PV Module String Sizing for Solectria Renewables PVI 13KW & PVI 15KW grid tied inverters. See bottom for step-by-step instructions Note that these are suggested configurations only. Verify all the actual site temperature extremes and conditions will yield voltages and power levels within the specifications of the inverter and other components used in the system. See bottom of chart for weblink to temperature data in your area. The Vocv & Vmpt values given in the tables use module manufacturers' ratings. Cell temp rise above ambient do not include effects of roofs or voltage drop through your wiring. Note that the inverter's maximum continuous AC power is limited to its 13.2 kW AC or 15.0 kW AC output rating. Also, refer to the inverter AC output power versus input voltage and current in the Technical Data section of the Installation and Operation Manual locat http://www.solren.com/custservice/manuals.html CEC, PTC AC system power ratings are based on PV module PTC power rating and PTC efficiencies of the PVI 13KW and PVI 15KW inverters. PTC ratings are based on the 480VAC versions (208VAC versions are 0.5% lower). Datasheets: http://www.solren.com/products/pwreleccomp.html Last updated:8/14/2009 Module Manufacturer Aleo Solar Module Model aleo S_18 | 230 Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OK Voltage @ MPT (STC) 29.1 VDC PTC Power Rating 204.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 7.9 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous output Current, short circuit 8.44 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC) OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F Modules total in array 50 60 70 80 55 66 77 88 Modules per string 10 10 10 10 11 11 11 11 Strings in Parallel 5 6 7 8 5 6 7 8 Voltage @ MPT (STC) 291.0 291.0 291.0 291.0 320.1 320.1 320.1 320.1 Vmpt @ max amb temp (30C, 86F amb) 250.1 250.1 250.1 250.1 275.1 275.1 275.1 275.1 Vmpt @ max amb temp (35C, 95F amb) 243.9 243.9 243.9 243.9 268.3 268.3 268.3 268.3 Vmpt @ max amb temp (40C, 104F amb) 237.7 237.7 237.7 237.7 261.4 261.4 261.4 261.4 Vmpt @ max amb temp (45C, 113F amb) 231.5 231.5 231.5 231.5 254.6 254.6 254.6 254.6 Vmpt @ max amb temp (50C, 122F amb 225.3 225.3 225.3 225.3 247.8 247.8 247.8 247.8 OCV @ 25 deg C cells 366.0 366.0 366.0 366.0 402.6 402.6 402.6 402.6 OCV @ coldest temp (-40C, -40F amb) 446.6 446.6 446.6 446.6 491.3 491.3 491.3 491.3 OCV @ coldest temp (-30C, -22F amb) 434.2 434.2 434.2 434.2 477.6 477.6 477.6 477.6 OCV @ coldest temp (-20C, -4F amb) 421.8 421.8 421.8 421.8 464.0 464.0 464.0 464.0 OCV @ coldest temp (-10C, 14F amb) 409.4 409.4 409.4 409.4 450.3 450.3 450.3 450.3 OCV @ coldest temp ( 0C, 32F amb) 397.0 397.0 397.0 397.0 436.7 436.7 436.7 436.7 Power @ MPT (STC) 11500 13800 16100 18400 12650 15180 17710 20240 PTC AC system power rating 9667 11601 13534 15468 10634 12761 14888 17015 Suggested Inverter PVI 13KW PVI 13KW PVI 15KW PVI 15KW PVI 13KW PVI 13KW PVI 15KW PVI 15KW Module Manufacturer Aleo Solar Module Model aleo S_18 | 225 Power @ MPT 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OK Voltage @ MPT (STC) 28.9 VDC PTC Power Rating 200.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 7.78 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous output Current, short circuit 8.34 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC) OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F Modules total in array 50 60 70 80 55 66 77 88 Modules per string 10 10 10 10 11 11 11 11 Strings in Parallel 5 6 7 8 5 6 7 8 Voltage @ MPT (STC) 289.0 289.0 289.0 289.0 317.9 317.9 317.9 317.9 Vmpt @ max amb temp (30C, 86F amb) 248.1 248.1 248.1 248.1 272.9 272.9 272.9 272.9 Vmpt @ max amb temp (35C, 95F amb) 241.9 241.9 241.9 241.9 266.1 266.1 266.1 266.1 Vmpt @ max amb temp (40C, 104F amb) 235.7 235.7 235.7 235.7 259.2 259.2 259.2 259.2 Vmpt @ max amb temp (45C, 113F amb) 229.5 229.5 229.5 229.5 252.4 252.4 252.4 252.4 Vmpt @ max amb temp (50C, 122F amb 223.3 223.3 223.3 223.3 245.6 245.6 245.6 245.6 OCV @ 25 deg C cells 364.0 364.0 364.0 364.0 400.4 400.4 400.4 400.4 OCV @ coldest temp (-40C, -40F amb) 444.6 444.6 444.6 444.6 489.1 489.1 489.1 489.1 OCV @ coldest temp (-30C, -22F amb) 432.2 432.2 432.2 432.2 475.4 475.4 475.4 475.4 OCV @ coldest temp (-20C, -4F amb) 419.8 419.8 419.8 419.8 461.8 461.8 461.8 461.8 OCV @ coldest temp (-10C, 14F amb) 407.4 407.4 407.4 407.4 448.1 448.1 448.1 448.1 OCV @ coldest temp ( 0C, 32F amb) 395.0 395.0 395.0 395.0 434.5 434.5 434.5 434.5 Power @ MPT (STC) 11250 13500 15750 18000 12375 14850 17325 19800 PTC AC system power rating 9450 11340 13230 15120 10395 12474 14553 16632 Suggested Inverter PVI 13KW PVI 13KW PVI 15KW PVI 15KW PVI 13KW PVI 13KW PVI 15KW PVI 15KW Module Manufacturer Aleo Solar Module Model aleo S_18 | 220 Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OK Voltage @ MPT (STC) 28.7 VDC PTC Power Rating 195.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 7.65 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous output Current, short circuit 8.24 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC) OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F Modules total in array 60 70 80 90 55 66 77 88 Modules per string 10 10 10 10 11 11 11 11 Strings in Parallel 6 7 8 9 5 6 7 8 Voltage @ MPT (STC) 287.0 287.0 287.0 287.0 315.7 315.7 315.7 315.7 Vmpt @ max amb temp (30C, 86F amb) 246.4 246.4 246.4 246.4 271.1 271.1 271.1 271.1 Vmpt @ max amb temp (35C, 95F amb) 240.3 240.3 240.3 240.3 264.3 264.3 264.3 264.3 Vmpt @ max amb temp (40C, 104F amb) 234.1 234.1 234.1 234.1 257.5 257.5 257.5 257.5 Vmpt @ max amb temp (45C, 113F amb) 228.0 228.0 228.0 228.0 250.8 250.8 250.8 250.8 Vmpt @ max amb temp (50C, 122F amb 221.8 221.8 221.8 221.8 244.0 244.0 244.0 244.0 OCV @ 25 deg C cells 363.0 363.0 363.0 363.0 399.3 399.3 399.3 399.3 OCV @ coldest temp (-40C, -40F amb) 443.0 443.0 443.0 443.0 487.2 487.2 487.2 487.2 OCV @ coldest temp (-30C, -22F amb) 430.7 430.7 430.7 430.7 473.7 473.7 473.7 473.7 OCV @ coldest temp (-20C, -4F amb) 418.4 418.4 418.4 418.4 460.2 460.2 460.2 460.2 OCV @ coldest temp (-10C, 14F amb) 406.1 406.1 406.1 406.1 446.7 446.7 446.7 446.7 OCV @ coldest temp ( 0C, 32F amb) 393.8 393.8 393.8 393.8 433.1 433.1 433.1 433.1 Power @ MPT (STC) 13200 15400 17600 19800 12100 14520 16940 19360 PTC AC system power rating 11085 12932 14780 16627 10161 12193 14226 16258 Suggested Inverter PVI 13KW PVI 13KW PVI 15KW PVI 15KW PVI 13KW PVI 13KW PVI 15KW PVI 15KW Module Manufacturer Aleo Solar Module Model aleo S_18 | 215 Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OK Voltage @ MPT (STC) 28.6 VDC PTC Power Rating 190.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 7.53 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous output Current, short circuit 8.13 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC) OCV @ 25 deg C cells 36.1 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F Modules total in array 60 70 80 90 55 66 77 88 Modules per string 10 10 10 10 11 11 11 11 Strings in Parallel 6 7 8 9 5 6 7 8 Voltage @ MPT (STC) 286.0 286.0 286.0 286.0 314.6 314.6 314.6 314.6 Vmpt @ max amb temp (30C, 86F amb) 245.4 245.4 245.4 245.4 270.0 270.0 270.0 270.0 Vmpt @ max amb temp (35C, 95F amb) 239.3 239.3 239.3 239.3 263.2 263.2 263.2 263.2 Vmpt @ max amb temp (40C, 104F amb) 233.1 233.1 233.1 233.1 256.4 256.4 256.4 256.4 Vmpt @ max amb temp (45C, 113F amb) 227.0 227.0 227.0 227.0 249.7 249.7 249.7 249.7 Vmpt @ max amb temp (50C, 122F amb 220.8 220.8 220.8 220.8 242.9 242.9 242.9 242.9 OCV @ 25 deg C cells 361.0 361.0 361.0 361.0 397.1 397.1 397.1 397.1 OCV @ coldest temp (-40C, -40F amb) 441.0 441.0 441.0 441.0 485.0 485.0 485.0 485.0 OCV @ coldest temp (-30C, -22F amb) 428.7 428.7 428.7 428.7 471.5 471.5 471.5 471.5 OCV @ coldest temp (-20C, -4F amb) 416.4 416.4 416.4 416.4 458.0 458.0 458.0 458.0 OCV @ coldest temp (-10C, 14F amb) 404.1 404.1 404.1 404.1 444.5 444.5 444.5 444.5 OCV @ coldest temp ( 0C, 32F amb) 391.8 391.8 391.8 391.8 430.9 430.9 430.9 430.9 Power @ MPT (STC) 12900 15050 17200 19350 11825 14190 16555 18920 PTC AC system power rating 10824 12628 14432 16236 9922 11906 13891 15875 Suggested Inverter PVI 13KW PVI 13KW PVI 15KW PVI 15KW PVI 13KW PVI 13KW PVI 15KW PVI 15KW Module Manufacturer Aleo Solar Module Model aleo S_18 | 210 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OK Voltage @ MPT (STC) 28.4 VDC PTC Power Rating 186.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 7.41 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous output Current, short circuit 8.03 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC) OCV @ 25 deg C cells 35.9 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F Modules total in array 60 70 80 90 55 66 77 88 Modules per string 10 10 10 10 11 11 11 11 Strings in Parallel 6 7 8 9 5 6 7 8 Voltage @ MPT (STC) 284.0 284.0 284.0 284.0 312.4 312.4 312.4 312.4 Vmpt @ max amb temp (30C, 86F amb) 243.7 243.7 243.7 243.7 268.1 268.1 268.1 268.1 Vmpt @ max amb temp (35C, 95F amb) 237.6 237.6 237.6 237.6 261.4 261.4 261.4 261.4 Vmpt @ max amb temp (40C, 104F amb) 231.5 231.5 231.5 231.5 254.7 254.7 254.7 254.7 Vmpt @ max amb temp (45C, 113F amb) 225.4 225.4 225.4 225.4 248.0 248.0 248.0 248.0 Vmpt @ max amb temp (50C, 122F amb 219.3 219.3 219.3 219.3 241.3 241.3 241.3 241.3 OCV @ 25 deg C cells 359.0 359.0 359.0 359.0 394.9 394.9 394.9 394.9 OCV @ coldest temp (-40C, -40F amb) 438.3 438.3 438.3 438.3 482.1 482.1 482.1 482.1 OCV @ coldest temp (-30C, -22F amb) 426.1 426.1 426.1 426.1 468.7 468.7 468.7 468.7 OCV @ coldest temp (-20C, -4F amb) 413.9 413.9 413.9 413.9 455.3 455.3 455.3 455.3 OCV @ coldest temp (-10C, 14F amb) 401.7 401.7 401.7 401.7 441.9 441.9 441.9 441.9 OCV @ coldest temp ( 0C, 32F amb) 389.5 389.5 389.5 389.5 428.5 428.5 428.5 428.5 Power @ MPT (STC) 12600 14700 16800 18900 11550 13860 16170 18480 PTC AC system power rating 10569 12330 14092 15853 9688 11626 13563 15501 Suggested Inverter PVI 13KW PVI 13KW PVI 15KW PVI 15KW PVI 13KW PVI 13KW PVI 15KW PVI 15KW
65
Embed
PV Module String Sizing for Solectria Renewables PVI 13KW & PVI 15KW … · PV Module String Sizing for Solectria Renewables PVI 13KW & PVI 15KW grid tied inverters. See bottom for
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
PV Module String Sizing for Solectria Renewables PVI 13KW & PVI 15KW grid tied inverters. See bottom for step-by-step instructions
Note that these are suggested configurations only. Verify all the actual site temperature extremes and conditions will yield voltages and power levels within the specifications of the inverter and other components used in the system.
See bottom of chart for weblink to temperature data in your area. The Vocv & Vmpt values given in the tables use module manufacturers' ratings. Cell temp rise above ambient do not include effects of roofs or voltage drop through your wiring.
Note that the inverter's maximum continuous AC power is limited to its 13.2 kW AC or 15.0 kW AC output rating. Also, refer to the inverter AC output power versus input voltage and current in the Technical Data section of the Installation and Operation
Manual locathttp://www.solren.com/custservice/manuals.htmlCEC, PTC AC system power ratings are based on PV module PTC power rating and PTC efficiencies of the PVI 13KW and PVI 15KW inverters. PTC ratings are based on the 480VAC versions (208VAC versions are 0.5% lower).
Datasheets: http://www.solren.com/products/pwreleccomp.htmlLast updated:8/14/2009 Module Manufacturer Aleo SolarModule Model aleo S_18 | 230 Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.1 VDC PTC Power Rating 204.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.9 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.44 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Aleo SolarModule Model aleo S_18 | 225 Power @ MPT 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.9 VDC PTC Power Rating 200.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.78 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.34 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Aleo SolarModule Model aleo S_18 | 220 Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.7 VDC PTC Power Rating 195.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.65 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.24 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Aleo SolarModule Model aleo S_18 | 215 Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.6 VDC PTC Power Rating 190.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.53 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.13 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.1 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Aleo SolarModule Model aleo S_18 | 210 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.4 VDC PTC Power Rating 186.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.41 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.03 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.9 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Alpha 230W (by Ningbo)Module Model TDB125x125-96-P (230W) Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 46.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.92 ADC Temp Coeff of Vmpt 0.205 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.205 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 58.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 220W (by Ningbo)Module Model TDB125x125-96-P (220W) Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 46.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.74 ADC Temp Coeff of Vmpt 0.204 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.18 ADC Temp Coeff of Vocv 0.204 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 58.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 210W (by Ningbo)Module Model TDB125x125-96-P (210W) Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 46 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.57 ADC Temp Coeff of Vmpt 0.202 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.05 ADC Temp Coeff of Vocv 0.202 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 57.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 180W (by Ningbo)Module Model TDB125x125-72-P (180W) Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.08 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.53 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 175W (by Ningbo)Module Model TDB125x125-72-P (175W) Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 154.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.96 ADC Temp Coeff of Vmpt 0.154 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.48 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 170W (by Ningbo)Module Model TDB125x125-72-P (170W) Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 149.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.86 ADC Temp Coeff of Vmpt 0.154 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.36 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 165W (by Ningbo)Module Model TDB125x125-72-P (165W) Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.8 VDC PTC Power Rating 145.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.74 ADC Temp Coeff of Vmpt 0.1533 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.26 ADC Temp Coeff of Vocv 0.1533 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 160W (by Ningbo)Module Model TDB125x125-72-P (160W) Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.6 VDC PTC Power Rating 140.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.63 ADC Temp Coeff of Vmpt 0.153 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.19 ADC Temp Coeff of Vocv 0.153 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Alpha 150W (by Ningbo)Module Model TDB125x125-72-P (150W) Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.2 VDC PTC Power Rating 131.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.39 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Astro PowerModule Model AP 1206 Power @ MPT 120.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.9 VDC PTC Power Rating 106.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.08 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.7 ADC Temp Coeff of Vocv 0.08 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Atlantis EnergyModule Model Sunslate-A Power @ MPT 13.3 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 2.93 VDC PTC Power Rating 11.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.54 ADC Temp Coeff of Vmpt 0.0158 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.84 ADC Temp Coeff of Vocv 0.0158 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 3.91 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
