DE1-1 Loadcentres and Circuit Breakers DE1 LOAD CENTRES 04/16 Square D QO ® Loadcentres and Circuit Breakers Selection Guide Contents Description Page General Information • Product Illustrations/Features 3-4 QO ® Breakers • QO ® Standard Breakers and Tandem Circuit Breakers. 5 • QO ® Special Breakers (QO-CAFI, QO-DF , QO-GFI, QO-EPD, QO-HID, QO-AFI, QO-K, and QO-HM) 6 • Circuit Breaker Factory Installed Accessories 7 • Circuit Breaker Wire Sizes 7 QO ® Loadcentres • QO ® Main Lugs Loadcentres - Type 1 Indoor 8 • QO ® 'Stand Alone' Generator Panels 8 • QO ® Combination SE 'all-in-one' Generator Panels 8 • QO ® Main Breaker Loadcentres - Type 1 Indoor 9 • QO ® Main Lugs/Main Breaker Loadcentres - Type 3R Weatherproof • QO ® Plug-on Neutral Loadcentres 10 11 • QO ® Recreational Vehicle Park (ServicePak® Panels) and Mobile Home and Trailer Loadcentres 12 Accessories • QO ® Loadcentre and Circuit Breaker Accessories 13 • QO ® single phase loadcentre field installed neutral extension kits 14 • Secondary Surge Suppressors and Surge Arresters 15 Dimensional Information • Enclosure Dimensions 16 HomeLine™ Loadcentres and Circuit Breakers Selection Guide General Information • Product Illustrations / Features 17-20 • Nomenclature Charts 21 HomeLine Breakers • Standard and Main Circuit Breakers 22 • Tandem and Quad Circuit Breakersr 23 • CAFI and DF 23 • GFI, AFCI 24 • Breaker Accessories 24 HomeLine Loadcentres • Indoor Single Phase Main Lug & Main Circuit Breaker Loadcentres 25 • Outdoor Single Phase Main Lug & Main Circuit Breaker Loadcentres 26 • HomeLine Fusible Loadcentre Inserts 27 • HomeLine Loadcentre Accessories 29 Technical Information • Wiring Diagrams 32-33 • Indoor Loadcentre Dimensions and Knockouts 34 • Outdoor Loadcentre Dimensions and Knockouts 35
44
Embed
QO - Mayer Electric – QO290VH QO390VH 100 ... † For more information consult Schneider Electric. Note: QO GFI, EPD, AFI, CAFI, and DF cannot be backfed. Two Pole QO-GFI One Pole
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Loadcentres and Circuit Breakers
DE
1L
OA
DC
EN
TR
ES
DE1_p01-2_TOC.fm Page 1 Monday, April 25, 2016 2:35 PM
Square D QO® Loadcentres and Circuit Breakers Selection Guide
Contents Description Page
General Information• Product Illustrations/Features 3-4
QO® Breakers• QO® Standard Breakers and Tandem Circuit Breakers. 5
DE1_p03-16.fm Page 4 Monday, April 25, 2016 2:28 PM
DE1-5
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
QO® Standard and Tandem Circuit Breakers
10-30 ampere breakers are suitable for use with 60°C or 75°C conductors. 35-125 ampere breakers are suitable for use with 75°C conductors.‡ High magnetic trip breakers are recommended for applications where high initial inrush current may occur.▲ SWD (switching duty) rated. Suitable for switching 120Vac fluorescent lighting loads.◆ HACR type for use with air conditioning, heating and refrigeration equipment having motor group combinations and marked for use with HACR type
circuit breakers. HACR labelled one pole QO breakers not stocked. Order Only. Add suffix -5385.▼ Requires four spaces (#1-300 kcmil Al/Cu). Not suitable for use in 3-phase panel. Use only in single phase panel rated 150A or greater.❒ CSA Listed for use ahead of QO, QO-GFI, QO-EPD, QOT and QO-PL 10,000 AIR circuit breakers to permit their application at 22,000A fault level.
Order Two QO1515 or QO2020 Circuit Breakers and Handle Tie Catalogue # QOTHT.
Application Information
• VISI-TRIP indication on all QO breakers.• QO, VISI-TRIP and QWIK-GARD are registered trademarks of Square D.• For more information consult Schneider Electric.
QWIK-GARD® circuit breakers provide overload and short circuit protection, combined with Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will trip when a fault current to ground is 6 milliamperes or more, for people protection. Do not connect to more than 250 feet of load conductor for the total one-way run to prevent nuisance tripping.
QO-KKey operated QO circuit breakers are available in single pole construction and can be mounted in any single pole space which will accept a standard QO. These circuit breakers can be turned ON or OFF or to RESET with a special key (Catalogue Number QOK10) included with the circuit breaker.
AmpereRating
One Pole 120Vac10,000 AIR
10 QO110K15 QO115K20 QO120K30 QO130K
QO-HM QO circuit breaker with high magnetics to withstand higher inrush currents than standard QO breaker.
AmpereRating
One Pole 120Vac10,000 AIR
15 QO115HM20 QO120HM
QO Combination Arc-Fault Interrupter (CAFI)QO Combination Arc-Fault Interrupter (CAFI) provides overload and short circuit protection, plus both series and parallel type arc protection as required in 2015 CEC. Integrated with Time Saver diagnostics, QO CAFI breaker improves circuit troubleshooting at the touch of a button.,
Circuit Breaker Type
AmpereRating
1P 120 Vac10K AIR1 Space Required
1P 120 Vac22K AIR1 Space
Required
2P 120/240 Vac10K AIR2 Space Required
2P 120/240 Vac22K AIR2 Space Required
QO Pigtail Neutral CAFI
15 QO115CAFI QO115VHCAFI QO215CAFI* QO215VHCAFI*
20 QO120CAFI QO120VHCAFI QO220CAFI* QO220VHCAFI*
QO Plug-on Neutral CAFI
15 QO115PCAFI QO115VHPCAFI
20 QO120PCAFI QO120VHPCAFI
* Rated for 120/240 ~60Hz, not for 208Y/120V
QO Dual Function Circuit BreakerQO Dual Function (DF) breaker provides both combination arc-fault and ground-fault (5mA classA) protection in a single compact device. Integrated with Plug-on Neutral and Time Saver Diagnostics features, QO DF breaker offers maximum circuit protection and installation flexibility.
Circuit Breaker Type AmpereRating
1P 120 Vac 10k AIR1 Space Required
1P 120 Vac 22k AIR1 Space Required
Catalog Number Catalog Number
QO Dual Function Circuit Breaker with Pigtail Neutral
15 QO115DF QO115VHDF
20 QO120DF QO120VHDF
QO Plug-on Neutral Dual Function Circuit Breaker
15 QO115PDF QO115VHPDF
20 QO120PDF QO120VHPDF
QO-HID QO-HID Circuit Breakers - For Use on High Intensity Discharge Lighting Systems
HID circuit breakers are for use on circuits feeding fluorescent and High Intensity Discharge (HID) lighting systems such as mercury vapour, metal halide, or high pressure sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
• VISI-TRIP indication on all QO breakers.• QO, VISI-TRIP and QWIK-GARD are registered trademarks of Square D.• For more information consult Schneider Electric.
Note:QO GFI, EPD, AFI, CAFI, and DF cannot be backfed.
