QUICK REFERENCEHeat/Cool Units
MODELNUMBER
COOLING(Btuh) EER ELECTRIC
HEAT (Btuh)
EVAP. FANCFM(HI
SPEED)
APPROX.WGT(SHIP)
1-PH, 60-HzVOLTS
CURRENT (AMPS) POWER (WATTS) BRANCHCIRCUITFUSE(AMPS)
APPLICATIONSWhether you are designing a new structure or replac-ing the packaged terminal air conditioning units in anexisting building, Carrier will meet your needs.• Hotels and motels• Nursing homes and assisted living care centers• Offices
• Apartments• Single-family dwellings• Home conversions and residential add-ons
NEW CONSTRUCTIONThe Carrier 52S unit is designed to meet the needs ofthe architect, engineer, and contractor. For unit instal-lation, Carrier’s expert support network will assist inall applicable aspects of the construction project, frompreparing a budget to start-up.
ADVANTAGES OF THE PACKAGED TERMINAL AIRCONDITIONER FOR NEW CONSTRUCTION
DESIGN FLEXIBILITYFOR THE
ARCHITECT/ENGINEER
• Super-quiet performance, indoors and out• No bulky duct system• No separate equipment room• No water towers or additional cooling equipment• No complex match-up of different HVAC components• Less sensitivity to building orientation (sun, wind, shade)• Optional architectural grille to permit custom exteriorappearance
INITIAL COST SAVINGSFOR THE
BUILDING OWNER
• No expensive component HVAC system purchase• No equipment room or maintenance engineering staff• Two-part delivery to minimize on-site damage• Weather-protected wall sleeve that goes in place during con-struction; chassis that slides in place after construction
• No seasonal changeover required for cooling or heating —units are self-contained comfort systems
LOWER OPERATING COSTSAND RELIABLE COMFORTFOR THE OCCUPANT
• Individual units allow tenants to choose the degree of comfortand operating economy
• Rapid servicing reduces downtime: complete chassis can bereplaced in minutes without disrupting other occupants.
• Each unit operates independently of other units in the building.No dependency by building on individual units.
RETROFIT/REPLACEMENTIf you are replacing existing units, your optionsinclude:• Replacing the existing wall sleeve with a CarrierWeather Last™ sleeve
• Installing the new unit into an existing Carrier sleeve.The 52S Series chassis fits into all of Carrier’s oldersleeves.
• Using an existing sleeve made by another manufac-turer. The 52S Series chassis can be adapted with asimple accessory kit to fit existing GE, Amana, andTrane wall sleeves. All other sleeve applications needapproval from Carrier.
2
PRODUCT OVERVIEWThis section summarizes product features, options, andaccessories covered in detail in later sections.
Polymer Sleeve — Designed for ruggedduty, acoustic absorption, and attractiveappearance for years to come.Rotary Compressors — Provide quiet,reliable operation.
Copper Tube Fin Coils— Enhanced coilsprovide durability, high performance, andease of operation.Fresh Air Control Arm — Allows out-door air into room through foam filter forimproved air quality.Fan Cycle Switch — Dual options:(1) Continuous fan operation.(2) Cycle fan ON and OFF with compres-
sor operation.Temperature Limiter — Allows tempera-ture range restraints for the unit by mak-ing a simple service adjustment.
Control Door — Provides protection forcontrols and enhances appearance.Easy Access to Electrical Compo-nents — Simply remove two screws anddrop down the control box.
Improved Condensate Removal — Mini-mizes condensate water on outside ofbuilding.
New One-Piece Filter Design — Pro-vides improved air filtration and can beremoved easily for cleaning.Durable Discharge Grille — Made ofpolycarbonate; holds up under the tough-est conditions.
Louvered Front Cover — Made of du-rable polycarbonate. Provides improvedperformance and quiet operation.
FACTORY-INSTALLEDOPTIONSCorrosion ProtectionAdditional corrosion protection for painted partition,painted control box, and outside coil in seacoastapplications.
Remote ControlPermits the unit to be operated automatically from aremote accessory thermostat.
A. 52S Cooling-Only Unit
B. 52S Cooling/Heating Unit
C. 52S Cooling/Heating Unit With Remote Control (Blank Plate)
Subbase
265 V Cord Kit
Thermostats
Architectural Outdoor Grillein Aluminum or Plastic
Lateral Duct Kit
Hard-Wire Kit
SecurityDoor Kit
Standard Grille
GE,Amana/TraneSleeve Retrofit Kits
Drain Kit
EnergyManagementKit
4
PRODUCT FEATURES AND BENEFITSThe 52S model is a single-package, through-the-wallunit for heating and cooling hotel rooms, offices, apart-ments, condominiums, and residential additions. The52S Series features include:• Quiet operation• Exceptional energy efficiency ratios (EERs)• Multi-room structure design• Fixed wall sleeve, slide-out chassis• Attractive, durable cabinet
• Chassis that retrofits to most major competitors’ sleeves• Low operating costs• No bulky duct system• No seasonal changeover
QUIET OPERATIONOccupants and neighbors are protected against noiseintrusion. Indoor sound reduction is achieved becauseof the unit’s design and its louvered front cover, splitscroll and blower, and heavy gage unit partition. Ro-tary compressors provide quiet, reliable operation. Thesplit scroll provides a more uniform air discharge.The new aerodynamic condenser shroud design im-proves airflow and reduces outdoor noise, providing amore relaxing outdoor environment. The propeller-type fan and stator design allow efficient low-speedoperation.
MOST EFFICIENTPERFORMANCEHigh EERs provide excellent operating economy. Thesystem operates without bulky ductwork, separate equip-ment room, and complex match-up of different com-ponents. Heating and cooling modes are available withoutseasonal changeover.
EFFICIENT FAN MOTORAn efficient, totally enclosed PSC (permanent split ca-pacitor) fan motor provides a choice of high or lowspeeds for heating and cooling. A fan-only setting pro-vides air circulation. The fan motor requires no main-tenance and no lubrication.
The Quiet is engineered into every 52S Unit.
5
PRODUCT FEATURES AND BENEFITS (cont)
NO-RUST WEATHER LAST™WALL SLEEVE AND FRONTPANELThe indoor front panel and wall sleeve use nonmetal-lic compounds that never rust or corrode, do not sup-port combustion, and do not give off toxic fumes. Theweather-resistant feature exceeds requirements of
Underwriters’ Laboratories and resists damage causedby impact and scratching. The Weather Last featurealso insulates and has up to 10 times the acoustic ab-sorption of metal cabinets.
