The Riello 40 FS series of one stage gas burners, is a complete range of products developed to respond to any request for light industrial application. The Riello 40 FS series is available in five different models, with an output ranging from 11 to 220 kW, divided in four different structures. All the models use the same components designed by Riello for the Riello 40 FS series. The high quality level guarantees safe working. The Riello 40 FS burners are fitted with a microprocessor - based flame control panel, with diagnostic functions. In developing these burners, special attention was paid to reducing noise, to the ease of installation and adjustment, to obtaining the smallest size possible to fit into any sort of boiler available on the market. All the models are approved by the EN 676 European Standard and conform to European Directives for EMC, Low Voltage, Machinery and Boiler Efficiency. All the Riello 40 FS burners are tested before leaving the factory. TS0027UK03 ONE STAGE GAS BURNERS RIELLO 40 FS SERIES FS3 11 ÷ 35 kW FS5 23 ÷ 58 kW FS8 46 ÷ 93 kW FS10 42 ÷ 116 kW FS20 81 ÷ 220 kW
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
The Riello 40 FS series of one stage gas burners, is a complete range of products developedto respond to any request for light industrial application. The Riello 40 FS series is availablein five different models, with an output ranging from 11 to 220 kW, divided in four differentstructures.All the models use the same components designed by Riello for the Riello 40 FS series.The high quality level guarantees safe working.The Riello 40 FS burners are fitted with a microprocessor - based flame control panel, withdiagnostic functions.In developing these burners, special attention was paid to reducing noise, to the ease ofinstallation and adjustment, to obtaining the smallest size possible to fit into any sort ofboiler available on the market.All the models are approved by the EN 676 European Standard and conform to EuropeanDirectives for EMC, Low Voltage, Machinery and Boiler Efficiency.All the Riello 40 FS burners are tested before leaving the factory.
TS0027UK03
ONE STAGE GAS BURNERSRIELLO 40 FS SERIES FS3 11 ÷ 35 kW
Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, thetechnical data, the equipment and the accessories can be changed.This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this informationshall not be divulged, nor duplicated in whole or in part.
Reference conditions:Temperature: 20 °CPressure: 1013.5 mbarAltitude: 100 m a.s.l.Noise was measured in the boiler room behind the burner at a distance of 1 meter.
2
3
FIRING RATES
Test conditions conforming to EN 676:Temperature: 20 °CPressure: 1013.5 mbarAltitude: 100 m a.s.l.
Useful working field for choosing the burner
0
0,5
kW
0
5
10
15
1
1,5
10 30 4020 50
10 20 30 40 50 600
0
0
0,8
40
0
8
16
24
32
1,6
2,4
3,2
4,0
4,848
20 40 60 80 100 120 140 160 180 200
FS3
FS5
FS20
FS8
FS10
hP
a (m
bar
)
mm
H2O
hP
a (m
bar
)
mm
H2O
Mcal/h
Mcal/h
kW4020 60 80 100 120 140 160 180 200 220 240
FUEL SUPPLY
GAS TRAIN
The burners are set for fuel supply from either the rightor left hand sides.
Depending on the gas output and the available pressurein the supply line, you should check the correct gas trainto be adapted to the system requirements.
The gas train is Multibloc type, containing the maincomponents in a single unit.Except for the MBC 65 DLE model, a valve seal control(as accessory) can be fitted to the Multibloc gas trains.
The MBC 65 DLE Multibloc gas train can be fitted onlyto the left of the burner.
Leak detection control device for valves 7 and 8 (accessory)
Gas train-burner adapter
Burner
Shutter with adjustment screws
Pressure regulator setting device
Regulation solenoid
Combustion head pressure
Upstream pressure from the filter
Upstream pressure from the control valve
Gas train supplied separately
To be performed by the installer
11
5
96
7 8
12
3
4
P2
10
12
P1
5
67 15
12
3
4
P2 P3
13
13
14
9
11 12
P1
4
PRESSURE DROP DIAGRAM
The diagrams indicate the minimum pressure drop of the burners with the various gas trains thatcan be combined with them; the values thus calculated represents the minimum required inputpressure to the gas train.
