of the transformer contains harmonics.
When a transformer is energized, the initial value of the flux may differ from theprospective flux. This causes a DC offset of the flux-linkage and a higher-than-rated
Section 12 1MRK 506 375-UEN -Control
294 Railway application RER670 2.2 IECApplication manual
peak value. The result is an inrush current that may be several times the value of thenominal current. Due to the low relative permeability of the ferromagnetic material insaturation, a marginal increase in the peak of the flux-linkage results in amagnification of the inrush current as shown in Figure 125.
Time
Vo
ltag
e &
Flu
x
Tim
e
Current
Voltage
Flux
Current when Voltage Zero switching
Current when Voltage Peak Switching
Saturation Curve
IEC15000177.vsd
IEC15000177 V1 EN
Figure 125: Flux-linkage/current relation
The transformer energization control function (XENCPOW) is used to minimizeinrush currents by energizing the transformer near the voltage peak. Energizing thetransformer at a voltage zero crossing results in the most severe inrush current.Energizing the transformer at voltage peak results in no DC offset other than thatcaused by the initial residual flux.
12.11.3 Setting guidelines
The controlled close operation of a transformer from the XENCPOW function isbased on the voltage waveform and circuit breaker operating time. The voltagewaveform is traced using the input signal fed to the function, and the breaker operatetime is taken from the setting. Incorrect operation may occur if the tBreaker setting isset incorrectly. Hence the operation accuracy of the XENCPOW function dependsstrongly on the accuracy of the breaker operate time setting.
The parameters for the XENCPOW function are set via the local HMI or PCM600.
1MRK 506 375-UEN - Section 12Control
Railway application RER670 2.2 IEC 295Application manual
The common base IED values for primary current IBase and primary voltage UBaseare set in the global base values for settings function GBASVAL.
GlobalBaseSel: This setting is used to select the GBASVAL function for the referenceof base values.
Operation: On or Off.
ULowLimit: This setting is used to set the voltage range where the transformer can beenergized without looking the voltage peak once the START input is activated. Thetypical setting is 20 % of UBase.
UHighLimit: This setting is used to set the voltage range where the transformer shouldnot be energized even when the START input is activated. The typical setting is 120 %of UBase.
tBreaker: It should be set to match the total closing time of the circuit breaker and itshould also include possible auxiliary relays in the closing circuit. A typical setting is80-150 ms.
tPulse: This setting is used to set the close command pulse duration. The setting mustbe grater than the critical impulse time of the circuit breakers to be closed from thetransformer energizing control function. The typical setting is 200 ms.
12.11.3.1 Setting examples
Refer to the transformer manufacturer’s operating requirements for the UHighLimitand ULowLimit settings.
Refer to the transformer circuit breaker manufacturer’s operating requirements for thetBreaker and tPulse settings.
Section 12 1MRK 506 375-UEN -Control
296 Railway application RER670 2.2 IECApplication manual
Section 13 Scheme communication
13.1 Scheme communication logic for distance orovercurrent protection ZCPSCH
13.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Scheme communication logic fordistance or overcurrent protection
ZCPSCH - 85
13.1.2 Application
To achieve fast clearing of a fault on the part of the line not covered by theinstantaneous zone 1, the stepped distance protection function can be supported withlogic that uses a communication channel.
One communication channel in each direction, which can transmit an on/off signal isrequired. The performance and security of this function is directly related to thetransmission channel speed and security against false or lost signals. Communicationspeed, or minimum time delay, is always of utmost importance because the purpose ofusing communication is to improve the tripping speed of the scheme.
To avoid false signals that could cause false tripping, it is necessary to pay attentionto the security of the communication channel. At the same time it is important to payattention to the communication channel dependability to ensure that proper signals arecommunicated during power system faults, the time during which the protectionschemes must perform their tasks flawlessly.
The logic supports the following communications schemes:
• blocking scheme (blocking)• permissive schemes (overreaching and underreaching)• unblocking scheme and direct intertrip
A permissive scheme is inherently faster and has better security against false trippingthan a blocking scheme. On the other hand, a permissive scheme depend on a receivedCR signal for a fast trip, so its dependability is lower than that of a blocking scheme.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 297Application manual
13.1.2.1 Blocking schemes
In a blocking scheme a reverse looking zone is used to send a block signal to theremote end to block an overreaching zone.
Since the scheme is sending the blocking signal during conditions where the protectedline is healthy, it is common to use the line itself as communication media (PLC). Thescheme can be used on all line lengths.
The blocking scheme is very dependable because it will operate for faults anywhereon the protected line if the communication channel is out of service. On the other hand,it is less secure than permissive schemes because it will trip for external faults withinthe reach of the tripping function if the communication channel is out of service.
Inadequate speed or dependability can cause spurious tripping for external faults.Inadequate security can cause delayed tripping for internal faults.
To secure that the send signal will arrive before the zone used in the communicationscheme will trip, the trip is released first after the time delay tCoord has elapsed. Thesetting of tCoord must be set longer than the maximal transmission time of thechannel. A security margin of at least 10 ms should be considered.
The timer tSendMin for prolonging the send signal is proposed to set to zero.
A B
ORB
Z revA
Z revA CSA TRIPB = ORB+ tCoord+ CR IEC09000015_2_en.vsd
IEC09000015 V2 EN
Figure 126: Principle of blocking scheme
OR: Overreaching
CR: Communication signal received
CS: Communication signal send
Z revA: Reverse zone
13.1.2.2 Permissive schemes
In permissive schemes, the permission to trip is sent from the local end to the remoteend(s), when the protection at the local end has detected a fault on the protected object.
Section 13 1MRK 506 375-UEN -Scheme communication
298 Railway application RER670 2.2 IECApplication manual
The received signal(s) is combined with an overreaching zone and gives aninstantaneous trip if the received signal is present during the time the chosen zone hasdetected a fault.
Either end may send a permissive (or command) signal to trip to the other end(s), andthe teleprotection equipment needs to be able to receive while transmitting.
A general requirement on permissive schemes is that it shall be fast and secure.
If the sending signal(s) is issued by underreaching or overreaching zone, it is dividedinto a permissive underreach or permissive overreach scheme.
Permissive underreaching schemePermissive underreaching scheme is not suitable to use on short line length due todifficulties for distance protection measurement in general to distinguish betweeninternal and external faults in those applications.
The underreaching zones at the local and remote end(s) must overlap in reach toprevent a gap between the protection zones where faults would not be detected. If theunderreaching zone do not meet the required sensitivity due to for instance fault infeedfrom the remote end, a blocking or permissive overreaching scheme should beconsidered.
The received signal (CR) must be received when the overreaching zone is activated toachieve an instantaneous trip. In some cases, due to the fault current distribution, theoverreaching zone can operate only after the fault has been cleared at the terminalnearest to the fault. There is a certain risk that in case of a trip from an independenttripping zone, the zone issuing the send signal (CS) resets before the overreachingzone has started at the remote terminal. To assure a sufficient duration of the receivedsignal (CR), the send signal (CS) can be prolonged by a tSendMin reset timer. Therecommended setting of tSendMin is 100 ms.
Since the received communication signal is combined with the output from anoverreaching zone, there is less concern about a false signal causing an incorrect trip.Therefore set the timer tCoord to zero.
Failure of the communication channel does not affect the selectivity, but delaystripping at one end(s) for certain fault locations.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 299Application manual
A B
ORA
ORB
URB
CSB
URA
CSA
TRIP: UR or OR+CRIEC09000013-2-en.vsd
IEC09000013 V2 EN
Figure 127: Principle of Permissive underreaching scheme
UR: Underreaching
OR: Overreaching
CR: Communication signal received
CS: Communication signal send
Permissive overreaching schemeIn a permissive overreaching scheme there is an overreaching zone that issues the sendsignal. At the remote end the received signal together with the start of an overreachingzone will give an instantaneous trip. The scheme can be used for all line lengths.
In permissive overreaching schemes, the communication channel plays an essentialroll to obtain fast tripping at both ends. Failure of the communication channel mayaffect the selectivity and delay the tripping at one end at least, for faults anywherealong the protected circuit.
Teleprotection, operating in permissive overreaching scheme, must consider besidesthe general requirement of fast and secure operation also consider requirement on thedependability. Inadequate security can cause unwanted tripping for external faults.Inadequate speed or dependability can cause delayed tripping for internal faults oreven unwanted operations.
This scheme may use virtually any communication media that is not adverselyaffected by electrical interference from fault generated noise or by electricalphenomena, such as lightning. Communication media that uses metallic paths areparticularly subjected to this type of interference, therefore they must be properlyshielded or otherwise designed to provide an adequate communication signal duringpower system faults.
The send signal (CS) might be issued in parallel both from an overreaching zone andan underreaching, independent tripping zone. The CS signal from the overreachingzone must not be prolonged while the CS signal from zone 1 can be prolonged.
Section 13 1MRK 506 375-UEN -Scheme communication
300 Railway application RER670 2.2 IECApplication manual
To secure correct operations of current reversal logic in case of parallel lines the sendsignal CS shall not be prolonged. Set the tSendMin to zero in this case.
There is no need to delay the trip at receipt of the signal, so set the timer tCoord to zero.
A B
ORA
ORB
ORA CSA TRIPB = ORB+ CRB , ORB+ T2
IEC09000014-1-en.vsd
IEC09000014 V1 EN
Figure 128: Principle of Permissive overreaching scheme
OR: Overreaching
CR: Communication signal received
CS: Communication signal send
T2: Timer step 2
Unblocking schemeMetallic communication paths adversely affected by fault generated noise may not besuitable for conventional permissive schemes that rely on a signal transmitted duringa protected line fault. With power line carrier for example, the communication signalmay be attenuated by the fault, especially when the fault is close to the line end,thereby disabling the communication channel.
To overcome the lower dependability in permissive schemes, an unblocking functioncan be used. Use this function at older, less reliable, power-line carrier (PLC)communication, where the signal has to be sent through the primary fault. Theunblocking function uses a guard signal CRG, which must always be present, evenwhen no CR signal is received. The absence of the CRG signal for minimum of thesecurity time duration is considered as a CR signal. This also enables a permissivescheme to operate when the line fault blocks the signal transmission. Set the tSecurityto 35 ms.
13.1.2.3 Intertrip scheme
In some power system applications, there is a need to trip the remote end breakerimmediately from local protections. This applies for instance when transformers orreactors are connected to the system without circuit-breakers or for remote trippingfollowing operation of breaker failure protection.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 301Application manual
In an intertrip scheme, the send signal is initiated by an underreaching zone or from anexternal protection (transformer or reactor protection). At the remote end, the receivedsignals initiate a trip without any further protection criteria. To limit the risk for anunwanted trip due to the spurious sending of signals, the timer tCoord should be set to10-30 ms dependant on the type of communication channel.
The general requirement for teleprotection equipment operating in intertrippingapplications is that it should be very secure and very dependable, since bothinadequate security and dependability may cause unwanted operation. In someapplications the equipment shall be able to receive while transmitting, and commandsmay be transmitted over longer time period than for other teleprotection systems.
13.1.3 Setting guidelines
The parameters for the scheme communication logic function are set via the local HMIor PCM600.
Configure the zones used for the CS send and for scheme communication tripping byusing the ACT configuration tool.
The recommended settings of tCoord timer are based on maximal recommendedtransmission time for analogue channels according to IEC 60834-1. It isrecommended to coordinate the proposed settings with actual performance for theteleprotection equipment to get optimized settings.
13.1.3.1 Blocking scheme
Set Operation On
Set SchemeType Blocking
Set tCoord 25 ms (10 ms + maximal transmission time)
Set tSendMin 0 s
Set Unblock Off(Set to NoRestart if Unblocking scheme with no alarm for loss of guard is to be used.Set to Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set tSecurity 0.035 s
13.1.3.2 Permissive underreaching scheme
Set Operation = On
Set SchemeType = Permissive UR
Set tCoord = 0 ms
Set tSendMin = 0.1 s
Set Unblock = Off
Set tSecurity = 0.035 s
Section 13 1MRK 506 375-UEN -Scheme communication
302 Railway application RER670 2.2 IECApplication manual
13.1.3.3 Permissive overreaching scheme
Set Operation = On
Set Scheme type = Permissive OR
Set tCoord = 0 ms
Set tSendMin = 0.1 s (0 s in parallel line applications)
Set Unblock = Off
Set tSecurity = 0.035 s
13.1.3.4 Unblocking scheme
Set Unblock = Restart(Loss of guard signal will give both trip and alarmChoose NoRestart if only trip is required)
Set tSecurity = 0.035 s
13.1.3.5 Intertrip scheme
Set Operation = On
Set SchemeType = Intertrip
Set tCoord = 50 ms (10 ms + maximal transmission time)
Set tSendMin = 0.1 s (0 s in parallel line applications)
Set Unblock = Off
Set tSecurity = 0.015 s
13.2 Current reversal and Weak-end infeed logic fordistance protection 2-phase ZCRWPSCH
13.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Current reversal and weak-end infeedlogic for distance protection 2-phase
ZCRWPSCH - 85
13.2.2 Application
13.2.2.1 Current reversal logic
In the case of parallel lines, overreaching permissive communication schemes cancause unwanted tripping due to current reversal. The unwanted tripping affects the
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 303Application manual
healthy line when a fault is cleared on the parallel line. This lack of security results ina total disconnection between the two buses.
To avoid this kind of disturbances, a fault current reversal logic (transient blockinglogic) can be used.
The unwanted operations that might occur can be explained by looking intoFigure 129 and Figure 130. Initially the protection A2 at A side will detect a fault inforward direction and send a communication signal to the protection B2 at remote end,which is measuring a fault in reverse direction.
L1
L2
A1
A2
B1
B2
IEC9900043-2.vsd
IEC99000043 V3 EN
Figure 129: Current distribution for a fault close to B side when all breakers areclosed
When the breaker B1 opens for clearing the fault, the fault current through B2 bay willinvert. If the communication signal has not reset at the same time as the distanceprotection function used in the teleprotection scheme has switched on to forwarddirection, we will have an unwanted operation of breaker B2 at B side.
L1
L2
A1
A2
B1
B2
IEC99000044-2.vsd
IEC99000044 V3 EN
Figure 130: Current distribution for a fault close to B side when breaker B1 hasopened
To handle this the send signal CS or CSLn from B2 is held back until the reverse zoneIRVLn has reset and the tDelayRev time has been elapsed. To achieve this the reversezone on the distance protection shall be connected to input IRV and the output IRVLshall be connected to input BLKCS on the communication function block ZCPSCH.
The function can be blocked by activating the input IRVBLK or the general BLOCKinput.
13.2.2.2 Weak-end infeed logic
Permissive communication schemes can basically operate only when the protection inthe remote IED can detect the fault. The detection requires a sufficient minimum fault
Section 13 1MRK 506 375-UEN -Scheme communication
304 Railway application RER670 2.2 IECApplication manual
current, normally >20% of Ir. The fault current can be too low due to an open breakeror low short-circuit power of the source. To overcome these conditions, weak-endinfeed (WEI) echo logic is used. The fault current can also be initially too low due tothe fault current distribution. Here, the fault current increases when the breaker opensat the strong terminal, and a sequential tripping is achieved. This requires a detectionof the fault by an independent tripping zone 1. To avoid sequential tripping asdescribed, and when zone 1 is not available, weak-end infeed tripping logic is used.The weak end infeed function only works together with permissive overreachcommunication schemes as the carrier send signal must cover the complete linelength.
The WEI function sends back (echoes) the received signal under the condition that nofault has been detected on the weak-end by different fault detection elements (distanceprotection in forward and reverse direction).
Also, the WEI function can be extended to trip the breaker in the weak side. The tripis achieved when one or more phase voltages are low during an echo function.
Together with the blocking teleprotection scheme some limitations apply:
• Only the trip part of the function can be used together with the blocking scheme.It is not possible to use the echo function to send the echo signal to the remote lineIED. The echo signal would block the operation of the distance protection at theremote line end and in this way prevents the correct operation of a completeprotection scheme.
• A separate direct intertrip channel must be arranged from remote end when a tripor accelerated trip is given there. The intertrip receive signal is connect to inputCRL.
• The WEI function shall be set to WEI=Echo&Trip. The WEI function block willthen give phase selection and trip the local breaker.
Avoid using WEI function at both line ends. It shall only be activated at the weak-end.
13.2.3 Setting guidelines
The parameters for the current reversal logic and the weak-end infeed logic (WEI)function are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
13.2.3.1 Current reversal logic
Set CurrRev to On to activate the function.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 305Application manual
Set tDelayRev timer at the maximum reset time for the communication equipment thatgives the carrier receive (CRL) signal plus 30 ms. A minimum setting of 40 ms isrecommended, typical 60 ms.
A long tDelayRev setting increases security against unwanted tripping, but delay thefault clearing in case of a fault developing from one line that evolves to the other one.The probability of this type of fault is small. Therefore set tDelayRev with a goodmargin.
Set the pick-up delay tPickUpRev to <80% of the minimum sum of breaker operatetime + communication delay time, but with a minimum of 20 ms.
13.2.3.2 Weak-end infeed logic
Set WEI to Echo, to activate the weak-end infeed function with only echo function.
Set WEI to Echo&Trip to obtain echo with trip.
Set tPickUpWEI to 10 ms, a short delay is recommended to avoid that spurious carrierreceived signals will activate WEI and cause unwanted carrier send (ECHO) signals.
Set the voltage criterion UPP< and UPN< for the weak-end trip to 70% of the systembase voltage UBase. The setting should be below the operate voltage of the system butabove the voltage that occurs for fault on the protected line.
13.3 Scheme communication logic for residualovercurrent protection ECPSCH
13.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Scheme communication logic forresidual overcurrent protection
ECPSCH - 85
13.3.2 Application
To achieve fast fault clearance of earth faults on the part of the line not covered by theinstantaneous step of the residual overcurrent protection, the directional residualovercurrent protection can be supported with a logic that uses communicationchannels.
One communication channel is used in each direction, which can transmit an on/offsignal if required. The performance and security of this function is directly related tothe transmission channel speed and security against false or lost signals.
Section 13 1MRK 506 375-UEN -Scheme communication
306 Railway application RER670 2.2 IECApplication manual
In the directional scheme, information of the fault current direction must betransmitted to the other line end.
With directional comparison in permissive schemes, a short operate time of theprotection including a channel transmission time, can be achieved. This short operatetime enables rapid autoreclosing function after the fault clearance.
The communication logic module enables blocking as well as permissive under/overreaching schemes. The logic can also be supported by additional logic for weak-end infeed and current reversal, included in the Current reversal and weak-end infeedlogic for residual overcurrent protection (ECRWPSCH) function.
Metallic communication paths adversely affected by fault generated noise may not besuitable for conventional permissive schemes that rely on signal transmitted during aprotected line fault. With power line carrier, for example, the communication signalmay be attenuated by the fault, especially when the fault is close to the line end,thereby disabling the communication channel.
To overcome the lower dependability in permissive schemes, an unblocking functioncan be used. Use this function at older, less reliable, power line carrier (PLC)communication, where the signal has to be sent through the primary fault. Theunblocking function uses a guard signal CRG, which must always be present, evenwhen no CR signal is received. The absence of the CRG signal during the security timeis used as a CR signal. This also enables a permissive scheme to operate when the linefault blocks the signal transmission. Set the tSecurity to 35 ms.
13.3.3 Setting guidelines
The parameters for the scheme communication logic for residual overcurrentprotection function are set via the local HMI or PCM600.
The following settings can be done for the scheme communication logic for residualovercurrent protection function:
Operation: Off or On.
SchemeType: This parameter can be set to Off , Intertrip, Permissive UR, PermissiveOR or Blocking.
tCoord: Delay time for trip from ECPSCH function. For Permissive under/overreaching schemes, this timer shall be set to at least 20 ms plus maximum reset timeof the communication channel as a security margin. For Blocking scheme, the settingshould be > maximum signal transmission time +10 ms.
Unblock: Select Off if unblocking scheme with no alarm for loss of guard is used. Setto Restart if unblocking scheme with alarm for loss of guard is used.
tSendMin: Time duration, the carrier send signal is prolonged.
tSecurity: The absence of CRG signal for a time duration of tSecurity is considered asCR signal.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 307Application manual
13.4 Current reversal and weak-end infeed logic forresidual overcurrent protection ECRWPSCH
13.4.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Current reversal and weak-end infeedlogic for residual overcurrent protection
ECRWPSCH - 85
13.4.2 Application
13.4.2.1 Fault current reversal logic
Figure 131 and figure 132 show a typical system condition, which can result in a faultcurrent reversal.
Assume that fault is near the B1 breaker. B1 Relay sees the fault in Zone1 and A1 relayidentifies the fault in Zone2.
Note that the fault current is reversed in line L2 after the breaker B1 opening.
It can cause an unselective trip on line L2 if the current reversal logic does not blockthe permissive overreaching scheme in the IED at B2.
L1
L2
A1
A2
B1
B2
IEC9900043-2.vsd
IEC99000043 V3 EN
Figure 131: Current distribution for a fault close to B side when all breakers areclosed
L1
L2
A1
A2
B1
B2
IEC99000044-2.vsd
IEC99000044 V3 EN
Figure 132: Current distribution for a fault close to B side when breaker at B1 isopened
Section 13 1MRK 506 375-UEN -Scheme communication
308 Railway application RER670 2.2 IECApplication manual
When the breaker on the parallel line operates, the fault current on the healthy line isreversed. The IED at B2 recognizes the fault in forward direction from reversedirection before breaker operates. As IED at B2 already received permissive signalfrom A2 and IED at B2 is now detecting the fault as forward fault, it will immediatelytrip breaker at B2. To ensure that tripping at B2 should not occur, the permissiveoverreaching function at B2 needs to be blocked by IRVL till the received permissivesignal from A2 is reset.
The IED at A2, where the forward direction element was initially activated, must resetbefore the send signal is initiated from B2. The delayed reset of output signal IRVLalso ensures the send signal from IED B2 is held back till the forward directionelement is reset in IED A2.
13.4.2.2 Weak-end infeed logic
Figure 133 shows a typical system condition that can result in a missing operation.Note that there is no fault current from node B. This causes that the IED at B cannotdetect the fault and trip the breaker in B. To cope with this situation, a selectable weak-end infeed logic is provided for the permissive overreaching scheme.
A B
IEC99000054-3-en.vsd
Strongsource
Weaksource
IEC99000054 V3 EN
Figure 133: Initial condition for weak-end infeed
13.4.3 Setting guidelines
The parameters for the current reversal and weak-end infeed logic for residualovercurrent protection function are set via the local HMI or PCM600.
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in a Global base values for settings functionGBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
13.4.3.1 Current reversal
The current reversal function is set on or off by setting the parameter CurrRev to On orOff. Time delays shall be set for the timers tPickUpRev and tDelayRev.
tPickUpRev is chosen shorter (<80%) than the breaker opening time, but minimum 20ms.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 309Application manual
tDelayRev is chosen at a minimum to the sum of protection reset time and thecommunication reset time. A minimum tDelayRev setting of 40 ms is recommended.
The reset time of the directional residual overcurrent protection (EF4PTOC) istypically 25 ms. If other type of residual overcurrent protection is used in the remoteline end, its reset time should be used.
The signal propagation time is in the range 3 – 10 ms/km for most types ofcommunication media. In communication networks small additional time delays areadded in multiplexers and repeaters. Theses delays are less than 1 ms per process. Itis often stated that the total propagation time is less than 5 ms.
When a signal picks-up or drops out there is a decision time to be added. This decisiontime is highly dependent on the interface between communication and protectionused. In many cases an external interface (teleprotection equipment) is used. Thisequipment makes a decision and gives a binary signal to the protection device. In caseof analog teleprotection equipment typical decision time is in the range 10 – 30 ms. Fordigital teleprotection equipment this time is in the range 2 – 10 ms.
If the teleprotection equipment is integrated in the protection IED the decision timecan be slightly reduced.
The principle time sequence of signaling at current reversal is shown.
Protection Function
Protection Function
Tele-ProtectionEquipment
Tele-ProtectionEquipment
Tele-communication
System
CS from the protection
function, operateand reset time
CS initiation to the
communicationsystem, operate and reset time
CS propagation, propagation
CR selection and decision, operate
and reset time
CR to the protection
function, operateand reset time
Time
Faultoccurs
Protectionpick-up CS initiation
CR to teleprot.
eq.
CR to prot.func
Fault current reversal
Sendingprotection
reset
CS to communication
drop
CRreception
dropCR to prot. funcdrop
Minimum setting of tDelay IEC05000536-2-en.vsd
IEC05000536 V2 EN
Figure 134: Time sequence of signaling at current reversal
Section 13 1MRK 506 375-UEN -Scheme communication
310 Railway application RER670 2.2 IECApplication manual
13.4.3.2 Weak-end infeed
The weak-end infeed can be set by setting the parameter WEI to Off, Echo or Echo &Trip. Operating zero sequence voltage when parameter WEI is set to Echo & Trip isset with 2U0>.