Removable Front Panel
ONE-PIECE WASHABLEINDOOR FILTER
The louvered front panel fits firmly onto the chassis.The panel is easily removed for service and filter ac-cess without removing screws. It provides front air in-take to enhance performance and quiet operation. Italso provides the option of flush mounting to the floor.
Removable Front Panel
The filter covers the entire surface area of the coil.Once the front panel is removed, the filter simply snapsout of the track. The one-piece, molded plastic framewith polyurethane filter retains its shape and meets hos-pital and nursing home requirements. The filter maybe washed or vacuumed repeatedly.
One-Piece Indoor Filter
6
DURABLE CONTROL PANELDOOR AND EASY-TO-USECONTROLS
WASHABLE VENT AIRFILTER
BI-DIRECTIONALDISCHARGEGRILLE
The reinforced control door conceals controls and fea-tures an attractive surface that will not chip. The hingeand door are extruded as one piece and provide pro-tection from demanding transient use. The door is slopedto discourage use as a shelf. Easily accessible fromthe room side, the control buttons and thermostat areclearly marked and simple to use.
52S Cooling/Heating Unit Control Panel
The unique duct system is activated by a two-positioncontrol. Fresh outside air is redirected by the vent doorto an inside low-pressure area. A molded plastic filterprevents dirt and debris from entering the room sideof the unit. The vent mechanism is made from non-corrosive material ensuring reliable operation. High-pressure airflow creates a tight, draft-free seal whenthe vent door is closed.
VENTDOOR
OUTDOORVENTFILTER
Outdoor Vent Filter Location(Left Side of Chassis)
The discharge grille is made of durable polycarbonateand is reversible. Air flows upward at an 80 degreeangle to the floor but can easily be adjusted towardthe horizontal for airflow at a 53 degree angle to thefloor. The discharge grille is cool to the touch duringthe heating cycle.
Reversible Polycarbonate Discharge Grille
7
PRODUCT FEATURES AND BENEFITS (cont)
EASY ACCESS TO CHASSISAccess to the chassis simply requires removing fourscrews and then sliding the chassis out of the sleevefor service. Once the power is turned off, connectorscan be separated on hard-wire units, or the power cordcan be disconnected on cord-connected units.
HIDDEN CONTROLSThe factory-wired control box houses all control com-ponents and is quickly accessible without removingthe chassis from the wall sleeve. Remove two screwsand the hinged door lowers, providing quick access toall the components and the wiring diagram.
Temperature LimiterThe limiter reduces operating costs by allowing theowner to control the range of cooling and heating tem-peratures available to the occupant. It is located underthe control panel, out of the occupant’s sight. Eachsetback on the limiter is equivalent to 5° F and therange of temperature settings available to the owner isfrom 60 to 90 F. The limiter is not pre-set at thefactory.The occupant’s temperature control knob is conve-niently located on the control panel and is clearly markedwith a range of dial settings.
Outdoor Air Vent ControlThe vent knob is located under the front panel. Thisknob slides to manually open and close the outdoorvent.
Fan Cycle SwitchThis switch (not available on RC models) allows thefan to operate in 2 modes:• Continuous — This setting allows the fan to run con-tinuously, circulating air even when the temperaturesetting has been satisfied. This setting, which helpsto keep the room temperature closer to the thermo-stat setting, is used for maximum comfort.
• Cycle — This setting allows the fan to cycle on andoff with the compressor during heating or cooling.The fan stops when the temperature setting is reached.The longer unit off-time makes this option moreenergy-efficient with only slightly wider variationsin room temperature.
Easy Service Access
8
ENHANCED COPPER TUBING
DEEP BASEPAN
CONDENSATE REMOVALSYSTEMCarrier’s 52S Series units have a slinger ring aroundthe outside of the outdoor fan propeller. Condensate(water) in the unit basepan is picked up by the slingerring and dispersed onto the hot outdoor condenser coil.The heat from the coil evaporates the condensate and
cools the coil at the same time, thereby removingcondensate and increasing the unit’s efficiency.NOTE: If it is necessary to remove 100% of the con-densate, we recommend using the Carrier Drain Kit(Part No.: DRAIN-KIT-4PK).
CARRIER WARRANTYCarrier’s full one-year warranty is the most compre-hensive in the industry. In addition, Carrier provides:• Full coverage for parts and labor.
• Four additional years of coverage on sealed refrig-eration systems.
• Limited second through fifth year coverage on non-refrigeration system parts.
Enhanced copper tubing is more efficient and durableand can be repaired in the field, if required.Because copper is a very stable metal, it is durableand resists corrosion. Enhanced copper tubingincreases:• heat transfer capability• the efficiency of the cooling and heating processes• thermal conductivity (by creating additional tube sur-face and turbulent refrigerant gas flow)
Every Carrier PTAC coil undergoes thorough leak test-ing and pressure testing up to 350 lbs per square inch.
Enhanced Copper Tubing
Seamless drawn basepan walls add protection againstwater accumulation resulting from storm-driven rainwith heavy wind.Carrier’s deep basepan holds up to two gallons of wa-ter without spilling. Closed cell foam insulators arelocated between the basepan and coils, keeping coilsfrom direct contact with standing condensate and thebasepan.
CONDENSATE DRAIN VALVEThe temperature-activated drain opens when the out-door temperature drops below 45 F to prevent waterfrom freezing in the basepan.
BASEPANCONDENSATEDRAIN VALVE
Deep Basepan Protects AgainstWater Accumulation
9
PRODUCT FEATURES AND BENEFITS (cont)
HEATPUMPSPAYTHEIROWNWAYHeat pump models are available at a nominal addi-tional cost. In many locales, the payback is realized injust a few months. Cost and payback details are pro-vided on the next page.
How The Heat Pump Works
Special Features
Two-Stage Indoor Thermostat:The indoor thermostat senses the indoor temperatureand automatically turns on electric heat to warm theroom quickly, automatically switches to heat pumpmodewhen the room reaches the desired temperature, andprovides automatic backup heat if the compressor shouldfail.
Outdoor Thermostat:During the heating cycle, the outdoor thermostat sensesoutdoor temperature. It switches the unit to electricheat mode when the outdoor temperature is 25 For below. The thermostat switches the unit back to heatpump mode when the outdoor temperature rises above40 F, which is enough to provide heat to meet de-mand. The entire operation is completely automatic.
Reversing Valve:The reversing valve provides quiet refrigerant flow af-ter the unit shuts off. The valve controls the directionof refrigerant flow for both heating and cooling func-tions and remains energized as long as the controls arein the heat position. When the cooling controls are ac-tivated, the valve automatically reverses to the cool-ing position.
Manual Compressor Override Switch:This switch completely locks out the compressor. Notethat the compressor and heater do not operate at thesame time, thus conserving energy.
