-
PROJECT MANUAL TOWN OF WOODBRIDGE
OLD WOODBRIDGE FIRE STATION RENOVATIONS 4 NEWTON ROAD
WOODBRIDGE, CT 06525 BID #2018-13
S/P+A PROJECT NO. 11.147
VOLUME 2 OF 2 CD Submission: December 21, 2012 Revised CD
Submission: June 9, 2017 Local Review Submission: July 28, 2017
Final CD Submission: March 16, 2018 Issued for Bid: May 18,
2018
Architects/Engineers/Interior Designers Silver/Petrucelli +
Associates, Inc. 3190 Whitney Avenue, Building 2 Hamden,
Connecticut 06518
-
TABLE OF CONTENTS
Old Woodbridge Fire Station Renovations TOC-1
RENOVATIONS OLD WOODBRIDGE FIRE STATION 4 NEWTON ROAD
WOODBRIDGE, CT 06525 BID #2018-13 S/P+A PROJECT NO. 11.147 DIVISION
0 – PROCUREMENT AND CONTRACT REQUIREMENTS PAGES
Invitation to Bid 1 Instructions to Bidders 7 Supplementary
Instructions to Bidders 1 Bid Form 4 CHRO Contract Compliance
Regulations Notification To Bidders 5 Attachment ‘A’ –
Non-Collusion Affidavit 1 Delinquent Tax Affidavit 1 Certification
of Bidder 1 Reference Sheet Listing 1 Form W-9, Request for
Taxpayer Identification Number and Certification 4 Standard Form of
Agreement between Owner and Contractor (AIA A101) 7 General
Conditions of the Contract for Construction (AIA A201) 40
Supplementary General Conditions 6 Project Application and Project
Certificate for Payment (AIA G702) 1 Project Application
Continuation Sheet (AIA G703) 1 Prevailing Wage Rate Information
Drawing List 2
DIVISION 1 – GENERAL REQUIREMENTS
Section 011000 Summary of Work 2 Section 012200 Unit Prices 2
Section 012300 Alternates 2 Section 012500 Substitution Procedures
4 Section 012600 Contract Modification Procedures 3 Section 012900
Payment Procedures 4 Section 013100 Project Management and
Coordination 10 Section 013200 Construction Progress Documentation
6 Section 013233 Photographic Documentation 2 Section 013300
Submittal Procedures 10 Section 014000 Quality Requirements 10
Section 014200 References 10 Section 015000 Temporary Facilities
and Controls 5 Section 016000 Product Requirements 5 Section 017300
Execution 8 Section 017700 Closeout Procedures 4 Section 017823
Operation and Maintenance Data 8 Section 017839 Project Record
Documents 4 Section 017900 Demonstration and Training 4
-
TABLE OF CONTENTS
Old Woodbridge Fire Station Renovations TOC-2
DIVISION 2 – EXISTING CONDITIONS
Section 024119 Selective Demolition 7 Data Gap Asbestos
Inspection, October 2008 59 Work Plan for the Removal of Exterior
Lead-Based Paint and Exterior
Painting, January 2009 38
DIVISION 3 – CONCRETE
Section 033000 Cast-In-Place Concrete 23
DIVISION 4 – MASONRY
Section 042200 Concrete Unit Masonry 11
DIVISION 5 – METALS
Section 055000 Metal Fabrications 7 Section 055213 Pipe and Tube
Railings 6
DIVISION 6 – WOOD, PLASTICS AND COMPOSITES
Section 061000 Rough Carpentry 8 Section 061600 Sheathing 5
Section 062013 Exterior Finish Carpentry 5 Section 062023 Interior
Finish Carpentry 6 Section 064116 Plastic-Laminate-Clad
Architectural Cabinets 7
DIVISION 7 – THERMAL AND MOISTURE PROTECTION
Section 071700 Bentonite Waterproofing 4 Section 072100 Thermal
Insulation 4 Section 072500 Weather Barriers 3 Section 072713
Modified Bituminous Sheet Air Barriers 7 Section 073113 Asphalt
Shingles 5 Section 074646 Fiber Cement Siding 4 Section 075216
Styrene-Butadiene-Styrene (SBS) Modified Bituminous Membrane
Roofing 10 Section 075323 Ethylene-Propylene-Diene-Monomer (EPDM)
Roofing 9 Section 076200 Sheet Metal Flashing and Trim 9 Section
077200 Roof Accessories 6 Section 078413 Penetration Firestopping 4
Section 079200 Joint Sealants 7
DIVISION 8 – OPENINGS
Section 081213 Hollow Metal Frames 7 Section 081416 Flush Wood
Doors 5 Section 081423 Clad Commercial Doors 6 Section 083113
Access Doors and Frames 4 Section 085200 Wood Windows 4
-
TABLE OF CONTENTS
Old Woodbridge Fire Station Renovations TOC-3
Section 087100 Door Hardware 17 Section 088000 Glazing 11
Section 089000 Louvers and Vents 5
DIVISION 9 – FINISHES
Section 092216 Non-Structural Metal Framing 4 Section 092900
Gypsum Board 6 Section 093000 Tiling 9 Section 095113 Acoustical
Panel Ceilings 7 Section 096400 Wood Flooring 5 Section 096513
Resilient Base and Accessories 5 Section 096519 Resilient Tile
Flooring 4 Section 099113 Exterior Painting 5 Section 099123
Interior Painting 7
DIVISION 10 – SPECIALTIES
Section 101400 Signage 6 Section 102113.13 Metal Toilet
Compartments 5 Section 102600 Wall and Door Protection 5 Section
102800 Toilet, Bath and Laundry Accessories 4 Section 104416 Fire
Extinguishers 3
DIVISION 11 – EQUIPMENT
Section 113100 Residential Appliances 8
DIVISION 12 – FURNISHINGS
Section 123623.13 Plastic-Laminate-Clad Countertops 5 Section
124813 Entrance Floor Mats and Frames 3
DIVISION 14 – CONVEYING EQUIPMENT
Section 142600 Limited-Use/Limited-Application Elevators 8
DIVISION 21 – FIRE SUPPRESSION
Section 210500 Common Work Results for Fire Suppression 9
Section 210548 Vibration and Seismic Controls for Fire Suppression
Piping and Equipment 4 Section 210553 Identification for Fire
Suppression Piping and Equipment 5
Section 211100 Facility Fire-Suppression Water-Service Piping 9
Section 211313 Wet-Pipe Sprinkler Systems 19 Section 211316
Dry-Pipe Sprinkler Systems 20
DIVISION 22 – PLUMBING
Section 220500 Common Work Results for Plumbing 13 Section
220516 Expansion Fittings and Loops for Plumbing Piping 4
-
TABLE OF CONTENTS
Old Woodbridge Fire Station Renovations TOC-4
Section 220519 Meters and Gages for Plumbing Piping 6 Section
220523 General-Duty Valves for Plumbing Piping 6 Section 220529
Hangers and Supports for Plumbing Piping and Equipment 11 Section
220548 Vibration and Seismic Controls for Plumbing Piping and
Equipment 8 Section 220553 Identification for Plumbing Piping and
Equipment 5 Section 220700 Plumbing Insulation 17 Section 221116
Domestic Water Piping 6 Section 221123 Domestic Water Pumps 5
Section 221316 Sanitary Waste and Vent Piping 7 Section 221413
Facility Storm Drainage Piping 7 Section 221423 Storm Drainage
Piping Specialties 6 Section 221519 Plumbing Specialties 6 Section
223400 Fuel-Fired, Domestic Water Heaters 6 Section 224000 Plumbing
Fixtures 5
DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING
Section 230000 Basic Mechanical Requirements 4 Section 230500
Common Work Results for HVAC 7 Section 230529 Hangers and Supports
for HVAC Piping and Equipment 10 Section 230548 Vibration and
Seismic Controls for HVAC Piping and Equipment 10 Section 230553
Identification for HVAC Piping and Equipment 4 Section 230593
Testing, Adjusting and Balancing for HVAC 15 Section 230713 Duct
Insulation 17 Section 230923.51 Toxic Gas Monitor 4 Section 230993
Sequence of Operations for HVAC Controls 21 Section 231123 Facility
Natural-Gas Piping 7 Section 232300 Refrigerant Piping 10 Section
232923 Variable Frequency Drives 14 Section 233113 Metal Ducts 14
Section 233300 Air Duct Accessories 14 Section 233423 HVAC Power
Ventilators 7 Section 233533 Listed Kitchen Ventilation System
Exhaust Ducts 4 Section 233713 Diffusers, Registers and Grilles 5
Section 233723 HVAC Gravity Ventilators 5 Section 233813
Commercial-Kitchen Hoods 8 Section 235123 Gas Vents 3 Section
235513.16 Gas-Fired Duct Heater 5 Section 235533.16 Gas-Fired Unit
Heaters 7 Section 236200 Packaged Compressor and Condenser Units 7
Section 237323 Indoor Air Handling Units 6 Section 237416 Packaged,
Small-Capacity, Rooftop Air-Conditioning Units 11 Section 238239.16
Propeller Unit Heaters 4 Section 238239.19 Wall Heaters 3 Section
238416.16 Indoor, Mechanical Dehumidification Units 4
DIVISION 26 – ELECTRICAL
Section 260500 Common Work Results for Electrical 4 Section
260509 Electrical Demolition Requirements 2 Section 260519
Low-Voltage Electrical Power Conductors and Cables 6
-
TABLE OF CONTENTS
Old Woodbridge Fire Station Renovations TOC-5
Section 260523 Control-Voltage Electrical Power Cables 11
Section 260526 Grounding and Bonding for Electrical Systems 7
Section 260529 Hangers and Supports for Electrical Systems 6
Section 260533 Raceway and Boxes for Electrical Systems 11 Section
260544 Sleeves and Sleeve Seals for Electrical Raceways and Cabling
4 Section 260548 Vibration and Seismic Controls for Electrical
Systems 7 Section 260553 Identification for Electrical Systems 10
Section 260573 Overcurrent Protective Device Coordination Study 5
Section 260574 Overcurrent Protective Device Arc-Flash Study 6
Section 260923 Lighting Control Devices 6 Section 262416
Panelboards 11 Section 262726 Wiring Devices 8 Section 262813 Fuses
4 Section 262816 Enclosed Switches and Circuit Breakers 9
Section 265100 Interior Lighting 11 Section 265219 Emergency and
Exit Lighting 9
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
Section 281300 Access Control 12 Section 283111 Digital,
Addressable Fire Alarm Systems 15
DIVISION 31 – EARTHWORK
Section 312000 Earth Moving 6
END OF TABLE OF CONTENTS
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-1
SECTION 113100 - RESIDENTIAL APPLIANCES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Cooking appliances. 2. Kitchen exhaust ventilation. 3.