>>>> NOTE >>>> 104 slate strings best for hot climates where the coldest ambient temp does not drop below 0C (32F) <<<< NOTE <<<<
Module Manufacturer Atlantis EnergyModule Model Sunslate-Q Power @ MPT 14.3 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 3.06 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.66 ADC Temp Coeff of Vmpt 0.012 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.14 ADC Temp Coeff of Vocv 0.012 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 3.7 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer BP SolarModule Model SX 3200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.5 VDC PTC Power Rating 177.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.16 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.7 ADC Temp Coeff of Vocv 0.111 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model SX 3195 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.4 VDC PTC Power Rating 173.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.96 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.6 ADC Temp Coeff of Vocv 0.111 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.7 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model SX 3190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.3 VDC PTC Power Rating 168.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.82 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.111 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model SX 3175 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.1 VDC PTC Power Rating 155.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.85 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 175 I Power @ MPT (STC) 175 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 155.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.9 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 4175 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.7 VDC PTC Power Rating 155.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.9 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model SX 170B Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.4 VDC PTC Power Rating 150.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.8 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 4170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.6 VDC PTC Power Rating 150.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.78 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model SX 160B Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 142.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.6 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.8 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 3160 Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.1 VDC PTC Power Rating 142.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.55 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.8 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 3150 Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.5 VDC PTC Power Rating 133.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.35 ADC Temp Coeff of Vmpt 0.16 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.75 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer BP SolarModule Model BP 3125 Power @ MPT 125.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.5 VDC PTC Power Rating 110.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.08 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.54 ADC Temp Coeff of Vocv 0.08 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.1 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Canadian Solar Inc. * - PTC power rating unavailableModule Model CS6P-240 Power @ MPT 240.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.91 ADC Temp Coeff of Vmpt 0.13 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.61 ADC Temp Coeff of Vocv 0.13 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-230 Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.8 VDC PTC Power Rating 204.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.71 ADC Temp Coeff of Vmpt 0.129 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.34 ADC Temp Coeff of Vocv 0.128 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-220 Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.3 VDC PTC Power Rating 195.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.52 ADC Temp Coeff of Vmpt 0.128 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.09 ADC Temp Coeff of Vocv 0.128 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-210 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.9 VDC PTC Power Rating 186.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.26 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.91 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.9 VDC PTC Power Rating 177.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.93 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.68 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.8 VDC PTC Power Rating 168.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.6 ADC Temp Coeff of Vmpt 0.126 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.33 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.7 VDC PTC Power Rating 159.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.26 ADC Temp Coeff of Vmpt 0.126 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.98 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.9 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS5A-180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.4 VDC PTC Power Rating 157.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.23 ADC Temp Coeff of Vmpt 0.158 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.7 ADC Temp Coeff of Vocv 0.158 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS6P-170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.7 VDC PTC Power Rating 150.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.93 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.62 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Canadian Solar Inc.Module Model CS5A-170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.4 VDC PTC Power Rating 148.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.95 ADC Temp Coeff of Vmpt 0.158 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.38 ADC Temp Coeff of Vocv 0.158 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer CEEGModule Model SST 190-72M Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.2 VDC PTC Power Rating 163.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.25 ADC Temp Coeff of Vmpt 0.134 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.5 ADC Temp Coeff of Vocv 0.134 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 45 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer CEEGModule Model SST 185-72M Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 158.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.17 ADC Temp Coeff of Vmpt 0.134 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.48 ADC Temp Coeff of Vocv 0.134 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer CEEGModule Model SST 180-72M Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.4 VDC PTC Power Rating 154.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.09 ADC Temp Coeff of Vmpt 0.134 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.134 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer CEEGModule Model SST 170-72M Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 145.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.83 ADC Temp Coeff of Vmpt 0.164 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.29 ADC Temp Coeff of Vocv 0.164 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 51 deg C 123.8 deg F
Module Manufacturer Centennial SolarModule Model CS 230 Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.1 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.64 ADC Temp Coeff of Vmpt 0.138 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.48 ADC Temp Coeff of Vocv 0.138 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Centennial SolarModule Model CS 220 Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.1 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.31 ADC Temp Coeff of Vmpt 0.138 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.138 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Centennial SolarModule Model CS 130 Power @ MPT 130.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.89 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.27 ADC Temp Coeff of Vmpt 0.0726 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.77 ADC Temp Coeff of Vocv 0.0726 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.01 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Centron SolarModule Model CS-P-280-DJ Power @ MPT 280.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.93 ADC Temp Coeff of Vmpt 0.153 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.76 ADC Temp Coeff of Vocv 0.153 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.77 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Centron SolarModule Model CS-S-180-DJ Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.97 ADC Temp Coeff of Vmpt 0.15 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.36 ADC Temp Coeff of Vocv 0.15 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Centron SolarModule Model CS-S-175-DJ Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.89 ADC Temp Coeff of Vmpt 0.15 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.25 ADC Temp Coeff of Vocv 0.15 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Day4 EnergyModule Model 48MC 180W Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.7 VDC PTC Power Rating 160.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.11 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.11 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.4 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Day4 EnergyModule Model 48MC 175W Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.4 VDC PTC Power Rating 156.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.48 ADC Temp Coeff of Vmpt 0.11 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.05 ADC Temp Coeff of Vocv 0.11 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.2 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Day4 EnergyModule Model 48MC 170W Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.04 VDC PTC Power Rating 151.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.38 ADC Temp Coeff of Vmpt 0.11 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.9 ADC Temp Coeff of Vocv 0.11 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 28.8 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer EPV SolarModule Model EPV-50 Power @ MPT 50.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 45 VDC PTC Power Rating 47.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.12 ADC Temp Coeff of Vmpt 0.168 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.41 ADC Temp Coeff of Vocv 0.168 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 60 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F *NOTC is estimated
Module Manufacturer EPVModule Model EPV-53 Power @ MPT 53.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 45 VDC PTC Power Rating 51.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.18 ADC Temp Coeff of Vmpt 0.168 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.47 ADC Temp Coeff of Vocv 0.168 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 60 VDC NOCT (nom. cell temp) 45 deg C 113 deg F *NOTC is estimated
Module Manufacturer EPVModule Model EPV-42 Power @ MPT 42.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 45 VDC PTC Power Rating 40.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 0.94 ADC Temp Coeff of Vmpt 0.168 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.18 ADC Temp Coeff of Vocv 0.168 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 60 VDC NOCT (nom. cell temp) 45 deg C 113 deg F *NOTC is estimated
Module Manufacturer EPVModule Model EPV-40 Power @ MPT 40.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 44 VDC PTC Power Rating 38.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 0.92 ADC Temp Coeff of Vmpt 0.168 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.17 ADC Temp Coeff of Vocv 0.168 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 59 VDC NOCT (nom. cell temp) 45 deg C 113 deg F *NOTC is estimated
Module Manufacturer ET SolarModule Model ET-M572185 Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.3 VDC PTC Power Rating 165.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.09 ADC Temp Coeff of Vmpt 0.117 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.8 ADC Temp Coeff of Vocv 0.117 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.6 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.95 ADC Temp Coeff of Vmpt 0.177 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.61 ADC Temp Coeff of Vocv 0.177 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.6 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572175 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.83 ADC Temp Coeff of Vmpt 0.176 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.5 ADC Temp Coeff of Vocv 0.176 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.3 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.1 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.71 ADC Temp Coeff of Vmpt 0.175 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.175 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572165 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.6 ADC Temp Coeff of Vmpt 0.175 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.19 ADC Temp Coeff of Vocv 0.175 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.1 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572160 Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.49 ADC Temp Coeff of Vmpt 0.174 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.07 ADC Temp Coeff of Vocv 0.174 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.9 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M572155 Power @ MPT 155.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.4 ADC Temp Coeff of Vmpt 0.172 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.98 ADC Temp Coeff of Vocv 0.172 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.3 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M53685 Power @ MPT 85.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 18.05 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.71 ADC Temp Coeff of Vmpt 0.087 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.29 ADC Temp Coeff of Vocv 0.087 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.94 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M53680 Power @ MPT 80.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.64 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.54 ADC Temp Coeff of Vmpt 0.087 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.98 ADC Temp Coeff of Vocv 0.087 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.88 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M53675 Power @ MPT 75.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.31 ADC Temp Coeff of Vmpt 0.086 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.72 ADC Temp Coeff of Vocv 0.086 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.73 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-M53670 Power @ MPT 70.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.9 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.14 ADC Temp Coeff of Vmpt 0.085 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.45 ADC Temp Coeff of Vocv 0.085 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.45 VDC NOCT (nom. cell temp) 44.4 deg C 111.92 deg F