In Hot Weather:Carrier’s Series 52 units provideindoor comfort in the same man-ner as conventional air condition-ers, removing heat and humidityfrom indoor air. The heat and hu-midity is released to the out-doors. Carrier’s high efficiencydesign saves energy and reducescooling costs.
In Cool Weather:When the outdoor temperature isabove 25 F, the heat pump drawsheat from outdoor air and uses itto heat indoor air. Since heat istransferred and not produced,Carrier’s heat pump uses less elec-tricity and reduces energy costssignificantly.
In Sub-Freezing Weather:When the outdoor temperaturefalls below 25 F, the unit auto-matically switches on a built-inelectric heater. The compressorstops and a blower circulateswarm air produced by the heater.When the outdoor temperaturerises above 40 F, heat pump op-eration resumes automatically.
10
HEAT PUMP ENERGYSAVINGS
CARRIER HEAT PUMP INITIAL COST VERSUS SAVINGS OVER HEAT/COOL MODELS
* Computer projections based on full cooling load at 95° F. Savings projected for 230-v ratings only.1 Heating load is 5,000 Btuh at winter design point temperature.2 Heating load is 10,000 Btuh at winter design point temperature.3 Heating load is 15,000 Btuh at winter design point temperature.
Heat pumps save more on operat-ing costs during the heating cyclethan heat/cool models. The table be-low shows that the higher initial costof purchasing a heat pump is quicklymade up in lower operating costs.Use the map to identify the climatezone’s designated number. Readingdown the left-hand column of thetable, select the cost/kWh rate in thiszone that most closely approxi-mates your local rate. The approxi-mated savings and payback periodis found at the intersection of yourzone/rate line and the desired BtuhCooling Capacity column. Exact sav-ings are determined by lifestyle, lo-cal electrical rates, and climaticconditions.
PRODUCT CATALOG NUMBERCooling-only units are not available with RC (remote control) option.
Standard 52S Unit• Chassis with front panel• Electro-mechanical pushbutton controls• Cord-connected chassis for 230/208V units• 265V cord or hard-wired accessory kit (must be or-dered separately)
Lead-time: Most 230/208V models are in stock; callfor lead-times for other models.
Standard 52S Unit
12
FACTORY-INSTALLEDOPTIONSRemote Control (RC)Carrier’s remote control option includes:• a standard chassis with front panel• factory-installed low voltage controls for remote ther-mostat operation
A wall thermostat must be ordered separately.NOTE: Both heat pump and heat/cool units operatewith a heat/cool thermostat. A heat pump thermostatshould never be used with this product.
Corrosion Protection (CP)To protect against the corrosive effects of a seacoastenvironment, this option includes:• a standard chassis with front panel• special protections consisting of:— painted control box and unit partitions— pre-coated aluminum coils with copper tubing— stainless steel tube sheets (outdoor coil)— totally enclosed fan motor with moisture-resistant
windingsNOTE: All installations within one mile of the sea coastor other corrosive environment must use CorrosionProtection (CP).
13
ORDERING DATA (cont)
FIELD-INSTALLEDACCESSORIES
Weather Last™ Wall Sleeve
Corrosion-Protected Polymer Sleeve
Part No.: WALL-SLEEVE-1PKPart No.: WALL-SLEEVE-9PKIt is recommended that a Carrier sleeve be used with aCarrier chassis. However, an accessory Retrofit Kit maybe ordered when fitting a new 52S unit into an exist-ing sleeve. See Accessory Retrofit Kit for GE Sleeveon page 20 and Amana/Trane Sleeve on page 21.The Carrier accessory wall sleeve is made from amoldedpolymer that is designed for strength and durability.This material has excellent corrosion resistance and aflammability rating of UL94-5V. The polymer sleeveabsorbs sound, provides better insulation than a metalsleeve, and offers years of protection against theelements.The beige (alpine mist) finish blends in well with in-side or outside decor. The sleeve surface is textured toprevent shine and hide scratches.The sleeve is packaged in a heavy-duty cardboard car-ton with an internal corrugated stiffener to reduce thechance of damage during shipping and construction.The rib configuration on the sleeve bottom allows easychassis removal and aids in drainage. Water that over-flows the basepan is channeled along the ribs to thedrain openings on the back of the unit.The sleeve isbuilt with a pitch of 1⁄4 in. per foot, so there is noneed to adjust the sleeve during installation.Overflowslots are in place to divert excess water during severeweather. Locating holes in the side panels allow easyfastening of the sleeve to wall openings. An accessorydrain kit is available, if needed. Refer to Drain Kit,page 16, for the part number.This sleeve accommodates all Carrier accessory grilles,which simply snap in place and require no screws.Refer to the 52S unit installation instructions for com-plete sleeve and chassis installation procedures. Referto dimension drawings (pages 22-27) for typical wallinstallation and unit dimensions.
When installing the Carrier wall sleeve, note thefollowing:• If more than 4 in. of sleeve project into the room orthe wall is less than 2 in. thick, an accessory sub-base must be used for support. Refer to the descrip-tion of the Accessory Subbase on page 17 for thepart number.
• For all applications with an accessory subbase, wallsleeve must exend 31⁄4 in. minimum into room andmust be 31⁄4 in. minimum to 51⁄2 in. maximum abovefloor (including carpeting). Refer to wall sleeve in-stallation instructions for further information.
• The Carrier sleeve must be mounted so that it is levelin all directions. See wall sleeve installation instruc-tions for leveling procedure.
• The sleeve should be caulked on all sides, includingboth inside and outside the building.
14
Aluminum ArchitecturalOutdoor Grilles (Louvered)Part No.: GRILLE-ALU-WHITEPart No.: GRILLE-ALU-BRONZPart No.: GRILLE-ALU-BROWNPart No.: GRILLE-ALU-BEIGEThis premium line of decorative outdoor grilles willenhance the appearance of any building. The grillesare made of strong, durable, extruded, anodized alu-minum and are designed to be mounted easily frominside the room. These elegant grilles have baked enamelfinishes available in several colors. See inside of backcover for standard colors. For more information oncustom colors and sizes, contact Reliable Products at1-800-624-3914.
Architectural Grille inAluminum or Plastic
Plastic Architectural OutdoorGrilles (Louvered)Part No.: GRILLE-PLA-BROWNPart No.: GRILLE-PLA-BEIGEThis value line of plastic outdoor grilles will blend at-tractively with most building exteriors. Mounted eas-ily from inside the room, the one-piece, molded grilleis designed for protection, enhanced appearance, andsuperior weather-resistance. The grille is made of du-rable polymer and has a colorfast, lightly-textured fin-ish that blends well with most exterior finishes. Seeinside of back cover for colors.