Two PoleQO-GFI
One PoleQO-CAFI(PON)
One PoleQO-DF(PON)
DE1_p03-16.fm Page 6 Monday, April 25, 2016 2:28 PM
DE1-7
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
10-30 ampere breakers are suitable for use with 60°C or 75°C conductors, 35-60 ampere breakers are suitable for use with 75°C conductors.
✱ Combination AFI devices provide protection against both high-energy parallel arcing (same as existing branch/feeder AFCI’s) and low energy (5A) series arcing.
Circuit Breaker Factory Installed AccessoriesRequires Additional Pole Space. Only one accessory per breaker. QO accessory terminals for (2) #14-12 Cu. Accessories are not available for Q2, QOM1, or QOB-VH (110-150 A) circuit breakers or QO molded case switches.
▲ Add suffix - 1021 for 240Vac shunt trip. Factory Installed Accessory✚ Do not exceed the load centre mains rating. Main Breakers include factory installed handle padlock attachment (padlock
QOM main circuit breaker in the 'off' position).
QO One Polewith Shunt Trip
QOK KeyOperated
DE1_p03-16.fm Page 7 Monday, April 25, 2016 2:28 PM
DE1-8
QO® Loadcentres and Circuit BreakersD
E1
LO
AD
CE
NT
RE
S
04/16
QO® Main Lugs Loadcentres (1Ø - 3W)
MainsAmpereRating
Number of Circuits
LoadcentreCatalogue Number
TrimCatalogue Number
Main Wire SizeAl or Cu
(AWG/MCM)Box Size
(see page 16)Standard
QOTandem
QO
301 2 QO1L30S● Included 12-10 Al or 14-10 Cu 12 4 QO2L30SC● Included 12-10 Al or 14-10 Cu 2
70 2 4 QO2L70S✚ Included 12-3 Al or 14-4 Cu 3
100
4 8 QO4L100S▲ Included 8-1 46 12 QO6L100S/F▲ Included 8-1 48 15 QO8L100S/F▲ Included 8-1 4
12 24 CQO112L100GC Included 4-1 616 32 CQO116L100GC Included 4-1 7
12524 48 CQO124L125GC Included 4 - 2/0 832 48 CQO132L125GC Included 4 - 2/0 940 48 CQO140L125GC Included 4 - 250 11
20032 64 CQO132L200GC Included 4 - 250 1140 80 CQO140L200GC Included 4 - 250 11
Service entrance approved.● Will not accept QO-GFI or QO-EPD breakers.✚ Maximum 20A QO-GFI breaker or AFI breaker.▲ Maximum 70A branch breaker.◆ Does not include a door.▼ Shunt trip feature not available on any 3Ø loadcentres.
Feed-thru lugs cannot be added in filed-use QO3125SL to feed-thru to another loadcentre.
• Bus on 2-8 cct loadcentres is one piece, solid aluminum.• Bus on 12-60 cct loadcentres is one piece, tin plated
copper• Neutral terminals, main and ground lugs on all devices
are Aluminum.• QODK60-2 door kit can be installed on 60A main lug
loadcentre.
Application Information
• All loadcentres are suitable for both flush or surface mounting, unless suffixed:- F - flush mounting only.- S - surface mounting only.
• All Type 1 loadcentres are approved for vertical, horizontal, or inverted mounting.
• All 100A loadcentres are approved for 100A max. QO branch circuit breakers.
• All 125A loadcentres are approved for 125A max. QO branch circuit breakers.
• The maximum QO branch circuit breaker is 70 ampere (single pole), 200 ampere (two pole) and 100 ampere (three pole). Two pole QO breakers rated 150 - 200 ampere are restricted to Square D QO Single Phase load center, Series G1.
• Main lugs loadcentres cannot be field converted to service entrance approved, main breaker loadcentres.
• QO is a registered trademark of Square D.• For more information, consult Schneider Electric.• GC includes ground bar combination surface/flush cover.
QO® Main Lugs Loadcentres - Type 1 Indoor
DE1_p03-16.fm Page 8 Monday, April 25, 2016 2:28 PM
DE1-9
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
QO® Main Breaker Loadcentres - Type 1 Indoor
Main Breaker Loadcentres (1PH - 3W)
BusAmpere Rating
Main BreakerAmps
Number of Circuits
LoadcentreCatalogue Number
TrimCatalogue Number
Main Wire SizeAl/Cu (AWG/MCM)
Box Size(see page 16)
Standard QO
TandemQO
Main Breaker Factory Installed100 60 12 24 CQO112M100C60 Included 4 - 1 6100 100 12 24 CQO112M100C100 Included 4 - 1 6100 60 16 32 CQO116M100C60 Included 4 - 1 7100 100 16 32 CQO116M100C100 Included 4 - 1 7125 60 24 48 CQO124M125C60 Included 4 - 2/0 8125 100 24 48 CQO124M125C100 Included 4 - 2/0 8125 100 32 54 CQO132M125C100 Included 4 - 2/0 9125 125 32 54 CQO132M125C125 Included 4 - 2/0 9125 100 40 54 CQO140M125C100 Included 4 - 2/0 11125 125 40 54 CQO140M125C125 Included 4 - 2/0 11
Main Breaker Factory Installed
200 20032 64 CQO132M200C Included 4 - 250 1140 80 CQO140M200C Included 4 - 250 11
◆ Does not include a door. Order kit # QODK60-2. • Bus on all devices is one-piece, solid copper, standard.● Rated 200A maximum with Aluminum conductors and 225A
maximum with Copper conductors.• Neutral terminals, main and ground lugs on all devices are
Aluminum, standard.
NQ Service Entrance Main Breaker Panelboards
Main Rating Catalogue Number 1 or 3 PhaseSpace Factory Installed
Main Breaker Enclosure Width Trim TypeStandard QO Tandem QO
• All loadcentres are suitable for both flush or surface mounting.
• All Type 1 loadcentres are approved for vertical, horizontal, or inverted mounting.
• All 100A loadcentres are approved for 100A max. QO branch circuit breakers.
• All 125A loadcentres are approved for 125A max. QO branch circuit breakers.
• The maximum QO branch circuit breaker is 70 ampere (single pole), 200 ampere (two pole) and 100 ampere (three pole). Two pole QO breakers rated 150 - 200 ampere are restricted to Square D QO Single Phase load center, Series G1.
• Main Breaker loadcentres are approved for service entrance use. The main breaker compartment can be sealed and the main breaker can be locked.
• QO-L main breakers are 10 kAIC rated, QO-VHL main breakers are 22 kAIC rated.
• QO is a registered trademark of Square D.• For more information, consult Schneider Electric.