Module Manufacturer ET SolarModule Model ET-P672280 Power @ MPT 280.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.72 VDC PTC Power Rating 250.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.63 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.98 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.78 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672275 Power @ MPT 275.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.72 VDC PTC Power Rating 245.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.49 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.96 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.78 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672270 Power @ MPT 270.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.4 VDC PTC Power Rating 241.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.42 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.9 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.63 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672265 Power @ MPT 265.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.4 VDC PTC Power Rating 236.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.28 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.9 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.63 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672260 Power @ MPT 260.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36 VDC PTC Power Rating 232.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.23 ADC Temp Coeff of Vmpt 0.15 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.79 ADC Temp Coeff of Vocv 0.15 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.49 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672255 Power @ MPT 255.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 227.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.23 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.85 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.88 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672250 Power @ MPT 250.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 223.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.12 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.81 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.88 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672245 Power @ MPT 245.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.95 VDC PTC Power Rating 218.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.01 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.7 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.85 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P672240 Power @ MPT 240.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.95 VDC PTC Power Rating 218.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.88 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.63 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.85 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660240 Power @ MPP (STC) 240.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 8.16 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.55 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660235 Power @ MPP (STC) 235.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.99 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660230 Power @ MPP (STC) 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.82 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660225 Power @ MPP (STC) 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.75 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660220 Power @ MPP (STC) 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.58 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660215 Power @ MPP (STC) 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.41 ADC Temp Coeff of Vmpp 0.125 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660210 Power @ MPP (STC) 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 28.75 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.3 ADC Temp Coeff of Vmpp 0.125 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.99 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660205 Power @ MPP (STC) 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 28.75 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.13 ADC Temp Coeff of Vmpp 0.125 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.8 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P660200 Power @ MPP (STC) 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 28.75 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 6.95 ADC Temp Coeff of Vmpp 0.125 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.71 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654215 Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.54 VDC PTC Power Rating 192.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.81 ADC Temp Coeff of Vmpt 0.115 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.115 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.2 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654210 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.54 VDC PTC Power Rating 187.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.63 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.114 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.83 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654205 Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.3 VDC PTC Power Rating 183.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.5 ADC Temp Coeff of Vmpt 0.113 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.113 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.8 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.21 VDC PTC Power Rating 178.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.36 ADC Temp Coeff of Vmpt 0.113 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.86 ADC Temp Coeff of Vocv 0.113 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.72 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654195 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27 VDC PTC Power Rating 174.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.22 ADC Temp Coeff of Vmpt 0.113 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.98 ADC Temp Coeff of Vocv 0.113 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.75 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.78 VDC PTC Power Rating 169.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.72 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.5 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654185 Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.45 VDC PTC Power Rating 165.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.99 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.7 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.3 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P654180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.45 VDC PTC Power Rating 160.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.81 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.6 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.35 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648195 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.5 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.29 ADC Temp Coeff of Vmpt 0.101 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.101 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.2 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.5 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.08 ADC Temp Coeff of Vmpt 0.101 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.41 ADC Temp Coeff of Vocv 0.101 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.2 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648185 Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.5 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.87 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.41 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.04 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.5 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.66 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.04 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648175 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.2 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.54 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.04 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.39 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648165 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.17 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.9 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648160 Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.95 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.8 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P648155 Power @ MPT 155.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23 VDC PTC Power Rating 0.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.73 ADC Temp Coeff of Vmpt 0.1 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.6 ADC Temp Coeff of Vocv 0.1 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636145 Power @ MPT 145.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.15 ADC Temp Coeff of Vmpt 0.076 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.076 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.96 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636140 Power @ MPT 140.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.95 ADC Temp Coeff of Vmpt 0.076 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.41 ADC Temp Coeff of Vocv 0.076 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.96 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636135 Power @ MPT 135.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.67 ADC Temp Coeff of Vmpt 0.076 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.41 ADC Temp Coeff of Vocv 0.076 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.96 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636130 Power @ MPT 130.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.47 ADC Temp Coeff of Vmpt 0.075 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.075 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.75 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636125 Power @ MPT 125.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.18 ADC Temp Coeff of Vmpt 0.075 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.8 ADC Temp Coeff of Vocv 0.075 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.75 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636120 Power @ MPT 120.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.89 ADC Temp Coeff of Vmpt 0.075 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.63 ADC Temp Coeff of Vocv 0.075 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.75 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer ET SolarModule Model ET-P636115 Power @ MPT 115.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.68 ADC Temp Coeff of Vmpt 0.075 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.55 ADC Temp Coeff of Vocv 0.075 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.75 VDC NOCT (nom. cell temp) 45.3 deg C 113.54 deg F
Module Manufacturer EvergreenModule Model ES-A-210 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 18.7 VDC PTC Power Rating 189.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 11.23 ADC Temp Coeff of Vmpt 0.08 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 12.2 ADC Temp Coeff of Vocv 0.074 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 23.1 VDC NOCT (nom. cell temp) 44.8 deg C 112.64 deg F
Module Manufacturer EvergreenModule Model ES-A-205 Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 18.4 VDC PTC Power Rating 185.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 11.15 ADC Temp Coeff of Vmpt 0.079 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 12.1 ADC Temp Coeff of Vocv 0.073 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.8 VDC NOCT (nom. cell temp) 44.8 deg C 112.64 deg F
Module Manufacturer EvergreenModule Model ES-A-200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 18.1 VDC PTC Power Rating 180.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 11.05 ADC Temp Coeff of Vmpt 0.078 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 12 ADC Temp Coeff of Vocv 0.072 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.5 VDC NOCT (nom. cell temp) 44.8 deg C 112.64 deg F
Module Manufacturer EvergreenModule Model ES-A-195 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.8 VDC PTC Power Rating 175.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 10.96 ADC Temp Coeff of Vmpt 0.077 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 11.9 ADC Temp Coeff of Vocv 0.071 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.3 VDC NOCT (nom. cell temp) 44.8 deg C 112.64 deg F
Module Manufacturer EvergreenModule Model ES-195-RL Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.1 VDC PTC Power Rating 173.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.2 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.15 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 45.9 deg C 114.62 deg F
Module Manufacturer EvergreenModule Model ES-A-190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 171.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 10.96 ADC Temp Coeff of Vmpt 0.075 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 11.8 ADC Temp Coeff of Vocv 0.07 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22 VDC NOCT (nom. cell temp) 44.8 deg C 112.64 deg F
Module Manufacturer EvergreenModule Model ES-190-RL Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.7 VDC PTC Power Rating 168.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.12 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.05 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.8 VDC NOCT (nom. cell temp) 45.9 deg C 114.62 deg F
Module Manufacturer EvergreenModule Model ES-180-RL Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.9 VDC PTC Power Rating 159.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.95 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.78 ADC Temp Coeff of Vocv 0.111 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.6 VDC NOCT (nom. cell temp) 45.9 deg C 114.62 deg F