StandardOutdoorAluminumGrillePart No.: GRILLE-ALU-STAMPThis cost-effective, one-piece standard grille is madefrom durable anodized aluminum. The grille is light-weight, has a clear finish, and is easy to install frominside the room.IMPORTANT: If you wish to use a grille notmade by Carrier for your Carrier unit(s), contactthe Carrier Application Engineering Group at1-800-894-6449.
Standard Grille
Sleeve Insulation KitPart No.: INSULATION-KITThe accessory sleeve insulation kit prevents indoorcondensation under low outdoor temperature condi-tions. In addition, this accessory reduces the transmis-sion of outdoor noise into the room. The kit comeswith pre-cut pieces of insulation and instructions forinstallation.
15
ORDERING DATA (cont)
Drain KitPart No.: DRAIN-KIT-4PKThis universal drain kit may be used internally or ex-ternally to route condensate to a drainage system. Itcan be field-installed on the Carrier wall sleeve.Although Carrier’s units are designed to dissipate allthe condensate generated during normal cooling, theremay be times when abnormal conditions cause morecondensate than the unit can dissipate. Heat pumps some-times generate condensate that the unit may not be de-signed to handle. If condensate that drips from the wallcase is objectionable, this internal/external drain kitshould be installed.The drain kit may be attached to the exterior right orleft side of the wall sleeve for external draining or maybe mounted to the room side of the wall sleeve for in-ternal draining.
Drain Kit
Hard-Wire KitPart No.: H/W-KIT-230VPart No.: H/W-KIT-230V-4PKPart No.: H/W-KIT-265VPart No.: H/W-KIT-265V-4PKThis accessory hard-wire kit provides a permanent con-nection to the unit. Electrical hard wiring is requiredwhen NEC (National Electrical Code) or local codesrestrict the use of power cord and plug connections.The hard-wire kit mounts on the right side of the unitand comes with 42 inches of flexible steel conduit, anelectrical junction box, and a unit-mounted connector.The 230 volt kit comes with an additional plug assem-bly to use when replacing the 230-volt cord.
Hard-Wire Kit
16
SubbasePart No.: SUB-BASEThis decorative subbase supports the unit and routeselectrical wires. The subbase mounts to the wall sleeveand comes with adjustable legs and side skirting toprovide a finished appearance.A subbase is required for installations where the wallsleeve extends 4 or more inches into the room or thewall is less than 2 in. thick. The minimum clearancebetween the bottom of the sleeve and the floor is31⁄4 in., and the maximum clearance is 51⁄2 inches. Thesubbase assembly comes with two leveling legs. Seethe wall sleeve installation information for levelinginstructions.The subbase is designed to accommodate various elec-trical configurations. Internal partitions and knockoutsallow easy and flexible field-installation of electricalconnections. The subbase supports both hard-wire andcord connections. Electrical receptacles must be field-supplied.The subbase, along with a field-supplied receptacle,must be installed if the 265-v Cord-Connection Kit(Part Nos. PLUG-265V-15AMP, PLUG-265V-20AMP,or PLUG-265V-30AMP) is used. See this page for moreinformation.
Subbase Assembly
265V Cord-Connection KitPart No.: PLUG-265V-15AMPPart No.: PLUG-265V-20AMPPart No.: PLUG-265V-30AMPThis 265-volt cord connection kit is an alternative to a265-volt permanent hard-wire connection. The kit con-tains an 18-inch cord and a unit-mounted plug con-nection. This field-installed accessory connects easilyto the right side of the unit and plugs into a receptaclein a subbase. The subbase, described in this section,and a field-supplied receptacle are required if this cord-connection kit is used. 265V Cord Kit
17
ORDERING DATA (cont)
Manual Changeover WallThermostatPart No.: HH01AD045This manual changeover wall thermostat provides areliable and consistent level of occupant temperaturecontrol for both heat pumps and heating/cooling units.The thermostat consists of a conventional vented coverand a coiled bimetal element. It is used only on re-mote control (RC) models. HEATCOOL
AUTO FANOFF
60 70 80 90
ON
Manual Thermostat
Lateral Duct KitPart No.: LAT-DUCT-PLENUM (Adapter Plenum)Part No.: EXTENSION-DUCT (Extension)The accessory lateral duct kit allows one unit to heator cool two rooms. The kit provides substantial sav-ings for apartments, hotel suites, and office suites byeliminating the need for separate units for every room.The amount of air that can be diverted to an adjoiningroom is adjustable from 10 to 40 percent.The lateral duct kit consists of two separate packages,the plenum and the extension duct. The kit mounts tothe wall sleeve and allows either right or left side duct-ing. Consider the following when designing a ductedapplication.1. The maximum extension of the duct length is 3 feet.2. The duct run must be straight and horizontal; no
bends or turns.3. The minimum recommended clearance between the
unit and the adjoining room wall is 6 inches.4. You must provide for return air from the adjoining
room.5. Carrier 52S units are not qualified for use with any
other ducting scheme.See page 23 for more information.
Lateral Duct Kit
Security Door KitPart No.: SECURITY-DOORThis key-locking security door kit prevents unautho-rized access to the unit’s heating and cooling controlsand prevents tampering with units in public locationsand institutions. This field-installed accessory in-cludes two matching keys and fits all Carrier 52Smodels. Keys are common to all Security Door kits.
Security Door Kit
18
Programmable ThermostatPart No.: TSTATCCPAC01-BThis microcomputer-controlled, programmable wall ther-mostat has enhanced features that provide automaticchangeover control for both heat pumps and heating/cooling units. It is used only on remote control (RC)models.NOTE: Both heat pumps and heat/cool units operatewith a heat/cool thermostat. A heat pump thermostatshould never be used with this product.
Programmable Thermostat
Replacement FiltersPart No.: AIR-FILTER-25PKThe Carrier 52S model replacement air filters come inpackages of 25. The filters save energy by preventingthe evaporator coils from being plugged with dirt andlint. These economical and sturdy mesh filters may bewashed, vacuumed, and reused. Carrier’s filters meetoriginal equipment specifications and are factory-authorized replacement parts.
Easily Replaceable Filters
Energy Management KitPart No.: EM-KITThis field-installed accessory kit allows individual unitsto be turned on and off from a remote location. Wheninstalled at a hotel front desk, the kit can help to con-serve energy by allowing hotel staff to easily turn offunits when rooms are not occupied.The kit incorporates Carrier’s Freeze Guard protectionthat prevents rooms from freezing during extreme orextended cold periods. Under these conditions, the FreezeGuard automatically disables front desk control andallows the unit to maintain a temperature of at least50 F in the room. When the room reaches 65 F, theFreeze Guard feature returns the unit control to thefront desk.This kit interfaces to most energy management sys-tems. When installed in locations other than the frontdesk, the kit can control unit operation by receivingsignals from field-supplied devices such as motion sen-sors or heat sensing detectors.