The zero sequence voltage for a fault at the remote line end and appropriate faultresistance is calculated.
To avoid unwanted trip from the weak-end infeed logic (if spurious signals shouldoccur), set the operate value of the broken delta voltage level detector (2U0) higherthan the maximum false network frequency residual voltage that can occur duringnormal service conditions. The recommended minimum setting is two times the falsezero-sequence voltage during normal service conditions.
1MRK 506 375-UEN - Section 13Scheme communication
Railway application RER670 2.2 IEC 311Application manual
Section 14 Logic
14.1 Tripping logic SMPPTRC
14.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Tripping logic SMPPTRC
1 -> 0
IEC15000314 V1 EN
94
14.1.2 Application
All trip signals from the different protection functions shall be routed through the triplogic. In its simplest form, the trip logic will only link the TRIP signal to a binaryoutput and make sure that the trip duration is sufficient.
Tripping logic SMPPTRC can be used in single-phase and two-phase railway supplysystems.
One SMPPTRC function block should be used per each breaker.
To prevent closing of a circuit breaker after a trip, the function offers a lockoutfunction.
14.1.2.1 Tripping
A simple application with tripping utilizes part of the function block. Connect theinputs from the protection function blocks to the input TRIN to combine the differentfunction outputs to this input. Connect the output TRIP to the binary outputs on the IOboard.
This signal can also be used for other purposes internally in the IED. An examplecould be the starting of breaker failure protection.
Set the required length of the trip pulse to for example, tTripMin = 150ms.
For special applications such as lockout refer to the separate section below. Thetypical connection is shown below in figure 135. Signals that are not used are dimmed.
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 313Application manual
BLOCK
TRIN
SETLKOUT
RSTLKOUT
SMPPTRC
TRIP
CLLKOUT
Impedance protection zone 1 TRIP
EF4PTOC TRIP
IEC16000184-1-en.vsd
Impedance protection zone 3 TRIP
Impedance protection zone 2 TRIPTMAGAPC
STDIR
START
STL1
STL2
FW
REV
IEC16000184 V1 EN
Figure 135: Tripping logic SMPPTRC is used for a simple tripping application
14.1.2.2 Lock-out
The function block is provided with possibilities to initiate lockout. The lockout canbe set to only activate the block closing output CLLKOUT or initiate the block closingoutput and also maintain the trip output signal TRIP (latched trip), by settingTripLockout=On.
The lockout can then be manually reset after checking the primary fault by activatingthe reset input RSTLKOUT. Note that the activation of the RSTLKOUT input willinitiate a short pulse of 3 ms. A new reset needs a new activation of the RSTLKOUTinput.
If external conditions are required to initiate a lockout but not initiate a trip, this canbe achieved by activating input SETLKOUT. The setting AutoLock = Off means thatthe internal trip will not activate lockout so only initiation of the input SETLKOUTwill result in lockout. This is normally the case for overhead line protection wheremost faults are transient. Unsuccessful autoreclose and back-up zone tripping can insuch cases be connected to initiate lockout by activating the input SETLKOUT.
14.1.2.3 Example of directional data
An example how to connect the directional data from different application functionsto the trip function is given below, see Figure 136:
Section 14 1MRK 506 375-UEN -Logic
314 Railway application RER670 2.2 IECApplication manual
IEC16000182-1-en.vsdx
BLOCK
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STDIR
STARTCOMB
BLOCK
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STDIR
STARTCOMB
BLOCK
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16
STDIR
SMAGAPC
START
FW
REV
PROTECTION 1
STL1
FWL1
REVL1
STL2
FWL2
REVL2
PROTECTION 2
STDIR
PROTECTION 3
-
-
-
BLOCKTRIN
SETLKOUT
RSTLKOUT
STDIR
TRIP
SMPPTRC
CLLKOUT
START
STL1
STL2
FW
REV
IEC16000182 V1 EN
Figure 136: Example of the connection of directional start logic.
Protection functions connect the directional data via the start combinator functionSTARTCOMB to the start matrix function SMAGAPC and then to the trip functionSMPPTRC, or directly to SMAGAPC and then to the SMPPTRC.
The SMAGAPC merge start and directional output signals from different applicationfunctions and create a common directional output signal STDIR to be connected toSMPPTRC.
The trip function SMPPTRC splits up the directional data as general output data forSTART, STL1, STL2, FW and REV.
All start and directional outputs are mapped to the 61850 logical node data model ofthe trip function and provided via the 61850 dirGeneral, dirPhsA and dirPhsB dataattributes.
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 315Application manual
14.1.2.4 Blocking of the function block
Total block of the trip function is done by activating the input BLOCK and can be usedto disable the outputs of the trip logic in the event of internal failures.
14.1.3 Setting guidelines
The parameters for tripping logic SMPPTRC are set via the local HMI or PCM600.
The following trip parameters can be set to regulate tripping.
Operation: Sets the mode of operation. Off switches the tripping off. The normalselection is On.
TripLockout: Sets the scheme for lockout. Off only activates the lockout output whenthe input SETLKOUT is activated. On activates the lockout output and latches theoutput TRIP when the input SETLKOUT is activated. The normal selection is Off.
AutoLock: Sets the scheme for lockout. Off only activates lockout through the inputSETLKOUT. On additionally allows activation of lockout from the trip functionitself. The normal selection is Off.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set toensure that the circuit breaker is tripped correctly. Normal setting is 0.150s.
14.2 Trip matrix logic TMAGAPC
14.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Trip matrix logic TMAGAPC - -
14.2.2 Application
The trip matrix logic TMAGAPC function is used to route trip signals and otherlogical output signals to different output contacts on the IED.
The trip matrix logic function has 3 output signals and these outputs can be connectedto physical tripping outputs according to the specific application needs for settablepulse or steady output.
14.2.3 Setting guidelines
Operation: Operation of function On/Off.
Section 14 1MRK 506 375-UEN -Logic
316 Railway application RER670 2.2 IECApplication manual
PulseTime: Defines the pulse time when in Pulsed mode. When used for directtripping of circuit breaker(s) the pulse time delay shall be set to approximately 0.150seconds in order to obtain satisfactory minimum duration of the trip pulse to the circuitbreaker trip coils.
OnDelay: Used to prevent output signals to be given for spurious inputs. Normally setto 0 or a low value.
OffDelay: Defines a delay of the reset of the outputs after the activation conditions nolonger are fulfilled. It is only used in Steady mode. When used for direct tripping ofcircuit breaker(s) the off delay time shall be set to at least 0.150 seconds in order toobtain a satisfactory minimum duration of the trip pulse to the circuit breaker tripcoils.
ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed.
14.3 Logic for group alarm ALMCALH
14.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Logic for group alarm ALMCALH - -
14.3.2 Application
Group alarm logic function ALMCALH is used to route alarm signals to differentLEDs and/or output contacts on the IED.
ALMCALH output signal and the physical outputs allows the user to adapt the alarmsignal to physical tripping outputs according to the specific application needs.
14.3.3 Setting guidelines
Operation: On or Off
14.4 Logic for group alarm WRNCALH
14.4.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Logic for group warning WRNCALH - -
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 317Application manual
14.4.1.1 Application
Group warning logic function WRNCALH is used to route warning signals to LEDsand/or output contacts on the IED.
WRNCALH output signal WARNING and the physical outputs allows the user toadapt the warning signal to physical tripping outputs according to the specificapplication needs.
14.4.1.2 Setting guidelines
OperationOn or Off
14.5 Logic for group indication INDCALH
14.5.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Logic for group indication INDCALH - -
14.5.1.1 Application
Group indication logic function INDCALH is used to route indication signals todifferent LEDs and/or output contacts on the IED.
INDCALH output signal IND and the physical outputs allows the user to adapt theindication signal to physical outputs according to the specific application needs.
14.5.1.2 Setting guidelines
Operation: On or Off
14.6 Configurable logic blocks
The configurable logic blocks are available in two categories:
• Configurable logic blocks that do not propagate the time stamp and the quality ofsignals. They do not have the suffix QT at the end of their function block name,for example, SRMEMORY. These logic blocks are also available as part of anextension logic package with the same number of instances.
• Configurable logic blocks that propagate the time stamp and the quality ofsignals. They have the suffix QT at the end of their function block name, forexample, SRMEMORYQT.
Section 14 1MRK 506 375-UEN -Logic
318 Railway application RER670 2.2 IECApplication manual
14.6.1 Application
A set of standard logic blocks, like AND, OR etc, and timers are available for adaptingthe IED configuration to the specific application needs.
14.6.2 Setting guidelines
There are no settings for AND gates, OR gates, inverters or XOR gates.
For normal On/Off delay and pulse timers the time delays and pulse lengths are setfrom the local HMI or via the PST tool.
Both timers in the same logic block (the one delayed on pick-up and the one delayedon drop-out) always have a common setting value.
For controllable gates, settable timers and SR flip-flops with memory, the settingparameters are accessible via the local HMI or via the PST tool.
14.6.2.1 Configuration
Logic is configured using the ACT configuration tool in PCM600.
Execution of functions as defined by the configurable logic blocks runs according toa fixed sequence with different cycle times.
For each cycle time, the function block is given an serial execution number. This isshown when using the ACT configuration tool with the designation of the functionblock and the cycle time, see example below.
IEC09000695_2_en.vsd
IEC09000695 V2 EN
Figure 137: Example designation, serial execution number and cycle time forlogic function
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 319Application manual
IEC09000310-2-en.vsd
IEC09000310 V2 EN
Figure 138: Example designation, serial execution number and cycle time forlogic function that also propagates timestamp and quality of inputsignals
The execution of different function blocks within the same cycle is determined by theorder of their serial execution numbers. Always remember this when connecting twoor more logical function blocks in series.
Always be careful when connecting function blocks with a fast cycletime to function blocks with a slow cycle time.Remember to design the logic circuits carefully and always check theexecution sequence for different functions. In other cases, additionaltime delays must be introduced into the logic schemes to preventerrors, for example, race between functions.
14.7 Fixed signal function block FXDSIGN
14.7.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Fixed signals FXDSIGN - -
14.7.2 Application
The Fixed signals function (FXDSIGN) has nine pre-set (fixed) signals that can beused in the configuration of an IED, either for forcing the unused inputs in otherfunction blocks to a certain level/value, or for creating certain logic. Boolean, integer,floating point, string types of signals are available.
One FXDSIGN function block is included in all IEDs.
Section 14 1MRK 506 375-UEN -Logic
320 Railway application RER670 2.2 IECApplication manual
Example for use of GRP_OFF signal in FXDSIGNThe Restricted earth fault function REFPDIF can be used both for auto-transformersand normal transformers.
When used for auto-transformers, information from both windings parts, togetherwith the neutral point current, needs to be available to the function. This means thatthree inputs are needed.
I3PW1CT1I3PW2CT1 I3P
REFPDIF
IEC09000619_3_en.vsd
IEC09000619 V3 EN
Figure 139: REFPDIF function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. Thismeans that only two inputs are used. Since all group connections are mandatory to beconnected, the third input needs to be connected to something, which is the GRP_OFFsignal in FXDSIGN function block.
I3PW1CT1I3PW2CT1 I3P
REFPDIF
GRP_OFFFXDSIGN
IEC09000620_3_en.vsd
IEC09000620 V3 EN
Figure 140: REFPDIF function inputs for normal transformer application
14.8 Boolean 16 to Integer conversion B16I
14.8.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Boolean 16 to integer conversion B16I - -
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 321Application manual
14.8.2 Application
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary(logical) signals into an integer. It can be used – for example, to connect logical outputsignals from a function (like distance protection) to integer inputs from anotherfunction (like line differential protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination ofup to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a valueaccording to the table below from 0 to 32768. This follows the general formula: INx= 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be availableon the output OUT as a sum of the values of all the inputs INx that are activated. OUTis an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 itcorresponds to that integer 65535 is available on the output OUT. B16I function isdesigned for receiving up to 16 booleans input locally. If the BLOCK input isactivated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block B16I.
Name of input Type Default Description Value whenactivated
Value whendeactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the B16I function block.
Section 14 1MRK 506 375-UEN -Logic
322 Railway application RER670 2.2 IECApplication manual
14.9 Boolean to integer conversion with logical noderepresentation, 16 bit BTIGAPC
14.9.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Boolean to integer conversion withlogical node representation, 16 bit
BTIGAPC - -
14.9.2 Application
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) isused to transform a set of 16 binary (logical) signals into an integer. BTIGAPC has alogical node mapping in IEC 61850.
The BTIGAPC function will transfer a combination of up to 16 binary inputs INxwhere 1≤x≤16 to an integer. Each INx represents a value according to the table belowfrom 0 to 32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sumof all the values on the activated INx will be available on the output OUT as a sum ofthe values of all the inputs INx that are activated. OUT is an integer. When all INxwhere 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535 isavailable on the output OUT. BTIGAPC function is designed for receiving up to 16booleans input locally. If the BLOCK input is activated, it will freeze the output at thelast value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block BTIGAPC.
Name of input Type Default Description Value whenactivated
Value whendeactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
Table continues on next page
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 323Application manual
Name of input Type Default Description Value whenactivated
Value whendeactivated
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the BTIGAPC function block.
14.10 Integer to Boolean 16 conversion IB16
14.10.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Integer to boolean 16 conversion IB16 - -
14.10.2 Application
Integer to boolean 16 conversion function (IB16) is used to transform an integer intoa set of 16 binary (logical) signals. It can be used – for example, to connect integeroutput signals from one function to binary (logical) inputs to another function. IB16function does not have a logical node mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination ofup to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a valueaccording to the table below from 0 to 32768. This follows the general formula: INx= 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be availableon the output OUT as a sum of the values of all the inputs INx that are activated. OUTis an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 itcorresponds to that integer 65535 is available on the output OUT. IB16 function isdesigned for receiving up to 16 booleans input locally. If the BLOCK input isactivated, it will freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the outputOUT on the function block IB16.
Section 14 1MRK 506 375-UEN -Logic
324 Railway application RER670 2.2 IECApplication manual
Name of input Type Default Description Value whenactivated
Value whendeactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can beconverted to an integer by the IB16 function block.
14.11 Integer to Boolean 16 conversion with logic noderepresentation ITBGAPC
14.11.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Integer to boolean 16 conversion withlogic node representation
ITBGAPC - -
14.11.2 Application
Integer to boolean 16 conversion with logic node representation function (ITBGAPC)is used to transform an integer into a set of 16 boolean signals. ITBGAPC function canreceive an integer from a station computer – for example, over IEC 61850–8–1. Thisfunction is very useful when the user wants to generate logical commands (for selector
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 325Application manual
switches or voltage controllers) by inputting an integer number. ITBGAPC functionhas a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function(ITBGAPC) will transfer an integer with a value between 0 to 65535 communicatedvia IEC 61850 and connected to the ITBGAPC function block to a combination ofactivated outputs OUTx where 1≤x≤16.
The values of the different OUTx are according to the Table 30.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
Table 30: Output signals
Name of OUTx Type Description Value whenactivated
Value whendeactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)are active equals 65535. This is the highest integer that can be converted by theITBGAPC function block.
14.12 Elapsed time integrator with limit transgression andoverflow supervision TEIGAPC
14.12.1 IdentificationFunction Description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2 devicenumber
Elapsed time integrator TEIGAPC - -
Section 14 1MRK 506 375-UEN -Logic
326 Railway application RER670 2.2 IECApplication manual
14.12.2 Application
The function TEIGAPC is used for user-defined logics and it can also be used fordifferent purposes internally in the IED. An application example is the integration ofelapsed time during the measurement of neutral point voltage or neutral current atearth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflowindication is fixed to 999999.9 seconds.
14.12.3 Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit floatrepresentation
99 999.99 seconds < tAlarm ≤ 999 999.0 seconds
99 999.99 seconds < tWarning ≤ 999 999.0 seconds
Note that tAlarm and tWarning are independent settings, that is, thereis no check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
14.13 Comparator for integer inputs - INTCOMP
14.13.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Comparison of integer values INTCOMP Int<=>
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 327Application manual
14.13.2 Application
The function gives the possibility to monitor the level of integer values in the systemrelative to each other or to a fixed value. It is a basic arithmetic function that can beused for monitoring, supervision, interlocking and other logics.
14.13.3 Setting guidelines
For proper operation of comparison the set value should be set within the range of ± 2×109.
Setting procedure on the IED:
EnaAbs: This setting is used to select the comparison type between signed andabsolute values.
• Absolute: Comparison is performed on absolute values of input and referencevalues
• Signed: Comparison is performed on signed values of input and reference values.
RefSource: This setting is used to select the reference source between input and settingfor comparison.
• Input REF: The function will take reference value from input REF• Set Value: The function will take reference value from setting SetValue
SetValue: This setting is used to set the reference value for comparison when settingRefSource is selected as SetValue.
14.13.4 Setting example
For absolute comparison between inputs:
Set the EnaAbs = Absolute
Set the RefSource = Input REF
Similarly for Signed comparison between inputs
Set the EnaAbs = Signed
Set the RefSource =Input REF
For absolute comparison between input and setting
Set the EnaAbs = Absolute
Set the RefSource = Set Value
Section 14 1MRK 506 375-UEN -Logic
328 Railway application RER670 2.2 IECApplication manual
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the EnaAbs = Signed
Set the RefSource = Set Value
SetValue shall be set between -2000000000 to 2000000000
14.14 Comparator for real inputs - REALCOMP
14.14.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Comparator for real inputs REALCOMP Real<=>
14.14.2 Application
The function gives the possibility to monitor the level of real values in the systemrelative to each other or to a fixed value. It is a basic arithmetic function that can beused for monitoring, supervision, interlocking and other logics.
14.14.3 Setting guidelines
Setting procedure on the IED:
EnaAbs: This setting is used to select the comparison type between signed andabsolute values.
• Absolute: Comparison is performed with absolute values of input and reference.• Signed: Comparison is performed with signed values of input and reference.
RefSource: This setting is used to select the reference source between input and settingfor comparison.
• Input REF: The function will take reference value from input REF• Set Value: The function will take reference value from setting SetValue
SetValue: This setting is used to set the reference value for comparison when settingRefSource is selected as Set Value. If this setting value is less than 0.2% of the set unitthen the output INLOW will never pickup.
1MRK 506 375-UEN - Section 14Logic
Railway application RER670 2.2 IEC 329Application manual
RefPrefix: This setting is used to set the unit of the reference value for comparisonwhen setting RefSource is selected as SetValue. It has 5 unit selections and they areMilli, Unity, Kilo, Mega and Giga.
EqualBandHigh: This setting is used to set the equal condition high band limit in % ofreference value. This high band limit will act as reset limit for INHIGH output whenINHIGH.
EqualBandLow: This setting is used to set the equal condition low band limit in % ofreference value. This low band limit will act as reset limit for INLOW output whenINLOW.
14.14.4 Setting example
Let us consider a comparison is to be done between current magnitudes in the rangeof 90 to 110 with nominal rating is 100 and the order is kA.
For the above condition the comparator can be designed with settings as follows,
EnaAbs = Absolute
RefSource = Set Value
SetValue = 100
RefPrefix = Kilo
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value
Operation
The function will set the outputs for the following conditions,
INEQUAL will set when the INPUT is between the ranges of 95 to 105 kA.
INHIGH will set when the INPUT crosses above 105 kA.
INLOW will set when the INPUT crosses below 95 kA.
If the comparison should be done between two current magnitudes then those currentsignals need to be connected to function inputs, INPUT and REF. Then the settingsshould be adjusted as below,
EnaAbs = Absolute
RefSource = Input REF
EqualBandHigh = 5.0 % of reference value
EqualBandLow = 5.0 % of reference value.
Section 14 1MRK 506 375-UEN -Logic
330 Railway application RER670 2.2 IECApplication manual
Section 15 Monitoring
15.1 Measurement
15.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Measurements CVMMXN
P_Q
IEC15000112 V1 EN
-
Phase current measurement CMMXU
I
IEC15000116 V1 EN
-
Phase-phase voltage measurement VMMXU
U
IEC15000117 V1 EN
-
Current sequence componentmeasurement
CMSQI
Isqi
IEC15000113 V1 EN
-
Voltage sequence componentmeasurement
VMSQI
Usqi
IEC15000114 V1 EN
-
Phase-neutral voltage measurement VNMMXU
UN
IEC15000115 V1 EN
-
15.1.2 Application
Measurement functions are used for power system measurement and supervision, forreporting to the local HMI, the monitoring tool within PCM600 or to station level forexample, via IEC 61850. The measurement functions operates properly for 16.7Hz,50Hz and 60Hz railway power supply systems. The possibility to continuouslymonitor measured values of active power, reactive power, currents, voltages,frequency, power factor etc. is vital for efficient production, transmission and
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 331Application manual
distribution of electrical energy. It provides to the system operator fast and easyoverview of the present status of the power system. Additionally, it can be used duringtesting and commissioning of protection and control IEDs in order to verify properoperation and connection of instrument transformers (CTs and VTs). During normalservice by periodic comparison of the measured value from the IED with otherindependent meters the proper operation of the IED analog measurement chain can beverified. Finally, it can be used to verify proper direction orientation for distance ordirectional overcurrent protection function.
Several instances of each type of measurement function blocks areavailable in the IED. The actual reported values from the IED aredependent on the logic configuration made in PCM600.
All measured values can be supervised with four settable limits:
• low-low limit• low limit• high limit• high-high limit
A zero clamping reduction is also supported, that is, the measured value below asettable limit is forced to zero which reduces the impact of noise in the inputs.
Dead-band supervision can be used to report the measured signal value to the stationlevel when a change in the measured value is above the set threshold limit or timeintegral of all changes since the last time value updating exceeds the threshold limit.The measure value can also be based on periodic reporting.
All measurement functions uses fundamental frequency phasors (i.e. DFT filtering)for internal calculations and for reporting of measured values. However, from thefollowing three measurement functions CMMXU, VMMXU and VNMMXU it is alsopossible to report the total measured quantity (i.e. true RMS filtering). By selecting theRMS mode, the reported value will in addition to the fundamental magnitude alsoinclude harmonics. The RMS measurement is often required for railway powersystems which are typically polluted by harmonics.
The measurement function CVMMXN is located under: Main menu/Measurement/Monitoring/Service values/CVMMXN
CVMMXN provides the following power system quantities:
• P, Q and S: two or single phase active, reactive and apparent power• PF: power factor• F: power system frequency
The CVMMXN function calculates two-phase power quantities by using fundamentalfrequency phasors (DFT values) of the measured current respectively voltage signals.The measured power quantities are available either, as instantaneously calculated
Section 15 1MRK 506 375-UEN -Monitoring
332 Railway application RER670 2.2 IECApplication manual
quantities or, averaged values over a period of time (low pass filtered) depending onthe selected settings.
The measuring functions CMMXU, VMMXU and VNMMXU are located under:
Main menu/Measurement/Monitoring/CurrentPhasors(I)/CMMXU
Main menu/Measurement/Monitoring/VoltagePhasors, phase-phase(U)/VMMXU
Main menu/Measurement/Monitoring/VoltagePhasors, phase-neutral(UN)/VNMMXU
CMMXU, VMMXU and VNMMXU provide physical quantities:
• I: phase currents (amplitude and angle) (CMMXU)• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)
(VMMXU, VNMMXU)
Fundamental frequency filtered values (DFT) or true RMS values can be selected asa measurement type in CMMXU, VMMXU and VNMMXU functions.
The measuring functions CMSQI and VMSQI are located under:
Main menu/Measurement/Monitoring/CurrentSequenceComponents(Isqi)/CMSQI
Main menu/Measurement/Monitoring/VoltageSequenceComponents(Usqi)/VMSQI
CMSQI and VMSQI provide sequence component quantities:
• I: sequence currents (positive and zero sequence, amplitude and angle)• U: sequence voltages (positive and zero sequence, amplitude and angle).
It is possible to calibrate the measuring function to get better than class 0.5presentation. This is accomplished by angle and amplitude compensation at 5%, 30%and 100% of the rated current and at 100% of the rated voltage.
15.1.3 Zero clamping
Measuring functions CVMMXN, CMMXU, VMMXU and VNMMXU have nointerconnections regarding any settings or parameters.
Zero clampings are also handled entirely by ZeroDb separately for each function'severy output signal. For example, zero clamping of U12 is handled by UL12ZeroDbin VMMXU, zero clamping of I1 is handled by IL1ZeroDb in CMMXU, and so on.