Refrigeration appliances. 4. Cleaning appliances.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project
site.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include installation details, material descriptions,
dimensions of individual components, and finishes for each
appliance.
2. Include rated capacities, operating characteristics,
electrical characteristics, and furnished accessories.
B. Samples: For each exposed product and for each color and
texture specified, in manufacturer's standard size.
C. Product Schedule: For appliances. Use same designations
indicated on Drawings.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For manufacturer.
B. Product Certificates: For each type of appliance.
C. Field quality-control reports.
D. Sample Warranties: For manufacturers' special warranties.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For each residential
appliance to include in operation and maintenance manuals.
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-2
1.7 WARRANTY
A. Special Warranties: Manufacturer agrees to repair or replace
residential appliances or components that fail in materials or
workmanship within specified warranty period except as qualified
below:
1. Warranty Period: One (1) year from date of Substantial
Completion.
B. Electric Range: Limited warranty, including parts and labor
for first year, for on-site service on surface-burner elements.
C. Refrigerator/Freezer, Sealed System: Limited warranty,
including parts and labor for first year, and parts thereafter, for
on-site service on the product.
D. Dishwasher: Limited warranty, including parts and labor for
first year, for on-site service on the product.
E. Clothes Washer and Dryer: Limited warranty, including parts
and labor for first year, for on-site service on the product.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain residential appliances from single
source and each type of residential appliance from single
manufacturer where available.
B. Manufacturers: Subject to compliance with requirements,
available manufacturers offering products that may be incorporated
into the Work include, but are not limited to, the following:
1. Bosch (B) 2. Broan-NuTone, LLC (BN) 3. Electrolux Home
Products (E) 4. General Electric Company (GE) 5. LG Electronics
(LG) 6. Maytag; a division of Whirlpool Corporation (M) 7. Sears
Brands LLC (Kenmore) 8. Summit Appliance Division (S) 9. U-Line (U)
10. Whirlpool Corporation (W) 11. Substitutions: Under provisions
of Section 012500 “Substitution Procedures”.
2.2 PERFORMANCE REQUIREMENTS
A. Electrical Appliances: Listed and labeled as defined in NFPA
70, by a qualified testing agency, and marked for intended location
and application.
B. Accessibility: Where residential appliances are indicated to
comply with accessibility requirements, comply with applicable
provisions in the ABA standards of the Federal agency having
jurisdiction and ICC A117.1.
http://www.specagent.com/LookUp/?uid=123456794812&mf=04&src=wdhttp://www.specagent.com/LookUp/?uid=123456794813&mf=04&src=wdhttp://www.specagent.com/LookUp/?uid=123456794823&mf=04&src=wdhttp://www.specagent.com/LookUp/?uid=123456794827&mf=04&src=wd
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-3
2.3 RANGES
A. Electric Range: Freestanding range with one (1) oven and
complying with AHAM ER-1.
1. Basis-of-Design Product: GE #JB450DFBB 2. Width: 30 inches.
3. Electric Burner Elements: Four (4).
a. Radiant Type: Two (2) 1500 W and two (2) 2600 W. b. Controls:
Manual-dial controls, located on front.
4. Oven Features:
a. Capacity: 5.0 cu. ft. b. Operation: Baking, convection and
pyrolytic self-cleaning or catalytic continuous
cleaning. c. Broiler: Located in top of oven. d. Oven Door(s):
Counterbalanced, removable, with observation window and full-
width handle. e. Electric Power Rating:
1) Oven(s): Manufacturer's standard. 2) Broiler: Manufacturer's
standard.
5. Anti-Tip Device: Manufacturer's standard. 6. Electric Power
Supply: As indicated on Drawings. 7. Material: Porcelain-enameled
steel with ceramic glass cooktop.
a. Color/Finish: Black.
2.4 KITCHEN EXHAUST VENTILATION
A. Overhead Exhaust Hood:
1. Basis-of-Design Product: GE #JVX5305DJBB 2. Type:
Wall-mounted, exhaust-hood system. 3. Dimensions:
a. Width: 30 inches. b. Depth: 20 inches.
4. Exhaust Fan: Two-speed fan built into hood and with 270-cfm
capacity.
a. Venting: As indicated on Drawings. b. Fan Control:
Hood-mounted fan switch, with separate hood-light control
switch.
5. Duct Type: As indicated on Drawings. 6. Finish: Baked
enamel.
a. Color: Black.
7. Features:
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-4
a. Permanent, washable charcoal-mesh filter(s). b. Built-in,
dual LED lighting.
2.5 REFRIGERATOR/FREEZERS
A. Refrigerator/Freezer: Two-door refrigerator/freezer with
freezer on top and complying with AHAM HRF-1.
1. Basis-of-Design Product: GE #GTE21GTHBB 2. Type:
Freestanding. 3. Dimensions:
a. Width: 32-7/8 inches. b. Depth: 34 inches. c. Height: 66¾
inches.
4. Storage Capacity:
a. Refrigeration Compartment Volume: 15.1 cu. ft. b. Freezer
Volume: 6.1 cu. ft. c. Shelf Area: Two (2) adjustable shelves.
5. General Features:
a. Door Configuration: Overlay. b. Separate touch-pad
temperature controls for each compartment.
6. Refrigerator Features:
a. Interior light in refrigeration compartment. b. Compartment
Storage: Two (2) drawers plus one (1) deli/snack drawer. c. Door
Storage: Modular compartments with gallon-milk-container
storage.
7. Freezer Features: One (1) freezer compartment.
a. Automatic defrost.
8. Appliance Color/Finish: Black.
2.6 DISHWASHERS
A. Dishwasher: Complying with AHAM DW-1.
1. Basis-of-Design Product: GE #GLDT690JBB 2. Type: Built-in
undercounter. 3. Dimensions:
a. Width: 24 inches. b. Depth: 24 inches. c. Height: 32-11/32
inches.
4. Capacity:
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-5
a. Water Consumption for Full Load: 3.0 gal. per cycle.
5. Sound Level: Maximum 57 dBA. 6. Tub and Door Liner: Stainless
steel with sealed detergent and automatic rinsing-aid
dispensers. 7. Rack System: PVC-coated sliding dish racks, with
removable cutlery basket. 8. Controls: Touch-pad controls with
seven (7) wash cycles and hot-air/heat-off drying
cycle options. 9. Features:
a. Delay-wash option. b. Digital display panel. c. Water
softener.
10. Appliance Color/Finish: Black.
2.7 CLOTHES WASHERS AND DRYERS
A. Clothes Washer: Complying with ASSE 1007.
1. Basis-of-Design Product: GE #GFW480SSKWW 2. Type:
Freestanding, front-loading unit. 3. Dimensions:
a. Width: 28 inches. b. Depth: 34-2/5 inches. c. Height: 39-2/5
inches.
4. Drum: Perforated stainless steel.
a. Capacity: 4.9 cu. ft.
5. Controls: Touch-pad and dial controls for water-fill levels,
wash/rinse water temperatures, and variable-speed and fabric
selectors.
a. Wash Cycles: Thirteen (13) wash cycles. b. Wash Temperatures:
Five (5) settings. c. Speed Combinations: Five (5).
6. Electrical Power: 120 V, 60 Hz, 1 phase, 15 A. 7. Motor:
Manufacturer's standard with built-in overload protector. 8.
Features:
a. Unbalanced-load compensator. b. Self-leveling legs. c.
Automatic dispenser for bleach, fabric softener and detergent. d.
End-of-cycle signal. e. Extra-rinse option. f. Delay-wash option.
g. Electronic temperature control. h. Water levels automatically
set.
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-6
9. Energy Performance, ENERGY STAR: Provide appliances that
qualify for the EPA/DOE ENERGY STAR product labeling program.
10. Appliance Finish: Painted steel.
a. Color: White.
B. Clothes Dryer: Complying with AHAM HLD-1.
1. Basis-of-Design Product: GE #GFD48ESSKWW 2. Type:
Freestanding, frontloading, electric unit. 3. Dimensions:
a. Width: 28 inches. b. Depth: 34-3/8 inches. c. Height: 39-2/5
inches.
4. Drum: Perforated stainless steel.
a. Capacity: 8.3 cu. ft.
5. Controls: Touch-pad and dial controls for drying cycle,
temperatures, and fabric selectors.
6. Electric-Dryer Power: 120/208 V, 60 Hz, 23 A. 7.
Features:
a. Removable lint filter. b. Electronic temperature and moisture
level sensor control. c. End-of-cycle signal. d. Interior drum
light. e. Self-leveling legs. f. Antibacterial cycle.
8. Appliance Finish: Painted Steel.
a. Color: White.