Module Manufacturer EvergreenModule Model ES-170-RL Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.3 VDC PTC Power Rating 150.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.72 ADC Temp Coeff of Vmpt 0.119 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.55 ADC Temp Coeff of Vocv 0.11 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.4 VDC NOCT (nom. cell temp) 45.9 deg C 114.62 deg F
Module Manufacturer EvergreenModule Model EC-120-GL Power @ MPT 120.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.6 VDC PTC Power Rating 107.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.82 ADC Temp Coeff of Vmpt 0.093 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.68 ADC Temp Coeff of Vocv 0.088 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.5 VDC NOCT (nom. cell temp) 44 deg C 111.2 deg F
Module Manufacturer EvergreenModule Model EC-115-GL Power @ MPT 115.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.1 VDC PTC Power Rating 103.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.73 ADC Temp Coeff of Vmpt 0.09 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.62 ADC Temp Coeff of Vocv 0.087 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.3 VDC NOCT (nom. cell temp) 44 deg C 111.2 deg F
Module Manufacturer EvergreenModule Model EC-110-GL Power @ MPT 110.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17 VDC PTC Power Rating 98.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.47 ADC Temp Coeff of Vmpt 0.09 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.48 ADC Temp Coeff of Vocv 0.087 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.3 VDC NOCT (nom. cell temp) 44 deg C 111.2 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer EvergreenModule Model EC-102-GL Power @ MPT 102.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17 VDC PTC Power Rating 91.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6 ADC Temp Coeff of Vmpt 0.09 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.05 ADC Temp Coeff of Vocv 0.087 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.3 VDC NOCT (nom. cell temp) 44 deg C 111.2 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer First Solar * - PTC Power Rating unavailableModule Model FS-280 Power @ MPT 80.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 71.3 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.12 ADC Temp Coeff of Vmpt 0.235 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.23 ADC Temp Coeff of Vocv 0.235 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 94 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer First SolarModule Model FS-277 Power @ MPT 77.5 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 70.9 VDC PTC Power Rating 73.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.09 ADC Temp Coeff of Vmpt 0.233 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.21 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 93 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer First SolarModule Model FS-275 Power @ MPT 75.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 69.4 VDC PTC Power Rating 70.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.08 ADC Temp Coeff of Vmpt 0.23 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.2 ADC Temp Coeff of Vocv 0.23 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 92 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer First SolarModule Model FS-272 Power @ MPT 72.5 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 67.9 VDC PTC Power Rating 68.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.07 ADC Temp Coeff of Vmpt 0.225 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 90 ADC Temp Coeff of Vocv 0.225 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 89 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer First SolarModule Model FS-270 Power @ MPT 70.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 67.1 VDC PTC Power Rating 66.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 1.04 ADC Temp Coeff of Vmpt 0.222 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.19 ADC Temp Coeff of Vocv 0.222 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 89 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer GE * - PTC Power Rating not available Module Model GEPVp-205-M Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.4 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.8 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.2 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer GEModule Model GEPVp-200-MS Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.3 VDC PTC Power Rating 173.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer GE/AstroPowerModule Model GEPVp-200-M Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.1 VDC PTC Power Rating 178.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.4 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.8 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 34 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer GE/AstroPowerModule Model GEPV-173-MCA (or -MCB) Power @ MPT 173.2 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.1 VDC PTC Power Rating 154.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.9 ADC Temp Coeff of Vmpt 0.13 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.5 ADC Temp Coeff of Vocv 0.13 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer GEModule Model GEPVc-170-MS Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.5 VDC PTC Power Rating 146.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.65 ADC Temp Coeff of Vmpt 0.15 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.15 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.9 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer GE/AstroPowerModule Model GEPV-165-MCA (or -MCB) Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25 VDC PTC Power Rating 146.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.6 ADC Temp Coeff of Vmpt 0.13 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.4 ADC Temp Coeff of Vocv 0.13 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer GE/AstroPowerModule Model GEPV-110-M Power @ MPT 110.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.7 VDC PTC Power Rating 97.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.6 ADC Temp Coeff of Vmpt 0.08 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.4 ADC Temp Coeff of Vocv 0.08 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Gro SolarModule Model ES-155-RL Power @ MPT 155.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24 VDC PTC Power Rating 137.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.46 ADC Temp Coeff of Vmpt 0.118 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.52 ADC Temp Coeff of Vocv 0.118 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer IsofonModule Model I-165 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 148.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 9.48 ADC Temp Coeff of Vmpt 0.063 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 10.14 ADC Temp Coeff of Vocv 0.078 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer IsofonModule Model I-150 Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.6 VDC PTC Power Rating 134.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.35 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.45 ADC Temp Coeff of Vocv 0.156 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer IsofonModule Model I-100 Power @ MPT 100.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 89.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.74 ADC Temp Coeff of Vmpt 0.063 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.54 ADC Temp Coeff of Vocv 0.078 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KanekaModule Model K60 &GSA-60 Power @ MPT 60.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 67 VDC PTC Power Rating 56.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 0.9 ADC Temp Coeff of Vmpt 0.25 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 1.19 ADC Temp Coeff of Vocv 0.25 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 92 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer KyoceraModule Model KD210GX-LP Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.6 VDC PTC Power Rating 184.6 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.9 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.58 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.2 VDC NOCT (nom. cell temp) 49 deg C 120.2 deg F
Module Manufacturer KyoceraModule Model KD205GX-LP Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.6 VDC PTC Power Rating 182.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.71 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.36 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC200GT Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.3 VDC PTC Power Rating 177.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.61 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.21 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC190GT Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.1 VDC PTC Power Rating 167.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.28 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.08 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC187G Power @ MPT 187.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.1 VDC PTC Power Rating 167.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.17 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.96 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KD180GX-LP Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.6 VDC PTC Power Rating 160.0 W estimated orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.63 ADC Temp Coeff of Vmpt 0.109 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.36 ADC Temp Coeff of Vocv 0.109 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC175GT Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.6 VDC PTC Power Rating 154.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.42 ADC Temp Coeff of Vmpt 0.109 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.09 ADC Temp Coeff of Vocv 0.109 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC170GT Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.4 VDC PTC Power Rating 150.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.27 ADC Temp Coeff of Vmpt 0.109 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.03 ADC Temp Coeff of Vocv 0.109 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC167G Power @ MPT 167.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.2 VDC PTC Power Rating 149.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.2 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 28.9 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC158G Power @ MPT 158.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.2 VDC PTC Power Rating 139.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.82 ADC Temp Coeff of Vmpt 0.11 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.58 ADC Temp Coeff of Vocv 0.11 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 28.9 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KD135GX-LP Power @ MPT 135.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.7 VDC PTC Power Rating 119.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.63 ADC Temp Coeff of Vmpt 0.082 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.37 ADC Temp Coeff of Vocv 0.082 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22.1 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC130GT & KC130TM Power @ MPT 130.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.6 VDC PTC Power Rating 115.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.39 ADC Temp Coeff of Vmpt 0.082 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.02 ADC Temp Coeff of Vocv 0.082 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.9 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer KyoceraModule Model KC125G Power @ MPT 125.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.4 VDC PTC Power Rating 111.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.2 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8 ADC Temp Coeff of Vocv 0.084 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.7 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
cool climates only and 5% low voltage tap recommended
Module Manufacturer KyoceraModule Model KC120-1 Power @ MPT 120.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.7 VDC PTC Power Rating 105.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.081 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.45 ADC Temp Coeff of Vocv 0.081 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
cold climates only and 5% low voltage tap recommended
Module Manufacturer KyoceraModule Model KC80 Power @ MPT 80.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.9 VDC PTC Power Rating 70.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.73 ADC Temp Coeff of Vmpt 0.082 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.97 ADC Temp Coeff of Vocv 0.082 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
cold climates only and 5% low voltage tap recommended
Module Manufacturer Matrix / PhotoWattModule Model PW 1650-175/24 (24V version) Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 158.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5 ADC Temp Coeff of Vmpt 0.158 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.158 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Matrix / PhotoWattModule Model PW 1650-165/24 (24V version) Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.4 VDC PTC Power Rating 149.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.8 ADC Temp Coeff of Vmpt 0.158 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.158 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer MitsubishiModule Model PV-UD190MF5 (UD5) Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.7 VDC PTC Power Rating 169.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.71 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.23 ADC Temp Coeff of Vocv 0.106 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.8 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer MitsubishiModule Model PV-UD185MF5 (UD5) Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.4 VDC PTC Power Rating 164.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.58 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.13 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.6 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer MitsubishiModule Model PV-MF185 UD4 Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.4 VDC PTC Power Rating 163.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.58 ADC Temp Coeff of Vmpt 0.106 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.13 ADC Temp Coeff of Vocv 0.106 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.6 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF180 UD4 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.2 VDC PTC Power Rating 160.0 W UD4 is 159W PTC orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.45 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.03 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.4 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF175 UD5 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.9 VDC PTC Power Rating 155.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.32 ADC Temp Coeff of Vmpt 0.083 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.93 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.2 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer MitsubishiModule Model PV-MF175 UD4 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.9 VDC PTC Power Rating 154.