Energy Management Kit
Control devices connected to the Energy ManagementKit must have normally open sets of contacts (whenthe switch is open, the unit operates). A 24-volt trans-former must be field supplied and connected to theEnergy Management Kit. (See typical wiring diagramon page 41.)
19
ORDERING DATA (cont)
Accessory Retrofit Kit for GESleevePart No.: GE-RETROFIT-KITThis kit contains the items that allow owners to installa 52S chassis into a plastic or metal GE sleeve so thatthere is no air leakage or damage to 52S unit compo-nents. The Retrofit Kit is an accessory and must be or-dered separately from the factory.To retrofit to a plastic GE sleeve, it is important to re-move the rear bottom seal from the sleeve (Figure A).To retrofit to metal sleeves, remove the metal clip onthe GE mounting rail and install the metal bracket pro-vided in the Retrofit Kit (Figure B).Both metal and plastic sleeves require placing two foambaffles (provided in the Retrofit Kit) on the outdoorcondenser coil tube sheets, one baffle on each tube sheet(Figure C). These baffles must be installed to preventair recirculation.
BOTTOM SEAL
GE SLEEVE
A. Location of Foam Seal to be Removed fromGE Plastic Sleeve
SLEEVEGE MOUNTING RAIL
METAL CLIP
SLOT
INSTALLED BRACKET
B. Bracket to be Attached to GE Metal Sleeve
C. Placement of Foam Baffles on Outdoor Coil Tube Sheets
Refer to the installation instructions for complete in-stallation procedures.IMPORTANT: Be sure that the foam baffles makea good seal between the grille and outdoor coil tubesheets. Improper installation of the foam baffles orneglecting to install them can result in condenser(outdoor) air recirculation. This will degrade theunit’s performance and shorten product life. Do notignore this step.Carrier does not assume responsi-bility for costs or damages resulting from misappli-cation of foam baffles.
20
Accessory Retrofit Kit ForAmana/Trane SleevePart No.: AM-RETROFIT-KITThis kit contains the items that allow owners to installa 52S chassis into an Amana or Trane sleeve so thatthere is no air leakage or damage to 52S unit compo-nents. The kit includes a bracket, foam baffles, screws,side angles, a foam seal, and foam gaskets. The retro-fit kit is an accessory and must be ordered separatelyfrom the factory.The installation requires adding a bracket (Figure A)to the wall sleeve to ensure that the chassis will belevel when it is placed in the metal sleeve. Attach foamseal to front of sleeve as shown in Figure A. Two foambaffles (provided in the Retrofit Kit) are placed on theoutdoor condenser coil tube sheets, one baffle on eachtube sheet (Figure B). These baffles must be installedto prevent air recirculation. Foam gaskets (Figure C)added to the basepan prevent water leakage.
SLEEVE
INSTALLEDBRACKET
ATTACHEDFOAM SEAL
A. Bracket Attached to Amana/Trane Metal Sleeve
B. Foam Baffles Attached on Outdoor Coil Tube Sheets
BASEPANNOTCHLOCATION (2)
GASKETS(2 EACH SIDE)
C. Gaskets Installed onto Basepan
Refer to the installation instructions for complete in-stallation procedures.IMPORTANT: Be sure that the foam baffles makea good seal between the grille and outdoor coil tubesheets. Improper installation of the foam baffles orneglecting to install them can result in condenser(outdoor) air recirculation. This will degrade theunit’s performance and shorten product life. Do notignore this step.Carrier does not assume responsi-bility for costs or damages resulting from misappli-cation of foam baffles.
21
DIMENSION DRAWINGS AND INSTALLATIONDATA — NEW CONSTRUCTION
NOTES:1. Sleeve can be flush mounted to floor, but front panel may
have to be notched to accommodate service cord (exceptwhen subbase is used).
2. Remote control models 52S series ‘‘RC’’ units uselow voltage connections (24 volt) qualified with aHH01AD045 manual changeover heat/cool thermostat.(Subbase included.)
52S Dimension Drawing
Proper building practices must be used when construct-ing a wall opening to support a PTAC wall sleeve andchassis.
If practices are unknown, consult your local architector building contractor.Installed wall sleeve must be level from side to sideand front to back.
TYPICAL WALL INSTALLATION
22
EXTENSIONMOUNTINGBRACKET
SIDE
0'-4 3/8"(112)
AIRFLOW
0'-6 7/8"(175)
SEENOTE
OUTSIDEWALL
AIRFLOW
INSIDEWALL
LATERAL DUCT EXTENSIONWALL OPENING
0'-7 1/8"(181)
0'-3 3/4"(95)
WALLREGISTER
ACCESSORY LATERALDUCT EXTENSION(LEFT OR RIGHT)
0'- 3 1/2" (89)
ACCESSORY LATERALDUCT ADAPTER
REVERSIBLEAIR GRILLE
2'-6 3/8"(772)
ADJUSTABLEAIR DEFLECTOR
END CAP
ALTERNATEEXTENSION POSITION
INSIDEWALL
AIRFLOW
2'-11 7/8"(911) MAX.
JUNCTION BOXACCESSORY
HARD WIRE KIT
10 1/4"(260)
3'-11 1/4"(1200) MAX.
7 1/2"
NOTE: For all applications with an accessory lateral duct,sleeve must extend into the room a minimum of one inch.
52S Lateral Duct
18" MINIMUM DISTANCE FROMSLEEVE TO BUILDING WALLS,
SHRUBS, WALKWAY, etc.
52S Outdoor Discharge Air Circulation
Blocking outdoor discharge air could cause prematurefailure of unit.
23
DIMENSION DRAWINGS AND INSTALLATIONDATA — NEW CONSTRUCTION (cont)
Wall Sleeve
Minimum Wall Sleeve Opening
Wall Sleeve Mounting Dimensions for Standard andAccessory Grilles
Wall Sleeve Mounting
24
NOTES:1. For all applications with an accessory subbase:
• Wall sleeve must extend 4 in. minimum into the roomand 31⁄4 in. minimum above the floor.
• Subbase height is adjustable from 31⁄4 in. minimum to51⁄2 in. maximum above floor (including carpeting).
Refer to wall sleeve installation instructions.2. Accessory subbase is required for applications where:
• Wall sleeve extends 4 or more inches into the room.• Wall thickness is less than 2 inches.