Example of CVMMXN operation
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 333Application manual
Outputs seen on the local HMI under Main menu/Measurements/Monitoring/Servicevalues(P_Q)/CVMMXN(P_Q):
S Apparent three-phase power
P Active three-phase power
Q Reactive three-phase power
PF Power factor
ILAG I lagging U
ILEAD I leading U
U System mean voltage, calculated according to selected mode
I System mean current, calculated according to selected mode
F Frequency
Relevant settings and their values on the local HMI under Main menu/Settings/IEDsettings/Monitoring/Servicevalues(P_Q)/CVMMXN(P_Q):
• When system voltage falls below UGenZeroDB, values for S, P, Q, PF, U and Fare forced to zero.
• When system current falls below IGenZeroDB, values for S, P, Q, PF, U and F areforced to zero.
• When the value of a single signal falls below its set deadband, the value is forcedto zero. For example, if the apparent three-phase power falls below SZeroDb, thevalue for S is forced to zero.
15.1.4 Setting guidelines
The available setting parameters of the measurement function CVMMXN, CMMXU,VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actual hardware(TRM) and the logic configuration made in PCM600.
The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.
GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.
Operation: Off/On. Every function instance (CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation(Off).
The following general settings can be set for the Measurement function(CVMMXN):
k: Low pass filter coefficient for power measurement.
Parameters IBase, Ubase and SBase have been implemented as asettings instead of a parameters, which means that if the values of the
Section 15 1MRK 506 375-UEN -Monitoring
334 Railway application RER670 2.2 IECApplication manual
parameters are changed there will be no restart of the application. Asrestart is required to activate new parameters values, the IED must berestarted in some way. Either manually or by changing some otherparameter at the same time.
The following general settings can be set for the Phase current measurement(CMMXU):
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, whereY is equal to 5, 30 or 100.
MeasurementType: This default setting is DFT, which gives fundamental frequencyamplitude and angle. It can be set as RMS, if true RMS value over one cycle isrequired.
The following general settings can be set for the Phase-phase voltage measurement(VMMXU):
UAmpComp100: Amplitude compensation to calibrate voltage measurements at100% of Ur.
MeasurementType: This default setting is DFT, which gives fundamental frequencyamplitude and angle. It can be set as RMS, if true RMS value over one cycle isrequired.
The following general settings can be set for all monitored quantities included in thefunctions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X insetting names below equals S, P, Q, PF, F, IL1-2, UL1-2, UL12, I1, 2I0, U1 or 2U0.
Xmin: Minimum value for analog signal X set directly in applicable measuring unit.
Xmax: Maximum value for analog signal X.
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXN.If measured value is below 5% of UBase and/or 5% of IBase calculated S, P, Q and PFwill be zero and these settings will override XZeroDb.
XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) orintegral deadband (Int deadband). The reporting interval is controlled by theparameter XDbRepInt.
XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and isreporting interval in seconds. Amplitude deadband is the setting value in % ofmeasuring range. Integral deadband setting is the integral area, that is, measured valuein % of measuring range multiplied by the time between two measured values.
XHiHiLim: High-high limit. Set in applicable measuring unit.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 335Application manual
XHiLim: High limit.
XLowLim: Low limit.
XLowLowLim: Low-low limit.
XLimHyst: Hysteresis value in % of range and is common for all limits.
All phase angles are presented in relation to defined reference channel. The parameterPhaseAngleRef defines the reference, see Section “Analog inputs”.
Calibration curvesIt is possible to calibrate the functions (CMMXU, VMMXU and VNMMXU) to getclass 0.5 presentations of currents and voltages. This is accomplished by amplitudeand angle compensation at 5, 30 and 100% of rated current and voltage. Thecompensation curve will have the characteristic for amplitude and anglecompensation of currents as shown in figure 141 (example). The first phase will beused as reference channel and compared with the curve for calculation of factors. Thefactors will then be used for all related channels.
IEC05000652 V2 EN
Figure 141: Calibration curves
Section 15 1MRK 506 375-UEN -Monitoring
336 Railway application RER670 2.2 IECApplication manual
15.1.4.1 Setting examples
Three setting examples, in connection to Measurement function (CVMMXN), areprovided:
• Measurement function (CVMMXN) application for a OHL• Measurement function (CVMMXN) application on the secondary side of a
transformer
For each of them detail explanation and final list of selected setting parameters valueswill be provided.
Several instances of each type of measurement function blocks areavailable in the IED. The actual reported values from the IED aredependent on the logic configuration made in PCM600.
Measurement function application for a 110kV OHLSingle line diagram for this application is given in figure 142:
110kV Busbar
110kV OHL
P Q
600/1 A
IEC16000124-1-en.vsdx
IED110 0,1kV
IEC16000124 V1 EN
Figure 142: Single line diagram for 110kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicatedin figure 142 it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRefusing PCM600 for analog input channels
2. Connect, in PCM600, measurement function to two-phase CT and VT inputs3. Set under General settings parameters for the Measurement function:
• general settings as shown in table 31.• level supervision of active power as shown in table 32.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 337Application manual
Table 31: General settings parameters for the Measurement function
Setting Short Description Selectedvalue
Comments
Operation Operation Off/On On Function must be On
k Low pass filter coefficient forpower measurement, U and I
0.00 Typically no additional filtering isrequired
UGenZeroDb Zero point clamping in % ofUbase
25 Set minimum voltage level to25%. Voltage below 25% will forceS, P and Q to zero.
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%.Current below 3% will force S, Pand Q to zero.
UBase (set inGlobal base)
Base setting for voltage level inkV
110.00 Set rated OHL phase-to-phasevoltage
IBase (set inGlobal base)
Base setting for current level in A 600 Set rated primary CT current usedfor OHL
SBase (set inGlobal base)
Base setting for power level inMVA
66 Set rated apparent two-phasepower which correspond to 110kVand 600A
Table 32: Settings parameters for level supervision
Setting Short Description Selectedvalue
Comments
PMin Minimum value -100 Minimum expected load
PMax Maximum value 100 Maximum expected load
PZeroDb Zero point clamping in 0.001% ofrange
1000 Set zero point clamping to 0,66MW that is, 1% of 66 MW
PRepTyp Reporting type db Select amplitude deadbandsupervision
PDbRepInt Cycl: Report interval (s), Db: In %of range, Int Db: In %s
5 Set ±Δdb=1,3 MW that is, 2%(larger changes than 1,3 MW willbe reported)
PHiHiLim High High limit (physical value) 120 High alarm limit that is, extremeoverload alarm
PHiLim High limit (physical value) 100 High warning limit that is, overloadwarning
PLowLim Low limit (physical value) -100 Low warning limit. Not active
PLowLowlLim Low Low limit (physical value) -120 Low alarm limit. Not active
PLimHyst Hysteresis value in % of range(common for all limits)
2 Set ±Δ Hysteresis MW that is, 2%
Measurement function application for a power transformerSingle line diagram for this application is given in Figure 143.
Section 15 1MRK 506 375-UEN -Monitoring
338 Railway application RER670 2.2 IECApplication manual
110kV Busbar
200/1
15kV Busbar
600/5
P Q
8,0 MVA
110/15kV
UL1 & UL2
IEC16000125-1-en.vsdx
IED
15/0,1kV
IEC16000125 V1 EN
Figure 143: Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure 143, it isnecessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRefdata using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in table
33.
The power P&Q measurement is needed towards busbar (not towards IED, as default).Proper inversion of current should be done in SMAI block for the current channels inorder to get correct direction of P&Q. Note that, in such case this SMAI block shallonly be used for the measurement functions.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 339Application manual
Table 33: General settings parameters for the Measurement function
Setting Short description Selectedvalue
Comment
Operation Operation Off/On On Function must be On
k Low pass filter coefficient forpower measurement, U and I
0.00 Typically no additional filtering isrequired
UGenZeroDb Zero point clamping in % ofUbase
25 Set minimum voltage level to 25%
IGenZeroDb Zero point clamping in % of Ibase 3 Set minimum current level to 3%
UBase (set inGlobal base)
Base setting for voltage level inkV
15.00 Set LV side rated phase-to-phasevoltage
IBase (set inGlobal base)
Base setting for current level in A 533A Set transformer LV winding ratedcurrent
SBase (set inGlobal base)
Base setting for power level inMVA
8 Set rated apparent power of thetransformer
15.2 Gas medium supervision SSIMG
15.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Insulation gas monitoring function SSIMG - 63
15.2.2 Application
Gas medium supervision (SSIMG) is used for monitoring the circuit breakercondition. Proper arc extinction by the compressed gas in the circuit breaker is veryimportant. When the pressure becomes too low compared to the required value, thecircuit breaker operation shall be blocked to minimize the risk of internal failure.Binary information based on the gas pressure in the circuit breaker is used as an inputsignal to the function. The function generates alarms based on the receivedinformation.
15.2.3 Setting guidelines
The parameters for Gas medium supervision SSIMG can be set via local HMI orProtection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision i.e.Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the circuitbreaker.
Section 15 1MRK 506 375-UEN -Monitoring
340 Railway application RER670 2.2 IECApplication manual
PresLOLimit: This is used to set the limit for a pressure lockout condition in the circuitbreaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in thecircuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in thecircuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication, givenin s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication,given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set timedelay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set timedelay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a settime delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a settime delay in s.
15.3 Liquid medium supervision SSIML
15.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Insulation liquid monitoring function SSIML - 71
15.3.2 Application
Liquid medium supervision (SSIML) is used for monitoring the transformers and tapchangers. When the level becomes too low compared to the required value, theoperation is blocked to minimize the risk of internal failures. Binary informationbased on the oil level in the transformer and the tap changer is used as input signals to
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 341Application manual
the function. In addition to that, the function generates alarms based on receivedinformation.
15.3.3 Setting guidelines
The parameters for Liquid medium supervision SSIML can be set via local HMI orProtection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of liquid medium supervisioni.e. Off/On.
LevelAlmLimit: This is used to set the limit for a level alarm condition in thetransformer.
LevelLOLimit: This is used to set the limit for a level lockout condition in thetransformer.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in thetransformer.
TempLOLimit: This is used to set the limit for a temperature lockout condition in thetransformer.
tLevelAlarm: This is used to set the time delay for a level alarm indication, given in s.
tLevelLockOut: This is used to set the time delay for a level lockout indication, givenin s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout indication,given in s.
tResetLevelAlm: This is used for the level alarm indication to reset after a set timedelay in s.
tResetLevelLO: This is used for the level lockout indication to reset after a set timedelay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a settime delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a settime delay in s.
15.4 Breaker monitoring SSCBR
15.4.1 Identification
Section 15 1MRK 506 375-UEN -Monitoring
342 Railway application RER670 2.2 IECApplication manual
Function description IEC 61850identification
IEC 60617identification
ANSI/IEEE C37.2device number
Breaker monitoring SSCBR - -
15.4.2 Application
The circuit breaker maintenance is usually based on regular time intervals or thenumber of operations performed. This has some disadvantages because there could bea number of abnormal operations or few operations with high-level currents within thepredetermined maintenance interval. Hence, condition-based maintenancescheduling is an optimum solution in assessing the condition of circuit breakers.
Circuit breaker contact travel timeAuxiliary contacts provide information about the mechanical operation, opening timeand closing time of a breaker. Detecting an excessive traveling time is essential toindicate the need for maintenance of the circuit breaker mechanism. The excessivetravel time can be due to problems in the driving mechanism or failures of the contacts.
Circuit breaker statusMonitoring the breaker status ensures proper functioning of the features within theprotection relay such as breaker control, breaker failure and autoreclosing. Thebreaker status is monitored using breaker auxiliary contacts. The breaker status isindicated by the binary outputs. These signals indicate whether the circuit breaker isin an open, closed or error state.
Remaining life of circuit breakerEvery time the breaker operates, the circuit breaker life reduces due to wear. The wearin a breaker depends on the interrupted current. For breaker maintenance orreplacement at the right time, the remaining life of the breaker must be estimated. Theremaining life of a breaker can be estimated using the maintenance curve provided bythe circuit breaker manufacturer.
Circuit breaker manufacturers provide the number of make-break operations possibleat various interrupted currents. An example is shown in figure 144.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 343Application manual
Num
ber o
f mak
e-br
eak
oper
atio
ns (
n)
Interrupted current (kA)
P1
P2
100000
50000
20000
10000
2000
5000
1000
100
200
500
10
20
50
0.1 0.2 0.5 1 2 5 10 20 50 100
IEC12000623_1_en.vsd
IEC12000623 V1 EN
Figure 144: An example for estimating the remaining life of a circuit breaker
Calculation for estimating the remaining life
The graph shows that there are 10000 possible operations at the rated operating currentand 900 operations at 10 kA and 50 operations at rated fault current. Therefore, if theinterrupted current is 10 kA, one operation is equivalent to 10000/900 = 11 operationsat the rated current. It is assumed that prior to tripping, the remaining life of a breakeris 10000 operations. Remaining life calculation for three different interrupted currentconditions is explained below.
• Breaker interrupts at and below the rated operating current, that is, 2 kA, theremaining life of the CB is decreased by 1 operation and therefore, 9999operations remaining at the rated operating current.
• Breaker interrupts between rated operating current and rated fault current, that is,10 kA, one operation at 10kA is equivalent to 10000/900 = 11 operations at the
Section 15 1MRK 506 375-UEN -Monitoring
344 Railway application RER670 2.2 IECApplication manual
rated current. The remaining life of the CB would be (10000 – 10) = 9989 at therated operating current after one operation at 10 kA.
• Breaker interrupts at and above rated fault current, that is, 50 kA, one operationat 50 kA is equivalent to 10000/50 = 200 operations at the rated operating current.The remaining life of the CB would become (10000 – 200) = 9800 operations atthe rated operating current after one operation at 50 kA.
Accumulated energyMonitoring the contact erosion and interrupter wear has a direct influence on therequired maintenance frequency. Therefore, it is necessary to accurately estimate theerosion of the contacts and condition of interrupters using cumulative summation ofIy. The factor "y" depends on the type of circuit breaker. The energy values wereaccumulated using the current value and exponent factor for CB contact openingduration. When the next CB opening operation is started, the energy is accumulatedfrom the previous value. The accumulated energy value can be reset to initialaccumulation energy value by using the Reset accumulating energy input, RSTIPOW.
Circuit breaker operation cyclesRoutine breaker maintenance like lubricating breaker mechanism is based on thenumber of operations. A suitable threshold setting helps in preventive maintenance.This can also be used to indicate the requirement for oil sampling for dielectric testingin case of an oil circuit breaker.
Circuit breaker operation monitoringBy monitoring the activity of the number of operations, it is possible to calculate thenumber of days the breaker has been inactive. Long periods of inactivity degrade thereliability for the protection system.
Circuit breaker spring charge monitoringFor normal circuit breaker operation, the circuit breaker spring should be chargedwithin a specified time. Detecting a long spring charging time indicates the time forcircuit breaker maintenance. The last value of the spring charging time can be givenas a service value.
Circuit breaker gas pressure indicationFor proper arc extinction by the compressed gas in the circuit breaker, the pressure ofthe gas must be adequate. Binary input available from the pressure sensor is based onthe pressure levels inside the arc chamber. When the pressure becomes too lowcompared to the required value, the circuit breaker operation is blocked.
15.4.3 Setting guidelines
The breaker monitoring function is used to monitor different parameters of the circuitbreaker. The breaker requires maintenance when the number of operations hasreached a predefined value. For proper functioning of the circuit breaker, it is alsoessential to monitor the circuit breaker operation, spring charge indication or breaker
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 345Application manual
wear, travel time, number of operation cycles and accumulated energy during arcextinction.
15.4.3.1 Setting procedure on the IED
The parameters for breaker monitoring (SSCBR) can be set using the local HMI orProtection and Control Manager (PCM600).
Common base IED values for primary current (IBase), primary voltage (UBase) andprimary power (SBase) are set in Global base values for settings function GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
Operation: On or Off.
OpenTimeCorr: Correction factor for circuit breaker opening travel time.
CloseTimeCorr: Correction factor for circuit breaker closing travel time.
tTrOpenAlm: Setting of alarm level for opening travel time.
tTrCloseAlm: Setting of alarm level for closing travel time.
OperAlmLevel: Alarm limit for number of mechanical operations.
OperLOLevel: Lockout limit for number of mechanical operations.
CurrExponent: Current exponent setting for energy calculation. It varies for differenttypes of circuit breakers. This factor ranges from 0.5 to 3.0.
AccStopCurr: RMS current setting below which calculation of energy accumulationstops. It is given as a percentage of IBase.
ContTrCorr: Correction factor for time difference in auxiliary and main contacts'opening time.
AlmAccCurrPwr: Setting of alarm level for accumulated energy.
LOAccCurrPwr: Lockout limit setting for accumulated energy.
SpChAlmTime: Time delay for spring charging time alarm.
tDGasPresAlm: Time delay for gas pressure alarm.
tDGasPresLO: Time delay for gas pressure lockout.
DirCoef: Directional coefficient for circuit breaker life calculation.
RatedOperCurr: Rated operating current of the circuit breaker.
RatedFltCurr: Rated fault current of the circuit breaker.
OperNoRated: Number of operations possible at rated current.
Section 15 1MRK 506 375-UEN -Monitoring
346 Railway application RER670 2.2 IECApplication manual
OperNoFault: Number of operations possible at rated fault current.
CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of maincontact separation.
15.5 Event function EVENT
15.5.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Event function EVENT
S00946 V1 EN
-
15.5.2 Application
When using a Substation Automation system with LON or SPA communication,time-tagged events can be sent at change or cyclically from the IED to the station level.These events are created from any available signal in the IED that is connected to theEvent function (EVENT). The EVENT function block is used for LON and SPAcommunication.
Analog, integer and double indication values are also transferred through the EVENTfunction.
15.5.3 Setting guidelines
The input parameters for the Event function (EVENT) can be set individually via thelocal HMI (Main Menu/Settings / IED Settings / Monitoring / Event Function) orvia the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)The inputs can be set individually as:
• NoEvents• OnSet, at pick-up of the signal• OnReset, at drop-out of the signal• OnChange, at both pick-up and drop-out of the signal• AutoDetect, the EVENT function makes the reporting decision (reporting criteria
for integers have no semantic, prefer to be set by the user)
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 347Application manual
LONChannelMask or SPAChannelMaskDefinition of which part of the event function block that shall generate events:
• Off• Channel 1-8• Channel 9-16• Channel 1-16
MinRepIntVal (1 - 16)A time interval between cyclic events can be set individually for each input channel.This can be set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, thatis, no cyclic communication.
It is important to set the time interval for cyclic events in an optimizedway to minimize the load on the station bus.
15.6 Disturbance report DRPRDRE
15.6.1 IdentificationFunction description IEC 61850 identification IEC 60617
identificationANSI/IEEE C37.2device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -
15.6.2 Application
To get fast, complete and reliable information about disturbances in the primary and/or in the secondary system it is very important to gather information on fault currents,voltages and events. It is also important having a continuous event-logging to be ableto monitor in an overview perspective. These tasks are accomplished by thedisturbance report function DRPRDRE and facilitate a better understanding of thepower system behavior and related primary and secondary equipment during and aftera disturbance. An analysis of the recorded data provides valuable information that canbe used to explain a disturbance, basis for change of IED setting plan, improveexisting equipment, and so on. This information can also be used in a longerperspective when planning for and designing new installations, that is, a disturbancerecording could be a part of Functional Analysis (FA).
Disturbance report DRPRDRE, always included in the IED, acquires sampled data ofall selected analog and binary signals connected to the function blocks that is,
Section 15 1MRK 506 375-UEN -Monitoring
348 Railway application RER670 2.2 IECApplication manual
• Maximum 30 external analog signals,• 10 internal derived analog signals, and• 352 binary signals
Disturbance report function is a common name for several functions; Indications(IND), Event recorder (ER), Event list (EL), Trip value recorder (TVR), Disturbancerecorder (DR) and Fault locator (FL).
Disturbance report function is characterized by great flexibility as far asconfiguration, starting conditions, recording times, and storage capacity areconcerned. Thus, disturbance report is not dependent on the operation of protectivefunctions, and it can record disturbances that were not discovered by protectivefunctions for one reason or another. Disturbance report can be used as an advancedstand-alone disturbance recorder.
Every disturbance report recording is saved in the IED. The same applies to all events,which are continuously saved in a ring-buffer. Local HMI can be used to getinformation about the recordings, and the disturbance report files may be uploaded inthe PCM600 using the Disturbance handling tool, for report reading or further analysis(using WaveWin, that can be found on the PCM600 installation CD). The user canalso upload disturbance report files using FTP or MMS (over 61850–8–1) clients.
If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder(record made and fault number) and the fault locator information are available. Thesame information is obtainable if IEC 60870-5-103 is used.
15.6.3 Setting guidelines
The setting parameters for the Disturbance report function DRPRDRE are set via thelocal HMI or PCM600.
It is possible to handle up to 40 analog and 352 binary signals, either internal signalsor signals coming from external inputs. The binary signals are identical in all functionsthat is, Disturbance recorder (DR), Event recorder (ER), Indication (IND), Trip valuerecorder (TVR) and Event list (EL) function.
User-defined names of binary and analog input signals is set using PCM600. Theanalog and binary signals appear with their user-defined names. The name is used inall related functions (Disturbance recorder (DR), Event recorder (ER), Indication(IND), Trip value recorder (TVR) and Event list (EL)).
Figure 145 shows the relations between Disturbance report, included functions andfunction blocks. Event list (EL), Event recorder (ER) and Indication (IND) usesinformation from the binary input function blocks (BxRBDR). Trip value recorder(TVR) uses analog information from the analog input function blocks (AxRADR),which is used by Fault locator (FL) after estimation by Trip Value Recorder (TVR).Disturbance report function acquires information from both AxRADR and BxRBDR.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 349Application manual
Trip value rec Fault locator
Event list
Event recorder
Indications
Disturbancerecorder
Disturbance Report
Binary signals
Analog signals
DRPRDRE FL
IEC09000336-3-en.vsdx
AxRADR
BxRBDR
IEC09000336 V3 EN
Figure 145: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influencesthe sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quickstatus information about the IED.
Green LED:
Steady light In Service
Flashing light Internal failure
Dark No power supply
Yellow LED:
Steady light Triggered on binary signal N with SetLEDx = Start (or Start andTrip)
Flashing light The IED is in test mode
Red LED:
Steady light Triggered on binary signal N with SetLEDx = Trip (or Start andTrip)
Flashing The IED is in configuration mode
Section 15 1MRK 506 375-UEN -Monitoring
350 Railway application RER670 2.2 IECApplication manual
OperationThe operation of Disturbance report function DRPRDRE has to be set On or Off. If Offis selected, note that no disturbance report is registered, and none sub-function willoperate (the only general parameter that influences Event list (EL)).
Operation = Off:
• Disturbance reports are not stored.• LED information (yellow - start, red - trip) is not stored or changed.
Operation = On:
• Disturbance reports are stored, disturbance data can be read from the local HMIand from a PC for example using PCM600.
• LED information (yellow - start, red - trip) is stored.
Every recording will get a number (0 to 999) which is used as identifier (local HMI,disturbance handling tool and IEC 61850). An alternative recording identification isdate, time and sequence number. The sequence number is automatically increased byone for each new recording and is reset to zero at midnight. The maximum number ofrecordings stored in the IED is 100. The oldest recording will be overwritten when anew recording arrives (FIFO).
To be able to delete disturbance records, Operation parameter has tobe On.
The maximum number of recordings depend on each recordings totalrecording time. Long recording time will reduce the number ofrecordings to less than 100.
The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of diskspace.
15.6.3.1 Recording times
The different recording times for Disturbance report are set (the pre-fault time, post-fault time, and limit time). These recording times affect all sub-functions more or lessbut not the Event list (EL) function.
Prefault recording time (PreFaultRecT) is the recording time before the starting pointof the disturbance. The setting should be at least 0.1 s to ensure enough samples for theestimation of pre-fault values in the Trip value recorder (TVR) function.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 351Application manual
Postfault recording time (PostFaultRecT) is the maximum recording time after thedisappearance of the trig-signal (does not influence the Trip value recorder (TVR)function).
Recording time limit (TimeLimit) is the maximum recording time after trig. Theparameter limits the recording time if some trigging condition (fault-time) is very longor permanently set (does not influence the Trip value recorder (TVR) function).
Operation in test modeIf the IED is in test mode and OpModeTest = Off. Disturbance report function does notsave any recordings and no LED information is displayed.
If the IED is in test mode and OpModeTest = On. Disturbance report function worksin normal mode and the status is indicated in the saved recording.
Post RetriggerDisturbance report function does not automatically respond to any new trig conditionduring a recording, after all signals set as trigger signals have been reset. However,under certain circumstances the fault condition may reoccur during the post-faultrecording, for instance by automatic reclosing to a still faulty power line.
In order to capture the new disturbance it is possible to allow retriggering (PostRetrig= On) during the post-fault time. In this case a new, complete recording will start and,during a period, run in parallel with the initial recording.