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.32 ADC Temp Coeff of Vmpt 0.083 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.93 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.2 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF170 UD4 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.7 VDC PTC Power Rating 149.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.19 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.83 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.9 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF170EB3 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.6 VDC PTC Power Rating 152.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.93 ADC Temp Coeff of Vmpt 0.085 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.38 ADC Temp Coeff of Vocv 0.106 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.6 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF165EB3 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.2 VDC PTC Power Rating 146.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.83 ADC Temp Coeff of Vmpt 0.105 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.36 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.4 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer MitsubishiModule Model PV-MF120EC3 Power @ MPT 120.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.6 VDC PTC Power Rating 107.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.84 ADC Temp Coeff of Vmpt 0.076 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.36 ADC Temp Coeff of Vocv 0.076 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 22 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer Open EnergyModule Model SP450 Power @ MPT 450.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 44.5 VDC PTC Power Rating 402.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 10.2 ADC Temp Coeff of Vmpt 0.15 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 11.3 ADC Temp Coeff of Vocv 0.15 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 53.3 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer REC SolarModule Model 235AE Power @ MPT (STC) 235.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.5 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.9 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model 230AE Power @ MPT (STC) 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.1 VDC PTC Power Rating 200.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.9 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.4 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.8 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model 225AE Power @ MPT (STC) 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.8 VDC PTC Power Rating 196.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.8 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.4 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model 220AE Power @ MPT (STC) 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.4 VDC PTC Power Rating 191.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.8 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.4 ADC Temp Coeff of Vocv 0.124 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model 215AE Power @ MPT (STC) 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28 VDC PTC Power Rating 187.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.7 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model SCM 215 Power @ MPT (STC) 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.3 VDC PTC Power Rating 191.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model SCM 210 (230 Wp) Power @ MPT (STC) 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.5 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8 ADC Temp Coeff of Vmpt 0.104 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.6 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.7 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model SCM 210 (225 Wp) Power @ MPT (STC) 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.4 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.9 ADC Temp Coeff of Vmpt 0.104 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.5 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.7 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model SCM 210 (220 Wp) Power @ MPT (STC) 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.7 ADC Temp Coeff of Vmpt 0.104 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model SCM 210 (215 Wp) Power @ MPT (STC) 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.104 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.2 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model SCM 210 Power @ MPT (STC) 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.5 ADC Temp Coeff of Vmpt 0.104 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer REC SolarModule Model 210AE Power @ MPT (STC) 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.6 VDC PTC Power Rating 182.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.1 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer REC SolarModule Model 205AE Power @ MPT (STC) 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 27.2 VDC PTC Power Rating 178.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SanyoModule Model HIT Power 215N or HIP-215NKHA Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 42 VDC PTC Power Rating 199.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.13 ADC Temp Coeff of Vmpt 0.143 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.61 ADC Temp Coeff of Vocv 0.143 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 51.6 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer SanyoModule Model HIT Power 210N or HIP-210NKHA Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 41.3 VDC PTC Power Rating 194.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.09 ADC Temp Coeff of Vmpt 0.142 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.57 ADC Temp Coeff of Vocv 0.142 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 50.9 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer SanyoModule Model HIT Power 205N or HIP-205NKHA Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 40.7 VDC PTC Power Rating 190.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.05 ADC Temp Coeff of Vmpt 0.14 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.54 ADC Temp Coeff of Vocv 0.14 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 50.3 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Sanyo * - PTC Power Rating not availableModule Model HIT Power 200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.59 ADC Temp Coeff of Vmpt 0.162 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.82 ADC Temp Coeff of Vocv 0.172 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.7 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer SanyoModule Model HIP-200BA19 (200W) Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.8 VDC PTC Power Rating 187.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.59 ADC Temp Coeff of Vmpt 0.172 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.83 ADC Temp Coeff of Vocv 0.172 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.7 VDC NOCT (nom. cell temp) 47.0 deg C 116.6 deg F
Module Manufacturer SanyoModule Model HIP-200BA3 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.8 VDC PTC Power Rating 188.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.59 ADC Temp Coeff of Vmpt 0.162 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.82 ADC Temp Coeff of Vocv 0.172 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.7 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer Sanyo * - PTC Power Rating not availableModule Model HIT Power 195 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.53 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.79 ADC Temp Coeff of Vocv 0.17 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.1 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer SanyoModule Model HIP-195BA19 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.3 VDC PTC Power Rating 181.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.53 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.79 ADC Temp Coeff of Vocv 0.17 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.1 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer SanyoModule Model HIP-195BA3 Power @ MPT 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.3 VDC PTC Power Rating 183.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.53 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.79 ADC Temp Coeff of Vocv 0.17 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.1 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer Sanyo * - PTC Power Rating not availableModule Model HIT Power 190 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.47 ADC Temp Coeff of Vmpt 0.164 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.75 ADC Temp Coeff of Vocv 0.169 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 67.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Sanyo Bifacial Module Values given do not include boosted power from back side of module.Module Model HIP-190DA3 (or DA1, DA2) Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 55.3 VDC PTC Power Rating 178.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.44 ADC Temp Coeff of Vmpt 0.17 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.7 ADC Temp Coeff of Vocv 0.17 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 68.1 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer SanyoModule Model HIP-190BA (or BA1-5) Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54.8 VDC PTC Power Rating 178.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.47 ADC Temp Coeff of Vmpt 0.164 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.75 ADC Temp Coeff of Vocv 0.202 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 67.5 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer SanyoModule Model HIP-186DA3 Power @ MPT 186.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54.8 VDC PTC Power Rating 173.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.4 ADC Temp Coeff of Vmpt 0.079 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.68 ADC Temp Coeff of Vocv 0.079 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 67.5 VDC NOCT (nom. cell temp) 46.6 deg C 115.88 deg F
Module Manufacturer Sanyo (not made since 2004)Module Model HIP-180BA2 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54 VDC PTC Power Rating 169.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 3.33 ADC Temp Coeff of Vmpt 0.164 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 3.65 ADC Temp Coeff of Vocv 0.202 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 66.4 VDC NOCT (nom. cell temp) 44.2 deg C 111.56 deg F
Module Manufacturer Schott SolarModule Model ASE-330-DGF/50 (330W) Power @ MPT 330.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54 VDC PTC Power Rating 297.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.1 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.7 ADC Temp Coeff of Vocv 0.251 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 66.3 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-300-DGF/50-320 Power @ MPT 320.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 51.6 VDC PTC Power Rating 287.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.2 ADC Temp Coeff of Vmpt 0.243 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.8 ADC Temp Coeff of Vocv 0.243 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 64.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-300-DGF/50 (315W, 36V) Power @ MPT 315.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 51.5 VDC PTC Power Rating 283.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.1 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.6 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 61 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-300-DGF/50-310 Power @ MPT 310.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 51.1 VDC PTC Power Rating 278.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.1 ADC Temp Coeff of Vmpt 0.24 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.5 ADC Temp Coeff of Vocv 0.24 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 63.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-300-DGF/50 (300W, 36V) Power @ MPT 300.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 51 VDC PTC Power Rating 269.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.9 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.5 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 61 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-300-DGF/50 (285W, 36V) Power @ MPT 285.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 50 VDC PTC Power Rating 255.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.7 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.3 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 61 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-290 Power @ MPT 290.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 50.1 VDC PTC Power Rating 260.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.8 ADC Temp Coeff of Vmpt 0.190 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.4 ADC Temp Coeff of Vocv 0.238 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 62.5 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-270-DGF/50 (270W, 36V) Power @ MPT 270.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 49.1 VDC PTC Power Rating 241.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.5 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.1 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 61.3 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model ASE-270-DGF/50 (260W, 36V) Power @ MPT 260.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 48.7 VDC PTC Power Rating 232.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.3 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.9 ADC Temp Coeff of Vocv 0.233 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 60.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Schott SolarModule Model Poly 220 Power @ MPP 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.7 VDC PTC Power Rating 193.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.41 ADC Temp Coeff of Vmpp 0.12 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.15 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 47.2 deg C 116.96 deg F
Module Manufacturer Schott SolarModule Model SAPC-175 Power @ MPP 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 35.4 VDC PTC Power Rating 154.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 4.95 ADC Temp Coeff of Vmpp 0.006 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.55 ADC Temp Coeff of Vocv 0.084 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SchucoModule Model SPV 210 SMAU-1 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.3 VDC PTC Power Rating 189.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.98 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.35 ADC Temp Coeff of Vocv 0.112 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.68 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer SchucoModule Model SPV 200 SMAU-1 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.38 VDC PTC Power Rating 180.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.89 ADC Temp Coeff of Vmpt 0.111 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.24 ADC Temp Coeff of Vocv 0.111 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.53 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer Schuco *-Temp Coeff of Vmpt/Vocv are estimatedModule Model S 180-SPU-4 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.2 VDC PTC Power Rating 161.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.45 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.03 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.4 VDC NOCT (nom. cell temp) 46.25 deg C 115.25 deg F