52S With Subbase
Accessory Subbase Electrical Connections
25
DIMENSION DRAWINGS AND INSTALLATIONDATA — NEW CONSTRUCTION (cont)
NOTES:1. Sleeve may be flush mounted to floor, but front panel may
have to be notched to accommodate service cord.2. If more than 4 in. of sleeve projects into room, an acces-
sory subbase must be used for support.3. For walls 2 in. thick or less, an accessory subbase must
be used for support.
Typical Wall Installation
NOTES:1. To permit outdoor grille to be attached to and supported
by unit sleeve, fabricate a sleeve extension so unit sleeveand baffles can reach outdoor grille. Be sure to provideflashing for proper condenser runoff to avoid water dam-age to room interior. Internal or external drain system maybe required.
2. Baffles may be part of the sleeve extension or fixed di-rectly to condenser coil tube sheets.
3. Caulk all joints between sleeve or baffles and opening inwall.
4. If grille is used on outdoor wall opening, do not install anadditional outdoor grille on unit sleeve.
Typical Deep Wall Installation
26
NOTES:1. Unit sleeve and sleeve extension (field fabricated) should
be connected before installing in wall opening.2. Sleeve extension is water bearing. It must be watertight
when installed against unit sleeve. Use quality grade seal-ant on all butting flanges. Attach both sections with boltsand nuts or self-tapping screws installed from unit sleeveto extension. Cut drain slots in front and rear flanges ofextension to line up with drain openings in unit sleeve.
3. Install 2 center baffles inside sleeve extension to pre-vent recirculation of outdoor air circuit.
4. Leave 3⁄8-in. roomside projection of extension and 1⁄4-in.outdoor projection of sleeve. This allows for unit casingclearance to finished wall plus ample edging to applyweather sealant between unit sleeve/extension assem-bly and wall opening.
5. Paint sleeve extension and seal corner and lap joints;clear all drain holes of excess sealant, paint, etc., to per-mit free drainage.
6. Install quality flashing under unit sleeve and extensionusing quality sealant between flashing and wall.
7. Install unit casing/extension assembly following stand-ard practices. Seal assembly to wall on all 4 sides, in-doors and outdoors.
8. Make provision for a condensate drain extension tubefor routing excess condensate from the wall sleeve throughthe sleeve extension to the building exterior.
9. Attach grille to the outside of the sleeve extension(using field-supplied fasteners).
10. Seal any gaps between grille and sleeve extension onall sides.
Wall Sleeve and Sleeve Extension (All Models; Field Fabricated)
Typical Curtain Wall Installation (All Models)
27
PRODUCT DATAPERFORMANCE AND ELECTRICAL DATA
MODEL 52SQ (230/208V)
MODELNUMBER
CAPACITY* (Btuh)HEATER
kW EER COP†VOLTAGERANGE(Volts)
AMPS WATTS
CoolingHeating
Cooling Heating** Cooling HeatingRev. Cyc. Electric
37 4.3 13052SQC314---3 20 19.4 B52SQC514---3 30 28.0 C
LEGENDEER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310/380-93.†Coefficient of Performance (COP) at 47 F outdoor ambient temperature.**Electric resistance heater power and fan motor power.
RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE 230/208OUTLET RATED VOLTS/AMPS 250/15 250/20 250/30
NEMA CONFIGURATION 6-15R 6-20R 6-30RTIME DELAY FUSE OR HACRCIRCUIT BREAKER (AMPS) 15 20* 30
HEATER (KILOWATTS) 2.3 3.4 5.0
LEGENDHACR — Heating, Air Conditioning, and RefrigerationNEMA — National Electrical Manufacturers Association*May be used for 15-amp applications if fused for 15 amps.
28
PERFORMANCE AND ELECTRICAL DATA
MODEL 52SQ (265V)
MODELNUMBER
CAPACITY* (Btuh)HEATER
kW EER COP† VOLTRANGE
AMPS WATTS
CoolingHeating
Cooling Heating** Cooling HeatingRev. Cycle Electric
37 4.20 13052SQC314---4 20 16.8 B52SQC514---4 25 24.5 C
LEGENDEER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310/380-93.†Coefficient of Performance (COP) at 47 F outdoor ambient temperature.**Electric resistance heater power and fan motor power.††All 265V units require either the Accessory Hard-Wire Kit or the AccessoryCord-Connected Kit for installation. Use of the Accessory Cord-ConnectedKit requires the installation of the Subbase along with a field-supplied recep-tacle. Receptacle configurations of the Accessory Cord-Connected Kit areshown at right.
RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE 265OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
NEMA CONFIGURATION 6-15R 6-20R 6-30RTIME DELAY FUSE OR HACRCIRCUIT BREAKER (AMPS) 15 20* 30
HEATER (KILOWATTS) 2.3 3.4 5.0
LEGENDHACR — Heating, Air Conditioning, and RefrigerationNEMA — National Electrical Manufacturers Association*May be used for 15-amp applications if fused for 15 amps.
35 4.7 13052SEC314---4 20 16.8 B52SEC514---4 25 24.4 C
LEGENDEER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310/380-93.†Electric resistance heater power and fan motor power.**All 265V units require either the Accessory Hard-Wire Kit or the AccessoryCord-Connected Kit for installation. Use of the Accessory Cord-ConnectedKit requires the installation of the Subbase along with a field-supplied recep-tacle. Receptacle configurations of the Accessory Cord-Connected Kit areshown at right.
RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE 265OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
EER — Energy Efficiency Ratio*Rated in accordance with ARI Standard 310/380-93.†All 265-v units require Accessory Hard-Wire Kit or theAccessory Cord-Connected Kit for installation. Use of theAccessory Cord-Connected Kit requires the installation ofthe Subbase, along with a field-supplied receptacle. Recep-tacle configurations of the Accessory Cord-Connected Kitare shown at right.
RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATEVOLTAGE 265
OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
OUTLET BLADE CONFIGURATION
A B C
FEMALE RECEPTACLEMFG. PART NO.HubbellEagle
—834B-BOX
—834B-BOX
9315—
TIME-DELAY FUSE OR HACRCIRCUIT BREAKER (AMPS) 15 20 30
HACR — Heating, Air Conditioning, and Refrigeration
33
PRODUCT DATA (cont)EXPANDED RATINGS DATA
COOLING PERFORMANCE — 52SC, SE, SQ 7000 AND 9000 BTU MODELS(230 AND 265 V)
ALL 7000 NOMINAL BTUH MODELSEvaporator entering air temp. — 80 F Evap. air — 280 CFM
INDOOR SOUND DATAThe table below indicates the approximate indoor soundlevel of a 52S unit. Tests were conducted in theCarrier Sound Testing Laboratory according to ARI(Air Conditioning and Refrigeration Institute) NoiseRating Standard 300 for non-ducted indoor air-conditioning equipment.
