Copyright : Coolibah Cabins C DETAIL SHEET No. JOB No. CHECKED DRAWN SCALE DATE REV. DATE BY AMENDMENTS CKD. JOB A3 GREGORY J. HAMILTON BUILDING PRACTITIONER No. DP-AD 222 THESE ARE THE PLANS REFERRED TO IN THE SPECIFICATION AND CONTRACT SIGNED : OWNERS ..................................................... ...................................................... BUILDER ..................................................... This drawing remains the property of and is approved for the use as described and may not be used or reproduced in whole or part without written permission Coolibah Cabins 90 Calotis Street Red Cliffs, Victoria 3496 Transportable Cabins, Granny Flats & Homes CLIENT PROPOSED NEW RELOCATABLE DWELLING LOT 13. DP 759091 14-16 REID STREET WILCANNIA NSW 2836 PERSPECTIVE VIEWS 14/08/20 16-306v5 1 of 10 G.H. G.J.H. FAR WEST LOCAL HEALTH DISTRICT PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT
10

PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

Oct 16, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENTPROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PERSPECTIVE VIEWS

14/08/20

16-306v5 1 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED NEW CABINFOR

FAR WEST LOCAL HEALTH DISTRICT

philpj
Placed Image
Page 2: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

S

N

E

W

SW

SE

NW

NE

No. 161012m²

R E I D S T R E E T

No.12

40.234m 37° 00' 00"B Y

R N

E S

S

T R

E E

T

F I E

L D

S

T R

E E

T

L A N E W A Y

EXISTINGELECTRICALMETER BOX.

EXISTINGPOWER POLE

EXISTINGTREE

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

EXISTINGCARPORT

EXISTINGSHED

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHB'GCARPORT

NEIGHB'GCARPORT

NEIGHB'GCARPORT

6800

3600

50.2

92m

307°

00'

00"

20.117m37° 00' 00"

20.117m37° 00' 00"

20.117m37° 00' 00"

20.117m37° 00' 00"

50.2

92m

307°

00'

00"

50.2

92m

307°

00'

00"

No. 141012m²No.12-14

Byrnes St

APPROX. 120.70m 37° 00' 00"

CONCRETE FOOTPATH CONCRETE FOOTPATHCONCRETE FOOTPATH

EXISTINGSEPTIC TANKS

C.O

.S.

C.O

.S.

LOT 132024m²

1260

40°

EXISTINGUNIT

PROPOSEDNEW DWELLING

EXISTINGUNIT

1200

1200

6590

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 500

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED SITE PLAN

14/08/20

16-306v5 2 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED SITE PLAN1:500

philpj
Placed Image
Page 3: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

STORMWATER NOTES90mm DIA. UPVC Stormwater drains from 100 x 50mm downpipes (denoted dp) to connect into existing stormwater system within property boundary as per Councils requirements with inspection openings every 9 meters of run and/or change in direction.(Spr) denotes 100 x 50mm spreader to discharge tolower roof.Overflow relief gully :-A minimium height of 150mm shall be maintainesbetween the top of the overflow relief gully riser and thelowest fixture connected to the drain. Top of Gully riserto be 75mm above natural surface or in paved area highenough to prevent the ingress of water.

S

N

E

W

SW

SE

NW

NE

No. 161012m²

R E I D S T R E E T

No.12

L A N E W A Y

EXISTINGELECTRICALMETER BOX.

EXISTINGPOWER POLE

EXISTINGTREE

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

EXISTINGUNIT

EXISTINGCARPORT

EXISTINGSHED

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHBOURINGDWELLING

NEIGHB'GCARPORT

NEIGHB'GCARPORT

NEIGHB'GCARPORT

No. 141012m²

No.12-14Byrnes St

CONCRETE FOOTPATH CONCRETE FOOTPATHCONCRETE FOOTPATH

EXISTINGSEPTIC TANKS

LOT 132024m²

NEW 90mm Ø UPVC STORMWATER PIPE TO CONNECT INTO EXISTINGSTORMWATER SYSTEM WITHIN PROPERTY BOUNDARY. (TYP).

PROPOSEDNEW DWELLING

dp

dp

sprdp

sprdp

EXISTINGUNIT

GENERAL NOTES

WATERPROOFING OF WET AREAS

Check and verify all measurements, dimensions and intent prior to

All works must comply with the B.C.A. and all relevant by-laws

Figured dimensions are to take precedence over all.

construction or fabrication.

All sections of the specification and drawings shall be taken in

inferred in the type of work generalised in this specification butWhere an item is usual or necessary or is reasonably or properly

clauses are in anyway applicable.be taken as referring to all other sections, if such provision andconjunction and any provisions or clause in any one section shall

not specifically mentioned, it shall be deemed to be included in thespecification.

2.

1.

6.

3.

5.

4.

& authorities.

Do not scale drawings.

Denotes articulation joint to be constructed in accordance withcaca technical note 61.

Overflow relief gully requirements are to comply with A.S. 3500.2-2003"Sanitary Plumbing & Sanitary Drainage"

Solid fuel combustion heaters are to be installed in accordance withA.S. 2918-2001. "Domestic Solid Fuel"

7.

8.

9.

AS 3740-2010, 'Waterproofing Of Wet Areas Within Residential Buildings'.sanitary compartments and the like shall be provided in accordance withWaterproofing of wet areas being bathrooms, shower rooms, laundries,

ENERGY EFFICIENCY INFORMATIONINSTALL.ITEMR 3.5 BULK INSULATION

R 2.0 BULK INSULATION & ANTIGLARE REFLECTIVE FOIL WRAP.RELFECTIVE FOIL WRAP TO COMPLY WITH AS/NZS 4200.1 and MUST BE INSTALLED IN ACCORDANCE WITH AS 4200.2.

ALUMINIUM IMPROVED HORIZONTAL SLIDING WINDOWS.

WEATHER STRIPPED.

RANGEHOOD, BATHROOM & ENSUITE EXHAUST FANS TO BESEALED UNITS DUCTED TO ROOF SPACE.

Floor

DwellingRoofs and CeilingsDwelling External Walls

Windows & Sliding Doors

External Doors

Exhaust Fans

ATC 3 (closely spaced obstructions)PS ( partial shielding)T0 (maximum slope <1:20)

N1DESIGN GUST WIND SPEED

TOPOGRAPHIC CLASSIFICATIONSHIELDING CLASSIFICATIONTERRAIN CATEGORYREGION

26m/s Serviceability (Vh,s) 34m/s Ultimate (Vh,u)

WIND LOADS FOR HOUSING CLASSIFICATION

STEEL FRAMED TIMBER FLOOR - UNENCLOSED PERIMETER INSTALL 'FOILBOARD GREEN 15' INSULATION PANELS BETWEEN FLOOR JOISTS SUPPORTED ON CONTINUOUS 25 x 25mm EQ. ANGLE BRACKET AT BTM OF JOISTS.(Total Added R-Value = R.2.05)

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

As indicated

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED STORMWATERLAYOUT PLAN

14/08/20

16-306v5 3 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED STORMWATER LAYOUT PLAN 1:500

philpj
Placed Image
philpj
Placed Image
Page 4: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

A9 of 10

A

2 N

o. R

OBE

SL.

DR

S.

18000

90

310090

510

90

5004232

5004

90

51090

3100

90

90

1450

90

3430

90

9028109080090102090389423238949010209080090281090

9014

5090

3430

90

5150

2800

90

2320

90

1020

90

90

2320

9010

20

90

2800

5150

WMWM

kitchen

REF/FRZ

ELECTRICHP & UBO

SSSB

O/HREF/FRZ

ELECTRICHP & UBO

SSSBO/H

robe

robe

SHRSHR

18000

W.11000H x 1210W

W.21000H x 1210W

W.3

900H

x 6

10W

W.41500H x 1450W

W.51500H x 1450W

W.61500H x 1450W

W.71500H x 1450W

W.8

900H

x 6

10W

90

3700

9090

3700

90

bedroomlivinglivingbedroom

bathbath

verandah& deck

l'dryl'drykitchen

M.H.820 CS

670

670

820

820

2 N

o. R

OBE

SL.

DR

S.

820 CS

670

670

820

820M.H.

3.5K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

MODWOOD DECKING

CARPET

VINYL PLANK

3.5K

W IN

DO

OR

SPLI

T SY

STEM

A/

C U

NIT

5.0K

W IN

DO

OR

SPLI

T SY

STEM

A/

C U

NIT

1500 x 900mm TILED &GRADED SHOWER BASETO FALL AT 1:60-1:80TOWARDS FLOOR WASTE.(TYP).

INTERNAL ELECTRICALSWITCHBOARD

S.A.S.A.SE

CUR

ITY

DO

OR

SEC

URIT

YD

OO

R82

0

SEC

URIT

YD

OO

R82

0

SEC

URIT

YD

OO

R

60/60/60 FIRE RATED TIMBER FRAMED INTERNAL WALL UP TO UNDERSIDE ROOF SHEETING

INTERNAL ELECTRICALSWITCHBOARD

5.0K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

3.5K

W IN

DO

OR

SPLI

T SY

STEM

A/

C U

NIT

5.0K

W IN

DO

OR

SPLI

T SY

STEM

A/

C U

NIT

3.5K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

5.0K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

150

x 50

mm

RH

SG

ALV.

RAF

TER

S

verandah& deckMODWOOD DECKING

150 x 50mm RHS GALV. PERIMITER BEAM

150 x 50mm RHS GALV. PERIMITER BEAM

150 x 50mm RHS GALV. PERIMITER BEAM

150 x 50mm RHS GALV. PERIMITER BEAM

70 x 50mm RHS GALV. BATTENS NOGGEDBETWEEN RAFTERS

150 x 50mm RHS GALV. PERIMITER BEAM

150 x 50mm RHS GALV. PERIMITER BEAM

VERANDAH & DECK - MODULE 19000

VERANDAH & DECK - MODULE 29000

90mm x 90mm DURAGALVERANDAH POSTS. (TYP).2 No.- 90mm x 50mm DURAGAL

VERANDAH POSTS. (TYP).

90x9

024

2090

x90 20

0

90x9

024

2090

x90 20

0

90x90

2885

90x90

2890

90x90

2905

90x50 90x50

2905

90x90

2890

90x90

2885

90x90

dp dp

sprspr

dp dp

9 of 10

CARPET

1500 x 900mm TILED &GRADED SHOWER BASETO FALL AT 1:60-1:80TOWARDS FLOOR WASTE.(TYP).

VINYL PLANK

250ltr MAINS PRESSURE

ELECTRIC HWS

S

N

E

WSW

SE

NW

NE

AREASCabin 92.70m² ( 9.98 SQS.)

Verandah & Deck 50.40m²

S.A.SMOKE ALARMS - INSTALL AC POWERED ALARMS WITH BATTERY BACK-UP AND BEINTERCONNECTED WHERE THERE IS MORE THAN ONE ALARM IN ACCORDANCE WITH B.C.A. PART 3.7.5.2 - 'SMOKE ALARM'

WINDOW H x W U-VALUE SHGC DESCRIPTION

WINDOW SCHEDULE

CLEAR GLAZED - HORIZONTAL SLIDING1000 x 1210W.1, W.2.

W.4, W.5, W.6, W.7.

1500 x 1450 CLEAR GLAZED - HORIZONTAL SLIDING

6.44 0.75

900 x 610W.3, W.8. 6.44 0.75 OBSCURE GLAZED - HORIZONTAL SLIDING

6.44 0.75

: ALL NEW WINDOWS TO BE FRAMED USING DOMESTIC ALUMINIUM IMPROVED SECTION.

: SINGLE GLAZED SASHS WITH INSECT SCREENS TO ALL OPENING SASHS AS NOTED.

: WINDOW GLAZING LESS THAN 500mm ABOVE FINISHED FLOOR LEVEL TO BE either : - GRADE A SAFETY GLASS or 5mm NOMINAL THICKNESS ORIDINARY ANNEALED GLASS PROVIDED THAT THE AREA OF THE GLAZING PANEL IS NOT MORE THAN 1.2m².

: ALL GLAZING IN BATHROOMS, ENSUITES, SPA ROOMS AND THE LIKE, INCLUDING SHOWER DOORS & SCREENS LESS THAN 2.0m ABOVE F.F.L. or THE BOTTOM OF THE BATH MUST - (i) for framed panels, be glazed with - (A) GRADE A SAFETY GLASS IN ACCORDANCE WITH TABLE 3.6.5 of the NCC 2016. (B) GRADE B SAFETY GLASS IN ACCORDANCE WITH TABLE 3.6.5 of the NCC 2016. (ii) for panels or doors with any edge exposed, BE TOUGHENED SAFETY GLASS IN ACCORDANCE WITH TABLE 3.6.6 of the NCC 2016 WITH A NOMINAL THICKNESS OF 6mm. : SLIDING DOOR GLAZING TO BE GRADE A SAFETY GLASS.

: ALL GLASS & GLAZING TO COMPLY WITH AS-1288, AS-2208, AS-2047.

PROPOSED FLOOR PLAN. 1:100.

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 100

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED FLOOR PLAN

14/08/20

16-306v5 4 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

DWELLING 1

philpj
Placed Image
Page 5: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

2400

CEIL

ING

HEIG

HT

COLORBOND CORRUGATED IRON 0.42mm BMTROOF SHEETING AT 20° PITCH. (TYP).

TYPICAL COLORBOND IRONRIDGE CAPPING. (TYP).

COLORBOND METAL GUTTERON COLORBOND FASCIA. (TYP).

ALUMINIUM SLIDING WINDOWS. (TYPICAL).

20° PITCH 20° PITCH

W.3.900H x 610W

1° MIN. PITCH

OPEN THRUVERANDAH

90 x 90mm DURAGAL VERANDAH POSTS. (TYP).

3.5KW OUTDOORSPLIT SYSTEM

A/C UNIT.

5.0KW OUTDOORSPLIT SYSTEM

A/C UNIT.

250ltr MAINS PRESSUREELECTRIC

HWS

2400

CEIL

ING

HEIG

HT

90 x 90mm DURAGAL VERANDAH POSTS. (TYP).

COLORBOND CORRUGATED IRON 0.42mm BMT ROOF SHEETING AT 20° PITCH. (TYP).

TYPICAL COLORBOND IRONRIDGE CAPPING. (TYP).

COLORBOND CORRUGATED IRONHORIZONTAL WALL CLADDING. (TYP).

3720

172

ALUMINIUM SLIDING WINDOWS. (TYPICAL).

W.41500H x 1450W

W.51500H x 1450W

W.61500H x 1450W

W.71500H x 1450W

COLORBOND STEELINE STEEL-RIB 500 0.48mm BMT ROOF SHEETING AT 1° MIN. PITCH TO VERANDAH ROOF. (TYP).

COLORBOND METAL GUTTERON COLORBOND FASCIA. (TYP).

3.5KW OUTDOORSPLIT SYSTEM A/C UNIT.

3.5KW OUTDOOR

SPLIT SYSTEM A/C UNIT.

CEIL

ING

HEIG

HT24

00

COLORBOND CORRUGATED IRON 0.42mm BMTROOF SHEETING AT 20° PITCH. (TYP).

ALUMINIUM SLIDING WINDOWS. (TYP).

COLORBOND CORRUGATED IRONHORIZONTAL WALL CLADDING. (TYP).

TYPICAL COLORBOND IRONRIDGE CAPPING. (TYP).

COLORBOND METAL GUTTERON COLORBOND FASCIA. (TYP).

W.1600H x 1210W

W.2600H x 1210W

5.0KW OUTDOOR

SPLIT SYSTEM A/C UNIT.

5.0KW OUTDOORSPLIT SYSTEM A/C UNIT.

250ltr MAINS PRESSUREELECTRIC

HWS

HWS

2400

CEIL

ING

HEIG

HT

COLORBOND CORRUGATED IRON 0.42mm BMTROOF SHEETING AT 20° PITCH. (TYP).

COLORBOND METAL GUTTERON COLORBOND FASCIA. (TYP).

COLORBOND CORRUGATED IRONHORIZONTAL WALL CLADDING. (TYP).

OBSCURE GLAZING TO WINDOWSSHOWN HATCHED. (TYP).

20° PITCH20° PITCH

W.8900H x 610W

OPEN THRUVERANDAH

1° MIN. PITCH

COLORBOND STEELINE STEEL-RIB 500 0.48mm BMT ROOF SHEETING AT 1° MIN. PITCH TO VERANDAH ROOF. (TYP).

3.5KW OUTDOORSPLIT SYSTEM

A/C UNIT.

5.0KW OUTDOORSPLIT SYSTEM

A/C UNIT.

250ltr MAINS PRESSUREELECTRIC

HWS

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 100

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED ELEVATIONS

14/08/20

16-306v5 5 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED west ELEVATION 1:100

PROPOSED east ELEVATION 1:100

PROPOSED south ELEVATION

PROPOSED north ELEVATIONDWELLING 1 DWELLING 1

DWELLING 1DWELLING 1

philpj
Placed Image
Page 6: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

770

3610

770

C H

OLD

D

OW

N P

ILE

L

150 x 75mm PFC BEARERS.(TYPICAL)

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYPICAL)

450mm x 450mm x 50mm THICKCONCRETE BLOCK WITH 89 x 89 x 2.0mmGALVANISED SHS STUMPS ON 250 PFC BEAM - 315mm LONG AT 2200mm MAXIMUM CTRS. ( TYP ).

SP1 - SCREW PILE HOLD DOWN ANCHORS AT 4400mm MAX. CTRS. (TYP).

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM

150

x 50

x 2

.0m

m G

ALVA

NIS

ED

RH

S PE

RIM

ETER

BEA

M

150

x 50

x 2

.0m

m G

ALVA

NIS

ED R

HS

PER

IMET

ER B

EAM

150

x 50

x 2

.0m

m

GAL

VAN

ISED

RH

S PE

RIM

ETER

BEA

RER

18000

6004200420042004200600

C S

TUM

PLC S

TUM

PLC S

TUM

PLC

STU

MP

LC S

TUM

PLC S

TUM

PLC S

TUM

PLC S

TUM

PL

HARDIES SCYON 'SECURA' 22mm THICKINTERIOR FLOORING TO WET AREAS.(TYPICAL TO BLUE SHADED AREAS).

SP1

22mm RED-TONGUE PARTICLEBOARD SHEET FLOORING - UNLESS NOTED OTHERWISE

800 2340 2340 2340 2350 2350 2340 2340 800

200mm WIDE x 90mm THICK x WIDTH OF BUILDINGCONCRETE STRIP PAD FOOTING WITH SL72 MESH IN CENTRE. (TYPICAL UNDER FIRE RATED WALL).

C H

OLD

D

OW

N P

ILE

L C H

OLD

D

OW

N P

ILE

L C H

OLD

D

OW

N P

ILE

L C H

OLD

D

OW

N P

ILE

L

5150

2800

C HOLD DOWN PILE & OUTSIDE FACE OF BEARER

L

C HOLD DOWN PILE & OUTSIDE FACE OF BEARER

L

150

x 50

x 2

.0m

m

GAL

VAN

ISED

RH

S PE

RIM

ETER

BEA

RER

SELECTED MODWOOD DECKING

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 450mm CTRS. (TYPICAL)

TO TOTAL VERANDAH DECK AREA

C HOLD DOWN PILE & OUTSIDE FACE OF BEARER

L

150 x 50 X 2.0mm RHS PERIMETER DECK BEARER. (TYPICAL)

150 x 50 X 2.0mm RHS DECK BEARER. (TYPICAL)

BEARER CLEAT PLATESWELDED TO CABIN CHASSISAND BOLTED TO VERANDAH DECK BEARER AT 4400mm MAX.CTRS. (TYP).

SP1SP1SP1 SP1

SP1 SP1 SP1 SP1 SP1

SP1 SP1SP1 SP1SP1

SP1 - SCREW PILE HOLD DOWN ANCHORS AT 4400mm MAX. CTRS. (TYP).

1. TREAT ALL SUB-SOILS FOR TERMITES AS PER AUSTRALIAN STANDARDS.

2. MINIMIUM ORDERING STRENGTH FOR ALL CONCRETE 25 M.P.a. (FULL STRENGTH AFTER 28 DAYS).

3. CONSULTANT TO CHECK, VERIFY AND APPROVE ACTUAL CONCRETE SLAB LAYOUT BEFORE ANY CONCRETE IS TO BE POURED.

CONCRETE NOTES:

Hold Down Screw Pile Detail 1:20 (SP1)

770

150 x 75mm PFC BEARERS. (TYPICAL)

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYPICAL)

22mm RED TONGUE PARTICLEBOARD SHEET FLOORING. (TYPICAL).

OU

TSID

E ED

GE

OF

BEAR

ER

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM. (TYP)

P1

FOILBOARD 'GREEN 15' INSULATED PANEL BETWEEN FLOOR JOISTS SUPPORTED ON CONTINUOUS 25 x 25mm EQ. ANGLE BRACKET AT BOTTOM OF JOISTS. (TYP).

SP1 - SCREW PILE HOLD DOWN ANCHORS AT 25° ANGLE TO NGL AS PER ENGINEERS DESIGN. (TYP).

GALVANISED CHAIN - 1.5 TONNECAPACITY EQUIVILENT RATED 'D' SHACKLE EACH END.

MINIMUM 2 x 14-20-22 CLASS 4TEK SCREWS PLACED 25mmFROM TOP EITHER SIDE.

CLEAT PLATE WELDED TO FLOOR JOISTS.

25°

REFER TOENLARGEMENT

770

150 x 75mm PFC BEARERS.(TYPICAL)

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYPICAL)

22mm BEIGE TONGUE PARTICLEBOARD SHEET FLOORING. (TYPICAL).

OU

TSID

E ED

GE

OF

BEAR

ER

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM. (TYP)

FOILBOARD 'GREEN 15' INSULATED PANEL BETWEEN FLOOR JOISTS SUPPORTED ON CONTINUOUS 25 x 25mm EQ. ANGLE BRACKET AT BOTTOM OF JOISTS. (TYP).450 x 450 x 50mm THICKPRECAST CONCRETE PAD. (TYP).

50

450

Typical Footing / Floor Framing Detail 1:2055

0

SCREW NUT HEIGHT ADJUSTER FITTINGWELDED TO 6mm BTM PLATE STUMP CAP& SLEAVE AND 6mm TOP PLATE SADDLEFOR BEARER SUPPORT - 100mm LONG.

89 x 89 x 2.0mm GALVANISED SHS STUMP FULLY WELDED TO 250 PFC BEAM BASEPLATE - 325mm LONG PFC.

225

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

As indicated

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED FLOOR FRAMINGLAYOUT PLAN

14/08/20

16-306v5 6 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED FLOOR FRAMING LAYOUT PLAN. 1:100.DWELLINGS 1 & 2

philpj
Placed Image
Page 7: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

450 x 450 x 50mm THICKPRECAST CONCRETE PAD. (TYP).

450

450

SCREW NUT HEIGHT ADJUSTER FITTINGWELDED TO 6mm BTM PLATE STUMP CAP& SLEAVE AND 6mm TOP PLATE SADDLEFOR BEARER SUPPORT - 100mm LONG.

89 x 89 x 2.0mm GALVANISED SHS STUMP FULLY WELDED TO 250 PFC BEAM BASEPLATE - 325mm LONG PFC.

100 250 100

6532

065

SECTION THRU TYPICAL EXTERNAL STEPS 1:20

280 280

180

180

180

GALVANISED 150 x 50 x 2.0mm RHSRISERS AT 280mm CTRS. (TYP).

GALVANISED 75 x 50 x 2.0mm UNEQUAL ANGLE JOISTS AT 450mm CTRS. (TYP).

90 x 19mm MERBAU DECKINGWITH 5.0mm MAX. GAP. (TYP).

22mm BEIGE-TONGUE FLOORING. (TYP).

GALVANISED 150 x 50 x 2.0mm RHSFLOOR JOISTS. (TYP).

N.G.L.

540

GALVANISED 30 x 30 x 2.0mm SHSSPACER UNDER EACH RISER. (TYP).

GALVANISED 75 x 50 x 2.0mm RHS BTM. RISER. (TYP).

M.S. ANGLE METAL BRACKET FIXED TO CONCRETE PAD.

300x300

GALVANISED 200 x 50 x 2.0mm RHSSTRINGERS WELDED TOFLOOR FRAME. (TYP).

LANDING & STEP NOTES :ALL LANDING & STEP STRUCTURAL STEEL FRAMING CONNECTIONS ARE TO BE FULLY WELDED. ALL TIMBER LANDINGS TO HAVE A R10 SLIP RESISTANCE CLASSIFICATION & TIMBER STEPS TO HAVE A R11 SLIP RESISTANCE CLASSIFICATION.

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

As indicated

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED FOOTING DETAILS

14/08/20

16-306v5 7 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

philpj
Placed Image
Page 8: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

TYPICAL FRL 60/60/60 FIRE RATED INTERNAL WALL DETAIL BETWEEN EACH UNIT. 1:10Rw = 58. Rw + Ctr = 50. Total R Value (m²K/W) = 4.0

F.F.L.

70mm GLASS WOOL BULK INSULATION BATTS (min. 11kg/m³)TO EACH WALL CAVITY. (TYP).

1 x 16mm FIRESTOPPLASTERBOARD LININGTO EACH INTERNAL WALLFACE. (TYP).

TYPICAL ARCHITRAVE.

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYP)

16 90 20 90 16

1 x 16mm FIRESTOPPLASTERBOARD LININGTO EACH INTERNAL WALLFACE. (TYP).

90mm x 35mm MGP 10TIMBER WALL STUDSAT 600mm CTRS. (TYP).90mm x 35mm MGP 10 TIMBER

WALL TOP & BTM PLATES. (TYP).

20mm MIN. AIR GAP BETWEENEACH WALL LEAF. (TYP).

22mm RED-TONGUE PARTICLEBOARDFLOORING - TERMITE TREATED. (TT22)and/or HARDIES SCYON SECURA 22mm THICKINTERIOR FLOORING. (TYP).

150 x 75mm PFC BEARERS. (TYPICAL)15

015

022

FOILBOARD 'GREEN 15' INSULATED PANEL BETWEEN FLOOR JOISTS SUPPORTED ON CONTINUOUS 25 x 25mm EQ. ANGLE BRACKET AT BOTTOM OF JOISTS. (TYP).

200

90

75

85150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYP)

PROVIDE FIRE-PROOF SEALANT AT TOP OF 75mm HEBEL PANEL-TO-FLOOR CONNECTIONAND BOTTOM OF 75mm HEBEL PANEL-TO- FOOTING CONNECTION.

200mmWIDE x 90mm THICK x WIDTH OF BUILDINGCONCRETE STRIP PAD FOOTING WITH SL72MESH IN CENTRE. (TYP).

75mm HEBEL PANEL FROM UNDERSIDE FLOORING DOWNTO CONCRETE FOOTING.

200 x 6mm PLATE WELDED TO OPEN FACE OF PFC BEARER TOES.

200

770

150 x 75mm PFC BEARERS. (TYPICAL)

22mm RED-TONGUE PARTICLEBOARD SHEET FLOORING. (TYPICAL).

OU

TSID

E ED

GE

OF

BEAR

ER

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM. (TYP)

550

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. BEYOND. (TYP)

PROVIDE FIRE-PROOF SEALANT AT TOP OF 75mm HEBEL PANEL-TO-FLOOR CONNECTIONAND BOTTOM OF 75mm HEBEL PANEL-TO- FOOTING CONNECTION.