DE1_p03-16.fm Page 9 Monday, April 25, 2016 2:28 PM
DE1-10
QO® Loadcentres and Circuit BreakersD
E1
LO
AD
CE
NT
RE
S
04/16
QO® Main Lugs/Main Breaker Loadcentres - Type 3R Weatherproof
Main Lugs Loadcentres (1Ø - 3W)
BusAmpereRating
Number of CircuitsMain Wire Size
Al or Cu(AWG/MCM)
Standard QO
TandemQO
LoadcentreCatalogue Number
TrimCatalogue Number
Box Size(see page 16)
70 2 4 QO2L70RB ✚ ✗ Included 12-3 Al or 14-4Cu 1RB6 12 QO6L100RB Included 8-1 2RB
100 8 15 QO8L100RB Included 8-1 2RB16 32 CQO116L100GRB Included 4-1 6RB
125 24 48 CQO124L125GRB Included 4-2/0 6RB200 40 80 CQO140L200GRB Included 4-250 8RB
Main Lugs Loadcentres (3Ø - 4W)
BusAmpereRating
Number of CircuitsMain Wire Size
Al or Cu(AWG/MCM)
Box Size(see page 16)
Standard QO
TandemQO
LoadcentreCatalogue Number
TrimCatalogue Number
100 3 QO403L100RB Included 12-1 Al or 14-1 Cu 3RB
125 12 24 QO312ML1RB Included 4-2/0 4RB125 20 40 QO320ML1RB Included 4-2/0 5RB200 30 60 QO330ML2RB Included 4-250 7RB225 42 60 QO342ML2RB Included 4-300 9RB
Main Breaker Loadcentres (1Ø - 3W)
BusAmpere Rating
Main BreakerAmps
Number of Circuits
LoadcentreCatalogue Number
TrimCatalogue Number
Main Wire SizeAl/Cu
(AWG/MCM)Box Size
(see page 16)Standard
QOTandem
QO
Main Breaker Factory Installed100 60 8 16 CQO18M100RB60 Included 4 - 1 4RB100 100 16 32 CQO116M100RB100 Included 4 - 1 6RB125 100 24 48 CQO124M125RB100 Included 4 - 2/0 6RB
Main Breaker Factory Installed200 200 40 80 CQO140M200RB Included 4-250 8RB
✚ Maximum 20 A QO-GFI breaker.▼ 60 amp, 2 wire 240V only. Not for hot tubs with neutral connection. Service Entrance approved.✗ Not rated for 22k AIC.
• Bus on 2-8 cct loadcentres is one-piece, solid aluminum. (Excluding CQO18M100RB.)• Bus on 8-42 cct, S-Series loadcentres is one-piece, solid copper.• Neutral terminals, main and ground lugs on all devices are Aluminum.
Application Information
• All 100A loadcentres are approved for 100A max. QO branch circuit breakers.
• All 125A loadcentres are approved for 125A max. QO branch circuit breakers.
• The maximum QO branch circuit breaker is 70 ampere (single pole), 200 ampere (two pole) and 100 ampere
(three pole). Two pole QO breakers rated 150 - 200 ampere are restricted to Square D QO Single Phase load center, Series G1..
• Main Breaker loadcentres are approved for service entrance use. The main breaker compartment can be sealed and the main breaker can be locked.
• Main lugs loadcentres cannot be field converted to service entrance approved, mainbreaker loadcentres.
• Weatherproof Loadcentres are supplied with main entry hole cut in top endwall and closing cap (BCAP) installed.Hole accepts 3/4 in. to 2 in. hubs. Gasket not required.
• QO is a registered trademark of Square D.
DE1_p03-16.fm Page 10 Monday, April 25, 2016 2:28 PM
DE1-11
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
QO® Plug-on Neutral Loadcentres
QO Plug-on Neutral Loadcentres
Mains RatingAmps
Number of Circuits
LoadcentreCatalogue Number
Main Wire SizeAl/Cu
(AWG/MCM)Box Size
(see page 16)Standard
QOTandem
QOTrim
Main Lugs Loadcentres (1Ø - 3W)
Indoor
125 24 47 CQO124L125GCPON Included 4 - 2/0 8
Main Breaker Loadcentres (1Ø - 3W)100 24 47 CQO124M125C100PON Included 4 - 2/0 8100 30 60 CQO130M225C100PON Included 4 - 2/0 10100 42 80 CQO142M225C100PON Included 4 - 2/0 12200 42 80 CQO142M200CPON Included 4 - 250 12200 60 80 CQO160M200CPON* Included 4 - 250 14
Outdoor 100 24 47 CQO124M125RB100PON Included 4 - 2/0 6RB
* Does not include a door. Order kit # QODK60-2. Plug-on Neutral loadcentres accept both pig-tail and Plug-on Neutral breakers
DE1_p03-16.fm Page 11 Monday, April 25, 2016 2:28 PM
DE1-12
QO® Loadcentres and Circuit BreakersD
E1
LO
AD
CE
NT
RE
S
04/16
QO® Recreational Vehicle Park Loadcentres (ServicePak®)QO® Mobile Home and Trailer Loadcentres
• Provide electrical power to individual recreational vehicle park sites.• Each receptacle protected by appropriate GFI or Standard QO® circuit breaker.• All receptacles and circuit breakers included.• 10,000 RMS Symmetrical Ampere short circuit current rating.• All enclosures are rainproof.
• No neutral bonding provisions. • Loop-Feed provisions. • Type 3R weatherproof.• Optional configurations not available.• Pedestal is factory installed only.
Recreational Vehicle Park Loadcentres (ServicePak® Panels)
PowerOutletConfig.
Main Wire SizeAmpere Rating Canada
Catalogue No.(AWG/MCM) Box Size
(see page 16)Mains Sub-feed Spaces Service Series Al CuUnderground or Overhead Loop-Feed Terminals - Non-Pedestal Mounted ◆
◆ Non-pedestal devices are supplied with main entry hole cut in top endwall and have closing cap (BCAP) installed. Hole accepts 3/4 in. to 2 1/2 in. hubs. Gasket not required.◆ Non-pedestal devices have provisions to field install a Type “B” bolt on hub on the bottom endwall. For bottom feed from a conduit riser, order Type “B” hub and two mounting screws P/N:
8002505501; and two hex nuts, P/N: 2340102000.● For pedestal devices, a stabilizer foot is available for use in unstable ground, P/N: HNPSF.‡ Will not accept QO-GFI circuit breakers.✚ Use #10 maximum size wire for QO-GFI circuit breakers.† 70A Max. branch circuit breaker and 70A Max. back fed main circuit breaker.
T T T T T
Application Information
• All Servicepak® Panels have their breakers and receptacles factory installed and prewired.
• Mobile Home and Trailer Loadcentres do not come with factory installed breakers. Order separately.
• Servicepak® Panels and Mobile Home and Trailer Loadcentres are not suitable for use as service equipment.
• All Servicepak® devices are set up for Loop-fed, therefore, there are 2 wires per phase, neutral and equipment ground.
• Servicepak® devices are suitable for surface mountingonly.
• Power Outlet Configurations, other than those shown above, are not available.
• Servicepak® is a Registered Trademark of Square D.• For more information, consult Schneider Electric.