2.8 GENERAL FINISH REQUIREMENTS
A. Protect mechanical finishes on exposed surfaces from damage
by applying a strippable, temporary protective covering before
shipping.
B. Appearance of Finished Work: Noticeable variations in same
piece are not acceptable. Variations in appearance of adjoining
components are acceptable if they are within the range of approved
Samples and are assembled or installed to minimize contrast.
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-7
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer
present, for compliance with requirements for installation
tolerances, power connections, and other conditions affecting
installation and performance of residential appliances.
B. Examine roughing-in for piping systems to verify actual
locations of piping connections before appliance installation.
C. Examine walls, ceilings, and roofs for suitable conditions
where overhead exhaust hoods will be installed.
D. Prepare written report, endorsed by Installer, listing
conditions detrimental to performance of the Work.
E. Proceed with installation only after unsatisfactory
conditions have been corrected.
3.2 INSTALLATION
A. Install appliances according to manufacturer's written
instructions.
B. Built-in Equipment: Securely anchor units to supporting
cabinets or countertops with concealed fasteners. Verify that
clearances are adequate for proper functioning and that rough
openings are completely concealed.
C. Freestanding Equipment: Place units in final locations after
finishes have been completed in each area. Verify that clearances
are adequate to properly operate equipment.
D. Range Anti-Tip Device: Install at each range according to
manufacturer's written instructions.
3.3 FIELD QUALITY CONTROL
A. Perform the following tests and inspections with the
assistance of a factory-authorized service representative:
1. Perform visual, mechanical, and electrical inspection and
testing for each appliance according to manufacturers' written
recommendations. Certify compliance with each manufacturer's
appliance-performance parameters.
2. Leak Test: After installation, test for leaks. Repair leaks
and retest until no leaks exist. 3. Operational Test: After
installation, start units to confirm proper operation. 4. Test and
adjust controls and safeties. Replace damaged and malfunctioning
controls and
components.
B. An appliance will be considered defective if it does not pass
tests and inspections.
C. Prepare test and inspection reports.
-
RESIDENTIAL APPLIANCES
Old Woodbridge Fire Station Renovations 113100-8
3.4 DEMONSTRATION
A. Engage a factory-authorized service representative to train
Owner's maintenance personnel to adjust, operate, and maintain
residential appliances.
END OF SECTION 113100
-
PLASTIC-LAMINATE-CLAD COUNTERTOPS
Old Woodbridge Fire Station Renovations 123623.13-1
SECTION 123623.13 - PLASTIC-LAMINATE-CLAD COUNTERTOPS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. Section includes plastic-laminate countertops.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product, including
high-pressure decorative laminate and adhesive for bonding plastic
laminate.
B. Shop Drawings: Show location of each item, dimensioned plans
and elevations, large-scale details, attachment devices, and other
components.
1. Show locations and sizes of cutouts and holes for plumbing
fixtures, faucets, electrical switches and outlets and other items
installed in plastic-laminate countertops.
C. Samples for Verification:
1. Plastic laminates, 12 by 12 inches, for each type, color,
pattern, and surface finish, with one (1) sample applied to core
material and specified edge material applied to one (1) edge.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For fabricator.
B. Product Certificates: For the following:
1. Composite wood products. 2. High-pressure decorative
laminate. 3. Adhesives.
1.5 QUALITY ASSURANCE
A. Fabricator Qualifications: Shop that employs skilled workers
who custom fabricate products similar to those required for this
Project and whose products have a record of successful in-service
performance.
B. Installer Qualifications: Fabricator of products.
-
PLASTIC-LAMINATE-CLAD COUNTERTOPS
Old Woodbridge Fire Station Renovations 123623.13-2
1.6 DELIVERY, STORAGE, AND HANDLING
A. Do not deliver countertops until painting and similar
operations that could damage countertops have been completed in
installation areas. If countertops must be stored in other than
installation areas, store only in areas where environmental
conditions comply with requirements specified in "Field Conditions"
Article.
1.7 FIELD CONDITIONS
A. Environmental Limitations: Do not deliver or install
countertops until building is enclosed, wet work is complete, and
HVAC system is operating and maintaining temperature and relative
humidity at occupancy levels during the remainder of the
construction period.
B. Field Measurements: Where countertops are indicated to fit to
other construction, verify dimensions of other construction by
field measurements before fabrication, and indicate measurements on
Shop Drawings. Coordinate fabrication schedule with construction
progress to avoid delaying the Work.
C. Established Dimensions: Where countertops are indicated to
fit to other construction, establish dimensions for areas where
countertops are to fit. Provide allowance for trimming at site, and
coordinate construction to ensure that actual dimensions correspond
to established dimensions.
PART 2 - PRODUCTS
2.1 PLASTIC-LAMINATE COUNTERTOPS
A. Quality Standard: Unless otherwise indicated, comply with the
"Architectural Woodwork Standards" for grades indicated for
construction, installation, and other requirements.
B. Grade: Custom.
C. High-Pressure Decorative Laminate: NEMA LD 3, Grade HGP.
1. Manufacturers: Subject to compliance with requirements,
available manufacturers offering products that may be incorporated
into the Work include, but are not limited to, the following:
a. Abet Laminati, Inc. b. Formica Corporation c. Lab Designs d.
Lamin-Art, Inc. e. Nevamar, Panolam Industries International, Inc.
brand f. Wilsonart International; Div. of Premark International,
Inc. g. Substitutions: Under provisions of Section 012500.
D. Colors, Patterns, and Finishes: Provide materials and
products that result in colors and textures of exposed laminate
surfaces complying with the following requirements:
1. As selected by Architect and Owner from manufacturer’s entire
range.
-
PLASTIC-LAMINATE-CLAD COUNTERTOPS
Old Woodbridge Fire Station Renovations 123623.13-3
E. Edge Treatment: PVC edge banding, 0.12-inch-thick, matching
laminate in color, pattern, and finish.
F. Core Material: Medium-density fiberboard (MDF).
G. Core Thickness: ¾-inch.
1. Build up countertop thickness to 1½ inches at front, back,
and ends with additional layers of core material laminated to
top.
H. Backer Sheet: Provide plastic-laminate backer sheet, NEMA LD
3, Grade BKL, on underside of countertop substrate.
2.2 WOOD MATERIALS
A. Wood Products: Provide materials that comply with
requirements of referenced quality standard unless otherwise
indicated.
1. Wood Moisture Content: Five to ten percent (5-10%).
B. Composite Wood Products: Provide materials that comply with
requirements of referenced quality standard for each type of
woodwork and quality grade specified unless otherwise
indicated.
1. Medium-Density Fiberboard: ANSI A208.2, Grade 130.
2.3 MISCELLANEOUS MATERIALS
A. Adhesives: Do not use adhesives that contain urea
formaldehyde.
1. Adhesive for Bonding Plastic Laminate: Contact cement, water
based.
a. Adhesive for Bonding Edges: Polyurethane hot-melt
adhesive.
2. VOC Limits for Installation Adhesives and Sealants: Use
products that comply with the following limits for VOC content when
calculated according to 40 CFR 59, Subpart D (EPA Method 24):
a. Wood Glues: 30 g/L. b. Multipurpose Construction Adhesives:
70 g/L. c. Structural Wood Member Adhesive: 140 g/L. d.
Architectural Sealants: 250 g/L.
2.4 FABRICATION
A. Fabricate countertops to dimensions, profiles, and details
indicated. Provide front and end overhang of 1 inch over base
cabinets.
B. Complete fabrication, including assembly, to maximum extent
possible before shipment to Project site. Disassemble components
only as necessary for shipment and installation. Where necessary
for fitting at site, provide ample allowance for scribing,
trimming, and fitting.
-
PLASTIC-LAMINATE-CLAD COUNTERTOPS
Old Woodbridge Fire Station Renovations 123623.13-4
1. Trial fit assemblies at fabrication shop that cannot be
shipped completely assembled. Install dowels, screws, bolted
connectors, and other fastening devices that can be removed after
trial fitting. Verify that various parts fit as intended and check
measurements of assemblies against field measurements before
disassembling for shipment.
C. Shop cut openings to maximum extent possible to receive
appliances, plumbing fixtures, electrical work, and similar items.
Locate openings accurately and use templates or roughing-in
diagrams to produce accurately sized and shaped openings. Sand
edges of cutouts to remove splinters and burrs.
1. Seal edges of openings in countertops with a coat of
varnish.
PART 3 - EXECUTION
3.1 PREPARATION
A. Before installation, condition countertops to average
prevailing humidity conditions in installation areas.
B. Before installing countertops, examine shop-fabricated work
for completion and complete work as required, including removal of
packing and backpriming.
3.2 INSTALLATION
A. Grade: Install countertops to comply with same grade as item
to be installed.
B. Assemble countertops and complete fabrication at Project site
to the extent that it was not completed in the shop.
1. Provide cutouts for appliances, plumbing fixtures, electrical
work, and similar items. 2. Seal edges of cutouts by saturating
with varnish.
C. Field Jointing: Where possible, make in the same manner as
shop jointing, using dowels, splines, adhesives, and fasteners
recommended by manufacturer. Prepare edges to be joined in shop so
Project-site processing of top and edge surfaces is not required.
Locate field joints where shown on Shop Drawings.
1. Secure field joints in plastic-laminate countertops with
concealed clamping devices located within 6 inches of front and
back edges and at intervals not exceeding 24 inches. Tighten
according to manufacturer's written instructions to exert a
constant, heavy-clamping pressure at joints.
D. Install countertops level, plumb, true, and straight. Shim as
required with concealed shims. Install level and plumb to a
tolerance of 1/8 inch in 96 inches.