Accessory or Optional WiringFactory WiringTo Indicate Common Potential OnlyNot to Represent WireNOTES:
1. Recommended for use on grounded power supply only.2. Compressor and fan motor thermally protected.3. Use copper conductors only.4. All wiring must conform with NEC (National Electrical Code)
and local codes.5. Dashed lines indicate components when used.
LEGEND
52SQ — Typical Wiring Schematic For Standard Units
37
WIRING DIAGRAMS (cont)
CAP — CapacitorCOMP — CompressorCR — Cooling RelayEQUIPGND
— Equipment Ground
FM — Fan MotorFR — Fan RelayHR — Heating RelayIFT — Indoor Frost ThermostatL — Power Supply LineOFT — Outdoor Frost ThermostatOL — Overload
52SQ — Typical Wiring Schematic For Remote Control Units
LEGEND
NOTES:1. Recommended for use on grounded power supply only.2. Compressor and fan motor thermally protected.3. Use copper conductors only.4. All wiring must conform with NEC (National Electrical Code)
and local codes.
5. Dashed lines indicate components when used.6. Control center uses thermostat part no. HH01AD045 or
equivalent.7. Field control wire suitable for NEC class 2 control circuit,
at 24 volts.
Component Connection(Unmarked)
Terminal Board Connection
Field Control WiringAccessory or Optional WiringFactory WiringTo Indicate CommonPotential Only Not toRepresent Wire
38
CAP — CapacitorCOMP — CompressorFCS — Fan Cycle SwitchFM — Fan MotorHTR — HeaterIT — Indoor ThermostatL — Power Supply LineOL — OverloadPL — PlugPLS — Primary Limit SwitchSLS — Secondary Limit Switch
ST — Start ThermistorSW — Selector Switch
Component Connection (Marked)
Component Connection (Unmarked)
Accessory or Optional WiringFactory WiringTo Indicate Common Potential OnlyNot to Represent Wire
52SE — Typical Wiring Schematic For Standard Units
LEGEND
NOTES:1. Recommended for use on grounded power supply only.2. Compressor and fan motor thermally protected.3. Use copper conductors only.4. All wiring must conform with NEC (National Electrical Code)
and local codes.5. Dashed lines indicate components when used.
39
WIRING DIAGRAMS (cont)
CAP — CapacitorCOMP — CompressorCR — Cooling RelayEQUIPGND
— Equipment Ground
FM — Fan MotorFR — Fan RelayHR — Heating RelayIFT — Indoor Frost ThermostatL — Power Supply LineOL — OverloadPL — PlugPLS — Primary Limit SwitchSLS — Secondary Limit SwitchSSS — Speed Selector SwitchST — Start Thermistor
TB — Terminal BoardTRANS — Transformer
Component Connection (Marked)
Component Connection (Unmarked)
Terminal Board Connection
Field Ground WiringField Control WiringAccessory or Optional WiringFactory WiringTo Indicate Common Potential OnlyNot to Represent Wire
52SE — Typical Wiring Schematic For Remote Control Units
LEGEND
NOTES:1. Recommended for use on grounded power supply only.2. Compressor and fan motor thermally protected.3. Use copper conductors only.4. All wiring must conform with NEC (National Electrical Code) and
local codes.
5. Dashed lines indicate components when used.6. Control center uses thermostat part no. HH01AD045 or equivalent.7. Field control wire suitable for NEC class 2 control circuit, at
24 volts.
40
PTAC #1
WG WG WG
PTAC #NPTAC #2
FRONT DESK SWITCH PANEL
24-VTRANSFORMER
(SEE NOTE)
LEGEND
AWG — American Wire GagePTAC — Packaged Terminal Air Conditioner
NOTES:1. To size transformer, use the following equation:
Quantity of PTAC units x 12 va = Transformer Size (va)Example: 110 PTAC Units x 12 va = 1320 va Transformer
2. Following are recommended wire sizes:AWG WIRE SIZE NO. MAXIMUM LENGTH (ft)
24 40022 60020 90018 150016 2000
Typical Wiring Schematic for Energy Management Kit
41
GUIDE SPECIFICATIONS
PACKAGED TERMINAL COOLING UNITWITH HEAT PUMP OR ELECTRIC HEATING
HVAC Guide SpecificationsSize Range: Cooling: 7,100 to 13,700 Btuh
Heating: 6,100 to 11,000 Btuh Heat Pump6,400 to 17,000 Btuh Electric
Carrier Model Numbers: 52SCCooling OnlyUnit
52SE Unit withElectric Heat
52SQ Heat Pump
Part 1 — General1.01 SYSTEM DESCRIPTION
Single piece, thru-the-wall electrically controlled unitusing hermetic rotary compressor for cooling andheat pump or electric resistance heat, as shown onthe contract drawings.
1.02 QUALITY ASSURANCEUnit shall be rated in accordance with ARI Stand-ard 310/380-93 and certified by UL and UL, Canada.
1.03 DELIVERY, STORAGE, AND HANDLINGUnit shall be stored and handled per manufactur-er’s recommendations.
Part 2 — Products2.01 EQUIPMENTA. General:
Factory-assembled, single-piece heating and/or cool-ing unit. Contained within the unit enclosure shallbe compressor, coils, fans and fan motor, heatingmeans, controls, all wiring and piping, and a fullrefrigerant charge (R-22).
B. Front Panel (supplied with unit) and Wall Sleeve:Wall sleeve and front panel shall be of plastic ma-terial. Front panel to have louvers in front surface.
C. Fans and Motor:1. Evaporator (indoor) fan shall be a single-inlet
squirrel cage blower with a corrosion-resistantfinish, discharging air upwards. Fan shall be dy-namically balanced.
2. Condenser (outdoor) fan shall be a propeller typewith corrosion-resistant finish, discharging air outthe rear of the unit, and shall be dynamicallybalanced.
3. Motor shall be totally enclosed, permanently lu-bricated, and multiple speed.
D. Compressor:The compressor shall be fully hermetic with inter-nal and external vibration isolation.
E. Coils:The coils shall have aluminum plate fins mechani-cally bonded to seamless copper tubes internallyenhanced (grooved) with all joints brazed.
F. Refrigerant Components:All piping, compressor, and expansion devices shallbe included.
G. Controls and Safeties:1. Controls shall consist of pushbutton OFF/FAN/
HEAT/COOL adjustable thermostat with upperand lower limits, VENTOPEN/CLOSE, and FANCYCLE switches. Additional controls for heatpumps include outdoor coil defrost thermostat.