Module Manufacturer Schuco *-Temp Coeff of Vmpt/Vocv are estimatedModule Model S 170-SPU-4 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.7 VDC PTC Power Rating 152.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.19 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.83 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.9 VDC NOCT (nom. cell temp) 46.25 deg C 115.25 deg F
Module Manufacturer Schuco *-Temp Coeff of Vmpt/Vocv are estimatedModule Model S 165-SPU-4 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.4 VDC PTC Power Rating 147.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.06 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.73 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.7 VDC NOCT (nom. cell temp) 46.2 deg C 115.16 deg F
Module Manufacturer SchucoModule Model S 165-SP & SP-2 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.2 VDC PTC Power Rating 152.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.83 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.36 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.4 VDC NOCT (nom. cell temp) 46.2 deg C 115.16 deg F
Module Manufacturer SchucoModule Model S 162-SP Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 24.2 VDC PTC Power Rating 152.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.83 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.36 ADC Temp Coeff of Vocv 0.105 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.4 VDC NOCT (nom. cell temp) 46.2 deg C 115.16 deg F
Module Manufacturer SchucoModule Model S 158-SP Power @ MPT 158.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.6 VDC PTC Power Rating 146.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.68 ADC Temp Coeff of Vmpt 0.112 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.33 ADC Temp Coeff of Vocv 0.104 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 30.1 VDC NOCT (nom. cell temp) 46.2 deg C 115.16 deg F
Module Manufacturer SES Module Model SwissTile Power @ MPT 18.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 3.3 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.61 ADC Temp Coeff of Vmpt 0.0114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.03 ADC Temp Coeff of Vocv 0.0114 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 4.0 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Shanghai Solar Module Model Monocrystalline S-180C Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.0 VDC PTC Power Rating 156.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC). Current @ MPT (STC) 4.86 ADC Temp Coeff of Vmpt 0.154 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.44 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.0 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SharpModule Model ND-V230A1 Power @ MPT (STC) 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.3 VDC PTC Power Rating 203.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.6 ADC Temp Coeff of Vmpt 0.133 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.24 ADC Temp Coeff of Vocv 0.133 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-224U1F (U2) Power @ MPT 224.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.28 VDC PTC Power Rating 197.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.66 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.33 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-220U1F (U2) Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.19 VDC PTC Power Rating 194.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.54 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.24 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-216U2 Power @ MPT 216.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.71 VDC PTC Power Rating 190.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.53 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.35 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-216U1F Power @ MPT 216.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.9 VDC PTC Power Rating 190.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.48 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-208U1 Power @ MPT 208.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.5 VDC PTC Power Rating 183.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.3 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.13 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.1 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-205U1 Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.9 VDC PTC Power Rating 180.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.12 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.91 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.3 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-200U1 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.5 VDC PTC Power Rating 176.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.02 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.82 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.5 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-198U1F Power @ MPT 198.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.3 VDC PTC Power Rating 174.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.52 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.23 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F *Temp coefficients based on estimates
Module Manufacturer SharpModule Model ND-187U1F Power @ MPT 187.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.8 VDC PTC Power Rating 164.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.25 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.99 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.7 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model NT-185U1 (24V module) Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.2 VDC PTC Power Rating 163.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.11 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.75 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.9 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model NT-180U1 (24V module) Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.86 VDC PTC Power Rating 159.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.02 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.6 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.8 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-176U1Y Power @ MPT (STC) 176.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.42 VDC PTC Power Rating 155.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.52 ADC Temp Coeff of Vmpt 0.096 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.22 ADC Temp Coeff of Vocv 0.096 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29.28 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model NT-175U1 (24V module) Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.4 VDC PTC Power Rating 154.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.95 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model NE-170U1 (24V module) Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.8 VDC PTC Power Rating 149.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.9 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.47 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-167U1 (or U3) Power @ MPT 167.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23.5 VDC PTC Power Rating 147.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.1 ADC Temp Coeff of Vmpt 0.096 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.91 ADC Temp Coeff of Vocv 0.096 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer Sharp (discontinued)Module Model NE-165U1 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.6 VDC PTC Power Rating 145.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.77 ADC Temp Coeff of Vmpt 0.144 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.46 ADC Temp Coeff of Vocv 0.144 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.1 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-123U1 (or ND-L3E1U) Power @ MPT 123.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 17.2 VDC PTC Power Rating 108.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.16 ADC Temp Coeff of Vmpt 0.072 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.072 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 21.3 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer SharpModule Model ND-N0ECU (140W) Power @ MPT 140.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 19.95 VDC PTC Power Rating 123.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.02 ADC Temp Coeff of Vmpt 0.084 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.81 ADC Temp Coeff of Vocv 0.084 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 24.85 VDC NOCT (nom. cell temp) 47.5 deg C 117.5 deg F
Module Manufacturer Siemens SolarModule Model SP150-24P Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34 VDC PTC Power Rating 134.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.4 ADC Temp Coeff of Vmpt 0.077 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.8 ADC Temp Coeff of Vocv 0.077 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SilikenModule Model SLK60P6L (233W) Power @ MPT 233.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.6 VDC PTC Power Rating 210.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.86 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.32 ADC Temp Coeff of Vocv 0.127 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.9 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer SilikenModule Model SLK60P6L (215W) Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.0 VDC PTC Power Rating 194.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.42 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.02 ADC Temp Coeff of Vocv 0.127 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar Fabrik SeriesModule Model SF 200A-220 Power @ MPP 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 28.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.7 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) EST purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.15 ADC Temp Coeff of Vocv 0.127 V/degC (Vocv) EST pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Solar Fabrik SeriesModule Model SF 200A-210 Power @ MPP 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 28.1 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.48 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) EST purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.96 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) EST pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Solar Fabrik SeriesModule Model SF 200A-200 Power @ MPP 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 27.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.27 ADC Temp Coeff of Vmpp 0.126 V/degC (Vmpp) EST purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.77 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) EST pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SolarFunModule Model SF190-27 (200W version) Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.7 VDC PTC Power Rating 176.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.49 ADC Temp Coeff of Vmpt 0.101 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.19 ADC Temp Coeff of Vocv 0.125 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SolarFunModule Model SF160-24 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.9 VDC PTC Power Rating 149.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.74 ADC Temp Coeff of Vmpt 0.135 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.12 ADC Temp Coeff of Vocv 0.165 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.5 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Solar PowerModule Model SP 205FP52 Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.8 VDC PTC Power Rating 184.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.95 ADC Temp Coeff of Vmpt 0.101 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.48 ADC Temp Coeff of Vocv 0.101 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.6 VDC NOCT (nom. cell temp) 48.6 deg C 119.48 deg F
Module Manufacturer Solar PowerModule Model SP 200FP12 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 25.41 VDC PTC Power Rating 183.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.87 ADC Temp Coeff of Vmpt 0.113 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.4 ADC Temp Coeff of Vocv 0.113 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.3 VDC NOCT (nom. cell temp) 48.6 deg C 119.48 deg F
Module Manufacturer Solar PowerModule Model SP 170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.97 VDC PTC Power Rating 146.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.86 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.28 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.3 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 245 mono Power @ MPT 245.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.1 VDC PTC Power Rating 0.0 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.14 ADC Temp Coeff of Vmpt 0.123 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.78 ADC Temp Coeff of Vocv 0.123 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37.3 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 240 mono Power @ MPT 240.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 8.02 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.66 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37.1 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 235 mono Power @ MPT 235.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.8 VDC PTC Power Rating 0.0 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.89 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.54 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 230 mono Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.6 VDC PTC Power Rating 0.0 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.76 ADC Temp Coeff of Vmpt 0.122 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.42 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.9 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 225 mono Power @ MPT 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.5 VDC PTC Power Rating 0.0 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.64 ADC Temp Coeff of Vmpt 0.121 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.121 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.8 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World / ShellModule Model SW 220 mono Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.3 VDC PTC Power Rating 0.0 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.51 ADC Temp Coeff of Vmpt 0.121 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.18 ADC Temp Coeff of Vocv 0.121 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar WorldModule Model SW 220 Poly Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.54 ADC Temp Coeff of Vmpt 0.126 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.08 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.6 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar WorldModule Model SW 185 mono Power @ MPT 185.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36 VDC PTC Power Rating 172.