E. Scribe and cut countertops to fit adjoining work, refinish
cut surfaces, and repair damaged finish at cuts.
F. Countertops: Anchor securely by screwing through corner
blocks of base cabinets or other supports into underside of
countertop.
-
PLASTIC-LAMINATE-CLAD COUNTERTOPS
Old Woodbridge Fire Station Renovations 123623.13-5
1. Install countertops with no more than 1/8-inch in 96-inch
sag, bow, or other variation from a straight line.
2. Secure backsplashes to tops with concealed metal brackets at
16 inches o.c. and to walls with adhesive.
3. Seal junctures of tops, splashes, and walls with
mildew-resistant silicone sealant or another permanently elastic
sealing compound recommended by countertop material
manufacturer.
3.3 ADJUSTING AND CLEANING
A. Repair damaged and defective countertops, where possible, to
eliminate functional and visual defects; where not possible to
repair, replace woodwork. Adjust joinery for uniform
appearance.
B. Clean countertops on exposed and semi-exposed surfaces. Touch
up shop-applied finishes to restore damaged or soiled areas.
END OF SECTION 123623.13
-
ENTRANCE FLOOR MATS AND FRAMES
Old Woodbridge Fire Station Renovations 124813-1
SECTION 124813 - ENTRANCE FLOOR MATS AND FRAMES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Roll-up rail mats. 2. Recessed frames.
1.3 COORDINATION
A. Coordinate size and location of recesses in concrete to
receive floor mats and frames.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions,
dimensions of individual components and profiles, and finishes for
floor mats and frames.
B. Shop Drawings:
1. Items penetrating floor mats and frames, including door
control devices. 2. Divisions between mat sections. 3. Perimeter
floor frames.
C. Samples: For the following products, in manufacturer's
standard sizes:
1. Floor Mat: Assembled sections of floor mat. 2. Tread Rail:
Sample of each type and color. 3. Frame Members: Sample of each
type and color.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For floor mats and frames to include in
maintenance manuals.
PART 2 - PRODUCTS
2.1 ENTRANCE FLOOR MATS AND FRAMES, GENERAL
A. Structural Performance: Provide roll-up rail mats and frames
capable of withstanding the following loads and stresses within
limits and under conditions indicated:
-
ENTRANCE FLOOR MATS AND FRAMES
Old Woodbridge Fire Station Renovations 124813-2
1. Uniform floor load of 300 lbf/sq. ft. 2. Wheel load of 350
lb. per wheel.
B. Accessibility Standard: Comply with applicable provisions in
ICC A117.1.
2.2 ROLL-UP RAIL MATS
A. Basis-of-Design Product:
1. Mats Inc.; Grate Mat
B. Manufacturers: Subject to compliance with requirements,
available manufacturers offering products that may be incorporated
into the Work include, but are not limited to, the following:
1. Pawling Corporation; Architectural Products Division 2.
Substitutions: Under provisions of Section 012500 “Substitution
Procedures”.
C. Roll-up, Aluminum-Rail Hinged Mats: Extruded-aluminum tread
rails 1¾ inches wide by 3/8-inch-thick, sitting on continuous vinyl
cushions.
1. Tread Inserts: ¼-inch-high, 28-oz./sq. yd. weight, level-cut,
nylon-pile, fusion-bonded carpet.
2. Colors, Textures, and Patterns of Inserts: As selected by
Architect from full range of colors.
3. Rail Color: Mill finish. 4. Hinges: Aluminum. 5. Mat Size: As
indicated required to fit existing recess.
2.3 FRAMES
A. Recessed Frames: Manufacturer's standard extrusion.
1. Extruded Aluminum: ASTM B 221, Alloy 6061-T6 or Alloy
6063-T5, T6, or T52.
a. Color: Mill finish.
2.4 FABRICATION
A. Floor Mats: Shop fabricate units to greatest extent possible
in sizes indicated. Unless otherwise indicated, provide single unit
for each mat installation; do not exceed manufacturer's recommended
maximum sizes for units that are removed for maintenance and
cleaning. Where joints in mats are necessary, space symmetrically
and away from normal traffic lanes. Miter corner joints in framing
elements with hairline joints or provide prefabricated corner units
without joints.
B. Recessed Frames: As indicated, for permanent recessed
installation, complete with corner pins or reinforcement and
anchorage devices.
1. Fabricate edge-frame members in single lengths or, where
frame dimensions exceed maximum available lengths, provide minimum
number of pieces possible, with hairline joints equally spaced and
pieces spliced together by straight connecting pins.
-
ENTRANCE FLOOR MATS AND FRAMES
Old Woodbridge Fire Station Renovations 124813-3
C. Coat concealed surfaces of aluminum frames that contact
cementitious material with manufacturer's standard protective
coating.
2.5 ALUMINUM FINISHES
A. Mill finish.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and floor conditions for compliance with
requirements for location, sizes, minimum recess depth, and other
conditions affecting installation of floor mats and frames.
B. Proceed with installation only after unsatisfactory
conditions have been corrected.
3.2 INSTALLATION
A. Install recessed mat frames and mats to comply with
manufacturer's written instructions so that tops of mats will be
flush with adjoining finished flooring. Set mats with tops at
height recommended by manufacturer for most effective cleaning
action; coordinate tops of mat surfaces with bottoms of doors that
swing across mats to provide clearance between door and mat. 1.
Install necessary shims, spacers, and anchorages for proper
location, and secure
attachment of frames. 2. Delay setting mats until construction
traffic has ended.
3.3 PROTECTION
A. After completing frame installation and concrete work,
provide temporary filler of plywood or fiberboard in recesses and
cover frames with plywood protective flooring. Maintain protection
until construction traffic has ended and Project is near
Substantial Completion.
END OF SECTION 124813
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-1
SECTION 142600 - LIMITED-USE/LIMITED-APPLICATION ELEVATORS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. Section includes limited-use/limited-application (LU/LA)
elevators.
B. Related Requirements:
1. Section 033000 "Cast-in-Place Concrete" for setting sleeves,
inserts, and anchoring devices in concrete.
2. Section 042000 "Unit Masonry" for setting sleeves, inserts,
and anchoring devices in masonry.
3. Section 099123 "Interior Painting" for field painting of
hoistway entrance doors and frames.
4. Section 096519 “Resilient Tile Flooring” for finish flooring
in elevator cars.
1.3 DEFINITIONS
A. Definitions in ASME A17.1/CSA B44 apply to Work of this
Section.
B. LU/LA: Limited use/limited application.
1.4 ACTION SUBMITTALS
A. Product Data: Include capacities, sizes, performances,
operations, safety features, finishes, and similar information.
Include Product Data for car enclosures, hoistway entrances, and
operation, control, and signal equipment.
B. Shop Drawings:
1. Include plans, elevations, sections, and large-scale details
indicating service at each landing, machine room layout,
coordination with building structure, relationships with other
construction, and locations of equipment.
2. Indicate loads imposed on building structure at points of
support and power requirements.
C. Samples: For exposed finishes of cars, hoistway doors and
frames, and signal equipment; 3-inch-square Samples of sheet
materials; and 4-inch lengths of running trim members.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-2
B. Seismic Qualification Certificates: For elevator equipment,
accessories, and components, from manufacturer.
1. Basis for Certification: Indicate whether withstand
certification is based on actual test of assembled components or on
calculation.
2. Dimensioned Outline Drawings of Equipment Unit: Identify
center of gravity and locate and describe mounting and anchoring
provisions.
3. Detailed description of equipment anchoring devices on which
the certification is based and their installation requirements.
C. Manufacturer Certificates: Signed by elevator manufacturer
certifying that hoistway, pit, and machine room layout and
dimensions, as shown on Drawings, and electrical service, as shown
and specified, are adequate for elevator being provided.
D. Preinstallation Examination Report: Indicating dimensional
discrepancies and conditions detrimental to performance or
indicating that dimensions and conditions were found to be
satisfactory.
E. Sample Warranty: For special warranty.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For elevators to include in
emergency, operation, and maintenance manuals.
1. Submit manufacturer's/installer's standard operation and
maintenance manual, according to ASME A17.1.
B. Inspection and Acceptance Certificates and Operating Permits:
As required by authorities having jurisdiction, for normal,
unrestricted elevator use.
C. Continuing Maintenance Proposal: Provide a continuing
maintenance proposal from Installer to Owner, in the form of a
standard one-year maintenance agreement, starting on date initial
maintenance service is concluded. State services, obligations,
conditions, and terms for agreement period and for future renewal
options.
1.7 QUALITY ASSURANCE
A. Installer Qualifications: Elevator manufacturer or an
authorized representative who is trained and approved by
manufacturer.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver, store, and handle materials, components, and
equipment in manufacturer's protective packaging. Store materials,
components, and equipment off of ground, under cover, and in a dry
location.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-3
1.9 COORDINATION
A. Coordinate installation of sleeves, block outs, and items
that are embedded in concrete or masonry for elevator equipment.
Furnish templates and installation instructions and deliver to
Project site in time for installation.
B. Coordinate locations and dimensions of other work relating to
LU/LA elevators including sumps and floor drains in pits; entrance
subsills; electrical service; and electrical outlets, lights, and
switches in hoistways, pits, and machine rooms.
1.10 WARRANTY
A. Manufacturer's Special Warranty: Manufacturer agrees to
repair or replace elevator work that fails in materials or
workmanship within specified warranty period.
1. Failures include, but are not limited to, operation or
control system failure, including excessive malfunctions;
performances below specified ratings; excessive wear; unusual
deterioration or aging of materials or finishes; unsafe conditions;
need for excessive maintenance; abnormal noise or vibration; and
similar unusual, unexpected, and unsatisfactory conditions.