When the retrig parameter is disabled (PostRetrig = Off), a new recording will not startuntil the post-fault (PostFaultrecT or TimeLimit) period is terminated. If a new trigoccurs during the post-fault period and lasts longer than the proceeding recording anew complete recording will be started.
Disturbance report function can handle a maximum of 3 simultaneous disturbancerecordings.
15.6.3.2 Binary input signals
Up to 352 binary signals can be selected among internal logical and binary inputsignals. The configuration tool is used to configure the signals.
For each of the 352 signals, it is also possible to select if the signal is to be used as atrigger for the start of the Disturbance report and if the trigger should be activated onpositive (1) or negative (0) slope.
OperationN: Disturbance report may trig for binary input N (On) or not (Off).
TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary inputN.
Func103N: Function type number (0-255) for binary input N according toIEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection, 176:transformer differential protection and 192: line differential protection.
Section 15 1MRK 506 375-UEN -Monitoring
352 Railway application RER670 2.2 IECApplication manual
Info103N: Information number (0-255) for binary input N according toIEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
15.6.3.3 Analog input signals
Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.
For retrieving remote data from LDCM module, the Disturbancereport function should be connected to a 8 ms SMAI function block ifthis is the only intended use for the remote data.
The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relativenominal value for analog input M in percent of nominal value.
15.6.3.4 Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
IndicationsIndicationMaN: Indication mask for binary input N. If set (Show), a status change ofthat particular input, will be fetched and shown in the disturbance summary on localHMI. If not set (Hide), status change will not be indicated.
SetLEDN: Set red LED on local HMI in front of the IED if binary input N changesstatus.
Disturbance recorderOperationM: Analog channel M is to be recorded by the disturbance recorder (On) ornot (Off).
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 353Application manual
If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in graph.
Event recorderEvent recorder (ER) function has no dedicated parameters.
Trip value recorderZeroAngleRef: The parameter defines which analog signal that will be used as phaseangle reference for all other analog input signals. This signal will also be used forfrequency measurement and the measured frequency is used when calculating tripvalues. It is suggested to point out a sampled voltage input signal, for example, a lineor busbar phase voltage (channel 1-30).
Event listEvent list (EL) (SOE) function has no dedicated parameters.
15.6.3.5 Consideration
The density of recording equipment in power systems is increasing, since the numberof modern IEDs, where recorders are included, is increasing. This leads to a vastnumber of recordings at every single disturbance and a lot of information has to behandled if the recording functions do not have proper settings. The goal is to optimizethe settings in each IED to be able to capture just valuable disturbances and tomaximize the number that is possible to save in the IED.
The recording time should not be longer than necessary (PostFaultrecT andTimeLimit).
• Should the function record faults only for the protected object or cover more?• How long is the longest expected fault clearing time?• Is it necessary to include reclosure in the recording or should a persistent fault
generate a second recording (PostRetrig)?
Minimize the number of recordings:
• Binary signals: Use only relevant signals to start the recording that is, protectiontrip, carrier receive and/or start signals.
• Analog signals: The level triggering should be used with great care, sinceunfortunate settings will cause enormously number of recordings. If neverthelessanalog input triggering is used, chose settings by a sufficient margin from normaloperation values. Phase voltages are not recommended for trigging.
There is a risk of flash wear out if the disturbance report triggers toooften.
Section 15 1MRK 506 375-UEN -Monitoring
354 Railway application RER670 2.2 IECApplication manual
Remember that values of parameters set elsewhere are linked to the information on areport. Such parameters are, for example, station and object identifiers, CT and VTratios.
15.7 Logical signal status report BINSTATREP
15.7.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Logical signal status report BINSTATREP - -
15.7.2 Application
The Logical signal status report (BINSTATREP) function makes it possible to pollsignals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs andcan be read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the inputsignal remains set for a longer period, the output will remain set until the input signalresets.
t t
INPUTn
OUTPUTn
IEC09000732-1-en.vsdIEC09000732 V1 EN
Figure 146: BINSTATREP logical diagram
15.7.3 Setting guidelines
The pulse time t is the only setting for the Logical signal status report(BINSTATREP). Each output can be set or reset individually, but the pulse time willbe the same for all outputs in the entire BINSTATREP function.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 355Application manual
15.8 Limit counter L4UFCNT
15.8.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Limit counter L4UFCNT -
15.8.2 Application
Limit counter (L4UFCNT) is intended for applications where positive and/or negativeflanks on a binary signal need to be counted.
The limit counter provides four independent limits to be checked against theaccumulated counted value. The four limit reach indication outputs can be utilized toinitiate proceeding actions. The output indicators remain high until the reset of thefunction.
It is also possible to initiate the counter from a non-zero value by resetting the functionto the wanted initial value provided as a setting.
If applicable, the counter can be set to stop or rollover to zero and continue countingafter reaching the maximum count value. The steady overflow output flag indicatesthe next count after reaching the maximum count value. It is also possible to set thecounter to rollover and indicate the overflow as a pulse, which lasts up to the first countafter rolling over to zero. In this case, periodic pulses will be generated at multipleoverflow of the function.
15.8.3 Setting guidelines
The parameters for Limit counter L4UFCNT are set via the local HMI or PCM600.
15.9 Running hour-meter TEILGAPC
15.9.1 IdentificationFunction Description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2 devicenumber
Running hour-meter TEILGAPC - -
Section 15 1MRK 506 375-UEN -Monitoring
356 Railway application RER670 2.2 IECApplication manual
15.9.2 Application
The function is used for user-defined logics and it can also be used for differentpurposes internally in the IED. An application example is to accumulate the totalrunning/energized time of the generator, transformer, reactor, capacitor bank or evenline.
Settable time limits for warning and alarm are provided. The time limit for overflowindication is fixed to 99999.9 hours. At overflow the accumulated time resets and theaccumulation starts from zero again.
15.9.3 Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in hours. Theachievable resolution of the settings is 0.1 hours (6 minutes).
tAlarm and tWarning are independent settings, that is, there is nocheck if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting tAddToTime is a user settable time parameter in hours.
15.10 Fault locator RWRFLO
15.10.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Fault locator RWRFLO -
15.10.2 Application
The main purpose of line protection and monitoring IEDs is to provide fast, selectiveand reliable operation regarding faults on a protected line section.
Information on distance-to-fault is more important for those involved in operation andmaintenance. Reliable information on fault location greatly decreases the downtimeof protected lines, and increases the total availability of the power system.
Transmission lines are typically made of single type of conductor. If a transmissionline is made of more than one section, the line parameters are different for eachsection, and the set-up cannot be considered as one single line. Fault locationalgorithms for a single line will thus not meet accuracy requirements in railway supply
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 357Application manual
system. This can be explained by considering an example of transmission line with 3sections as shown in the figure 147:
Source A
1 2 3
RFLO
Source B
IEC15000299-1-en.vsdx
IEC15000299 V1 EN
Figure 147: Single line diagram with three line sections
For example, consider a case where the line angle of line 1 is 70 degrees, line 2 is 55degrees and line 3 is 45 degrees. The area that remains between line sections 1, 2, 3 andthe sum of the three line sections denotes inaccuracy (see figure 148). Thus summingup of the line parameters and considering it as one line should not be done for faultlocation algorithm.
R(Ohm)
X(O
hm
)
1+2+
3
2
1
3
IEC15000300-1-en.vsdx
IEC15000300 V1 EN
Figure 148: R-X diagram showing positive sequence impedances of three linesections
The fault locator (RWRFLO) is started with the input CALCDIST to which trip signalsindicating in-line faults are connected, typically distance protection zone 1 andaccelerating zone or the line differential protection. Disturbance report must also be
Section 15 1MRK 506 375-UEN -Monitoring
358 Railway application RER670 2.2 IECApplication manual
started for the same faults since the function uses pre-fault and fault information fromthe trip value recorder function (TVR).
Besides this, the function must be informed about faulted phases for correct loopselection (phase-selective outputs from distance protections, directional over-currentprotection and so on). The following loops are used for different types of faults:
• For two-phase faults: loop L1-L2• For phase-to-earth faults: L1N, L2N : phase-to-earth loop
RWRFLO function indicates distance-to-faults as a percentage of the line length andin kilometres. The calculated distance-to-fault is stored together with the recordeddisturbances. Information can be read on the local HMI or uploaded to PCM600. Isalso available on the station bus according to IEC 61850-8-1.
Distance-to-fault can be recalculated on the local HMI by using the measuringalgorithm for different fault loops.
15.10.3 Setting guidelines
In RWRFLO, the setting NrOfSections is set according to the number of sectionsavailable in the transmission line. The maximum number of sections in the faultlocator is ten.
The setting parameters are:
LineLength1 Set with length of section 1 in km
RL1 Set with positive sequence resistance of section 1 per phase
XL1 Set with positive sequence reactance of section 1 per phase
REOverRL1 Set with ratio of RE by RL of section 1, this can be derived from positive and zerosequences impedances as:
1*2
1011
RL
RLRREOverRL
IECEQUATION15082 V1 EN
Where R01 is zero sequence resistance of section 1 per phase.
XEOverXL1 Set with ratio of XE by XL of section 1, this can be derived from positive and zerosequences impedances as:
1*2
1011
XL
XLXXEOverXL
IECEQUATION15083 V1 EN
Where X01 is zero sequence reactance of section 1 per phase.
The settings are set in the same way for line sections 2, 3 and so on.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 359Application manual
15.10.3.1 Setting example
Consider a 110kV/16.7Hz system with three transmission line sections (see Figure149).
Source A
1 2 3
RFLO
Source B
IEC15000299-1-en.vsdx
IEC15000299 V1 EN
Figure 149: Single line diagram with three line sections
RWRFLO function should set for the NrOfSections. Since number of transmissionline sections is three, the NrOfSections should also be set to three (3). Table 34provides the system line specifications for three transmission lines.
Table 34: Line specifications for three transmission line sections
Parameter Line section 1 Line section 2 Line section 3LineLength(km) 4.8 40.3 18.2
RL Positive sequenceresistance (Ohm/Ph.)
RL1 = 0.575 RL2= 11.122 RL3= 5.609
XL Positive sequencereactance (Ohm/Ph.)
XL1 = 1.206 XL2= 10.034 XL3= 4.765
R0 Zero sequenceresistance (Ohm/Ph.)
R01 = 0.543 R02 = 8.293 R03 = 3.752
X0 Zero sequencereactance (Ohm/Ph.)
X01 = 1.284 X02 = 12.429 X03 = 6.858
Setting related to line section 1
1*2
1011
RL
RLRREOverRL
IECEQUATION15082 V1 EN (Equation 72)
REOverRL1 = The positive sequence resistance. REOverRL1 should be set as-0.02783.
1*2
1011
XL
XLXXEOverXL
IECEQUATION15083 V1 EN (Equation 73)
XEOverXL1 = The positive sequence reactance. REOverRL1 should be set as 0.0323.
Section 15 1MRK 506 375-UEN -Monitoring
360 Railway application RER670 2.2 IECApplication manual
Setting related to line section 2
2*2
2022
RL
RLRREOverRL
IECEQUATION15112 V1 EN (Equation 74)
REOverRL2 = The positive sequence resistance. REOverRL2 should be set as -0.1272.
2*2
2022
XL
XLXXEOverXL
IECEQUATION15113 V1 EN (Equation 75)
XEOverXL2 = The positive sequence reactance. REOverRL2 should be set as 0.1193.
Setting related to line section 3
3*2
3033
RL
RLRREOverRL
IECEQUATION15114 V1 EN (Equation 76)
REOverRL3 = The positive sequence resistance. REOverRL3 should be set as-0.16554.
3*2
3033
XL
XLXXEOverXL
IECEQUATION15115 V1 EN (Equation 77)
XEOverXL3 = The positive sequence reactance. REOverRL3 should be set as 0.219.
1MRK 506 375-UEN - Section 15Monitoring
Railway application RER670 2.2 IEC 361Application manual
Section 16 Metering
16.1 Pulse-counter logic PCFCNT
16.1.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Pulse-counter logic PCFCNT
S00947 V1 EN
-
16.1.2 Application
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses,for instance pulses coming from an external energy meter, for calculation of energyconsumption values. The pulses are captured by the binary input module (BIM), andread by the PCFCNT function. The number of pulses in the counter is then reported viathe station bus to the substation automation system or read via the station monitoringsystem as a service value. When using IEC 61850–8–1, a scaled service value isavailable over the station bus.
The normal use for this function is the counting of energy pulses from external energymeters. An optional number of inputs from an arbitrary input module in IED can beused for this purpose with a frequency of up to 40 Hz. The pulse-counter logicPCFCNT can also be used as a general purpose counter.
16.1.3 Setting guidelines
Parameters that can be set individually for each pulse counter from PCM600:
• Operation: Off/On• tReporting: 0-3600s• EventMask: NoEvents/ReportEvents
Configuration of inputs and outputs of PCFCNT is made via PCM600.
1MRK 506 375-UEN - Section 16Metering
Railway application RER670 2.2 IEC 363Application manual
On the Binary input module (BIM), the debounce filter default time is set to 1 ms, thatis, the counter suppresses pulses with a pulse length less than 1 ms. The inputoscillation blocking frequency is preset to 40 Hz meaning that the counter detects theinput to oscillate if the input frequency is greater than 40 Hz. Oscillation suppressionis released at 30 Hz. Block/release values for oscillation can be changed on the localHMI and PCM600 under Main menu/Configuration/I/O modules.
The setting is common for all input channels on BIM, that is, if limitchanges are made for inputs not connected to the pulse counter, thesetting also influences the inputs on the same board used for pulsecounting.
16.2 Function for energy calculation and demand handlingETPMMTR
16.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Function for energy calculation anddemand handling
ETPMMTR W_Varh -
16.2.2 Application
Energy calculation and demand handling function (ETPMMTR) is intended forstatistics of the forward and reverse active and reactive energy. It has a high accuracybasically given by the measurements function (CVMMXN). This function has a sitecalibration possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of (CVMMXN) as shown infigure 150.
Section 16 1MRK 506 375-UEN -Metering
364 Railway application RER670 2.2 IECApplication manual
CVMMXN
P_INST
Q_INST
ETPMMTR
P
Q
RSTACC
RSTDMD
STARTACC
STOPACC
IEC13000190-2-en.vsdx
IEC13000190 V2 EN
Figure 150: Connection of energy calculation and demand handling functionETPMMTR to the measurements function (CVMMXN)
The energy values can be read through communication in MWh and MVArh inmonitoring tool of PCM600 and/or alternatively the values can be presented on thelocal HMI. The local HMI graphical display is configured with PCM600 GraphicalDisplay Editor tool (GDE) with a measuring value which is selected to the active andreactive component as preferred. Also all Accumulated Active Forward, ActiveReverse, Reactive Forward and Reactive Reverse energy values can be presented.
Maximum demand values are presented in MWh or MVArh in the same way.
Alternatively, the energy values can be presented with use of the pulse countersfunction (PCGGIO). The output energy values are scaled with the pulse output settingvalues EAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERVAccPlsQty of theenergy metering function and then the pulse counter can be set-up to present thecorrect values by scaling in this function. Pulse counter values can then be presentedon the local HMI in the same way and/or sent to the SA (Substation Automation)system through communication where the total energy then is calculated bysummation of the energy pulses. This principle is good for very high values of energyas the saturation of numbers else will limit energy integration to about one year with50 kV and 3000 A. After that the accumulation will start on zero again.
16.2.3 Setting guidelines
The parameters are set via the local HMI or PCM600.
The following settings can be done for the energy calculation and demand handlingfunction ETPMMTR:
GlobalBaseSel: Selects the global base value group used by the function to defineIBase, UBase and SBase as applicable.
Operation: Off/On
1MRK 506 375-UEN - Section 16Metering
Railway application RER670 2.2 IEC 365Application manual
EnaAcc: Off/On is used to switch the accumulation of energy on and off.
tEnergy: Time interval when energy is measured.
tEnergyOnPls: gives the pulse length ON time of the pulse. It should be at least 100ms when connected to the Pulse counter function block. Typical value can be 100 ms.
tEnergyOffPls: gives the OFF time between pulses. Typical value can be 100 ms.
EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It should beselected together with the setting of the Pulse counter (PCGGIO) settings to give thecorrect total pulse value.
ERFAccPlsQty and ERVAccPlsQty : gives the MVArh value in each pulse. It shouldbe selected together with the setting of the Pulse counter (PCGGIO) settings to givethe correct total pulse value.
For the advanced user there are a number of settings for direction, zero clamping, maxlimit, and so on. Normally, the default values are suitable for these parameters.
Section 16 1MRK 506 375-UEN -Metering
366 Railway application RER670 2.2 IECApplication manual
Section 17 Ethernet-based communication
17.1 Access point
17.1.1 Application
The access points are used to connect the IED to the communication buses (like thestation bus) that use communication protocols. The access point can be used for singleand redundant data communication. The access points are also used forcommunication with the merging units and for time synchronization using PrecisionTime Protocol (PTP).
17.1.2 Setting guidelines
The physical ports allocated to access points 2–6 have to be added inthe hardware tool in PCM600 before the access points can beconfigured. The factory setting only includes the physical portsallocated to the front port and access point 1.
The settings for the access points are configured using the Ethernet configuration tool(ECT) in PCM600.
The access point is activated if the Operation checkbox is checked for the respectiveaccess point and a partial or common write to IED is performed.
To increase security, it is recommended to deactivate the access pointwhen it is not in use.
Redundancy and PTP cannot be set for the front port (Access point 0) as redundantcommunication and PTP are only available for the rear optical Ethernet ports.
Subnetwork shows the SCL subnetwork to which the access point is connected. Thiscolumn shows the SCL subnetworks available in the PCM600 project. SCLsubnetworks can be created/deleted in the Subnetworks tab of IEC 61850Configuration tool in PCM600.
When saving the ECT configuration after selecting a subnetwork,ECT creates the access point in the SCL model. Unselecting thesubnetwork removes the access point from the SCL model. Thiscolumn is editable for IEC61850 Ed2 IEDs and not editable for
1MRK 506 375-UEN - Section 17Ethernet-based communication
Railway application RER670 2.2 IEC 367Application manual
IEC61850 Ed1 IEDs because in IEC61850 Ed1 only one access pointcan be modelled in SCL.
The IP address can be set in IP address. ECT validates the value, the access pointshave to be on separate subnetworks.
The subnetwork mask can be set in Subnet mask. This field will be updated to the SCLmodel based on the Subnetwork selection.
To select which communication protocols can be run on the respective access points,check or uncheck the check box for the relevant protocol. The protocols are notactivated/deactivated in ECT, only filtered for the specific access point. Forinformation on how to activate the individual communication protocols, see thecommunication protocol chapters.
To increase security it is recommended to uncheck protocols that arenot used on the access point.
The default gateway can be selected by entering the IP address in Default gateway.The default gateway is the router that is used to communicate with the devices in theother subnetwork. By default this is set to 0.0.0.0 which means that no default gatewayis selected. ECT validates the entered value, but the default gateway has to be in thesame subnetwork as the access point. The default gateway is the router that is beingused as default, that is when no route has been set up for the destination. Ifcommunication with a device in another subnetwork is needed, a route has to be set up.For more information on routes, see the Routes chapter in the Technical manual andthe Application manual.
DHCP can be activated for the front port from the LHMI in Main menu/Configuration/Communication/Ethernet configuration/Front port/DHCP:1
17.2 Redundant communication
17.2.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
IEC 62439-3 Parallel redundancyprotocol
PRP - -
IEC 62439-3 High-availability seamlessredundancy
HSR - -
Access point diagnostic for redundantEthernet ports
RCHLCCH - -
Section 17 1MRK 506 375-UEN -Ethernet-based communication
368 Railway application RER670 2.2 IECApplication manual
17.2.2 Application
Dynamic access point diagnostic (RCHLCCH) is used to supervise and assureredundant Ethernet communication over two channels. This will secure data transfereven though one communication channel might not be available for some reason
Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy(HSR) provides redundant communication over station bus running the availablecommunication protocols. The redundant communication uses two Ethernet ports.
IEC09000758-4-en.vsd
Switch A
AP1 PhyPortB PhyPortA
AP1 PhyPortA PhyPortB
AP1
PhyPortB PhyPortA
AP1
PhyPortA PhyPortB
Switch B
Device 1 Device 2
Device 3 Device 4
IEC09000758 V4 EN
Figure 151: Parallel Redundancy Protocol (PRP)
1MRK 506 375-UEN - Section 17Ethernet-based communication
Railway application RER670 2.2 IEC 369Application manual
IEC16000038-1-en.vsdx
AP1 PhyPortB PhyPortA
AP1 PhyPortA PhyPortB
AP1
PhyPortA PhyPortB
AP1
PhyPortB PhyPortA
Device 1 Device 2
Device 3 Device 4
IEC16000038 V1 EN
Figure 152: High-availability Seamless Redundancy (HSR)
17.2.3 Setting guidelines
Redundant communication is configured with the Ethernet configuration tool inPCM600.
Redundancy: redundant communication is activated when the parameter is set toPRP-0, PRP-1 or HSR. The settings for the next access point will be hidden andPhyPortB will show the second port information. Redundant communication isactivated after a common write to IED is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-networks. PRP-1 and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in EthernetConfiguration Tool can be used to activate the access point.
Section 17 1MRK 506 375-UEN -Ethernet-based communication
370 Railway application RER670 2.2 IECApplication manual
IEC16000039-1-en.vsdx
IEC16000039 V1 EN
Figure 153: ECT screen with Redundancy set to PRP-1 on Access point 1 andHSR Access point 3
17.3 Merging unit
17.3.1 Application
The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED tocommunicate with devices providing measured values in digital format, commonlyknown as Merging Units (MU). The rear access points are used for thecommunication.
The merging units (MU) are called so because they can gather analog values from oneor more measuring transformers, sample the data and send the data over process busto other clients (or subscribers) in the system. Some merging units are able to get datafrom classical measuring transformers, others from non-conventional measuringtransducers and yet others can pick up data from both types.
When configuring RER670 for 9-2LE streams in a 16.7Hz system, theIED shall be set to 16.7Hz and the MU to 50Hz (4kHz sampling).
1MRK 506 375-UEN - Section 17Ethernet-based communication
Railway application RER670 2.2 IEC 371Application manual
IEC17000044-1-en.vsdx
IEC17000044 V1 EN
Figure 154: Merging unit
17.3.2 Setting guidelines
For information on the merging unit setting guidelines, see section IEC/UCA61850-9-2LE communication protocol.
17.4 Routes
17.4.1 Application
Setting up a route enables communication to a device that is located in anothersubnetwork. Routing is used when the destination device is not in the samesubnetwork as the default gateway.
The route specifies that when a package is sent to the destination device it should besent through the selected router. If no route is specified the source device will not findthe destination device.
17.4.2 Setting guidelines
Routes are configured using the Ethernet configuration tool in PCM600.
Operation for the route can be set to On/Off by checking and unchecking the check-box in the operation column.
Gateway specifies the address of the gateway.
Destination specifies the destination.
Destination subnet mask specifies the subnetwork mask of the destination.
Section 17 1MRK 506 375-UEN -Ethernet-based communication
372 Railway application RER670 2.2 IECApplication manual
Section 18 Station communication
18.1 Communication protocols
Each IED is provided with several communication interfaces enabling it to connect toone or many substation level systems or equipment, either on the SubstationAutomation (SA) bus or Substation Monitoring (SM) bus.
Available communication protocols are:
• IEC 61850-8-1 communication protocol• IEC/UCA 61850-9-2LE communication protocol• LON communication protocol• SPA communication protocol• IEC 60870-5-103 communication protocol• DNP 3.0 communication protocol
Several protocols can be combined in the same IED.
18.2 IEC 61850-8-1 communication protocol
18.2.1 Application IEC 61850-8-1
IEC 61850-8-1 communication protocol allows vertical communication to HSIclients and allows horizontal communication between two or more intelligentelectronic devices (IEDs) from one or several vendors to exchange information and touse it in the performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard, allows the IEDs to communicate state and control information amongstthemselves, using a publish-subscribe mechanism. That is, upon detecting an event,the IED(s) use a multi-cast transmission to notify those devices that have registered toreceive the data. An IED can, by publishing a GOOSE message, report its status. It canalso request a control action to be directed at any device in the network.
Figure 155 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1specifies only the interface to the substation LAN. The LAN itself is left to the systemintegrator.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 373Application manual
KIOSK 2 KIOSK 3
Station HSIBase System
EngineeringWorkstation
SMSGateway
Printer
CC
IEC09000135_en.vsd
KIOSK 1
IED 1
IED 2
IED 3
IED 1
IED 2
IED 3
IED 1
IED 2
IED 3
IEC09000135 V1 EN
Figure 155: SA system with IEC 61850–8–1
Figure156 shows the GOOSE peer-to-peer communication.