NATURAL GAS LPG
FS3 FS3
MU
LTIB
LOC
Gas train
MBC 65 DLE
Code
3970569
Terminal strip Plug and socket
•
Name
MBC 65 DLE
MBDLE 405
MBDLE 405
MBDLE 407
MBDLE 410
Code
3970569
3970530
3970500
3970531
3970532
Ø i
1/2"
1/2"
3/4"
3/4"
1"
Ø o
1/2"
1/2"
3/4"
3/4"
3/4"
X mm
307
321
371
371
405
Y mm
155
186
186
186
221
Z mm
122
120
120
120
145
W mm
31
46
46
46
55
Y
Z X
W
4
10
6
8
12
kcal/h x 1000
kW
5 10 15 20 25 30
20 3510
2
0
15 25 3011
G20 G25
0
2
6
8
10
12
14
4
MBC 65 DLE
4
10
6
8
12
kcal/h x 1000
kW
5 10 15 20 25 30
20 3510
2
0
15 25 3011
LPG
MBC 65 DLE
9,5 9,5
The dimensions of the gas trains vary depending on their construction features.The following table shows the dimensions of the gas trains that can be fitted to Riello 40 FS burners,intake and outlet diameters.
With installed plug (if the plug is not necessary, remove it in accordancewith gas train instruction manual indication).
5
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
Y
ZX
Øi
W
Øi
ØoØo
NATURAL GAS LPG
FS5 FS5
NATURAL GAS LPG
FS8 FS8
0
2
6
8
10
12
14
4
Gas train
MBC 65 DLE
MBDLE 405
MBDLE 407
Code
3970569
3970530
3970531
Terminalstrip
Plug andsocket
•
•
•
OutputkW
-
-
-
Gas train
MBDLE 405
MBDLE 407
Code
3970530
3970531
Terminalstrip
Plug andsocket
•
•
OutputkW
≤ 80 (*)
-
(*) With natural gas.
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
4
10
6
8
12
kcal/h x 1000
kW
10 20 30 50
20 60
2
0
30 40 50
14
16
40
5823
G20 G25
MBDLE 407MBDLE 405M
BC 6
5 DL
E
4
10
6
8
12
kcal/h x 1000
kW
10 20 30 50
20 60
2
0
30 40 50
14
16
40
5823
LPG
MBDLE 405
MBDLE 407
MBC 65 DLE
6050 70 80kcal/h X 1000
kW40
0
30 8050 7060 90
2
4
8
6
10
12
14
39,530
100 110
G20 G25
16
18
90
9346
MBDLE 407
MBDLE
405
6050 70 80kcal/h X 1000
kW40
0
30 8050 7060 90
2
4
8
6
10
12
14
30
100 110
LPG
90
9346
MBDLE 407MBDLE
405
39,5
22
0
2
6
8
10
12
16
18
20
14
4
With installed plug (if the plug is not necessary, remove it in accordancewith gas train instruction manual indication).
With installed plug (if the plug is not necessary, remove it in accordancewith gas train instruction manual indication).
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
6
NATURAL GAS LPG
FS10 FS10
NATURAL GAS LPG
FS20 FS20
For pressure levels different from those indicated above, pleasecontact Riello Burners Technical Office.In LPG plants, Multibloc gas trains do not operate below 0°C.They are only suitable for gaseous LPG (liquid hydrocarbons destroythe seal materials).
note
Gas train
MBDLE 405
MBDLE 407
MBDLE 410
Code
3970500
3970531
3970532
Terminalstrip
Plug andsocket
•
•
•
OutputkW
≤ 80 (*)
-
-
(*) With natural gas.
Gas train
MBDLE 407
MBDLE 410
Code
3970531
3970532
Terminalstrip
Plug andsocket
•
•
OutputkW
≤ 180 (*)
-
(*) With natural gas.
kcal/h x 1000
kW116
605042
10070 9080 110
G20 G25
MBDLE 410
55 6560 10040 45 50 70 75 80 85 90 95
0
2
8
12
10
4
6
14
MBDLE 407
MBDLE 405
kcal/h x 1000
kW116
6050 10070 9080 110
LPG
MBDLE 410
55 6560 10040 45 50 70 75 80 85 90 95
0
2
8
12
10
4
6
14
MBDLE 407MBDLE 4
05
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
MBDLE 410
kW120
0
10081
200
5
10
15
20
25
140 180160 220
kcal/h x 1000100 20080 120 140 18016070
30G20 G25
0
5
15
25
30
35
10
4045
MBDLE 407MBDLE 410
kW120
0
10081
200
5
10
15
20
25
140 180160 220
kcal/h x 1000100 20080 120 140 18016070
30LPG
MBDLE 407
4042
40
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
ΔP
com
busti
on h
ead
+ ga
s tra
inco
mbu
stion
hea
dPr
essu
re lo
ssm
ba
r
0
2
6
8
10
12
16
18
14
4
20
With installed plug (if the plug is not necessary, remove it in accordancewith gas train instruction manual indication).