2. Warranty Period: Two (2) years from date of Substantial
Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Basis-of-Design Product:
1. Garaventa Lift; Elvoron
B. Manufacturers: Subject to compliance with requirements,
manufacturers offering products that may be incorporated into the
Work include, but are not limited to, the following:
1. Liftavator, Inc. 2. Schumacher Elevator Corp. 3.
Substitutions: Under provisions of Section 012500 “Substitution
Procedures”.
C. Source Limitations: Obtain elevators through one (1) source
from a single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Regulatory Requirements: Comply with ASME A17.1/CSA B44.
B. Accessibility Requirements: Comply with requirements for
LU/LA elevators in the United States Access Board's ADA-ABA
Accessibility Guidelines and with ICC A117.1.
C. Seismic Performance: Elevator system shall withstand the
effects of earthquake motions determined according to ASCE/SEI 7
and shall comply with elevator seismic requirements in ASME
A17.1/CSA B44. Refer to Structural Drawings.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-4
1. The term "withstand" means "the system will remain in place
without separation of any parts when subjected to the seismic
forces specified."
2.3 SYSTEMS AND COMPONENTS
A. Elevator System, General: Manufacturer's standard LU/LA
elevator. Unless otherwise indicated, manufacturers' standard
components shall be used, as included in standard LU/LA elevators
and as required for complete system.
1. Rated Load: 1400 lb. 2. Rated Speed: 25 to 30 fpm.
B. Machine Type: Hydraulic, holeless, beside the car;
direct-acting hydraulic or roped hydraulic.
C. Pump Units: Positive-displacement type with a maximum of ten
percent (10%) variation between no load and full load and with
minimum pulsations.
1. Pump shall be submersible type, suspended inside oil tank
from vibration isolation mounts.
2. Motor shall have variable-voltage, variable-frequency motor
control. 3. System shall have hydraulic silencer and flexible
piping connectors at pump unit.
D. Hydraulic Fluid: Elevator manufacturer's standard fluid with
additives as needed to prevent oxidation of fluid, corrosion of
cylinder and other components, and other adverse effects.
E. Inserts: Furnish required concrete and masonry inserts and
similar anchoring devices for installing guide rails, machinery,
and other components of elevator work. Device installation is
specified in another Section.
2.4 OPERATION SYSTEMS
A. General: Provide manufacturer's standard microprocessor
operation system for single automatic operation.
B. Standby Power Operation: On activation of standby power, car
is returned to a designated floor and parked with doors open. Car
can be manually put into service on standby power, either for
return operation or for regular operation, by switches in control
panel located at main lobby. Manual operation causes automatic
operation to cease.
C. Battery-Powered Lowering: When power fails, car is lowered to
the lowest floor, opens its car and hoistway doors, and shuts down.
System includes rechargeable battery and automatic recharging
system.
D. Provide automatic operation of lights and ventilation
fans.
E. Emergency Operation: Phase I emergency recall operation and
Phase II emergency in-car operation.
F. Keyswitch Operation: A key switch in the car shall be
provided for in-car control of each elevator when on Phase II of
Special Emergency Service.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-5
2.5 DOOR REOPENING DEVICES
A. Infrared Array: Provide door-reopening devices with a uniform
array of 36 or more microprocessor-controlled, infrared light beams
projecting across car entrance. Interruption of one or more light
beams shall cause doors to stop and reopen.
2.6 CAR ENCLOSURES
A. General: Provide steel-framed car enclosures with wall
panels, car roof, access doors, power door operators, and
ventilation. Provide finished car including materials and finishes
specified below.
B. Materials and Finishes: Manufacturer's standards, but not
less than the following:
1. Floor Finish: Specified in Section 096519 “Resilient Tile
Flooring”. 2. Plastic-Laminate Wall Panels: Plastic laminate
adhesively applied to ½ inch fire-
retardant-treated particleboard with plastic-laminate panel
backing and manufacturer's standard protective edge trim. Panels
have a flame-spread index of 25 or less, when tested according to
ASTM E 84.
3. Sills: Extruded or machined aluminum, with grooved surface,
¼-inch-thick. 4. Metal Ceiling: Flush panels, fabricated from
stainless-steel sheet. 5. Lighting: Not less than four (4) recessed
low-voltage LED lamps. Provide battery backup
power source with automatic charging.
a. Light Fixture Efficiency: Not less than 35 lumens/watt.
6. Handrail: 1½ inches round, satin stainless steel, No. 4
finish, on one (1) side of car.
C. Car Doors: Manufacturer's standard units complete with track
systems, hardware, sills, and accessories.
1. Operation: Power-operated, automatic. 2. Type: Horizontal
sliding. 3. Clear Opening Width: 36 inches. 4. Door Height: 80
inches. 5. Stainless-Steel Doors: Flush, hollow-metal construction;
fabricated from stainless-steel
sheet or by laminating stainless-steel sheet to exposed faces
and edges of enameled cold-rolled steel doors using adhesive that
fully bonds metal to metal without telegraphing or oil-canning.
Satin, No. 4 finish.
2.7 HOISTWAY ENTRANCES
A. General: Provide manufacturer's standard door-and-frame
hoistway entrances, same size as car doors, complete with track
systems, hardware, sills, and accessories.
1. Operation: Power-operated, automatic. 2. Type: Horizontal
sliding.
B. Coordinate frame size and profile with hoistway wall
construction.
C. Materials and Fabrication: Manufacturer's standards, but not
less than the following:
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-6
1. Stainless-Steel Frames: Formed from stainless-steel sheet;
satin, No. 4 finish. 2. Stainless-Steel Doors: Flush, hollow-metal
construction; fabricated from stainless-steel
sheet or by laminating stainless-steel sheet to exposed faces
and edges of enameled cold-rolled steel doors using adhesive that
fully bonds metal to metal without telegraphing or oil-canning.
Satin, No. 4 finish.
3. Sills: Extruded or machined aluminum, with grooved surface,
¼-inch-thick. 4. Non-shrink, Nonmetallic Grout: Factory-packaged,
non-staining, noncorrosive,
nongaseous grout complying with ASTM C 1107.
D. Fire-Rated Hoistway Entrance Assemblies: Door and frame
assemblies shall comply with NFPA 80 and be listed and labeled by a
testing and inspecting agency acceptable to authorities having
jurisdiction based on testing at as-close-to-neutral pressure as
possible according to NFPA 252 or UL 10B.
1. Fire-Protection Rating: 1 hour.
2.8 SIGNAL EQUIPMENT
A. General: Provide hall-call and car-call buttons that light
when activated and remain lit until call has been fulfilled.
Provide vandal-resistant buttons and lighted elements illuminated
with light-emitting diodes.
1. Finish: Satin stainless steel, No. 4 finish.
B. Car-Control Stations: Provide manufacturer's standard
car-control stations. Mount in side panel adjacent to car door
unless otherwise indicated.
1. Mark buttons and switches for function. Use both tactile
symbols and Braille. 2. Provide "No Smoking" sign matching
car-control station, either integral with car-control
station or mounted adjacent to it, with text and graphics as
required by authorities having jurisdiction.
C. Emergency Communication System: Two-way voice communication
system, with visible signal, which dials preprogrammed number of
monitoring station and does not require handset use. System is
contained in flush-mounted cabinet, with identification,
instructions for use, and battery backup power supply.
D. Car Position Indicator: Provide digital-type position
indicator in elevator car. Also, provide audible signal to indicate
to passengers that car is either stopping at or passing each of the
floors served. Include travel direction arrows if not provided in
car-control station.
E. Hall Push-Button Stations: Wall-mounted or jamb-mounted units
equipped with buttons for calling elevator and for indicating
desired direction of travel where applicable.
F. Hall Lanterns: Wall-mounted or jamb-mounted units with
illuminated arrows; but provide single arrow at terminal
landings.
G. Hall Annunciator: With each hall lantern, provide audible
signals indicating car arrival and direction of travel. Signals
sound once for up and twice for down.
1. At manufacturer's option, audible signals may be placed on
car.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-7
H. Emergency Pictorial Signs: Fabricate from materials matching
hall push-button stations, with text and graphics as required by
authorities having jurisdiction, indicating that in case of fire,
elevators are out of service and exits should be used instead.
Provide one sign at each hall push-button station unless otherwise
indicated.
2.9 FINISH MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008, commercial steel, Type
B, exposed, matte finish.
B. Stainless-Steel Sheet: ASTM A 240, Type 304.
C. Stainless-Steel Bars: ASTM A 276, Type 304.
D. Stainless-Steel Tubing: ASTM A 554, Grade MT 304.
E. Aluminum Extrusions: ASTM B 221, Alloy 6063.
F. Plastic Laminate: High-pressure type complying with NEMA LD
3, Type HGS for flat applications. Color as selected by Architect
and Owner from manufacturer’s full range.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine elevator areas, with Installer present, for
compliance with requirements for installation tolerances and other
conditions affecting performance of the Work. Verify critical
dimensions and examine supporting structure and other conditions
under which elevator work is to be installed.
B. Prepare written report, endorsed by Installer, listing
conditions detrimental to performance of the Work.
C. Proceed with installation only after unsatisfactory
conditions have been corrected.
3.2 INSTALLATION
A. Install cylinder plumb and accurately located for elevator
car position and travel. Anchor securely in place, supported at pit
floor and braced at intervals as needed to maintain alignment.
Anchor cylinder guides at spacing needed to maintain alignment and
avoid overstressing guides.
B. Sound Isolation: Mount rotating and vibrating equipment on
vibration-isolating mounts to minimize vibration transmission to
structure and structure-borne noise from elevator system.
C. Lubricate operating parts of systems as recommended by
manufacturers.