DE1_p03-16.fm Page 12 Monday, April 25, 2016 2:28 PM
DE1-13
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
Accessories
Description Catalogue Number
Handle AttachmentsHandle Tie: Converts any two adjacent 120/240Vac single pole QO breakers to independent trip two pole .......................... QO1HT
Converts any two adjacent 120/240Vac single pole side-by-side Tandem breakers to independent trip two pole QOTHTHandle Lock-Off: Clamp for holding QO single pole handle in “ON” or “OFF” position.................................................................... QO1LO
Clamp for holding QO, either 1, 2 or 3-pole breaker handles in “ON” or “OFF” position...................................... HLO1Handle Padlock Attachment: For padlocking single pole QO breaker in “ON” or “OFF” position
Loose Attachment QOHPLFixed Attachment QO1PA
For padlocking single pole side-by-side QO Tandem breaker in “ON” or “OFF” position.... ................................. QOTHPAFor 2 and 3-pole QO breakers which require padlocking in either “ON” or “OFF” position
For padlocking QOM main circuit breakers in “OFF”...............................................................50-125A... ........... . QOM1PA150-225A... ...................................................................................................................................................... .... QOM2PAFor padlocking 2-Pole QO-GFI in either “ON” or “OFF” position.......... .............................................. .................. GFI2PA
Mechanical Interlock Attachment: For interlocking the handles of two 2-pole or one 2-pole and one 1-pole QO breakers mounted side-by-sideso that only one breaker can be “ON” at a time..... .............................................................................................. QO2DTI
Sub-feed lugs 125 ampere two pole plug-on – 2 spaces required (#12-2/0 Al/Cu)..................................................................... QO2125SL125 ampere three pole plug-on – 3 spaces required (#12-2/0 Al/Cu) .................................................................. QO3125SL
Filler Plates Fills branch breaker openings in cover................................................................................................................. QOFPFills QOM1 main breaker opening in cover...............................................................100-125A........................... . QOM1FPFills QOM2 main breaker opening in cover...............................................................150-225A........................... . QOM2FPFills main breaker opening in 3Ø covers (S-Series)............................................................................................. KFP
Lock Kits Converts door latch from spring catch to lock type .............................................................................................. PK6FL
Neutral / Ground Lugs Field installed for #12 to 2 Al or #14 to 4 Cu wire ................................................................................................ LK70ANField installed for #6 to 2/0 Al/Cu wire.................................................................................................................. LK100ANField installed for #14 to 2/0 Al/Cu wire................................................................................................................ LK125ANField installed for #2 to 3/0 Al/Cu wire.................................................................................................................. LK150ANField installed for #4 to 300 MCM Al/Cu............................................................................................................... LK225AN
Neutral Extension kits Field installed on 1ph QO loadcentres See page DE1-12
Ground Bar Kits Standard PK15GTA with a #1 to 4/0 Cu/Al Lug................................................................................................... . PK15GTALStandard PK18GTA with a #1 to 4/0 Cu/Al Lug................................................................................................. ... PK18GTALStandard PK23GTA with a #1 to 4/0 Cu/Al Lug................................................................................................... . PK23GTALInsulator Kit for PK9GTA thru PK27GTA.. .......................................................................................................... .. PKGTAB
Miscellaneous QO main breaker barrier. .................................................................................................................................. ... 4055952201
Retaining Kit: Secures circuit breaker to interior when used as a back-fed main.For use on QO6L100S/F, RB and QO8L100S/F, RB Loadcentres. ................................................................... ... PK2MBSecures circuit breaker to interior when used as a back-fed main. For 3Ø Loadcentres (S-Series)................... . PK3MB
Cover Sealing Strap: Provides means of sealing trim mounting screws on QO load centre covers.. ................................................. ... QO1SEJoint Compound For use on plug-on connectors only. Recommended for use whenever QO plug-on breakers are removed and
reinstalled for any reason. 57g container ............................................................................................................ . PJC7201Touch–up Paint Aerosol spray paint can – ASA 49 ....................................................................................................................... W469X83
PK2MB
PK3MB
PK6FLHLO-1
QO1HPL
QO1PL
QO2DTI
QO1LO
PKGTAB
QOFP
QO1PA
QOSAMK
QOTHPA
QO1HT
HLO1
Application Information
• QO is a registered trademarks of Square D.• For more information consult Schneider Electric.
DE1_p03-16.fm Page 13 Monday, April 25, 2016 2:28 PM
DE1-14
QO® Loadcentres and Circuit BreakersD
E1
LO
AD
CE
NT
RE
S
04/16
QO® Single Phase Loadcentre - Field Installed Neutral Extension Kits
• Multiple length kits available• Kit includes a left and right side neutral bar• Left side or right side installation option
Loadcentre catalogue number
Reference neutral kit(s)*
CQO124L125GC 1
CQO124L125GRB 1
CQO124M125C60 1
CQO124M125C100 1
CQO124M125RB100 1
CQO132L125GC 1
CQO132L200GC 1
CQO132M125C100 1
CQO132M125C125 1
CQO132M125C60 1
CQO132M125C70 1
CQO132M200C 1
CQO140L125GC 2
CQO140L200GC 2
CQO140L200GRB 2
CQO140M125C100 2
CQO140M125C125 2
CQO140M150C 2
CQO140M200C 2
CQO140M200RB 2
CQO142L225GC 1 or 3
CQO160L225GC 2 , 3 or 4
CQO160M200C 2 , 3 or 4
CQO124M60CD 1
CQO124M100CD 1
CQO132M100CD 1
CQO132M125CD 1
CQO140M200CD 2
CQO112L100GC –
CQO116L100GC –
CQO116L100GRB –
CQO116M100C60 –
CQO116M100C100 –
CQO116M100RB100 –
CQO18M100RB60 –
CQO112M100C60 –
CQO18M100RB100 –
Loadcentre catalogue number
Reference neutral kit(s)*
* Neutral kit reference number description
Reference neutral kit(s) Neutral kit catalogue number Neutral kit description
1 QONK1 14 neutral ports x 2
2 QONK2 22 neutral ports x 2
3 QONK3 34 neutral ports x 2
4 QONK4 41 neutral ports x 2
– – Neutral kit is not available
*Installing the Neutral Bar Extensions When installing the QO neutral bar extension kits, circuit breaker mounting spaces need to be left open below the neutral extension kits for ground fault interrupters, arc fault interrupters and the larger amperage branch circuit breakers rated 150–200 A that would extend beyond the neutral bars. These circuit breaker types will not fit over the OQ neutral extension kit bars.
Application Information
• For more information, contact our Customer Information Centre @ 1-800-565-6699.
DE1_p03-16.fm Page 14 Monday, April 25, 2016 2:28 PM
DE1-15
QO® Loadcentres and Circuit Breakers
DE
1L
OA
D C
EN
TR
ES
04/16
Secondary Surge Suppressors and Surge Arresters
SURGEBREAKER PLUS® • Suitable for use in service entrance locations.• Meets requirements of CSA C22.2 No. 8, UL 1449, 3rd Edition, ANSI/IEEE C62.41
and cULus Listed.• AC line protection.• Four line telephone protection.• Two line coaxial protection.• Suitable for indoor applications only.• Flush or surface mounting.• LED status indicator.• Modular design with optional accessories.
Single Phase Three Wire – 120/240 Vac
Description Catalogue Number
Surgebreaker Plus SDSB80111C
SURGEBREAKER™ Secondary Surge Arrester• Suitable for use in service entrance locations.• Meets CSA C22.2 No. 8, CSA C233.1, ANSI/IEEE C62.11.• QO2175SB for QO load centers and combination devices, NQOD panelboards.• Plug–on design requires two pole spaces.• LED indicates operational status.