Control Protection Control ProtectionControl and protection
GOOSE
en05000734.vsd
Station HSIMicroSCADA
Gateway
IEDA
IEDA
IEDA
IEDA
IEDA
IEC05000734 V1 EN
Figure 156: Example of a broadcasted GOOSE message
Section 18 1MRK 506 375-UEN -Station communication
374 Railway application RER670 2.2 IECApplication manual
18.2.2 Setting guidelines
There are two settings related to the IEC 61850–8–1 protocol:
Operation: User can set IEC 61850 communication to On or Off.
GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sentand received. This is only valid for Edition 1 and can be ignored if Edition 2 is used.For Edition 2, the Ethernet link selection is done with the Ethernet Configuration Tool(ECT) in PCM600.
18.2.3 Horizontal communication via GOOSE
18.2.3.1 Sending data
In addition to the data object and data attributes of the logical nodes, it is possible tosend the outputs of the function blocks using the generic communication blocks. Theoutputs of this function can be set in a dataset and be sent in a GOOSE Control Blockto other subscriber IEDs. There are different function blocks for different type ofsending data.
Generic communication function for Single Point indication SPGAPC,SP16GAPC
ApplicationGeneric communication function for Single Point Value (SPGAPC) function is usedto send one single logical output to other systems or equipment in the substation.SP16GAPC can be used to send up to 16 single point values from the applicationfunctions running in the same cycle time. SPGAPC has one visible input andSPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelinesThere are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
ApplicationGeneric communication function for measured values (MVGAPC) function is used tosend the instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to ananalog value and to permit measurement supervision on that value.
Setting guidelinesThe settings available for Generic communication function for Measured Value(MVGAPC) function allows the user to choose a deadband and a zero deadband forthe monitored signal. Values within the zero deadband are considered as zero.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 375Application manual
The high and low limit settings provides limits for the high-high-, high, normal, lowand low-low ranges of the measured value. The actual range of the measured value isshown on the range output of MVGAPC function block. When a Measured valueexpander block (RANGE_XP) is connected to the range output, the logical outputs ofthe RANGE_XP are changed accordingly.
18.2.3.2 Receiving data
The GOOSE data must be received at function blocks. There are different GOOSEreceiving function blocks depending on the type of the received data. Refer to theEngineering manual for more information about how to configure GOOSE.
Function block type Data TypeGOOSEBINRCV 16 single point
GOOSEINTLKRCV 2 single points16 double points
GOOSEDPRCV Double point
GOOSEINTRCV Integer
GOOSEMVRCV Analog value
GOOSESPRCV Single point
GOOSEXLNRCV Switch status
ApplicationThe GOOSE receive function blocks are used to receive subscribed data from theGOOSE protocol. The validity of the data value is exposed as outputs of the functionblock as well as the validity of the communication. It is recommended to use theseoutputs to ensure that only valid data is handled on the subscriber IED. An examplecould be to control the external reservation before operating on a bay. In the figurebelow, the GOOSESPRCV is used to receive the status of the bay reservation. Thevalidity of the received data is used in additional logic to guarantee that the value hasgood quality before operation on that bay.
GOOSESPRCV
Block Spout DataValid CommValid Test
AND AND
Input1 outInput2 NoputInput3Input4
Input1 outInput2 NoputInput3Input4
Ext_Res_OK_To_Operate
IEC16000082=1=en.vsdIEC16000082 V1 EN
Figure 157: GOOSESPRCV and AND function blocks - checking the validity ofthe received data
Section 18 1MRK 506 375-UEN -Station communication
376 Railway application RER670 2.2 IECApplication manual
18.3 IEC/UCA 61850-9-2LE communication protocol
18.3.1 Introduction
Every IED can be provided with communication interfaces enabling it to connect tothe process buses in order to get data from analog data acquisition units close to theprocess (primary apparatus), commonly known as Merging Units (MU). The protocolused in this case is the IEC/UCA 61850-9-2LE communication protocol.
The IEC/UCA 61850-9-2LE standard does not specify the quality of the sampledvalues. Thus, the accuracy of the current and voltage inputs to the merging unit and theinaccuracy added by the merging unit must be coordinated with the requirement forthe actual type of protection function.
Factors influencing the accuracy of the sampled values from the merging unit are, forexample, anti aliasing filters, frequency range, step response, truncating, A/Dconversion inaccuracy, time tagging accuracy etc.
In principle, the accuracy of the current and voltage transformers, together with themerging unit, will have the same quality as the direct input of currents and voltages.
The process bus physical layout can be arranged in several ways, described in AnnexB of the standard, depending on what are the needs for sampled data in a substation.
IEC06000537 V1 EN
Figure 158: Example of a station configuration with separated process bus andstation bus
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 377Application manual
The IED can get analog values simultaneously from a classical CT or VT and from aMerging Unit, like in this example:
The merging units (MU) are called so because they can gather analog values from oneor more measuring transformers, sample the data and send the data over process busto other clients (or subscribers) in the system. Some merging units are able to get datafrom classical measuring transformers, others from non-conventional measuringtransducers and yet others can pick up data from both types. The electronic part of anon-conventional measuring transducer (like a Rogowski coil or a capacitive divider)can represent a MU by itself as long as it can send sampled data over process bus.
Section 18 1MRK 506 375-UEN -Station communication
378 Railway application RER670 2.2 IECApplication manual
CTCT
ABBMerging
Unit
Ethernet Switch
IED
CombiSensor
Conventional VT
IEC61850-9-2LE
IEC61850-9-2LE
SplitterElectrical-to-
Optical Converter
1PPS
1PPS
110 V1 A1 A
IEC61850-8-1
Station Wide SCADA System
Station Wide GPS Clock
Other Relays
IEC61850-8-1
en08000069-3.vsd
IEC08000069 V2 EN
Figure 159: Example of a station configuration with the IED receiving analogvalues from both classical measuring transformers and mergingunits.
18.3.2 Setting guidelines
Merging Units (MUs) have several settings on local HMI under:
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 379Application manual
• Main menu/Configuration/Analog modules/MUx:92xx. The correspondingsettings are also available in PST (PCM600).
• Main menu/Configuration/Communication/Merging units configuration/MUx:92xx. The corresponding settings are also available in ECT (PCM600).
XX can take value 01–12.
18.3.2.1 Specific settings related to the IEC/UCA 61850-9-2LE communication
The process bus communication IEC/UCA 61850-9-2LE has specific settings, similarto the analog inputs modules.
If there are more than one sample group involved, time synch is mandatory. If there isno time synchronization, the protection functions will be blocked due to conditionblocking.
CTStarPointx: These parameters specify the direction to or from object. See alsosection "Setting of current channels".
SyncLostMode: If this parameter is set to Block and the IED hardware timesynchronization is lost or the synchronization to the MU time is lost, the protectionfunctions in the list 35 will be blocked due to conditional blocking. If this parameteris set to BlockOnLostUTC, the protection functions in list 35 are blocked if the IEDhardware time synchronization is lost or the synchronization of the MU time is lost orthe IED has lost global common synchronization (i.e. GPS, IRIG-B or PTP). SYNCHoutput will be set if IED hardware time synchronization is lost. MUSYNCH output willbe set if either of MU or IED hardware time synchronization is lost.
18.3.2.2 Loss of communication when used with LDCM
If IEC/UCA 61850-9-2LE communication is lost, see examples in figures 160, 161and 162, the protection functions in table 35 are blocked as per graceful degradation.
Case 1:
IEC13000298-2-en.vsd
IEDIED
MU
OK
OK
Direct transfer trip (DTT) local remote
IEC13000298 V2 EN
Figure 160: Normal operation
Section 18 1MRK 506 375-UEN -Station communication
380 Railway application RER670 2.2 IECApplication manual
Case 2:
Failure of the MU (sample lost) blocks the sending of binary signals through LDCM.The received binary signals are not blocked and processd normally.
→DTT from the remote end is still processed.
IEC13000299-2-en.vsd
Direct transfer trip (DTT) local remote
IEDIED
MU
Not OK
OK
IEC13000299 V2 EN
Figure 161: MU failed, mixed system
Case 3:
Failure of one MU (sample lost) blocks the sending and receiving of binary signalsthrough LDCM.
→DTT from the remote end is not working.
IEC13000300-2-en.vsd
Direct transfer trip (DTT) local remote
IEDIED
MU
Not OK
Not OK
MU
IEC13000300 V2 EN
Figure 162: MU failed, 9-2 system
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 381Application manual
Table 35: Blocked protection functions if IEC/UCA 61850-9-2LE communication is interruptedand functions are connected to specific MUs
Function description IEC 61850 identification Function description IEC 61850 identificationAccidental energizingprotection forsynchronous generator
AEGPVOC Two step overvoltageprotection
O2RWPTOV
Overcurrent protectionwith binary release
BRPTOC Four step single phaseovercurrent protection
PH4SPTOC
Capacitor bankprotection
CBPGAPC Radial feederprotection
PAPGAPC
Pole discordanceprotection
CCPDSC Instantaneous phaseovercurrent protection
PHPIOC
Breaker failureprotection
CCRWRBRF PoleSlip/Out-of-stepprotection
PSPPPAM
Breaker failureprotection, singlephase version
CCSRBRF Restricted earth faultprotection, lowimpedance
REFPDIF
Current circuitsupervison
CCSSPVC Two step residualovervoltage protection
ROV2PTOV
Compensated over-and undervoltageprotection
COUVGAPC Rate-of-changefrequency protection
SAPFRC
General currrent andvoltage protection
CVGAPC Overfrequencyprotection
SAPTOF
Current reversal andweakend infeed logicfor residual overcurrentprotection
ECRWPSCH Underfrequencyprotection
SAPTUF
Two step residualovercurrent protection
EF2PTOC Sudden change incurrent variation
SCCVPTOC
Instantaneous residualovercurrent protection
EFRWPIOC Sensitive Directionalresidual over currentand power protetcion
SDEPSDE
Phase selection,quadrilateralcharacteristic with fixedangle
FDPSPDIS Synchrocheck,energizing check, andsynchronizing
SESRSYN
Faulty phaseidentification with loadenchroachment
FMPSPDIS Circuit breakercondition monitoring
SSCBR
Phase selection,quadrilateralcharacteristic withsettable angle
FRPSPDIS Insulation gasmonitoring
SSIMG
Frequency timeaccumulationprotection
FTAQFVR Insulation liquidmonitoring
SSIML
Fuse failuresupervision
FRWSPVC Stub protection STBPTOC
Generator differentialprotection
GENPDIF Transformer differentialprotection, two winding
T1PPDIF
Table continues on next page
Section 18 1MRK 506 375-UEN -Station communication
382 Railway application RER670 2.2 IECApplication manual
Function description IEC 61850 identification Function description IEC 61850 identificationDirectional Overpowerprotection
GOPPDOP Transformer differentialprotection, threewinding
T3WPDIF
Generator rotoroverload protection
GRPTTR Automatic voltagecontrol for tapchanger,single control
TR1ATCC
Generator statoroverload protection
GSPTTR Automatic voltagecontrol for tapchanger,parallel control
TR8ATCC
DirectionalUnderpower protection
GUPPDUP Thermal overloadprotection, two timeconstants
TRPTTR
1Ph High impedancedifferential protection
HZPDIF Two step undervoltageprotection
U2RWPTUV
Line differentialprotection, 3 CT sets,2-3 line ends
L3CPDIF Voltage differentialprotection
VDCPTOV
Line differentialprotection, 6 CT sets,3-5 line ends
L6CPDIF Fuse failuresupervision
VDRFUF
Low active power andpower factor protection
LAPPGAPC Voltage-restrained timeovercurrent protection
VRPVOC
Negative sequenceovercurrent protection
LCNSPTOC Local acceleration logic ZCLCPSCH
Negative sequenceovervoltage protection
LCNSPTOV Schemecommunication logicfor distance orovercurrent protection
ZCPSCH
Three phaseovercurrent
LCP3PTOC Current reversal andweak-end infeed logicfor distance protection
ZCRWPSCH
Three phaseundercurrent
LCP3PTUC Automatic switch ontofault logic, voltage andcurrent based
ZCVPSOF
Thermal overloadprotection, one timeconstant
LCPTTR Underimpedanceprotection forgenerators andtransformers
ZGTPDIS
Zero sequenceovercurrent protection
LCZSPTOC Fast distanceprotection
ZMFCPDIS
Zero sequenceovervoltage protection
LCZSPTOV High speed distanceprotection
ZMFPDIS
Line differentialcoordination
LDLPSCH Distance measuringzone, quadrilateralcharacteristic for seriescompensated lines
ZMCAPDIS
Additional securitylogic for differentialprotection
LDRGFC Distance measuringzone, quadrilateralcharacteristic for seriescompensated lines
ZMCPDIS
Loss of excitation LEXPDIS Fullscheme distanceprotection, mhocharacteristic
ZMHPDIS
Table continues on next page
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 383Application manual
Function description IEC 61850 identification Function description IEC 61850 identificationThermal overloadprotection, one timeconstant
LFPTTR Fullscheme distanceprotection,quadrilateral for earthfaults
ZMMAPDIS
Loss of voltage check LOVPTUV Fullscheme distanceprotection,quadrilateral for earthfaults
ZMMPDIS
Line differentialprotection 3 CT sets,with inzonetransformers, 2-3 lineends
LT3CPDIF Distance protectionzone, quadrilateralcharacteristic
ZMQAPDIS
Line differentialprotection 6 CT sets,with inzonetransformers, 3-5 lineends
LT6CPDIF Distance protectionzone, quadrilateralcharacteristic
ZMQPDIS
Negativ sequence timeovercurrent protectionfor machines
NS2PTOC Distance protectionzone, quadrilateralcharacteristic, separatesettings
ZMRAPDIS
Four step directionalnegative phasesequence overcurrentprotection
NS4PTOC Distance protectionzone, quadrilateralcharacteristic, separatesettings
ZMRPDIS
Four step phaseovercurrent protection
OC4PTOC Power swing detection ZMRPSB
Overexcitationprotection
OEXPVPH Mho Impedancesupervision logic
ZSMGAPC
Out-of-step protection OOSPPAM Transformer tankovercurrent protection
TPPIOC
Transformerenergization control
XENCPOW Fault locator, multisection
RWRFLO
Two steps directionalphase overcurrentprotection
D2PTOC Distance protection,quadrilateralcharacteristic
ZRWPDIS
18.3.2.3 Setting examples for IEC/UCA 61850-9-2LE and time synchronization
The IED and the Merging Units (MU) should use the same time reference especiallyif analog data is used from several sources, for example from an internal TRM and anMU, or if several physical MUs are used. Having the same time reference is importantto correlate data so that channels from different sources refer to the correct phaseangle.
When only one MU is used as an analog source, it is theoretically possible to dowithout time synchronization. However, this would mean that timestamps for analogand binary data/events become uncorrelated. If the IED has no time synchronizationsource configured, then the binary data/events will be synchronized with the mergingunit. However, the global/complete time might not be correct. Disturbance recordingsthen appear incorrect since analog data is timestamped by MU, and binary events use
Section 18 1MRK 506 375-UEN -Station communication
384 Railway application RER670 2.2 IECApplication manual
the internal IED time. It is thus recommended to use time synchronization also whenanalog data emanate from only one MU.
An external time source can be used to synchronize both the IED and the MU. It is alsopossible to use the MU as a clock master to synchronize the IED from the MU. Whenusing an external clock, it is possible to set the IED to be synchronized via PPS, IRIG-B or PTP. It is also possible to use an internal GPS receiver in the IED (if the externalclock is using GPS).
Using PTP for synchronizing the MU
SAM600 VT SAM600 CT
SAM600 TS
IED
PTP9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN
Figure 163: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 385Application manual
• HwSyncSrc: is not used as the SW-time and HW-time are connected with eachother due to PTP
• SyncLostMode : set to Block to block protection functions if time synchronizationis lost or set to BlockOnLostUTC if the protection functions are to be blockedwhen global common synchronization is lost
• SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase angleerror of 0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/Ethernet configuration/Access point/AP_X:
• Operation: On• PTP: On
Two status monitoring signals can be:
• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED
• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.
Using MU for time synchronization via PPS
This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.
IED
MU
Analog data
PPS
IEC/UCA 61850-9-2LE
Synchronization
IEC10000061=2=en=Original.vsd
IEC10000061 V2 EN
Figure 164: Setting example when MU is the synchronizing source
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
Section 18 1MRK 506 375-UEN -Station communication
386 Railway application RER670 2.2 IECApplication manual
• HwSyncSrc: set to PPS as generated by the MU (ABB MU)• SyncLostMode : set to Block to block protection functions if time synchronization
is lost• SyncAccLevel: can be set to 4μs since this corresponds to a maximum phase angle
error of 0.072 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/General:
• fineSyncSource can be set to something different to correlate events and data toother IEDs in the station.
Two status monitoring signals can be:
• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED.
• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.
SMPLLOST indicates that merging unit data are generated by internal substitution orone/more channel's Quality is not good or merging unit is in Testmode/detailedquality=Test, IED is not in test mode.
Using external clock for time synchronization
This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.
IED
MU
data
PPS
IEC/UCA 61850-9-2LE
PPS / IRIG-B
STATIONCLOCK
IEC10000074=2=en=Original.vsd
IEC10000074 V2 EN
Figure 165: Setting example with external synchronization
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 387Application manual
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
• HwSyncSrc: set to PPS/IRIG-B depending on available outputs on the clock• SyncLostMode: set to Block to block protection functions if time synchronization
is lost• SyncAccLevel: can be set to 4μs since this corresponds to a maximum phase angle
error of 0.072 degrees at 50Hz• fineSyncSource: should be set to IRIG-B if available from the clock. If PPS is used
for HWSyncSrc , “full-time” has to be acquired from another source. If stationclock is on the local area network (LAN) and has an sntp-server, this is one option.
Two status monitoring signals can be:
• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED (that is loss of thehardware synchSrc).
• MUSYNCH signal on the MUx function block monitors the synchronization flagsmpSynch in the datastream and IED hardware time synchronization.
No time synchronization
This example is not valid when GPS time is used for differentialprotection, when PTP is enabled or when the PMU report is used.
IEC/UCA 61850-9-2LE
Data
MU
IED
IEC10000075=2=en=Original.vsd
IEC10000075 V2 EN
Figure 166: Setting example without time synchronization
It is also possible to use IEC/UCA 61850-9-2LE communication without timesynchronization.
Section 18 1MRK 506 375-UEN -Station communication
388 Railway application RER670 2.2 IECApplication manual
Settings on the local HMI under Main menu/Configuration/Time/Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
• HwSyncSrc: set to Off• SyncLostMode: set to No block to indicate that protection functions are not
blocked• SyncAccLevel: set to unspecified
Two status monitoring signals with no time synchronization:
• SYNCH signal on the MUx function block indicates that protection functions areblocked due to loss of internal time synchronization to the IED. SinceSyncLostMode is set to No block, this signal is not set.
• MUSYNCH signal on the MUx function block is set if the datastream indicatestime synchronization loss. However, protection functions are not blocked.
To get higher availability in protection functions, it is possible to avoid blockingduring time synchronization loss if there is a single source of analog data. This meansthat if there is only one physical MU and no TRM, parameter SyncLostMode is set toNo block but parameter HwSyncSrc is still set to PPS. This maintains analog andbinary data correlation in disturbance recordings without blocking protectionfunctions if PPS is lost.
18.3.3 IEC 61850 quality expander QUALEXP
The quality expander component is used to display the detailed quality of anIEC/UCA 61850-9-2LE analog channel. The component expands the channel qualityoutput of a Merging Unit analog channel received in the IED as per the IEC 61850-7-3standard. This component can be used during the ACT monitoring to get the particularchannel quality of the Merging Unit.
Figure 167 depicts the usage of the quality expander block in ACT.
IEC16000073-1-en.vsdx
IEC16000073 V1 EN
Figure 167: Quality expander block in ACT
The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard.When written to IED, the configuration will show the expanded form of the respectiveMU channel quality information during the online monitoring in the ACT.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 389Application manual
The quality expander function is intended for monitoring purposes,not for being used in a logic controlling the behaviour of the protectionor control functions in the IED. The function outputs are updated onceevery second and, therefore, do not reflect the quality bits in real time.
18.4 LON communication protocol
18.4.1 Application
Control Center
IED IEDIED
Gateway
Star couplerRER 111
Station HSIMicroSCADA
IEC05000663-1-en.vsd
IEC05000663 V2 EN
Figure 168: Example of LON communication structure for a substationautomation system
An optical network can be used within the substation automation system. This enablescommunication with the IEDs through the LON bus from the operator’s workplace,from the control center and also from other IEDs via bay-to-bay horizontalcommunication. For LON communication an SLM card should be ordered for theIEDs.
The fibre optic LON bus is implemented using either glass core or plastic core fibreoptic cables.
Section 18 1MRK 506 375-UEN -Station communication
390 Railway application RER670 2.2 IECApplication manual
Table 36: Specification of the fibre optic connectors
Glass fibre Plastic fibreCable connector ST-connector snap-in connector
Cable diameter 62.5/125 m 1 mm
Max. cable length 1000 m 10 m
Wavelength 820-900 nm 660 nm
Transmitted power -13 dBm (HFBR-1414) -13 dBm (HFBR-1521)
Receiver sensitivity -24 dBm (HFBR-2412) -20 dBm (HFBR-2521)
The LON ProtocolThe LON protocol is specified in the LonTalkProtocol Specification Version 3 fromEchelon Corporation. This protocol is designed for communication in controlnetworks and is a peer-to-peer protocol where all the devices connected to the networkcan communicate with each other directly. For more information of the bay-to-baycommunication, refer to the section Multiple command function.
Hardware and software modulesThe hardware needed for applying LON communication depends on the application,but one very central unit needed is the LON Star Coupler and optical fibres connectingthe star coupler to the IEDs. To interface the IEDs from the MicroSCADA withClassic Monitor, application library LIB520 is required.
The HV Control 670 software module is included in the LIB520 high-voltage processpackage, which is a part of the Application Software Library in MicroSCADAapplications.
The HV Control 670 software module is used for control functions in the IEDs. Themodule contains a process picture, dialogues and a tool to generate a process databasefor the control application in MicroSCADA.
When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB isused together with 670 series Object Type files.
The HV Control 670 software module and 670 series Object Typefiles are used with both 650 and 670 series IEDs.
Use the LON Network Tool (LNT) to set the LON communication. This is a softwaretool applied as one node on the LON bus. To communicate via LON, the IEDs needto know
• The node addresses of the other connected IEDs.• The network variable selectors to be used.
This is organized by LNT.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 391Application manual
The node address is transferred to LNT via the local HMI by setting the parameterServicePinMsg = Yes. The node address is sent to LNT via the LON bus, or LNT canscan the network for new nodes.
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This canbe changed by LNT.
18.4.2 MULTICMDRCV and MULTICMDSND
18.4.2.1 Identification
Function description IEC 61850identification
IEC 60617identification
ANSI/IEEE C37.2device number
Multiple command and receive MULTICMDRCV - -
Multiple command and send MULTICMDSND - -
18.4.2.2 Application
The IED provides two function blocks enabling several IEDs to send and receivesignals via the interbay bus. The sending function block, MULTICMDSND, takes 16binary inputs. LON enables these to be transmitted to the equivalent receivingfunction block, MULTICMDRCV, which has 16 binary outputs.
18.4.2.3 Setting guidelines
SettingsThe parameters for the multiple command function are set via PCM600.
The Mode setting sets the outputs to either a Steady or Pulsed mode.
18.5 SPA communication protocol
18.5.1 Application
SPA communication protocol is an alternative to IEC 60870-5-103, and they use thesame rear communication port.
When communicating with a PC connected to the utility substation LAN via WANand the utility office LAN (see Figure 169), and when using the rear optical Ethernetport, the only hardware required for a station monitoring system is:
• Optical fibres from the IED to the utility substation LAN• PC connected to the utility office LAN
Section 18 1MRK 506 375-UEN -Station communication
392 Railway application RER670 2.2 IECApplication manual
IED IEDIED
Substation LAN
IEC05000715-4-en.vsd
Remote monitoring
Utility LAN
WAN
IEC05000715 V4 EN
Figure 169: SPA communication structure for a remote monitoring system via asubstation LAN, WAN and utility LAN
SPA communication is mainly used for the Station Monitoring System. It can includedifferent IEDs with remote communication possibilities. Connection to a PC can bemade directly (if the PC is located in the substation), via a telephone modem througha telephone network with ITU (former CCITT) characteristics or via a LAN/WANconnection.
glass <1000 m according to optical budget
plastic <25 m (inside cubicle) according to optical budget
FunctionalityThe SPA protocol V2.5 is an ASCII-based protocol for serial communication. Thecommunication is based on a master-slave principle, where the IED is a slave and thePC is the master. Only one master can be applied on each fibre optic loop. A programis required in the master computer for interpretation of the SPA-bus codes and fortranslation of the data that should be sent to the IED.