With installed plug (if the plug is not necessary, remove it in accordancewith gas train instruction manual indication).
7
SELECTING THE FUEL SUPPLY LINES
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 1 2 3 4 5 106 20
50 60 10080 200 400 800 1000600
3
69
12152230
45 61 76 95 122 152 V
PRESSURE DROP (mbar)
1 2 3 4 5 6 7 8 10 20 30 40
PIPE DIAMETER
1,4
PIPE LENGTH (m)
1/2
3/4
1"
1" 1/2
6"
1" 1/4
4"
3"2" 1/22"
= Gas output Nmc/h
f1 - G20
= 0,62 - G251,18 - G31{
fV
15,34
Figure A
8
The following diagram enables pressure drop in a pre-existing gas line to be calculated and to select thecorrect gas train.The diagram can also be used to select a new gas line when fuel output and pipe length are known. Thepipe diameter is selected on the basis of the desired pressure drop. The diagram uses methane gas asreference; if another gas is used, conversion coefficient and a simple formula (on the diagram) transformthe gas output to a methane equivalent (refer to figure A). Please note that the gas train dimensions musttake into account the back pressure of the combustion chamber during operations.
Control of the pressure drop in an existing gas line or selecting a new gas supply line.The methane output equivalent is determined by the formula fig. A on the diagram and the conversioncoefficient.
Once the equivalent output has been determined on the delivery scale ( ), shown at the top of thediagram, move vertically downwards until you cross the line that represents the pipe diameter; at thispoint, move horizontally to the left until you meet the line that represents the pipe length.Once this point is established you can verify, by moving vertically downwards, the pipe pressure dropof on the botton scale below (mbar).By subtracting this value from the pressure measured on the gas meter, the correct pressure value willbe found for the choice of gas train.
Example: - gas used G25- gas output 9.51 mc/h- pressure at the gas meter 20 mbar- gas line length 15 m- conversion coefficient 0.62 (see figure A)
- once the value of 15.34 has been identified on the output scale ( ), moving vertically downwards youcross the line that represents 1" 1/4 (the chosen diameter for the piping);
- from this point, move horizontally to the left until you meet the line that represents the length of 15 mof the piping;
- move vertically downwards to determine a value of 1.4 mbar in the pressure drop botton scale;- subtract the determined pressure drop from the meter pressure, the correct pressure level will be found
for the choice of gas train;
- correct pressure = ( 20-1.4 ) = 18.6 mbar
V
V
V
9
COMBUSTION HEAD
The combustion head in Riello 40 FS burners is the result of aninnovative design, which allows combustion with low pollutingemissions, while being easy to adapt to all the various types ofboilers and combustion chambers.
Combustion head Flange
Simple adjustment allowsthe internal geometry ofthe combustion head tobe adapted to the burneroutput.
VENTILATION
Air suction
The different ventilation circuits always ensure low noise levelswith high performance of pressure and air delivery, in spite of theircompact size.The burners are fitted with an adjustable air pressure switch,conforming to EN 676 standards.
Dimensions of the flame
Example:Burner thermal output = 350 kW;L flame (m) = 1,2 m (medium value);D flame (m) = 0,6 m (medium value)
D
L
Burner output (MW)
Flam
e le
ng
th (
m)
Flam
e d
iam
eter
(m
)
0 2
1
1 3
2
4 5
0 0
0,5
1L max
L min
D max
D min
The FS3, FS5 and FS8 models are fitted with the new MG 557 microprocessor control panel.
For helping the commissioning and maintenance work, there are two main elements:
The lock-out reset button is the central operating element for resetting the burner controland for activating / deactivating the diagnostic functions.
The multi-color LED is the central indication element for visual diagnosis and interfacediagnosis.
Both elements are located under the transparent cover of lock-out reset button, as showed below.
There are two diagnostic choices, for indication of operation and diagnosis of fault cause:
- visual diagnosis:
ADJUSTMENT
All these models are one stage operation.