DescriptionCatalogueNumber
QO SurgebreakercULus ListedSecondary Surge Arrester150Vac line–to–ground maximum
QO2175SB
Hard–Wired Secondary Surge Arresters• Suitable for use in service entrance locations.• cULus Listed Secondary Surge Arresters.• Meets CSA C233.1, ANSI/IEEE C62.11.• Suitable for indoor and outdoor applications.• LED indicates operational status.
tral, ground and trim screws• Additional ground bar provisions
• Trims have automatic flushadjustment
• Fusible loadcentre inserts(HFLCI)
Accessories: • Secondary Surge Arresters
• Sub-Feed Lugs
• Filler Plates (for branch and mainbreakers)
• Door Lock Kits
• Neutral Lugs
• Neutral extension kits
DE1_p17.fm Page 17 Monday, April 25, 2016 1:46 PM
Canadian HomeLine™ Circuit Breakers and LoadcentresProduct Description
DE
1L
OA
DC
EN
TR
ES
DE1-1804/16
The Residential Solution for Canadian Electrical Contractors
HomeLine™ circuit breaker loadcentres from Schneider Electric are CSAcertified panelboards. They are designed to meet residential requirements toprotect electrical systems, equipment, and people.
Features
Indoor (NEMA Type 1), Main Breaker, 12 to 60 spaces
• Single phase, 120/240V
• 200A maximum tin plated aluminum bus
• 60 spaces, 120 circuits max
• Short circuit rating
k standard 22kAIC – main breaker (50A thru 200A)
k series ratings up to 100kAIC
• Distributed neutral bar design
• Robertson/Slot neutral, ground and trim screws
• Shielded bus bar
• Appliance white combination flush/surface mount trim
• Automatic flush trim adjustment with shutter type twistouts
• Top or bottom feed
• Multiple horizontal and vertical ground bar mounting positions
• Straight in wiring for main and branch wiring
• Removable interiors
• Tangential main knockouts
• Provision for optional door lock
• Welded box construction
Indoor (NEMA Type 1), Main Lug, 2 to 42 spaces
• Single phase, 120/240V
• 225A maximum tin plated aluminum bus
• 42 spaces, 84 circuits max
• Short circuit rating
k standard 10kAIC – main lug
k series ratings up to 100kAIC
• Robertson/Slot neutral, ground and trim screws
• 2 to 6 space single row loadcentres, ASA49 grey
• Top or bottom feed
• Welded box construction
HomeLine Fusible Loadcentre Inserts (HFLCI)Indoor (NEMA Type 1), Main Lug, 12 spaces
• Single phase, 120/240V
• 125A maximum tin plated aluminum bus
• 12 spaces, 24 circuits max
• Short circuit rating
k standard 10kAIC
k series ratings up to 100kAIC
• Robertson/Slot neutral, ground and trim screws
• Architectural white surface mount trim with door
HomeLine™ Main Breaker Loadcentre
Flush Cover
DE1_p18.fm Page 18 Monday, April 25, 2016 1:49 PM
Canadian HomeLine™ Circuit Breakers and LoadcentresGeneral Information and Application Data
DE
1L
OA
DC
EN
TR
ES
DE1-1904/16
Outdoor (NEMA Type 3R), Main Breaker,8 to 20 spaces
1. CSA certified for use as HACR type circuit breakers.
2. Cat# represents two 1P outer poles and one 2P inner circuit breaker with common trip.
3. CHOMT tandems require 1 space.
4. CHOMT quad tandems require 2 spaces.
HomeLine Combination Arc-Fault Interrupter (CAFI)HomeLine Combination Arc-Fault Interrupter (CAFI) provides overload and short circuit protection, plus both series and paralleltype arc protection as required in 2015 CEC. Integrated with Time Saver diagnostics, HomeLine CAFI breaker improves circuittroubleshooting at the touch of a button.
* Rated for 120/240V ~ 60 Hz, not for 208Y/120V
HomeLine Dual Function Circuit BreakerHomeLine Dual Function (DF) breaker provides both combination arc-fault and ground-fault (5mA classA) protection in a singlecompact device. Integrated with Plug-on Neutral and Time Saver Diagnostics features, HomeLine DF breaker offers maximumcircuit protection and installation flexibility.
1. GFI breakers maximum 250 feet (one way) feeder length
2. Use solid conductor only when #14 wire is used
Ground Fault Devices (GFI)
Spa PackA complete kit consisting of a Type 3R enclosure, factory installed 2P50AGFCI circuit breaker.
Arc faults are any abnormal flow of electricity that create an arc, spark orflash which is hot and capable of igniting flammable materials, therebyincreasing the potential for a residential fire.
Canadian HomeLine™ Circuit Breakers and LoadcentresType 1 Main Lug and Main Circuit Breaker Loadcentres
DE
1L
OA
DC
EN
TR
ES
DE1_p25-26.fm Page 25 Monday, April 25, 2016 5:08 PM
04/16
k Does not include a door. Order kit # CHOMDK602.- Main Breaker loadcentres are approved for service entrance use. The main breaker compartment can be sealed and the main breaker can be locked.- All type 1 loacentres are approved for vertical, horizontal, or inverted mounting.- Canadian HomeLine loadcentres 8/16-space and above (double-row construction) come with Plug-on Neutral capability as standard.
Single-Phase, Three-Wire, 120/240 Vac Main Lugs – Indoor
MainsRating
inAmps
LoadcentreCatalogue Number
Maximum Numberof Circuits
LoadcentreCover
CatalogueNumber
ServiceEntranceApproved
MaximumShortCircuitRating
MainWireSize
AWG/kcmilAl/Cu
EnclosureNo.
(Pages34-35)
Top orBottomMains
PositionStandard 1"Tandem or
Quad
Factory-Installed Main Lugs
70 CHOM24L70F/S 2 4 Included N 10,000 A#12–3
#14–42 Top
100 CHOM612L100F/S 6 12 Included N 10,000 A #8–1 4 Top
125 CHOM48L125GC 4 8 Included N 10,000 A #4–2/0 21 Top
Factory-Installed Main Lugs
125
CHOM816L125GC 8 16 Included N 10,000 A #6–2/0 6 Both
CHOM1224L125GC 12 24 Included N 10,000 A #6–2/0 6 Both
CHOM1632L125GC 16 32 Included N 10,000 A #6–2/0 8 Both
CHOM2448L125GC 24 48 Included N 10,000 A #6–2/0 8 Both
CHOM3060L125GC 30 60 Included N 10,000 A #6-2/0 10 Both
Factory-Installed Main Lugs
225CHOM3060L225GC 30 60 Included N 10,000 A #6–250 10 Both
CHOM4284L225GC 42 84 Included N 10,000 A #6–250 12 Both
Single-Phase, Three-Wire, 120/240 Vac Main Circuit Breaker – Indoor
MainsRating
inAmps
LoadcentreCatalogue Number
Maximum Numberof Circuits
LoadcentreCover
CatalogueNumber
ServiceEntranceApproved
MaximumShortCircuitRating
MainWireSize
AWG/kcmilAl/Cu
EnclosureNo.