D. Alignment: Coordinate installation of hoistway entrances with
installation of elevator guide rails for accurate alignment of
entrances with car. Reduce clearances to minimum, safe, workable
dimension at each landing.
E. Leveling Tolerance: ¼-inch, up or down, regardless of load
and direction of travel.
-
LIMITED-USE/LIMITED APPLICATION ELEVATORS
Old Woodbridge Fire Station Renovations 142600-8
F. Set sills flush with finished floor surface at landing. Fill
space under sill solidly with non-shrink, nonmetallic grout.
G. Locate hall lanterns either above or beside hoistway entrance
at a minimum of 72 inches above finished floor unless hall lanterns
are built into entrance frames.
3.3 FIELD QUALITY CONTROL
A. Acceptance Testing: On completion of elevator installation
and before permitting elevator use, perform acceptance tests as
required and recommended by ASME A17.1/CSA B44 and by authorities
having jurisdiction.
B. Advise Owner, Architect, and authorities having jurisdiction
in advance of dates and times that tests are to be performed.
3.4 DEMONSTRATION
A. Engage a factory-authorized service representative to train
Owner's maintenance personnel to operate, adjust, and maintain
elevator(s).
B. Check operation of elevator with Owner's personnel present
before date of Substantial Completion and again not more than one
(1) month before end of warranty period. Determine that operation
systems and devices are functioning properly.
3.5 MAINTENANCE SERVICE
A. Initial Maintenance Service: Beginning at Substantial
Completion, maintenance service shall include one (1) year’s full
maintenance by skilled employees of elevator Installer. Include
monthly preventive maintenance, repair or replacement of worn or
defective components, lubrication, cleaning, and adjusting as
required for proper elevator operation. Parts and supplies shall be
manufacturer's authorized replacement parts and supplies.
1. Perform maintenance during normal working hours. 2. Include
24-hour-per-day, 7-day-per-week emergency callback service with
response time
of two (2) hours or less.
END OF SECTION 142600
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-1
SECTION 210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Piping materials and installation instructions common to most
piping systems. 2. Mechanical sleeve seals. 3. Sleeves. 4.
Escutcheons. 5. Grout. 6. Equipment installation requirements
common to equipment sections. 7. Painting and finishing. 8.
Concrete bases. 9. Supports and anchorages.
1.3 DEFINITIONS
A. Finished Spaces: Spaces other than mechanical and electrical
equipment rooms, furred spaces, pipe chases, unheated spaces
immediately below roof, spaces above ceilings, unexcavated spaces,
crawlspaces, and tunnels.
B. Exposed, Interior Installations: Exposed to view indoors.
Examples include finished occupied spaces and mechanical equipment
rooms.
C. Exposed, Exterior Installations: Exposed to view outdoors or
subject to outdoor ambient temperatures and weather conditions.
Examples include rooftop locations.
D. Concealed, Interior Installations: Concealed from view and
protected from physical contact by building occupants. Examples
include above ceilings and in chases.
E. Concealed, Exterior Installations: Concealed from view and
protected from weather conditions and physical contact by building
occupants but subject to outdoor ambient temperatures. Examples
include installations within unheated shelters.
F. The following are industry abbreviations for rubber
materials:
1. EPDM: Ethylene-propylene-diene terpolymer rubber. 2. NBR:
Acrylonitrile-butadiene rubber.
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-2
1.4 SUBMITTALS
A. Product Data: For the following:
1. Mechanical sleeve seals. 2. Escutcheons.
B. Welding certificates.
1.5 QUALITY ASSURANCE
A. Steel Support Welding: Qualify processes and operators
according to AWS D1.1, "Structural Welding Code--Steel."
B. Steel Pipe Welding: Qualify processes and operators according
to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and
Brazing Qualifications."
1. Comply with provisions in ASME B31 Series, "Code for Pressure
Piping." 2. Certify that each welder has passed AWS qualification
tests for welding processes
involved and that certification is current.
C. Electrical Characteristics for Fire-Suppression Equipment:
Equipment of higher electrical characteristics may be furnished
provided such proposed equipment is approved in writing and
connecting electrical services, circuit breakers, and conduit sizes
are appropriately modified. If minimum energy ratings or
efficiencies are specified, equipment shall comply with
requirements.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver pipes and tubes with factory-applied end caps.
Maintain end caps through shipping, storage, and handling to
prevent pipe end damage and to prevent entrance of dirt, debris,
and moisture.
1.7 COORDINATION
A. Arrange for pipe spaces, chases, slots, and openings in
building structure during progress of construction, to allow for
fire-suppression installations.
B. Coordinate installation of required supporting devices and
set sleeves in poured-in-place concrete and other structural
components as they are constructed.
C. Coordinate requirements for access panels and doors for
fire-suppression items requiring access that are concealed behind
finished surfaces. Access panels and doors are specified in Section
083113 "Access Doors and Frames."
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-3
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where subparagraph titles below
introduce lists, the following requirements apply for product
selection:
1. Manufacturers: Subject to compliance with requirements,
provide products by the manufacturers specified.
2.2 PIPE, TUBE, AND FITTINGS
A. Refer to individual Division 21 piping Sections for pipe,
tube, and fitting materials and joining methods.
B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe
fittings.
2.3 JOINING MATERIALS
A. Refer to individual Division 21 piping Sections for special
joining materials not listed below.
B. Pipe-Flange Gasket Materials: Suitable for chemical and
thermal conditions of piping system contents.
1. ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch
maximum thickness unless thickness or specific material is
indicated.
a. Full-Face Type: For flat-face, Class 125, cast-iron and
cast-bronze flanges. b. Narrow-Face Type: For raised-face, Class
250, cast-iron and steel flanges.
2. AWWA C110, rubber, flat face, 1/8-inch-thick, unless
otherwise indicated; and full-face or ring type, unless otherwise
indicated.
C. Flange Bolts and Nuts: ASME B18.2.1, carbon steel, unless
otherwise indicated.
D. Solder Filler Metals: ASTM B 32, lead-free alloys. Include
water-flushable flux according to ASTM B 813.
E. Brazing Filler Metals: AWS A5.8, BCuP Series,
copper-phosphorus alloys for general-duty brazing, unless otherwise
indicated; and AWS A5.8, BAg1, silver alloy for refrigerant piping,
unless otherwise indicated.
F. Welding Filler Metals: Comply with AWS D10.12 for welding
materials appropriate for wall thickness and chemical analysis of
steel pipe being welded.
2.4 MECHANICAL SLEEVE SEALS
A. Description: Modular sealing element unit, designed for field
assembly, to fill annular space between pipe and sleeve.
1. Manufacturers:
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-4
a. Advance Products & Systems, Inc. b. Calpico, Inc. c.
Metraflex Co. d. Pipeline Seal and Insulator, Inc.
2. Sealing Elements: EPDM interlocking links shaped to fit
surface of pipe. Include type and number required for pipe material
and size of pipe.
3. Pressure Plates: Carbon steel. Include two (2) for each
sealing element. 4. Connecting Bolts and Nuts: Carbon steel with
corrosion-resistant coating of length
required to secure pressure plates to sealing elements. Include
one for each sealing element.
2.5 SLEEVES
A. Galvanized-Steel Sheet: 0.0239-inch minimum thickness; round
tube closed with welded longitudinal joint.
B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40,
galvanized, plain ends.
C. Cast Iron: Cast or fabricated "wall pipe" equivalent to
ductile-iron pressure pipe, with plain ends and integral waterstop,
unless otherwise indicated.
D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with
integral clamping flange. Include clamping ring and bolts and nuts
for membrane flashing.
1. Underdeck Clamp: Clamping ring with set screws.
E. Molded PVC: Permanent, with nailing flange for attaching to
wooden forms.
F. PVC Pipe: ASTM D 1785, Schedule 40.
G. Molded PE (Polyethylene): Reusable, PE, tapered-cup shaped,
and smooth-outer surface with nailing flange for attaching to
wooden forms.
2.6 ESCUTCHEONS
A. Description: Manufactured wall and ceiling escutcheons and
floor plates, with an ID to closely fit around pipe, tube, and
insulation of insulated piping and an OD that completely covers
opening.
B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass
with polished chrome-plated finish.
C. One-Piece, Cast-Brass Type: With set screw.
1. Finish: Polished chrome-plated and rough brass.
D. Split-Casting, Cast-Brass Type: With concealed hinge and set
screw.
1. Finish: Polished chrome-plated and rough brass.
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-5
E. One-Piece, Stamped-Steel Type: With set screw or spring clips
and chrome-plated finish.
F. Split-Plate, Stamped-Steel Type: With concealed hinge, set
screw or spring clips, and chrome-plated finish.
G. One-Piece, Floor-Plate Type: Cast-iron floor plate.
H. Split-Casting, Floor-Plate Type: Cast brass with concealed
hinge and set screw.
2.7 GROUT
A. Description: ASTM C 1107, Grade B, non-shrink and
nonmetallic, dry hydraulic-cement grout.
1. Characteristics: Post-hardening, volume-adjusting,
non-staining, noncorrosive, nongaseous, and recommended for
interior and exterior applications.
2. Design Mix: 5000-psi, 28-day compressive strength. 3.
Packaging: Premixed and factory packaged.
PART 3 - EXECUTION
3.1 PIPING SYSTEMS - COMMON REQUIREMENTS
A. Install piping according to the following requirements and
Division 21 Sections specifying piping systems.
1. Provide seismic restraint in accordance with the State of
Connecticut Building Code for project-specific building seismic
design criteria.
B. Drawing plans, schematics, and diagrams indicate general
location and arrangement of piping systems. Indicated locations and
arrangements were used to size pipe and calculate friction loss,
expansion, pump sizing, and other design considerations. Install
piping as indicated unless deviations to layout are approved on
Coordination Drawings.