For the specification of the SPA protocol V2.5, refer to SPA-bus CommunicationProtocol V2.5.
18.5.2 Setting guidelines
SPA, IEC 60870-5-103 and DNP3 use the same rear communication port. This portcan be set for SPA use on the local HMI under Main menu /Configuration /Communication /Station communication/Port configuration/SLM optical serialport/PROTOCOL:1. When the communication protocol is selected, the IED isautomatically restarted, and the port then operates as a SPA port.
The SPA communication setting parameters are set on the local HMI under Mainmenu/Configuration/Communication/Station communication/SPA/SPA:1.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 393Application manual
The most important SPA communication setting parameters are SlaveAddress andBaudRate. They are essential for all communication contact to the IED. SlaveAddressand BaudRate can be set only on the local HMI for rear and front channelcommunication.
SlaveAddress can be set to any value between 1–899 as long as the slave number isunique within the used SPA loop. BaudRate (communication speed) can be setbetween 300–38400 baud. BaudRate should be the same for the whole stationalthough different communication speeds in a loop are possible. If differentcommunication speeds are used in the same fibre optical loop or RS485 network, takethis into account when making the communication setup in the communication master(the PC).
With local fibre optic communication, communication speed is usually set to 19200 or38400 baud. With telephone communication, the speed setting depends on the qualityof the connection and the type of modem used. Refer to technical data to determine therated communication speed for the selected communication interfaces.
The IED does not adapt its speed to the actual communicationconditions because the communication speed is set on the local HMI.
Section 18 1MRK 506 375-UEN -Station communication
394 Railway application RER670 2.2 IECApplication manual
18.6 IEC 60870-5-103 communication protocol
18.6.1 Application
TCP/IP
Control Center
IED IEDIED
Gateway
Star coupler
Station HSI
IEC05000660-4-en.vsdIEC05000660 V4 EN
Figure 170: Example of IEC 60870-5-103 communication structure for asubstation automation system
IEC 60870-5-103 communication protocol is mainly used when a protection IEDcommunicates with a third party control or monitoring system. This system must havesoftware that can interpret the IEC 60870-5-103 communication messages.
When communicating locally in the station using a Personal Computer (PC) or aRemote Terminal Unit (RTU) connected to the Communication and processingmodule, the only hardware needed is optical fibres and an opto/electrical converter forthe PC/RTU, or a RS-485 connection depending on the used IED communicationinterface.
18.6.1.1 Functionality
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information with a control system. In IEC terminology aprimary station is a master and a secondary station is a slave. The communication isbased on a point-to-point principle. The master must have software that can interpretthe IEC 60870-5-103 communication messages. For detailed information about IEC60870-5-103, refer to IEC 60870 standard part 5: Transmission protocols, and to the
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 395Application manual
section 103, Companion standard for the informative interface of protectionequipment.
18.6.1.2 Design
GeneralThe protocol implementation consists of the following functions:
• Event handling• Report of analog service values (measurands)• Fault location• Command handling
• Autorecloser ON/OFF• Teleprotection ON/OFF• Protection ON/OFF• LED reset• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)• Time synchronization
HardwareWhen communicating locally with a Personal Computer (PC) or a Remote TerminalUnit (RTU) in the station, using the SPA/IEC port, the only hardware needed is:·Optical fibres, glass/plastic· Opto/electrical converter for the PC/RTU· PC/RTU
CommandsThe commands defined in the IEC 60870-5-103 protocol are represented in dedicatedfunction blocks. These blocks have output signals for all available commandsaccording to the protocol. For more information, refer to the Communication protocolmanual, IEC 60870-5-103.
• IED commands in control direction
Function block with defined IED functions in control direction, I103IEDCMD. Thisblock use PARAMETR as FUNCTION TYPE, and INFORMATION NUMBERparameter is defined for each output signal.
• Function commands in control direction
Function block with pre-defined functions in control direction, I103CMD. This blockincludes the FUNCTION TYPE parameter, and the INFORMATION NUMBERparameter is defined for each output signal.
• Function commands in control direction
Section 18 1MRK 506 375-UEN -Station communication
396 Railway application RER670 2.2 IECApplication manual
Function block with user defined functions in control direction, I103UserCMD. Thesefunction blocks include the FUNCTION TYPE parameter for each block in the privaterange, and the INFORMATION NUMBER parameter for each output signal.
Status
For more information on the function blocks below, refer to theCommunication protocol manual, IEC 60870-5-103.
The events created in the IED available for the IEC 60870-5-103 protocol are basedon the:
• IED status indication in monitor direction
Function block with defined IED functions in monitor direction, I103IED. This blockuse PARAMETER as FUNCTION TYPE, and INFORMATION NUMBERparameter is defined for each input signal.
• Function status indication in monitor direction, user-defined
Function blocks with user defined input signals in monitor direction, I103UserDef.These function blocks include the FUNCTION TYPE parameter for each block in theprivate range, and the INFORMATION NUMBER parameter for each input signal.
• Supervision indications in monitor direction
Function block with defined functions for supervision indications in monitordirection, I103Superv. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.
• Earth fault indications in monitor direction
Function block with defined functions for earth fault indications in monitor direction,I103EF. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.
• Fault indications in monitor direction
Function block with defined functions for fault indications in monitor direction,I103FLTPROT. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each input signal.
This block is suitable for distance protection, line differential, transformerdifferential, over-current and earth-fault protection functions.
• Autorecloser indications in monitor direction
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 397Application manual
Function block with defined functions for autorecloser indications in monitordirection, I103AR. This block includes the FUNCTION TYPE parameter, and theINFORMATION NUMBER parameter is defined for each output signal.
MeasurandsThe measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to thestandard.
• Measurands in public range
Function block that reports all valid measuring types depending on connected signals,I103Meas.
• Measurands in private range
Function blocks with user defined input measurands in monitor direction,I103MeasUsr. These function blocks include the FUNCTION TYPE parameter foreach block in the private range, and the INFORMATION NUMBER parameter foreach block.
Fault locationThe fault location is expressed in reactive ohms. In relation to the line length inreactive ohms, it gives the distance to the fault in percent. The data is available andreported when the fault locator function is included in the IED.
Disturbance recordings
• The transfer functionality is based on the Disturbance recorder function. Theanalog and binary signals recorded will be reported to the master by polling. Theeight last disturbances that are recorded are available for transfer to the master. Afile that has been transferred and acknowledged by the master cannot betransferred again.
• The binary signals that are included in the disturbance recorder are those that areconnected to the disturbance function blocks B1RBDR to B22RBDR. Thesefunction blocks include the function type and the information number for eachsignal. For more information on the description of the Disturbance report in theTechnical reference manual. The analog channels, that are reported, are thoseconnected to the disturbance function blocks A1RADR to A4RADR. The eightfirst ones belong to the public range and the remaining ones to the private range.
18.6.2 Settings
Section 18 1MRK 506 375-UEN -Station communication
398 Railway application RER670 2.2 IECApplication manual
18.6.2.1 Settings for RS485 and optical serial communication
General settingsSPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM opticalserial port while DNP and IEC 60870-5-103 additionally can utilize the RS485 port.A single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.
1. The port specific IEC 60870-5-103 protocol parameters are configured under:Main menu/Configuration/Communication/Station Communication/IEC60870-5-103/• <config-selector>• SlaveAddress• BaudRate• RevPolarity (optical channel only)• CycMeasRepTime• MasterTimeDomain• TimeSyncMode• EvalTimeAccuracy• EventRepMode• CmdMode• RepIntermediatePos
<config-selector> is:• “OPTICAL103:1” for the optical serial channel on the SLM• “RS485103:1” for the RS485 port
2. The protocol to activate on a physical port is selected under:Main menu/Configuration/Communication/Station Communication/Portconfiguration/• RS485 port
• RS485PROT:1 (off, DNP, IEC103)• SLM optical serial port
• PROTOCOL:1 (off, DNP, IEC103, SPA)
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
Figure 171: Settings for IEC 60870-5-103 communication
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 399Application manual
The general settings for IEC 60870-5-103 communication are the following:
• SlaveAddress and BaudRate: Settings for slave number and communicationspeed (baud rate).The slave number can be set to any value between 1 and 254. The communicationspeed, can be set either to 9600 bits/s or 19200 bits/s.
• RevPolarity: Setting for inverting the light (or not). Standard IEC 60870-5-103setting is On.
• CycMeasRepTime: See I103MEAS function block for more information.• EventRepMode: Defines the mode for how events are reported. The event buffer
size is 1000 events.
Event reporting modeIf EventRepMode = SeqOfEvent, all GI and spontaneous events will be delivered in theorder they were generated by BSW. The most recent value is the latest value delivered.All GI data from a single block will come from the same cycle.
If EventRepMode = HiPriSpont, spontaneous events will be delivered prior to GIevent. To prevent old GI data from being delivered after a new spontaneous event, thepending GI event is modified to contain the same value as the spontaneous event. Asa result, the GI dataset is not time-correlated.
18.6.2.2 Settings from PCM600
I103USEDEFFor each input of the I103USEDEF function there is a setting for the informationnumber of the connected signal. The information number can be set to any valuebetween 0 and 255. To get proper operation of the sequence of events the event masksin the event function is to be set to ON_CHANGE. For single-command signals, theevent mask is to be set to ON_SET.
In addition there is a setting on each event block for function type. Refer to descriptionof the Main Function type set on the local HMI.
CommandsAs for the commands defined in the protocol there is a dedicated function block witheight output signals. Use PCM600 to configure these signals. To realize theBlockOfInformation command, which is operated from the local HMI, the outputBLKINFO on the IEC command function block ICOM has to be connected to an inputon an event function block. This input must have the information number 20 (monitordirection blocked) according to the standard.
Disturbance RecordingsFor each input of the Disturbance recorder function there is a setting for theinformation number of the connected signal. The function type and the informationnumber can be set to any value between 0 and 255. To get INF and FUN for therecorded binary signals, there are parameters on the disturbance recorder for each
Section 18 1MRK 506 375-UEN -Station communication
400 Railway application RER670 2.2 IECApplication manual
input. The user must set these parameters to whatever he connects to thecorresponding input.
Refer to description of Main Function type set on the local HMI.
Recorded analog channels are sent with ASDU26 and ASDU31. One informationelement in these ASDUs is called ACC, and it indicates the actual channel to beprocessed. The channels on disturbance recorder are sent with an ACC as shown inTable 37.
Table 37: Channels on disturbance recorder sent with a given ACC
DRA#-Input ACC IEC 60870-5-103 meaning1 1 IL1
2 2 IL2
3 3 IL3
4 4 IN
5 5 UL1
6 6 UL2
7 7 UL3
8 8 UN
9 64 Private range
10 65 Private range
11 66 Private range
12 67 Private range
13 68 Private range
14 69 Private range
15 70 Private range
16 71 Private range
17 72 Private range
18 73 Private range
19 74 Private range
20 75 Private range
21 76 Private range
22 77 Private range
23 78 Private range
24 79 Private range
25 80 Private range
26 81 Private range
27 82 Private range
28 83 Private range
29 84 Private range
30 85 Private range
31 86 Private range
Table continues on next page
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 401Application manual
DRA#-Input ACC IEC 60870-5-103 meaning32 87 Private range
33 88 Private range
34 89 Private range
35 90 Private range
36 91 Private range
37 92 Private range
38 93 Private range
39 94 Private range
40 95 Private range
18.6.3 Function and information types
Product type IEC103mainFunType value Comment:
REL 128 Compatible range
REC 242 Private range, use default
RED 192 Compatible range
RET 176 Compatible range
REB 207 Private range
REG 150 Private range
REQ 245 Private range
RER 152 Private range
RES 118 Private range
Refer to the tables in the Technical reference manual /Station communication,specifying the information types supported by the communication protocol IEC60870-5-103.
To support the information, corresponding functions must be included in theprotection IED.
There is no representation for the following parts:
• Generating events for test mode• Cause of transmission: Info no 11, Local operation
Glass or plastic fibre should be used. BFOC/2.5 is the recommended interface to use(BFOC/2.5 is the same as ST connectors). ST connectors are used with the opticalpower as specified in standard.
Section 18 1MRK 506 375-UEN -Station communication
402 Railway application RER670 2.2 IECApplication manual
For more information, refer to IEC standard IEC 60870-5-103.
18.7 DNP3 Communication protocol
18.7.1 Application
For more information on the application and setting guidelines for the DNP3communication protocol refer to the DNP3 Communication protocol manual.
1MRK 506 375-UEN - Section 18Station communication
Railway application RER670 2.2 IEC 403Application manual
Section 19 Remote communication
19.1 Binary signal transfer
19.1.1 IdentificationFunction description IEC 61850 identification IEC 60617
identificationANSI/IEEE C37.2device number
Binary signal transfer, receiveBinSignRec1_1BinSignRec1_2BinSignReceive2
- -
Binary signal transfer, 2Mbitreceive
BinSigRec1_12MBinSigRec1_22M - -
Binary signal transfer,transmit
BinSignTrans1_1BinSignTrans1_2BinSignTransm2
- -
Binary signal transfer, 2Mbittransmit
BinSigTran1_12MBinSigTran1_22M - -
19.1.2 Application
The IEDs can be equipped with communication devices for line differentialcommunication (not applicable for RER670) and/or communication of binary signalsbetween IEDs. The same communication hardware is used for both purposes.
Sending of binary signals between two IEDs is used in teleprotection schemes and fordirect transfer trips. In addition to this, there are application possibilities, for example,blocking/enabling functionality in the remote substation, changing setting group inthe remote IED depending on the switching situation in the local substation and so on.
If equipped with a 64kbit/s LDCM module, the IED can be configured to send either192 binary signals or 3 analog and 8 binary signals to a remote IED. If equipped witha 2Mbps LDCM module, the IED can send 9 analog channels and 192 binary channelsto a remote IED.
Link forwardingIf it is not possible to have a communication link between each station, the solution hasbeen to set the protection up in a slave-master-slave configuration. This means that inFigure 172, only IED-B has access to all currents and, therefore, this is the only placewhere the differential current is evaluated. If the evaluation results in a trip, the tripsignal will be sent over the two communication links.
1MRK 506 375-UEN - Section 19Remote communication
Railway application RER670 2.2 IEC 405Application manual
IED-A IED-B IED-C
IEC16000077-1-en.vsd
3-end differential protection with two communication links
Ldcm312
Ldcm312
Ldcm313
Ldcm312
IEC16000077 V1 EN
Figure 172: Three-end differential protection with two communication links
If the LDCM is in 2Mbit mode, you can send the three local currents as well as thethree remote currents from the other links by configuring the transmitters in IED-B:
1. Ldcm312 transmitter sends the local currents and the three currents received byLdcm313.
2. Ldcm313 transmitter sends the three local currents and the three currents receivedfrom Ldcm312.
As a result, six currents are received in IED-A and IED-C. These currents can beconnected to the protection function together with the local three currents.
In order to forward the logic signals (for example, inter-trip or inter-block) between IED-A and IED-C, the setting LinkForwarded shouldbe defined. In IED-B, it is set to LDCM313 for Ldcm312 and toLDCM312 for ldcm313.
This setup results in a master-master-master configuration, but without the benefit ofreverting to a slave-master-slave configuration in case of a communication linkinterruption. In case of a communication link interruption, all three IEDs would beblocked.
19.1.2.1 Communication hardware solutions
The LDCM (Line Data Communication Module) has an optical connection such thattwo IEDs can be connected over a direct fibre, as shown in figure 173. The distanceto be covered with this solution is up to typical 3km (SR), 80km (MR) and 110km(LR).
Section 19 1MRK 506 375-UEN -Remote communication
406 Railway application RER670 2.2 IECApplication manual
LDCM
LDCM
LDCM
LDCMLDCM
LDCMLDCMLDCM
LDCMLDCM
LDCM
LDCMLD
CMLD
CM
LDCMLDCM
en06000519-2.vsdIEC06000519 V2 EN
Figure 173: Direct fibre optical connection between two IEDs with LDCM
The LDCM can also be used together with an external optical to galvanic G.703converter as shown in figure 174. These solutions are aimed for connections to amultiplexer, which in turn is connected to a telecommunications transmissionnetwork (for example PDH).
Telecom. Network
*) *)
Multiplexer Multiplexer
en05000527-2.vsd*) Converting optical to galvanic G.703
IEC05000527 V2 EN
Figure 174: LDCM with an external optical to galvanic converter and a multiplexer
When an external modem G.703 is used, the connection between LDCM and themodem is made with a multimode fibre of max. 3 km length. The IEEE/ANSI C37.94protocol is always used between LDCM and the modem.
19.1.3 Setting guidelines
64 kbit and 2 Mbit mode common settings
ChannelMode defines how an IED discards the LDCM information when one of theIEDs in the system is out of service: it can either be done on the IED out of service bysetting all local LDCMs to channel mode OutOfService or at the remote end by setting
1MRK 506 375-UEN - Section 19Remote communication
Railway application RER670 2.2 IEC 407Application manual
the corresponding LDCM to channel mode Blocked. If OutOfService is selected, theIED should have active communication to the remote end during the wholemaintenance process, that is, no restart or removal of the fibre can be done.
This setting does not apply to two-end communication.
Blocked IED does not use data from the LDCM
OutOfService IED informs the remote end that it is out of service
TerminalNo is used to assign a unique address to each LDCM in all current differentialIEDs. Up to 256 LDCMs can be assigned a unique number. For example, in a localIED with two LDCMs:
• LDCM for slot 305: set TerminalNo to 1 and RemoteTermNo to 2• LDCM for slot 306: set TerminalNo to 3 and RemoteTermNo to 4
In multiterminal current differential applications,with 4 LDCMs in each IED, up to 20unique addresses must be set.
A unique address is necessary to give high security against incorrectaddressing in the communication system. If the same number is usedfor TerminalNo in some of the LDCMs, a loop-back test in thecommunication system can give an incorrect trip.
RemoteTermNo is used to assign a number to each related LDCM in the remote IED.For each LDCM, RemoteTermNo is set to a different value than TerminalNo, but equalto the TerminalNo of the remote end LDCM. In the remote IED, TerminalNo andRemoteTermNo are reversed as follows:
• LDCM for slot 305: set TerminalNo to 2 and RemoteTermNo to 1• LDCM for slot 306: set TerminalNo to 4 and RemoteTermNo to 3
The redundant channel is always configured to the lower position, forexample:
• Slot 305: main channel• Slot 306: redundant channel
The same is applicable for slot 312-313 and slot 322-323.
DiffSync defines the method of time synchronization for the line differential function:Echo or GPS.
Section 19 1MRK 506 375-UEN -Remote communication
408 Railway application RER670 2.2 IECApplication manual
Using Echo in this case is safe only if there is no risk of varyingtransmission asymmetry.
GPSSyncErr: when GPS synchronization is lost, synchronization of the linedifferential function continues for 16 s based on the stability in the local IED clocks.After that, setting Block blocks the line differential function or setting Echo keeps iton by using the Echo synchronization method.
Using Echo in this case is safe only if there is no risk of varyingtransmission asymmetry.
CommSync defines the Master and Slave relation in the communication system, andshould not be mistaken for the synchronization of line differential current samples.When direct fibre is used, one LDCM is set as Master and the other as Slave. When amodem and multiplexer is used, the IED is always set as Slave because thetelecommunication system provides the clock master.
OptoPower has two settings: LowPower is used for fibres 0 – 1 km and HighPower forfibres >1 km.
ComAlarmDel defines the time delay for communication failure alarm. Incommunication systems, route switching can sometimes cause interruptions with aduration of up to 50 ms. Too short a time delay can thus cause nuisance alarms.
ComAlrmResDel defines the time delay for communication failure alarm reset.
RedChSwTime defines the time delay before switching over to a redundant channel incase of primary channel failure.
RedChRturnTime defines the time delay before switching back to the primary channelafter channel failure.
AsymDelay denotes asymmetry which is defined as transmission delay minus receivedelay. If fixed asymmetry is known, Echo synchronization method can be used,provided that AsymDelay is properly set. From the definition follows that asymmetryis always positive at one end and negative at the other end.
MaxTransmDelay indicates maximum transmission delay. Data for maximum 40 mstransmission delay can be buffered up. Delay times in the range of some ms arecommon. If data arrive in wrong order, the oldest data is disregarded.
MaxtDiffLevel indicates the maximum time difference allowed between internalclocks in respective line ends.
64 kbit mode specific settings
TransmCurr is used to select among the following:
1MRK 506 375-UEN - Section 19Remote communication
Railway application RER670 2.2 IEC 409Application manual
• one of the two possible local currents is transmitted• sum of the two local currents is transmitted• channel is used as a redundant backup channel
1½ breaker arrangement has two local currents, and the Current Transformer (CT)earthing for those can differ. CT-SUM transmits the sum of the two CT groups. CT-DIFF1 transmits CT group 1 minus CT group 2 and CT-DIFF2 transmits CT group 2minus CT group 1.
CT-GRP1 and CT-GRP2 transmit the respective CT groups, and settingRedundantChannel determines that the channel is used as a redundant backupchannel. The redundant channel takes the CT group setting of the main channel.
RemAinLatency corresponds to LocAinLatency set in the remote IED.
AnalogLatency specifies the time delay (number of samples) between actual samplingand the time the sample reaches LDCM. The value is set to 2 when transmitting analogdata. When a merging unit according to IEC 61850-9-2 is used instead of the TRM,this parameter shall be set to 5.
CompRange value indicates the current peak value over which truncation is made. Toset this value, knowledge of fault current levels is required. It is recommended to setthe minimum range that will cover the expected fault current value. For example, if a40kA fault level is expected on the network, the 0-50kA settings range should bechosen.
2 Mbit mode specific settings
RedundantCh is used to set the channel as a redundant backup channel. The redundantchannel takes the CT group setting of the main channel, and ignores the CT groupconfigured in its own transmit block.
LinkForwarded is used to configure the LDCM to merge the inter-trip and blocksignals from another LDCM-receiver. This is used when the analog signals for theLDCM-transmitter is connected to the receiver of another LDCM.
Section 19 1MRK 506 375-UEN -Remote communication
410 Railway application RER670 2.2 IECApplication manual
Section 20 Security
20.1 Authority status ATHSTAT
20.1.1 Application
Authority status (ATHSTAT) function is an indication function block, which informsabout two events related to the IED and the user authorization:
• the fact that at least one user has tried to log on wrongly into the IED and it wasblocked (the output USRBLKED)
• the fact that at least one user is logged on (the output LOGGEDON)
The two outputs of ATHSTAT function can be used in the configuration for differentindication and alarming reasons, or can be sent to the station control for the samepurpose.
20.2 Self supervision with internal event list INTERRSIG
20.2.1 Application
The protection and control IEDs have many functions included. The included self-supervision with internal event list function block provides good supervision of theIED. The fault signals make it easier to analyze and locate a fault.
Both hardware and software supervision is included and it is also possible to indicatepossible faults through a hardware contact on the power supply module and/orthrough the communication.
Internal events are generated by the built-in supervisory functions. The supervisoryfunctions supervise the status of the various modules in the IED and, in case of failure,a corresponding event is generated. Similarly, when the failure is corrected, acorresponding event is generated.
Apart from the built-in supervision of the various modules, events are also generatedwhen the status changes for the:
• built-in real time clock (in operation/out of order).• external time synchronization (in operation/out of order).
1MRK 506 375-UEN - Section 20Security
Railway application RER670 2.2 IEC 411Application manual
Events are also generated:
• whenever any setting in the IED is changed.
The internal events are time tagged with a resolution of 1 ms and stored in a list. Thelist can store up to 40 events. The list is based on the FIFO principle, that is, when itis full, the oldest event is overwritten. The list contents cannot be modified, but thewhole list can be cleared using the Reset menu in the LHMI.
The list of internal events provides valuable information, which can be used duringcommissioning and fault tracing.
The information can, in addition to be viewed on the built in HMI, also be retrievedwith the aid of a PC with PCM600 installed and by using the Event Monitoring Tool.The PC can either be connected to the front port, or to the port at the back of the IED.
20.3 Change lock CHNGLCK
20.3.1 Application
Change lock function CHNGLCK is used to block further changes to the IEDconfiguration once the commissioning is complete. The purpose is to make itimpossible to perform inadvertent IED configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that doesnot involve reconfiguring of the IED:
• Monitoring• Reading events• Resetting events• Reading disturbance data• Clear disturbances• Reset LEDs• Reset counters and other runtime component states• Control operations• Set system time• Enter and exit from test mode• Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The CHNGLCKfunction is configured using ACT.
LOCK Binary input signal that will activate/deactivate the function, defined in ACT orSMT.