(Pages34-35)
Top orBottomMains
PositionStandard 1"Tandem or
Quad
Factory-Installed Main Circuit Breaker
30 CHOM1224M30GC 12 24 Included Y 10,000 A #6-2/0 6 Both
50 CHOM1224M50GC 12 24 Included Y 22,000 A #6-2/0 6 Both
60CHOM1224M60GC 12 24 Included Y 22,000 A #6-2/0 6 Both
CHOM1632M60GC 16 32 Included Y 22,000 A #6-2/0 7 Both
70CHOM1224M70GC 12 24 Included Y 22,000 A #6-2/0 6 Both
CHOM1632M70GC 16 32 Included Y 22,000 A #6-2/0 7 Both
100
CHOM1224M100GC 12 24 Included Y 22,000 A #6-2/0 6 Both
CHOM1632M100GC 16 32 Included Y 22,000 A #6-2/0 7 Both
CHOM2448M100GC 24 48 Included Y 22,000 A #6-2/0 8 Both
CHOM3060M100GC 30 60 Included Y 22,000 A #6-2/0 10 Both
125
CHOM1224M125GC 12 24 Included Y 22,000 A #6-2/0 6 Both
CHOM1632M125GC 16 32 Included Y 22,000 A #6-2/0 8 Both
CHOM2448M125GC 24 48 Included Y 22,000 A #6-2/0 8 Both
CHOM3060M125GC 30 60 Included Y 22,000 A #6-2/0 10 Both
Factory-Installed Main Circuit Breaker
100
CHOM3060M2100GC 30 60 Included Y 22,000 A #4–250 10 Both
CHOM4284M2100GC 42 84 Included Y 22,000 A #4–250 12 Both
CHOM60120M2100GC 60 120 Included k Y 22,000 A #4–250 24 Both
150
CHOM2040M150GC 20 40 Included Y 22,000 A #4–250 9 Both
CHOM3060M150GC 30 60 Included Y 22,000 A #4–250 10 Both
CHOM60120M150GC 60 120 Included k Y 22,000 A #4–250 24 Both
200
CHOM2040M200GC 20 40 Included Y 22,000 A #4–250 9 Both
CHOM3060M200GC 30 60 Included Y 22,000 A #4–250 10 Both
CHOM4284M200GC 42 84 Included Y 22,000 A #4–250 12 Both
CHOM60120M200GC 60 120 Included k Y 22,000 A #4–250 24 Both
DE1-25DE1-25
Canadian HomeLine™ Circuit Breakers and LoadcentresType 3R Main Lug and Main Circuit Breaker Loadcentres
DE
1L
OA
DC
EN
TR
ES
DE1_p25-26.fm Page 26 Monday, April 25, 2016 5:08 PM
Single-Phase, Three-Wire, 120/240 Vac Main Lugs – Rainproof
MainsRating
in Amps
LoadcentreCatalogueNumber
Maximum Numberof Circuits
LoadcentreCover
CatalogueNumber
ServiceEntranceApproved
MaximumShort
CircuitRating
MainWireSize
AWG/kcmilAl/Cu
EnclosureNo.
(Pages34-35)
Top orBottomMains
PositionStandard 1"Tandem or
Quad
Factory-Installed Main Lugs
70 CHOM24L70RB 2 4 Included N 10,000 A #12–3 Al#14–4 Cu 1R Top
100 CHOM612L100RB 6 12 Included N 10,000 A #8–1 2R Top
125 CHOM48L125GRB 4 8 Included N 10,000 A #12–2/0 Al#14–2/0 Cu 15R Top
Factory-Installed Main Lugs
125 CHOM816L125GRB 8 16 Included N 10,000 A #6–2/0 3R Top
CHOM1224L125GRB 12 24 Included N 10,000 A #6–2/0 3R Top
Single-Phase Three Wire 120/240 Vac Main Breaker – Rainproof
Factory-Installed Main Circuit Breaker
100CHOM816M100GRB 8 16 Included Y 22,000 A #6-1 3R Top
CHOM1224M100GRB 12 24 Included Y 22,000 A #6-2/0 3R Top
Factory-Installed Main Circuit Breaker
200 CHOM2040M200GRB 20 40 Included Y 22,000 A #4–250 6R Top
DE1-2604/16
- Canadian HomeLine loadcentres 8/16-space and above (double-row construction) come with Plug-on Neutral capability as standard.
DE1-27
Canadian HomeLine™ Circuit Breakers and LoadcentresLoadcentres
DE
1H
OM
EL
INE
04/16
HomeLine Fusible Loadcentre Inserts (HFLCI)
Fusible Loadcentre Inserts
• HomeLine Fusible Loadcentre Inserts (HFLCI) offer the safety and reliability of a modern circuit breaker loadcentre systemfeaturing HomeLine circuit breakers.
• Easily replaces outdated fusible loadcentres.
• Eliminates drywall removal and repair.
• Eliminates painting new drywall.
• No holes to drill.
• No new ground required.
• No branch conductors or conduit to remove.
• Using the HomeLine FLCI substantially reduces installation time, as much as 80%, allowing for the economical replacement ofold fusible loadcentres.
Step #1
Identify Box Dimensions andCatalogue Number
Step #2
Remove Old FusibleInterior
Step #3
Install New HFLCI
Step #4
Complete Installation
DE1_p27.fm Page 27 Monday, April 25, 2016 2:04 PM
DE1-28
Canadian HomeLine™ Circuit Breakers and LoadcentresLoadcentres
DE
1L
OA
DC
EN
TR
ES
04/16
HomeLine Fusible Loadcentre Inserts (HFLCI)
READ THIS FIRST!
To select the proper HFLCI, follow these three steps:
Step 1: Find your fusible loadcentre catalogue number using columns 1 and 2.
Step 2: Confirm that the original fusible loadcentre box dimensions match those in columns 5, 6, and 7.
Step 3: Use column 3 to identify the HomeLine Fusible Loadcentre Insert (HFLCI) catalogue number.
CAUTION: Do not proceed with an installation unless both the existing catalogue number and box dimensions match.
Note: Not suitable for use with Canadian HomeLine AFI, CAFI, DF or GFI devices.
1 2 3 4 5 6 7
OriginalManufacturer
Original MainLug Loadcentre
CatalogueNumber
HomeLineCatalogueNumber**
Maximum Numberof Circuits
Box Dimensions
Height Width Depth
Standard 1" Tandemor Quad Inches mm Inches mm Inches mm
** HomeLine FLCI's include distribution section interior, trim, door and painted architectural white.
DE1_p28.fm Page 28 Monday, April 25, 2016 2:05 PM
Canadian HomeLine™ Circuit Breakers and Loadcentres
DE
1L
OA
DC
EN
TR
ES
DE1-2904/16
Accessories
• Plug-in surge breaker
• Ground bars
• Neutral lugs
• Filler plates
• Type 3R rain hubs
• Type 3R coupling trough
• Door lock
• Main lugs
• Replacement covers
• Replacement interiors
RB Hub
BC200 Enclosure Coupling
CHOM Surgebreaker®
Surge Arrester2 spaces required.
PK15GTA
LK100AN
HOMFPQOM1FP
QOM2FP
PK6FL
QOL125
QOL225
DE1_p29.fm Page 29 Monday, April 25, 2016 2:05 PM
Canadian HomeLine™ Circuit Breakers and LoadcentresHomeLine Loadcentre Accessories
DE1-3004/16
DE
1L
OA
DC
EN
TR
ES
* No door on cover.
Replacement Covers, 1 Phase, Type 1 Enclosures ONLY
Reference Loadcentre CatalogueNumber
ReplacementCoverCatalogueNumber
CHOM24L70S * 4055800801
CHOM24L70RB 4056314401
CHOM24L70F * 4055800701
CHOM48L125GC 4055844801
CHOM48L125GRB 4056318650
CHOM612L100S * 4055801702
CHOM612L100F * 4055801801
CHOM612L100RB 4056318550
CHOM816M100GRB 4056319050
CHOM1224M100GRB 4056319050
CHOM2040M200GRB 4056319150
CHOM 8-16,12-24 ML-MB loadcentres CHOMC12UC
CHOM 16-32 60-100A MB loadcentres CHOMC21UC
CHOM 16-32 125A, 24-48 ML-MB loadcentres CHOMC24UC
CHOM 30-60 100-125A MB loadcentres CHOMC30U125C
CHOM 30-60 150-225A ML-MB loadcentres CHOMC30UC
CHOM 42-84 ML-MB loadcentres CHOMC42UC
CHOM 20-40 MB loadcentres CHOMC20UC
Door Lock Kits, 1 Phase, Type 1 Enclosures ONLY
Catalogue Number Description
PK6FL For use with type 1 CanadianHomeLine Loadcentres.