C. Install piping in concealed locations, unless otherwise
indicated and except in equipment rooms and service areas.
D. Install piping indicated to be exposed and piping in
equipment rooms and service areas at right angles or parallel to
building walls. Diagonal runs are prohibited unless specifically
indicated otherwise.
E. Install piping above accessible ceilings to allow sufficient
space for ceiling panel removal.
F. Install piping to permit valve servicing.
G. Install piping at indicated slopes.
H. Install piping free of sags and bends.
I. Install fittings for changes in direction and branch
connections.
J. Install piping to allow application of insulation.
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-6
K. Select system components with pressure rating equal to or
greater than system operating pressure.
L. Install escutcheons for penetrations of walls, ceilings, and
floors according to the following:
1. New Piping:
a. Piping with Fitting or Sleeve Protruding from Wall:
One-piece, deep-pattern type. b. Chrome-Plated Piping: One-piece,
cast-brass type with polished chrome-plated
finish. c. Insulated Piping: One-piece, stamped-steel type with
spring clips. d. Bare Piping at Wall and Floor Penetrations in
Finished Spaces: One-piece, cast-
brass type with polished chrome-plated finish. e. Bare Piping at
Ceiling Penetrations in Finished Spaces: One-piece or
split-casting,
cast-brass type with polished chrome-plated finish. f. Bare
Piping in Unfinished Service Spaces: One-piece, cast-brass type
with rough-
brass finish. g. Bare Piping in Equipment Rooms: One-piece,
cast-brass type. h. Bare Piping at Floor Penetrations in Equipment
Rooms: One-piece, floor-plate
type.
M. Sleeves are not required for core-drilled holes.
N. Permanent sleeves are not required for holes formed by
removable PE sleeves.
O. Install sleeves for pipes passing through concrete and
masonry walls, gypsum-board partitions, and concrete floor and roof
slabs.
1. Cut sleeves to length for mounting flush with both
surfaces.
a. Exception: Extend sleeves installed in floors of mechanical
equipment areas or other wet areas 2 inches above finished floor
level. Extend cast-iron sleeve fittings below floor slab as
required to secure clamping ring if ring is specified.
2. Install sleeves in new walls and slabs as new walls and slabs
are constructed. 3. Install sleeves that are large enough to
provide ¼-inch annular clear space between sleeve
and pipe or pipe insulation. Use the following sleeve
materials:
a. Steel Pipe Sleeves: For pipes smaller than NPS 6 (DN 150). b.
Steel Sheet Sleeves: For pipes NPS 6 (DN 150) and larger,
penetrating gypsum-
board partitions. c. Stack Sleeve Fittings: For pipes
penetrating floors with membrane waterproofing.
Secure flashing between clamping flanges. Install section of
cast-iron soil pipe to extend sleeve to 2 inches above finished
floor level. Refer to Section 076200 "Sheet Metal Flashing and
Trim" for flashing.
1) Seal space outside of sleeve fittings with grout.
4. Except for underground wall penetrations, seal annular space
between sleeve and pipe or pipe insulation, using joint sealants
appropriate for size, depth, and location of joint. Refer to
Section 079200 "Joint Sealants" for materials and installation.
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-7
P. Aboveground, Exterior-Wall Pipe Penetrations: Seal
penetrations using sleeves and mechanical sleeve seals. Select
sleeve size to allow for 1-inch annular clear space between pipe
and sleeve for installing mechanical sleeve seals.
1. Install steel pipe for sleeves smaller than 6 inches in
diameter. 2. Install cast-iron "wall pipes" for sleeves 6 inches
and larger in diameter. 3. Mechanical Sleeve Seal Installation:
Select type and number of sealing elements
required for pipe material and size. Position pipe in center of
sleeve. Assemble mechanical sleeve seals and install in annular
space between pipe and sleeve. Tighten bolts against pressure
plates that cause sealing elements to expand and make watertight
seal.
Q. Underground, Exterior-Wall Pipe Penetrations: Install
cast-iron "wall pipes" for sleeves. Seal pipe penetrations using
mechanical sleeve seals. Select sleeve size to allow for 1-inch
annular clear space between pipe and sleeve for installing
mechanical sleeve seals.
1. Mechanical Sleeve Seal Installation: Select type and number
of sealing elements required for pipe material and size. Position
pipe in center of sleeve. Assemble mechanical sleeve seals and
install in annular space between pipe and sleeve. Tighten bolts
against pressure plates that cause sealing elements to expand and
make watertight seal.
R. Fire-Barrier Penetrations: Maintain indicated fire rating of
walls, partitions, ceilings, and floors at pipe penetrations. Use
only UL-Listed components and assemblies. Seal pipe penetrations
with firestop materials. Refer to Section 078413 "Penetration
Firestopping" for materials.
S. Verify final equipment locations for roughing-in.
T. Refer to equipment specifications in other Sections of these
Specifications for roughing-in requirements.
3.2 PIPING JOINT CONSTRUCTION
A. Join pipe and fittings according to the following
requirements and Division 21 Sections specifying piping
systems.
B. Ream ends of pipes and tubes and remove burrs. Bevel plain
ends of steel pipe.
C. Remove scale, slag, dirt, and debris from inside and outside
of pipe and fittings before assembly.
D. Soldered Joints: Apply ASTM B 813, water-flushable flux,
unless otherwise indicated, to tube end. Construct joints according
to ASTM B 828 or CDA's "Copper Tube Handbook," using lead-free
solder alloy complying with ASTM B 32.
E. Brazed Joints: Construct joints according to AWS's "Brazing
Handbook," "Pipe and Tube" Chapter, using copper-phosphorus brazing
filler metal complying with AWS A5.8.
F. Threaded Joints: Thread pipe with tapered pipe threads
according to ASME B1.20.1. Cut threads full and clean using sharp
dies. Ream threaded pipe ends to remove burrs and restore full ID.
Join pipe fittings and valves as follows:
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-8
1. Apply appropriate tape or thread compound to external pipe
threads unless dry seal threading is specified.
2. Damaged Threads: Do not use pipe or pipe fittings with
threads that are corroded or damaged. Do not use pipe sections that
have cracked or open welds.
G. Welded Joints: Construct joints according to AWS D10.12,
using qualified processes and welding operators according to Part 1
"Quality Assurance" Article. Site welding is NOT allowed; only
shop-welding is permitted. Welded fittings are NOT allowed on
galvanized pipe.
H. Flanged Joints: Select appropriate gasket material, size,
type, and thickness for service application. Install gasket
concentrically positioned. Use suitable lubricants on bolt
threads.
3.3 PAINTING
A. Painting of fire-suppression systems, equipment, and
components is specified in Division 09 Sections "Interior Painting"
and "Exterior Painting.". Finish colors and reflectivities shall be
selected by Architect in the field.
B. Damage and Touchup: Repair marred and damaged factory-painted
finishes with materials and procedures to match original factory
finish.
3.4 ERECTION OF METAL SUPPORTS AND ANCHORAGES
A. Refer to Section 055000 "Metal Fabrications" for structural
steel.
B. Cut, fit, and place miscellaneous metal supports accurately
in location, alignment, and elevation to support and anchor
fire-suppression materials and equipment.
C. Field Welding: NOT allowed.
3.5 ERECTION OF WOOD SUPPORTS AND ANCHORAGES
A. Cut, fit, and place wood grounds, nailers, blocking, and
anchorages to support, and anchor fire-suppression materials and
equipment.
B. Select fastener sizes that will not penetrate members if
opposite side will be exposed to view or will receive finish
materials. Tighten connections between members. Install fasteners
without splitting wood members.
C. Attach to substrates as required to support applied
loads.
3.6 GROUTING
A. Mix and install grout for fire-suppression equipment base
bearing surfaces, pump and other equipment base plates, and
anchors.
B. Clean surfaces that will come into contact with grout.
C. Provide forms as required for placement of grout.
D. Avoid air entrapment during placement of grout.
-
COMMON WORK RESULTS FOR FIRE SUPPRESSION
Old Woodbridge Fire Station Renovations 210500-9
E. Place grout, completely filling equipment bases.
F. Place grout on concrete bases and provide smooth bearing
surface for equipment.
G. Place grout around anchors.
H. Cure placed grout.
END OF SECTION 210500
-
VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
Old Woodbridge Fire Station Renovations 210548-1
SECTION 210548 - VIBRATION AND SEISMIC CONTROLS FOR
FIRE-SUPPRESSION PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Isolation pads. 2. Isolation mounts. 3. Restrained
elastomeric isolation mounts. 4. Restraining braces.
1.3 DEFINITIONS
A. IBC: International Building Code.
B. ICC-ES: ICC-Evaluation Service.
C. OSHPD: Office of Statewide Health Planning and Development
for the State of California.
D. NFPA: National Fire Protection Association
E. CSBC: Connecticut State Building Code
1.4 PERFORMANCE REQUIREMENTS
A. Seismic-Restraint Loading:
1. Provide seismic restraints in accordance with the Connecticut
State Building Code.
1.5 SUBMITTALS
A. Product Data: For the following:
1. Include rated load, rated deflection, and overload capacity
for each vibration isolation device.
2. Illustrate and indicate style, material, strength, fastening
provision, and finish for each type and size of seismic-restraint
component used.
B. Delegated-Design Submittal: For vibration isolation and
seismic-restraint details indicated to comply with performance
requirements and design criteria, including analysis data signed
and sealed by the qualified professional engineer responsible for
their preparation.
-
VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
Old Woodbridge Fire Station Renovations 210548-2
1. Design Calculations: Calculate static and dynamic loading due
to equipment weight and operation, seismic forces required to
select vibration isolators, seismic restraints, and for designing
vibration isolation bases.