Section 20 1MRK 506 375-UEN -Security
412 Railway application RER670 2.2 IECApplication manual
When CHNGLCK has a logical one on its input, then all attempts tomodify the IED configuration and setting will be denied and themessage "Error: Changes blocked" will be displayed on the localHMI; in PCM600 the message will be "Operation denied by activeChangeLock". The CHNGLCK function should be configured so thatit is controlled by a signal from a binary input card. This guaranteesthat by setting that signal to a logical zero, CHNGLCK is deactivated.If any logic is included in the signal path to the CHNGLCK input, thatlogic must be designed so that it cannot permanently issue a logicalone to the CHNGLCK input. If such a situation would occur in spiteof these precautions, then please contact the local ABB representativefor remedial action.
20.4 Denial of service SCHLCCH/RCHLCCH
20.4.1 Application
The denial of service functionality is designed to limit the CPU load that can beproduced by Ethernet network traffic on the IED. The communication facilities mustnot be allowed to compromise the primary functionality of the device. All inboundnetwork traffic will be quota controlled so that too heavy network loads can becontrolled. Heavy network load might for instance be the result of malfunctioningequipment connected to the network.
The functions Access point diagnostics function block measure the IED load fromcommunication and, if necessary, limit it for not jeopardizing the IEDs control andprotection functionality due to high CPU load. The function has the following denialof service related outputs:
• LINKSTS indicates the Ethernet link status for the rear ports (singlecommunication)
• CHALISTS and CHBLISTS indicates the Ethernet link status for the rear portschannel A and B (redundant communication)
• LinkStatus indicates the Ethernet link status for the front port
20.4.2 Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
1MRK 506 375-UEN - Section 20Security
Railway application RER670 2.2 IEC 413Application manual
Section 21 Basic IED functions
21.1 IED identifiers TERMINALID
21.1.1 Application
IED identifiers (TERMINALID) function allows the user to identify the individualIED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
21.2 Product information PRODINF
21.2.1 Application
Product information contains unchangeable data that uniquely identifies the IED.
Product information data is visible on the local HMI under Main menu/Diagnostics/IED status/Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers:
• ProductVer• ProductDef• FirmwareVer• SerialNo• OrderingNo• ProductionDate• IEDProdType
This information is very helpful when interacting with ABB product support (forexample during repair and maintenance).
21.2.2 Factory defined settings
The factory defined settings are very useful for identifying a specific version and veryhelpful in the case of maintenance, repair, interchanging IEDs between differentSubstation Automation Systems and upgrading. The factory made settings can not be
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 415Application manual
changed by the customer. They can only be viewed. The settings are found in the localHMI under Main menu/Diagnostics/IED status/Product identifiers
The following identifiers are available:
• IEDProdType• Describes the type of the IED. Example: REL670
• ProductDef• Describes the release number from the production. Example: 2.1.0
• FirmwareVer• Describes the firmware version.• The firmware version can be checked from Main menu/Diagnostics/IED
status/Product identifiers• Firmware version numbers run independently from the release production
numbers. For every release number there can be one or more firmwareversions depending on the small issues corrected in between releases.
• ProductVer• Describes the product version. Example: 2.1.0
1 is the Major version of the manufactured product this means, new platform of theproduct
2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product
3 is the Major revision of the manufactured product this means, functions or hardware iseither changed or enhanced in the product
• IEDMainFunType• Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).• SerialNo• OrderingNo• ProductionDate
21.3 Measured value expander block RANGE_XP
21.3.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Measured value expander block RANGE_XP - -
Section 21 1MRK 506 375-UEN -Basic IED functions
416 Railway application RER670 2.2 IECApplication manual
21.3.2 Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXUand VNMMXU), current and voltage sequence measurement functions (CMSQI andVMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) areprovided with measurement supervision functionality. All measured values can besupervised with four settable limits, that is low-low limit, low limit, high limit andhigh-high limit. The measure value expander block ( RANGE_XP) has beenintroduced to be able to translate the integer output signal from the measuringfunctions to 5 binary signals, that is below low-low limit, below low limit, normal,above high-high limit or above high limit. The output signals can be used as conditionsin the configurable logic.
21.3.3 Setting guidelines
There are no settable parameters for the measured value expander block function.
21.4 Parameter setting groups
21.4.1 Application
Six sets of settings are available to optimize IED operation for different power systemconditions. By creating and switching between fine tuned setting sets, either from thelocal HMI or configurable binary inputs, results in a highly adaptable IED that cancope with a variety of power system scenarios.
Different conditions in networks with different voltage levels require highly adaptableprotection and control units to best provide for dependability, security and selectivityrequirements. Protection units operate with a higher degree of availability, especially,if the setting values of their parameters are continuously optimized according to theconditions in the power system.
Operational departments can plan for different operating conditions in the primaryequipment. The protection engineer can prepare the necessary optimized and pre-tested settings in advance for different protection functions. Six different groups ofsetting parameters are available in the IED. Any of them can be activated through thedifferent programmable binary inputs by means of external or internal control signals.
A function block, SETGRPS, defines how many setting groups are used. Setting isdone with parameter MAXSETGR and shall be set to the required value for each IED.Only the number of setting groups set will be available in the Parameter Setting toolfor activation with the ActiveGroup function block.
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 417Application manual
21.4.2 Setting guidelines
The setting ActiveSetGrp, is used to select which parameter group to be active. Theactive group can also be selected with configured input to the function blockSETGRPS.
The length of the pulse, sent out by the output signal SETCHGD when an active grouphas changed, is set with the parameter t.
The parameter MAXSETGR defines the maximum number of setting groups in use toswitch between. Only the selected number of setting groups will be available in theParameter Setting tool (PST) for activation with the ActiveGroup function block.
21.5 Rated system frequency PRIMVAL
21.5.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Primary system values PRIMVAL - -
21.5.2 Application
The rated system frequency and phase rotation direction are set under Main menu/Configuration/ Power system/ Primary Values in the local HMI and PCM600parameter setting tree.
21.5.3 Setting guidelines
Set the system rated frequency. Refer to section "Signal matrix for analog inputsSMAI" for description on frequency tracking.
21.6 Global base values GBASVAL
21.6.1 IdentificationFunction description IEC 61850
identificationIEC 60617identification
ANSI/IEEE C37.2device number
Global base values GBASVAL - -
Section 21 1MRK 506 375-UEN -Basic IED functions
418 Railway application RER670 2.2 IECApplication manual
21.6.2 Application
Global base values function (GBASVAL) is used to provide global values, commonfor all applicable functions within the IED. One set of global values consists of valuesfor current, voltage and apparent power and it is possible to have twelve different sets.
This is an advantage since all applicable functions in the IED use a single source ofbase values. This facilitates consistency throughout the IED and also facilitates asingle point for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one outof the twelve sets of GBASVAL functions.
21.6.3 Setting guidelines
UBase: Phase-to-phase voltage value to be used as a base value for applicablefunctions throughout the IED.
IBase: Phase current value to be used as a base value for applicable functionsthroughout the IED.
SBase: Standard apparent power value to be used as a base value for applicablefunctions throughout the IED, typically SBase=UBase·IBase.
21.7 Signal matrix for binary inputs SMBI
21.7.1 Application
The Signal matrix for binary inputs function SMBI is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMBI represents theway binary inputs are brought in for one IED configuration.
21.7.2 Setting guidelines
There are no setting parameters for the Signal matrix for binary inputs SMBI availableto the user in Parameter Setting tool. However, the user shall give a name to SMBIinstance and the SMBI inputs, directly in the Application Configuration tool. Thesenames will define SMBI function in the Signal Matrix tool. The user defined name forthe input or output signal will also appear on the respective output or input signal.
21.8 Signal matrix for binary outputs SMBO
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 419Application manual
21.8.1 Application
The Signal matrix for binary outputs function SMBO is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMBO represents theway binary outputs are sent from one IED configuration.
21.8.2 Setting guidelines
There are no setting parameters for the Signal matrix for binary outputs SMBOavailable to the user in Parameter Setting tool. However, the user must give a name toSMBO instance and SMBO outputs, directly in the Application Configuration tool.These names will define SMBO function in the Signal Matrix tool.
21.9 Signal matrix for mA inputs SMMI
21.9.1 Application
The Signal matrix for mA inputs function SMMI is used within the ApplicationConfiguration tool in direct relation with the Signal Matrix tool. SMMI represents theway milliamp (mA) inputs are brought in for one IED configuration.
21.9.2 Setting guidelines
There are no setting parameters for the Signal matrix for mA inputs SMMI availableto the user in the Parameter Setting tool. However, the user must give a name to SMMIinstance and SMMI inputs, directly in the Application Configuration tool.
21.10 Signal matrix for analog inputs SMAI
21.10.1 Application
Signal matrix for analog inputs (SMAI), also known as the preprocessor functionblock, analyses the connected four analog signals (two Ph-N inputs, one Ph-Ph inputand neutral) and calculates all relevant information from them such as the phasormagnitude, phase angle, frequency, true RMS value, harmonics, sequencecomponents and so on. This information is then used by the respective functionsconnected to this SMAI block in the ACT (for example protection, measurement ormonitoring functions).
Section 21 1MRK 506 375-UEN -Basic IED functions
420 Railway application RER670 2.2 IECApplication manual
21.10.2 Frequency values
A valid input voltage signal level for frequency measurement can be set with SMAIsetting MinValFreqMeas in % of UBase. If the input signal level (positive sequenceor single phase voltage) is lower than the MinValFreqMeas level, then the frequencyoutput is invalid and the connected frequency functions will be blocked.
21.10.3 Setting guidelines
The parameters for the signal matrix for analog inputs (SMAI) functions are set via thelocal HMI or PCM600.
Application functions should be connected to a SMAI block with same task cycle asthe application function, except for e.g. measurement functions that run in slow cycletasks.
Negation: If the user wants to negate the 2ph signal, it is possible to choose to negateonly the phase signals Negate2Ph, only the neutral signal NegateN or both Negate2Ph+N. Negation means rotation with 180° of the vectors.
GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).
MinValFreqMeas: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase (for each instance n).
A valid input voltage signal level for frequency measurement can be set with SMAIsetting MinValFreqMeas in % of UBase. If the input signal level (positive sequenceor single phase voltage) is lower than the MinValFreqMeas level, then the frequencyoutput is invalid and the connected frequency functions will be blocked.
Even if the user sets the AnalogInputType of a SMAI block to“Current”, the MinValFreqMeas is still visible. However, using thecurrent channel values as base for frequency measurement is notrecommendable for a number of reasons, not last among them beingthe low level of currents that one can have in normal operatingconditions.
The preprocessing block shall only be used to feed functions withinthe same execution cycles. The only exceptions are the measurementfunctions (CVMMXN, CMMXU,VMMXU, etc.).
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 421Application manual
21.11 Test mode functionality TESTMODE
21.11.1 Application
The protection and control IEDs may have a complex configuration with manyincluded functions. To make the testing procedure easier, the IEDs include the featurethat allows individual blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enablesthe user to follow the operation of several related functions to check correctfunctionality and to check parts of the configuration, and so on.
21.11.1.1 IEC 61850 protocol test mode
The IEC 61850 Test Mode has improved testing capabilities for IEC 61850 systems.Operator commands sent to the IEC 61850 Mod determine the behavior of thefunctions. The command can be given from the LHMI under the Main menu/Test/Function test modes menu or remotely from an IEC 61850 client. The possible valuesof IEC 61850 Mod are described in Communication protocol manual, IEC 61850Edition 1 and Edition 2.
To be able to set the IEC 61850 Mod the parameter remotely, the PSTsetting RemoteModControl may not be set to Off. The possible valuesare Off, Maintenance or All levels. The Off value denies all access todata object Mod from remote, Maintenance requires that the categoryof the originator (orCat) is Maintenance and All levels allow anyorCat.
The mod of the Root LD.LNN0 can be configured under Main menu/Test/Functiontest modes/Communication/Station communication/IEC61850 LD0 LLN0/LD0LLN0:1
When the Mod is changed at this level, all components under the logical device updatetheir own behavior according to IEC 61850-7-4. The supported values of IEC 61850Mod are described in Communication protocol manual, IEC 61850 Edition 2. TheIEC 61850 test mode is indicated with the Start LED on the LHMI.
The mod of an specific component can be configured under Main menu/Test/Function test modes/Communication/Station Communication
It is possible that the behavior is also influenced by other sources as well, independentof the mode, such as the insertion of the test handle, loss of SV, and IED configurationor LHMI. If a function of an IED is set to Off, the related Beh is set to Off as well. Therelated mod keeps its current state.
Section 21 1MRK 506 375-UEN -Basic IED functions
422 Railway application RER670 2.2 IECApplication manual
When the setting Operation is set to Off, the behavior is set to Off and it is not possibleto override it. When a behavior of a function is Offthe function will not execute.
When IEC 61850 Mod of a function is set to Off or Blocked, the StartLED on the LHMI will be set to flashing to indicate the abnormaloperation of the IED.
The IEC 61850-7-4 gives a detailed overview over all aspects of the test mode andother states of mode and behavior.
• When the Beh of a component is set to Test, the component is not blocked and allcontrol commands with a test bit are accepted.
• When the Beh of a component is set to Test/blocked, all control commands witha test bit are accepted. Outputs to the process via a non-IEC 61850 link data areblocked by the LN. Only process-related outputs on LNs related to primaryequipment are blocked. If there is an XCBR, the outputs EXC_Open andEXC_Close are blocked.
• When the Beh of a component is set to Blocked, all control commands with a testbit are accepted. Outputs to the process via a non-IEC 61850 link data are blockedby the LN. In addition, the components can be blocked when their Beh isblocked. This can be done if the component has a block input. The block status ofa component is shown as the Blk output under the Test/Function status menu. Ifthe Blk output is not shown, the component cannot be blocked.
21.11.2 Setting guidelines
There are two possible ways to place the IED in the TestMode= On” state. If, the IEDis set to normal operation (TestMode = Off), but the functions are still shown being inthe test mode, the input signal INPUT on the TESTMODE function block might beactivated in the configuration.
Forcing of binary input and output signals is only possible when the IED is in IED testmode.
21.12 Time synchronization TIMESYNCHGEN
21.12.1 Application
Use time synchronization to achieve a common time base for the IEDs in a protectionand control system. This makes it possible to compare events and disturbance databetween all IEDs in the system. If a global common source (i.e. GPS) is used indifferent substations for the time synchronization, also comparisons and analysisbetween recordings made at different locations can be easily performed and a moreaccurate view of the actual sequence of events can be obtained.
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 423Application manual
Time-tagging of internal events and disturbances are an excellent help whenevaluating faults. Without time synchronization, only the events within one IED canbe compared with each other. With time synchronization, events and disturbanceswithin the whole network, can be compared and evaluated.
In the IED, the internal time can be synchronized from the following sources:
• GPS• IRIG-B• IEEE 1588 (PTP)
For IEDs using IEC/UCA 61850-9-2LE in "mixed mode" a time synchronizationfrom an external clock is recommended to the IED and all connected merging units.The time synchronization from the clock to the IED can be PTP, optical PPS or IRIG-B. For IEDs using IEC/UCA 61850-9-2LE from one single MU as analog data source,the MU and IED still need to be synchronized to each other. This could be done byletting the MU supply a PPS signal to the IED or by supplying a PPS signal from theIED to the MU, by using a GTM.
The selection of the time source is done via the corresponding setting.
It is possible to set a backup time-source for GPS signal, for instance SNTP. In thiscase, when the GPS signal quality is bad, the IED will automatically choose SNTP asthe time-source. At a given point in time, only one time-source will be used.
If PTP is activated, the device with the best accuracy within the synchronizing groupwill be selected as the source. For more information about PTP, see the Technicalmanual.
IEEE 1588 (PTP)PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3for power utility automation is a synchronization method that can be used to maintaina common time within a station. This time can be synchronized to the global timeusing, for instance, a GPS receiver. If PTP is enabled on the IEDs and the switches thatconnect the station are compatible with IEEE 1588, the station will becomesynchronized to one common time with an accuracy of under 1us. Using an IED as aboundary clock between several networks will keep 1us accuracy on three levels orwhen using an HSR, 15 IEDs can be connected in a ring without losing a singlemicrosecond in accuracy.
21.12.2 Setting guidelines
All the parameters related to time are divided into two categories: System time andSynchronization.
Section 21 1MRK 506 375-UEN -Basic IED functions
424 Railway application RER670 2.2 IECApplication manual
21.12.2.1 System time
21.12.2.2 Synchronization
The setting parameters for the real-time clock with external time synchronization areset via local HMI or PCM600. The path for Time Synchronization parameters on localHMI is Main menu/Configuration/Time/Synchronization. The parameters arecategorized as Time Synchronization (TIMESYNCHGEN) and IRIG-B settings(IRIG-B:1) in case that IRIG-B is used as the external time synchronization source.
IEEE 1588 (PTP)Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configurationtool /ECT) in PCM600.
PTP can be set to On,Off or Slave only. When set to Slave only the IED is connectedto the PTP-group and will synchronize to the grandmaster but cannot function as thegrandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To setone IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000093-1-en.vsdx
IEC16000093 V1 EN
Figure 175: Enabling PTP in ECT
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 425Application manual
Setting example
9-2
REC
PTP
PTP
Station bus
GPS
SAM600-TS
SAM600-CT
SAM600-VT
PTP
PTP
9-2
PTP
REL
MU
GTM
PPS
IEC16000167-1-en.vsdx
9-2
9-2 9-2
Process bus
IEC16000167 V1 EN
Figure 176: Example system
Figure 176 describes an example system. The REC and REL are both using the 9-2stream from the SAM600, and gets its synch from the GPS. Moreover, the REL andREC both acts as a boundary clock to provide synch to the SAM600. The RELcontains a GTM card, which has a PPS output that is used to synchronize mergingunits that are not PTP compliant. As a side effect, the GTM contains a GPS receiverand the REL acts as a backup of the GPS on the station bus.
On all access points, the PTP parameter is “ON”.
On the REL, the parameter FineSyncSource (under Configuration/Time/Synchronization/TIMESYNCHGEN:1/General) is set to “GPS” if there is a GPSantenna attached.
If the GTM is used as a PPS output only, the FineSynchSource is not set.
21.12.2.3 Process bus IEC/UCA 61850-9-2LE synchronization
When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it isessential that the merging units are synchronized with the hardware time of the IED(see Technical manual, section Design of the time system (clock synchronization) ). Toachieve this, PTP, PPS or IRIG-B can be used depending of the facilities of themerging unit.
If the merging unit supports PTP, use PTP. If PTP is used in the IED and the mergingunit is not PTP capable, then synchronize the merging unit from the IED via a PPS out
Section 21 1MRK 506 375-UEN -Basic IED functions
426 Railway application RER670 2.2 IECApplication manual
from the GTM. If PTP is used in the IED and the merging unit cannot be synchronizedfrom the IED, then use GPS-based clocks to provide PTP synch as well as sync to themerging unit.
If synchronization of the IED and the merging unit is based on GPS, set the parameterLostSyncMode to BlockOnLostUTC in order to provide a block of protection functionswhenever the global common time is lost.
If PTP is not used, use the same synchronization method for the HwSyncSrc as themerging unit provides. For instance, if the merging unit provides PPS assynchronization, use PPS as HwSyncSrc. If either PMU or LDCM in GPS-mode isused, that is, the hardware and software clocks are connected to each other,HwSyncSrc is not used and other means to synchronize the merging unit to the IED isrequired. Either FineSyncSource is set to the same source that the merging unit uses,or the PPS output from the GTM module is used to synchronize the merging unit. Ifthe PPS output from the GTM module is used to synchronize the merging unit and PTPis not used, the IED does not know how the merging unit is synchronized and theparameter LostSyncMode must be set to NoBlock.
1MRK 506 375-UEN - Section 21Basic IED functions
Railway application RER670 2.2 IEC 427Application manual
Section 22 Requirements
22.1 Current transformer requirements
The performance of a protection function will depend on the quality of the measuredcurrent signal. Saturation of the current transformers (CTs) will cause distortion of thecurrent signals and can result in a failure to operate or cause unwanted operations ofsome functions. Consequently CT saturation can have an influence on both thedependability and the security of the protection. This protection IED has beendesigned to permit heavy CT saturation with maintained correct operation.
22.1.1 Current transformer basic classification and requirements
To guarantee correct operation, the current transformers (CTs) must be able tocorrectly reproduce the current for a minimum time before the CT will begin tosaturate. To fulfill the requirement on a specified time to saturation the CTs mustfulfill the requirements of a minimum secondary e.m.f. that is specified below.
CTs are specified according to many different classes and standards. In principle,there are three different types of protection CTs. These types are related to the designof the iron core and the presence of airgaps. Airgaps affects the properties of theremanent flux.
The following three different types of protection CTs have been specified:
• The High Remanence type with closed iron core and no specified limit of theremanent flux
• The Low Remanence type with small airgaps in the iron core and the remanentflux limit is specified to be maximum 10% of the saturation flux
• The Non Remanence type with big airgaps in the iron core and the remanent fluxcan be neglected
Even though no limit of the remanent flux is specified in the IEC standard for closedcore CTs, it is a common opinion that the remanent flux is normally limited tomaximum 75 - 80 % of the saturation flux.
Since approximately year 2000 some CT manufactures have introduced new corematerials that gradually have increased the possible maximum levels of remanent fluxeven up to 95 % related to the hysteresis curve. Corresponding level of actualremanent flux is 90 % of the saturation flux (Ψsat). As the present CT standards haveno limitation of the level of remanent flux, these CTs are also classified as forexample, class TPX, P and PX according to IEC. The IEC TR 61869-100, Edition 1.02017-01, Instrument transformers – Guidance for application of current transformers
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 429Application manual
in power system protection, is the first official document that highlighted thisdevelopment. So far remanence factors of maximum 80% have been considered whenCT requirements have been decided for ABB IEDs. Even in the future this level ofremanent flux probably will be the maximum level that will be considered whendecided the CT requirements. If higher remanence levels should be considered, itshould often lead to unrealistic CT sizes.
Thus, now there is a need to limit the acceptable level of remanent flux. To be able toguarantee the performance of protection IEDs, we need to introduce the followingclassification of CTs.
There are many different standards and a lot of classes but fundamentally there arefour different types of CTs:
• Very High Remanence type CT• High Remanence type CT• Low Remanence type CT• Non Remanence type CT
The Very High Remanence (VHR) type is a CT with closed iron core (for example.protection classes TPX, P, PX according to IEC, class C, K according to ANSI/IEEE)and with an iron core material (new material, typically new alloy based magneticmaterials) that gives a remanent flux higher than 80 % of the saturation flux.
The High Remanence (HR) type is a CT with closed iron core (for example,protection classes TPX, P, PX according to IEC, class C, K according to ANSI/IEEE)but with an iron core material (traditional material) that gives a remanent flux that islimited to maximum 80 % of the saturation flux.
The Low Remanence (LR) type is a CT with small airgaps in the iron core (forexample, TPY, PR, PXR according to IEC) and the remanent flux limit is specified tobe maximum 10% of the saturation flux.
The Non Remanence (NR) type is a CT with big airgaps in the core (for example,TPZ according to IEC) and the remanent flux can be neglected.
It is also possible that different CT classes of HR and LR type may be mixed.
CT type VHR (using new material) should not be used for protection CT cores. Thismeans that it is important to specify that the remanence factor must not exceed 80 %when ordering for example, class P, PX or TPX CTs. If CT manufacturers are usingnew core material and are not able to fulfill this requirement, the CTs shall be specifiedwith small airgaps and therefore will be CTs of LR type (for example, class PR, TPYor PXR). Very high remanence level in a protection core CT can cause the followingproblems for protection IEDs:
1. Unwanted operation of differential (i.e. unit) protections for external faults2. Unacceptably delayed or even missing operation of all types of protections (for
example, distance, differential, overcurrent, etc.) which can result in loosingprotection selectivity in the network
Section 22 1MRK 506 375-UEN -Requirements
430 Railway application RER670 2.2 IECApplication manual
No information is available about how frequent the use of the new iron core materialis for protection CT cores, but it is known that some CT manufacturers are using thenew material while other manufacturers continue to use the old traditional corematerial for protection CT cores. In a case where VHR type CTs have been alreadyinstalled, the calculated values of Eal for HR type CTs, for which the formulas aregiven in this document, must be multiplied by factor two-and-a-half in order for VHRtype CTs (i.e. with new material) to be used together with ABB protection IEDs.However, this may result in unacceptably big CT cores, which can be difficult tomanufacture and fit in available space.
Different standards and classes specify the saturation e.m.f. in different ways but it ispossible to approximately compare values from different classes. The rated equivalentlimiting secondary e.m.f. Eal according to the IEC 61869–2 standard is used to specifythe CT requirements for the IED. The requirements are also specified according toother standards.
22.1.2 Conditions
The requirements are a result of investigations performed in our network simulator.The current transformer models are representative for current transformers of highremanence and low remanence type. The results may not always be valid for nonremanence type CTs (TPZ).