BURNER OPERATION MODE
Ou
tpu
tC
hec
ked
Var
iab
le
Air adjustment for FS10 and FS20
Switch
Air adjustment for FS3, FS5 and FS8
Switch
bar°C
ON
OFF
time
time
ON
OFF
One stage operation
10
Indication of operation:
In normal operation, the variousstatus are indicated in the formof colour codes according to thetable below.
Diagnosis of fault causes:
After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosisaccording to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3seconds.
Example of flashes sequence:
Interval 2 sPress reset for 3 s
Error code table
Probable cause
The flame does not stabilise at the end of the safety time:- faulty ionisation probe- faulty or soiled gas valves- neutral/phase exchange- faulty ignition transformer- poor burner regulation (insufficient gas)
Min. air pressure switch does not close or is already closed before the limitthermostat closed:
- air pressure switch faulty- air pressure switch incorrectly regulated
Presence of flame:- in stand-by position after heat demand- during pre-purging
Loss air pressure:- during pre-purging- during safety time or operations
Loss of flame 4 times during operations after 3 attempts of re-cycle:- poor burner regulation (insufficient gas)- faulty or soiled gas valves- short circuit between ionisation probe and earth- faulty ionisation probe
by the interface adapter and aPC with dedicated software.
The FS10 and FS20 models are also fitted with the RMG 88.620 A2 microprocessor control panel forthe supervision during intermittent operation.
For helping the commissioning and maintenance work, there are two main elements:
The lock-out reset button is the central operating element for resetting the burner controland for activating / deactivating the diagnostic functions.
The multi-color LED is the central indication element for visual diagnosis and interfacediagnosis.
Both elements are located under the transparent cover of lock-out reset button, as showed below.
There are two diagnostic choices, for indication of operation and diagnosis of fault cause:
- visual diagnosis:
- interface diagnosis: by the interface adapter anda PC with dedicated softwareor by a predisposed flue gasanalyzer (see paragraphaccessories).
Switch
Switch
Indication of operation:
In normal operation, thevarious status are indicatedin the form of colour codesaccording to the table below.The interface diagnosis (withadapter) can be activated bypressing the lock-out buttonfor > 3 seconds.
(A) - (B) Lock-out is shown by a led on the appliance.
START UP CYCLE
Correct operation for FS10 and FS20models:0s The burner begins the ignition cycle0s-2s Safety time2s-40s Pre-purge with the air damper open40s Ignition.
Error code table
Possible cause of fault
No establishment of flame at the end of safety time: - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner, no fuel- faulty ignition equipment
Faulty air pressure monitor
Simulation of flame on burner start up
Loss of flame during operation: - faulty or soiled fuel valves- faulty or soiled flame detector- poor adjustment of burner
Wiring error or internal fault
Flash code
Diagnosis of fault causes:After lock-out has occurred, the red signal lamp is steady on. In this status, the visual fault diagnosisaccording to the error code table can be activated by pressing the lock-out reset button for > 3 seconds.The interface diagnosis (with adapter) can be activated by pressing again the lock-out button for > 3seconds.The flashes of red LED are a signal with this sequence:(e.g. signal with n° 3 flashes – faulty air pressure monitor)
LED off3 sec. 3 sec. 3 sec.
Correct operation for FS3, FS5 and FS8 models:0s The burner begins the ignition cycle0s-4s The control box waits still after the heat request4s-44s Pre-purging time with start of the fan motor44s-47s FS5 and FS8 safety time as total ignition time44s-49s FS3 safety time as total ignition time.
Lock-out due to ignition failureIf the flame does not light within the safety limit time (3s for FS 5 and FS8; 5s for FS3) the burner locks-out.
M
TRM
FS3 - FS5 - FS8
FS10 - FS20
(A)
Time (s) Time (s)
TLMIV
SO
Time (s)Time (s) Time (s)
(B)Lock-out due to ignition failure
max. 2s 40s
Ignitiontransformer
Lock-out
Normal Lock-out due to ignition failure
3smax. 2s 40s
40 s 3 s for FS5 and FS85 s for FS3
4 s40 s
Normal
3 s for FS5 and FS85 s for FS3
4 s
Lock-out during pre-purging time
4 s
ϑP
13
Lock-out due to ignition failureIf the flame does not light within the safety limit (3s) the burner locks-out. When the flame-failure occursduring working, shut down takes place within one second.
lock- out lock- out
40 s = pre-purging time
2 flashes
3 flashes
4 flashes
7 flashes
10 flashes
Electrical connections must be made by qualified and skilledpersonnel in conformity with the local regulations in force.
