PROJECT NARRATIVE The Central Cooling and Heating Plant is a (+/-)7,924 S.F. structure containing equipment to serve chillers, cooling towers and boilers to serve hot and cold water supply to campus facilities. Support offices and maintenance spaces are included in the facility construction. TABLE 5-1: FLOOR HAZARD INFORMATION and FLOOR LOADS FLOOD HAZARD AREA Base Flood Elevation _______________ MSL NGVD or FIRM Design Floor Elevation _______________ MSL IBC 1612.3 and ASCE 24 NON-HIGH VELOCITY WAVE ACTION Elevation of Lowest Proposed Floor _______________ MSL Meet ASCE 24 Section 2.6.2.1 Dry flood proofing _____ no _____ yes per ASCE 24 HIGH-VELOCITY WAVE ACTION Elevation of bottom of Lowest Horizontal Structural Member of lowest floor __________________ MSL Flotation resistant _____ no _____ yes per ASCE 24 Breakaway wall _____ no _____ yes per ASCE 24 IBC 1612 and SE-900, as applicable N/A 43.0 Zone X, Community # 450104, Panel # 0517 43.0 40.67 TABLE 5-2: SOILS & SITE SOILS INVESTIGATION (If available) SOILS CLASSIFICATION Site Class (seismic class) Classes Soil of Materials (UCS System) Allowable Footing Bearing Pressure ___________________ ___________________ ___________________ psf per IBC 1613.5.2 per IBC 1802.3 Class 4 (SP, SC, SM) Seismic Site Class E 2,000 MINIMUM DESIGN SOIL BEARING LOAD ______________ psf per IBC table 1804.2.1 1633-09-237 Dated 10-9-09 (per IBC table 1804.2.1) no yes COMPACTION Subgrade _____________ % ASTM D698 ASTM D1557 AASHTO (only for paving & roads) Base _____________ % ASTM D698 ASTM D1557 AASHTO (only for paving & roads) Other _____________ % ASTM D698 ASTM D1557 AASHTO (only for paving & roads) MINIMUM DESIGN SOIL LATERAL LOAD ____________________ psf per IBC table 1610.1 FOOTINGS Undisturbed Footings Compacted Fill Material ELEVATIONS Elevation of Water Table Elevation of lowest footing Elevation of lowest floor or basement no yes per IBC table 1803.5 no yes 2,000 98 100 NA 80 (Active Lateral) ______________ MSL ______________ MSL ______________ MSL 41.67 (TOF) 36.7 43.0 ____________________ psf 720 (Passive Lateral) Water at 4'-4" to 5'-4" below exist. ground surface (4.8' Average). TABLE 5-4: BUILDING AREA AREA LIMIT BY TABLE 503 OF IBC (Do not indicate increases for sprinklers & street frontage.) AREA MODIFICATION FROM EQUATIONS 5-1 OF IBC (Insert equation from IBC 506.1 with completed calculations in this Box) (Equation 5-1) Aa = At + [ At x If] + [At x Is] Aa = Allowable area per floor (square feet). At = Tabular area per floor in accordance with Table 503 If = Area increase factor due to frontage (percent as calculated in accordance with Section 506.2 Is = Area increase due to sprinkler protection as calculated in accordance with Section 506.3 Aa = Total Allowed Area of Building (summary of all stories) AREA AS DESIGNED PER STORY (Repeat for each story) Total Designed Area of Building ________________ SF ________________ SF (FIRST FLOOR) ________________ SF ________________ SF (maximum area per story) ________________ SF (maximum modified area per story) ________________ SF (area limitation per story) 15,500 27,125 27,125 54,250 6,273 7,916 ________________ SF (SECOND FLOOR) 1,643 TABLE 5-5: BUILDING HEIGHT In Feet In Stories In Feet AS DESIGNED AS DESIGNED AS DESIGNED AS DESIGNED AS ALLOWED BY IBC AS ALLOWED BY IBC AS ALLOWED BY IBC AS ALLOWED BY IBC Without any Allowable Increase (per IBC Table 503) Allowable Height Increase (per IBC 504.2) 32'-0" Total Height including any Allowable Increase 2 55'-0" 2 N/A N/A 0 0 32'-0" 2 55'-0" 2 In Stories TABLE 5-6 BUILDING DESIGN OCCUPANT LOAD FIRST FLOOR Floor Area Gross/Net Sq. Ft. Max. Area allowed per Occupant (NSF/GSF) Occupants on this Floor for this Function Design Occupant Load Function of Space Factory (F) Floor or Level Total Building Design Occupant Load: 100 gross 57 5,620 gross Industrial Areas Subtotal Design Occupant Load for This Story: 64 70 100 gross 7 653 gross Business Areas MEZZA- NINES Factory (F) 100 gross 0 0 gross Industrial Areas Subtotal Design Occupant Load for This Story: 6 300 gross 6 1,643 gross Storage & Mechanical 100 gross 0 0 gross Business Areas TABLE 5-8: FIRE RESISTANCE RATING OF BUILDING ELEMENTS BUILDING ELEMENT Structural Frame (per IBC Table 601) Rating As Provided (in hours) Testing Agency & Design No. (UL, FM, etc) -- -- Bearing Walls Exterior Interior (per IBC Table 601) Rating As Required (in hours) Designers Wall/Partition Key Code Nonbearing Walls & Partitions Exterior Interior (per IBC Table 601 & 602) Floor Construction including supporting beams & joists (per IBC Table 601) Roof Construction including supporting beams & joists (per IBC Table 601) Fire Walls (per IBC Section 705) Fire Barriers (per IBC Section 706) Shaft Enclosures (per IBC Section 707) Fire Partitions (per IBC Section 708) Opening & Protective Listing by Category (fire shutters, doors, etc. per IBC Section 715) -- -- -- 0 0 -- -- -- -- -- -- 0 0 -- -- 0 -- -- -- 0 -- -- 0 N/A -- -- -- 1 Hour 1 Hour -- -- N/A -- -- -- N/A -- -- -- N/A -- -- -- TABLE 5-9: STRUCTURAL DESIGN INFORMATION OCCUPANCY CATEGORY (IES) OCCUPANCY CATEGORY (IES) OCCUPANCY CATEGORY (IES) OCCUPANCY CATEGORY (IES) IBC Table 1604.5 LIVE LOADS LIVE LOADS LIVE LOADS LIVE LOADS Floor Live Load F ________________PSF List the F for each occupancy Roof Live Load R ________________PSF Ground Snow Load P ________________PSF IBC (Figure 1608.2) ll ll g 20 150 WIND LOADS Analysis Procedure _______________________ASCE 7 Basic Wind Speed V = _______________________3 sec gust IBC Fig 1609 Exposure Category _______________________ Wind Importance Factor I = _______________________ASCE 7 (Table 6.1) Internal Pressure Coefficient GC = _______________________ASCE 7 External Pressure Coefficient GC = _______________________ASCE 7 p pi w 3s 130 MPH ANALYTICAL PROCEDURE C 7.2 PSF 1.15 39.8 PSF SEISMIC LOADS Seismic Importance Factor I = ________ASCE 7 Soil Class ________IBC 1613.5.2 Mapped Spectral Response Accelerations S = ________ S = _________ Design Spectral Response Acceleration Parameters S = ________ S = _________ Seismic Use Group ________ASCE 7 (Seismic Occupancy Category IBC) Seismic Design Category ________IBC Tables 1613.5.6(1) & 1613.5.6(2) Basic Seismic Force Resisting System _______________________________________________ Design Base Shear ________KIPS Seismic Response Coefficient(s) C = ________ASCE 7 Response Modification Factor(s) R = ________ASCE 7 Analysis Procedure ___________________________ 10 s DS l Dl S D 1.5 0.55 3 0.557 D 153 SPECIAL REINFORCED CMU SHEAR WALLS 0.285 5.0 0.166 0.251 ARCHITECTURAL-MECHANICAL-ETC. LOADS ARCHITECTURAL-MECHANICAL-ETC. LOADS ARCHITECTURAL-MECHANICAL-ETC. LOADS ARCHITECTURAL-MECHANICAL-ETC. LOADS Provide as applicable: architectural items, mechanical, plumbing, etc. per ASCE 7 SPECIAL LOADS SPECIAL LOADS SPECIAL LOADS SPECIAL LOADS Provide as applicable: architectural items, mechanical, plumbing, etc. per ASCE 7 *per IBC Chapter 16 and ASCE 7 - Information may be shown on initial Structural Sheet of the drawings or on Sheet with other code information. List floor design loads on structural plans Equivalent Lateral Force TABLE 5-12 MECHANICAL INFORMATION AIR COMFORT SYSTEMS AIR COMFORT SYSTEMS AIR COMFORT SYSTEMS AIR COMFORT SYSTEMS Overall Thermal Transfer Value (OTTV): ____________________ Heating Load: ____________________BTU/S.F. Cooling Load: ____________________S.F./Ton OTHER LOADING FEATURES OTHER LOADING FEATURES OTHER LOADING FEATURES OTHER LOADING FEATURES Glass: U-Factor: _____________ Window-to-Wall Ratio ______________ Insulation Value: Roof: _____________ Exterior Walls: ______________ N/A 39 0.6 15.2 15.74 0.6 Outside Air minimum while occupied ________ CFM _____________ Occupants *Actual Occupant Load 800 2* MECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENT MECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENT MECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENT MECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENT Chilled water air handling unit with hot water reheat. Ventilation Fans with Unit Heaters for main plant area. Fan Coil Units with electric heat for office areas. 3.84 TABLE 5-13: ELECTRICAL INFORMATION SERVICE TRANSFORMER: ________By Utility ________By Agency _________KVA Primary _________Voltage/Phase NA ELECTRICAL SERVICE INFORMATION ELECTRICAL SERVICE INFORMATION ELECTRICAL SERVICE INFORMATION ELECTRICAL SERVICE INFORMATION: Service Voltage/Phase _________________________Amperes Service Entrance Conductors Size: _________________________Quantity per Phase Total Connected Load: _________________________KVA Estimated Maximum Demand: _________________________KVA Fault Current Rating of Overcurrent Device: _________________________ Available Fault Current At The Service Disconnecting Means: _________________________ Interrupting Capacity of Service Overcurrent Device: _________________________ Grounding Electrode System Components: _________________________per NEC 250-C _________________________ _________________________ _________________________ _________________________ NA EMERGENCY SERVICE INFORMATION Emergency Generator: ____No ____Yes ____KVA Voltage/Phase __________ __________Fuel Exit/ Emergency Lights Backup Power: ____Integral Battery _____Generator Fire Alarm System: ____Manual ____Automatic ____Addressable ____Class A ____Class B 4,000 10 3,640 3,276 65,000 A 4,000 A a) Ground Rod Cluster LIGHTNING PROTECTION PROVIDED LIGHTNING PROTECTION PROVIDED LIGHTNING PROTECTION PROVIDED LIGHTNING PROTECTION PROVIDED ____No ____Yes COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED Contact Chief Information Office for applicability, (803) 898-8121 _____Not Required _____Yes b) Metal Building Frame 480/227V, 3-phase, 4-wire 600 MCM c) Metal Water Pipes d) Metal Gas Pipes e) Rebar in Concrete Slab f) Lighting Protection System 52,298 A 5.1.3 CODES AND STANDARDS A. International Building Code (IBC), 2006 Edition. B. International Existing Building Code (IEBC), 2006 Edition C. International Fire Code (IFC), 2006 Edition. D. International Energy Conservation Code (IECC), 2006 Edition. E. International Fuel Gas Code (IFGC), 2006 Edition. F. International Mechanical Code (IMC), 2006 Edition. G. International Plumbing Code (IPC), 2006 Edition. 1. Section 305.6.1, insert "24" and insert "24" 2. Section 904.1, insert "8" H. International Private Sewage Disposal Code (IPSDC), 2006 Edition. I. International Property Maintenance Code (IPMC), 2006 Edition. J. International Residential Code for One and Two Family Dwellings (IRC), 2006 Edition with the following insertions: 1. P2603.1, insert "12" and insert "24" K. International Wildland - Urban Interface Code (IUWIC), 2006 Edition, Note: The IUWIC does not supersede existing stationary requirements L. International Code Council Electric Code, 2006 Edition M. National Electrical Code (NEC) [NFPA 70], 2008 Edition N. National Electrical Safety Code, ANSI-C2-2002 Edition O. Latest edition of the American National Standards Institute, Inc. (ANSI) document A117.1, Accessible and Useable Buildings and Facilities. Note that this standard is the standard adopted by the South Carolina Accessibility Act but this requirement does not relieve the Agency or the design professional from the Federal Statutory requirements that design and construction comply with the Americans With Disabilities Act Accessibility Guidelines for Buildings and Facilities. See http://www.access-board.gov./adaag/html/adaag.htm P. State Fire Marshal rules, regulations, and policies. See http://www.llr.state.sc.us/firemarshall.asp Q. South Carolina Elevator Code & Regulations. See http://www.llr.state.sc.us/Labor/index.aspfile=elevatorsindex.htm R. State of SC Telephone Equipment Room and Communications/Data Systems Policies as formulated by the Office of Information Resources (OIR) Telecommunications. S. International Code Council Performance Code (ICCPC), 2006 Edition, upon State Engineer's written approval. T. Governors executive Order No. 82-19 (April 1982) - State of SC Building Standards in Floodplain Areas. U. The South Carolina Modular Buildings Construction Act S.C. Code 23-43-10 et. Seq. TABLE 5-10: PLUMBING INFORMATION FIRST FLOOR: FACTORY OCCUPANCY: 70 Persons (35 Male and 35 Female)* Water Closets Req'd.: Male: 1 (1 per 100* per IPC 419.2 - no more than 66.7% of required water closets may be substituted with urinals) Female: 1 (1 per 100) Lavatories Req'd.: Male: 1 (1 per 100) Female: 1 (1 per 100) Drinking Fountains Req'd.: 1 (1 per 100) Water Closets MALE REQUIRED. Lavatories: WATER SYSTEM WATER SYSTEM WATER SYSTEM WATER SYSTEM Service Line Size ____________Inches Peak ____________GPM 4 150 Total Demand ____________No. Fixture Units 38.25 SANITARY SEWER SYSTEM SANITARY SEWER SYSTEM SANITARY SEWER SYSTEM SANITARY SEWER SYSTEM Loading __________________________________________________GPD __________________________________________________ Service Line Size _______________________________Inches Slope _______________________________min inches/ft. MINIMUM PLUMBING FIXTURES REQUIRED/PROVIDED MINIMUM PLUMBING FIXTURES REQUIRED/PROVIDED MINIMUM PLUMBING FIXTURES REQUIRED/PROVIDED MINIMUM PLUMBING FIXTURES REQUIRED/PROVIDED per IBC Section 403 & Table 403.1 per IBC Section 403 & Table 403.1 per IBC Section 403 & Table 403.1 per IBC Section 403 & Table 403.1 Urinals: OTHER FIXTURES: Unisex Toilet Service Sink MALE PROVIDED FEMALE REQUIRED: FEMALE PROVIDED: REQUIRED. PROVIDED Drinking Fountains 1 2 per IBC Section 403 & Table 403.1 0 1 1* 1 1 1* 1 1* 1 1* 1 1* 0 0 N/A N/A * Toilet and Lavatories provided at Unisex Toilet Room Per IBC 2902.2 Exception 2 - Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers of 15 or less. 6" Building, 8" Cooling Towers 1/8" per 1'-0" 150 (excludes Cooling Tower bleed off); Cooling Tower bleed off = 16,000 GPD at peak TABLE 5-7: GENERAL FIRE PROTECTION REQUIREMENTS Fireblocking Required SEPARATIONS Draftstopping Required Smoke Control System Required Smoke Barriers Required Fire Partition Required Fire Barrier Required Smoke Partitions Required SEPARATIONS SUPPRESSION Fire Alarm System Required Emergency Alarm System Required Standpipes Required Sprinklers Required Sprinklers Provided Portable extinguishers required Other suppression systems required Smoke & heat vents required Other: (Indicate other provided fire and life safety features not listed above if any) per IBC Section 717 per IBC Section 717 per IBC Section 909 per IBC Section 407 & 408 per IBC Section 407 per IBC Section 419 per IBC Section 706 per IBC Section 907 per IFC 908 per IFC Section 905 per IFC Section 903 per IFC 906 per IFC 904 per IFC 910 no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes no yes TABLE 5-3: BASIC BUILDING CODE INFORMATION CONSTRUCTION CLASSIFICATION OCCUPANCY GROUP (indicate all) (Note IBC 506.4.1) OCCUPANCY GROUP (indicate most restrictive) Does building require Incidental Use Area Separation? Does building have Accessory Occupancy (ies)? What percent of story is accessory occupancy? Mixed Occupancy Non separation Separation OTHER FIRE PROTECTION SYSTEMS, DEVICES OR FEATURES If the building has any special or notable fire protection or safety feature of hazard the designers should list them here, describe the performance characteristics and refer to locations in construction documents. (e.g. fire extinguishers, smoke-evacuation/control/compartments. Note IBC 414.1.3) (IBC 508.3) (IBC 508.3.1) (IBC 508.2.2) (IBC 508.3.2) (IBC 508.3) (IBC 506.4.1) __________ SF __________ % no yes _______________________________ (IBC Table 503) _______________________________ (IBC Table 302) Type _______________________________ (IBC Table 602) IIB F-1 (FACTORY); B (BUSINESS) F-1 FACTORY 646 9.6 no yes no yes no yes no yes CENTRAL COOLING AND HEATING PLANT CONSULTANT: SHEET NUMBER CHECK BY: DRAWN BY: DATE: DWG JOB NO.: PLOT DATE: 09107 HORRY COUNTY, SOUTH CAROLINA DATE REV: STATE PROJECT NO.: H17-9569-LC Watson Tate Savory Liollio A R C H I T E C T U R E Charleston Asheville Charlotte Columbia RRF CME A0.1 CODE INFORMATION 07/05/11 REV. DATE DESCRIPTION
24
Embed
PROJECT NARRATIVE TABLE 5-3: BASIC BUILDING … · FLOOD HAZARD AREA Base Flood Elevation ... Subgrade _____ % ASTM D698 ASTM D1557 AASHTO ... Drinking Fountains Req'd.: 1 …
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
PROJECT NARRATIVE
The Central Cooling and Heating Plant is a (+/-)7,924 S.F. structure containing equipment to serve chillers,cooling towers and boilers to serve hot and cold water supply to campus facilities. Support offices andmaintenance spaces are included in the facility construction.
TABLE 5-1: FLOOR HAZARD INFORMATION and FLOOR LOADS
FLOOD HAZARD AREA
Base Flood Elevation _______________ MSL NGVD or FIRMDesign Floor Elevation _______________ MSL IBC 1612.3 and ASCE 24
NON-HIGH VELOCITY WAVE ACTION
Elevation of Lowest Proposed Floor _______________ MSL Meet ASCE 24 Section 2.6.2.1Dry flood proofing _____ no _____ yes per ASCE 24
HIGH-VELOCITY WAVE ACTION
Elevation of bottom of Lowest Horizontal Structural Member of lowest floor __________________ MSLFlotation resistant _____ no _____ yes per ASCE 24Breakaway wall _____ no _____ yes per ASCE 24
IBC 1612 and SE-900, as applicable
N/A
43.0
Zone X,Community # 450104,Panel # 0517
43.0
40.67
TABLE 5-2: SOILS & SITE
SOILS INVESTIGATION (If available)
SOILS CLASSIFICATION
Site Class (seismic class)Classes Soil of Materials (UCS System)Allowable Footing Bearing Pressure
Base _____________ % ASTM D698 ASTM D1557AASHTO (only for paving & roads)
Other _____________ % ASTM D698 ASTM D1557AASHTO (only for paving & roads)
MINIMUM DESIGN SOIL LATERAL LOAD____________________ psf per IBC table 1610.1
FOOTINGS
Undisturbed FootingsCompacted Fill Material
ELEVATIONS
Elevation of Water Table
Elevation of lowest footingElevation of lowest floor or basement
no yes
per IBC table 1803.5no yes
2,000
98
100
NA
80 (Active Lateral)
______________ MSL
______________ MSL______________ MSL
41.67 (TOF)
36.7
43.0
____________________ psf720 (Passive Lateral)
Water at 4'-4" to 5'-4" below exist.ground surface (4.8' Average).
TABLE 5-4: BUILDING AREA
AREA LIMIT BY TABLE 503 OF IBC(Do not indicate increases for sprinklers & street frontage.)
AREA MODIFICATION FROM EQUATIONS 5-1 OF IBC(Insert equation from IBC 506.1 with completed calculations in this Box)(Equation 5-1)
Aa = At + [ At x If] + [At x Is]
Aa = Allowable area per floor (square feet).At = Tabular area per floor in accordance with Table 503If = Area increase factor due to frontage (percent as calculated
in accordance with Section 506.2Is = Area increase due to sprinkler protection as calculated
in accordance with Section 506.3
Aa =
Total Allowed Area of Building(summary of all stories)
AREA AS DESIGNED PER STORY(Repeat for each story)
Total Designed Area of Building
________________ SF
________________ SF(FIRST FLOOR)
________________ SF
________________ SF(maximum area per story)
________________ SF(maximum modified area per story)
________________ SF(area limitation per story)
15,500
27,125
27,125
54,250
6,273
7,916
________________ SF(SECOND FLOOR)
1,643
TABLE 5-5: BUILDING HEIGHT
In Feet In Stories In Feet
AS DESIGNEDAS DESIGNEDAS DESIGNEDAS DESIGNED AS ALLOWED BY IBCAS ALLOWED BY IBCAS ALLOWED BY IBCAS ALLOWED BY IBC
Without any Allowable Increase(per IBC Table 503)
Allowable Height Increase(per IBC 504.2)
32'-0"
Total Height including anyAllowable Increase
2 55'-0" 2
N/A N/A 0 0
32'-0" 2 55'-0" 2
In Stories
TABLE 5-6 BUILDING DESIGN OCCUPANT LOAD
FIRSTFLOOR
Floor AreaGross/Net Sq. Ft.
Max. Area allowedper Occupant
(NSF/GSF)
Occupants onthis Floor for
this Function
Design OccupantLoadFunction of Space
Factory (F)
Floor orLevel
Total Building Design Occupant Load:
100 gross 575,620 gross Industrial Areas
Subtotal Design Occupant Load for This Story: 64
70
100 gross 7653 gross Business Areas
MEZZA-NINES
Factory (F)
100 gross 00 gross Industrial Areas
Subtotal Design Occupant Load for This Story: 6
300 gross 61,643 gross Storage & Mechanical
100 gross 00 gross Business Areas
TABLE 5-8: FIRE RESISTANCE RATING OF BUILDING ELEMENTS
BUILDING ELEMENT
Structural Frame(per IBC Table 601)
Rating As Provided(in hours)
Testing Agency & Design No.(UL, FM, etc)
----
Bearing WallsExteriorInterior
(per IBC Table 601)
Rating As Required(in hours)
Designers Wall/PartitionKey Code
Nonbearing Walls & PartitionsExteriorInterior
(per IBC Table 601 & 602)
Floor Construction including supportingbeams & joists(per IBC Table 601)
Roof Construction including supportingbeams & joists(per IBC Table 601)
Floor Live Load F ________________PSF List the F for each occupancyRoof Live Load R ________________PSFGround Snow Load P ________________PSF IBC (Figure 1608.2)
Seismic Importance Factor I = ________ASCE 7Soil Class ________IBC 1613.5.2Mapped Spectral Response Accelerations S = ________ S = _________Design Spectral Response Acceleration Parameters S = ________ S = _________Seismic Use Group ________ASCE 7 (Seismic Occupancy Category IBC)Seismic Design Category ________IBC Tables 1613.5.6(1) & 1613.5.6(2)Basic Seismic Force Resisting System _______________________________________________Design Base Shear ________KIPSSeismic Response Coefficient(s) C = ________ASCE 7Response Modification Factor(s) R = ________ASCE 7Analysis Procedure ___________________________
10
s
DS
l
Dl
S
D1.5
0.55
30.557
D
153
SPECIAL REINFORCED CMU SHEAR WALLS
0.285
5.0
0.166
0.251
ARCHITECTURAL-MECHANICAL-ETC. LOADSARCHITECTURAL-MECHANICAL-ETC. LOADSARCHITECTURAL-MECHANICAL-ETC. LOADSARCHITECTURAL-MECHANICAL-ETC. LOADS Provide as applicable: architectural items,mechanical, plumbing, etc. per ASCE 7
SPECIAL LOADSSPECIAL LOADSSPECIAL LOADSSPECIAL LOADS Provide as applicable: architectural items,mechanical, plumbing, etc. per ASCE 7
*per IBC Chapter 16 and ASCE 7 - Information may be shown on initial Structural Sheet of the drawings or on Sheet withother code information. List floor design loads on structural plans
Equivalent Lateral Force
TABLE 5-12 MECHANICAL INFORMATION
AIR COMFORT SYSTEMSAIR COMFORT SYSTEMSAIR COMFORT SYSTEMSAIR COMFORT SYSTEMSOverall Thermal Transfer Value (OTTV): ____________________Heating Load: ____________________BTU/S.F.Cooling Load: ____________________S.F./Ton
OTHER LOADING FEATURESOTHER LOADING FEATURESOTHER LOADING FEATURESOTHER LOADING FEATURESGlass: U-Factor: _____________ Window-to-Wall Ratio ______________Insulation Value: Roof: _____________ Exterior Walls: ______________
N/A39
0.615.2 15.74
0.6
Outside Air minimum while occupied ________ CFM _____________ Occupants *Actual Occupant Load800 2*
MECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENTMECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENTMECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENTMECHANICAL SYSTEMS, SERVICE SYSTEMS & EQUIPMENTChilled water air handling unit with hot water reheat.Ventilation Fans with Unit Heaters for main plant area.Fan Coil Units with electric heat for office areas.
3.84
TABLE 5-13: ELECTRICAL INFORMATION
SERVICE TRANSFORMER: ________By Utility ________By Agency_________KVA Primary _________Voltage/PhaseNA
ELECTRICAL SERVICE INFORMATIONELECTRICAL SERVICE INFORMATIONELECTRICAL SERVICE INFORMATIONELECTRICAL SERVICE INFORMATION:Service Voltage/Phase _________________________Amperes
Service Entrance Conductors Size: _________________________Quantity per Phase
Total Connected Load: _________________________KVAEstimated Maximum Demand: _________________________KVAFault Current Rating of Overcurrent Device: _________________________Available Fault Current At The Service Disconnecting Means: _________________________
Interrupting Capacity of Service Overcurrent Device: _________________________
Grounding Electrode System Components: _________________________per NEC 250-C
_________________________
_________________________
_________________________
_________________________
NA
EMERGENCY SERVICE INFORMATIONEmergency Generator: ____No ____Yes ____KVA Voltage/Phase __________ __________Fuel
COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED COMMUNICATIONS COORDINATED Contact Chief Information Office for applicability, (803) 898-8121_____Not Required _____Yes
b) Metal Building Frame
480/227V, 3-phase, 4-wire
600 MCM
c) Metal Water Pipes
d) Metal Gas Pipes
e) Rebar in Concrete Slab
f) Lighting Protection System
52,298 A
5.1.3 CODES AND STANDARDS
A. International Building Code (IBC), 2006 Edition.B. International Existing Building Code (IEBC), 2006 EditionC. International Fire Code (IFC), 2006 Edition.D. International Energy Conservation Code (IECC), 2006 Edition.E. International Fuel Gas Code (IFGC), 2006 Edition.F. International Mechanical Code (IMC), 2006 Edition.G. International Plumbing Code (IPC), 2006 Edition.
H. International Private Sewage Disposal Code (IPSDC), 2006 Edition.I. International Property Maintenance Code (IPMC), 2006 Edition.J. International Residential Code for One and Two Family Dwellings (IRC), 2006 Edition with the following
insertions:1. P2603.1, insert "12" and insert "24"
K. International Wildland - Urban Interface Code (IUWIC), 2006 Edition,Note: The IUWIC does not supersede existing stationary requirements
L. International Code Council Electric Code, 2006 EditionM. National Electrical Code (NEC) [NFPA 70], 2008 EditionN. National Electrical Safety Code, ANSI-C2-2002 EditionO. Latest edition of the American National Standards Institute, Inc. (ANSI) document A117.1, Accessible and
Useable Buildings and Facilities. Note that this standard is the standard adopted by the South CarolinaAccessibility Act but this requirement does not relieve the Agency or the design professional from the FederalStatutory requirements that design and construction comply with the Americans With Disabilities Act AccessibilityGuidelines for Buildings and Facilities. See http://www.access-board.gov./adaag/html/adaag.htm
P. State Fire Marshal rules, regulations, and policies. See http://www.llr.state.sc.us/firemarshall.aspQ. South Carolina Elevator Code & Regulations. See http://www.llr.state.sc.us/Labor/index.aspfile=elevatorsindex.htmR. State of SC Telephone Equipment Room and Communications/Data Systems Policies as formulated by the Office of
Information Resources (OIR) Telecommunications.S. International Code Council Performance Code (ICCPC), 2006 Edition, upon State Engineer's written approval.T. Governors executive Order No. 82-19 (April 1982) - State of SC Building Standards in Floodplain Areas.U. The South Carolina Modular Buildings Construction Act S.C. Code 23-43-10 et. Seq.
TABLE 5-10: PLUMBING INFORMATION
FIRST FLOOR:FACTORY OCCUPANCY: 70 Persons (35 Male and 35 Female)*
Water Closets Req'd.: Male: 1 (1 per 100* per IPC 419.2 - no more than 66.7% of required water closets may be substituted with urinals)
Female: 1 (1 per 100)Lavatories Req'd.: Male: 1 (1 per 100)
Female: 1 (1 per 100)Drinking Fountains Req'd.: 1 (1 per 100)
Water Closets
MALE REQUIRED.
Lavatories:
WATER SYSTEMWATER SYSTEMWATER SYSTEMWATER SYSTEM
Service Line Size ____________Inches
Peak ____________GPM
4
150
Total Demand ____________No. Fixture Units38.25
SANITARY SEWER SYSTEMSANITARY SEWER SYSTEMSANITARY SEWER SYSTEMSANITARY SEWER SYSTEM
* Toilet and Lavatories provided at Unisex Toilet Room Per IBC 2902.2 Exception 2 - Separate facilities shall notbe required in structures or tenant spaces with a total occupant load, including both employees and customersof 15 or less.
6" Building, 8" Cooling Towers1/8" per 1'-0"
150 (excludes Cooling Tower bleed off);Cooling Tower bleed off = 16,000 GPD at peak
TABLE 5-7: GENERAL FIRE PROTECTION REQUIREMENTS
Fireblocking Required
SEPARATIONS
Draftstopping Required
Smoke Control System Required
Smoke Barriers Required
Fire Partition Required
Fire Barrier Required
Smoke Partitions Required
SEPARATIONS
SUPPRESSION
Fire Alarm System Required
Emergency Alarm System Required
Standpipes Required
Sprinklers Required
Sprinklers Provided
Portable extinguishers required
Other suppression systems required
Smoke & heat vents required
Other: (Indicate other provided fire and life safety features not listed above if any)
per IBC Section 717
per IBC Section 717
per IBC Section 909
per IBC Section 407 & 408
per IBC Section 407
per IBC Section 419
per IBC Section 706
per IBC Section 907
per IFC 908
per IFC Section 905
per IFC Section 903
per IFC 906
per IFC 904
per IFC 910
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
no yes
TABLE 5-3: BASIC BUILDING CODE INFORMATION
CONSTRUCTION CLASSIFICATION
OCCUPANCY GROUP (indicate all)(Note IBC 506.4.1)
OCCUPANCY GROUP (indicate most restrictive)
Does building require Incidental Use Area Separation?
Does building have Accessory Occupancy (ies)?What percent of story is accessory occupancy?
Mixed Occupancy
Non separation
Separation
OTHER FIRE PROTECTION SYSTEMS, DEVICES OR FEATURESIf the building has any special or notable fire protection or safety feature of hazard the designers should list themhere, describe the performance characteristics and refer to locations in construction documents. (e.g. fireextinguishers, smoke-evacuation/control/compartments. Note IBC 414.1.3)
(IBC 508.3)
(IBC 508.3.1)
(IBC 508.2.2)
(IBC 508.3.2)
(IBC 508.3)(IBC 506.4.1)
__________ SF__________ %
no yes
_______________________________ (IBC Table 503)
_______________________________ (IBC Table 302)
Type _______________________________ (IBC Table 602)IIB
EXPOSED CMU WITH PAINT FINISHAT LOCKER ROOM (TYP.)
D
FIRST FLOOR0' - 0"
T16
FULL-HEIGHTLOCKERS
8' -
0"
3
FIRST FLOOR0' - 0"
6' - 0" (6 FULL SIZE LOCKERS)
8' -
0"
106
T16 T16 T16 T16 T16 T16
STEEL COLUMN, SEE STRUCTURAL
3
FIRST FLOOR0' - 0"
MIN
.
1' -
6"
3' -
3"
2' -
9"
T1
T2
T3T6
T8
3' - 0" 6"
FIRST FLOOR0' - 0"
T10
T12
T11
T15
8' -
0"T3
FIRST FLOOR0' - 0"
4' -
0"
2' -
9"
3' -
3"
MIN
.
1' -
6"
1' - 6"
T10
T3
T13
T12
T14
1
PARTITION TYPE 1:8" REINFORCED FULL HEIGHT
CMU WALL (SEE STRUCTURAL)
PARTITION TYPE 2:8" REINFORCED PARTIAL HEIGHT
CMU WALL (SEE STRUCTURAL)
PARTITION TYPE LEGEND:
2
PARTITION TYPE 3:4" FULL HEIGHT CMU WALL
(SEE STRUCTURAL)
3
PARTITION TYPE 4:6" REINFORCED FULL HEIGHT
CMU WALL (SEE STRUCTURAL)
4
CE
NT
RA
L C
OO
LIN
G A
ND
HE
AT
ING
PLA
NT
CONSULTANT:
SHEET NUMBER
CHECK BY:
DRAWN BY:
DATE:
DWG JOB NO.:
PLOT DATE:
09107
HO
RR
Y C
OU
NT
Y, S
OU
TH
CA
RO
LIN
A
DATE
REV:
STATE PROJECT NO.:
H17-9569-LC
Watson Tate Savory LiollioA R C H I T E C T U R E
Charleston Asheville Charlotte Columbia
RRF
CME
A7.4
TO
ILE
T P
LA
NS
, E
LE
VA
TIO
NS
& D
ET
AIL
S
07/05/11
1/2" = 1'-0"A7.4
1 ENLARGED FIRST FLOOR PLAN
1/2" = 1'-0"A7.4
2 TOILET 107 - NORTH ELEVATION 1/2" = 1'-0"A7.4
4 TOILET 107 - SOUTH ELEVATION
1/2" = 1'-0"A7.4
5 TOILET 107 - WEST ELEVATION
N
TOILET ACCESSORIES
NO. ITEM MOUNTING HEIGHT MFG. MODEL NO.
T1 36" STAINLESS STEEL HORIZONTAL GRAB BAR WITH SATIN FINISH(HORIZONTALLY MOUNTED)
2'-9" TO CENTERLINE OF GRAB BAR BOBRICK B-5806 x 36
T2 42" STAINLESS STEEL HORIZONTAL GRAB BAR WITH SATIN FINISH(HORIZONTALLY MOUNTED)
2'-9" TO CENTERLINE OF GRAB BAR BOBRICK B-5806 x 42
T3 18" STAINLESS STEEL VERTICAL GRAB BAR WITH SATIN FINISH (VERTICALLYMOUNTED)
3'-3" TO CENTERLINE OF BOTTOM MOUNTING PLATE BOBRICK B-5806 x 18
T4 SURFACE MOUNTED MULTI-ROLL TOILET TISSUE DISPENSER 19" TO BOTTOM OF UNIT, PROVIDE 1 1/2" MIN OF CLEARANCE BETWEENTOILIET TISSUE DISPENSER AND GRAB BAR
BOBRICK B-2888
T5 AUTOMATIC HAND DRYER ELECT. 38" TO BOTTOM OF DRYER BOBRICK B-700
T6 SURFACE MOUNTED STAINLESS STEEL PAPER TOWEL DISPENSER AND WASTERECEPTACLE (14" X 28")
48" TO BOTTOM OF TOWEL DISPENSER PORTION OF UNIT BOBRICK B-3699
T7 SURFACE MOUNTED SOAP DISPENSER 49" TO TOP OF DISPENSER BOBRICK B-2112
T8 GLASS MIRROR WITH STAINLESS STEEL ANGLE FRAME (24" x 48") 3'-4" TO BOTTOM OF MIRROR BOBRICK B-165 2448
T9 HEAVY-DUTY ROBE HOOK 48" TO CENTERLINE OF ROBE HOOK BOBRICK B-2116
T10 HEAVY-DUTY SHOWER CURTAIN ROD WITH CONCEALED MOUNTING,42" X 72" VINYL SHOWER CURTAIN
STAINLESS STEEL SHOWER CURTAIN HOOKS
COORDINATE MOUNTING HEIGHT WITH CURTAIN MFR. BOBRICK B-6107B204-2
B204-1
T11 REVERSIBLE SOLID PHENOLIC FOLDING SHOWER SEAT 18" FROM SEAT FROM FINISH FLOOR BOBRICK B-5181
T12 HORIZONTAL SHOWER COMPARTMENT GRAB BAR (24" X 36") 3'-2" TO CENTERLINE OF GRAB BAR BOBRICK B-58616.99