Surge Protective Device
DescriptionCatalogueNumber
Surge arrester for 1PH3W system150Vac maximum phase-to-ground CHOM2175SB
Interchangeable Hubs
Conduit Size Type B HubsClosing Plate BCAP
3/4" B0751" B100
1 1/4" B1251 1/2" B150
2" B2002 1/2" B250
Coupling Trough
Catalogue Number Description
BC200 BC200 - enclosure coupling for RB devices
Filler Plates
Description Catalogue Number
Branch Breaker HOMFP
QOM1 Main Breaker QOM1FP
QOM2 Main Breaker QOM2FP
Optional Neutral Lugs
Wire Size Catalogue Number
#12-2 AL#14-4 Cu LK70AN
#6-2/0 AL/Cu LK100AN
#14-2/0 AL/Cu LK125AN
#2-3/0 Al/Cu LK150AN
Main Lug Kits
Catalogue Number DescriptionQOL125 125A Kit
QOL225 225A Kit
B-150
DE1_p30.fm Page 30 Monday, April 25, 2016 2:06 PM
Canadian HomeLine™ Circuit Breakers and LoadcentresTechnical Information
DE
1L
OA
DC
EN
TR
ES
DE1_p31-35.fm Page 31 Monday, April 25, 2016 2:08 PM
TECHNICAL INFORMATION
Grounding Bar Kits
All PK equipment grounding bar kits are suppliedwith mounting screws, necessary installation
instructions and an “Equipment GroundingTerminal” self-adhesive label.
Wire Range Table
n screw
s Section of Size 1 Ground
0.3125[8]
D
CatalogueNumber
TotalQty.
TerminalsApproximate
OverallLength
DistanceBetweenMounting
HolesMounting
Quantity Each SizeSee “Wire Range
Table” below.
I II III IV V VI in [mm] in [mm]
PK0GTA2 2 — — — — — 2 1.75 [44] Onehole
Onehole Top
PK0GTA6 6 — — — — 6 — 4.61 [117] 1.69 [43] Top
PK3GTA1 3 3 — — — — — 1.38 [35] Onehole
Onehole Top
PK4GTA 4 4 — — — — — 1.63 [41] Onehole
Onehole Top
PK5GTA 5 5 — — — — — 2.25 [57] 1.25 [32] Top
PK7GTA 7 7 — — — — — 2.88 [73] 1.25 [32]Topor
Side
PK9GTA1 9 9 — — — — — 3.25 [83] Onehole
Onehole Top
PK9GTA 9 9 — — — — — 3.78 [96] 3.13 [80] Top
PK12GTA 12 12 — — — — — 4.70 [119] 3.13 [80] Top
PK15GTA 15 15 — — — — — 5.63 [143] 3.13 [80] Top
PK15GTAL 16 15 1 — — — — 8.13 [207] 3.13 [80] Top
PK15GTA6 1 21 15 — — 6 — — 5.88 [149] ✒ 2 Top
PK18GTA 18 18 — — — — — 6.56 [167] 3.13 [80] Top
PK18GTAL 19 18 1 — — — — 8.81 [224] 3.13 [80] Top
PK23GTA 23 23 — — — — — 8.11 [206] 3.13 [80] Top
PK23GTAL 24 23 1 — — — — 9.44 [240] 3.13 [80] Top
PK27GTA 327or26
27or26
— 1 — — — 9.36 [238] 3.13 [80] Top
1 Mounting screws 21594-14241(two required) and 21594-17121(two required).2 3.13 in. (80 mm) on small terminals; 5.25 in. (133 mm) on large terminals.3 PK27GTA includes one main grounding lug that mounts with two terminal screws and requires
three terminals for mounting.
Size Cu (AWG) Al (AWG)
I (1) #14–#4 or (2) #14 or #12 (1) #12–#4 or (2) #12 or #10
II (1) #1–4/0 (1) #1–4/0
III (1) #6–2/0 (1) #6–2/0
IV (1) #6–3/0 (1) #6–3/0
V (1) #14–1/0 (1) #14–1/0
VI (1) #10–2/0 (1) #6–2/0
DE1-3104/16
Canadian HomeLine™ Circuit Breakers and LoadcentresWiring Diagrams
DE
1L
OA
DC
EN
TR
ES
DE1_p31-35.fm Page 32 Monday, April 25, 2016 2:08 PM
WIRING DIAGRAMS
CHOM24L70S/F
CHOM24L70RB
SN
CHOM612L100S/F
CHOM612L100RB
S/N
CHOM816L125GC
CHOM816L125GRB
CHOM1224L125GC
S N
S N
SN
SN
SN
CHOM1632L125GC
CHOM3060L225GC CHOM4284L225GCCHOM2448L125GC
CHOM1224L125GRB
SN
SN
SN
SN
SN
SN
SN
DE1-3204/16
Canadian HomeLine™ Circuit Breakers and LoadcentresWiring Diagrams
DE
1L
OA
DC
EN
TR
ES
DE1_p31-35.fm Page 33 Monday, April 25, 2016 2:08 PM
1-Phase, 3-Wire Main Circuit Breakers
SN
CHOM816M100RB
SNMAIN
SN
CHOM1224M100GC
SNMAIN
SN
CHOM1632M100GCCHOM1632M125GC
SNMAIN
CHOM2040M150GC
SNMAIN
SN
CHOM2448M100GCCHOM2448M125GC
CHOM3060M100GCCHOM3060M125GC
MAINSN
CHOM60120M200GC
SN
CHOM4284M200GCCHOM4284M2100GC
CHOM1224M125GCCHOM1224M100GR
CHOM2040M200GCCHOM2040M200GRB
MAIN
MAIN
CHOM3060M150GCCHOM3060M200GCCHOM3060M2100GC
MAINSN
SN
SN
SN
SN
SN
DE1-3304/16
Canadian HomeLine™ Circuit Breakers and LoadcentresWiring Diagrams
DE
1L
OA
DC
EN
TR
ES
Indoor Dimensions and Knockouts
DE1_p31-35.fm Page 34 Monday, April 25, 2016 2:08 PM
Indoor Dimensions
BoxNo.
W H D
in. mm in. mm in. mm
2 4.81 122 9.30 236 3.19 81
4 8.88 226 12.57 319 3.80 97
6 14.25 362 17.92 455 3.75 95
7 14.25 362 20.92 531 3.75 95
8 14.25 362 26.04 661 3.75 95
9 14.25 362 29.86 758 3.75 95
10 14.25 362 33.78 858 3.75 95
12 14.25 362 39.37 1000 3.75 95
21 8.88 226 14.80 376 3.80 97
24* 14.25 362 48.50 1232 3.75 95
Knockouts
Symbol A B C D E F G H I
ConduitSize
0.50 in.13 mm
0.75 in.19 mm
1.00 in.25 mm
1.25 in.32 mm
1.50 in.38 mm
2.00 in.51 mm
2.50 in.64 mm
3.00 in.76 mm
3.50 in.89 mm
* Note: Box 24 knockout drawing to follow.