2. Seismic-Restraint Details:
a. Design Analysis: To support selection and arrangement of
seismic restraints. Include calculations of combined tensile and
shear loads.
b. Details: Indicate fabrication and arrangement. Detail
attachments of restraints to the restrained items and to the
structure. Show attachment locations, methods, and spacings.
Identify components, list their strengths, and indicate directions
and values of forces transmitted to the structure during seismic
events. Indicate association with vibration isolation devices.
C. Welding certificates.
1.6 QUALITY ASSURANCE
A. Comply with seismic-restraint requirements in the Connecticut
State Building Code and NFPA 13 unless requirements in this Section
are more stringent.
B. Welding: Qualify procedures and personnel according to AWS
D1.1, "Structural Welding Code - Steel."
C. Seismic-restraint devices shall have horizontal and vertical
load testing and analysis and shall bear anchorage preapproval OPA
number from OSHPD, preapproval by ICC-ES, or preapproval by another
agency acceptable to authorities having jurisdiction, showing
maximum seismic-restraint ratings. Ratings based on independent
testing are preferred to ratings based on calculations. If
preapproved ratings are not available, submittals based on
independent testing are preferred. Calculations (including
combining shear and tensile loads) to support seismic-restraint
designs must be signed and sealed by a qualified professional
engineer.
PART 2 - PRODUCTS
2.1 SEISMIC-RESTRAINT DEVICES
A. Manufacturers: Subject to compliance with requirements,
provide products by one (1) of the following:
1. Cooper B-Line, Inc.; a division of Cooper Industries 2.
Hilti, Inc. 3. Mason Industries 4. TOLCO Incorporated; a brand of
NIBCO INC. 5. Unistrut; Tyco International, Ltd.
B. Channel Support System: MFMA-3, shop- or field-fabricated
support assembly made of slotted steel channels with accessories
for attachment to braced component at one end and to building
structure at the other end and other matching components and with
corrosion-resistant coating; and rated in tension, compression, and
torsion forces.
-
VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
Old Woodbridge Fire Station Renovations 210548-3
C. Hanger Rod Stiffener: Steel tube or steel
slotted-support-system sleeve with internally bolted connections to
hanger rod.
D. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene
bushings designed for rigid equipment mountings and matched to type
and size of anchor bolts and studs.
E. Bushing Assemblies for Wall-Mounted Equipment Anchorage:
Assemblies of neoprene elements and steel sleeves designed for
rigid equipment mountings and matched to type and size of
attachment devices used.
F. Resilient Isolation Washers and Bushings: One-piece, molded,
oil- and water-resistant neoprene, with a flat washer face.
G. Mechanical Anchor Bolts: Drilled-in and stud-wedge or
female-wedge type in zinc-coated steel for interior applications
and stainless steel for exterior applications. Select anchor bolts
with strength required for anchor and as tested according to ASTM E
488. Minimum length of eight times (8x) diameter.
H. Adhesive Anchor Bolts: Drilled-in and capsule anchor system
containing polyvinyl or urethane methacrylate-based resin and
accelerator, or injected polymer or hybrid mortar adhesive. Provide
anchor bolts and hardware with zinc-coated steel for interior
applications and stainless steel for exterior applications. Select
anchor bolts with strength required for anchor and as tested
according to ASTM E 488.
2.2 FACTORY FINISHES
A. Finish: Manufacturer's standard paint applied to
factory-assembled and -tested equipment before shipping.
1. Powder coating on springs and housings. 2. All hardware shall
be galvanized. Hot-dip galvanize metal components for exterior use.
3. Baked enamel or powder coat for metal components on isolators
for interior use. 4. Color-code or otherwise mark vibration
isolation and seismic-control devices to indicate
capacity range.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and equipment to receive vibration isolation
and seismic-control devices for compliance with requirements for
installation tolerances and other conditions affecting
performance.
B. Examine roughing-in of reinforcement and cast-in-place
anchors to verify actual locations before installation.
C. Proceed with installation only after unsatisfactory
conditions have been corrected.
3.2 VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICE
INSTALLATION
A. Piping Restraints:
-
VIBRATION AND SEISMIC CONTROLS FOR FIRE SUPPRESSION PIPING AND
EQUIPMENT
Old Woodbridge Fire Station Renovations 210548-4
1. Comply with requirements in MSS SP-127, NFPA 13 and the
Connecticut State Building Code.
3.3 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION
A. Install flexible connections in piping where they cross
seismic joints, where adjacent sections or branches are supported
by different structural elements, and where the connections
terminate with connection to equipment that is anchored to a
different structural element from the one supporting the
connections as they approach equipment. Comply with requirements in
Section 211313 "Wet-Pipe Sprinkler Systems" for piping flexible
connections.
END OF SECTION 210548
-
IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT
Old Woodbridge Fire Station Renovations 210553-1
SECTION 210553 - IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND
EQUIPMENT
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including
General and Supplementary Conditions and Division 01 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Equipment labels. 2. Warning signs and labels. 3. Pipe
labels. 4. Stencils. 5. Valve tags. 6. Warning tags.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For color, letter style, and graphic representation
required for each identification material and device.
C. Equipment-Label Schedule: Include a listing of all equipment
to be labeled and the proposed content for each label.
D. Pipe-Label Schedule: Include a listing of all pipe systems to
be labeled and the proposed content for each label.
E. Valve Schedules: Valve numbering scheme.
1.4 CLOSEOUT SUBMITTALS
A. Maintenance Data: For each piping system to include in
maintenance manuals.
PART 2 - PRODUCTS
2.1 EQUIPMENT LABELS
A. Metal Labels for Equipment:
1. Material and Thickness: Brass, 0.032-inch-thick, with
predrilled holes for attachment hardware.
2. Letter Color: Red. 3. Background Color: White.
-
IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT
Old Woodbridge Fire Station Renovations 210553-2
4. Minimum Label Size: Length and width vary for required label
content, but not less than 2½-by-¾-inch.
5. Minimum Letter Size: ¼-inch for name of units if viewing
distance is less than 24 inches, ½-inch for viewing distances up to
72 inches, and proportionately larger lettering for greater viewing
distances. Include secondary lettering two-thirds to three-fourths
the size of principal lettering.
6. Fasteners: Stainless-steel rivets or self-tapping screws. 7.
Adhesive: Contact-type permanent adhesive, compatible with label
and with substrate.
B. Label Content: Include equipment's Drawing designation or
unique equipment number, Drawing numbers where equipment is
indicated (plans, details, and schedules), and the Specification
Section number and title where equipment is specified.
C. Equipment-Label Schedule: For each item of equipment to be
labeled, on 8½-by-11-inch bond paper. Tabulate equipment
identification number and identify Drawing numbers where equipment
is indicated (plans, details, and schedules) and the Specification
Section number and title where equipment is specified. Equipment
schedule shall be included in operation and maintenance data.
2.2 WARNING SIGNS AND LABELS
A. Material and Thickness: Multilayer, multicolor, plastic
labels for mechanical engraving, 1/8-inch-thick, with predrilled
holes for attachment hardware.
B. Letter Color: Black.
C. Background Color: Yellow.
D. Maximum Temperature: Able to withstand temperatures up to 160
deg F (71 deg C).
E. Minimum Label Size: Length and width vary for required label
content, but not less than 2½-by-¾-inch.
F. Minimum Letter Size: ¼-inch for name of units if viewing
distance is less than 24 inches, ½-inch for viewing distances up to
72 inches, and proportionately larger lettering for greater viewing
distances. Include secondary lettering two-thirds to three-fourths
the size of principal lettering.
G. Fasteners: Stainless-steel rivets or self-tapping screws.
H. Adhesive: Contact-type permanent adhesive, compatible with
label and with substrate.
I. Label Content: Include caution and warning information, plus
emergency notification instructions.
2.3 PIPE LABELS
A. General Requirements for Manufactured Pipe Labels:
Preprinted, color-coded, with lettering indicating service and
showing flow direction.
-
IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT
Old Woodbridge Fire Station Renovations 210553-3
B. Pretensioned Pipe Labels: Precoiled, semi-rigid plastic
formed to cover full circumference of pipe and to attach to pipe
without fasteners or adhesive.
C. Self-Adhesive Pipe Labels: Printed plastic with contact-type,
permanent-adhesive backing.
D. Pipe-Label Contents: Include identification of piping service
using same designations or abbreviations as used on Drawings; pipe
size; and an arrow indicating flow direction.
1. Flow-Direction Arrows: Integral with piping-system service
lettering to accommodate both directions, or as separate unit on
each pipe label to indicate flow direction.
2. Lettering Size: At least 1½ inches high.
E. Pipe-Label Colors:
1. Background Color: Red. 2. Letter Color: White.
2.4 VALVE TAGS
A. Valve Tags: Stamped or engraved with ¼-inch letters for
piping-system abbreviation and ½-inch numbers.
1. Tag Material: Brass, 0.032-inch-thick, with predrilled holes
for attachment hardware. 2. Fasteners: Brass wire-link chain,
beaded chain or S-hook. 3. Valve-Tag Color: Red. 4. Letter Color:
White.
B. Valve Schedules: For each piping system, on 8½-by-11-inch
(A4) bond paper. Tabulate valve number, piping system, system
abbreviation (as shown on valve tag), location of valve (room or
space), normal-operating position (open, closed, or modulating),
and variations for identification. Mark valves for emergency
shutoff and similar special uses.
1. Valve-tag schedule shall be included in operation and
maintenance data.
2.5 WARNING TAGS
A. Warning Tags: Preprinted or partially preprinted,
accident-prevention tags, of plasticized card stock with matte
finish suitable for writing.
1. Size: Approximat