2. Safeties shall consist of automatic reset over-temperature and overcurrent protection forcom-pressor,inherent, automatic reset over-temperatureprotection forfan motor; two over-temperatureprotectors forheater.
H. Operating Characteristics:Unit shall be capable of starting and running at 115 Fambient outdoor temperature per maximum loadcriteria ofARI Standard 310. Compressor with stand-ard controls shall be capable of operation down to25 F ambient outdoor temperature for heat pumpand 55 F ambient outdoor temperature for cooling.
I. Electrical Requirements:230/208-Volt: Shall be prewired with one plug touse with appropriate wall receptacle as specifiedon unit nameplate.265-Volt: Shall be hard-wired or cord-connectedthrough subbase.
J. Filter:1. One-piece washable type that filters supply air.2. One-piece washable type filter in vent door fil-
ters outdoor air.K. Special Features:
Certain standard features are not applicable whenthe features designated are specified. Contactyour local Carrier Sales Office for amendingspecifications.1. Factory-installed electric heater for use with
heat pump or heat/cool units2. RC—Remote control permits unit control from
remote thermostat3. CP — Corrosion protection provides for extra
paint on control box, partition top cover andexterior coil
4. Standard grille (aluminum)5. Architectural grille (plastic or aluminum)6. Hard-wire kit7. Drain kit8. Subbase9. Wall sleeve10. Lateral duct kit11. Energy management accessory kit12. Cord-connection kit (265 V)
42
TYPICALWARRANTY
FULL ONE-YEAR WARRANTY - During the first year after purchase, CARRIER will,through its authorized independent servicing dealers or service stations*, and free of chargeto the users or subsequent users, repair or replace any parts which are defective in mate-rial or workmanship. The replacement part can be a new or remanufactured part as provid-ed at CARRIER’S sole option.
FULL EXTENDED FOUR-YEAR WARRANTY ON SEALED REFRIGERATIONSYSTEM ONLY - During the second through fifth years after date of original purchase,CARRIER will, through its authorized independent servicing dealers or service stations, andfree of charge to the users or subsequent users, repair or replace the compressor, con-denser, evaporator or connecting tubing if defective in material or workmanship. Thereplacement part can be a new or remanufactured part as provided at CARRIER’S soleoption.
LIMITED EXTENDED FOUR-YEAR WARRANTY ON NON-SEALED REFRIGERATIONSYSTEM ONLY - During the second through fifth years after date of original purchase,CARRIER will, through its authorized independent servicing dealers or service stations, andfree of charge to the users or subsequent users, repair or replace any non-sealed systempart (motor, solenoid, thermistor, thermostat, relays, switch, capacitor, overload, drain valve,bulb heater, fan, stator) if defective in material or workmanship. The replacement part canbe a new or remanufactured part as provided at CARRIER’S sole option. THIS LIMITEDWARRANTY DOES NOT INCLUDE LABOR, user is responsible for labor, including cost ofdiagnosis of problem, removal and transportation of the air conditioner to and from the serv-ice center, and reinstallation charges necessary to accomplish repair.
LIMITATION OF WARRANTIES - ALL IMPLIED WARRANTIES (INCLUDING IMPLIEDWARRANTIES OF MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THEPERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN AND APPLIES. SOMESTATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTYLASTS, SO THAT THE ABOVE LIMITATION MAY NOT APPLY TO YOU. THE EXPRESSEDWARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BEALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHERPERSON WHATSOEVER.
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DUR-ING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW ORREMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAININGPERIOD OF THIS WARRANTY.
CARRIER WILL NOT BE RESPONSIBLE FOR:
1. Damage due to failure to perform maintenance as outlined in the owner’s manual.
2. Instructions on method of control and use of air conditioning unit after initial installation.
3. Damage or repairs needed as consequence of faulty installation or application. This isthe responsibility of the installer.
4. Failure to start due to voltage conditions, blown fuses, open circuit breakers or anyother damage due to the inadequacy or interruption of electrical services.
5. Damage or repairs needed as consequence of any misapplication, abuse unauthorizedalteration, improper servicing or operation.
6. Damage as a result of floods, winds, fires, lightning, accidents, or other conditionsbeyond the control of CARRIER.
7. Damage as a result of corrosive environment (corrosive environment defined as instal-lation or operation of the product within one mile of a seawater body). EXCEPTION TOCORROSIVE ENVIRONMENT IN ABOVE PARAGRAPH - Packaged terminal units (52Series) built with corrosion protection are exempt from the exclusion - “CorrosiveEnvironment.” The model number is identified on the nameplate with a CP suffix.
8. Reimbursement for replacement parts or or repair services which are not supplied ordesignated by CARRIER and which are specifically covered under this warranty.
9. CARRIER products installed outside the continental U.S.A., Alaska, Hawaii andCanada.
10. Shipping damage or damage as a result of transporting the unit. This is theresponsibility of the selling dealer or servicing dealer.
11. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIALDAMAGE OF ANY NATURE WHATSOEVER. Some states do not allow the exclusionor limitation of incidental or consequential damages, so that above limitation or exclu-sion may not apply to you.
NOTE: Service and Maintenance items excluded in this warranty may be covered by aseparate service agreement through the seller at the time of purchase.
* Authorized independent dealers or service stations are registered with Carrier Air Conditioning thru its distributor organization.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
1. CHECK THE THINGS YOU CAN DO YOURSELF.These include being sure that air conditioner is pluggedfirmly in an appropriate receptacle, checking the fuse orcircuit breaker and ensuring its replacement or resetting,if necessary, and reading the instruction book to ensurethat all controls are set properly. By doing this you cansave money. Many unnecessary service calls result inthe serviceman doing what the owner can do for him orherself.
2. CONTACT YOUR DEALER OR THE CARRIERAUTHORIZED SERVICE CENTER HE RECOM-MENDS. They have been set up to handle the greatmajority of all possible service problems. The quickest,surest and best way to get your air conditioner back inservice is to use this step before proceeding further.
3. CONTACT THE CARRIER DISTRIBUTOR SERVICINGYOUR AREA. Your dealer knows the distributor’s nameor you can consult your yellow pages.
4. CONTACT CARRIER IF A SATISFACTORY SOLUTIONIS NOT REACHED IN STEP 2 AND 3.
Carrier Air ConditioningConsumer Relations DepartmentCarrier Parkway, P.O. Box 4808Syracuse, New York 13221Telephone: 1-800 Carrier (227-7437)From Canada 1-315-432-7885
IF YOUR AIR CONDITIONER DOES NOT WORK, FOLLOW THESE STEPS IN ORDER: