® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: QS Sensor Module QSM Sensor Interfaces 369242k 1 12.22.15 QS Sensor Module The QS Sensor Module (QSM) is a ceiling-mounted device that integrates LutronR wireless and wired sensors and controls through the QS communication link to Energi Savr NodeTM (ESN) units, GRAFIK EyeR QS control units, QuantumR systems, SivoiaR QS shades / draperies, and myRoomT control modules. Features • Uses Clear ConnectR RF Technology for communication with Radio Powr SavrTM occupancy sensors, Radio Powr Savr T daylight sensors, and PicoR wireless controllers. • QSM connects to four LutronR wired sensors or controls—occupancy sensors, daylight sensors, EcoSystemR infrared (IR) receivers, or EcoSystemR wallstations. Does not apply to wireless only models. • Powered by the QS link—no line voltage connections are required. • Contact Lutron for compatibility details with the QuantumR system. • Compatible with the entire ESN product family: — Allows LutronR wired occupancy sensors, daylight sensors, EcoSystemR wall stations, EcoSystemR IR receivers, PicoR wireless controllers, Radio Powr Savr T wireless occupancy sensors and daylight sensors to control ESN units. • Compatible with GRAFIK EyeR QS control units. — GRAFIK EyeR QS control unit models starting with QSGR. — Allows LutronR wired or Radio Powr Savr T wireless occupancy sensors and daylight sensors linked to a QSM to control the GRAFIK EyeR QS control unit. — Contact Lutron for compatibility with PicoR wireless controllers, EcoSystemR wallstations, and EcoSystemR infrared (IR) receivers. • Compatible with SivoiaR QS shades / draperies. — Allows PicoR wireless controllers to control SivoiaR QS shades / draperies (QSM models with wireless inputs only). • Compatible with myRoomT power modules. — Allows Lutron wired & wireless occupancy sensors to control power modules. — Allows PicoR wireless controls to control power modules. System Example QS link Control Power 120-277 V~ Emergency Contact Closure Input Programmable Contact Closure Input Wireless Communication Wired Daylight Sensors (up to 4) 2 Wired Daylight Sensors (up to 4) 1,2 EcoSystemR Digital Links (up to 64 ballasts each) Wired Occupancy Sensors (up to 4) Wired Occupancy Sensors (up to 4) 1 Wired EcoSystemR Wallstation or IR receivers (up to 4) Wired EcoSystemR Wallstation or IR receivers (up to 4) 1 QSM IR Transmitter IR Transmitter OR OR OR OR seeTouchR QS Wallstation Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM) Radio Powr SavrT Daylight Sensor (up to 10 per QSM) Pico® Wireless Controller (up to 10 per QSM) Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. Notes: 1 Up to 4 wired inputs total (of any type). 2 Up to 16 wired daylight sensors total per EcoSystemR link.
6
Embed
QS Sensor Module (QSM) SPEC 369242 · QS Sensor Module QSM Sensor Interaces 369242k 1 12.22.15 QS Sensor Module The QS Sensor Module (QSM) is a ceiling-mounted device that integrates
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 1 12.22.15
QS Sensor ModuleThe QS Sensor Module (QSM) is a ceiling-mounted device that integrates LutronR wireless and wired sensors and controls through the QS communication link to Energi Savr NodeTM (ESN) units, GRAFIK EyeR QS control units, QuantumR systems, SivoiaR QS shades / draperies, and myRoomT control modules.
Features•UsesClearConnectR RF Technology for communication
with Radio Powr SavrTM occupancy sensors, Radio Powr SavrT daylight sensors, and PicoR wireless controllers.
•QSMconnectstofourLutronR wired sensors or controls—occupancy sensors, daylight sensors, EcoSystemR infrared (IR) receivers, or EcoSystemR wallstations. Does not apply to wireless only models.
sensors, EcoSystemR wall stations, EcoSystemR IR receivers, PicoR wireless controllers, Radio Powr SavrT wireless occupancy sensors and daylight sensors to control ESN units.
•CompatiblewithGRAFIK EyeR QS control units. — GRAFIK EyeR QS control unit models starting
with QSGR.
— Allows LutronR wired or Radio Powr SavrT wireless occupancy sensors and daylight sensors linked to a QSM to control the GRAFIK EyeR QS control unit.
—ContactLutronforcompatibilitywithPicoR wireless controllers, EcoSystemR wallstations, and EcoSystemR infrared (IR) receivers.
•CompatiblewithSivoiaR QS shades / draperies. — Allows PicoR wireless controllers to control SivoiaR QS
shades / draperies (QSM models with wireless inputs only).
•CompatiblewithmyRoomT power modules. — Allows Lutron wired & wireless occupancy sensors to
control power modules. — Allows PicoR wireless controls to control power
modules.
System Example
LUTRON
LUTRON
QS link
ControlPower120-277 V~
Emergency Contact Closure
Input
Programmable Contact Closure Input
Wireless Communication
Wired Daylight Sensors (up to 4) 2
Wired Daylight Sensors (up to 4) 1,2
EcoSystemR Digital Links (upto64ballastseach)
Wired Occupancy Sensors (up to 4)
Wired Occupancy Sensors (up to 4) 1
Wired EcoSystemR Wallstation or IR receivers (up to 4)
Wired EcoSystemR Wallstation or IR receivers (up to 4) 1
QSM
IR Transmitter
IR TransmitterOR OR
OR OR
seeTouchR QS Wallstation
Radio Powr SavrTM Occupancy Sensor (up to 10 per QSM)
Radio Powr SavrT Daylight Sensor (up to 10 per QSM)
Pico® Wireless Controller(upto10 per QSM)
Apple, iPhone, and iPod touch are trademarks of AppleInc.,registeredintheU.S.andothercountries.
max100mA(modelswithoutwiredinput)•PowerDrawUnits:(PDU) RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronR P/N 369405) for information concerning PDUsontheQSLink.UseonlyLutronR approved power sources.
•10-yearpowerfailurememory:restoressettingsand programming after power interruption.
Regulatory•LutronR Quality Systems registered to ISO 9001.2008.
•LutronR Radio Powr SavrTM Occupancy sensor (up to 10)
•LutronR Radio Powr SavrT daylight sensor (up to 10)•LutronR PicoR wireless controllers (up to 10)
Wired Inputs
•Thereare4universalwiredinputs.Eachinputcanaccept one of the following:- LutronR EcoSystemR wallstations- LutronR occupancy sensors (LOS- series)- LutronR daylightsensors(EC-DIR-series)- LutronR EcoSystemRinfrared(IR)receivers(EC-IR,EC-DIR-series)
- LutronR Wired PicoR Controls•UseofboththeinfraredreceiveranddaylightsensorontheEC-DIR-seriessensorsisconsideredtwowired inputs on a QSM
•Maximumwiringdistance=150ft(46m)•Onlywired(LOS-series)andwirelessoccupancysensorsmaybeusedinmyRoomT; no EcosystemR wallstations, daylight sensors, EcosystemR IR receivers or wired PicoR controls
QS Link Limits
•The QS link can have up to 100 devices.•EachQSMcountsas1devicetowardsthe
the QS link. •WiredsensorsaddtothePDUdrawofaQSM.RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronR P/N 369405) for information concerningPDUs.
Mechanical Dimensions (All Models)Front View Side View Back View
(QSM2-4W-Cshown)
Mounted (-C Models) Mounted (-J Models)
1.17 in (30 mm)
Ceilingthicknessrangefor-CmodelsMin 0.30 in (8 mm) to Max1.20in(30mm)
Ceiling Ceiling
4.04 in (103 mm)
UseappropriateMudRingforceilingtilethickness
UseMudRingwithholespacingshownbelow.(Mud Ring not included with any QSM models)
Ceiling Ceiling
2.75 in (70 mm)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 5 12.22.15
Wiring: QS Link and Wired Inputs1
Input 11,2,3
Daylight sensor
EcoSystemR infrared (IR) receiver
Occupancy sensor
EcoSystemR wallstation or PicoRWiredControls
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2)
Lutron®CableStandard:C-CBL-522S-WH-1
Plenum:C-PCBL-522S-CLMax.WiredInputwire
length 150 ft (46 m)per input
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2) Lutron®CableStandard:C-CBL-522S-WH-1Plenum:C-PCBL-522S-CLMax.WiredInputwire length 150 ft (46 m)per input
22 AWG to 14 AWG (0.5 mm2 to 2.0 mm2) Max.QSlinkwire length 2000 ft (610 m)
Input 31,2
Input 21,2
QS Link
Input 41,2
Com
mon
V
+
MUX
MUX
Red
+20
–20V
+20
–20V
+20
–20V
+20
–20V
Bla
ckCOM–Com
mon
COM–Com
mon
COM–Com
mon
COM–Com
mon
Yello
wS1 –Signa
lS2–Signa
l
S4–Signa
lS3–Signa
lB
lue
or G
ray
Bla
ck
Red
Red
Red
Bla
ck
Bla
ck
Whi
te
Whi
te
1 Only on QSM models with wired inputs.2 Note: Forreferenceonly.Eachinputisuniversalandcanacceptanyoftheinputsshownabove.3OnlydaylightsensorsignalconnectedtoQSMshownabove.UseofIRsignalcountsasan
additional input on the QSM.
Back View (QSM2-4W-Cshown)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242k 6 12.22.15
Wiring: Device PowerSingle QSM powered by an ESN unit
Multiple QSMs powered by an ESN unit and a QS Link Power SupplyNote:AQSLinkPowerSupplymaybenecessaryifPDUsrequiredbyQSMsexceedavailablePDUsfromthedevice supplying power.
ESN unit
ESN unit
QSM QSM
COM
COM
COM
COM
COM
MUX
MUX
MUX
MUX
MUX
V+
V+
V+
V+
MUX
MUX
MUX
MUX
MUX
ESN unit
QSM A
The ESN unit powers QSM A; no terminal 2 connection betweenQSMAandQSLink Power Supply
The QS Link Power Supply powersQSMBandC;
QS Link Power Supply
QSM B
QSMC
MUXand_ occupy terminals 2 and 3 on the QS Link Power Supply.