WIRING DIAGRAMS
FS3 is fitted with terminal strip: FS5, FS10 andFS20 are fitted with 7 and 6 pole sockets, FS8is available in both the configurations
ONE STAGE OPERATION
Control box fitted with an ignition transformerin FS3, FS5 and FS8 models
In FS10 and FS20 models the control box isseparated from the ignition transformer
FS3 - FS5 - FS8
FS10 - FS20
Burner electrical wiring Gas train electrical wiring
The emission data have beenmeasured in the variousmodels at maximum output, inconformity with EN 676standard.
PPGV10V11
VPS
B5
N
L1
T6
T8T7
X6
3 2 1
321
3 2 N Ph1
PTS
T6A
X7
S3
N L
B4
B4 S3 T2 N L1T1
ϑ
TLP ϑ
h1
~230V 50Hz
The following table shows the supply lead sections and types of fuse to be used.
FS3Model
A
mm2
FL
230V
T61
F = Fuse L = Lead section
FS5
230V
T61
FS10
230V
T61
FS20
230V
T61
FS8
230V
T61
Special attention has been paidto noise reduction in the FS3model. The model is fitted withsound-proofing material insidethe cover.
mg
/kW
h
80
CO EMISSIONS
mg
/kW
h
0
10
20
30
40
NOISE EMISSIONS (sound pressure)
dB
(A)
0
80
85
90
95
100
105
110
115
50
20
40
60
120
FS3 FS5 FS10 FS20FS8
FS3 FS5 FS10 FS20FS8
FS3 FS5 FS10 FS20FS8
15
OVERALL DIMENSIONS (mm)
These models are distinguished by their reduced size, inrelation to the outputs achieved, which means they can befitted to any boiler actually on the market.
Z
X
Z
Y
PACKAGING
BURNER
BURNER-BOILER MOUNTING FLANGE
365435473473525
325345413413453
511
13,61717
300315320320365
A2-B2
F
C
R
A1-B1
Model
FS3
FS5
FS8
FS10
FS20
X Y kg
FS3 - FS5 - FS10 FS20
Q
Q
A
D
Reduction nipple**
Rp 1/2” - Rp 3/8”
* With reduction nipple** Standard equipment on R40 FS3
F
C R
C1
16
Z
F E
IV
M
N
H
Model A D H
FS3
FS5
FS8
FS10
FS20
215233262262298
252272305305350
230295347346389
E
100100110110120
F
9191105105125
I N
165180204204230
M
3748616167
Rp 3/8”*Rp 1/2”Rp 3/4”Rp 3/4”Rp 3/4”
Z
2528333333
V
132138142142152
Q
Model
FS3
FS5
FS8
FS10
FS20
----
155
A1 A2
----
200
B1
----
155
B2
----
200
C
140140160160170
C1
130130130130
-
F
170170185185170
Q
4545454590
R
1010111111
INSTALLATION DESCRIPTION
Installation, start up and maintenance must be carried out byqualified and skilled personnel.The burner is set in factory on standard calibration (minimumoutput), if necessary adjustments can be made on the basisof the maximum output of the boiler.All operations must be performed as described in the technicalhandbook supplied with the burner.
The air damper position can be easily adjusted removingthe burner cover.
Head setting is easy and aided by a graduated scale, atest point allows reading the air pressure in thecombustion head.
Riello 40 FS burners are fitted with an air pressureswitch which, in accordance with EN 676 standards,can be adjusted by the installer using a graduatedselector, on the basis of the effective working conditions.
Maintenance is easily solved because the combustionhead can be disassemblied without having to removethe burner from the boiler.
BURNER SETTING
MAINTENANCE
17
BURNER ACCESSORIES
Remote reset control kit for MG 557/3/5 control boxThe MG 557 control box can be remotely released using an electric commandkit. This kit must be installed in conformity with the local authority.
7-pin plug kitIf necessary a 7-pin plug kit is available (in packaging of n. 5 pieces).