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.1 ADC Temp Coeff of Vmpt 0.126 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.5 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.5 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World (Shell)Module Model SW 175 mono/T / SQ175-PC (or -PPower @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 162.7 W 158.3W for mono/P orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.89 ADC Temp Coeff of Vmpt 0.125 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World (Shell)Module Model SW 165 mono/T /SQ165-PC (or -P) Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.3 VDC PTC Power Rating 154.0 W 149.1W for momo/P orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.68 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World (Shell)Module Model SQ160-PC Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 141.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.58 ADC Temp Coeff of Vmpt 0.167 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.9 ADC Temp Coeff of Vocv 0.161 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.5 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World (Shell)Module Model SW 155 mono/T /SQ165-PC (or -P) Power @ MPT 155.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.8 VDC PTC Power Rating 143.8 W 139.9W for momo/P orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.46 ADC Temp Coeff of Vmpt 0.124 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.9 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.6 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Solar World (Shell)Module Model SP150-PC (or -P) Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34 VDC PTC Power Rating 131.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.4 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.8 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.4 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Solar World (Shell)Module Model SP140-PC (or -P) Power @ MPT 140.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33 VDC PTC Power Rating 122.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.25 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 4.7 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SolartechModule Model SPM 230P Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.96 VDC PTC Power Rating 197.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.43 ADC Temp Coeff of Vmpt 0.133 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.97 ADC Temp Coeff of Vocv 0.133 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.95 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 225P Power @ MPT 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.44 VDC PTC Power Rating 193.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.92 ADC Temp Coeff of Vmpt 0.133 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.27 ADC Temp Coeff of Vocv 0.133 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37.08 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 220P Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.2 VDC PTC Power Rating 189.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.32 ADC Temp Coeff of Vmpt 0.133 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.85 ADC Temp Coeff of Vocv 0.133 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.90 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 215P Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.55 VDC PTC Power Rating 184.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.54 ADC Temp Coeff of Vmpt 0.132 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.00 ADC Temp Coeff of Vocv 0.132 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.72 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 210P Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.97 VDC PTC Power Rating 180.10 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.25 ADC Temp Coeff of Vmpt 0.129 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.76 ADC Temp Coeff of Vocv 0.129 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 35.90 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 205P Power @ MPT 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.35 VDC PTC Power Rating 175.7 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.24 ADC Temp Coeff of Vmpt 0.131 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.77 ADC Temp Coeff of Vocv 0.131 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.42 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolonModule Model Blue 220/01 (220W) Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.8 VDC PTC Power Rating 194.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.65 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.3 ADC Temp Coeff of Vocv 0.127 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.40 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolartechModule Model SPM 200P Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.44 VDC PTC Power Rating 171.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.04 ADC Temp Coeff of Vmpt 0.130 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.62 ADC Temp Coeff of Vocv 0.130 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.24 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F *estimated NOCT
Module Manufacturer SolyndraModule Model SL-001-200 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 78.3 VDC PTC Power Rating 189.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.55 ADC Temp Coeff of Vmpt 0.239 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.78 ADC Temp Coeff of Vocv 0.239 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 99.7 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-191 Power @ MPT 191.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 76.1 VDC PTC Power Rating 181.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.51 ADC Temp Coeff of Vmpt 0.236 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.77 ADC Temp Coeff of Vocv 0.236 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 98.2 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-182 Power @ MPT 182.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 73.9 VDC PTC Power Rating 172.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.46 ADC Temp Coeff of Vmpt 0.232 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.76 ADC Temp Coeff of Vocv 0.232 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 96.7 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-173 Power @ MPT 173.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 71.7 VDC PTC Power Rating 163.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.41 ADC Temp Coeff of Vmpt 0.228 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.75 ADC Temp Coeff of Vocv 0.228 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 95.2 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-165 Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 69.6 VDC PTC Power Rating 156.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.37 ADC Temp Coeff of Vmpt 0.225 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.74 ADC Temp Coeff of Vocv 0.225 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 93.9 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-157 Power @ MPT 157.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 67.5 VDC PTC Power Rating 148.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.33 ADC Temp Coeff of Vmpt 0.222 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.73 ADC Temp Coeff of Vocv 0.222 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 92.5 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer SolyndraModule Model SL-001-150 Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 65.7 VDC PTC Power Rating 141.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 2.28 ADC Temp Coeff of Vmpt 0.219 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 2.72 ADC Temp Coeff of Vocv 0.219 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 91.4 VDC NOCT (nom. cell temp) 41.7 deg C 107.06 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model 315 SOLAR PANEL Power @ MPT 315.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54.7 VDC PTC Power Rating 291.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.76 ADC Temp Coeff of Vmpt 0.176 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 6.14 ADC Temp Coeff of Vocv 0.176 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 64.6 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Modules total in array 30 36 42 48 54Modules per string 6 6 6 6 6Strings in Parallel 5 6 7 8 9Voltage @ MPT (STC) 328.2 328.2 328.2 328.2 328.2Vmpt @ max amb temp (30C, 86F amb) 296.5 296.5 296.5 296.5 296.5Vmpt @ max amb temp (35C, 95F amb) 291.2 291.2 291.2 291.2 291.2Vmpt @ max amb temp (40C, 104F amb) 286.0 286.0 286.0 286.0 286.0Vmpt @ max amb temp (45C, 113F amb) 280.7 280.7 280.7 280.7 280.7Vmpt @ max amb temp (50C, 122F amb 275.4 275.4 275.4 275.4 275.4OCV @ 25 deg C cells 387.6 387.6 387.6 387.6 387.6OCV @ coldest temp (-40C, -40F amb) 456.2 456.2 456.2 456.2 456.2OCV @ coldest temp (-30C, -22F amb) 445.7 445.7 445.7 445.7 445.7OCV @ coldest temp (-20C, -4F amb) 435.1 435.1 435.1 435.1 435.1OCV @ coldest temp (-10C, 14F amb) 424.6 424.6 424.6 424.6 424.6OCV @ coldest temp ( 0C, 32F amb) 414.0 414.0 414.0 414.0 414.0Power @ MPT (STC) 9450 11340 13230 15120 17010PTC AC system power rating 8267 9920 11574 13227 14880Suggested Inverter PVI 13KW PVI 13KW PVI 13KW PVI 13KW PVI 15KW
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model 305 SOLAR PANEL Power @ MPT 305.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 54.7 VDC PTC Power Rating 281.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.58 ADC Temp Coeff of Vmpt 0.176 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.96 ADC Temp Coeff of Vocv 0.176 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 64.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Modules total in array 30 36 42 48 54Modules per string 6 6 6 6 6Strings in Parallel 5 6 7 8 9Voltage @ MPT (STC) 328.2 328.2 328.2 328.2 328.2Vmpt @ max amb temp (30C, 86F amb) 296.5 296.5 296.5 296.5 296.5Vmpt @ max amb temp (35C, 95F amb) 291.2 291.2 291.2 291.2 291.2Vmpt @ max amb temp (40C, 104F amb) 286.0 286.0 286.0 286.0 286.0Vmpt @ max amb temp (45C, 113F amb) 280.7 280.7 280.7 280.7 280.7Vmpt @ max amb temp (50C, 122F amb 275.4 275.4 275.4 275.4 275.4OCV @ 25 deg C cells 385.2 385.2 385.2 385.2 385.2OCV @ coldest temp (-40C, -40F amb) 453.8 453.8 453.8 453.8 453.8OCV @ coldest temp (-30C, -22F amb) 443.3 443.3 443.3 443.3 443.3OCV @ coldest temp (-20C, -4F amb) 432.7 432.7 432.7 432.7 432.7OCV @ coldest temp (-10C, 14F amb) 422.2 422.2 422.2 422.2 422.2OCV @ coldest temp ( 0C, 32F amb) 411.6 411.6 411.6 411.6 411.6Power @ MPT (STC) 9150 10980 12810 14640 16470PTC AC system power rating 7972 9566 11161 12755 14350Suggested Inverter PVI 13KW PVI 13KW PVI 13KW PVI 13KW PVI 15KW
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-230 BLK Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 41 VDC PTC Power Rating 213.5 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.61 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.99 ADC Temp Coeff of Vocv 0.1325 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 48.7 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-225 BLK Power @ MPT 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 41 VDC PTC Power Rating 207.1 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.49 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.87 ADC Temp Coeff of Vocv 0.1325 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 48.5 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-220 Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 40 VDC PTC Power Rating 203.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.5 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.9 ADC Temp Coeff of Vocv 0.1368 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 47.8 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-215-BLK Power @ MPT 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 39.8 VDC PTC Power Rating 197.6 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.4 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.8 ADC Temp Coeff of Vocv 0.1368 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 48.3 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-210-WHT Power @ MPT 210.0 W 210 For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 40 VDC PTC Power Rating 193.7 W 190.9 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.25 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.75 ADC Temp Coeff of Vocv 0.1368 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 47.7 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer Sunpower Order Positive Ground Option for Sunpower arraysModule Model SPR-205-BLK Power @ MPT 210.0 W 210 For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 40 VDC PTC Power Rating 189.0 W 190.9 orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.13 ADC Temp Coeff of Vmpt 0.1368 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.53 ADC Temp Coeff of Vocv 0.1368 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 47.8 VDC NOCT (nom. cell temp) 50.5 deg C 122.9 deg F
Module Manufacturer SuntechModule Model STP280(S)-24/Vb-1 Power @ MPT 280.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 252.0 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.95 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.33 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Suntech * PTC power rating is 000W for the STP-000, the STP-0 has a PTC power of 000W
Module Model STP270(S)-24/Vb-1 Power @ MPT 270.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 242.8 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.71 ADC Temp Coeff of Vmpt 0.152 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.14 ADC Temp Coeff of Vocv 0.152 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.8 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Suntech * PTC power rating is 000W for the STP-000, the STP-0 has a PTC power of 000W
Module Model STP260(S)-24/Vb-1 Power @ MPT 260.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35 VDC PTC Power Rating 233.6 0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.43 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.04 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.3 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer SuntechModule Model STP210(S)-24(18)/Ub-1 Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.4 VDC PTC Power Rating 189.0 188.5 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.95 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.33 ADC Temp Coeff of Vocv 0.114 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.6 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Suntech * PTC power rating is 179.8W for the STP-200-24/Ab-1, the STP-200S-24/Ab-1 has a PTC power of 179.3W
Module Model STP200(S)-24(18)/Ub-1 Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.2 VDC PTC Power Rating 179.8 179.3 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.63 ADC Temp Coeff of Vmpt 0.114 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.114 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.6 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Suntech * PTC power rating is 170.6W for the STP-190-24/Ab-1, the STP-190S-24/Ab-1 has a PTC power of 170.2W
Module Model STP190(S)-24(18)/Ub-1 Power @ MPT 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 26.2 VDC PTC Power Rating 170.6 170.2 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.25 ADC Temp Coeff of Vmpt 0.113 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.84 ADC Temp Coeff of Vocv 0.113 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33.2 VDC NOCT (nom. cell temp) 45 deg C 113 deg F
