This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
INDOOR UNIT FEATURES• Ducted air handler provides a solution to cool and heat large zones• Highly efficient totally enclosed ECM motor• Selectable external static pressure: 0.30, 0.50 and 0.80 in.WG with 3 fan speeds at each static setting• 1 inch R4.2 fiberglass free insulation reduces condensation and boosts efficiency• Positive pressure cabinet with air leakage of less than 1.0% at 1.0 in.WG• Unique blow through design allows simple coil cleaning when the blower is removed• Multi-position installation: horizontal (left or right), vertical (up or down). For downflow configurations, the CMA-1 is recommended for proper
management of condensate to prevent water blow-off in certain conditions• Optional electric heat kit for additional heat capacity• Optional humidifier control and ERV control• Multiple control options available:
○ kumo cloud® smart device app for remote access ○ Third-party interface options ○ Wired or wireless controllers
OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Wide heating range: heating performance down to -13°F (average of 80% heating capacity)• High speed heating at start up: Hyper-Heating INVERTER® reduces the time for heating at start up by about half compared to standard models• Power receiver pre-charged with refrigerant volume for piping length up to 100 ft.• High pressure/temperature protection• Built-in base pan heater• Flash injection circuit provides efficient high heating capacities at low ambient temperatures
PVA-A42AA7 & PUZ-HA42NKA142,000 BTU/H MULTI-POSITION AIR HANDLER
Maximum Capacity BTU/H 42,000Rated Capacity BTU/H 42,000Minimum Capacity BTU/H 17,000Maximum Power Input W 3,960Rated Power Input W 3,960Moisture Removal Pints/h 5.3Sensible Heat Factor 0.86Power Factor % 92.0/92.0
Heating at 47°F2
Maximum Capacity BTU/H 54,000Rated Capacity BTU/H 48,000Minimum Capacity BTU/H 23,900Maximum Power Input W 4,570Rated Power Input W 3,850Power Factor % 92.0/92.0
Heating at 17°F3
Maximum Capacity BTU/H 48,000Rated Capacity BTU/H 38,500Maximum Power Input W 6,635Rated Power Input W 4,925
Heating at 5°F4Maximum Capacity BTU/H 48,000Maximum Power Input W 6,865
Heating at -13°F7 Maximum Capacity BTU/H 38,400
Efficiency
SEER 15.4EER1 10.6HSPF [IV] 10.0COP at 47°F2 3.7COP at 17°F at Maximum Capacity3 2.1COP at 5°F at Maximum Capacity4 1.9COP at -13°F at Maximum Capacity7 1.6ENERGY STAR® Certified No
Electrical
Voltage, Phase, Frequency 208/230, 1, 60Guaranteed Voltage Range V AC 187 - 253Voltage: Indoor - Outdoor, S1-S2 V AC 208/230Voltage: Indoor - Outdoor, S2-S3 V DC 24Short-circuit Current Rating [SCCR] kA 5Recommended Fuse/Breaker Size (Oudoor) A 40Recommended Wire Size [Indoor - Outdoor] AWG 14
Indoor Unit
MCA A 5.63Fan Motor Full Load Amperage A 4.50Fan Motor Output W 430Airflow Rate at Cooling, Dry CFM 1040–1262–1485Airflow Rate at Heating, Dry CFM 1040–1262–1485Sound Pressure Level [Cooling] dB[A] 36–40–44Sound Pressure Level [Heating] dB[A] 36–40–44External Static Pressure in.WG 0.30–0.5–0.8Drain Pipe Size In. [mm] 3/4 FPT [19.05]Coating on Heat Exchanger —External Finish Color Galvanized steel cabinet-Powder coated Slate GrayUnit Dimensions W x D x H: In. [mm] 25 x 21-5/8 x 59-1/2 [635 x 548 x 1511]Package Dimensions W x D x H: In. [mm] 13-7/16 x 34-11/16 x 65 [340 x 880 x 1,650]Unit Weight Lbs. [kg] 211 [96]Package Weight Lbs. [kg] 243 [110]
Indoor Unit Operating Temperature Range
Cooling Intake Air Temp [Maximum / Minimum]* °F 95 DB, 71 WB / 67 DB, 57 WBHeating Intake Air Temp [Maximum / Minimum] °F 80 DB / 70 DB
NOTES:AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB(Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
» Wind baffles required to operate below 23°F DB in cooling mode. » Cooling-only system with wind baffle: -40°F - 115°F. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):• System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SPECIFICATIONS: PVA-A42AA7 & PUZ-HA42NKA1test
Outdoor Unit
MCA A 36.0MOCP A 44Fan Motor Output W 74Airflow Rate CFM 3319/3319Refrigerant Control LEVDefrost Method Reverse CycleSound Pressure Level, Cooling1 dB(A) 49Sound Pressure Level, Heating2 dB(A) 51Compressor Type ScrollCompressor Model ANB42FJTMTCompressor Rated Load Amps A 19.0Compressor Locked Rotor Amps A 28.0Compressor Oil Type // Charge oz. FVC68D // 1.7,57External Finish Color Ivory Munsell 3Y 7.8/1.1Base Pan Heater Built-inUnit Dimensions W x D x H: In. [mm] 41-5/16 x 14-3/16 x 52-11/16 [1050 x 360 x 1338]Package Dimensions W x D x H: In. [mm] 43 x 18 x 57 [1110 x 480 x 1440]Unit Weight Lbs. [kg] 283 [128]Package Weight Lbs. [kg] 307 [139]
*Outdoor Unit Operating Temperature Range (Cooling Air Temp (Maximum / Minimum)):• Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
» Wind baffles required to operate below 23°F DB in cooling mode. » Cooling-only system with wind baffle: -40°F - 115°F. » Heat pump system with wind baffle: 0°F - 115°F. » Refer to wind baffle documentation for further information.
**Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):• System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
3-Pin Connector PAC-715ADBACnet® and Modbus Interface PAC-UKPRC001-CN-1CN24 Relay Kit CN24RELAY-KIT-CM3Connector cable for remote display PAC-SA88HA-EPIT Extender PAC-WHS01IE-Ekumo station® for kumo cloud® PAC-WHS01HC-ELockdown bracket for remote controller RCMKP1CBRemote Operation Adapter‡ PAC-SF40RM-EThermostat Interface PAC-US444CN-1USNAP Adapter PAC-WHS01UP-E
Remote Sensor
Flush Mount Temperature Sensor PAC-USSEN001-FM-1Remote Temperature Sensor PAC-SE41TS-EWireless temperature and humitity sensor for kumo cloud® PAC-USWHS003-TH-1
Wired Remote Controller
Airzone ZBS Wired Blueface Principal Controller White AZZBSBLUEFACECBAirzone ZBS Wired Lite Controller White AZZBSLITECBAirzone ZBS Wired Think Controller White AZZBSTHINKCBAirzone ZBS Wireless Lite Controller White AZZBSLITERBAirzone ZBS Wireless Think Controller White AZZBSTHINKRBDeluxe Wired MA Remote Controller† PAR-40MAAUSimple MA Remote Controller† PAC-YT53CRAU-JTouch MA Controller† PAR-CT01MAU-SB
Wireless Remote Controller
kumo touch™ RedLINK™ Wireless Controller MHK2Wireless MA Receiver PAR-FA32MA-WWireless MA Remote Controller PAR-FL32MA-EWireless Remote Contoller PAR-SL100A-E
Condensate Blue Diamond Sensor Extension Cable — 15 Ft. C13-103
Control Wire20/2PR, 1PR shielded + 1PR plenum wire for Airzone, 100 ft reel CW2042S2-10020/2PR, shielded + 1PR plenum wire for Airzone, 500 ft reel CW2042S2-500
Disconnect Switch(30A/600V/UL) [fits 2” X 4” utility box] - Black TAZ-MS303(30A/600V/UL) [fits 2” X 4” utility box] - White TAZ-MS303W
Downflow Kit Condensate Management Kit for downflow installation CMA-1Electric Heat Lockout Electric Heat Lockout ETC-211000-MIT
Electric Kit Heats
10kW Electric Heater EH10-MPA-LB15kW Electric Heater EH15-MPAS-LB17kW Electric Heater EH17-MPAS-LB
Lineset
10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-10100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-10015’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-1530’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-3050’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-5065’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation) MPLS385812T-65
Terminal Block Separate Terminal Power Block SPTB1
NOTES:‡PAC-SF40RM-E (Unable to use with wireless remote controller)
Mounting Pad Condensing Unit Mounting Pad: 24” x 42” x 3” ULTRILITE2Optional Defrost Heater Optional Defrost Heater PAC-SJ20BH-E
Stand
18” Dual Fan Stand QSMS1802M24” Dual Fan Stand QSMS2402MCondenser Wall Bracket QSWB2000M-1Condenser Wall Bracket -Stainless Steel Finish QSWBSSOutdoor Unit Stand — 12” High QSMS1202M
Wind Baffle Front Wind Baffle WB-PA3 (two pieces are required)