Box 10
A
AA,B,C A, B, C
A, B, C, D
Box 2
A,B
Box 4
A
B, C,D, E B, C, D, E
B, C, D, E
B, C,D, E B, C, D, E
B, C, D, EA
C, D, E, F
A
A, B, C, D
A, BB, C, D, E
A, B
A
B, C, D, E
C, D, E,F,G
Box 6
A, B, C, D
A A, BB, C, D,E
B, C, D, E
C, D, E, F
Box 8
C, D, E,F,G
C, D, E, FD, E,F, G
D, E, F, G
A
A, B
A, B, C, D
B, C, D, EC, D, E, FA A, B
D, E,F, G
Box 9
B, C
B, C, D, E
C, D, E,F,G
B, C
A
A, B
D, E,F, G
C, D, E, FA, B, C, D,
D, E, F, GC, D, E, F
B, C, D, E
C, D, E,F,G A A, B
B, C, D, ED, E, F, G
D, E, F, GC, D, E, F
A, B, C, D
B, C, D, E
B, C, D, E
D, E, F, G
C, D, E,F, G
C, D, E, F
A, BA
A
A, B
B, C
B, C, D, E
Box 12
A
B, C, D, E
B, C, D, EA, B A B, C, D, E
B, C, D, E
B, C, D, E
B, C, D, E
Box 21
INDOOR DIMENSIONS AND KNOCKOUTS
C, D, E, F
A
A, B, C, D
A, BB, C, D, E
A, B
B, C, D, E
C, D, E,F,G
Box 7
A
DE1-3404/16
Canadian HomeLine™ Circuit Breakers and LoadcentresOutdoor Dimensions and Knockouts
DE
1L
OA
DC
EN
TR
ES
DE1_p31-35.fm Page 35 Monday, April 25, 2016 2:08 PM
OUTDOOR DIMENSIONS AND KNOCKOUTS
Outdoor Dimensions
Box No.W H D
in. mm in. mm in. mm
1R1
1 CHOME250SPA top endwall has no hub opening.
4.88 124 9.38 238 4.00 102
2R 8.88 226 12.65 321 4.27 108
3R 14.75 375 18.92 481 4.52 115
6R 14.75 375 29.86 758 4.52 115
15R 8.88 226 14.80 376 4.27 108
Knockouts
Symbol A B C D E F G H
ConduitSize
0.50 in.13 mm
0.75 in.19 mm
1.00 in.25 mm
1.25 in.32 mm
1.50 in.38 mm
2.00 in.51 mm
2.50 in.64 mm
3.00 in.76 mm
Box 3RBox 1R
2.5 in. (64 mm)Hub Max.
A, B, C, DAA, B
Box 2R
2.5 in. (64 mm)Hub Max.
B, C, D, E A
B, C, D, E A, B
B, C,D, E
2.5 in. (64 mm)Hub Max.
C, D, E F, G
C, D,E, F A A,
BC, D,E, F,G
A, B, CC, D, E, F
C, D, E, F, G
C, D,E, F A A, B C, D,
E, F, G
A, B, CC, D, E, F
Box 6R
2.5 in. (64 mm)Hub Max.
Box 15R
2.5 in. (64 mm)Hub Max.
B, C, D, E A
B, C, D, EA, BB, C, D, E
E.&O.E.
DE1-3504/16
DE1-36
Intentionally left blankD
E1
LO
AD
CE
NT
RE
S
04/16
DE1_p36_blank.fm Page 36 Monday, April 25, 2016 2:19 PM
Stab-lok Circuit BreakersGeneral Information
DE
1L
OA
DC
EN
TR
ES
DE1_P37-41.fm Page 37 Monday, April 25, 2016 2:24 PM
DE1_P37-41.fm Page 40 Monday, April 25, 2016 2:24 PM
Ground Fault Circuit Breakers and Spa Pack
Circuit Breakers
Notes:
1. Submersible pump installations require ground fault protection to themaximum sensitivity level of 10mA. These breakers are designed tomeet the Canadian Electrical Code under rule CEC 26-956
2. GFI breakers maximum 250 feet (one way) feeder length
Side blanking plate for RH104-8CHTS using non-twist lock receptacle kits.
Side blanking plate for RH104-8CHTS using twist lock receptacle kits.
RM00
RMBLTL
DE1-42 04/16
Stab-lok Loadcentres and Circuit BreakersAccessories
DE
1L
OA
DC
EN
TR
ES
DE1_P42-44.fm Page 43 Monday, April 25, 2016 2:26 PM
Stab-lok Loadcentre Accessories
Note: For use with W98 Series Stab-lok loadcentres.
Note: For use with W98 Series Stab-lok loadcentre interior. Single phaseonly.
Door Kits, 1 Phase, Type 1 Enclosures ONLY
Reference LoadcentreCatalogue Number
Door KitCatalogueNumber
List Price Std. PackageSize
108-16-125 DK1W98
3
112-24-125 DK2W98
116-32-125 DK3W98
120-40-125 DK4W98
124-48-125 DK5W98
132-64-225 DK8W98
142-84-225 DK9W98
BE108-16-1CXXX DK1BEW98
BE112-24-1CXXX DK2BEW98
BE116-32-1CXXX DK3BEW98
BE120-40-1CXXX DK4BEW98
BE124-48-1CXXX DK5BEW98
BE132-64-1CXXX DK6BEW98
BE120-40-2CXXX DK7BEW98
BE124-48-2CXXX DK7BEW98
BE132-64-2CXXX DK8BEW98
BE142-84-2CXXX DK9BEW98
Door Lock Kits, 1 Phase, Type 1 Enclosures ONLY
Catalogue Number List Price Description
PK6FL For use with 125 and 225A W98Series Stab-lok loadcentres.
Main Lug Kits
Max. Bus Rating (A) Main Lug Kit CatalogueNumber List Price
125A QOL125
225A QOL225
Filler Plates
CatalogueNumber Description List
Price
PF1
Filler plate for NA or NC breakers. For use inpresent design of Stab-lok enclosures, except400 A - see BFAB. Will also fit previous designusing 1/2” metal KO’s PF1 consists of 1 strip of 41/2” plastic fillers suitable for 4 NC poles or 2 NApoles.Minimum order quantity 25
BFAB
Filler plate for 1 NA breaker. For use in present400 A enclosure design and previous enclosuredesigns using aluminum center strip.Minimum order quantity: 50
DK3W98
PK6FL
BFABPF1
DE1-4304/16
Stab-lok Circuit BreakersD
E1
LO
AD
CE
NT
RE
S
DE1_P42-44.fm Page 44 Monday, April 25, 2016 2:26 PM
Stab-lok Loadcentre Accessories
* For use with 125A W98 Series Stab-lok Loadcentres.
** Sub-feed lugs for 225A W98 Series may be ordered as a factory installed option.
Note: Suitable for Cu/Al conductors.
Sub-Feed Kits, MLO Panels Only
EnclosureCat.No.
OrderingCatalogueNumber
ListPrice
AmpRating
(A)Lug Range
10816125
SFL125W98* 125 A #6-300MCM1122412511632125120401251244812531224 S/F SFL100 100 A #14-1/031836 S/F