Module Manufacturer Suntech * PTC power rating is 162.5W for the STP-180-24/Ab-1, the STP-180S-24/Ab-1 has a PTC power of 159.1W
Module Model STP180(S)-24/Ab-1 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.6 VDC PTC Power Rating 162.5 159.1 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 5.05 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.4 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Suntech * PTC power rating is 157.8W for the STP-175-24/Ab-1, the STP-175S-24/Ab-1 has a PTC power of 154.5W
Module Model STP175(S)-24/Ab-1 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 157.8 154.5 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.95 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.2 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Suntech * PTC power rating is 153.2W for the STP-170-24/Ab-1, the STP-170S-24/Ab-1 has a PTC power of 150.0W
Module Model STP170(S)-24/Ab-1 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.2 VDC PTC Power Rating 153.2 150.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.83 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.14 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.8 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Suntech * PTC power rating is 144W for the STP-160-24/Ab-1, the STP-160S-24/Ab-1 has a PTC power of 140.9W
Module Model STP160(S)-24/Ab-1 Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.4 VDC PTC Power Rating 144.0 140.9 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.65 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer SunwizeModule Model SW180 Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.6 VDC PTC Power Rating 157.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.92 ADC Temp Coeff of Vmpt 0.167 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.167 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44 VDC NOCT (nom. cell temp) 49 deg C 120.2 deg F
Module Manufacturer SunwizeModule Model SW175 Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.5 VDC PTC Power Rating 153.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.8 ADC Temp Coeff of Vmpt 0.167 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.2 ADC Temp Coeff of Vocv 0.167 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.9 VDC NOCT (nom. cell temp) 49 deg C 120.2 deg F
Module Manufacturer SunwizeModule Model SW170 Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.25 VDC PTC Power Rating 148.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.69 ADC Temp Coeff of Vmpt 0.167 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.15 ADC Temp Coeff of Vocv 0.167 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.9 VDC NOCT (nom. cell temp) 49 deg C 120.2 deg F
Module Manufacturer SunwizeModule Model SW160 Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33.4 VDC PTC Power Rating 139.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.79 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.43 ADC Temp Coeff of Vocv 0.165 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer SunwizeModule Model SW155 Power @ MPT 155.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33.4 VDC PTC Power Rating 135.3 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.65 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.28 ADC Temp Coeff of Vocv 0.165 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer SunwizeModule Model SW150 Power @ MPT 150.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33.4 VDC PTC Power Rating 130.9 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.5 ADC Temp Coeff of Vmpt 0.165 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.11 ADC Temp Coeff of Vocv 0.165 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42 VDC NOCT (nom. cell temp) 43 deg C 109.4 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO5 (240W) Power @ MPT 240.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.84 ADC Temp Coeff of Vmpt 0.131 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.38 ADC Temp Coeff of Vocv 0.131 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37.5 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO5 (230W) Power @ MPT 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.66 ADC Temp Coeff of Vmpt 0.13 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.18 ADC Temp Coeff of Vocv 0.13 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO5 (220W) Power @ MPT 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.39 ADC Temp Coeff of Vmpt 0.128 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8 ADC Temp Coeff of Vocv 0.128 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.8 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO5 (210W) Power @ MPT 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 29.2 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.19 ADC Temp Coeff of Vmpt 0.127 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.86 ADC Temp Coeff of Vocv 0.127 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.4 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO5 (200W) Power @ MPT 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 28.7 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 6.97 ADC Temp Coeff of Vmpt 0.126 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 7.75 ADC Temp Coeff of Vocv 0.126 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO1 (180W) Power @ MPT 180.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.8 VDC PTC Power Rating 161.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.9 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.35 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 44.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO1 (175W) Power @ MPT 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 36.2 VDC PTC Power Rating 156.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.85 ADC Temp Coeff of Vmpt 0.154 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.30 ADC Temp Coeff of Vocv 0.154 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.9 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO1 (170W) Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.8 VDC PTC Power Rating 151.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.76 ADC Temp Coeff of Vmpt 0.153 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.25 ADC Temp Coeff of Vocv 0.153 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.6 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Trina SolarModule Model TSM-DCO1 (165W) Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 35.6 VDC PTC Power Rating 147.2 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.65 ADC Temp Coeff of Vmpt 0.151 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.20 ADC Temp Coeff of Vocv 0.151 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 43.2 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer Uni-SolarModule Model PVL144 Power @ MPT 144.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33 VDC PTC Power Rating 136.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.36 ADC Temp Coeff of Vmpt 0.102 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.3 ADC Temp Coeff of Vocv 0.176 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 46.2 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Uni-SolarModule Model PVL136 Power @ MPT 136.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 33 VDC PTC Power Rating 128.8 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.1 ADC Temp Coeff of Vmpt 0.102 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.175 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 46.2 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Uni-SolarModule Model ES-124 Power @ MPT 124.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 30 VDC PTC Power Rating 117.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.13 ADC Temp Coeff of Vmpt 0.093 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.16 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Uni-SolarModule Model PVL-68 Power @ MPT 68.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 16.5 VDC PTC Power Rating 64.4 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.13 ADC Temp Coeff of Vmpt 0.051 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.1 ADC Temp Coeff of Vocv 0.088 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 23.1 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer WanXiang Solar * - values for Vmpt, Vocv and NOCT are estimated; PTC power rating not available; Suggested Inverters estimatedModule Model WXS165S Power @ MPT 165.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.74 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.75 ADC Temp Coeff of Vmpt 0.150 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.150 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42.84 VDC NOCT (nom. cell temp) 47 deg C 116.6 deg F
Module Manufacturer WanXiang Solar * - values for Vmpt, Vocv and NOCT are estimated; PTC power rating not available; Suggested Inverters estimatedModule Model WXS160S Power @ MPT 160.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 34.04 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 4.7 ADC Temp Coeff of Vmpt 0.155 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 5.4 ADC Temp Coeff of Vocv 0.155 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 42.48 VDC NOCT (nom. cell temp) 48 deg C 118.4 deg F
Module Manufacturer Yingli SolarModule Model YL230 (156) Power @ MPP 230.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.5 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.8 ADC Temp Coeff of Vmpp 0.137 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.4 ADC Temp Coeff of Vocv 0.137 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 37 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Yingli SolarModule Model YL225 (156) Power @ MPP 225.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29.5 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.63 ADC Temp Coeff of Vmpp 0.135 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.28 ADC Temp Coeff of Vocv 0.135 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Yingli SolarModule Model YL220 (156) Power @ MPP 220.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.59 ADC Temp Coeff of Vmpp 0.135 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.15 ADC Temp Coeff of Vocv 0.135 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36.5 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Yingli SolarModule Model YL215 (156) Power @ MPP 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 29 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.41 ADC Temp Coeff of Vmpp 0.133 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.133 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 36 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Yingli SolarModule Model YL175 Power @ MPP 175.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 23 VDC PTC Power Rating 0.0 W* orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.61 ADC Temp Coeff of Vmpp 0.107 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.2 ADC Temp Coeff of Vocv 0.107 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer Yingli SolarModule Model YLDJ-3 23V version Power @ MPT 170.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPT (STC) 23 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPT (STC) 7.4 ADC Temp Coeff of Vmpt 0.085 V/degC (Vmpt) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.1 ADC Temp Coeff of Vocv 0.107 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 29 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA215-A01 Power @ MPP 215.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.9 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 8.31 ADC Temp Coeff of Vmpp 0.122 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.77 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 33 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA210-A01 Power @ MPP 210.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 8.14 ADC Temp Coeff of Vmpp 0.122 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.74 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA205-A01 Power @ MPP 205.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.8 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.96 ADC Temp Coeff of Vmpp 0.122 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.71 ADC Temp Coeff of Vocv 0.122 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.9 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA200-A01 Power @ MPP 200.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.7 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.78 ADC Temp Coeff of Vmpp 0.121 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.68 ADC Temp Coeff of Vocv 0.121 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.8 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA195-A01 Power @ MPP 195.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.7 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.6 ADC Temp Coeff of Vmpp 0.121 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.65 ADC Temp Coeff of Vocv 0.121 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.8 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
Module Manufacturer YocasolModule Model PCA190-A01 Power @ MPP 190.0 W For Vmpt @ max amb temp and OCV @ coldest temperaturegreen is OK, red is not OKVoltage @ MPP (STC) 25.6 VDC PTC Power Rating 0.0 W orange is acceptable but should be avoided where possible (inverter will hold at 225VDC).Current @ MPP (STC) 7.42 ADC Temp Coeff of Vmpp 0.12 V/degC (Vmpp) purple is OK but indicates inverter will limit to 15 kW AC continuous outputCurrent, short circuit 8.62 ADC Temp Coeff of Vocv 0.12 V/degC (Vocv) pink is acceptable but should be avoided where possible (inverter will not run above 450VDC)OCV @ 25 deg C cells 32.7 VDC NOCT (nom. cell temp) 46 deg C 114.8 deg F
To find your region's ave hot temp. and coldest temp use this link and follow the steps below: Step-by-Step Instructions to use this string sizing charthttp://www.weather.com/maps/home.htmlSTEP 1: Enter your zip code STEP 1: Select the PV Module Manufacturer and Module Model you would like to use by scrolling down to it.
STEP 2: Click go STEP 2: Decide how many modules and DC Watts you would like, find the closest value to this in the "Power STEP 3: Scroll down and click "averages" (yellow button) @ MPT" line of near the bottom of the chart for the chosen moduleNote that in some cases there
STEP 4: The orange graph shows average high temp to use foVmpt @ max amb temp. may be close Wattage values in a couple locations on this line.STEP 5: At the bottom of the page, use "lowest recorded temp" foOCV @ coldest temp. STEP 3: Determine your maximum ambient temperature or average high temperature and the colde
recorded temperature in you area (use the yellow instructions and weblink to the left if you doBelow are NEC multipliers for Voc. The tables above use module manufacturers' specifications for Vo know these values)
-40F to -22F -22F to -4F -4F to 14F 14F to 32F 32F to 50F 50F to 77C STEP 4: Use these values to verify that theVmpt @ typical hot temp. is in the green or orange zoneMinimum cold extreme temperature range -40C to -30C -30C to -20C -20C to -10C -10C to 0C 0C to 10C 10C to 25C STEP 5: Use these values to verify that theOCV @ coldest temp. is in the green or orange zonemultiplier for extreme cold OCV per NEC 1.25 1.20 1.17 1.13 1.10 1.06 STEP 6: The "Modules per string" and the "Strings in Parallel" lines will let you know the array confuguration
* OCV acceptable if lowest temp does not go below 10C (50F).