75mm HEBEL PANEL FROM UNDERSIDE FLOORING DOWN TO CONCRETE FOOTING.CUT AROUND 150 x 75mm PFC BEARER TO MEET ADJOINING 75mm HEBEL END PANEL.PROVIDE FIRE-PROOF SEALANT ALONG JOIN BETWEEN PANELS.

200 x 6mm PLATE WELDED TO OPEN FACE OF PFC BEARER TOES & ENCLOSING PLATE BACK TO BACK FLANGE OF PFC.( FULLY WELDED ALL ROUND.)

75mm HEBEL END PANEL FROM UNDERSIDE FLOORING DOWNTO CONCRETE FOOTING.

PROVIDE FIRE-PROOF SEALANTALONG JOIN BETWEEN 75mmHEBEL PANELS.

TYPICAL FRL 60/60/60 FIRE RATED SUB-FLOOR DETAIL BETWEEN EACH UNIT. 1:10

Rw = 58. Rw + Ctr = 50. Total R Value (m²K/W) = 4.0

200mmWIDE x 90mm THICK x WIDTH OF BUILDINGCONCRETE STRIP PAD FOOTING WITH SL72MESH IN CENTRE. (TYP).

232

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 10

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED FIRE RATED WALLDETAIL - FRL 60/60/60

14/08/20

16-306v5 8 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

philpj
Placed Image
Page 9: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

20° PITCH 20° PITCH

R 3.5 BULK INSULATION BATTSTO CEILING. (TYP).

70 x 35mm MGP 12 ROOF BATTENSAT 900mm END SPANS AND 1200mmINTERMEDIATE SPANS.

10mm PLASTERBOARD CEILINGLINING ON METAL CEILING BATTENSAT 450mm CTS. (TYP).

TIMBER ROOF TRUSSES AT 900mm CTS.AS PER ROOF TRUSS MANUFACTURERSDESIGN. (TYP).

COLORBOND OGEE EAVE GUTTERON COLORBOND METAL FASCIA.(TYPICAL).

living

10mm PLASTERBOARD INTERNALWALL LINING. (TYP).

R 2.0 BULK INSULATIONBATTS TO EXTERNAL WALLS(TYPICAL).

TYPICAL PLASTERCORNICE.

150 x 75mm PFC BEARERS. (TYPICAL)

150 x 50 x 2.0mm GALVANISED RHS FLOOR JOISTS AT 600mm CTRS. (TYPICAL)

22mm RED TONGUE PARTICLEBOARD SHEETFLOORING. (TYPICAL).

TYPICAL SELECTED SKIRTING.

150 x 75mm PFC BEARERS. (TYPICAL)

CEI

LIN

G H

EIG

HT

2400

COLORBOND CORRUGATED IRON 0.42mm BMTROOF SHEETING AT 20° PITCH. (TYP).

TYPICAL COLORBOND IRONRIDGE CAPPING. (TYP).

ALUMINIUM SLIDING WINDOWS. (TYPICAL).

COLORBOND CORRUGATED IRONHORIZONTAL WALL CLADDING. (TYP).

COLORBOND CORRUGATED IRON HORIZONTAL WALL CLADDING. (TYP).

450 x 450 x 50mm THICK PRECAST CONCRETE PAD. (TYP).

SCREW NUT HEIGHT ADJUSTER FITTINGWELDED TO 6mm BTM PLATE STUMP CAP& SLEAVE AND 6mm TOP PLATE SADDLEFOR BEARER SUPPORT - 100mm LONG.

450 x 450 x 50mm THICK PRECAST CONCRETE PAD. (TYP).

SCREW NUT HEIGHT ADJUSTER FITTINGWELDED TO 6mm BTM PLATE STUMP CAP& SLEAVE AND 6mm TOP PLATE SADDLEFOR BEARER SUPPORT - 100mm LONG.

89 x 89 x 2.0mm GALVANISED SHS STUMP FULLY WELDED TO 250 PFC BEAM BASEPLATE - 325mm LONG PFC.

FOILBOARD 'GREEN 15' INSULATED PANEL BETWEEN FLOOR JOISTS SUPPORTED ON CONTINUOUS 25 x 25mm EQ. ANGLE BRACKET AT BOTTOM OF JOISTS. (TYP).

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM.

150 x 50 x 2.0mm GALVANISED RHS PERIMETER BEAM.

kitchen

EXTERNAL WALL FRAMING:-2/90 x 35mm MGP 10 TOP PLATES.90 x 45mm MGP 10 BOTTOM PLATE.90 x 35mm MGP 10 WALL FRAMINGSTUDS AT 600mm CTS. AND REFLECTIVE FOIL WRAP INSULATIONTO EXTERNAL FACE OF FRAME.

SP1SP1 - SCREW PILE HOLD DOWN ANCHORS AT 25° ANGLE TO NGL AS PER ENGINEERS DESIGN. (TYP). SP1

SP1 - SCREW PILE HOLD DOWN ANCHORS AT 25° ANGLE TO NGL AS PER ENGINEERS DESIGN. (TYP).

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 20

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED SECTION A-A

14/08/20

16-306v5 9 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

4 of 10SECTION A-A 1:50

philpj
Placed Image
Page 10: PROPOSED NEW CABIN FOR FAR WEST LOCAL HEALTH DISTRICT

ELECTRICAL LEGEND

3-IN-1 ~TWO HEATER, EXHAUST FAN & 60W LIGHT. (VENT TO ROOF SPACE ONLY).

20W BATTEN HOLDER

}}

UNLESS NOTED OTHERWISE.DOUBLE G.P.O.

SINGLE G.P.O.

EXHAUST FAN & 20W LIGHT

3-IN-1 ~FOUR HEATER, EXHAUST FAN & 60WLIGHT. (VENT TO ROOF SPACE ONLY).

DUAL CAT6 OUTLET

TWIN SLIMLINE FLUORESCENT LIGHT AND ACRYLIC DIFFUSER. (2 x 28W)

ELECTRICAL LIGHT SWITCH.

ELECTRICAL WIRING.

MAN HOLE. (600 x 600).

HOT WATER UNIT.

1.8m ANTENNA & CABLING TO COMMS CABINET(for feed in micro wave link)

MOUNTED 300mm ABOVE F.L.

T.V. COAXIAL OUTLET.

TELEPHONE OUTLET.

EXTERNAL FLOODLIGHT.

ELECTRICAL SWITCHBOARD

S.A.

hws

M.H.

X

20W WALL MOUNTED BATTEN HOLDER

22W CIRCULAR FLUORESCENT LIGHT

CEILING FAN WITH 24W LED LIGHT.

CEILING FAN.

DATA OUTLET.

SINGLE SLIMLINE FLUORESCENT LIGHT AND ACRYLIC DIFFUSER. (1 x 28W)

LIGHT SENSOR

15W LED DOWN LIGHT.

22

32 32W CIRCULAR FLUORESCENT LIGHT

SMOKE ALARMS - INSTALL AC POWERED ALARMS WITH BATTERY BACK-UP AND BEINTERCONNECTED WHERE THERE IS MORE THAN ONE ALARM IN ACCORDANCE WITH B.C.A. PART 3.7.2 - 'SMOKE ALARM'

EXHAUST FAN

4Ru COMMS CABINET & SWITCHABLE FANWITH SIDE ACCESS CABINET

X

32

32

32

32

X

3232

X

X

XXX

X

X

X

XX

NOTE :1. ALL CABLING TO BE CAT 6A SHIELDED.2. PATCH PANEL = 2 PORT.

INTERNAL ELECTRICALSWITCHBOARD

INTERNAL ELECTRICALSWITCHBOARD

SPLI

T SY

STEM

A/

C U

NIT

SPLI

T SY

STEM

A/

C U

NIT

SPLI

T SY

STEM

A/

C U

NIT

SPLI

T SY

STEM

A/

C U

NIT

3.5K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

5.0K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

3.5K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

5.0K

W O

UTD

OO

RSP

LIT

SYST

EM

A/C

UN

IT.

250ltr MAINS PRESSURE

ELECTRIC HWS

X X

Copyright : Coolibah CabinsC

DETAIL

SHEET No.JOB No.

CHECKED

DRAWN

SCALE

DATE

REV. DATE BY AMENDMENTS CKD.JOB

A3

GREGORY J. HAMILTONBUILDING PRACTITIONER No. DP-AD 222THESE ARE THE PLANS REFERRED TO

IN THE SPECIFICATION AND CONTRACTSIGNED :

OWNERS ..................................................... ......................................................

BUILDER .....................................................

This drawing remains the property of

and is approved for the use as described and may not be used or reproduced in whole or part

without written permission

Coolibah Cabins

90 Calotis StreetRed Cliffs, Victoria 3496

Transportable Cabins, Granny Flats & Homes

CLIENT

1 : 100

PROPOSED NEWRELOCATABLE DWELLINGLOT 13. DP 75909114-16 REID STREETWILCANNIANSW 2836

PROPOSED ELECTRICAL LAYOUTPLAN

14/08/20

16-306v5 10 of 10

G.H.G.J.H.

FAR WEST LOCAL HEALTHDISTRICT

PROPOSED ELECTRICAL LAYOUT PLAN 1:100DWELLING 1