18
Kit code
FS3 - FS5 - FS8
Burner
Remote reset control kit for MG 557/3/5 control box
3002750
End cone with turbulator disk
Kit code
3000916
3000917
3000918
3000919
FS5
FS8
FS10
FS20
Burner
End cone with turbulator disk
Projection (mm)
+15
+18
+18
+23
LPG kitFor burning LPG gas, a special kit is available to be fitted to the combustion head on the burner, asshown in the following table:
Kit code forextended head
FS3
FS5
FS8
FS10
FS20
Burner
LPG kit
Kit code forstandard head
3000881
3000882
3000927
3000884
3000886
3000881
3000882
3000927
3000884
3000886
Extended head kit“Standard head” burners can be transformed into “extended head” versions by using the special kit.Below the KITS available for the various burners are listed, showing the original and the extendedlengths.
Kit code
3000820
3000864
3000920
3000873
FS3 - FS5
FS8 - FS10
FS8
FS20
Burner
Extended head kit
Extendedhead length
(mm)
125
170
278
280
Standardhead length
(mm)
100
110
110
120
Kit code
3000945FS3 - FS5 - FS8 - FS10 - FS20
Burner
7-pin plug kit
PC interface kitTo connect the flame control panel to a personal computer for the transmission of operation, faultsignals and detailed service information, an interface adapter with PC software are available.
Burner Kit code
3002731
3002719
Interface kit
FS3 - FS5 - FS8
FS10 - FS20
19
Town gas kit
Kit code
3000888
3000889
3000890
3000891
3000893
FS3
FS5
FS8
FS10
FS20
Burner
Town gas kit
Seal control kitTo test the valve seals on the gas train, (except for the model with Multibloc MBC 65 DLE) a special"seal control kit" is available.
GAS TRAIN ACCESSORIES
Kit codeBurner
Seal control kit
3010123FS5 - FS8 - FS10 - FS20
Continuous ventilation kit for RMG control boxIf the burner requires continuous ventilation in the stages without flame, a special kit is available asgiven in the following table.
Kit code
3010094FS10 - FS20
Burner
Continuous ventilation kit for RMG control box
Ground fault interrupter kitA “Ground fault interrupter kit” is available as a safety device in case of electrical system fault. It issupplied with burners pin plug.
FS5 - FS8 - FS10 - FS20
Burner Kit code
3001180
Ground fault interrupter kit
SPECIFICATION
A special index guides your choice of boiler from thevarious models available in the FS series.Below is a clear and detailed specification descriptionof the product.
The R40 series balanced flue gas burner has been specificallydesigned to meet the increasing trend towards the use of balancedflue, otherwise known as room sealed appliances, which avoid thenecessity of having a chimney to discharge the products ofcombustion.
Balanced flue products are completely sealed from the environmentin which they are installed, drawing air for combustion directly fromthe outside, thereby ensuring no unwelcome smells from thecombustion.
As a result of the burner components being completely enclosedthis provides an additional benefit of low sound levels.
This version is available for FS3 and FS5 only.
Overall dimensions (mm)
288
249
96 308
91
20
Electrical supply to the system : 1/230/50 1/230V/50Hz
Burner
Monoblock, gas burners, completely automatic, with one stage settings fitted with:- Fan with forward curve blades- Cover lined with sound-deadening material- Metallic and fixed air damper with adjustment- Single phase electric motor 230 V, 50 Hz- Combustion head fitted with:
- stainless steel head cone, resistant to high temperatures- ignition electrodes- ionisation probe- gas distributor- flame stability disk- flame inspection window
- Adjustable air pressure switch, with graduated selector, to guarantee burner lock out in the caseof insufficient combustible air
- Microprocessor-based flame control panel MG 557 (with diagnostic, remote reset, continuous purge integrated, recycle, post-purge)- IP X0D electric protection level.
Gas train
Fuel supply line in the Multibloc configuration, fitted with:- Filter- Pressure stabiliser- Minimum gas pressure switch- Safety valve- Single stage working valve with ignition gas output regulator.
Standard equipment:- Flange insulation screen- Screws and nuts for fixing the flange to the boiler- 7-pole socket- Hinge- Reduction nipple Rp 1/2” - Rp 3/8” (for R40 FS3 only)- Grommet- Instruction handbook for installation, use and maintenance- Spare parts catalogue.
Available accessories to be ordered separately:- Remote reset kit for MG 557/3/5 control box- Extended head kit- End cone with turbulator disk- LPG kit- 7-pin plug kit- Town gas kit- PC interface kit- Ground fault interrupter kit- Continuous ventilation kit for RMG control box- Balanced flue version- Seal control kit.
PRODUCT SPECIFICATION
21
22
23