The performances of the protection functions have been checked in the range fromsymmetrical to fully asymmetrical fault currents. Primary time constants of at least120 ms have been considered at the tests. The current requirements below are thusapplicable both for symmetrical and asymmetrical fault currents.
Depending on the protection function phase-to-earth, phase-to-phase and three-phasefaults have been tested for different relevant fault positions for example, close inforward and reverse faults, zone 1 reach faults, internal and external faults. Thedependability and security of the protection was verified by checking for example,time delays, unwanted operations, directionality, overreach and stability.
The remanence in the current transformer core can cause unwanted operations orminor additional time delays for some protection functions. As unwanted operationsare not acceptable at all maximum remanence has been considered for fault casescritical for the security, for example, faults in reverse direction and external faults.Because of the almost negligible risk of additional time delays and the non-existentrisk of failure to operate the remanence have not been considered for the dependabilitycases. The requirements below are therefore fully valid for all normal applications.
It is difficult to give general recommendations for additional margins for remanenceto avoid the minor risk of an additional time delay. They depend on the performanceand economy requirements. When current transformers of low remanence type (forexample, TPY, PR) are used, normally no additional margin is needed. For currenttransformers of high remanence type (for example, P, PX, TPX) the small probabilityof fully asymmetrical faults, together with high remanence in the same direction as theflux generated by the fault, has to be kept in mind at the decision of an additional
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 431Application manual
margin. Fully asymmetrical fault current will be achieved when the fault occurs atapproximately zero voltage (0°). Investigations have shown that 95% of the faults inthe network will occur when the voltage is between 40° and 90°. In addition fullyasymmetrical fault current will not exist in all phases at the same time.
22.1.3 Fault current
The current transformer requirements are based on the maximum fault current forfaults in different positions. Maximum fault current will occur for three-phase faultsor single phase-to-earth faults. The current for a single phase-to-earth fault will exceedthe current for a three-phase fault when the zero sequence impedance in the total faultloop is less than the positive sequence impedance.
When calculating the current transformer requirements, maximum fault current forthe relevant fault position should be used and therefore both fault types have to beconsidered.
22.1.4 Secondary wire resistance and additional load
The voltage at the current transformer secondary terminals directly affects the currenttransformer saturation. This voltage is developed in a loop containing the secondarywires and the burden of all relays in the circuit. For earth faults the loop includes thephase and neutral wire, normally twice the resistance of the single secondary wire. Forthree-phase faults the neutral current is zero and it is just necessary to consider theresistance up to the point where the phase wires are connected to the common neutralwire. The most common practice is to use four wires secondary cables so it normallyis sufficient to consider just a single secondary wire for the three-phase case.
The conclusion is that the loop resistance, twice the resistance of the single secondarywire, must be used in the calculation for phase-to-earth faults and the phase resistance,the resistance of a single secondary wire, may normally be used in the calculation forthree-phase faults.
As the burden can be considerable different for three-phase faults and phase-to-earthfaults it is important to consider both cases. Even in a case where the phase-to-earthfault current is smaller than the three-phase fault current the phase-to-earth fault canbe dimensioning for the CT depending on the higher burden.
In isolated or high impedance earthed systems the phase-to-earth fault is not thedimensioning case. Therefore, the resistance of the single secondary wire can alwaysbe used in the calculation for this kind of power systems.
22.1.5 General current transformer requirements
The current transformer ratio is mainly selected based on power system data forexample, maximum load and/or maximum fault current. It should be verified that thecurrent to the protection is higher than the minimum operating value for all faults that
Section 22 1MRK 506 375-UEN -Requirements
432 Railway application RER670 2.2 IECApplication manual
are to be detected with the selected CT ratio. It should also be verified that themaximum possible fault current is within the limits of the IED.
The current error of the current transformer can limit the possibility to use a verysensitive setting of a sensitive residual overcurrent protection. If a very sensitivesetting of this function will be used it is recommended that the current transformershould have an accuracy class which have an current error at rated primary current thatis less than ±1% (for example, 5P). If current transformers with less accuracy are usedit is advisable to check the actual unwanted residual current during thecommissioning.
22.1.6 Rated equivalent secondary e.m.f. requirements
With regard to saturation of the current transformer all current transformers of highremanence and low remanence type that fulfill the requirements on the ratedequivalent limiting secondary e.m.f. Eal below can be used. The characteristic of thenon remanence type CT (TPZ) is not well defined as far as the phase angle error isconcerned. If no explicit recommendation is given for a specific function we thereforerecommend contacting ABB to confirm that the non remanence type can be used.
The CT requirements for the different functions below are specified as a ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard.Requirements for CTs specified according to other classes and standards are given atthe end of this section.
22.1.6.1 Breaker failure protection
The CTs must have a rated equivalent limiting secondary e.m.f. Eal that is larger thanor equal to the required rated equivalent limiting secondary e.m.f. Ealreq below:
sr Ral alreq op ct L 2
pr r
I SE E 5 I R RI I
æ ö³ = × × × + +ç ÷
è øEQUATION1380 V2 EN (Equation 78)
where:
Iop The primary operate value (A)
Ipr The rated primary CT current (A)
Isr The rated secondary CT current (A)
Ir The rated current of the protection IED (A)
Rct The secondary resistance of the CT (W)
RL The resistance of the secondary cable and additional load (W). The loop resistance containingthe phase and neutral wires, must be used for faults in solidly earthed systems. The resistanceof a single secondary wire should be used for faults in high impedance earthed systems.
SR The burden of an IED current input channel (VA). SR=0.020 VA/channel for Ir=1 A and SR=0.150VA/channel for Ir=5 A
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 433Application manual
22.1.6.2 Restricted earth fault protection (low impedance differential)
The requirements are specified separately for solidly earthed and impedance earthedtransformers. For impedance earthed transformers the requirements for the phase CTsare depending whether it is three individual CTs connected in parallel or it is a cableCT enclosing all three phases.
Neutral CTs and phase CTs for solidly earthed transformersThe neutral CT and the phase CTs must have a rated equivalent limiting secondarye.m.f. Eal that is larger than or equal to the maximum of the required rated equivalentlimiting secondary e.m.f. Ealreq below:
230 sr Ral alreq rt ct L
pr r
I SE E I R RI I
æ ö³ = × × × + +ç ÷
è øEQUATION2237 V2 EN (Equation 79)
22 sr Ral alreq etf ct L
pr r
I SE E I R RI I
æ ö³ = × × × + +ç ÷
è øEQUATION2238 V2 EN (Equation 80)
Where:
Irt The rated primary current of the power transformer (A)
Ietf Maximum primary fundamental frequency phase-to-earth fault current that passes theCTs and the power transformer neutral (A)
Ipr The rated primary CT current (A)
Isr The rated secondary CT current (A)
Ir The rated current of the protection IED (A)
Rct The secondary resistance of the CT (Ω)
RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.
SR The burden of a REx670 current input channel (VA). SR=0.020 VA / channel for IR = 1A and SR = 0.150 VA / channel for IR = 5 A
In substations with breaker-and-a-half or double-busbar double-breaker arrangement,the fault current may pass two main phase CTs for the restricted earth fault protectionwithout passing the power transformer. In such cases and if both main CTs have equalratios and magnetization characteristics the CTs must satisfy Requirement 79 and theRequirement 80:
2sr R
al alreq ef ct Lpr r
I SE E I R RI I
æ ö³ = × × + +ç ÷
è øEQUATION2239 V2 EN (Equation 81)
Section 22 1MRK 506 375-UEN -Requirements
434 Railway application RER670 2.2 IECApplication manual
Where:
Ief Maximum primary fundamental frequency phase-to-earth fault current that passes twomain CTs without passing the power transformer neutral (A)
Neutral CTs and phase CTs for impedance earthed transformersThe neutral CT and phase CTs must have a rated equivalent limiting secondary e.m.f.Eal that is larger than or equal to the required rated equivalent limiting secondary e.m.f.Ealreq below:
23 sr Ral alreq etf ct L
pr r
I SE E I R RI I
æ ö³ = × × × + +ç ÷
è øEQUATION2240 V2 EN (Equation 82)
Where:
Ietf Maximum primary fundamental frequency phase-to-earth fault current that passesthe CTs and the power transformer neutral (A)
Ipr The rated primary CT current (A)
Isr The rated secondary CT current (A)
Ir The rated current of the protection IED (A)
Rct The secondary resistance of the CT (Ω)
RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.
SR The burden of a REx670 current input channel (VA). SR = 0.020 VA / channel for Ir= 1 A and SR = 0.150 VA / channel for Ir = 5 A
In case of three individual CTs connected in parallel (Holmgren connection) on thephase side the following additional requirements must also be fulfilled.
The three individual phase CTs must have a rated equivalent limiting secondary e.m.f.Eal that is larger than or equal to the maximum of the required rated equivalent limitingsecondary e.m.f. Ealreq below:
22 sr Ral alreq tf ct Lsw
pr r
I SE E I R RI I
æ ö³ = × × × + +ç ÷
è øEQUATION2241 V2 EN (Equation 83)
Where:
Itf Maximum primary fundamental frequency three-phase fault current that passes theCTs and the power transformer (A).
RLsw The resistance of the single secondary wire and additional load (Ω).
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 435Application manual
In impedance earthed systems the phase-to-earth fault currents often are relativelysmall and the requirements might result in small CTs. However, in applications wherethe zero sequence current from the phase side of the transformer is a summation ofcurrents from more than one CT (cable CTs or groups of individual CTs in Holmgrenconnection) for example, in substations with breaker-and-a-half or double-busbardouble-breaker arrangement or if the transformer has a T-connection to differentbusbars, there is a risk that the CTs can be exposed for higher fault currents than theconsidered phase-to-earth fault currents above. Examples of such cases can be cross-country faults or phase-to-phase faults with high fault currents and unsymmetricaldistribution of the phase currents between the CTs. The zero sequence fault currentlevel can differ much and is often difficult to calculate or estimate for different cases.To cover these cases, with summation of zero sequence currents from more than oneCT, the phase side CTs must fulfill the Requirement 84 below:
2sr R
al alreq f ct Lpr r
I SE E I R RI I
æ ö³ = × × + +ç ÷
è øEQUATION2242 V2 EN (Equation 84)
Where:
If Maximum primary fundamental frequency three-phase fault current that passes theCTs (A)
RL The resistance of the secondary wire and additional load (Ω). The loop resistancecontaining the phase and neutral wires shall be used.
22.1.7 Current transformer requirements for CTs according to otherstandards
All kinds of conventional magnetic core CTs are possible to use with the IEDs if theyfulfill the requirements corresponding to the above specified expressed as the ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard. Fromdifferent standards and available data for relaying applications it is possible toapproximately calculate a secondary e.m.f. of the CT comparable with Eal. Bycomparing this with the required rated equivalent limiting secondary e.m.f. Ealreq it ispossible to judge if the CT fulfills the requirements. The requirements according tosome other standards are specified below.
22.1.7.1 Current transformers according to IEC 61869-2, class P, PR
A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. EALF.The value of the EALF is approximately equal to the corresponding Eal. Therefore, theCTs according to class P and PR must have a secondary limiting e.m.f. EALF thatfulfills the following:
Section 22 1MRK 506 375-UEN -Requirements
436 Railway application RER670 2.2 IECApplication manual
ALF alreqE maxE
EQUATION1383 V4 EN (Equation 85)
22.1.7.2 Current transformers according to IEC 61869-2, class PX, PXR (andold IEC 60044-6, class TPS and old British Standard, class X)
CTs according to these classes are specified approximately in the same way by a ratedknee point e.m.f. Eknee (Ek for class PX and PXR, EkneeBS for class X and the limitingsecondary voltage Ual for TPS). The value of the Eknee is lower than the correspondingEal according to IEC 61869-2. It is not possible to give a general relation between theEknee and the Eal but normally the Eknee is approximately 80 % of the Eal. Therefore,the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f.Eknee that fulfills the following:
( )knee k kneeBS al alreqE E E U 0.8 maximum of E» » » > ×
EQUATION2100 V2 EN (Equation 86)
22.1.7.3 Current transformers according to ANSI/IEEE
Current transformers according to ANSI/IEEE are partly specified in different ways.A rated secondary terminal voltage UANSI is specified for a CT of class C. UANSI is thesecondary terminal voltage the CT will deliver to a standard burden at 20 times ratedsecondary current without exceeding 10 % ratio correction. There are a number ofstandardized UANSI values for example, UANSI is 400 V for a C400 CT. Acorresponding rated equivalent limiting secondary e.m.f. EalANSI can be estimated asfollows:
alANSI sr ct ANSI sr ct sr bANSIE 20 I R U 20 I R 20 I Z= × × + = × × + × ×
EQUATION971 V2 EN (Equation 87)
where:
ZbANSI The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific Cclass (W)
UANSI The secondary terminal voltage for the specific C class (V)
The CTs according to class C must have a calculated rated equivalent limitingsecondary e.m.f. EalANSI that fulfils the following:
alANSI alreqE maximum of E>
EQUATION1384 V2 EN (Equation 88)
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 437Application manual
A CT according to ANSI/IEEE is also specified by the knee point voltage UkneeANSIthat is graphically defined from an excitation curve. The knee point voltage UkneeANSInormally has a lower value than the knee-point e.m.f. according to IEC and BS.UkneeANSI can approximately be estimated to 75 % of the corresponding Eal accordingto IEC 61869-2. Therefore, the CTs according to ANSI/IEEE must have a knee pointvoltage UkneeANSI that fulfills the following:
kneeANSI alreqV 0.75 (max imum of E )> ×EQUATION2101 V2 EN (Equation 89)
22.2 Voltage transformer requirements
The performance of a protection function will depend on the quality of the measuredinput signal. Transients caused by capacitive voltage transformers (CVTs) can affectsome protection functions.
Magnetic or capacitive voltage transformers can be used.
The capacitive voltage transformers (CVTs) should fulfill the requirements accordingto the IEC 61869-5 standard regarding ferro-resonance and transients. The ferro-resonance requirements of the CVTs are specified in chapter 6.502 of the standard.
The transient responses for three different standard transient response classes, T1, T2and T3 are specified in chapter 6.503 of the standard. CVTs according to all classescan be used.
The protection IED has effective filters for these transients, which gives secure andcorrect operation with CVTs.
22.3 SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than 4-5switches or routers away from the IED. The SNTP server is dedicated for its task, orat least equipped with a real-time operating system, that is not a PC with SNTP serversoftware. The SNTP server should be stable, that is, either synchronized from a stablesource like GPS, or local without synchronization. Using a local SNTP server withoutsynchronization as primary or secondary server in a redundant configuration is notrecommended.
Section 22 1MRK 506 375-UEN -Requirements
438 Railway application RER670 2.2 IECApplication manual
22.4 PTP requirements
For PTP to perform properly, the Ethernet equipment that is used needs to becompliant with IEEE1588. The clocks used must follow the IEEE1588 standard BMC(Best Master Algorithm) and shall, for instance, not claim class 7 for a longer timethan it can guarantee 1us absolute accuracy.
22.5 Sample specification of communication requirementsfor the protection and control terminals in digitaltelecommunication networks
The communication requirements are based on echo timing.
Bit Error Rate (BER) according to ITU-T G.821, G.826 and G.828
• <10-6 according to the standard for data and voice transfer
Bit Error Rate (BER) for high availability of the differential protection
• <10-8-10-9 during normal operation• <10-6 during disturbed operation
During disturbed conditions, the trip security function can cope with high bit errorrates up to 10-5 or even up to 10-4. The trip security can be configured to beindependent of COMFAIL from the differential protection communicationsupervision, or blocked when COMFAIL is issued after receive error >100ms.(Default).
Synchronization in SDH systems with G.703 E1 or IEEE C37.94
The G.703 E1, 2 Mbit shall be set according to ITU-T G.803, G.810-13
• One master clock for the actual network• The actual port Synchronized to the SDH system clock at 2048 kbit• Synchronization; bit synchronized, synchronized mapping• Maximum clock deviation <±50 ppm nominal, <±100 ppm operational• Jitter and Wander according to ITU-T G.823 and G.825• Buffer memory <250 μs, <100 μs asymmetric difference• Format.G 704 frame, structured etc.Format.• No CRC-check
Synchronization in PDH systems connected to SDH systems
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 439Application manual
• Independent synchronization, asynchronous mapping• The actual SDH port must be set to allow transmission of the master clock from
the PDH-system via the SDH-system in transparent mode.• Maximum clock deviation <±50 ppm nominal, <±100 ppm operational• Jitter and Wander according to ITU-T G.823 and G.825• Buffer memory <100 μs• Format: Transparent• Maximum channel delay• Loop time <40 ms continuous (2 x 20 ms)
IED with echo synchronization of differential clock (without GPS clock)
• Both channels must have the same route with maximum asymmetry of 0,2-0,5ms, depending on set sensitivity of the differential protection.
• A fixed asymmetry can be compensated (setting of asymmetric delay in built inHMI or the parameter setting tool PST).
IED with GPS clock
• Independent of asymmetry.
22.6 IEC/UCA 61850-9-2LE Merging unit requirements
The merging units that supply the IED with measured values via the process bus mustfulfill the IEC/UCA 61850-9-2LE standard.
This part of the IEC 61850 is specifying “Communication Service Mapping (SCSM)– Sampled values over ISO/IEC 8802”, in other words – sampled data over Ethernet.The 9-2 part of the IEC 61850 protocol uses also definitions from 7-2, “Basiccommunication structure for substation and feeder equipment – Abstractcommunication service interface (ACSI)”. The set of functionality implemented inthe IED (IEC/UCA 61850-9-2LE) is a subset of the IEC 61850-9-2. For example theIED covers the client part of the standard, not the server part.
The standard does not define the sample rate for data, but in the UCA users grouprecommendations there are indicated sample rates that are adopted, by consensus, inthe industry.
There are two sample rates defined: 80 samples/cycle (4000 samples/sec. at 50Hz or4800 samples/sec. at 60 Hz) for a merging unit “type1” and 256 samples/cycle for amerging unit “type2”. The IED can receive data rates of 80 samples/cycle.
Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of thesampled values, only the transportation. Thus, the accuracy of the current and voltageinputs to the merging unit and the inaccuracy added by the merging unit must becoordinated with the requirement for actual type of protection function.
Section 22 1MRK 506 375-UEN -Requirements
440 Railway application RER670 2.2 IECApplication manual
Factors influencing the accuracy of the sampled values from the merging unit are forexample anti aliasing filters, frequency range, step response, truncating, A/Dconversion inaccuracy, time tagging accuracy etc.
In principle the accuracy of the current and voltage transformers, together with themerging unit, shall have the same quality as direct input of currents and voltages.
1MRK 506 375-UEN - Section 22Requirements
Railway application RER670 2.2 IEC 441Application manual
Section 23 Glossary
AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with timesynchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fibre optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signalsbetween IEDs
CAN Controller Area Network. ISO standard (ISO 11898) forserial communication
CB Circuit breaker
CBM Combined backplane module
1MRK 506 375-UEN - Section 23Glossary
Railway application RER670 2.2 IEC 443Application manual
CCITT Consultative Committee for International Telegraph andTelephony. A United Nations-sponsored standards bodywithin the International Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involvestwo twisted pairs making it possible to transmit informationin both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchangeformat for Disturbance recorder according to IEEE/ANSIC37.111, 1999 / IEC 60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involvesfour twisted pairs, two of which are used for transmittingdata in both directions and two for transmitting clocksignals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The USdeveloper of the TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
Section 23 1MRK 506 375-UEN -Glossary
444 Railway application RER670 2.2 IECApplication manual
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
ECT Ethernet configuration tool
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility
EMF Electromotive force
EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fibre connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech,data and protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission ofup to seven duplex channels of digital data over opticalfibers
FPN Flexible product naming
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines usedby local telephone companies. Can be transported overbalanced and unbalanced lines
GCM Communication interface module with carrier of GPSreceiver module
1MRK 506 375-UEN - Section 23Glossary
Railway application RER670 2.2 IEC 445Application manual
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLCstandard
HFBR connector type Plastic fiber connector
HMI Human-machine interface
HSAR High speed autoreclosing
HSR High-availability Seamless Redundancy
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6:Requirements for protective current transformers fortransient performance
IEC 60870-5-103 Communication standard for protection equipment. A serialmaster/slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/son twisted-pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules.References the CMC (IEEE P1386, also known as CommonMezzanine Card) standard for the mechanics and the PCIspecifications from the PCI SIG (Special Interest Group) forthe electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices(IEDs) Cyber Security Capabilities
IED Intelligent electronic device
IET600 Integrated engineering tool
I-GIS Intelligent gas-insulated switchgear
Section 23 1MRK 506 375-UEN -Glossary
446 Railway application RER670 2.2 IECApplication manual
IOM Binary input/output module
Instance When several occurrences of the same function areavailable in the IED, they are referred to as instances of thatfunction. One instance of a function is identical to another ofthe same kind but has a different number in the IED userinterfaces. The word "instance" is sometimes defined as anitem of information that is representative of a type. In thesame way an instance of a function in the IED isrepresentative of a type of function.
IP 1. Internet protocol. The network layer for the TCP/IPprotocol suite widely used on Ethernet networks. IP is aconnectionless, best-effort packet-switching protocol. Itprovides packet routing, fragmentation and reassemblythrough the data link layer.2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level 20
IP 40 Ingression protection, according to IEC 60529, level 40
IP 54 Ingression protection, according to IEC 60529, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B,standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDCM Line data communication module
LDD Local detection device
LED Light-emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MIM Milli-ampere module
MPM Main processing module
MVAL Value of measurement
MVB Multifunction vehicle bus. Standardized serial busoriginally developed for use in trains.
NCC National Control Centre
1MRK 506 375-UEN - Section 23Glossary
Railway application RER670 2.2 IEC 447Application manual
NOF Number of grid faults
NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OEM Optical Ethernet module
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event thanstart/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is overreachingwhen the impedance presented to it is smaller than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhapsit should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in nearproximity to the measured and/or controlled components
PRP Parallel redundancy protocol
PSM Power supply module
PST Parameter setting tool within PCM600
PTP Precision time protocol
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digitaldata in point-to-point connections
RS485 Serial link according to EIA standard RS485
Section 23 1MRK 506 375-UEN -Glossary
448 Railway application RER670 2.2 IECApplication manual
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close
SCL Short circuit location
SCS Station control system
SCADA Supervision, control and data acquisition
SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SFP Small form-factor pluggable (abbreviation)Optical Ethernet port (explanation)
SLM Serial communication module.
SMA connector Subminiature version A, A threaded connector withconstant impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronizecomputer clocks on local area networks. This reduces therequirement to have accurate hardware clocks in everyembedded system in a network. Each embedded node caninstead synchronize with a remote clock, providing therequired accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocol for point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transportlayer protocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. Thede facto standard Ethernet protocols incorporated into4.2BSD Unix. TCP/IP was developed by DARPA for
1MRK 506 375-UEN - Section 23Glossary
Railway application RER670 2.2 IEC 449Application manual
Internet working and encompasses both network layer andtransport layer protocols. While TCP and IP specify twoprotocols at specific protocol layers, TCP/IP is often used torefer to the entire US Department of Defense protocol suitebased upon these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedanceversion of a BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents andvoltages taken from the process into levels suitable forfurther signal processing.
TYP Type identification
UMT User management tool
Underreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is underreachingwhen the impedance presented to it is greater than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay does not “see” the fault butperhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale,maintained by the Bureau International des Poids etMesures (BIPM), which forms the basis of a coordinateddissemination of standard frequencies and time signals.UTC is derived from International Atomic Time (TAI) bythe addition of a whole number of "leap seconds" tosynchronize it with Universal Time 1 (UT1), thus allowingfor the eccentricity of the Earth's orbit, the rotational axis tilt(23.5 degrees), but still showing the Earth's irregularrotation, on which UT1 is based. The CoordinatedUniversal Time is expressed using a 24-hour clock, and usesthe Gregorian calendar. It is used for aeroplane and shipnavigation, where it is also sometimes known by themilitary name, "Zulu time." "Zulu" in the phonetic alphabetstands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
Section 23 1MRK 506 375-UEN -Glossary
450 Railway application RER670 2.2 IECApplication manual
X.21 A digital signalling interface primarily used for telecomequipment
3IO Three times zero-sequence current.Often referred to as theresidual or the earth-fault current
3UO Three times the zero sequence voltage. Often referred to asthe residual voltage or the neutral point voltage
1MRK 506 375-UEN - Section 23Glossary
Railway application RER670 2.2 IEC 451Application manual
—ABB AB Grid Automation Products721 59 Västerås, SwedenPhone: +46 (0) 21 32 50 00
abb.com/protection-control
© Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. 1M
RK
50
6 3
75-U
EN